8 ÷ 74 kW - cf distribution

8 ÷ 74 kW - cf distribution
8 ÷ 74 kW
Air conditioners with displacement air delivery
technicalcatalogue
T_HH_1112_GB
INDICE
GENERAL CHARACTERISTICS ................................................................................................. 3
SERIES IDENTIFICATION ........................................................................................................... 4
MODEL IDENTIFICATION ........................................................................................................... 4
WORKING LIMITS ....................................................................................................................... 5
AIR CONDITIONING SYSTEM WITH DISPLACEMENT AIR DELIVERY .................................... 6
ENERGY SAVING (FREE-COOLING) ......................................................................................... 7
MAIN COMPONENTS .................................................................................................................. 8
OPTIONAL ACCESSORIES ...................................................................................................... 10
TECHNICAL DATA – HEAT HUNTER DX ................................................................................. 11
TECHNICAL DATA – HEAT HUNTER DW ................................................................................ 13
TECHNICAL DATA – HEAT HUNTER CW ................................................................................ 15
ELECTRICAL DATA ................................................................................................................... 16
MP.COM: MICROPROCESSOR CONTROL SYSTEM .............................................................. 17
MISTRAL CONTROL LOGIC ..................................................................................................... 18
AIR-RAIL PATENTED AIR-DISTRIBUTION SYSTEM ............................................................... 20
OPTIONAL ACCESSORIES – CONDENSATE DISCHARGE PUMP (KIT) ............................... 25
OPTIONAL ACCESSORIES – PLENUM WITH FREE-COOLING DAMPER ............................. 26
OPTIONAL ACCESSORIES – FRESH AIR KIT ......................................................................... 27
UNIT DRAWINGS ...................................................................................................................... 29
TYPICAL INSTALLATION DIAGRAMS FOR DIRECT EXPANSION MACHINES WITH
REMOTE AIR COOLED CONDENSER ..................................................................................... 44
2
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
GENERAL CHARACTERISTICS
HEAT HUNTER: Air conditioners with displacement air delivery. R410C refrigerant charge.
The machines are made for indoor installation.
The constructive solutions and the internal lay-out allow high application flexibility and the frontal
access to the main components for the inspection and routine maintenance.
Machines supply fully assembled with refrigerant charge and control systems. The installation
requires electrical and hydraulic /refrigerant connections only allowing high costs and time
reduction.
Final assembly on all machines before shipment including running test, reading and monitoring
of operating parameters, alarms simulation and visual check.
Design, assembly and test as per the Company Quality Assurance program in full compliance
with ISO 9001. RC Group has been the first Italian company in its segment to get the ISO 9001 in
th
October 13 , 1991 with certificate ICIM 0018.
The machines are in full compliance with European Norms 2006/42CE, 2006/95CE,
2004/108CE, 97/23CE and subsequent amendments.
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
3
SERIES IDENTIFICATION
HEAT HUNTER DX – Air conditioners equipped with scroll compressors and inverter
controlled centrifugal fans.
Air suction from the top and air delivery from the front side.
DX Air cooled unit
Cooling capacity 7,8 ÷ 45,5 kW
DW Water cooled unit
Cooling capacity 8,2 ÷ 49,7 kW
HEAT HUNTER CW – Chiller water fed air conditioners equipped with inverter controlled
centrifugal fans.
Air suction from the top and air delivery from the front side.
CW Chiller water fed
Cooling capacity 17,0 ÷ 74,3 kW
MODEL IDENTIFICATION
HEAT HUNTER DX DL FC 010 HH0
4
DX
Unit type
DX direct expansion – air cooled
DW direct expansion – water cooled
CW chiller water fed
DL
Air delivery
DL Displacement
FC
Version
-- Standard
FC with free-cooling plenum
010
Cooling capacity (kW)
HH0
Cabinet size
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
WORKING LIMITS
COOLING - room air temperature:
14°C
minimum temperature with wet bulb.
16°C
minimum temperature with dry bulb.
24°C
maximum temperature with wet bulb.
32°C
maximum temperature with dry bulb.
COOLING - room air humidity:
20%RH
minimum relative humidity.
75%RH
maximum relative humidity.
REMOTE AIR COOLED CONDENSER
Ambient temperature:
20°C
minimum temperature with nominal air flow rate.
20/-15°C
temperature range with air flow rate control
45°C
maximum temperature.
WATER COOLED CONDENSER
Water temperature:
30/48°C temperature range from the condenser.
The values are indicative. The working temperatures are influenced by a
series of variables as:
 Working conditions
 Thermal load
 Cleanness status of the condensing coils
 Set of the microprocessor control
STORING TEMPERATURE
If the machine is not installed on receipt and is stored for a long time, store it in a protected
place, at temperatures ranging between -30°C and 50°C in absence of superficial
condensation and direct sun light.
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
5
AIR CONDITIONING SYSTEM WITH DISPLACEMENT AIR DELIVERY
The basic concept of the air conditioning system with displacement air delivery is based on
the natural convection principle, where the cold air is at the lower ambient zones, while the hot
air is at the higher ones.
This concept has been developed and applied by RC GROUP for the air conditioning in
Telephone Exchangers and Hi-Tech. facilities.
The modern Telecom devices have the aim of heat dissipation by air suction from the lower
side close to the floor, for discharge from the top side.
The air circulation inside the Telecom device can be in natural convenction mode or through
internal fans.
The RC GROUP free-cooling air conditioning system with displacement air delivery supplies
the cold air directly into the room close to the floor with extremely low air speed and intakes
the air from the top side of the conditioner where the air temperature is higher.
Therefore, the Telecom devices intakes the cold air from the bottom and discharges the hot
air from the top.
The system and the extremely low air speed, causes a high air stratification with 10°C
temperature difference between the coldest and the most hot zone. For example we can
consider a temperature condition of 22°C close to the floor and 32°C close to the ceiling with a
mean temperature of 26°C at 1,7m height from the floor.
By hot air suction in the higher ambient zone, the air conditioner remarkably increases both
the thermodynamic performance and the efficiency, with consequent working conditions and
energy consumption optimization.
DISPLACEMENT PLANT
Return air flow (hot air)
Delivery air flow (cold air)
Rack
HEAT HUNTER air conditioner
6
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
ENERGY SAVING (FREE-COOLING)
For an energy-saving, the RC GROUP conditioners are equipped with a proportional
automatic free-cooling system in order to obtain free cooling when the indoor temperature is
higher than outdoor one.
Practically, the fresh air is used as coolant, when the outside conditions allow for this, in order
to cool the ambient.
The cooling system is fully proportional and allows three working mode type:
total free-cooling: only fresh air is used to cool the ambient
partial free-cooling: the fresh air is used for a pre-cooling and the compressor is used
to balance the load.
mechanical cooling: the compressor is used to cool the ambient.
The fresh air put in the ambient causes an internal pressure increase, that must be avoided to
grant a correct performance of the plant.
For this reason it is necessary to install an overpressure damper close to the ceiling, to allow
the hot air discharge.
Please note the overpressure damper, necessary for the correct running of the plant, placed
at the opposite side of the air conditioner close to the ceiling.
DISPLACEMENT PLANT WITH FREE-COOLING
Overpressure damper
Fresh air inlet
Return air flow (hot air)
Air delivery flow (cold air)
Rack
HEAT HUNTER air conditioner
Free-cooling plenum
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
7
MAIN COMPONENTS
COMMON COMPONENTS

Base, inner frame and upper perimetral frame painted with epoxy powders. The inner
frame is provided with seals to ensure air tight with the panels. Base, inner frame and
upper perimetral frame in Black colour.

Galvanized steel sheet panels externally coated with PVC film. The panels are internally
insulated with noise absorption material and fixed to the frame with non visible bolts
system. The panels have a colour similar to RAL 7015 - Slate gray - with hammered
finish.

Electric board in separate technical compartment on the unit front.

Electric board, regulations and control devices in separated technical side compartment
on the unit front (starting from H4 casing included).

Air flow:
Air intake from the unit top.
- Air delivery from the unit front through special grille directly obtained on frontal
panels.

Patented AIR-RAIL system to "guide" the laminar air flow through aerodynamic inductors
placed on unit base.

Washable air filters with cells in synthetic fibre having G4 efficiency.

Air flow equalizer system placed upflow of the cooling coil.

Double suction centrifugal fan with forward blades, directly coupled to a 3 phase – 6 poles
electric motor with external rotor.

Inverter for the continuous control of the fan rotation speed.

Rubber holders for supply fans.

Rubber gasket for the fan outlet sealing to the unit structure.

Cooling coil with copper pipes, aluminium finning and galvanized thick steel frame

Condensate tray made of peraluman with PVC flexible discharge.

Temperature sensors on air intake.

Temperature sensor on air delivery.

MP.COM microprocessor control system with display and keyboard.

Patented MISTRAL logic for the control of the temperature gradient and the air flow.

Electric board: on units size HH1, HH2 and HH3 the electric board is mounted on slides
and completely extractable. The electric board includes:
Door lock main switch.
Magnetothermic automatic switches.
Contactors.
Auxiliary circuit and microprocessor feeding by transformer.
8
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
DIRECT EXPANSION UNITS COMPONENTS

SCROLL type hermetic compressor with built-in integral electric protection, built-in
silencer on gas discharge and crankcase electric heater.

Rubber holders for compressor.
 Phases monitoring relay for each compressor.

Components of cooling circuit:
Thermostatic expansion valve with external equalizer.
Liquid and moisture indicator.
Dryer and anti-acid gas filter.
Solenoid valve on liquid line.
Liquid received complete with accessories.
Low pressure safety switch.
High pressure safety switch.
High pressure transducer, on gas discharge, for monitoring, control and safety
functions of the condensing pressure.
Copper piping.
- Flexible piping for pressure switches connection.
R407C refrigerant charge and non freezing oil charge.
DX VERSION

0÷10V proportional signal to manage the condensing control system of the remote air
cooled condenser.

Valves on gas delivery and liquid return for unit connection to remote air cooled
condenser.
DW VERSION

Stainless steel AISI 316 welded plate type water cooled condenser for city, well or tower
water.
WARNING
For DX units it is necessary to provide the refrigerant charge for the connection pipes
and for the remote air cooled condenser.
CHILLED WATER UNITS COMPONENTS
CW VERSION

2-way motorized cooling valve with proportional action. The 2-way valve is for plant with
variable water flow. It is possible to modify the valve in 3-way by removing the cap on the
third way valve (by-pass way).

Copper water pipes with anticondensate insulation.
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
9
OPTIONAL ACCESSORIES



















Remote air cooled condensers equipped with axial fans (TEAM MATE), available in
standard solution (STD), low noise (LNO) and extremely low noise (ELN).
Proportional controlled steam humidifier with immersed electrodes fitted with safety and
running accessories (temperature and humidity sensor on air intake is included).
Dehumidification system through air flow reduction. This accessory includes the
installation of the temperature/humidity combined sensor on the air intake.
Electric heater consisting of aluminium armoured elements with integral finning fitted with
safety thermostat.
Compressor capacitor for power factor - cosø 0,9 (DX / DW versions).
Compressor noise deadening cap for a noise reduction of about 5 dB(A) (DX / DW
versions).
Water regulating calve for condensing control (DW version)
Disposable air filters with F5 efficiency.
Kit for condensate discharge that include water pump with float switch and 10m linear of
discharge plastic pipe.
Clogged filters alarm through differential air pressure switch on air side.
Air flow loss alarm.
Floor water presence alarm with sensor.
Additional underfloor water sensor kit.
Temperature/humidity probe on air intake
Remote room temperature probe.
Chilled water inlet / outlet probes (CW version)
Fresh air kit
Plenum with damper for direct Free-Cooling.
MP.COM microprocessor control accessories:
Remote terminal
Line current indication.
Line voltage indication.
Clock card for alarms date and time displaying and memorization.
Serial port RCcom, MBUS/JBUS
Serial port LON
Serial port TREND
Serial port BACnet for Ethernet
Serial port BACnet for MS/TP
Data logger for the memorization of the intervened alarms.
WARNING
RC GROUP reserves the right to accept the matching of the optional installed on the
unit.
10
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
TECHNICAL DATA – HEAT HUNTER DX
Direct expansion, air cooled
MODEL
SIZE
COOLING CAPACITY (1)
Total
kW
Sensible
kW
Compressor power input
kW
Compressor operating current
A
SUPPLY FANS
n.
Air flow
m3/h
Nominal external static pressure
Pa
Max external static pressure (2)
Pa
Operating power input
kW
Max operating current (FLA)
A
COMPRESSOR
Quantity
n.
Max operating current (FLA)
A
Starting current (LRA)
A
Capacity steps
n.
AIR FILTERS
n.
Efficiency
REFRIGERANT
Refrigerant charge (3)
kg
Gas circuit
n.
POWER SUPPLY
V/Ph/Hz
ENERGY EFFICIENCY INDEXES (4)
EER – Energy Efficiency Index
kW/kW
SOUND LEVEL – ISO3744(5)
On air delivery
dB(A)
On air intake
dB(A)
DIMENSIONS
mm
Length
mm
Width
mm
Height
NET WEIGHT
kg
REMOTE CONDENSER (6)
Quantity
n.
TEAM MATE
ELECTRIC HEATER
kW
Capacity
A
Operating current (OA)
n.
Capacity steps
HUMIDIFIER
kg/h
Steam capacity
kW
Power input
A
Operating current (OA)
A
Max operating current (FLA)
REFRIGERANT CONNECTIONS
ODS Ø
Gas delivery
ODS Ø
Liquid return
CONNECTIONS ISO228/1-G
FØ
Humidifier filling
Condensate discharge – rubber pipe F Ø
008
HH0
009
HH0
010
HH0
013
HH1
015
HH1
017
HH1
7,8
7,4
1,7
3,1
1
2200
0
100
0,22
3,40
scroll
1
4,7
28,0
1
1
G4
R410A
2,8
1
400/3/50+N
8,8
8,4
2,1
4,0
1
2200
0
100
0,22
3,40
scroll
1
6,0
38,0
1
1
G4
R410A
2,8
1
400/3/50+N
10,2
9,7
2,5
4,9
1
2200
0
100
0,22
3,40
scroll
1
7,0
46,0
1
1
G4
R410A
2,8
1
400/3/50+N
13,7
13,0
3,0
5,0
1
3300
0
65
0,45
3,40
scroll
1
8,0
43,0
1
2
G4
R410A
3,5
1
400/3/50+N
15,9
15,2
3,8
6,3
1
3300
0
65
0,45
3,40
scroll
1
10,3
51,5
1
2
G4
R410A
3,5
1
400/3/50+N
17,5
16,4
4,2
7,5
1
3300
0
65
0,45
3,40
scroll
1
11,8
64,0
1
2
G4
R410A
3,5
1
400/3/50+N
3,61
3,40
3,39
3,75
3,43
3,39
51,5
57,2
51,5
57,2
51,5
57,2
59,1
64,9
59,1
64,9
59,1
64,9
785
600
1980
205
785
600
1980
205
785
600
1980
205
1470
600
1980
310
1470
600
1980
320
1470
600
1980
320
1
M 11
1
M 11
1
M 14
1
M 17
1
M 20
1
M 25
2,6
3,7
1
2,6
3,7
1
2,6
3,7
1
3,0
4,3
1
3,0
4,3
1
3,0
4,3
1
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
12
12
12
12
12
12
16
12
16
12
16
12
3/4"
1/2"
3/4"
1/2"
3/4"
1/2"
3/4"
1/2"
3/4"
1/2"
3/4"
1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristic referred to room condition at 26°C with 45%UR at 1,7m height from the floor, equivalent to a cooling coil inlet air
temperature of 30°C with 35%UR; air to the condenser at 35°C.
2. Available pressure for Free-Cooling system and ducting, corresponding to nominal air flow with Inverter output at 50Hz.
3. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.
4. The index include the remote air cooled condenser
5. Noise pressure level at 1 meter in free field.
6. For matching to other remote air cooled condensers please refer to RC WORLD selection program
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
11
DATI TECNICI – HEAT HUNTER DX
Direct expansion, air cooled
MODEL
SIZE
COOLING CAPACITY (1)
Total
kW
Sensible
kW
Compressor power input
kW
Compressor operating current
A
SUPPLY FANS
n.
Air flow
m3/h
Nominal external static pressure
Pa
Max external static pressure (2)
Pa
Operating power input
kW
Max operating current (FLA)
A
COMPRESSOR
Quantity
n.
Max operating current (FLA)
A
Starting current (LRA)
A
Capacity steps
n.
AIR FILTERS
n.
Efficiency
REFRIGERANT
Refrigerant charge (3)
kg
Gas circuit
n.
POWER SUPPLY
V/Ph/Hz
ENERGY EFFICIENCY INDEXES (4)
EER – Energy Efficiency Index
kW/kW
SOUND LEVEL – ISO3744(5)
On air delivery
dB(A)
On air intake
dB(A)
DIMENSIONS
mm
Length
mm
Width
mm
Height
NET WEIGHT
kg
REMOTE CONDENSER (6)
Quantity
n.
TEAM MATE
ELECTRIC HEATER
kW
Capacity
A
Operating current (OA)
n.
Capacity steps
HUMIDIFIER
kg/h
Steam capacity
kW
Power input
A
Operating current (OA)
A
Max operating current (FLA)
REFRIGERANT CONNECTIONS
ODS Ø
Gas delivery
ODS Ø
Liquid return
CONNECTIONS ISO228/1-G
FØ
Humidifier filling
Condensate discharge – rubber pipe F Ø
021
HH2
023
HH2
027
HH2
030
HH2
038
HH3
045
HH3
21,3
20,3
4,2
7,5
2
6600
0
65
1,00
3,40
scroll
1
11,8
64,0
1
3
G4
R410A
4,5
1
400/3/50+N
23,8
22,7
5,0
8,8
2
6600
0
65
1,00
3,40
scroll
1
15,0
75,0
1
3
G4
R410A
4,5
1
400/3/50+N
27,7
26,5
6,3
11,4
2
6600
0
65
1,00
3,40
scroll
1
16,0
95,0
1
3
G4
R410A
4,7
1
400/3/50+N
30,3
29,0
7,2
13,4
2
6600
0
65
1,00
3,40
scroll
1
21,0
111,0
1
3
G4
R410A
4,8
1
400/3/50+N
39,1
37,4
8,4
15,5
3
10000
0
65
1,63
3,40
scroll
1
22,0
118,0
1
4
G4
R410A
7,7
1
400/3/50+N
45,5
43,6
10,6
19,3
3
10000
0
65
1,63
3,40
scroll
1
31,0
140,0
1
4
G4
R410A
7,7
1
400/3/50+N
3,70
3,64
3,54
3,46
3,62
3,42
62,2
68,0
62,2
68,0
62,2
68,0
62,2
68,0
64,3
70,0
64,3
70,0
2005
600
1980
390
2005
600
1980
390
2005
600
1980
425
2005
600
1980
440
2540
600
1980
530
2540
600
1980
540
1
M 25
1
M 30
1
M 35
1
M 35
1
M 45
1
M 50
4,5
6,5
1
4,5
6,5
1
4,5
6,5
1
4,5
6,5
1
6,0
8,7
1
6,0
8,7
1
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
18
16
18
16
22
16
22
16
22
22
26
22
3/4"
1/2"
3/4"
1/2"
3/4"
1/2"
3/4"
1/2"
3/4"
1/2"
3/4"
1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1.
Characteristic referred to room condition at 26°C with 45%UR at 1,7m height from the floor, equivalent to a cooling coil inlet air
temperature of 30°C with35%UR; air to the condenser at 35°C.
2.
Available pressure for Free-Cooling system and ducting, corresponding to nominal air flow with Inverter output at 50Hz.
3.
Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.
4.
The index include the remote air cooled condenser
5.
Noise pressure level at 1 meter in free field.
6.
For matching to other remote air cooled condensers please refer to RC WORLD selection program
12
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
TECHNICAL DATA – HEAT HUNTER DW
Direct expansion, water cooled
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
Compressor power input
Compressor operating current
Condenser water flow rate
Condenser pressure drop
SUPPLY FANS
Air flow
Nominal external static pressure
Max external static pressure (2)
Operating power input
Max operating current (FLA)
COMPRESSOR
Quantity
Max operating current (FLA)
Starting current (LRA)
Capacity steps
WATER COOLED CONDENSER
Water volume
Max water flow rate
AIR FILTERS
Efficiency
REFRIGERANT
Refrigerant charge
Gas circuit
POWER SUPPLY
ENERGY EFFICIENCY INDEXES
EER – Energy Efficiency Index
SOUND LEVEL – ISO3744(3)
On air delivery
On air intake
DIMENSIONS
Length
Width
Height
NET WEIGHT
ELECTRIC HEATER
Capacity
Operating current (OA)
Capacity steps
HUMIDIFIER
Steam capacity
Power input
Operating current (OA)
Max operating current (FLA)
CONNECTIONS ISO228/1-G
Condenser water inlet/outlet
Humidifier filling
Condensate discharge – rubber pipe
008
HH0
009
HH0
010
HH0
013
HH1
015
HH1
017
HH1
kg
n.
V/Ph/Hz
8,2
7,8
1,5
2,8
1,4
3
1
2200
0
100
0,22
3,40
scroll
1
4,7
28,0
1
1
0,9
1,8
1
G4
R410A
3,0
1
400/3/50+N
9,2
8,8
1,8
3,6
1,6
3
1
2200
0
100
0,22
3,40
scroll
1
6,0
38,0
1
1
1,0
2,1
1
G4
R410A
3,0
1
400/3/50+N
10,7
10,2
2,2
4,4
1,9
4
1
2200
0
100
0,22
3,40
scroll
1
7,0
46,0
1
1
1,2
2,3
1
G4
R410A
3,1
1
400/3/50+N
14,7
14,0
2,4
4,2
2,5
5
1
3300
0
65
0,44
3,40
scroll
1
8,0
43,0
1
1
1,5
3,2
2
G4
R410A
4,0
1
400/3/50+N
17,0
16,2
3,1
5,3
2,9
7
1
3300
0
65
0,44
3,40
scroll
1
10,3
51,5
1
1
1,5
3,7
2
G4
R410A
4,4
1
400/3/50+N
18,4
16,8
3,7
6,7
3,2
8
1
3300
0
65
0,44
3,40
scroll
1
11,8
64,0
1
1
1,8
4,1
2
G4
R410A
4,4
1
400/3/50+N
kW/kW
4,90
4,53
4,50
5,23
4,82
4,49
dB(A)
dB(A)
51,5
57,2
51,5
57,2
51,5
57,2
59,1
64,9
59,1
64,9
59,1
64,9
mm
mm
mm
kg
785
600
1980
215
785
600
1980
215
785
600
1980
215
1470
600
1980
320
1470
600
1980
340
1470
600
1980
340
kW
A
n.
2,6
3,7
1
2,6
3,7
1
2,6
3,7
1
3,0
4,3
1
3,0
4,3
1
3,0
4,3
1
kg/h
kW
A
A
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
MØ
FØ
FØ
1"
3/4"
1/2"
1"
3/4"
1/2"
1"
3/4"
1/2"
1 1/2"
3/4"
1/2"
1 1/2"
3/4"
1/2"
1 1/2"
3/4"
1/2"
kW
kW
kW
A
m3/h
kPa
n.
m3/h
Pa
Pa
kW
A
n.
A
A
n.
n.
l
m3/h
n.
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristic referred to room condition at 26 C with 45%UR at 1,7m height from the floor, equivalent to a cooling coil inlet
air temperature of 30°C with 35%UR; water temperature to the condenser at 30/36°C.
2. Available pressure for Free-Cooling system and ducting, corresponding to nominal air flow with Inverter output at 50Hz.
3. Noise pressure level at 1 meter in free field.
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
13
DATI TECNICI – HEAT HUNTER DW
Espansione diretta, condensato ad acqua
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
Compressor power input
Compressor operating current
Condenser water flow rate
Condenser pressure drop
SUPPLY FANS
Air flow
Nominal external static pressure
Max external static pressure (2)
Operating power input
Max operating current (FLA)
COMPRESSOR
Quantity
Max operating current (FLA)
Starting current (LRA)
Capacity steps
WATER COOLED CONDENSER
Water volume
Max water flow rate
AIR FILTERS
Efficiency
REFRIGERANT
Refrigerant charge
Gas circuit
POWER SUPPLY
ENERGY EFFICIENCY INDEXES
EER – Energy Efficiency Index
SOUND LEVEL – ISO3744(3)
On air delivery
On air intake
DIMENSIONS
Length
Width
Height
NET WEIGHT
ELECTRIC HEATER
Capacity
Operating current (OA)
Capacity steps
HUMIDIFIER
Steam capacity
Power input
Operating current (OA)
Max operating current (FLA)
CONNECTIONS ISO228/1-G
Condenser water inlet/outlet
Humidifier filling
Condensate discharge – rubber pipe
021
HH2
023
HH2
027
HH2
030
HH2
038
HH3
045
HH3
kg
n.
V/Ph/Hz
23,1
22,0
3,4
6,3
3,8
5
2
6600
0
65
1,00
3,40
scroll
1
11,8
64,0
1
1
1,8
5,1
3
G4
R410A
5,4
1
400/3/50+N
25,2
24,0
4,3
7,8
4,3
7
2
6600
0
65
1,00
3,40
scroll
1
15,0
75,0
1
1
1,8
5,6
3
G4
R410A
5,7
1
400/3/50+N
29,0
27,6
5,6
10,5
5,0
9
2
6600
0
65
1,00
3,40
scroll
1
16,0
95,0
1
1
2,5
6,4
3
G4
R410A
5,9
1
400/3/50+N
32,6
31,0
5,9
11,6
5,6
6
2
6600
0
65
1,00
3,40
scroll
1
21,0
111,0
1
1
3,0
7,2
3
G4
R410A
6,4
1
400/3/50+N
41,3
39,4
7,3
13,9
7,0
10
3
10000
0
65
1,63
3,40
scroll
1
22,0
118,0
1
1
3,0
9,1
4
G4
R410A
9,3
1
400/3/50+N
49,7
47,2
8,5
16,2
8,4
25
3
10000
0
65
1,63
3,40
scroll
1
31,0
140,0
1
1
4,0
12,1
4
G4
R410A
9,5
1
400/3/50+N
kW/kW
5,29
4,77
4,39
4,72
4,65
4,91
dB(A)
dB(A)
62,2
68,0
62,2
68,0
62,2
68,0
62,2
68,0
64,3
70,0
64,3
70,0
mm
mm
mm
kg
2005
600
1980
405
2005
600
1980
405
2005
600
1980
440
2005
600
1980
455
2540
600
1980
550
2540
600
1980
565
kW
A
n.
4,5
6,5
1
4,5
6,5
1
4,5
6,5
1
4,5
6,5
1
6,0
8,7
1
6,0
8,7
1
kg/h
kW
A
A
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
MØ
FØ
FØ
1 1/2"
3/4"
1/2"
1 1/2"
3/4"
1/2"
1 1/2"
3/4"
1/2"
1 1/2"
3/4"
1/2"
1 1/2"
3/4"
1/2"
2"
3/4"
1/2"
kW
kW
kW
A
m3/h
kPa
n.
m3/h
Pa
Pa
kW
A
n.
A
A
n.
n.
l
m3/h
n.
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristic referred to room condition at 26°C with 45%UR at 1,7m height from the floor, equivalent to a cooling coil inlet air
temperature of 30°C with 35%UR; water temperature to the condenser at 30/36°C.
2. Available pressure for Free-Cooling system and ducting, corresponding to nominal air flow with Inverter output at 50Hz.
3. Noise pressure level at 1 meter in free field.
14
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
TECHNICAL DATA – HEAT HUNTER CW
Chilled water
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SUPPLY FANS
Air flow
Nominal external static pressure
Max external static pressure (2)
Operating power input
Max operating current (FLA)
COOLING COIL
Water flow rate
dP coil + valve
AIR FILTERS
Efficiency
POWER SUPPLY
SOUND LEVEL – ISO3744(3)
On air delivery
On air intake
DIMENSIONS
Length
Width
Height
NET WEIGHT
ELECTRIC HEATER
Capacity
Operating current (OA)
Capacity steps
HUMIDIFIER
Steam capacity
Power input
Operating current (OA)
Max operating current (FLA)
CONNECTIONS ISO228/1-G
Water inlet/outlet
Humidifier filling
Condensate discharge – rubber pipe
014
HH0
021
HH1
025
HH1
044
HH2
066
HH3
kW
kW
n.
m3/h
Pa
Pa
kW
A
17,0
15,9
1
2200
0
100
0,2
3,4
25,7
23,8
1
3330
0
65
0,5
3,4
36,0
35,1
2
5500
0
65
0,9
3,4
54,7
51,1
2
6660
0
65
1,0
3,4
74,3
71,5
3
10000
0
65
1,6
3,4
m3/h
kPa
n.
2,7
39
1
G4
400/3/50+N
4,1
30
1
G4
400/3/50+N
5,7
39
2
G4
400/3/50+N
8,7
65
2
G4
400/3/50+N
11,8
47
2
G4
400/3/50+N
dB(A)
dB(A)
55,3
57,2
63,1
65,0
63,3
65,2
66,3
68,2
68,1
70,0
mm
mm
mm
kg
785
600
1980
165
1470
600
1980
270
1470
600
1980
290
2005
600
1980
355
2540
600
1980
435
kW
A
n.
2,6
3,7
1
3,0
4,3
1
3,0
4,3
1
4,5
6,5
1
6,0
8,7
1
kg/h
kW
A
A
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
3
2,3
3,2
4,5
MØ
FØ
FØ
1"
3/4"
1/2"
1 1/4"
3/4"
1/2"
1 1/4"
3/4"
1/2"
1 1/2"
3/4"
1/2"
2"
3/4"
1/2"
V/Ph/Hz
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristic referred to room condition at 26°C with 45%UR at 1,7m height from the floor, equivalent to a cooling coil inlet air
temperature of 30°C with 35%UR; chilled water temperature 7/12°C.
2. Available pressure for Free-Cooling system and ducting, corresponding to nominal air flow with Inverter output at 50Hz.
3. Noise pressure level at 1 meter in free field.
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
15
ELECTRICAL DATA
MAXIMUM ELECTRICAL ABSORPTION CALCULATION
This chapter has the aim to explain the calculation of the maximum absorbed current by the
unit (A), corresponding to extreme working conditions.
Example in cooling mode for unit HEAT.HUNTER.DW.027.HH2
COOLING (1)
- Main fans (FLA)
- Compressor (FLA)
- Electric heaters (OA)
Absorbed current
A
A
A
A
3,4
16,0
6,5
25,9
+
+
=
COOLING (2)
- Main fans (FLA)
- Compressor (FLA)
- Humidifier (FLA)
Absorbed current
A
A
A
A
3,4
16,0
4,5
23,9
+
+
=
HEATING (3)
- Main fans (FLA)
- Electric heaters (OA)
- Humidifier (FLA)
Absorbed current
A
A
A
A
3,4
6,5
4,5
14,4
+
+
=
The COOLING (1) working condition corresponds to the unit maximum electric absorption.
I
IMPORTANT
For the axial and centrifugal fans, the current nominal values have been considered
equal to the data plate values. For this reason, the nominal current and the data plate
current is the same.
Actually, the real absorbed current is normally lower than the data plate value.
These values depend on the unit working conditions and on the type of control of the
plant.
16
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
MP.COM: MICROPROCESSOR CONTROL SYSTEM
The MP.COM microprocessor control system is equipped with 8 keys terminal and back
lighted graphic display on which all information in different languages or easily identifiable
symbols are displayed.
The system disposes of a “flash” memory that preserves the information even in absence of
power supply.
KEYBOARD FUNCTIONS
KEY 1
Switches on/off the unit.
KEY 2
Stops the alarm acoustical signal and displays the intervened alarm.
KEY 3
Accedes to the parameters of possible units connected in LAN network.
LAN connection with 3 wires without additional accessories. It is possible to connect
in network different capacity units and with different number of compressors.
KEY 4
Home key – displays the main screen.
KEY 5
Accedes to control and visualization menus as:
Unit working status
Set-points
Alarms reset (protected by password)
Service parameters setting (protected by password)
Intervened alarms history
Setting for main components manual operation (protected by password)
Date and time setting
Setting of communication system for SMS messages dispatch
KEY 6
Scroll the pages inside each menu and decreases the displayed value
KEY 7
Scroll the pages inside each menu and increases the displayed value
KEY 8
Shift the cursor inside each menu and confirm a parameter insertion
REMOTE CONTROLS/ALARMS
INLETS
1 External enabling
2 Cooling enabling
4 Smoke/Fire alarm
•
•
•
OUTLETS
1 General alarm 1 – deviating contact
2 General alarm 2 – programmable deviating contact (optional)
3 General alarm 3 - programmable deviating contact (optional)
••
••
••
• controls/alarms for remotization
•• voltage free controls/alarms for remotization
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
17
MISTRAL CONTROL LOGIC
The HEAT HUNTER air-conditioners are controlled trough the patented MISTRAL
(Modulating control of Indoor STRAtification Layer) control logic.
Since the engine of a displacement system is the difference between the air temperature
close to the ceiling and close to the floor (room Dt), for a correct plant working condition this
difference must be the same in every working conditions.
The system controls the room air temperature. The humidity control is optional.
THE ROOM AIR TEMPERATURE CONTROL
The room air temperature control is obtained by three different measured temperature:

conditioner air intake temperature

room temperature close to the conditioner (with additional sensor)

conditioner air delivery temperature
The room temperature corresponds to the mean air temperature at 1,7m height from floor in
the racks corridor.
The control logic foresees that the conditioner air delivery temperature is controlled through a
variation of the conditioner air flow, keeping the room Dt constant.
The temperature is controlled through the conditioner air intake probe, it activates the
compressor when the temperature rises.
The conditioner air delivery probe controls the supply fan speed between 75% and 100%, to
maintain the air delivery temperature set-point.
With compressor off the air flow is automatically reduced to 30% of the nominal air flow.
ADDITIONAL TEMPERATURE SENSOR
Each conditioner can be wired to an additional probe to measure the room temperature in a
determinate point of the room.
These additional probes must be used only if strictly requested.
We suggest two types of usage:

The presence of a highly temperature sensitive device and/or with a thermal load higher
than the average. In this situation the probe should be placed close to the device and
wired to the nearest conditioner.

Some particular situations of the room lay-out.
The additional probe compensates the compressor set-point, increasing or decreasing it, to
keep the air temperature set-point where the probe is installed.
On the contrary, with room temperature lower than set-point, the control is made by
temperature measured by conditioner as previously described.
THE ROOM RELATIVE HUNIDITY CONTROL
The room relative humidity control takes place only if the conditioner is equipped with the
additional Relative Humidity probe.
When the relative humidity exceeds the set-point, the control decreases the air delivery
temperature set-point. This reduction causes not only an automatic air flow reduction and an
increase of the differentials set-point, but also a lower relative humidity of the air delivery, able
to increase the latent heat and to correctly dehumidify the room.
ADVANTAGE OF THE MISTRAL LOGIC
The MISTRAL control logic allows two types of advantages.
The first advantage regards the temperature gradient in the room where the air-conditioner
has been installed.
Within the air-conditioner’s range of operation, i.e. when the capacity delivered by it is greater
than 0%, thanks to the patented MISTRAL control logic, the gradient is equal to the designed
value.
18
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
On the contrary, with the traditional control logic, without modifying the air flow, the gradient
decreases and its values prevent the correct operation of the system, because the
displacement principle cannot work well if the differential temperature values are too low.
TEMPERATURE GRADIENT
MISTRAL – The temperature gradient
CARICO
MISTRAL control logic
Traditional control logic
Area for a correct performance of the Displacement system
The other advantage is connected with the power consumption of the fans, of the variation if
the air flow depends on a variation in the fan’s rpm.
With the traditional system the ventilation capacity is always at its peak, regardless of the air
temperature in the room (and accordingly, regardless of the capacity required by the system).
When using the system patented by RC, the capacity decreases considerably according to the
room temperature (i.e. the capacity required by the system).
This decrease is different according as the fans are supplied through Inverter or phase-cut
electronic regulator.
Thanks to MISTRAL control logic, it is possible to obtain the best energy savings in every load
conditions, even at 100%. Indeed, in a plant with two Heat Hunter air conditioners (Master and
Slave), it is more convenient to have both conditioners working at 50% than only one working
at 100% of the load.
With both conditioners working at 50%, the supply fan power input for each unit is the 12,5%
of the maximum.
In this way 75% energy saving in supply fans power input is achieved.
SUPPLY FAN
ELECTRIC CONSUMPTION
MISTRAL – Supply fans electric consumption
LOAD
MISTRAL – Inverter controlled supply fan
Phase-cut controlled supply fan
Traditional supply fan
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
19
AIR-RAIL PATENTED AIR-DISTRIBUTION SYSTEM
The AIR-RAIL distribution system can create an "adhering vein of air", so as to "guide" the air
flow by induction and to convey it where it is actually needed, and thus preventing any bypass phenomena after the collision between the air flow leaving the air-conditioner and the
racks.
The formation of the adhering vein is essential, because the displacement distribution, due to
the low speed, does not produce any induction effect. The flow is properly distributed where
there is enough space, but encounters a few problems when the distance between the airconditioner and the rack is limited.
The base of the unit is provided with a series of nozzles that can be capped, where only a
minimum percentage (< 10%) of the air moved by the air conditioner can flow.
Patented AIR-RAIL system
Nozzles
This air forms an adhering vein, at the floor level, that can pull the displacement air flow by
induction.
In practice, this vein makes it possible to convey the air in a proper way, like a sort of rail,
preventing the air from hitting the racks.
AIR-RAIL Typical working diagram
Air conditioner
Rack
Displacement air flow
Adhering air vein
20
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
Nozzles are fitted uncapped while the unused nozzles have to be capped.
In this way, if the air is pulled towards the corridor, the adhering air vein releases, by
induction, some space where the leaving air is conveyed on the side of the displacement
diffuser above the capped nozzles.
AIR-RAIL – Typical installation diagram
Displacement air flow
Displacement air flow
Uncapped nozzles
Capped nozzles
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
21
OPTIONAL ACCESSORIES – REMOTE AIR COOLED CONDENSER
Remote air cooled condenser series TEAM MATE with horizontal air flow, from coil to fan.
The machines are made with weather resistant materials and suitable for outdoor installation.
Design, assembly and test as per the Company Quality Assurance program in full compliance
with ISO 9001. RC Group has been the first Italian company in its segment to get the ISO 9001
th
in October 13 , 1991 with certificate ICIM 0018.
The machines are in full compliance with European Norms 2006/42CE, 2006/95CE,
2004/108CE, 97/23CE and subsequent amendments.
SERIES IDENTIFICATION
TEAM MATE remote air cooled condensers equipped with axial
fans.
Nominal capacity: 11,9 ÷ 294,0 kW
The TEAM MATE series is available in 3 versions:
 TEAM MATE STD - No air flow and sound level
reduction
 TEAM MATE LNO – Air flow reduction at 85% with
consequent sound level reduction.
 TEAM MATE ELN – Air flow reduction at 70% with
further sound level reduction.
TEAM MATE
MAIN COMPONENTS
FRAMEWORK
 Base, self supporting frame and panelling in steel plate with protective surfaces
treatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted
with epoxy powders.
 Colour: RAL 9002
FANS SECTION
 Axial fans with sickle-shaped blades, fan guard and optimized for low noise levels.
 External rotor electric motor with stepless variable speed for condensing pressure
control.
 IP54 enclosure class.
CONDENSING COIL
 Heat exchanger coil with internally corrugated copper tubes and high efficiency
aluminium fins, specifically developed to provide high heat transfer and lower
pressure drops. The combination of two factors, special tubes and fins, allow to
optimally combine the following aspects:
Maximum capacity relative to the size of the exchanger.
Minimum charge of refrigerant.
Reduction of the air flow required for the heat exchange.
 Frame in galvanized steel.
REFRIGERANT CIRCUIT
 Valves on gas and liquid line for coupling to refrigerant pipe. The condenser is
supplied with nitrogen seal.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation, IP54 enclosure class,
complete with:

Terminals for power supply (from network).
230/1/50

Terminals for 0÷10V signal for condensing control system (connect to indoor
machine).

Terminals for alarm signal (connect to indoor machine).

Fans speed regulator for condensing control.
OPTIONAL ACCESSORY

22
Support legs for vertical air flow.
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
TECHNICAL DATA
MODEL
M 11
M 14
M 17
M 20
M 25
M 30
TEAM MATE STD
AXIAL FANS
Air flow
Operating power input
Max operating current (FLA)
SOUND PRESSURE LEVEL (1)
n.
m³/h
kW
A
dB(A)
1
4900
0,25
1,18
63,0
1
4500
0,25
1,18
63,0
1
5200
0,25
1,18
63,0
1
6400
0,39
1,80
65,0
1
9600
0,53
2,85
67,0
1
9500
0,53
2,85
67,0
TEAM MATE LNO
AXIAL FANS
Air flow
Operating power input
Max operating current (FLA)
SOUND PRESSURE LEVEL (1)
n.
m³/h
kW
A
dB(A)
1
4165
0,21
1,18
59,1
1
3825
0,21
1,18
59,1
1
4420
0,21
1,18
59,1
1
5540
0,33
1,80
61,1
1
8160
0,45
2,85
63,1
1
8075
0,45
2,85
63,1
TEAM MATE ELN
AXIAL FANS
Air flow
Operating power input
Max operating current (FLA)
SOUND PRESSURE LEVEL (1)
n.
m³/h
kW
A
dB(A)
1
3430
0,18
1,18
54,5
1
3150
0,18
1,18
54,5
1
3640
0,18
1,18
54,5
1
4480
0,27
1,80
56,5
1
6720
0,37
2,85
58,5
1
6650
0,37
2,85
58,5
230/1/50
0,8
230/1/50
1,2
230/1/50
1,7
230/1/50
1,7
230/1/50
2,0
230/1/50
3,0
875
540
726
51,0
875
540
726
54,5
1200
540
726
66,0
1200
540
726
72,0
1400
665
1026
102,0
1400
665
1026
111,0
M 35
M45
M50
M60
M70
COMMON DATA
POWER SUPPLY
REFRIGERANT CHARGE (2)
DIMENSIONS
Length
Width
Height
NET WEIGHT
V/ph/Hz
kg
mm
mm
mm
kg
MODEL
TEAM MATE STD
AXIAL FANS
Air flow
Operating power input
Max operating current (FLA)
SOUND PRESSURE LEVEL (1)
n.
m³/h
kW
A
dB(A)
1
9100
0,53
2,85
67,0
2
12000
0,78
3,60
67,4
2
17000
1,08
5,70
69,4
-
-
TEAM MATE LNO
AXIAL FANS
Air flow
Operating power input
Max operating current (FLA)
SOUND PRESSURE LEVEL (1)
n.
m³/h
kW
A
dB(A)
1
7735
0,45
2,85
63,1
2
10200
0,66
3,60
63,6
-
2
13600
0,92
5,70
65,5
2
15300
0,92
5,70
65,5
TEAM MATE ELN
AXIAL FANS
Air flow
Operating power input
Max operating current (FLA)
SOUND PRESSURE LEVEL (1)
n.
m³/h
kW
A
dB(A)
1
6370
0,37
2,85
58,5
2
8400
0,55
3,60
58,9
-
2
11200
0,76
5,70
60,8
2
12600
0,76
5,70
60,8
230/1/50
4,0
230/1/50
4,7
230/1/50
4,1
230/1/50
230/1/50
1400
665
1026
120,0
1600
665
1026
153,0
1850
665
1026
175,0
1850
665
1026
188,0
2320
665
1140
214,0
COMMON DATA
POWER SUPPLY
REFRIGERANT CHARGE (2)
DIMENSIONS
Length
Width
Height
NET WEIGHT
1.
2.
V/ph/Hz
kg
mm
mm
mm
kg
Sound pressure level [Lp] 1m far according to ISO EN 3744.
The condenser is supplied with nitrogen seal. For the refrigerant charge consider, in addition to the these value, even
the refrigerant pipes for the connection to the indoor machine and lubricant oil in 10% ratio of charged refrigerant.
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
23
ACOUSTIC DATA
TEAM MATE STD
MODEL
Sound power level [Lw] (1)
Sound pressure level at 1m [Lp] (2)
Sound pressure level at 5m [Lp] (3)
Sound pressure level at 10m [Lp] (3)
dB(A)
dB(A)
dB(A)
dB(A)
M 11
76,8
63,0
51,3
45,6
M 14
76,8
63,0
51,3
45,6
M 17
77,1
63,0
51,5
45,9
M 20
79,1
65,0
53,5
47,9
M 25
81,8
67,0
56,1
50,5
MODEL
Sound power level [Lw] (1)
Sound pressure level at 1m [Lp] (2)
Sound pressure level at 5m [Lp] (3)
Sound pressure level at 10m [Lp] (3)
dB(A)
dB(A)
dB(A)
dB(A)
M 30
81,8
67,0
56,1
50,5
M 35
81,8
67,0
56,1
50,5
M45
82,4
67,4
56,6
51,1
M50
84,5
69,4
58,7
53,2
M 11
M 14
M 17
M 20
M 25
72,9
59,1
47,4
41,7
72,9
59,1
47,4
41,7
73,2
59,1
47,7
42,0
75,2
61,1
49,7
44,0
77,9
63,1
52,2
46,6
M 30
M 35
M45
M60
M70
77,9
63,1
52,2
46,6
77,9
63,1
52,2
46,6
78,5
63,6
52,7
47,2
80,7
65,5
54,8
49,3
81,1
65,5
55,1
49,7
M 11
M 14
M 17
M 20
M 25
68,2
54,5
42,8
37,1
68,2
54,5
42,8
37,1
68,6
54,5
43,0
37,4
70,6
56,5
45,0
39,4
73,3
58,5
47,5
42,0
M 30
M 35
M45
M60
M70
73,3
58,5
47,5
42,0
73,3
58,5
47,5
42,0
73,9
58,9
48,1
42,6
76,0
60,8
50,2
44,7
76,5
60,8
50,5
45,1
TEAM MATE LNO
MODEL
Sound power level [Lw] (1)
Sound pressure level at 1m [Lp] (2)
Sound pressure level at 5m [Lp] (3)
Sound pressure level at 10m [Lp] (3)
dB(A)
dB(A)
dB(A)
dB(A)
MODEL
Sound power level [Lw] (1)
Sound pressure level at 1m [Lp] (2)
Sound pressure level at 5m [Lp] (3)
Sound pressure level at 10m [Lp] (3)
dB(A)
dB(A)
dB(A)
dB(A)
TEAM MATE ELN
MODEL
Sound power level [Lw] (1)
Sound pressure level at 1m [Lp] (2)
Sound pressure level at 5m [Lp] (3)
Sound pressure level at 10m [Lp] (3)
dB(A)
dB(A)
dB(A)
dB(A)
MODEL
Sound power level [Lw] (1)
Sound pressure level at 1m [Lp] (2)
Sound pressure level at 5m [Lp] (3)
Sound pressure level at 10m [Lp] (3)
dB(A)
dB(A)
dB(A)
dB(A)
1.
2.
3.
Sound power level [Lw] according to ISO EN 9614 - 2.
Sound pressure level [Lp] according to ISO EN 3744.
Sound pressure level [Lp] in free field conditions.
IMPORTANT
For further information about units acoustic data, please refer to “The Noise” bulletin of
RC GROUP technical literature.
24
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
OPTIONAL ACCESSORIES – CONDENSATE DISCHARGE PUMP (KIT)
The optional is supplied in mounting kit.
A plastic case includes the vertical type pump, the water tank with float plus safety switch and
hydraulic and electric connection.
Together the pump 10 linear meters of plastic discharge pipe is supplied.
The optional has to be installed as shown in the documentation delivered together with the
unit.
Wiring includes power supply and an alarm, displayed on microprocessor, that includes motor
pump thermal protection and tank overflow.
The condensate discharge pump operation is fully automatic.
TECHNICAL DATA
Power supply
Power input
Absorbed current
Capacity tank
Discharge pipe
Maximum water flow
Minimum water flow
Discharge head
- with min. water flow
- with max. water flow
W
A
l
Ø mm
l/h
l/h
230/1/50
75
0,5
2
10/16
300
3
mH2O
mH2O
4,5
0,3
CONDENSATE DISCHARGE PUMP
Condensate discharge  3/8”
Condensate inlet
 28
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
25
OPTIONAL ACCESSORIES – PLENUM WITH FREE-COOLING DAMPER
The plenum allows direct free-cooling, which is a direct fresh air put into the room through the
air conditioner.
The optional has the same dimensional and constructive characteristics of the conditioner and
is placed on the upper side of the unit.
A two-way damper controls the outdoor and return air flows through a proportional servomotor
directly driven by microprocessor.
The cooling system is fully proportional and allows three working mode types:

total free-cooling: only fresh air is used to cool the ambient.

partial free-cooling: the fresh air is used for a pre-cooling and the compressor is used to
balance the load.

mechanical cooling: the compressor is used to cool the ambient.
COMPONENTS:

Housing made of galvanized steel sheet inner frame that includes gaskets for air
tightening.

Panels in galvanized steel sheet externally coated with PVC film. Panels are internally
insulated by noise absorption material (self-extinguish class 1) and are fixed with screws.

Two-way damper (fresh air and return) in galvanized stell sheet with steel pins rotating on
nylon brushing.

Proportional servomotor directly driven by microprocessor.

Terminals for servomotor electric connection to the unit.
The servomotor electric cable is contained inside the unit electric board.
PLENUM WITH FREE-COOLING DAMPER
1.
2.
3.
4.
5.
Free-cooling plenum
Damper
Fresh air section
Room air section
Fresh air ducting
WARNING
The fresh air ducting is at Customer care.
We suggest you to install a protection grille on fresh air intake.
IT IS COMPULSORY TO INSTALL AN OVERPRESSURE DAMPER TO ALLOW THE
ROOM AIR EXHAUSTION
26
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
OPTIONAL ACCESSORIES – FRESH AIR KIT
The optional is associated to the Plenum with Free-Cooling damper and allows the fresh air
ducting. The optional include the overpressure damper for the air exhaustion from the room.
The kit include:
 HEAT HUNTER HH0
n° 1 x 6 meter of spiral flexible PVC pipe
Conveyor with 1 oval nozzle
n° 1 grille for fresh air 500x500
n° 1 overpressure damper 500x450h
gaskets, metal bands and screws for mounting.

HEAT HUNTER HH1 / HH2
n° 2 x 6 meter of spiral flexible PVC pipe
Conveyor with 2 oval nozzles
n° 2 grilles for fresh air 500x500
n° 2 overpressure damper 500x450h
gaskets, metal bands and screws for mounting.

HEAT HUNTER HH3
n° 3 x 6 meter of spiral flexible PVC pipe
Conveyor with 3 oval nozzles
n° 3 grilles for fresh air 500x500
n° 3 overpressure damper 500x450h
gaskets, metal bands and screws for mounting.
-
FRESH AIR KIT
FRESH AIR GRILLE
1.
2.
3.
4.
5.
OVERPRESSURE DAMPER
Free-cooling plenum
Damper
Conveyor
Flexible PVC pipe
Fresh air grille
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
27
OVERPRESSURE DAMPER – (Unit with fresh air kit)
For a correct performance of the plant it is necessary to install an overpressure damper close
to the ceiling.
The damper must allow air exhaustion when air conditioners work in Free-Cooling mode. The
fresh air put in inside the ambient causes an internal pressure increase, that must be avoided
to grant a correct performance of the plant.
OVERPRESSURE DAMPER
1.
2.
Fresh air ducting
Overpressure damper
OVERPRESSURE DAMPER – (Unit with Free-cooling plenum and without fresh air kit)
The Customer will provide the installation of an overpressure damper.
The overpressure damper airflow has to be the summa of all conditioners air flow installed into
the room.
Example:
Plant with two Heat.Hunter units model 026 HH2 with free-cooling plenum with nominal air
3
flow of 6.660 m /h each.
The overpressure damper has to be dimensioned for an air exhaustion of 6,660 + 6,660 =
3
13,320 m /h.
28
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DX HH0
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
29
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DX HH1, mod.013 P1
30
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DX HH1, mod.015, 017 P1
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
31
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DX HH2, mod.021, 023 P1
32
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DX HH2, mod.027, 030 P1
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
33
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DX HH3, mod.038 P1
34
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DX HH3, mod.045 P1
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
35
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DW HH0
36
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DW HH1, mod.013 P1
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
37
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DW HH1, mod.015, 017 P1
38
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DW HH2, mod.021, 023 P1
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
39
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DW HH2, mod.027 P1
40
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DW HH2, mod.030 P1
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
41
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DW HH3, mod.038 P1
42
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
UNIT DRAWINGS
Dimensions in mm
HEAT HUNTER DW HH3, mod.045 P1
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
43
TYPICAL INSTALLATION DIAGRAMS FOR DIRECT EXPANSION MACHINES
WITH REMOTE AIR COOLED CONDENSER
HEAT HUNTER DX
1)
2)
3)
4)
5)
6)
Air conditioner
Remote air cooled condenser
Gas discharge line
Liquid line
Trap. Foresee a trap every 5m of the rising pipe.
Additional liquid receiver external to the conditioner with cocks and safety valve.
Suggested part in the following cases:
a) refrigerant line longer than 25-30m
b) plant operation with ambient temperature lower than 0°C Install the liquid receiver close to the air conditioner.
7) Solenoid valve of the liquid line. It is an optional accessory of the air conditioner for refrigeration plants with
refrigerant pipe longer than 10m
THIS DIAGRAM APPLIES TO EACH REFRIGERANT CIRCUIT OF THE UNIT.
WARNING
It is necessary to provide the refrigerant charge for the connection pipes and for the
remote air cooled condenser.
Charge refrigerant in the suitable quantity and lubricant oil in 10% ratio of charged
refrigerant.
Lubricant oil must be the same type as the charged one as shown on the compressor
plate.
44
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
TYPICAL INSTALLATION DIAGRAMS FOR DIRECT EXPANSION MACHINES WITH
REMOTE AIR COOLED CONDENSER
HEAT HUNTER DX
1)
2)
3)
4)
5)
6)
7)
Air conditioner
Remote air cooled condenser
Gas discharge line
Liquid line
Non - return valve.
Additional liquid receiver external to the conditioner with cocks and safety valve.
Install the liquid receiver close to the air conditioner.
Solenoid valve of the liquid line. It is an optional accessory of the air conditioner for refrigeration plants with
refrigerant pipe longer than 10m
THIS DIAGRAM APPLIES TO EACH REFRIGERANT CIRCUIT OF THE UNIT.
WARNING
It is necessary to provide the refrigerant charge for the connection pipes and for the
remote air cooled condenser.
Charge refrigerant in the suitable quantity and lubricant oil in 10% ratio of charged
refrigerant.
Lubricant oil must be the same type as the charged one as shown on the compressor
plate.
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
45
46
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
RC GROUP S.p.A. ● T_HH_1112_GB ● R410A
47
The continuous improvement of products may imply changes in the data shown in this catalogue.
RC GROUP S.p.A. • Via Roma, 5 • 27010 Valle Salimbene (PV), Italy
www.rcgroup.it • Tel. +39 (0) 382 433 811 • Fax +39 (0) 382 587 148
T_HH_1112_GB
Was this manual useful for you? yes no
Thank you for your participation!