Siemens 9300 Switchboard Meter Installation Instructions

Below you will find brief information for 9300 Switchboard Meter. This document provides instructions for installing and wiring the 9300 Series switchboard meter. It includes information on unit dimensions, suggested mounting hole dimensions, voltage and current terminals, powering the switchboard meter, connecting the unit’s chassis ground, and power system wiring diagrams.

PDF Download
Document
Siemens 9300 Switchboard Meter Installation Instructions | Manualzz

Advertisement

Advertisement

Advertisement

Key features

  • Switchboard compatible
  • Pre-wired meter chassis
  • Compatible with S1 or FT21 cases
  • Includes display unit and ribbon cable
  • Detailed installation instructions
  • Power system wiring diagrams included
  • Safety warnings and precautions
  • Transformer-coupled systems
  • Chassis ground connection
  • Optional P24 power supply

Frequently asked questions

The switchboard meter is pre-wired for use in systems that use PTs with 120V, 110V, 69.3V or 63.5V secondaries. Using the switchboard meter in other applications or in higher voltage systems may permanently damage the meter.

The ground terminal on the rear of the switchboard case provides the chassis ground connection. The chassis ground source must be installed before the switchboard meter can be installed — a good low impedance chassis ground connection is essential for the meter’s surge and transient protection circuitry to function effectively. The ground should be wired to the earth ground using a dedicated AWG 14 (2.5mm2) or larger wire to a point where there will be no voltage error due to distribution voltage drops. Do not rely on metal door hinges as a ground path. Ensure that the ground terminal screw is tightened down securely onto the ground wire.

The document provides wiring diagrams for 4-wire Wye, 2½-element, 2 PT, 3-wire Delta, 2-element, 2 PT & 2 CT, and other configurations. Refer to the document for specific wiring instructions and diagrams.