DESCRIPTION
YORK Sunline 2000™ heat pumps are convertible single
package units with a common cabinet and a common roof
curb for the 3, 4 and 5 ton sizes. The units were designed for
light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.
TECHNICAL GUIDE
SINGLE PACKAGE HEAT PUMP UNITS
All units include:
•
Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
3, 4 & 5 NOMINAL TONS
•
Permanently lubricated motors
10.0 SEER
•
Bottom or side air discharge configuration capability
(field convertible)
•
Manufactured under the quality standards of ISO9001
•
SimplicityTM Control Board
•
Copper tube/aluminum fin coils
•
Easy access to all components
•
Rigging holes in base rails for lifting
•
Fork lift slots on three sides
•
Single point power connection
•
Complete factory package - tested, charged and wired
•
CSA agency listing on all units
BQ 036, 048 & 060
WARRANTY
•
Factory Limited Parts Warranty
•
One-year parts warranty
•
A Five-year parts warranty on the compressor and
electric heat elements.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21508-005-A-0305
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
BELT DRIVE) - SIDE DUCT APPLICATION . . . 22
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . 3
10 SUPPLY AIR BLOWER PERFORMANCE (3 - 5
TON DIRECT DRIVE) - SIDE DUCT
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . 23
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . 12
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 13
11 BELT DRIVE BLOWER MOTOR AND DRIVE
DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 40
12 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . 24
13 ELECTRIC HEATER CFM LIMITATIONS . . . . . 24
LIST OF FIGURES
Fig. #
Pg. #
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . 12
2 TYPICAL FIELD POWER & CONTROL WIRING 34
3 UNIT DIMENSIONS (3 - 5 TON HEAT PUMP)
FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4 UNIT WITH ECONOMIZER RAINHOOD . . . . . . 35
5 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . 36
6 UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . 36
7 DISCONNECT/BLOWER ACCESS LOCATION 37
8 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . 38
9 FOUR AND SIX POINT LOADING . . . . . . . . . . . 39
14 ELECTRICAL DATA - BQ036 & 048 DIRECT
DRIVE WITHOUT POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
15 ELECTRICAL DATA - BQ060 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE
OUTLET
26
16 ELECTRICAL DATA - BQ036 & 048 BELT
DRIVE WITHOUT POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
17 ELECTRICAL DATA - BQ060 BELT DRIVE
WITHOUT POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
18 ELECTRICAL DATA - BQ036 & 048 DIRECT
DRIVE WITH POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . 40
19 ELECTRICAL DATA - BQ060 DIRECT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . 30
LIST OF TABLES
Pg. #
20 ELECTRICAL DATA - BQ036 & 048 BELT DRIVE
WITH POWR’D CONVENIENCE OUTLET . . . . 31
1 SOUND POWER RATING . . . . . . . . . . . . . . . . . 15
21 ELECTRICAL DATA - BQ060 BELT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . 32
2 CAPACITY RATINGS . . . . . . . . . . . . . . . . . . . . 15
22 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . 33
3 BQ036 COOLING CAPACITIES (3 TON) . . . . . 16
23 ELECTRIC HEAT CORRECTION FACTORS . . 33
4 BQ048 COOLING CAPACITIES (4 TON) . . . . . 17
24 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . 33
5 BQ060 COOLING CAPACITIES (5 TON) . . . . . 18
25 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . 37
6 BQ HEATING CAPACITIES . . . . . . . . . . . . . . . . 19
26 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . 37
7 SUPPLY AIR BLOWER PERFORMANCE (3 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . 20
27 BQ 4 POINT LOADS WEIGHT DISTRIBUTION 39
Tbl. #
8 SUPPLY AIR BLOWER PERFORMANCE (4 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . 21
9 SUPPLY AIR BLOWER PERFORMANCE (5 TON
2
28 BQ 6 POINT LOADS WEIGHT DISTRIBUTION 39
29 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 39
30 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . 39
Unitary Products Group
036-21508-005-A-0305
PRODUCT NOMENCLATURE
3-5 Ton Sunline Model Number Nomenclature
B Q 048 C00 A 2 A AA 1
Product Generation
1 = First Generation
2 = Second Generation
Product Catagory
D = Air Cond., Single Package
B = Heat Pump, Single Package
Product Identifier
M = R-22 Standard Efficiency (DCG/DCE)
F = R-22 Medium Efficiency (DEG/DEE)
H = R-22 High Efficiency (DHG/DHE)
Q = R-22 Std. Effic Heat Pump (BCH)
Nominal Cooling
Capacity - MBH
036 = 3 Ton
048 = 4 Ton
060 = 5 Ton
Installation Options
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
E05 = 5 kW Electric Heat
E07 = 7 kW Electric Heat
E10 = 10 kW Electric Heat
E15 = 15 kW Electric Heat
E20 = 20 kW Electric Heat
E30 = 30 kW Electric Heat
Voltage
1 = 208/230-1-60
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4, & 5
Additional Options
(See Next Page)
Options
1 = Disconnect
2 = Non-Pwr'd Conv Oultet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Airflow
A= Direct Drive
B = Direct Drive/Single Input Econo
D = Direct Drive/Motorized Damper
L = Direct Drive/BAS Ready Econ (No BAS Controller)/2" Pleated Filters/Extra xfrmr & circuit bkr.
N = Belt Drive
P = Belt Drive/Single Input Econo
R = Belt Drive/Motorized Damper
Y = Belt Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
Unitary Products Group
3
036-21508-005-A-0305
PRODUCT NOMENCLATURE - Continued
3-6T Sunline Model Number Nomenclature
Standard Cabinet
AA
AB
AC
AD
AE
AF
AG
AH
AJ
AK
AL
AM
AN
AS
CA
CB
CC
CD
CE
CF
CG
CH
CJ
CK
CL
CM
CN
CP
CQ
CR
CS
CT
CU
CV
CW
CX
JA
JB
JC
JD
JE
JF
JG
JH
JJ
JK
JL
JM
JN
JP
JQ
4
None
Phase Monitor
Coil Guard
Dirty Filter Switch
Phase Monitor & Coil Guard
Phase Monitor & Dirty Filter Switch
Coil Guard & Dirty Filter Switch
Phase Monitor, Coil Guard, & Dirty Filter Switch
SS Drain Pan
SS Drain Pan & Phase Monitor
SS Drain Pan & Coil Guard
SS Drain Pan & Dirty Filter Switch
SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch
Bottom Drain Connection
CPC Controller with Dirty Filter Switch & Air Proving Switch
CPC Controller, DFS, APS & Phase Monitor
CPC Controller, DFS, APS & Coil Guard
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Cond. Coil
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Evap. Coil
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS, SS Drain Pan
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
Johnson UNT Controller, DFS, APS & Phase Monitor
Johnson UNT Controller, DFS, APS & Coil Guard
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Unitary Products Group
036-21508-005-A-0305
Standard Cabinet
JR
JS
JT
JU
JV
JW
JX
HA
HB
HC
HD
HE
HF
HG
HH
HJ
HK
HL
HM
HN
HP
HQ
HR
HS
HT
HU
HV
HW
HX
NA
NB
NC
ND
NE
NF
NG
NH
NJ
NK
NL
NM
NN
NP
NQ
NR
NS
NT
NU
NV
NW
NX
TA
TB
TC
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS, SS Drain Pan
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
Novar ETC-3 Controller, DFS, APS & Phase Monitor
Novar ETC-3 Controller, DFS, APS & Coil Guard
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS, SS Drain Pan
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Technicoat Condenser Coil
Technicoat Condenser Coil & Phase Monitor
Technicoat Condenser Coil & Coil Guard
Unitary Products Group
5
036-21508-005-A-0305
Standard Cabinet
TD
TE
TF
TG
TH
TJ
TK
TL
TM
TN
TP
TQ
TR
TS
TT
TU
TV
TW
TX
TY
TZ
T1
T3
T4
T6
T7
T9
LA
LB
LC
LD
LE
LF
LG
LH
LJ
LK
LL
LM
LN
LP
LQ
LR
LS
LT
LU
LV
LW
LX
WA
WB
WC
WD
WE
6
Technicoat Condenser Coil & Dirty Filter Switch
Technicoat Condenser Coil, Phase Monitor, & Coil Guard
Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator Coil
Technicoat Evaporator Coil & Phase Monitor
Technicoat Evaporator Coil & Coil Guard
Technicoat Evaporator Coil & Dirty Filter Switch
Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils
Technicoat Evaporator & Condenser Coils & Phase Monitor
Technicoat Evaporator & Condenser Coils & Coil Guard
Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Condenser & SS Drain Pan
Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & SS Drain Pan
Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils & SS Drain Pan
Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Simplicity Intelli-Comfort Controller
Simplicity Intelli-Comfort Controller, & Phase Monitor
Simplicity Intelli-Comfort Controller, & Coil Guard
Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, SS Drain Pan
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Intelli-Comfort w/Mod Link Controller
Intelli-Comfort w/Mod Link Controller, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil
Unitary Products Group
036-21508-005-A-0305
Standard Cabinet
WF
WG
WH
WJ
WK
WL
WM
WN
WP
WQ
WR
WS
WT
WU
WV
WW
WX
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, SS Drain Pan
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Hinged Filter Door & Toolless Access Cabinet
BA
BB
BC
BD
BE
BF
BG
BH
BJ
BK
BL
BM
BN
BS
DA
DB
DC
DD
DE
DF
DG
DH
DJ
DK
DL
DM
DN
DP
DQ
DR
DS
DT
DU
DV
DW
Hinged Filter Door & Toolless Access Panels
Phase Monitor, Hinged Filter Door & Toolless Access Panels
Coil Guard, Hinged Filter Door & Toolless Access Panels
Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels
Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Phase Monitor, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Coil Guard, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Phase Monitor & Coil Guard, Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Bottom Drain Connection, Hinged Filter Door & Toolless Access Panels
CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
Unitary Products Group
7
036-21508-005-A-0305
Hinged Filter Door & Toolless Access Cabinet
DX
EA
EB
EC
ED
EE
EF
EG
EH
EJ
EK
EL
EM
EN
EP
EQ
ER
ES
ET
EU
EV
EW
EX
GA
GB
GC
GD
GE
GF
GG
GH
GJ
GK
GL
GM
GN
GP
GQ
GR
GS
GT
GU
GV
GW
GX
PA
PB
8
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless
Access Panels
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door &
Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access
Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless
Access Panels
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Unitary Products Group
036-21508-005-A-0305
Hinged Filter Door & Toolless Access Cabinet
PC
PD
PE
PF
PG
PH
PJ
PK
PL
PM
PN
PP
PQ
PR
Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
PS Novar ETC-3 Controller, DFS, APS, SS Drain Pan
PT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
PU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
PV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
PW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
PX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U1 Technicoat Condenser & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U4 Technicoat Evaporator & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U7 Technicoat Evaporator & Condenser Coils & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless
Access Panels
QA Simplicity Intelli-Comfort Controller with Hinged Filter Door & Toolless Access Panels
QB Simplicity Intelli-Comfort Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
QC Simplicity Intelli-Comfort Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Unitary Products Group
9
036-21508-005-A-0305
Hinged Filter Door & Toolless Access Cabinet
QD
QE
QF
QG
QH
QJ
QK
QL
QM
QN
QP
QQ
QR
QS
QT
QU
QV
QW
QX
Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolles
Simplicity Intelli-Comfort Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
XA Intelli-Comfort w/Mod Link Controller, Hinged Filter Door & Toolless Access Panels
XB Intelli-Comfort w/Mod Link Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XC Intelli-Comfort w/Mod Link Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
XF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
XK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
XP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
XQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolles
XS Intelli-Comfort w/Mod Link Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
XT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
XU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
XV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
XW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
XX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
10
Unitary Products Group
036-21508-005-A-0305
FEATURES
•
All models are available with a wide variety of factorymounted options such as electric heaters, phase monitor,
convenience outlet, dirty filter switch, disconnect switch,
smoke detectors, and coil guards to make them suitable for
almost every application.
Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
•
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
•
Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. For bottom
duct, remove the sheet metal panels from the supply and
return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear
of the unit.
All models are available with these “factory mounted” outdoor
air damper options:
•
Single enthalpy economizer
•
Motorized outdoor air damper
Supply air blowers are equipped with either a direct drive or a
belt drive that can be adjusted to meet the exact requirements of the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system components.
•
Simplicity™ Controls - Simplicity™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•
•
All units have long lasting powder paint cabinets with 750
hour salt spray test approval under ASTM-B117 procedures.
All models are CSA listed.
•
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty
•
Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
Unitary Products Group
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
•
BAS Controls - York’s Sunline™ series units offer factory mounted BAS controls such as SImplicity™
INTELLI-Comfort™, Novar, Honeywell, Johnson, and
CPC.
11
036-21508-005-A-0305
FIGURE 1 -
UNIT CUTAWAY
FACTORY-INSTALLED OPTIONS
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
•
ELECTRIC HEATERS - Wired for single point power
supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•
FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
•
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
•
DISCONNECT SWITCH - For heat pump units with electric heat, an HACR breaker sized to the unit is provided.
For heat pump units without electric heat, a switch sized
to the largest electric heat available for the particular unit
is provided. Factory-installed option only.
•
BAS - Building Automation System Controls
Simplicity™ INTELLI-Comfort™ CONTROL - The
York® Simplicity™ INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving
switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
12
PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes
Technicoat 10-1TM processes. Coating is applied by total
immersion of the complete coil for maximum protection.
Unitary Products Group
036-21508-005-A-0305
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™using CO2 sensors. It uses an inside CO2 sensor
to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to
provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the
equipment when harsh operating conditions exist.
Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the
on-board connection for hot gas re-heat system. It uses
the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The Simplicity™
INTELLI-Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate
comfort.
•
Simplicity™ INTELLI-Comfort™ with MOD LINK CONTROL - The York® Simplicity™ INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
•
Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
•
JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air proving switch.
•
•
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•
BOTTOM DRAIN CONNECTION - An optional bottom
drain connection is available for inside the curb connections for applications in cold environments to reduce
freezing drain lines.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
•
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
NOTE:Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for
tool-less operation.
FIELD-INSTALLED ACCESSORIES
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
•
ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•
STAINLESS STEEL DRAIN PAN - An optional rustproof stainless steel drain pan is available to provide
years of trouble-free operation in corrosive environments.
•
ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association
(NRCA) and are shipped knocked-down for field assembly.
Unitary Products Group
13
036-21508-005-A-0305
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
•
POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
•
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
•
CO2 SENSOR - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
present limits.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•
HAIL GUARD - Hail guard is available to protect the unit
from hail damage. This is a sloped hood that fits above
the coil.
The power exhaust option can only be used on bottom duct configurations.
•
14
BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
Unitary Products Group
036-21508-005-A-0305
TABLE 1: SOUND POWER RATING1
UNIT
SIZE
ESP
SOUND POWER (db 10-12 Watts)
BLOWER
Octave Band Centerline Frequency (Hz)
CFM
IWG
SPEED
KW
63
125
250
500
1,000
2,000
4,000
8,000
SWL
dB(A)
dB(A)
@
10Ft.2
036
1,200
0.6
LOW
0.60
84
84
74
67
69
62
57
52
74
41
048
1,600
0.55
HIGH
0.80
85
85
75
68
70
63
58
53
75
42
060
2,000
0.45
HIGH
1.00
86
86
76
69
71
64
59
54
76
43
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
TABLE 2: CAPACITY RATINGS
ARI RATINGS1
UNIT SIZE
(MBH)
036
048
060
COOLING PERFORMANCE
MBH
39
48
59
SEER
10.00
10.20
10.00
EER
9.20
9.25
9.20
SOUND
HEATING CAPACITY
RATING2
bels
HSPF
8.6
8.6
8.4
7.3
6.7
7.0
47°F
MBH
39.0
48.0
59.0
17°F
COP
3.0
3.0
3.0
MBH
23.0
26.4
36.0
COP
2.1
2.0
2.1
NOTES:
1. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
2. Rated in accordance with ARI Standard 270.
SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input
in watt-hoursduring the same period.
EER = Energy Efficiency Ratio-the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in
BTUH per watt (BTUH/watt).
COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supplementary resistance
(BTU’s per hour) divided by the total electric input (watts) x 3.412.
HSPF = Heating Seasonal Performance Factor - the total heating output during a normal annual usage period for heating divided by the total electric power input during
the same period. (Based on Region IV minimum design heating requirement).
Unitary Products Group
15
036-21508-005-A-0305
TABLE 3: BQ036 COOLING CAPACITIES (3 TON)
AIR ON
EVAPORATOR
COIL
CFM
1750
1500
1400
1200
1050
900
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
AIR ON
EVAPORATOR
COIL
CFM
1750
1500
1400
1200
1050
900
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
TOTAL
CAP.1
MBH
INPUT kW
51
46
42
42
49
45
41
41
48
44
40
40
47
41
38
37
45
41
36
36
45
39
35
35
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.2
3.2
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
2
86
37
40
42
42
35
39
41
41
33
39
40
40
31
36
38
37
28
34
36
36
26
31
35
35
83
32
40
42
42
30
37
41
41
29
36
39
40
27
32
37
37
25
30
35
36
24
28
34
35
80
28
36
41
42
26
33
40
41
24
32
38
39
24
29
36
36
22
27
33
34
20
25
32
32
77
24
31
39
40
22
29
37
38
20
28
34
35
20
25
32
33
19
24
30
31
17
22
29
30
74
19
26
34
35
18
24
32
34
16
23
30
31
16
22
29
30
16
20
27
28
15
19
25
26
71
21
29
30
20
28
29
20
26
27
18
25
26
17
24
25
17
23
24
TOTAL
68
16
24
25
15
24
25
15
22
23
14
21
22
14
21
22
14
20
21
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
CAP.1
MBH
INPUT kW
47
44
38
37
46
42
37
36
45
41
36
36
44
39
35
35
42
38
34
33
40
35
32
31
3.7
3.7
3.6
3.6
3.7
3.7
3.6
3.6
3.7
3.7
3.6
3.5
3.7
3.6
3.6
3.5
3.6
3.6
3.5
3.5
3.6
3.6
3.5
3.5
2
86
34
38
38
37
32
36
37
36
30
36
36
36
29
34
35
35
26
31
34
33
23
27
32
31
83
29
38
38
37
28
34
37
36
27
33
35
36
25
30
34
35
23
27
33
33
21
25
30
31
80
25
34
37
37
24
30
36
36
22
29
34
35
22
27
33
34
20
25
31
31
17
22
28
28
77
22
29
35
35
20
27
33
33
18
26
30
31
18
23
29
31
17
22
28
28
15
19
25
26
74
17
24
30
30
16
22
28
29
15
21
27
27
14
20
26
28
14
18
25
25
13
17
22
23
71
20
26
26
18
25
25
18
23
24
17
23
24
15
22
22
15
20
21
68
15
21
22
14
21
21
13
19
20
13
19
20
12
19
20
12
17
18
TEMPERATURE OF AIR ON CONDENSER COIL
105°F
TOTAL
1
POWER
CAP.
MBH
INPUT2 kW
44
40
35
35
43
38
34
34
42
37
33
32
41
35
32
31
40
34
30
30
38
32
29
29
4.0
4.0
3.9
3.9
4.0
4.0
3.9
3.9
4.0
4.0
3.9
3.8
4.0
3.9
3.9
3.8
3.9
3.9
3.8
3.8
3.9
3.9
3.8
3.8
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
86
31
34
35
35
30
32
34
34
28
32
33
32
27
30
32
31
24
28
30
30
21
25
29
29
83
27
34
35
35
26
31
34
34
25
30
32
32
23
27
31
31
22
24
29
30
20
22
27
29
80
24
31
34
35
22
27
33
34
21
26
31
31
20
24
30
31
19
22
27
28
16
20
25
26
77
20
26
32
33
19
24
30
31
17
23
28
28
17
21
26
27
16
19
25
25
14
18
23
24
74
16
22
28
29
15
20
26
28
14
19
24
24
13
18
24
25
14
16
22
23
12
15
20
21
71
18
24
25
16
23
24
16
21
21
15
21
21
14
20
20
13
18
19
TOTAL
1
68
13
20
20
12
19
20
12
18
18
11
17
18
11
17
18
11
16
17
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
CAP.
MBH
INPUT2 kW
42
36
34
33
41
35
33
32
39
34
32
32
37
32
30
29
35
31
29
28
34
29
27
26
4.2
4.1
4.1
4.1
4.2
4.1
4.1
4.1
4.2
4.1
4.1
4.0
4.2
4.1
4.1
4.0
4.1
4.0
4.0
4.0
4.1
4.0
4.0
4.0
86
30
31
34
33
29
30
33
32
26
30
32
32
24
28
30
29
21
25
29
28
19
23
27
26
83
26
31
34
33
25
28
33
32
23
27
31
32
21
24
29
29
19
22
28
28
18
20
25
26
80
23
28
33
33
21
25
32
32
19
24
30
31
18
22
28
29
17
20
26
26
15
18
24
23
77
19
24
31
31
18
22
29
29
16
21
27
28
15
19
25
25
14
18
24
24
12
16
21
22
74
15
20
27
27
15
18
25
26
13
17
24
24
12
17
22
23
12
15
21
21
11
14
18
19
71
16
23
23
15
22
22
15
20
21
14
19
20
12
19
19
12
17
17
68
12
19
19
11
19
19
11
17
18
10
16
17
10
16
17
10
15
15
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.35kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
16
Unitary Products Group
036-21508-005-A-0305
TABLE 4: BQ048 COOLING CAPACITIES (4 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
INPUT2 kW
CFM
WB °F
CAP.1
MBH
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
56
53
49
49
55
52
48
48
53
51
47
47
52
49
46
45
50
47
44
44
4.1
4.0
4.0
3.9
4.0
4.0
3.9
3.9
4.0
4.0
3.9
3.9
4.0
3.9
3.8
3.8
3.9
3.9
3.8
3.7
2000
1800
1600
1400
1200
85°F
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
TOTAL
86
83
80
77
74
71
68
CAP.1
MBH
42
48
49
49
40
47
48
48
37
46
47
47
34
42
46
45
31
38
44
44
36
47
49
49
35
44
48
48
33
42
47
47
30
38
45
45
27
35
42
43
31
41
48
49
30
39
47
48
28
37
46
47
26
34
42
43
24
31
39
39
26
36
44
44
25
34
43
43
24
33
41
42
22
30
38
39
20
28
35
36
30
38
38
29
38
38
28
37
38
26
34
35
24
32
32
25
33
33
24
33
33
24
32
33
22
30
31
21
28
29
28
28
28
28
28
29
26
27
25
25
53
51
46
46
53
51
47
45
52
50
45
44
49
47
43
42
47
45
40
40
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
INPUT2 kW
4.5
4.4
4.3
4.3
4.4
4.4
4.3
4.2
4.4
4.3
4.2
4.1
4.3
4.2
4.1
4.1
4.2
4.2
4.1
4.0
86
83
80
77
74
71
68
40
46
46
46
38
44
47
45
36
44
45
44
33
42
43
42
29
37
40
40
35
45
46
46
33
44
47
45
32
43
45
44
29
38
42
42
25
34
39
39
29
41
45
46
28
39
45
45
27
38
44
44
25
34
40
40
22
30
36
36
24
35
41
41
23
34
40
40
23
34
40
40
21
30
36
36
18
27
32
32
30
35
35
29
36
35
29
36
36
26
32
32
23
29
29
24
30
30
24
31
30
25
31
31
22
28
28
20
25
25
24
24
26
25
27
27
24
24
22
22
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
TOTAL
1
CFM
2000
1800
1600
1400
1200
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
51
46
43
43
50
45
42
42
49
44
41
41
47
42
39
39
44
40
38
37
4.9
4.7
4.6
4.6
4.8
4.7
4.6
4.5
4.8
4.6
4.5
4.4
4.7
4.5
4.4
4.4
4.6
4.5
4.4
4.3
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
40
42
43
43
38
41
42
42
35
40
41
41
32
38
39
39
28
36
38
37
35
42
43
43
33
41
42
42
31
40
41
41
28
36
38
39
25
32
36
37
29
39
42
43
28
37
41
42
26
35
40
41
24
32
37
37
21
29
34
34
24
34
37
38
23
32
37
37
22
31
35
36
20
28
33
33
18
25
29
30
28
32
32
27
32
33
26
32
32
24
28
29
22
27
27
23
27
28
22
27
27
22
27
28
20
25
25
18
22
23
21
22
22
23
23
23
20
21
20
20
49
41
40
40
47
40
39
38
46
39
37
37
44
37
36
36
42
36
35
35
5.2
5.0
4.9
4.8
5.1
4.9
4.8
4.7
5.1
4.9
4.7
4.7
5.0
4.8
4.7
4.6
4.9
4.7
4.6
4.6
86
83
80
77
74
71
68
39
40
40
40
37
37
39
38
34
36
37
37
31
36
36
36
28
34
35
35
34
40
40
40
32
36
39
38
29
36
37
37
27
34
35
36
24
31
34
35
29
37
39
40
27
35
37
38
25
32
36
37
23
30
34
34
21
27
30
31
23
32
34
34
22
30
34
33
20
28
33
34
19
26
30
31
17
24
28
29
26
29
30
25
29
30
23
28
28
21
26
26
20
24
24
21
23
24
20
24
25
19
24
25
17
22
23
17
20
21
18
19
19
20
19
20
18
19
17
18
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.35kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
Unitary Products Group
17
036-21508-005-A-0305
TABLE 5: BQ060 COOLING CAPACITIES (5 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
INPUT2 kW
CFM
WB °F
CAP.1
MBH
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
68
65
61
60
67
64
60
59
66
63
59
58
64
61
57
57
62
59
55
55
5.7
5.6
5.6
5.5
5.6
5.6
5.5
5.5
5.6
5.5
5.4
5.4
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.3
2500
2250
2000
1750
1500
85°F
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
TOTAL
86
83
80
77
74
71
68
CAP.1
MBH
51
58
61
60
48
57
60
59
45
56
59
58
42
52
57
57
38
48
55
55
44
56
61
60
42
54
60
59
40
51
59
58
37
47
56
57
34
43
52
54
38
50
59
59
36
48
57
58
34
45
55
57
32
42
51
53
30
39
47
49
31
43
53
53
30
42
51
52
29
40
50
52
27
37
46
48
25
35
43
45
37
46
47
36
45
46
35
44
46
33
41
44
31
39
41
30
39
40
30
39
40
29
39
41
28
37
39
26
35
37
33
33
33
34
33
36
32
34
30
32
67
64
59
58
66
63
57
57
65
61
56
56
62
59
54
54
60
57
52
52
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
INPUT2 kW
6.0
5.9
5.9
5.8
5.9
5.9
5.8
5.8
5.9
5.9
5.8
5.7
5.9
5.8
5.7
5.7
5.8
5.8
5.7
5.6
86
83
80
77
74
71
68
51
56
59
58
48
55
57
57
45
55
56
56
43
53
54
54
41
51
52
52
45
56
59
58
42
54
57
57
40
51
56
56
38
48
54
54
36
46
52
52
38
50
57
57
36
48
55
56
34
45
54
55
33
44
52
53
32
42
50
51
31
43
50
51
30
42
50
50
29
40
49
50
28
39
48
49
28
38
46
47
37
44
44
35
44
45
34
44
44
34
43
43
34
42
42
30
38
39
29
38
39
29
38
39
29
38
39
29
38
39
31
32
32
33
33
34
33
34
34
35
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
TOTAL
1
CFM
2500
2250
2000
1750
1500
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
64
59
54
54
63
58
53
53
62
57
52
52
60
55
50
50
57
53
48
48
6.0
5.9
5.9
5.8
5.9
5.9
5.8
5.8
5.9
5.9
5.8
5.7
5.9
5.8
5.7
5.7
5.8
5.8
5.7
5.6
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
51
51
54
54
48
51
53
53
45
51
52
52
41
48
50
50
38
47
48
48
44
51
54
54
42
51
53
53
39
49
52
52
37
46
50
50
34
43
48
48
38
49
51
52
36
46
52
52
34
44
51
51
32
41
48
48
30
38
45
45
31
42
46
46
30
40
46
46
28
38
46
46
27
36
43
43
25
34
41
41
36
40
41
34
40
41
33
40
40
31
39
39
30
37
38
29
33
33
28
34
35
27
35
36
26
34
34
26
32
32
26
26
28
27
30
31
29
30
28
28
60
54
49
49
60
54
49
49
59
53
48
47
56
51
46
45
53
48
44
43
6.9
6.6
6.5
6.5
6.8
6.6
6.5
6.4
6.8
6.5
6.4
6.4
6.7
6.5
6.4
6.3
6.6
6.4
6.3
6.2
86
83
80
77
74
71
68
50
54
49
49
47
47
49
49
44
45
48
47
40
43
46
45
36
41
44
43
43
53
49
49
41
47
49
49
38
45
48
47
35
43
46
45
31
39
44
43
37
47
48
49
35
45
47
48
33
42
46
46
30
38
43
43
27
35
39
40
30
41
42
43
29
39
42
43
27
36
42
43
25
33
38
38
23
30
35
36
34
35
35
32
36
37
31
36
36
29
33
33
26
30
30
27
28
28
26
30
31
26
31
32
24
28
28
22
26
26
22
23
24
25
25
25
24
25
22
23
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.35kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
18
Unitary Products Group
036-21508-005-A-0305
TABLE 6: BQ HEATING CAPACITIES
Model Tonnage
CFM
RET. AIR °F
55
1750
70
80
55
1400
70
80
3
55
1200
70
80
55
1050
70
80
55
2000
70
80
55
4
1600
70
80
55
1200
70
80
55
2500
70
80
55
5
2000
70
80
55
1500
70
80
Unitary Products Group
CAP
& KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
OUTDOOR AIR TEMPERATURE, °F (72% RH)
-10
13.1
2.9
11.9
3
10.9
3.1
12.4
2.7
11.4
2.9
10.4
3
11.8
2.7
10.8
2.9
9.9
2.9
11.2
2.6
10.2
2.8
9.3
2.8
12.3
3.4
11.8
3.5
10.9
3.6
12.1
3.3
11.6
3.4
10.7
3.5
10.9
3.1
10.5
3.2
9.6
3.3
18.2
5
17.5
5.2
16.1
5.4
18
4.7
17.3
4.9
15.9
5.1
16.2
4.5
15.6
4.7
14.4
4.9
0
16.4
3
15
3.1
13.6
3.2
15.5
2.9
14.1
3
13.1
3.1
14.8
2.8
13.5
3
12.4
3.1
14.1
2.7
12.8
2.9
11.7
3
17.3
3.5
16.6
3.6
15.3
3.7
17
3.4
16.3
3.5
15
3.6
15.3
3.2
14.7
3.3
13.5
3.4
24.7
5.1
23.7
5.3
21.8
5.6
24.4
4.8
23.5
5
21.6
5.3
22
4.6
21.2
4.8
19.5
5
10
23.5
3.2
21.5
3.4
19.6
3.4
22.5
3
20.3
3.2
18
3.2
21.3
3
19.4
3.1
17.8
3.2
20.3
2.9
18.5
3
16.7
3.1
22.5
3.6
21.6
3.8
19.9
4
22
3.5
21.2
3.6
19.5
3.8
19.9
3.3
19.1
3.4
17.6
3.5
31.1
5.2
29.9
5.4
27.5
5.7
30.8
4.9
29.6
5.1
27.2
5.4
27.8
4.7
26.7
4.9
24.6
5.1
20
29.1
3.3
26.7
3.4
24.3
3.5
27.7
3.1
25.2
3.3
23.2
3.4
26.5
3.1
24
3.3
22
3.4
25.2
3
22.8
3.2
20.7
3.3
28.2
3.6
27.1
3.8
24.9
4
27.7
3.6
26.6
3.7
24.5
3.9
24.9
3.4
24
3.5
22
3.6
38.4
5.3
37
5.5
34
5.8
38.1
5
36.6
5.2
33.7
5.5
34.3
4.8
33
5
30.4
5.2
30
30.2
3.5
27.7
3.6
25.2
3.8
28.7
3.3
26.1
3.5
24.2
3.6
27.5
3.3
24.9
3.4
22.9
3.5
26.1
3.3
23.6
3.3
21.5
3.4
36.3
3.8
34.9
4
32.1
4.1
34.5
3.6
33.2
3.8
30.5
4
31.7
3.5
30.5
3.6
28.1
3.8
45.6
5.3
43.9
5.6
40.4
5.9
45
5.3
43.3
5.5
39.8
5.8
41.4
5
39.8
5.2
36.6
5.5
40
41.7
3.7
38.2
3.8
34.8
3.9
39.6
3.5
36.1
3.7
33.3
3.8
37.8
3.4
34.4
3.6
31.5
3.7
35.9
3.3
32.7
3.5
29.8
3.6
44.5
4
42.8
4.2
39.4
4.4
42.3
3.8
40.7
4
37.4
4.2
38.9
3.7
37.4
3.8
34.4
4
55.4
5.6
53.3
5.9
49
6
54.7
5.5
52.6
5.8
48.4
6.1
50.2
5.3
48.3
5.5
44.5
5.8
50
47
3.8
43.1
3.9
39.3
4.1
44.7
3.6
40.7
3.8
37.6
3.9
42.7
3.5
38.8
3.7
35.6
3.8
40.6
3.5
36.9
3.6
33.6
3.7
53.8
4.6
51.7
4.8
47.6
5
51.2
4.4
49.2
4.6
45.3
4.8
47
4.2
45.2
4.4
41.6
4.6
64.7
5.9
62.2
6.2
57.2
6.5
63.9
5.8
61.4
6.1
56.5
6.4
58.7
5.5
56.4
5.8
51.9
6.1
60
48.2
3.9
44.1
4.1
40.2
4.2
45.8
3.7
41.6
3.9
38.5
4
43.7
3.6
39.7
3.8
36.5
3.9
41.6
3.5
37.8
3.7
34.4
3.8
61.6
5.2
59.2
5.4
54.5
5.7
58.6
5
56.3
5.2
51.8
5.4
53.8
4.8
51.7
5
47.6
5.2
75.6
6.5
72.7
6.8
66.9
7.2
74.7
6.4
71.8
6.7
66.1
7
68.6
6.1
66
6.4
60.7
6.7
19
036-21508-005-A-0305
TABLE 7: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
3
1, 2
UNIT
TONNAGE
3
1, 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
843
860
880
925
919
1005
956
1065
993
1145
1030
1195
1067
1235
1900
817
775
854
850
893
920
930
995
970
1065
1008
1125
1046
1170
1800
790
700
828
760
867
840
906
905
944
980
985
1040
1025
1100
1700
-
-
802
670
840
745
881
815
920
900
961
970
1001
1030
1600
-
-
-
-
818
665
858
740
898
820
940
890
980
950
1500
-
-
-
-
-
-
842
695
882
755
922
835
962
895
1400
-
-
-
-
-
-
833
650
867
705
904
765
942
820
1300
-
-
-
-
-
-
-
-
858
665
893
725
932
785
1200
-
-
-
-
-
-
-
-
847
640
880
680
916
730
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
1.10
1.20
1.30
0.80
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
1103
1270
-
-
-
-
-
-
-
-
-
-
-
-
1900
1085
1210
-
-
-
-
-
-
-
-
-
-
-
-
1800
1064
1145
1102
1180
-
-
-
-
-
-
-
-
-
-
1700
1040
1075
1081
1115
1121
1140
-
-
-
-
-
-
-
-
1600
1020
1005
1060
1050
1100
1085
-
-
-
-
-
-
-
-
1500
1003
945
1044
995
1086
1035
-
-
-
-
-
-
-
-
1400
982
880
1024
920
1067
965
1107
1000
-
-
-
-
-
-
1300
970
835
1010
870
1053
920
1099
960
-
-
-
-
-
-
1200
953
780
992
815
1034
855
1080
905
-
-
-
-
-
-
0.90
1.00
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.
20
Unitary Products Group
036-21508-005-A-0305
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
4
1, 2
UNIT
TONNAGE
4
1, 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
843
860
880
925
919
1005
956
1065
993
1145
1030
1195
1067
1235
1900
817
775
854
850
893
920
930
995
970
1065
1008
1125
1046
1170
1800
790
700
828
760
867
840
906
905
944
980
985
1040
1025
1100
1700
-
-
802
670
840
745
881
815
920
900
961
970
1001
1030
1600
-
-
-
-
818
665
858
740
898
820
940
890
980
950
1500
-
-
-
-
-
-
842
695
882
755
922
835
962
895
1400
-
-
-
-
-
-
833
650
867
705
904
765
942
820
1300
-
-
-
-
-
-
-
-
858
665
893
725
932
785
1200
-
-
-
-
-
-
-
-
847
640
880
680
916
730
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3
1.10
1.20
1.30
0.80
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
1103
1270
-
-
-
-
-
-
-
-
-
-
-
-
1900
1085
1210
-
-
-
-
-
-
-
-
-
-
-
-
1800
1064
1145
1102
1180
-
-
-
-
-
-
-
-
-
-
1700
1040
1075
1081
1115
1121
1140
-
-
-
-
-
-
-
-
1600
1020
1005
1060
1050
1100
1085
-
-
-
-
-
-
-
-
1500
1003
945
1044
995
1086
1035
-
-
-
-
-
-
-
-
1400
982
880
1024
920
1067
965
1107
1000
-
-
-
-
-
-
1300
970
835
1010
870
1053
920
1099
960
-
-
-
-
-
-
1200
953
780
992
815
1034
855
1080
905
-
-
-
-
-
-
0.90
1.00
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
Unitary Products Group
21
036-21508-005-A-0305
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
5
1, 2
UNIT
TONNAGE
5
1, 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2500
1059
1560
1077
1590
1095
1630
1114
1650
1134
1660
1158
1685
1181
1720
2400
1032
1405
1054
1470
1074
1525
1094
1560
1116
1595
1140
1620
1167
1640
2300
1005
1260
1024
1275
1049
1370
1069
1440
1090
1475
1116
1505
1142
1535
2200
980
1160
1002
1170
1022
1190
1044
1250
1066
1350
1090
1410
1117
1440
2100
930
1060
957
1070
983
1080
1010
1100
1039
1160
1064
1260
1092
1340
2000
877
950
908
975
941
1000
976
1020
1009
1050
1040
1100
1070
1225
1900
-
-
-
-
894
885
940
940
980
980
1014
1020
1047
1095
1800
-
-
-
-
855
815
903
860
950
905
988
940
1022
970
1700
-
-
-
-
-
-
884
815
925
850
964
880
1001
910
1600
-
-
-
-
-
-
864
770
908
805
948
835
987
870
1500
-
-
-
-
-
-
-
-
882
740
926
780
965
830
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
1.10
1.20
1.30
0.80
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2400
1193
1665
-
-
-
-
-
-
-
-
-
-
-
-
2300
1170
1580
1202
1620
-
-
-
-
-
-
-
-
-
-
2200
1148
1480
1180
1530
-
-
-
-
-
-
-
-
-
-
2100
1121
1385
1155
1425
1190
1475
-
-
-
-
-
-
-
-
2000
1100
1285
1133
1340
1169
1385
1205
1445
-
-
-
-
-
-
1900
1079
1180
1110
1240
1143
1280
1178
1330
1222
1375
-
-
-
-
1800
1058
1060
1090
1135
1122
1190
1158
1240
1196
1295
-
-
-
-
1700
1035
960
1071
1030
1103
1100
1134
1140
1164
1175
1197
1205
-
-
1600
1020
900
1056
965
1088
1035
1118
1065
1145
1105
1170
1130
1198
1150
1500
1004
860
1038
880
1070
925
1101
980
1130
1045
1158
1075
1184
1110
0.90
1.00
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
22
Unitary Products Group
036-21508-005-A-0305
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (3 - 5 TON DIRECT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
3
4
5
4
5
MOTOR SPEED
1
1
1
UNIT
TONNAGE
3
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2
0.20
1
1
0.40
0.50
0.60
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
HI
-
-
-
-
-
-
1720
825
1665
795
MED
1660
850
1630
820
1590
780
1550
750
1500
720
LOW
1470
750
1440
725
1410
700
1370
675
1330
650
HI
-
-
-
-
2000
1010
1950
975
1905
945
MED
1810
910
1780
880
1740
850
1700
825
1665
800
LOW
1635
810
1610
780
1580
760
1555
740
1540
730
HI
-
-
-
-
2500
1400
2420
1350
2340
1300
MED
2390
1350
2350
1300
2300
1255
2245
1210
2190
1165
LOW
2270
1320
2230
1270
2190
1220
2145
1170
2090
1110
MOTOR SPEED
1
0.30
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2
0.80
0.90
0.70
WATTS
1.00
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
HI
1600
765
1540
735
1490
700
1380
670
MED
1450
690
1400
665
1360
650
1270
610
LOW
1290
625
1250
610
1220
600
1130
560
HI
1840
910
1770
825
1660
825
1530
775
MED
1620
775
1560
740
1480
700
1390
660
LOW
1510
715
1460
690
1400
660
1300
615
HI
2260
1250
2160
1190
2060
1135
1925
1065
MED
2130
1120
2065
1075
1990
1030
1900
970
LOW
2030
1070
1960
1020
1890
970
1810
920
1. Side Duct application (230/460/575 Volts)
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance
values.
TABLE 11: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
MOTOR1
ADJUSTABLE MOTOR PULLEY
BELT
(NOTCHED)
FIXED BLOWER PULLEY
MODEL
SIZE
BLOWER
RANGE
(RPM)
HP
FRAME
DESIGNATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIGNATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIGNATION
PITCH
LENGTH
(IN.)
QTY.
3 TON
790/1120
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK61
5.9
5.7
1
A36
37.3
1
4 TON
790/1120
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK61
5.9
5.7
1
A36
37.3
1
5 TON
850/1220
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK56
5.4
5.2
1
A36
37.3
1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located
in the moving air, upstream of any heating device.
Unitary Products Group
23
036-21508-005-A-0305
TABLE 12: STATIC RESISTANCES
RESISTANCE, IWG
DESCRIPTION
CFM
1000
1200
1400
1600
1800
2000
2200
2400
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
5-15KW
0.04
0.05
0.06
0.07
0.08
0.10
0.12
0.14
0.16
20-30KW
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.14
0.16
ECONOMIZER1, 2
ELECTRIC
HEATERS1
BOTTOM DUCT CONNECTIONS1
2600
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 13: ELECTRIC HEATER CFM LIMITATIONS
UNIT MODEL SIZE NOMINAL
TONS
3
4
5
24
MINIMUM SUPPLY AIR CFM
VOLTAGE
HEATER SIZE NOMINAL KW
5
7
10
15
20
30
208/230-1-60
1100
1100
1200
1200
1300
-
208/230-3-60
1100
1100
1200
1200
1300
-
460-3-60
-
1100
1200
1200
1300
-
575-3-60
-
-
1200
1200
1300
-
208/230-1-60
1300
1300
1300
1300
1300
-
208/230-3-60
1300
1300
1300
1300
1300
-
460-3-60
-
1300
1300
1300
1300
-
575-3-60
-
-
1300
1300
1400
-
208/230-1-60
1600
1600
1600
1600
1600
1600
208/230-3-60
1600
1600
1600
1600
1600
1600
460-3-60
-
1600
1600
1600
1600
1600
575-3-60
-
-
1600
1600
1600
1800
Unitary Products Group
036-21508-005-A-0305
TABLE 14: ELECTRICAL DATA - BQ036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
19.0
105
1.7
4.4
0.0
230-1-60
19.0
105
1.7
4.4
0.0
208-3-60
11.9
85
1.7
4.4
0.0
230-3-60
11.9
85
1.7
4.4
0.0
460-3-60
5.9
42
1.0
2.2
0.0
575-3-60
4.8
34
1
2.2
0.0
208-1-60
25.0
105
2.3
5.0
0.0
230-1-60
25.0
105
2.3
5.0
0.0
208-3-60
14.7
130
2.3
5.0
0.0
230-3-60
14.7
130
2.3
5.0
0.0
460-3-60
7.7
64
1.3
2.2
0.0
575-3-60
6.4
52
1.3
2.2
0.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746 2
2
2CE04511046
2CE04511546 2
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746 2
2
2CE04511046
2CE04511546 2
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
29.9
53.9
63.5
77.9
101.4
125.4
29.9
57.5
68.9
85.1
112.7
140.3
21.0
34.9
40.4
48.7
62.3
76.1
21.0
36.9
43.5
52.8
68.8
84.7
10.6
20.8
25.8
31.0
39.9
8.6
21.3
27.7
34.1
38.6
62.6
72.2
86.6
110.1
134.0
38.6
66.2
77.6
93.8
121.4
149.0
25.7
39.6
45.1
53.4
67.0
80.8
25.7
41.6
48.2
57.5
73.5
89.4
13.1
23.3
28.3
33.6
42.4
10.8
23.5
29.9
36.3
Max Fuse /
BRKR1 Size
Amps
45
60
70
80
110
150
45
70
80
90
125
150
30
40
45
50
70
80
30
45
50
60
70
90
15
25
30
35
40
15
25
30
35
60
80
90
100
125
150
60
80
90
100
125
150
40
50
50
60
70
90
40
50
50
60
80
90
15
25
30
35
45
15
25
35
40
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
25
036-21508-005-A-0305
TABLE 15: ELECTRICAL DATA - BQ060 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
32.1
148
2.3
6.6
0.0
230-1-60
32.1
148
2.3
6.6
0.0
208-3-60
19.3
137
2.3
6.6
0.0
230-3-60
19.3
137
2.3
6.6
0.0
460-3-60
10.0
62
1.3
3.3
0.0
575-3-60
7.9
50
1.3
3.3
0.0
5
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2CE04511046 2
2CE04511546 2
2CE04512046 2
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
49.0
73.1
82.7
97.1
120.5
144.6
182.4
49.0
76.6
88.1
104.2
131.8
159.4
203.2
33.0
46.9
52.5
60.8
74.3
88.2
110.1
33.0
49.0
55.6
64.9
80.8
96.8
122.0
17.1
27.3
32.3
37.5
46.4
60.4
13.6
26.3
32.7
39.1
50.1
Max Fuse /
BRKR1 Size
Amps
80
100
100
110
125
150
200
80
100
110
125
150
175
225
50
60
60
70
80
90
125
50
60
70
70
90
100
125
25
35
35
40
50
70
20
30
35
40
60
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
26
Unitary Products Group
036-21508-005-A-0305
TABLE 16: ELECTRICAL DATA - BQ036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Compressors
Model
Tonnage
Voltage
RLA
Each
LRA
Each
OD Fan ID Blower
Motor
Motor
FLA
FLA
Conv
Outlet
Amps
208-1-60
19.0
105
1.7
7.6
0.0
230-1-60
19.0
105
1.7
7.6
0.0
208-3-60
11.9
85
1.7
5.2
0.0
230-3-60
11.9
85
1.7
5.2
0.0
460-3-60
5.9
42
1.0
2.6
0.0
575-3-60
4.8
34
1
2
0.0
208-1-60
25.0
105
2.3
7.6
0.0
230-1-60
25.0
105
2.3
7.6
0.0
208-3-60
14.7
130
2.3
5.2
0.0
230-3-60
14.7
130
2.3
5.2
0.0
460-3-60
7.7
64
1.3
2.6
0.0
575-3-60
6.4
52
1.3
2
0.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Max Fuse /
BRKR1
Size Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
33.0
57.1
66.7
81.1
104.6
128.6
33.0
60.7
72.1
88.3
115.9
143.5
21.8
35.7
41.2
49.5
63.1
76.9
21.8
37.7
44.3
53.6
69.6
85.5
11.0
21.2
26.2
31.4
40.3
8.4
21.1
27.5
33.9
41.2
65.2
74.8
89.2
112.7
136.7
38.8
66.4
77.8
94.0
121.6
149.2
25.9
39.8
45.3
53.6
67.2
81.0
25.9
41.8
48.4
57.7
73.7
89.6
13.5
23.7
28.7
34.0
42.8
11.4
23.8
30.2
36.5
50
70
70
90
110
150
50
70
80
90
125
150
30
40
45
50
70
80
30
45
50
60
70
90
15
25
30
35
45
15
25
30
35
60
80
90
100
125
150
60
80
90
100
125
150
40
50
50
60
70
90
40
50
50
60
80
90
20
25
30
35
45
15
25
35
40
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
27
036-21508-005-A-0305
TABLE 17: ELECTRICAL DATA - BQ060 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
32.1
148
2.3
7.6
0.0
230-1-60
32.1
148
2.3
7.6
0.0
208-3-60
19.3
137
2.3
5.2
0.0
230-3-60
19.3
137
2.3
5.2
0.0
460-3-60
10.0
62
1.3
2.6
0.0
575-3-60
7.9
50
1.3
2
0.0
5
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2CE04511046 2
2CE04511546 2
2CE04512046 2
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
50.0
74.1
83.7
98.1
121.5
145.6
183.4
50.0
77.6
89.1
105.2
132.8
160.4
204.2
31.6
45.5
51.1
59.4
72.9
86.8
108.7
31.6
47.6
54.2
63.5
79.4
95.4
120.6
16.4
26.6
31.6
36.8
45.7
59.7
12.5
25.3
31.6
38.0
49.1
Max Fuse /
BRKR1 Size
Amps
80
100
100
110
125
150
200
80
100
110
125
150
175
225
50
60
60
70
80
90
110
50
60
60
70
80
100
125
25
30
35
40
50
60
20
30
35
40
50
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
28
Unitary Products Group
036-21508-005-A-0305
TABLE 18: ELECTRICAL DATA - BQ036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
19.0
105
1.7
4.4
10.0
230-1-60
19.0
105
1.7
4.4
10.0
208-3-60
11.9
85
1.7
4.4
10.0
230-3-60
11.9
85
1.7
4.4
10.0
460-3-60
5.9
42
1.0
2.2
5.0
575-3-60
4.8
34
1
2.2
4.0
208-1-60
25.0
105
2.3
5.0
10.0
230-1-60
25.0
105
2.3
5.0
10.0
208-3-60
14.7
130
2.3
5.0
10.0
230-3-60
14.7
130
2.3
5.0
10.0
460-3-60
7.7
64
1.3
2.2
5.0
575-3-60
6.4
52
1.3
2.2
4.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
39.8
63.9
73.5
87.9
111.4
135.4
39.8
67.5
78.9
95.1
122.7
150.3
31.0
44.9
50.4
58.7
72.3
86.1
31.0
46.9
53.5
62.8
78.8
94.7
15.6
25.8
30.8
36.0
44.9
12.6
25.3
31.7
38.1
48.6
72.6
82.2
96.6
120.1
144.1
48.6
76.2
87.6
103.8
131.4
159.0
35.7
49.6
55.1
63.4
77.0
90.8
35.7
51.6
58.2
67.5
83.5
99.4
18.2
28.4
33.4
38.7
47.5
14.8
27.5
33.9
40.5
Max Fuse /
BRKR1 Size
Amps
50
70
80
90
125
150
50
80
90
100
125
175
40
50
60
60
80
90
40
50
60
70
80
100
20
30
35
40
45
15
30
35
40
70
90
100
110
125
150
70
90
100
110
150
175
50
60
60
70
80
100
50
60
60
70
90
100
25
30
35
40
50
20
30
35
45
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
29
036-21508-005-A-0305
TABLE 19: ELECTRICAL DATA - BQ060 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
32.1
148
2.3
6.6
10.0
230-1-60
32.1
148
2.3
6.6
10.0
208-3-60
19.3
137
2.3
6.6
10.0
230-3-60
19.3
137
2.3
6.6
10.0
460-3-60
10.0
62
1.3
3.3
5.0
575-3-60
7.9
50
1.3
3.3
4.0
5
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2CE04511046 2
2CE04511546 2
2CE04512046 2
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
59.0
83.1
92.7
107.1
130.5
154.6
192.4
59.0
86.6
98.1
114.2
141.8
169.4
213.2
43.0
56.9
62.5
70.8
84.3
98.2
120.1
43.0
59.0
65.6
74.9
90.8
106.8
132.0
22.1
32.3
37.3
42.5
51.4
65.4
17.6
30.3
36.7
43.1
54.1
Max Fuse /
BRKR1 Size
Amps
90
110
110
125
150
175
200
90
110
110
125
150
175
225
60
70
70
80
90
100
125
60
70
80
80
100
110
150
30
40
40
45
60
70
25
35
40
45
60
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
30
Unitary Products Group
036-21508-005-A-0305
TABLE 20: ELECTRICAL DATA - BQ036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
19.0
105
1.7
7.6
10.0
230-1-60
19.0
105
1.7
7.6
10.0
208-3-60
11.9
85
1.7
5.2
10.0
230-3-60
11.9
85
1.7
5.2
10.0
460-3-60
5.9
42
1.0
2.6
5.0
575-3-60
4.8
34
1
2
4.0
208-1-60
25.0
105
2.3
7.6
10.0
230-1-60
25.0
105
2.3
7.6
10.0
208-3-60
14.7
130
2.3
5.2
10.0
230-3-60
14.7
130
2.3
5.2
10.0
460-3-60
7.7
64
1.3
2.6
5.0
575-3-60
6.4
52
1.3
2
4.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
43.0
67.1
76.7
91.1
114.6
138.6
43.0
70.7
82.1
98.3
125.9
153.5
31.8
45.7
51.2
59.5
73.1
86.9
31.8
47.7
54.3
63.6
79.6
95.5
16.0
26.2
31.2
36.4
45.3
12.4
25.1
31.5
37.9
51.2
75.2
84.8
99.2
122.7
146.7
51.2
78.8
90.2
106.4
134.0
161.6
35.9
49.8
55.3
63.6
77.2
91.0
35.9
51.8
58.4
67.7
83.7
99.6
18.6
28.8
33.8
39.1
47.9
15.0
27.8
34.2
40.5
Max Fuse /
BRKR1 Size
Amps
60
80
80
100
125
150
60
80
90
100
150
175
40
50
60
60
80
90
40
50
60
70
80
100
20
30
35
40
50
15
30
35
40
70
90
90
110
125
150
70
90
100
110
150
175
50
60
60
70
80
100
50
60
60
70
90
100
25
30
35
40
50
20
30
35
45
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
31
036-21508-005-A-0305
TABLE 21: ELECTRICAL DATA - BQ060 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
32.1
148
2.3
7.6
10.0
230-1-60
32.1
148
2.3
7.6
10.0
208-3-60
19.3
137
2.3
5.2
10.0
230-3-60
19.3
137
2.3
5.2
10.0
460-3-60
10.0
62
1.3
2.6
5.0
575-3-60
7.9
50
1.3
2
4.0
5
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2CE04511046 2
2CE04511546 2
2CE04512046 2
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
60.0
84.1
93.7
108.1
131.5
155.6
193.4
60.0
87.6
99.1
115.2
142.8
170.4
214.2
41.6
55.5
61.1
69.4
82.9
96.8
118.7
41.6
57.6
64.2
73.5
89.4
105.4
130.6
21.4
31.6
36.6
41.8
50.7
64.7
16.5
29.3
35.6
42.0
53.1
Max Fuse /
BRKR1 Size
Amps
90
110
110
125
150
175
200
90
110
110
125
150
175
225
60
70
70
80
90
100
125
60
70
70
80
90
110
150
30
35
40
45
60
70
20
30
40
45
60
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
32
Unitary Products Group
036-21508-005-A-0305
TABLE 22: PHYSICAL DATA
BQ
MODELS
Centrifugal Blower (Dia. x Wd. in.)
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
CONDENSER
COILS
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS
CHARGE
12 X 10
12 X 10
1/2
3/4
1
1 1/2
1 1/2
1 1/2
Rows Deep
4
3
3
Fins Per Inch
16
15
15
Face Area (Sq. Ft.)
4.3
5.1
5.1
Propeller Dia. (in.)
22
22
24
Fan Motor Hp
1/3
1/2
1/2
4500
Nom. CFM
4300
4200
Rows Deep
1
1
1
Fins Per Inch
20
20
20
Face Area (Sq. Ft.)
17.1
17.1
17.1
Reciprocating Type
1
1
1
Quantity Per Unit (15” X 20” X 1” or 2“)
2
2
2
Quantity Per Unit (14” X 25” X 1” or 2“)
1
1
1
Total Face Area (sq. ft.)
6.6
6.6
6.6
Refrigerant 22
(lbs./oz.)
7/12
9/2
8/4
NOMINAL VOLTAGE
VOLTAGE
208
208
1.00
0.92
480
460
0.92
600
575
0.92
Unitary Products Group
060
12 X 10
Fan Motor HP (Belt Drive)
kW CAP. MULTIPLIER
230
048
Fan Motor HP (Direct Drive)
TABLE 23: ELECTRIC HEAT CORRECTION
FACTORS
240
036
TABLE 24: VOLTAGE LIMITATIONS1
VOLTAGE
POWER SUPPLY
MIN.
MAX.
208/230-3-60
187
253
460-3-60
414
506
575-3-60
518
506
1. Utilization Range “A” in accordance with ARI Standard
110.
33
036-21508-005-A-0305
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTECTION AND WIRING.
TYPICAL CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT 1
TERMINALS
ADD
JUMPER
RH
UNIT TERMINAL
STRIP TB1
RC
R
Y
Y1
24 VOLT
TRANSFORMER
Y2
W
W1
W2
G
G
C
1
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
COOLING / HEATING (ELECTRONIC THERMOSTAT)
SINGLE STAGE
COOLING / HEATING (ELECTRONIC THERMOSTAT)
MULTI STAGE
THERMOSTAT1
TERMINALS
ADD
JUMPER
RC
UNIT TERMINAL
STRIP TB1
RH
R
Y1
Y1
2
Y2
W1
4
3
G
B
C
LED 1
ADD
JUMPER
X
NOT
USED
OCC
4
ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).
2
SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3
SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER.
RC
R
Y
Y1
W
W1
G
G
24 VOLT
TRANSFORMER
TO REMOTE SENSOR
2TH040702224 IF USED
1
UNIT TERMINAL
STRIP TB1
C
A2
T
4
ADD
JUMPER
A1
T
1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.
FIGURE 2 -
34
W2
G
COM
RH
Y2
W1
W2
LED 2
THERMOSTAT1
TERMINALS
24 VOLT
TRANSFORMER
TYPICAL FIELD POWER & CONTROL WIRING
Unitary Products Group
036-21508-005-A-0305
FIGURE 3 -
UNIT DIMENSIONS (3 - 5 TON HEAT PUMP) FRONT VIEW
DETAIL “A”
FIGURE 4 -
UNIT WITH ECONOMIZER RAINHOOD
Unitary Products Group
35
036-21508-005-A-0305
DETAIL “B”
FIGURE 5 -
UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
FIGURE 6 -
UNIT DIMENSIONS (REAR VIEW)
36
Unitary Products Group
036-21508-005-A-0305
FILTER
ACCESS
BLOWER MOTOR
ACCESS
DOT PLUGS
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
the blower compartment)
A,B
WIRING ENTRY
(See Detail “B”)
CONTROL BOX
ACCESS
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
FIGURE 7 -
DISCONNECT/BLOWER ACCESS LOCATION
TABLE 25: UTILITIES ENTRY
HOLE
OPENING SIZE (DIA.)
TABLE 26: MINIMUM CLEARANCES
USED FOR
Side
A
7/8” KO1
Control Wiring2
B
2” KO1
Power Wiring
C
1-5/8” KO
Gas Piping (Front)
D
1-1/2” KO
Gas Piping (Bottom)
Bottom
Side
Bottom
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.
LOCATION
CLEARANCE
Front
24” (Cooling/Electric Heat)
32” (Gas Heat)
Rear
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
Left Side (Filter Access)
24” (Less Economizer)
36” (With Economizer)
Right Side (Cond. Coil)
24”
Below Unit1
0”
Above Unit2
72” (For
Condenser Air Discharge)
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
Unitary Products Group
37
036-21508-005-A-0305
FIGURE 8 -
38
TYPICAL APPLICATIONS
Unitary Products Group
036-21508-005-A-0305
BACK OF UNIT
A
447/8
BACK OF UNIT
A
447/8
821/4
821/4
D
B
F
X
X
B
APPROXIMATE
CENTER OF GRAVITY
FIGURE 9 -
CONDENSER COIL
END OF UNIT
C
Y
FRONT OF UNIT
C
E
APPROXIMATE
CENTER OF GRAVITY
D
Y
FRONT OF UNIT
CONDENSER COIL
END OF UNIT
FOUR AND SIX POINT LOADING
TABLE 27: BQ 4 POINT LOADS WEIGHT DISTRIBUTION
UNIT
TOTAL
A
B
C
D
BQ036
628
139
137
174
177
BQ048
668
148
146
185
189
BQ060
693
154
151
192
196
TABLE 28: BQ 6 POINT LOADS WEIGHT DISTRIBUTION
TOTAL
A
B
C
D
E
F
BQ036
UNIT
628
93
92
91
116
117
119
BQ048
668
99
98
97
123
125
126
BQ060
693
103
102
100
128
129
131
3 TON
4 TON
5 TON
628
668
693
TABLE 29: CENTER OF GRAVITY
DIMENSION
3 - 5 TON
X
40-¾”
Y
19-¾”
TABLE 30: OPERATING WEIGHTS (LBS.)
MODEL SIZE
BASIC UNIT
BQ
Economizer
50
Motorized Damper
OPTIONS
Electric Heater
26
5 - 7 kW
18
10 - 15 kW
23
20 - 30 kW
ACCY.
Unitary Products Group
28
Roof Curb
92
Barometric Relief / Fixed Air Damper
10
Belt-Drive Blower
5
39
036-21508-005-A-0305
FIGURE 10 - ROOF CURB DIMENSIONS
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline 2000TM units are convertible single package
heat pumps. Although the units are primarily designed for
curb mounting on a roof, they can also be slab-mounted at
ground level or set on steel beams above a finished roof.
Models are available with a wide variety of factory-mounted
options and field-installed accessories to make them suitable
for almost every application. All units are self-contained and
assembled on full perimeter base rails with holes in the four
corners for overhead rigging. Every unit is completely piped,
wired, charged and tested at the factory to simplify the field
installation and to provide years of dependable operation. All
models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the
supply and return air openings through the base of the unit.
For horizontal duct, remove the supply and return air panels
on the rear of the unit.
All non-Scroll compressors include crankcase heaters and all
compressors have internal pressure relief. Every refrigerant
circuit includes a liquid line filter-drier, a discharge line high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch.The unit control circuit
40
includes a 75 VA transformer, a 24-volt circuit breaker and a
relay board with a compressor lockout circuit, a terminal strip
for thermostat wiring, plus an additional set of pin connectors
to simplify the interface of additional field controls. All units
have long lasting powder paint cabinets with 750 hour salt
spray test approval under ASTMB117 procedures. All models
are CSA listed. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater elements carry a 5-year warranty.
DESCRIPTION
Units shall be factory-assembled, single packaged heat
pumps designed for outdoor mounted installation.
The units shall have minimum SEER ratings of 10.0. They
shall have built-in field convertible duct connections for down
discharge supply/return or horizontal discharge supply/return,
and be available with factory installed options or field installed
accessories. The units shall be factory wired, piped, charged
with R-22 refrigerant and factory tested prior to shipment. All
unit wiring shall be both numbered and color coded. All units
the cooling performance shall be rated in accordance with
DOE and ARI test procedures. Units shall be CSA listed,
classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 750 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be insu-
Unitary Products Group
036-21508-005-A-0305
lated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the
furnace compartment and be fastened with ridged fasteners
to prevent insulation from entering the air stream. Cabinet
panels shall be “large” size, easily removable for servicing
and maintenance. Full perimeter base rails shall be provided
to assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 1" filters
shall be furnished and be accessible through a removable
access door, sealed airtight. Units filter track shall be
designed to accommodate either 1” or 2” filters. Fan performance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating air bypass of the coils. Condensate pan shall be internally sloped
and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female
and be a ridged mount connection.
b.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a.
Independent fixed-orifice expansion devices.
b.
Filter drier/strainer to eliminate any moisture or foreign matter.
c.
Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary
servicing or troubleshooting without losing charge.
d.
The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.
UNIT CONTROLS
a.
Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
b.
Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
c.
Loss-of-charge/Low-pressure switch.
d.
High-pressure switch.
e.
Freeze-protection thermostat, evaporator coil.
f.
If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
g.
Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
h.
Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
i.
Unit control board shall have on-board diagnostics
and fault code display.
j.
Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.
k.
Control board shall monitor each refrigerant safety
switch independently.
l.
Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi-speed, or a factory
installed belt drive assembly that includes an adjustable pitch
motor pulley. Job site selected (B.H.P.) brake horsepower
shall not exceed the motors nameplate horsepower rating,
plus the service factor. Units shall be designed not to operate
above service factor. Fan wheel shall be double-inlet type
with forward-curved blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant air volume. Bearings shall be sealed
and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and
staged independently.
REFRIGERANT COMPONENTS
Compressor:
a.
b.
Shall be internally protected with internal high-pressure relief and over temperature protection.
Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent
mounting.
Coils:
a.
Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
ELECTRIC HEATING SECTION
Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
Unitary Products Group
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
stages of capacity - 16 KW and above on 208/230 volt heaters and 20 KW and above on 460 and 575 volt heaters. The
heating section shall have a primary limit control(s) and auto-
41
036-21508-005-A-0305
matic reset to prevent the heating element system from operating at an excessive temperature. The heating section
assembly shall slide out of the unit for easy maintenance and
service. Units with Electric Heating shall be wired for a single
point power supply with branch circuit fusing (where
required).
•
UNIT OPERATING CHARACTERISTICS
a.
Unit shall be capable of starting and running at
125°F outdoor temperature, exceeding maximum
load criteria of ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 0°F outdoor temperature. Unit shall be
provided with fan time delay to prevent cold air
delivery before heat exchanger warms up (Gas heat
only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
STANDARD LIMITED WARRANTIES
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
•
BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
Compressor 5 Years
•
Electric Heat Element 5 Years
•
ELECTRIC HEATERS
•
Other Parts 1 Year
•
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD Contains all hood panels and the hardware for assembling.
•
MANUAL OUTDOOR AIR DAMPER
•
COIL GUARD KIT - Guard for cooling coil.
•
HAIL GUARD
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•
42
ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully
close on power loss.
OTHER FACTORY INSTALLED OPTIONS
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
•
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
•
DIRTY FILTER SWITCH
•
PHASE MONITOR
•
COIL GUARD
•
POWERED GFI CONVENIENCE OUTLET
•
NON-POWERED GFI CONVENIENCE OUTLET
Unitary Products Group
036-21508-005-A-0305
•
BAS CONTROLS (SImplicity™ INTELLI-Comfort™,
CPC, JOHNSON, HONEYWELL, NOVAR)
•
BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)
•
HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
•
•
BOTTOM DRAIN CONNECTION
•
2" PLEATED FILTERS
•
DISCONNECT SWITCH
•
SUPPLY AIR SMOKE DETECTOR
•
RETURN AIR SMOKE DETECTOR
STAINLESS STEEL DRAIN PAN
Unitary Products Group
43
Subject to change without notice. Printed in U.S.A.
Copyright © 2005 by Unitary Products Group. All rights reserved.
Unitary
Products
Group
5005
York
Drive
036-21508-005-A-0305
Supersedes: 036-21508-004-A-0504
Norman
OK
73069
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project