DISTRIBUTION SERIES DC Load Distribution Panels The Power of Reliability

DISTRIBUTION SERIES  DC Load Distribution Panels The Power of Reliability
The Power of Reliability
DC Load Distribution Panels
DISTRIBUTION SERIES
DC Load Distribution Panels
The ICT DISTRIBUTION SERIES fuse-protected DC load
distribution panels allow you to connect multiple DC loads to a
single power source, thereby providing a flexible, cost effective
approach to site DC power design. The 1RU 19-inch rackmount
design saves valuable space, and the fuses are mounted on the
front for easy replacement. Twelve output circuits allow you to
expand your system as your needs grow, without giving up more
valuable rack space.
From the Standard model for applications where no remote
monitoring or control is required, to Intelligent and Broadband
models that are I.P. enabled for remote monitoring and power
control, the ICT Distribution Series has a model that will meet
your requirements for 12, 24, or 48VDC applications.
Ease of Installation and Use
Space Saving Design
Fuses are mounted on the front to facilitate easy replacement.
Alarm LED indicators and Form C alarm contacts are provided on all
models to assist with troubleshooting and fault detection. Heavy
duty stud connectors are provided for the main DC inputs, and
space saving terminal blocks are used for the outputs. The I.P.
enabled models have an intuitive, easy to use Graphical User
Interface that can be accessed from a standard web browser.
The 1RU 19-inch standard rack mounting with handles saves
valuable rack space. Twelve individual DC output circuits and the
150 amp continuous current rating help reduce the need for
multiple panels. Input and output cables do not require extra room
above or below the panel chassis.
Remote Monitoring
All models come with a 3-year warranty. The convection cooled
design means there are no moving parts to fail. Intelligent and
Broadband models are I.P. enabled for remote monitoring, and the
Remote Power Control models allow remote shutdown or power
cycling of individual outputs. Firmware can be updated remotely
over the web.
The Intelligent and Broadband models are I.P. enabled, and utilize a
built-in Ethernet connector and integrated web server to allow
users to remotely monitor load conditions at the panel. This can
provide an indication of a problem with the DC power service, or
with an individual device such as a radio, repeater, or RF amplifier
that is connected to the panel. These models will also send text or
email alerts to indicate when a fault status is triggered. Up to 30
hours of data logging is provided.
Performance and Flexibility
Remote Power Control
All models feature a continuous current rating of 150 amps to allow
a large number of DC devices to be connected to a single panel. The
Standard and Intelligent models utilize nine standard ATO type fuses
rated at up to 25A each, plus three Maxi fuses with 40A ratings,
allowing you to mix the size and type of devices you can connect to
these 12 or 24VDC models. Broadband models feature 12 GMT
fuses rated at 15A each.
The Remote Power Control models allow the individual DC outputs
to be turned on and off remotely using the TCP/IP connection. This
allows connected devices to be turned on and off or power cycled,
potentially averting the need for an on-site service visit. The power
cycling feature allows outputs to restart automatically, allowing
device such as LAN links to be power cycled without risk of losing
communications to the panel. Automatic load shedding is provided
with user definable settings, allowing non-critical loads to be shut
down in order to prolong power to critical loads.
Lowest Cost of Ownership
Page 1
Innovative Circuit Technology Ltd.
26921 Gloucester Way, Langley, BC, Canada V4W 3Y3
Tel: 604-856-6303 | Fax: 604-856-6365 | Email: sales@ictcorporate.com | www.ict-power.com
800-313-002
The Power of Reliability
DC Load Distribution Panels
Output 1
Amps:
4.58
Volts: 13.8
Output 6
Amps:
1.74
Volts: 54.4
Output 6
Amps:
1.74
Volts: 54.4
ICT180-12
ICT180-12I
ICT180-12B
ICT180-12IRC
Standard
Distribution
Panel
Intelligent Panel
with TCP/IP
Remote Monitoring
Broadband Panel
with TCP/IP
Remote Monitoring
Intelligent Panel
With TCP/IP Remote
Power Control
ICT180-12BRC or
ICT180-12BRCP
Broadband Panel With
TCP/IP Remote Power Control
Power Specifications
Application Voltage
-48VDC
12 and 24VDC
12 and 24VDC
Panel Current Rating (Peak)
180A
Panel Current Rating (Continuous)
150A
ATO Fuse Rating (Max)
Number of MAXI Fused Outputs
MAXI Fuse Ratings (Max)
Number of GMT Fused Outputs
GMT Fuse Rating (Max)
(5)
-20C to +60C
Operating Temperature Range
Number of ATO Fused DC Outputs
-48VDC / +48VDC
40A (1)(2)
15A (1)(3)
-------
3
3
40A
-------------
9
25A (1)(2)
9
25A (1)(2)
(1)(2)
40A
-------
Operating Voltage Range
(1)(2)
------10-30VDC
-------------
9
25A (1)(2)
3
12
10-60VDC
12
15A (1)(3)
10-30VDC
10-60VDC
Mechanical
1RU - 19 Inch Rack Mount With Handles
Form Factor
Dimensions (inches) L x W x H
5.4 x 19.0 x 1.72
Weight (lbs/kg)
4.0 lbs / 1.8 kg
9.29 x 19.0 x 1.72
7.0 lbs / 3.2 kg
Fuse Position
Front Panel
LED Alarm Indicators
Front Panel
----
LCD Digital Display
Front Panel
Connectors
DC input stud connectors, DC output terminal blocks, Form C alarm contacts, grounding stud, RJ-45 Ethernet (4)
Rear Panel
Environment
-20C to +60C
Operating Temperature Range
Communications and Control
Form C alarm contacts (C/NO/NC)
Remote Alarms
----------------------
-------
-------
Auto Load Shedding
----
----
----
User selectable low-voltage setting and
output selection, manual or auto restart
Unassisted Power Cycling
----
----
----
Outputs will power cycle with no
external command required
LAN Communications
Security
Remote Status Monitoring
Email and SMS Alerts
Data Logging
Remote Power Control
Power-up Delay Sequencing
TCP/IP, built-in web server and graphical user interface
SSL encryption, password protected
System voltage and current, current draw at each output
Two individual email or text accounts, adjustable intervals
Up to 30 hours at 1 minute sampling rate, csv file download
Each DC output on/off selectable
User selectable 0 to 60 second delay
between outputs energizing
(1) Please follow all recommendations of the fuse manufacturer. Generally fuses and wiring should be continuously operated at no more than 80% of their current rating.
(2) 12/24V models ship with assortment of ATO fuses installed. (3) 48V models ship without GMT fuses. (4) Intelligent and Broadband models only. (5) ICT180-12BRC
is factory configured for negative 48VDC (positive ground), while ICT180-12BRCP is configured for positive 48VDC (negative ground) installation.
ICT logos and slogans © copyright Innovative Circuit Technology Ltd. Specifications subject to change without notice.
Page 2
Innovative Circuit Technology Ltd.
26921 Gloucester Way, Langley, BC, Canada V4W 3Y3
Tel: 604-856-6303 | Fax: 604-856-6365 | Email: sales@ictcorporate.com | www.ict-power.com
800-313-002
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising