120 vac photoelectric smoke alarms 9120 series - bristol

120 VAC PHOTOELECTRIC SMOKE ALARMS
9120 SERIES
Features
•
•
•
•
•
•
•
•
•
•
•
Description
The 9120 Series of photoelectric smoke alarms is
designed for residential applications, including homes,
apartments, hospitals, hotels and offices, in compliance
with UL 217, applicable UBC/UFC Standards and NFPA
74 / NFPA 72, Chapter 2. Available in many different
models, the 9120 Series is engineered to virtually
eliminate nuisance alarms and deliver outstanding
performance wherever reliable fire protection is
required.
The 9120 Series is provided with a 9 VDC alkaline
battery for back-up in the event building power is lost.
The battery impedence is verified and the detector
provides a low or missing battery warning. The 9120
Series provides an exclusive patented three position
test feature that simulates a 0.85% and 3.5% actual
smoke condition in full compliance with NFPA 74/NFPA
72, Chapter 2 and UL Standards.
Options include self-restoring 135°F integral or isolated
thermals, and Form A/Form C dry contacts for remote
annunciation. Tandem interconnection of up to 12 units
is available on several models; tandem interconnection
of up to 6 units is available on “F” models, which
activate the dry contacts from a remote alarm through
the tandem wire or a local alarm.
Engineering Specifications
The Photoelectric Smoke alarm shall be a 9120 Series
or approved equal which shall provide at least the
following features and functions.
1. Nominal sensitivity shall be 2.5%.
2. The alarm shall utilize an infrared LED sensing
circuit which pulses in 4 to 5 second intervals when
subjected to smoke. After 2 consecutive pulses in
smoke, the alarm will activate.
3. The alarm shall have a 9 VDC alkaline batteryas
a back-up in the event building power is lost.
4. The 9 VDC battery impedence shall be verified by
the circuit of the smoke alarm.
•
•
•
•
5.
6.
7.
8.
9.
10.
11.
12.
13.
90dBA Solid-State Piezo Horn
Nominal 2.5% Sensitivity
5-to-1 Signal-to-Noise Ratio
Pulsing LED Sensing Chamber
Fully Insect Screened
Functional Test Switch — Patented Three
Position Test — Compliance to 4.5.5 (NFPA 74)
or 2.4.5.5 NFPA 72, Ch. 2
Solid-State LED Condition Indicator
Quick-Disconnect Wiring Harness
9 VDC Alkaline Battery
Mounting Hardware Adapts to Standard Junction
Boxes
Dust Cover to Prevent Contamination During
Installation
On-Site Maintenance Washing Program
Low or Missing Battery Indicator
1 Year Warranty From Date of Purchase
UL listed for 30 foot spacing (Refer to NFPA 72
for proper smoke detector placement.)
The alarm shall provide an indicator when the
battery is low in power or high impedence or is
missing.
The alarm shall provide minimum 5-to-1 signal-tonoise ratio in the optics frame to assure stability of
operation in environments of high RF and transient
conditions.
The sensing chamber shall be fully screened to
prevent entrance of small insects, thus reducing
the probability of false alarms.
A solid state piezo alarm rated at 90dBA at 10ft.
A visual LED monitor (condition indicator) will
slow pulse in normal operation and rapid pulse
in alarm.
An easily accessible test knob shall be provided. The test knob in the TEST position will simulate
an actual smoke condition of approximately
3.5% causing the detector to alarm within 20-36
seconds. It will also have the capability of testing
to 0.85% as a required minimum. A magnetic
switch closure or other switch closure, or smoke
generating equipment which does not scatter the
light beam or test sensitivity is not sufficient, as
indicated in National Code.
The detector shall have tandem interconnect
capability of up to 12 units or 6 units with relay.
Unit must be UL 217 listed for both wall and ceiling
mount.
Unit shall also meet all requirements of the State
of California Fire Marshal.
MEA
approved
CATALOG NUMBER
NOT TO BE USED FOR INSTALLATION PURPOSES.
5118
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
Electrical Specifications
Operating Voltage . . . . . . . . . . . . . . . . . 120 VAC, 60Hz
Operating Current . . . . . . . . . . . . . . . . . . . . . .045 amps
Operating Current (Relay Options) . . . . . . . . . 070 amps
Operating Ambient Temp Range . . . . . . . .40°F to 100°F
Alarm Horn Rating . . . . . . . . . . . . . . . . . .90dBA at 10 ft.
Nominal Sensitivity . . . . . . . . . . . . . . .2.5% Obscuration
“F” Auxiliary Relay . . . . .1 Form A & 1 Form C (0.5 amp)
“T” Integral Thermal (Self-Restoring) . . . . 135°F at 50ft.
Size . . . . . . . . . Diameter: 6.5 in. OA (5.75 in. at Ceiling)
Depth: 2.625 in.
Secondary Power Source: . . . . Alkaline 9 VDC Battery
Wiring Diagrams
Relay Models
ELECTRICAL
BOX
120 VOLTS
60 HZ
QUICK
DISCONNECT
TYPE PLUG
1
HOT
NEUT
TANDEM WIRE
2
3
ELECTRICAL
BOX
1
2
3
ELECTRICAL
BOX
RED / YEL
WHT
BLK
1
2
3
LIMITATIONS:
Maximum of 12 alarms
may be connected
together. Do not
exceed 125 feet
between each detector.
Do not exceed 1125
feet between the first
and last alarm.
SMOKE
ALARM
SMOKE
ALARM
NOTE: The smoke
alarms cannot be
nterconnected to
detectors from other
manufacturers.
Isolated thermal with optional
accessory contacts.
Models
9120F
9120TF
Models
9120
SMOKE
ALARM
SMOKE
ALARM
YEL
ACCESS
CONTACTS
BRN
BRN
GREY
GREY
HEAT
SENSOR
ORN
BLU
ALARM
CONTACTS
YEL
VIO
VIO/BLK
RED/YEL
TANDEM
HF ONLY
Tandem Wiring Diagram
BLK
ACCESS
CONTACTS
ORN
BLU
ALARM
CONTACTS
VIO
VIO/BLK
WHT
POWER
RED/YEL
TANDEM
BLK
SMOKE
ALARM
A MAXIMUM OF
SIX (6) ALARMS
WITH A RELAY
MAY BE TANDEM
INTERCONNECTED.
TO ADDITIONAL
SMOKE OR HEAT
ALARMS
WHT
POWER
CAUTION:
RED/YELLOW wire to be capped
when not in use. This wire is for
tandem connection only. Do not
connect to any other circuit.
RELAY CONTACTS
RATED LOAD RESISTIVE
1.0 AMP @ 24 VDC
0.6 AMP @ 125 VAC MAX
0.3 AMP @ 220 VAC MAX
(MAX 12 ALARMS
PER SYSTEM)
Ordering Information
Options
Model Number
Voltage
9120
12 VAC/ 9 VDC
9120T
120 VAC/9 VDC
9120F
120 VAC/9 VDC
9120TF
120 VAC/9 VDC
Ingetral 135°F
Thermal
Tandem up to 12
units
Tandem up to 6
units
Form A/Form C
Contacts
•
•
•
•
•
•
•
•
NOT TO BE USED FOR INSTALLATION PURPOSES.
Distributed by:
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: (905) 660-4655
Fax: (905) 660-4113
Web page: http://www.mircom.com
U.S.A.
60 Industrial Parkway
Cheektowaga, New York 14227
Toll Free: (888) 660-4655
Fax Toll Free: (888) 660-4113
Email: mail@mircom.com
ISO 9001:2000
REGISTERED
CAT. 5118
Rev. 4