UniclassEPIC JT42 JT90 L634 L511 CI/SfB (56.3) July 2012UF428 Surface heating and cooling solutions by Wavin Composite Manifold Installation Guide For residential and light commercial applications Solutions for Essentials Composite Manifold - Usability, Versatility and Reliability Thank you for purchasing our Composite Manifold. Please read through this guide before beginning any installation and operation work. Only competent persons with certification recognised It is important that the Composite Manifold is checked upon under Building Regulations – Part P should carry out delivery, and that any damaged or missing items are reported electrical installation or servicing work. Other persons are immediately. Any claims registered more than 72 hours after not permitted to open the control centre cover and/or delivery will not be accepted. make any modifications. l Each Starter Pack (88UH110) contains: l Each Control Pack (88UH211) contains: • 2 x Combined Inlets • 1” Mixing Unit • 2 x End Caps • Flow Watch Protection Thermostat • 2 x Brackets and Spacers • Bracket and Spacer • 1 x Installation Kit •Installation Kit • 1 x Flow Temperature Gauge • 1 x Combined Pressure and Return Temperature Gauge l Ancillary components available for the Composite Manifold include: • 22mm Isolation Valves (pair) (88UH311) l Each 1 Port Pack (88UH111) contains: • Clip-On Thermometer (pack of 10) (47UH750) • 1 Port Flow Module • 230V 2 Wire Actuator (52UH402) • 1 Port Return Module • 24V 2 Wire Actuator (52UH602) • Pipe Clamps (pack of 2) (15UH236) l Each 3 Port Pack (88UH113) contains: • 3 Port Flow Module • Curved Pipe Supports (pack of 2) (15UH239) • 3 Port Return Module Installers: Please complete this guide and pass to the end user or leave with the UFH manifold after installation. Project Reference Number: ______________________________________ Plumber Name: ______________________________________ Name: ______________________________________ Company: ______________________________________ Company: ______________________________________ Address: ______________________________________ Address: ______________________________________ 2 Electrician ______________________________________ ______________________________________ Postcode: ______________________________________ Postcode: ______________________________________ Tel: Tel: ______________________________________ Telephone: 01392 444122 ______________________________________ Fax: 01392 444135 Contents 1. Manifold Overview 4. Commissioning 1.1 Manifold Design 4 4.1 Quick Circuit Balancing 10 1.2 Manifold Dimensions 4 4.2 Flushing and Filling 11 4.3 Hydraulic Pressure Testing 11 4.4 Electrical Installation 2. Preparation for Installation Further Information, Sales and Technical Enquiries Please contact: 12 2.1 Pack Requirements 5 Tel: 01392 444122 4.5 Temperature and Pump Settings*12 2.2 Required Tools 5 Fax: 01392 444135 4.6 Advanced Circuit Balancing 2.3 General Installation Instructions 5 E-mail: [email protected] 3. Installation 3.1 Mounting Brackets 6 3.2 Assembling and Mounting Arms 7 3.3 Installing Guages 8 3.4 Modifying Control Packs* 8 3.5 Connecting Control Pack* 9 3.6 Circuit Connection 9 3.7 Connection to Primary Pipework 9 Email: [email protected] 13 5. Troubleshooting and Maintenence 5.1 Troubleshooting 13 5.2 Checking System Performance 14 5.3 Care and Cleaning 14 6. Technical Specification 14 7. Commissioning Record 15 www.thermoboard.co.uk 3 1. Manifold Overview 1.1 Manifold Design 1 Bracket + Bracket Spacer 6 1 2 Flow Watch Protection 7 2 Thermostat 3 Flow Water Temperature 8 3 Sensor 4 Circulator Pump (Grundfos 30 20 40 50 °C 10 UPS 25/60) 9 60 70 0 80 4 5 Thermostatic Actuator 10 6 Automatic Air Vent 5 7 Flow Temperature Gauge 2 8 Balancing Knob and 4 6 8 0 0 20 bar 80 60 40 Memory Ring 9 16mm Pipe Connector 11 10 Thermoelectric Actuator 13 14 11 Isolation Cap/ 12 Thermoelectric Actuator Mount 12 Combined Pressure & Return Temperature Gauge 13 Fill/Drain Valve 14 Isolation Valves 1.2 Manifold Dimensions Manifold Type Height Depth* Width in mm / No. of Ports 1 2 3 4 5 6 7 8 9 10 11 12 Exc Control Pack 390 120 260 310 360 410 460 510 560 610 660 710 760 810 Inc Control Pack 430 160 400 450 500 550 600 650 700 750 800 850 900 950 Note: Dimensions include Wavin isolation valves *Where required, the depth of the manifold can be reduced by 15mm if the bracket spacers are not installed. 4 Telephone: 01392 444122 Fax: 01392 444135 2. Preparation for Installation 2.1 Pack Requirements Starter Pack 1 Port Pack 3 Port Pack Number of Ports 1 2 3 4 5 6 7 8 9 10 11 12 Starter Packs 1 1 1 1 1 1 1 1 1 1 1 1 1 Port Packs 1 2 0 1 2 0 1 2 0 1 2 0 3 Port Packs 0 0 1 1 1 2 2 2 3 3 3 4 Note: A Composite Manifold Control Pack will be required for systems designed to have water temperature regulation through the manifold. 2.2 Required Tools Depending on the specific project you will need some or all of the 2.3 General Installation Instructions following tools to assemble and mount the Composite Manifold: lPen/Pencil lSpirit Level lTape Measure/Rule l10mm Care should be taken by the installer throughout the installation process to ensure the safety of the installer and others. Site Preparation Store the packaged manifolds inside a building, sheltered from 1. Masonry Drill Bit rain and sunlight. Do not place other materials on top of the l3mm Twist or Lip & Spur Drill Bit packaging. l10mm Socket/Open-End Wrench l22, 26, 32 and 38mm Open-End Wrenches lLarge lFill Flat Bladed Screwdriver and Drain pipes with 3/4” female connection lHydraulic Pressure Tester with 3/4” female connection For tools required to complete the electrical installation please refer to the appropriate control installation manual. 2. Clean the floor from other materials before starting work. Do l Assemble l Use the manifold under clean conditions. appropriate pipe cutters to cut the pipes clean and square. l Support connecting pipework parallel to and centred with the manifold connections. l Wear protective gloves to minimise risk of receiving cuts. Do Not Note: Over tightening connections may damage the manifold and will l Do not use a wrench to connect manifold extensions void warranty. l Do not use the manifold and its accessories for purposes other than for which they are intended. l Do not exceed specifications – failure to do so will void the warranty. l Do not allow corrosive substances to come into contact with the manifold and its accessories e.g. flux Email: [email protected] www.thermoboard.co.uk 5 3. Installation 3.1 Mounting Brackets l Identify l Refer l Accounting a suitable location to mount the manifold (Masonry – 10mm Dia, Timber – 3mm Dia) to (1) and the table below for bracket spacing l Manifold l Clip should be mounted at least 300mm from pipe level l Accurately for the wall construction, drill suitably sized holes brackets on to bracket spacers (2) l Screw measure and mark fixing locations ensuring they are brackets to wall using a 10mm Socket/Open-End Wrench, being careful not to over tighten and ensuring the ends level and square marked top are correctly positioned A* C B 30 20 40 50 °C 10 60 70 0 2 80 4 6 8 0 0 20 bar 80 60 40 1 2 Distance in mm / No. of Ports Bracket Spacing 1 2 3 4 5 6 7 8 9 10 11 12 A* 90 90 140 140 140 140 140 140 140 140 210 210 B 120 120 120 170 220 270 320 370 420 420 400 400 C 30 80 80 80 80 80 80 80 80 130 130 180 *Only applicable when control pack is being installed Note: The figure above and the rest of this installation guide assumes the manifold will be assembled in and installed in a left handed configuration. If it is preferential to assemble and install the manifold in a right handed configuration please mirror the figure above. 6 Telephone: 01392 444122 Fax: 01392 444135 3. Installation 3.2 Assembling and Mounting Arms Assembling Arms 1 Starting with the Combined Inlet, add 3 Port modules followed by 1 Port modules as required l If the ports are required to point downwards, screw the manifold together with the Combined Inlet upright in your left hand and the top of the Port modules towards you (1) l If the ports are required to point upwards, screw the manifold together with the Combined Inlet upright in your left hand and the top of the Port modules away from you. 1 2 Screw the end cap on to the manifold arm (2) 3 Repeat the process for the other manifold arm 4 To mount the manifold arms on the brackets, locate the ridge along the bottom of the manifold arm into the grooves on the brackets and rotate so that the top clicks in place (3) • Flow arm (Red Caps) should be mounted in the top position (4) • Return arm (Blue Caps) should be mounted in the bottom position (4) 2 Note: The return arm can be mounted vertically or at an inclined angle. It is suggested that it is mounted vertically when the manifold is installed close to the pipe level and inclined when it is intended to secure the pipe to the wall with suitable clamps. Mounting Arms Click Extending an existing manifold 1 Isolate the manifold from the primary heating circuit 2 Isolate the heating circuits on the flow and return manifold arms 3 Carefully depressurise and then drain the manifold using the fill/ drain valves, taking care to collect all of the water in a suitable container 3 Disconnect the manifold arms from isolation valves or control 4 pack depending on configuration 5 Remove the manifold arms from the brackets by lifting the top clips and rotating the top of the manifold arms away from the wall 6 Unscrew end caps 7 Continue installation according to this guide, repositioning brackets as required 8 Dispose of collected water in compliance with National Health & 4 Safety Regulations. Email: [email protected] www.thermoboard.co.uk 7 3. Installation 3.3 Installing Guages 1 Remove plugs from the front of the combined inlets using a large flat bladed screwdriver (1 & 2) 3 Push the temperature gauge into its mount (3) 4 Insert the combined pressure and temperature gauge into the 2 Insert the temperature gauges mount into the combined inlet on the second combined inlet on the return arm and lightly tighten using a 22mm open-end wrench (4) flow arm and lightly tighten using a 22mm open-end wrench (3) 1 2 3 4 Note: Care should be taken not to cross thread or over tighten the gauges as they are installed. 3.4 Modifying Control Pack* For right handed manifold assemblies it is necessary to modify the 4 Loosen the connection between pump and the mixing body of the control pack, rotate the mixing body through 180° and control pack, allowing it to be fitted to the right hand side. 1 Remove Flow Water Temperature Sensor from its housing (1) 2 Remove the Flow Water Temperature Sensor Housing using a re-tighten connection (4) 5 Insert the Flow Water Temperature Sensor back into its housing (5) 38mm open-end wrench and install it on the opposite end of the control packs flow arm (2) 3 Unclip and remove Flow Watch Protection Thermostat and locate in a mirrored orientation on the flow arm of the control pack (3) 1 2 3 4 Note: *Only applies to installations requiring a control pack. 5 8 Telephone: 01392 444122 Fax: 01392 444135 3. Installation 3.5 Connecting Control Pack* 1 Ensure bracket adaptors are positively located on the control 4Using 26 and 38mm open-end wrenches, place one on the nut packs bracket and that the bottom adaptor is aligned to the and one on the adjacent brass section of the combined inlets, bottom arm of the manifold (1) and tighten until sealed 2Clip the control pack into the bracket (2) Note: Air vent bottles should not be used as a lever to restrain 3Insert the 1” fibre washers supplied as part of the installation kit and hand tighten the connections between the control pack and the manifold while tightening the union connections between the control pack or isolation valves the manifold (3) 1 2 3 Note: *Only applies to installations requiring a control pack 3.6 Circuit Connection Cleanly cut the heating circuit tails to the correct length (level 1 with the interface between the port on the manifold arm and the inserted pipe adaptor) using a suitable pipe cutter inserted into pipe 5 Using a 22mm open-end wrench fully tighten the pipe adaptor 2 Slide the pipe adaptors nut over the end of the pipe, followed by the split olive (1) Fully insert the spigot of the pipe adaptor into the end of the 3 pipe (1) 1 1 4 Hand tighten the nut, ensuring the (2) spigot remains fully 6 Affix the circuit labels provided to the manifold arms (3) 7 Record the circuit lengths in the Commissioning Record located in section 6 of this guide 2 3 3.7 Connection to Primary Pipework Insert the 1” fibre washers supplied as part of the installation kit and hand tighten the connections between the assembled manifold and the isolation valves. Connect the isolation valves to the assembled manifold using the 1” fibre washers supplied in the installation kit (1) Support connecting pipework parallel to and centred with the isolation valves to prevent leaks (2) Note: The Wavin isolation valves are colour coded and have a flat faced, male 1” G connection to the manifold with a 22mm compression fitting to the primary pipework. Email: [email protected] 1 1 www.thermoboard.co.uk 2 9 4. Commissioning 4.1 Quick Circuit Balancing The Wavin Composite Manifold uses the unique Memory Ring to 1 Lift balancing cap and memory ring (1) enable quick and easy balancing. Rotate clockwise until valve is closed (2) 2 3 Refer to recorded circuit lengths in the Commissioning Record Example: and identify the correct Memory Ring setting using the table Longest circuit connected to manifold = 110m below (3) 4 Rotate memory ring anti-clockwise until the correct value is Length of circuit to be balanced = 100m aligned with pointer on balancing cap (4) Memory ring setting = 10.8 5 Push memory ring down into position (5) Open the balancing valve to its balanced position by rotating the 6 Note: From this point the circuit can be isolated and rebalanced balancing cap anti-clockwise until the pointer reaches the stop simply by lifting and turning the balancing cap between its closed on the memory ring (6) and its balanced position marked by the memory ring. 7 Push the balancing cap down into position (7) 2 6 1 5 7 4 3 Circuit Length Longest -10m -20m -30m -40m -50m -60m -70m ≤-75m Setting 12.0 10.8 9.6 8.4 7.2 6.0 4.8 3.6 3.0 Memory Ring Setting = (Circuit Length – Longest Circuit Length) x 0.12 + 12 The minimum recommended setting is 3.0 10 Telephone: 01392 444122 Fax: 01392 444135 4. Commissioning 4.2 Flushing and Filling The underfloor heating (UFH) system can be filled via the primary flow connection (setting the Thermostatic Actuator to 6 if acontrol pack is installed), however it is recommended that the first flush and fill is conducted by connecting a mains pressure feed to the fill/ drain ports. This will ensure that any debris or contaminants are not 4 Attach a drain pipe to the fill/drain port on the return side of the manifold (4) 5 Open the valves to the filling/drain pipes (5) 6 Open the first circuit (both the flow and return sides) (6) flushed into other components on the heating system. 7 Flush until the discharge water is clear and free of air (7) 1 Ensure all isolation, fill/drain, balancing and return isolation valves 8 Close the circuits return valve, followed by its flow valve (8) are closed (1) 9 Repeat steps 6 to 8 for all other circuits (9) 2 Open the caps on the automatic air vents, 1 1/ turns (2) 2 3 Attach a filling pipe to the fill/drain port on the flow side of the Note: Maximum permissible pressure during flushing and filling is 5 bar manifold (3) 2 6 8 9 1 3 4 7 4.3 Hydraulic Pressure Testing 1 Close isolation valves on the primary connection to the manifold Note: Repairs to circuits must be kept accessible with their precise 2 Open all circuit valves on flow and return arms location recorded in the Commissioning Record. 3 Connect a hydraulic pressure tester to one fill/drain port 4 Raise the pressure to 1bar. Hold this pressure for 45 minutes and inspect system for leaks. If fittings are present within the system it is recommended that they are flexed during this inspection 5 Increase the pressure to 6 bar. Hold this pressure for 15 minutes and continue to inspect 6 Reduce the pressure to 2bar. Hold this pressure for 45 minutes and continue to inspect If a pressure loss is observed • Pressurise the system to its previous test pressure and isolate all circuits • Observe for a continued pressure drop over the same test period 7 Safely depressurise the system If a further drop occurs there is 8 Record the test results in the Commissioning Record a leak from the manifold 9 Dispose of the discharged water in compliance with National • Identify the leak and call Health & Safety Regulations If there is a danger of freezing, suitable measures (such as the addition Technical Support (01392 444122) If the pressure drop ceases, there is a leak from a circuit • Open and close each circuit in turn, observing the pressure gauge for an instant pressure drop If a leak is identified • Safely depressurise the system • Isolate the leaking circuit • Locate and repair the leak • Repeat the pressure test of anti-freeze additives or building conditioning) must be taken. Email: [email protected] www.thermoboard.co.uk 11 4. Commissioning 4.4 Electrical Installation 3 Electrical connections to the circulating pump, flow watch protection Mounting the actuators: thermostat and actuators should be made in accordance with the 1 Unscrew the blue isolation caps from the thermoelectric actuator instructions supplied with the control centre used. mounts. (1) 2 Push the head of the actuators onto the adaptor until they click. (2) Note: To make mounting easier, Wavin actuators are in the open position and will not close the valve until after their first activation. 1 2 4.5 Temperature and Pump Settings* Initial heating should commence with the flow water temperature Products with restricted operating temperatures should not be between 20°C and 25°C. This temperature should be maintained installed without first ensuring they are suitable for use and will not for at least 3 days. The flow water temperature should then be adversely restrict the system performance. increased to the systems design temperature. This temperature 1 Commission the Grundfos circulator in accordance with the should be maintained until the moisture-content of the floor and air are both stable (minimum 4 days). For Screed Floors the maximum recommended flow temperature is 55°C. A standard sand/cement screed should be allowed to cure for 21 days after being laid before commencing the initial heating procedure. Under no circumstances should the underfloor heating be used to speed up the curing process. For other coverings please refer to the manufacturers instructions. For Timber Floors the maximum recommended flow temperature is 60°C. Before laying timber flooring, it should be acclimatised to manufacturers instructions and set it to speed III 2 Adjust the flow water temperature by turning the thermostatic actuator. Refer to the table below and/or the temperature gauge on the flow arm of the manifold to achieve the correct setting 3 Disengage the discrete white lock ring around the base of the blue thermostatic actuator and reposition it to prevent overheating due to tampering 4 Set the Flow Watch thermostat 10°C higher than the setting of the thermostatic actuator the room with the UFH system at design temperature until such time that its moisture content is stable, typically around 10%. Heated floor surfaces should not exceed 9°C above the design room Note: Some heat sources will have an operational requirement for temperature (15°C for peripheral areas). the difference in flow and return temperatures to be greater than a specific value. As a result it may be necessary to reduce the pump Note: *Only applies to installations requiring a control pack 12 speed in order to increase the temperature drop. Position 1 2 3 4 5 6 Temp (°C) 10 20 30 40 50 60 Telephone: 01392 444122 Fax: 01392 444135 4. Commissioning / 5. Troubleshooting and Maintenence 4.6 Advanced Circuit Balancing The Quick Circuit Balancing (section 4.1 page 10) method 3 Adjust each circuit’s setting until they all have an identical return applies hydraulic balance to the circuits and does not take into water temperature, ensuring that the circuit with the highest consideration the project specific details which affect the heating specific demand is set to 12 and all other circuit’s are balanced demand on each circuit. against it Advanced balancing matches the return water temperature of each circuit. It only needs to be applied if some circuits on the manifold supply an area with an unusually high demand. 1 Install Wavin clip-on thermometers on the return of each circuit connecting to the manifold 2 Run the system in heating mode for 3 hours with continuous There will be a 2–3 minute delay between changing the setting and observing a change 4 After 20–30 minutes repeat from step 3 until the return water temperatures remain balanced demand. This may require the room thermostats to be set above each room’s design temperature 5.1 Troubleshooting Symptom No heat in any zone Problem Solution UFH system not turning on Ensure the UFH controls are programmed correctly, and the heat source isavailable to provide hot water for the programmed period. Heat source/UFH pump not running Ensure at least one thermostat is calling for heat and that the switched lives to the boiler and the circulators become live according to demand. Primary flow and return pipes crossed Check the flow and return pipes from the heat source are correctly connected to the manifold. Valves closed Check the isolation valves are open, the balancing valves are in theirbalanced positions and that the thermoelectric actuators are opening ondemand (a white band will be visible on the raised cap). UFH keeps switching off Flow Water Protection thermostat is activating Check the flow temperature from the manifold is correct and that limit thermostat is set 10°C higher. If flow temperature is not responding correctly check thermostatic actuator for fault Some zones do not become warm Air trapped within pipework Set the UFH pump to speed setting III, open the balancing valve fully for the problem zone ensuring all other zones are isolated. Air should automatically vent from the system. Manifold incorrectly balanced Perform Quick and if necessary Advanced Circuit Balancing. Manifold incorrectly balanced Perform Quick and if necessary Advanced Circuit Balancing. Flow temperature set too low Check the blending valve is set correctly and that the primary flow temperature into the mixing valve is equal to or warmer than the required secondary flow water temperature. High heat losses Some rooms will have higher heat losses than others, such as a conservatory. The effects can be compensated for by setting the heating to come on for longer in these zones. Thermally resistive floor finish Some floor constructions work more efficiently with underfloor heating. For example stone or tiled floors have a greater heat output than carpeted ones (check floor manufacturers details). Zone takes a long time to warm up Email: [email protected] www.thermoboard.co.uk 13 5. Troubleshooting and Maintenence / 6. Technical Specification 5.2 Checking System Performance Once the system is fully commissioned, thermostats should be re-checked to ensure they are operating the correct thermoelectric actuator. If the thermostat calculates the room will take 45 minutes to reach 20°C from the current temperature, the heating would be turned on at 6:15am. If the heated property is newly constructed or if it has had substantial work carried out on it, the moisture in the air and fabric of the property will significantly increase the heat losses. As a result it may not be possible to achieve the desired temperatures until the moisture content has normalised. Where standard thermostats are used, it is recommended that from a cold start the system should be programmed to start its heating cycle 1–11/ hours before the set room temperature is required. An Infra red thermometer can be used to check the floor temperature. The underfloor heating should typically exhibit a surface temperature of 27–29°C, when the ambient air temperature is about 18–20°C. Wavin programmable thermostats incorporate optimised start, and will therefore calculate the correct time to turn the underfloor heating on in each zone, in order to achieve the set temperature at the set time. For example, if a temperature of 20°C is required at 7:00am, this time and temperature is what would be set on the thermostat. 2 Warm up times for underfloor heating systems vary according to the following factors: l External temperature l Target internal temperature l Level of insulation l Ventilation rate l Mean water temperature l Floor construction l Floor covering 5.3 Care and Cleaning l During all construction activities cover the manifold with a polyethylene sheet or an enclosure to prevent damage. l Periodically inspect the system for leaks and erosion of brass and plastic components. l l Follow the heat source recommendations with regards to flushing and additives. Clean the manifold with a soft cloth. Note: Do NOT use detergents to clean the manifold. 6 Technical Specification Material Connections Medium Pressure Temperature Maximum Flow Rate Manifold Size Standards BBA Certificate Manifold Body PA6.6 - Glass Filled Manifold Seals EPDM Control Pack / Connections Brass Primary 1” G Flat Faced Female Union Secondary Pipe Adapters for 16mm x 1.8mm Polybutylene Pipe Fill / Drain 3/4” G Flat Faced Male Water, Glycol Solutions Max Percentage of Glycol 30% Maximum Testing Pressure 8 bar Maximum Operating Pressure 4 bar Maximum Temperature 100°C Maximum Operating Temperature 70°C Minimum Temperature 4°C Controlled Temperature Range* 10-60°C Primary 60 l/min (30 l/min)* Secondary 8 l/min Maximum Number of Ports 12 BS EN ISO 15876-1 : 2003, BS EN ISO 15876-3 : 2003 and BS EN ISO 15876-5 : 2003, application class 4, for a lifetime of 25 years and a design pressure of 4 bar. 92/2823 *Only applies to installations requiring a control pack 14 Telephone: 01392 444122 Fax: 01392 444135 7. Commissioning Record 7 Commissioning Record Manifold Number Temperature Setting* Pump Setting* Flushed and Filled Pressure Test Completed Fully Operational Circuit Number Room Served Zone Number Circuit Length Memory Ring Setting Passed Pressure Test? 1 2 3 4 5 6 7 8 9 10 11 12 Location of Leak Action Taken Location of Fitting if Repaired Passed Pressure Test? Yes / No Yes / No Yes / No Yes / No name company I ______________________________________ of ______________________________________ hereby declare that the UFH system is fully comissioned in accordace with the guidelines set out within this installation guide. Signed: ______________________________________ Note: Failure to present this comissioning record (accurately completed with the declaration signed), when required, will void system warranty. Email: [email protected] www.thermoboard.co.uk 15 Surface heating and cooling solutions by Wavin Thermoboard – ensuring the right solution Under the Thermoboard brand Wavin offers solutions for surface heating and cooling for domestic and light commercial environments. Thermoboard systems and services are designed to enable speedy selection and correct installation of the right solution for each situation – ensuring project success, with complete peace of mind. UFH it’s what we do ISO 9001:2000 Wavin is a member of the Underfloor Heating Manufacturers Association Wavin operates a programme of continuous product development, and therefore reserves the right to modify or amend the specification of their products without notice. All information in this publication is given in good faith, and believed to be correct at the time of going to press. However, no responsibility can be accepted for any errors,omissions or incorrect assumptions. Users should satisfy themselves that products are suitable for the purpose and application intended. Wavin Underfloor Heating Division The Dart Building Grenadier Road Exeter Business Park Exeter, Devon EX1 3QF Tel: 01392 444 122 [email protected] Wavin provides effective solutions for essential needs of daily life: safe distribution of drinking water; sustainable management of rainwater and waste water; energy efficient heating and cooling for buildings. Wavin’s European leadership, local presence, commitment to innovation and technical support, all benefit our customers. We consistently achieve the highest sustainability standards, ensure total reliability of supply to support our customers to achieve their objectives. www.thermoboard.co.uk UF428 – July 2012 Solutions for Essentials
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement