user manual indoor unit
USER'S MANUAL
MATRIX 2 SERIES
indoor unit
ASH-09AIM2 PT, ASH-13AIM2 PT
ASH-18AIM2 PT, ASH-24AIM2 PT
„Original instruction“
Precautions
WARNING
Operation and Maintenance
This appliance can be used by children aged from 8
years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience and
knowledge if they have been given supervision or
instruction concerning use of the appliance in a safe
way and understand the hazards involved.
Children shall not play with the appliance.
Cleaning and user maintenance shall not be made by
children without supervision.
Do not connect air conditioner to multi-purpose socket.
Otherwise, it may cause fire hazard.
Do disconnect power supply when cleaning air
conditioner. Otherwise, it may cause electric shock.
.
If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
Do not wash the air conditioner with water to avoid
electric shock.
Do not spray water on indoor unit. It may cause electric
shock or malfunction.
After removing the filter, do not touch fins to avoid injury.
Do not use fire or hair dryer to dry the filter to avoid
deformation or fire hazard.
1
Precautions
WARNING
Maintenance must be performed by qualified
professionals. Otherwise, it may cause personal injury
or damage.
Do not repair air conditioner by yourself. It may cause
electric shock or damage. Please contact dealer when
you need to repair air conditioner.
Do not extend fingers or objects into air inlet or air
outlet. It may cause personal injury or damage.
Do not block air outlet or air inlet. It may cause
malfunction.
Do not spill water on the remote controller, otherwise the
remote controller may be broken.
When below phenomenon occurs, please turn off air
conditioner and disconnect power immediately, and then
contact the dealer or qualified professionals for service.
● Power cord is overheating or damaged.
● There’s abnormal sound during operation.
● Circuit break trips off frequently.
● Air conditioner gives off burning smell.
● Indoor unit is leaking.
If the air conditioner operates under abnormal conditions,
it may cause malfunction, electric shock or fire hazard.
When turning on or turning off the unit by emergency
operation switch, please press this switch with an insulating
object other than metal.
Do not step on top panel of outdoor unit, or put heavy
objects. It may cause damage or personal injury.
2
Precautions
WARNING
Attachment
Installation must be performed by qualified professionals.
Otherwise, it may cause personal injury or damage.
Must follow the electric safety regulations when installing
the unit.
According to the local safety regulations, use qualified
power supply circuit and circuit break.
Do install the circuit break. If not, it may cause malfunction.
An all-pole disconnection switch having a contact separation
of at least 3mm in all poles should be connected in fixed
wiring.
Including an circuit break with suitable capacity, please
note the following table.Air switch should be included
magnet buckle and heating buckle function, it can protect
the circuit-short and overload.
Air Conditioner should be properly grounded. Incorrect
grounding may cause electric shock.
Don't use unqualified power cord.
Make sure the power supply matches with the
requirement of air conditioner.Unstable power supply or
incorrect wiring or malfunction. Please install proper power
supply cables before using the air conditioner.
Properly connect the live wire, neutral wire and
grounding wire of power socket.
Be sure to cut off the power supply before proceeding
any work related to electricity and safety.
3
Precautions
WARNING
Do not put through the power before finishing installation.
If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
The temperature of refrigerant circuit will be high, please
keep the interconnection cable away from the copper
tube.
The appliance shall be installed in accordance with
national wiring regulations.
Installation must be performed in accordance with the
requirement of NEC and CEC by authorized personnel
only.
The air conditioner is the first class electric appliance. It
must be properly grounding with specialized grounding
device by a professional. Please make sure it is always
grounded effectively, otherwise it may cause electric shock.
The yellow-green wire in air conditioner is grounding
wire, which can't be used for other purposes.
The grounding resistance should comply with national
electric safety regulations.
The appliance must be positioned so that the plug is
accessible.
All wires of indoor unit and outdoor unit should be
connected by a professional.
If the length of power connection wire is insufficient, please
contact the supplier for a new one. Avoid extending the
wire by yourself.
4
Precautions
WARNING
For the air conditioner with plug, the plug should be
reachable after finishing installation.
For the air conditioner without plug, an circuit break
must be installed in the line.
If you need to relocate the air conditioner to another
place, only the qualified person can perform the work.
Otherwise, it may cause personal injury or damage.
Select a location which is out of reach for children and
far away from animals or plants.If it is unavoidable,
please add the fence for safety purpose.
The indoor unit should be installed close to the wall.
Working temperature range
Maximum cooling
Maximum heating
Indoor side DB/WB(°C)
32/23
27/-
NOTICE:
Outdoor side DB/WB(°C)
48/26
24/18
● The operating temperature range (outdoor temperature) for cooling is -15℃~48℃;
The operating temperature range (outdoor temperature) for heating is -20°C~24°C
is -15℃~24 Heating temperature range for the model with electric heating belt
for chassis is -20℃~24℃ .
5
Parts name
Indoor Unit
air inlet
panel
aux.button
horizontal louver
air outlet
cooling
indicator
power
indicator
receiver
window
display
F
C
• •
HOUR
ONOFF
/
heating
indicator
temp.
indicator
drying
indicator
(Display content or position may be different from above
graphics, please refer to actual products)
NOTICE:
remote control
Actual product may be different from above graphics, please refer to actual
products.
6
Buttons on remote controller
F
C
• •
1
2 1 / 2) )
2
HOUR
ONOFF
3
1
ON/OFF button
2
- button
3
+ button
4
MODE button
5
FAN button
6
SWING button
7
I FEEL button
8
4
02'(
6
6:,1* ,)((/
)$1
/
button
5
9
7
10 TEMP button
SLEEP button
8
6/((3
9
11 TIMER-ON button
10
7(03
7,0(521
11
12 CLOCK button
12
&/2&.
7,0(52))
13
13 TIMER-OFF button
14
785%2 /,*+7 ;)$1
16
14 TURBO button
15
15 LIGHT button
16 X-FAN button
Introduction for icons on display screen
X-fan
set fan speed
I feel
8℃ heating function
send signal
turbo mode
ventilation operation
health mode
Operation mode
Auto mode
Cool mode
Dry mode
Fan mode
Heat mode
set temperature
set time
TIMER ON/TIMER OFF
Clock
Sleep mode
light
Child lock
Up & down swing
Temp. display type
:Set temp.
:Indoor ambient temp.
:Outdoor ambient temp.
7
Introduction for buttons on remote controller
Note:
● After putting through power, air conditioner will give out a sound and operation
indicator " " is ON (red indicator). You can operate the air conditioner through
the remote controller.
● At ON status, after each pressing button on remote controller, the signal icon " "
on remote controller will flash once. Air conditioner will give out a sound, which
indicates the signal has been sent to air conditioner.
1
ON/OFF button
Press this button to turn on the unit. Press this button again to turn off the unit.
2
- button
Press this button to decrease set temperature. Holding it down above 2 seconds
rapidly decreases set temperature. In AUTO mode, set temperature is not
adjustable.
3
+ button
Press this button to increase set temperature. Holding it down above 2 seconds
rapidly increases set temperature. In AUTO mode, set temperature is not
adjustable.
4
MODE button
Each time you press this button, a mode is selected in a sequence that goes from
AUTO, COOL, DRY, FAN, and HEAT*, as the following:
AUTO
COOL
DRY
FAN
HEAT*
*Note: Only for models with heating function.
After energization, AUTO mode is defaulted. In AUTO mode, the set temperature
will not be displayed on the LCD, and the unit will automatically select the suitable
operation mode in accordance with the room temperature to make indoor room
comfortable. (As for cooling only unit, it won’t have any action when it receives the
signal of heating operation.)
8
Introduction for buttons on remote controller
5 FAN button
This button is used for setting Fan Speed in the sequence that goes from AUTO,
,
, to
, then back to Auto.
Auto
Low speed
6
High speed
Medium speed
SWING button
Press this button to set up &down swing angle, which circularly changes as below:
OFF
This remote controller is universal. If any command
will carry out the command as
,
or
is sent out, the unit
indicates the guide louver swings as:
7
I FEEL button
Press this button to turn on I FEEL function. The unit automatically adjust temperature according to the sensed temperature. Press this button again to cancel I FEEL
function.
8
/
button
Press this button to achieve the on and off of healthy and scavenging functions in
operation status. Press this button for the first time to start scavenging function;
LCD displays " ". Press the button for the second time to start healthy and
scavenging functions simultaneously; LCD displays " " and " ". Press this
button for the third time to quit healthy and scavenging functions simultaneously.
Press the button for the fourth time to start healthy function; LCD display " ".
Press this button again to repeat the operation above. (This function is applicable
to partial of models)
9
SLEEP button
Press this button to go into the SLEEP operation mode. Press it again to cancel
this function. This function is available in COOL, HEAT (Only for models with
heating function) mode to maintain the most comfortable temperature for you.
9
Introduction for buttons on remote controller
10 TEMP button
Press this button can see indoor set temperature, indoor ambient temperature or
outdoor ambient temperature on indoor unit’s display. Temperature is set circularly
by remote controller as below:
no display
● When selecting " " by remote controller or no display, temperature indicator on
indoor unit displays set temperature.
● When selecting " " by remote controller, temperature indicator on indoor unit
displays indoor ambient temperature.
● When selecting "
" by remote controller, temperature indicator on indoor unit
displays outdoor ambient temperature.
Note:
● Outdoor ambient temperature display may can’t be selected for some models.
When indoor unit receives "
" signal, it displays indoor set temperature.
● Only for the model whose indoor unit has dual-8 display.
11
TIMER-ON button
Press this button to initiate the auto-ON timer. To cancel the auto-timer program,
simply press this button again.
After press of this button,
disappears and "ON" blinks. 00:00 is displayed for
ON time setting. Within 5 seconds, press + or - button to adjust the time value.
Every press of either button changes the time setting by 1 minute. Holding down
either button rapidly changes the time setting by 1 minute and then 10 minutes.
Within 5 Seconds after setting, press TIMER ON button to confirm.
12
CLOCK button
Press CLOCK button,
blinking. Within 5 seconds, pressing + or - button adjusts
the present time. Holding down either button above 2 seconds increases or
decreases the time by 1 minute every 0.5 second and then by 10 minutes every
0.5 second. During blinking after setting, press CLOCK button again to confirm the
setting, and then
will be constantly displayed.
13 TIMER-OFF button
Press this button to initiate the auto-off timer. To cancel the auto-timer program,
simply press the button again. TIMER OFF setting is the same as TIMER ON.
10
Introduction for buttons on remote controller
14 TURBO button
Press this button to activate / deactivate the Turbo function which enables the
unitto reach the preset temperature in the shortest time. In COOL mode, the unit
will blow strong cooling air at super high fan speed. In HEAT mode, the unit will
blow strong heating air at super high fan speed.
15
LIGHT button
Press LIGHT button to turn on the display's light and press this button again to turn
off the display's light. If the light is turned on,
is displayed. If the light is turned
off,
disappears.
16
X-FAN button
Pressing X-FAN button in COOL or DRY mode,
the icon is displayed and the
indoor fan will continue operation for 2 minutes in order to dry the indoor unit even
though you have turned off the unit.
After energization, X-FAN OFF is defaulted. X-FAN is not available in AUTO, FAN
or HEAT mode.
Function introduction for combination buttons
Combination of "+" and "-" buttons: About lock
Press "+" and "-" buttons simultaneously to lock or unlock the keypad. If the remote
controller is locked, is displayed. In this case, pressing any button, blinks
three times.
Combination of "MODE" and "-" buttons:
About switch between Fahrenheit and centigrade
At unit OFF, press "MODE" and "-" buttons simultaneously to switch between °C
and °F.
11
Function introduction for combination buttons
Combination of "TEMP" and "CLOCK" buttons:
About Energy-saving Function
Press "TEMP" and "CLOCK" simultaneously in COOL mode to start energy-saving
function. Nixie tube on the remote controller displays "SE". Repeat the operation to
quit the function.
Combination of "TEMP" and "CLOCK" buttons:
About 8°C Heating Function
Press "TEMP" and "CLOCK" simultaneously in HEAT mode to start 8°C Heating
Function Nixie tube on the remote controller displays " " and a selected
temperature of "8°C" (46°F if Fahrenheit is adopted). Repeat the operation to quit
the function.
About Back-lighting Function
★ About HEALTH function (COLD PLASMA)
Turn on the unit, start up the fan (Breezing and X-FAN are excluded) and press
HEATLTH button on remote controller to start health function (If there is not
HEALTH button on remote controller, the unit defaults health function ON. )
12
Operation guide
1. After putting through the power, press "ON/OFF" button on remote controller to
turn on the air conditioner.
2. Press "MODE" button to select your required mode: AUTO, COOL, DRY, FAN,
HEAT.
3. Press "+" or "-" button to set your required temperature. (Temperature can’t be
adjusted under auto mode).
4. Press "FAN" button to set your required fan speed: auto, low, medium and high
speed.
5. Press "SWING" button to select fan blowing angle.
Replacement of batteries in remote controller
battery
1. Press the back side of remote controller marked
the cover of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and
make sure the position of "+" polar and "-" polar
are correct.
3. Reinstall the cover of battery box.
reinstall
remove
Cover of battery box
NOTICE
● During operation, point the remote control signal sender at the receiving
window on indoor unit.
● The distance between signal sender and receiving window should be no
more than 8m, and there should be no obstacles between them.
or wireless telephone; remote controller should be close to indoor unit during
operation.
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the
batteries.
● If the display on remote controller is fuzzy or there’s no display, please
replace batteries.
13
Emergency operation
If remote controller is lost or damaged, please use auxiliary button to turn
on or turn off the air conditioner. The operation in details are as below:
air conditioner. When the air conditioner is turned on, it will operate under
auto mode.
panel
aux. button
WARNING:
Use insulated object to press the auto button
Clean and maintenance
WARNING
■ Turn off the air conditioner and disconnect the power before cleaning the air
conditioner to avoid electric shock.
■ Do not wash the air conditioner with water to avoid electric shock.
■ Do not use volatile liquid to clean the air conditioner.
Clean surface of indoor unit
When the surface of indoor unit is dirty, it is recommended to use a soft dry cloth
or wet cloth to wipe it.
NOTICE:
● Do not remove the panel when cleaning it.
14
Clean and maintenance
1
Open panel
3
Pull out the panel to a certain
● Use dust catcher or water to
the water (below 45℃ ) to clean
it, and then put it in a shady
and cool place to dry.
2
4
panel cover tightly.
WARNING
operation environment, clean frequency can be increased.
15
Clean and maintenance
NOTICE: Checking before use-season
1. Check whether air inlets and air outlets are blocked.
2. Check whether circuit break, plug and socket are in good condition.
3. Check whether filter is clean.
4. Check whether drainage pipe is damaged.
NOTICE: Checking after use-season
1. Disconnect power supply.
2. Clean filter and indoor unit’s panel.
Notice for recovery
1. Many packing materials are recyclable materials.
Please dispose them in appropriate recycling unit.
2. If you want to dispose the air conditioner, please contact local dealer or
consultant service center for the correct disposal method.
16
Malfunction analysis
General phenomenon analysis
Please check below items before asking for maintenance. If the malfunction still
can’t be eliminated, please contact local dealer or qualified professionals.
Phenomenon
Check items
Solution
● Whether it's interfered severely ● Pull out the plug. Reinsert
(such as static electricity,stable the plug after about 3min, and
voltage)?
then turn on the unit again.
Indoor unit
can’t receive
remote
controller’s
signal or
remote
controller
has no
action.
● Whether remote controller is
within the signal receiving
range?
● Signal receiving range is 8m.
● Whether there are obstacles?
● Remove obstacles.
● Whether remote controller is
● Select proper angle and point
pointing at the receiving
the remote controller at the rewindow?
ceiving window on indoor unit.
● Is sensitivity of remote contro- ● Check the batteries. If the
ller low; fuzzy display and no
power of batteries is too low,
display?
please replace them.
● Check whether remote cont● No display when operating
roller appears to be damaged.
remote controller?
If yes, replace it.
● Fluorescent lamp in room?
No air
emitted
from
indoor
unit
● Take the remote controller
close to indoor unit.
● Turn off the fluoresent lamp
and then try it again.
● Air inlet or air outlet of indoor
unit is blocked?
● Eliminate obstacles.
● Under heating mode, indoor
temperature is reached to set
temperature?
● After reaching to set temperature, indoor unit will stop blowing out air.
● Heating mode is turned on just ● In order to prevent blowing
now?
out cold air, indoor unit will be
started after delaying for several minutes, which is a normal phenomenon.
17
Malfunction analysis
Phenomenon
Air conditioner can’t
operate
Mist is emitted from
indoor unit’s
air outlet
Set temperature can’t
be adjusted
Cooling
(heating)
effect is
not good.
Check items
Solution
● Power failure?
● Wait until power recovery.
● Is plug loose?
● Reinsert the plug.
● Circuit break trips off or
fuse is burnt out?
● Ask professional to replace
circuit break or fuse.
● Wiring has malfunction?
● Ask professional to replace it.
● Unit has restarted immediately
● Wait for 3min, and then turn
after stopping operation?
on the unit again.
● Whether the function setting
for remote controller is
correct?
● Reset the function.
● Indoor temperature and humidity is high?
● Because indoor air is cooled
rapidly. After a while, indoor
temperature and humidity will
be decrease and mist will
disappear.
● Unit is operating under auto
mode?
● Temperature can’t be adjusted under auto mode.
Please switch the operation
mode if you need to adjust
temperature.
● Your required temperature
exceeds the set temperature
range?
● Set temperature range:
16℃ ~30℃ .
● Voltage is too low?
● Wait until the voltage
resumes normal.
● Filter is dirty?
● Clean the filter.
● Set temperature is in proper
range?
● Adjust temperature to proper
range.
● Door and window are open?
● Close door and window.
18
Malfunction analysis
Phenomenon
Odours are
emitted
Check items
Solution
● Whether there’s odour source, ● Eliminate the odour source.
such as furniture and cigarette,
● Clean the filter.
etc.
Air conditioner ● Whether there’s interference,
such as thunder, wireless
operates normally suddenly devices, etc.
“Water
flowing”
noise
Cracking
noise
● Air conditioner is turned on or
turned off just now?
● Air conditioner is turned on or
turned off just now?
19
● Disconnect power, put back
power, and then turn on the
unit again.
● The noise is the sound of
refrigerant flowing inside
the unit, which is a normal
phenomenon.
● This is the sound of friction
caused by expansion and/or
contraction of panel or other
parts due to the change of
temperature.
Malfunction analysis
Error Code
● When air conditioner status is abnormal, temperature indictor on indoor unit will
ation of error code.
Indoor
display
Error code
Error code
Above indicator diagram is only
for reference. Please refer to
actual product for the actual
indicator and position.
Troubleshooting
Heating indicator ON 10s OFF 0.5s
Means defrosting status. It’s the normal phenomenon.
E5: overcurrent protection
Power indicator blinks and E5 is displayed
C5:Connector jumper malfunction
Check if the connector jumper contacts the
properly. If replace the PCB, please take off
the old for the new PCB.
Check if indoor room temp. sensor is connected
properly?
Check if indoor tube temp. sensor is
connected properly?
● Feedback terminal of PG motor hasn’t been
connected firmly.
● The control end of PG motor hasn’t been
connected firmly.
● Fan blade hasn’t been installed correctly
and it can’t run smoothly.
● Motor hasn’t been installed correctly and tightly.
● Motor has been damaged.
● Control panel has been damaged.
F1:Indoor ambient temp. sensor
malfunction
F2:Evaporator temp.sensor
malfunction
H6:PC motor (indoor fan) can’t run
U8:Malfunction of zero cross detection
circuit for PG motor (indoor fan)
Defrosting or oil return mode
Control panel has been damaged.
It is normal. The indicating lamp in heat mode will
wink 0.5s and light 10s.
Note:
service.
WARNING
■ When below phenomenon occurs, please turn off air conditioner and disconfor service.
● Power cord is overheating or damaged.
● There’s abnormal sound during operation.
● Circuit break trips off frequently.
● Air conditioner gives off burning smell.
● Indoor unit is leaking.
■ If the air conditioner operates under abnormal conditions, it may cause
20
At least 15cm
Space to the ceiling
Installation dimension diagram
Space to the wall
Space to the wall
At least 15cm
e
ac
to
le
the
m
0c
30
on
cti
tru
s
ob
Space to the floor
At
t
as
Sp
21
At least 250cm
At least 15cm
Tools for installation
1 Level meter
2 Screw driver
3 Impact drill
4 Drill head
5 Pipe expander
6 Torque wrench
7 Open-end wrench
8 Pipe cutter
9 Leakage detector
10 Vacuum pump
11 Pressure meter
12 Universal meter
13 Inner hexagon spanner
Note:
14 Measuring tape
● Please contact the local agent for installation.
● Don't use unqualified power cord.
Selection of installation location
Basic requirement
Installing the unit in the following places maycause malfunction. If it is unavoidable,
please consult the local dealer:
1. The place with strong heat sources, vapors, flammable or explosive gas, or
volatile objects spread in the air.
2. The place with high-frequency devices (such as welding machine, medical
equipment).
3. The place near coast area.
4. The place with oil or fumes in the air.
5. The place with sulfureted gas.
6. Other places with special circumstances.
7. Do not use the unit in the immediate surroundings of a laundry a bath a
shower or a swimming pool.
Indoor unit
1. There should be no obstruction near air inlet .
2. Select a location where the condensation water can be dispersed easily and
won't affect other people.
3. Select a location which is convenient to connect the outdoor unit and near the
power socket.
4. Select a location which is out of reach for children.
5. The location should be able to withstand the weight of indoor unit and won't
increase noise and vibration.
6. The appliance must be installed 2.5m above floor.
7. Don't install the indoor unit right above the electric appliance.
8. Please try your best to keep way from fluorescent lamp.
22
Requirements for electric connection
Safety precaution
1. Must follow the electric safety regulations when installing the unit.
2. According to the local safety regulations, use qualified power supply circuit and
circuit break.
3. Make sure the power supply matches with the requirement of air conditioner.
Unstable power supply or incorrect wiring or malfunction. Please install proper
power supply cables before using the air conditioner.
4. Properly connect the live wire, neutral wire and grounding wire of power socket.
5. Be sure to cut off the power supply before proceeding any work related to
electricity and safety.
6. Do not put through the power before finishing installation.
7. If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
8. The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
9. The appliance shall be installed in accordance with national wiring regulations.
10.Installation must be performed in accordance with the requirement of NEC
and CEC by authorized personnel only
Grounding requirement
1. The air conditioner is the first class electric appliance. It must be properly
grounding with specialized grounding device by a professional. Please make
sure it is always grounded effectively, otherwise it may cause electric shock.
2. The yellow-green wire in air conditioner is grounding wire, which can't be used
for other purposes.
3. The grounding resistance should comply with national electric safety regulations.
4. The appliance must be positioned so that the plug is accessible.
5. An all-pole disconnection switch having a contact separation of at least 3mm in
all poles should be connected in fixed wiring. For models with a power plug,
make sure the plug is within reach after installation.
23
Installation of indoor unit
Step one: choosing installation location
rm it with the client.
Step two: install wall-mounting frame
1. Hang the wall-mounting frame on the wall; adjust it in horizontal position with the
plastic expansion particles in the holes.
3. Fix the wall-mounting frame on the wall with tapping screws (ST4.2X25TA) and
.
Step three: open piping hole
1. Choose the position of piping hole according to the direction of outlet pipe. The
position of piping hole should be a little lower than the wall-mounted frame,
shown as below.
09、12K:
Wall
Space
to the
wall
above
150mm
Mark in the middle of it
Left
Φ55mm
Rear piping hole
Level meter
Wall
Space
to the
wall
above
150mm
Right
Φ55mm
Rear piping hole
24K:
18K:
Wall
Space
to the
wall
above
150mm
Mark in the middle of it
Left
Φ55mm
Rear piping hole
Level meter
Wall
Wall
Space
to the
wall
above
150mm
Space
to the
wall
above
150mm
Right
Φ55mm
Rear piping hole
Mark in the middle of it
Left
Φ70mm
Rear piping hole
Level meter
Wall
Space
to the
wall
above
150mm
Right
Φ70mm
Rear piping hole
2. Open a piping hole with the diameter of Φ55 or Φ70 on the selected outlet pipe
position. In order to drain smoothly, slant the piping hole on the wall slightly
downward to the outdoor side with the gradient of 5-10°.
24
Installation of indoor unit
Indoor
Note:
● Pay attention to dust prevention and
take relevant safety measures when
opening the hole.
● The plastic expansion particles are
not provided and should be bought
locally.
outdoor
Φ55/
Φ70
5-10°
Step four: outlet pipe
2. When select leading out the pipe
from left or right, please cut off the
corresponding hole on the bottom
case.
1. The pipe can be led out in the
direction of right, rear right, left or
rear left.
left
right
left
rear right
rear left
right
cut off
the hole
1. Aim the pipe joint at the corresponding
bellmouth.
pipe joint
union nut
pipe
2. Pretightening the union nut with hand.
3. Adjust the torque force by referring to the following sheet. Place the open-end
wrench on the pipe joint and place the torque wrench on the union nut. Tighten
the union nut with torque wrench.
25
Installation of indoor unit
open-end
wrench
union nut
torque wrench
pipe
Hex nut diameter Tightening torque (N.m)
15~20
Φ6
Φ 9.52
30~40
Φ 12
45~55
Φ 16
60~65
Φ 19
70~75
indoor pipe
4. Wrap the indoor pipe and joint of connection pipe with insulating pipe, and
then wrap it with tape.
insulating pipe
Step six: install drain hose
1. Connect the drain hose to the outlet pipe of
indoor unit.
drain hose
outlet pipe
2. Bind the joint with tape.
outlet
pipe
tape
drain hose
drain hose
Note:
● Add insulating pipe in the indoor
drain hose in order to prevent
condensation.
● The plastic expansion particles are
not provided.
insulating pipe
Step seven: connect wire of indoor unit
panel
screw
1. Open the panel, remove the screw
on the wiring cover and then take
down the cover.
wiring cover
26
Installation of indoor unit
2. Make the power connection wire go
through the cable-cross hole at the back
of indoor unit and then pull it out from
the front side.
cable-cross
hole
power connection
wire
3. Remove the wire clip; connect the power connection wire to the wiring terminal
with wire clip.
N(1)
2
blue black
3
brown
yellowgreen
Outdoor unit connection
4.Put wiring cover back and then tighten the screw.
5.Close the panel.
Note:
● All wires of indoor unit and outdoor unit should be connected by a professional.
for a new one. Avoid extending the wire by yourself.
installation.
● For the air conditioner without plug, an circuit break must be installed in the line.
The circuit break should be all-pole parting and the contact parting distance
should be more than 3mm.
27
Installation of indoor unit
Step eight: bind up pipe
1. Bind up the connection pipe, power
cord and drain hose with the band.
indoor unit
gas
pipe
connection pipe
drain hose
band
indoor and
outdoor power cord
indoor power cord
liquid pipe
band
3. Bind them evenly.
4. The liquid pipe and gas pipe should
be bound separately at the end.
drain hose
2. Reserve a certain length of drain
hose and power cord for installation
when binding them. When binding to
a certain degree, separate the indoor
power and then separate the drain
hose.
Note:
● The power cord and control wire
can't be crossed or winding.
● The drain hose should be bound
at the bottom.
Step nine: hang the indoor unit
1. Put the bound pipes in the wall pipe and then make them pass through the wall
hole.
2. Hang the indoor unit on the wall-mounting frame.
3. Stuff the gap between pipes and wall hole with sealing gum.
4. Fix the wall pipe.
5. Check if the indoor unit is installed firmly and closed to the wall.
indoor
wall pipe
upper hook
outdoor
sealing gum
lower hook of
wall-mounting frame
Note:
● Do not bend the drain hose too excessively in order to prevent blocking.
28
Check after installation
● Check according to the following requirement after finishing installation.
Items to be checked
Possible malfunction
Has the unit been installed firmly?
The unit may drop, shake or emit noise.
Have you done the refrigerant leakage
test?
It may cause insufficient cooling
(heating) capacity.
Is heat insulation of pipeline sufficient?
It may cause condensation and water
dripping.
Is water drained well?
It may cause condensation and water
dripping.
Is the voltage of power supply according to the voltage marked on the
nameplate?
It may cause malfunction or damaging
the parts.
Is electric wiring and pipeline installed
correctly?
It may cause malfunction or damaging
the parts.
Is the unit grounded securely?
It may cause electric leakage.
Does the power cord follow the specification?
It may cause malfunction or damaging
the parts.
Is there any obstruction in the air inlet
and outlet?
It may cause insufficient cooling
(heating) capacity.
The dust and sundries caused during
installation are removed?
It may cause malfunction or damaging
the parts.
The gas valve and liquid valve of
connection pipe are open completely?
It may cause insufficient cooling
(heating) capacity.
Test operation
1. Preparation of test operation
● The client approves the air conditioner.
● Specify the important notes for air conditioner to the client.
2. Method of test operation
● Put through the power, press ON/OFF button on the remote controller to start
operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and HEAT to check
whether the operation is normal or not.
● If the ambient temperature is lower than 16℃ , the air conditioner can’t
start cooling.
29
Configuration of connection pipe
1. Standard length of connection pipe
● 5m, 7.5m, 8m.
2. Min. length of connection pipe is 3m.
3. Max. length of connection pipe and max. high difference.
Cooling
capacity
Max length
Max height
of connecdifference
tion pipe
Cooling
capacity
Max length
Max height
of connecdifference
tion pipe
5000Btu/h
(1465W)
15
5
24000Btu/h
(7032W)
25
10
7000Btu/h
(2051W)
15
5
28000Btu/h
(8204W)
30
10
9000Btu/h
(2637W)
15
5
36000Btu/h
(10548W)
30
20
12000Btu/h
(3516W)
20
10
42000Btu/h
(12306W)
30
20
18000Btu/h
(5274W)
25
10
48000Btu/h
(14064W)
30
20
4. The additional refrigerant oil and refrigerant charging required after prolonging
connection pipe
● After the length of connection pipe is prolonged for 10m at the basis of
standard length, you should add 5ml of refrigerant oil for each additional 5m
of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis
of liquid pipe):
Additional refrigerant charging amount = prolonged length of liquid pipe ×
additional refrigerant charging amount per meter
● Basing on the length of standard pipe, add refrigerant according to the
requirement as shown in the table. The additional refrigerant charging amount
per meter is different according to the diameter of liquid pipe. See the
following sheet.
30
Configuration of connection pipe
Additional refrigerant charging amount for R410A and R134a
Diameter of connection pipe
Outdoor unit throttle
Liquid pipe(mm)
Gas pipe(mm)
Cooling only(g/m) Cooling and heating(g/m)
Φ6
Φ9.52 or Φ12
15
20
Φ6 or Φ9.52
Φ16 or Φ19
15
50
Φ12
Φ19 or Φ22.2
30
120
Φ16
Φ25.4 or Φ31.8
60
120
Φ19
_
250
250
Φ22.2
_
350
350
31
Pipe expanding method
Note:
Improper pipe expanding is the main cause of refrigerant leakage. Please expand
the pipe according to the following steps:
A: Cut the pipe
● Confirm the pipe length according to
the distance of indoor unit and
outdoor unit.
● Cut the required pipe with pipe cutter.
E: Expand the port
● Expand the port with expander.
hard
mold
expander
pipe
pipe
pipe cutter
leaning
uneven
Note:
● "A" is different according to the
diameter, please refer to the sheet
below:
burr
B: Remove the burrs
● Remove the burrs with shaper and
prevent the burrs from getting into
the pipe.
pipe
shaper
downwards
A(mm)
Outer diameter
(mm)
Max
Min
Φ6-6.35(1/4")
1.3
0.7
Φ9.52(3/8")
1.6
1.0
Φ12-12.7(1/2")
1.8
1.0
Φ15.8-16(5/8")
2.4
2.2
F: Inspection
● Check the quality of expanding port.
If there is any blemish, expand the
port again according to the steps
above.
C: Put on suitable insulating pipe
D: Put on the union nut
● Remove the union nut on the indoor
connection pipe and outdoor valve;
install the union nut on the pipe.
smooth surface
improper expanding
union pipe
leaning
pipe
the length is equal
32
damaged
surface
crack
uneven
thickness
ELECTRIC SCHEMATIC DIAGRAM
ASH-09AIM2 PT indoor / ASH-13AIM2 PT indoor
ASH-18AIM2 PT indoor
33
ELECTRIC SCHEMATIC DIAGRAM
ASH-24AIM2 PT indoor
34
RATING LABEL
35
ENERGY LABEL
36
NOTE CONCERNING PROTECTION OF ENVIRONMENT
This product must not be disposed of via normal household waste after its
service life, but must be taken to a collection station for the recycling of
electrical and electronic devices. The symbol on the product, the
operating instructions or the packaging indicate such disposal procedures.
The materials are recyclable in accordance with their respective symbols. By means
of re-use, material recycling or any other form of recycling old appliances you are
making an important contribution to the protection of our environment. Please ask
your local council where your nearest disposal station is located.
INFORMATION CONCERNING USED REFRIGERANT
MEDIUM
This unit is containing fluorinated gases included in the Kyoto protocol. The
maintanance and the liquidation must be carried out by qualified personel.
Type of refrigerant: R410A
The composition of the cooling medium R410A: (50% HFC-32, 50% HFC-125)
The quantity of the refrigerant: please see the unit label.
The value GWP: 2088
GWP = Global Warming Potential
In case of quality problem or other please contact your local supplier or authorized
service center.
Emergency number: 112
PRODUCER
Producer: SINCLAIR CORPORATION Ltd., 1-4 Argyll St., London W1F 7LD, UK,
www.sinclair-eu.com
This product was manufactured in China (Made in China).
REPRESENTATIVE, TECHNICAL SUPPORT
NEPA spol. s r.o.
Purkyňova 45
612 00 Brno
Czech Republic
Tel.: +420 541 590 140
Fax: +420 541 590 124
www.nepa.cz
[email protected]
37
Was this manual useful for you? yes no
Thank you for your participation!