EZ-Temp
™
Microprocessor
Temperature
Control Guide
TABLE OF CONTENTS
Model 90000 Dual Limit Manual Reset for Direct Fired Storage Water Heaters
2-3
Model 90000CE Combination Operating Limit Manual Reset High Limit for Commercial Boilers
2-3
Model 90100 Averaging Limit Manual Reset for Commercial Direct Fired Storage Water Heaters
4-5
Model 90200 Single Limit for Direct or Indirect Fired Storage Water Heaters, or Single Limit
Manual Reset for Hot Water Boilers, or Operating Limit for Commercial Boilers
6-7
Model 90200E Manual Reset High Limit for Commercial Boilers
8-9
Model 90200H Proportional Modulating Control for Commercial Boilers
10-11
Model 90200H Proportional Modulating Control for Commercial Boilers Instruction Manual
12-15
EZ-Temp™ Temperature Controls - Model 90224 Low Voltage Single Limit for Indirect Fired
Storage Water Heaters
16-17
Model 90300 Dual Limit Manual Reset for Commercial Direct Fired Storage Water Heaters
18-19
Model 90320 240 VAC Dual Limit for Direct Fired Storage Water Heaters
20-21
Model 90524A Triple Limit or Cold Start for Hot Water Boilers
22-23
Model 90524A Instruction Manual
24-31
Model 99000A Operating Limit Manual Reset High Limit Commercial Boiler Package
32-33
Model 99000B Operating Limit Manual Reset High Limit for Lo-Hi-Lo Mode of Operation
Commercial Boiler Package
34-35
Model 99000C Operating Limit Manual Reset High Limit for Lo-Hi-Lo Mode of Operation
Commercial Boiler Package
36-37
Model 99000D Operating Limit Manual Reset High Limit and Proportional Control for Full
Modulation Mode of Operation for Commercial Boilers
38-39
Model 99000E Operating Limit Manual Reset High Limit and Proportional Control for Full
Modulation Mode of Operation for Commercial Boilers
40-41
EZ-Temp Instruction Manual for Older Style E-clamp with Red Sensor Retainer Plug
42-43
EZ-Temp Instruction Manual for Well Clamp with Sensor Retainer Spring
44-45
Thermister Resistance Chart for EZ-Temp Sensors
46-47
70 Maple Street, East Longmeadow, MA 01028
Telephone: 413-525-7700
1
2
Data sheet
Specifications
s #ARLINS-ODELMICROPROCESSOROPERATEDMULTIPLECONTACTTEMperature limit controls are available in four configurations, described
below. Each model provides two contacts — one for operating limit and
one from high limit.
s 2EFERTOSEPARATEPRODUCTLISTINGSHEETSFORPREDElNEDMODELSORREquest a control to meet your specifications, within the available ranges
listed below.
Multiple sensor option (1 or 2)
90000A
90000AL
Dual limit temperature control
7.$/ 1(,& ,#'(&'*(+(1 "1(-,
7+ /1+ ,2 */$0$1-,'(&'*(+(1
7$*$"1/-,("0$,0-/0-.$/ 1(,& ,#'(&'*(+(1
7,#$.$,# ,1-.$/ 1(,&*(+(1"-,1 "1
7,#$.$,#$,1'(&'*(+(1"-,1 "1
90000B
90000BL
Temperature limit control
7.$/ 1(,& ,#'(&'*(+(1 "1(-,
7+ /1+ ,2 */$0$1-,'(&'*(+(1
7$*$"1/-,("0$,0-/
7.$/ 1(,& ,#*(+(1"-,1 "10(,0$/($0
90000C
90000CL
Redundant limit temperature control
7.$/ 1(,& ,#'(&'*(+(1 "1(-,
7+ /1+ ,2 */$0$1-,'(&'*(+(1
7$*$"1/-,("0$,0-/0-.$/ 1(,& ,#'(&'*(+(1
7.$/ 1(,& ,#*(+(1"-,1 "10(,0$/($0
(Using individual and/or dual sensor assemblies)
Easy remote sense
90000CE
90000CEL
(Electronic sensors, wired to control)
Smart manual reset
(Manual reset only if operating limit doesn’t open)
Control model
Serviceman reset protection
Contacts
(1)
Power-independent lockout
Wires
Diagnostic LED’s
(Power, call for heat, and lockout/latchup)
(2)
Latch-up mode shuts down the control after three consecutive lockouts, and requires a
special procedure to reset. This ensures the owner will call in a licensed technician to
troubleshoot and correct burner problems.
The 90000 provides two limit relays. Carlin’s patented SMC technology (Safety Monitoring
Circuit) monitors the contacts of both relays. Lockout occurs if a limit relay contact is found
closed when it should be open.
2***- #
-")$#/-1-/
2 ,1(15
C/CL
(,0$/($0
VAC
VAC
/$#4'(1$4'(1$
(&'*(+(1INOUT
!* ")/$#
!* ")5$**-4
.$/*(+(1INOUT
!* ")&/$$,
!* ")
black
(+(10OUT
,5/ ,&$!$14$$,
81-
8
Adjustable oper. limit range
Fixed high limit temperature
CE/CEL
VACVA
VAC-1$21/ *
(Power cycling won’t reset from lockout or latch-up)
(1)
B/BL
(,#$.$,#$,1
Contact rating
SMC Technology
A/AL
Control power input /$#4'(1$4(/$
(Latch-up after three consecutive lockouts )
(2)
Combination operating limit and manual reset
high limit control
7,#$.$,#$,1-.$/ 1(,& ,#'(&'*(+(1"-,1 "10(,0$/($0
7$*$"1/-,("0$,0-/0-.$/ 1(,& ,#'(&'*(+(1
7-")-21-,#( &,-01("% (*2/$ ,#*(+(1 "1(-,
7 ,2 */$0$1%/-+*-")-21
7(&'*(+(11$01%2,"1(-,
,53 *2$%/-+
81-
8
,53 *2$%/-+
81-
8
Fixed differential (subtractive)
,53 *2$%/-+81-
8
Operating temperature limits
81-
8
Storage temperature limits
Agencies
TECH SUPPORT 800-989-2275
6
81-8
Recognized & Listed
,(1$#1 1$0 , #
carlincombustion.com
3
Model 90000 Microprocessor Temperature Controls — Data sheet — Operation & Dimensions
Model 90000A, B, C, & CE diagnostic LED’s
GREEN
– OFF
– ON Power
RED
– OFF
– ON Lockout
– FLASHING (Slow) Latch-up
AMBER
– OFF
– ON Control call for heat
– FLASHING (Fast) Hi-Test
Electrical shock hazard: Disconnect power to appliance when wiring or
servicing any electrical component.
Operation
Power OFF
(See wiring diagrams below for wiring connections.)
Configurations
With no power applied to the red-white wire, all lights are off. Power can
be wired directly from appliance 120 VAC terminal to maintain power at all
times. Or jumper red-white wire and black-green wire to cycle power with
the appliance limit circuit.
s Control kits — 90000 controls mount to a standard 4x4 J-box,
supplied with the control. Mount the box directly to a well (new or
existing) with hardware supplied, or panel mount. See below for
dimensions.
s Well kits — Wells for 90000 sensors are available in the sizes shown
below. Well kits include sensor mounting hardware designed to hold
sensor securely in position.
s Sensors — Sensors are available in single and dual configurations.
s Notice: UL-Listed control — UL-Listed controls are supplied complete with control, J-Box, well, sensor, and mounting hardware.
Power ON
When power is applied to the red-white wire, the green LED turns on.
Self-test
When power is applied, the 90000 performs a self-test, checking sensor(s)
and microprocessor and verifying limit contacts are open. The power-up test
lasts from 3 to 5 seconds. The 90000 continues diagnostic checing during
the operating cycle as well. Any self-check failure causes a lockout (see
below).
Operate
If the temperature at the operating sensor(s) is below setpoint by at least the
fixed differential, the control closes the operating limit contacts. The amber
LED turns on.
Stand-by
When the operating sensor(s) see setpoint temperature or above, the 90000
opens the operating limit contact. The amber LED turns off.
Limit action
90000A, B or C: If the high limit sensor(s) see a temperature above high
limit setting, the control opens the high limit contacts, turns on the red LED
and checks the operating limit contacts. If the operating limit contacts are
open, the control will automatically reset when temperature drops below
high limit setting minus differential. The high limit contacts close and the
red LED turns off. Diagnostic failures invoke “limit action” until cause is
cleared.
Lockout
If the high limit sensor(s) sees a temperature above high limit setting and
the 90000A, B, or C model finds the operating limit contacts closed, the high
limit contact opens, the red LED turns on and lockout occurs. If the high
limit sensor on the 90000CE sees a temperature above the high limit setting,
the high limit contact opens, the red LED turns on and lockout occurs. When
the temperature drops below high limit setting minus differential, reset the
control by pressing the manual reset button. The control will not reset by
cycling power off and on.
Latch-up
)F THE LOCKS OUT THREE CONSECUTIVE TIMES IT ENTERS LATCHUP 2ESET
from latch-up requires a special procedure, intended to require licensed
serviceman intervention. During latch-up, the red LED stays on and the
GREEN,%$mASHESSLOW2ESETASFOLLOWS
............
Hold reset button at least 10 seconds. The green LED flashes faster.
............
Continue holding button another 20 seconds. The control resets and the red
LED turns off.
............
h(I4ESTvMODE#%/.,9USEDTOTESTh(IGH,IMIT2ESETvATOPERATING
boiler temperature. Start test with system operational and calling for heat.
Turn setpoint full clockwise to Hi-Test position. Green LED flashes fast.
The setpoint now adjusts both the high and operating limits. Turn setpoint
slowly counter clockwise until Lockout occurs. Now the setpoint temperature
equals the hi-limit sensor temperature. Test is complete, adjust setpoint to
THEDESIREDOPERATINGLIMIT2EMOVEFROMLOCKOUT
Temperature is less than high limit setting minus differential:
Power must flow through the contacts in the direction shown. Changing
flow direction will cause the control to lockout or fail to operate.
90000A
G
G
90000B, C, CE
N
White
Wiring shown cycles power with appliance limit circuit. To
maintain constant power on 90000A, connect direct to
red/white wire from appliance 120 vac.
120 VAC
120 VAC
CONNECTIONS
AT APPLIANCE
POWER TO
APPLIANCE
Red/White
Service
switch
H
G
G
N
White
Red/White
120 VAC
120 VAC
CONNECTIONS
AT APPLIANCE
POWER TO
APPLIANCE
Service
switch
HIGH LIMT
H
Black-red
HIGH LIMIT
Black-yellow
High limit OUT
Operating Limit IN
Black-green
OPERATING LIMIT
Black
High limit
Limit sensor
OPERATING LIMIT
Black
Sensor
Dual limit OUT
To sensor (90000C and 90000CE use 2 sensors connected the same as the 90000A)
Operating limit OUT
To high limit sensor
To operating limit sensor
© Copyright 2010 — Carlin Combustion Technology, Inc.
Carlin part number MN90000C Rev. 01/26/10
4
Data sheet
Specifications
•
•
Carlin’s 90100 microprocessor-operated, multiple-contact temperature
limit controls are available in three configurations, described below.
Each model provides two contacts — one for operating limit and one
from high limit.
Refer to separate product listing sheets for pre-defined models, or
request a control to meet your specifications, within the available
ranges listed below.
Multiple sensors (2 or 3)
(Using individual and/or dual sensor assemblies)
Sensor averaging
(Average operating limit, high limit or both)
Easy remote sense
(Electronic sensors, wired to control)
Smart manual reset
(Manual reset only if operating limit doesn’t open)
Serviceman reset protection
(Latch-up after three consecutive lockouts (1))
Power-independent lockout
(Power cycling won’t reset from lockout or latch-up)
Diagnostic LED’s
(Power, call for heat, and lockout/latchup)
SMC Technology
(2)
(1) Latch-up mode shuts down the control after three consecutive lockouts, and requires
a special procedure to reset. This ensures the owner will call in a licensed technician to
troubleshoot and correct burner problems.
(2) The 90100 provides two limit relays. Carlin’s patented SMC technology (Safety Monitoring Circuit) monitors the contacts of both relays. Lockout occurs if a limit relay contact is
found closed when it should be open.
TECH SUPPORT 800-989-2275
carlincombustion.com
5
Model 90100 Microprocessor Temperature Controls — Data sheet — Operation & Dimensions
Model 90100 diagnostic LED’s
Configurations
GREEN
– OFF
– ON Power
•
RED
– OFF
– ON Lockout
AMBER
– OFF
– ON Control call for heat
– FLASHING Latch-up
•
Electrical shock hazard: Disconnect power to appliance when wiring or
servicing any electrical component.
Operation
(See wiring diagrams below for wiring connections.)
Power OFF
With no power applied to the red-white wire, all lights are off. Power can be
wired directly from appliance 120 VAC terminal to maintain power at all times.
Or jumper red-white wire and black-green wire to cycle power with the appliance limit circuit.
Power ON
When power is applied to the red-white wire, the green LED turns on.
Self-test
When power is applied, the 90100 performs a self-test, checking sensor(s)
and microprocessor and verifying limit contacts are open. The power-up test
lasts from 3 to 5 seconds. The 90100 continues diagnostic checking during
the operating cycle as well. Any self-check failure causes a lockout (see
below).
Operate
If the temperature at the operating sensor(s) is below setpoint by at least the
fixed differential, the control closes the operating limit contacts. The amber
LED turns on.
Stand-by
When the operating sensor(s) see setpoint temperature or above, the 90100
opens the operating limit contact. The amber LED turns off.
Limit action
If the high limit sensor(s) see a temperature above high limit setting, the
90100 opens the high limit contacts, turns on the red LED and checks the
operating limit contacts. If the operating limit contacts are open, the control
will automatically reset when temperature drops below high limit setting minus
differential. The high limit contacts close and the red LED turns off.
Lockout
If the high limit sensor(s) sees a temperature above high limit setting and
the 90100 finds the operating limit contacts closed, the red LED turns on and
lockout occurs. (Lockout also occurs on any diagnostic test failure.) When
the temperature drops below high limit setting minus differential, reset the
control by pressing the manual reset button. The control will not reset by
cycling power off and on.
Latch-up
If the 90100 locks out three consecutive times, it enters latch-up. Reset from
latch-up requires a special procedure, intended to require licensed serviceman intervention. During latch-up, the red LED stays on and the green LED
flashes. Reset as follows:
............
Temperature must be less than high limit setting minus differential.
............
Hold reset button at least 10 seconds. The green LED flashes faster.
............
Continue holding button another 20 seconds. The control resets and the red
LED turns off.
•
Control kits — 90100 controls mount to a standard 4x4 J-box,
supplied with the control. Mount the box directly to a well (new
or existing) with hardware supplied, or panel mount. See below
for dimensions.
Well kits — Wells for 90100 sensors are available in the sizes
shown below. Well kits include sensor mounting hardware designed to hold sensor securely in position.
Sensors — Sensors are available in single and dual configurations.
Power must flow through the contacts in the direction shown. Changing
flow direction will cause the control to lockout or fail to operate.
© Copyright 2005 — Carlin Combustion Technology, Inc.
Carlin part number MN90100C Rev. 01/31/05
6
Data sheet
Specifications
s #ARLINS -ODEL !, ", $, AND ', MICROPROCESSOROPERATED
TEMPERATURECONTROLSARE5,,ISTEDANDPROVIDEDASACOMPLETEPACK
AGECONSISTINGOFCONTROL*BOXSENSORANDWELL-ODEL!
" $ OR ' CONTROLS ARE 5, 2ECOGNIZED AND PROVIDED AS INDIVIDUAL
COMPONENTSWITH*BOXSENSORANDWELLAVAILABLESEPARATELY
s #ARLINSMODELMICROPROCESSOROPERATEDTEMPERATURECONTROLS
ARE AVAILABLE IN FOUR CONlGURATIONS DESCRIBED BELOW %ACH MODEL
PROVIDESONELIMITDUTYRATEDCONTACT
s 2EFERTOSEPARATEPRODUCTLISITNGSHEETSFORPREDElNEDMODELSOR
REQUEST A CONTROL TO MEET YOUR SPECIlCATIONS WITHIN THE AVAILABLE
RANGESLISTEDBELOW
Microprocessor-operated
90200AL
Temperature limit control
7
!/$ )-,/(0$"-,1 "1
7
$*$"1/-,("0$,0-/
7*-")-21-,#( &,-01("% (*2/$
7/$0$1%/-+*-")-213( .-4$/"5"*$
90200BL
Temperature limit control
7
+ )$-,/(0$"-,1 "1
7
$*$"1/-,("0$,0-/
7*-")-21-,#( &,-01("% (*2/$
7/$0$1%/-+*-")-213( .-4$/"5"*$
90200DL
Temperature limit control
7"-,1 "10
!/$ )
+ )$-,/(0$
7
$*$"1/-,("0$,0-/
7*-")-21-,#( &,-01("% (*2/$
7/$0$1%/-+*-")-213( .-4$/"5"*$
90200GL
Temperature limit control
7
!/$ )-,/(0$(0-* 1$#"-,1 "1
7
$*$"1/-,("0$,0-/
7*-")-21-,#( &,-01("% (*2/$
7/$0$1%/-+*-")-213( .-4$/"5"*$
(Processor coordinates limit and diagnostic functions)
Easy remote sense
(Electronic sensor, wired to control)
Control model
AL
Contacts
Select from break-on-rise,
make-on-rise or SPDT operation
"1(-,-,1$+.$/ 12/$/(0$
Contact rating
Wires
!/$ )0
+ )$0
2***- #
-")$#/-1-/
2 ,1(15
(Control locks out on diagnostic failure)
Diagnostic/status LED’s
!* ")
)$-,/(0$OUT
NA
(LED’s indicate power, call for heat, and lockout)
Fixed differential (subtractive)
!/$ )0
+ )$0
NA
!* ")
!*)4'(1$ !*)4'(1$
!* ")
&/$$,
!* ")
,5/ ,&$!$14$$,81-8
,53 *2$%/-+81-
8
81-
8
Storage temperature limits
681-
8
TECH SUPPORT 800-989-2275
!/$ )0
Operating temperature limits
Agencies
GL
/$#4'(1$4'(1$
/$ )-,/(0$OUT
Adjustable oper. limit range
DL
VAC
VAC
VACH(+(1INN
Self-checking program
BL
VAC
VA
Control power input /$#4'(1$4(/$
Recognized & Listed
"-+.-,$,1,(1$#1 1$0 , #
carlincombustion.com
7
Model 90200 Microprocessor Temperature Controls — Data sheet — Operation & Dimensions
Model 90200 diagnostic LED’s
nOFF
nON Power on Center AMBER
nOFF
nON Call for low fire (90200GL only)
Right AMBER
nOFF
nON Control call for heat or high fire
GREEN
nFLASHING Lockout
s
Electrical shock hazard:$ISCONNECTPOWERTOAPPLIANCEWHENWIRINGOR
SERVICINGANYELECTRICALCOMPONENT
Operation
s
s
3EEWIRINGDIAGRAMSBELOWFORWIRINGCONNECTIONS
Indicator LED’s
Configurations
90200CONTROLSHAVEAGREEN,%$POWERLOCKOUTINDICATOR
AND CENTER AMBER ,%$ ,OW &IRE INDICATOR ONLY PRESENT
ON ', RIGHT AMBER ,%$ OPERATION OR (IGH &IRE
INDICATOR
Power OFF 7ITHNOPOWERAPPLIEDTOTHEREDWHITEWIREALLLIGHTSARE
OFF
Power ON 7HENPOWERISAPPLIEDTOTHEREDWHITEWIRETHEGREENAND
CENTERAMBER,%$SONLYPRESENTON',TURNON
Self-test
7HEN POWER IS APPLIED THE PERFORMS A SELFTEST
CHECKING THE SENSOR AND MICROPROCESSOR 4HE POWERUP
TESTLASTSFROMTOSECONDS
4HECONTINUESDIAGNOSTICCHECKINGDURINGTHEOPERAT
INGCYCLEASWELL!NYSELFCHECKFAILURECAUSESALOCKOUT
SEEBELOW
Call for heat 7HENTHETEMPERATUREATTHEOPERATINGSENSORISATORBELOW
or high fire SETPOINTMINUSlXEDDIFFERENTIALTHECONTROLPOWERSTHELIMIT
RELAYBREAKONRISECONTACTCLOSESMAKEONRISECONTACT
OPENS4HECENTERAMBER,%$IFPRESENTTURNSOFFTHE
RIGHTAMBER,%$TURNSON
Stand-by
7HENTHEOPERATINGSENSORREACHESSETPOINTTEMPERATUREOR
or low fire ABOVETHETURNSOFFTHERELAYBREAKONRISECONTACT
OPENSMAKEONRISECONTACTCLOSES4HECENTERAMBER,%$
IFPRESENTTURNSONANDTHERIGHTAMBER,%$TURNSOFF
Lockout
)FTHECONTROLDETECTSADIAGNOSTICFAILURElockout OCCURS
$URINGLOCKOUTTHEGREEN,%$mASHES
!FTERTHETEMPERATUREDROPSBELOWHIGHLIMITSETTINGMINUS
DIFFERENTIALRESETTHECONTROLBYTURNINGPOWEROFFTHENBACK
ON4HEGREEN,%$WILLSTOPmASHING
s
Mounting ˆ !, ", $, AND ', CONTROLS MOUNT TO A
STANDARD X *BOX SUPPLIED WITH THE CONTROL -OUNT THE BOX
DIRECTLY TO A WELL NEW OR EXISTING WITH HARDWARE SUPPLIED OR
PANELMOUNT3EEBELOWFORDIMENSIONS
Well kits ˆ7ELLSFOR!,",$,AND',SENSORSAREAVAIL
ABLEINTHESIZESSHOWNBELOW7ELLKITSINCLUDESENSORMOUNTING
HARDWAREDESIGNEDTOHOLDSENSORSECURELYINPOSITION
Sensors ˆ3ENSORSAREAVAILABLESEPARATELYFOR!"$AND
'ONLY4HESENSORISSUPPLIEDWITH!,",$,AND',
NOTICE ˆ5,,ISTEDMODEL!,",$,',CONTROLSMUST
BE SHIPPED COMPLETE WITH A SENSOR WELL AND *BOX /NLY 5,
RECOGNIZEDCOMPONENTMODELS!"$AND'CONTROLSCAN
BEPURCHASEDASINDIVIDUALCOMPONENTS
0OWERMUSTmOWTHROUGHTHECONTACTSINTHEDIRECTIONSHOWN#HANGING
mOWDIRECTIONWILLCAUSETHECONTROLTOLOCKOUTORFAILTOOPERATE
90200AL or BL
G
G
N
White
120 VAC
120 VAC
CONNECTIONS
AT APPLIANCE
POWER TO
APPLIANCE
Red/White
Service
switch
H
Limit contact: Model A breaks on temperature rise; Model B makes on temperature rise
Limit OUT
Black
Sensor
To sensor
90200DL
G
G
90200GL
G
N
White
N
White
120 VAC
120 VAC
CONNECTIONS
AT APPLIANCE
POWER TO
APPLIANCE
Limit OUT
Black
Service
switch
BREAK ON TEMP RISE
Red/White
H
120 VAC
120 VAC
CONNECTIONS
AT APPLIANCE
POWER TO
APPLIANCE
Red/White
Service
switch
Black/Green
MAKE ON TEMP RISE
Control contact — Breaks on temperature rise
Make-on-rise contact OUT
Black-white
Low-fire control to burner
Black
Sensor
G
To sensor
© Copyright 2008 — Carlin Combustion Technology, Inc.
Sensor
To sensor
Carlin part number MN90200C Rev. 10/30/08
H
8
Manual Reset High Limit
Data sheet
Specifications
s
s
s
-ODEL%,CONTROLIS5,LISTEDANDPROVIDEDASACOMPLETEPACKAGE
CONSISTINGOFCONTROL*BOXSENSORANDWELL-ODEL%CONTROL
IS5,RECOGNIZEDANDPROVIDEDASINDIVIDUALCOMPONENTSWITH*BOX
SENSORANDWELLAVAILABLESEPARATELY
#ARLINS-ODEL%AND%,MICROPROCESSOROPERATEDTEM
PERATURE CONTROLS ARE DESCRIBED BELOW 4HE % AND %,
PROVIDEASINGLECONTACTBREAKONRISEWITHMANUALRESET
2EFER TO SEPARATE PRODUCT LISTING SHEETS FOR PREDElNED MODELS OR
REQUEST A CONTROL TO MEET YOUR SPECIlCATIONS WITHIN THE AVAILABLE
RANGESLISTEDBELOW
Microprocessor-operated
(Processor coordinates limit and diagnostic functions)
90200E
90200EL
Temperature limit control
5-"'+*-&." +*/ /
5(+ '+0/+*!&$*+./& #&(0-"(&)&/ /&+*
5)*0(-"."/#-+)(+ '+0/
5*+-"."/#-+),+2"-&*/"--0,/&+*
Easy remote sense
Control model
(Electronic sensor, wired to control)
Control power input -"!2%&/"2&-"
VACVA
Contacts
-"'+*-&."
Contact rating
Break-on-rise operation
Wires
90200E & 90200EL
0(((+!
+ '"!-+/+-
0*/&/3
VAC"0/-(
VACHOT&)&/IN
Self-checking program
(Control locks out on diagnostic failure)
Diagnostic/status LED’s
&)&/OUT
Adjustable limit range
VACAMPS
VACAMPS
3
2%&/"
-"!2%&/"
( '
*3-*$""/2""*6/+
6
Fixed differential (subtractive)
*31(0"#-+)6/+6
Operating temperature limits
6/+6
Storage temperature limits
Agencies
(LED’s indicate power and lockout)
TECH SUPPORT 800-989-2275
46/+6
Recognized & Listed
+),+*"*/*&/"!//".*!
carlincombustion.com
9
Model 90200E/EL Microprocessor Temperature Controls — Data sheet — Operation & Dimensions
Model 90200E/EL diagnostic LED’s
GREEN
nOFF
nON Power on
RED
nOFF
nON Lockout
nFLASHING Lockout pending
Electrical shock hazard:$ISCONNECTPOWERTOAPPLIANCEWHENWIRINGOR
SERVICINGANYELECTRICALCOMPONENT
Operation
s
s
s
3EEWIRINGDIAGRAMSBELOWFORWIRINGCONNECTIONS
Indicator LED’s
Configuration
90200EAND90200ELCONTROLSHAVEAGREEN,%$POWERLOCKOUT
PENDINGINDICATORANDRED,%$LOCKOUT
Power OFF 7ITHNOPOWERAPPLIEDTOTHEREDWHITEWIREALLLIGHTSAREOFF
Power ON 7HEN POWER IS APPLIED TO THE REDWHITE WIRE THE GREEN ,%$
TURNSON
Self-test
7HENPOWERISAPPLIEDTHE%%,PERFORMSASELFTEST
CHECKING THE SENSOR AND MICROPROCESSOR 4HE POWERUP TEST
LASTSFROMTOSECONDS
4HE %%, CONTINUES DIAGNOSTIC CHECKING DURING THE
OPERATINGCYCLEASWELL!NYSELFCHECKFAILURECAUSESALOCKOUT
SEEBELOW
Call for heat 7HENTHETEMPERATUREATTHEOPERATINGSENSORISBELOWSETPOINT
MINUSlXEDDIFFERENTIALTHECONTROLPOWERSTHELIMITRELAYTHE
BREAKONRISECONTACTCLOSES
Lockout
pending
)FADIAGNOSTICFAILUREOCCURSORTHESENOSRTEMPERATURERISES
ABOVETHELIMITSETTINGTHEGREEN,%$WILLmASHFORSECONDS
)FTHECONDITIONSTILLEXISTSAFTERSECONDSTHECONTROLWILLENTER
LOCKOUT)FTHECONDITIONCORRECTSBEFORESECONDSTHEGREEN
,%$WILLRETURNTONORMAL
Lockout
$URINGLOCKOUTTHEGREEN,%$STOPSmASHINGANDSTAYSONAND
THERED,%$TURNSON
!FTERTHETEMPERATUREDROPSBELOWHIGHLIMITSETTINGMINUSDIF
FERENTIALRESETTHECONTROLBYPRESSINGTHERESETBUTTON
s
Mounting ˆ%%,CONTROLSMOUNTTOASTANDARDX*BOX
SUPPLIEDWITHTHECONTROL-OUNTTHEBOXDIRECTLYTOTHEWELLWITH
HARDWARESUPPLIEDORPANELMOUNT3EEBELOWFORDIMENSIONS
Well kits ˆ 7ELLS FOR %%, SENSORS ARE AVAILABLE IN THE
SIZESSHOWNBELOW7ELLKITSINCLUDESENSORMOUNTINGHARDWARE
DESIGNEDTOHOLDSENSORSECURELYINPOSITION
Sensors ˆ3ENSORSAREAVAILABLESEPARATELYFOR%ONLY4HE
SENSORISSUPPLIEDWITH%,
NOTICE ˆ5,LISTED-ODEL%,CONTROLSMUSTBESHIPPED
COMPLETE WITH A SENSOR WELL AND *BOX /NLY 5, RECOGNIZED
COMPONENT-ODEL%CONTROLSCANBEPURCHASEDASINDIVIDUAL
COMPONENTS
0OWERMUSTmOWTHROUGHTHECONTACTSINTHEDIRECTIONSHOWN#HANGING
mOWDIRECTIONWILLCAUSETHECONTROLTOFAILTOOPERATE
© Copyright 2008 — Carlin Combustion Technology, Inc.
Carlin part number MN90200EC Rev. 08/1/08
10
Data sheet
Features
s
s
s
s
s
s
s
%LECTRONICSENSORINPUT
operating temperatureADJUSTMENT
lXEDtemperature differential
modulating bandADJUSTMENT
,OCKOUTONDIAGNOSTICFAILURE
,ATCHUPONHARDWAREFAILURE
)SOLATEDPROPORTIONALOHMMODULATINGCONTROLOUTPUT
(ˆONWIRESIN*BOX
(4ˆONTERMINALSONFRONTOFCONTROL
Specifications
s #ARLINS -ODEL ( MICROPROCESSOR OPERATED TEMPERATURE CONTROL
ISDESIGNEDTOOPERATEOHMMODULATEDDEVICESREPLICATINGOLDER
SLIDEWIREDEVICESANDISAVAILABLEINCONlGURATIONSDESCRIBEDBELOW
.OTETHAT((4CONTROLSREQUIREAVOLTPOWERINPUT4HE
OHMCIRCUITISISOLATED
s &ORELECTRONICMODMOTORCONTROLSYSTEMSSUCHAS3IEMENS31CONSULT
MANUFACTURER
s 2EFERTOSEPARATEPRODUCTLISTINGSHEETSFORPREDElNEDMODELSORRE
QUESTACONTROLTOMEETYOURSPECIlCATIONSWITHINTHEAVAILABLERANGES
LISTEDBELOW
Model
90200H
Input power (L1-L2)
(SHOWNˆ(4ALSOAVAILABLEWITH
TERMINALSTRIPONFRONTFORLOWVOLTAGECONNECTIONS
135-ohm proportional output
Modulating output
Control
Max drive
Balance circuit
Connections:
(For regulating 135-ohm modulating devices)
120 VAC H/N
Microprocessor-operated
To “W” on device
To “R” on device
To “B” on device
90200HT
120 VAC, 2 VA
3.5 +/- 0.5 VDC, 4.2 +/- 0.2 mA
20 VDC O.C., 6 mA S. C.
Adjustment on rear of control
5 wires
(no terminals)
2 wires (120 VAC)
3 terminals (mod)
Red/White & White wires
Yellow/White wire
Yellow/Red wire
Yellow/Black wire
“White” terminal
“Red” terminal
“Black” terminal
(Processor coordinates operation and diagnostic)
Operating temp.
range
Adjustable
(any range between 40°F and 250°F)
Easy remote sense
Temp. differential
range
Fixed (any value between 1°F and 10°F)
(Electronic sensor, wired to control)
Self-checking program
(Control locks out on diagnostic failure)
Diagnostic/status LED’s
(LED’s indicate power, call for heat, and lockout)
Modulating band
range
Adjustable
(Any range between 10°F and 100°F)
Ambient temp.
limits
+32°F to +140°F (0°C to +60°C)
Storage temp.
limits
-40°F to +185°F (-40°C to +85°C)
Agencies
UL & ULC Recognized & Listed
Component US and Canada
TECH SUPPORT 800-989-2275
carlincombustion.com
11
Model 90200H/HT Microprocessor Temperature Controls — Data sheet
Model 90200H/HT diagnostic LED’s
90200H/HTCONTROLSHAVEAGREEN,%$POWERFAULTINDICATORANDAMBER,%$lRINGRATE
PERCENTFAULTINDICATOR3EE,%$CONDITIONSBELOW
GREEN
Figure 1
Wiring connections
90200H
n/.Indicates control is oprational)
White
nShort on/Long off flash
nLong on/Short off flash
Yellow/White
nFLASH uniformly ABOUTONCEPERSECONDEQUALONOFFDURATIONS
AMBER
Red/White
nOFF
nOFF
n/.
nShort on/Long off flash
nLong on/Short off flash
N
R
Yellow/Black
Sensor
90200HT
B
Red/White
H
Service
switch
White
Power Off: When no power is applied to the Red-White wire, the modulating
output is at LOW FIRE.
Power On: When power is applied to the Red-White wire, the circuit is energized
starting the Fault Log Display followed by the Self Test. When these are complete
the control becomes operational and turns the Green LED on steady
135-ohm
modulated
device
To sensor
W
R
R
B
Sensor
120 VAC
N
W
LED’s Control status
120 VAC
W
Yellow/Red
nON time equals firing rate percentage
Operation
H
Service
switch
B
135-ohm
modulated
device
To sensor
Swap connections to B and W to reverse the motor direction.
See Fault log display below — faults will display when power is applied.
NOTE: When flashing, the LED’s flash once every second in Fault display mode. The
green LED flashes once every 3 seconds when in Self Test mode.
Configurations
Self Test: When the fault log display is complete, the self test checks the sensor and the microprocessor and internal circuits. This test lasts up to 6 seconds
before the control becomes fully operational. During the self test the green LED
flashes on once every 3 seconds.
s Control kits ˆ((4CONTROLSMOUNTTOASTANDARDX*BOX
SUPPLIEDWITHTHECONTROL-OUNTTHEBOXDIRECTLYTOAWELLNEWOR
EXISTINGWITHHARDWARESUPPLIEDORPANELMOUNT3EE&IGUREFOR
DIMENSIONS
Burner @ High-Fire: When the sensor temp is at or below the operating
temp minus 1/2 the modulating band, the modulation signal is at High-fire. The
Amber LED is full on.
s Well kits ˆ7ELLSFOR(SENSORSAREAVAILABLEINTHESIZES
SHOWN IN &IGURE 7ELL KITS INCLUDE SENSOR MOUNTING HARDWARE
DESIGNEDTOHOLDSENSORSECURELYINPOSITION
Burner @ Low-Fire: When the sensor temp is at or above the operating
temp plus 1/2 the modulating band, the modulation signal is at Low-fire. The
Amber LED is full off.
Burner in Proportional Modulation: When the sensor temperature is in
the modulating band (1/2 the band setting either side of the operating temp),
the control modulation signal varies proportionally between high and low fire. The
Amber LED flashes proportionally. The percentage of time the LED is on equals
the modulating output percentage.
s Sensors ˆ3ENSORSAREAVAILABLEINSINGLECONlGURATIONS
Figure 2
Mounting the 90200H/HT
Lockout: The control goes into lockout on ANY of the fault code conditions
and Logs the fault code indicated below under “Fault log display.”
While in lockout, the Motor modulation output is at low fire. The Amber LED is
off. The green LED flashes uniformly once per second.
Reset from Lockout:4HE CONTROL AUTOMATICALLY RESETS FROM ,OCKOUT WHEN
!,,CONDITIONSRETURNTONORMAL4HECONTROLRETURNSTOWHATEVERSTATEISDElNED
BYITSINPUTS
,ATCHUP#ONTROLGOESINTO,ATCHUPONHARDWAREFAILURE#ONTROLSHOULDBERE
PLACED4HEGREEN,%$ISOFF4HEAMBER,%$ISON4HISWILLOCCURIMMEDIATELYIF
POWERISTURNEDOFFANDBACKONAGAININCONTROLISINLATCHUP
Fault log display (based on LED status)
If the control has detected a fault condition, it will display the fault conditions when
power is turned off, then turned on again. Each fault code will occur 4 times. The control
will then display the next fault code, if any. The fault log is erased after displaying the
results. The codes will display in the following sequence:
1
)NTERNALCONTROLMICROPROCESSORFAILURE
4EMPERATURESENSORISSHORTED
4EMPERATURESENSORISOPEN2EPEATSTHESAMECODE
4
)NTERNALCONTROLMICROPROCESSORˆPINISOPEN
-ODULATINGBANDINTERNALCIRCUITISOPEN
6
/PERATINGTEMPERATUREINTERNALCIRCUITISOPEN2EPEATSTHESAMECODE
7
#ONTROLINTERNALDIAGNOSTICFAILURE
© Copyright 2009 — Carlin Combustion Technology, Inc.
Carlin part number MN90200HC Rev. 04/16/09
12
Instructions
Features
s
s
s
s
s
s
s
%LECTRONICSENSORINPUT
operating temperatureADJUSTMENT
lXEDtemperature differential
modulating bandADJUSTMENT
,OCKOUTONDIAGNOSTICFAILURE
,ATCHUPONHARDWAREFAILURE
)SOLATEDPROPORTIONALOHMMODULATINGCONTROLOUTPUT
(ˆONWIRESIN*BOX
(4ˆONTERMINALSONFRONTOFCONTROL
Specifications
s #ARLINS -ODEL ( MICROPROCESSOR OPERATED TEMPERATURE CONTROL
ISDESIGNEDTOOPERATEOHMMODULATEDDEVICESREPLICATINGOLDER
SLIDEWIREDEVICESANDISAVAILABLEINCONlGURATIONSDESCRIBEDBELOW
.OTETHAT((4CONTROLSREQUIREAVOLTPOWERINPUT4HE
OHMCIRCUITISISOLATED
s &ORELECTRONICMODMOTORCONTROLSYSTEMSSUCHAS3IEMENS31CONSULT
MANUFACTURER
s 2EFERTOSEPARATEPRODUCTLISTINGSHEETSFORPREDElNEDMODELSORRE
QUESTACONTROLTOMEETYOURSPECIlCATIONSWITHINTHEAVAILABLERANGES
LISTEDBELOW
Model
90200H
Input power (L1-L2)
(SHOWNˆ(4ALSOAVAILABLEWITH
TERMINALSTRIPONFRONTFORLOWVOLTAGECONNECTIONS
135-ohm proportional output
Modulating output
Control
Max drive
Balance circuit
Connections:
(For regulating 135-ohm modulating devices)
120 VAC H/N
Microprocessor-operated
To “W” on device
To “R” on device
To “B” on device
90200HT
120 VAC, 2 VA
3.5 +/- 0.5 VDC, 4.2 +/- 0.2 mA
20 VDC O.C., 6 mA S. C.
Adjustment on rear of control
5 wires
(no terminals)
2 wires (120 VAC)
3 terminals (mod)
Red/White & White wires
Yellow/White wire
Yellow/Red wire
Yellow/Black wire
“White” terminal
“Red” terminal
“Black” terminal
(Processor coordinates operation and diagnostic)
Operating temp.
range
Adjustable
(any range between 40°F and 250°F)
Easy remote sense
Temp. differential
range
Fixed (any value between 1°F and 10°F)
(Electronic sensor, wired to control)
Self-checking program
(Control locks out on diagnostic failure)
Diagnostic/status LED’s
(LED’s indicate power, call for heat, and lockout)
Modulating band
range
Adjustable
(Any range between 10°F and 100°F)
Ambient temp.
limits
+32°F to +140°F (0°C to +60°C)
Storage temp.
limits
-40°F to +185°F (-40°C to +85°C)
Agencies
UL & ULC Recognized & Listed
Component US and Canada
TECH SUPPORT 800-989-2275
carlincombustion.com
13
Model 90200H/HT Microprocessor Temperature Controls — Instructions
Where appliance instructions differ from this manual, follow the appliance instructions.
Model 90200H/HT diagnostic LED’s
90200H/HTCONTROLSHAVEAGREEN,%$POWERFAULTINDICATORANDAMBER,%$lRINGRATE
PERCENTFAULTINDICATOR3EE,%$CONDITIONSBELOW
GREEN
Figure 1
Wiring connections
90200H
n/.Indicates control is oprational)
White
nShort on/Long off flash
nLong on/Short off flash
Yellow/White
nFLASH uniformly ABOUTONCEPERSECONDEQUALONOFFDURATIONS
AMBER
Red/White
nOFF
nOFF
n/.
nShort on/Long off flash
nLong on/Short off flash
90200HT
Operation
N
W
R
Yellow/Black
B
Power Off: When no power is applied to the Red-White wire, the modulating
output is at LOW FIRE.
Power On: When power is applied to the Red-White wire, the circuit is energized
starting the Fault Log Display followed by the Self Test. When these are complete
the control becomes operational and turns the Green LED on steady
135-ohm
modulated
device
To sensor
Red/White
H
Service
switch
White
W
R
R
B
Sensor
120 VAC
N
W
LED’s Control status
120 VAC
Yellow/Red
Sensor
nON time equals firing rate percentage
H
Service
switch
B
135-ohm
modulated
device
To sensor
Swap connections to B and W to reverse the motor direction.
See Fault log display below — faults will display when power is applied.
NOTE: When flashing, the LED’s flash once every second in Fault display mode. The
green LED flashes once every 3 seconds when in Self Test mode.
Configurations
Self Test: When the fault log display is complete, the self test checks the sensor and the microprocessor and internal circuits. This test lasts up to 6 seconds
before the control becomes fully operational. During the self test the green LED
flashes on once every 3 seconds.
s Control kits ˆ((4CONTROLSMOUNTTOASTANDARDX*BOX
SUPPLIEDWITHTHECONTROL-OUNTTHEBOXDIRECTLYTOAWELLNEWOR
EXISTINGWITHHARDWARESUPPLIEDORPANELMOUNT3EE&IGUREFOR
DIMENSIONS
Burner @ High-Fire: When the sensor temp is at or below the operating
temp minus 1/2 the modulating band, the modulation signal is at High-fire. The
Amber LED is full on.
s Well kits ˆ7ELLSFOR(SENSORSAREAVAILABLEINTHESIZES
SHOWN IN &IGURE 7ELL KITS INCLUDE SENSOR MOUNTING HARDWARE
DESIGNEDTOHOLDSENSORSECURELYINPOSITION
Burner @ Low-Fire: When the sensor temp is at or above the operating
temp plus 1/2 the modulating band, the modulation signal is at Low-fire. The
Amber LED is full off.
Burner in Proportional Modulation: When the sensor temperature is in
the modulating band (1/2 the band setting either side of the operating temp),
the control modulation signal varies proportionally between high and low fire. The
Amber LED flashes proportionally. The percentage of time the LED is on equals
the modulating output percentage.
s Sensors ˆ3ENSORSAREAVAILABLEINSINGLECONlGURATIONS
Figure 2
Mounting the 90200H/HT
Lockout: The control goes into lockout on ANY of the fault code conditions
and Logs the fault code indicated below under “Fault log display.”
While in lockout, the Motor modulation output is at low fire. The Amber LED is
off. The green LED flashes uniformly once per second.
Reset from Lockout:4HE CONTROL AUTOMATICALLY RESETS FROM ,OCKOUT WHEN
!,,CONDITIONSRETURNTONORMAL4HECONTROLRETURNSTOWHATEVERSTATEISDElNED
BYITSINPUTS
,ATCHUP#ONTROLGOESINTO,ATCHUPONHARDWAREFAILURE#ONTROLSHOULDBERE
PLACED4HEGREEN,%$ISOFF4HEAMBER,%$ISON4HISWILLOCCURIMMEDIATELYIF
POWERISTURNEDOFFANDBACKONAGAININCONTROLISINLATCHUP
Fault log display (based on LED status)
If the control has detected a fault condition, it will display the fault conditions when
power is turned off, then turned on again. Each fault code will occur 4 times. The control
will then display the next fault code, if any. The fault log is erased after displaying the
results. The codes will display in the following sequence:
1
)NTERNALCONTROLMICROPROCESSORFAILURE
4EMPERATURESENSORISSHORTED
4EMPERATURESENSORISOPEN2EPEATSTHESAMECODE
4
)NTERNALCONTROLMICROPROCESSORˆPINISOPEN
-ODULATINGBANDINTERNALCIRCUITISOPEN
6
/PERATINGTEMPERATUREINTERNALCIRCUITISOPEN2EPEATSTHESAMECODE
7
#ONTROLINTERNALDIAGNOSTICFAILURE
-2-
Carlin part number MN90200HM Rev. 04/16/09
14
Model 90200H/HT Microprocessor Temperature Controls — Instructions
Where appliance instructions differ from this manual, follow the appliance instructions.
Figure 3
90200H Equivalent circuit diagram
Wiring connections
Line voltage power to control
5. When the throttle arm stops moving and the Amber LED is full ON (if not
full on, the water temperature is too hot — wait for it to cool), turn the
rear calibration pot slowly ccw until the arm just starts to move away
from Hi-Fire.
1. 90200H and 90200HT controls require a 120 VAC power source as shown
in Figure 3. The power must be taken from the appliance line voltage power
source to ensure correct phasing.
6. When the arm stops, slowly turn the pot cw until the arm just starts to
move toward Hi-Fire.
Modulating terminal wiring
7. Setup is complete. Remove power, re-mount the control for operation,
then Set Band and Operating temperature setpoints to desired operating
settings.
1. Connect the modulating device’s R, B and W terminals to the three 90200H/
HT wires as shown in Figure 3.
s
07-3ETUPTOGUARANTEEBURNERh&ULLOFFvPOSITION
0ERFORMSTEPSFROMhFULLONvSETUPABOVE
Setup Procedure:
s
Mount the control so there will be access to the back when the system is
powered up. Be careful when making rear adjustments as circuits will have
power.
s
07-3ETUPTOGUARANTEEBURNERh&ULLONvPOSITION
1. Set the rear calibration potentiometer to the full cw position.
2. Set the Modulation Band setpoint to its min value.
3. Set the Operating Temperature setpoint to its mid value.
0OWERUPCONTROLWITHTHESTRIPEDYELLOWWIRESCONNECTEDTOTHEBURNERS
proportional throttle motor. Apply power to the throttle motor. The throttle
arm should move toward Hi-Fire. (If not, power down & reverse the connections to the B & W pins on the motor).
Carlin part number MN90200HM Rev. 04/16/09
2. Allow the burner to heat the vessel, and when the Amber LED starts flashing
(vessel temperature is in proportional band), set the Operating temperature
setpoint to its min value. The Amber LED should turn off.
3. Set the rear calibration potentiometer to the full ccw position.
4. When the throttle arm stops moving at Lo-Fire, turn the rear calibration
pot slowly cw until the arm just moves away from Lo-Fire.
5. When the motor stops, turn the pot ccw slowly until the motor starts to
move toward Lo-Fire.
6. Setup is complete. Remove power, set Band Temperature and Operating
temperature setpoints to desired operating settings.
-3-
15
Model 90200H/HT Microprocessor Temperature Controls — Data sheet
© Copyright 2009 — Carlin Combustion Technology, Inc.
Carlin part number MN90200HC Rev. 04/16/09
16
Specifications
•
•
24VAC
Carlin’s Model 90224 microprocessor-operated temperature controls are
available in two configurations, described below. Each model provides
one contact (either normally-open or normally-closed).
Refer to separate product listing sheets for pre-defined models, or request a control to meet your specifications, within the available ranges
listed below.
Microprocessor-operated
(Processor coordinates operation and diagnostic)
Easy remote sense
90224A
Temperature control
• 1 break-on-rise contact
• 1 electronic sensor
• lockout on diagnostic failure
• reset from lockout via power cycle
90224B
Temperature control
• 1 make-on-rise contact
• 1 electronic sensor
• lockout on diagnostic failure
• reset from lockout via power cycle
(Electronic sensor, wired to control)
Control model
Select from break-on-rise or
make-on-rise operation
A
Control power input (black-red wire)
Contacts
(action on temperature rise:)
1
1
(breaks)
(makes)
Contact rating
Self-checking program
(Control locks out on diagnostic failure)
Diagnostic/status LED’s
Wires
Quantity
Contact IN / OUT
Adjustable operating range
B
24 VAC, 1 VA
24 VAC, 1 AMP
2
2
black-red / black-yellow
Any range between 50°F to 240°F
Fixed differential (subtractive)
Any value from 5°F to 100°F
Operating temperature limits
+32°F to +140°F
Storage temperature limits
Agencies
(LED’s indicate power, call for heat, and lockout)
TECH SUPPORT 800-989-2275
–40°F to +185°F
UL & ULC recognized component
United States & Canada
carlincombustion.com
17
Model 90224 Microprocessor Temperature Controls — Data sheet — Operation & Dimensions
Model 90224 diagnostic LED’s
Configurations
GREEN
•
– OFF
– FLASH Slowly (every 3 seconds) Power on
– FLASH Rapidly (every second) Lockout
AMBER
– OFF
Operation
– ON Control call for heat
(See wiring diagrams below for wiring connections.)
•
•
Control kits — 90224 controls mount to a standard 4x4 J-box,
supplied with the control. Mount the box directly to a well (new or
existing) with hardware supplied, or panel mount. See below for
dimensions.
Well kits — Wells for 90224 sensors are available in the sizes shown
below. Well kits include sensor mounting hardware designed to hold
sensor securely in position.
Sensors — Sensors are available in single configurations.
Indicator LED’s
90224 controls have a green LED (power/lockout indicator) and
amber LED (operation indicator).
Power OFF With no power applied to black/red wire, all lights are off.
Power ON
When power is applied to the black/red wire, the green LED turns
on, flashing every 3 seconds.
Self-test
When power is applied, the 90224 performs a self-test, checking
the sensor and microprocessor. The power-up test lasts from 3
to 5 seconds.
The 90224 continues diagnostic checking during the operating
cycle as well. Any self-check failure causes a lockout (see below).
Call for heat When the temperature at the operating sensor is below setpoint
minus fixed differential, the 90224 break-on-rise contact is closed,
or the make-on-rise contact is open. The amber LED is on.
Stand-by
When the 90224 operating sensor reaches setpoint temperature
or above, the 90224 break-on-rise contact opens; or the makeon-rise contact closes. The amber LED turns off.
Lockout
If the control detects a diagnostic failure, lockout occurs. During
lockout, the green LED flashes every second.
After the temperature drops below setpoint minus differential,
reset the control by turning power off, then back on. The green
LED will flash more slowly, every 3 seconds.
Power must flow through the contacts in the direction shown. Changing
flow direction will cause the control to lockout or fail to operate.
The 90224 is polarity-sensitive with some controls. If the 90224 goes to
lockout on power up, disconnect power. Swap the wires coming to the
black/red and black/yellow lead wires. Restore power and restart.
© Copyright 2005 — Carlin Combustion Technology, Inc.
Carlin part number MN90224C Rev. 08/09/05
18
$ATASHEET
-ULTIPLESENSOROPTION
5SINGINDIVIDUALANDORDUALSENSORASSEMBLIES
3ENSOR2EDUNDANCY
(IGHERTEMPERATUREOFTWOOPERATINGSENSORSUSED
%ASYREMOTESENSE
3PECIlCATIONS
s
s
#ARLINS -ODEL MICROPROCESSOROPERATED MULTIPLECONTACT
TEMPERATURELIMITCONTROLSAREAVAILABLEASDESCRIBEDBELOW4HEMODEL
PROVIDESTWOCONTACTSˆONEFOROPERATINGLIMITANDONEFROMHIGH
LIMIT
2EFER TO SEPARATE PRODUCT LISTING SHEETS FOR PREDElNED MODELS OR
REQUEST A CONTROL TO MEET YOUR SPECIlCATIONS WITHIN THE AVAILABLE
RANGESLISTEDBELOW
%LECTRONICSENSORSWIREDTOCONTROL
3MARTMANUALRESET
-ANUALRESETONLYIFOPERATINGLIMITDOESNTOPEN
3ERVICEMANRESETPROTECTION
,ATCHUPAFTERTHREECONSECUTIVELOCKOUTS
0OWERINDEPENDENTLOCKOUT
0OWERCYCLINGWONTRESETFROMLOCKOUTORLATCHUP
$IAGNOSTIC,%$S
0OWERCALLFORHEATANDLOCKOUTLATCHUP
3-#4ECHNOLOGY
,ATCHUPMODESHUTSDOWNTHECONTROLAFTERTHREECONSECUTIVELOCKOUTSANDREQUIRES
ASPECIALPROCEDURETORESET4HISENSURESTHEOWNERWILLCALLINALICENSEDTECHNICIANTO
TROUBLESHOOTANDCORRECTBURNERPROBLEMS
4HEPROVIDESTWOLIMITRELAYS#ARLINSPATENTED3-#TECHNOLOGY3AFETY-ONITOR
ING#IRCUITMONITORSTHECONTACTSOFBOTHRELAYS,OCKOUTOCCURSIFALIMITRELAYCONTACTIS
FOUNDCLOSEDWHENITSHOULDBEOPEN
4%#(3500/24
CARLINCOMBUSTIONCOM
19
-ODEL-ICROPROCESSOR4EMPERATURE#ONTROLSˆ$ATASHEETˆ/PERATION$IMENSIONS
-ODELDIAGNOSTIC,%$S
'2%%.
n/&&
n/.0OWER
n&,!3().',ATCHUP
2%$
n/&&
n/.,OCKOUT
!-"%2
n/&&
n/.#ONTROLCALLFORHEAT
%LECTRICALSHOCKHAZARD$ISCONNECTPOWERTOAPPLIANCEWHENWIRINGOR
SERVICINGANYELECTRICALCOMPONENT
/PERATION
3EEWIRINGDIAGRAMSBELOWFORWIRINGCONNECTIONS
0OWER/&&
7ITHNOPOWERAPPLIEDTOTHEREDWHITEWIREALLLIGHTSAREOFF0OWERCANBEWIRED
DIRECTLYFROMAPPLIANCE6!#TERMINALTOMAINTAINPOWERATALLTIMES
0OWER/.
7HENPOWERISAPPLIEDTOTHEREDWHITEWIRETHEGREEN,%$TURNSON
3ELFTEST
7HENPOWERISAPPLIEDTHEPERFORMSASELFTESTCHECKINGSENSORSAND
MICROPROCESSORANDVERIFYINGLIMITCONTACTSAREOPEN4HEPOWERUPTESTLASTSFROM
TOSECONDS4HECONTINUESDIAGNOSTICCHECKINGDURINGTHEOPERATINGCYCLE
ASWELL!NYSELFCHECKFAILURECAUSESALOCKOUTSEEBELOW
/PERATE
)FTHETEMPERATUREATBOTHOPERATINGSENSORSISBELOWSETPOINTBYATLEASTTHElXED
DIFFERENTIALTHECONTROLCLOSESTHEOPERATINGLIMITCONTACTS4HEAMBER,%$TURNS
ON
3TANDBY
7HENEITHEROPERATINGSENSORSEESSETPOINTTEMPERATUREORABOVETHEOPENS
THEOPERATINGLIMITCONTACT4HEAMBER,%$TURNSOFF
,IMITACTION
)F THE HIGH LIMIT SENSOR SEES A TEMPERATURE ABOVE HIGH LIMIT SETTING THE OPENSTHEHIGHLIMITCONTACTSTURNSONTHERED,%$ANDCHECKSTHEOPERATINGLIMIT
CONTACTS)FTHEOPERATINGLIMITCONTACTSAREOPENTHECONTROLWILLAUTOMATICALLYRESET
WHENTEMPERATUREDROPSBELOWHIGHLIMITSETTINGMINUSDIFFERENTIAL4HEHIGHLIMIT
CONTACTSCLOSEANDTHERED,%$TURNSOFF
,OCKOUT
)FTHEHIGHLIMITSENSORSEESATEMPERATUREABOVEHIGHLIMITSETTINGANDTHE
lNDSTHEOPERATINGLIMITCONTACTSCLOSEDTHERED,%$TURNSONANDLOCKOUTOCCURS
,OCKOUTALSOOCCURSONANYDIAGNOSTICTESTFAILURE7HENTHETEMPERATUREDROPS
BELOWHIGHLIMITSETTINGMINUSDIFFERENTIALRESETTHECONTROLBYPRESSINGTHEMANUAL
RESETBUTTON4HECONTROLWILLNOTRESETBYCYCLINGPOWEROFFANDON
,ATCHUP
)F THE LOCKS OUT THREE CONSECUTIVE TIMES IT ENTERS LATCHUP 2ESET FROM
LATCHUPREQUIRESASPECIALPROCEDUREINTENDEDTOREQUIRELICENSEDSERVICEMAN
INTERVENTION$URINGLATCHUPTHERED,%$STAYSONANDTHEGREEN,%$mASHES
2ESETASFOLLOWS
4EMPERATUREMUSTBELESSTHANHIGHLIMITSETTINGMINUSDIFFERENTIAL
(OLDRESETBUTTONATLEASTSECONDS4HEGREEN,%$mASHESFASTER
#ONTINUEHOLDINGBUTTONANOTHERSECONDS4HECONTROLRESETSANDTHERED,%$
TURNSOFF
#ONlGURATIONS
s
s
s
#ONTROLKITSˆCONTROLSMOUNTTOASTANDARDX*BOX
SUPPLIEDWITHTHECONTROL-OUNTTHEBOXDIRECTLYTOAWELLNEW
OREXISTINGWITHHARDWARESUPPLIEDORPANELMOUNT3EEBELOW
FORDIMENSIONS
7ELLKITSˆ7ELLSFORSENSORSAREAVAILABLEINTHESIZES
SHOWNBELOW7ELLKITSINCLUDESENSORMOUNTINGHARDWAREDE
SIGNEDTOHOLDSENSORSECURELYINPOSITION
3ENSORSˆ3ENSORSAREAVAILABLEINSINGLEANDDUALCONlGURA
TIONS
0OWERMUSTmOWTHROUGHTHECONTACTSINTHEDIRECTIONSHOWN#HANGING
mOWDIRECTIONWILLCAUSETHECONTROLTOLOCKOUTORFAILTOOPERATE
¥#OPYRIGHTˆ#ARLIN#OMBUSTION4ECHNOLOGY)NC
9Whb_dfWhjdkcX[hCD/&)&&9H[l$&'%)'%&+
20
Data sheet
Multiple sensor option (3)
Specifications
•
(Using individual and/or dual sensor assemblies)
Sensor Redundancy
(Higher temperature of two operating sensors used)
•
Carlin’s Model 90320 microprocessor-operated, multiple-contact temperature limit controls are available as described below. The model provides two contacts — one for operating limit and one for high limit.
Refer to separate product listing sheets for pre-defined models, or request a control to meet your specifications, within the available ranges
listed below.
Easy remote sense
(Electronic sensors, wired to control)
Smart manual reset
90320B
(Manual reset only if operating limit doesn’t open)
Serviceman reset protection
(Latch-up after three consecutive lockouts (1))
Control model
Contacts
(Power cycling won’t reset from lockout or latch-up)
Contact rating
Diagnostic LED’s
Wires
(Power, call for heat, and lockout/latchup)
(1)
(2)
The 90320 provides two limit relays. Carlin’s patented SMC technology (Safety Monitoring
Circuit) monitors the contacts of both relays. Lockout occurs if a limit relay contact is found
closed when it should be open.
240 VAC, 50/60 hz, 12 VA
2 in series
Motor load
General
Quantity
240 VAC Hot / Neutral
Limits OUT
(2)
Latch-up mode shuts down the control after three consecutive lockouts, and requires a
special procedure to reset. This ensures the owner will call in a licensed technician to
troubleshoot and correct burner problems.
B
Control power input (red-white wire)
Power-independent lockout
SMC Technology
Dual limit temperature control
• operating and high limit action
• smart manual reset on high limit
• operating limit sensors, redundant
• high limit sensor
• operating and limit contacts in series
240 VAC, 50/60 hz, 1 HP
120/240 VAC, 50/60 hz, 15 AMPS
3
red-white / white
black
Adjustable oper. limit range
Any range between 50°F to 240°F
Fixed high limit temperature
Any value from 160°F to 240°F
Fixed differential (subtractive)
Any value from 5°F to 100°F
Operating temperature limits
+32°F to +140°F
Storage temperature limits
–40°F to +185°F
Agencies
TECH SUPPORT 800-989-2275
—
carlincombustion.com
21
Model 90320 Microprocessor Temperature Controls — Data sheet — Operation & Dimensions
Model 90320 diagnostic LED’s
GREEN
– OFF
– ON Power
RED
– OFF
– ON Lockout
AMBER
– OFF
– ON Control call for heat
Configurations
•
– FLASHING Latch-up
•
Electrical shock hazard: Disconnect power to appliance when wiring or
servicing any electrical component.
Operation
(See wiring diagrams below for wiring connections.)
Power OFF
With no power applied to the red-white wire, all lights are off. Power can be wired
directly from appliance 240 VAC terminal to maintain power at all times.
Power ON
When power is applied to the red-white wire, the green LED turns on.
Self-test
When power is applied, the 90320 performs a self-test, checking sensor(s) and
microprocessor and verifying limit contacts are open. The power-up test lasts from
3 to 5 seconds. The 90320 continues diagnostic checking during the operating cycle
as well. Any self-check failure causes a lockout (see below).
Operate
If the temperature at both operating sensors is below setpoint by at least the fixed
differential, the control closes the operating limit contacts. The amber LED turns
on.
Stand-by
When either operating sensor sees setpoint temperature or above, the 90320 opens
the operating limit contact. The amber LED turns off.
Limit action
If the high limit sensor sees a temperature above high limit setting, the 90320 opens
the high limit contacts, turns on the red LED and checks the operating limit contacts.
If the operating limit contacts are open, the control will automatically reset when
temperature drops below high limit setting minus differential. The high limit contacts
close and the red LED turns off.
Lockout
If the high limit sensor sees a temperature above high limit setting and the 90320
finds the operating limit contacts closed, the red LED turns on and lockout occurs.
(Lockout also occurs on any diagnostic test failure.) When the temperature drops
below high limit setting minus differential, reset the control by pressing the manual
reset button. The control will not reset by cycling power off and on.
Latch-up
If the 90320 locks out three consecutive times, it enters latch-up. Reset from latch-up
requires a special procedure, intended to require licensed serviceman intervention.
During latch-up, the red LED stays on and the green LED flashes. Reset as follows:
............
Temperature must be less than high limit setting minus differential.
............
Hold reset button at least 10 seconds. The green LED flashes faster.
............
Continue holding button another 20 seconds. The control resets and the red LED turns
off.
•
Control kits — 90320 controls mount to a standard 4x4 J-box,
supplied with the control. Mount the box directly to a well (new or
existing) with hardware supplied, or panel mount. See below for
dimensions.
Well kits — Wells for 90320 sensors are available in the sizes shown
below. Well kits include sensor mounting hardware designed to hold
sensor securely in position.
Sensors — Sensors are available in single and dual configurations.
Power must flow through the contacts in the direction shown. Changing
flow direction will cause the control to lockout or fail to operate.
90320B
G
G
White
240 VAC, 50/60 HZ
240 VAC, 50/60 HZ
CONNECTIONS AT APPLIANCE
POWER TO APPLIANCE
Appliance limits
Red/White
OPERATING LIMT
Service
switch
HIGH LIMIT
Dual limit OUT
Black
Sensor 2
To operating limit sensor #2
High limit
To high limit sensor
Sensor 1
To operating limit sensor # 1
© Copyright 2006 — Carlin Combustion Technology, Inc.
Carlin part number MN90320C Rev. 02/15/06
22
Data sheet
Functions
s Carlin’s 90524 triple limit control provides high limit function and can also
provide:
s Minimum water temperature control for operation with a tankless heater
in a boiler. (Function can be turned off by turning LOW LIMIT setting to
“OFF.”)
s Low temperature limit to prevent flow through boiler if temperature is
below preset minimum — for preventing condensation in conventional
boilers.
s Operates as a cold-start control when Low Limit is in “OFF” position.
s Provides input from zone controllers or relays and output to enable
circulators.
s Provides operation of burner/gas valve and heating circulator.
Specifications
Easy-wire terminal strip
Microprocessor-operated
(Processor coordinates operation and diagnostic)
Easy remote sense
(Electronic sensor, wired to control)
Self-checking program
(Control locks out on diagnostic failure)
Diagnostic/status LED’s
(LED’s indicate power, call for heat, and lockout)
SMC technology on burner
relay (lockout when welded contact sensed)
s Carlin’s Model 90524 microprocessor-operated temperature controls are
described below.
s Refer to separate product listing sheets for pre-defined models, or request
a control to meet your specifications, within the available ranges listed
below.
Model
90524A
Input power (L1-L2)
Control power (T-T)
High limit range
High limit differential
120 VAC, 10 VA, 60 Hz
24 VAC, 130 mA
Adjustable
Fixed if low limit is used or if differential
setpoint is OFF
Adjustable if low limit is turned OFF
Adjustable with OFF position
Adjustable (fixed if differential setpoint is
OFF)
Fixed
Fixed
Low limit range
Low limit differential
Low temp function
Low temp differential
Temperature ranges
Setting —
Differential —
Contact ratings
Full load
Locked rotor
Ambient temperature
Storage temperature
Agencies
Any value/range between 50° & 250°
Any value/range between 5°F and 100°F
Burner, circulator and ZC contacts
120 VAC, 10 amps (total current on all
contacts not to exceed 16 amps)
120 VAC, 60 amps (total current on all
contacts not to exceed 96 amps)
+32°F to +140°F (0°C to +60°C)
-40°F to +185°F (-40°C to +85°C)
UL Listed US and Canada
TECH SUPPORT 800-989-2275
carlincombustion.com
23
Model 90524 Microprocessor Temperature Controls — Data sheet
Figure 1
Equivalent circuit diagram (the 90524 controls power to the burner and circulators as in the simplified circuit below)
Model 90524 diagnostic LED’s
Configurations
LED’s
s Control kits — 90524 controls mount to a standard 4x4 J-box, supplied
with the control. Mount the box directly to a well (new or existing) with
hardware supplied, or panel mount. See Figure 2 for dimensions.
s Well kits — Wells for 90524 sensors are available in the sizes shown in
Figure 2. Well kits include sensor mounting hardware designed to hold
sensor securely in position.
s Sensors — Sensors are available in single configurations.
90524 controls have a green LED (power/lockout indicator) and amber LED’s
(operation indicator) for Burner and Circulator.
– OFF
GREEN
– ON Power on
– FLASH Slowly (once per second) Soft lockout
– FLASH Rapidly (twice per second) Hard lockout
AMBER
– OFF
– ON Burner on or Circulators powered
Figure 2
Mounting the 90524
LED indications
Power OFF — With no power applied, the thermostat (TT) circuit and all
output contacts are de-energized. All LED’s are off.
Power ON — When power is applied to the L1/L2 terminals, the thermostat
circuit is energized. Voltage (24 VAC) is applied to the thermostat terminals.
The 90524 starts a self test to check the sensor and the microprocessor,
and to verify that the limit contacts are open. The 90524 becomes fully
operational after this 2-second self test.
or
Soft lockout — Green light flashing once per second,
burner light off, burner contact open, and circulator light on or off — occurs
if control senses internal failure or sensor problem (open or shorted sensor).
The control will revert to normal operation if the problem is corrected within
15 seconds. Otherwise, the control enters hard lockout.
Hard lockout — Green light flashing twice per second, burner light off and
burner contacts open, circulator light on and circulator contacts closed —
occurs when burner contact is sensed closed, and does not clear after two
attempts. Reset by cycling power off/on.
Latchup — Green light off, burner light off, B1 contact open, circulator light
on, and ZC and C1 contacts closed — occurs when burner contact is sensed
closed, and does not clear after three attempts. Not resettable — requires
control replacement.
Fault log
90524 controls self monitor and indicate fault conditions with the LED’s. Fault conditions
are recorded in the retrievable fault log. For applications that might encounter unexplainable
control outages, contact Carlin Technical Support for instructions to access the fault log and
interpret the results.
© Copyright 2008 — Carlin Combustion Technology, Inc.
Carlin part number MN90524C Rev. 11/24/08
24
Instructions
Functions
F
Front
s Carlin’s 90524A can be operated as either a triple limit control or a cold-start
control, determined by the setting of the LOW LIMIT adjustment.
s Triple limit operation (LOW LIMIT on): Provides adjustable high limit setting and maintains an adjustable minimum temperature in the boiler (low
limit setting) while in stand-by (no space heating call); used for tankless
heater applications. (See Figure 3 , page 4.)
s Cold-start operation (LOW LIMIT off): Provides adjustable high limit setting and low temperature protection (delays circulator start until the boiler
is heated above the fixed minimum temperature setpoint); used to prevent
condensation in the boiler on cold start. (See Figure 4 , page 4.)
s The 90524A provides input from zone controllers or relays (ZR contact) and
output to enable circulators (C1 contact) or zone controllers (ZC contact).
The gas valve/burner output is on the B1 terminal. Call for heat input is on
the T-T terminals.
Specifications
Rear
s Carlin’s Model 90524A microprocessor-operated temperature controls are
described below.
s Refer to separate product listing sheets for pre-defined models, or request
a control to meet your specifications, within the available ranges listed
below.
(size reduced)
Easy-wire terminal strip
Microprocessor-operated
(Processor coordinates operation and diagnostic)
Easy remote sense
(Electronic sensor, wired to control)
Self-checking program
(Control locks out on diagnostic failure)
Diagnostic/status LED’s
(LED’s indicate power, call for heat, and lockout)
SMC technology on burner relay
Model
90524A
Input power (L1-L2)
Control power (T-T)
High limit range
High limit differential
120 VAC, 10 VA, 60 Hz
24 VAC, 130 mA
Adjustable
Adjustable (fixed if low limit is used or if
differential setpoint is OFF)
Adjustable with OFF position
Low limit range
Low limit differential
Low temp function
Low temp differential
Temperature ranges
Setting —
Differential —
Contact ratings
Full load
Locked rotor
Ambient temperature
Storage temperature
Agencies
Adjustable (fixed if differential setpoint is
OFF)
Fixed
Fixed
Any value/range between 50° & 250°
Any value/range between 5°F and 100°F
Burner, circulator and ZC contacts
120 VAC, 10 amps (total current on all
contacts not to exceed 16 amps)
120 VAC, 60 amps (total current on all
contacts not to exceed 96 amps)
+32°F to +140°F (0°C to +60°C)
-40°F to +185°F (-40°C to +85°C)
UL Listed US and Canada
(lockout when welded contact sensed)
TECH SUPPORT 800-989-2275
carlincombustion.com
25
Model 90524A Triple limit or cold-start control — Instructions
Where appliance instructions differ from this manual, follow the appliance instructions.
Figure 1
90524A components
1
2
Front
3
1
Green LED — POWER ON (Lockout, see
page 3)
2
Amber LED — CIRCULATOR ON
3
Amber LED — BURNER ON
4
Thermostat T-T input terminals
5
Terminal strip (back of control)
6
Sensor terminal strip (quick-release style)
7
Differential adjustment (adjusts High Limit
differential when in cold-start operation;
adjusts Low Limit differential when in triple
limit operation) — when in OFF position,
default high and low limit differentials are
used
8
Hidden reset button
9
Low limit adjustment (set to OFF for coldstart operation)
10
High limit setpoint adjustment
4
Rear
10
7
9
8
6
5
–2–
Carlin
C
li partt number
b MN90524AM R
Rev. 01/19/09
26
Model 90524A Triple limit or cold-start control — Instructions
Where appliance instructions differ from this manual, follow the appliance instructions.
Configurations
Model 90524A diagnostic LED’s
s Control kits — 90524A controls mount to a standard 4x4 J-box, supplied
with the control. Mount the box directly to a well (new or existing) with
hardware supplied, or panel mount. See Figure 2 for dimensions.
s Well kits — Wells for 90524A sensors are available in the sizes shown
in Figure 2. Well kits include sensor mounting hardware designed to
hold sensor securely in position.
s Sensors — Sensors are available in single configurations.
90524A controls have three LED’s, as explained below. See following pages for operating
sequence and LED behavior.
Figure 2
Mounting the 90524A
Left LED
POWER ON
Center LED
CIRCULATOR ON
green
Right LED
BURNER ON
amber
amber
The LED’s can be off, on or flashing. The symbols below are used in this manual to show
the state of these LED’s during operation of the control.
Green LED
OFF
– ON Power on
FLASH Slowly (once per second) Soft lockout
FLASH Rapidly (twice per second) Hard lockout
Amber LED’s
;
OFF
– ON Burner on or Circulators powered
Indicates the LED in this position can be either on or off.
LED status
Indicates the following:
Power OFF
With no power applied, the thermostat (TT) circuit and all output contacts are de-energized. All LED’s are off.
Power ON
;
Soft lockout
When power is applied to the L1/L2 terminals, the thermostat circuit is
energized. Voltage (24 VAC) is applied to the thermostat terminals. The
90524A starts a self test to check the sensor and the microprocessor,
and to verify that the limit contacts are open. The 90524A becomes
fully operational after this 2-second self test.
Green LED flashing once per second, burner LED off, B1 contact open,
and circulator LED on or off — occurs if control senses internal failure
or sensor problem (open or shorted sensor).
The control will revert to normal operation if the problem is corrected
within 15 seconds. Otherwise, the control enters hard lockout. See
“Fault log” information below.
Green LED flashing twice per second, burner LED off and B1 contacts
open, circulator LED on and circulator contacts closed — occurs when
burner contact is sensed closed, and does not clear after two attempts
Hard lockout or soft lockout has timed out.
Reset by cycling power off/on.
Latchup
Green LED off, burner LED off, B1 contact open, circulator LED on, and
ZC and C1 contacts closed — occurs when burner contact is sensed
closed, and does not clear after three attempts.
Not resettable — requires control replacement.
Definitions
90524A controls self monitor, and can indicate fault conditions with
the LED’s.
High limit Shut-off temperature during space heating (call for heat at
T-T or ZR).
s Setpoint is adjustable at lower front center of control.
s Differential is fixed when in triple limit operation (LOW
LIMIT on).
s Differential is adjustable on back of control when in cold
start operation (LOW LIMIT set to OFF).
Low limit Temperature maintained during stand-by (no call for heat
at T-T or ZR) when in triple limit operation (LOW LIMIT on).
s The setpoint for the low limit (minimum temperature in
the boiler during standby) is adjustable with the lower
left adjustment.
s The differential for low limit is adjustable with the adjustment on the back of the control.
s The circulator output at C1 is activated only when
the temperature in the boiler is above the low limit
setting.
Low temp Boiler condensation protection setting when in cold-start
operation (LOW LIMIT set to OFF).
s This setting is fixed.
s The differential is fixed.
s The circulator outputs are disabled until the boiler temperature rises above the low temp setting.
Carlin part number MN90524AM Rev. 01/19/09
Fault conditions are recorded in the retrievable fault log. Two conditions, caused by sensor detection problems, are shown below. Other
LED conditions displayed in the fault log are related to internal control
problems. Reset the control as explained above. Controls in latchup
cannot be reset. They must be replaced.
Fault
log
To access the fault log, press the hidden reset button (located left of
the LOW LIMIT adjustment on the front of the control). Hold for one
second or longer. All three LED’s will come on for 1 second, then go off
for 1 second. If any error codes have been logged since the last error
code display, the LED’s will flash a pattern four times for each error
code, then proceed to the next. After all codes have been shown, the
error code log will automatically clear.
For applications that might encounter unexplainable control outages,
contact Carlin Technical Support for instructions to access the fault log
and interpret the results.
Sensor OPEN fault code.
Sensor open
The sensor is detected OPEN (resistance more than 60 Kohms).
Sensor SHORTED fault code.
Sensor shorted The sensor is detected SHORTED (resistance less than 300 ohms).
–3–
27
Model 90524A Triple limit or cold-start control — Instructions
Where appliance instructions differ from this manual, follow the appliance instructions.
Figure 3
Equivalent circuit diagram — Triple limit operation (LOW LIMIT on)
Triple limit operation — Setup & adjustment
;
s Set low limit setpoint on front of control (item 9, page 2). Set low limit differential
at the adjustment potentiometer on the back of the control (item 7, page 2). The
differential range is shown on the control label. Rotate the potentiometer fully
counterclockwise for minimum setting, fully clockwise for maximum setting.
s Set high limit setpoint on front of control (item 10, page 2). High limit differential
is fixed.
Triple limit sequence of operation
;
Figure 4
Burner turns ON when sensor temp is below the high limit (minus
high limit differential) — AND — sensor temp is below low limit
setting (minus low limit differential) OR there is a call for heat at
T-T or ZR.
;
;
;;
;;
Burner turns OFF when sensor temp is above high limit setting —
OR — when sensor temp is above the low limit AND there is no
call for heat at T-T or ZR.
Circulator turns ON when sensor temp is at or above low limit —
AND — there is a call for heat at T-T.
Circulator turns OFF when the sensor temp goes below the low
limit setting (minus the low limit differential) — OR — there is no
call for heat at T-T.
Zone feed (terminal ZC) turns ON when sensor temp is at or above
the low limit.
Zone feed (terminal ZC) turn OFF when sensor temp goes below
the low limit setting (minus the low limit differential).
Equivalent circuit diagram — Cold-start operation (LOW LIMIT set to OFF)
Cold-start operation — Setup & adjustment
;
Burner turns OFF when sensor temp is above high limit setting —
OR — there is no call for heat at T-T or ZR.
s Set low limit adjust on front of control to OFF (item 9, page 2). This activates the
low temp setting. Low temp and its differential are fixed settings.
;
s Set high limit setpoint on front of control (item 10, page 2). Set high limit differential
at the adjustment potentiometer on back of the control (item 7, page 2).
Circulator turns ON when sensor temp is at or above low temp —
AND — there is a call for heat at T-T.
;
Circulator turns OFF when the sensor temp goes below the low
temp setting (minus the low temp differential) — OR — there is
no call for heat at T-T.
;;
Zone feed (terminal ZC) turns ON when sensor temp is at or above
the low temp.
;;
Zone feed (terminal ZC) turn OFF when sensor temp goes below
the low temp setting (minus the low temp differential).
Cold start sequence of operation
;
–4–
Burner turns ON when sensor temp is below the high limit (minus
high limit differential) — AND — there is a call for heat at T-T or
ZR.
Carlin part number MN90524AM Rev. 01/19/09
28
Model 90524A Triple limit or cold-start control — Instructions
Where appliance instructions differ from this manual, follow the appliance instructions.
Figure 5
Typical — Triple limit operation (LOW LIMIT ON) — Multi-zone controller, zoning with zone valves
Carlin part number MN90524AM Rev. 01/19/09
–5–
29
Model 90524A Triple limit or cold-start control — Instructions
Where appliance instructions differ from this manual, follow the appliance instructions.
Figure 6
–6–
Typical — Triple limit operation (LOW LIMIT ON) — Multi-zone controller, zoning with circulators
Carlin part number MN90524AM Rev. 01/19/09
30
Model 90524A Triple limit or cold-start control — Instructions
Where appliance instructions differ from this manual, follow the appliance instructions.
Figure 7
Typical — Cold-start operation (LOW LIMIT OFF) — Delays circulator until boiler has heated above LOW TEMP setting
Carlin part number MN90524AM Rev. 01/19/09
–7–
31
Model 90524A Microprocessor Temperature Controls — Data sheet
© Copyright 2008 — Carlin Combustion Technology, Inc.
Carlin part number MN90524AM Rev. 01/19/09
32
EZ-Temp™
Model
99000A
On-Off Mode of Operation
Data sheet
Specifications
s The EZ-Temp Commercial Boiler Package controls are
provided as an assembled package. Pre-assembled
and pre-wired operating limit and manual reset high limit
temperature controls for commercial boilers and similar
applications. Includes EZ-Temp model 90200EL manual
reset high limit temperature control and EZ-Temp model
90200AL operating temperature limit control, mounted and wired on a two-gang J-box with terminal strips,
one dual sensor, 3/4” immersion well (1.55” length) and
mounting hardware.
s Model 90200AL and 90200EL microprocessor-operated
temperature controls are UL Listed. The 90200AL provides a single contact (break-on-rise) and the 90200EL
provides a single contact (break-on-rise) with a manual
reset.
s The 90200A and 90200E are UL Recognized and may be
purchased separately for replacement.
Microprocessor-operated
90200AL
Temperature limit control
6 .#(,+.'/#!,+0!0
6#)#!0.,+'!/#+/,.
6,!(,10,+"'%+,/0'!$')1.#
6#/#0$.,*),!(,102'-,3#.!4!)#
90200EL
Manual reset high limit control
6 .#(,+.'/#!,+0!0
6#)#!0.,+'!/#+/,.
6,!(,10,+"'%+,/0'!$')1.#+")'*'0
!0',+
6+1).#/#0$.,*),!(,10
6,.#/#0$.,*-,3#.'+0#..1-0',+
(Processor coordinates limit and diagnostic functions)
Easy Remote Sense
(Electronic sensors, wired to control)
Break-on-Rise Operation
Self-checking Program
Control model
AL
Contacts
!0',+,+0#*-#.01.#.'/#
Contact Rating
(Control locks out on diagnostic failure)
.#(,+.'/#
.#(,+.'/#
VAC
Full load
VAC
Locked rotor
Quantity
Wires
EL
VAC
Power input
3
3
120 VAC#10.)
&'0#
120 VAC,0,.
'*'0
#"&'0#
Break-on-rise
OUT
)!(
Diagnostic/status LED’s
Adjustable operating limit
range
(LED’s indicate “Power”, “Call for Heat”, and “Lockout”)
Fixed differential (subtractive)
+42)1#$.,*70,7
Operating temperature limits
70,7
Storage temperature limits
Agencies
TECH SUPPORT 800-989-2275
70,
7
70,
7
570,7
+"'2'"1)!,+0.,)/.#Listed
$,.+'0#"00#/+"
carlincombustion.com
33
Model 99000A Commercial Boiler Control Package for On-Off Mode — Data Sheet
Model 90200AL diagnostic LED’s
GREEN
– OFF
– ON Power
AMBER
– OFF
– ON Control call for heat
Dimensions
– FLASHING Lockout
4.12”
Model 90200EL diagnostic LED’s
GREEN
– OFF
– ON Power
RED
– OFF
– ON Lockout
– FLASHING Lockout Pending
Electrical shock hazard: Disconnect power to appliance
when wiring or servicing any electrical component.
Operation (See wiring diagrams for connections)
Power Indicator
When power is applied to unit, the green LED
is turned ON.
Lockout Pending
90200EL: If a diagnostic failure occurs or
the sensor temperature rises above the high
limit setting, the green LED will flash for 5
seconds. If the conditiion still exists after 5
seconds, the control will enter lockout requiring manual reset. The red LED turns ON
and the limit contact opens. (If the condition
corrects before 5 seconds, the green LED
will return to normal).
Lockout Indicator
Lockout Indicator
90200AL: When a diagnostic failure occurs,
the LED blinks and the contact opens. The
control will reset when the failure is removed
and power is cycled.
Call for Heat
90200AL: When the temperature at the
sensor is at or below set point minus fixed
differential, the control powers the limit
relay (break-on-rise contact closes). The
Amber LED turns ON. When temperature
is at or above set point, the contact opens.
2.12”
6.75”
J-Box
Terminal Strip
90200EL
EZ-Temp
SENSOR
INPUT
S
S1
S
S1
S1
DOUBLE
S2
SENSOR
Sensor Well: Located on JBox back center knockout.
5.25”
** Conduit connection.
Locate at any knockout.
90200AL
**
J-Box
Terminal Strip
EZ-Temp
SENSOR
INPUT
TO BURNER PRIMARY CONTROL
L2
(BREAK ON TEMPERATURE RISE).
To Wht
B2
To Blk
B1
To Red / Wht
BL1
120 VAC NEUTRAL OUT.
120 VAC LIMIT OUT.
120 VAC FEED OUT. (IF NEEDED)
L1
S
S2
S
S2
N
H
LWCO Limit, if used
SERVICE
SWITCH
TECH
SUPPORT
120 Vac Power
to Appliance
G
HOTLINE
800-989-2275
Carlin Combustion Technology, Inc.
70 Maple Street
e-mail us at:
© Copyright 2010 — Carlin Combustion Technology, Inc.
East Longmeadow, MA 01028
[email protected]
Phone 413–525–7700
Fax 413–525–8306
vist our website: www.carlincombustion.com
Carlin part number MN99000AC Rev. 01/27/10
34
EZ-Temp™
Model
99000B
Lo-Hi-Lo Mode of Operation
Data sheet
Specifications
s The EZ-Temp Commercial Boiler Package controls are
provided as an assembled package. Pre-assembled and
pre-wired operating limit, manual reset high limit temperature and two position step modulating controls for
commercial boilers and similar applications. Includes
EZ-Temp model 90200AL operating temperature limit
control, EZ-Temp model 90200EL manual reset high limit
temperature control, and EZ-Temp model 90200GL two
position step modulating Lo-Hi-Lo temperature control,
mounted and wired on a three-gang J-box with terminal
strips, one triple sensor, 3/4” immersion well (1.55” length)
and mounting hardware.
s Carlin’s model 90200AL, 90200EL, and 90200GL microprocessor-operated temperature controls are UL Listed.
Each control provides a single contact (break-on-rise).
Microprocessor-operated
(Processor coordinates limit and diagnostic functions)
90200AL
Operating limit control
8
"0%!*.-0)1%#.-2!#2
8
%+%#20.-)#1%-1.0
8.#*.32.-$)!'-.12)#&!)+30%
8%1%2&0.,+.#*.324)!/.5%0#6#+%
90200EL
Manual reset high limit control
8
"0%!*.-0)1%#.-2!#2
8
%+%#20.-)#1%-1.0
8.#*.32.-$)!'-.12)#&!)+30%!-$+),)2!#2).8!-3!+0%1%2&0.,+.#*.32
8.0%1%2&0.,/.5%0)-2%003/2).-
90200GL
Two position step modulating Lo-Hi-Lo control
8
"0%!*.-0)1%#.-2!#2
8
%+%#20.-)#1%-1.0
8.#*.32.-$)!'-.12)#&!)+30%
8%1%2&0.,+.#*.324)!/.5%0#6#+%
Easy Remote Sense
(Electronic sensors, wired to control)
Break-on-Rise Operation
Self-checking Program
(Control locks out on diagnostic failure)
Control model
Contacts
Diagnostic/status LED’s
AL
EL
!#2).-.-2%,/%0!230%0)1%
Contact Rating
(LED’s indicate “Power”, “Call for Heat”, and “Lockout”)
"0%!*.-0)1%
"0%!*.-0)1%
VAC
Locked rotor
3
3
120 VAC%320!+
%$ ()2%
Break-on-rise
OUT
+!#*
Modulating IN
4
()2%
120 VAC.2.0
),)2
Adjustable operating limit
range
"0%!*.-0)1%
VAC
Full load
Quantity
Wires
GL
VAC
Power input
92.9
Fixed differential (subtractive)
+!#*0%%-
92.9
92.9
-64!+3%&0.,92.
9
Operating temperature limits
92.
9
Storage temperature limits
792.
9
Agencies
TECH SUPPORT 800-989-2275
-$)4)$3!+#.-20.+1!0%Listed
&.0-)2%$2!2%1!-!$!
carlincombustion.com
35
Model 99000B Commercial Boiler Control Package for Lo-Hi-Lo Mode — Data Sheet
Model 90200AL diagnostic LED’s
– OFF
– ON Power
AMBER
– OFF
– ON Control call for heat
**
– FLASHING Lockout
Model 90200EL diagnostic LED’s
GREEN
– OFF
– ON Power
RED
– OFF
– ON Lockout
– FLASHING Lockout Pending
EZ-Temp
SENSOR
INPUT
– ON Power
– OFF
– ON Low Fire Calling
AMBER
– OFF
B1
BL1
To Red / Wht
120 VAC NEUTRAL OUT.
120 VAC LIMIT OUT.
120 VAC FEED OUT. (IF NEEDED)
L1
N
S
S2
H
S
S2
SERVICE
SWITCH
120 Vac Power
to Appliance
G
90200EU
– FLASHING Lockout
– ON High Fire Calling
Electrical shock hazard: Disconnect power to appliance
when wiring or servicing any electrical component.
EZ-Temp
SENSOR
INPUT
S2
S1
S3
S
S1
S
S1
TRIPLE
SENSOR
Sensor Well: Located on JBox back center knockout.
90200GU
Operation (See wiring diagrams for connections)
When power is applied to unit, the green LED
is turned ON.
Lockout Pending
90200EL: If a diagnostic failure occurs or
the sensor temperature rises above the high
limit setting, the green LED will flash for 5
seconds. If the conditiion still exists after 5
seconds, the control will enter lockout requiring manual reset. (If the condition corrects
before 5 seconds, the green LED will return
to normal).
Lockout Indicator
90200AL and 90200GL: When a diagnostic
failure occurs, the LED blinks and the contact
opens. The control will reset when the failure
is removed and power is cycled.
Call for Heat
When the temperature at the sensor is below
set point minus fixed differential, the control
powers the limit relay (break-on-rise contact
closes). On the 90200GL, the High Fire
LED turns ON and the Low Fire LED turns
OFF. On the 90200AL, the Amber LED turns
ON. When temperature is at or above set
point, the contact opens. On the 90200GL,
the High Fire LED is turned OFF and the Low
Fire LED is turned ON. On the 90200AL, the
Amber LED turns OFF.
EZ-Temp
SENSOR
INPUT
S
S3
S
S3
J-Box
Terminal Strip
Power Indicator
Lockout Indicator
To Blk
LWCO Limit, if used
J-Box
Terminal Strip
– OFF
AMBER
(BREAK ON TEMPERATURE RISE).
To Wht
B2
Model 90200GL diagnostic LED’s
GREEN
TO BURNER PRIMARY CONTROL
L2
J-Box
Terminal Strip
GREEN
90200AU
** Conduit connection.
Locate at any knockout.
**
Load Out
LFOUT
LFIN
Feed In
DRY CONTACT FOR
LOW-FIRE ACTUATOR
CONTROL.
(CONTACT BREAKS ON
TEMPERATURE RISE).
Dimensions
4.12”
6.75”
TECH
5.25”
6.75”
SUPPORT
HOTLINE
800-989-2275
Carlin Combustion Technology, Inc.
70 Maple Street
e-mail us at:
© Copyright 2010 — Carlin Combustion Technology, Inc.
East Longmeadow, MA 01028
[email protected]
Phone 413–525–7700
Fax 413–525–8306
vist our website: www.carlincombustion.com
Carlin part number MN99000BC Rev. 01/27/10
36
EZ-Temp™
Model
99000C
Lo-Hi-Lo Mode of Operation
Data sheet
Specifications
s The EZ-Temp Commercial Boiler Package controls are
provided as an assembled package. Pre-assembled and
pre-wired operating limit and manual reset high limit and
two positon step modulating control for commercial boilers and similar applications. Includes EZ-Temp model
90000CEL combination operating limit and manual reset
high limit and EZ-Temp model 90200GL two position step
modulating Lo-Hi-Lo temperature controls, mounted and
wired on a two-gang J-box with terminal strips, one triple
sensor, 3/4” immersion well (1.55” length) and mounting
hardware.
s Model 90000CEL and 90200GL microprocessor-operated
temperature controls are UL Listed. The 90000CEL provides 2 contacts (break-on-rise) and the 90200GL provides a single contact (break-on-rise).
s The 90000CE and 90200G are UL Recognized and may
be purchased separately for replacement.
90000CEL
Microprocessor-operated
(Processor coordinates limit and diagnostic functions)
90200GL
Easy Remote Sense
(Electronic sensors, wired to control)
Two position step modulating
Lo-Hi-Lo control
8
"0%!*.-0)1%#.-2!#2
8
%+%#20.-)#1%-1.0
8.#*.32.-$)!'-.12)#&!)+30%
8%1%2&0.,+.#*.324)!/.5%0#6#+%
Control model
CEL
!#2).-.-2%,/%0!230%0)1%
Contact Rating
"0%!*.-0)1%
"0%!*.-0)1%
VAC
Full load
VAC
Locked rotor
Quantity
3
4
120 VAC%320!+
Self-checking Program
(Control locks out on diagnostic failure)
GL
VAC
Power input
Contacts
Break-on-Rise Operation
Combination operating limit and
manual reset high limit control
8"0%!*.-0)1%#.-2!#21
8%+%#20.-)#1%-1.01
8.#*.32.-$)!'-.12)#&!)+30%!-$+),)2
!#2).8!-3!+0%1%2&0.,()'(+),)2+.#*.32
8.0%1%2&0.,/.5%0)-2%003/2).8)'(+),)22%12&3-#2).-
Wires
()2%
120 VAC.2
),)2
%$ ()2%
Break-on-rise
OUT
+!#*
Diagnostic/status LED’s
+!#*0%%-
Adjustable operating limit range
92.9
92.9
(LED’s indicate “Power On”, “Call for Heat”, “Lockout”,
“High fire Calling” and “Low Fire Calling”)
Fixed high limit range
92.9
.-%
Fixed differentials (subtractive)
Modulating IN
Operating temperature limits
Storage temperature limits
Agencies
TECH SUPPORT 800-989-2275
-64!+3%&0.,92.
9
92.
9
792.
9
-$)4)$3!+#.-20.+1!0%Listed
&.0-)2%$2!2%1!-!$!
carlincombustion.com
37
Model 99000C Commercial Boiler Control Package for On-Off Mode — Data Sheet
Model 90000CEL diagnostic LED’s
GREEN
– OFF
– ON Power
RED
– OFF
– ON Lockout
– OFF
– FLASHING (Fast) Hi-Test
– ON Call for Heat
Model 90200GL diagnostic LED’s
GREEN
– OFF
– ON Power
AMBER
– OFF
– ON Low Fire Calling
AMBER
– OFF
N
SERVICE SWITCH
90000CEU
– FLASHING Lockout
EZ-Temp
SENSOR
INPUT
– ON High Fire Calling
**
L2
J-Box
Terminal Strip
AMBER
– FLASHING (Slow) Latch-up
TO BURNER PRIMARY CONTROL
(BREAK ON TEMPERATURE RISE).
To Wht
B2
LWCO Limit, if used
B1
BL1
To Blk
To Red / Wht
H
G
120 VAC NEUTRAL OUT.
120 VAC LIMIT OUT.
120 VAC FEED OUT. (IF NEEDED)
L1
S2
S2
S
S1/S2
S1
S1
S2
S1
S3
TRIPLE
SENSOR
Sensor Well: Located on JBox back center knockout.
90200GU
Electrical shock hazard: Disconnect power to appliance
when wiring or servicing any electrical component.
Power On
When power is applied to unit, the green LED turns ON.
Lockout
90000CEL: When the temperature at the High-Limit sensor
reaches the High-Limit set point or a diagnostic fault occurs,
the control goes into Lockout. The red LED turns ON and both
contacts open. The control will automatically reset when all
diagnostic faults are removed. Manual reset is required to resume operation after an over temperature High-Limit Lockout.
Lockout
90200GL: When a diagnostic fault occurs, the control goes into
Lockout. The green LED starts flashing and the contact opens
putting the control into Low Fire. The control will automatically
reset when all faults are removed.
Call for Heat
90000CEL: When the temperature at the Operating-Limit sensor
is below the Operating-Limit set point minus the fixed differential, the control powers the operating relay and it’s break-onrise contact closes. The Amber “Call for Heat” LED turns ON.
J-Box
Terminal Strip
EZ-Temp
SENSOR
INPUT
Operation (See wiring diagrams for connections)
S
S3
S
S3
**
Load Out
LFOUT
LFIN
Feed In
DRY CONTACT FOR
LOW-FIRE ACTUATOR
CONTROL.
(CONTACT BREAKS ON
TEMPERATURE RISE).
** Conduit connection.
Locate at any knockout.
Dimensions
4.12”
When the temperature is above the set point, the contact opens
and the Amber LED Turns OFF.
High-Fire Calling 90200GL: When the temperature at the sensor is below the
Low-Fire Calling Low-Fire set point minus the fixed differential, the control powers the relay and the break-on-rise contact closes. The Amber
High-Fire Calling LED turns ON and the Amber Low-Fire Calling
LED turns OFF.
High-Fire Calling When the temperature is above the set point, the contact opens.
Low-Fire Calling The Amber High-Fire Calling LED turns OFF and the Amber Low
Fire Calling LED turns ON.
Latch-up
(90000CEL)
If the 90000CEL locks out three consecutive times, it enters
latch-up. Reset from latch-up requires a special procedure,
intended to require licensed serviceman intervention. During
latch-up, the red LED stays on and the green LED slow flashes.
Reset as follows:
2.12”
After boiler is less than high limit setting minus differential:
. . . . . . . . . . . . Hold reset button at least 10 seconds. The green LED flashes
faster.
. . . . . . . . . . . . Continue holding button another 20 seconds. The control resets
and the red LED turns off.
6.75”
High Limit Test “Hi-Test” mode (90000CEL ONLY), used to test “High Limit Reset” at operating boiler temperature. Start test with system operational and calling for heat. Turn setpoint full clockwise to HiTest position. Green LED flashes fast. The setpoint now adjusts
both the high and operating limits. Turn setpoint slowly counter
clockwise until Lockout occurs. Now the setpoint temperature
equals the hi-limit sensor temperature. Test is complete, adjust
setpoint to the desired operating limit. Remove from lockout.
TECH
SUPPORT
HOTLINE
5.25”
800-989-2275
Carlin Combustion Technology, Inc.
70 Maple Street
e-mail us at:
© Copyright 2010 — Carlin Combustion Technology, Inc.
East Longmeadow, MA 01028
[email protected]
Phone 413–525–7700
Fax 413–525–8306
vist our website: www.carlincombustion.com
Carlin part number MN99000CC Rev. 01/27/10
120 Vac Power
to Appliance
38
EZ-Temp™
Model
99000D
Proportional Mode of Operation
Data sheet
Specifications
s The EZ-Temp Commercial Boiler Package controls are
provided as an assembled package. Pre-assembled and
pre-wired operating limit, manual reset high limit temperap
ture and proportional control for commercial boilers and
tu
ssimilar applications. Includes EZ-Temp model 90200AL
operating temperature limit control, EZ-Temp model
o
90200EL manual reset high limit temperature control, and
9
EZ-Temp model 90200HL proprotional control, mounted
E
and wired on a three-gang J-box with terminal strips,
a
one triple sensor, 3/4” immersion well (1.55” length) and
o
mounting hardware.
m
s Carlin’s model 90200AL, 90200EL, and 90200HL microprocessor-operated temperature controls are described
below. The 90200AL and 90200EL each provide a single
contact (break-on-rise). The 90200HL provides a proportional modulating control output.
90200AL
Temperature limit control
8
"0%!*.-0)1%#.-2!#2
8
%+%#20.-)#1%-1.0
8.#*.32.-$)!'-.12)#&!)+30%
8%1%2&0.,+.#*.324)!/.5%0#6#+%
90200EL
Manual reset high limit control
8
"0%!*.-0)1%#.-2!#2
8
%+%#20.-)#1%-1.0
8.#*.32.-$)!'-.12)#&!)+30%!-$+),)2!#2).8!-3!+0%1%2&0.,+.#*.32
8.0%1%2&0.,/.5%0)-2%003/2).-
90200HL
Proportional modulating control
8
%+%#20.-)#1%-1.0
8.#*.32.-$)!'-.12)#&!)+30%
832.0%1%2&0.,+.#*.325(%-&!3+20%,.4%$
Microprocessor-operated
(Processor coordinates limit and diagnostic functions)
Easy Remote Sense
(Electronic sensors, wired to control)
Break-on-Rise Operation
Control model
AL
EL
Self-checking Program
Contacts
(Control locks out on diagnostic failure)
Contact Rating
"0%!*.-0)1%
!#2).-.-2%,/%0!230%0)1%
(LED’s indicate “Power”, “Call for Heat”, and “Lockout”)
Wires
.-%
Full load
Locked rotor
Quantity
Diagnostic/status LED’s
HL
Power input
3
3
120 %320!+
()2%
120 .2
),)2
%$()2%
Break-on-rise
OUT
5
+!#*
%++.5()2%
Low Fire
Common
%++.5%$
High Fire
%++.5+!#*
Adjustable operating limit range
92.9
Fixed differential (subtractive)
92.9
92.9
92.
9
-64!+3%&0.,92.
9
92.9
Operating zone limits
Operating temperature limits
Storage temperature limits
Agencies
TECH SUPPORT 800-989-2275
92.
9
792.
9
-$)4)$3!+#.-20.+1!0%Listed
&.0-)2%$2!2%1!-!$!
carlincombustion.com
39
Model 99000D Commercial Boiler Control Package for Lo-Hi-Lo Mode — Data Sheet
Model 90200AL diagnostic LED’s
GREEN
– OFF
– ON Power
– FLASHING Lockout
AMBER
– OFF
– ON Control Call for heat
90200A
**
TO BURNER PRIMARY CONTROL
J-Box
Terminal Strip
L2
Model 90200EL diagnostic LED’s
GREEN
RED
– OFF
– OFF
– ON Power
– FLASHING Lockout Pending
– ON Lockout
LWCO Limit, if used
B1
BL1
S
EZ-Temp
SENSOR
INPUT
To White
B2
S
To Black
To Red / White
(BREAK ON TEMPERATURE RISE).
120 VAC NEUTRAL OUT.
120 VAC LIMIT OUT.
120 VAC FEED OUT. (IF NEEDED)
L1
N
S2
H
SERVICE
SWITCH
S2
120 Vac Power
to Appliance
G
Model 90200HL diagnostic LED’s
– OFF
– ON Power
– FLASHING Lockout
AMBER
– OFF Low Fire
– ON High Fire
– FLASHING % High Fire
J-Box
Terminal Strip
90200E
GREEN
Electrical shock hazard: Disconnect power to appliance
when wiring or servicing any electrical component.
EZ-Temp
SENSOR
INPUT
Power
When power is applied to unit, the green LED
is turned ON.
Lockout
90200EL: If a diagnostic failure occurs or the
sensor temperature rises above the limit setting, the green LED will flash for 5 seconds.
If the conditiion still exists after 5 seconds,
the control will enter lockout. (If the condition
corrects before 5 seconds, the green LED
will return to normal).
Lockout
90200EL: When the sensor temperature
reaches the limit set point or a diagnostic
failure occurs, the LED turns ON and the contact opens. Manual reset required to resume
operation. If lockout was from a diagnostic
failure, the control will reset automatically
when failure is removed.
Lockout
When a diagnostic fault occurs, the control
goes into Lockout and the green LED starts
flashing. On the 90200AL, the contact
opens. On the 90200HL, the output goes to
full Low Fire. Either control will automatically
reset when all faults are removed from it.
Call for Heat
90200AL: When the temperature at the sensor is below set point minus fixed differential,
the control powers the limit relay (break-onrise contact closes). The Amber LED turns
ON. When temperature is at or above set
point, the contact opens. The Amber LED
turns OFF.
High Fire
90200HL: When the temperature is at or
below the operating temperature minus 1/2
the zone temperature, the control is requesting High Fire and the LED is ON. When the
temperature is at or above the operating temperature plus 1/2 the zone temperature, the
control is requesting Low Fire and the LED is
OFF. In between the control modulates the
motor to a position proportional to the sensor
temperature. The LED blinks with an ON
time proportional to this position.
Low Fire
S
S1
S
S1
TRIPLE
SENSOR
Sensor Well: Located on
J-Box back center
90200H
EZ-Temp
SENSOR
INPUT
J-Box
Terminal Strip
Operation (See wiring diagrams for connections)
S2
S1
S3
S
S3
S
S3
** Conduit connection.
Locate at any knockout.
OUTPUT TO 135 PROPORTIONAL
ACTUATOR
**
Wht
To White lead
Red
To Red lead
Blk
To Black lead
SUPPORT
WIPER COMMON
HIGH FIRE
Dimensions
5.25”
4.12”
6.75”
TECH
LOW FIRE
HOTLINE
6.75”
800-989-2275
Carlin Combustion Technology, Inc.
70 Maple Street
e-mail us at:
© Copyright 2010 — Carlin Combustion Technology, Inc.
East Longmeadow, MA 01028
[email protected]
Phone 413–525–7700
Fax 413–525–8306
vist our website: www.carlincombustion.com
Carlin part number MN99000DC Rev. 01/27/10
40
EZ-Temp™
Model
99000E
Full Proportional Mode of Operation
Data sheet
Specifications
s The EZ-Temp Commercial Boiler Package controls are provided as an assembled package. Pre-assembled and pre-wired
operating limit and manual reset high limit and proportional
modulating control for commercial boilers and similar applications. Includes EZ-Temp model 90000CEL combination
operating limit and manual reset high limit and and EZ-Temp
model 90200HL proportional modulating temperature controls,
mounted and wired on a two-gang J-box with terminal strips,
one triple sensor, 3/4” immersion well (1.55” length) and mounting hardware.
s Model 90000CEL and 90200HL microprocessor-operated
temperature controls are UL Listed. The 90000CEL provides
2 contacts (break-on-rise). The 90200HL provides a 135 ohm
proportional modulating control output.
s The 90000CE and 90200H are UL Recognized and may be
purchased separately for replacement.
90000CEL
Combination operating limit and
manual reset high limit control
8"0%!*.-0)1%#.-2!#21
8%+%#20.-)#1%-1.01
8.#*.32.-$)!'-.12)#&!)+30%!-$+),)2!#2).8!-3!+0%1%2&0.,()'(+),)2+.#*.32
8.0%1%2&0.,/.5%0)-2%003/2).8)'(+),)22%12&3-#2).-
90200HL
Proportional modulating control
8
%+%#20.-)#1%-1.0
8.#*.32.-$)!'-.12)#&!)+30%
832.0%1%2&0.,+.#*.325(%-&!3+20%,.4%$
Microprocessor-operated
(Processor coordinates limit and diagnostic functions)
Control model
Power input
Easy Remote Sense
(Electronic sensors, wired to control)
Contacts
Wires
Break-on-Rise Operation
HL
"0%!*.-0)1%
.-%
Full load
Locked rotor
3
5
!#2).-.-2%,/%0!230%0)1%
Contact Rating
CEL
Quantity
120 %320!+
()2%
120 .2
),)2
%$()2%
Break-on-rise
OUT
+!#*
%++.5()2%
Self-checking Program
Low Fire
(Control locks out on diagnostic failure)
Common
%++.5%$
High Fire
%++.5+!#*
92.9
Diagnostic/status LED’s
(LED’s indicate “Power On”, “Call for Heat”, “Lockout”,
and High Fire Calling”)
Adjustable operating limit range
92.9
Fixed high limit range
92.9
.-%
Adjustable band range
92.
9
-64!+3%&0.,9
2.
9
92.9
Fixed differentials (subtractive)
Operating temperature limits
Storage temperature limits
Agencies
TECH SUPPORT 800-989-2275
92.
9
792.
9
-$)4)$3!+#.-20.+1!0%Listed
&.0-)2%$2!2%1!-!$!
carlincombustion.com
41
Model 99000E Commercial Boiler Control Package for Full Proportional Mode of Operation — Data Sheet
Model 90000CEL diagnostic LED’s
GREEN
– OFF
– ON Power
RED
– OFF
– ON Lockout
AMBER
– OFF
– ON Call for Heat
Dimensions
– FLASHING (Slow) Latch-up
4.12”
– FLASHING (Fast) Hi-Test
Model 90200HL diagnostic LED’s
GREEN
– OFF
– ON Power
– FLASHING Lockout
AMBER
– OFF Low Fire
– ON High Fire
– FLASHING % High Fire
Electrical shock hazard: Disconnect power to appliance
when wiring or servicing any electrical component.
Operation (See wiring diagrams for connections)
Power On
When power is applied to unit, the green LED turns ON.
Self Test
90200HL: When the fault log display is complete, the self test
checks the sensor and the microprocessor and verifies that all
systems are operational. This test lasts up to 15 seconds before the
control becomes fully operational. During the self test, the green
LED blinks at a rate of 3 seconds per blink.
Lockout
90000CEL: When the temperature at the High-Limit sensor reaches
the High-Limit set point or a diagnostic fault occurs, the control
goes into Lockout. The red LED turns ON and both contacts open.
The control will automatically reset when all diagnostic faults are
removed. Manual reset is required to resume operation after an
over temperature High-Limit Lockout.
Lockout
90200HL: When a diagnostic fault occurs, the control goes into
Lockout. The green LED starts flashing and the control goes into
Low Fire. The control will automatically reset when all faults are
removed.
Call for Heat
2.12”
6.75”
90000CEL: When the temperature at the Operating-Limit sensor is
below the Operating-Limit set point minus the fixed differential, the
control powers the operating relay and it’s break-on-rise contact
closes. The Amber “Call for Heat” LED turns ON.
When the temperature is above the set point, the contact opens and
the Amber LED Turns OFF.
5.25”
High-Fire Calling 90200HL: When the temperature is at or below the operating temperature minus 1/2 the band temperature, the control is requesting
High Fire and the LED is ON. When the temperature is at or above
the operating temperature plus 1/2 the band temperature, the
control is requesting Low Fire and the LED is OFF. In between, the
control modulates the motor to a position proportional to the sensor
temperature. The LED blinks with an ON time proportional to this
position.
(90000CEL)
If the 90000CEL locks out three consecutive times, it enters latchup. Reset from latch-up requires a special procedure, intended to
require licensed serviceman intervention. During latch-up, the red
LED stays on and the green LED slow flashes. Reset as follows.
**
B2
LWCO Limit, if used
B1
120 Vac Power
to Appliance
120 VAC NEUTRAL OUT.
120 VAC LIMIT OUT.
To Red / White
L1
S2
EZ-Temp
SENSOR
INPUT
S
S2
S2
S1
S3
S1 & 2
S1
S1
TRIPLE
SENSOR
Sensor Well: Located on JBox back center knockout.
After boiler is less than high limit setting minus differential:
High Limit Test “Hi-Test” mode (90000CEL ONLY), used to test “High Limit Reset”
at operating boiler temperature. Start test with system operational
and calling for heat. Turn setpoint full clockwise to Hi-Test position.
Green LED flashes fast. The setpoint now adjusts both the high
and operating limits. Turn setpoint slowly counter clockwise until
Lockout occurs. Now the setpoint temperature equals the hi-limit
sensor temperature. Test is complete, adjust setpoint to the desired
operating limit. Remove from lockout.
90200H
** Conduit connection.
Locate at any knockout.
EZ-Temp
SENSOR
INPUT
J-Box
Terminal Strip
. . . . . . . . . . . . Continue holding button another 20 seconds. The control resets and
the red LED turns off.
SUPPORT
To White
To Black
H
G
120 VAC FEED OUT. (IF NEEDED)
BL1
. . . . . . . . . . . . Hold reset button at least 10 seconds. The green LED flashes faster.
TECH
TO BURNER PRIMARY CONTROL
(BREAK ON TEMPERATURE RISE).
L2
J-Box
Terminal Strip
Latch-up
N
SERVICE SWITCH
90000CE
S
S3
S
S3
OUTPUT TO 135
PROPORTIONAL ACTUATOR
**
Wht
To White lead
Red
To Red lead
Blk
HOTLINE
To Black lead
LOW FIRE
WIPER COMMON
HIGH FIRE
Reverse Low Fire and High Fire leads
to reverse motor direction.
800-989-2275
Carlin Combustion Technology, Inc.
70 Maple Street
e-mail us at:
© Copyright 2010 — Carlin Combustion Technology, Inc.
East Longmeadow, MA 01028
[email protected]
Phone 413–525–7700
Fax 413–525–8306
vist our website: www.carlincombustion.com
Carlin part number MN99000EC Rev. 01/27/10
42
TM
EZ-Temp
Microprocessor
Temperature Controls
Instruction Manual
E-Clamp Style with red sensor retainer plug
Installer/servicer — Except where specifically stated otherwise,
this manual must be used only by a qualified service technician.
Read and follow all instructions in this manual and in the appliance
manual. Failure to comply with this or other requirements in this
manual could result in severe personal injury, death or substantial
property damage.
This symbol calls out a hazard that could cause severe personal
injury, death or substantial property damage if the instructions
given are not followed.
Wiring: Refer to EZ-Temp data sheet for wiring information.
Verify ratings: Verify the ratings of the control meet the requirements of the appliance as specified in the appliance instructions.
Refer to the EZ-Temp control data sheet for required electrical
supply and load ratings. Verify that the controls, wiring and installation comply with all applicable codes.
Electrical shock hazard: Disconnect power to appliance when
wiring or servicing any electrical component.
Scald hazard: Water hotter than 130°F can cause serious burns or
death. Follow water heating appliance manufacturer’s guidelines
when installing temperature limit controls - DO NOT install a control
that can be set at a higher temperature than specified. Also verify
that the installation includes all water temperature regulating
means needed to ensure the safety of building occupants, in
compliance with all applicable codes.
Verify operation: Test the controls/appliance to verify the appliance
operates as specified in the appliance manual before leaving the
installation.
© Copyright 2008 — Carlin Combustion Technology, Inc.
Carlin Combustion Technology, Inc.
70 Maple Street
Ph 413-525-7700
TECH SUPPORT 800-989-2275
East Longmeadow, MA 01028
Fx 413-525-8306
carlincombustion.com
43
EZ-Temp Microprocessor Temperature Control — Instruction manual
Install sensor(s)
Configurations
To install a new immersion well:
Carlin EZ-Temp components are available in the following configurations, allowing use
with existing wells in addition to EZ-Temp wells.
1. Turn off power to the appliance and close isolation valves.
2. Follow appliance instructions to drain the appliance so water line is below
the insertion tapping.
3. Remove existing well and sensor. Apply a small amount of pipe dope to the
new well and secure in tapping.
4. Insert EZ-Temp sensor into well and secure sensor in place as described in
the following.
5. Refill appliance with water, following appliance manual procedures.
When routing sensor wires, avoid sharp edges and use strain
relief bushings at penetrations to prevent movement or electrical
shorting of the sensor. Sensor wires are not low voltage, and must
be routed in conduit.
Configuration A: Sensor and well only
1. Insert the sensor into well (1) until the sensor (2) tip bottoms in the well
socket.
2. EZ-Temp well: Slide the rubber retainer (3) over the sensor wires until it
firmly contacts the sensor casing. Slide the retainer washer (4) and the jam
nut (5) over the wires. Thread the jam nut into the well until snug.
3. Existing well: Press the sensor retainer plug (11) into the well until it securely
holds the sensor wires, to prevent movement of the sensor.
Surface-mount sensors are also available.
s Control kits
EZ-Temp controls mount to a standard 4x4 J-box or can be panel mounted.
Control kits include the control and sensor(s) (item 2) plus hardware needed
for mounting to an existing well (items 10 and 11). To obtain an EZ-Temp well
and hardware, obtain an EZ-Temp well kit, below.
s Well kits
EZ-Temp wells are available in the sizes shown below. Well kits include a
well (item 1), rubber sensor retainer (item 3), retainer washer (item 4), jam
nut (item 5), and J-box lock washer (item 8).
s Sensor Kits
Sensor kits include only the sensor (item 2). Sensors are available in single
and dual configurations (two sensors in the same assembly). For controls
that use multiple sensors, obtain separate sensor kits or a sensor kit and a
dual sensor.
Configuration B: Sensor, EZ-Temp well and J-box
1. Insert the sensor into well (1) until the sensor (2) tip bottoms in the well
socket.
2. Slide the rubber retainer (3) over the sensor wires until it firmly contacts the
sensor casing. Slide the retainer washer (4) over the wires.
3. Slide the lock washer (8), J-box (7), and jam nut (4) over the wires.
4. Thread the jam nut into the well and tighten to secure the J-box and sensor
in place.
Configuration C: Sensor, EZ-Temp well and J-box
1. Insert the sensor into well (1) until the sensor (2) tip botoms in the well
socket.
2. Slide the J-box (7) over the wires and secure the J-box in place by snapping
the retainer ring (10) onto the well shoulder.
3. Press the sensor retainer plug (11) into the well until it securely holds the
sensor wires, to prevent movement of the sensor.
Mount the control
1. Insert sensor wire terminals into the labelled openings on the back of the
control. Press into place firmly.
2. Attach the control to the 4x4 J-box or panel mount, as desired.
Wire the control
1. Control wiring (including sensor wires) must be routed through conduit
or electrical enclosures. Follow all applicable codes and the appliance
manual.
2. Follow the burner and appliance wiring diagrams to connect the control(s)
into the appliance limit circuit.
3. For specific applications, contact your Carlin supplier for further information.
Set the control
1. Follow the appliance manual to set the correct limit temperature for the
appliance. To adjust the EZ-Temp control:
s
)NSERTASCREWDRIVERINTOTHESETTINGSLOTANDROTATEUNTILTHEINDICATORPOINTS
to the desired temperature.
2. Test the operation of the appliance and the new limit control(s) to verify
correct operation.
3. NOTE: EZ-Temp controls have a subtractive differential — control contacts
trigger when the temperature setting is reached. Contacts reset after temperature drops below setpoint minus the differential amount.
–2–
Carlin part number MNEZT Rev. 12/08/2008
44
TM
EZ-Temp
Microprocessor
Temperature Controls
Instruction Manual
Well clamp with sensor retainer spring
Installer/servicer — Except where specifically stated otherwise,
this manual must be used only by a qualified service technician.
Read and follow all instructions in this manual and in the appliance
manual. Failure to comply with this or other requirements in this
manual could result in severe personal injury, death or substantial
property damage.
This symbol calls out a hazard that could cause severe personal
injury, death or substantial property damage if the instructions
given are not followed.
Wiring: Refer to EZ-Temp data sheet for wiring information.
Verify ratings: Verify the ratings of the control meet the requirements of the appliance as specified in the appliance instructions.
Refer to the EZ-Temp control data sheet for required electrical
supply and load ratings. Verify that the controls, wiring and installation comply with all applicable codes.
Electrical shock hazard: Disconnect power to appliance when
wiring or servicing any electrical component.
Scald hazard: Water hotter than 130°F can cause serious burns or
death. Follow water heating appliance manufacturer’s guidelines
when installing temperature limit controls - DO NOT install a control
that can be set at a higher temperature than specified. Also verify
that the installation includes all water temperature regulating
means needed to ensure the safety of building occupants, in
compliance with all applicable codes.
Verify operation: Test the controls/appliance to verify the appliance
operates as specified in the appliance manual before leaving the
installation.
© Copyright 2008 — Carlin Combustion Technology, Inc.
Carlin Combustion Technology, Inc.
70 Maple Street
Ph 413-525-7700
TECH SUPPORT 800-989-2275
East Longmeadow, MA 01028
Fx 413-525-8306
carlincombustion.com
45
EZ-Temp Microprocessor Temperature Control — Instruction manual
Install sensor(s)
Configurations
To install a new immersion well:
1. Turn off power to the appliance and close isolation valves.
2. Follow appliance instructions to drain the appliance so water line is below
the insertion tapping.
3. Remove existing well and sensor. Apply a small amount of pipe dope to the
new well and secure in tapping.
4. Insert EZ-Temp sensor into well and secure sensor in place as described in
the following.
5. Refill appliance with water, following appliance manual procedures.
Carlin EZ-Temp components are available in the following configurations, allowing use
with existing wells in addition to EZ-Temp wells.
When routing sensor wires, avoid sharp edges and use strain
relief bushings at penetrations to prevent movement or electrical
shorting of the sensor. Sensor wires are not low voltage, and must
be routed in conduit.
s Well kits
EZ-Temp wells are available in the sizes shown below. Well kits include a
well (item 1), rubber sensor retainer (item 3), retainer washer (item 4), jam
nut (item 5), and J-box lock washer (item 8).
Configuration A: Sensor and well only
1. Insert the sensor into well (1) until the sensor (2) tip bottoms in the well
socket.
2. EZ-Temp well: Slide the rubber retainer (3) over the sensor wires until it
firmly contacts the sensor casing. Slide the retainer washer (4) and the jam
nut (5) over the wires. Thread the jam nut into the well until snug.
3. Existing well: Press the sensor retainer plug (11) into the well until it securely
holds the sensor wires, to prevent movement of the sensor.
s Sensor Kits
Sensor kits include only the sensor (item 2). Sensors are available in single
and dual configurations (two sensors in the same assembly). For controls
that use multiple sensors, obtain separate sensor kits or a sensor kit and a
dual sensor.
Surface-mount sensors are also available.
s Control kits
EZ-Temp controls mount to a standard 4x4 J-box or can be panel mounted.
Control kits include the control and sensor(s) (item 2) plus hardware needed
for mounting to an existing well (items 10 and 11). To obtain an EZ-Temp well
and hardware, obtain an EZ-Temp well kit, below.
A
Configuration B: Sensor, EZ-Temp well and J-box
1. Insert the sensor into well (1) until the sensor (2) tip bottoms in the well
socket.
2. Slide the rubber retainer (3) over the sensor wires until it firmly contacts the
sensor casing. Slide the retainer washer (4) over the wires.
3. Slide the lock washer (8), J-box (7), and jam nut (4) over the wires.
4. Thread the jam nut into the well and tighten to secure the J-box and sensor
in place.
Configuration C: Sensor, EZ-Temp well and J-box
1. Remove the center knock-out from one side of the J-box (7).
2. Position the well clamp (10) over the end of the well (9) (sensor not yet
installed) and slide the well clamp (10) toward the side of the J-box (9)
engaging the keyslot opening with the well undercut.
3. Position the flat washer (13) over the open knockout and install the tensioning screw (14) through the flat washer (13) and into the well clamp (10),
tighten.
4. Position the rubber retainer (12) over the sensor leads until the retainer stops
at the sensor body.
5. Position the retainer spring (11) near the end of the rubber retainer as
shown.
6. Slide sensor and retainer/sping assembly into well. Squeeze retainer spring
ends together as the spring enters the well. The end of the spring should
be within the well bore.
B
Sensor, J-box & EZ-Temp well
C
Mount the control
1. Insert sensor wire terminals into the labelled openings on the back of the
control. Press into place firmly.
2. Attach the control to the 4x4 J-box or panel mount, as desired.
Wire the control
1. Control wiring (including sensor wires) must be routed through conduit
or electrical enclosures. Follow all applicable codes and the appliance
manual.
2. Follow the burner and appliance wiring diagrams to connect the control(s)
into the appliance limit circuit.
3. For specific applications, contact your Carlin supplier for further information.
Sensor, J-box & existing well
EZ-Temp well
EZ-Temp sensor
EPDM rubber retainer
Retainer washer
Jam nut
Sensor leads
J-box, 4 x 4
Set the control
1. Follow the appliance manual to set the correct limit temperature for the
appliance. To adjust the EZ-Temp control:
s
)NSERTASCREWDRIVERINTOTHESETTINGSLOTANDROTATEUNTILTHEINDICATORPOINTS
to the desired temperature.
2. Test the operation of the appliance and the new limit control(s) to verify
correct operation.
3. NOTE: EZ-Temp controls have a subtractive differential — control contacts
trigger when the temperature setting is reached. Contacts reset after temperature drops below setpoint minus the differential amount.
–2–
Lock washer
Existing well
Well clamp
Sensor retainer spring
3.8” rubber retainer
Flat washer
Tensioning screw
Carlin part number MNEZT5 Rev. 12/08/2008
46
/…iÀ“ˆÃ̜ÀÊ,iÈÃÌ>˜Vi
qÊ<‡/i“«Ê-i˜ÃœÀÃ
#ARLIN5n2ESIDENTIAL/IL"URNERSn0AGE
47
/…iÀ“ˆÃ̜ÀÊ,iÈÃÌ>˜Vi
qÊ<‡/i“«Ê-i˜ÃœÀÃ
#ARLIN5n2ESIDENTIAL/IL"URNERSn0AGE
TECH
SUPPORT
HOTLINE
800-989-2275
Carlin Combustion Technology, Inc.
70 Maple Street East Longmeadow, MA 01028 Phone 413–525–7700 Fax 413–525–8306
e-mail us at: [email protected]
© Copyright 2010 — Carlin Combustion Technology, Inc.
vist our website: www.carlincombustion.com
Carlin part number MNEZTEMP Rev. 03/26/10