PROFIBUS Tester BC-700-PB - Encon

PROFIBUS Tester BC-700-PB - Encon
User Manual
PROFIBUS Tester 5 BC-700-PB
Getting Started with PROFIBUS Tester 5 BC-700-PB
Insert graphic file
from e.g.
\\Sfiler\iap_intern\10_Marketing\02_Materials\02-11_Photos
For positioning data see
..\<projectdirectory>\Images\readme_insert_graphics.txt"
Version: MMA-NN-006005-EN-1408-1.01
© Copyright 2014 Softing Industrial Automation GmbH
Disclaimer of liability
The information contained in these instructions corresponds to the technical status at the time of printing of it and is
passed on with the best of our knowledge. The information in these instructions is in no event a basis for warranty
claims or contractual agreements concerning the described products, and may especially not be deemed as warranty
concerning the quality and durability pursuant to Sec. 443 German Civil Code. We reserve the right to make any
alterations or improvements to these instructions without prior notice. The actual design of products may deviate from
the information contained in the instructions if technical alterations and product improvements so require.
It may not, in part or in its entirety, be reproduced, copied, or transferred into electronic media.
Softing Industrial Automation GmbH
Richard-Reitzner-Allee 6
85540 Haar / Germany
Tel: + 49 89 4 56 56-0
Fax: + 49 89 4 56 56-488
Internet: http://industrial.softing.com
Email:
[email protected]
Support: [email protected]
The latest version of this manual is also available in the Softing download area at: http://industrial.softing.com.
Table of Contents
Table of Contents
Chapter 1
Introduction
..................................................................................7
1.1
1.2
1.2.1
About PROFIBUS
................................................................................................
Tester 5 BC-700-PB
7
About this document
................................................................................................ 7
Purpose
..................................................................................................................... 7
1.2.2
Target
group
.....................................................................................................................
7
1.2.3
Conventions
used
.....................................................................................................................
8
1.2.4
Document
history
.....................................................................................................................
8
1.3
1.4
1.4.1
Scope of delivery
................................................................................................ 8
Optional accessories
................................................................................................ 9
D-sub
adapter cable for testing live systems
.....................................................................................................................
9
1.4.2
Adapter
set for M12 connection technology
.....................................................................................................................
10
1.4.3
Fieldbus
shield digital leakage current clamp
.....................................................................................................................
10
1.4.4
Adapter
for testing PROFIBUS PA networks
.....................................................................................................................
10
1.4.5
Spare
rechargeable battery
.....................................................................................................................
11
1.4.6
Service
interfaces for PROFIBUS DP
.....................................................................................................................
12
type D-sub
1.4.6.1 Connection
.......................................................................................................
12
type M12
1.4.6.2 Connection
.......................................................................................................
13
1.5
1.6
Chapter 2
2.1
2.2
Chapter 3
3.1
3.2
3.3
System requirements
................................................................................................ 13
Connectors and
................................................................................................
controls
14
Prepare..................................................................................15
device
Insert battery ................................................................................................ 15
Charge battery
................................................................................................ 16
Startup..................................................................................17
Power-up ................................................................................................ 17
Power-up behaviour
................................................................................................
without USB connection
17
Power-up behaviour
................................................................................................
with USB connected
18
Chapter 4
Power-off
and sleep mode
..................................................................................19
Chapter 5
Install software
and connect to PC
..................................................................................20
Chapter 6
Connection
to PROFIBUS
..................................................................................21
6.1
6.1.1
General information
................................................................................................ 21
Possible
side effects when testing a live bus
.....................................................................................................................
21
PROFIBUS Tester BC-700-PB - User Manual
3
Table of Contents
6.1.2
Connection
types
.....................................................................................................................
21
6.1.3
Adapter
cable
.....................................................................................................................
22
6.1.4
Strain
relief
.....................................................................................................................
22
6.1.5
Using
the security lock port
.....................................................................................................................
23
6.1.6
Test
locations
.....................................................................................................................
23
6.2
6.3
6.3.1
Simple connection
................................................................................................
for tests during system shutdown
23
Connection for
................................................................................................
testing a live bus (DP)
24
Connection
via D-sub connector with service socket
.....................................................................................................................
25
6.3.2
Direct
cable connection
.....................................................................................................................
26
6.3.3
Connection
via M12 connector
.....................................................................................................................
27
6.4
6.5
6.5.1
Master simulator,
................................................................................................
topology scan and cable test
27
Connecting to................................................................................................
PROFIBUS-PA networks
29
Test
locations
.....................................................................................................................
29
6.5.2
Requirements
for analyzing a live bus
.....................................................................................................................
31
6.5.3
Analyzing
during system shutdown
.....................................................................................................................
31
6.5.4
Bus
connection
.....................................................................................................................
31
Chapter 7
7.1
7.2
7.3
7.4
7.5
7.6
Display..................................................................................32
and controls in stand-alone mode
Main display ................................................................................................ 32
User interface................................................................................................ 32
Operating functions
................................................................................................
and softkeys
34
Device status................................................................................................ 35
Menu functions
................................................................................................ 36
Organize and................................................................................................
store test results
39
Chapter 8
Import data
into the PC
..................................................................................41
Chapter 9
Licenses
..................................................................................42
Chapter 10
Firmware
update
..................................................................................43
Chapter 11
Maintenance
and service
..................................................................................44
Chapter 12
Troubleshooting
..................................................................................45
Chapter 13
Tips and
tricks for cable testing
..................................................................................47
13.1
13.2
13.3
Chapter 14
14.1
4
Assessment criteria
................................................................................................ 47
List of fault indications
................................................................................................
and remedial measures
48
Metering the cable
................................................................................................
segment length correctly
51
Notes on
battery use
..................................................................................53
Lithium backup
................................................................................................
battery
53
PROFIBUS Tester BC-700-PB - User Manual
Table of Contents
14.2
Rechargeable................................................................................................
battery pack
53
14.2.1 Guidelines
and warnings on battery use
.....................................................................................................................
53
14.2.2 Charging
..................................................................................................................... 54
14.2.3 Discharging
..................................................................................................................... 55
14.2.4 Storage
and transportation
.....................................................................................................................
55
14.2.5 Battery
life
.....................................................................................................................
55
14.2.6 Battery
warranty
.....................................................................................................................
55
Chapter 15
Technical
data
..................................................................................56
Chapter 16
Declarations
by the manufacturer
..................................................................................58
Chapter 17
Recycling
..................................................................................59
PROFIBUS Tester BC-700-PB - User Manual
5
This page is intentionally left blank.
Chapter 1 - Introduction
1
Introduction
1.1
About PROFIBUS Tester 5 BC-700-PB
The PROFIBUS Tester 5 BC-700-PB is a powerful tool that allows full testing of the bus
physics and bus communication on PROFIBUS DP and PROFIBUS PA segments
(option). Using the integrated master simulator, you can also test the bus physics if the
PLC is currently not in operation, or individually check "suspicious" bus stations. The cable
test function examines the cabling in PROFIBUS DP segments, locates unwanted
reflections on the line and verifies proper termination of cable segments. The tool is
powered either by its built-in battery or through an external AC adapter.
The PROFIBUS Tester 5 BC-700-PB is the first battery-powered tester, which combines
the assessment of bus physics and bus communication as well as cable testing in one
device. It is therefore the only and truly mobile PROFIBUS diagnostic tool.
1.2
About this document
Read this manual before starting
For damages due to improper connection, implementation or operation
Softing refuses any liability according to our existing guarantee obligations.
CAUTION
Refer also to the safety precautions for battery and battery pack in section
Notes on battery use 53 .
1.2.1
Purpose
This document describes PROFIBUS Tester 5 BC-700-PB. It provides information about
putting into service and also provides detailed information regarding its safe and correct
operation.
1.2.2
Target group
This document is addressed to operating staff which is adept in operating PROFIBUSsystems such as:
Maintenance personnel
Commissioner
Application engineers and developers
Trainers
PROFIBUS Tester BC-700-PB - User Manual
7
Chapter 1 - Introduction
1.2.3
Conventions used
The following conventions are used throughout Softing customer documentation:
Keys, buttons, menu items, commands and
Open Start
Control Panel
other elements involving user interaction are Programs
set in bold font and menu sequences are
separated by an arrow
Buttons from the user interface are enclosed Press [Start] to start the application
in brackets and set to bold typeface
MaxDlsapAddressSupported=23
Coding samples, file extracts and screen
output is set in Courier font type
Filenames and directories are written in italic Device description files are located in C:
\StarterKit\delivery\software\Device
Description files
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury.
Note
This symbol is used to call attention to notable information that should be
followed during installation, use, or servicing of this device.
Hint
This symbol is used when providing you with helpful user hints.
1.2.4
1.3
Document history
Document version
Modifications compared to the previous version
Version 1.00
Version 1.01
none - initial document version
Editorial modifications due to internal review
Order numbers for optional accessories added
New device status symbols added
New cable test note added
Scope of delivery
The PROFIBUS Tester 5 comes in a carrying case comprising:
Test tool with RS485 interface
Rechargeable battery pack (internal battery)
Wide-range power supply with European and US mains power cables
RS485 D-sub adapter cable BC-600-PB-CB-DSUB-2 "Standard" (cable petrol blue,
light connector) for PROFIBUS DP
8
PROFIBUS Tester BC-700-PB - User Manual
Chapter 1 - Introduction
USB cable, 3 m
Terminal block for trigger input/output
CD-ROM with driver software, PC software and detailed integrated help system in
English and German
PROFIBUS Tester 5 BC-700-PB User Manual and Quick Startup Guide for the
PROFIBUS Diagnostics Suite PC software.
Figure 1: PROFIBUS Tester 5 BC-700-PB with carrying case
1.4
Optional accessories
1.4.1
D-sub adapter cable for testing live systems
This D-sub adapter cable is optimized for reduced influence on live PROFIBUS DP
segment operation. Thereby it is most suitable for testing of running plants. The risk of
critical influences on bus operation which can cause a plant standstill is significantly
reduced.
Note
When using this cable it is not possible to use the three active functions
master simulator, topology scan and cable testing (see Master simulator,
topology scan and cable test 27 ).
PROFIBUS Tester BC-700-PB - User Manual
9
Chapter 1 - Introduction
Figure 2: D-sub adapter cable with reduced influence on bus operation
Softing Order No.: BC-600-PB-CB-DSUB-1
1.4.2
Adapter set for M12 connection technology
Using the M12 adapter set, you can connect the PROFIBUS Tester 5 to field devices with
M12 connectors. The set comprises an M12 adapter cable with special pin layout and an
M12 terminating resistor that you can screw on, if required.
Figure 3: Special adapter set for M12
Softing Order No.: BC-600-PB-CB-M12
1.4.3
Fieldbus shield digital leakage current clamp
When routing PROFIBUS cables in high-interference environments, electromagnetic
interference can affect the signal quality. By measuring the shield currents with the digital
leakage current clamp, you can locate EMC problem areas and take appropriate
countermeasures. The digital leakage current clamp is supplied in a handy case, including
measuring cables. There is also an empty compartment for the fieldbus shield digital
leakage current clamp in the carrying case of the PROFIBUS Tester 5 BC-700-PB.
Figure 4: Fieldbus shield digital leakage current clamp
Softing Order No.: PB-LSZ-CHB3
1.4.4
Adapter for testing PROFIBUS PA networks
The BC-700-H1 adapter and the supplied test equipment set allows to connect the
10
PROFIBUS Tester BC-700-PB - User Manual
Chapter 1 - Introduction
PROFIBUS Tester 5 to PROFIBUS PA network segments. It converts the MBP-coded
(manchester bus powered) PROFIBUS-PA signal to a format which is appropriate for the
RS-485 interface of PROFIBUS Tester 5. The POWER LED indicates if the BC-700-H1 is
correctly connected to PROFIBUS-Tester 5. If the PA-STATE LED is lit, the BC-700-H1
adapter is correctly connected to a PROFIBUS-PA network and detects a PROFIBUS-PA
DC feeding voltage greater than 9 Volts.
Figure 5: BC-700-H1 Adapter
Figure 6: Supplied test equipment set for connecting to PROFIBUS PA segments
Softing Oder No.: DDL-NL-006010 (Adapter and test equipment)
1.4.5
Spare rechargeable battery
Intensive use of PROFIBUS-Tester 5 during the work day may exhaust the rechargeable
battery faster than expected. Plus, charging and discharging will typically wear out the
battery pack over the time (refer to Notes on battery use 53 ). PROFIBUS-Tester 5
contains an energy management. If the measures for energy saving are not sufficient or
are perceived as a disturbance it is recommended to operate on the device in conjunction
with an external power supply. Alternatively the user may use a spare rechargeable
battery.
PROFIBUS Tester BC-700-PB - User Manual
11
Chapter 1 - Introduction
Figure 7: Rechargeable battery pack
Softing Order No.: ABA-NN-006012
1.4.6
Service interfaces for PROFIBUS DP
1.4.6.1 Connection type D-sub
The D-sub service interface provides a PROFIBUS access point for testing if the existing
D-sub connectors have no service socket or if the bus stations are connected via a
terminal block. The service interface can power the terminating resistor of the D-sub
connector. You can thus use it as an active bus termination at the beginning or end of the
bus.
If the PLC allows dropping and adding bus stations on the live bus, you will need this
external bus termination to be able to exchange the first and last bus stations without
causing problems on the bus.
The compact unit is rail mounted like a terminal block and powered by an external 24 VDC
power supply. The package includes a 90° angled PROFIBUS connector with a
switchable terminating resistor.
Figure 8: D-sub service interface for testing a live bus
Softing Order No.: BC-PBMB-PB-S
12
PROFIBUS Tester BC-700-PB - User Manual
Chapter 1 - Introduction
1.4.6.2 Connection type M12
The M12 service interface comprises an IP68 rated T piece, an end cap for the service
output of the T piece, and a 1 m PROFIBUS DP cable fitted with a male/female M12
connector on each end.
Figure 9: M12 service interface for testing a live bus
Softing Order No.: BC-M12DP-PB
1.5
System requirements
Hardware
PC
USB 2.0
Operating system
Windows XP (with Microsoft Windows .NET Framework 3.5 installed) or
Windows 7 (32 bit or 64 bit) or
Windows 8 and Windows 8.1 (32 bit or 64 bit)
PROFIBUS Tester BC-700-PB - User Manual
13
Chapter 1 - Introduction
1.6
Connectors and controls
Figure 10: Connectors, buttons and status displays on the PROFIBUS Tester 5 BC-700PB
14
PROFIBUS Tester BC-700-PB - User Manual
Chapter 2 - Prepare device
2
Prepare device
2.1
Insert battery
Switch off device and disconnect charger
Always switch off the device and disconnect the charger before removing or
installing the battery.
1.
Take a screwdriver (Philipps) and open the head screws on the back side of the
device.
2.
Remove the back cover.
Figure 11: Removing the back cover of PROFIBUS-Tester 5
3.
Make sure that the provided battery is free of damage such as missing insulation of
wire leads, puncture or deformation. Insert the provided battery (standard accessory).
The connecting plug is protected against polarity reversal. Check that the connecting
plug is properly connected.
4.
Mount the back cover and fix the screws.
PROFIBUS Tester BC-700-PB - User Manual
15
Chapter 2 - Prepare device
2.2
Charge battery
Your battery has been partially charged at the factory. If the PROFIBUS Tester 5 indicates
a low charge, do the following:
1.
Connect the external AC adapter (standard accessory) to a wall outlet.
2.
Connect the external AC adapter to the PROFIBUS Tester 5.
3.
The PROFIBUS-Tester 5 will automatically start charging. The power key on top of
the PROFIBUS Tester 5 is going to blink equally during the charge process. The
graphical display remains switched off. The device is fully charged if the power key
flares up very shortly.
Alternatively you may power on the device in order to receive additional information
about the charge process. The battery charge level indicator is located at the upper
left corner of the screen.
the battery is being charged (white flash symbol).
the PROFIBUS-Tester 5 is fully charged (without mains charger connected)
the PROFIBUS-Tester 5 is fully charged (with mains charger connected)
4.
You can disconnect the AC adapter from the device, then from the wall outlet. We
recommend switching off the device in order to save energy.
Hint
You do not need to charge the battery for a specific length of time, and you
can use the device while it is charging.
16
PROFIBUS Tester BC-700-PB - User Manual
Chapter 3 - Startup
3
Startup
Hint
You can find information on the installation of PROFIBUS Diagnostics Suite
and on the corresponding drivers in section Install software and connect to
PC 20 and in the PROFIBUS Diagnostics Suite User Manual.
3.1
Power-up
1.
Acclimate to room temperature
Before being connected to the AC mains power, the PROFIBUS Tester 5 and the AC
adapter must be acclimated to room temperature to avoid condensation. This may
take up to 60 minutes.
2.
Switch on
Switch on the tool by pressing the power key at the upper front edge. Make sure that
you have either connected it to a power supply, or that you have inserted the battery.
The display lights, performs a self-test and the splash screen is shown.
Hint
We recommend operating the device solely using the wide-range power
supply supplied or using the integrated battery to avoid equalizing currents
which can falsify the test results.
The tool is powered by a built-in three cells lithium ion accumulator with 11.1 VDC.
Alternatively the tool can be powered by 24 VDC through the external wide-range power
supply.
3.2
Power-up behaviour without USB connection
If not connected to an USB port, the PROFIBUS Tester 5 starts up in stand-alone mode
(see Display and controls in stand-alone mode 32 ) and is immediately ready for testing.
During program start-up the splash screen is shown for a few seconds and displays "USB
NOT CONNECTED":
Figure 12: Splash screen – starting without USB-connection
PROFIBUS Tester BC-700-PB - User Manual
17
Chapter 3 - Startup
3.3
Power-up behaviour with USB connected
Install drivers before connecting
Make sure the required USB drivers are installed before connecting the test
tool to the PC or notebook. You can find them on the PROFIBUS
Diagnostics Suite PC software CD.
On successful completion of the self-test, the PROFIBUS Tester 5 displays:
Figure 13: Power-up display when USB connected
When you start the PROFIBUS Diagnostics Suite control and evaluation software on your
computer and select the PROFIBUS Tester and a network for testing in its user interface,
the test tool switches to PC mode.
At this point, you can also start a firmware update instead of using the control and
evaluation software (refer also to Firmware update 43 ).
The display shows:
Figure 14: Display at testing with PC software
18
PROFIBUS Tester BC-700-PB - User Manual
Chapter 4 - Pow er-off and sleep m ode
4
Power-off and sleep mode
Power-off
Press power key for more than three seconds in order to power-off the device.There is no
power consumption during the device being powered off. The device can be stored for
long a period of time.
Activate sleep mode
If you want to change manually to sleep mode, actuate shortly the power key. During sleep
mode the PROFIBUS-Tester 5 is saving energy and the power key will blink slowly.
If a measurement function is currently active, it is not possible to switch to sleep mode.
Depending on the settings in energy management, the PROFIBUS-Tester 5 may
automatically change to sleep mode after a predefined period of time.
Return to normal operation mode
You can recover normal operation very quickly by shortly actuating the power key a
second time. The lastly shown menu screen will be displayed which was active before
changing to sleep mode.
Automatic power-off
If the PROFIBUS-Tester 5 is in sleep mode for more than 2 hours, it will automatically
power-off.
PROFIBUS Tester BC-700-PB - User Manual
19
Chapter 5 - Install softw are and connect to PC
5
Install software and connect to PC
Installing
Install the software and the required drivers from your PROFIBUS Diagnostics Suite CDROM. For detailed installation instructions refer to the supplied Quick Startup Guide.
Connecting to a PC
Use the included USB cable to connect the tool to a PC or notebook.
Always connect directly to an USB port
We recommend connecting the unit directly to an USB port (USB 2.0) on the
PC or on the notebook. When you use external USB hubs, notebook docking
stations or USB 3.0 ports for connection, problems may occur.
20
PROFIBUS Tester BC-700-PB - User Manual
Chapter 6 - Connection to PROFIBUS
6
Connection to PROFIBUS
6.1
General information
6.1.1
Possible side effects when testing a live bus
Test tool side effects
When you connect a test tool, side effects on the system under test are
generally unavoidable. If the PROFIBUS is already disturbed to a certain
degree or if Simatic Diagnostic Repeaters are used, the operation of the
PROFIBUS might nevertheless be affected occasionally. Compliance with
the connection notes is mandatory.
6.1.2
Connection types
You can connect a bus station to a PROFIBUS network either
using connectors such as
o
D-sub connectors 25 , most of which have an integrated terminating resistor and,
optionally, an additional service socket
o
M12 connectors
o
Special vendor-specific hybrid connectors; they are used in combination with
special cables to supply power via the bus
13
for environments requiring increased IP ratings
or
using terminals for direct connection.
Due to the daisy-chain topology, the connection points of the bus stations are the typical
points for connecting the test tool.
PROFIBUS Tester BC-700-PB - User Manual
21
Chapter 6 - Connection to PROFIBUS
6.1.3
Adapter cable
The PROFIBUS Tester 5 is supplied with the D-sub adapter cable BC 600-PB-CB-DSUB2 „Standard" (light connector). For testing on live systems the optional D-sub adapter
cable BC-600-PB-CB-DSUB-2 is recommended. An M12 adapter set is optionally
available, see D-sub adapter cable for testing live systems 9 .
Only use original short cables
Only use the original short cables with special pin layout to connect the unit
to a PROFIBUS network.
Do not cascade more than two D-sub connectors with service sockets at
the same time!
Figure 15: Unallowed cascading of D-sub connectors
6.1.4
Strain relief
Use the strain relief supplied with the test tool. Thus you avoid the device from falling
down.
Figure 16: Recommended use of retaining strap
22
PROFIBUS Tester BC-700-PB - User Manual
Chapter 6 - Connection to PROFIBUS
Avoid stress on connectors and bus stations
Avoid stress on connectors and bus stations which might be caused by the
device's own weight. Ensure proper strain relief by using suitable supports,
cable ties, etc. When this is not possible, you need to select a different
connection point to avoid damage.
6.1.5
Using the security lock port
When using trend logging, the PROFIBUS Tester 5 is typically operated in an unattended
manner over a prolonged period of time. You can connect a Kensington lock to the
security lock port to prevent your device being stolen. The Kensington lock is not part of
the product delivery. To use this feature, you have to purchase the Kensington lock
additionally. To use the Kensington lock, refer to the product manual. Tie the Kensington
lock cable to a fixed object and install the other end of the cable to the security lock port.
Figure 17: Using a Kensington lock
6.1.6
Test locations
The PROFIBUS Tester 5 can basically carry out tests anywhere on a physical PROFIBUS
segment. Note that the use of repeaters creates separate physical segments that each
needs to be measured individually. For the best and most informative results, perform the
tests at the beginning and at the end of each physical segment. If these test results
indicate problems that cannot be clearly classified right away, you should carry out one or
more additional tests at the center.
6.2
Simple connection for tests during system shutdown
If all bus stations provide D-sub connectors with an additional service socket, you can
simply plug in the PROFIBUS Tester 5 at that socket (see figure below). If a D-sub
PROFIBUS Tester BC-700-PB - User Manual
23
Chapter 6 - Connection to PROFIBUS
connector does not provide a service socket, you can plug in the D sub adapter cable
underneath. Keep in mind that you should never cascade more than two D-sub
connectors (see also Adapter cable 22 ).
When using M12 connection technology, the M12 adapter cable is "looped" into the bus. It
is essential to ensure proper termination at the beginning and at the end of the bus by
using the terminating resistor provided with the M12 adapter set.
Shut down complete installation before connecting
Shut down the PLC and all the devices connected to the PROFIBUS as all
these simple connection types will divide the bus.
Figure 18: Connection points at system shutdown
6.3
Connection for testing a live bus (DP)
To test a live PROFIBUS with the PROFIBUS Tester 5 during operation, appropriate
connection possibilities have to be provided. If no suitable connection points are available
in the existing installation, it is recommended to install them during system shutdown. This
will make future maintenance work much easier.
24
PROFIBUS Tester BC-700-PB - User Manual
Chapter 6 - Connection to PROFIBUS
Shut down complete installation before connecting
Shut down the PLC and all the devices connected to the PROFIBUS as all
these simple connection types will divide the bus.
Use D-sub adapter cable BC-600-PB-CB-DSUB-1 for testing on live
systems
For testing on live systems we highly recommend using the optional D-sub
adapter cable BC-600-PB-CB-DSUB-1 with reduced influence on bus
operation.
6.3.1
Connection via D-sub connector with service socket
If all bus stations provide D-sub connectors with an additional service socket, you can
simply plug in the PROFIBUS Tester 5 at that socket:
Figure 19: Connection points for the D-sub adapter cable
PROFIBUS Tester BC-700-PB - User Manual
25
Chapter 6 - Connection to PROFIBUS
6.3.2
Direct cable connection
To test a live PROFIBUS, you will need additional D-sub service interface of the type BCPBMB-PB-S (see Service interfaces for PROFIBUS DP 12 ).
Figure 20: Service interface provide connection points at direct cable connection
26
PROFIBUS Tester BC-700-PB - User Manual
Chapter 6 - Connection to PROFIBUS
6.3.3
Connection via M12 connector
To test a live PROFIBUS, you will need additional service interface of the type BC-M12DPPB (see Adapter set for M12 connection technology 10 ).
Tests on a live PROFIBUS are only allowed on bus segments providing D-sub connection
technology. Only D-sub connectors with service socket can be used as connection points
for the test tool. For this reason, tests can often only be performed at a bus end.
Figure 21: Connection points for the M12 adapter cable
Connect T-fitting between existing cable and 1 meter connection
cable
Always connect one end of the T-fitting to the already existing cable and the
other end to the 1 meter connection cable which is supplied with the service
interface.
Do not screw the T-fitting of the M12 service interface directly onto a slave.
6.4
Master simulator, topology scan and cable test
Master simulator
The master simulator allows checking the bus cabling and the station addresses during
installation and commissioning, when the PLC (master) is not in operation yet. In addition,
you can use this mode to check individual "suspicious" bus stations that have been
disconnected from the bus.
PROFIBUS Tester BC-700-PB - User Manual
27
Chapter 6 - Connection to PROFIBUS
Topology scan
The topology scan determines the sequence and distances of all passive bus stations
(slaves). This feature requires correct bus cabling, a very good signal quality, and a
connection point located directly at the beginning or end of the bus.
Cable test
The cable test assesses the wiring and can be used to determine a faulty cable location
(e.g. short circuit) by means of reflection test.
All three features can only be used during shutdown of the installation. The D-sub cable
BC-600-PB-CB-DSUB-2 which is included in the standard scope of supply must be used.
As long as communication is detected on the bus, i.e. at least one device is an active
master, the functions are disabled. If necessary, disconnect every single active device
(PLC, MPI and, if necessary, diagnostic repeaters) from the power supply or the bus. If an
active device is at the end of the bus you want to test, its PROFIBUS connector needs to
be unplugged and connected directly to the PROFIBUS Tester 5 BC-700-PB. The bus
termination in the device connector will then be powered by the PROFIBUS Tester 5 BC700-PB.
Figure 22: Connection points for topology scan and cable test
Bus stations must only be disconnected from the power supply or the bus
during shutdown of the installation
28
PROFIBUS Tester BC-700-PB - User Manual
Chapter 6 - Connection to PROFIBUS
The three functions can be started also when the PROFIBUS Tester 5 BC700-PB is disconnected from the bus. If you then connect the test device to
a live bus, this can cause bus communication problems or a shutdown of
the installation.
Special case: Active devices at both ends of the bus
On the very rare occasion when there is an active device at each end of the bus, do the
following:
1.
When using D-sub connection:
a.
Additionally switch on the terminating resistor in the D-sub connector of the last
slave.
b.
Make sure the outgoing cable to the active device at the bus end is connected to
the outgoing connector (marked with "OUT", an outgoing arrow, or "A2/B2").
Figure 23: Checking the connection direction at the D-sub connector
2.
When using M12 connection:
a.
Connect the cable from the bus start or test tool to the incoming M12 connector
of the last slave.
b.
A bus termination is required at the outgoing M12 connector of the last slave.
6.5
Connecting to PROFIBUS-PA networks
6.5.1
Test locations
There are several ways to connect bus stations to PROFIBUS PA:
Using terminals for direct connection
Using M12 connectors in the field (unfortunately there is no rule defining on which
sides the male and female connectors are to be used)
Field distributors and T pieces are widely used. As opposed to PROFIBUS DP, spur
cables are allowed to a limited extent for PROFIBUS PA.
The following types of DP/PA fieldbus couplers are the most common:
Simatic DP/PA couplers from Siemens, also as part of DP/PA links
PROFIBUS Tester BC-700-PB - User Manual
29
Chapter 6 - Connection to PROFIBUS
SK1, SK2 and SK3 segment couplers, e.g. from Pepperl+Fuchs (or sometimes under
a different label)
Irrespective of the connection types used for the field devices, the fieldbus couplers are
usually installed in a control cabinet, and the PA output is connected there via terminals.
Connection to MBP-IS is not allowed.
You can use the connection points of bus stations or access points inside the field
distributors as connection points. Establishing the electrical connections required for
measuring may vary from system to system and might not be possible during operation.
Figure 24: Connection points for PROFIBUS PA
Hint
An appropriate connection point is located directly at the DP/PA coupler. At
this point, the tool can continue to analyze the bus communication even
when lines are interrupted. The measurements are not affected by repeaters
or field barriers.
30
PROFIBUS Tester BC-700-PB - User Manual
Chapter 6 - Connection to PROFIBUS
6.5.2
Requirements for analyzing a live bus
When using the PROFIBUS Tester 5 and the BC-700-H1 adapter to carry out
measurements on an MBP segment during operation, it is preferable to connect the tool
via free bus connection terminals of the DP/PA fieldbus coupler. If the bus begins at the
coupler, you can simply use the second terminal block at the DP/PA coupler or at the SK1
or SK2 to sample the bus signal. If the couplers mentioned above are not located at the
beginning of the bus or if the bus begins with an SG3 coupler or if you are interested in the
PROFIBUS PA signal at another test location, we recommend connecting a short spur
cable to rail mounted terminals during system shutdown. This gives you an appropriate
connection point and makes future maintenance work much easier.
6.5.3
Analyzing during system shutdown
If there is no possibility for connection, you need to improvise in order to pick up the bus
signal at an existing terminal block of the fieldbus coupler, the field distributor, segment
protector or a field device. For example, you can try a double assignment of bus terminals.
Shut down the system before you divide the bus.
Disconnect all bus stations from the power supply.
6.5.4
Bus connection
The supplied test equipment set allows to easily connect the BC-700-H1 adapter to the
PROFIBUS PA segment. Alternatively you can use a short length of PROFIBUS PA
standard cable to connect the tool to the bus.
Figure 25: PROFIBUS-PA pin assigment
Do not use in hazardous areas
The PROFIBUS Tester 5 and BC-700-H1 adapter must not be used in
hazardous areas and must not be connected to an intrinsically safe MBP-IS
segment (blue terminals of fieldbus coupler; in some cases blue bus
cables).
PROFIBUS Tester BC-700-PB - User Manual
31
Chapter 7 - Display and controls in stand-alone m ode
7
Display and controls in stand-alone mode
The PROFIBUS Tester 5 always starts in stand-alone mode unless it is USB connected to
a PC or notebook. The readings are shown on the graphical display. You can control the
tool with the four softkeys, the scroll wheel and the push button in center of the scroll
wheel (see Connectors and controls 14 ).
When you establish a USB connection during stand-alone mode while a test is running,
the test will be aborted and the tool will be reset (restarted). The display briefly shows:
"Switching to PC mode".
7.1
Main display
The start page is displayed after start-up in stand-alone mode (or when all dialogs or
functions have been stopped and you have been returned to the main menu). The main
menu is your starting point where you can open any of the test functions or additional
administrative functions.
Figure 26: Start menu
7.2
User interface
The user interface of PROFIBUS Tester 5 comprises four parts:
Device Status in the upper right corner, which provides information such as the
battery charge level indicator, system load status, memory information, state of
master simulator, connected interfaces and adapters,…
Application Status at the upper edge on the left displays which function or sub-function
is currently selected.
The Workspace in the center of the graphical user interface contains the start page,
detail views for the bus analyzes and views for administrative purposes. At a glance
the user views the most important information with respect to the selected test
function.
Control information is shown at the lower edge of the user interface. The meaning of
the four softkeys is explained in Operating functions 34 .
32
PROFIBUS Tester BC-700-PB - User Manual
Chapter 7 - Display and controls in stand-alone m ode
Figure 27: Division of screen areas
The presentation of dialog information comprises four layouts:
Additional information which is typically less important is shown on user request in
Info-dialogs. Access to this read-only function or information is subjected to a submenu function or to the [Info]-softkey.
Other functions may require appropriate user input by means of input dialogs. The
colors light blue and blue indicate, which elements are selectable or changeable by
means of the input focus (cursor).
Error messages are displayed in error dialogs.
The PROFIBUS-Tester 5 contains a context-sensitive online help, which is shown in
quick reference dialogs using a smaller font size.
PROFIBUS Tester BC-700-PB - User Manual
33
Chapter 7 - Display and controls in stand-alone m ode
Figure 28: Dialogs in the user interface
7.3
Operating functions and softkeys
Use the scroll wheel, in order to move the cursor within lists, tables, dialogs and
alphabetic strings. Selected elements are blue highlighted. Press the central button of the
scroll wheel or press the Selection- or [Info]-softkey in order to call functions or to request
additional information. The appearance of controls will change in a context-sensitive
manner. If a softkey is grayed out, the corresponding operating function is disabled:
Symbol
Function
Open menu/ submenu
Browse backwards, leave menu function
Browse tab to the left
Browse tab to the right
Confirm/ select (central push button in scroll wheel)
Start a stopped function
Stop a running function
Request details for selected elements (press briefly) or
Open context-sensitive reference (press button approx. for 2 seconds)
Open context-sensitive reference
34
PROFIBUS Tester BC-700-PB - User Manual
Chapter 7 - Display and controls in stand-alone m ode
7.4
Device status
The table below indicates the symbols which may be displayed in the device status.
Device status information is available and visible at any time of device operation in standalone mode.
Symbol
Description
Battery charge level (approx. 100 %, 66 %, 33 %)
,
,
Critical battery voltage level. PROFIBUS Tester 5 is going to
shut down automatically in a couple of minutes. Connect
PROFIBUS-Tester 5 to the AC adapter.
AC adapter connected and battery is charging.
Battery completely charged - without AC adapter connected.
Battery completely charged - with AC adapter connected.
Battery not found or defective. The device runs with external
power supply.
There is activity on the bus. If the LED is green, but no baud
rate is detected (e.g. in Bus Status function), the activity on the
bus results from disturbances and not from regular frames.
No bus activity, open circuit voltage within correct range
between 0.8 V and 1.4 V. The bus termination is correct, but no
frames are transmitted on the bus. To run a test, you have to
either switch on the PROFIBUS master or activate the master
simulator.
No bus activity, open circuit voltage below 0.8 V or above 1.4 V.
If an open circuit voltage greater than 0 V is displayed in Bus
Status function, the bus has not been properly terminated. An
open circuit voltage of about 0.5 V to 0.6 V is a sign that no
power is supplied to one of the two bus terminations.
Master simulator is active. You can start the master simulator
from the "Extras > Master simulator" menu.
PROFIBUS Tester BC-700-PB - User Manual
35
Chapter 7 - Display and controls in stand-alone m ode
7.5
Menu functions
The following table gives a brief overview about the menu functions of PROFIBUS-Tester
5 in stand-alone mode. The online help contains a more detailed description of operating
functions (use the [ ]-softkey in the corresponding context).
Menu
directory
Menu
function
Short description
(> sub menu
function)
Test
Functions
Bus Status
> Overview
Bus Status
> Detail view
Signal Quality
Signal Quality
> Select test
location
Signal Quality
> Settings
evaluation
Cable Test
Cable Test
> Edit
Configuration
36
Bus Status function (Overview) assesses bus physics
and bus communication and displays the test result in a
simplified view.
Bus Status function (Detail view) assesses bus physics
and bus communication and displays the test result in
table form.
The signal quality test determines the signal quality index
for each bus station and displays the test result in a bar
diagram. The test location is particularly important when
you are testing the signal quality.
Additional information is available such as Signal/ Noise
ratio, edges and numerical values with respect to signal
quality testing.
The test location is particularly important when you are
testing the signal quality. It is recommended to make at
least two signal quality tests per physical segment (at
both ends of the corresponding segment).
The signal quality evaluation settings contain limit values
for the quality index, signal/noise ratio, rise time and
timeout.
The cable test function examines the cabling in
PROFIBUS segments. This test detects the cable
segment length, scans for unwanted reflections on the
line and verifies proper termination of the cable. In case
of a fault you will get an error description and a distance
indication (if possible) for troubleshooting actions. Tests
regarding cabling can only be made from one end of the
PROFIBUS line. Active stations (Masters, MPI panel,...)
must be disconnected during testing of the respective
cable segment.
For further information and starting points in order to
correctly interprete the fault indication see List of fault
indications and remedial measures 48 .
In the context of cable testing it is recommended to
provide additional information about the corresponding
cable segment (physical segment). This is important for
proper detection of line length, compliance with
maximum allowed segment length as well as for proper
documentation of test results. Please give full particulars
with respect to the configuration of each cable segment.
PROFIBUS Tester BC-700-PB - User Manual
Chapter 7 - Display and controls in stand-alone m ode
Menu
directory
Menu
function
Short description
(> sub menu
function)
Recording
Functions
Cable Test
> Cable
Segment List
The cable segment list shows all segments which
belong to the currently selected network in a tabular
overview. Plus, an OK- or error-message is displayed (if
available). Particularly in the context of acceptance
control the commissioner can get a survey over the
cabling of the network.
Quick Test
The Quick Test allows full testing of bus physics and
bus communication. The test data is stored in the tool. It
can subsequently be imported by the PROFIBUS
Diagnostics Suite software application.
The residual waiting period is displayed during the quick
test. After completion of the test, a tabular overview is
displayed which informs you about existing and missing
quick tests respectively.
Trend logging is used for detecting rare or sporadic
faults over a prolonged period of time. The function
monitors both the bus physics and critical events in the
bus communication. The test data is stored in the tool. It
can subsequently be imported by the PROFIBUS
Diagnostics Suite software application. The tool displays
the duration of the running trend test.
After completion of the test, a tabular overview is
displayed which informs you about existing and missing
trend tests respectively. The Trend Test runs until
manually stopped, is aborted automatically when the
power supply is interrupted or when the maximum
logging time of 99 hours and 59 minutes is reached.
Trend
Network
Networks
Management
Select network - The PROFIBUS-Tester 5 stores the
test results that are associated with a real PROFIBUS
network in a separate file folder for that network. Three
configurable folder structures exist. The radio button
shows which network is currently selected.
Each network contains at least one physical segment
and test location.
Networks
Segment list - The signals of stations located behind a
> Edit Network repeater are regenerated and transmitted by the
repeater. Therefore, all stations behind the same
repeater will have identical quality test results. When
using repeaters, you will thus have to test each segment
separately.
One test location belongs exclusively to one segment.
PROFIBUS Tester BC-700-PB - User Manual
37
Chapter 7 - Display and controls in stand-alone m ode
Menu
directory
Menu
function
Short description
(> sub menu
function)
Networks >
Segment list
> Edit
Segment
Assign test locations to segments: Those test locations
are particularly important which are located within the
currently tested physical segment. It is recommended to
make at least two signal quality tests per physical
segment (at both ends of the corresponding segment).
Test Locations Manage test locations: Particularly when testing signal
quality, the test location has a major influence on the test
result.
To find typical PROFIBUS faults, it is recommended to
measure the signal quality at different locations on the
bus, at least at both line ends. If a PROFIBUS network
comprises multiple segments connected through
repeaters, you have to measure each segment
separately.
Extras
Master
Simulator
Using the master simulator, you can even test the signal
quality while you are still setting up a PROFIBUS
installation and the actual master is not operational yet.
The master simulator is disabled by default when you
switch on the tool. You can only select a baud rate on
the display and thus start the master simulator if no
other master is active.
If you use the master simulator in a trend test, quick test
recording or when running the Bus Status function, the
values for the critical events will not be informative
because the master simulator does not execute a
regular DP protocol.
Settings
Energy
Management
The energy management settings have a considerable
bearing on battery life of the test device with respect to
one battery charge. It is recommended to activate the
automatic profile "economy".
Here you can select the operating language
Hardware information is displayed here (version- and
serial numbers).
Here you can obtain licensing information
Language
Hardware
Information
License
38
PROFIBUS Tester BC-700-PB - User Manual
Chapter 7 - Display and controls in stand-alone m ode
7.6
Organize and store test results
PROFIBUS Tester 5 comprises three predefined network folders: a default network folder
and two empty folders.
A network folder is a directory containing all the test results assigned to a network. The
name of the network folder is the same as the network name displayed during the data
import into the PC.
The default network is provided for spontaneous tests and is a fixed component of the
project management and cannot be deleted. However, you can rename and edit the
default network and start testing using this network. If you are deleting all networks,
automatically the default network including a default segment and a default test location
will be generated in the network folder.
A network in PROFIBUS Tester 5 comprises one or more segments, and one or more
test locations. A minimum network configuration (default network) comprises one
segment (default segment) and one test location (default test location).
The test location has a major influence on the test result, particularly when testing signal
quality, using the oscilloscope function or using the cable test function. To store all test
results within a network in the PROFIBUS Tester 5, you have to set the radio button to the
corresponding network in the networks function (see also User interface 32 ).
Figure 29: Select Network – the radio button is set to "engine production"
Test results in stand-alone mode are stored under the specified test location in the
network you have defined as the storage location. Thus, test results will be organized and
stored in PROFIBUS Tester 5 according to their test location. Refer to the figure below to
see an example network which could be organized as follows in PROFIBUS Tester 5
(recommendation):
1.
Use the Networks/ select network function and select an empty network folder.
Enter the network name (e.g. "engine production").
2.
Use the Edit network sub-function and rename the default segment (e.g. to
"heating") and add two new segments (e.g. "foundry" and "conveyor belt").
3.
Use the Test locations function and generate six test locations.
PROFIBUS Tester BC-700-PB - User Manual
39
Chapter 7 - Display and controls in stand-alone m ode
4.
Assign test location to segments. You can do this in Test locations or in Networks
Edit Network
Edit segment-subfunction.
Figure 30: Example network comprising three segments, 13 PROFIBUS stations, 2
repeaters and 6 recommended test locations (two per segment)
40
PROFIBUS Tester BC-700-PB - User Manual
Chapter 8 - Im port data into the PC
8
Import data into the PC
Quick Tests, cable test results and Trend logs stored in the test tool can be imported into
the PC software.
1.
To do this, start the PROFIBUS Diagnostics Suite.
2.
Connect the PROFIBUS Tester 5 BC-700-PB to the PC via USB. An additional Import
Test Data dialog box appears automatically showing the test data previously saved:
Figure 31: Importing test data
3.
The Import Test Data dialog box has been completed in advance and contains
already the network designations, segment designations and the test location
designations, which have been derived from the network management of PROFIBUS
Tester 5 BC-700-PB.
For ALL the stored data, you need to fully select the action to be performed, the network/
project and the test location to which you want to store the data. The default action Import
& Delete deletes the test data in the tool after the import is complete. This frees the
allocated memory locations for new tests.
The imported Quick Tests, cable test results and Trend logs are fully compatible with the
test data that can be acquired using the PC software.
PROFIBUS Tester BC-700-PB - User Manual
41
Chapter 9 - Licenses
9
Licenses
Some main menu functions of PROFIBUS Tester 5 require a license activation or may be
blocked respectively. You can view the license activation status in the menu function
License in the Settings directory.
Figure 32: Viewing the license activation status
Disabled functions or functions without a license will be grayed out or are not visible in the
main menu in stand-alone mode. In PC mode of operation in conjunction with the PC
software PB-DIAG-SUITE the corresponding functions are blocked, too. When USB is
connected you can view the license activation status in PC-software PB-DIAG-SUITE, too
(Help
Hardware Info).
42
PROFIBUS Tester BC-700-PB - User Manual
Chapter 10 - Firm w are update
10
Firmware update
Firmware updates are made available as required. They are provided with the updates to
the PC software (see Install software and connect to PC 20 ) and allow access to new or
improved functionality. How to update the firmware is described in detail in the separate
PROFIBUS Diagnostics Suite – Quick Startup Guide.
PROFIBUS Tester BC-700-PB - User Manual
43
Chapter 11 - Maintenance and service
11
Maintenance and service
The PROFIBUS Tester 5 is maintenance-free and does not require calibration. It is
recommended to exclude this device from control of measuring and monitoring of devices.
Repairs/ service exchange (RMA) may only be carried out by the device manufacturer. All
returns must be made without supplied carrying case and accessories (unless otherwise
agreed). Please also include a brief fault description and a phone number at which we can
contact you should we need further details. In case of returns within the warranty period,
please also enclose a copy of the invoice or delivery note.
The built-in battery is subjected to normal wear and tear. The battery capacity decreases
in the course of years; this is typical for specified normal operation. Exhaustive discharge
and overcharge or exhaustive operation of the device in conjunction with very high or low
temperatures will accelerate the battery ageing process (refer to Notes on battery use) 53 .
44
PROFIBUS Tester BC-700-PB - User Manual
Chapter 12 - Troubleshooting
12
Troubleshooting
Problem
Causes and remedies
The display of the
PROFIBUS Tester 5
remains blank.
Possible cause:
The PROFIBUS Tester 5 either needs an external power
supply or you have to install the built-in battery.
Remedy:
Use the supplied external AC adapter to connect the tool to
the mains power supply.
Charge the built-in battery
Alternative cause:
The tool is defective.
The rechargeable battery is defective
Remedy:
Return the tool to the manufacturer.
Replace the rechargeable battery
The display shows the
following error
message: "USB
ERROR - Refer to
manual or disconn. for
stand-alone mode".
Possible cause:
This error message can be caused by poor physical
connection via USB ("loose" contact).
Remedy:
Check the USB cable and connector.
Alternative cause:
The device may be connected via external USB hub,
notebook docking stations or USB 3.0 port which could
evoke problems during driver installation
Remedy:
It is recommended to connect the unit directly to a USB 2.0
port
The baud rate is not
detected automatically
on a live PROFIBUS.
Possible cause:
Massive disturbances in the bus physics.
Remedy:
Manually set the baud rate and repeat the test.
A main menu function
is grayed out or is not
visible respectively
Possible cause:
Missing license
PROFIBUS Tester BC-700-PB - User Manual
Out-dated firmware version is in use
Remedy:
Please check your bill of delivery if the license is included in
your order.
Please download the latest firmware version
45
Chapter 12 - Troubleshooting
Problem
Causes and remedies
It is not possible to
activate the sleep
mode for energy saving
Possible cause:
Test function is currently active
Remedy:
Stop running test functions before activating the sleep mode
After some minutes the
display becomes dark.
Possible cause:
Backlight was switched off automatically in the context of
energy saving settings
Remedy:
Actuate any push button or scroll wheel
Alternative cause:
The tool automatically entered the sleep mode/ powered off
in the context of energy saving settings
Remedy:
Actuate the power key in order to power up the device
The device is running
but does not react to
any user input.
Possible cause:
The program has crashed
Remedy:
Actuate power key for at least three seconds in order to
power off the device
Switch off the power supply. As the case may be, open head
screws on the back of the device and remove the
connecting plug of the rechargeable battery
After switching on the
device, the splash
screen persists and
shows "Selftest failed!
System halted"
Possible cause:
Self-testing has identified faulty device components
Remedy:
Return the tool to the manufacturer
Optional: Press the key combination [Softkey 1] + [Softkey 4]
during switch-on of the device. Detailed information about
self-testing is shown.
You can find support contact data on the cover sheet's back side of this document.
46
PROFIBUS Tester BC-700-PB - User Manual
Chapter 13 - Tips and tricks for cable testing
13
Tips and tricks for cable testing
Perform cable test without mains adapter
When using the cable test function we recommend removing the mains
adapter and operating on the PROFIBUS-Tester 5 by means of the built-in
battery in stand-alone operation mode.
13.1
Assessment criteria
The cable test function examines the cabling in PROFIBUS DP segments and
summarizes the test result in a single statement ("Ok" or "Error"). Amongst technical
criteria with respect to the cabling the overall assessment incorporates additional criteria
with respect to the workflow and to plant planning. Under certain conditions a user may not
be able to successfully finish cable testing in a dedicated segment (e.g. at a very early
installation phase of a facility, when there is no possibility to power the bus terminators). In
such a case it is recommended, to add a comment to the corresponding test report which
clarifies the circumstances that lead to the negative cable test result. Not all errors will
inevitably lead to downtimes or represent under the specific circumstances a severe error.
At last, the commissioner or maintenance personnel decides, if a PROFIBUS-network is
functioning properly or not. The corresponding person gets necessary information and
recommendations by means of using appropriate PROFIBUS diagnostic tools. The table
below contains assessment criteria which must be fulfilled in order to successfully
complete the cable testing function. The table describes also, under which conditions the
cable test will result in an error or failure.
Failed, if at least one of the following
criteria is fulfilled
Substatial troubleshooting effort was
carried out unsuccessfully and there are
still errors on the cabling
The corresponding PROFIBUS DP
segment is still affected by reflections on
the cable
The user did not run through the tree steps
of cable testing
Detection of the cable segment length fails
Bus termination is not as expected
The detected cable segment length
exceeds the limit value specified by PI
(PROFIBUS PROFINET International)
PROFIBUS Tester BC-700-PB - User Manual
Passed, if all of the following criteria
are fulfilled
All cabling errors have been successfully
eliminated
The corresponding PROFIBUS DP cable
segment is free of reflections
The user has run through each of the three
steps of cable testing successfully
The cable segment length has been
successfully detected
The terminators at both ends of the cable
segment are switched on and properly
powered
The baudrate (entered by user) and the
detected cable segment length fit together
according to PI recommendation
(PROFIBUS PROFINET International)
47
Chapter 13 - Tips and tricks for cable testing
13.2
List of fault indications and remedial measures
The classifying text messages in the graphical user interface of PROFIBUS Tester 5
which describe the cabling errors are kept concisely. The table below lists possible
cabling error messages and provides a detailed description of the discovered fault
indications. The column on the right contains "remedial measures" and further starting
points in order to correctly interpret and to repair the indicated fault.
The PROFIBUS Tester 5 uses amongst other methods impulse reflectometry for
assessing the cabling and classifying and locating errors on the cable. Multiple cable
errors, which exist simultaneously on the cable may result in an imprecise cable test
result. Please bear in mind, the more the corrective repair of the cable is proceeding, the
more precise the cable test results in the corresponding PROFIBUS cable segment will
be.
Electromagnetic interferences may influence PROFIBUS cable testing in a negative
manner because cable conductors may act like an antenna. Please bear this in mind
during cable testing and take care of proper functional earthing of your plant respectively.
Existing high frequency noise voltage may negatively influence the PROFIBUS Tester 5 if
operated by means of the external power supply. We recommend operating on the
PROFIBUS-Tester 5 by means of the built-in battery under the above mentioned prevailing
conditions.
Cable testing error
message from
graphical user
interface of
PROFIBUS-Tester 5
Remedial measures - starting points for correctly
interpreting and repairing the indicated fault
Break on line A
The green signal line of the PROFIBUS-cable is broken. Please
search for damage on the cable in the vicinity of the indicated
error location. Possibly the error could come from a fatigue
breakage or a faultily assembled PROFIBUS-connector. The
green signal line typically is connected to Pin 8 of the
PROFIBUS Sub-D type connector.
The red signal line of the PROFIBUS-cable is broken. Please
search for damage on the cable in the vicinity of the indicated
error location. Possibly the error could come from a fatigue
breakage or a faultily assembled PROFIBUS-connector. The
red signal line typically is connected to Pin 3 of the PROFIBUS
Sub-D type connector.
The shielding conductor is broken in the tested cable segment.
Alternatively electromagnetic shielding is not applied for in a
continuous manner. Please search for damage on the cable in
the vicinity of the indicated error location. Possibly the error
could come from a fatigue breakage or a faultily assembled
PROFIBUS-connector.
In rare cases electromagnetic shielding may be disrupted
intentionally in order to avoid electromagnetic interferences.
Please check this issue with the planning personnel of the
PROFIBUS-facility.
Break on line B
Break on shield
48
PROFIBUS Tester BC-700-PB - User Manual
Chapter 13 - Tips and tricks for cable testing
Cable testing error
message from
graphical user
interface of
PROFIBUS-Tester 5
Remedial measures - starting points for correctly
interpreting and repairing the indicated fault
Short circuit between A There is an unusual low ohmic or capacitive resistance
and B
between signal lines A and B. Please search for damage on the
cable in the vicinity of the indicated error location. Possibly the
error could come from a severe crush of the cable or multiple
unpowered bus terminators.
Plus, be on the lookout for illegal spur lines and check, if
moisture penetrated the cabling or if the cabling is heavily
soiled.
Short circuit between A There is an unusual low ohmic or capacitive resistance
and shield
between the mentioned signal lines and conductors. Possibly
Short circuit between B the error could come from a severe crush of the cable or a
faultily assembled PROFIBUS-connector.
and shield
Short circuit between A, Plus, be on the lookout for illegal spur lines and check, if
moisture penetrated the cabling or if the cabling is heavily
B and shield
soiled.
Capacitive Load / Spur There is an unusual capacitive load between signal lines A and
Line
B and the shield conductor. Possibly the error could come from
an illegal spur line or from interference-suppression capacitors.
This is common usage with "over-compensated" or defective
PROFIBUS-devices.
Disconnect the devices in the vicinity of the indicated error
location and repeat cable testing in order to encircle the error.
Unknown error
The cable is still affected by unwanted reflections. Though it is
not possible to classify the fault indication. Please search for
damage on the cable in the vicinity of the indicated error
location and check if the PROFIBUS-connector has been
properly assembled.
Unwanted reflections may emerge from transitions between
media and signal conductors which have different impedance
values (e.g. two different cable types).
Sending pulse could
Please do not fall below the minimum cable length of 3 meters.
not be detected. The
The intended use of cable testing requires a cable with
cable is either too short adequate length.
or not connected.
(Near-end) terminator
During the first of the three steps of cable testing the
switched on
PROFIBUS Tester requires an open cable on both sides.
No reflections could be However, the tester detected an ohmic resistance between the
signal wires and the resistance value is in the range of bus
detected. Please
terminators. Please make sure, that every bus terminator on
remove terminators.
every PROFIBUS-connector is switched off or is deactivated.
Please take into consideration, that dip-switches for switching
on/off bus terminators may be defective.
PROFIBUS Tester BC-700-PB - User Manual
49
Chapter 13 - Tips and tricks for cable testing
Cable testing error
message from
graphical user
interface of
PROFIBUS-Tester 5
Remedial measures - starting points for correctly
interpreting and repairing the indicated fault
Idle voltage too high
The ideal idle voltage between signal wires A and B of a cable
segment, which is properly terminated on both sides is
approximately 1.1 Volts. However, the PROFIBUS-Tester
detected voltage values higher than 3 Volts between the signal
wires A-B; A-Shield and/or B-Shield. These unwanted potential
differences obstruct the cable testing function and the test
results will become void. Plus, running leakage currents may
damage the PROFIBUS-Tester.
Please take care of proper functional earthing of your plant.
We recommend to remove the mains adapter and to operate
on the PROFIBUS-Tester 5 by means of the built-in battery if
you are receiving this error message. This will avoid damage
caused by leakage currents.
Please take also into consideration that the error cause could
be a defective RS-485 driver of a PROFIBUS-device.
Troubleshooting EMC and earthing issues are a highly complex
field of activity. Therefore it is recommended to ask service
providers which are primarily specialized in troubleshooting the
above mentioned issues.
Far-end / Near-end
The corresponding bus terminator has been switched on, but
terminator not powered the terminator is improperly powered by 5 V supply voltage, yet.
During the cable testing the PROFIBUS Tester requires a
properly terminated cable at the far end (2nd test step) or on
both sides of the cable segment (3rd test step). A properly
terminated cable segment consists of activated and powered
bus terminators on both sides of the cable.
Please make sure that the corresponding PROFIBUS-device at
the corresponding end of the cable segment is powered. Plus,
the activated bus terminator is properly plugged to a powered
PROFIBUS-device.
No terminator detected There is neither an unpowered bus terminator nor there was
detected a bus terminator at all in the respective cable
segment.
During the cable testing the PROFIBUS Tester requires a
properly terminated cable at the far end (2nd test step) or on
both sides of the cable segment (3rd test step).
When using D-sub connection, activated bus terminators are
only effective at the incoming connector of PROFIBUSconnectors. The incoming connector is marked with "IN", an
incoming arrow or "A1/B1". Please be also on the lookout for
PROFIBUS-cables which have been connected by mistake to
the outgoing connector.
50
PROFIBUS Tester BC-700-PB - User Manual
Chapter 13 - Tips and tricks for cable testing
Cable testing error
message from
graphical user
interface of
PROFIBUS-Tester 5
Remedial measures - starting points for correctly
interpreting and repairing the indicated fault
Far-end / Near-end
The PROFIBUS Tester detects an ohmic resistance between
terminator wrong or not the signal wires A and B, but the resistance value is not as
adapted
expected in the range of a bus terminator.
Please make sure, that the bus terminator is properly powered
and the PROFIBUS-connector has been properly powered.
Take into consideration that multiple bus terminators may be
switched on and that dip-switches for switching on/off bus
terminators may be defective (due to aging and soiling).
Line A and B
The green and the red signal line are interchanged. Possible
interchanged
cause might be a PROFIBUS connector which is assembled
improperly. Please bear in mind that after having two times
interchanged line A and B, this error cannot be recognized
anymore. Only when interchanging both lines for a third time,
you may recognize the error.
Typically, the tester will not return a measured distance. In
order to localize the fault location we recommend shortening
the respective cable segment step by step by switching on bus
terminators within the cable segment.
Repeat the cable test after each shortening procedure until the
error is no longer reported.
The last active bus terminator is the faulty one.
Near end terminator
This message is a note and not an error message. The cable
was powered by
test has been passed successfully. The bus terminating
internal 5 V power
resistor has been switched on at the test location but is not
supply
powered via a PROFIBUS station. Possible causes: The
related cable end is not connected to an activated PROFIBUS
station or the 5 V power supply of the related PROFIBUS
station is defective. The PROFIBUS tester was able to supply
the bus terminating resistor with its tester-internal 5 V power
supply.
13.3
Metering the cable segment length correctly
Directly after starting the cable test function you will see the actual segment configuration.
In the context of cable testing it is recommended to provide the number of connectors and
connected devices in the respective cable segment. The provided number of these
elements should be as precise as possible in order to correctly detect cable segment
length or the distance to the error. This chapter illustrates, how connectors and devices
influence the detection of the cable length.
Connectors: Please specify, how many 12 MBit/s PROFIBUS-connectors exist in the
respective cable segment and enter the number in the segment configuration. The series
inductance within the 12 MBit/s PROFIBUS-connectors act like a delay element on the
cable with respect to impulse reflectometry. Every connector corresponds to approx. 50
cm cable length.
PROFIBUS Tester BC-700-PB - User Manual
51
Chapter 13 - Tips and tricks for cable testing
Devices: Please specify, how many PROFIBUS devices are connected to the respective
cable segment (Master, Slave, repeater; typ. not more than 32). The RS485-driver unit of
each PROFIBUS-station acts like a RC-cicuit (delay element) on the cable. In the context
of impulse reflectometry this corresponds to additional 20 cm cable length per device.
Consequently, the combination consisting of connector plus device corresponds to
approx. 70 cm cable length.
Example: A cable segment has approx. 50 m effective cable length and contains 20
PROFIBUS devices, which are connected to the line by means of 12 MBit/s Sub-D type
connectors. Without indicating the number of connectors and devices the PROFIBUS
Tester 5 BC-700-PB will detect a total cable segment length of 64 meters, which
corresponds to a systematic error of measurement of approx. 28 %. The more precise
you will enter the number of connectors and devices into the segment configuration, the
more precise the length indication will be (cable segment length or distance to error).
The cable length detection is optimized for standard PROFIBUS cable type A. The
detected cable segment length will show a methodical error in measurement, if you are
using a fieldbus cable with deviating impedance value.
52
PROFIBUS Tester BC-700-PB - User Manual
Chapter 14 - Notes on battery use
14
Notes on battery use
14.1
Lithium backup battery
CAUTION
This product contains a lithium-metal backup battery!
The lithium content is not more than 1 g. The battery has been successfully tested by the
manufacturer in accordance with the UN Manual of Test and Criteria (test procedures of
Part III, Sub-Section 38.3).
Improper handling of lithium batteries can cause the batteries to ignite or explode and pose
a burn hazard to users. If the product is properly handled, this battery does not need to be
replaced during the lifetime of the product. Therefore, opening the product is unnecessary
and not permitted. The product must only be operated within the specified temperature
range. Do not expose to heat above this temperature range and keep away from open fire.
Store in a dry place.
14.2
Rechargeable battery pack
14.2.1 Guidelines and warnings on battery use
Read and understand these safety instructions and warnings before
using or charging your rechargeable battery pack
Failure to read and follow the below instructions may result in fire, personal
injury and damage to property if charged or used improperly.
CAUTION
The rechargeable battery pack contains < 2 g Lithium.
Softing Industrial Automation GmbH, its distributors or retailers assume no liability for
failures to comply with these warnings and safety guidelines.
By purchasing this battery, the buyer assumes all risks associated with lithium
batteries. If you do not agree with these conditions, return the battery immediately
before use.
Never charge batteries unattended. When charging the battery pack you should
always remain in constant observation to monitor the charging process and react to
potential problems that may occur.
We recommend, to charge the Lithium-ion battery inside the device via the external
AC adaptor.
If at any time you witness a battery starting to “balloon” or swell up, discontinue
charging process immediately, disconnect the battery and observe it in a safe place
for approximately 15 minutes. This may cause the battery to leak, and the reaction
with air may cause the chemicals to ignite, resulting in fire.
PROFIBUS Tester BC-700-PB - User Manual
53
Chapter 14 - Notes on battery use
Since delayed chemical reaction can occur, it is best to observe the battery as a
safety precaution. Battery observation should occur in a safe area outside of any
building or vehicle and away from any combustible material.
You must not short circuit the wire leads! Never place the cells on a conductive
surface.
Wire lead shorts can cause fire! If you accidentally short the wires, the battery must
be placed in a safe area for observation for approximately 15 minutes. Additionally, if a
short occurs and contact is made with metal (such as rings on your hand), severe
injuries may occur due to conductibility of electric current.
A battery can still ignite even after 10 minutes.
In the event of a crash, you must remove battery for observation and place in a safe
open area away from any combustible material for approximately 30 minutes.
Never store or charge battery pack inside your car in extreme temperatures, since
extreme temperatures could ignite fire. Keep in mind the maximum allowed storage
temperature. Refer to Storage and Transportation 55 for more information.
Use caution to avoid puncture of the cell. Puncture of cells may cause fire.
You must not pull the wire leads when you carry or remove the battery from the
device.
In case of cells being damaged, do not use the battery anymore!
You must not open the cells. Oxygen and lithium will heavily react with each other!
If the electrolyte may get in contact with your skin or with our eyes, please give a wash
by using plenty of water and soap and call on a doctor.
Defective lithium ion batteries may evaporate substances which are harmful to
health! You must not inhale!
Please return old battery packs to a recycling center or hand over to us for proper
disposal. You must not ship battery packs which are clearly damaged. Please contact
our support department.
You must not throw battery packs on the fire.
14.2.2 Charging
Use only the wide-range power supply (AC adapter) provided with the tool (see
Scope of delivery 8 ) in order to charge the battery. Set voltage and current correctly
(failure to do so can cause fire).
Never charge batteries unattended.
Charge in an isolated area, away from other flammable materials.
For operating temperatures while charging refer to Specifications
temperature).
54
56
(operating
PROFIBUS Tester BC-700-PB - User Manual
Chapter 14 - Notes on battery use
14.2.3 Discharging
The energy management of the device complies with the following recommendations for
discharging lithium ion batteries:
You may not discharge the battery more than 80 % of nominal capacity.
Do not discharge battery to a level below 3.3 V per cell under load. Deep discharge
below 3.3 V per cell can deteriorate battery performance and without load not less than
3.5 V.
Operating Temperatures Discharge, refer to Specifications
56
(operating temperature).
14.2.4 Storage and transportation
Store battery at room temperature between 12°C/53F and 18°C/65F for best results.
(This corresponds to a battery charge level of 33%, refer to Device status 35 ).
Do not expose battery pack to direct sunlight (heat) for extended periods
When transporting or temporarily storing in a vehicle, temperature range should be
greater than 7°C/20F, but no more than 66°C/150F.
Storing battery at temperatures greater than 77°C/170F for extended periods of time
(more than 2 hours) may cause damage to battery and possible fire.
14.2.5 Battery life
Charging and discharging will typically wear out the battery pack over the time. Due to this
aging the usable battery capacity will decrease accordingly. Higher current loads and deep
discharge processes will considerably increase the aging process.
You will have best results with respect to battery life, if you
avoid deep discharging
charge the battery properly
store the battery at recommended temperatures
avoid overloading
switch off the device when not being used for a longer period of time.
14.2.6 Battery warranty
Product warranty is limited to original defects in material and workmanship. Warranty
does not cover collateral damage. Due to the nature and use of this product there is no
term warranty. Misuse, abuse, incorrect charging and other inappropriate use of this
product are not covered under warranty.
If you do not agree with these conditions, return the lithium polymer battery immediately
and before any use.
PROFIBUS Tester BC-700-PB - User Manual
55
Chapter 15 - Technical data
15
Technical data
Power Supply /
battery
RS485 (DP)
USB
Trigger
Internal memory
capacity
Dimensions
Weight
Protection class
Permissible ambient
conditions
Conformity
56
Via external AC adapter 100 V .. 240 VAC 50/60 Hz (galvanically
isolated) or built-in three cells lithium ion accumulator with 11.1
VDC
Rechargeable battery has a run-time of up to 5 hours (run-time
depends on the executed test functions and rate of wear of the
rechargeable battery)
Battery is charged via external AC adapter.
PROFIBUS D-sub connector (female), 9-pin,switchable power
supply for ext. bus termination
Protocol and frame analysis:
PROFIBUS DP and DPV1, automatic baud rate detection 9.6
kbit/s .. 12 Mbit/s
Signal analysis:
PROFIBUS DP, DPV1, FMS and MPI
Signal quality index 0 .. 5000 determined from signal waveform
as well as signal/noise ratio and rise time
Signal sampling with 8/16 samples per bit
Oscillogram display:
test range ±5V at 10mV resolution (differential), 0V…15V at 15mV
resolution (A or B to DGND)
Sampling rate:
up to 384 MSamples/s, for signal details: 2,400 sampled points,
for oscillogram analysis: 8,192 sampled points
Topology scan:
active, maximum distance 230 m, accuracy ±2 m
Cable test:
active, permitted cable segment length 5 m ... 1500 m, accuracy
5%
V 2.0, high speed 480 Mbit/s, galvanically isolated
IN : L=0 .. 0.8 V; H=2.4 .. 24 V; pulse > 10 µs, active high
OUT: approx. 5 V, active low (connection to storage oscilloscope)
3 network directories for storing Quick Tests and Trend logs
Trend logging: max. 99 hours
HxWxD: 35 x 220 x 110 mm
Test tool without cable: approx. 0.75 kg
Complete tool with carrying case, without accessories: approx.
4.2 kg
IP 20
Operating temperature 0 .. 50 °C
Storage temperature -20 .. 70 °C,
Air humidity 10 .. 90% without condensation
CE, FCC, VCCI
PROFIBUS Tester BC-700-PB - User Manual
Chapter 15 - Technical data
Operation
PC operating
software
Via graphical color display, four function keys and scroll wheel
including central push-button or via PC/notebook.
Localization of the display texts: English and German
PROFIBUS Diagnostic Suite, see separate documentation
PROFIBUS Tester BC-700-PB - User Manual
57
Chapter 16 - Declarations by the m anufacturer
16
Declarations by the manufacturer
This device complies to the EU product directive 2004/108/EC according to the following
directives:
EN 61000-6-4:2007+A1:2011 Electromagnetic compatibility (EMC) – Part 6-4: Generic
standards – Emission standard for industrial environments
EN 55022:2010 - Information technology equipment - Radio disturbance
characteristics - Limits and methods of measurement - Class A product
EN 61000-6-2:2005 - Electromagnetic compatibility (EMC) -- Part 6-2: Generic
standards - Immunity for industrial environments
EN 61326-1:2013
A Declaration of Conformity in compliance with the above standards has
been made and can be requested from Softing Industrial Automation GmbH.
Note
To fulfill the EMC requirements, the other components (AC adapter,
PROFIBUS stations, etc.) also have to meet the EMC requirements. A
shielded cable must be used. In addition, the cable shield must be grounded
properly.
Note
Additional tests have been performed successfully proving compatibility with
the requirements set forth by FCC and VCCI.
58
PROFIBUS Tester BC-700-PB - User Manual
Chapter 17 - Recycling
17
Recycling
This symbol is required in accordance with the Waste Electrical and Electronic Equipment
(WEEE) Directive of the European Union. The presence of this marking on the product
indicates:
1. The device was put on the European Market after August 13, 2005
2. The device is not to be disposed of via the municipal waste collection system of any
member state of the European Union.
**This appliance is labeled in accordance with European Directive 2002/96/EC concerning
waste electrical and electronic equipment (WEEE). The Directive determines the
framework for the return and recycling of used appliances as applicable throughout the
European Union. This label is applied to various products to indicate that the product is not
to be thrown away, but rather reclaimed upon end of life per this Directive.
**It is very important that customers understand and follow all laws regarding the proper
decontamination and safe disposal of electrical equipment. For Softing products bearing
this label please contact your dealer or local Softing office for details on the take back
program that will facilitate the proper collection, treatment, recovery, recycling and safe
disposal of device.
PROFIBUS Tester BC-700-PB - User Manual
59
Related Documents
PROFIBUS Diagnostics Suite
- User Manual "Getting Started"
- PB-DIAG-SUITE online help
Softing Industrial Automation GmbH
Richard-Reitzner-Allee 6
85540 Haar / Germany
Tel: + 49 89 4 56 56-0
Fax: + 49 89 4 56 56-488
Internet: http://industrial.softing.com
Email:
[email protected]
Support: [email protected]
Was this manual useful for you? yes no
Thank you for your participation!