4
463
Acvatix™
3-port seat valves, external thread, PN 16
Bronze CuSn5Zn5Pb2 valve body
VXG41..
k vs
1.6…40 m
3
/h
Flat sealing connections with external thread G…B to ISO 228-1
Sets of ALG..3 threaded fittings with threaded connection available from Siemens
Can be equipped with SAX.. electromotoric or SKD.. and SKB.. electrohydraulic actuators
VXG41..01 3-port seat valves are DVGW tested
Use
For use in heating, ventilating and air conditioning systems as a control valve for mixing and diverting functions. For closed and open circuits (mind
« cavitation
»
VXG41..01 Three-port seat valves for distribution or supply of cold water to storage or heat exchanger for hot water treatment in the drinking water installation.
CE1N4463en
15.11.2010
Building Technologies
Type summary
Accessories
Order
Delivery
Example:
Spare parts, rev. no.
Type / stock no. DN
15
k vs
[m
3
/h]
S v
1,6
2,5
> 50
4,0
20 6,3
25 10
40 25
50 40
1)
These types, as a standard, are equipped with a tight bypass. DVGW verified, DVGW applications according to drinking water regulation 2001. For medium temperatures up to 90 °C
DN = Nominal size k vs
= Nominal flow rate of cold water (5...30 °C) through the fully open valve (H
100
) by a differential pressure of 100 kPa (1 bar)
S v k vr
= Rangeability k vs
/ k vr
= Smallest k v
value, at which the flow characteristic tolerances can still be maintained, by a differential pressure of 100 kPa (1 bar)
Type Stock No.
ALG..3
1)
ALG..3
Description
Set of 3 threaded fittings for 3-port valves, consisting of
ALG..3B
1)
S55846-Z1..
- 3 union nuts, 3 discs and 3 flat seals
ALG..3B are brass fittings, for media temperatures up to 100 °C.
ASZ6.5 ASZ6.5 Electric stem heating element, AC 24 V / 30 W, required for media below 0 °C. For electrohydraulic actuators SKD.., SKB.. below 0 °C
1)
Applications requiring union fittings with DVGW approval must be delivered by thirds.
When ordering please give type, stock no., designation and quantity.
Type Stock no. Designation
VXG41.2501 VXG41.2501 Valve
ALG253B S55846-Z105 Set of threaded fittings
Valves, actuators and accessories are packed and supplied separately.
See overview, page 10.
Quantity
2
2
2/10
Siemens
Building Technologies
3-port seat valves, external thread, PN 16 CE1N4463en
15.11.2010
Equipment combinations
Valves
VXG41.1301
3)
VXG41.1401
3)
VXG41.15 VXG41.1501
VXG41.20 VXG41.2001
VXG41.25 VXG41.2501
VXG41.32 VXG41.3201
VXG41.40 VXG41.4001
VXG41.50 VXG41.5001
SAX..
1)
Actuators
SKD..
1)
SKB..
Mixing Diverting Mixing Diverting Mixing Diverting
p max
Type / stock no.
Fitting sets
Malleable cast iron
Type Stock no.
Brass
800 200
800
2)
ALG203 ALG203B
Actuator overview
Note:
100
2)
1)
Usable up to maximum medium temperature of 150 °C
2)
If noise is permitted, the same values apply as for the mixing valve.
3)
Use the valves in conjunction with actuators SKD.. or SKB.. to ensure compliance with the bypass leakage rate.
p max
= Maximum permissible differential pressure across valve’s control path, valid for the entire actuating range of the motorized valve
Type Actuator type
Operating voltage
Positioning signal
Spring return
Positioning time
Positioning force
Data sheet
SAX31.00
SAX31.03
SAX81.00
SAX81.03
Electromotoric
AC 230 V
AC/DC 24 V
3-position
No
120 s
30 s
120 s 800 N
DC 0…10 V
1)
30 s
SAX61.03
SKD32.50
SKD32.21
SKD32.51
SKD82.50
AC 230 V
30 s
Electrohydraulic
3- position
Yes
No 120 s 1000 N
SKD82.51
SKD60
AC 24 V
Yes
No
DC 0…10 V
1)
30 s
SKD62..
Yes
SKB32.50
No
AC 230 V
SKB32.51
Yes
3- position
SKB82.50
ElectroNo
120 s 2800 N
SKB82.51
hydraulic Yes
AC 24 V
SKB60
DC 0…10 V
1)
No
SKB62..
Yes
Actuators SAX81.. and SAX61.. are UL listed
1)
or DC 4…20 mA or 0…1000 Ω
Pneumatic actuators are available on request from your local office or branch.
Application is possible only if the VXG41.. is used as a mixing valve.
N4501
N4563
N4564
Siemens
Building Technologies
3-port seat valves, external thread, PN 16
3/10
CE1N4463en
15.11.2010
Technical design / mechanical design
Valve cross section
A
B
AB
A
B
AB
Guided perforated plug which is integrated in the valve stem.
A pressed-in stainless steel seat ring is used as seat A – AB.
Sizing
Flow diagram
«Mixing»
DN
- k vs
50 -
40
40 -
25
32 -
16
25 -
10
20 -
6,3
15 -
4
15 -
2,5
15 -
1,6
p max
= Maximum permissible differential pressure across the valve (mixing: port A - AB, B - AB), valid for the entire actuating range of the motorized valve
p v100
= Differential pressure across the fully open valve and the valve’s control path
A – AB, B - AB by a volume flow V
100
V
100
= Volume flow through the fully open valve (H
100
)
100 kPa = 1 bar
10 mWC
1 m
3
/h = 0.278 l/s water at 20 °C
4/10
Siemens
Building Technologies
3-port seat valves, external thread, PN 16 CE1N4463en
15.11.2010
Valve flow characteristic
Cavitation
Note on chilled water
High temperature hot water example:
1
0.8
B -
A
B
0.6
0.4
A
B
AB
0.2
A -
AB
0
0 0.2 0.4
0.6
0.8
Stroke H / H
100
1
Throughport
0 ...30 %: linear
30 ...100 %: equal-percentage n gl
= 3 to VDI / VDE 2173
Bypass
0...100 %: linear
Mixing:
flow from port A and port B to port AB
Diverting: flow from port AB to port A
and port B
Port I = constant flow
Port II = variable flow
Port III = bypass (variable flow)
Use the 3-port valve primarily as a mixing valve.
Cavitation accelerates wear on the valve plug and seat, and also results in undesirable noise. Cavitation can be avoided by not exceeding the differential pressure shown in
the flow diagram on page 4, and by adhering to the static pressures shown below.
To avoid cavitation in chilled water circuits ensure sufficient counter pressure at valve outlet, e.g. by a throttling valve after the heat exchanger. Select the pressure drop across the valve at maximum according to the 80 °C curve in the flow diagram below.
2500
25
Mixing
p max
2000 20
p
1 p
3
1500
18
0
° C
16
0
°C
14
0
°C
12
0
10
0
°C
°C
80
°C
15
p
2
p max'
M
1000 10
M
Diverting
p max p
1 p
3
500
5
p max' p
2
0
0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
p
max
[kPa]
p max
= Differential pressure with valve almost closed, at which cavitation can largely be avoided
Situation bypass p
1
= Static pressure at inlet p
2
= Static pressure at outlet
M = Pump
Pressure p
1
at valve inlet: 500 kPa (5 bar)
Water temperature: 120 °C
From the diagram above, it will be seen that with the valve almost closed, the maximum permissible differential pressure
p max
is 200 kPa (2 bar).
Siemens
Building Technologies
3-port seat valves, external thread, PN 16
5/10
CE1N4463en
15.11.2010
Working pressure and temperature
16
15
14
13
12
1
0
- 60 -40
-25
0 20 80 100 120
150
180
Working temperature [°C]
Working pressure and medium temperature staged as per ISO 7005
Current local legislation must be observed.
Notes
Engineering
Mounting
Orientation
In open circuits, there is a risk of valve plug seizing caused by scale deposits. Thus, use only the most powerful actuator SKB.. for these applications. Additionally, periodic actuation (twice or three times per week) must be planned.
With closed and open circuits always use a strainer upstream of the valve to increase the valve's functional safety.
Ensure cavitation-free flow, refer to page 5.
To ensure the reliability of the valve, we recommend the fitting of a strainer at the valve inlet in closed and open circuits.
For media below 0 °C, use the electric stem heating element to prevent the valve stem from freezing in the sealing gland. For safety reasons, the stem heating element has been designed for AC 24 V / 30 W operating voltage.
Both valve and actuator can easily be assembled at the mounting location. Neither special tools nor adjustments are required.
The valve is supplied with Mounting Instructions 4 319 9563 0.
90° 90°
Direction of flow
Commissioning
When mounting, pay attention to the valve's flow direction symbol
:
Mixing from
A / B to AB
A AB
Diverting from
AB to A / B
AB A
B B
Commission the valve only if the actuator has been mounted correctly.
Valve stem retracts: Throughport A – AB opens, bypass B closes
Valve stem extends: Throughport A – AB closes, bypass B opens
6/10
Siemens
Building Technologies
3-port seat valves, external thread, PN 16 CE1N4463en
15.11.2010
Maintenance
Disposal
Warning
Stem sealing gland
VXG41.. valves require no maintenance.
When doing service work on the valve / actuator:
Deactivate the pump and turn off the power supply
Close the shutoff valves
Fully reduce the pressure in the piping system and allow pipes to completely cool down
If necessary, disconnect the electrical wires.
Before putting the valve into operation again, make certain the actuator is correctly fitted.
The glands can be exchanged without removing the valve, provided the pipes are depressurized and cooled off and the stem surface is unharmed, refer to «spare parts»,
If the stem is damaged in the gland range, replace the entire stem-plug-unit.
Contact your local office or branch.
Before disposal the valve must be dismantled and separated into its various constituent materials.
Legislation may demand special handling of certain components, or it may be sensible from a ecological point of view.
Current local legislation must be observed.
Warranty
The technical data given for these applications is valid only in conjunction with the
Siemens actuators as detailed under «Equipment combinations», page 3.
All terms of the warranty will be invalidated by the use of actuators from other manufacturers.
Siemens
Building Technologies
3-port seat valves, external thread, PN 16
7/10
CE1N4463en
15.11.2010
Technical data
Functional data PN class
Operating pressure
PN 16 to ISO 7268 to ISO 7005 within the permissible medium temperature range according to the diagram on
Throughport
0…30 %
Throughport
30…100 %
Bypass
0…100%
linear
equal percentage; n gl
= 3 to VDI / VDE 2173
linear vs
value to DIN EN 1349
Bypass standard version 0.5…2% of k vs
value
Bypass VXG41..01
0…0.02% of k vs
value
Permissible media water cooling water, chilled water, low temperature hot water, high temperature hot water, water with anti-freeze; recommendation: water treatment to VDI 2035 drinking water VXG41..01, < 90 °C
Medium -25...150 °C
DVGW applications, VXG41..01, chilled- and low temperature hot water max. 90 °C
Rangeability > 50
DN ≥20: >100
Nominal stroke 20 mm
Industry standards Pressure Equipment Directive
Pressure Accessories
Fluid group 2
DVGW approval No.
Environmental compatibility
PED 97/23/EC as per article 1, section 2.1.4 without CE-marking as per article 3, section 3
(sound engineering practice)
DW-6341BU0025
ISO 14001 (Environment)
ISO 9001 (Quality)
SN 36350 (Environmentally compatible products)
RL 2002/95/EG (RoHS) bronze CuSn5Zn5Pb2 stainless steel
Materials
Dimensions / Weight
Valve body
Seat, plug, stem
Sealing gland gland materials
Refer to «Dimensions»
External thread connections dezincification-free brass, silicon-free
EPDM O rings, silicon-free
G..B to ISO 228-1
1)
Media below 0 °C: Stem heating element required to prevent freezing of the valve stem in the sealing gland.
With ALG..B fittings for media temperature up to 100 °C
Applications requiring union fittings with DVGW approval must be delivered by thirds.
8/10
Siemens
Building Technologies
3-port seat valves, external thread, PN 16 CE1N4463en
15.11.2010
Dimensions
B
DN = Nominal size
H = Total actuator height plus minimum distance to the wall or the ceiling for mounting, connection, operation, service, etc.
H1 = Dimension from the pipe centre to install the actuator (upper edge)
H2 = Valve in the «Closed» position means that the stem is fully extended
L2
Type
VXG41.1301
L1
DN B
[mm]
G
[inch]
L1
[mm]
L2
[mm]
L3
[mm]
H1
[mm]
H2
[mm]
H
SAX.. SKD.. SKB.. [kg]
VXG41.1401
VXG41.15 VXG41.1501
15 G1B
10 122.5 > 526 > 601
VXG41.20 VXG41.2001 20 G1¼B
VXG41.25 VXG41.2501 25 G1½B
VXG41.32 VXG41.3201 32
14
G2B
105 52.5 52.5 34 130.5
> 534 > 609
kg
1.30
1.42
1.65
2.10
VXG41.40 VXG41.4001 40 15 G2¼B 130 65 65
VXG41.50 VXG41.5001 50 16 G2¾B 150 75 75
Threaded fittings
Type / Stock No. Type
46 142.5
> 546 > 621
2.80
3.90
Stock No. for valve type G Rp
[inch] [inch]
S55846-Z101
Rp ½
G 1¼ Rp ¾
G 1½ Rp 1
G 2 Rp 1¼
G 2¼ Rp 1½
G 2¾ Rp 2
On valve side: cylindrical thread to ISO 228-1
On pipe side: with cylindrical thread to ISO 7-1
For drinking water applications according to DVGW drinking water regulation 2001 threaded fittings must be obtained from local dealer.
ALG..B for media temperatures up to 100 °C
Applications requiring union fittings with DVGW approval must be delivered by thirds.
Siemens
Building Technologies
3-port seat valves, external thread, PN 16
9/10
CE1N4463en
15.11.2010
Spare parts
Revision numbers
Order numbers for spare parts
Sealing gland
Type
VXG41.1301
VXG41.1401
VXG41.15
VXG41.1501
VXG41.20
VXG41.2001
VXG41.25
VXG41.2501
VXG41.32
VXG41.3201
VXG41.40
VXG41.4001
VXG41.50
VXG41.5001
25
25
32
32
40
15
15
15
15
20
20
40
50
50
DN
74 284 0047 0
74 284 0047 0
4 284 8874 0
74 284 0047 0
4 284 8874 0
74 284 0047 0
4 284 8874 0
74 284 0047 0
4 284 8874 0
74 284 0047 0
4 284 8874 0
74 284 0047 0
4 284 8874 0
74 284 0047 0
Set
Plug with stem, circlip, sealing
74 676 0166 0
74 676 0167 0
74 676 0135 0
74 676 0137 0
74 676 0121 0
74 676 0126 0
74 676 0122 0
74 676 0127 0
74 676 0123 0
74 676 0128 0
74 676 0124 0
74 676 0129 0
74 676 0125 0
74 676 0130 0
Type
VXG41.1301
VXG41.1401
VXG41.15
VXG41.1501
VXG41.20
Valid from rev. no.
..B
..B
..A
..B
..A
Type Valid from rev. no.
Type Valid from rev. no.
VXG41.2001
..B
VXG41.25
..A
VXG41.2501
..B
VXG41.32
..A
VXG41.40
VXG41.4001
VXG41.50
VXG41.5001
..A
..B
..A
..B
VXG41.3201
..B
10/10
Siemens
Building Technologies
© 1998 - 2010 Siemens Switzerland Ltd
3-port seat valves, external thread, PN 16
Subject to alteration
CE1N4463en
15.11.2010