ELECTRICAL SPECIFICATIONS D: RACEWAYS 1. EMT conduit shall be used in all locations which call for conduit unless noted therwise. Conduits routed thru areas of significant temperature differences shall be provided with seal-off fittings to minimize condensation. Conduits penetrating fire walls shall be firestopped per NEC & details shown on drawings. 2. Rigid PVC Schedule 40 shall be used for all underground or below slab conduit runs. 3. Heavy wall rigid steel onduit shall be used in all exposed interior applications below structural ceiling and exterior exposed applications. provide 2 coats of rust inhibiting paint for exterior runs. Paint shall match surface conduit is attached to. 4. 'MC' cable may be used for all branch circuits as allowed by the National Electrical Code & the authority having jurisdiction. Cable shall be installed in a neat professional manner adhering to industry standards. 5. When power or control conductors are installed in a raceway, a green equipment grounding conductor shall be included in each raceway system and shall be sized as shown on the drawings or if not noted on the drawings, then in accordance with Table 250-95 of the NEC, or as indicated on the drawings If green insulation is not available, the grounding conductor shall be bare and clearly and permanently marked at all tap and terminating points by green "scotch" marking tape, code markers, or other approved means. 2. Compression type lugs and connectors shall be used for all terminations and splices. All terminations shall be permanently identified and numbered, using "Brady" labels or other approved equal. Wire numbering shall be panelboard and circuit numbers. Also, all wiring which passes through junction or pull boxes shall be identified with appropriate numbers. When panelboard/circuit numbers are not appropriate for identification, the contractor shall assign a unique number and record this number on the construction set. H: WIRING DEVICES 1. Provide wiring devices which are UL listed and which comply with NEMA WD 1 and other applicable UL and NEMA standards. Device Color shall be white unless otherwise noted. Coverplate color shall match device color. Confirm color selection with architect before purchasing and installing. 2. Receptacles: Devices shall be specification grade, NEMA 5-20R configuration. Duplex type, Hubbell Cat No. CR5362, single outlet type, Hubbell Cat No. CR5361, GFCI duplex, Hubbell Cat No. CR GF5362. Catalog numbers for Hubbell are shown for reference purposes and equivalent receptacles by other manufacturers as noted above are also approved. Receptacles shall comply with UL 498 and NEMA WD 1. Special receptacles not shown below shall be specification grade with Nema configuration as noted on the drawings. 3. Ground-fault interrupter (GFI or GFCI) receptacles as indicated above shall be designed for and installed in a 2-3/4 inch deep outlet box without adapter, grounding type, Class A, Group 1, per UL Standard 94.3. 4. Snap switches: Devices shall be specification grade quiet type, 20 A 120/277V, single pole Hubbell Cat No. CS1221, two pole Hubbell Cat No. CS1222, three pole, Hubbell Cat No. CS1223, and four pole, Hubbell Cat No. CS1224. Catalog numbers for Hubbell are shown for reference purposes and equivalent receptacles by other manufacturers as noted above are also approved. Devices shall be specification grade, quiet type ac switches, and shall comply with UL 20 and NEMA WD1. 5. Approved manufacturers for wiring devices: Hubbell P&S 6. All conduit shall be securely fastened in full accordance and as directed by the latest edition of the National Electrical Code. In addition to the NEC requirements, conduit hangers, supports, or fastenings shall be provided at each elbow and at the end (within 6") of each straight run terminating at a box or cabinet. 7. Conduits or boxes may not be supported by ceiling support wires or other ceiling supporting hardware. 7. Wiring device accessories 9. The use of perforated iron for supporting conduits will not be permitted. 10. Conduit runs between outlets shall contain not more than the equivalent of three (3) quarter bends. Provide junction and/or pull boxes where shown on the drawings or as required, whether shown on the drawings or not. Pull boxes shall be approved for use in the area where they are to be installed. Pull boxes or junction boxes shall be provided in accordance with the following schedule: i. Straight runs - not over one hundred (100) feet apart. ii. One (1) 90 degree bend - not over seventy five (75) feet apart. iii. Two (2) or more 90 degree bends - not over fifty (50) feet apart. 11. In Class I and Class II hazard areas, as designated on the drawings, explosion-proof flexible metal conduit shall be used for all final conduit terminations at motors and to all other devices subject to vibration or movement. This shall include all pendant mounted lighting fixtures and conduit runs at building expansion joints in Class I and Class II hazard areas. Electrical ground continuity shall be provided as noted above. 12. Telephone and data (including other special communication systems such as cable TV) conduits shall be a minimum of 3/4" in size unless noted otherwise, and shall run continuous from outlet to outlet and back to the main terminal board, or shall be stubbed into the ceiling space (6" above the ceiling) and provided with a plastic bushing. Bond conduit stub with a #10 bare copper conductor to the nearest electrical outlet box or continuous metal conduit body. Refer to plans for specific details about the routing of the conduits. All empty conduits shall be provided with a #10 pull wire. 13. Cables installed in plenums without conduit shall be UL classified for low flame resistance and low smoke properties with "FEP" Teflon or Halar insulation suitable for plenum applications per Article 760 of the N.E.C. 14. Conduits below grade shall be installed in conformance with: Provide all necessary trenching, backfill & removal of trenched material from site. ii. iii. iv. The bottom of the trench shall be undisturbed earth or thoroughly compacted fill. The contractor shall be responsible for such compaction. the bottom shall be free of projecting rocks or other foreign matter. Where muck or unstable ground is encountered in the bottom of the trench, it shall be excavated to a depth of at least 12in. below the bottom line of the ducts and replaced with pea gravel in the proper grade. Duct shall not be installed on or in frozen ground. sheeting or bracing shall be provided where necessary to protect the work or adjacent property. Sheeting, bracing, and pea gravel shall be installed by the electrical contractor at no additional expense to the owner. Backfill shall consist of 3 inches of compacted sand below conduits and 12" above conduits. Clean screened fill shall be installed and compacted to 6" below final grade or as detailed in architectural specifications. Final grade patch shall be by E.C. Duct joints shall be sealed with waterproof joint compound. Ducts shall be supported at least 3in. above the trench bottom on plastic supports with spacing not exceed 5'. Before duct is placed, supports shall be aligned, set to grade, and placed in concrete to prevent movement when encasement is placed. Ducts shall be secured to supports and spacers placed for tiered ducts. All secondary power service underground ducts shall be encased with 3000 psi concrete. All underground ducts shall be 4" in diameter schedule 40 rigid non-metallic (P.V.C.) ducts with ground wires, unless specifically indicated otherwise on the drawings. concrete encasement shall be in accordance with the applicable provisions of the general trades portion of the specifications. v. Encasement shall be continuous monolithic pour providing a minimum of 3" completely arownd the ducts. Concrete shall not be poured directly on top of the ducts, but shall be poured from the sides and allowed to flow over the ducts. vi. Bell ends shall be installed at all duct terminations or as required by the power company. Fittings, couplings and other accessories, as recommended by the manufacturer, shall be provided and installed. vii. Ducts shall be cleaned by rodding and brushing. It shall be the contractors responsibility to assure a full bore opening throughout the duct system. E: FITTINGS FOR CONDUIT 1. Couplings and connectors for EMT: Die cast zinc, steel, or aluminum compression type. Set screw type will also be permitted. Approved manufacturers, Thomas & Betts, Steel City, O-Z Gedney. 2. Fittings for rigid plastic conduit: Polyvinyl chloride, joints solvent welded in field, providing continuity of mechanical strength and water tightness. Fittings and cement shall be produced by the same manufacturer as the conduit. 3. Fittings for rigid conduit: Cast or malleable iron bodies, zinc or cadmium plated, with full threaded hubs, screw covers and gaskets when located in areas requiring gaskets. Approved manufacturers: Crouse-Hinds, Pyle National, Appleton. 4. Couplings and connectors for flexible steel conduit: Malleable iron or steel, zinc or cadmium plated and shall fasten to the conduit by a clamping action around the periphery. Connectors for "liquid-tight" flexible conduit shall be approved for the purpose and maintain the liquid-tight feature of the installation. Approved manufacturers: Thomas & Betts, Steel City, O-Z Gedney. 3. Outdoor and Site Lighting Installation: i. Site lighting luminaires shall be as called for on the drawings. ii. Bases for site and roadway luminaires where required, shall be augered into the earth and concrete shall be poured into the augered hole without a sona tube below grade to allow the concrete to fill the natural crevices in the earth. Portion of base above grade shall be formed using a sonatube. Exposed portion of finished base shall be smoothed, and voids filled with grout. iv. Anchor bolts for poles shall be performed for the pole bolt circle at the factory. i. Standard enclosure shall be NEMA 1, unless noted otherwise, with primer and finish paint of the manufacturers standard. Cabinets shall be oversized where necessary to accommodate the entrance of several large conduits and/or when necessary to avoid overcrowding except cabinets for panels mounted flush shall be not more than 22 inches wide and 5-3/4 inches deep unless otherwise approved by the architect/engineer. Trims shall contain hinged doors and shall be equipped with flush chrome plated combination key locks and catches. Locks shall be all keyed alike and two keys furnished to the owner. ii. Column-type enclosures shall be similar to the standard enclosure except panel shall be approximately 8-1/2 inches wide for mounting between building column webs as indicated, and provided with extension trough and pullbox with neutral bar when shown on the drawings. iii. Where spaces are noted on the drawing, equip the panelboard with bus and all necessary hardware for future circuit breaker installation. iv. Metal frame and plastic covered typewritten card shall be mounted inside each panel door. Information entered onto the cards shall correspond to the circuit numbers as installed in the field. 2. Overcurrent Protective Devices i. General use circuit breakers for panelboards shall be bolt-on molded plastic case type, 1, 2, or 3 pole, quick-make, quick-break, with trip-free operating handle, position indicating and thermal-magnetic trip device. Furnish 2 and 3 pole breakers with common operating handle and common trip mechanism. All circuit breakers used for switching applications shall be U.L. listed type "SWD" for that application. all circuit breakers used for protection of motors, refrigeration equipment, or HVAC equipment shall be U.L. listed type "HACR" for that application. ii. Circuit breakers furnished with panelboards shall conform to the following interrupting ratings (symmetrical) in amperes unless otherwise noted: Voltage Rating i. Wall plates: Single and combination, of types, sizes, and with ganging and cutouts as indicated. Provide plates and attachment screws which mate and match with wiring devices to which attached. Provide wall plates with engraved legend where indicated. Provide smooth nylon coverplates for finished areas, and galvanized steel plate for unfinished areas. Trip Rating No. of Poles 15-100 ampere 15-100 ampere 125-225 ampere 250-400 ampere 15-100 ampere 15-100 ampere 125-225 ampere 250-400 ampere 400-800 ampere 120 240 240 240 277 480 480 480 480 ii. Floor service outlets: Modular, above-floor service outlets and fittings of types and ratings indicated. Construct of die cast aluminum, satin finish. Use design compatible with floor outlet wiring methods indicated. Provide 20 Amperes, 125 Volts, gray duplex receptacles. NEMA configuration 5-20R where indicated. Provide with 3/4 inch or 1 inch NPT, 1 inch long, locking nipple for installation where compatible with wiring method. I.c. Amperes (Symmetrical) 1 2&3 2&3 2&3 1 2&3 2&3 2&3 2&3 Frame Size ii. Duplex receptacles shall be wired with the neutral wire to the silver binding screw. iii. Three phase receptacles shall be wired such that all have the same phase sequence. iv. The receptacle circuit and panel number shall be indicated on the inside of all outlet boxes, or directly on the conductors by means of a wire labeling system. v. Combination switch/receptacle shall be installed in a two gang box with a combination switch/receptacle coverplate. Connect the receptacle to the lighting circuit ahead of the switch and locate the switch on the side of the box closest to the door. Note, this method is to be used only for 120 Volt lighting system. 277 Volt lighting switches and 120 Volt receptacles shall be located in separate boxes. vi. Confirm final location of all wiring devices and outlet boxes with owner/architect prior to rough-in. 9. Wiring devices listed or noted on the drawings as weatherproof shall be provided with a cover which maintains the weatherproof integrity when the cover is closed. Receptacles noted as suitable for operation in a wet locations shall be provided with a cover which will allow the receptacle to remain operational during wet conditions with a plug inserted into the receptacle. I: LIGHTING 1. Lighting Fixtures: see drawings for manufacturers catolog numbers. 22,000 22,000 22,000 42,000 25,000 25,000 30,000 42,000 42,000 100 amp 100 amp 225 amp 400 amp 100 amp 100 amp 225 amp 400 amp 800 amp iii. Ground fault circuit interrupters shall be similar to general use circuit breakers specified; 15-20 ampere, 1 or 2 pole with 5ma sensitivity. Furnish when indicated on drawing. iv. Fuses over 600 ampere shall be Bussman Hi-cap time delay type KRP-C, or Gould Shawmut A4BQ (601-2000 ampere) or Gould Shawmut A4BY (2001-6000 ampere) 600 volt, UL Class l with minimum interrupting rating of 200,000 ampere rms symmetrical. v. Fuses 600 ampere or below shall be Bussman low-peak dual element type LPN-RK (250 volt) or LPSRK (600 volt) or Gould Shawmut Amp-trap type A2K (250 volt) or A6K (600 volt) UL Class RK1 with minimum interrupting rating of 200,000 ampere rms symmetrical. vi. Provide spare circuit breakers installed in panelboards as indicated on the panel schedule as shown on the drawings. Provide 10% spare (minimum of 3) of each type and rating of fuses installed. 3. Safety Switches i. Provide fusible or non-fusible safety switches as indicated on the drawings. Switches shall be quickmake, quick-break, heavy duty visible blade type, horsepower and I squared T rated. Use NEMA 12 enclosures in factory areas, NEMA 1 enclosures in other indoor areas and NEMA 4X stainless steel type enclosures outside unless otherwise indicated on the drawings. Furnish three pole, single-throw switches unless otherwise indicated, with current and voltage ratings as indicated. ii. Suspended ceiling systems shall be supported for fixture installation as noted above, and as a minimum condition, as noted in ANSI/ASTM C636-76, par. 2-7, CEILING FIXTURES. iii. Install fixtures in accordance with the Architectural Reflected Ceiling Plans. Where substantial differences may occur between the Reflected Ceiling Plans and the Electrical Plans, inform the Architect/Engineer for resolution of the discrepancy. iv. The Contractor shall coordinate fixture construction details with ceiling system in which they are installed, i.e.: support system dimensions, flanges where required, acoustical tile or pan pattern, etc. v. Rows of fixtures shall be installed accurately as to line and level. Fixtures shall be securely mounted so that they will not be distorted by handling incidental to normal maintenance. vi. Surface type fluorescent lighting fixtures mounted on acoustical ceiling must be coordinated with the Architectural drawings in order that a main "T" runner will be placed in the center of each fixture and/or each row of fixtures. Main "T" runner shall be of at least the same length as the lighting fixture and shall be supported to carry at least twice the weight of the lighting fixture. vii. All fixtures shall be securely supported with approved hangers. Where fixtures will be installed in suspended ceilings, any Code-required additional ceiling supports as approved by the Architect, shall be provided by this Contractor. viii. Provide supports for all lighting fixtures as detailed on the Drawings, as specified, or as required by the fixture specified. Fixtures installed in unfinished areas (areas including but not necessarily limited to warehouses, factory areas, manufacturing areas, office spaces without lay-in ceilings, and spaces above lay-in ceilings) shall not be fastened directly to the structure. In these cases, unistrut type channel along with the appropriate fasteners and clips shall be used to support the fixtures. Refer to the drawings for specific support requirements in addition to those noted here. ix. Fixtures shall not hang directly from conduit boxes unless the boxes have been specifically designed for such purposes. These boxes shall be supported independent of the conduit system and shall not rely upon the conduit for support. x. Lay-in troffers in suspended ceilings and surface type fixtures mounted to suspended ceilings shall be secured mechanically by screws, rivets, clips, etc. as per Section 410-16(C), NEC. Additionally, layin fixtures shall also be supported by two independent support wires running from diagonally opposite corners of the fixture to the overhead structure. Surface mount fixtures shall be additionally supported by means of at least two clips for each fixture which surround the T-bar and are tied to the overhead structure with a separate wire. The surface fixtures shall be secured to these clips. xi. Plaster frames shall be furnished for each recessed fixture installed in plaster ceilings and walls. 9. The armor of interlocked armor cable, wiring channels, cable trays, and all metallic conduit including rigid, EMT, and flexible conduit shall be connected at each end to the equipment ground conductor utilizing a conduit grounding bushing. Junction boxes and other enclosures (sizes above 5" x 5") shall utilize an equipment ground lug to securely bond the equipment grounding conductor to the enclosure. 10. Where any grounding conductor requires physical protection to maintain grounding integrity, it shall be run through a non-ferrous conduit or bonded to a continuous steel conduit at both ends. 11. The grounding electrode system shall consist of 3 4" diameter x 10' copper clad ground rods. Exterior ground rods shall be driven to 12" below finished grade & be provided with a 12" diameter x 30" long rigid pvc pipe w/ screw cover for inspection purposed. center ground rod in pipe & install pipe flush with grade. pvc pipe and cover shall be traffic rated. interior ground rods shall be driven to 6" above grade & installed as close to a wall as possible. all connections to ground rods shall be cadweld type. L: EXECUTION 1. The contractor shall exercise due caution when working so as not to damage that portion of the electrical system that is to remain. 2. Positively no conduit or wire removed shall be reused in the new installation. 3. All circuits shall be identified on the panel directories by this contractor. At the completion of the job, the contractor shall provide each panelboard with a new typed directory with the existing loads as noted from the old directory and the new loads as installed. 4. The contractor shall keep on the job, one complete set of working drawings on which he shall record any deviations or changes from such contract drawings made during construction. Record drawings shall show changes in the following: i. Size, type, capacity, etc. of any material, device or piece of equipment. ii. Location of any device or piece of equipment. iii. Location of any outlet or source in the building service system. iv. Routing of any conduit, or other building electrical service. These drawings shall be kept clean and undamaged, and shall not be used for any other purpose than recording deviations from working drawings and exact locations of concealed work. After the job is completed, this set of drawings shall be delivered to the owner in good condition, as a permanent record of the installation as actually constructed. M: CUTTING AND REPAIRING 1. All necessary cutting in walls, floors and other such work shall be neatly and carefully done and the work shall be repaired in an approved and workmanlike manner. No cutting into the structural parts of the building, which may impair its strength, shall be permitted without the prior written approval of the owner. If such cutting is permitted, the area shall be suitably reinforced to restore the structural integrity of the work to its designed value. 2. The electrical contractor shall be responsible for all damage to work of his, or other trades, caused by his work or through the neglect of his workmen. All patching and repairing of damaged work shall be done by the trade which originally installed it, at the direction of the owner's representative, and the cost of such repair shall be paid by the electrical contractor. 3. Absolutely no cutting of wall, floor or other finished material or fastening of electrical components to the exposed surfaces of finished areas will be permitted. 1. The testing work shall include all labor, materials, tools, and equipment to perform and record all necessary tests and adjustments of equipment, including Load Center Unit Substations, Motor Control Centers, High Voltage Cable, 600 Volt Wire and Cable, and Grounding, as indicated on the drawings, specified herein, or where necessary to verify performance requirements. 2. Inspection tests shall provide a visual inspection of electrical equipment for manufacturing, shipping or installation defects. 3. Acceptance tests shall show that the methods and materials used in the installation of equipment conform to applicable codes and standards, and the manufacturers installation instructions, and to determine that the equipment involved may be energized for operational tests. 4. Operational tests shall show the electrical equipment will perform the functions for which it was designed. 5. The services of a recognized independent testing laboratory shall be engaged to conduct all tests described herein with the exception of routine insulation resistance, continuity and rotation tests. 6. Perform all acceptance and operational tests in the presence of the Architect/Engineer. Notify the Architect/Engineer of time of test at least two (2) days prior to testing. Notify manufacturers of electrical equipment to permit their representatives to witness the test should they so request. 7. Submit test reports, including complete data and actual readings taken, for all equipment tested to the Architect/Engineer for approval after each test performed. Do not energize any equipment for operating tests until data has been approved. Include copies of the final approved test reports upon completion of the work as part of the required operating and maintenance data to be furnished as specified in Division 1. 8. Give each power feeder and subfeeder cable (600 Volt Wire and Cable) a continuity and megger test. Isolate power cables to be megger tested by opening switches at each end of cable prior to testing. Apply megger tests, using a 1000 volt megger, between each conductor and ground with the other two conductors in the conduit grounded to the same ground. Minimum acceptable readings for disconnected cables shall be 1 (one) megohm. Cable must pass megger test to be reported as acceptable. 9. The following test and inspections shall be made on the grounding system. ii. Provide safety switches with an external operating handle interlocked with the cover door to prevent the door from being opened while the switch is in the "on" position except by operating an inconspicuous interlock defeating mechanism. Provide means for padlocking the operating handle in the "off" position. Equip switches with auxiliary contacts when indicated. 2. Indoor Installation: i. The Contractor shall refer to the Architectural drawings for ceiling type, construction and details of mounting. Adjust fixture trim ring as required for correct mounting in ceiling fixture is to be installed. All fixtures shall be supported per NEC Article 410. 8. Motors shall be connected to the equipment ground conductor with a conduit grounding bushing and with a bolted solderless lug connection on the metal frame. N: TESTING 8. Wiring device installation: i. Install switches and receptacles in outlet boxes as specified elsewhere in this specification. Install single pole toggle switches so that the switch is on in the "up" position. Install receptacles with the U-shaped ground slot at the top or to the left. 7. Convenience outlets shall be self-grounding type or shall have a green grounding conductor installed from the ground lug on the outlet to the outlet box. J. Lighting and Receptacle Panelboards 1. Panelboards for 480/277, 208/120, or 240/120 volt lighting and receptacle service shall be dead front type, conforming to NEMA standard PB-1-1-71 and UL 67, and consisting of three phase, three or four wire solid neutral, main lugs or main overcurrent device as indicated, branch overcurrent devices as noted and equipment ground bar, all in a surface or flush mounted code gauge galvanized sheet steel cabinet as indicated. Enclosure to be NEMA 1 unless noted otherwise with primer and finish paint of the manufacturers standard. All busing shall be copper. 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc xxi. Solid state transformers for low voltage lighting shall not be used for dimming applications unless the transformer and dimmer are a U. L. listed assembly specifically intended for the application. iii. Bases shall have reinforcing steel as indicated on the contract drawings and shall be Class 'A' concrete. 6. Dimmer switches: solid state dimmer switches conforming to NEMA WD 1, mounted in outlet boxes For incandescent fixtures; switch poles and wattage as indicated, 120 V, 60-Hz, continuously adjustable toggle, single-pole, with on-off switch. Equip with electromagnetic filter to eliminate noise, RF and TV interference. Dimmers to be Lutron "Nova T-Star" series for dimmers rated up to 1500 watts and "Nova" series for 2000 watt dimmers. Lighting switches shown adjacent to dimmers shall be Lutron "Nova T-Star" or standard "Nova" style to match dimmers and shall be provided with a single, one piece coverplate. Color shall be specified by architect. 8. Horizontal and vertical conduit runs may be supported by one-hole malleable straps, clamp backs, or other approved devices with suitable bolts, expansion shields (where needed) or beam type clamps for mounting to building structure or special brackets. xx. Low voltage lighting transformers should be protected by fuses. Fuse sizes shall be as recommended by the transformer manufacturer. Busman type HRS or Littelfuse 155020, fuse holders are recommended. 6. Lighting fixtures permanently connected to the conduit system shall be grounded by means of a grounding conductor run inside the conduit. Fixtures mounted on trollies or portable lighting units shall be grounded by means of a grounding conductor in the portable cord. 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. 4. Discrepancies between the drawings or between the drawings and actual field conditions shall be brought to the attention of the architect and the engineer prior to submitting the bid. The more comprehensive and most expensive scope of work shall be considered for the electrical bid unless written clarification is provided by the architect and the engineer prior to submitting the bid. xix. All lamps shall be in working order at the time of final acceptance of the work by the Owner and Architect/Engineer. This Contractor shall replace all defective lamps with new lamps until the work is finally accepted. iii. Fuse clips shall be rejection type for fuses specified (up to 600 ampere). Fuses clips for 601 ampere to 6000 ampere shall be suitable for UL Class l fuses. 4. Transformers i. Transformers shall be indoor dry, two winding, quiet type, with ventilated enclosure, conforming to NEMA standards, 220 degrees celcius insulation for continuous operation in a 40 degree celsius ambient temperature with a temperature rise not to exceed 80 degrees celsius. Provide a minimum of two 2-1/2% FCAN and four 2-1/2% FCBN taps in the primary winding for transformers over 25 KVA and a minimum of two 2-1/2% FCBN taps for transformers 25 KVA and below. Transformers 25 KVA through 75 KVA shall be designed for floor or wall mounting. ii. Sound levels shall not exceed those established in ANSI standard C89 shown in the following table: KVA dB level 0-150 42 iii. Furnish transformers having voltage, KVA ratings and connections as indicated on the drawings. i. Inspect ground conductors and connections for compliance with plans and specifications and for satisfactory workmanship. After installation of the grounding electrodes, provide ground resistance testing prior to the interconnection of other grounding systems. Do not perform tests under unusually wet weather; tests should be performed during normal weather conditions. REVISIONS ii. Reports shall include all resistance readings obtained, temperature, humidity and condition of the soil at the time of the tests. 10. Operational tests shall be performed on all electrical systems, and shall include, but not be limited to, building lighting system, panelboards, motor starters and control devices, alarm circuits and site lighting equipment. O: GUARANTEE 1. Material, equipment and installation shall be guaranteed for a period of one year from the date of acceptance. Defects which appear during that time period shall be corrected by this contractor at his expense. 9 3. The contractor shall visit the job site and become familiar with all existing conditions. Submission of a bid assumes the contractor has reviewed or accepts all field Conditions and existing conditions. No additional compensations shall be allowed for labor or material because of ignorance of these conditions before or after bid submission. 1. Conductors shall be new, 600 volt, 90c, type XHHW, THHN or THWN insulation, stranded copper for feeders rated above 60 amps. Compact aluminum may be used for feeders of 150amps or higher. Minimum size shall be #12 AWG for runs of less than 100 feet total circuit length (out and back for single phase circuits and out only for three phase circuits with no neutral). Use #10 AWG for circuits longer than 100 feet. Other sizes shall be as noted. Control wiring may be #14 AWG. All 120 volt and 277 volt circuits shall have a dedicated neutral conductor. The neutral conductor shall be the same size as the phase conductor. All conductors shall be copper. 5. Where building type conductors are installed in a raceway, a green equipment grounding conductor shall be included in each raceway system. 10 2. The electrical, mechanical, architectural, structural, and all other drawings as well as the specifications and addendums are part of the contract documents. any electrical requirements called for on other trades contract documents shall be included in the electrical bid. G: CONDUCTORS xviii. At the time of final inspection all fixtures and equipment shall be complete with all required glassware and/or reflectors, clean and free of defects. Any glass-ware, or reflectors, etc., which have defects shall be replaced at the Contractor's expense before final acceptance. 8 1. The drawings represent the design for the listed manufacturers' requirements. If any substitutions are accepted by the engineer, this contractor shall be responsible for all necessary modifications, including cost, to the electrical system required because of the substituted equipment or material. i. Wood - wood screws. ii. Concrete - expansion bolts or cast in place anchors. iii. Structural steel - approved brackets or machine bolts. 4. Any item covered by the preceding paragraph which is within six feet of grounded metal and not directly interconnected with the grounded metal shall have a flexible bare copper cable connection not smaller than #6 AWG to the grounding system. CHINO, CA 91710 C: GENERAL REQUIREMENTS 2. Electrical supports shall be attached to the structure by one of the following methods: xvii. When fixtures are installed in a fire proof ceiling, the fixture shall be U. L. listed to maintain the fire proof rating or the fixture shall be fire proofed by the electrical contractor using a U. L. accepted standard. see architectual drawings for ceiling ratings. 11995 CENTRAL AVE. The National Electrical Code - sometimes referred to herein as the "NEC" - (NFPA-70). ii. National Electrical Safety Code (ANSI-C2). iii. All applicable state and local codes. iv. Applicable provisions of the Occupational Safety and Health Act. 1. Supports shall be suitable for the device or equipment to be mounted. All supports shall present a neat appearance, and shall be installed in such a way that they do not detract from the appearance of the space. Supports shall have adequate strength and shall be installed so as to properly support the device or equipment mounted on them. 3. The entire power and lighting system shall be permanently and effectively grounded including panels, starter enclosures, motor frames, and other exposed, non-current carrying parts of the electrical equipment. The equipment ground conductor shall be separate from the neutral conductor and shall not be used as a load current carrying conductor. 7 i. F: ELECTRICAL SUPPORTING DEVICES 2. Ground conductors shall be stranded, annealed copper with green insulation (insulation material as specified for general building use). xvi. Where a modular wiring system is installed, all ceiling mounted recessed fluorescent lighting fixtures shall be furnished with suitable receptacles to match the modular wiring system furnished and installed by this Contractor. Each fixture shall be equipped to permit either single or multiple fixture circuit wiring as is appropriate for the fixture type. 6 3. Perform all work in accordance with the latest edition of applicable codes including, but not necessarily limited to those listed below: Entering or cross-connecting enclosures containing arcing or high temperature devices. Two-inch conduit and larger entering any enclosure. Passing from Division 1 to Division 2, from Division 2 to non-classified areas, with or without a barrier. Multi-conductor and shielded cables. 1. The entire power, lighting system as well as building structure, mechanical & plumbing systems, fences & simalar metal objects shall be permanently and effectively grounded in accordance with the minimum requirements of the National Electrical Code, or as specified herein, whichever is the more stringent. 5 2. The contractor shall secure all permits and pay all fees that are required by the applicable local and state codes. i. ii. iii. iv. xv. Branch circuit conductors shall be run in fluorescent fixture wiring channels only as permitted by the N.E.C. The Contractor shall be responsible for providing all necessary boxes and conduit for an approved installation. K: RACEWAY AND GENERAL GROUNDING HARBOR FREIGHT TOOLS 1. All work included by the drawings and specifications, together with all material (or equipment) furnished, shall comply with the latest published codes and standards listed insofar as such shall apply. All electrical items shall be UL labeled & listed. 8. Conduit Fittings in Classified (Hazardous) Areas: Conduit seals and/or drain seals shall be installed in strict accordance with the NEC in classified (Hazardous) areas designated on the drawings, with special attention to the following: xiv. Incandescent fixtures shall be thermally rated, protected and marked for their application especially in recessed mounting, to protect against over-temperature and combustion. The installation shall comply with Section 410-65 thru 410-72 the NEC. Siemens Cleveland Switchboard Co. 4 B: CODES, PERMITS AND FEES 7. Outlet, Pull, Terminal and Junction Boxes in Classified (Hazardous) Areas: Cast boxes shall be copper-free aluminum with integral hubs or box wall thickness sufficient for a minimum of five full tapered threads. Covers shall be screw-on bolt-on through 12" x 12" boxes and hinged removable bolt-on covers for larger boxes. Boxes other than outlet boxes shall be equipped with a breather drain and equipment grounding lug and all boxes shall be, as applicable, for installation in the particular classified (hazardous) areas which are designated on the drawings. Approved Manufactures: Crouse-Hinds, Pyle-National, Appleton, Adalet, O-Z Gedney, or Killark. General Electric Company Cutler Hammer/Westinghouse Square D 3 4. The electrical contractor shall warrant all work & material indicated on these electrical drawings for a period of 1 year from the date of final acceptance. Warranty shall include any additional labor or material required to repair or replace defective item. xiii. Fixtures shall be installed with due regard for beams, piping, ductwork, and other mechanical or plumbing equipment. TYPE 3. The electrical contractor shall not attach to, cover up, or finish against any defective work, or install in a manner which will prevent proper installation of the work of other trades. 6. Fittings for conduits : All conduit runs at building expansion joints shall be provided with O-Z type expansion fittings. Sizes shall be as dictated by the conduit size. A bonding jumper shall be securely connected to each conduit. Exterior exposed runs of PVC conduit shall be provided with expansion fittings at intervals not exceeding manufaturers recommendations. viii. Approved Manufacturers for Power Distribution Equipment: DATE 2. The exact location of all items shown on the electrical drawings is dependent upon field conditions. Review the plans and specifications for all parts and consult with other trades of this project for pertinent data on sizes, locations, wiring, etc., as required for a complete electrical installation. xii. Pendant mounted fixtures shall utilize mounting hardware as called for on the drawing. mount fixtures at elevations as noted on the drawings. Wherever the mounting surface slopes, fixtures shall be provided with universal type fixture hangers to allow the fixture to hang plumb. 1 i. Furnish and install new conduit and wire. ii. Furnish and install all fuses, circuit breakers, panelboards etc. iii. Install new lighting fixtures as indicated. iv. Furnish & install new light fixtures as indicated. v. Furnish & install communications devices. 5. Bushings: Grounding type, with insulating plastic insert; malleable iron, zinc or cadmium plated, for steel conduit and aluminum alloy for aluminum conduit. Install grounding type bushings as required in the grounding section of this specification. 2 1. The electrical contractor shall provide all labor, material, equipment, and tools necessary for demolition and removal of existing and the complete installation of the new electrical work, ready to use, as shown on the drawings or specified herein. Work shall include, but not be limited to the following: # A: DESCRIPTION OF WORK 5. Panelboard and Transformer Installation i. Mount panelboards at uniform height throughout the building, and such that the top switch is not more than 79 inches above floor when measured to the center of the switch handle. ii. Install handle guards on all breakers for night lighting, emergency, and similar circuits when indicated. iii. Each panelboard shall be identified with a legend plate of lamicoid plastic inside the door for panelboards in finished areas and on the outside of panelboards in unfinished areas with the panel designation as shown on the drawings. ELECTRICAL SPECIFICATIONS iv. Install not less than two spare 1-1/4 inch conduits from each flush mounted panel to an accessible area above the ceiling. DATE 07/08/15 v. When branch circuits are not scheduled on the drawing, they shall be arranged to balance the phase loads on each panelboard and the loads shall be equally distributed on each of the phases of the panelboard. JOB NO. 15166 vi. Mount panelboard, safety switches, and similar equipment securely to walls or steel supports. Equipment mounted on the building perimeter foundation walls shall be shimmed at least 1/4 inch from the wall to permit back ventilation. vii. Provide supports for truss mounted and wall mounted transformers. All transformers which are mounted above panelboards shall be mounted away from the wall by an amount equal to the depth of the panelboard. The width of the panelboard shall also be maintained clear behind the transformer. E0.1 SHEET NO. F) ALL UNUSED WIRE (POWER & COMMUNICATION) SHALL BE REMOVED. G) ALL EXISTING WIRING (POWER & COMMUNICATION) THAT IS TO REMAIN SHALL BE REWORKED OR REPLACED WITH CODE COMPLIANT MATERIAL & SUPPORTS. ANY EXISTING SURFACE MOUNTED CONDUITS SHALL BE REMOVED OR RELOCATED SO THAT THEY ARE IN THE JOIST SPACE OR WITHIN WALL CAVITIES. H) EXISTING LIGHT FIXTURES THAT REMAIN OR ARE BEING RELOCATED SHALL BE CLEANED AND RE-LAMPED WITH 4' T8 LAMPS. BROKEN LENSES SHALL BE REPLACED. PROVIDE NEW T8 BALLASTS IF REQUIRED. I) EXISTING LIGHT FIXTURES, ELECTRICAL / TELECOMMUNICATION DEVICES, PANELBOARDS ETC. THAT ARE NOT TO BE REMOVED SHALL BE NOTED AS EXISTING TO REMAIN ON THE DRAWINGS. SEE ARCHITECTURAL & MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION ON SCOPE OF DEMOLITION. CASH WRAP POWER / COMMUNICATION DETAIL SCALE: NOT TO SCALE +72" 30A DEDICATED ISO GROUND QUAD OUTLET MOUNTED WITHIN THE CASHWRAP SO THAT BOTTOM OF QUAD IS 2" ABOVE LOWEST SHELF. SEE DETAIL 1/E1.0. COLOR TO BE ORANGE. 05 COORDINATE ROUGH-IN LOCATION WITH MANUFACTURERS SHOP DRAWINGS PRIOR TO INSTALLATION. 06 DUPLEX OUTLET MOUNTED ON WALL AT 12" ABOVE WINDOW. MOUNT FLUSH IN CEILING IF CEILING IS WITHIN 12" OF TOP OF WINDOW. 07 DUPLEX OUTLET MOUNTED FLUSH IN CEILING FOR INSTALLATION OF INTERIOR MOUNTED NEON SIGNS BY T.G.C. 08 J-BOXES WITH SERVICE DISC SWITCH FOR SIGN CIRCUITS. COORDINATE ROUGH-IN REQUIREMENTS WITH SYSTEM CONTRACTOR. 09 ´+,*+&203$570(1732:(532/(72%()851,6+('%<+)7$1',167$//('%<(&(&6+$//(;7(1'81,67587 )5207+(32:(532/(83727+(522)6758&785($7 ´$))$1'&211(&77281,675876(&85('72522) STRUCTURE (UNISTRUT TO BE PAINTED WHITE). 10 WEATHERPROOF PUSH BUTTON MOUNTED +48" CONNECT TO SERVICE BELL. EDWARDS #852. 11 SERVICE BELL MOUNTED TO BOTTOM OF ROOF STRUCTURE. EDWARDS #340-10G5. 12 REMOVE EXISTING ELECTRICAL PANELS. 13 G.C. SHALL COORDINATE NEW SWITCH & METER REQUIREMENTS WITH POWER COMPANY IMMEDIATELY UPON RECEIVING CONTRACT. 14 EXHAUST FAN SOLID STATE SPEED CONTROLLER PROVIDED BY MC WIRED & INSTALLED BY E.C. 15 DUPLEX RECEPTACLE FOR SUSPENDED MONITOR. E.C. SHALL PROVIDE MC CABLE & CAST BOX & MOUNT RECEPTACLE ON MONITOR ARM. COORDINATE EXACT LOCATION WITH COMMUNICATIONS CONTRACTOR. 16 NOTE NOT USED. 17 240V CHARGER & BOOST TRANSFORMER (208:240V) PROVIDED BY HFT WIRED AND INSTALLED BY E.C. COORDINATE ROUGH-IN REQUIREMENTS WITH EQUIPMENT MANUFACTURER PRIOR TO INSTALLATION. P-34 17 L-25/2 (39,41) 10-2 CONNECT TO FORKLIFT CHARGER. COORDINATE EXACT ROUGH-IN WITH EQUIPMENT SUPPLIER. RECEIVING AREA LIGHTING CONTROL PANEL OVERRIDE SWITCH P-29 12-2 #12 ISO GND 3 APPROXIMATE LOCATION OF EXISTING TELEPHONE DEMARK B.5 P-30 LIGHTING CONTROL PANEL 6 10-2 L P-11 10-2 #10 ISO GND M 4 10 EXISTING 600A DISCONNECT SWITCH & METER +78" AFF +78" AFF +78" AFF B L-26 R18 8 TO PUSHBUTTON AT RECEIVING DOOR 10-2 10-2 10-2 P-12 P-8 J D P-31 B T 11 15 P-33 WP/GFI ON ROOF P-38 SALES AREA DD 12-2 P-33 WP/GFI ON ROOF P-38 RTU-3 7 L-20,R20 10-2 100A/WP RTU-2 M-125/3 (7,9,11) 1-3 P-7 10-2 #10 ISO GND P-33 WP/GFI ON ROOF P-38 DD 200A/WP M-100/3 (2,4,6) 2-3 A.8 SALES REPLENISHMENT DD 200A/WP RTU-1 A.7 M-125/3 (1,3,5) 1-3 4 10-2 6 P-6 9 L-40,R24 10-2 P-8 10-2 RTU-4 R R MANAGER 3 P-20 10-2 #10 ISO GND M-40/3 (8,10,12) P-15 +44" H P-28 GFI EF P-41 8-3 WOMEN R 10-2 10-2 10-2 1 10-2 R P-19 P-18 R R 10-2 10-2 P-41 P-3 P-41 DAMPER #10 ISO GND #10 ISO GND 10-2 R m 10-2 10-2 MEN 10-2 R GFI P-24 m P-17 +44" J P-28 +44"/GFI +101" P-21 +48"/GFI 10-2 EF 2 CASH ROOM P-1 10-2 3 #10 ISO GND P-28 5 +23"/GFI 10-2 R m 2 P-3 R J R REVISIONS P-36 GFI P-23 J P-4 P-4 L-25,R23 GFI P-28 +44"/GFI TYPE 60A/WP 10-2 R 1.5KW WATER HEATER DD 10-2 DATE L-40,R24 6 P-33 WP/GFI ON ROOF P-38 H P-23 +48"/GFI R P-23 GFI # 4 P-5 10-2 #10 ISO GND BREAK ROOM 10-2 R P-3 R POWER PLAN A P-2 10-2 3 #10 ISO GND 10-2 POWER PLAN SCALE 1/8" = 1'-0" DATE 07/08/15 JOB NO. 15166 E1.0 SHEET NO. 9 4 P-9 10-2 #10 ISO GND 10 +78" AFF 10-2 8 P-39 7 P-39 6 P-39 5 P-39 4 9 3 P-10 10-2 L-42,R24 1 6 J PHOTOCELL PC ON WALL MOUNTED AT 15'-0". SHIELD FROM ARTIFICIAL LIGHT SOURCES. P L-42,R24 2 1 E1.0 DEDICATED ISOLATED GROUND QUAD OUTLET ON DEDICATED CIRCUIT. COLOR TO BE ORANGE. 04 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. E) CONTINUITY OF CIRCUITS INTERRUPTED BY REMOVAL OF ELECTRICAL DEVICES SHALL BE MAINTAINED. PROVIDE A DEDICATED CIRCUIT & WIRE THRU TIME CLOCK. UTILIZE SAME CIRCUIT IF THERE ARE TWO EXHAUST FANS. 03 CHINO, CA 91710 D) EXISTING CONDUITS, CIRCUITS OR SYSTEMS PASSING THROUGH THE REMODELED AREAS WHICH SERVE UNREMODELED AREAS SHALL REMAIN AND BE PROTECTED DURING DEMOLITION AND REMODELING, AND SHALL BE RELOCATED AND REROUTED. 02 11995 CENTRAL AVE. C) EXISTING CONDUITS, CIRCUITS OR SYSTEMS IN WALLS OR CEILING BEING REMOVED WHICH SERVE SURROUNDING UN REMODELED AREAS SHALL BE REWORKED AND MAINTAINED. PROVIDE A JUNCTION BOX ON WALL ABOVE CEILING FOR RACK POWER. COORDINATE ALL CONNECTION REQUIREMENTS WITH RACK SUPPLIER PRIOR TO ROUGH-IN PROVIDE MC CONDUIT DOWN WALL & INTO RACK ENCLOSURE. CONNECT TO RACK POWER SYSTEM AS WELL AS PROVIDING A SEPARATE QUAD RECEPTACLE MOUNTED IN RACK. COORDINATE EXACT LOCATION WITH HFT PRIOR TO INSTALLATION. HARBOR FREIGHT TOOLS B) REMOVE AND/OR RELOCATE EXISTING ELECTRICAL DEVICES NOT NOTED AS EXISTING TO REMAIN. COORDINATE SUCH CONDITIONS WITH ARCHITECTURAL DRAWINGS. 01 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc POWER PLAN NOTES GENERAL ELECTRICAL DEMOLITION NOTES A) NO ATTEMPT HAS BEEN MADE TO INDICATE ALL EXISTING ELECTRICAL DEVICES, LIGHT FIXTURES, COMMUNICATION DEVICES, WIRING, CONDUIT, ETC. TO BE REMOVED AND/OR RELOCATED. HOWEVER, THE ELECTRICAL CONTRACTOR SHALL FIELD VERIFY THE EXTENT OF DEMOLITION PRIOR TO SUBMITTING BID. N GENERAL NOTES ALL SALES & SALES REPLENISHMENT AREA LIGHTING CIRCUITS SHALL BE B ALL NIGHT / EMERGENCY / EXIT LIGHTING CIRCUITS SHALL BE #12 GA. x1" BENT PLATE CONNECT TO STRUCTURE AS REQUIRED STRUCTURE STRUCTURE #12 GA. SLACK SUSPENSION WIRES W/ 3 TIGHT TURNS IN 1-1/2" AT EACH END. TYPICAL. #10 SHEET METAL SCREWS UTILIZE ANTI SWAY #12 AWG SLACK SUSPENSION WIRE SUPPORTS WITH 3 TIGHT TURNS IN 1/2" OF EACH OTHER IF OBSTRUCTION (WALL, COLUMN, DUCTWORK, OTHER FIXTURE, ETC.) OCCURS WITHIN THE CIRCUMFERENCE OF THE FIXTURE SWAYING AT A 45 DEGREE ANGLE FROM PLUMB. ATTACH TO FIXTURE AS SHOWN IN ADJACENT DETAIL. #12 GA. x1" BENT PLATE CHAIN TO UNISTRUT MOUNTING BRACKET. CHAIN SHALL BE SEISMIC RATED WITH CLOSED HOOKS. SEISMIC RATED INDEPENDENTLY SUPPORTED TBAR GRID CLIP WITH #12AWG TIE WIRE TO STRUCTURE CADDY CLIP 515 SERIES MOUNTED IN ALL FOUR CORNERS CEILING GRID FIXTURE TYPE CD, C1D, CDE, C1DE SALES LIGHT FIXTURE MOUNTING DETAIL RECESSED LIGHT FIXTURE SEISMIC MOUNTING DETAIL N.T.S. ALL EXTERIOR LIGHTING FIXTURES SHALL BE E FIXTURES LOCATED IN THE SALES REPLENISHMENT AREA SHALL BE MOUNTED AS HIGH AS POSSIBLE MAXIMUM 15' AFF TO THE BOTTOM OF THE JOISTS OR ON UNISTRUT MOUNTED TO THE BOTTOM OF THE JOIST WHERE FIXTURE LOCATIONS DO NOT LINE UP WITH THE JOIST. IF JOISTS ARE HIGHER THAN 15'-6" AFF TO BOTTOM CHANGE TYPE 'D' FIXTURES TO TYPE 'C' FIXTURES & MOUNT FIXTURES AT 15'-0" AFF. F ELECTRICAL CONTRACTOR SHALL INSTALL ALL EMERGENCY BALLASTS IF SHIPPED SEPARATELY. COORDINATE WITH VENDOR. G FOR EMERGENCY FIXTURES AE, A1E, BE, CE, C1E, DE & D1E NOT SHOWN AS NIGHT LIGHTS, RUN AN EXTRA HOT CONDUCTOR (BYPASSING ALL CONTROL) AND CONNECT TO EMERGENCY BALLAST. FIXTURES SHALL BE SHUT OFF WITH LOCAL LIGHT FIXTURE CONTROL. 01 LIGHT FIXTURES WITH NO LETTER DESIGNATION ARE EXISTING TO REMAIN. CLEAN, RELAMP & REBALLAST TO 4' LAMP T8 SYSTEM AS REQUIRED. 02 DIGITAL SWITCH PROGRAMMED FOR SALES REPLENISHMENT DIMMING. 03 DIGITAL SWITCH. PROGRAM TO DIM SALES AREA FIXTURES. 04 MOUNT OCCUPANCY SENSOR @ +44" A.F.F. 05 IF EXISTING EXTERIOR LIGHTING / PYLON SIGNS, ETC ARE CONTROLLED BY EXISTING DISTRIBUTION SYSTEM LOCATED IN HFT SPACE, CLEAN, RELAMP & RETROFIT EXISTING FIXTURES, REROUTE, EXTEND BRANCH CIRCUITING TO PANEL 'L' & 'P'. 06 DIGITAL SWITCH PROGRAMMED FOR SALES/SALES REPLENISHMENT 2 HOUR OVERRIDE. 5 INDICATES CIRCUIT NUMBER. TYPICAL. INDICATES RELAY NUMBER. TYPICAL. 5 L-1,R1 L-2,R2 L-4,R4 L-3,R3 L-5,R5 L-7,R7 C1DE EM1 L-9,R9 L-16 L-10,R10 EM1 L-16 C1D L-18,R17 L-8,R8 C1D C1DE L-16,R19 C1DE NL C1D C1DE C1D C1DE C1D 5 L-6,R6 L-18,R17 DDE 29'-5" DDE 6 L-11,R11 D1e B.5 CDE CDE DDE D1D DD SA L-18,R17 L-17,R17 5 EM1 L-16,R19 DDE EM1 EM1 NL DDE L-16 L-16 EM5 L-16 B L-16 L-16,R19 L-18,R17 L-16,R19 5 CDE CD CDE CDE CD CDE CD CDE CD DD CDE NL 40'-6" L-12,R12 5 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. 4 A.8 DD NL A.7 CD DDE DDE CHINO, CA 91710 3 11995 CENTRAL AVE. 2 HARBOR FREIGHT TOOLS 1 EM5 L-16 L-16 8-2 N.T.S. N.T.S. EM1 DIMMING CONTROL. EMERGENCY BALLASTS SHALL BE WIRED TO POWER (2) LAMPS PER FIXTURE. REWORK EMERGENCY BALLAST WIRING AS REQUIRED TO ILLUMINATE THE TWO LAMPS THAT OCCUR ABOVE THE MAIN EGRESS AISLES. FIXTURE TYPE AD, ADE, BD, BDE & BE 1" L-17,R17 14-2 LIGHTING PLAN NOTES FIXTURE TYPE CD, C1D, CDE, C1DE ATTACHMENT OF ANTI SWAY SUSPENSION WIRES TO FIXTURES DETAIL W/ D TO STRUCTURE #12 AWG SLACK SUSPENSION WIRES W/ 3 TIGHT TURNS IN 1-1/2" AT EACH END. TYPICAL. 10-3 C ROOF OR FLOOR ABOVE #12 GA. x1" BENT PLATE 10-2 8-2 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc UNISTRUT AS REQUIRED A 5 CD SA L-17,R17 REVISIONS L-18,R17 4 oc 3 os D1d ADE D1a DD D1f ADE a 2 DDE CD D1c L-15 BE BDE c CD TYPE CDE L-14,R14 os b os CDE CDE L-14,R15 CDE L-16 EM1 L-16 EM1 EM1 D1g os L-18,R17 DDE DDE e EM1 L-16 EM5 L-16 SCALE 1/8" = 1'-0" 9 LIGHTING PLAN L-16 A LIGHTING PLAN 8 7 6 5 4 3 2 # os d 1 5 L-13,R13 L-14,R16 CDE L-16,R19 D1b ADE CDE N ADE BDE BE DATE 07/08/15 JOB NO. 15166 E1.1 SHEET NO. 10 DDE oc 4 NL DATE BD PS OS OS 18/3 COPPER HDU POWER UTILITY DEMAND RESPONSE SYMBOL 14/3 COPPER D2 TYPICAL CAT 6 CAT 6 SYMBOL D1 CAT 6 TYPICAL CAT 6 P/S 120V MPU DIGITAL SWITCH LEVITON #RLVSW-1W 14/2 COPPER 0-10V 10/2 COPPER 120V TO DIMMABLE FIXTURES 10/2 COPPER 120V TO NON-DIMMABLE FIXTURES / LOADS DIGITAL SWITCH LEVITON #RLVSW-2W LOCATED IN INDIVIDUAL ROOMS SEE FLOOR PLAN FOR QUANTITIES & LOCATIONS LIGHTING CONTROL SYSTEM SCHEMATIC DIGITAL SWITCH LEVITON #RLVSW-1W RJ45 JACK NEXT TO OVERRIDE SWITCHES FOR CONNECTION OF HDV. DIGITAL SWITCH LEVITON #RLVSW-1W LOCATED AT TELEPHONE BOARD. PROGRAM SWITCH AS 2 HOUR OVERRIDE FOR SALE/STOCK ROOM LIGHTING. PROVIDE PHENOLIC LABEL ABOVE SWITCH DESCRIBING FUNCTION. LOCATED IN MANAGERS OFFICE. PROGRAM ONE SWITCH TO DIM SALES FLOOR LIGHTING. PROVIDE PHENOLIC LABELS ABOVE EACH SWITCH & DATA OUTLET DESCRIBING FUNCTION. NO SCALE LEVITON GRENMAX #R32TC-100-RPM16-116 RELAY TYPES AS SHOWN IN LIGHTING CONTROL PANEL TABLE. PHOTO SENSOR DIGITAL SWITCH TIME CLOCK OVERRIDE L-1 SALES FLOOR 1 1DS NO NO d EMPLOYEE e L-2 SALES FLOOR 2 1DS NO NO d CUSTOMER e L-3 SALES FLOOR 3 1DS NO NO d EMPLOYEE e L-4 SALES FLOOR 4 1DS NO NO d CUSTOMER e L-5 SALES FLOOR 5 1DS NO NO d EMPLOYEE e L-6 SALES FLOOR 6 1DS NO NO d CUSTOMER e L-7 SALES FLOOR 7 1DS NO NO d EMPLOYEE e L-8 SALES FLOOR 8 1DS NO NO d CUSTOMER e L-9 SALES FLOOR 9 1DS NO NO d EMPLOYEE e L-10 SALES FLOOR 10 1DS NO NO d CUSTOMER e L-11 STOCK LIGHTING 11 1DS NO NO f EMPLOYEE e L-12 STOCK LIGHTING 12 1DS NO NO f EMPLOYEE e L-13 CORRIDOR LIGHTING 13 1DS d,e NO g 24 HOUR NO L-14 MANAGER LIGHTING 14 1DS a NO NO 24 HOUR NO L-14 CASH ROOM RECEPTACLE 15 1DS b NO NO 24 HOUR NO L-14 BREAK LIGHTING 16 1DS c NO NO 24 HOUR NO P/C ON T/C OFF P/C ON T/C OFF L-17,18 EXTERIOR LIGHTING 17 2TB NO OUTDOOR NO L-26 EXTERIOR SIGNS 18 2TB NO OUTDOOR NO L-16 EMERGENCY / NIGHT LIGHTING 19 1DS NO NO d 24 HOUR NO L-20 CEILING RECEPTACLES 20 2TB NO NO NO CUSTOMER NO L-23 CASH ROOM RECEPTACLE 21 2TB b NO NO NO NO L-24 MANAGER OFFICE RECEPTACLE 22 2TB a NO NO NO NO NO NO L-25 BREAK ROOM RECEPTACLE 23 2TB c NO NO NO NO L-40,42 CEILING RECEPTACLES 24 2TB NO NO NO CUSTOMER NO - SPARE 25 1DS - - - - - - SPARE 26 1DS - - - - - - SPARE 27 1DS - - - - - - SPARE 28 1DS - - - - - - SPARE 29 1DS - - - - - - SPARE 30 2TB - - - - - - SPARE 31 2TB - - - - - - SPARE 32 2TB - - - - - TIME CLOCK SETTINGS EMPLOYEE 90 MINUTES BEFORE OPEN 'ON', 90 MINUTES AFTER CLOSE 'OFF' 2 HOUR OVERRIDE CUSTOMER 10 MINUTES BEFORE OPEN 'ON', 10 MINUTES AFTER CLOSE 'OFF' 2 HOUR OVERRIDE P/C ON P/C OFF EXTERIOR PHOTOCELL 'ON' & 'OFF' - P/C ON T/C OFF EXTERIOR PHOTOCELL 'ON', 2 HOURS AFTER CLOSE 'OFF' - 24 HOUR LOCAL OCCUPANCY SENSOR 'ON' - 'OFF' - NOTES: 1) HARBOR FREIGHT THRU ITS LIGHTING VENDOR SHALL SUPPLY ALL NECESSARY PARTS & SERVICE FOR A DIMMABLE LIGHTING CONTROL SYSTEM. THE ELECTRICAL CONTRACTOR SHALL WIRE & INSTALL THE SYSTEM & COORDINATE WITH THE SYSTEM MANUFACTURER PROGRAMMING, LABELING & TRAINING RELATED TO THE SYSTEM. a) b) c) d) e) f) g) h) i) j) COMPLETE 5-100% DIMMING FOR INTERIOR LIGHT FIXTURES DAYLIGHT ZONES CONTROLLED BY INTERIOR PHOTO SENSORS MINIMUM 4 ZONE TIME CLOCK FUNCTION EXTERIOR ZONES CONTROLLED BY EXTERIOR PHOTOCELL / TIME CLOCK COMBINATION ENCLOSED ROOM DIMMING / OCCUPANCY CONTROLS DEMAND RESPONSE CONTROL INTEGRATION WITH POWER COMPANY SWITCHED EMERGENCY & NON-SWITCHED EMERGENCY (NIGHT LIGHT) FIXTURES EXHAUST FAN CONTROL FUTURE INTEGRATION CAPABILITY INTO OWNERS NETWORK OFFICE AREA OCCUPANCY CONTROL OF CERTAIN RECEPTACLES. 2) THE LIGHTING SYSTEM VENDOR SHALL VERIFY THAT THE 0-10V DIMMING BALLASTS PROVIDED BY THE LIGHT FIXTURE MANUFACTURER ARE COMPATIBLE FOR USE WITH THE LIGHTING CONTROL SYSTEM. 3) THE LIGHTING CONTROL SYSTEM MANUFACTURER SHALL INCLUDE IN THE COST OF THE SYSTEM A MINIMUM OF 2 SITE VISITS TO AID THE ELECTRICAL CONTRACTOR WITH THE INSTALLATION, COMMISSIONING & PROGRAMMING & OPERATION OF THE SYSTEM. THE SECOND SITE VISIT SHALL INCLUDE A MINIMUM OF 4 HOURS OF TRAINING WITH THE OWNERS AUTHORIZED PERSONNEL. 4) HARBOR FREIGHT SHALL RETAIN THE SERVICES OF AN INDEPENDENT THIRD PARTY CONTRACTOR TO PROVIDE COMPLETE COMMISSIONING OF THE LIGHTING CONTROL SYSTEM AS WELL AS PROVIDING ALL REQUIRED DOCUMENTATION TO THE AUTHORITY HAVING JURISDICTION TO RECEIVE A CERTIFICATE OF OCCUPANCY. COMMISSIONING AGENT SHALL BE LICENSED BY THE STATE OF CALIFORNIA & LOCAL AUTHORITIES TO PERFORM SAID DUTIES. ELECTRICAL CONTRACTOR SHALL COORDINATE ON SITE WITH THE COMMISSIONING AGENT & PROVIDE NECESSARY LABOR TO AID WITH THE COMMISSIONING OF THE SYSTEM. 5) THE LIGHTING CONTROL PANEL SHALL BE HOUSED IN A SINGLE LOCKING NEMA 1 VENTILATED CABINET & INCLUDE THE FOLLOWING EQUIPMENT. POWER SUPPLY, CPU, LOW VOLTAGE INPUT TERMINATION BLOCK & CONTROL RELAYS. RELAYS MAY BE DIMMING & SWITCHING TYPE OR LATCHING TYPE. THE SYSTEM SHALL HAVE A SHORT CIRCUIT CURRENT RATING OF 25,000 AMPERES. 6) THE LIGHTING CONTROL PANEL SHALL BE ABLE TO MONITOR A CONTACT CLOSURE EVENT PROVIDED BY THE POWER COMPANY FOR THE DEMAND RESPONSE REQUIREMENT OF CALIFORNIA'S TITLE 24 AND ADJUST THE DIMMING OUTPUT OF THE RELAYS TO 85 PERCENT MAXIMUM OUTPUT AUTOMATICALLY. 7) THE LIGHTING CONTROL PANEL SHALL BE CAPABLE OF INDIVIDUAL CONTROL OF EACH RELAY BASED ON INPUTS FROM THE INTEGRATED TIME CLOCK FUNCTION OR REMOTE LOW VOLTAGE INPUTS SUCH AS OCCUPANCY SENSORS, PHOTO SENSORS & DIGITAL SWITCHES. 8) INTERIOR PHOTO SENSORS SHALL BE PROGRAMMED WITH A 20 MINUTE DELAY. SENSORS SHALL BE CALIBRATED IN THE FIELD BY BOTH THE ELECTRICAL CONTRACTOR & THE SENSOR MANUFACTURER. SENSORS SHALL CONTROL ONLY LIGHT FIXTURES LOCATED IN THE SAME DAY LIGHTING ZONE AS THE SENSOR. SENSORS SHALL BE CALIBRATED TO PROVIDE MINIMUM FOOT CANDLES VALUES AS MEASURED AT 3'-0" AFF IN THE FOLLOWING AREAS: SALES AREA - 90FC OFFICE AREA - 50FC STOCK AREA - 40FC. 9) OCCUPANCY SENSORS SHALL BE PROGRAMMED WITH A 5 MINUTE DELAY. SENSORS SHALL CONTROL LIGHT FIXTURES / DESIGNATED RECEPTACLES THAT ARE LOCATED IN THE SAME ROOM AS THE SENSOR. 10) HANDHELD DISPLAY UNIT HAS A HIGH RESOLUTION COLOR GRAPHIC SCREEN & SHALL CONNECT TO THE LIGHTING CONTROL SYSTEM VIA CAT 6 CABLE. UNIT CAN BE CONNECTED TO LUMACAN PORT LOCATIONS (RELAY CABINET, LOW VOLTAGE PANEL, DIGITAL SWITCHES): UNIT SHALL HAVE RECHARGEABLE BATTERY. 11) DIGITAL SWITCHES SHALL BE CONNECTED TO THE LIGHTING CONTROL PANEL VIA A CAT 6 CABLE & RJ45 CONNECTOR. SWITCHES SHALL COME WITH NUMBER OF BUTTONS AND COLOR AS INDICATED ON PLANS. 12) ALL LOW VOLTAGE WIRING INSTALLED BY THE ELECTRICAL CONTRACTOR SHALL BE PLENUM RATED & APPROVED FOR INTENDED USE BY THE LIGHTING CONTROL SYSTEM MANUFACTURER. CATEGORY 6 WIRING & TERMINATIONS SHALL BE INSTALLED, TESTED & LABELED PER THE LATEST EIA/TIA 568B STANDARDS. 120 OR 277V FROM BRANCH PANEL H N 13) ROOMS SMALLER THAN 100 SQUARE FEET SHALL BE CONTROLLED BY A STANDARD 120 VOLT OCCUPANCY SENSOR. LIGHT FIXTURES SHALL NOT BE DIMMED IN THESE AREAS. SEE FLOOR PLANS FOR DETAILS. 14) THE LIGHTING CONTROL SYSTEM MANUFACTURER SHALL PROVIDE A FULL 3 YEAR WARRANTY FROM THE DATE OF OWNER ACCEPTANCE. THREE SETS OF MAINTENANCE MANUALS SHALL BE PROVIDED TO THE OWNER WITHIN 2 WEEKS OF OWNER ACCEPTANCE. 10/2 COPPER STANDARD NON-DIMMING BALLAST EMERGENCY BALLAST WHEN PRESENT NON-DIMMABLE LIGHT FIXTURE(S), SIGN(S) & RECEPTACLES REVISIONS 10/2 COPPER 10/2 COPPER STANDARD NON-DIMMING BALLAST 0-10V 14/2 COPPER NON-DIMMABLE LIGHT FIXTURE(S), SIGN(S) & RECEPTACLES EMERGENCY BALLAST WHEN PRESENT NON-DIMMABLE LIGHT FIXTURE(S), SIGN(S) & RECEPTACLES STANDARD NON-DIMMING BALLAST DIMMABLE LIGHT FIXTURE(S) 0-10V DIMMING BALLAST EMERGENCY BALLAST WHEN PRESENT EMERGENCY BALLAST WHEN PRESENT EXIT SIGN H N 120 OR 277V FROM BRANCH PANEL H N 120 OR 277V FROM BRANCH PANEL H N 120 OR 277V FROM BRANCH PANEL LEVITON LATCHING RELAY #RELAY 2TB LEVITON LATCHING RELAY #RELAY 1TB LEVITON DIMMING RELAY #RELAY 1DS NO SCALE NO SCALE NO SCALE 9 10 8 7 6 5 4 10/2 COPPER 3 INDIVIDUAL RELAY IN GREENMAX PANEL 2 10/2 COPPER 1 INDIVIDUAL RELAY IN GREENMAX PANEL # 10/2 COPPER DATE TYPE INDIVIDUAL RELAY IN GREENMAX PANEL 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc INDOOR PHOTO SENSOR. LEVITON #ODCOP-OXW OR CEILING MOUNTED OCCUPANCY SENSOR LEVITON #OSC20-MOW. SEE FLOOR PLAN FOR EXACT QUANTITIES PS OCC SENSOR 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. HANDHELD DISPLAY UNIT. PROVIDE 10'-0" CAT 6 PATCH CABLE & STORE IN RELAY CABINET RELAY TYPE CHINO, CA 91710 PC RELAY # 11995 CENTRAL AVE. PHOTOCELL ON WALL. SHIELD FROM ARTIFICIAL LIGHT SOURCES. LEVITON #PCOUT-000 DESCRIPTION HARBOR FREIGHT TOOLS LIGHTING CONTROL PANEL CIRCUIT # LIGHTING CONTROL / DIMMING SYSTEM DATE 07/08/15 JOB NO. 15166 E1.1A SHEET NO. SECURITY SYSTEM NOTES GENERAL ELECTRICAL / COMMUNICATION / SECURITY NOTES HFTS COMMUNICATIONS CONTRACTOR SHALL PROVIDE & INSTALL ALL CABLE, JACKS, PATCH CORDS, SPEAKERS, TELEPHONE EQUIPMENT ETC FOR A COMPLETE LOW VOLTAGE COMMUNICATIONS SYSTEM. (1)HONEYWELL ADEMPCO VISTA - 20P (8) ZONE CONTROL PANEL AND (1) HONEYWELL #4219 ADEMCO VISTA EXPANDER MOUNTED IN THE CASH OFFICE ABOVE CEILING. SECURITY CONTRACTOR TO CLEARLY LABEL SECURITY PANEL. S2 (1)HONEYWELL #6160 KEYPAD MOUNTED OUTSIDE OF THE MANAGERS OFFICE WALL. BOTTOM OF KEYPAD SHALL BE 44" AFF. S3 (1)HONEYWELL WAVE2 2-TONE SOUNDER (SIREN HORN) ON THE MANAGERS OFFICE WALL FACING THE SALES FLOOR MOUNTED AT 12' AFF. 02 THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUIT, BOXES, PULL STRINGS, 120V POWER SLEEVES FOR COMMUNICATIONS WIRING & EQUIPMENT. COORDINATE WITH COMMUNICATIONS CONTRACTOR & SEE SYMBOL LEGEND FOR ADDITIONAL DETAILS. S4 (1)HONEYWELL #FG1625 GLASS BREAK DETECTOR CEILING MOUNTED IN THE MIDDLE OF THE VESTIBULE 5 FEET FROM THE PERIMETER GLASS PANES ENTRANCE/EXIT DOORS. GLASS BREAK DETECTOR SHOULD FACE GLASS PANES. 03 ALL CONDUITS SHALL BE PROVIDED WITH PLASTIC BUSHINGS AT EACH END, PULL STRINGS & BE BONDED TO LOCAL BUILDING STEEL. S5 (1)HONEYWELL #FG1625 GLASS BREAK DETECTOR ALONG THE INTERIOR OF GLASS STOREFRONT 5 FEET FROM GLASS PANES FOR EVERY 25 FEET OF STOREFRONT GLASS. GLASS BREAK DETECTORS SHOULD FACE GLASS PANES. THE COMMUNICATIONS CONTRACTOR SHALL PROVIDE A COMPLETE COMMUNICATIONS SYSTEM LABELING SYSTEM. INCLUDE BUT NOT LIMITED TO: CABLES, JACKS, PATCH PANEL RACKS, ETC. ALL LABELING SHALL COMPLY WITH STANDARDS OF EIA/TIA 606. 07 THE COMMUNICATIONS CONTRACTOR SHALL TEST EACH CABLE AFTER INSTALLATION AND TERMINATION TO CERTIFY THAT EACH CABLE COMPLIES WITH TIA/EIA CATEGORY 6 STANDARDS. PROVIDE DOCUMENTATION PER HFT REQUIREMENTS. 08 SECURITY SYSTEM WIRING SHALL BE HONEYWELL #11045501 PLENUM GENESIS 22/4 STRANDED UNSHIELDED CABLE. 09 EACH SPECIFIED ALARM CONTACT AND EACH SPECIFIED ALARM SENSOR SHOULD BE WIRED IN A CLOCKWISE MANNER TO ITS OWN DESIGNATED ZONE STARTING AT THE MAIN CUSTOMER ENTRANCE / EXIT DOOR CONTACTS. 10 S6 (1)WALL MOUNTED BOSCH #DS860 SERIES TRITECH PIR/MICROWAVE DETECTOR MOUNTED AT 9'-6" AFF FOR 60 LINEAR FOOT OF STOREFRONT GLASS SHOOTING SIDEWAYS ACROSS THE GLASS. NO MOTION DETECTORS IN THE VESTIBULE. S7 &(,/,1*02817('%26&+'63$125$0,&75,7(&+'(7(&725$7 72 $)))256725()5217*/$66,17+((9(17 (S6) CANNOT BE WALL MOUNTED. E1 4'x8'x3/4" PAINTED FIRE RATED PLYWOOD FOR TELEPHONE BACKBOARD. REFER TO DETAIL ON SHEET E2.2 FOR MORE DETAILS. S8 (1)WALL MOUNTED BOSCH #DS860 SERIES TRITECH PIR/MICROWAVE DETECTOR ABOVE VESTIBULE DOOR FRAME FACING SALES FLOOR MOUNTED AT 9'-6" AFF. E2 1-1/2" EMT CONDUIT FROM 9' AFF TO JOIST SPACE HOMERUN CONTINUOUS CONDUIT TO TELEPHONE DEMARK (COORDINATE LOCATION WITH LANDLORD). STUB CONDUIT AT 8' AFF TO TELEPHONE DEMARK. S9 &(,/,1*02817('%26&+'63$1250$,&75,7(&+'(7(&725,17+(&(17(52)7+(&$6+2)),&($:$<)520$1< AIR DEVICES. E3 12"x4"x1/2" COPPER BUS BAR MOUNTED AT 84" AFF U.O.N. ON INSULATORS. PROVIDE BAR WITH (6) EQUALLY SPACED 3/8" DIAMETER HOLES. CONNECT BAR TO HFT'S MAIN PANELS GROUND BAR WITH #4AWG COPPER CONDUCTORS. S10 (1)WALL MOUNTED BOSCH #DS860 SERIES TRITECH PIR/MICROWAVE DETECTOR ABOVE ALL EGRESS DOOR FRAMES (EXCEPT IF EGRESS DOOR IS ADJACENT TO RECEIVING OVERHEAD DOOR) AT 8'-0" AFF. E4 4" DIAMETER EMT CONDUIT RISER FROM JOIST SPACE INTO TOP OF RACK. S11 MAIN CUSTOMER ENTRANCE / EXIT DOORS: FOR NEW DORMA DOORS, WIRE INTO THE DOOR FRAME HEADER TO POINT OF CONNECTION TERMINAL STRIP. FOR EXISTING DOORS TO REMAIN, INSTALL (1) NASCOM N505A/ST ON THE SURFACE (INTERIOR) OF EACH DOOR. E5 2 COMPARTMENT POWER POLE. ELECTRICAL KEY NOTES E6 NOTE NOT USED. E7 20A 120 VOLT DUPLEX RECEPTACLE AT JOIST SPACE FOR SECURITY CAMERA MONITOR. COORDINATE EXACT LOCATION WITH COMMUNICATIONS CONTRACTOR. MOUNT FLUSH IN CEILING WHERE CEILINGS OCCUR, RECEPTACLE SHALL BE WHITE WITH WHITE COVER PLATE. COORDINATE EXACT LOCATION WITH SECURITY VENDOR. PROVIDE 2 GANG BOX WITH 1 1/2" CONDUIT & PULL STRING TO JOIST SPACE. EACH SPECIFIED ALARM CONTACT AND EACH SPECIFIED ALARM SENSOR SHOULD BE SPECIFICALLY LABELED ACCORDING TO ITS DESIGNATED CONTACT OR SENSOR NAME, ITS LOCATION WITHIN THE STORE & PROGRAMMED SEPARATELY TO ITS OWN DESIGNATED ZONE. S12 11 THE CONTRACTOR SHOULD NEVER PROGRAM / INSTALL ANY TYPE OF LOCKOUT CODE INTO THE PANEL OR EXPANDER. S13 (1) HONEYWELL #959 DOOR CONTACT FOR OVERHEAD DOOR. E8 12 COORDINATE CONDUIT AND/OR JUNCTION BOXES AS REQUIRED FOR SECURITY SYSTEM. S14 &(,/,1*02817('%26&+'63$1250$,&75,7(&+'(7(&725,17+(&(17(52)7+(5(&(,9,1*$5($02817('$7 TO 25' AFF. (NO OTHERS NEEDED IN SALES REPLENISHMENT). E9 (3) 1 1/2" CONDUITS & PULL STRINGS FROM TOP OF SECURITY PANEL TO JOIST SPACE. 13 ALL PRODUCTS SPECIFIED ARE FEATURED IN PRODUCT BROCHURES FROM THE MANUFACTURER. E10 1" CONDUIT WITH PULL STRING FROM AMPLIFIER TO JOIST SPACE. E11 2" CONDUIT SLEEVE BETWEEN BACKBOARD & EXISTING TELEPHONE CABINET. (1) NASCOM N200AU/ST DOOR CONTACT FOR EXTERIOR DOORS AND ROOF HATCH (IF APPLICABLE). (2) DOOR CONTACTS REQUIRED AT DOUBLE DOORS. SP C7 C9 CAM C9 CAM C9 CAM NOTE NOT USED. E13 FLUSH SINGLE GANG BOX MOUNTED AT 48" AFF WITH 3/4" EMT CONDUIT STUB TO CEILING JOIST. E14 FLUSH SINGLE GANG BOX AT 114" AFF WITH 3/4" EMT CONDUIT TO JOIST SPACE FOR MOTION SENSOR. E15 3/4" CONDUIT STUBBED INTO DOOR FRAME FOR DOOR CONTACT. E16 PROVIDE 3/4" EMT CONDUIT DROP FROM JOIST & SINGLE GANG BOX MOUNTED AT 12'-0" FOR SALES REPLENISHMENT MOTION SENSOR. E17 PROVIDE 2 GANG BOX AT 4" AFF. WITH 3/4" CONDUIT STUB TO JOIST SPACE FOR OVERHEAD DOOR CONTACT. E18 PROVIDE OCTAGONAL BOX ON BOTTOM OF JOIST. S14 E18 M COMMUNICATIONS KEY NOTES E17 RECEIVING AREA DC E2 C1 S13 C1 25 PAIR CATEGORY (3) 24AWG TWISTED PAIR CABLE. TERMINATE AT TELEPHONE DEMARK AS DIRECTED BY TELEPHONE COMPANY. TERMINATE AT HFT PHONE BOARD ON 66 PUNCH DOWN BLOCK. C2 (3) 4 PAIR CAT 5 24AWG CABLES BETWEEN HFT PHONE BOARD & RACK. TERMINATE ON BOTH ENDS. C3 24"Wx43"Dx80"H FLOOR MOUNTED LOCKABLE RACK PER HFT STANDARDS. C4 (2) 4 PAIR CAT 5 24AWG DATA CABLE BETWEEN REGISTERS & HFT RACK. TERMINATE ON BOTH ENDS. C8 E3 E1 C2 E8 C6 E12 C6 C5 (1) 4 PAIR CAT 5 24AWG CABLE BETWEEN REGISTER & HFT RACK FOR TELEPHONE. TERMINATE ON BOTH ENDS. C6 DAISY CHAIN (1) 24AWG 4 PAIR CAT5 PLENUM RATED CABLE FOR THE SALES AREA SPEAKERS.HOMERUN CABLE FROM CLOSEST SPEAKER TO AMPLIFIER ON PHONE RACK. TERMINATE CABLE AT SPEAKERS & AMPLIFIER. SPEAKERS PER HFT STANDARDS. CABLE SHALL BE BELDEN #2C18-CMP-GY-RFA-BED. C7 DAISY CHAIN (1) 24AWG 4 PAIR CAT5 PLENUM RATED CABLE FOR THE SALES REPLENISHMENT AREA PAGING SPEAKERS.HOMERUN CABLE FROM CLOSEST SPEAKER TO AMPLIFIER ON PHONE RACK. TERMINATE CABLE AT SPEAKERS & AMPLIFIER. SPEAKERS PER HFT STANDARDS. CABLE SHALL BE BELDEN #2C18-CMP-GY-RFA-BED. C8 (1) 4 PAIR CAT 5 24AWG CABLE BETWEEN DOCK DOOR & HFT RACK FOR TELEPHONE. TERMINATE ON BOTH ENDS. C9 SECURITY CAMERA & (1) CAT 5 24AWG 4 PAIR CABLE FROM CAMERA TO RACK, TERMINATE CABLES AT BOTH ENDS. C10 (1) CAT 5 24AWG CABLE FROM TRAFFIC COUNTER TO HFT RACK. TERMINATE AT BOTH ENDS. C11 (1) CAT 5 24AWG CABLE FROM WIRELESS ACCESS POINT TO HFT RACK. TERMINATE AT BOTH ENDS. C12 (1) CAT 5 24AWG 4 PAIR CABLE FROM TIME CLOCK (CENTERED BETWEEN WINDOW & DOOR) TO HFT RACK. TERMINATE AT BOTH ENDS. C13 (2) CAT 5 24AWG 4 PAIR CABLES FROM PRINTER/FAX TO HFT RACK. TERMINATE AT BOTH ENDS. C14 (2) CAT 5 24AWG 4 PAIR CABLES FROM MANAGERS WORK STATION TO HFT RACK. TERMINATE AT BOTH ENDS. C15 (2) CAT 5 24AWG 4 PAIR CABLES FROM MANAGERS WALL TO HFT RACK. TERMINATE AT BOTH ENDS. C16 NOTE NOT USED. C17 (1) RG59 COAXIAL CABLE FROM CCTV MONITOR TO RACK. TERMINATE AT BOTH ENDS. C5 C18 (1) CAT 5 24AWG 4 PAIR CABLE FROM CASH ROOM TO HFT RACK. TERMINATE AT BOTH ENDS. C4 C19 (1) RJ31X PHONE JACK MOUNTED AT +101" AFF FOR SECURITY PANEL. SP SP B.5 E10 20'-0" 52'-0" C5 GB S5 C4 E5 M C4 C9 CAM E14 DC S10 C9 CAM C11 E15 S12 WAP B S12 DC S11 E15 DC E7 CAM GB S5 C9 S11 E15 DC A.8 SALES AREA C17 SALES REPLENISHMENT C10 A.7 E5 C4 C9 CAM COMMUNICATIONS SYMBOL LEGEND SYMBOL 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc 06 D) ALL EXISTING WIRING (POWER & COMMUNICATION) THAT IS TO REMAIN SHALL BE REWORKED OR REPLACED WITH CODE COMPLIANT MATERIAL & SUPPORTS. ANY EXISTING SURFACE MOUNTED CONDUITS SHALL BE REMOVED OR RELOCATED SO THAT THEY ARE IN THE JOIST SPACE OR WITHIN WALL CAVITIES. 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. THE COMMUNICATIONS CONTRACTOR SHALL PROVIDE A COMPLETE DATA COMMUNICATIONS SYSTEM WITH EQUIPMENT, PATCH PANELS, CABLE, JACKS, J HOOKS, BOXES, LABELING, TESTING, ETC. ALL EQUIPMENT SHALL BE SUPPLIED & INSTALLED PER CATEGORY 6 (BICSI AND EIA/TIA) INSTALLATION STANDARDS. C) ALL UNUSEDWIRE (POWER & COMMUNICATION) SHALL BE REMOVED. CHINO, CA 91710 ALL LOW VOLTAGE CABLES SHALL BE PLENUM RATED. 05 B) REMOVE AND/OR RELOCATE EXISTING DEVICES ON WALLS OR CEILING BEING REMOVED. COORDINATE SUCH CONDITIONS WITH ARCHITECTURAL DRAWINGS. 11995 CENTRAL AVE. 04 A) NO ATTEMPT HAS BEEN MADE TO INDICATE ALL EXISTING ELECTRICAL DEVICES, LIGHT FIXTURES, COMMUNICATION DEVICES, WIRING, CONDUIT, ETC. TO BE REMOVED AND/OR RELOCATED. HOWEVER, THE ELECTRICAL CONTRACTOR SHALL FIELD VERIFY THE EXTENT OF DEMOLITION PRIOR TO SUBMITTING BID. HARBOR FREIGHT TOOLS 01 GENERAL ELECTRICAL DEMOLITION NOTES S1 DESCRIPTION GB S5 20'-0" 52'-0" CAM SECURITY CAMERA DC DOOR CONTACT GB GLASS BREAK DETECTOR M &(,/,1*02817(''(7(&725 REVISIONS S6 C7 E14 M SP C6 C6 SP C12 SP E3 WIRELESS ACCESS POINT 9 10 8 7 SPEAKERS & AMPLIFIER 6 SP S9 5 DATA CABLE 4 E4 WAP MEN C9 SPEAKERS 3 S S3 M CA C3 CAM S2 K E13 C9 WALL MOUNTED MOTION DETECTOR POWER POLE BREAK ROOM 2 +44" MANAGER TYPE WOMEN C13 DATE M 1 C9 # CA M SP C14 M CASH ROOM C9 CAM C18 C19 E15 S12 DC C9 CAM E14 S10 M A S1 E9 COMMUNICATIONS PLAN SCALE 1/8" = 1'-0" COMMUNICATIONS PLAN DATE 07/08/15 JOB NO. 15166 E1.2 SHEET NO. N ELECTRICAL SYMBOL LEGEND WIRE LEGEND SYMBOL Fill Tag (2) #12, #12GND-3/4"C Fill 4-4 (4) #4, #4GND-1 1/4 "C 4/0-3 Fill 12-3 (3) #12, #12GND-3/4"C 2-2 (2) #2, #4GND-1"C 4/0-4 (4) #4/0, #2GND-2 1/2"C 12-4 (4) #12, #12GND-3/4"C 2-3 (3) #2, #4GND-1 1/4 "C 300-2 (2) 300KCMIL, #1/0GND-2"C 10-2 (2) #10, #10GND-3/4"C 2-4 (4) #2, #4GND-1 1/4" C 300-3 (3) 300KCMIL, #1/0GND-21/2" C 10-3 (3) #10, #10GND-3/4"C 1-2 (2) #1, #4GND-1 1/4" C 300-4 (4) 300KCMIL, #1/0GND-2 1/2"C 10-4 (4) #10, #10GND-3/4"C 1-3 (3) #1, #4GND-1 1/4" C 350-2 (2) 350KCMIL, #3/0GND-2"C 8-2 (2) #8, #8GND-3/4"C 1-4 (4) #1, #4GND-1 1/2" C 350-3 (3) 350KCMIL, #3/0GND-2 1/2"C 8-3 (3) #8, #8GND-1"C 1/0-2 (2) #1/0, #2GND-1 1/4" C 350-4 (4) 350KCMIL, #3/0GND-3"C 8-4 (4) #8, #8GND-1"C 1/0-3 (3) #1/0, #2GND-1 1/2" C 500-2 (2) 500KCMIL, #3/0GND-2 1/2"C 6-2 (2)#6, #6GND-1"c 1/0-4 (4) #1/0, #2GND-1 1/2" C 500-3 (3) 500KCMIL, #3/0GND-3"C 6-3 (3) #6, #6GND-1"C 3/0-2 (2) #3/0, #2GND-1 1/2" C 500-4 (4) 500KCMIL, #3/0GND-3 1/2" C 6-4 (4) #6, #6GND-1"C 3/0-3 (3) #3/0, #2GND-2" C 600-2 (2) 600KCMIL, #3/0GND-3"C 4-2 (2) #4, #4GND-1"C 3/0-4 (4) #3/0, #2GND-2" C 600-3 (3) 600KCMIL, #3/0GND-3 1/2" C DOUBLE DUPLEX RECEPTACLE - 20 AMPERE, 125 VOLT - MOUNTED AT 15" AFF UON (TO BOTTOM) 4-3 (3) #4, #4GND-1"C 4/0-2 (2) #4/0, #2GND-2" C 600-4 (4) 600KCMIL, #3/0GND-3 1/2" C DUPLEX RECEPTACLE MOUNTED IN A FLUSH FLOOR BOX. PROVIDE ALUMINIUM DUAL FLIP LID ACTIVATION KIT. HOMERUN TO PANEL "A" INDICATING CIRCUIT NUMBER(S) - ALL WIRING SHALL BE #12 WITH EQUIPMENT GROUND WIRE UON (INCREASE TO #10 FOR CIRCUITS OVER 100 FT.) - ALL HOMERUNS ARE TO A 20 AMPERE, 1 POLE CIRCUIT BREAKER U.O.N. QUANITY OF CONDUCTORS AS NECESSARY TO ACCOMMODATE CIRCUITS AND CONTROL INDICATED. CROSS HATCHES INDICATE REQUIRED LIGHTING CONTROL U.O.N. (3) #4/0, #2GND-2" C A-2 A-2 CONDUIT RUN IN OR UNDER FLOOR SLAB (1" C. MINIMUM, UON) SCHEDULE 40 PVC CONDUIT RUN AT 36" BELOW FINISHED GRADE. CONTRACTOR SHALL BORE BELOW STREET. COORDINATE WITH CITY. TRANSITION TO HEAVYWALL RIGID STEEL CONDUIT 2 FEET BELOW GRADE WHEN CONDUIT IS TO RISE ABOVE GRADE. 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc Tag DESCRIPTION Tag No Tag SWITCH - 20 AMPERE, 120/277 VOLT, SINGLE POLE - MTD AT 48" AFF UON ("a"=DENOTES SWITCHING,"K" = KEY OPERATED, "P" = PILOT LIGHT, "IL"= ILLUMINATED TOGGLE, "3" = THREE-WAY, "4" = FOUR-WAY, "M"= MANUAL MOTOR STARTER. "D"= DIMMER SWITCH "LUTRON NOVA SERIES") S DUPLEX RECEPTACLE - 20 AMPERE, 125 VOLT - MOUNTED AT 15" AFF UON (TO BOTTOM). SUBSCRIPT "T" DENOTES TAMPER RESISTANT. C=WHITE RECEPTACLE & COVER MOUNTED FLUSH IN CEILING. IF CEILING IS MORE THEN 15" ABOVE TOP OF WINDOW MOUNT RECEPTACLES 12" ABOVE TOP OF WINDOW. IG= ISOLATED GROUND TYPE. TVSS= SURGE PROTECTED TYPE. NOTE: CONDUIT SIZES ARE FOR EMT & IMC. FOR PVC & RGC INCREASE CONDUIT BY (1) TRADE SIZE. FOR FLEXIBLE CONDUIT SIZES REFER TO NEC. ALL WIRE SIZES SHOWN ON DRAWINGS ARE FOR COPPER CONDUCTORS JUNCTION BOX - MOUNTING HEIGHT AND SIZE AS REQUIRED BY CODE OR AS NOTED ON DRAWINGS J J JUNCTION BOX - FOR SIGN. PROVIDE LOCAL DISCONNECT & COORDINATE LOCATION & MOUNTING HEIGHT WITH SIGN CONTRACTOR IN THE FIELD. S HEAVY DUTY NON FUSIBLE DISCONNECT SWITCH. SPECIAL NEMA CONFIGURED OUTLET MOUNTED AS REQUIRED TO SERVE APPLIANCE. VERIFY CONFIGURATION PRIOR TO ROUGH-IN AND ADJUST WIRING AND CIRCUIT BREAKER SIZE AS REQUIRED. GROUND ROD- 3/4" X 10' COPPER CLAD GR WIRE LEGEND TAG (12= CONDUCTOR SIZE, 4= QUANTITY OF CONDUCTORS.) 12-4 DUCT MOUNTED SMOKE DETECTOR. SEE DETAIL THIS SHEET. DD AFF ABOVE FINISHED FLOOR AC INDICATES DEVICE MOUNTED AT 8" ABOVE COUNTER EC ELECTRICAL CONTRACTOR GFI GROUND FAULT CIRCUIT INTERRUPTER TYPE UON UNLESS OTHERWISE NOTED IG ISOLATED GROUND EX EXISTING TO REMAIN Soc a,b WALL MOUNTED MULTI TECHNOLOGY DUAL CIRCUIT OCCUPANCY SENSOR WITH WHITE FINISH HUBBEL # LHMTD2W Soc a WALL MOUNTED MULTI TECHNOLOGY SINGLE CIRCUIT OCCUPANCY SENSOR WITH WHITE FINISH HUBBEL # LHMTSW OC CEILING MOUNTED OCCUPANCY SENSOR HUBBELL #OMNIDT1000 20A 120 VOLT RECEPTACLE MOUNTED AT 15" AFF U.O.N. CONTROLLED BY LOCAL OCCUPANCY SENSOR. PROVIDE COVERPLATE WITH BLACK SCREENED LETTERS "SWITCHED". R CONTRACTOR SHALL COORDINATE ALL LOCAL REQUIREMENTS WITH REGARDS TO CONNECTING THE ELECTRICAL SERVICE. METER, CT BOXES, DISCONNECT SWITCHES ETC. SHALL BE PURCHASED & INSTALLED PER THE LOCAL POWER COMPANY REQUIREMENTS & AUTHORITY HAVING JURISDICTION. COORDINATION SHALL OCCUR WITHIN 1 WEEK OF RECEIVING CONTRACT. INCLUDE IN BID ANY EXPEDITED SHIPPING CHARGES FOR ANY LONG LEAD ELECTRICAL DISTRIBUTION EQUIPMENT. COORDINATE ANY REQUIRED SERVICE SHUT DOWNS WITH LANDLORD. 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. COMMUNICATION OUTLET MOUNTED IN A FLUSH FLOOR BOX. PROVIDE (4) JACKS AND AN ALUMINIUM DUAL FLIP LID ACTIVATION KIT. D CHINO, CA 91710 FLUSH COMMUNICATIONS OUTLET WITH TWO GANG BOX SINGLE GANG EXTENSION RING, MOUNTED AT 15" AFF U.O.H. (TO BOTTOM) AND 1" CONDUIT, STUBBED TO NEAREST ACCESSIBLE CEILING. PROVIDE BLANK COVER. W=MOUNTED 54" AFF. 11995 CENTRAL AVE. A.F. HARBOR FREIGHT TOOLS HEAVY DUTY FUSIBLE DISCONNECT SWITCH. FUSE SIZE TO BE DETERMINED FROM EQUIPMENT TO BE SERVED NAMEPLATE DATA 15 2 SETS 350-4 1/0-4 EXISTING 120/208V 3PH 4WSN 600A MAIN SERVICE DISCONNECT SWITCH WITH INTEGRAL METER BASE 1/0-4 M M REVISIONS W/#2 ISO GND L P 600A TYPE 150/3 150/3 9 10 8 7 6 5 4 3 2 1 ISO GND BUS # DATE 600A EXISTING 600 AMP SERVICE CONDUCTORS EXISTING GROUNDING ELECTRODE SYSTEM ONE LINE DIAGRAM & DETAILS DATE 07/08/15 JOB NO. 15166 120/208V 3PH 4WSN ONE LINE DIAGRAM N.T.S. E2.0 SHEET NO. L LIGHT FIXTURE SCHEDULE SECURITY LIGHTING# R243BLW-E100-DIM PHILIPS F32T8-ADV841 (3) LAMPS BD 2X4 (2) LAMP T8 FLUORESCENT TROFFER FOR INSTALLATION IN LAY-IN ACOUSTIC CEILING TILE GRID SECURITY LIGHTING# R242BLW-DIM PHILIPS F32T8-ADV841 (2) LAMPS CKT. 1.3 SALES LIGHTING 2 C C 20/1 1.3 SALES LIGHTING 4 C C 20/1 1.2 SALES LIGHTING 6 C C 20/1 1.3 SALES LIGHTING 8 C 20/1 1.1 SALES LIGHTING 10 C 20/1 1.0 REPLENISHMENT LIGHTING 12 C 20/1 0.5 BREAK ROOM, OFFICE LIGHTING 14 C,L 20/1 0.7 EMERGENCY LIGHTING 16 C 20/1 1.0 EXTERIOR LIGHTING 18 C C 20/1 1.2 INTERIOR SIGN 20 C - 20/1 - SPARE 22 MANAGERS OFFICE RECEPTACLES 24 EXTERIOR SIGN 26 3 SALES LIGHTING 1.3 20/1 5 SALES LIGHTING 1.3 20/1 7 SALES LIGHTING 1.3 20/1 9 SALES LIGHTING 1.3 20/1 C 11 SALES REPLENISHMENT LIGHTING 0.9 20/1 C 13 CORRIDOR LIGHTING 0.4 20/1 C 15 TOILET ROOM LIGHTING 0.2 20/1 - 17 EXTERIOR LIGHTING 0.8 20/1 C 0 20/1 MISC. HVAC REC. DESCRIPTION LTG. CKT SECURITY LIGHTING# TC232B-120-CSHC-CS8-COUPLER-L-E96-DIM 114 SECURITY LIGHTING# C232B-120-CSHC-CS8-COUPLER-L-DIM PHILIPS F32T8-ADV841 (2) LAMPS 120/277 58 SALES & STORAGE AREA FOR OPEN CEILINGS PROVIDE CHAIN & INSTALL AT 12'-0"(CSHC). RUN IN CONTINUOUS ROWS WHERE SHOWN. PROVIDED WITH COUPLER. NOTE #3 PHILIPS F32T8-ADV841 (2) LAMPS SPARE 58 SALES & STORAGE AREA FOR OPEN CEILINGS PROVIDE CHAIN & INSTALL AT 12'-0"(CSHC). RUN IN CONTINUOUS ROWS WHERE SHOWN. EMERGENCY BALLAST. SEE GENERAL NOTE #1,2,3. PROVIDED WITH COUPLER. 19 120/277 21 SPARE 1.2 20/1 SALES & STORAGE AREA SURFACE MOUNTED. FOR CEILING MOUNT PROVIDE CEILING CLIPS & SUPPORT FROM STRUCTURE AS REQUIRED BY CODE. FOR JOIST MOUNT, PROVIDE MOUNTING HARDWARE & UNISTRUT AS REQUIRED. RUN IN CONTINOUS ROWS WHERE SHOWN. PROVIDED WITH COUPLER SALES & STORAGE AREA SURFACE MOUNTED. FOR CEILING MOUNT PROVIDE CEILING CLIPS & SUPPORT FROM STRUCTURE AS REQUIRED BY CODE. FOR JOIST MOUNT, PROVIDE MOUNTING HARDWARE & UNISTRUT AS REQUIRED. RUN IN CONTINOUS ROWS WHERE SHOWN. EMERGENCY BALLAST. SEE GENERAL NOTE #1,2. PROVIDED WITH COUPLER SALES & STORAGE AREA SURFACE MOUNTED. FOR CEILING MOUNT PROVIDE CEILING CLIPS & SUPPORT FROM STRUCTURE AS REQUIRED BY CODE. FOR JOIST MOUNT, PROVIDE MOUNTING HARDWARE & UNISTRUT AS REQUIRED. RUN IN CONTINOUS ROWS WHERE SHOWN. PROVIDED WITH COUPLER SALES & STORAGE AREA SURFACE MOUNTED. FOR CEILING MOUNT PROVIDE CEILING CLIPS & SUPPORT FROM STRUCTURE AS REQUIRED BY CODE. FOR JOIST MOUNT, PROVIDE MOUNTING HARDWARE & UNISTRUT AS REQUIRED. RUN IN CONTINOUS ROWS WHERE SHOWN. EMERGENCY BALLAST. SEE GENERAL NOTE #1,2. PROVIDED WITH COUPLER 23 CASH ROOM RECEPTACLES 1.0 20/1 C C 20/1 25 BREAK ROOM RECEPTACLES 1.0 20/1 C C 20/1 1.2 27 SPARE - 20/1 - - 20/1 - SPARE 28 29 SPARE - 20/1 - - 20/1 - SPARE 30 31 SPARE - 20/1 - - 20/1 - SPARE 32 33 SPARE - 20/1 - - 20/1 - SPARE 34 35 SPARE - 20/1 - - 20/1 - SPARE 36 37 SPARE - 20/1 - - 20/1 - SPARE 38 - C 20/1 0.2 - CEILING RECEPTACLES 40 - - 20/1 0.2 - CEILING RECEPTACLES 42 1.4 11.8 120/277 PHILIPS F32T8-ADV841 (4) LAMPS D1DE SECURITY LIGHTING# C232B-120-CS8-COUPLER-L-E96-DIM PHILIPS F32T8-ADV841 (2) LAMPS 114 120/277 114 120/277 120/277 58 120/277 58 SECURITY LIGHTING# R242BLW-E100 PHILIPS F32T8-ADV841 (2) LAMPS 120/277 EM1 SELF-POWERED EXIT SIGN WITH LED LAMPS UNIVERSAL MOUNTED - SINGLE FACE NOTE #4 SECURITY LIGHTING# PRB INCLUDED 120/277 7 SALES & STORAGE AREA EM2 SELF-POWERED EXIT SIGN WITH LED LAMPS UNIVERSAL MOUNTED - DOUBLE FACE NOTE #4 SECURITY LIGHTING# PRB INCLUDED 120/277 7 SALES & STORAGE AREA EM3 SURFACE MOUNTED 2 HEAD EMERGENCY UNIT WITH REMOTE CAPACITY DUAL LITE# LZ30 INCLUDED 120/277 15 SALES & STORAGE AREA EM4 EXTERIOR WP 2 LAMP REMOTE HEADS SECURITY LIGHTING# 2A6H6A-MPWP2 INCLUDED 6 - EXTERIOR EM5 EXTERIOR WP LED EMERGENCY FIXTURE COOPER LIGHTING# AEL2-31-BZ INCLUDED 120/277 15 EXTERIOR SA EXTERIOR WALL MOUNTED FIXTURE COOPER LIGHTING# XTOR2A LED 120/277 20 EXTERIOR WALL MOUNTED FIXTURE AT 15'-0" ABOVE FINISHED GRADE NOTE #5 TOILET ROOM EMERGENCY BALLAST. SEE GENERAL NOTE #1,2. VERIFY THAT EM BALLAST IS WIRED FOR APPROPRIATE VOLTAGE PRIOR TO WIRING FIXTURE. FACTORY INSTALLED WHIP CONNECTION. 58 41 REMOTE CAPACITY MOUNT EXIT SIGNS A MAXIMUM OF 1'-0" ABOVE TOP OF EGRESS DOOR. PROVIDE PENDANT IF REQUIRED. IN SALES AREA MOUNT EXIT SIGNS 6" BELOW TYPE 'C' FIXTURES. IN SALES REPLENISHMENT AREA MOUNT EXIT SIGNS 12" BELOW TYPE D FIXTURES. BUS RATING: 600A A.I.C.: 65,000 600A MAIN LUGS ONLY C/B MISC. 11.7 1 11.7 RTU-1 125/3 REMARKS AMPS CONN.: 443.3 AMPS DEMAND.: 468.1 - - - - C/B BREAKER REMARKS C-CONTACTOR CONTROLLED, S-SHUNT TRIP, L-LOCK ON, G-GFCI, A-ARC FAULT, SW-SWITCHING DUTY, HA-HACR, HI-HID KVA CONNECTED MISC. HVAC REC. DESCRIPTION LTG. 8.7 100/3 CKT 2 8.7 RTU-2 4 11.7 - - 8.7 6 7 11.7 - - 3.6 8 - - - - - - - - - - - - - - - - - - - - - - 125/3 11.7 11.7 11 13 21.2 PANEL 'L' 4.6 4.0 150/3 17 - 19 - SPARE 125/3 - 23 25 125/3 SPACE 29 TOTALS 21.2 LOAD 4.6 CONNECTED 70.2 4.0 40/3 3.6 RTU-4 10 3.6 12 14 150/3 CONNECTED DEMAND LIGHTING 21.2 26.5 RECEPTACLE 4.6 4.6 HVAC 0.0 0.0 MISC 4.0 4.0 MOUNTING: SURFACE LOCATION: BUS RATING: 200A A.I.C.: 65,000 CKT. 5 RTU-3 LOAD TOTALS AMPS CONN.: 63.1 AMPS DEMAND.: 55.3 BREAKER REMARKS C-CONTACTOR CONTROLLED, S-SHUNT TRIP, L-LOCK ON, G-GFCI, A-ARC FAULT, SW-SWITCHING DUTY, HA-HACR, HI-HID 6.5 0.4 15.8 PANEL 'P' 16 18 60/3 - 20 SPARE 22 - LTG. REC. HVAC C/B MISC. REMARKS C/B KVA CONNECTED MISC. HVAC REC. DESCRIPTION LTG. CKT ISO GND RECEPTACLE 0.4 20/1 - - 20/1 0.4 ISO GND RECEPTACLE 2 3 GENERAL RECEPTACLE 0.8 20/1 - - 20/1 0.8 GENERAL RECEPTACLE 4 5 CASHWRAP RECEPTACLE (D) (ISO GND.) 0.8 20/1 - - 20/1 0.8 CASHWRAP RECEPTACLE 6 7 CASHWRAP RECEPTACLE (D) (ISO GND.) 0.8 20/1 - - 20/1 0.4 SALES OUTLET 8 9 CASHWRAP RECEPTACLE (D) (ISO GND.) 0.8 20/1 - - 20/1 11 CASHWRAP RECEPTACLE (D) (ISO GND.) 0.8 20/1 - - 20/1 13 SPARE 20/1 - - 20/1 15 HAND DRYER 1.2 20/1 - - 20/1 0.6 17 HAND DRYER 1.2 20/1 - - 20/1 0.4 ISO GND RECEPTACLE 18 19 ISO GND RECEPTACLE 20/1 - - 20/1 0.4 ISO GND RECEPTACLE 20 21 REFRIGERATOR 20/1 - - 30/1 SPARE 22 23 BREAKROOM RECEPTACLE 0.4 20/1 - - 20/1 0.8 BREAKROOM RECEPTACLE 24 25 SECURITY ISO GND RECEPTACLE 0.4 20/1 - - 20/1 0.4 TELEPHONE ISO GND RECEPTACLE 26 27 SECURITY ISO GND RECEPTACLE 0.4 20/1 - - 20/1 0.8 TOILET ROOM RECEPTACLE 28 29 MUSIC RECEPTACLE 0.8 20/1 - - 20/1 0.2 TIME CLOCK 30 31 DOOR BELL 20/1 - L 20/1 FACP 32 33 ROOF RECEPTACLE 20/1 - - 20/1 STOCK RECEPTACLE 34 35 SPARE - 20/1 - - 20/1 1.5 WATER HEATER 36 37 SPARE - 20/1 - L 20/1 0.1 DUCT DETECTOR 38 39 SALES RECEPTACLE 20/1 - - 20/1 - SPARE 40 41 RESTROOM EXHAUST FAN 20/1 C - 20/1 - SPARE 42 0.00 TOTALS - 0.4 0.8 0.2 1.0 0.8 0.4 0.00 TOTALS 8.6 0.4 3.4 0.8 1.0 - - 0.5 0.4 3.1 LOAD CONNECTED DEMAND LIGHTING - - RECEPTACLE 15.8 12.9 HVAC 0.4 0.5 MISC 6.5 6.5 0.00 7.2 CASHWRAP RECEPTACLE 10 POWER DOORS 12 SPARE 14 ISO GND RECEPTACLE 16 REVISIONS 24 26 60/3 KVA CONNECTED DESCRIPTION 1 SPARE 28 30 6.5 37.3 15.8 0.00 TOTALS DEMAND LIGHTING 21.2 26.5 RECEPTACLE 20.4 15.2 HVAC 107.5 116.3 MISC 10.5 10.5 9 HVAC 0.00 LIGHTING & PANEL SCHEDULES DATE 07/08/15 JOB NO. 15166 E2.1 SHEET NO. 10 REC. 4.0 8 LTG. 0.00 COMMENTS: PROVIDE ISO GND BUS COMMENTS: DESCRIPTION 3.2 VOLTAGE: 120/208V-3PH-4W REFER TO SHEET A0.0 FOR LIGHTING VENDOR CONTACT INFORMATION. VOLTAGE: 120/208V-3PH-4W KVA CONNECTED 8.4 200A MAIN LUG ONLY M LOCATION: 2.0 P FIXTURES SHALL BE SUPPLIED WITH A 0-10V DIMMING BALLAST FOR 5-100 PERCENT DIMMING CAPABILITY AND RAPID START SOCKETS BALLASTS SHALL BE ADVANCE MARK 7 SERIES. MOUNTING: SURFACE 25/2 PROVIDE WITH 2 HEAD MOUNTING PLATE. WIRE TO EM3. MANUFACTURER SHALL WIRE EMERGENCY BALLAST TO OPERATE 2 LAMPS. THE LAMPS SHALL BE RIGHT NEXT TO EACH OTHER SO ONLY 4' OF 8' FIXTURE IS ILLUMINATED BY THE EMERGENCY BALLAST. 4. CHARGER EMERGENCY LIGHTS EQUIPPED WITH 90 MINUTE BATTERY BACK-UP. WIRE AHEAD OF LOCAL CONTROL FOR EMERGENCY FIXTURES ADE, A1DE, BDE, CDE, C1DE, DDE & D1DE NOT SHOWN AS NIGHT LIGHTS, RUN AN EXTRA HOT CONDUCTOR (BYPASSING ALL CONTROL) AND CONNECT TO EMERGENCY BALLAST. FIXTURES SHALL BE SHUT OFF WITH LOCAL LIGHT FIXTURE CONTROL. FOR ALL CHAIN MOUNTED FIXTURES E.C. SHALL PROVIDE EXTENSIONS AS REQUIRED TO INSTALL LIGHT FIXTURES AT HEIGHTS AS NOTED. 2.0 TOTALS LIGHTING FIXTURE SCHEDULE NOTES (SEE REMARKS) 3. 39 1.0 6 SECURITY LIGHTING# TC232B-120-CS8-COUPLER-L-DIM 4' - 2 LAMP T8 SURFACE MOUNTED STRIP FLUORESCENT FIXTURE WITH 1100 LUMEN BATTERY BALLAST 27 20/1 SALES & STORAGE AREA FOR OPEN CEILINGS PROVIDE CHAIN & INSTALL AT 12'-0"(CSHC). RUN IN CONTINUOUS ROWS WHERE SHOWN. EMERGENCY BALLAST. SEE GENERAL NOTE #1,2,3. PROVIDED WITH COUPLER. D1D 21 C PHILIPS F32T8-ADV841 (4) LAMPS PHILIPS F32T8-ADV841 (2) LAMPS 15 C/B C SALES & STORAGE AREA FOR OPEN CEILINGS PROVIDE CHAIN & INSTALL AT 12'-0"(CSHC). RUN IN CONTINUOUS ROWS WHERE SHOWN. PROVIDED WITH COUPLER. NOTE #3 SECURITY LIGHTING# C232B-120-CS8-COUPLER-L-DIM 9 KVA CONNECTED REMARKS 20/1 114 4' - 2 LAMP T8 SURFACE MOUNTED STRIP FLUORESCENT FIXTURE 3 C/B MISC. 120/277 DDE CKT. HVAC PHILIPS F32T8-ADV841 (4) LAMPS PHILIPS F32T8-ADV841 (4) LAMPS 5. REC. 0.9 SECURITY LIGHTING# TC232B-120-CSHC-CS8-COUPLER-L-DIM SECURITY LIGHTING# TC232B-120-CS8-COUPLER-L-E96-DIM 2. LTG. SALES LIGHTING 114 8' - 4 LAMP T8 SURFACE MOUNTED STRIP FLUORESCENT FIXTURE WITH 1100 LUMEN BATTERY BALLAST 1. KVA CONNECTED DESCRIPTION 1 120/277 4' - 2 LAMP T8 CHAIN MOUNTED STRIP FLUORESCENT SECURITY LIGHTING# C232B-120-CSHC-CS8-COUPLER-L-E96-DIM FIXTURE WITH 1100 LUMEN BATTERY BALLAST BE COMMENTS: SECURITY LIGHTING# R242BLW-E100-DIM C1DE 2X4 (2) LAMP T8 FLUORESCENT TROFFER WITH 400 LUMEN BATTERY BALLAST FOR INSTALLATION IN LAY-IN ACOUSTIC CEILING TILE GRID TOILET ROOM FACTORY INSTALLED WHIP CONNECTION VOLTAGE: 120/208V-3PH-4W TOILET ROOM EMERGENCY BALLAST. SEE GENERAL NOTE #1,2. VERIFY THAT EM BALLAST IS WIRED FOR APPROPRIATE VOLTAGE PRIOR TO WIRING FIXTURE. FACTORY INSTALLED WHIP CONNECTION. 4' - 2 LAMP T8 CHAIN MOUNTED STRIP FLUORESCENT FIXTURE 8' - 4 LAMP T8 SURFACE MOUNTED STRIP FLUORESCENT FIXTURE 58 BREAKER REMARKS C-CONTACTOR CONTROLLED, S-SHUNT TRIP, L-LOCK ON, G-GFCI, A-ARC FAULT, SW-SWITCHING DUTY, HA-HACR, HI-HID PHILIPS F32T8-ADV841 (2) LAMPS C1D DD 120/277 97.4 7 8' - 4 LAMP T8 CHAIN MOUNTED STRIP FLUORESCENT FIXTURE WITH 1100 LUMEN BATTERY BALLAST CDE 88 82.7 5 8' - 4 LAMP T8 CHAIN MOUNTED STRIP FLUORESCENT FIXTURE 120/277 OFFICES EMERGENCY BALLAST. SEE GENERAL NOTE #1,2. VERIFY THAT EM BALLAST IS WIRED FOR APPROPRIATE VOLTAGE PRIOR TO WIRING FIXTURE. FACTORY INSTALLED WHIP CONNECTION. 120/277 AMPS CONN.: AMPS DEMAND.: 4 CD 88 OFFICES FACTORY INSTALLED WHIP CONNECTION. 3 BDE 2X4 (2) LAMP T8 FLUORESCENT TROFFER WITH 400 LUMEN BATTERY BALLAST FOR INSTALLATION IN LAY-IN ACOUSTIC CEILING TILE GRID A.I.C.: 65,000 200A MAIN LUG ONLY 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc ADE 2X4 (3) LAMP T8 FLUORESCENT TROFFER WITH 400 LUMEN BATTERY BALLAST FOR INSTALLATION IN LAY-IN ACOUSTIC CEILING TILE GRID LOCATION: BUS RATING: 200A 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. PHILIPS F32T8-ADV841 (3) LAMPS MOUNTING: SURFACE CHINO, CA 91710 SECURITY LIGHTING# R243BLW-DIM REMARKS 11995 CENTRAL AVE. AD 2X4 (3) LAMP T8 FLUORESCENT TROFFER FOR INSTALLATION IN LAY-IN ACOUSTIC CEILING TILE GRID WATTS HARBOR FREIGHT TOOLS VOLT TYPE LAMPS DATE MANUFACTURER 2 DESCRIPTION 1 SYMBOL # TYPE 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc 8'-0" DATA RACK COPPER GROUND BAR CONDUIT STUBBED INTO JOIST SPACE, TYP. NOTE: FIRE ALARM VENDOR SHALL CLEARLY LABEL THE FIRE ALARM CONTROL PANEL IN FIELD. APPROVED PANELS: FIRE-LITE MODEL #'S MS5, MS10, MS9050, AND MS9200 SILENT KNIGHT MODEL #'S SK5600, SK5700, SK5808, SK5820, SK5208, AND SK-4. TIME CLOCK J-BOX FOR DATA CONNECTIONS AS REQUIRED J-BOX 24V DC POWER SUPPLY QUAD RECEPTACLE 1'-0" 1'-3" REVISIONS TYPE 9 PHONE BOARD DETAIL G.C. TO USE FULL SCALE TEMPLATE FOR TELCO BOARD EQUIPMENT LOCATIONS. G.C. TO CONTACT SE BLUEPRINT AT (216)241-2250 TO ORDER FULL SCALE PHONE BOARD TEMPLATE FOR DELIVERY TO SITE. DATE 07/08/15 JOB NO. 15166 E2.2 SHEET NO. 10 8 7 6 5 DATE 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc FULL SCALE TELEPHONE BOARD TEMPLATE # ARCHITECTS, INC. SHELF MOUNTED TO PHONE BOARD FOR MUSIC AMPLIFIER 2'-0" BINDER 4 ;/21*39&78%( FOR PLAN STORAGE W/ REMOVABLE CAP - CLEARLY LABEL "PLANS" ON TUBE 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. FIRE ALARM CONTROL PANEL (AS REQUIRED) 3 2"x2" WOOD BLOCKING CLIPED TO TELPHONE BOARD WITH 1/2" PLYWOOD COVER SCREWED TO BLOCKING TO HOLD (3) RING PAPER WORK BINDER 66 PUNCH DOWN BLOCK VALCOM 3-ZONE PAGE CONTROL 1 MAIN DMARK - AS REQUIRED DMARK MAY NOT BE LOCATED IN HFT SPACE AVAYA IP500 PHONE SYSTEM 2 66 PUNCH DOWN BLOCK P L A N S 48" MIN. TO FINISH FLOOR OVERRIDE SWITCH CHINO, CA 91710 SURGE PROTECTOR 11995 CENTRAL AVE. 4'-0" TELEPHONE JACKS HARBOR FREIGHT TOOLS MODULAR JACK SHEET NO. DATE 07/08/15 JOB NO. 15166 E3.0 TITLE 24 COMPLIANCE FORMS 10 9 8 7 6 5 4 3 2 1 # DATE TYPE REVISIONS CHINO, CA 91710 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. 11995 CENTRAL AVE. HARBOR FREIGHT TOOLS 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc SHEET NO. DATE 07/08/15 JOB NO. 15166 E3.1 TITLE 24 COMPLIANCE FORMS 10 9 8 7 6 5 4 3 2 1 # DATE TYPE REVISIONS CHINO, CA 91710 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. 11995 CENTRAL AVE. HARBOR FREIGHT TOOLS 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc SHEET NO. DATE 07/08/15 JOB NO. 15166 E3.2 TITLE 24 COMPLIANCE FORMS 10 9 8 7 6 5 4 3 2 1 # DATE TYPE REVISIONS CHINO, CA 91710 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. 11995 CENTRAL AVE. HARBOR FREIGHT TOOLS 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc SHEET NO. DATE 07/08/15 JOB NO. 15166 E3.3 TITLE 24 COMPLIANCE FORMS 10 9 8 7 6 5 4 3 2 1 # DATE TYPE REVISIONS CHINO, CA 91710 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. 11995 CENTRAL AVE. HARBOR FREIGHT TOOLS 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc SHEET NO. DATE 07/08/15 JOB NO. 15166 E3.4 TITLE 24 COMPLIANCE FORMS 10 9 8 7 6 5 4 3 2 1 # DATE TYPE REVISIONS CHINO, CA 91710 7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose. 11995 CENTRAL AVE. HARBOR FREIGHT TOOLS 17710 Detroit Avenue Lakewood, Ohio 44107 Phone (216) 521-5134 Fax (216) 521-4824 www.adaarchitects.cc
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement