MultiPlus Inverter/Charger

MultiPlus Inverter/Charger
MultiPlus Inverter/Charger
800 VA –. 5 kVA
Lithium Ion battery compatible
www.victronenergy.com
Two AC Outputs
The main output has no break functionality. The MultiPlus takes over the supply to the connected loads in the
event of a grid failure or when shore/generator power is disconnected. This happens so fast (less than
20 milliseconds) that computers and other electronic equipment will continue to operate without disruption.
The second output is live only when AC is available on one of the inputs of the MultiPlus. Loads that should not
discharge the battery, like a water heater for example can be connected to this output (second output available
on models rated at 3 kVA and more).
Virtually unlimited power thanks to parallel operation
Up to 6 Multis can operate in parallel to achieve higher power output. Six 24/5000/120 units, for example, will
provide 25 kW / 30 kVA output power with 720 Amps charging capacity.
Three phase capability
In addition to parallel connection, three units of the same model can be configured for three phase output. But
that’s not all: up to 6 sets of three units can be parallel connected for a huge 75 kW / 90 kVA inverter and more
than 2000 Amps charging capacity.
MultiPlus
24/3000/70
PowerControl - Dealing with limited generator, shore side or grid power
The MultiPlus is a very powerful battery charger. It will therefore draw a lot of current from the generator or
shore side supply (nearly 10 A per 5 kVA Multi at 230 VAC). With the Multi Control Panel a maximum generator
or shore current can be set. The MultiPlus will then take account of other AC loads and use whatever is extra for
charging, thus preventing the generator or shore supply from being overloaded.
PowerAssist - Boosting the capacity of shore or generator power
This feature takes the principle of PowerControl to a further dimension. It allows the MultiPlus to supplement
the capacity of the alternative source. Where peak power is so often required only for a limited period, the
MultiPlus will make sure that insufficient shore or generator power is immediately compensated for by power
from the battery. When the load reduces, the spare power is used to recharge the battery.
Solar energy: AC power available even during a grid failure
The MultiPlus can be used in off grid as well as grid connected PV and other alternative energy systems.
Loss of mains detection software is available.
System configuring
In case of a stand-alone application, if settings have to be changed, this can be done in a matter of
minutes with a DIP switch setting procedure.
Parallel and three phase applications can be configured with VE.Bus Quick Configure and VE.Bus System
Configurator software.
Off grid, grid interactive and self-consumption applications, involving grid-tie inverters and/or MPPT
Solar Chargers can be configured with Assistants (dedicated software for specific applications).
MultiPlus Compact
12/2000/80
On-site Monitoring and control
Several options are available: Battery Monitor, Multi Control Panel, Ve.Net Blue Power Panel, Color Control Panel,
smartphone or tablet (Bluetooth Smart), laptop or computer (USB or RS232).
Remote Monitoring and control
Victron Ethernet Remote, Victron Global Remote and the Color Control Panel.
Data can be stored and displayed on our VRM (Victron Remote Management) website, free of charge.
Remote configuring
When connected to the Ethernet, systems with a Color Control panel can be accessed remotely and settings can
be changed.
Color Control Panel, showing a
PV application
MultiPlus
12 Volt
24 Volt
48 Volt
PowerControl
PowerAssist
Transfer switch (A)
Input voltage range (V DC)
Output
Cont. output power at 25°C (VA) (3)
Cont. output power at 25°C (W)
Cont. output power at 40°C (W)
Cont. output power at 65°C (W)
Peak power (W)
Maximum efficiency (%)
Zero load power (W)
Zero load power in AES mode (W)
Zero load power in Search mode (W)
C 12/800/35
C 24/ 800/16
C 12/1200/50
C 24/1200/25
C 12/1600/70
C 24/1600/40
C 12/2000/80
C 24/2000/50
Yes
Yes
16
Yes
Yes
16
Yes
Yes
16
Yes
Yes
30
800
700
650
400
1600
92 / 94
8 / 10
5/8
2/3
AC Input
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A) (4)
Charge current starter battery (A)
Battery temperature sensor
35 / 16
Auxiliary output (5)
Programmable relay (6)
Protection (2)
VE.Bus communication port
General purpose com. port
Remote on-off
Common Characteristics
n. a.
n. a.
Common Characteristics
Battery-connection
230 V AC-connection
Weight (kg)
Dimensions (hxwxd in mm)
10
Safety
Emission, Immunity
Road vehicles
Anti-islanding
1) Can be adjusted to 60 HZ; 120 V 60 Hz on request
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 230 VAC on inverter output
g) input voltage ripple too high
12/3000/120
24/3000/70
48/3000/35
Yes
Yes
16 or 50
24/5000/120
48/5000/70
Yes
Yes
100
INVERTER
9,5 – 17 V
19 – 33 V
38 – 66 V
Output voltage: 230 VAC ± 2%
Frequency: 50 Hz ± 0,1% (1)
1200
1600
2000
3000
5000
1000
1300
1600
2400
4000
900
1200
1400
2200
3700
600
800
1000
1700
3000
2400
3000
4000
6000
10.000
93 / 94
93 / 94
93 / 94
93 / 94 / 95
94 / 95
8 / 10
8 / 10
9 / 11
20 / 20 / 25
30 / 35
5/8
5/8
7/9
15 / 15 / 20
25 / 30
2/3
2/3
3/4
8 / 10 / 12
10 / 15
CHARGER
Input voltage range: 187-265 VAC
Input frequency: 45 – 65 Hz
Power factor: 1
14,4 / 28,8 / 57,6
13,8 / 27,6 / 55,2
13,2 / 26,4 / 52,8
50 / 25
70 / 40
80 / 50
120 / 70 / 35
120 / 70
4 (12 V and 24 V models only)
yes
GENERAL
n. a.
n. a.
n. a.
Yes (16A)
Yes (25A)
Yes
a-g
For parallel and three phase operation, remote monitoring and system integration
n. a.
n. a.
n. a.
Yes
Yes
Yes
Operating temp. range: -40 to +65°C (fan assisted cooling) Humidity (non-condensing): max 95%
ENCLOSURE
Material & Colour: aluminium (blue RAL 5012)
Protection category: IP 21
battery cables of 1.5 meter
M8 bolts
Four M8 bolts (2 plus and 2 minus connections)
G-ST18i connector
Spring-clamp
Screw terminals 13 mm2 (6 AWG)
10
10
12
18
30
375x214x110
520x255x125
362x258x218
444x328x240
STANDARDS
EN-IEC 60335-1, EN-IEC 60335-2-29, IEC 62109-1
EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
12V and 24V models: ECE R10-4
See our website
3) Non-linear load, crest factor 3:1
4) At 25˚C ambient
5) Switches off when no external AC source available
6) Programmable relay that can a.o. be set for general alarm,
DC under voltage or genset start/stop function
AC rating: 230 V/4A
DC rating: 4 A up to 35 VDC, 1 A up to 60 VDC
Computer controlled operation and monitoring
Several interfaces are available:
Digital Multi Control Panel
-
A convenient and low cost solution for
remote monitoring, with a rotary knob to
set PowerControl and PowerAssist levels.
Color Control GX
Provides monitor and control. Locally, and also remotely on the
VRM Portal.
MK3-USB VE.Bus to USB interface
Connects to a USB port (see ‘A guide to VEConfigure’)
VE.Bus to NMEA 2000 interface
Blue Power Panel
Connects to a Multi or Quattro and all
VE.Net devices, in particular the VE.Net
Battery Controller.
Graphic display of currents and voltages.
Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands
General phone: +31 (0)36 535 97 00 | Fax: +31 (0)36 535 97 40
E-mail: [email protected] | www.victronenergy.com
Connects the device to a NMEA2000 marine electronics network.
See the NMEA2000 & MFD integration guide
BMV-700 Battery Monitor
The BMV-700 Battery Monitor features
an advanced microprocessor control
system combined with high resolution
measuring systems for battery voltage
and charge/discharge current. Besides
this, the software includes complex
calculation algorithms, like Peukert’s
formula, to exactly determine the state
of charge of the battery. The BMV-700
selectively displays battery voltage,
current, consumed Ah or time to go.
The monitor also stores a host of data