ELECTRICAL SPECIFICATIONS
D: RACEWAYS
1. EMT conduit shall be used in all locations which call for conduit unless noted therwise. Conduits routed thru areas
of significant temperature differences shall be provided with seal-off fittings to minimize condensation. Conduits
penetrating fire walls shall be firestopped per NEC & details shown on drawings.
2. Rigid PVC Schedule 40 shall be used for all underground or below slab conduit runs.
3. Heavy wall rigid steel onduit shall be used in all exposed interior applications below structural ceiling and exterior
exposed applications. provide 2 coats of rust inhibiting paint for exterior runs. Paint shall match surface conduit is
attached to.
4. 'MC' cable may be used for all branch circuits as allowed by the National Electrical Code & the authority having
jurisdiction. Cable shall be installed in a neat professional manner adhering to industry standards.
5. When power or control conductors are installed in a raceway, a green equipment grounding conductor shall be
included in each raceway system and shall be sized as shown on the drawings or if not noted on the drawings, then
in accordance with Table 250-95 of the NEC, or as indicated on the drawings If green insulation is not available, the
grounding conductor shall be bare and clearly and permanently marked at all tap and terminating points by green
"scotch" marking tape, code markers, or other approved means.
2. Compression type lugs and connectors shall be used for all terminations and splices. All terminations shall
be permanently identified and numbered, using "Brady" labels or other approved equal. Wire numbering
shall be panelboard and circuit numbers. Also, all wiring which passes through junction or pull boxes shall
be identified with appropriate numbers. When panelboard/circuit numbers are not appropriate for
identification, the contractor shall assign a unique number and record this number on the construction set.
H: WIRING DEVICES
1. Provide wiring devices which are UL listed and which comply with NEMA WD 1 and other applicable UL
and NEMA standards. Device Color shall be white unless otherwise noted. Coverplate color
shall match device color. Confirm color selection with architect before purchasing and installing.
2. Receptacles: Devices shall be specification grade, NEMA 5-20R configuration. Duplex type, Hubbell Cat
No. CR5362, single outlet type, Hubbell Cat No. CR5361, GFCI duplex, Hubbell Cat No. CR GF5362. Catalog
numbers for Hubbell are shown for reference purposes and equivalent receptacles by other manufacturers as
noted above are also approved. Receptacles shall comply with UL 498 and NEMA WD 1. Special
receptacles not shown below shall be specification grade with Nema configuration as noted on the drawings.
3. Ground-fault interrupter (GFI or GFCI) receptacles as indicated above shall be designed for and installed in
a 2-3/4 inch deep outlet box without adapter, grounding type, Class A, Group 1, per UL Standard 94.3.
4. Snap switches: Devices shall be specification grade quiet type, 20 A 120/277V, single pole Hubbell Cat
No. CS1221, two pole Hubbell Cat No. CS1222, three pole, Hubbell Cat No. CS1223, and four pole, Hubbell Cat
No. CS1224. Catalog numbers for Hubbell are shown for reference purposes and equivalent receptacles by
other manufacturers as noted above are also approved. Devices shall be specification grade, quiet type ac
switches, and shall comply with UL 20 and NEMA WD1.
5. Approved manufacturers for wiring devices:
Hubbell
P&S
6. All conduit shall be securely fastened in full accordance and as directed by the latest edition of the National
Electrical Code. In addition to the NEC requirements, conduit hangers, supports, or fastenings shall be provided at
each elbow and at the end (within 6") of each straight run terminating at a box or cabinet.
7. Conduits or boxes may not be supported by ceiling support wires or other ceiling supporting hardware.
7. Wiring device accessories
9. The use of perforated iron for supporting conduits will not be permitted.
10. Conduit runs between outlets shall contain not more than the equivalent of three (3) quarter bends. Provide
junction and/or pull boxes where shown on the drawings or as required, whether shown on the drawings or not.
Pull boxes shall be approved for use in the area where they are to be installed. Pull boxes or junction boxes shall
be provided in accordance with the following schedule:
i. Straight runs - not over one hundred (100) feet apart.
ii. One (1) 90 degree bend - not over seventy five (75) feet apart.
iii. Two (2) or more 90 degree bends - not over fifty (50) feet apart.
11. In Class I and Class II hazard areas, as designated on the drawings, explosion-proof flexible metal conduit shall be
used for all final conduit terminations at motors and to all other devices subject to vibration or movement. This shall
include all pendant mounted lighting fixtures and conduit runs at building expansion joints in Class I and Class II
hazard areas. Electrical ground continuity shall be provided as noted above.
12. Telephone and data (including other special communication systems such as cable TV) conduits shall be a
minimum of 3/4" in size unless noted otherwise, and shall run continuous from outlet to outlet and back to the main
terminal board, or shall be stubbed into the ceiling space (6" above the ceiling) and provided with a plastic bushing.
Bond conduit stub with a #10 bare copper conductor to the nearest electrical outlet box or continuous metal conduit
body. Refer to plans for specific details about the routing of the conduits. All empty conduits shall be provided with
a #10 pull wire.
13. Cables installed in plenums without conduit shall be UL classified for low flame resistance and low smoke
properties with "FEP" Teflon or Halar insulation suitable for plenum applications per Article 760 of the N.E.C.
14. Conduits below grade shall be installed in conformance with:
Provide all necessary trenching, backfill & removal of trenched material from site.
ii.
iii.
iv.
The bottom of the trench shall be undisturbed earth or thoroughly compacted fill. The contractor shall be
responsible for such compaction. the bottom shall be free of projecting rocks or other foreign matter. Where
muck or unstable ground is encountered in the bottom of the trench, it shall be excavated to a depth of at
least 12in. below the bottom line of the ducts and replaced with pea gravel in the proper grade. Duct shall
not be installed on or in frozen ground. sheeting or bracing shall be provided where necessary to protect the
work or adjacent property. Sheeting, bracing, and pea gravel shall be installed by the electrical contractor at
no additional expense to the owner. Backfill shall consist of 3 inches of compacted sand below conduits and
12" above conduits. Clean screened fill shall be installed and compacted to 6" below final grade or as
detailed in architectural specifications. Final grade patch shall be by E.C.
Duct joints shall be sealed with waterproof joint compound. Ducts shall be supported at least 3in. above the
trench bottom on plastic supports with spacing not exceed 5'. Before duct is placed, supports shall be
aligned, set to grade, and placed in concrete to prevent movement when encasement is placed. Ducts shall
be secured to supports and spacers placed for tiered ducts.
All secondary power service underground ducts shall be encased with 3000 psi concrete. All underground
ducts shall be 4" in diameter schedule 40 rigid non-metallic (P.V.C.) ducts with ground wires, unless
specifically indicated otherwise on the drawings. concrete encasement shall be in accordance with the
applicable provisions of the general trades portion of the specifications.
v. Encasement shall be continuous monolithic pour providing a minimum of 3" completely arownd the ducts.
Concrete shall not be poured directly on top of the ducts, but shall be poured from the sides and allowed to
flow over the ducts.
vi. Bell ends shall be installed at all duct terminations or as required by the power company. Fittings, couplings
and other accessories, as recommended by the manufacturer, shall be provided and installed.
vii. Ducts shall be cleaned by rodding and brushing. It shall be the contractors responsibility to assure a full bore
opening throughout the duct system.
E: FITTINGS FOR CONDUIT
1. Couplings and connectors for EMT: Die cast zinc, steel, or aluminum compression type. Set screw type will
also be permitted. Approved manufacturers, Thomas & Betts, Steel City, O-Z Gedney.
2. Fittings for rigid plastic conduit: Polyvinyl chloride, joints solvent welded in field, providing continuity of
mechanical strength and water tightness. Fittings and cement shall be produced by the same manufacturer
as the conduit.
3. Fittings for rigid conduit: Cast or malleable iron bodies, zinc or cadmium plated, with full threaded hubs,
screw covers and gaskets when located in areas requiring gaskets. Approved manufacturers: Crouse-Hinds,
Pyle National, Appleton.
4. Couplings and connectors for flexible steel conduit: Malleable iron or steel, zinc or cadmium plated and
shall fasten to the conduit by a clamping action around the periphery. Connectors for "liquid-tight" flexible
conduit shall be approved for the purpose and maintain the liquid-tight feature of the installation. Approved
manufacturers: Thomas & Betts, Steel City, O-Z Gedney.
3. Outdoor and Site Lighting Installation:
i. Site lighting luminaires shall be as called for on the drawings.
ii. Bases for site and roadway luminaires where required, shall be augered into the earth and concrete
shall be poured into the augered hole without a sona tube below grade to allow the concrete to fill the
natural crevices in the earth. Portion of base above grade shall be formed using a sonatube. Exposed
portion of finished base shall be smoothed, and voids filled with grout.
iv. Anchor bolts for poles shall be performed for the pole bolt circle at the factory.
i. Standard enclosure shall be NEMA 1, unless noted otherwise, with primer and finish paint of the
manufacturers standard. Cabinets shall be oversized where necessary to accommodate the entrance of
several large conduits and/or when necessary to avoid overcrowding except cabinets for panels
mounted flush shall be not more than 22 inches wide and 5-3/4 inches deep unless otherwise approved
by the architect/engineer. Trims shall contain hinged doors and shall be equipped with flush chrome
plated combination key locks and catches. Locks shall be all keyed alike and two keys furnished to the
owner.
ii. Column-type enclosures shall be similar to the standard enclosure except panel shall be approximately
8-1/2 inches wide for mounting between building column webs as indicated, and provided with
extension trough and pullbox with neutral bar when shown on the drawings.
iii. Where spaces are noted on the drawing, equip the panelboard with bus and all necessary hardware for
future circuit breaker installation.
iv. Metal frame and plastic covered typewritten card shall be mounted inside each panel door.
Information entered onto the cards shall correspond to the circuit numbers as installed in the field.
2. Overcurrent Protective Devices
i. General use circuit breakers for panelboards shall be bolt-on molded plastic case type, 1, 2, or 3 pole,
quick-make, quick-break, with trip-free operating handle, position indicating and thermal-magnetic
trip device. Furnish 2 and 3 pole breakers with common operating handle and common trip
mechanism. All circuit breakers used for switching applications shall be U.L. listed type "SWD"
for that application. all circuit breakers used for protection of motors, refrigeration equipment, or
HVAC equipment shall be U.L. listed type "HACR" for that application.
ii. Circuit breakers furnished with panelboards shall conform to the following interrupting ratings
(symmetrical) in amperes unless otherwise noted:
Voltage
Rating
i. Wall plates: Single and combination, of types, sizes, and with ganging and cutouts as indicated.
Provide plates and attachment screws which mate and match with wiring devices to which attached.
Provide wall plates with engraved legend where indicated. Provide smooth nylon coverplates for
finished areas, and galvanized steel plate for unfinished areas.
Trip
Rating
No. of
Poles
15-100 ampere
15-100 ampere
125-225 ampere
250-400 ampere
15-100 ampere
15-100 ampere
125-225 ampere
250-400 ampere
400-800 ampere
120
240
240
240
277
480
480
480
480
ii. Floor service outlets: Modular, above-floor service outlets and fittings of types and ratings indicated.
Construct of die cast aluminum, satin finish. Use design compatible with floor outlet wiring methods
indicated. Provide 20 Amperes, 125 Volts, gray duplex receptacles. NEMA configuration 5-20R
where indicated. Provide with 3/4 inch or 1 inch NPT, 1 inch long, locking nipple for installation
where compatible with wiring method.
I.c. Amperes
(Symmetrical)
1
2&3
2&3
2&3
1
2&3
2&3
2&3
2&3
Frame
Size
ii. Duplex receptacles shall be wired with the neutral wire to the silver binding screw.
iii. Three phase receptacles shall be wired such that all have the same phase sequence.
iv. The receptacle circuit and panel number shall be indicated on the inside of all outlet boxes, or directly
on the conductors by means of a wire labeling system.
v. Combination switch/receptacle shall be installed in a two gang box with a combination
switch/receptacle coverplate. Connect the receptacle to the lighting circuit ahead of the switch and
locate the switch on the side of the box closest to the door. Note, this method is to be used only for
120 Volt lighting system. 277 Volt lighting switches and 120 Volt receptacles shall be located in
separate boxes.
vi. Confirm final location of all wiring devices and outlet boxes with owner/architect prior to rough-in.
9. Wiring devices listed or noted on the drawings as weatherproof shall be provided with a cover which
maintains the weatherproof integrity when the cover is closed. Receptacles noted as suitable for operation
in a wet locations shall be provided with a cover which will allow the receptacle to remain operational
during wet conditions with a plug inserted into the receptacle.
I: LIGHTING
1. Lighting Fixtures: see drawings for manufacturers catolog numbers.
22,000
22,000
22,000
42,000
25,000
25,000
30,000
42,000
42,000
100 amp
100 amp
225 amp
400 amp
100 amp
100 amp
225 amp
400 amp
800 amp
iii. Ground fault circuit interrupters shall be similar to general use circuit breakers specified; 15-20
ampere, 1 or 2 pole with 5ma sensitivity. Furnish when indicated on drawing.
iv. Fuses over 600 ampere shall be Bussman Hi-cap time delay type KRP-C, or Gould Shawmut A4BQ
(601-2000 ampere) or Gould Shawmut A4BY (2001-6000 ampere) 600 volt, UL Class l with
minimum interrupting rating of 200,000 ampere rms symmetrical.
v. Fuses 600 ampere or below shall be Bussman low-peak dual element type LPN-RK (250 volt) or LPSRK (600 volt) or Gould Shawmut Amp-trap type A2K (250 volt) or A6K (600 volt) UL Class RK1
with minimum interrupting rating of 200,000 ampere rms symmetrical.
vi. Provide spare circuit breakers installed in panelboards as indicated on the panel schedule as shown on
the drawings. Provide 10% spare (minimum of 3) of each type and rating of fuses installed.
3. Safety Switches
i. Provide fusible or non-fusible safety switches as indicated on the drawings. Switches shall be quickmake, quick-break, heavy duty visible blade type, horsepower and I squared T rated. Use NEMA 12
enclosures in factory areas, NEMA 1 enclosures in other indoor areas and NEMA 4X stainless steel type
enclosures outside unless otherwise indicated on the drawings. Furnish three pole, single-throw switches
unless otherwise indicated, with current and voltage ratings as indicated.
ii. Suspended ceiling systems shall be supported for fixture installation as noted above, and as a
minimum condition, as noted in ANSI/ASTM C636-76, par. 2-7, CEILING FIXTURES.
iii. Install fixtures in accordance with the Architectural Reflected Ceiling Plans. Where substantial
differences may occur between the Reflected Ceiling Plans and the Electrical Plans, inform the
Architect/Engineer for resolution of the discrepancy.
iv. The Contractor shall coordinate fixture construction details with ceiling system in which they are
installed, i.e.: support system dimensions, flanges where required, acoustical tile or pan pattern, etc.
v. Rows of fixtures shall be installed accurately as to line and level. Fixtures shall be securely mounted
so that they will not be distorted by handling incidental to normal maintenance.
vi. Surface type fluorescent lighting fixtures mounted on acoustical ceiling must be coordinated with the
Architectural drawings in order that a main "T" runner will be placed in the center of each fixture
and/or each row of fixtures. Main "T" runner shall be of at least the same length as the lighting fixture
and shall be supported to carry at least twice the weight of the lighting fixture.
vii. All fixtures shall be securely supported with approved hangers. Where fixtures will be installed in
suspended ceilings, any Code-required additional ceiling supports as approved by the Architect, shall
be provided by this Contractor.
viii. Provide supports for all lighting fixtures as detailed on the Drawings, as specified, or as required by
the fixture specified. Fixtures installed in unfinished areas (areas including but not necessarily limited
to warehouses, factory areas, manufacturing areas, office spaces without lay-in ceilings, and spaces
above lay-in ceilings) shall not be fastened directly to the structure. In these cases, unistrut type
channel along with the appropriate fasteners and clips shall be used to support the fixtures. Refer to
the drawings for specific support requirements in addition to those noted here.
ix. Fixtures shall not hang directly from conduit boxes unless the boxes have been specifically designed
for such purposes. These boxes shall be supported independent of the conduit system and shall not
rely upon the conduit for support.
x. Lay-in troffers in suspended ceilings and surface type fixtures mounted to suspended ceilings shall be
secured mechanically by screws, rivets, clips, etc. as per Section 410-16(C), NEC. Additionally, layin fixtures shall also be supported by two independent support wires running from diagonally opposite
corners of the fixture to the overhead structure. Surface mount fixtures shall be additionally supported
by means of at least two clips for each fixture which surround the T-bar and are tied to the overhead
structure with a separate wire. The surface fixtures shall be secured to these clips.
xi. Plaster frames shall be furnished for each recessed fixture installed in plaster ceilings and walls.
9. The armor of interlocked armor cable, wiring channels, cable trays, and all metallic conduit including rigid,
EMT, and flexible conduit shall be connected at each end to the equipment ground conductor utilizing a
conduit grounding bushing. Junction boxes and other enclosures (sizes above 5" x 5") shall utilize an
equipment ground lug to securely bond the equipment grounding conductor to the enclosure.
10. Where any grounding conductor requires physical protection to maintain grounding integrity, it shall be run
through a non-ferrous conduit or bonded to a continuous steel conduit at both ends.
11. The grounding electrode system shall consist of 3 4" diameter x 10' copper clad ground rods. Exterior ground
rods shall be driven to 12" below finished grade & be provided with a 12" diameter x 30" long rigid pvc pipe
w/ screw cover for inspection purposed. center ground rod in pipe & install pipe flush with grade. pvc pipe
and cover shall be traffic rated. interior ground rods shall be driven to 6" above grade & installed as close to
a wall as possible. all connections to ground rods shall be cadweld type.
L: EXECUTION
1. The contractor shall exercise due caution when working so as not to damage that portion of the electrical
system that is to remain.
2. Positively no conduit or wire removed shall be reused in the new installation.
3. All circuits shall be identified on the panel directories by this contractor. At the completion of the job, the
contractor shall provide each panelboard with a new typed directory with the existing loads as noted from
the old directory and the new loads as installed.
4. The contractor shall keep on the job, one complete set of working drawings on which he shall record any
deviations or changes from such contract drawings made during construction. Record drawings shall show
changes in the following:
i. Size, type, capacity, etc. of any material, device or piece of equipment.
ii. Location of any device or piece of equipment.
iii. Location of any outlet or source in the building service system.
iv. Routing of any conduit, or other building electrical service.
These drawings shall be kept clean and undamaged, and shall not be used for any other purpose than
recording deviations from working drawings and exact locations of concealed work. After the job is
completed, this set of drawings shall be delivered to the owner in good condition, as a permanent record of
the installation as actually constructed.
M: CUTTING AND REPAIRING
1. All necessary cutting in walls, floors and other such work shall be neatly and carefully done and the work
shall be repaired in an approved and workmanlike manner. No cutting into the structural parts of the
building, which may impair its strength, shall be permitted without the prior written approval of the owner.
If such cutting is permitted, the area shall be suitably reinforced to restore the structural integrity of the
work to its designed value.
2. The electrical contractor shall be responsible for all damage to work of his, or other trades, caused by his
work or through the neglect of his workmen. All patching and repairing of damaged work shall be done by
the trade which originally installed it, at the direction of the owner's representative, and the cost of such
repair shall be paid by the electrical contractor.
3. Absolutely no cutting of wall, floor or other finished material or fastening of electrical components to the
exposed surfaces of finished areas will be permitted.
1. The testing work shall include all labor, materials, tools, and equipment to perform and record all necessary
tests and adjustments of equipment, including Load Center Unit Substations, Motor Control Centers, High
Voltage Cable, 600 Volt Wire and Cable, and Grounding, as indicated on the drawings, specified herein, or
where necessary to verify performance requirements.
2. Inspection tests shall provide a visual inspection of electrical equipment for manufacturing, shipping or
installation defects.
3. Acceptance tests shall show that the methods and materials used in the installation of equipment conform to
applicable codes and standards, and the manufacturers installation instructions, and to determine that the
equipment involved may be energized for operational tests.
4. Operational tests shall show the electrical equipment will perform the functions for which it was designed.
5. The services of a recognized independent testing laboratory shall be engaged to conduct all tests described
herein with the exception of routine insulation resistance, continuity and rotation tests.
6. Perform all acceptance and operational tests in the presence of the Architect/Engineer. Notify the
Architect/Engineer of time of test at least two (2) days prior to testing. Notify manufacturers of electrical
equipment to permit their representatives to witness the test should they so request.
7. Submit test reports, including complete data and actual readings taken, for all equipment tested to the
Architect/Engineer for approval after each test performed. Do not energize any equipment for operating
tests until data has been approved. Include copies of the final approved test reports upon completion of the
work as part of the required operating and maintenance data to be furnished as specified in Division 1.
8. Give each power feeder and subfeeder cable (600 Volt Wire and Cable) a continuity and megger test.
Isolate power cables to be megger tested by opening switches at each end of cable prior to testing. Apply
megger tests, using a 1000 volt megger, between each conductor and ground with the other two conductors
in the conduit grounded to the same ground. Minimum acceptable readings for disconnected cables shall be
1 (one) megohm. Cable must pass megger test to be reported as acceptable.
9. The following test and inspections shall be made on the grounding system.
ii. Provide safety switches with an external operating handle interlocked with the cover door to prevent
the door from being opened while the switch is in the "on" position except by operating an
inconspicuous interlock defeating mechanism. Provide means for padlocking the operating handle in
the "off" position. Equip switches with auxiliary contacts when indicated.
2. Indoor Installation:
i. The Contractor shall refer to the Architectural drawings for ceiling type, construction and details of
mounting. Adjust fixture trim ring as required for correct mounting in ceiling fixture is to be installed.
All fixtures shall be supported per NEC Article 410.
8. Motors shall be connected to the equipment ground conductor with a conduit grounding bushing and with a
bolted solderless lug connection on the metal frame.
N: TESTING
8. Wiring device installation:
i. Install switches and receptacles in outlet boxes as specified elsewhere in this specification. Install
single pole toggle switches so that the switch is on in the "up" position. Install receptacles with the
U-shaped ground slot at the top or to the left.
7. Convenience outlets shall be self-grounding type or shall have a green grounding conductor installed from
the ground lug on the outlet to the outlet box.
J. Lighting and Receptacle Panelboards
1. Panelboards for 480/277, 208/120, or 240/120 volt lighting and receptacle service shall be dead front
type, conforming to NEMA standard PB-1-1-71 and UL 67, and consisting of three phase, three or
four wire solid neutral, main lugs or main overcurrent device as indicated, branch overcurrent devices
as noted and equipment ground bar, all in a surface or flush mounted code gauge galvanized sheet
steel cabinet as indicated. Enclosure to be NEMA 1 unless noted otherwise with primer and finish
paint of the manufacturers standard. All busing shall be copper.
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
xxi. Solid state transformers for low voltage lighting shall not be used for dimming applications unless the
transformer and dimmer are a U. L. listed assembly specifically intended for the application.
iii. Bases shall have reinforcing steel as indicated on the contract drawings and shall be Class 'A' concrete.
6. Dimmer switches: solid state dimmer switches conforming to NEMA WD 1, mounted in outlet boxes For
incandescent fixtures; switch poles and wattage as indicated, 120 V, 60-Hz, continuously adjustable toggle,
single-pole, with on-off switch. Equip with electromagnetic filter to eliminate noise, RF and TV
interference. Dimmers to be Lutron "Nova T-Star" series for dimmers rated up to 1500 watts and "Nova"
series for 2000 watt dimmers. Lighting switches shown adjacent to dimmers shall be Lutron "Nova T-Star"
or standard "Nova" style to match dimmers and shall be provided with a single, one piece coverplate.
Color shall be specified by architect.
8. Horizontal and vertical conduit runs may be supported by one-hole malleable straps, clamp backs, or other
approved devices with suitable bolts, expansion shields (where needed) or beam type clamps for mounting to
building structure or special brackets.
xx. Low voltage lighting transformers should be protected by fuses. Fuse sizes shall be as
recommended by the transformer manufacturer. Busman type
HRS or Littelfuse 155020, fuse holders are recommended.
6. Lighting fixtures permanently connected to the conduit system shall be grounded by means of a grounding
conductor run inside the conduit. Fixtures mounted on trollies or portable lighting units shall be grounded
by means of a grounding conductor in the portable cord.
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
4. Discrepancies between the drawings or between the drawings and actual field conditions shall be brought to the
attention of the architect and the engineer prior to submitting the bid. The more comprehensive and most expensive
scope of work shall be considered for the electrical bid unless written clarification is provided by the architect and
the engineer prior to submitting the bid.
xix. All lamps shall be in working order at the time of final acceptance of the work by the Owner and
Architect/Engineer. This Contractor shall replace all defective lamps with new lamps until the work is
finally accepted.
iii. Fuse clips shall be rejection type for fuses specified (up to 600 ampere). Fuses clips for 601 ampere
to 6000 ampere shall be suitable for UL Class l fuses.
4. Transformers
i. Transformers shall be indoor dry, two winding, quiet type, with ventilated enclosure, conforming to
NEMA standards, 220 degrees celcius insulation for continuous operation in a 40 degree
celsius ambient temperature with a temperature rise not to exceed 80 degrees celsius.
Provide a minimum of two 2-1/2% FCAN and four 2-1/2%
FCBN taps in the primary winding for transformers over 25 KVA and a minimum of two 2-1/2%
FCBN taps for transformers 25 KVA and below. Transformers 25 KVA through 75 KVA shall be
designed for floor or wall mounting.
ii. Sound levels shall not exceed those established in ANSI standard C89 shown in the following table:
KVA
dB level
0-150
42
iii. Furnish transformers having voltage, KVA ratings and connections as indicated on the drawings.
i. Inspect ground conductors and connections for compliance with plans and specifications and for
satisfactory workmanship. After installation of the grounding electrodes,
provide ground resistance testing prior to the interconnection of other grounding systems. Do not
perform tests under unusually wet weather; tests should be performed during normal weather
conditions.
REVISIONS
ii. Reports shall include all resistance readings obtained, temperature, humidity and condition of the soil
at the time of the tests.
10. Operational tests shall be performed on all electrical systems, and shall include, but not be limited to,
building lighting system, panelboards, motor starters and control devices, alarm circuits and site lighting
equipment.
O: GUARANTEE
1. Material, equipment and installation shall be guaranteed for a period of one year from the date of
acceptance. Defects which appear during that time period shall be corrected by this contractor at his
expense.
9
3. The contractor shall visit the job site and become familiar with all existing conditions. Submission of a bid assumes
the contractor has reviewed or accepts all field Conditions and existing conditions. No additional compensations
shall be allowed for labor or material because of ignorance of these conditions before or after bid submission.
1. Conductors shall be new, 600 volt, 90c, type XHHW, THHN or THWN insulation, stranded copper for feeders
rated above 60 amps. Compact aluminum may be used for feeders of 150amps or higher. Minimum size shall
be #12 AWG for runs of less than 100 feet total circuit length (out and back for single phase circuits and out
only for three phase circuits with no neutral). Use #10 AWG for circuits longer than 100 feet. Other sizes shall
be as noted. Control wiring may be #14 AWG. All 120 volt and 277 volt circuits shall have a dedicated neutral
conductor. The neutral conductor shall be the same size as the phase conductor. All conductors shall be
copper.
5. Where building type conductors are installed in a raceway, a green equipment grounding conductor shall be
included in each raceway system.
10
2. The electrical, mechanical, architectural, structural, and all other drawings as well as the specifications and
addendums are part of the contract documents. any electrical requirements called for on other trades
contract documents shall be included in the electrical bid.
G: CONDUCTORS
xviii. At the time of final inspection all fixtures and equipment shall be complete with all required glassware
and/or reflectors, clean and free of defects. Any glass-ware, or reflectors, etc., which have defects
shall be replaced at the Contractor's expense before final acceptance.
8
1. The drawings represent the design for the listed manufacturers' requirements. If any substitutions are accepted by
the engineer, this contractor shall be responsible for all necessary modifications, including cost, to the electrical
system required because of the substituted equipment or material.
i. Wood - wood screws.
ii. Concrete - expansion bolts or cast in place anchors.
iii. Structural steel - approved brackets or machine bolts.
4. Any item covered by the preceding paragraph which is within six feet of grounded metal and not directly
interconnected with the grounded metal shall have a flexible bare copper cable connection not smaller than
#6 AWG to the grounding system.
CHINO, CA 91710
C: GENERAL REQUIREMENTS
2. Electrical supports shall be attached to the structure by one of the following methods:
xvii. When fixtures are installed in a fire proof ceiling, the fixture shall be U. L. listed to maintain the
fire proof rating or the fixture shall be fire proofed by the electrical contractor using a U. L.
accepted standard. see architectual drawings for ceiling ratings.
11995 CENTRAL AVE.
The National Electrical Code - sometimes referred to herein as
the "NEC" - (NFPA-70).
ii. National Electrical Safety Code (ANSI-C2).
iii. All applicable state and local codes.
iv. Applicable provisions of the Occupational Safety and Health Act.
1. Supports shall be suitable for the device or equipment to be mounted. All supports shall present a neat
appearance, and shall be installed in such a way that they do not detract from the appearance of the space.
Supports shall have adequate strength and shall be installed so as to properly support the device or
equipment mounted on them.
3. The entire power and lighting system shall be permanently and effectively grounded including panels,
starter enclosures, motor frames, and other exposed, non-current carrying parts of the electrical equipment.
The equipment ground conductor shall be separate from the neutral conductor and shall not be used as a
load current carrying conductor.
7
i.
F: ELECTRICAL SUPPORTING DEVICES
2. Ground conductors shall be stranded, annealed copper with green insulation (insulation material as
specified for general building use).
xvi. Where a modular wiring system is installed, all ceiling mounted recessed fluorescent lighting fixtures
shall be furnished with suitable receptacles to match the modular wiring system furnished and installed
by this Contractor. Each fixture shall be equipped to permit either single or multiple fixture circuit
wiring as is appropriate for the fixture type.
6
3. Perform all work in accordance with the latest edition of applicable codes including, but not necessarily limited to
those listed below:
Entering or cross-connecting enclosures containing arcing or high temperature devices.
Two-inch conduit and larger entering any enclosure.
Passing from Division 1 to Division 2, from Division 2 to non-classified areas, with or without a barrier.
Multi-conductor and shielded cables.
1. The entire power, lighting system as well as building structure, mechanical & plumbing systems, fences &
simalar metal objects shall be permanently and effectively grounded in accordance with the
minimum requirements of the National Electrical Code, or as specified herein, whichever is the more
stringent.
5
2. The contractor shall secure all permits and pay all fees that are required by the applicable local and state codes.
i.
ii.
iii.
iv.
xv. Branch circuit conductors shall be run in fluorescent fixture wiring channels only as permitted by the
N.E.C. The Contractor shall be responsible for providing all necessary boxes and conduit for an
approved installation.
K: RACEWAY AND GENERAL GROUNDING
HARBOR FREIGHT TOOLS
1. All work included by the drawings and specifications, together with all material (or equipment) furnished, shall
comply with the latest published codes and standards listed insofar as such shall apply. All electrical items shall be
UL labeled & listed.
8. Conduit Fittings in Classified (Hazardous) Areas: Conduit seals and/or drain seals shall be installed in strict
accordance with the NEC in classified (Hazardous) areas designated on the drawings, with special attention
to the following:
xiv. Incandescent fixtures shall be thermally rated, protected and marked for their application especially in
recessed mounting, to protect against over-temperature and combustion. The installation shall comply
with Section 410-65 thru 410-72 the NEC.
Siemens
Cleveland Switchboard Co.
4
B: CODES, PERMITS AND FEES
7. Outlet, Pull, Terminal and Junction Boxes in Classified (Hazardous) Areas: Cast boxes shall be copper-free
aluminum with integral hubs or box wall thickness sufficient for a minimum of five full tapered threads.
Covers shall be screw-on bolt-on through 12" x 12" boxes and hinged removable bolt-on covers for larger
boxes. Boxes other than outlet boxes shall be equipped with a breather drain and equipment grounding lug
and all boxes shall be, as applicable, for installation in the particular classified (hazardous) areas which are
designated on the drawings. Approved Manufactures: Crouse-Hinds, Pyle-National, Appleton, Adalet,
O-Z Gedney, or Killark.
General Electric Company
Cutler Hammer/Westinghouse
Square D
3
4. The electrical contractor shall warrant all work & material indicated on these electrical drawings for a period of 1
year from the date of final acceptance. Warranty shall include any additional labor or material required to repair or
replace defective item.
xiii. Fixtures shall be installed with due regard for beams, piping, ductwork, and other mechanical or
plumbing equipment.
TYPE
3. The electrical contractor shall not attach to, cover up, or finish against any defective work, or install in a manner
which will prevent proper installation of the work of other trades.
6. Fittings for conduits : All conduit runs at building expansion joints shall be provided with O-Z type expansion fittings. Sizes
shall be as dictated by the conduit size. A bonding jumper shall be securely connected to each conduit. Exterior exposed
runs of PVC conduit shall be provided with expansion fittings at intervals not exceeding manufaturers recommendations.
viii. Approved Manufacturers for Power Distribution Equipment:
DATE
2. The exact location of all items shown on the electrical drawings is dependent upon field conditions. Review the
plans and specifications for all parts and consult with other trades of this project for pertinent data on sizes,
locations, wiring, etc., as required for a complete electrical installation.
xii. Pendant mounted fixtures shall utilize mounting hardware as called for on the drawing. mount fixtures
at elevations as noted on the drawings. Wherever the mounting surface slopes, fixtures shall
be provided with universal type fixture hangers to allow the fixture to hang plumb.
1
i. Furnish and install new conduit and wire.
ii. Furnish and install all fuses, circuit breakers, panelboards etc.
iii. Install new lighting fixtures as indicated.
iv. Furnish & install new light fixtures as indicated.
v. Furnish & install communications devices.
5. Bushings: Grounding type, with insulating plastic insert; malleable iron, zinc or cadmium plated, for steel
conduit and aluminum alloy for aluminum conduit. Install grounding type bushings as required in the
grounding section of this specification.
2
1. The electrical contractor shall provide all labor, material, equipment, and tools necessary for demolition and removal
of existing and the complete installation of the new electrical work, ready to use, as shown on the drawings or
specified herein. Work shall include, but not be limited to the following:
#
A: DESCRIPTION OF WORK
5. Panelboard and Transformer Installation
i. Mount panelboards at uniform height throughout the building, and such that the top switch is not more
than 79 inches above floor when measured to the center of the switch handle.
ii. Install handle guards on all breakers for night lighting, emergency, and similar circuits when indicated.
iii. Each panelboard shall be identified with a legend plate of lamicoid plastic inside the door for
panelboards in finished areas and on the outside of panelboards in unfinished areas with the panel
designation as shown on the drawings.
ELECTRICAL
SPECIFICATIONS
iv. Install not less than two spare 1-1/4 inch conduits from each flush mounted panel to an accessible area
above the ceiling.
DATE
07/08/15
v. When branch circuits are not scheduled on the drawing, they shall be arranged to balance the phase
loads on each panelboard and the loads shall be equally distributed on each of the phases of the
panelboard.
JOB NO.
15166
vi. Mount panelboard, safety switches, and similar equipment securely to walls or steel supports.
Equipment mounted on the building perimeter foundation walls shall be shimmed at least 1/4 inch
from the wall to permit back ventilation.
vii. Provide supports for truss mounted and wall mounted transformers. All transformers which are
mounted above panelboards shall be mounted away from the wall by an amount equal to the depth of
the panelboard. The width of the panelboard shall also be maintained clear behind the transformer.
E0.1
SHEET NO.
F) ALL UNUSED WIRE (POWER & COMMUNICATION) SHALL BE REMOVED.
G) ALL EXISTING WIRING (POWER & COMMUNICATION) THAT IS TO REMAIN SHALL BE REWORKED OR REPLACED WITH CODE
COMPLIANT MATERIAL & SUPPORTS. ANY EXISTING SURFACE MOUNTED CONDUITS SHALL BE REMOVED OR RELOCATED SO THAT
THEY ARE IN THE JOIST SPACE OR WITHIN WALL CAVITIES.
H) EXISTING LIGHT FIXTURES THAT REMAIN OR ARE BEING RELOCATED SHALL BE CLEANED AND RE-LAMPED WITH 4' T8 LAMPS.
BROKEN LENSES SHALL BE REPLACED. PROVIDE NEW T8 BALLASTS IF REQUIRED.
I) EXISTING LIGHT FIXTURES, ELECTRICAL / TELECOMMUNICATION DEVICES, PANELBOARDS ETC. THAT ARE NOT TO BE REMOVED
SHALL BE NOTED AS EXISTING TO REMAIN ON THE DRAWINGS. SEE ARCHITECTURAL & MECHANICAL DRAWINGS FOR ADDITIONAL
INFORMATION ON SCOPE OF DEMOLITION.
CASH WRAP POWER / COMMUNICATION DETAIL
SCALE: NOT TO SCALE
+72"
30A
DEDICATED ISO GROUND QUAD OUTLET MOUNTED WITHIN THE CASHWRAP SO THAT BOTTOM OF QUAD IS 2" ABOVE
LOWEST SHELF. SEE DETAIL 1/E1.0. COLOR TO BE ORANGE.
05
COORDINATE ROUGH-IN LOCATION WITH MANUFACTURERS SHOP DRAWINGS PRIOR TO INSTALLATION.
06
DUPLEX OUTLET MOUNTED ON WALL AT 12" ABOVE WINDOW. MOUNT FLUSH IN CEILING IF CEILING IS WITHIN 12" OF TOP OF
WINDOW.
07
DUPLEX OUTLET MOUNTED FLUSH IN CEILING FOR INSTALLATION OF INTERIOR MOUNTED NEON SIGNS BY T.G.C.
08
J-BOXES WITH SERVICE DISC SWITCH FOR SIGN CIRCUITS. COORDINATE ROUGH-IN REQUIREMENTS WITH SYSTEM
CONTRACTOR.
09
´+,*+&203$570(1732:(532/(72%()851,6+('%<+)7$1',167$//('%<(&(&6+$//(;7(1'81,67587
)5207+(32:(532/(83727+(522)6758&785($7
´$))$1'&211(&77281,675876(&85('72522)
STRUCTURE (UNISTRUT TO BE PAINTED WHITE).
10
WEATHERPROOF PUSH BUTTON MOUNTED +48" CONNECT TO SERVICE BELL. EDWARDS #852.
11
SERVICE BELL MOUNTED TO BOTTOM OF ROOF STRUCTURE. EDWARDS #340-10G5.
12
REMOVE EXISTING ELECTRICAL PANELS.
13
G.C. SHALL COORDINATE NEW SWITCH & METER REQUIREMENTS WITH POWER COMPANY IMMEDIATELY UPON RECEIVING
CONTRACT.
14
EXHAUST FAN SOLID STATE SPEED CONTROLLER PROVIDED BY MC WIRED & INSTALLED BY E.C.
15
DUPLEX RECEPTACLE FOR SUSPENDED MONITOR. E.C. SHALL PROVIDE MC CABLE & CAST BOX & MOUNT RECEPTACLE ON
MONITOR ARM. COORDINATE EXACT LOCATION WITH COMMUNICATIONS CONTRACTOR.
16
NOTE NOT USED.
17
240V CHARGER & BOOST TRANSFORMER (208:240V) PROVIDED BY HFT WIRED AND INSTALLED BY E.C. COORDINATE
ROUGH-IN REQUIREMENTS WITH EQUIPMENT MANUFACTURER PRIOR TO INSTALLATION.
P-34
17
L-25/2
(39,41)
10-2
CONNECT TO FORKLIFT CHARGER.
COORDINATE EXACT ROUGH-IN
WITH EQUIPMENT SUPPLIER.
RECEIVING AREA
LIGHTING CONTROL
PANEL OVERRIDE SWITCH
P-29 12-2
#12 ISO GND 3
APPROXIMATE LOCATION OF
EXISTING TELEPHONE DEMARK
B.5
P-30
LIGHTING CONTROL PANEL
6
10-2
L
P-11 10-2
#10 ISO GND
M
4
10
EXISTING 600A DISCONNECT SWITCH & METER
+78" AFF
+78" AFF
+78" AFF
B
L-26
R18
8
TO PUSHBUTTON AT
RECEIVING DOOR
10-2
10-2
10-2
P-12
P-8
J
D
P-31
B T
11
15
P-33
WP/GFI
ON ROOF
P-38
SALES AREA
DD
12-2
P-33
WP/GFI
ON ROOF
P-38
RTU-3
7
L-20,R20
10-2
100A/WP
RTU-2
M-125/3
(7,9,11)
1-3
P-7 10-2
#10 ISO GND
P-33
WP/GFI
ON ROOF
P-38
DD
200A/WP
M-100/3
(2,4,6)
2-3
A.8
SALES REPLENISHMENT
DD
200A/WP
RTU-1
A.7
M-125/3
(1,3,5)
1-3
4
10-2
6
P-6
9
L-40,R24
10-2
P-8
10-2
RTU-4
R
R
MANAGER
3 P-20 10-2 #10 ISO GND
M-40/3
(8,10,12)
P-15
+44" H
P-28
GFI
EF P-41
8-3
WOMEN
R
10-2
10-2
10-2
1
10-2
R
P-19
P-18
R
R
10-2
10-2
P-41
P-3
P-41
DAMPER
#10 ISO GND
#10 ISO GND
10-2
R
m
10-2
10-2
MEN
10-2
R
GFI
P-24
m
P-17
+44" J
P-28
+44"/GFI
+101"
P-21
+48"/GFI
10-2
EF
2
CASH ROOM
P-1 10-2 3
#10 ISO GND
P-28 5
+23"/GFI
10-2
R
m
2
P-3
R
J
R
REVISIONS
P-36
GFI
P-23
J
P-4
P-4
L-25,R23
GFI
P-28
+44"/GFI
TYPE
60A/WP
10-2
R
1.5KW
WATER HEATER
DD
10-2
DATE
L-40,R24
6
P-33
WP/GFI
ON ROOF
P-38
H
P-23
+48"/GFI
R P-23
GFI
#
4
P-5 10-2
#10 ISO GND
BREAK ROOM
10-2
R P-3 R
POWER PLAN
A
P-2 10-2 3
#10 ISO GND
10-2
POWER PLAN
SCALE 1/8" = 1'-0"
DATE
07/08/15
JOB NO.
15166
E1.0
SHEET NO.
9
4
P-9 10-2
#10 ISO GND
10
+78" AFF
10-2
8
P-39
7
P-39
6
P-39
5
P-39
4
9
3
P-10
10-2
L-42,R24
1
6
J
PHOTOCELL PC ON WALL MOUNTED
AT 15'-0". SHIELD FROM ARTIFICIAL
LIGHT SOURCES.
P
L-42,R24
2
1
E1.0
DEDICATED ISOLATED GROUND QUAD OUTLET ON DEDICATED CIRCUIT. COLOR TO BE ORANGE.
04
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
E) CONTINUITY OF CIRCUITS INTERRUPTED BY REMOVAL OF ELECTRICAL DEVICES SHALL BE MAINTAINED.
PROVIDE A DEDICATED CIRCUIT & WIRE THRU TIME CLOCK. UTILIZE SAME CIRCUIT IF THERE ARE TWO EXHAUST FANS.
03
CHINO, CA 91710
D) EXISTING CONDUITS, CIRCUITS OR SYSTEMS PASSING THROUGH THE REMODELED AREAS WHICH SERVE UNREMODELED AREAS
SHALL REMAIN AND BE PROTECTED DURING DEMOLITION AND REMODELING, AND SHALL BE RELOCATED AND REROUTED.
02
11995 CENTRAL AVE.
C) EXISTING CONDUITS, CIRCUITS OR SYSTEMS IN WALLS OR CEILING BEING REMOVED WHICH SERVE SURROUNDING UN REMODELED
AREAS SHALL BE REWORKED AND MAINTAINED.
PROVIDE A JUNCTION BOX ON WALL ABOVE CEILING FOR RACK POWER. COORDINATE ALL CONNECTION REQUIREMENTS
WITH RACK SUPPLIER PRIOR TO ROUGH-IN PROVIDE MC CONDUIT DOWN WALL & INTO RACK ENCLOSURE. CONNECT TO
RACK POWER SYSTEM AS WELL AS PROVIDING A SEPARATE QUAD RECEPTACLE MOUNTED IN RACK. COORDINATE EXACT
LOCATION WITH HFT PRIOR TO INSTALLATION.
HARBOR FREIGHT TOOLS
B) REMOVE AND/OR RELOCATE EXISTING ELECTRICAL DEVICES NOT NOTED AS EXISTING TO REMAIN. COORDINATE SUCH CONDITIONS
WITH ARCHITECTURAL DRAWINGS.
01
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
POWER PLAN NOTES
GENERAL ELECTRICAL DEMOLITION NOTES
A) NO ATTEMPT HAS BEEN MADE TO INDICATE ALL EXISTING ELECTRICAL DEVICES, LIGHT FIXTURES, COMMUNICATION DEVICES,
WIRING, CONDUIT, ETC. TO BE REMOVED AND/OR RELOCATED. HOWEVER, THE ELECTRICAL CONTRACTOR SHALL FIELD VERIFY THE
EXTENT OF DEMOLITION PRIOR TO SUBMITTING BID.
N
GENERAL NOTES
ALL SALES & SALES REPLENISHMENT AREA LIGHTING CIRCUITS SHALL BE
B
ALL NIGHT / EMERGENCY / EXIT LIGHTING CIRCUITS SHALL BE
#12 GA. x1" BENT PLATE
CONNECT TO STRUCTURE
AS REQUIRED
STRUCTURE
STRUCTURE
#12 GA. SLACK SUSPENSION
WIRES W/ 3 TIGHT TURNS IN
1-1/2" AT EACH END. TYPICAL.
#10 SHEET
METAL SCREWS
UTILIZE ANTI SWAY #12 AWG SLACK SUSPENSION
WIRE SUPPORTS WITH 3 TIGHT TURNS IN 1/2" OF
EACH OTHER IF OBSTRUCTION (WALL, COLUMN,
DUCTWORK, OTHER FIXTURE, ETC.) OCCURS
WITHIN THE CIRCUMFERENCE OF THE FIXTURE
SWAYING AT A 45 DEGREE ANGLE FROM PLUMB.
ATTACH TO FIXTURE AS SHOWN IN ADJACENT
DETAIL.
#12 GA. x1" BENT PLATE
CHAIN TO UNISTRUT MOUNTING
BRACKET. CHAIN SHALL BE SEISMIC
RATED WITH CLOSED HOOKS.
SEISMIC RATED INDEPENDENTLY
SUPPORTED TBAR GRID CLIP WITH
#12AWG TIE WIRE TO STRUCTURE
CADDY CLIP 515 SERIES MOUNTED IN
ALL FOUR CORNERS
CEILING GRID
FIXTURE TYPE CD, C1D, CDE, C1DE
SALES LIGHT FIXTURE MOUNTING DETAIL
RECESSED LIGHT FIXTURE SEISMIC
MOUNTING DETAIL
N.T.S.
ALL EXTERIOR LIGHTING FIXTURES SHALL BE
E
FIXTURES LOCATED IN THE SALES REPLENISHMENT AREA SHALL BE MOUNTED AS HIGH AS POSSIBLE MAXIMUM 15' AFF TO THE
BOTTOM OF THE JOISTS OR ON UNISTRUT MOUNTED TO THE BOTTOM OF THE JOIST WHERE FIXTURE LOCATIONS DO NOT LINE
UP WITH THE JOIST. IF JOISTS ARE HIGHER THAN 15'-6" AFF TO BOTTOM CHANGE TYPE 'D' FIXTURES TO TYPE 'C' FIXTURES &
MOUNT FIXTURES AT 15'-0" AFF.
F
ELECTRICAL CONTRACTOR SHALL INSTALL ALL EMERGENCY BALLASTS IF SHIPPED SEPARATELY. COORDINATE WITH VENDOR.
G
FOR EMERGENCY FIXTURES AE, A1E, BE, CE, C1E, DE & D1E NOT SHOWN AS NIGHT LIGHTS, RUN AN EXTRA HOT CONDUCTOR
(BYPASSING ALL CONTROL) AND CONNECT TO EMERGENCY BALLAST. FIXTURES SHALL BE SHUT OFF WITH LOCAL LIGHT
FIXTURE CONTROL.
01
LIGHT FIXTURES WITH NO LETTER DESIGNATION ARE EXISTING TO REMAIN. CLEAN, RELAMP & REBALLAST TO 4' LAMP T8
SYSTEM AS REQUIRED.
02
DIGITAL SWITCH PROGRAMMED FOR SALES REPLENISHMENT DIMMING.
03
DIGITAL SWITCH. PROGRAM TO DIM SALES AREA FIXTURES.
04
MOUNT OCCUPANCY SENSOR @ +44" A.F.F.
05
IF EXISTING EXTERIOR LIGHTING / PYLON SIGNS, ETC ARE CONTROLLED BY EXISTING DISTRIBUTION SYSTEM LOCATED IN
HFT SPACE, CLEAN, RELAMP & RETROFIT EXISTING FIXTURES, REROUTE, EXTEND BRANCH CIRCUITING TO PANEL 'L' & 'P'.
06
DIGITAL SWITCH PROGRAMMED FOR SALES/SALES REPLENISHMENT 2 HOUR OVERRIDE.
5
INDICATES CIRCUIT NUMBER. TYPICAL.
INDICATES RELAY NUMBER. TYPICAL.
5
L-1,R1
L-2,R2
L-4,R4
L-3,R3
L-5,R5
L-7,R7
C1DE
EM1
L-9,R9
L-16
L-10,R10
EM1 L-16
C1D
L-18,R17
L-8,R8
C1D
C1DE
L-16,R19
C1DE
NL
C1D
C1DE
C1D
C1DE
C1D
5
L-6,R6
L-18,R17
DDE
29'-5"
DDE
6
L-11,R11
D1e
B.5
CDE
CDE
DDE
D1D
DD
SA
L-18,R17
L-17,R17
5
EM1
L-16,R19
DDE
EM1
EM1
NL
DDE
L-16
L-16
EM5
L-16
B
L-16
L-16,R19
L-18,R17
L-16,R19
5
CDE
CD
CDE
CDE
CD
CDE
CD
CDE
CD
DD
CDE
NL
40'-6"
L-12,R12
5
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
4
A.8
DD
NL
A.7
CD
DDE
DDE
CHINO, CA 91710
3
11995 CENTRAL AVE.
2
HARBOR FREIGHT TOOLS
1
EM5
L-16 L-16
8-2
N.T.S.
N.T.S.
EM1
DIMMING CONTROL.
EMERGENCY BALLASTS SHALL BE WIRED TO POWER (2) LAMPS PER FIXTURE. REWORK EMERGENCY BALLAST WIRING AS
REQUIRED TO ILLUMINATE THE TWO LAMPS THAT OCCUR ABOVE THE MAIN EGRESS AISLES.
FIXTURE TYPE AD, ADE, BD, BDE & BE
1"
L-17,R17
14-2
LIGHTING PLAN NOTES
FIXTURE TYPE CD, C1D, CDE, C1DE
ATTACHMENT OF ANTI SWAY
SUSPENSION WIRES TO FIXTURES DETAIL
W/
D
TO STRUCTURE
#12 AWG SLACK SUSPENSION
WIRES W/ 3 TIGHT TURNS IN
1-1/2" AT EACH END. TYPICAL.
10-3
C
ROOF OR FLOOR ABOVE
#12 GA. x1" BENT PLATE
10-2
8-2
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
UNISTRUT AS REQUIRED
A
5
CD
SA
L-17,R17
REVISIONS
L-18,R17
4
oc
3
os
D1d
ADE D1a
DD
D1f
ADE
a
2
DDE
CD
D1c
L-15
BE
BDE
c
CD
TYPE
CDE
L-14,R14
os
b
os
CDE
CDE
L-14,R15
CDE
L-16
EM1
L-16
EM1
EM1
D1g
os
L-18,R17
DDE
DDE
e EM1
L-16
EM5
L-16
SCALE 1/8" = 1'-0"
9
LIGHTING PLAN
L-16
A
LIGHTING PLAN
8
7
6
5
4
3
2
#
os
d
1
5
L-13,R13
L-14,R16
CDE
L-16,R19
D1b
ADE
CDE
N
ADE
BDE
BE
DATE
07/08/15
JOB NO.
15166
E1.1
SHEET NO.
10
DDE
oc
4
NL
DATE
BD
PS
OS
OS
18/3 COPPER
HDU
POWER
UTILITY
DEMAND
RESPONSE
SYMBOL
14/3 COPPER
D2
TYPICAL
CAT 6
CAT 6
SYMBOL
D1
CAT 6
TYPICAL
CAT 6
P/S
120V
MPU
DIGITAL
SWITCH
LEVITON
#RLVSW-1W
14/2 COPPER 0-10V
10/2 COPPER 120V
TO DIMMABLE
FIXTURES
10/2 COPPER 120V
TO NON-DIMMABLE
FIXTURES / LOADS
DIGITAL
SWITCH
LEVITON
#RLVSW-2W
LOCATED IN INDIVIDUAL
ROOMS SEE FLOOR
PLAN FOR QUANTITIES
& LOCATIONS
LIGHTING CONTROL SYSTEM SCHEMATIC
DIGITAL
SWITCH
LEVITON
#RLVSW-1W
RJ45 JACK NEXT TO OVERRIDE
SWITCHES FOR CONNECTION OF HDV.
DIGITAL
SWITCH
LEVITON
#RLVSW-1W
LOCATED AT
TELEPHONE BOARD.
PROGRAM SWITCH
AS 2 HOUR OVERRIDE
FOR SALE/STOCK
ROOM LIGHTING.
PROVIDE PHENOLIC
LABEL ABOVE
SWITCH DESCRIBING
FUNCTION.
LOCATED IN
MANAGERS OFFICE.
PROGRAM ONE
SWITCH TO DIM
SALES FLOOR
LIGHTING. PROVIDE
PHENOLIC LABELS
ABOVE EACH SWITCH
& DATA OUTLET
DESCRIBING
FUNCTION.
NO SCALE
LEVITON GRENMAX
#R32TC-100-RPM16-116
RELAY TYPES AS
SHOWN IN LIGHTING
CONTROL PANEL
TABLE.
PHOTO
SENSOR
DIGITAL
SWITCH
TIME CLOCK
OVERRIDE
L-1
SALES FLOOR
1
1DS
NO
NO
d
EMPLOYEE
e
L-2
SALES FLOOR
2
1DS
NO
NO
d
CUSTOMER
e
L-3
SALES FLOOR
3
1DS
NO
NO
d
EMPLOYEE
e
L-4
SALES FLOOR
4
1DS
NO
NO
d
CUSTOMER
e
L-5
SALES FLOOR
5
1DS
NO
NO
d
EMPLOYEE
e
L-6
SALES FLOOR
6
1DS
NO
NO
d
CUSTOMER
e
L-7
SALES FLOOR
7
1DS
NO
NO
d
EMPLOYEE
e
L-8
SALES FLOOR
8
1DS
NO
NO
d
CUSTOMER
e
L-9
SALES FLOOR
9
1DS
NO
NO
d
EMPLOYEE
e
L-10
SALES FLOOR
10
1DS
NO
NO
d
CUSTOMER
e
L-11
STOCK LIGHTING
11
1DS
NO
NO
f
EMPLOYEE
e
L-12
STOCK LIGHTING
12
1DS
NO
NO
f
EMPLOYEE
e
L-13
CORRIDOR LIGHTING
13
1DS
d,e
NO
g
24 HOUR
NO
L-14
MANAGER LIGHTING
14
1DS
a
NO
NO
24 HOUR
NO
L-14
CASH ROOM RECEPTACLE
15
1DS
b
NO
NO
24 HOUR
NO
L-14
BREAK LIGHTING
16
1DS
c
NO
NO
24 HOUR
NO
P/C ON T/C
OFF
P/C ON T/C
OFF
L-17,18
EXTERIOR LIGHTING
17
2TB
NO
OUTDOOR
NO
L-26
EXTERIOR SIGNS
18
2TB
NO
OUTDOOR
NO
L-16
EMERGENCY / NIGHT LIGHTING
19
1DS
NO
NO
d
24 HOUR
NO
L-20
CEILING RECEPTACLES
20
2TB
NO
NO
NO
CUSTOMER
NO
L-23
CASH ROOM RECEPTACLE
21
2TB
b
NO
NO
NO
NO
L-24
MANAGER OFFICE RECEPTACLE
22
2TB
a
NO
NO
NO
NO
NO
NO
L-25
BREAK ROOM RECEPTACLE
23
2TB
c
NO
NO
NO
NO
L-40,42
CEILING RECEPTACLES
24
2TB
NO
NO
NO
CUSTOMER
NO
-
SPARE
25
1DS
-
-
-
-
-
-
SPARE
26
1DS
-
-
-
-
-
-
SPARE
27
1DS
-
-
-
-
-
-
SPARE
28
1DS
-
-
-
-
-
-
SPARE
29
1DS
-
-
-
-
-
-
SPARE
30
2TB
-
-
-
-
-
-
SPARE
31
2TB
-
-
-
-
-
-
SPARE
32
2TB
-
-
-
-
-
TIME CLOCK SETTINGS
EMPLOYEE
90 MINUTES BEFORE OPEN 'ON', 90 MINUTES AFTER CLOSE 'OFF'
2 HOUR OVERRIDE
CUSTOMER
10 MINUTES BEFORE OPEN 'ON', 10 MINUTES AFTER CLOSE 'OFF'
2 HOUR OVERRIDE
P/C ON P/C OFF
EXTERIOR PHOTOCELL 'ON' & 'OFF'
-
P/C ON T/C OFF
EXTERIOR PHOTOCELL 'ON', 2 HOURS AFTER CLOSE 'OFF'
-
24 HOUR
LOCAL OCCUPANCY SENSOR 'ON' - 'OFF'
-
NOTES:
1) HARBOR FREIGHT THRU ITS LIGHTING VENDOR SHALL SUPPLY ALL
NECESSARY PARTS & SERVICE FOR A DIMMABLE LIGHTING CONTROL SYSTEM.
THE ELECTRICAL CONTRACTOR SHALL WIRE & INSTALL THE SYSTEM &
COORDINATE WITH THE SYSTEM MANUFACTURER PROGRAMMING, LABELING &
TRAINING RELATED TO THE SYSTEM.
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
COMPLETE 5-100% DIMMING FOR INTERIOR LIGHT FIXTURES
DAYLIGHT ZONES CONTROLLED BY INTERIOR PHOTO SENSORS
MINIMUM 4 ZONE TIME CLOCK FUNCTION
EXTERIOR ZONES CONTROLLED BY EXTERIOR PHOTOCELL / TIME CLOCK
COMBINATION
ENCLOSED ROOM DIMMING / OCCUPANCY CONTROLS
DEMAND RESPONSE CONTROL INTEGRATION WITH POWER COMPANY
SWITCHED EMERGENCY & NON-SWITCHED EMERGENCY (NIGHT LIGHT)
FIXTURES
EXHAUST FAN CONTROL
FUTURE INTEGRATION CAPABILITY INTO OWNERS NETWORK
OFFICE AREA OCCUPANCY CONTROL OF CERTAIN RECEPTACLES.
2) THE LIGHTING SYSTEM VENDOR SHALL VERIFY THAT THE 0-10V DIMMING
BALLASTS PROVIDED BY THE LIGHT FIXTURE MANUFACTURER ARE COMPATIBLE
FOR USE WITH THE LIGHTING CONTROL SYSTEM.
3) THE LIGHTING CONTROL SYSTEM MANUFACTURER SHALL INCLUDE IN THE COST
OF THE SYSTEM A MINIMUM OF 2 SITE VISITS TO AID THE ELECTRICAL
CONTRACTOR WITH THE INSTALLATION, COMMISSIONING & PROGRAMMING &
OPERATION OF THE SYSTEM. THE SECOND SITE VISIT SHALL INCLUDE A
MINIMUM OF 4 HOURS OF TRAINING WITH THE OWNERS AUTHORIZED
PERSONNEL.
4) HARBOR FREIGHT SHALL RETAIN THE SERVICES OF AN INDEPENDENT THIRD
PARTY CONTRACTOR TO PROVIDE COMPLETE COMMISSIONING OF THE
LIGHTING CONTROL SYSTEM AS WELL AS PROVIDING ALL REQUIRED
DOCUMENTATION TO THE AUTHORITY HAVING JURISDICTION TO RECEIVE A
CERTIFICATE OF OCCUPANCY. COMMISSIONING AGENT SHALL BE LICENSED BY
THE STATE OF CALIFORNIA & LOCAL AUTHORITIES TO PERFORM SAID DUTIES.
ELECTRICAL CONTRACTOR SHALL COORDINATE ON SITE WITH THE
COMMISSIONING AGENT & PROVIDE NECESSARY LABOR TO AID WITH THE
COMMISSIONING OF THE SYSTEM.
5) THE LIGHTING CONTROL PANEL SHALL BE HOUSED IN A SINGLE LOCKING NEMA 1
VENTILATED CABINET & INCLUDE THE FOLLOWING EQUIPMENT. POWER SUPPLY,
CPU, LOW VOLTAGE INPUT TERMINATION BLOCK & CONTROL RELAYS. RELAYS
MAY BE DIMMING & SWITCHING TYPE OR LATCHING TYPE. THE SYSTEM SHALL
HAVE A SHORT CIRCUIT CURRENT RATING OF 25,000 AMPERES.
6) THE LIGHTING CONTROL PANEL SHALL BE ABLE TO MONITOR A CONTACT
CLOSURE EVENT PROVIDED BY THE POWER COMPANY FOR THE DEMAND
RESPONSE REQUIREMENT OF CALIFORNIA'S TITLE 24 AND ADJUST THE DIMMING
OUTPUT OF THE RELAYS TO 85 PERCENT MAXIMUM OUTPUT AUTOMATICALLY.
7) THE LIGHTING CONTROL PANEL SHALL BE CAPABLE OF INDIVIDUAL CONTROL OF
EACH RELAY BASED ON INPUTS FROM THE INTEGRATED TIME CLOCK FUNCTION
OR REMOTE LOW VOLTAGE INPUTS SUCH AS OCCUPANCY SENSORS, PHOTO
SENSORS & DIGITAL SWITCHES.
8) INTERIOR PHOTO SENSORS SHALL BE PROGRAMMED WITH A 20 MINUTE DELAY.
SENSORS SHALL BE CALIBRATED IN THE FIELD BY BOTH THE ELECTRICAL
CONTRACTOR & THE SENSOR MANUFACTURER. SENSORS SHALL CONTROL
ONLY LIGHT FIXTURES LOCATED IN THE SAME DAY LIGHTING ZONE AS THE
SENSOR. SENSORS SHALL BE CALIBRATED TO PROVIDE MINIMUM FOOT
CANDLES VALUES AS MEASURED AT 3'-0" AFF IN THE FOLLOWING AREAS:
SALES AREA - 90FC
OFFICE AREA - 50FC
STOCK AREA - 40FC.
9) OCCUPANCY SENSORS SHALL BE PROGRAMMED WITH A 5 MINUTE DELAY.
SENSORS SHALL CONTROL LIGHT FIXTURES / DESIGNATED RECEPTACLES THAT
ARE LOCATED IN THE SAME ROOM AS THE SENSOR.
10) HANDHELD DISPLAY UNIT HAS A HIGH RESOLUTION COLOR GRAPHIC SCREEN &
SHALL CONNECT TO THE LIGHTING CONTROL SYSTEM VIA CAT 6 CABLE. UNIT
CAN BE CONNECTED TO LUMACAN PORT LOCATIONS (RELAY CABINET, LOW
VOLTAGE PANEL, DIGITAL SWITCHES): UNIT SHALL HAVE RECHARGEABLE
BATTERY.
11) DIGITAL SWITCHES SHALL BE CONNECTED TO THE LIGHTING CONTROL PANEL
VIA A CAT 6 CABLE & RJ45 CONNECTOR. SWITCHES SHALL COME WITH NUMBER
OF BUTTONS AND COLOR AS INDICATED ON PLANS.
12) ALL LOW VOLTAGE WIRING INSTALLED BY THE ELECTRICAL CONTRACTOR
SHALL BE PLENUM RATED & APPROVED FOR INTENDED USE BY THE LIGHTING
CONTROL SYSTEM MANUFACTURER. CATEGORY 6 WIRING & TERMINATIONS
SHALL BE INSTALLED, TESTED & LABELED PER THE LATEST EIA/TIA 568B
STANDARDS.
120 OR 277V
FROM BRANCH
PANEL
H
N
13) ROOMS SMALLER THAN 100 SQUARE FEET SHALL BE CONTROLLED BY A
STANDARD 120 VOLT OCCUPANCY SENSOR. LIGHT FIXTURES SHALL NOT BE
DIMMED IN THESE AREAS. SEE FLOOR PLANS FOR DETAILS.
14) THE LIGHTING CONTROL SYSTEM MANUFACTURER SHALL PROVIDE A FULL 3
YEAR WARRANTY FROM THE DATE OF OWNER ACCEPTANCE. THREE SETS OF
MAINTENANCE MANUALS SHALL BE PROVIDED TO THE OWNER WITHIN 2 WEEKS
OF OWNER ACCEPTANCE.
10/2 COPPER
STANDARD
NON-DIMMING
BALLAST
EMERGENCY
BALLAST WHEN
PRESENT
NON-DIMMABLE LIGHT
FIXTURE(S), SIGN(S) &
RECEPTACLES
REVISIONS
10/2 COPPER
10/2 COPPER
STANDARD
NON-DIMMING
BALLAST
0-10V 14/2 COPPER
NON-DIMMABLE LIGHT FIXTURE(S),
SIGN(S) & RECEPTACLES
EMERGENCY
BALLAST WHEN
PRESENT
NON-DIMMABLE LIGHT
FIXTURE(S), SIGN(S) &
RECEPTACLES
STANDARD
NON-DIMMING
BALLAST
DIMMABLE LIGHT FIXTURE(S)
0-10V
DIMMING
BALLAST
EMERGENCY
BALLAST WHEN
PRESENT
EMERGENCY
BALLAST WHEN
PRESENT
EXIT SIGN
H
N
120 OR 277V
FROM BRANCH
PANEL
H
N
120 OR 277V
FROM BRANCH
PANEL
H
N
120 OR 277V
FROM BRANCH
PANEL
LEVITON LATCHING RELAY #RELAY 2TB
LEVITON LATCHING RELAY #RELAY 1TB
LEVITON DIMMING RELAY #RELAY 1DS
NO SCALE
NO SCALE
NO SCALE
9
10
8
7
6
5
4
10/2 COPPER
3
INDIVIDUAL RELAY IN
GREENMAX PANEL
2
10/2 COPPER
1
INDIVIDUAL RELAY IN
GREENMAX PANEL
#
10/2 COPPER
DATE
TYPE
INDIVIDUAL RELAY IN
GREENMAX PANEL
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
INDOOR PHOTO SENSOR. LEVITON #ODCOP-OXW
OR CEILING MOUNTED OCCUPANCY SENSOR
LEVITON #OSC20-MOW. SEE FLOOR PLAN FOR
EXACT QUANTITIES
PS
OCC
SENSOR
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
HANDHELD DISPLAY UNIT. PROVIDE 10'-0" CAT 6
PATCH CABLE & STORE IN RELAY CABINET
RELAY
TYPE
CHINO, CA 91710
PC
RELAY #
11995 CENTRAL AVE.
PHOTOCELL ON WALL. SHIELD
FROM ARTIFICIAL LIGHT
SOURCES. LEVITON #PCOUT-000
DESCRIPTION
HARBOR FREIGHT TOOLS
LIGHTING CONTROL PANEL
CIRCUIT #
LIGHTING CONTROL
/ DIMMING SYSTEM
DATE
07/08/15
JOB NO.
15166
E1.1A
SHEET NO.
SECURITY SYSTEM NOTES
GENERAL ELECTRICAL /
COMMUNICATION / SECURITY NOTES
HFTS COMMUNICATIONS CONTRACTOR SHALL PROVIDE & INSTALL ALL CABLE, JACKS, PATCH CORDS, SPEAKERS,
TELEPHONE EQUIPMENT ETC FOR A COMPLETE LOW VOLTAGE COMMUNICATIONS SYSTEM.
(1)HONEYWELL ADEMPCO VISTA - 20P (8) ZONE CONTROL PANEL AND (1) HONEYWELL #4219 ADEMCO VISTA EXPANDER MOUNTED IN
THE CASH OFFICE ABOVE CEILING. SECURITY CONTRACTOR TO CLEARLY LABEL SECURITY PANEL.
S2
(1)HONEYWELL #6160 KEYPAD MOUNTED OUTSIDE OF THE MANAGERS OFFICE WALL. BOTTOM OF KEYPAD SHALL BE 44" AFF.
S3
(1)HONEYWELL WAVE2 2-TONE SOUNDER (SIREN HORN) ON THE MANAGERS OFFICE WALL FACING THE SALES FLOOR MOUNTED AT 12'
AFF.
02
THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUIT, BOXES, PULL STRINGS, 120V POWER SLEEVES FOR
COMMUNICATIONS WIRING & EQUIPMENT. COORDINATE WITH COMMUNICATIONS CONTRACTOR & SEE SYMBOL LEGEND
FOR ADDITIONAL DETAILS.
S4
(1)HONEYWELL #FG1625 GLASS BREAK DETECTOR CEILING MOUNTED IN THE MIDDLE OF THE VESTIBULE 5 FEET FROM THE PERIMETER
GLASS PANES ENTRANCE/EXIT DOORS. GLASS BREAK DETECTOR SHOULD FACE GLASS PANES.
03
ALL CONDUITS SHALL BE PROVIDED WITH PLASTIC BUSHINGS AT EACH END, PULL STRINGS & BE BONDED TO LOCAL
BUILDING STEEL.
S5
(1)HONEYWELL #FG1625 GLASS BREAK DETECTOR ALONG THE INTERIOR OF GLASS STOREFRONT 5 FEET FROM GLASS PANES FOR
EVERY 25 FEET OF STOREFRONT GLASS. GLASS BREAK DETECTORS SHOULD FACE GLASS PANES.
THE COMMUNICATIONS CONTRACTOR SHALL PROVIDE A COMPLETE COMMUNICATIONS SYSTEM LABELING SYSTEM.
INCLUDE BUT NOT LIMITED TO: CABLES, JACKS, PATCH PANEL RACKS, ETC. ALL LABELING SHALL COMPLY WITH
STANDARDS OF EIA/TIA 606.
07
THE COMMUNICATIONS CONTRACTOR SHALL TEST EACH CABLE AFTER INSTALLATION AND TERMINATION TO CERTIFY
THAT EACH CABLE COMPLIES WITH TIA/EIA CATEGORY 6 STANDARDS. PROVIDE DOCUMENTATION PER HFT
REQUIREMENTS.
08
SECURITY SYSTEM WIRING SHALL BE HONEYWELL #11045501 PLENUM GENESIS 22/4 STRANDED UNSHIELDED CABLE.
09
EACH SPECIFIED ALARM CONTACT AND EACH SPECIFIED ALARM SENSOR SHOULD BE WIRED IN A CLOCKWISE MANNER TO
ITS OWN DESIGNATED ZONE STARTING AT THE MAIN CUSTOMER ENTRANCE / EXIT DOOR CONTACTS.
10
S6
(1)WALL MOUNTED BOSCH #DS860 SERIES TRITECH PIR/MICROWAVE DETECTOR MOUNTED AT 9'-6" AFF FOR 60 LINEAR FOOT OF
STOREFRONT GLASS SHOOTING SIDEWAYS ACROSS THE GLASS. NO MOTION DETECTORS IN THE VESTIBULE.
S7
&(,/,1*02817('ƒ%26&+'63$125$0,&75,7(&+'(7(&725$7
72
$)))256725()5217*/$66,17+((9(17
(S6) CANNOT BE WALL MOUNTED.
E1
4'x8'x3/4" PAINTED FIRE RATED PLYWOOD FOR TELEPHONE BACKBOARD. REFER TO DETAIL ON SHEET E2.2 FOR MORE
DETAILS.
S8
(1)WALL MOUNTED BOSCH #DS860 SERIES TRITECH PIR/MICROWAVE DETECTOR ABOVE VESTIBULE DOOR FRAME FACING SALES
FLOOR MOUNTED AT 9'-6" AFF.
E2
1-1/2" EMT CONDUIT FROM 9' AFF TO JOIST SPACE HOMERUN CONTINUOUS CONDUIT TO TELEPHONE DEMARK
(COORDINATE LOCATION WITH LANDLORD). STUB CONDUIT AT 8' AFF TO TELEPHONE DEMARK.
S9
&(,/,1*02817('ƒ%26&+'63$1250$,&75,7(&+'(7(&725,17+(&(17(52)7+(&$6+2)),&($:$<)520$1<
AIR DEVICES.
E3
12"x4"x1/2" COPPER BUS BAR MOUNTED AT 84" AFF U.O.N. ON INSULATORS. PROVIDE BAR WITH (6) EQUALLY SPACED 3/8"
DIAMETER HOLES. CONNECT BAR TO HFT'S MAIN PANELS GROUND BAR WITH #4AWG COPPER CONDUCTORS.
S10
(1)WALL MOUNTED BOSCH #DS860 SERIES TRITECH PIR/MICROWAVE DETECTOR ABOVE ALL EGRESS DOOR FRAMES (EXCEPT IF
EGRESS DOOR IS ADJACENT TO RECEIVING OVERHEAD DOOR) AT 8'-0" AFF.
E4
4" DIAMETER EMT CONDUIT RISER FROM JOIST SPACE INTO TOP OF RACK.
S11
MAIN CUSTOMER ENTRANCE / EXIT DOORS: FOR NEW DORMA DOORS, WIRE INTO THE DOOR FRAME HEADER TO POINT OF
CONNECTION TERMINAL STRIP. FOR EXISTING DOORS TO REMAIN, INSTALL (1) NASCOM N505A/ST ON THE SURFACE (INTERIOR) OF
EACH DOOR.
E5
2 COMPARTMENT POWER POLE.
ELECTRICAL KEY NOTES
E6
NOTE NOT USED.
E7
20A 120 VOLT DUPLEX RECEPTACLE AT JOIST SPACE FOR SECURITY CAMERA MONITOR. COORDINATE EXACT LOCATION
WITH COMMUNICATIONS CONTRACTOR. MOUNT FLUSH IN CEILING WHERE CEILINGS OCCUR, RECEPTACLE SHALL BE
WHITE WITH WHITE COVER PLATE. COORDINATE EXACT LOCATION WITH SECURITY VENDOR.
PROVIDE 2 GANG BOX WITH 1 1/2" CONDUIT & PULL STRING TO JOIST SPACE.
EACH SPECIFIED ALARM CONTACT AND EACH SPECIFIED ALARM SENSOR SHOULD BE SPECIFICALLY LABELED ACCORDING
TO ITS DESIGNATED CONTACT OR SENSOR NAME, ITS LOCATION WITHIN THE STORE & PROGRAMMED SEPARATELY TO ITS
OWN DESIGNATED ZONE.
S12
11
THE CONTRACTOR SHOULD NEVER PROGRAM / INSTALL ANY TYPE OF LOCKOUT CODE INTO THE PANEL OR EXPANDER.
S13
(1) HONEYWELL #959 DOOR CONTACT FOR OVERHEAD DOOR.
E8
12
COORDINATE CONDUIT AND/OR JUNCTION BOXES AS REQUIRED FOR SECURITY SYSTEM.
S14
&(,/,1*02817('ƒ%26&+'63$1250$,&75,7(&+'(7(&725,17+(&(17(52)7+(5(&(,9,1*$5($02817('$7
TO 25' AFF. (NO OTHERS NEEDED IN SALES REPLENISHMENT).
E9
(3) 1 1/2" CONDUITS & PULL STRINGS FROM TOP OF SECURITY PANEL TO JOIST SPACE.
13
ALL PRODUCTS SPECIFIED ARE FEATURED IN PRODUCT BROCHURES FROM THE MANUFACTURER.
E10
1" CONDUIT WITH PULL STRING FROM AMPLIFIER TO JOIST SPACE.
E11
2" CONDUIT SLEEVE BETWEEN BACKBOARD & EXISTING TELEPHONE CABINET.
(1) NASCOM N200AU/ST DOOR CONTACT FOR EXTERIOR DOORS AND ROOF HATCH (IF APPLICABLE). (2) DOOR CONTACTS REQUIRED AT
DOUBLE DOORS.
SP
C7
C9 CAM
C9 CAM
C9 CAM
NOTE NOT USED.
E13
FLUSH SINGLE GANG BOX MOUNTED AT 48" AFF WITH 3/4" EMT CONDUIT STUB TO CEILING JOIST.
E14
FLUSH SINGLE GANG BOX AT 114" AFF WITH 3/4" EMT CONDUIT TO JOIST SPACE FOR MOTION SENSOR.
E15
3/4" CONDUIT STUBBED INTO DOOR FRAME FOR DOOR CONTACT.
E16
PROVIDE 3/4" EMT CONDUIT DROP FROM JOIST & SINGLE GANG BOX MOUNTED AT 12'-0" FOR SALES REPLENISHMENT
MOTION SENSOR.
E17
PROVIDE 2 GANG BOX AT 4" AFF. WITH 3/4" CONDUIT STUB TO JOIST SPACE FOR OVERHEAD DOOR CONTACT.
E18
PROVIDE OCTAGONAL BOX ON BOTTOM OF JOIST.
S14 E18
M
COMMUNICATIONS KEY NOTES
E17
RECEIVING AREA
DC
E2 C1
S13
C1
25 PAIR CATEGORY (3) 24AWG TWISTED PAIR CABLE. TERMINATE AT TELEPHONE DEMARK AS DIRECTED BY TELEPHONE
COMPANY. TERMINATE AT HFT PHONE BOARD ON 66 PUNCH DOWN BLOCK.
C2
(3) 4 PAIR CAT 5 24AWG CABLES BETWEEN HFT PHONE BOARD & RACK. TERMINATE ON BOTH ENDS.
C3
24"Wx43"Dx80"H FLOOR MOUNTED LOCKABLE RACK PER HFT STANDARDS.
C4
(2) 4 PAIR CAT 5 24AWG DATA CABLE BETWEEN REGISTERS & HFT RACK. TERMINATE ON BOTH ENDS.
C8
E3
E1
C2 E8
C6
E12
C6
C5
(1) 4 PAIR CAT 5 24AWG CABLE BETWEEN REGISTER & HFT RACK FOR TELEPHONE. TERMINATE ON BOTH ENDS.
C6
DAISY CHAIN (1) 24AWG 4 PAIR CAT5 PLENUM RATED CABLE FOR THE SALES AREA SPEAKERS.HOMERUN CABLE FROM
CLOSEST SPEAKER TO AMPLIFIER ON PHONE RACK. TERMINATE CABLE AT SPEAKERS & AMPLIFIER. SPEAKERS PER HFT
STANDARDS. CABLE SHALL BE BELDEN #2C18-CMP-GY-RFA-BED.
C7
DAISY CHAIN (1) 24AWG 4 PAIR CAT5 PLENUM RATED CABLE FOR THE SALES REPLENISHMENT AREA PAGING
SPEAKERS.HOMERUN CABLE FROM CLOSEST SPEAKER TO AMPLIFIER ON PHONE RACK. TERMINATE CABLE AT SPEAKERS
& AMPLIFIER. SPEAKERS PER HFT STANDARDS. CABLE SHALL BE BELDEN #2C18-CMP-GY-RFA-BED.
C8
(1) 4 PAIR CAT 5 24AWG CABLE BETWEEN DOCK DOOR & HFT RACK FOR TELEPHONE. TERMINATE ON BOTH ENDS.
C9
SECURITY CAMERA & (1) CAT 5 24AWG 4 PAIR CABLE FROM CAMERA TO RACK, TERMINATE CABLES AT BOTH ENDS.
C10
(1) CAT 5 24AWG CABLE FROM TRAFFIC COUNTER TO HFT RACK. TERMINATE AT BOTH ENDS.
C11
(1) CAT 5 24AWG CABLE FROM WIRELESS ACCESS POINT TO HFT RACK. TERMINATE AT BOTH ENDS.
C12
(1) CAT 5 24AWG 4 PAIR CABLE FROM TIME CLOCK (CENTERED BETWEEN WINDOW & DOOR) TO HFT RACK. TERMINATE AT
BOTH ENDS.
C13
(2) CAT 5 24AWG 4 PAIR CABLES FROM PRINTER/FAX TO HFT RACK. TERMINATE AT BOTH ENDS.
C14
(2) CAT 5 24AWG 4 PAIR CABLES FROM MANAGERS WORK STATION TO HFT RACK. TERMINATE AT BOTH ENDS.
C15
(2) CAT 5 24AWG 4 PAIR CABLES FROM MANAGERS WALL TO HFT RACK. TERMINATE AT BOTH ENDS.
C16
NOTE NOT USED.
C17
(1) RG59 COAXIAL CABLE FROM CCTV MONITOR TO RACK. TERMINATE AT BOTH ENDS.
C5
C18
(1) CAT 5 24AWG 4 PAIR CABLE FROM CASH ROOM TO HFT RACK. TERMINATE AT BOTH ENDS.
C4
C19
(1) RJ31X PHONE JACK MOUNTED AT +101" AFF FOR SECURITY PANEL.
SP
SP
B.5
E10
20'-0"
52'-0"
C5
GB S5
C4
E5
M
C4
C9 CAM
E14
DC
S10
C9 CAM
C11
E15 S12
WAP
B
S12
DC
S11 E15 DC
E7
CAM
GB S5
C9
S11 E15 DC
A.8
SALES AREA
C17
SALES REPLENISHMENT
C10
A.7
E5
C4
C9 CAM
COMMUNICATIONS SYMBOL LEGEND
SYMBOL
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
06
D) ALL EXISTING WIRING (POWER & COMMUNICATION) THAT IS TO REMAIN SHALL BE REWORKED OR REPLACED WITH CODE
COMPLIANT MATERIAL & SUPPORTS. ANY EXISTING SURFACE MOUNTED CONDUITS SHALL BE REMOVED OR RELOCATED SO THAT
THEY ARE IN THE JOIST SPACE OR WITHIN WALL CAVITIES.
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
THE COMMUNICATIONS CONTRACTOR SHALL PROVIDE A COMPLETE DATA COMMUNICATIONS SYSTEM WITH EQUIPMENT,
PATCH PANELS, CABLE, JACKS, J HOOKS, BOXES, LABELING, TESTING, ETC. ALL EQUIPMENT SHALL BE SUPPLIED &
INSTALLED PER CATEGORY 6 (BICSI AND EIA/TIA) INSTALLATION STANDARDS.
C) ALL UNUSEDWIRE (POWER & COMMUNICATION) SHALL BE REMOVED.
CHINO, CA 91710
ALL LOW VOLTAGE CABLES SHALL BE PLENUM RATED.
05
B) REMOVE AND/OR RELOCATE EXISTING DEVICES ON WALLS OR CEILING BEING REMOVED. COORDINATE SUCH CONDITIONS WITH
ARCHITECTURAL DRAWINGS.
11995 CENTRAL AVE.
04
A) NO ATTEMPT HAS BEEN MADE TO INDICATE ALL EXISTING ELECTRICAL DEVICES, LIGHT FIXTURES, COMMUNICATION DEVICES,
WIRING, CONDUIT, ETC. TO BE REMOVED AND/OR RELOCATED. HOWEVER, THE ELECTRICAL CONTRACTOR SHALL FIELD VERIFY
THE EXTENT OF DEMOLITION PRIOR TO SUBMITTING BID.
HARBOR FREIGHT TOOLS
01
GENERAL ELECTRICAL DEMOLITION NOTES
S1
DESCRIPTION
GB S5
20'-0"
52'-0"
CAM
SECURITY CAMERA
DC
DOOR CONTACT
GB
GLASS BREAK DETECTOR
M
&(,/,1*02817('ƒ'(7(&725
REVISIONS
S6
C7
E14 M
SP
C6
C6
SP
C12
SP
E3
WIRELESS ACCESS POINT
9
10
8
7
SPEAKERS & AMPLIFIER
6
SP
S9
5
DATA CABLE
4
E4
WAP
MEN
C9
SPEAKERS
3
S S3
M
CA
C3
CAM
S2
K E13
C9
WALL MOUNTED MOTION DETECTOR
POWER POLE
BREAK ROOM
2
+44"
MANAGER
TYPE
WOMEN
C13
DATE
M
1
C9
#
CA
M
SP
C14
M
CASH ROOM
C9 CAM
C18
C19
E15 S12 DC
C9 CAM
E14 S10
M
A
S1 E9
COMMUNICATIONS PLAN
SCALE 1/8" = 1'-0"
COMMUNICATIONS
PLAN
DATE
07/08/15
JOB NO.
15166
E1.2
SHEET NO.
N
ELECTRICAL SYMBOL LEGEND
WIRE LEGEND
SYMBOL
Fill
Tag
(2) #12, #12GND-3/4"C
Fill
4-4
(4) #4, #4GND-1 1/4 "C
4/0-3
Fill
12-3
(3) #12, #12GND-3/4"C
2-2
(2) #2, #4GND-1"C
4/0-4
(4) #4/0, #2GND-2 1/2"C
12-4
(4) #12, #12GND-3/4"C
2-3
(3) #2, #4GND-1 1/4 "C
300-2
(2) 300KCMIL, #1/0GND-2"C
10-2
(2) #10, #10GND-3/4"C
2-4
(4) #2, #4GND-1 1/4" C
300-3
(3) 300KCMIL, #1/0GND-21/2" C
10-3
(3) #10, #10GND-3/4"C
1-2
(2) #1, #4GND-1 1/4" C
300-4
(4) 300KCMIL, #1/0GND-2 1/2"C
10-4
(4) #10, #10GND-3/4"C
1-3
(3) #1, #4GND-1 1/4" C
350-2
(2) 350KCMIL, #3/0GND-2"C
8-2
(2) #8, #8GND-3/4"C
1-4
(4) #1, #4GND-1 1/2" C
350-3
(3) 350KCMIL, #3/0GND-2 1/2"C
8-3
(3) #8, #8GND-1"C
1/0-2
(2) #1/0, #2GND-1 1/4" C
350-4
(4) 350KCMIL, #3/0GND-3"C
8-4
(4) #8, #8GND-1"C
1/0-3
(3) #1/0, #2GND-1 1/2" C
500-2
(2) 500KCMIL, #3/0GND-2 1/2"C
6-2
(2)#6, #6GND-1"c
1/0-4
(4) #1/0, #2GND-1 1/2" C
500-3
(3) 500KCMIL, #3/0GND-3"C
6-3
(3) #6, #6GND-1"C
3/0-2
(2) #3/0, #2GND-1 1/2" C
500-4
(4) 500KCMIL, #3/0GND-3 1/2" C
6-4
(4) #6, #6GND-1"C
3/0-3
(3) #3/0, #2GND-2" C
600-2
(2) 600KCMIL, #3/0GND-3"C
4-2
(2) #4, #4GND-1"C
3/0-4
(4) #3/0, #2GND-2" C
600-3
(3) 600KCMIL, #3/0GND-3 1/2" C
DOUBLE DUPLEX RECEPTACLE - 20 AMPERE, 125 VOLT - MOUNTED AT 15" AFF UON (TO BOTTOM)
4-3
(3) #4, #4GND-1"C
4/0-2
(2) #4/0, #2GND-2" C
600-4
(4) 600KCMIL, #3/0GND-3 1/2" C
DUPLEX RECEPTACLE MOUNTED IN A FLUSH FLOOR BOX. PROVIDE ALUMINIUM DUAL FLIP LID ACTIVATION
KIT.
HOMERUN TO PANEL "A" INDICATING CIRCUIT NUMBER(S) - ALL WIRING SHALL BE #12 WITH EQUIPMENT GROUND WIRE UON
(INCREASE TO #10 FOR CIRCUITS OVER 100 FT.) - ALL HOMERUNS ARE TO A 20 AMPERE, 1 POLE CIRCUIT BREAKER U.O.N. QUANITY OF CONDUCTORS AS NECESSARY TO ACCOMMODATE CIRCUITS AND CONTROL INDICATED. CROSS HATCHES
INDICATE REQUIRED LIGHTING CONTROL U.O.N.
(3) #4/0, #2GND-2" C
A-2
A-2
CONDUIT RUN IN OR UNDER FLOOR SLAB (1" C. MINIMUM, UON)
SCHEDULE 40 PVC CONDUIT RUN AT 36" BELOW FINISHED GRADE. CONTRACTOR SHALL BORE BELOW
STREET. COORDINATE WITH CITY. TRANSITION TO HEAVYWALL RIGID STEEL CONDUIT 2 FEET BELOW
GRADE WHEN CONDUIT IS TO RISE ABOVE GRADE.
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
Tag
DESCRIPTION
Tag
No Tag
SWITCH - 20 AMPERE, 120/277 VOLT, SINGLE POLE - MTD AT 48" AFF UON ("a"=DENOTES
SWITCHING,"K" = KEY OPERATED, "P" = PILOT LIGHT, "IL"= ILLUMINATED TOGGLE, "3" =
THREE-WAY, "4" = FOUR-WAY, "M"= MANUAL MOTOR STARTER. "D"= DIMMER SWITCH
"LUTRON NOVA SERIES")
S
DUPLEX RECEPTACLE - 20 AMPERE, 125 VOLT - MOUNTED AT 15" AFF UON (TO BOTTOM). SUBSCRIPT "T" DENOTES TAMPER
RESISTANT. C=WHITE RECEPTACLE & COVER MOUNTED FLUSH IN CEILING. IF CEILING IS MORE THEN 15" ABOVE TOP OF
WINDOW MOUNT RECEPTACLES 12" ABOVE TOP OF WINDOW. IG= ISOLATED GROUND TYPE. TVSS= SURGE PROTECTED TYPE.
NOTE: CONDUIT SIZES ARE FOR EMT & IMC. FOR PVC & RGC INCREASE CONDUIT BY (1) TRADE SIZE. FOR
FLEXIBLE CONDUIT SIZES REFER TO NEC. ALL WIRE SIZES SHOWN ON DRAWINGS ARE FOR COPPER CONDUCTORS
JUNCTION BOX - MOUNTING HEIGHT AND SIZE AS REQUIRED BY CODE OR AS NOTED ON
DRAWINGS
J
J
JUNCTION BOX - FOR SIGN. PROVIDE LOCAL DISCONNECT & COORDINATE LOCATION & MOUNTING HEIGHT WITH SIGN
CONTRACTOR IN THE FIELD.
S
HEAVY DUTY NON FUSIBLE DISCONNECT SWITCH.
SPECIAL NEMA CONFIGURED OUTLET MOUNTED AS REQUIRED TO SERVE APPLIANCE. VERIFY
CONFIGURATION PRIOR TO ROUGH-IN AND ADJUST WIRING AND CIRCUIT BREAKER SIZE AS REQUIRED.
GROUND ROD- 3/4" X 10' COPPER CLAD
GR
WIRE LEGEND TAG (12= CONDUCTOR SIZE, 4= QUANTITY OF CONDUCTORS.)
12-4
DUCT MOUNTED SMOKE DETECTOR. SEE DETAIL THIS SHEET.
DD
AFF
ABOVE FINISHED FLOOR
AC
INDICATES DEVICE MOUNTED AT 8" ABOVE COUNTER
EC
ELECTRICAL CONTRACTOR
GFI
GROUND FAULT CIRCUIT INTERRUPTER TYPE
UON
UNLESS OTHERWISE NOTED
IG
ISOLATED GROUND
EX
EXISTING TO REMAIN
Soc
a,b
WALL MOUNTED MULTI TECHNOLOGY DUAL CIRCUIT OCCUPANCY
SENSOR WITH WHITE FINISH HUBBEL # LHMTD2W
Soc
a
WALL MOUNTED MULTI TECHNOLOGY SINGLE CIRCUIT
OCCUPANCY SENSOR WITH WHITE FINISH HUBBEL # LHMTSW
OC
CEILING MOUNTED OCCUPANCY SENSOR
HUBBELL #OMNIDT1000
20A 120 VOLT RECEPTACLE MOUNTED AT 15" AFF U.O.N.
CONTROLLED BY LOCAL OCCUPANCY SENSOR. PROVIDE
COVERPLATE WITH BLACK SCREENED LETTERS "SWITCHED".
R
CONTRACTOR SHALL COORDINATE ALL LOCAL REQUIREMENTS WITH
REGARDS TO CONNECTING THE ELECTRICAL SERVICE. METER, CT BOXES,
DISCONNECT SWITCHES ETC. SHALL BE PURCHASED & INSTALLED PER
THE LOCAL POWER COMPANY REQUIREMENTS & AUTHORITY HAVING
JURISDICTION. COORDINATION SHALL OCCUR WITHIN 1 WEEK OF
RECEIVING CONTRACT. INCLUDE IN BID ANY EXPEDITED SHIPPING
CHARGES FOR ANY LONG LEAD ELECTRICAL DISTRIBUTION EQUIPMENT.
COORDINATE ANY REQUIRED SERVICE SHUT DOWNS WITH LANDLORD.
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
COMMUNICATION OUTLET MOUNTED IN A FLUSH FLOOR BOX. PROVIDE (4) JACKS AND
AN ALUMINIUM DUAL FLIP LID ACTIVATION KIT.
D
CHINO, CA 91710
FLUSH COMMUNICATIONS OUTLET WITH TWO GANG BOX SINGLE GANG EXTENSION RING, MOUNTED AT 15" AFF U.O.H. (TO
BOTTOM) AND 1" CONDUIT, STUBBED TO NEAREST ACCESSIBLE CEILING. PROVIDE BLANK COVER. W=MOUNTED 54" AFF.
11995 CENTRAL AVE.
A.F.
HARBOR FREIGHT TOOLS
HEAVY DUTY FUSIBLE DISCONNECT SWITCH. FUSE SIZE TO BE DETERMINED FROM EQUIPMENT TO
BE SERVED NAMEPLATE DATA
15
2 SETS
350-4
1/0-4
EXISTING
120/208V 3PH 4WSN
600A MAIN SERVICE
DISCONNECT SWITCH
WITH INTEGRAL METER BASE
1/0-4
M
M
REVISIONS
W/#2 ISO GND
L
P
600A
TYPE
150/3
150/3
9
10
8
7
6
5
4
3
2
1
ISO GND BUS
#
DATE
600A
EXISTING 600 AMP
SERVICE CONDUCTORS
EXISTING GROUNDING
ELECTRODE SYSTEM
ONE LINE DIAGRAM
& DETAILS
DATE
07/08/15
JOB NO.
15166
120/208V 3PH 4WSN ONE LINE DIAGRAM
N.T.S.
E2.0
SHEET NO.
L
LIGHT FIXTURE SCHEDULE
SECURITY LIGHTING#
R243BLW-E100-DIM
PHILIPS
F32T8-ADV841
(3) LAMPS
BD
2X4 (2) LAMP T8 FLUORESCENT TROFFER FOR
INSTALLATION IN LAY-IN ACOUSTIC CEILING TILE
GRID
SECURITY LIGHTING#
R242BLW-DIM
PHILIPS
F32T8-ADV841
(2) LAMPS
CKT.
1.3
SALES LIGHTING
2
C
C
20/1
1.3
SALES LIGHTING
4
C
C
20/1
1.2
SALES LIGHTING
6
C
C
20/1
1.3
SALES LIGHTING
8
C
20/1
1.1
SALES LIGHTING
10
C
20/1
1.0
REPLENISHMENT LIGHTING
12
C
20/1
0.5
BREAK ROOM, OFFICE LIGHTING
14
C,L
20/1
0.7
EMERGENCY LIGHTING
16
C
20/1
1.0
EXTERIOR LIGHTING
18
C
C
20/1
1.2
INTERIOR SIGN
20
C
-
20/1
-
SPARE
22
MANAGERS OFFICE RECEPTACLES
24
EXTERIOR SIGN
26
3
SALES LIGHTING
1.3
20/1
5
SALES LIGHTING
1.3
20/1
7
SALES LIGHTING
1.3
20/1
9
SALES LIGHTING
1.3
20/1
C
11
SALES REPLENISHMENT LIGHTING
0.9
20/1
C
13
CORRIDOR LIGHTING
0.4
20/1
C
15
TOILET ROOM LIGHTING
0.2
20/1
-
17
EXTERIOR LIGHTING
0.8
20/1
C
0
20/1
MISC.
HVAC
REC.
DESCRIPTION
LTG.
CKT
SECURITY LIGHTING#
TC232B-120-CSHC-CS8-COUPLER-L-E96-DIM
114
SECURITY LIGHTING#
C232B-120-CSHC-CS8-COUPLER-L-DIM
PHILIPS
F32T8-ADV841
(2) LAMPS
120/277
58
SALES & STORAGE AREA
FOR OPEN CEILINGS PROVIDE CHAIN & INSTALL AT 12'-0"(CSHC). RUN IN
CONTINUOUS ROWS WHERE SHOWN. PROVIDED WITH COUPLER. NOTE #3
PHILIPS
F32T8-ADV841
(2) LAMPS
SPARE
58
SALES & STORAGE AREA
FOR OPEN CEILINGS PROVIDE CHAIN & INSTALL AT 12'-0"(CSHC). RUN IN CONTINUOUS ROWS
WHERE SHOWN. EMERGENCY BALLAST. SEE GENERAL NOTE #1,2,3. PROVIDED WITH COUPLER.
19
120/277
21
SPARE
1.2
20/1
SALES & STORAGE AREA
SURFACE MOUNTED. FOR CEILING MOUNT PROVIDE CEILING CLIPS & SUPPORT FROM STRUCTURE AS
REQUIRED BY CODE. FOR JOIST MOUNT, PROVIDE MOUNTING HARDWARE & UNISTRUT AS REQUIRED.
RUN IN CONTINOUS ROWS WHERE SHOWN. PROVIDED WITH COUPLER
SALES & STORAGE AREA
SURFACE MOUNTED. FOR CEILING MOUNT PROVIDE CEILING CLIPS & SUPPORT FROM STRUCTURE AS
REQUIRED BY CODE. FOR JOIST MOUNT, PROVIDE MOUNTING HARDWARE & UNISTRUT AS REQUIRED. RUN IN
CONTINOUS ROWS WHERE SHOWN. EMERGENCY BALLAST. SEE GENERAL NOTE #1,2. PROVIDED WITH COUPLER
SALES & STORAGE AREA
SURFACE MOUNTED. FOR CEILING MOUNT PROVIDE CEILING CLIPS & SUPPORT FROM STRUCTURE AS
REQUIRED BY CODE. FOR JOIST MOUNT, PROVIDE MOUNTING HARDWARE & UNISTRUT AS REQUIRED.
RUN IN CONTINOUS ROWS WHERE SHOWN. PROVIDED WITH COUPLER
SALES & STORAGE AREA
SURFACE MOUNTED. FOR CEILING MOUNT PROVIDE CEILING CLIPS & SUPPORT FROM STRUCTURE AS
REQUIRED BY CODE. FOR JOIST MOUNT, PROVIDE MOUNTING HARDWARE & UNISTRUT AS REQUIRED. RUN IN
CONTINOUS ROWS WHERE SHOWN. EMERGENCY BALLAST. SEE GENERAL NOTE #1,2. PROVIDED WITH COUPLER
23
CASH ROOM RECEPTACLES
1.0
20/1
C
C
20/1
25
BREAK ROOM RECEPTACLES
1.0
20/1
C
C
20/1
1.2
27
SPARE
-
20/1
-
-
20/1
-
SPARE
28
29
SPARE
-
20/1
-
-
20/1
-
SPARE
30
31
SPARE
-
20/1
-
-
20/1
-
SPARE
32
33
SPARE
-
20/1
-
-
20/1
-
SPARE
34
35
SPARE
-
20/1
-
-
20/1
-
SPARE
36
37
SPARE
-
20/1
-
-
20/1
-
SPARE
38
-
C
20/1
0.2
-
CEILING RECEPTACLES
40
-
-
20/1
0.2
-
CEILING RECEPTACLES
42
1.4
11.8
120/277
PHILIPS
F32T8-ADV841
(4) LAMPS
D1DE
SECURITY LIGHTING#
C232B-120-CS8-COUPLER-L-E96-DIM
PHILIPS
F32T8-ADV841
(2) LAMPS
114
120/277
114
120/277
120/277
58
120/277
58
SECURITY LIGHTING#
R242BLW-E100
PHILIPS
F32T8-ADV841
(2) LAMPS
120/277
EM1
SELF-POWERED EXIT SIGN WITH LED LAMPS UNIVERSAL MOUNTED - SINGLE FACE NOTE #4
SECURITY LIGHTING#
PRB
INCLUDED
120/277
7
SALES & STORAGE AREA
EM2
SELF-POWERED EXIT SIGN WITH LED LAMPS UNIVERSAL MOUNTED - DOUBLE FACE NOTE #4
SECURITY LIGHTING#
PRB
INCLUDED
120/277
7
SALES & STORAGE AREA
EM3
SURFACE MOUNTED 2 HEAD EMERGENCY
UNIT WITH REMOTE CAPACITY
DUAL LITE#
LZ30
INCLUDED
120/277
15
SALES & STORAGE AREA
EM4
EXTERIOR WP 2 LAMP REMOTE HEADS
SECURITY LIGHTING#
2A6H6A-MPWP2
INCLUDED
6
-
EXTERIOR
EM5
EXTERIOR WP LED EMERGENCY FIXTURE
COOPER LIGHTING#
AEL2-31-BZ
INCLUDED
120/277
15
EXTERIOR
SA
EXTERIOR WALL MOUNTED FIXTURE
COOPER LIGHTING#
XTOR2A
LED
120/277
20
EXTERIOR WALL MOUNTED FIXTURE AT 15'-0" ABOVE FINISHED GRADE
NOTE #5
TOILET ROOM
EMERGENCY BALLAST. SEE GENERAL NOTE #1,2. VERIFY THAT EM BALLAST IS WIRED FOR
APPROPRIATE VOLTAGE PRIOR TO WIRING FIXTURE. FACTORY INSTALLED WHIP CONNECTION.
58
41
REMOTE
CAPACITY
MOUNT EXIT SIGNS A MAXIMUM OF 1'-0" ABOVE TOP OF EGRESS DOOR. PROVIDE PENDANT IF REQUIRED. IN SALES AREA MOUNT EXIT SIGNS 6" BELOW TYPE 'C' FIXTURES.
IN SALES REPLENISHMENT AREA MOUNT EXIT SIGNS 12" BELOW TYPE D FIXTURES.
BUS RATING: 600A
A.I.C.: 65,000
600A MAIN LUGS ONLY
C/B
MISC.
11.7
1
11.7
RTU-1
125/3
REMARKS
AMPS CONN.:
443.3
AMPS DEMAND.:
468.1
-
-
-
-
C/B
BREAKER REMARKS
C-CONTACTOR CONTROLLED, S-SHUNT TRIP,
L-LOCK ON, G-GFCI, A-ARC FAULT,
SW-SWITCHING DUTY, HA-HACR, HI-HID
KVA CONNECTED
MISC.
HVAC
REC.
DESCRIPTION
LTG.
8.7
100/3
CKT
2
8.7
RTU-2
4
11.7
-
-
8.7
6
7
11.7
-
-
3.6
8
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
125/3
11.7
11.7
11
13
21.2
PANEL 'L'
4.6
4.0
150/3
17
-
19
-
SPARE
125/3
-
23
25
125/3
SPACE
29
TOTALS
21.2
LOAD
4.6
CONNECTED
70.2
4.0
40/3
3.6
RTU-4
10
3.6
12
14
150/3
CONNECTED
DEMAND
LIGHTING
21.2
26.5
RECEPTACLE
4.6
4.6
HVAC
0.0
0.0
MISC
4.0
4.0
MOUNTING: SURFACE
LOCATION:
BUS RATING: 200A
A.I.C.: 65,000
CKT.
5
RTU-3
LOAD
TOTALS
AMPS CONN.:
63.1
AMPS DEMAND.:
55.3
BREAKER REMARKS
C-CONTACTOR CONTROLLED, S-SHUNT TRIP,
L-LOCK ON, G-GFCI, A-ARC FAULT,
SW-SWITCHING DUTY, HA-HACR, HI-HID
6.5
0.4
15.8
PANEL 'P'
16
18
60/3
-
20
SPARE
22
-
LTG.
REC.
HVAC
C/B
MISC.
REMARKS
C/B
KVA CONNECTED
MISC.
HVAC
REC.
DESCRIPTION
LTG.
CKT
ISO GND RECEPTACLE
0.4
20/1
-
-
20/1
0.4
ISO GND RECEPTACLE
2
3
GENERAL RECEPTACLE
0.8
20/1
-
-
20/1
0.8
GENERAL RECEPTACLE
4
5
CASHWRAP RECEPTACLE (D) (ISO GND.)
0.8
20/1
-
-
20/1
0.8
CASHWRAP RECEPTACLE
6
7
CASHWRAP RECEPTACLE (D) (ISO GND.)
0.8
20/1
-
-
20/1
0.4
SALES OUTLET
8
9
CASHWRAP RECEPTACLE (D) (ISO GND.)
0.8
20/1
-
-
20/1
11
CASHWRAP RECEPTACLE (D) (ISO GND.)
0.8
20/1
-
-
20/1
13
SPARE
20/1
-
-
20/1
15
HAND DRYER
1.2
20/1
-
-
20/1
0.6
17
HAND DRYER
1.2
20/1
-
-
20/1
0.4
ISO GND RECEPTACLE
18
19
ISO GND RECEPTACLE
20/1
-
-
20/1
0.4
ISO GND RECEPTACLE
20
21
REFRIGERATOR
20/1
-
-
30/1
SPARE
22
23
BREAKROOM RECEPTACLE
0.4
20/1
-
-
20/1
0.8
BREAKROOM RECEPTACLE
24
25
SECURITY ISO GND RECEPTACLE
0.4
20/1
-
-
20/1
0.4
TELEPHONE ISO GND RECEPTACLE
26
27
SECURITY ISO GND RECEPTACLE
0.4
20/1
-
-
20/1
0.8
TOILET ROOM RECEPTACLE
28
29
MUSIC RECEPTACLE
0.8
20/1
-
-
20/1
0.2
TIME CLOCK
30
31
DOOR BELL
20/1
-
L
20/1
FACP
32
33
ROOF RECEPTACLE
20/1
-
-
20/1
STOCK RECEPTACLE
34
35
SPARE
-
20/1
-
-
20/1
1.5
WATER HEATER
36
37
SPARE
-
20/1
-
L
20/1
0.1
DUCT DETECTOR
38
39
SALES RECEPTACLE
20/1
-
-
20/1
-
SPARE
40
41
RESTROOM EXHAUST FAN
20/1
C
-
20/1
-
SPARE
42
0.00
TOTALS
-
0.4
0.8
0.2
1.0
0.8
0.4
0.00
TOTALS
8.6
0.4
3.4
0.8
1.0
-
-
0.5
0.4
3.1
LOAD
CONNECTED
DEMAND
LIGHTING
-
-
RECEPTACLE
15.8
12.9
HVAC
0.4
0.5
MISC
6.5
6.5
0.00
7.2
CASHWRAP RECEPTACLE
10
POWER DOORS
12
SPARE
14
ISO GND RECEPTACLE
16
REVISIONS
24
26
60/3
KVA CONNECTED
DESCRIPTION
1
SPARE
28
30
6.5
37.3
15.8
0.00
TOTALS
DEMAND
LIGHTING
21.2
26.5
RECEPTACLE
20.4
15.2
HVAC
107.5
116.3
MISC
10.5
10.5
9
HVAC
0.00
LIGHTING & PANEL
SCHEDULES
DATE
07/08/15
JOB NO.
15166
E2.1
SHEET NO.
10
REC.
4.0
8
LTG.
0.00
COMMENTS: PROVIDE ISO GND BUS
COMMENTS:
DESCRIPTION
3.2
VOLTAGE: 120/208V-3PH-4W
REFER TO SHEET A0.0
FOR LIGHTING VENDOR
CONTACT INFORMATION.
VOLTAGE: 120/208V-3PH-4W
KVA CONNECTED
8.4
200A MAIN LUG ONLY
M
LOCATION:
2.0
P
FIXTURES SHALL BE SUPPLIED WITH A 0-10V DIMMING BALLAST FOR 5-100 PERCENT DIMMING CAPABILITY AND RAPID START SOCKETS BALLASTS SHALL BE ADVANCE
MARK 7 SERIES.
MOUNTING: SURFACE
25/2
PROVIDE WITH 2 HEAD MOUNTING PLATE.
WIRE TO EM3.
MANUFACTURER SHALL WIRE EMERGENCY BALLAST TO OPERATE 2 LAMPS. THE LAMPS SHALL BE RIGHT NEXT TO EACH OTHER SO ONLY 4' OF 8' FIXTURE IS ILLUMINATED
BY THE EMERGENCY BALLAST.
4.
CHARGER
EMERGENCY LIGHTS EQUIPPED WITH
90 MINUTE BATTERY BACK-UP. WIRE
AHEAD OF LOCAL CONTROL
FOR EMERGENCY FIXTURES ADE, A1DE, BDE, CDE, C1DE, DDE & D1DE NOT SHOWN AS NIGHT LIGHTS, RUN AN EXTRA HOT CONDUCTOR (BYPASSING ALL CONTROL) AND
CONNECT TO EMERGENCY BALLAST. FIXTURES SHALL BE SHUT OFF WITH LOCAL LIGHT FIXTURE CONTROL.
FOR ALL CHAIN MOUNTED FIXTURES E.C. SHALL PROVIDE EXTENSIONS AS REQUIRED TO INSTALL LIGHT FIXTURES AT HEIGHTS AS NOTED.
2.0
TOTALS
LIGHTING FIXTURE SCHEDULE NOTES (SEE REMARKS)
3.
39
1.0
6
SECURITY LIGHTING#
TC232B-120-CS8-COUPLER-L-DIM
4' - 2 LAMP T8 SURFACE MOUNTED STRIP
FLUORESCENT FIXTURE WITH 1100 LUMEN BATTERY
BALLAST
27
20/1
SALES & STORAGE AREA
FOR OPEN CEILINGS PROVIDE CHAIN & INSTALL AT 12'-0"(CSHC). RUN IN CONTINUOUS ROWS WHERE
SHOWN. EMERGENCY BALLAST. SEE GENERAL NOTE #1,2,3. PROVIDED WITH COUPLER.
D1D
21
C
PHILIPS
F32T8-ADV841
(4) LAMPS
PHILIPS
F32T8-ADV841
(2) LAMPS
15
C/B
C
SALES & STORAGE AREA
FOR OPEN CEILINGS PROVIDE CHAIN & INSTALL AT 12'-0"(CSHC). RUN IN
CONTINUOUS ROWS WHERE SHOWN. PROVIDED WITH COUPLER. NOTE #3
SECURITY LIGHTING#
C232B-120-CS8-COUPLER-L-DIM
9
KVA CONNECTED
REMARKS
20/1
114
4' - 2 LAMP T8 SURFACE MOUNTED STRIP
FLUORESCENT FIXTURE
3
C/B
MISC.
120/277
DDE
CKT.
HVAC
PHILIPS
F32T8-ADV841
(4) LAMPS
PHILIPS
F32T8-ADV841
(4) LAMPS
5.
REC.
0.9
SECURITY LIGHTING#
TC232B-120-CSHC-CS8-COUPLER-L-DIM
SECURITY LIGHTING#
TC232B-120-CS8-COUPLER-L-E96-DIM
2.
LTG.
SALES LIGHTING
114
8' - 4 LAMP T8 SURFACE MOUNTED STRIP
FLUORESCENT FIXTURE WITH 1100 LUMEN BATTERY
BALLAST
1.
KVA CONNECTED
DESCRIPTION
1
120/277
4' - 2 LAMP T8 CHAIN MOUNTED STRIP FLUORESCENT SECURITY LIGHTING#
C232B-120-CSHC-CS8-COUPLER-L-E96-DIM
FIXTURE WITH 1100 LUMEN BATTERY BALLAST
BE
COMMENTS:
SECURITY LIGHTING#
R242BLW-E100-DIM
C1DE
2X4 (2) LAMP T8 FLUORESCENT TROFFER WITH
400 LUMEN BATTERY BALLAST FOR INSTALLATION
IN LAY-IN ACOUSTIC CEILING TILE GRID
TOILET ROOM
FACTORY INSTALLED WHIP CONNECTION
VOLTAGE: 120/208V-3PH-4W
TOILET ROOM
EMERGENCY BALLAST. SEE GENERAL NOTE #1,2. VERIFY THAT EM BALLAST IS WIRED FOR
APPROPRIATE VOLTAGE PRIOR TO WIRING FIXTURE. FACTORY INSTALLED WHIP CONNECTION.
4' - 2 LAMP T8 CHAIN MOUNTED STRIP
FLUORESCENT FIXTURE
8' - 4 LAMP T8 SURFACE MOUNTED STRIP
FLUORESCENT FIXTURE
58
BREAKER REMARKS
C-CONTACTOR CONTROLLED, S-SHUNT TRIP,
L-LOCK ON, G-GFCI, A-ARC FAULT,
SW-SWITCHING DUTY, HA-HACR, HI-HID
PHILIPS
F32T8-ADV841
(2) LAMPS
C1D
DD
120/277
97.4
7
8' - 4 LAMP T8 CHAIN MOUNTED STRIP FLUORESCENT
FIXTURE WITH 1100 LUMEN BATTERY BALLAST
CDE
88
82.7
5
8' - 4 LAMP T8 CHAIN MOUNTED STRIP
FLUORESCENT FIXTURE
120/277
OFFICES
EMERGENCY BALLAST. SEE GENERAL NOTE #1,2. VERIFY THAT EM BALLAST IS WIRED FOR
APPROPRIATE VOLTAGE PRIOR TO WIRING FIXTURE. FACTORY INSTALLED WHIP CONNECTION.
120/277
AMPS CONN.:
AMPS DEMAND.:
4
CD
88
OFFICES
FACTORY INSTALLED WHIP CONNECTION.
3
BDE
2X4 (2) LAMP T8 FLUORESCENT TROFFER WITH
400 LUMEN BATTERY BALLAST FOR INSTALLATION
IN LAY-IN ACOUSTIC CEILING TILE GRID
A.I.C.: 65,000
200A MAIN LUG ONLY
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
ADE
2X4 (3) LAMP T8 FLUORESCENT TROFFER WITH
400 LUMEN BATTERY BALLAST FOR INSTALLATION
IN LAY-IN ACOUSTIC CEILING TILE GRID
LOCATION:
BUS RATING: 200A
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
PHILIPS
F32T8-ADV841
(3) LAMPS
MOUNTING: SURFACE
CHINO, CA 91710
SECURITY LIGHTING#
R243BLW-DIM
REMARKS
11995 CENTRAL AVE.
AD
2X4 (3) LAMP T8 FLUORESCENT TROFFER FOR
INSTALLATION IN LAY-IN ACOUSTIC CEILING TILE
GRID
WATTS
HARBOR FREIGHT TOOLS
VOLT
TYPE
LAMPS
DATE
MANUFACTURER
2
DESCRIPTION
1
SYMBOL
#
TYPE
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
8'-0"
DATA RACK
COPPER GROUND BAR
CONDUIT STUBBED INTO
JOIST SPACE, TYP.
NOTE:
FIRE ALARM VENDOR SHALL
CLEARLY LABEL THE FIRE
ALARM CONTROL PANEL IN
FIELD.
APPROVED PANELS:
FIRE-LITE
MODEL #'S MS5, MS10,
MS9050, AND MS9200
SILENT KNIGHT
MODEL #'S SK5600, SK5700,
SK5808, SK5820, SK5208, AND
SK-4.
TIME CLOCK
J-BOX FOR DATA
CONNECTIONS AS
REQUIRED
J-BOX
24V DC POWER
SUPPLY
QUAD RECEPTACLE
1'-0"
1'-3"
REVISIONS
TYPE
9
PHONE BOARD
DETAIL
G.C. TO USE FULL SCALE TEMPLATE FOR
TELCO BOARD EQUIPMENT LOCATIONS. G.C. TO
CONTACT SE BLUEPRINT AT (216)241-2250 TO
ORDER FULL SCALE PHONE BOARD TEMPLATE
FOR DELIVERY TO SITE.
DATE
07/08/15
JOB NO.
15166
E2.2
SHEET NO.
10
8
7
6
5
DATE
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
FULL SCALE TELEPHONE
BOARD TEMPLATE
#
ARCHITECTS, INC.
SHELF MOUNTED TO PHONE
BOARD FOR MUSIC AMPLIFIER
2'-0"
BINDER
4
‘;/21*39&78%(
FOR PLAN STORAGE W/
REMOVABLE CAP - CLEARLY
LABEL "PLANS" ON TUBE
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
FIRE ALARM CONTROL
PANEL (AS REQUIRED)
3
2"x2" WOOD BLOCKING CLIPED TO
TELPHONE BOARD WITH 1/2" PLYWOOD
COVER SCREWED TO BLOCKING TO
HOLD (3) RING PAPER WORK BINDER
66 PUNCH DOWN
BLOCK
VALCOM 3-ZONE PAGE
CONTROL
1
MAIN DMARK - AS REQUIRED DMARK MAY NOT BE LOCATED
IN HFT SPACE
AVAYA IP500 PHONE SYSTEM
2
66 PUNCH DOWN
BLOCK
P
L
A
N
S
48" MIN. TO FINISH FLOOR
OVERRIDE
SWITCH
CHINO, CA 91710
SURGE PROTECTOR
11995 CENTRAL AVE.
4'-0"
TELEPHONE JACKS
HARBOR FREIGHT TOOLS
MODULAR JACK
SHEET NO.
DATE
07/08/15
JOB NO.
15166
E3.0
TITLE 24
COMPLIANCE
FORMS
10
9
8
7
6
5
4
3
2
1
#
DATE
TYPE
REVISIONS
CHINO, CA 91710
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
11995 CENTRAL AVE.
HARBOR FREIGHT TOOLS
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
SHEET NO.
DATE
07/08/15
JOB NO.
15166
E3.1
TITLE 24
COMPLIANCE
FORMS
10
9
8
7
6
5
4
3
2
1
#
DATE
TYPE
REVISIONS
CHINO, CA 91710
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
11995 CENTRAL AVE.
HARBOR FREIGHT TOOLS
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
SHEET NO.
DATE
07/08/15
JOB NO.
15166
E3.2
TITLE 24
COMPLIANCE
FORMS
10
9
8
7
6
5
4
3
2
1
#
DATE
TYPE
REVISIONS
CHINO, CA 91710
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
11995 CENTRAL AVE.
HARBOR FREIGHT TOOLS
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
SHEET NO.
DATE
07/08/15
JOB NO.
15166
E3.3
TITLE 24
COMPLIANCE
FORMS
10
9
8
7
6
5
4
3
2
1
#
DATE
TYPE
REVISIONS
CHINO, CA 91710
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
11995 CENTRAL AVE.
HARBOR FREIGHT TOOLS
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc
SHEET NO.
DATE
07/08/15
JOB NO.
15166
E3.4
TITLE 24
COMPLIANCE
FORMS
10
9
8
7
6
5
4
3
2
1
#
DATE
TYPE
REVISIONS
CHINO, CA 91710
7KLVGRFXPHQW³,QVWUXPHQWRI6HUYLFH´ZDVSUHSDUHGE\$'$$UFKLWHFWV,QF³$'$´VSHFLILFDOO\IRUWKHUHIHUHQFHGSURMHFWDQGLVQRWLQWHQGHGIRUDQ\RWKHUXVH$'$UHWDLQVDOOFRPPRQODZVWDWXWRU\DQGRWKHU
reserved rights, including copyrights. This Instrument of Service shall not be used on other projects, for additions to this project or for completion of this project by others without ADA's prior written consent. Any
unauthorized use of this Instrument of Service shall be at the User's sole risk and without liability to ADA. ADA makes no warranties, express or implied, of merchantability or of fitness for a particular purpose.
11995 CENTRAL AVE.
HARBOR FREIGHT TOOLS
17710 Detroit Avenue Lakewood, Ohio 44107
Phone (216) 521-5134
Fax (216) 521-4824
www.adaarchitects.cc

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement