Predator XP - HVAC Tech Support

Predator XP - HVAC Tech Support
246824-YTG-E-0507
®
TECHNICAL GUIDE
Description
®
R-410A
ZH/ZR/XP SERIES
6-1/2 - 12-1/2 TON
60 Hertz
ASHRAE 90.1 COMPLIANT
YORK® Predator® units are convertible single packages with a
common footprint cabinet and common roof curb for all 6-1/2
through 12-1/2 ton models. All units have two compressors with
independent refrigeration circuits to provide 2 stages of cooling.
The units were designed for light commercial applications and
can be easily installed on a roof curb, slab, or frame.
All Predator® units are self-contained and assembled on rigid
full perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
All units are convertible between side and down airflow.
Independent economizer designs are used on side and down
discharge applications, as well as all tonnage sizes.
Predator® units are available in the following configurations:
cooling only, cooling with electric heat, cooling with gas heat,
heat pump, and heat pump with electric heat. Electric heaters
are available as factory-installed options or field-installed
accessories.
Tested in accordance with:
6-1/2 THROUGH 10 TON
12-1/2 TON
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
246824-YTG-E-0507
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Component Location
Cooling With Gas Heat
[email protected]®FRQWUROERDUG
)LOWHUDFFHVV
'LVFRQQHFWORFDWLRQ
ZVFUHZFRQQHFWRUIRU7VWDW
´WKURZDZD\
ZLULQJDQGQHWZRUNFRQQHFWLRQV RSWLRQDOGLVFRQQHFWVZLWFK
7HUPLQDOEORFNIRU
KLYROWDJHFRQQHFWLRQ
)LOWHUGULHU
VROLGFRUH
&RQGHQVHUVHFWLRQ
6HFRQGPRGHO
QDPHSODWH
LQVLGHKLQJHG
DFFHVVSDQHO
6OLGHRXWPRWRUDQG
EORZHUDVVHPEO\IRU
HDV\DGMXVWPHQW
DQGVHUYLFH
'XDOVWDJH
FRROLQJIRU
PD[LPXP
FRPIRUW
3RZHUYHQWRUPRWRU
&RPSUHVVRU
DFFHVVKLJK
HIILFLHQF\
FRPSUHVVRU
ZFUDQNFDVH
KHDWHU
JDXJHDOXPL
QL]HGVWHHOWXEXODU
KHDWH[FKDQJHUIRU
ORQJOLIHVWDLQOHVV
VWHHORSWLRQ
%DVHUDLOVZIRUNOLIW
VORWVWKUHHVLGHV
DQGOLIWLQJKROHV
7ZRVWDJHJDV
KHDWLQJWRPDLQWDLQ
ZDUPFRPIRUWDEOH
WHPSHUDWXUH
5RRIFXUEVLQHLJKWDQG
IRXUWHHQLQFKKHLJKWV5RRI
FXUEVIRUWUDQVLWLRQLQJIURP
<RUN6XQOLQHŒIRRWSULQWWR
WKH=+/ZR6HULHVIRRWSULQWV
are DOVRDYDLODEOHILHOG
installed DFFHVVRU\
2
%HOWGULYH
EORZHUPRWRU
6OLGHRXWGUDLQSDQ
ZLWKVWHHO´137
IHPDOHFRQQHFWLRQ
7RROOHVV
GRRUODWFK
6LGHHQWU\SRZHU
DQGFRQWUROZLULQJ
NQRFNRXWV
,QWHOOLJHQWFRQWURO
ERDUGIRUVDIHDQG
HIILFLHQWRSHUDWLRQ
&RPSUHVVRUDFFHVV
KLJKHIILFLHQF\FRPSUHVVRU
ZFUDQNFDVHKHDWHU
Unitary Products Group
246824-YTG-E-0507
Heat Pump
Simplicity® Control
board w/screw connectors for T-stat wiring and
network connection
Terminal block
for hi-voltage
connection
Disconnect location
(optional disconnect switch)
Filter access
(2” throw-away)
Filter drier (solid core)
Condenser
section
Second Model
Nameplate Inside
Control Door
Slide-out motor and
blower assembly for
easy adjustment and
service.
Dual stage cooling for maximum
comfort (7-1/2 12-1/2 Only)
Compressor #2
Access (High-Eff
Compressor)
Base Rails w/ Forklift Slots (3 Sides)
& Lifting Holes
Belt-drive
blower
motor
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
Sunline™ footprint to the
XP series footprint are also
available (field installed
accessory)
Toolless
Door Latch
Unitary Products Group
Side entry power
and control wiring
knockouts
Compressor #1 Access
(High-Eff Compressor)
Slide-out drain pain
with steel 3/4” NPT,
Female Connection
3
246824-YTG-E-0507
Nomenclature
6.5-12.5 Ton York® Model Number Nomenclature
Z H 090 N10 A 2 A AA 4 0 1 2 4 A
Product Category
Product Style
A = Style A
B = Style B
C = Style C
Z = A/C, Single Pkg., R-410A
X = HP, Single Pkg., R-410A
Product Identifier
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
H = 11.0+ EER A/C
P = 11.0 EER HP
R = Reheat
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller, DFS, APS
Nominal Cooling Capacity
Honeywell Controller, DFS, APS
078 = 6.5 Ton
090 = 7.5 Ton
102 = 8.5 Ton
120 = 10.0 Ton
150 = 12.5 Ton
Simplicity IntelliComfort Controller
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated filters
BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)
Shipping Bag
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No heat installed
Product Generation
Gas Heat Options
4 = Fourth Generation
N10 = 100 MBH Output Aluminized Steel
N15 = 150 MBH Output Aluminized Steel
N20 = 200 MBH Output Aluminized Steel
S10 = 100 MBH Output Stainless Steel
S15 = 150 MBH Output Stainless Steel
S20 = 200 MBH Output Stainless Steel
Additional Options
AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
Electric Heat Options
E09 = 9 KW
E18 = 18 KW
E24 = 24 KW
E36 = 36 KW
E54 = 54 KW
RC = Coil Guard, Shipping Bag & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Airflow
Installation Options
A = Std. Motor
B = Std. Motor/Econo./Barometric Relief (Downflow
Only)
C = Std. Motor/Econo./Power Exhaust (Downflow Only)
D = Std. Motor/Motorized Damper (Downflow Only)
E = Std. Motor/Horizontal Economizer (No Baro.)
F = Std. Motor/Slab Econo./Power Exhaust
(Downflow Only)
G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only)
N = Hi Static Mtr.
P = Hi Static Mtr./Econo./Barometric Relief
(Downflow Only)
Q = Hi Static Mtr./Econo./Power Exhaust
(Downflow Only)
R = Hi Static Mtr./Motorized Damper (Downflow Only)
S = Hi Static Mtr./Horizontal Economizer (No Baro.)
T = Hi Static Mtr./Slab Econo./Power Exhaust
(Downflow Only)
U = Hi Static Mtr./Slab Econo./Barometric Relief
(Downflow only)
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
4
Unitary Products Group
246824-YTG-E-0507
Features and Benefits
Standard Features
• High Efficiency – High efficiency units reach as high as
11.5 EER. Gas/electric units have electronic spark ignition
and power vented combustion with steady state efficiencies
of 80%. These efficiencies exceed all legislated minimum
levels and provide low operating costs.
• Service Friendly – The Predator® incorporates a number
of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other
unauthorized persons. It is recommended that the panels
be secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access to
the condenser coils for cleaning or inspection.
Both the unit control board and ignition control board utilize
flash codes to aid in diagnosis of unit malfunctions. Unique
alarm codes quickly identify the source of the unit alarm.
All units use the same standard filter size. This
standardization removes any confusion on which filter
sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit
easy cleaning. The drain pan is accessed by removing the
drain pan cover plate on the rear of the unit. Once the plate is
removed, the drain pan slides out through the rear of the unit.
All Predator® units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
• Environmentally Aware – For improved Indoor Air
Quality, foil faced insulation is used exclusively
throughout the units.
• Balanced Heating – The Predator® offers “Ultimate
Heating Comfort” with a balance between 1st and 2nd stage
gas heating. The first stage of a gas heat Predator® unit
provides 60% of the heating capacity. Balanced heating
allows the unit to better maintain desired temperatures.
• Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two side
duct covers from the outside of the unit and installs them
over the down shot openings. No panel cutting is required.
Convertible airflow design allows maximum field flexibility
and minimum inventory.
• System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frosting
when the economizer operates at low outdoor air
temperatures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and low-
Unitary Products Group
pressure switches. Internal compressor protection is
standard on all compressors. Crankcase heaters are
standard on reciprocating compressors. Scroll compressors
do not require crankcase heaters. Phase Monitors are
standard on units with scroll compressors. This accessory
monitors the incoming power to the unit and protects the
unit from phase loss and reversed phase rotation.
• Advanced Controls - Simplicity® ZH/ZR/XP control
boards have standardized a number of features
previously available only as options or by utilizing
additional controls.
• Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down to
0°F outdoor ambient without additional assistance.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air
temperature is low or when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life,
an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti-short cycle delay can be temporarily
overridden with the push of a button.
• Lead-Lag - An integrated Lead-Lag option allows equal
run time hours on all compressors, thereby extending
the life of all compressors. This option is selectable on
the unit control board.
• Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling
fan delay times are independent of one another. All units
are programmed with default values based upon their
configuration of cooling and heat.
• Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the gas
valve, if applicable, and the temperature limit switch on
gas and electric heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
• Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a “three
times, you’re out” philosophy. The high and lowpressure switches and the freezestats must trip three
times within two hours before the unit control board will
lock out the associated compressor.
• On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and flash
an alarm code on the control board LED. Each high and
low-pressure switch alarm as well as each freezestat
alarm has its own flash code. The control board saves the
five most recent alarms in memory, and these alarms can
be reviewed at any time. Alarms and programmed values
are retained through the loss of power.
• Reliable – From the beginning – All units undergo
computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term – All
Predator® units are painted with a long lasting, powder
paint that stands up over the life of the unit. The paint
used has been proven by a 1000 hour salt spray test.
5
246824-YTG-E-0507
• Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
To further simplify planning and installation, Predator®
ZH/ZR/XP cabinets are designed to fit your roof. With the
optional roof curb, the unit ductwork is designed to fit
around 24” on-center joists or between 48” on-center
joists.
The drain pan can be rotated to drain to either the front or
the rear of the unit. Additionally, the drain pan can be
fitted to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
• Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer forklift
access from 3 sides, and rigging holes are available so that
an overhead crane can be used to place the units on a roof.
• Easy Installation – Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the unit.
A clearly identified location is provided to mount a field
supplied electrical disconnect switch. Utility connections can
be made quickly and with a minimum amount of field labor.
All units are shipped with 2” throw-away filters installed.
• Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to handle
most airflow requirements. For high static applications,
factory installed alternate indoor fan motors are available.
With the optional indoor fan motor, all units can supply
nominal airflow at a minimum of 1.5” ESP.
• Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry a 10year warranty.
Factory Installed Options
YORK® offers several equipment options factory installed, for
the Predator® line.
• Optional Factory Installed Economizers - Predator units
offer a variety of optional factory installed economizers
with low leak dampers. The outdoor air enthalpy sensor
enables economizer operation if the outdoor enthalpy is
less than the setpoint of the economizer logic module. See
economizer options section to determine the correct
economizer for your application.
• Downflow Economizer - (With barometric relief) The economizer is provided with a single enthalpy input.
The economizer is 2% low leakage type, and is shipped
installed and wired. The installer needs only to
assemble and mount the outdoor air hood (Provided).
The economizer has spring return, fully modulating
damper actuators and is capable of introducing up to
100% outdoor air. As the outdoor air intake dampers
open, the return air dampers close. The changeover
from mechanical refrigeration to economizer operation is
regulated by the standard single enthalpy input. There is
6
•
•
•
•
an optional input dual dry bulb available. To meet
regulated air standards, the economizer control accepts
an optional CO2 input for demand ventilation. With
single enthalpy input, the economizer control monitors
outdoor air. The dual enthalpy kit provides a second
input used to monitor the return air. With a dual input kit
installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
• Horizontal Economizer - (Without barometric relief) All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizers only.
• BAS Ready Economizer -(With barometric relief) The economizer is provided with an actuator that
requires a 0-10V DC input from an external source (i.e.,
field installed building automation system controller).
Power exhaust options are available. The economizer is
2% low leakage type with spring return and fully
modulating dampers capable of introducing up to 100%
outside air. Also include 2” pleated filters.
• Slab Economizer for Energy Recovery Ventilators(With barometric relief and Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type, and is shipped
installed and wired. The economizer has spring return,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to
economizer operation is regulated by the standard
single enthalpy input. There is an optional input dual dry
bulb available. To meet regulated air standards, the
economizer control accepts an optional CO2 input for
demand ventilation.With single enthalpy input, the
economizer control monitors outdoor air. The dual
enthalpy kit provides a second input used to monitor the
return air. With a dual input kit installed, the economizer
control compares the values of the two enthalpy or
temperature inputs and positions the dampers to
provide the maximum efficiency possible.
Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer.
Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly
with an outdoor air hood and filters. The outdoor air
dampers open to the preset position when the indoor fan
motor is energized. The damper has a range of 0% to
100% outdoor air entry. Factory installed option or field
installed accessory.
Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
Aluminized Steel Gas Heat Exchanger - For
applications in non-corrosive environments.
Unitary Products Group
246824-YTG-E-0507
• Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
• Stainless Steel Drain Pan - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
• Electric Heaters - The electric heaters range from 9kW to
54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
• Disconnect Switch - For gas heat units and cooling units
with electric heat, a HACR breaker sized to the unit is
provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
• Convenience Outlet - (Non-Powered/Powered) - This
option locates a 120V single-phase GFCI outlet with cover,
on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source and
wiring. The “Powered” option is powered by a stepdown
transformer in the unit. Factory installed option only.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air.
Factory installed smoke detectors in the return air, may be
subjected to freezing temperatures during "off" times due
to out side air infiltration. These smoke detectors have an
operational limit of 32 °F to 131°F. Smoke detectors
installed in areas that could be out side those limitations
will have to be moved to prevent having false alarms.
• Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally, this
kit stops animals and foreign objects from entering the
space between the inner condenser coil and the main
cabinet. This is not a hail guard kit.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
• Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• Hot Gas Bypass - Allows operation during low load
conditions while avoiding coil frosting and damage to
compressor. When suction pressure falls below valve
Unitary Products Group
setpoint, the valve modulates hot gas to the inlet of the
evaporator.
Control Options
• BAS - Building Automation System Controls Simplicity®
INTELLI-Comfort™ Control - The York® Simplicity®
INTELLI-Comfort™ control is factory installed. It includes a
supply air sensor, a return air sensor, and an outside air
sensor. There are provisions for a field installed dirty filter
indicator switch, an air-proving switch, an Outside Air
Humidity sensor, a Return Air Humidity sensor, an Inside
IAQ sensor, and an Outside Air IAQ sensor. Construction
mode operation, 365-day real time clock with 7 day
programming plus holiday scheduling is built-in. Two
different modes of demand ventilation are achieved through
the INTELLI-Comfort™ using CO2 sensors. It uses an
inside CO2 sensor to perform Demand Ventilation. It can
also use an Outside CO2 sensor to perform Differential
Demand Ventilation. It uses a Patented Comfort Ventilation
algorithm to provide comfortable ventilation air
temperature. The patented economizer-loading algorithm
will protect the equipment when harsh operating conditions
exist. Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the onboard connection for hot gas re-heat system. It uses the
INTELLI-Start™ algorithm to maximize energy savings by
recovering the building from the Unoccupied Setpoints to
the Occupied Setpoints just in time for the Occupied Time
Period to begin. The Simplicity® INTELLI-Comfort™
balances space temperature, ventilation air temperature,
CO2 and humidity for ultimate comfort.
• Simplicity® INTELLI-Comfort™ with ModLINC
Control - The York® Simplicity® INTELLI-Comfort™ with
ModLINC control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an
additional control to translate communications from
MODBUS to the BACnet MSTP protocol.
• Novar® BAS Control - The Novar® ETC-3 building
automation system controller is factory installed. Incudes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
• Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air proving switch.
• CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
• Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
Field Installed Accessories
YORK® offers several equipment accessories for field
installation, for the Predator® line.
• Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
7
246824-YTG-E-0507
•
•
•
•
•
•
•
8
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer
control accepts an optional CO2 input for demand
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit provides a
second input used to monitor the return air. With a dual input
kit installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
Horizontal Economizer - (Without barometric relief) All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizer.
Slab Economizer for Energy Recovery Ventilator(Without barometric relief or Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer
control accepts an optional CO2 input for demand
ventilation.With single enthalpy input, the economizer control
monitors outdoor air. The dual enthalpy kit provides a
second input used to monitor the return air. With a dual input
kit installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
You can order 1EH0409 Barometric Relief/FA Hood for
field installations without an ERV.
Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
Power Exhaust - This accessory installs in the unit with a
down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a
horizontal flow application.
Manual Outdoor Air Damper - Like the motorized outdoor
air damper, each manual outdoor air damper includes a
slide-in damper assembly with an outdoor air hood and
filters. Customers have a choice of dampers with ranges of
0% to 100% or 0% to 35% outdoor air entry.
Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
•
•
•
•
•
•
•
•
•
•
•
•
•
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
CO2 Sensor - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
preset limits.
Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be
installed to prevent the flue exhaust from entering nearby
fresh air intakes.
-60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
Gas Heat High Altitude Kit - This kit converts a gas heat
unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and propane.
Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains the
main burner orifices and gas valve replacement springs.
Gas Piping Kit - Contains pipe nipples, fittings and gas cock
required for gas supply connection with external shut off.
Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. Cooling units
include an adapter panel for easy installation of the
electric heaters. Necessary hardware and connectors are
included with the heaters. All heaters are intended for
single point power supply.
Low Limit / Compressor Lockout Kit
• Compressor Lockout (CLO): To prevent mechanical
(compressorized) operation of the unit during cold
outdoor conditions where there is a risk of returning
liquid refrigerant back to the compressors.
• Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing the
units first stage heating means when there is a demand
for cooling during cold outside conditions.
Metal Frame Filter Kit - Metal frame with polyester filter
medium.
• Permanent Filters - Permanent filters are available.
Unitary Products Group
246824-YTG-E-0507
• Roof Curbs - The roof curbs have insulated decks and are
shipped disassembled The roof curbs are available in 8” and
14” heights. For applications with security concerns, burglar
bars are available for the duct openings of the roof curbs.
• Roof Curb Transition - Single Piece Adapter (10” High) Roof curbs for transitioning from Sunline™ units to
Predator® units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
• Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with twostage heat/two-stage cool or two-stage cooling only
thermostats, depending upon unit configuration.
Accessories
Part Number
1RC0470
1RC0471
1RC0472
1BD0408
2TP04520925
2TP04521825
2TP04522425
2TP04523625
2TP04525425
2TP04520946
2TP04521846
2TP04522446
2TP04523646
2TP04525446
2TP04520958
2TP04521858
2TP04522458
2TP04523658
2TP04525458
2TP04540925
2TP04541825
2TP04542425
2TP04543625
2TP04540946
2TP04541846
2TP04542446
2TP04543646
2TP04540958
2TP04541858
2TP04542458
2TP04543658
1FA0413
1FA0414
2MD04702724
2MD04703324
2EE04705424
2EE04705524
2EE04705224
2EE04705624
2PE04703225
2PE04703246
2PE04703258
2EC04700924
1EH0407
1RD0411
1EH0408
1EH0409
2AQ04700424
2AQ04700324
Description
Roof Curb, 8" Height
Roof Curb, 14" Height
Roof Curb, Transition (7.5 T through 12.5 T)
Burglar Bars, Downflow
Electric Heat 9kW 230V
Electric Heat 18kW 230V
Electric Heat 24kW 230V
Electric Heat 36kW 230V
Electric Heat 54kW 230V
Electric Heat 9kW 460V
Electric Heat 18kW 460V
Electric Heat 24kW 460V
Electric Heat 36kW 460V
Electric Heat 54kW 460V
Electric Heat 9kW 575V
Electric Heat 18kW 575V
Electric Heat 24kW 575V
Electric Heat 36kW 575V
Electric Heat 54kW 575V
Electric Heat 9kW 230V, 42" Tall Cabinet
Electric Heat 18kW 230V, 42" Tall Cabinet
Electric Heat 24kW 230V, 42" Tall Cabinet
Electric Heat 36kW 230V, 42" Tall Cabinet
Electric Heat 9kW 460V, 42" Tall Cabinet
Electric Heat 18kW 460V, 42" Tall Cabinet
Electric Heat 24kW 460V, 42" Tall Cabinet
Electric Heat 36kW 460V, 42" Tall Cabinet
Electric Heat 9kW 575V, 42" Tall Cabinet
Electric Heat 18kW 575V, 42" Tall Cabinet
Electric Heat 24kW 575V, 42" Tall Cabinet
Electric Heat 36kW 575V, 42" Tall Cabinet
Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief)
Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)
Economizer, Downflow (Incl. Barometric Relief & All Hoods)
Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief)
Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief)
"Downflow Economizer, Slab type for ERV (no Barometric Relief or FA hood)", 42" Tall Cabinet
Power Exhaust, Downflow, 230V (For Units with Economizer only)
Power Exhaust, Downflow, 460V(For Units with Economizer only)
Power Exhaust, Downflow, 580V (For Units with Economizer only)
Dual Enthalpy Control (Use with Single Enthalpy Economizer)
Hood Kit, Downflow Economizer (Included with all Downflow Economizers)
Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)
Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood)
Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood)
CO2 Detector Unit Mount
CO2 Detector Space Mount
Unitary Products Group
9
246824-YTG-E-0507
Accessories (Continued)
Part Number
2SD04700424
2MK04700624
1CG0419
1CG0420
1CG0424
1CG0425
1CG0427
1CG0428
1HG0411
1HG0415
1GP0405
1NP0442
1HA0442
1HA0443
1FE0412
2BC04700106
2BC04700151
2BC04700154
1FL0402
1FL0423
2DF0401
1FF0410
1FF0411
Description
Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer)
Low Limit / Compressor Lockout Kit
Coil Guard (Electric / Electric & HP models), 8-1/2 and 10 Ton
Coil Guard (Gas / Electric models), 8-1/2 and 10 Ton
Coil Guard (Electric / Electric and HP models), 12-1/2 Ton
Coil Guard (Gas / Electric models), 12-1/2 Ton
Coil Guard (Electric / Electric & HP Models), 6-1/2 and 7-1/2 Ton
Coil Guard (Gas / Electric Models), 6-1/2 and 7-1/2 Ton
Hail Guard Kit
Hail Guard Kit, 42" Tall Cabinet
Gas Piping Kit
Propane Conversion Kit
High Altitude Kit for Natural Gas
High Altitude Kit for Propane
Flue Exhaust Extension Kit
Gas Heat Kit, -60 deg F, 230V
Gas Heat Kit, -60 deg F, 460V
Gas Heat Kit, -60 deg F, 575V
Permanent Filter Kit
Permanent Filter Kit, 42" Tall Cabinet
Dirty Filter Switch
Filter Frame Kit, Metal
Metal Filter Frame Kit, 42" Tall Cabinet
Guide Specifications
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility. YORK®
Predator® units are convertible single packages with a
common footprint cabinet and common roof curb for all 6-1/2
through 12-1/2 ton models. All units have two compressors
with independent R-410a refrigeration circuits to provide 2
stages of cooling. The units were designed for light commercial
applications and can be easily installed on a roof curb, slab, or
frame. All Predator® units are self-contained and assembled
on rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging. Every unit is completely charged
with R-410a, wired, piped, and tested at the factory to provide
a quick and easy field installation. All units are convertible
between side and down airflow. Independent economizer
designs are used on side and down discharge applications, as
well as all tonnage sizes. Predator® units are available in the
following configurations: cooling only, cooling with electric
heat, cooling with gas heat, heat pump, and heat pump with
electric heat. Electric heaters are available as factory-installed
options or field-installed accessories.
DESCRIPTION
Units shall be factory assembled, single package, (Elec/Elec, Gas/
Elec), designed for outdoor installation. They shall have built in
field convertible duct connections for down discharge supply/return
or horizontal discharge supply/return and be available with factory
installed options or field installed accessories. The units shall be
factory wired, piped and charged with R-410a refrigerant and
factory tested prior to shipment. All unit wiring shall be both
10
numbered and color coded. The cooling performance shall be
rated in accordance with DOE and ARI test procedures. Units shall
be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up to
1” thick insulation coated on the airside. Aluminum foil faced
insulation shall be used in the unit’s compartments and be
fastened to prevent insulation from entering the air stream.
Cabinet doors shall be hinged with toolless access for easy
servicing and maintenance. Full perimeter base rails shall be
provided to assure reliable transit of equipment, overhead
rigging, fork truck access and proper sealing on roof curb
applications. Disposable 2” filters shall be furnished and be
accessible through hinged access door. Fan performance
measuring ports shall be provided on the outside of the cabinet
to allow accurate air measurements of evaporator fan
performance without removing panels or creating bypass of the
coils. Condensate pan shall be slide out design, constructed of
a non corrosive material, internally sloped and conforming to
ASHRAE 62-B9 standards. Condensate connection shall be a
minimum of ¾” I.D. female and be rigid mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall not
exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service
Unitary Products Group
246824-YTG-E-0507
factor. Fan wheel shall be double inlet type with forward curve
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
volume. Bearings shall be sealed and permanently lubricated
for longer life and no maintenance. Entire blower assembly and
motor shall be slide out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge air
vertically, have aluminum blades riveted to corrosion resistant
steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently
lubricated bearings internally protected against overload
conditions and staged independently. A cleaning window shall be
provided on two sides of the units for coil cleaning.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or –
10% of the unit nameplate voltage.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.
b. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice
expansion devices.
or
thermally
operated
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
d. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit
Unitary Products Group
should any of the following standard safety devices trip
and shut off compressor:
c. Loss-of-charge/Low-pressure switch.
• High-pressure switch.
• Freeze-protection thermostat, evaporator coil. If any of
the above safety devices trip, an LED (light-emitting
diode) indicator shall flash a diagnostic code that
indicates which safety switch has tripped.
d. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
e. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
f. Unit control board shall have on-board diagnostics and
fault code display.
g. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 ºF.
h. Control board shall monitor each refrigerant safety switch
independently.
i. Control board shall retain last 5 fault codes in nonvolatile memory, which will not be lost in the event of a
power loss.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. The heat exchanger shall
be of the tubular type, constructed of T1-40 aluminized steel for
corrosion resistance and allowing minimum mixed air entering
temperature of 40 ºF. Burners shall be of the in-shot type, constructed of aluminum-coated steel. All gas piping shall enter the
unit cabinet at a single location, through either the side or bottom, without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft pressure sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls. Unit shall have two independent
stages of capacity (60% 1st stage, 100% 2nd stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 9 thru 54 KW, offering two states
of capacity all sizes. The heating section shall have a primary
limit control(s) (automatic reset) to prevent the heating element
system from operating at an excessive temperature. The Heating Section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating Sections shall be
wired for a single point power supply with branch circuit fusing
(where required).
11
246824-YTG-E-0507
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor
temperature, exceeding maximum load criteria of ARI Standard
340/360. The compressor, with standard controls, shall be
capable of operation down to 0 ºF outdoor temperature. Unit
shall be provided with fan time delay to prevent cold air delivery
before heat exchanger warms up. (Gas heat only)
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5 Years,
Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years,
Parts – 1 Year
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be
made available by either/or):
• ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER
– Outdoor and return air dampers that are interlocked and
positioned by a fully-modulating, spring-return damper
actuator. The maximum leakage rate for the outdoor air
intake dampers shall not exceed 2% when dampers are
fully closed and operating against a pressure differential
of 0.5 IWG. A unit-mounted potentiometer shall be
provided to adjust the outdoor and return air damper
assembly to take in outdoor air to meet the minimum
ventilation requirement of the conditioned space during
normal operation. During economizer operation, a mixedair temperature control shall modulate the outdoor and
return air damper assembly to prevent the supply air
temperature from dropping below 55 ºF. Changeover from
compressor to economizer operation shall be provided by
an integral electronic enthalpy control that feeds input into
the basic module. The outdoor intake opening shall be
covered with a rain hood that matches the exterior of the
unit. Water eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
Available with barometric relief or power exhaust.
• MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and
return air dampers that are interlocked and positioned by
a 2-position, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG. A
unit-mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
– regardless of the outdoor air enthalpy. Dampers return
to the fully closed position when the indoor fan motor is
de-energized. Dampers shall fully close on power loss.
12
ADDITIONAL FACTORY INSTALLED OPTIONS
• ALTERNATE INDOOR BLOWER MOTOR – For
applications with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
• CONVENIENCE OUTLET (POWERED/NON-POWERED)–
Unit can be provided with an optional 120VAC GFCI outlet
with cover on the corner of the unit housing the compressors.
• ELECTRIC HEAT - Electric Heaters range from 9 kW to
54 kW and are available in all the voltage options of the
base unit.
• PHASE MONITOR - Designed to prevent damage in outof-phase condition.
• COIL GUARD - Designed to prevent condenser coil
damage.
• BAS CONTROLS - Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
• DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally highpressure drop across the filters.
• BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
• DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest
electric heat available.
• STAINLESS STEEL HEAT EXCHANGER – For
applications in a corrosive environment, this option
provides a full stainless steel heat exchanger assembly.
• SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
• ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
• BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
• PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
• 60ºF GAS HEAT KIT – Provides an electric heat kit for the
gas compartment for use in extreme low ambient
conditions.
• ECONOMIZER (Downflow and Horizontal flow)
• POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
• DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
Unitary Products Group
246824-YTG-E-0507
REHEAT MODE SEQUENCE OF OPERATION
The reheat control board allows the user to select two different
modes of operation via a jumper connection on the board. (See
Figure 3.) Each mode is described below.
On units with economizers, the unit will not operate in the
reheat mode if there is a call for cooling and the economizer is
operating as first stage of cooling.
All safety devices function as previously described.
“NORMAL” MODE
"ALTERNATE” MODE
When the reheat control board (RCB) detects a need for dehumidification (24VAC) at "HUM" via the field supplied dehumidistat connected to RHTB-1 and RHTB-2 and there is not a call for
cooling, it energizes the hot gas relay (HGR), which energizes
the 3-way valve (SOL 3), the condenser coil valve (SOL 2), and
de-energizes the reheat coil bleed valve (SOL 1). (In the
ZR150, SOL 2 is only energized when the discharge pressure
in circuit #1 rises above 400 psig and de-energizes SOL 2 after
the discharge pressure falls below 320 psig. Both outdoor fans
of circuit #1 in the ZR150 also disengage to conserve energy.)
The Y1 signal is passed to the unit control board (UCB), which
engages circuit # 1, resulting in circuit #1 reheat mode operation.
When the RCB detects a need for dehumidification (24VAC) at
"HUM" via the field supplied dehumidistat connected to RHTB-1
and RHTB-2, and there is not a call for cooling, it energizes the
HGR, which energizes the SOL 3, SOL 2, and de-energizes
SOL 1. (In the ZR150, SOL 2 is only energized when the discharge pressure in circuit #1 rises above 400 psig and de-energizes SOL 2 after the discharge pressure falls below 320 psig.
Both outdoor fans of circuit #1 in the ZR150 also disengage to
conserve energy.) The unit then operates with circuit #1 in
reheat mode and circuit #2 in cooling mode.
When the room thermostat calls for first stage cooling, with or
without a call for dehumidification, the RCB senses a signal
through "Y1", de-energizing the HGR, which de-energizes SOL
3 and SOL 2 and energizes SOL 1, engaging circuit #1, resulting in circuit #1 cooling mode operation.
When the room thermostat calls for second stage cooling, the
RCB senses a signal through "Y1" & "Y2" and engages circuit
#1 and circuit #2 in cooling mode.
Indoor blower operation is initiated upon a call for first stage
cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not
operate in the reheat mode, even if there is a call for dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call
for heating.
Unitary Products Group
When the room thermostat calls for first stage cooling while
there is still a call for dehumidification, no operational change is
made. The call for cooling is ignored and the unit continues to
operate with circuit #1 in reheat mode and circuit #2 in cooling
mode.
When the room thermostat calls for second stage cooling, the
RCB senses a signal through "Y1" and "Y2" and de-energizes
the HGR, which de-energizes SOL 3 and SOL 2, and energizes
SOL 1. Both circuits operate in the cooling mode.
Indoor blower operation is initiated upon a call for first stage
cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not
operate in the reheat mode, even if there is still a call for dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call
for heating.
All safety devices function as previously described.
13
246824-YTG-E-0507
Reheat Control Board
R
Y1
P4
Y2
K1
G
W1
K2
W2
OCC
K4
C
K3
COM
`
P6
P5
P3
HGRR
HGR
MODE
SELECTION
JUMPER
14
HUM
DEHUMIDISTAT
HARNESS
CONNECTION
Unitary Products Group
246824-YTG-E-0507
XP078-150 Physical Data
Component
Models
XP078
XP090
XP102
XP120
XP150
6.5
7.5
8.5
10
12.5
Gross Capacity @ ARI A point (Btu)
80000
95000
104000
122000
156000
ARI net capacity (Btu)
78000
92000
100000
118000
150000
EER
11.0
11.0
11.0
11.0
11.0
SEER
-
-
-
-
-
IPLV
12.4
12.4
12.4
12.4
11.9
Nominal CFM
2600
3000
3400
4000
5000
System power (KW)
7.10
8.35
9.10
10.70
13.60
R-410a
R-410a
R-410a
R-410a
R-410a
System 1
9-0
9-8
13-8
14-0
16-0
System 2
9-4
9-0
13-0
14-0
16-0
47°F capacity rating (MBH)
78.0
92.0
94.0
110.0
144.0
System power (KW) / COP
6.5 / 3.50
7.6 / 3.50
7.8 / 3.50
9.2 / 3.50
13.2 / 3.20
17°F capacity rating (MBH
48.0
55.0
57.0
66.0
90.0
System power (KW) / COP
6.2 / 2.30
7.0 / 2.30
7.3 / 2.30
8.3 / 2.30
11.9 / 2.20
-
-
-
-
-
Length
89
89
89
89
119-7/16
Width
59
59
59
59
59
Height
42
42
50-3/4
50-3/4
50-3/4
920
920
1135
1135
1400
Scroll
Scroll
Scroll
Scroll
Scroll
2
2
2
2
2
50 / 100
50 / 100
50 / 100
50 / 100
50 / 100
23.8
23.8
29.0
29.0
47.5
2
2
2
2
2
Nominal Tonnage
ARI COOLING PERFORMANCE
Refrigerant type
Refrigerant charge (lb-oz)
ARI HEATING PERFORMANCE
HSPF (Btu/Watts-hr)
DIMENSIONS (inches)
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
20
20
20
20
15
Tube diameter (in.)
3/8
3/8
3/8
3/8
3/8
Split-face
Split-face
Split-face
Split-face
Split-face
13.2
Circuitry Type
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.6
10.6
13.2
13.2
Rows
3
3
4
4
4
Fins per inch
15
15
15
15
15
Tube diameter
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Split-face
Split-face
Split-face
Split-face
Split-face
TXV
TXV
TXV
TXV
TXV
Refrigerant control
Unitary Products Group
19
246824-YTG-E-0507
XP078-150 Physical Data (Continued)
Models
Component
XP078
XP090
XP102
XP120
XP150
6.5
7.5
8.5
10
12.5
2
2
2
2
4
Nominal Tonnage
CONDENSER FAN DATA
Quantity
Fan diameter (Inch)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
No. speeds
1
1
1
1
1
Number of motors
2
2
2
2
4
1/3
1/3
1/3
1/3
1/3
Motor HP each
RPM
850
850
850
850
850
Nominal total CFM
6800
6800
6800
6800
14000
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
1
1
12 x 12
12 x 12
15 x 15
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
2
1-1/2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
56
56
56
184T
Frame size
FILTERS
Quantity - Size
4 - 25 x 16 x 2
4 - 25 x 16 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
ZH/ZR/XP078-150 Unit Limitations
Unit Limitations
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
20
Model
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
Unit Voltage
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
Unitary Products Group
246824-YTG-E-0507
XP078-150 Cooling Capacities
XP078 (6.5 Ton)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
101.5
92.3
83.1
76.7
105.5
95.9
86.3
79.8
78.2
109.5
99.6
89.6
82.8
81.2
113.6
103.2
92.9
85.8
84.2
105.5
95.0
87.7
86.1
107.8
97.0
89.7
87.9
4.7
4.8
4.9
4.8
4.8
4.8
4.9
4.8
4.8
4.8
4.9
4.9
4.8
4.9
4.8
4.9
5.0
4.9
4.9
4.9
4.9
4.8
4.9
4.8
4.9
4.8
4.8
41.0
52.5
64.0
76.7
45.8
58.9
72.0
79.8
78.2
50.6
65.3
79.9
82.8
81.2
55.4
71.7
87.9
85.8
84.2
76.3
92.5
87.7
86.1
80.9
97.0
89.7
87.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
84.3
77.8
71.3
65.2
88.0
81.2
74.4
68.0
68.8
91.7
84.6
77.5
70.8
71.7
95.3
88.0
80.6
73.7
74.6
90.2
82.6
75.5
76.5
92.4
84.7
77.4
78.3
6.6
6.5
6.4
6.4
6.6
6.4
6.3
6.4
6.4
6.5
6.4
6.3
6.3
6.3
6.5
6.3
6.2
6.3
6.3
6.4
6.3
6.3
6.3
6.4
6.3
6.3
6.3
37.4
48.6
59.9
65.2
42.5
54.7
66.8
68.0
68.8
47.7
60.7
73.7
70.8
71.7
52.9
66.7
80.6
73.7
74.6
71.4
82.6
75.5
76.5
76.1
84.7
77.4
78.3
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
33.6
26.4
92.9
5.7
45.3
38.2
31.1
85.1
5.6
57.1
50.0
42.9
35.8
77.2
5.6
74.1
60.8
53.6
46.5
39.4
71.0
5.6
37.6
29.4
96.8
5.7
50.7
42.5
34.3
88.6
5.6
63.8
55.6
47.4
39.2
80.4
5.6
78.0
67.5
59.3
51.1
42.9
73.9
5.6
78.2
70.1
61.9
53.7
45.5
73.5
5.6
41.6
32.3
100.6
5.7
56.0
46.7
37.4
92.1
5.6
70.4
61.1
51.8
42.6
83.6
5.6
81.9
74.3
65.0
55.7
46.5
76.8
5.6
81.2
77.2
67.9
58.6
49.3
76.5
5.6
45.6
35.3
104.4
5.6
61.3
51.0
40.6
95.6
5.6
77.0
66.7
56.3
46.0
86.8
5.6
85.8
81.1
70.7
60.3
50.0
79.8
5.6
84.2
84.2
73.8
63.5
53.1
79.4
5.6
65.0
53.7
42.5
97.9
5.6
81.6
70.3
59.0
47.8
88.8
5.6
87.7
85.4
74.1
62.8
51.6
81.6
5.6
86.1
86.1
74.8
63.5
52.3
81.3
5.6
68.7
56.5
44.3
100.1
5.6
86.1
73.9
61.7
49.6
90.9
5.6
89.7
89.7
77.5
65.3
53.1
83.5
5.6
87.9
87.9
75.7
63.6
51.4
83.1
5.6
95°F
30.6
23.6
78.5
7.4
41.7
34.7
27.7
72.1
7.3
52.7
45.7
38.7
31.7
65.7
7.2
65.2
56.2
49.2
42.3
35.3
59.9
7.2
34.3
26.1
81.4
7.3
46.5
38.2
30.0
74.8
7.2
58.6
50.4
42.2
33.9
68.2
7.2
68.0
62.1
53.8
45.6
37.4
62.1
7.2
68.8
62.8
54.6
46.4
38.2
64.4
7.2
38.0
28.5
84.3
7.3
51.3
41.8
32.4
77.4
7.2
64.5
55.1
45.6
36.2
70.6
7.1
70.8
67.9
58.4
49.0
39.5
64.3
7.1
71.7
68.7
59.3
49.8
40.4
66.7
7.2
41.6
31.0
87.2
7.2
56.1
45.4
34.7
80.1
7.2
70.5
59.8
49.1
38.5
73.1
7.1
73.7
73.7
63.0
52.3
41.7
66.6
7.1
74.6
74.6
63.9
53.2
42.6
69.0
7.1
59.9
48.4
36.9
81.8
7.2
75.3
63.8
52.3
40.8
74.6
7.1
75.5
75.5
64.0
52.6
41.1
68.0
7.1
76.5
76.5
65.0
53.5
42.0
70.5
7.2
63.8
51.5
39.2
83.5
7.2
80.1
67.8
55.5
43.2
76.2
7.2
77.4
77.4
65.1
52.8
40.5
69.4
7.2
78.3
78.3
66.0
53.7
41.5
72.0
7.2
90
39.2
50.6
62.0
71.0
44.2
56.8
69.4
73.9
73.5
49.2
63.0
76.8
76.8
76.5
54.1
69.2
84.3
79.8
79.4
73.8
87.6
81.6
81.3
78.5
90.9
83.5
83.1
33.1
46.3
59.6
59.9
40.2
52.2
64.1
62.1
64.4
47.4
58.0
68.6
64.3
66.7
54.5
63.8
73.1
66.6
69.0
68.3
74.6
68.0
70.5
72.7
76.2
69.4
72.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
32.1
25.0
43.5
36.4
29.4
54.9
47.8
40.8
33.7
69.6
58.5
51.4
44.4
36.0
27.7
48.6
40.4
32.1
61.2
53.0
44.8
36.5
73.0
64.8
56.6
48.4
73.5
66.5
58.3
50.1
39.8
30.4
53.6
44.3
34.9
67.5
58.1
48.7
39.4
76.4
71.1
61.7
52.4
76.5
72.9
63.6
54.2
43.6
33.1
58.7
48.2
37.7
73.8
63.2
52.7
42.2
79.8
77.4
66.9
56.3
79.4
79.4
68.9
58.4
62.5
51.1
39.7
78.4
67.1
55.7
44.3
81.6
80.4
69.1
57.7
81.3
81.3
69.9
58.5
66.2
54.0
41.8
83.1
70.9
58.6
46.4
83.5
83.5
71.3
59.0
83.1
83.1
70.9
58.7
105°F
28.6
21.6
39.4
32.4
25.4
50.2
43.2
36.2
29.2
59.9
50.6
43.6
36.6
32.1
23.9
44.0
35.8
27.6
55.9
47.7
39.6
31.4
62.1
55.9
47.7
39.6
64.4
58.0
49.8
41.6
35.6
26.2
48.6
39.2
29.9
61.7
52.3
42.9
33.5
64.3
61.2
51.9
42.5
66.7
63.5
54.1
44.8
39.0
28.5
53.2
42.6
32.1
67.4
56.8
46.3
35.7
66.6
66.6
56.0
45.4
69.0
69.0
58.5
47.9
56.9
45.5
34.1
70.6
60.6
49.3
37.9
68.0
68.0
56.6
45.2
70.5
70.5
59.1
47.8
60.5
48.4
36.2
73.9
64.5
52.3
40.1
69.4
69.4
57.2
45.1
72.0
72.0
59.8
47.6
65
37.3
40.2
41.8
43.0
44.8
45.8
47.8
46.3
47.1
46.8
46.4
29.7
31.4
33.5
33.1
35.4
34.8
37.3
33.9
36.4
32.9
35.5
51
246824-YTG-E-0507
XP078 (6.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
72.6
66.3
60.1
54.6
74.7
68.3
61.9
56.2
60.0
76.9
70.3
63.7
57.8
61.8
79.0
72.3
65.5
59.4
63.5
73.5
66.6
60.4
64.5
74.7
67.7
61.4
65.6
8.1
8.1
8.0
8.0
8.1
8.0
8.0
7.9
8.0
8.1
8.0
8.0
7.9
8.0
8.0
8.0
7.9
7.9
8.0
8.0
8.0
7.9
8.0
8.1
8.0
8.0
8.0
28.9
44.0
59.2
54.6
38.0
49.6
61.3
56.2
60.0
47.1
55.3
63.4
57.8
61.8
56.2
60.9
65.5
59.4
63.5
65.1
66.6
60.4
64.5
69.4
67.7
61.4
65.6
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
26.6
19.6
66.7
8.9
37.1
30.2
23.2
60.6
8.9
47.6
40.7
33.8
26.8
54.5
8.9
54.6
44.9
38.0
31.0
24.1
49.3
8.8
29.8
21.7
68.1
8.9
41.5
33.4
25.3
61.9
8.8
53.2
45.1
37.0
28.8
55.7
8.8
56.2
49.8
41.6
33.5
25.4
50.3
8.7
60.0
53.1
45.0
36.9
28.8
55.6
8.9
33.1
23.8
69.5
8.8
46.0
36.7
27.4
63.2
8.8
58.8
49.5
40.2
30.9
56.8
8.8
57.8
54.6
45.3
36.0
26.7
51.3
8.7
61.8
58.3
49.0
39.7
30.4
56.8
8.8
36.4
25.9
70.9
8.8
50.4
39.9
29.4
64.4
8.8
64.3
53.9
43.4
32.9
58.0
8.8
59.4
59.4
49.0
38.5
28.0
52.3
8.7
63.5
63.5
53.0
42.5
32.1
57.9
8.8
53.8
42.6
31.3
65.1
8.8
66.0
57.5
46.2
35.0
58.6
8.8
60.4
60.4
49.2
37.9
26.6
52.9
8.7
64.5
64.5
53.3
42.0
30.8
58.6
8.9
57.3
45.3
33.2
65.8
8.9
67.7
61.1
49.1
37.0
59.2
8.9
61.4
61.4
49.4
37.3
25.3
53.4
8.8
65.6
65.6
53.5
41.5
29.5
59.2
8.9
90
29.0
41.7
54.5
49.3
38.6
47.1
55.7
50.3
55.6
48.2
52.5
56.8
51.3
56.8
57.8
57.9
58.0
52.3
57.9
62.0
58.6
52.9
58.6
65.8
59.2
53.4
59.2
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
22.9
17.6
34.8
27.9
21.0
45.1
38.2
31.3
24.4
49.3
39.3
32.3
25.4
27.6
19.5
39.1
31.0
22.9
50.5
42.4
34.4
26.3
50.3
43.6
35.5
27.5
55.6
48.3
40.2
32.2
32.3
21.5
43.3
34.1
24.8
55.9
46.7
37.4
28.2
51.3
48.0
38.7
29.5
56.8
53.1
43.9
34.7
37.1
23.4
47.5
37.2
26.8
58.0
50.9
40.5
30.1
52.3
52.3
42.0
31.6
57.9
57.9
47.6
37.2
50.8
39.7
28.5
58.6
54.3
43.2
32.0
52.9
52.9
41.7
30.6
58.6
58.6
47.4
36.3
54.1
42.2
30.3
59.2
57.8
45.9
33.9
53.4
53.4
41.5
29.6
59.2
59.2
47.3
35.4
65
18.5
19.4
24.1
20.3
25.5
21.2
26.8
19.4
25.1
17.7
23.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
52
Unitary Products Group
246824-YTG-E-0507
XP090 (7.5 Ton)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
117.7
108.9
100.0
94.6
122.0
112.8
103.6
98.0
94.3
126.2
116.7
107.2
101.4
97.6
130.4
120.6
110.7
104.7
100.8
122.0
112.1
106.0
102.1
123.5
113.4
107.2
103.3
5.8
5.7
5.7
5.6
5.8
5.7
5.7
5.6
5.6
5.8
5.8
5.7
5.6
5.6
5.8
5.8
5.7
5.6
5.6
5.8
5.7
5.6
5.7
5.8
5.7
5.7
5.7
48.9
63.3
77.7
94.6
54.1
69.7
85.4
98.0
94.3
59.3
76.2
93.0
101.4
97.6
64.5
82.6
100.7
104.7
100.8
87.6
107.1
106.0
102.1
92.5
113.4
107.2
103.3
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
104.4
95.9
87.4
79.8
107.4
98.7
89.9
82.1
81.9
110.4
101.4
92.4
84.4
84.2
113.4
104.1
94.9
86.7
86.5
104.6
95.3
87.0
86.8
105.0
95.7
87.4
87.2
7.4
7.3
7.2
7.2
7.4
7.3
7.3
7.2
7.2
7.4
7.4
7.3
7.2
7.2
7.5
7.4
7.3
7.2
7.2
7.4
7.3
7.3
7.3
7.4
7.3
7.3
7.3
43.3
57.2
71.0
79.8
47.9
63.0
78.1
82.1
81.9
52.6
68.9
85.2
84.4
84.2
57.3
74.8
92.2
86.7
86.5
80.2
94.0
87.0
86.8
85.7
95.7
87.4
87.2
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
40.3
31.8
111.1
6.6
54.7
46.2
37.6
102.4
6.5
69.2
60.6
52.0
43.4
93.7
6.4
85.6
75.3
66.8
58.2
49.6
87.2
6.4
44.3
34.5
114.7
6.6
59.9
50.1
40.3
105.7
6.5
75.6
65.7
55.9
46.1
96.8
6.5
92.0
81.7
71.9
62.1
52.3
90.1
6.4
94.3
85.9
76.1
66.2
56.4
88.1
6.4
48.2
37.2
118.3
6.6
65.1
54.0
43.0
109.0
6.6
82.0
70.9
59.8
48.8
99.8
6.5
98.3
88.2
77.1
66.0
55.0
92.9
6.4
97.6
92.6
81.5
70.5
59.4
90.9
6.4
52.2
39.9
121.9
6.7
70.3
58.0
45.6
112.3
6.6
88.4
76.1
63.7
51.4
102.8
6.5
104.7 94.6
82.3
69.9
57.6
95.7
6.4
100.8 99.3
87.0
74.7
62.4
93.7
6.4
74.4
61.3
48.1
113.3
6.6
93.5
80.4
67.2
54.1
103.7
6.5
106.0 100.9 87.8
74.6
61.5
96.5
6.5
102.1 101.3 88.2
75.0
61.9
94.4
6.5
78.6
64.6
50.6
114.2
6.6
98.7
84.7
70.7
56.7
104.6
6.5
107.2 107.2 93.3
79.3
65.3
97.3
6.5
103.3 103.3 89.3
75.3
61.3
95.2
6.5
95°F
35.0
26.8
96.3
8.3
48.9
40.7
32.4
88.5
8.2
62.8
54.5
46.3
38.0
80.7
8.1
79.8
67.3
59.0
50.8
42.5
74.7
8.1
38.5
29.1
98.6
8.3
53.6
44.2
34.8
90.6
8.3
68.7
59.3
49.8
40.4
82.6
8.2
82.1
73.1
63.7
54.3
44.8
76.5
8.1
81.9
75.5
66.1
56.7
47.3
76.1
8.1
42.0
31.4
100.9
8.4
58.3
47.7
37.1
92.7
8.3
74.6
64.0
53.4
42.8
84.5
8.2
84.4
78.9
68.4
57.8
47.2
78.2
8.1
84.2
81.6
71.0
60.4
49.8
77.9
8.1
45.5
33.7
103.1
8.4
63.0
51.2
39.5
94.8
8.3
80.5
68.7
57.0
45.2
86.4
8.2
86.7
84.8
73.0
61.3
49.5
80.0
8.2
86.5
87.6
75.8
64.1
52.3
79.6
8.2
67.5
54.7
41.9
94.9
8.3
86.1
73.4
60.6
47.8
86.5
8.2
87.0
86.1
73.3
60.6
47.8
80.1
8.2
86.8
87.4
74.6
61.8
49.1
79.7
8.2
71.9
58.2
44.4
95.0
8.3
91.8
78.0
64.2
50.4
86.6
8.3
87.4
87.4
73.6
59.8
46.0
80.1
8.2
87.2
87.2
73.4
59.6
45.8
79.8
8.2
90
46.1
60.2
74.4
87.2
51.0
66.4
81.7
90.1
88.1
55.9
72.5
89.1
92.9
90.9
60.9
78.7
96.5
95.7
93.7
83.9
100.5
96.5
94.4
89.1
104.6
97.3
95.2
37.8
53.5
69.2
74.7
43.9
59.2
74.5
76.5
76.1
50.1
64.9
79.8
78.2
77.9
56.2
70.6
85.1
80.0
79.6
75.6
85.8
80.1
79.7
80.6
86.6
80.1
79.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
37.7
29.3
51.8
43.4
35.0
66.0
57.6
49.1
40.7
82.7
71.3
62.9
54.5
41.4
31.8
56.8
47.1
37.5
72.1
62.5
52.9
43.3
87.0
77.4
67.8
58.2
88.1
80.7
71.1
61.5
45.1
34.3
61.7
50.9
40.0
78.3
67.4
56.6
45.8
91.4
83.6
72.7
61.9
90.9
87.1
76.3
65.4
48.8
36.8
66.6
54.6
42.6
84.4
72.4
60.4
48.3
95.7
89.7
77.6
65.6
93.7
93.5
81.4
69.4
70.9
58.0
45.0
89.8
76.9
63.9
51.0
96.5
93.5
80.5
67.6
94.4
94.4
81.4
68.4
75.2
61.4
47.5
95.2
81.4
67.5
53.6
97.3
97.3
83.4
69.6
95.2
95.2
81.3
67.5
105°F
31.4
23.4
45.4
37.4
29.3
59.4
51.4
43.4
35.3
74.7
62.6
54.6
46.5
34.7
25.5
50.0
40.8
31.6
65.3
56.1
46.9
37.7
76.5
68.3
59.1
49.9
76.1
69.7
60.5
51.3
38.0
27.6
54.5
44.2
33.8
71.1
60.7
50.4
40.0
78.2
74.0
63.6
53.2
77.9
75.5
65.2
54.8
41.3
29.7
59.1
47.6
36.0
76.9
65.4
53.9
42.3
80.0
79.6
68.1
56.6
79.6
81.3
69.8
58.3
63.1
50.7
38.2
80.8
69.7
57.2
44.7
80.1
79.9
67.4
54.9
79.7
80.6
68.1
55.6
67.2
53.8
40.3
84.6
73.9
60.5
47.1
80.1
80.1
66.7
53.3
79.8
79.8
66.4
52.9
65
46.1
48.6
51.8
51.1
54.6
53.6
57.4
54.6
55.5
55.7
53.6
38.5
40.7
42.1
42.9
44.4
45.1
46.7
42.5
43.1
39.9
39.5
53
246824-YTG-E-0507
XP090 (7.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
88.3
81.1
74.0
69.6
89.8
82.6
75.3
70.8
70.3
91.4
84.0
76.6
72.0
71.5
92.9
85.4
77.9
73.3
72.7
85.2
77.7
73.1
72.6
85.0
77.5
72.9
72.4
9.2
9.1
9.1
9.0
9.3
9.2
9.1
9.1
9.1
9.3
9.2
9.1
9.1
9.1
9.3
9.2
9.2
9.1
9.1
9.2
9.2
9.1
9.1
9.3
9.2
9.1
9.1
32.2
49.8
67.3
69.6
39.9
55.3
70.8
70.8
70.3
47.5
60.9
74.3
72.0
71.5
55.1
66.5
77.9
73.3
72.7
71.0
77.7
73.1
72.6
75.5
77.5
72.9
72.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
27.8
20.0
80.3
10.2
41.9
34.1
26.3
73.8
10.1
56.1
48.2
40.4
32.6
67.3
10.0
69.6
57.9
50.1
42.3
34.5
64.5
10.0
30.9
21.9
81.1
10.2
46.4
37.4
28.4
74.5
10.1
61.8
52.9
43.9
34.9
68.0
10.0
70.8
63.4
54.5
45.5
36.5
65.2
10.0
70.3
63.9
54.9
46.0
37.0
64.5
10.0
34.0
23.8
81.9
10.2
50.8
40.6
30.5
75.3
10.1
67.6
57.5
47.3
37.2
68.7
10.1
72.0
69.0
58.8
48.7
38.5
65.9
10.0
71.5
69.5
59.4
49.2
39.1
65.2
10.0
37.0
25.7
82.7
10.2
55.2
43.9
32.6
76.0
10.2
73.4
62.1
50.8
39.5
69.3
10.1
73.3
74.5
63.2
51.9
40.6
66.5
10.1
72.7
75.1
63.8
52.5
41.2
65.9
10.0
58.8
46.6
34.5
75.5
10.2
75.4
65.9
53.8
41.6
68.9
10.1
73.1
73.7
61.5
49.3
37.1
66.1
10.1
72.6
73.7
61.5
49.4
37.2
65.4
10.1
62.4
49.4
36.3
75.0
10.2
77.5
69.8
56.7
43.7
68.4
10.1
72.9
72.9
59.8
46.8
33.7
65.6
10.1
72.4
72.4
59.3
46.2
33.2
65.0
10.1
90
26.0
46.1
65.7
64.5
35.8
51.5
67.2
65.2
64.5
45.6
56.9
68.7
65.9
65.2
55.4
62.4
69.3
66.5
65.9
66.4
68.9
66.1
65.4
70.4
68.4
65.6
65.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
24.0
16.6
38.5
30.9
23.3
52.7
45.1
37.5
29.9
64.5
53.2
45.6
38.0
27.1
18.3
42.7
34.0
25.2
58.4
49.6
40.9
32.1
65.2
58.6
49.9
41.1
64.5
58.1
49.4
40.6
30.2
20.0
47.0
37.1
27.2
64.1
54.2
44.3
34.3
65.9
64.0
54.1
44.1
65.2
63.5
53.6
43.6
33.3
21.7
51.3
40.2
29.1
69.3
58.7
47.7
36.6
66.5
66.5
58.3
47.2
65.9
65.9
57.7
46.7
54.5
42.6
30.7
68.9
62.2
50.3
38.4
66.1
66.1
55.6
43.7
65.4
65.4
55.0
43.1
57.7
45.0
32.3
68.4
65.7
53.0
40.3
65.6
65.6
52.9
40.2
65.0
65.0
52.3
39.6
65
30.4
32.3
31.8
34.2
33.7
36.1
35.6
31.8
31.2
27.5
26.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
54
Unitary Products Group
246824-YTG-E-0507
XP102 (8.5 Ton)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
120.9
113.7
106.4
96.7
126.2
118.6
110.9
100.9
100.3
131.4
123.5
115.5
105.1
104.4
136.7
128.4
120.1
109.3
108.6
132.2
123.6
112.5
111.8
136.0
127.2
115.7
115.0
6.2
6.1
6.0
5.9
6.2
6.1
6.0
6.0
5.9
6.2
6.1
6.0
6.0
6.0
6.2
6.1
6.0
6.0
6.0
6.2
6.1
6.0
6.0
6.3
6.2
6.1
6.1
58.3
69.9
81.4
96.7
62.1
78.1
94.1
100.9
100.3
65.9
86.3
106.8
105.1
104.4
69.7
94.6
119.5
109.3
108.6
101.6
123.3
112.5
111.8
108.6
127.2
115.7
115.0
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
116.2
105.1
94.0
87.9
120.4
108.9
97.4
91.1
91.1
124.5
112.6
100.7
94.2
94.2
128.7
116.4
104.1
97.4
97.4
118.8
106.3
99.4
99.4
121.3
108.4
101.4
101.4
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.7
7.7
7.9
7.9
7.8
7.7
7.7
7.9
7.9
7.9
7.8
7.8
7.9
7.9
7.8
7.8
7.9
7.9
7.8
7.8
46.9
64.7
82.5
87.9
56.5
73.1
89.7
91.1
91.1
66.1
81.5
96.9
94.2
94.2
75.7
89.9
104.1
97.4
97.4
96.9
106.3
99.4
99.4
103.9
108.4
101.4
101.4
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
45.7
36.0
118.6
7.0
60.2
50.5
40.8
109.4
6.9
74.6
65.0
55.3
45.6
100.2
6.9
94.3
79.3
69.6
59.9
50.2
92.3
6.8
51.0
39.8
123.3
7.0
67.0
55.8
44.7
113.7
7.0
83.0
71.8
60.7
49.5
104.2
6.9
99.3
87.7
76.5
65.4
54.3
96.0
6.8
100.5 89.7
78.6
67.5
56.3
95.7
6.8
56.2
43.6
128.0
7.0
73.7
61.2
48.6
118.1
7.0
91.3
78.7
66.1
53.5
108.1
6.9
104.3 96.1
83.5
70.9
58.3
99.6
6.9
104.6 98.3
85.8
73.2
60.6
99.3
6.9
61.5
47.5
132.7
7.1
80.5
66.5
52.5
122.4
7.0
99.6
85.6
71.5
57.5
112.1
7.0
109.3 104.5 90.4
76.4
62.4
103.3
6.9
108.6 106.9 92.9
78.9
64.9
103.0
6.9
86.1
70.7
55.3
125.5
7.1
106.7 91.0
75.5
60.1
115.0
7.0
112.5 110.1 94.7
79.2
63.8
105.9
6.9
111.8 111.0 95.5
80.1
64.7
105.6
6.9
91.8
74.9
58.1
128.6
7.1
113.8 96.4
79.5
62.7
117.8
7.0
115.7 115.7 98.9
82.1
65.2
108.6
7.0
115.0 115.0 98.2
81.4
64.5
108.2
7.0
95°F
39.8
29.8
107.5
8.9
54.7
44.7
34.7
97.2
8.8
69.6
59.6
49.5
39.5
86.8
8.8
87.9
71.6
61.6
51.5
41.5
80.7
8.7
44.9
33.3
111.4
8.9
61.5
49.9
38.3
100.6
8.9
78.1
66.5
54.9
43.3
89.9
8.8
91.1
79.9
68.3
56.7
45.1
83.5
8.7
90.8
79.2
67.6
56.0
44.4
85.1
8.8
50.0
36.8
115.2
9.0
68.3
55.1
41.9
104.0
8.9
86.6
73.4
60.2
47.0
92.9
8.9
94.2
88.2
75.0
61.8
48.6
86.4
8.8
94.1
87.5
74.3
61.0
47.8
88.0
8.8
55.0
40.2
119.0
9.0
75.1
60.3
45.5
107.5
9.0
95.2
80.4
65.6
50.8
96.0
8.9
97.4
96.6
81.8
67.0
52.2
89.2
8.8
97.4
95.7
80.9
66.1
51.3
90.9
8.8
80.7
64.4
48.2
109.5
9.0
101.8 85.9
69.7
53.4
97.8
8.9
99.4
99.0
82.8
66.5
50.3
90.9
8.8
99.4
98.6
82.3
66.1
49.9
92.6
8.8
86.2
68.6
50.9
111.6
9.0
108.4 91.4
73.8
56.1
99.7
8.9
101.4 101.4 83.8
66.1
48.4
92.6
8.9
101.4 101.4 83.8
66.1
48.5
94.4
8.9
90
52.6
67.3
82.0
92.3
59.3
75.6
91.9
96.0
95.7
66.0
83.9
101.8
99.6
99.3
72.7
92.2
111.8
103.3
103.0
99.2
114.8
105.9
105.6
106.2
117.8
108.6
108.2
44.1
62.6
81.1
80.7
56.2
71.1
86.0
83.5
85.1
68.4
79.7
91.0
86.4
88.0
80.5
88.3
96.0
89.2
90.9
95.4
97.8
90.9
92.6
102.5
99.7
92.6
94.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
42.8
32.9
57.4
47.6
37.7
72.1
62.3
52.4
42.5
91.1
75.4
65.6
55.7
47.9
36.6
64.2
52.9
41.5
80.5
69.2
57.8
46.4
95.2
83.8
72.4
61.0
95.7
84.5
73.1
61.7
53.1
40.2
71.0
58.1
45.2
89.0
76.1
63.2
50.3
99.2
92.2
79.3
66.4
99.3
92.9
80.0
67.1
58.3
43.8
77.8
63.4
49.0
97.4
83.0
68.5
54.1
103.3 100.5 86.1
71.7
103.0 101.3 86.9
72.5
83.4
67.6
51.8
104.3 88.4
72.6
56.8
105.9 104.5 88.7
72.9
105.6 104.8 88.9
73.1
89.0
71.8
54.5
111.1 93.9
76.7
59.4
108.6 108.6 91.3
74.1
108.2 108.2 91.0
73.7
105°F
37.9
28.3
52.5
42.4
32.3
67.1
56.5
46.4
36.3
80.7
68.6
58.5
48.4
43.5
31.8
59.4
47.6
35.9
75.2
63.5
51.7
40.0
83.5
77.0
65.3
53.5
85.0
73.3
61.6
49.8
49.2
35.3
66.3
52.9
39.4
83.4
70.4
57.0
43.6
86.4
85.5
72.1
58.7
87.9
81.4
67.9
54.5
54.8
38.8
73.2
58.1
43.0
91.5
77.4
62.3
47.2
89.2
93.9
78.9
63.8
90.9
89.4
74.3
59.2
78.8
62.2
45.6
95.6
82.9
66.3
49.7
90.9
93.3
76.7
60.1
92.6
91.9
75.3
58.7
84.4
66.3
48.2
99.7
88.4
70.3
52.2
92.6
92.6
74.6
56.5
94.4
94.4
76.3
58.2
65
45.9
49.7
50.3
53.5
54.2
57.3
58.1
57.1
57.3
56.8
56.5
38.3
41.8
38.1
45.2
41.1
48.7
44.1
43.5
42.1
38.4
40.1
55
246824-YTG-E-0507
XP102 (8.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
98.9
89.2
79.6
73.4
102.3
92.4
82.4
76.0
79.1
105.8
95.5
85.1
78.5
81.8
109.2
98.6
87.9
81.1
84.4
100.3
89.4
82.5
85.9
101.9
90.9
83.9
87.3
10.0
9.9
9.8
9.7
10.0
9.9
9.8
9.8
9.8
10.1
10.0
9.9
9.8
9.8
10.1
10.0
9.9
9.8
9.9
10.0
9.9
9.9
9.9
10.1
10.0
9.9
9.9
41.2
60.4
79.6
73.4
55.9
69.1
82.4
76.0
79.1
70.7
77.9
85.1
78.5
81.8
85.4
86.6
87.9
81.1
84.4
93.9
89.4
82.5
85.9
101.1
90.9
83.9
87.3
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
36.0
26.8
90.2
11.1
50.3
40.1
30.0
81.3
11.0
64.5
53.4
43.3
33.2
72.4
10.9
73.4
65.6
55.4
45.3
35.2
66.2
10.8
42.2
30.3
93.3
11.1
57.3
45.4
33.5
84.1
11.0
72.3
60.5
48.6
36.7
74.9
10.9
76.0
74.1
62.3
50.4
38.5
68.5
10.8
79.1
67.5
55.6
43.7
31.8
73.1
10.8
48.4
33.8
96.4
11.2
64.3
50.6
37.0
86.9
11.0
80.1
67.5
53.8
40.2
77.3
10.9
78.5
82.7
69.1
55.5
41.8
70.7
10.8
81.8
75.3
61.6
48.0
34.4
75.6
10.9
54.6
37.3
99.5
11.2
71.3
55.9
40.5
89.7
11.1
87.9
74.5
59.1
43.7
79.8
10.9
81.1
91.3
75.9
60.6
45.2
73.0
10.9
84.4
83.1
67.7
52.3
37.0
78.0
10.9
76.9
60.0
43.0
91.0
11.1
89.4
79.9
63.0
46.0
81.0
11.0
82.5
87.6
70.7
53.7
36.8
74.0
10.9
85.9
85.2
68.3
51.3
34.4
79.1
10.9
82.6
64.1
45.6
92.3
11.1
90.9
85.4
66.8
48.3
82.1
11.0
83.9
83.9
65.4
46.8
28.3
75.1
10.9
87.3
87.3
68.8
50.3
31.8
80.3
11.0
90
44.1
58.2
72.4
66.2
59.4
67.2
74.9
68.5
73.1
74.8
76.1
77.3
70.7
75.6
90.2
85.0
79.8
73.0
78.0
91.0
81.0
74.0
79.1
92.3
82.1
75.1
80.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
31.8
25.3
48.0
37.8
27.6
62.0
50.4
40.2
30.0
66.2
66.2
52.3
42.2
40.8
28.8
55.1
43.1
31.1
69.4
57.4
45.4
33.4
68.5
68.5
59.2
47.2
73.1
61.6
49.6
37.6
49.9
32.3
62.2
48.4
34.6
76.9
64.5
50.6
36.8
70.7
70.7
66.1
52.3
75.6
69.2
55.3
41.5
58.9
35.9
69.4
53.7
38.0
79.8
71.5
55.8
40.2
73.0
73.0
73.0
57.4
78.0
76.8
61.1
45.5
75.1
57.8
40.5
81.0
76.9
59.6
42.3
74.0
74.0
64.6
47.3
79.1
78.5
61.2
43.9
80.8
61.8
42.9
82.1
82.1
63.4
44.4
75.1
75.1
56.2
37.2
80.3
80.3
61.3
42.4
65
32.0
35.2
25.5
38.5
27.7
41.7
29.8
30.0
26.6
18.3
23.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
56
Unitary Products Group
246824-YTG-E-0507
XP120 (10 Ton)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
132.6
125.0
117.5
105.6
142.4
134.2
126.1
113.4
111.1
152.2
143.4
134.6
121.2
118.8
162.0
152.6
143.2
128.9
126.4
153.5
144.1
129.7
127.1
154.4
145.0
130.4
127.9
6.7
6.9
7.0
6.6
6.8
7.0
7.1
6.7
6.9
6.9
7.1
7.2
6.8
7.0
7.0
7.2
7.3
6.9
7.1
7.0
7.2
6.8
7.0
6.9
7.1
6.6
6.8
57.3
74.4
91.5
105.6
64.4
86.2
108.1
113.4
111.1
71.5
98.1
124.6
121.2
118.8
78.6
109.9
141.1
128.9
126.4
115.1
143.0
129.7
127.1
120.3
145.0
130.4
127.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
129.5
118.6
107.8
101.0
134.9
123.6
112.3
105.3
104.0
140.4
128.6
116.9
109.6
108.2
145.8
133.6
121.4
113.8
112.5
136.1
123.6
115.9
114.5
138.5
125.9
118.0
116.6
9.2
9.1
9.0
9.0
9.2
9.1
9.1
9.0
9.0
9.3
9.2
9.1
9.0
9.1
9.3
9.2
9.1
9.0
9.1
9.2
9.1
9.0
9.1
9.2
9.1
9.0
9.1
54.8
75.0
95.2
101.0
64.6
84.3
103.9
105.3
104.0
74.3
93.5
112.7
109.6
108.2
84.1
102.7
121.4
113.8
112.5
109.7
123.6
115.9
114.5
116.6
125.9
118.0
116.6
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
45.8
36.7
131.0
8.0
65.3
56.2
47.1
121.8
8.0
84.9
75.8
66.7
57.6
112.6
8.0
105.6 91.5
82.4
73.3
64.2
103.3
7.8
52.7
40.9
138.6
8.0
74.5
62.8
51.0
128.9
8.1
96.3
84.6
72.9
61.1
119.2
8.1
113.4 102.2 90.5
78.7
67.0
109.3
7.8
111.1 103.3 91.6
79.9
68.1
107.6
8.0
59.6
45.2
146.3
8.1
83.7
69.3
55.0
136.0
8.1
107.8 93.4
79.1
64.7
125.8
8.1
121.2 112.9 98.5
84.1
69.8
115.4
7.9
118.8 114.1 99.7
85.4
71.0
113.5
8.0
66.5
49.5
153.9
8.2
92.9
75.9
58.9
143.1
8.2
119.3 102.3 85.3
68.3
132.3
8.2
128.9 123.5 106.5 89.5
72.6
121.4
8.0
126.4 124.9 107.9 90.9
73.9
119.4
8.1
97.2
79.4
61.5
144.8
8.1
124.8 107.0 89.1
71.2
133.9
8.1
129.7 127.0 109.1 91.2
73.4
122.8
7.9
127.1 126.4 108.5 90.6
72.7
120.8
8.0
101.6 82.8
64.1
146.5
8.1
130.4 111.6 92.9
74.1
135.4
8.1
130.4 130.4 111.7 92.9
74.2
124.2
7.8
127.9 127.9 109.1 90.3
71.6
122.2
8.0
95°F
45.7
34.2
120.4
10.4
63.5
51.9
40.4
109.9
10.3
81.2
69.7
58.1
46.6
99.5
10.2
101.0 83.6
72.0
60.5
48.9
93.0
10.1
51.2
37.9
125.1
10.4
70.9
57.6
44.3
114.2
10.3
90.6
77.3
63.9
50.6
103.4
10.2
105.3 92.7
79.4
66.0
52.7
96.7
10.2
104.0 92.8
79.5
66.1
52.8
95.6
10.2
56.8
41.6
129.9
10.5
78.4
63.3
48.2
118.6
10.4
100.0 84.9
69.8
54.7
107.3
10.3
109.6 101.8 86.7
71.6
56.5
100.4
10.2
108.2 102.0 86.8
71.7
56.6
99.2
10.3
62.3
45.4
134.6
10.5
85.8
69.0
52.1
122.9
10.5
109.4 92.5
75.6
58.7
111.2
10.4
113.8 111.0 94.1
77.2
60.3
104.0
10.3
112.5 111.1 94.2
77.3
60.4
102.8
10.3
91.5
73.4
55.3
124.7
10.4
116.6 98.5
80.4
62.2
112.9
10.3
115.9 114.5 96.4
78.2
60.1
105.6
10.3
114.5 113.8 95.7
77.6
59.5
104.4
10.3
97.2
77.9
58.5
126.6
10.4
123.8 104.5 85.1
65.7
114.5
10.3
118.0 118.0 98.6
79.3
59.9
107.1
10.2
116.6 116.6 97.2
77.9
58.5
105.9
10.3
90
56.1
74.7
93.4
103.3
64.5
85.2
106.0
109.3
107.6
72.9
95.8
118.6
115.4
113.5
81.3
106.3
131.3
121.4
119.4
112.4
133.3
122.8
120.8
118.5
135.4
124.2
122.2
49.5
71.4
93.2
93.0
63.4
81.3
99.2
96.7
95.6
77.3
91.3
105.2
100.4
99.2
91.2
101.2
111.2
104.0
102.8
107.3
112.9
105.6
104.4
113.4
114.5
107.1
105.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
45.7
35.4
64.4
54.1
43.7
83.0
72.7
62.4
52.1
103.3 87.5
77.2
66.9
52.0
39.4
72.7
60.2
47.7
93.5
80.9
68.4
55.9
109.3 97.4
84.9
72.4
107.6 98.1
85.5
73.0
58.2
43.4
81.0
66.3
51.6
103.9 89.2
74.4
59.7
115.4 107.4 92.6
77.9
113.5 108.0 93.3
78.6
64.4
47.4
89.4
72.4
55.5
114.3 97.4
80.4
63.5
121.4 117.3 100.3 83.4
119.4 118.0 101.0 84.1
94.4
76.4
58.4
120.7 102.7 84.7
66.7
122.8 120.7 102.7 84.7
120.8 120.1 102.1 84.1
99.4
80.3
61.3
127.1 108.1 89.0
69.9
124.2 124.2 105.2 86.1
122.2 122.2 103.2 84.1
105°F
41.8
31.1
59.9
48.4
37.0
78.0
65.7
54.3
42.8
93.0
75.3
63.9
52.4
48.4
34.8
67.7
54.1
40.6
87.1
73.5
59.9
46.3
96.7
84.2
70.6
57.0
95.6
84.7
71.1
57.5
55.0
38.5
75.6
59.8
44.1
96.1
81.2
65.5
49.8
100.4 93.0
77.3
61.6
99.2
93.6
77.9
62.1
61.6
42.1
83.4
65.6
47.7
105.2 89.0
71.2
53.3
104.0 101.9 84.1
66.2
102.8 102.5 84.6
66.8
88.5
69.6
50.8
109.4 94.5
75.7
56.8
105.6 104.5 85.7
66.8
104.4 104.2 85.3
66.5
93.6
73.7
53.8
113.5 100.0 80.1
60.3
107.1 107.1 87.3
67.4
105.9 105.9 86.0
66.1
65
56.6
59.9
60.5
63.1
63.8
66.4
67.2
66.7
66.1
67.0
65.0
41.0
43.4
43.9
45.9
46.4
48.4
49.0
48.0
47.6
47.5
46.3
57
246824-YTG-E-0507
XP120 (10 Ton) (Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
111.3
101.2
91.1
85.0
115.3
104.9
94.4
88.1
87.1
119.4
108.5
97.7
91.2
90.1
123.4
112.2
101.0
94.2
93.2
113.4
102.1
95.3
94.2
114.6
103.2
96.3
95.2
11.5
11.4
11.3
11.2
11.6
11.5
11.4
11.3
11.4
11.7
11.6
11.5
11.4
11.5
11.8
11.7
11.6
11.5
11.5
11.7
11.6
11.5
11.5
11.6
11.5
11.4
11.5
44.2
67.7
91.1
85.0
62.3
78.4
94.4
88.1
87.1
80.3
89.0
97.7
91.2
90.1
98.4
99.7
101.0
94.2
93.2
105.0
102.1
95.3
94.2
110.3
103.2
96.3
95.2
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
37.9
28.1
102.2
12.7
56.3
44.9
33.6
92.5
12.6
74.8
61.8
50.4
39.1
82.8
12.5
85.0
67.1
55.8
44.4
33.0
77.0
12.4
45.5
31.7
105.5
12.8
64.5
50.7
36.8
95.5
12.7
83.5
69.7
55.8
42.0
85.5
12.6
88.1
75.7
61.9
48.0
34.2
79.5
12.5
87.1
76.5
62.7
48.8
35.0
78.6
12.5
53.2
35.3
108.8
12.9
72.7
56.4
40.1
98.5
12.8
92.3
77.6
61.3
45.0
88.1
12.7
91.2
84.3
68.0
51.6
35.3
82.0
12.6
90.1
85.2
68.9
52.6
36.3
81.1
12.7
60.8
38.9
112.1
13.0
80.9
62.2
43.4
101.5
12.9
101.0 85.5
66.7
47.9
90.8
12.9
94.2
92.8
74.1
55.3
36.5
84.4
12.7
93.2
93.8
75.1
56.3
37.5
83.6
12.8
85.4
65.8
46.3
102.1
12.9
102.1 90.5
70.9
51.4
91.4
12.8
95.3
94.6
75.0
55.4
35.8
84.9
12.7
94.2
94.5
74.9
55.4
35.8
84.0
12.7
89.9
69.5
49.1
102.7
12.8
103.2 95.6
75.2
54.8
91.9
12.7
96.3
96.3
75.9
55.5
35.1
85.4
12.6
95.2
95.2
74.8
54.4
34.0
84.5
12.7
90
45.2
64.0
82.8
77.0
65.3
75.4
85.5
79.5
78.6
85.4
86.8
88.1
82.0
81.1
105.5
98.2
90.8
84.4
83.6
102.1
91.4
84.9
84.0
102.7
91.9
85.4
84.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
30.9
25.1
52.7
41.5
30.2
71.8
57.9
46.6
35.3
77.0
58.9
47.6
36.3
42.7
28.6
61.3
47.2
33.1
80.0
65.9
51.8
37.7
79.5
67.2
53.1
39.0
78.6
68.4
54.3
40.2
54.4
32.1
69.9
53.0
36.1
88.1
73.9
57.0
40.1
82.0
75.5
58.6
41.7
81.1
76.8
59.9
43.0
66.1
35.6
78.5
58.8
39.0
90.8
81.9
62.2
42.5
84.4
83.7
64.0
44.3
83.6
83.6
65.5
45.8
82.4
62.1
41.7
91.4
86.5
66.2
45.9
84.9
84.6
64.3
44.0
84.0
84.0
64.6
44.3
86.3
65.4
44.4
91.9
91.1
70.2
49.3
85.4
85.4
64.5
43.6
84.5
84.5
63.6
42.7
65
25.1
24.9
26.1
24.8
26.1
24.6
26.1
23.7
23.9
22.7
21.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
58
Unitary Products Group
246824-YTG-E-0507
XP150 (12.5 Ton)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
163.7
158.9
154.2
145.0
169.7
164.7
159.8
150.3
147.7
175.7
170.5
165.4
155.6
152.9
181.6
176.3
171.0
160.9
158.1
180.7
175.3
164.9
162.0
185.0
179.5
168.8
165.9
9.7
9.5
9.4
9.3
9.7
9.5
9.4
9.3
9.4
9.7
9.5
9.4
9.3
9.4
9.7
9.5
9.4
9.3
9.4
9.6
9.5
9.4
9.4
9.6
9.5
9.4
9.4
70.7
95.0
119.4
145.0
77.1
103.5
129.9
150.3
147.7
83.5
112.0
140.4
155.6
152.9
89.9
120.4
150.9
160.9
158.1
125.2
159.2
164.9
162.0
129.9
167.4
168.8
165.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
155.1
148.5
141.8
133.3
160.4
153.5
146.6
137.8
135.3
165.6
158.5
151.4
142.3
139.8
170.8
163.5
156.2
146.8
144.2
167.7
160.2
150.5
147.9
171.8
164.1
154.2
151.5
11.6
11.5
11.4
11.3
11.6
11.6
11.5
11.3
11.4
11.7
11.7
11.6
11.4
11.5
11.8
11.7
11.7
11.5
11.5
11.7
11.6
11.5
11.5
11.7
11.6
11.5
11.5
64.1
89.6
115.1
133.3
71.2
99.2
127.1
137.8
135.3
78.4
108.8
139.2
142.3
139.8
85.5
118.4
151.3
146.8
144.2
125.0
157.7
150.5
147.9
131.6
164.1
154.2
151.5
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
58.2
45.7
159.4
10.6
82.6
70.1
57.6
153.7
10.5
106.9 94.4
81.9
69.4
148.0
10.4
137.7 121.3 108.8 96.4
83.9
139.1
10.3
63.4
49.7
165.0
10.7
89.8
76.1
62.3
159.1
10.6
116.2 102.4 88.7
75.0
153.2
10.5
145.4 131.7 118.0 104.2 90.5
144.0
10.3
147.7 135.9 122.2 108.4 94.7
141.5
10.4
68.5
53.6
170.6
10.7
97.0
82.0
67.1
164.5
10.6
125.5 110.5 95.5
80.6
158.4
10.5
153.2 142.1 127.1 112.1 97.2
148.9
10.4
152.9 146.6 131.6 116.7 101.7
146.3
10.4
73.7
57.5
176.2
10.7
104.2 88.0
71.8
169.9
10.6
134.7 118.5 102.3 86.1
163.6
10.5
160.9 152.4 136.2 120.0 103.8
153.8
10.4
158.1 157.3 141.1 124.9 108.7
151.2
10.4
108.5 91.8
75.2
174.2
10.6
140.3 123.6 107.0 90.3
167.7
10.6
164.9 160.6 144.0 127.3 110.6
157.7
10.4
162.0 161.6 145.0 128.3 111.6
154.9
10.5
112.8 95.7
78.5
178.4
10.7
145.8 128.7 111.6 94.5
171.8
10.6
168.8 168.8 151.7 134.6 117.5
161.5
10.4
165.9 165.9 148.8 131.7 114.6
158.7
10.5
95°F
51.2
38.3
147.3
13.0
76.7
63.8
51.0
140.1
12.9
102.2 89.4
76.5
63.6
133.0
12.8
131.3 111.2 98.3
85.4
72.6
126.1
12.6
56.6
42.0
152.0
13.0
84.6
70.0
55.4
144.6
12.9
112.5 97.9
83.3
68.7
137.2
12.8
136.5 121.9 107.3 92.7
78.1
130.1
12.7
135.3 121.8 107.2 92.6
78.0
128.0
12.7
62.0
45.7
156.7
13.1
92.4
76.1
59.8
149.0
13.0
122.9 106.5 90.2
73.9
141.4
12.9
141.6 132.6 116.2 99.9
83.6
134.1
12.7
139.8 132.5 116.2 99.8
83.5
131.9
12.8
67.4
49.4
161.3
13.1
100.3 82.3
64.2
153.5
13.0
133.2 115.1 97.1
79.0
145.7
12.9
146.8 143.3 125.2 107.1 89.0
138.1
12.8
144.2 143.2 125.1 107.1 89.0
135.9
12.8
106.2 87.3
68.5
157.5
13.0
141.1 122.2 103.4 84.6
149.5
12.9
150.5 148.7 129.9 111.1 92.2
141.7
12.8
147.9 147.3 128.5 109.7 90.8
139.4
12.8
112.0 92.4
72.8
161.6
13.0
148.9 129.3 109.7 90.1
153.3
12.9
154.2 154.2 134.6 115.0 95.4
145.4
12.8
151.5 151.5 131.9 112.3 92.7
143.0
12.8
90
67.4
92.3
117.2
139.1
74.2
101.3
128.5
144.0
141.5
80.9
110.4
139.8
148.9
146.3
87.7
119.4
151.1
153.8
151.2
125.1
158.4
157.7
154.9
130.7
165.8
161.5
158.7
58.0
86.8
115.6
126.1
67.7
96.2
124.8
130.1
128.0
77.3
105.7
134.0
134.1
131.9
86.9
115.1
143.2
138.1
135.9
122.1
148.3
141.7
139.4
129.1
153.3
145.4
143.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
54.7
42.0
79.6
67.0
54.3
104.6 91.9
79.2
66.5
134.5 116.3 103.6 90.9
60.0
45.8
87.2
73.0
58.9
114.4 100.2 86.0
71.9
140.9 126.8 112.6 98.5
141.5 128.9 114.7 100.5
65.3
49.6
94.7
79.1
63.4
124.2 108.5 92.9
77.2
147.4 137.3 121.7 106.0
146.3 139.6 123.9 108.3
70.6
53.4
102.3 85.1
68.0
134.0 116.8 99.7
82.6
153.8 147.8 130.7 113.6
151.2 150.3 133.1 116.0
107.3 89.6
71.8
140.7 122.9 105.2 87.4
157.7 154.7 136.9 119.2
154.9 154.5 136.7 119.0
112.4 94.0
75.7
147.4 129.0 110.7 92.3
161.5 161.5 143.2 124.8
158.7 158.7 140.3 122.0
105°F
47.7
34.5
73.7
60.6
47.5
99.8
86.7
73.6
60.5
124.4 104.1 91.0
77.9
52.8
37.8
81.3
66.4
51.5
109.9 95.0
80.1
65.2
129.0 114.1 99.1
84.2
128.0 114.9 100.0 85.1
57.9
41.2
88.9
72.2
55.5
120.0 103.3 86.5
69.8
133.5 124.0 107.3 90.6
131.9 125.0 108.2 91.5
63.0
44.5
96.5
78.0
59.5
130.1 111.5 93.0
74.5
138.1 134.0 115.4 96.9
135.9 135.0 116.5 97.9
102.6 83.1
63.5
137.9 118.8 99.3
79.8
141.7 139.7 120.1 100.6
139.4 139.0 119.5 100.0
108.6 88.1
67.6
145.7 126.0 105.5 85.1
145.4 145.4 124.9 104.4
143.0 143.0 122.5 102.1
65
78.2
84.3
86.4
90.4
92.6
96.4
98.9
101.4
101.2
106.4
103.6
64.8
69.3
70.2
73.8
74.8
78.4
79.4
81.1
80.5
83.9
81.6
59
246824-YTG-E-0507
XP150 (12.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
139.5
131.8
124.1
118.9
143.6
135.7
127.8
122.4
120.6
147.7
139.6
131.5
125.9
124.1
151.8
143.5
135.1
129.4
127.6
147.4
138.8
133.0
131.0
151.3
142.5
136.5
134.5
14.4
14.2
14.1
14.0
14.4
14.3
14.1
14.0
14.1
14.5
14.3
14.1
14.1
14.1
14.5
14.3
14.2
14.1
14.1
14.4
14.2
14.1
14.1
14.4
14.2
14.2
14.2
52.0
84.1
116.1
118.9
64.1
93.3
122.5
122.4
120.6
76.2
102.5
128.8
125.9
124.1
88.3
111.7
135.1
129.4
127.6
119.1
138.8
133.0
131.0
126.5
142.5
136.5
134.5
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
44.1
30.8
131.7
15.8
70.7
57.4
44.1
123.5
15.6
97.4
84.0
70.7
57.4
115.3
15.4
117.5 97.0
83.7
70.3
57.0
111.7
15.4
48.9
33.7
135.2
15.8
78.1
62.9
47.6
126.8
15.6
107.2 92.0
76.8
61.6
118.4
15.4
121.5 106.2 91.0
75.8
60.6
114.7
15.4
120.6 108.1 92.8
77.6
62.4
113.3
15.4
53.7
36.6
138.8
15.8
85.4
68.3
51.2
130.1
15.6
117.1 100.0 82.9
65.8
121.5
15.4
125.4 115.4 98.3
81.2
64.1
117.8
15.4
124.1 117.4 100.3 83.2
66.1
116.3
15.4
58.5
39.5
142.3
15.9
92.7
73.7
54.8
133.5
15.6
127.0 108.0 89.0
70.0
124.6
15.4
129.4 124.6 105.7 86.7
67.7
120.8
15.4
127.6 126.8 107.8 88.8
69.8
119.2
15.4
98.9
78.8
58.6
137.3
15.7
134.7 115.3 95.2
75.0
128.1
15.5
133.0 130.6 110.4 90.2
70.1
124.2
15.5
131.0 130.7 110.5 90.3
70.1
122.6
15.5
105.2 83.8
62.5
141.1
15.7
142.5 122.7 101.3 80.0
131.7
15.5
136.5 136.5 115.2 93.8
72.5
127.6
15.5
134.5 134.5 113.2 91.8
70.5
126.0
15.5
90
47.4
81.4
115.3
111.7
62.4
90.4
118.4
114.7
113.3
77.3
99.4
121.5
117.8
116.3
92.2
108.4
124.6
120.8
119.2
116.2
128.1
124.2
122.6
123.9
131.7
127.6
126.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
40.6
27.0
67.8
54.2
40.6
95.0
81.4
67.8
54.2
110.5 89.9
76.4
62.8
45.1
29.5
74.8
59.3
43.7
104.6 89.1
73.5
58.0
114.0 98.4
82.9
67.3
113.3 101.2 85.6
70.1
49.6
32.1
81.9
64.4
46.9
114.2 96.7
79.2
61.7
117.4 106.9 89.4
71.9
116.3 109.9 92.4
74.9
54.1
34.6
89.0
69.5
50.0
123.8 104.4 84.9
65.5
120.8 115.3 95.9
76.4
119.2 118.6 99.1
79.7
95.3
74.5
53.7
128.1 111.9 91.0
70.2
124.2 121.5 100.7 79.8
122.6 122.3 101.5 80.6
101.7 79.5
57.3
131.7 119.4 97.2
74.9
127.6 127.6 105.4 83.2
126.0 126.0 103.8 81.6
65
49.2
51.8
54.6
54.4
57.4
57.0
60.2
59.0
59.8
61.0
59.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
60
Unitary Products Group
246824-YTG-E-0507
XP078-150 Heating Capacities
XP078-150
Size
(Tons)
Model
Air Over Evaporator
Coil
CFM
DB (°F)
55
1950
70
80
55
078
(6.5)
XP
2600
70
80
55
3250
70
80
55
2250
70
80
55
090
(7.5)
XP
3000
70
80
55
3750
70
80
55
2550
70
80
55
102
(8.5)
XP
3400
70
80
55
4250
70
80
Unitary Products Group
Capacity1 &
kW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
Outdoor Temperature (°F @ 72% RH)
-10
0
10
20
30
40
50
60
18.7
4.8
13.9
5.6
11.6
6.4
21.8
4.2
16.9
5.0
14.7
5.8
22.9
3.9
18.1
4.7
15.8
5.5
19.0
5.0
14.7
6.1
11.6
6.9
22.0
4.4
17.7
5.4
14.5
6.2
21.7
4.0
17.4
5.0
14.3
5.8
9.4
4.9
12.2
6.1
11.1
6.9
14.9
4.3
17.7
5.6
16.6
6.4
17.2
4.0
20.0
5.2
18.9
6.1
29.2
4.9
24.4
5.7
22.1
6.5
32.3
4.3
27.4
5.1
25.2
6.0
33.5
4.0
28.6
4.9
26.3
5.6
31.5
5.2
27.2
6.3
24.1
7.1
34.4
4.6
30.2
5.6
27.0
6.4
34.2
4.2
29.9
5.2
26.8
6.1
22.3
5.1
25.1
6.3
24.0
7.1
27.8
4.5
30.6
5.8
29.4
6.6
30.1
4.2
32.9
5.4
31.8
6.3
39.8
5.1
35.0
5.9
32.6
6.7
42.9
4.5
37.9
5.3
35.8
6.1
44.0
4.2
39.2
5.0
36.9
5.8
43.9
5.4
39.7
6.5
36.5
7.3
46.9
4.8
42.6
5.8
39.4
6.7
46.6
4.4
42.3
5.4
39.2
6.3
35.1
5.3
37.9
6.5
36.8
7.3
40.6
4.7
43.4
6.0
42.3
6.8
42.9
4.4
45.7
5.6
44.6
6.5
50.3
5.2
45.5
6.0
43.2
6.8
53.4
4.6
48.5
5.4
46.3
6.3
54.6
4.3
49.7
5.2
47.4
6.0
56.4
5.6
52.1
6.7
49.0
7.5
59.3
5.0
55.1
6.0
51.9
6.9
59.1
4.6
54.8
5.6
51.7
6.5
48.0
5.5
50.8
6.7
49.7
7.5
53.5
4.9
56.3
6.2
55.1
7.0
55.8
4.6
58.6
5.9
57.5
6.7
60.9
5.4
56.0
6.2
53.7
7.0
64.0
4.8
59.0
5.6
56.8
6.4
65.1
4.5
60.3
5.3
58.0
6.1
68.8
5.9
64.6
6.9
61.5
7.7
71.8
5.2
67.5
6.3
64.4
7.1
71.5
4.8
67.3
5.8
64.1
6.7
60.8
5.7
63.7
6.9
62.5
7.7
66.3
5.2
69.1
6.4
68.0
7.2
68.6
4.8
71.4
6.1
70.3
6.9
71.4
5.5
66.6
6.3
64.3
7.1
74.5
4.9
69.6
5.7
67.4
6.6
75.6
4.6
70.8
5.5
68.5
6.3
81.3
6.1
77.0
7.1
73.9
7.9
84.2
5.4
80.0
6.5
76.8
7.3
84.0
5.0
79.7
6.0
76.6
6.9
73.7
5.9
76.5
7.1
75.4
7.9
79.2
5.4
82.0
6.6
80.8
7.4
81.5
5.0
84.3
6.3
83.2
7.1
81.9
5.7
77.1
6.5
74.8
7.3
85.1
5.1
80.1
5.9
77.9
6.7
86.2
4.8
81.4
5.6
79.0
6.4
93.8
6.3
89.5
7.3
86.4
8.1
96.7
5.6
92.5
6.7
89.3
7.5
96.5
5.2
92.2
6.3
89.1
7.1
86.5
6.1
89.4
7.3
88.2
8.2
92.0
5.6
94.8
6.8
93.7
7.6
94.3
5.2
97.1
6.5
96.0
7.3
92.5
5.8
87.7
6.7
85.3
7.4
95.6
5.2
90.7
6.0
88.5
6.9
96.7
4.9
91.9
5.8
89.6
6.6
106.2
6.5
101.9
7.5
98.8
8.4
109.2
5.8
104.9
6.9
101.7
7.7
108.9
5.4
104.6
6.5
101.5
7.3
99.4
6.3
102.2
7.5
101.1
8.4
104.9
5.8
107.7
7.0
106.6
7.8
107.2
5.4
110.0
6.7
108.9
7.5
61
246824-YTG-E-0507
XP078-150 (Continued)
Size
(Tons)
Model
Air Over Evaporator
Coil
CFM
DB (°F)
55
3000
70
80
55
120
(10)
XP
4000
70
80
55
5000
70
80
55
3750
70
80
55
150
(12.5)
XP
5000
70
80
55
6250
70
80
Capacity1 &
kW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
Outdoor Temperature (°F @ 72% RH)
-10
0
10
20
30
40
50
60
14.5
5.9
11.2
7.0
7.8
7.9
24.6
5.5
21.2
6.7
17.9
7.6
21.2
5.0
17.8
6.2
14.4
7.0
26.2
8.0
22.8
9.5
19.5
10.7
34.3
7.2
30.9
8.7
27.6
9.9
36.3
6.8
32.9
8.3
29.6
9.5
29.4
6.0
26.0
7.2
22.7
8.1
39.5
5.7
36.1
6.8
32.8
7.7
36.0
5.2
32.6
6.3
29.3
7.2
45.3
8.4
41.9
9.9
38.7
11.1
53.4
7.6
50.1
9.1
46.7
10.3
55.5
7.2
52.0
8.7
48.8
9.9
44.3
6.2
40.9
7.4
37.6
8.3
54.3
5.8
51.0
7.0
47.6
7.9
50.9
5.3
47.5
6.5
44.2
7.4
64.5
8.8
61.0
10.3
57.8
11.5
72.6
8.0
69.2
9.5
65.8
10.7
74.6
7.6
71.1
9.1
67.9
10.3
59.1
6.4
55.7
7.5
52.4
8.4
69.2
6.0
65.8
7.2
62.5
8.1
65.8
5.5
62.4
6.6
59.0
7.5
83.6
9.2
80.2
10.7
76.9
11.9
91.7
8.4
88.3
9.9
85.0
11.1
93.7
8.0
90.3
9.5
87.0
10.7
74.0
6.5
70.6
7.7
67.3
8.6
84.1
6.2
80.7
7.3
77.4
8.2
80.6
5.6
77.2
6.8
73.9
7.7
102.7
9.6
99.3
11.1
96.1
12.3
110.8
8.8
107.5
10.3
104.1
11.5
112.8
8.4
109.4
9.9
106.2
11.1
88.9
6.7
85.5
7.9
82.1
8.8
98.9
6.3
95.5
7.5
92.2
8.4
95.5
5.8
92.1
7.0
88.8
7.9
121.9
10.0
118.4
11.5
115.2
12.7
130.0
9.2
126.6
10.7
123.2
11.9
132.0
8.8
128.5
10.3
125.3
11.5
103.7
6.9
100.3
8.0
97.0
8.9
113.8
6.5
110.4
7.6
107.1
8.5
110.3
6.0
107.0
7.1
103.6
8.0
141.0
10.4
137.6
11.9
134.3
13.1
149.1
9.6
145.7
11.1
142.4
12.3
151.1
9.2
147.7
10.7
144.4
11.9
118.6
7.0
115.2
8.2
111.9
9.1
128.7
6.6
125.3
7.8
122.0
8.7
125.2
6.1
121.8
7.3
118.5
8.2
160.1
10.8
156.7
12.3
153.5
13.5
168.2
10.0
164.8
11.5
161.5
12.7
170.2
9.6
166.8
11.1
163.6
12.3
1. These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh = 3.415 x
kW.
62
Unitary Products Group
246824-YTG-E-0507
XP078-150 Side Duct Application
XP078 (6.5 Ton) Side Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
754
779
809
842
879
918
960
1004
1050
1.5 HP & Field Supplied Drive
0.24
814
0.44
872
0.37
840
0.58
898
0.52
870
0.73
928
0.69
903
0.90
961
0.87
939
1.08
998
1.08
979
1.28 1037
1.30 1020 1.50 1079
1.54 1065 1.74 1123
1.79 1111 2.00 1169
0.63
0.76
0.91
1.08
1.26
1.46
1.68
1.92
2.18
929
955
985
1018
1054
1093
1135
1179
-
0.79
0.92
1.07
1.24
1.42
1.63
1.85
2.09
-
Standard 1.5 HP & Drive
985
0.93 1039 1.07
1010 1.07 1065 1.21
1040 1.22 1095 1.36
1073 1.39 1128 1.52
1110 1.57 1165 1.71
1149 1.77 1204 1.91
1191 1.99 1246 2.13
1235 2.23
-
1094
1120
1150
1183
1220
1259
1301
-
1.20
1.34
1.48
1.65
1.84
2.04
2.26
-
1150
1176
1206
1239
1275
1315
-
Hi Static 2 HP & Drive
1.33 1207 1.45 1266
1.46 1233 1.59 1292
1.61 1263 1.74 1321
1.78 1296 1.91 1355
1.96 1332 2.09 1391
2.16 1371 2.29
2 HP & Field Supplied Drive
1.59
1.72
1.87
2.04
2.22
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XP090 (7.5 Ton) Side Duct
Air Flow
(CFM)
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
779
0.37
840
0.58
809
0.52
870
0.73
842
0.69
903
0.90
879
0.87
939
1.08
918
1.08
979
1.28
960
1.30 1020 1.50
1004 1.54 1065 1.74
1050 1.79 1111 2.00
1099 2.07 1159 2.27
1149 2.36 1209 2.56
898
928
961
998
1037
1079
1123
1169
1218
1268
0.76
0.91
1.08
1.26
1.46
1.68
1.92
2.18
2.45
2.74
955
985
1018
1054
1093
1135
1179
1226
1274
1324
Standard 1.5 HP & Drive
0.92 1010 1.07 1065
1.07 1040 1.22 1095
1.24 1073 1.39 1128
1.42 1110 1.57 1165
1.63 1149 1.77 1204
1.85 1191 1.99 1246
2.09 1235 2.23 1290
2.34 1281 2.49 1336
2.62 1330 2.76 1385
2.91 1380 3.05 1435
1.21
1.36
1.52
1.71
1.91
2.13
2.37
2.63
2.90
3.19
1120
1150
1183
1220
1259
1301
1345
1391
1440
1490
Hi Static 3 HP & Drive
1.34 1176 1.46 1233 1.59 1292
1.48 1206 1.61 1263 1.74 1321
1.65 1239 1.78 1296 1.91 1355
1.84 1275 1.96 1332 2.09 1391
2.04 1315 2.16 1371 2.29 1430
2.26 1356 2.39 1413 2.51 1472
2.50 1400 2.62 1457 2.75 1516
2.75 1447 2.88 1504 3.01 1562
3.03 1495 3.15 1552 3.28 1611
3.32 1545 3.44
3 HP & Field Supplied Drive
1.72
1.87
2.04
2.22
2.43
2.65
2.89
3.14
3.42
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XP102 (8.5 Ton) Side Duct
Air Flow
(CFM)
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
632
0.23
684
0.44
639
0.32
691
0.53
646
0.41
698
0.62
654
0.50
706
0.71
663
0.60
714
0.81
673
0.71
724
0.93
684
0.84
735
1.05
696
0.98
747
1.19
709
1.14
761
1.35
724
1.31
776
1.52
740
1.50
792
1.71
734
741
748
756
765
774
785
798
811
826
842
0.65
0.74
0.82
0.92
1.02
1.13
1.25
1.39
1.55
1.72
1.92
783
790
797
805
813
823
834
846
860
874
890
Standard 2 HP & Drive
0.84
830
1.03
876
0.93
837
1.12
883
1.02
844
1.21
890
1.11
852
1.30
898
1.21
861
1.40
907
1.32
871
1.51
917
1.45
882
1.63
928
1.59
894
1.78
940
1.75
907
1.93
953
1.92
922
2.11
968
2.11
938
2.30
984
1.21
1.30
1.39
1.48
1.58
1.69
1.82
1.96
2.12
2.29
2.48
921
928
936
943
952
962
973
985
999
1013
1029
1.39
1.48
1.57
1.66
1.76
1.87
2.00
2.14
2.29
2.47
2.66
966
972
980
987
996
1006
1017
1029
1043
1057
1073
Hi Static 3 HP & Drive
1.56 1009 1.74 1051 1.91
1.65 1015 1.83 1058 2.00
1.74 1023 1.92 1065 2.09
1.83 1031 2.01 1073 2.18
1.93 1039 2.11 1082 2.28
2.05 1049 2.22 1091 2.39
2.17 1060 2.34 1102 2.52
2.31 1072 2.48 1115 2.66
2.47 1086 2.64 1128 2.81
2.64 1100 2.82 1143 2.99
2.83 1116 3.01 1159 3.18
3 HP & Field Supplied Drive
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Unitary Products Group
71
246824-YTG-E-0507
XP120 (10 Ton) Side Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
646
654
663
673
684
696
709
724
740
757
776
795
816
2 HP & Field Supplied Drive
0.41
698
0.62
748
0.50
706
0.71
756
0.60
714
0.81
765
0.71
724
0.93
774
0.84
735
1.05
785
0.98
747
1.19
798
1.14
761
1.35
811
1.31
776
1.52
826
1.50
792
1.71
842
1.71
809
1.92
859
1.94
827
2.15
877
2.19
847
2.40
897
2.45
868
2.66
918
0.82
0.92
1.02
1.13
1.25
1.39
1.55
1.72
1.92
2.13
2.35
2.60
2.86
797
805
813
823
834
846
860
874
890
908
926
946
967
1.02
1.11
1.21
1.32
1.45
1.59
1.75
1.92
2.11
2.32
2.55
2.79
3.06
844
852
861
871
882
894
907
922
938
955
974
993
1014
Standard 2 HP & Drive
1.21
890
1.39
936
1.30
898
1.48
943
1.40
907
1.58
952
1.51
917
1.69
962
1.63
928
1.82
973
1.78
940
1.96
985
1.93
953
2.12
999
2.11
968
2.29 1013
2.30
984
2.48 1029
2.51 1001 2.69 1046
2.74 1020 2.92 1065
2.98 1040 3.16 1085
3.25 1061 3.43
-
1.57
1.66
1.76
1.87
2.00
2.14
2.29
2.47
2.66
2.87
3.10
3.34
-
980
987
996
1006
1017
1029
1043
1057
1073
1091
1109
-
1.74
1.83
1.93
2.05
2.17
2.31
2.47
2.64
2.83
3.04
3.27
-
Hi Static 3 HP & Drive
1023 1.92 1065 2.09
1031 2.01 1073 2.18
1039 2.11 1082 2.28
1049 2.22 1091 2.39
1060 2.34 1102 2.52
1072 2.48 1115 2.66
1086 2.64 1128 2.81
1100 2.82 1143 2.99
1116 3.01 1159 3.18
1134 3.22 1176 3.39
1152 3.45
3 HP & Field Supplied Drive
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XP150 (12.5 Ton) Side Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
673
684
696
709
724
740
757
776
795
816
839
862
886
912
939
967
0.71
0.84
0.98
1.14
1.31
1.50
1.71
1.94
2.19
2.45
2.73
3.03
3.34
3.67
4.02
4.39
724
735
747
761
776
792
809
827
847
868
890
914
938
964
990
1018
3 HP & Field Supplied Drive
0.93
774
1.13
823
1.32
871
1.05
785
1.25
834
1.45
882
1.19
798
1.39
846
1.59
894
1.35
811
1.55
860
1.75
907
1.52
826
1.72
874
1.92
922
1.71
842
1.92
890
2.11
938
1.92
859
2.13
908
2.32
955
2.15
877
2.35
926
2.55
974
2.40
897
2.60
946
2.79
993
2.66
918
2.86
967
3.06 1014
2.94
940
3.14
989
3.34 1037
3.24
964
3.44 1012 3.64 1060
3.55
988
3.76 1037 3.95 1084
3.89 1014 4.09 1063 4.28 1110
4.23 1041 4.44 1089 4.63 1137
4.60 1068 4.80 1117 4.99 1165
Hi Static 5 HP & Drive
1.51
1.63
1.78
1.93
2.11
2.30
2.51
2.74
2.98
3.25
3.53
3.82
4.14
4.47
4.82
5.18
917
928
940
953
968
984
1001
1020
1040
1061
1083
1106
1131
1156
1183
1211
1.69
1.82
1.96
2.12
2.29
2.48
2.69
2.92
3.16
3.43
3.71
4.01
4.32
4.65
5.00
5.36
962
973
985
999
1013
1029
1046
1065
1085
1106
1128
1151
1176
1201
1228
1256
Standard 3 HP & Drive
1.87 1006 2.05 1049 2.22 1091
2.00 1017 2.17 1060 2.34 1102
2.14 1029 2.31 1072 2.48 1115
2.29 1043 2.47 1086 2.64 1128
2.47 1057 2.64 1100 2.82 1143
2.66 1073 2.83 1116 3.01 1159
2.87 1091 3.04 1134 3.22 1176
3.10 1109 3.27 1152 3.45 1194
3.34 1129 3.52 1172 3.69 1214
3.61 1150 3.78 1193 3.95 1235
3.89 1172 4.06 1215 4.23 1257
4.18 1195 4.36 1238 4.53 1281
4.50 1220 4.67 1263 4.85 1305
4.83 1246 5.01 1289 5.18 1331
5.18 1272 5.35 1315 5.53 1358
5.54 1300 5.72
5 HP & Field Supplied Drive
2.39
2.52
2.66
2.81
2.99
3.18
3.39
3.62
3.86
4.13
4.41
4.70
5.02
5.35
5.70
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
72
Unitary Products Group
246824-YTG-E-0507
XP078-150 Bottom Duct Application
XP078 (6.5 Ton) Bottom Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
775
0.32
849
0.54
805
0.46
879
0.68
842
0.62
916
0.84
885
0.81
959
1.02
933
1.01 1007 1.23
985
1.24 1059 1.46
1040 1.49 1114 1.71
1097 1.77 1171 1.98
1157 2.06 1231 2.28
923
953
990
1033
1081
1132
1187
1245
-
Standard 1.5 HP & Drive
0.72
997
0.89 1071
0.86 1027 1.03 1101
1.02 1064 1.19 1138
1.21 1107 1.38 1181
1.41 1155 1.58 1229
1.64 1206 1.81 1281
1.90 1261 2.06 1336
2.17
-
1.05
1.19
1.35
1.53
1.74
1.97
2.22
-
1147
1177
1214
1257
1305
1356
-
Hi Static 2 HP & Drive
1.20 1224 1.35 1303 1.51
1.34 1254 1.49 1333 1.65
1.50 1291 1.65 1370 1.81
1.68 1334 1.83 1413 1.99
1.89 1382 2.04 1461 2.20
2.12 1433 2.27
2 HP & Field Supplied Drive
1385
1414
1451
1495
-
1.68
1.82
1.98
2.17
-
1469
1499
1536
-
1.88
2.02
2.18
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XP090 (7.5 Ton) Bottom Duct
Air Flow
(CFM)
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
805
0.46
879
0.68
842
0.62
916
0.84
885
0.81
959
1.02
933
1.01 1007 1.23
985
1.24 1059 1.46
1040 1.49 1114 1.71
1097 1.77 1171 1.98
1157 2.06 1231 2.28
1219 2.38 1293 2.60
1282 2.72 1356 2.93
953
990
1033
1081
1132
1187
1245
1305
1367
1430
Standard 1.5 HP & Drive
0.86 1027 1.03 1101
1.02 1064 1.19 1138
1.21 1107 1.38 1181
1.41 1155 1.58 1229
1.64 1206 1.81 1281
1.90 1261 2.06 1336
2.17 1319 2.34 1393
2.47 1379 2.63 1453
2.78 1440 2.95 1515
3.12 1504 3.29 1578
1.19
1.35
1.53
1.74
1.97
2.22
2.49
2.79
3.11
3.45
Hi Static 3 HP & Drive
1177 1.34 1254 1.49 1333
1214 1.50 1291 1.65 1370
1257 1.68 1334 1.83 1413
1305 1.89 1382 2.04 1461
1356 2.12 1433 2.27 1512
1411 2.37 1488 2.52 1567
1469 2.64 1546 2.80 1625
1529 2.94 1606 3.09 1685
1590 3.26 1667 3.41
3 HP & Field Supplied Drive
1.65
1.81
1.99
2.20
2.43
2.68
2.96
3.25
-
1414
1451
1495
1542
1594
1649
1706
1766
-
1.82
1.98
2.17
2.37
2.60
2.85
3.13
3.43
-
1499
1536
1579
1627
1679
1734
1791
-
2.02
2.18
2.36
2.57
2.80
3.05
3.33
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XP102 (8.5 Ton) Bottom Duct
Air Flow
(CFM)
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
662
0.53
717
0.68
677
0.63
732
0.78
693
0.75
748
0.90
712
0.88
767
1.03
733
1.03
788
1.18
757
1.20
811
1.36
782
1.40
837
1.55
810
1.61
865
1.76
841
1.85
896
2.00
874
2.11
928
2.26
909
2.38
963
2.53
770
784
801
819
841
864
890
918
948
981
1016
0.83
0.93
1.04
1.17
1.33
1.50
1.69
1.91
2.14
2.40
2.68
Standard 2 HP & Drive
821
0.96
870
1.09
835
1.06
885
1.19
852
1.18
901
1.31
871
1.31
920
1.44
892
1.46
941
1.59
915
1.64
964
1.77
941
1.83
990
1.96
969
2.04 1018 2.18
999
2.28 1049 2.41
1032 2.54 1082 2.67
1067 2.81 1117 2.95
918
933
949
968
989
1012
1038
1066
1097
1130
1164
1.22
1.32
1.44
1.57
1.72
1.89
2.09
2.30
2.54
2.80
3.07
Hi Static 3 HP & Drive
965
1.35 1010 1.47 1055 1.59
979
1.44 1025 1.57 1069 1.69
996
1.56 1041 1.68 1085 1.80
1014 1.69 1060 1.81 1104 1.94
1036 1.84 1081 1.97 1125 2.09
1059 2.02 1104 2.14 1149 2.26
1085 2.21 1130 2.33 1174 2.45
1113 2.43 1158 2.55 1203 2.67
1143 2.66 1189 2.78 1233 2.91
1176 2.92 1222 3.04 1266 3.16
1211 3.20 1256 3.32 1301 3.44
3 HP & Field Supplied Drive
1098
1112
1129
1148
1169
1192
1218
1246
1276
1309
-
1.71
1.81
1.92
2.06
2.21
2.38
2.58
2.79
3.03
3.28
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Unitary Products Group
73
246824-YTG-E-0507
XP120 (10 Ton) Bottom Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
693
0.75
748
0.90
712
0.88
767
1.03
733
1.03
788
1.18
757
1.20
811
1.36
782
1.40
837
1.55
810
1.61
865
1.76
841
1.85
896
2.00
874
2.11
928
2.26
909
2.38
963
2.53
946
2.68 1000 2.83
985
3.00 1040 3.15
1026 3.33
-
801
819
841
864
890
918
948
981
1016
1053
1092
-
1.04
1.17
1.33
1.50
1.69
1.91
2.14
2.40
2.68
2.98
3.29
-
Standard 2 HP & Drive
852
1.18
901
1.31
949
1.44
996
871
1.31
920
1.44
968
1.57 1014
892
1.46
941
1.59
989
1.72 1036
915
1.64
964
1.77 1012 1.89 1059
941
1.83
990
1.96 1038 2.09 1085
969
2.04 1018 2.18 1066 2.30 1113
999
2.28 1049 2.41 1097 2.54 1143
1032 2.54 1082 2.67 1130 2.80 1176
1067 2.81 1117 2.95 1164 3.07 1211
1104 3.11 1154 3.24 1202 3.37
1143 3.43
3 HP & Field Supplied Drive
Hi Static 3 HP & Drive
1.56 1041 1.68 1085
1.69 1060 1.81 1104
1.84 1081 1.97 1125
2.02 1104 2.14 1149
2.21 1130 2.33 1174
2.43 1158 2.55 1203
2.66 1189 2.78 1233
2.92 1222 3.04 1266
3.20 1256 3.32 1301
-
1.80
1.94
2.09
2.26
2.45
2.67
2.91
3.16
3.44
-
1129
1148
1169
1192
1218
1246
1276
1309
-
1.92
2.06
2.21
2.38
2.58
2.79
3.03
3.28
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XP150 (12.5 Ton) Bottom Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
757
782
810
841
874
909
946
985
1026
1069
1114
1161
1210
1260
3 HP & Field Supplied Drive
1.20
811
1.36
864
1.40
837
1.55
890
1.61
865
1.76
918
1.85
896
2.00
948
2.11
928
2.26
981
2.38
963
2.53 1016
2.68 1000 2.83 1053
3.00 1040 3.15 1092
3.33 1081 3.48 1133
3.69 1124 3.84 1177
4.06 1169 4.21 1222
4.45 1216 4.60 1268
4.86 1264 5.01 1317
5.28 1315 5.43 1367
1.50
1.69
1.91
2.14
2.40
2.68
2.98
3.29
3.63
3.98
4.35
4.74
5.15
5.57
915
941
969
999
1032
1067
1104
1143
1184
1228
1273
1319
1368
1418
1.64
1.83
2.04
2.28
2.54
2.81
3.11
3.43
3.76
4.12
4.49
4.88
5.29
5.71
964
990
1018
1049
1082
1117
1154
1193
1234
1277
1322
1369
1418
-
Standard 3 HP & Drive
1.77 1012 1.89 1059
1.96 1038 2.09 1085
2.18 1066 2.30 1113
2.41 1097 2.54 1143
2.67 1130 2.80 1176
2.95 1164 3.07 1211
3.24 1202 3.37 1248
3.56 1241 3.69 1287
3.90 1282 4.02 1328
4.25 1325 4.38 1372
4.62 1370 4.75 1417
5.01 1417 5.14 1463
5.42 1465 5.55 1512
5 HP & Field Supplied Drive
2.02
2.21
2.43
2.66
2.92
3.20
3.49
3.81
4.15
4.50
4.87
5.26
5.67
-
1104
1130
1158
1189
1222
1256
1294
1333
1374
1417
1462
1509
-
2.14
2.33
2.55
2.78
3.04
3.32
3.62
3.93
4.27
4.62
5.00
5.38
-
Hi Static 5 HP & Drive
1149 2.26 1192 2.38
1174 2.45 1218 2.58
1203 2.67 1246 2.79
1233 2.91 1276 3.03
1266 3.16 1309 3.28
1301 3.44 1344 3.56
1338 3.74 1381 3.86
1377 4.05 1420 4.18
1418 4.39 1461 4.51
1461 4.74 1505 4.87
1506 5.12 1550 5.24
1553 5.51 1596 5.63
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
74
Unitary Products Group
246824-YTG-E-0507
RPM Selection
Size
(Tons)
078
(6.5)
Model
ZH
090
(7.5)
ZH
102
(8.5)
ZH
120
(10)
ZH
150
(12.5)
ZH
078
(6.5)
ZR
090
(7.5)
ZR
102
(8.5)
ZR
120
(10)
ZR
150
(12.5)
ZR
078
(6.5)
XP
090
(7.5)
XP
102
(8.5)
XP
120
(10)
XP
150
(12.5)
XP
Unitary Products Group
HP
1.5
2
1.5
3
2
3
2
3
3
5
1.5
2
1.5
3
2
3
2
3
3
5
1.5
2
1.5
3
2
3
2
3
3
5
Max
BHP
1.73
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
1.73
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
1.73
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
Motor
Sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower
Sheave
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
6 Turns
Open
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
5 Turns
Open
897
1039
897
1088
735
880
785
880
880
1095
897
1039
897
1088
735
880
785
880
880
1095
897
1039
897
1088
735
880
785
880
880
1095
4 Turns
Open
945
1094
945
1147
775
928
821
928
928
1136
945
1094
945
1147
775
928
821
928
928
1136
945
1094
945
1147
775
928
821
928
928
1136
3 Turns
Open
991
1150
991
1205
815
972
858
972
972
1175
991
1150
991
1205
815
972
858
972
972
1175
991
1150
991
1205
815
972
858
972
972
1175
2 Turns
Open
1035
1207
1035
1265
851
1016
901
1016
1016
1216
1035
1207
1035
1265
851
1016
901
1016
1016
1216
1035
1207
1035
1265
851
1016
901
1016
1016
1216
1 Turn
Open
1079
1256
1079
1312
889
1067
940
1067
1067
1272
1079
1256
1079
1312
889
1067
940
1067
1067
1272
1079
1256
1079
1312
889
1067
940
1067
1067
1272
Fully
Closed
1126
1308
1126
1365
930
1110
980
1110
1110
N/A
1126
1308
1126
1365
930
1110
980
1110
1110
N/A
1126
1308
1126
1365
930
1110
980
1110
1110
N/A
75
246824-YTG-E-0507
Additional Static Resistance
Size
(Tons)
078 (6.5)
090 (7.5)
Model
ZH/ZR/XP
102 (8.5)
120 (10) ZH/ZR/XP
150 (12.5)
CFM
Cooling Only1
Economizer2 3
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
0.00
-0.01
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
-0.09
-0.09
-0.10
-0.11
0.06
0.07
0.08
0.09
0.11
0.12
0.14
0.16
0.18
0.20
0.23
0.25
0.28
0.30
0.33
0.36
0.39
0.42
0.45
0.48
0.52
0.56
0.60
0.07
0.09
0.11
0.13
0.16
0.18
0.20
0.22
0.24
0.27
0.29
0.31
0.30
0.35
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
0.06
0.07
0.07
0.07
95
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
18
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
Electric Heat kW2
24
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.56
36
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
54
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.62
0.65
1. Add these values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
76
Unitary Products Group
246824-YTG-E-0507
Drive Selection
1.
Determine desired airflow.
2.
Calculate or measure the amount of external static pressure.
3.
Using the operating point determined from steps 1 & 2, locate this point on the appropriate supply air blower performance table.
(Linear interpolation may be necessary.)
4.
Noting the RPM and BHP from step 3, locate the appropriate model and drive on the RPM selection table.
5.
Review the BHP compared to the motor options available. Select the appropriate motor.
6.
Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
7.
Determine turns open to obtain the desired operation point.
Example
1.
19000 CFM
2.
5.4 iwg
3.
Using the supply air blower performance table below, the following data point was located: 1150 RPM & 36 BHP.
4.
Using the RPM selection table below, Size X and Model Y is found.
5.
36 BHP exceeds the maximum continuous BHP rating of the 30 HP motor. The 40 HP motor is required.
6.
1150 RPM is within the range of the 30 & 40 HP drives, but step 5 requires the 40 HP motor.
7.
Using the 40 HP motor and drive, 5.5 turns open will achieve 1150 RPM.
Example Supply Air Blower Performance
Air Flow
(CFM)
18000
19000
20000
21000
Available External Static Pressure - IWG
3.0
3.4
3.8
4.2
4.6
5.0
5.4
5.8
6.2
6.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
800
850
900
950
10.00
12.00
14.00
16.00
30 HP & Field Supplied Drive
850 14.00 900 18.00
900 16.00 950 20.00
950 18.00 1000 22.00
1000 20.00 1050 24.00
950
1000
1050
1100
22.00
24.00
26.00
28.00
1000
1050
1100
1150
Standard 30 HP & Drive
26.00 1050 30.00 1100
28.00 1100 32.00 1150
30.00 1150 34.00 1200
32.00 1200 36.00 1250
34.00
36.00
38.00
40.00
1150
1200
1250
1300
Alternate 40 HP & Drive
38.00 1200 42.00 1250
40.00 1250 44.00 1300
42.00 1300 46.00 1350
44.00 1350 48.00 1400
46.00
48.00
50.00
52.00
Table X: RPM Selection
Size
(Tons)
Model
HP
X
Y
30
40
Unitary Products Group
Max
BHP
34.50
46.00
Motor
Sheave
1VL51
1VL63
Blower
Sheave
BK99
BK67
6 Turns
Open
1000
1125
5 Turns
Open
1025
1175
4 Turns
Open
1045
1250
3 Turns
Open
1060
1325
2 Turns
Open
1110
1400
1 Turn
Open
1150
1475
Fully
Closed
N/A
N/A
77
246824-YTG-E-0507
Altitude/Temperature Correction Factors
Air
Temp.
40
50
60
70
80
90
100
0
1.060
1.039
1.019
1.000
0.982
0.964
0.946
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
Altitude (Ft.)
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
&RUUHFWLRQ)DFWRU
6HD/HYHO
IW
IW
IW
IW
IW
IW
IW
IW
IW
IW
$LU7HPSHUDWXUHž)
78
Unitary Products Group
246824-YTG-E-0507
Gas Heat Minimum Supply Air
Supply Air (CFM)
Size
(Tons)
Model
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Heat Size
Cooling
10
15
10
15
10
15
15
20
15
20
ZH/ZR
ZH/ZR
ZH/ZR
ZH/ZR
ZH/ZR
Heating
Min
1950
1950
2250
2250
2550
2550
3000
3000
3750
3750
Max
3250
3250
3750
3750
4250
4250
5000
5000
6250
6250
Min
1950
1950
2250
2250
2550
2550
3000
3000
3750
3750
Max
3250
3250
3750
3750
4250
4250
5000
5000
6250
6250
9
1950
1950
1950
2250
2250
2250
2550
2550
2550
-
Minimum Supply Air (CFM)
Heater kW
18
24
36
1950
1950
1950
1950
1950
1950
1950
1950
1950
2250
2250
2250
2250
2250
2250
2250
2250
2250
2550
2550
2550
2550
2550
2550
2550
2550
2550
3000
3000
3000
3000
3000
3000
3000
3000
3000
3750
3750
3750
3750
3750
3750
3750
3750
3750
Electric Heat Minimum Supply Air
Size
(Tons)
Model
Voltage
078
(6.5)
ZH/ZR/XP
090
(7.5)
ZH/ZR/XP
102
(8.5)
ZH/ZR/XP
120
(10)
ZH/ZR/XP
150
(12.5)
ZH/ZR/XP
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
54
3500
3000
3500
4000
3750
3750
Indoor Blower Specifications
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Motor
Model
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
HP
RPM
Eff.
SF
Frame
1-1/2
2
1-1/2
3
2
3
2
3
3
5
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.87
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
56
56
56
56
56
56
56
56
56
184T
Motor Sheave
Datum Dia.
Bore (in.)
(in.)
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
4.3 - 5.3
1-1/8
Model
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
Datum Dia.
Bore (in.)
(in.)
7.0
1
6.0
1
7.0
1
5.7
1
8.5
1
7.0
1
8.0
1
7.0
1
7.0
1
6.7
1
Model
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Power Exhaust Specifications
Model
Voltage
2PE04703225
2PE04703246
2PE04703258
208/230-1-60
460-1-60
575-1-60
HP
3/4
3/4
3/4
Motor
RPM1
1075
1075
1050
QTY
1
1
1
LRA
7.8
3.4
2.9
Motor
FLA
5
2.2
1.5
MCA
6.3
2.8
1.9
Fuse Size
10
5
4
CFM @
0.1 ESP
3800
3800
3800
1. Motors are multi-tapped and factory wired for high speed.
Unitary Products Group
79
246824-YTG-E-0507
Electric Heat Multipliers
Voltage
Nominal
kW Capacity Multipliers1
Applied
208
230
460
575
240
480
600
0.75
0.92
0.92
0.92
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Sound Performance
Indoor Sound Power Levels
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Model
CFM
ESP
(IWG)
Blower
RPM
BHP
Sound Rating1
dB (A)
63
Sound Power, dB (10-12) Watts
Octave Band Centerline Frequency (Hz)
125
250
500
1000
2000
4000
8000
ZH/ZR/XP
2600
0.6
812
1.14
74
71
73
73
71
69
65
65
60
ZH/ZR/XP
3000
0.6
854
1.47
77
74
76
76
74
72
68
68
63
ZH/ZR/XP
3400
0.6
872
1.65
80
77
79
79
77
75
71
71
66
ZH/ZR/XP
4000
0.6
959
2.29
83
80
82
82
80
78
74
74
69
ZH/ZR/XP
5000
0.6
1132
3.74
87
84
86
86
84
82
78
78
73
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.
Outdoor Sound Power Levels
ZH/ZR/XP078-150
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Model
Sound Rating1
dB (A)
125
Octave Band Centerline Frequency (Hz)
250
500
1000
2000
4000
8000
ZH
83
88.0
82.5
81.5
78.0
73.0
69.0
62.0
ZH
83
89.5
83.5
82.0
78.0
72.5
68.0
60.5
ZH
90
93.5
92.5
88.0
84.5
79.0
74.5
68.0
ZH
90
94.0
92.0
88.5
84.5
80.0
75.5
68.5
ZH
84
90.0
84.5
81.5
77.5
72.0
68.5
61.5
ZR/XP
83
88.0
82.5
81.5
78.0
73.0
69.0
62.0
ZR/XP
83
89.5
83.5
82.0
78.0
72.5
68.0
60.5
ZR/XP
83
89.0
84.5
81.5
78.0
72.5
68.5
70.5
ZR/XP
83
89.5
83.5
81.0
78.0
72.0
68.5
70.5
ZR/XP
84
90.0
84.5
81.5
77.5
72.0
68.5
61.5
1. Rated in accordance with ARI 270 standard.
80
Unitary Products Group
246824-YTG-E-0507
XP078-150 Standard Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
6.2
5.5
0.0
230
14.1
95.0
22.0
1.5
6.2
5.5
0.0
460
6.4
45.0
10.0
0.8
3.1
2.2
0.0
575
5.4
38.0
8.5
0.6
2.4
1.8
0.0
208
15.6
83.1
21.4
1.5
6.2
5.5
0.0
230
15.6
83.1
21.4
1.5
6.2
5.5
0.0
460
6.9
41.0
9.7
0.8
3.1
2.2
0.0
575
5.4
33.0
7.5
0.6
2.4
1.8
0.0
208
16.7 120.0 26.0
1.5
8.2
5.5
0.0
230
16.7 120.0 26.0
1.5
8.2
5.5
0.0
460
8.7
60.0
13.5
0.8
4.1
2.2
0.0
575
6.7
42.0
10.5
0.6
3.6
1.8
0.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
Stages
Amps
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
40.9
64.5
87.8
103.4
129.4
40.9
68.0
95.1
113.1
143.2
19.1
32.6
46.2
55.2
70.2
15.8
26.6
37.4
44.6
56.6
44.3
67.9
91.1
106.8
132.8
44.3
71.4
98.4
116.5
146.5
20.2
33.8
47.3
56.3
71.3
15.8
26.6
37.4
44.6
56.6
48.8
72.4
95.6
111.2
137.3
48.8
75.8
102.9
120.9
151.0
25.3
38.8
52.3
61.4
76.4
19.9
30.7
41.5
48.7
60.8
46.4
70.0
93.3
108.9
134.9
46.4
73.5
100.6
118.6
148.7
21.3
34.8
48.4
57.4
72.4
17.6
28.4
39.2
46.4
58.4
49.8
73.4
96.6
112.3
138.3
49.8
76.9
103.9
122.0
152.0
22.4
36.0
49.5
58.5
73.5
17.6
28.4
39.2
46.4
58.4
54.3
77.9
101.1
116.7
142.8
54.3
81.3
108.4
126.4
156.5
27.5
41.0
54.5
63.6
78.6
21.7
32.5
43.3
50.5
62.6
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
50
60
70
70
90
100
110
110
150
150
50
60
70
80
100
110
125
125
150
150
25
25
35
35
50
50
60
60
80
80
20
20
30
30
40
40
45
50
60
60
50
60
70
80
100
100
110
125
150
150
50
60
80
80
100
110
125
125
150
175
25
25
35
40
50
50
60
60
80
80
20
20
30
30
40
40
45
50
60
60
60
70
80
80
100
110
125
125
150
150
60
70
80
90
110
110
125
150
175
175
30
35
40
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
97
246824-YTG-E-0507
XP078-150 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
1.5
8.2
5.5
0.0
230
17.9 120.0 28.0
1.5
8.2
5.5
0.0
460
9.6
70.0
15.0
0.8
4.1
2.2
0.0
575
7.4
53.0
11.5
0.6
3.6
1.8
0.0
208
23.1 160.0 36.0
1.5
10.9
5.5
0.0
230
23.1 160.0 36.0
1.5
10.9
5.5
0.0
460
12.2
87.0
19.0
0.8
5.3
2.2
0.0
575
8.7
62.0
13.5
0.6
4.1
1.8
0.0
120
(10)
150
(12.5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
51.5
98.3
113.9
140.0
151.1
51.5
105.6
123.6
153.7
153.7
27.3
54.4
63.4
78.4
78.4
21.5
43.1
50.3
62.3
62.3
68.9
115.7
131.3
157.4
157.4
68.9
123.0
141.0
171.1
171.1
36.0
63.0
72.0
87.1
87.1
26.1
47.7
54.9
67.0
67.0
57.0
103.8
119.4
145.5
158.0
57.0
111.1
129.1
159.2
159.2
29.5
56.6
65.6
80.6
80.6
23.3
44.9
52.1
64.1
64.1
74.4
121.2
136.8
162.9
162.9
74.4
128.5
146.5
176.6
176.6
38.2
65.2
74.2
89.3
89.3
27.9
49.5
56.7
68.8
68.8
1
Model
kW
Stages
Amps
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
60
70
100
110
125
125
150
150
175
175
60
70
110
125
125
150
175
175
175
175
35
35
60
60
70
70
80
90
80
90
25
30
45
45
60
60
70
70
70
70
90
90
125
125
150
150
175
175
175
175
90
90
125
150
150
150
175
200
175
200
45
50
70
70
80
80
90
90
90
90
30
35
50
50
60
60
70
70
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
98
Unitary Products Group
246824-YTG-E-0507
XP078-150 Hi Static Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
8.2
5.5
0.0
230
14.1
95.0
22.0
1.5
8.2
5.5
0.0
460
6.4
45.0
10.0
0.8
4.1
2.2
0.0
575
5.4
38.0
8.5
0.6
3.6
1.8
0.0
208
15.6
83.1
21.4
1.5
10.9
5.5
0.0
230
15.6
83.1
21.4
1.5
10.9
5.5
0.0
460
6.9
41.0
9.7
0.8
5.3
2.2
0.0
575
5.4
33.0
7.5
0.6
4.1
1.8
0.0
208
16.7 120.0 26.0
1.5
10.9
5.5
0.0
230
16.7 120.0 26.0
1.5
10.9
5.5
0.0
460
8.7
60.0
13.5
0.8
5.3
2.2
0.0
575
6.7
42.0
10.5
0.6
4.1
1.8
0.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
42.9
66.5
89.8
105.4
131.4
42.9
70.0
97.1
115.1
145.2
20.1
33.6
47.2
56.2
71.2
17.0
27.8
38.6
45.8
57.8
49.0
72.6
95.8
111.5
137.5
49.0
76.1
103.1
121.2
151.2
22.4
36.0
49.5
58.5
73.5
17.5
28.3
39.1
46.3
58.3
51.5
75.1
98.3
113.9
140.0
51.5
78.5
105.6
123.6
153.7
26.5
40.0
53.5
62.6
77.6
20.4
31.2
42.0
49.2
61.3
48.4
72.0
95.3
110.9
136.9
48.4
75.5
102.6
120.6
150.7
22.3
35.8
49.4
58.4
73.4
18.8
29.6
40.4
47.6
59.6
54.5
78.1
101.3
117.0
143.0
54.5
81.6
108.6
126.7
156.7
24.6
38.2
51.7
60.7
75.7
19.3
30.1
40.9
48.1
60.1
57.0
80.6
103.8
119.4
145.5
57.0
84.0
111.1
129.1
159.2
28.7
42.2
55.7
64.8
79.8
22.2
33.0
43.8
51.0
63.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
60
70
80
90
100
110
125
150
150
50
60
70
80
100
110
125
125
150
175
25
25
35
40
50
50
60
60
80
80
20
20
30
30
40
45
50
50
60
60
60
70
80
80
100
110
125
125
150
150
60
70
80
90
110
110
125
150
175
175
25
30
40
40
50
60
60
70
80
80
20
20
30
35
40
45
50
50
60
70
60
70
80
90
100
110
125
125
150
150
60
70
80
90
110
125
125
150
175
175
35
35
45
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
99
246824-YTG-E-0507
XP078-150 Hi Static Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
1.5
10.9
5.5
0.0
230
17.9 120.0 28.0
1.5
10.9
5.5
0.0
460
9.6
70.0
15.0
0.8
5.3
2.2
0.0
575
7.4
53.0
11.5
0.6
4.1
1.8
0.0
208
23.1 160.0 36.0
1.5
16.1
5.5
0.0
230
23.1 160.0 36.0
1.5
16.1
5.5
0.0
460
12.2
87.0
19.0
0.8
8.1
2.2
0.0
575
8.7
62.0
13.5
0.6
6.0
1.8
0.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
54.2
101.0
116.6
142.7
154.5
54.2
108.3
126.3
156.4
156.4
28.5
55.6
64.6
79.6
79.6
22.0
43.6
50.8
62.8
62.8
74.1
120.9
136.5
162.6
162.6
74.1
128.2
146.2
176.3
176.3
38.8
65.8
74.8
89.9
89.9
28.0
49.6
56.8
68.9
68.9
59.7
106.5
122.1
148.2
161.4
59.7
113.8
131.8
161.9
161.9
30.7
57.8
66.8
81.8
81.8
23.8
45.4
52.6
64.6
64.6
79.6
126.4
142.0
168.1
168.1
79.6
133.7
151.7
181.8
181.8
41.0
68.0
77.0
92.1
92.1
29.8
51.4
58.6
70.7
70.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
70
110
110
125
125
150
150
175
175
70
70
110
125
150
150
175
175
175
175
35
40
60
60
70
70
80
90
80
90
25
30
45
50
60
60
70
70
70
70
90
100
125
150
150
150
175
175
175
175
90
100
150
150
150
175
200
200
200
200
50
50
70
70
80
80
90
100
90
100
35
35
50
60
60
60
70
80
70
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
100
Unitary Products Group
246824-YTG-E-0507
XP078-150 Standard Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
6.2
5.5
10.0
230
14.1
95.0
22.0
1.5
6.2
5.5
10.0
460
6.4
45.0
10.0
0.8
3.1
2.2
5.0
575
5.4
38.0
8.5
0.6
2.4
1.8
4.0
208
15.6
83.1
21.4
1.5
6.2
5.5
10.0
230
15.6
83.1
21.4
1.5
6.2
5.5
10.0
460
6.9
41.0
9.7
0.8
3.1
2.2
5.0
575
5.4
33.0
7.5
0.6
2.4
1.8
4.0
208
16.7 120.0 26.0
1.5
8.2
5.5
10.0
230
16.7 120.0 26.0
1.5
8.2
5.5
10.0
460
8.7
60.0
13.5
0.8
4.1
2.2
5.0
575
6.7
42.0
10.5
0.6
3.6
1.8
4.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
50.9
74.5
97.8
113.4
139.4
50.9
78.0
105.1
123.1
153.2
24.1
37.6
51.2
60.2
75.2
19.8
30.6
41.4
48.6
60.6
54.3
77.9
101.1
116.8
142.8
54.3
81.4
108.4
126.5
156.5
25.2
38.8
52.3
61.3
76.3
19.8
30.6
41.4
48.6
60.6
58.8
82.4
105.6
121.2
147.3
58.8
85.8
112.9
130.9
161.0
30.3
43.8
57.3
66.4
81.4
23.9
34.7
45.5
52.7
64.8
56.4
80.0
103.3
118.9
144.9
56.4
83.5
110.6
128.6
158.7
26.3
39.8
53.4
62.4
77.4
21.6
32.4
43.2
50.4
62.4
59.8
83.4
106.6
122.3
148.3
59.8
86.9
113.9
132.0
162.0
27.4
41.0
54.5
63.5
78.5
21.6
32.4
43.2
50.4
62.4
64.3
87.9
111.1
126.7
152.8
64.3
91.3
118.4
136.4
166.5
32.5
46.0
59.5
68.6
83.6
25.7
36.5
47.3
54.5
66.6
Stages Amps
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
80
80
100
110
125
125
150
150
60
70
80
90
110
125
125
150
175
175
30
30
40
40
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
60
70
80
90
110
110
125
125
150
150
60
70
90
90
110
125
150
150
175
175
30
30
40
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
70
80
90
90
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
35
40
45
50
60
60
70
70
90
90
30
30
35
40
50
50
60
60
70
70
101
246824-YTG-E-0507
XP078-150 Standard Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
1.5
8.2
5.5
10.0
230
17.9 120.0 28.0
1.5
8.2
5.5
10.0
460
9.6
70.0
15.0
0.8
4.1
2.2
5.0
575
7.4
53.0
11.5
0.6
3.6
1.8
4.0
208
23.1 160.0 36.0
1.5
10.9
5.5
10.0
230
23.1 160.0 36.0
1.5
10.9
5.5
10.0
460
12.2
87.0
19.0
0.8
5.3
2.2
5.0
575
8.7
62.0
13.5
0.6
4.1
1.8
4.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
61.5
108.3
123.9
150.0
163.6
61.5
115.6
133.6
163.7
163.7
32.3
59.4
68.4
83.4
83.4
25.5
47.1
54.3
66.3
66.3
78.9
125.7
141.3
167.4
167.4
78.9
133.0
151.0
181.1
181.1
41.0
68.0
77.0
92.1
92.1
30.1
51.7
58.9
71.0
71.0
67.0
113.8
129.4
155.5
170.5
67.0
121.1
139.1
169.2
169.2
34.5
61.6
70.6
85.6
85.6
27.3
48.9
56.1
68.1
68.1
84.4
131.2
146.8
172.9
173.9
84.4
138.5
156.5
186.6
186.6
43.2
70.2
79.2
94.3
94.3
31.9
53.5
60.7
72.8
72.8
1
Stages Amps
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
110
125
125
150
150
175
175
175
70
80
125
125
150
150
175
175
175
175
40
40
60
70
70
80
90
90
90
90
30
30
50
50
60
60
70
70
70
70
100
100
150
150
150
150
175
175
175
175
100
100
150
150
175
175
200
200
200
200
50
50
70
80
80
80
100
100
100
100
35
40
60
60
60
70
80
80
80
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
102
Unitary Products Group
246824-YTG-E-0507
XP078-150 Hi Static Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
8.2
5.5
10.0
230
14.1
95.0
22.0
1.5
8.2
5.5
10.0
460
6.4
45.0
10.0
0.8
4.1
2.2
5.0
575
5.4
38.0
8.5
0.6
3.6
1.8
4.0
208
15.6
83.1
21.4
1.5
10.9
5.5
10.0
230
15.6
83.1
21.4
1.5
10.9
5.5
10.0
460
6.9
41.0
9.7
0.8
5.3
2.2
5.0
575
5.4
33.0
7.5
0.6
4.1
1.8
4.0
208
16.7 120.0 26.0
1.5
10.9
5.5
10.0
230
16.7 120.0 26.0
1.5
10.9
5.5
10.0
460
8.7
60.0
13.5
0.8
5.3
2.2
5.0
575
6.7
42.0
10.5
0.6
4.1
1.8
4.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
52.9
76.5
99.8
115.4
141.4
52.9
80.0
107.1
125.1
155.2
25.1
38.6
52.2
61.2
76.2
21.0
31.8
42.6
49.8
61.8
59.0
82.6
105.8
121.5
147.5
59.0
86.1
113.1
131.2
161.2
27.4
41.0
54.5
63.5
78.5
21.5
32.3
43.1
50.3
62.3
61.5
85.1
108.3
123.9
150.0
61.5
88.5
115.6
133.6
163.7
31.5
45.0
58.5
67.6
82.6
24.4
35.2
46.0
53.2
65.3
58.4
82.0
105.3
120.9
146.9
58.4
85.5
112.6
130.6
160.7
27.3
40.8
54.4
63.4
78.4
22.8
33.6
44.4
51.6
63.6
64.5
88.1
111.3
127.0
153.0
64.5
91.6
118.6
136.7
166.7
29.6
43.2
56.7
65.7
80.7
23.3
34.1
44.9
52.1
64.1
67.0
90.6
113.8
129.4
155.5
67.0
94.0
121.1
139.1
169.2
33.7
47.2
60.7
69.8
84.8
26.2
37.0
47.8
55.0
67.1
Stages Amps
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
80
90
100
110
125
125
150
150
60
70
80
90
110
125
150
150
175
175
30
30
40
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
70
80
90
90
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
30
35
45
45
60
60
70
70
80
90
25
25
35
35
45
45
60
60
70
70
70
80
90
100
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
40
40
50
50
60
70
70
70
90
90
30
30
40
40
50
50
60
60
70
70
103
246824-YTG-E-0507
XP078-150 Hi Static Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
1.5
10.9
5.5
10.0
230
17.9 120.0 28.0
1.5
10.9
5.5
10.0
460
9.6
70.0
15.0
0.8
5.3
2.2
5.0
575
7.4
53.0
11.5
0.6
4.1
1.8
4.0
208
23.1 160.0 36.0
1.5
16.1
5.5
10.0
230
23.1 160.0 36.0
1.5
16.1
5.5
10.0
460
12.2
87.0
19.0
0.8
8.1
2.2
5.0
575
8.7
62.0
13.5
0.6
6.0
1.8
4.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
64.2
111.0
126.6
152.7
167.0
64.2
118.3
136.3
166.4
166.4
33.5
60.6
69.6
84.6
84.6
26.0
47.6
54.8
66.8
66.8
84.1
130.9
146.5
172.6
173.5
84.1
138.2
156.2
186.3
186.3
43.8
70.8
79.8
94.9
94.9
32.0
53.6
60.8
72.9
72.9
69.7
116.5
132.1
158.2
173.9
69.7
123.8
141.8
171.9
171.9
35.7
62.8
71.8
86.8
86.8
27.8
49.4
56.6
68.6
68.6
89.6
136.4
152.0
178.1
180.4
89.6
143.7
161.7
191.8
191.8
46.0
73.0
82.0
97.1
97.1
33.8
55.4
62.6
74.7
74.7
1
Stages Amps
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
80
80
125
125
150
150
175
175
175
175
80
80
125
125
150
150
175
175
175
175
40
45
70
70
70
80
90
90
90
90
30
35
50
50
60
60
70
70
70
70
100
110
150
150
150
175
175
200
175
200
100
110
150
150
175
175
200
200
200
200
50
50
80
80
80
90
100
100
100
100
40
40
60
60
70
70
80
80
80
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
104
Unitary Products Group
246824-YTG-E-0507
XP078-150 Typical Wiring Diagrams
Typical XP078-120 Heat Pump with/without Electric Heat Wiring Diagram
Unitary Products Group
113
246824-YTG-E-0507
Typical XP150 Heat Pump with/without Electric Heat Wiring Diagram
114
Unitary Products Group
246824-YTG-E-0507
Weights and Dimensions
ZH/ZR/XP078-150 Unit Weights
Unit 4 Point Load Weight
Unit 6 Point Load Weight
FRONT
FRONT
LEFT
LEFT
B
C
B
A
A
E
F
D
Y
X
FRONT
LEFT
Weight (lbs.)
Center of Gravity
Size
Model
Shipping Operating
X
Y
(Tons)
078
ZH
905
900
38
23
(6.5)
090
ZH
925
920
38
23
(7.5)
102
ZH
1140
1135
38
25.5
(8.5)
120
ZH
1140
1135
38
25.5
(10)
150
ZH
1405
1400
51
25.5
(12.5)
078
ZR
970
965
38
23
(6.5)
090
ZR
970
965
38
23
(7.5)
102
ZR
1205
1200
38
25.5
(8.5)
120
ZR
1205
1200
38
25.5
(10)
150
ZR
1470
1465
51
25.5
(12.5)
078
XP
925
920
38
23
(6.5)
090
XP
925
920
38
23
(7.5)
102
XP
1140
1135
38
25.5
(8.5)
120
XP
1140
1135
38
25.5
(10)
150
XP
1405
1400
51
25.5
(12.5)
Unitary Products Group
D
C
4 Point Load Location (lbs.)
A
B
C
D
A
6 Point Load Location (lbs.)
B
C
D
E
F
201
150
234
315
141
115
95
149
180
221
206
153
240
322
144
117
97
152
184
225
281
209
275
369
197
160
133
175
211
259
281
209
275
369
197
160
133
175
211
259
258
347
456
339
164
198
243
319
260
216
216
161
251
337
151
123
102
160
193
236
216
161
251
337
151
123
102
160
193
236
297
221
291
390
208
170
141
185
223
274
297
221
291
390
208
170
141
185
223
274
270
363
477
355
172
207
254
334
272
226
206
153
240
322
144
117
97
152
184
225
206
153
240
322
144
117
97
152
184
225
281
209
275
369
197
160
133
175
211
259
281
209
275
369
197
160
133
175
211
259
258
347
456
339
164
198
243
319
260
216
115
246824-YTG-E-0507
ZH/ZR/XP078-150 Unit Accessory Weights
Unit Accessory
Economizer
Power Exhaust
Electric Heat1
Gas Heat2
Weight (lbs.)
Shipping
Operating
90
85
155
150
80
80
110
110
1. Weight given is for the maximum heater size available
(54KW).
2. Weight given is for the maximum number of tube heat
exchangers available (8 tube).
ZH/ZR/XP078-150 Unit Dimensions
ZH/ZR/XP078-120
ZH/ZR/XP150
116
Unitary Products Group
246824-YTG-E-0507
ZH/ZR/XP078-150 Unit Physical Dimensions
Unit Model Number
A
42
42
50 3/4
50 3/4
50 3/4
078
090
102
120
150
Detail A
B
89
89
89
89
119 1/2
Base
Pan
17-13/16
E
15 3/16
15 3/16
17 3/16
17 3/16
17 3/16
F
6 3/16
6 3/16
6 3/16
6 3/16
6 3/16
Detail B
Gas Pipe Inlet
5-1/4
Dimension (in.)
C
D
22 1/8
18 3/16
22 1/8
18 3/16
30 3/16
24 3/16
30 3/16
24 3/16
30 3/16
24 3/16
View of Wall Across from Coil
ZH/ZR/XP078-150 Unit Clearances
Direction
Top1
Front
Rear
Distance (in.)
72
36
36
Direction
Right
Left
Bottom2
Distance (in.)
12
36
0
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustable floors made from wood or class A, B or C roof covering materials.
ZH/ZR/XP078-150 Unit Bottom Duct Openings
Unitary Products Group
117
246824-YTG-E-0507
ZH/ZR/XP078-150 Unit Electrical Entry
'LVFRQQHFW6ZLWK&RYHU
3RZHU(QWU\‘
&RQWURO(QWU\‘
3RZHU(QWU\‘
&RQYHQLHQFH2XWOHW&RYHU
&RQYHQLHQFH2XWOHW
3RZHU(QWU\‘
)5217
ZH/ZR/XP078-120 Unit Side Duct Openings
'RW3OXJV
$
5HWXUQ
$LU
6XSSO\
$LU
'
%
&
118
Unitary Products Group
246824-YTG-E-0507
ZH/ZR/XP150 Unit Side Duct Openings
'RW3OXJV
$
'
%
&
Side Duct Dimensions
Unit Model Number
078
090
102
120
150
A
27 3/4
27 3/4
28 1/4
28 1/4
28 1/4
Dimension (in.)
B
C
12 1/16
27 1/2
12 1/16
27 1/2
18 1/16
28 1/4
18 1/16
28 1/4
18 1/16
28 1/4
D
16
16
18 1/4
18 1/4
18 1/4
ZH/ZR/XP078-150 Unit Left Duct Opening
Unitary Products Group
119
246824-YTG-E-0507
ZH/ZR/XP078-150 Unit Accessory Dimensions
ZH/ZR/XP078-150 Roof Curb
RIGHT
80-5/8
INSULATED DECK UNDER
CONDENSER SECTION
20
SUPPLY
20
6
RETURN
2 TYP.
30
INSULATED DECK UNDER
COMPRESSOR SECTION
50-1/2
FRONT
8 or 14
ZH/ZR/XP078-150 Transition Roof Curb
7<3
5(7851
6833/<
)5217
120
5,*+7
Unitary Products Group
246824-YTG-E-0507
ZH/ZR/XP078-150 Economizer Assembly
58 1/4
88 1/4
39 1/2
or
47 1/2
Outside Air
Intake Hood
35 3/4
Relief Hood for
Power Exhaust or
Barometric Relief
26
Unitary Products Group
25 3/4
26
30 1/4
121
246824-YTG-E-0507
Economizer Options
Economizer Usage
Application
Cabinet Height
Description
Model
Bottom Return
All
Downflow economizer with barometric relief
2EE04705424
Side Return
All
Horizontal economizer without barometric relief
2EE047055241
42"
Slab Economizer, 42” tall cabinet
2EE047056242
50"
Slab Economizer, 50” tall cabinet
2EE047052242
ERV or End Return
1. Barometric relief must be ordered seperately and installed in duct work.
2. Barometric relief or fresh air hood not included. Must be ordered seperately.
Factory Installed Downflow Economizer
2EE04705424
Fresh Air Hood
2EE04705424
2EE04705424
2EE04705424
Fresh Air Damper Return Air Damper
Barometric Relief Damper
2EE04705424
Barometric Relief Hood
Field Installed Downflow Economizer W/Power Exhaust
2EE04705424
Fresh Air Hood
122
2EE04705424
2EE04705424
Fresh Air Damper Return Air Damper
2PE047032XX
Power Exhaust
2EE04705424
Barometric Relief Damper
2EE04705424
Barometric Relief Hood
Unitary Products Group
246824-YTG-E-0507
Field Installed Horizontal Economizer W/Power Exhaust
2EE04705524
Return Air Damper
Field Installed
Duct Work
2EE04705524
Fresh Air Damper
2PE047032XX
Power Exhaust
1EH0408
Barometric
Relief Damper
1EH0408
Barometric
Relief Hood
2EE04705524
Fresh Air Hood
Slab Economizer Downflow W/Power Exhaust
1EH0409
Fresh Air Hood
2EE04705X24
Slab Economizer
2PE047032XX
Power Exhaust
1EH0409 Barometric
Relief Damper
Unitary Products Group
1EH0409 Barometric
Relief Hood
123
Slab Economizer End Return W/Power Exhaust
1EH0409
Fresh Air Hood
Field Installed
Duct Work
2EE04705X24
Slab Economizer
1EH0409
Barometric Relief Hood
1EH0409
Barometric Relief Damper
Subject to change without notice. Printed in U.S.A.
Copyright © 2007 by Unitary Products Group. All rights reserved.
Unitary
Products
Group
2PE047032XX
Power Exhaust
246824-YTG-E-0507
Supersedes: 246824-YTG-D-0806
5005
York
Drive
Norman
OK
73069