NOTE: Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and will be out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.

1. Remove the detector cover by placing a small-bladed screwdriver in the cover removal slot and twisting it slightly until the cover can be turned counterclockwise for removal.

2. Remove the screen by pulling it straight out (see Figure 8). Vacuum the screen thoroughly.

3. Clean the black vaned chamber piece by vacuuming or blowing out dust and particles.

4. To reinstall the screen, rotate the screen on the housing until it drops into the alignment slots. Carefully push the screen onto the base, making sure it fits tightly to the chamber. Replacement screens are available (order part number RS23).

5. Replace the cover by rotating it clockwise until it locks in place.

6. Reinstall the detector into the system, enable system operation, and notify the proper authorities that the system is back on line.

In general, detectors cannot be expected to provide warnings for fires resulting from inadequate fire protection practices, violent explosions, escaping gases that ignite, improper storage of flammable liquids like cleaning solvents that ignite, other similar safety hazards, arson, smoking in bed, children playing with matches or lighters, etc. Smoke detectors used in high air velocity conditions may have a delay in alarm due to dilution of smoke densities created by frequent and rapid air exchanges.

Additionally, high air velocity environments may create increased dust contamination, demanding more frequent detector maintenance.

To keep your equipment in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and

NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA

72, the National Fire Alarm Code, shall be followed. A preventative maintenance agreement should be arranged through the local manufacturer’s representative. Though smoke detectors are designed for long life, they may fail at any time. Any smoke detector, fire alarm equipment, or any component of that system which fails shall be repaired or replaced as soon as possible.

WARNING

LIMITATIONS OF SMOKE DETECTORS/TRANSMITTERS action, but will do so only when used in conjunction with an authorized fire alarm system. This detector must be installed in accordance with

NFPA standard 72..... smoke detectors will not work if the power supply is cut off for any reason.

Alarm signal sent by the wireless transmitter in this detector may be blocked or reflected by metal before reaching the alarm receiver. Even if the signal path has been recently checked, blockage can occur if a metal object is moved into the path.

of heat which is needed to drive smoke up to the ceiling where the smoke detector is usually located. For this reason, there may be large delays in detecting a smoldering fire with either an ionization-type detector or a photoelectric-type detector. Either one of them may alarm only after flaming has initiated, which will generate the heat needed to drive the smoke to the ceiling.

Smoke from fires in chimneys, in walls, on roofs, or on the other side of a closed door may not reach the smoke detector and alarm it. A detector cannot quickly detect, or sense at all, a fire developing on another level of a building. Alarm warning devices, such as bell or horns, may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors, or on another level. Persons may not hear a warning device over the noise levels of a radio, air conditioner or other devices, however loud, may not warn hearing-impaired people or waken deep sleepers.

located, a fire within any of these rooms could prevent the QED control from reporting a fire.

and photoelectronic detectors are required to pass fire tests of the flaming and smoldering types. This is to ensure that both can detect a wide range of fires. Ionization detectors offer a broad range of firesensing capability, but they are somewhat better at detecting fastflaming fires than slow-smoldering fires. Photoelectronic detectors sense smoldering fires better than flaming fires, which have little, if any, visible smoke. Because fires develop in different ways, and are often unpredictable in their growth, neither type of detector is always best, and a given detector may not always provide early warning of a specific type of fire.

AD300-00-00 4

Alarm Device Manufacturing Company, a Division of Pittway Corporation

(“Seller”), 165 Eileen Way, Syosset, NY 11791, warrants its security equipment (the “product”) to be free from defects in materials and workmanship for one year from date of original purchase, under normal use and service. Seller’s obligation is limited to repairing or replacing, at its option, free of charge for parts, labor, or transportation, any part proven to be defective in materials or workmanship under normal use and service.

Seller shall have no obligation under this warranty otherwise if the product is altered or improperly repaired or serviced by anyone other than the seller. In case of defect, contact the security professional who installed and maintains your security system or the Seller for product repair.

This one year Limited Warranty is in lieu of all other express warranties, obligations, or liabilities. THERE ARE NO EXPRESS WARRANTIES

WHICH EXTEND BEYOND THE FACE HEREOF. ALL IMPLIED WAR-

RANTIES, OBLIGATIONS, OR LIABILITIES MADE BY SELLER IN

CONNECTION WITH THIS PRODUCT, INCLUDING ANY IMPLIED

WARRANTY OF MERCHANTABILITY, OR FITNESS FOR A PARTICU-

LAR PURPOSE OR OTHERWISE, ARE LIMITED IN DURATION TO A

PERIOD OF ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE.

ANY ACTION OR BREACH OF ANY WARRANTY, INCLUDING BUT

NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY,

MUST BE BROUGHT WITHIN 18 MONTHS OF DATE OF ORIGINAL

PURCHASE. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE

FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR

BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR

IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSO-

EVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER’S

OWN NEGLIGENCE OR FAULT. Some states do not allow limitations on how long an implied warranty lasts or the exclusion of incidental or consequential damages, so above limitation or exclusion may not apply to you.

Seller does not represent that the product may not be compromised or circumvented; that the product will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; or that the product will in all cases provide adequate warning or protection. Buyer understands that a properly installed and maintained alarm my only reduce the risk of a burglary, robbery, or fire occurring without providing an alarm, but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or property loss as a result. CONSEQUENTLY, SELLER

SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROP-

ERTY DAMAGE, OR OTHER LOSS BASED ON A CLAIM THAT THE

PRODUCT FAILED TO GIVE WARNING. However, if seller is held liable, whether directly or indirectly, for any loss or damage arising under this

Limited Warranty or otherwise, regardless of cause or origin, Seller’s maximum liability shall not in any case exceed the purchase price of the product, and shall be the complete and exclusive remedy against Seller.

This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. No increase or alteration, written or verbal, to this warranty is authorized.

I56-918-06

© ADEMCO 1998

Previous Menu

For use with QED control panel ONLY!

Built-in Wireless T ransmitter Installation Instructions

Power Source: Two 3-volt CR123A Lithium Batteries (included). (Replace with Duracell DL123A, Sanyo

CR123A, Panasonic CR123A, ADEMCO 466, or Varta CR123A.)

Maintenance Limits (Maintenance signal is activated at either smoke level):

Height:

Diameter:

Weight:

Operating Ambient Temperature Range:

Operating Humidity Range:

Heat Sensor:

Agency Listings:

Hot Sensitivity: 0.65% ± 0.15% per foot

Cold Sensitivity: less than 6% per foot

2.5 inches (14 cm)

5.5 inches (64 mm)

0.7 lb. (310 g)

4.4° to 37.8° C (40° to 100° F)

5% to 95% Relative Humidity

135° F Fixed Temperature Electronic Thermistors

UL 217; UL 268 – Residential, Commercial Installations

Before installing detectors, please thoroughly read these installation instructions and Manual I56-407, Guide for Proper Use of System Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from

ADEMCO.

NOTICE: This manual should be left with the owner/user of this equipment.

IMPORTANT: This detector must be tested and maintained regularly following

NFPA 72 requirements. The detector should be cleaned at least once a year.

WARNING: Do not use the maintenance signal as an indication that the detector has reached the limits of its nominal sensitivity range. Maintenance only indicates that the detector may need cleaning or can no longer respond to smoke and shall not be used as a sensitivity indicating means.

To replace batteries:

1.

Remove the detector from its mounting plate by twisting the detector counterclockwise. Remove batteries, if replacing, and dispose properly.

2.

Install two new 3-volt CR123A Lithium batteries in the battery compartment. Follow the polarity diagram inside the compartment.

3.

Reinstall the smoke detector onto the mounting plate by turning the detector clockwise.

4. Test the detector as described in the TESTING TRANSMITTER SIG-

NAL section of this manual. The LED should flash about once every 40 seconds to indicate normal operation. If the batteries are not installed correctly, the smoke detector will not operate and the batteries may be damaged. If the detector does not appear to be sending a signal during any of the tests, check for correct battery installation.

GENERAL DESCRIPTION

The 5808 photoelectronic smoke/heat detector with built-in wireless transmitter is intended for use with wireless alarm systems that support QED 5800 series devices. Refer to QED control communicator installation instructions for compatibility. The 5808 smoke/heat detector can be used with 5881 series

(L, M, H) and 5881EH receivers for residential installations. The 5808 smoke/ heat detector can be used with the 5881EH receiver for commercial installations. The transmitter can send alarm, tamper, maintenance (when QED control panels are equipped to process maintenance signals), and battery condition messages to the QED system's receiver. The maintenance signal will either indicate that the photo chamber requires cleaning or that the detector can no longer respond to smoke and may need replacement. Refer to the wireless system's instructions for the maximum number of transmitters that can be supported.

The 5808 sounds its built-in horn when smoke reaches the detector (the

LED also flashes rapidly) or when the air temperature reaches 135° F (the

LED flashes normally, about once every 40 seconds). A message is also sent to the wireless QED control panel and the smoke detector's ID number is displayed at the console. The alarm message is transmitted every 4 seconds until the smoke condition has cleared and the detector has reset.

About 1 second after the horn stops, a RESTORE message is transmitted to the QED control panel and the ID number can be cleared from the panel.

During normal, maintenance, and low battery conditions, the LED flashes approximately once every 40 seconds.

BATTERY INSTALLATION AND REPLACEMENT

The 5808 is powered by two 3-volt CR123A or DL123A Lithium batteries

(included). The detector checks for low batteries at every normal LED flash.

If a low battery is detected, the transmitter sends a low battery message to the QED control panel, which beeps and displays the detector's ID. This condition will exist for a minimum of seven days, and then the detector's horn will "chirp" about every 40 seconds. The batteries should be replaced

BEFORE the chirps begin. BE SURE TO REPLACE BOTH BATTERIES

WITH FRESH ONES.

Indicator Light

Pulsing: Normal/Thermal Alarm

Fast Blink: Smoke Alarm

None: Call for Service

Test Module

Port

Test Switch

Figure 1. 5808 Wireless Smoke/ Heat Detector

A78-2332-01

PROGRAMMING

The smoke detector’s ID must be enrolled in the QED control panel during installation of the system. The QED control panel should be programmed to enroll the 5808 as an “RF” unit (must be programmed as “supervised RF” for UL installations). Put the QED control panel in the program ming mode and perform the following:

With the QED control panel, program the detector as loop 1 and either manually enter the serial number that is on the label of the 5808, or press the test switch to cause a transmission. Additional transmissions will cause the “Confirm” display to appear on the keypad display.

See the QED control unit’s installation instructions for further details.

AD300-00-00 I56-918-06

ADEMCO, 165 Eileen Way, Syosset, New York 11791

SMOKE DETECTOR LIMITATIONS

• Smoke detectors will not sense a fire if the smoke does not reach the

sensor or if the air temperature does not reach 135° F. In order for a smoke detector to sense smoke, it must be installed in the immediate vicinity of the fire. In addition, smoke from fires in chimneys, in walls, on roofs, in remote parts of the building, or on another level from where the smoke detector is located, may not reach the smoke detector quickly enough for occupants to escape unharmed. For this reason, installer shall install smoke detectors on every level, in every sleeping area, and in every bedroom of the household.

• Smoke detectors may not be heard. The alarm horn in this smoke detector meets or exceeds current Underwriter's Laboratories standards.

However, if the smoke detector is not located in the same room as the occupant, or if it is blocked by a closed door or normal noise, the alarm horn may not be heard. In addition, sound sleepers, or persons who are under the influence of drugs or alcohol may not hear the alarm or be able to react to it. Therefore, locate this smoke detector, which has a sounder rated at 85 dB at 10 feet, on every level, in every sleeping area, and in every bedroom of the household.

• In general, detectors may not always warn you about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.

• Smoke detectors are not fool-proof. Like all electronic devices, smoke detectors have limitations. No type of smoke detector can sense every kind of fire every time. In addition, smoke from slow, smoldering fires rises slowly and may not reach the smoke detector until actual flame breaks out. This type of smoke may not reach the smoke detector in time for occupants to escape unharmed.

• Smoke detectors are not a substitute for life or property insurance.

Though smoke detectors have been responsible for saving many lives, they are not warranted or implied to protect lives or property in the event of a fire.

To keep your equipment in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72, the

National Fire Alarm Code, shall be followed. A preventative maintenance agreement should be arranged through the local manufacturer’s representative. Though smoke detectors are designed for long life, they may fail at any time. Any smoke detector, fire alarm equipment, or any component of that system which fails shall be repaired or replaced as soon as possible.

Where to Install Smoke Detectors

Warning: As a minimum requirement, smoke detectors must be installed in accordance with the National Fire Protection Agency (NFPA)

Standard 72, Chapter 5, which defines the standards for the National

Fire Alarm Code (National Fire Protection Association, Batterymarch

Park, MA 02269-9101). In addition, observe all local and national building and electrical codes.

Recommended Smoke Detector Locations:

DINING ROOM KITCHEN BEDROOM BEDROOM

HORIZONTAL

DISTANCE

FROM PEAK

3 FEET

(.9M)

Figure 4. Recommended smoke detector location in rooms with sloped, gabled or peaked ceilings.

A78-1171-05

Where Smoke Detectors Should NOT Be Installed

• In or near areas where combustion particles are normally present

such as kitchens; in garages where there are particles of combustion in vehicle exhausts; near furnaces, hot water heaters, or gas space

heaters. Install detectors at least 20 feet (6 meters) away from kitchens and other areas where combustion particles are normally present.

• On the ceiling in rooms next to kitchens where there is no transom between the kitchen and these rooms. Instead, install the smoke detector on an inside wall, furthest from the kitchen (See Figure 5). Be sure not to install smoke detectors within 4" of the ceiling or any corner or more than 6" from the ceiling.

AIR INLET

AIR RETURN BATH STOVE

BEDROOM

KITCHEN

CORRECT

INCORRECT

LIVING

ROOM

BEDROOM

Figure 5. Recommended smoke detector locations to avoid air streams with combustion particles

78-1171-06

• In damp or very humid areas, or next to bathrooms with showers.

The moisture in humid air can enter the sensing chamber as water vapor, then cool and condense into droplets that cause a nuisance alarm. Install detectors at least 5 feet (1.5 meters) away from bathrooms.

• In very cold or very hot rooms or areas. Operating temperature of the smoke detector is 40°F to 100°F (4°C to 38°C).

• In dusty, dirty, or insect-infested areas. Dust and dirt can build up on the detector’s sensing chamber and make it overly sensitive, or can block openings to the sensing chamber and keep the detector from sensing smoke.

Near fresh air inlets or returns or excessively drafty areas. Air conditioners, heaters, fans, and fresh air intakes and returns can drive smoke away from smoke detectors, making the detectors less effective.

• In dead air spaces at the top of a peaked ceiling or wall/ceiling intersect.

Dead air may prevent smoke from reaching a detector.

• Near fluorescent light fixtures. Install detectors at least 10 feet

(3 meters) away from such light fixtures.

LIVING ROOM BEDROOM

SMOKE DETECTORS FOR MINIMUM PROTECTION

SMOKE DETECTORS FOR MORE PROTECTION AND

REQUIRED IN NEW CONSTRUCTION

A78-1171-01

Figure 2. Single-floor residence with only one sleeping area

AD300-00-00

FAMILY ROOM KITCHEN DINING

ROOM

BEDROOM

LIVING ROOM

BEDROOM

BEDROOM

SMOKE DETECTORS FOR

MINIMUM PROTECTION

SMOKE DETECTORS FOR

MORE PROTECTION AND

REQUIRED IN NEW CONSTRUCTION

A78-1171-02

Figure 3. Single-floor residence with more than one sleeping area

WHAT TO DO IN CASE OF FIRE

1. DON’T PANIC — escape may depend on clear thinking.

2. Get out of the house following the planned escape routes, if possible.

Do not stop to dress or to collect anything.

3. Open doors carefully only after feeling them to see if they are hot. If a door is hot, do not open it— follow an alternate escape route.

4. Keep close to the floor — smoke and hot gases rise. Breathe through a cloth (wet, if possible) and take short shallow breaths.

5. Keep doors and windows closed unless it is necessary to open them for escape.

6. Meet at your meeting place after leaving your home.

7. Call the local fire department as soon as possible from outside the home.

8. Never re-enter a burning building.

2

For more information about fire safety, contact your local fire depart-

I56-918-06 ment. They can supply more detailed information about making your home as free from fire hazards as possible and about planning for escape in case of fire.

MOUNTING

First, determine the best location for the smoke detector; a location that provides strong wireless transmission paths and proper smoke detection. A GOOD TRANSMISSION PATH MUST BE ESTABLISHED

FROM THE PROPOSED MOUNTING LOCATION BEFORE PERMA-

NENTLY INSTALLING THE DETECTOR. To check, perform the test described in the TESTING TRANSMITTER SIGNAL section of this manual. To mount the detector:

1. Once a suitable location has been determined, install the mounting bracket on the ceiling or on the wall (if local ordinances permit). Use the two screws and anchors provided.

2. Prior to mounting the detector to the mounting bracket, the system must "enroll" the detector's ID. See the PROGRAMMING section for the steps to follow.

3. Turn the detector in a clockwise direction in the mounting bracket until it clicks into place.

4. Test the detector immediately after completing the installation (as described in the TESTING section of this manual) and refer to the QED control system's instructions for additional information concerning the use of wireless smoke detectors.

TAMPER SLOT

(DEPRESS TAB

TO REMOVE

DETECTOR)

TAMPER RESISTANT TAB

(CUT OFF SMALL TAB TO

ACTIVATE TAMPER PROOF

FEATURE)

Figure 6. Detector Mounting Bracket

BRACKET INDICATES

POSITION OF LED WHEN

DETECTOR IS INSTALLED

A78-2333-03

Figure 7. Mount Detector Across Ceiling Panel Support

A78-2620-00

CAUTION

DO NOT attach the detector to removable ceiling panels. Attach the detector across panel support as shown in Figure 7.

TAMPER PROTECTION

This detector has a built-in tamper switch that will cause a CHECK signal to be displayed at the console of the detector if it is removed from its installation bracket. The mounting bracket can also be made tamperproof by breaking off the smaller tab at the scribed line (see Figure 6), thus preventing removal of the detector without a tool. To remove the detector, use a small screwdriver to depress the tamperproof tab and turn the detector counterclockwise.

TESTING

NOTE: Before testing, notify the proper authorities that the smoke detector system is undergoing maintenance and will temporarily be out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.

Detectors must be tested after installation and following periodic maintenance. The 5808 may be tested as follows:

A. TEST SWITCH

1. A recessed test switch is located on the detector housing.

2. Push and hold the recessed test switch with a 0.1" maximum

AD300-00-00 3 diameter tool (an allen wrench or small screwdriver.)

3. The LED on the detector should blink once per second and the horn should sound within 3 seconds.

B. TEST MODULE (Model No. MOD400R)

The MOD400R test module can be used with a DMM or analog voltmeter to check the detector sensitivity as described in the test module’s manual.

C. SMOKE ENTRY TEST

Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through the detector until the unit alarms.

D. DIRECT HEAT METHOD (Hair dryer of 1000-1500 watts)

Direct the heat toward either side thermistor. Be sure to hold the heat source about 12 inches from the detector to avoid damage to the plastic. The detector will reset only after it has time to cool.

Smoke detection testing is recommended for verifying system protection capability.

A detector that fails to activate with any of these tests should first be cleaned as outlined in this manual's MAINTENANCE section. If the detector still fails to activate, return for repair.

Notify the proper authorities that the system is back on line.

TESTING TRANSMITTER SIGNAL

NOTE: Remove battery tab before installation.

This test should be performed before installation to determine a strong communication path with the QED control panel and after installation is complete. Also, the owner/user should test the unit at least weekly.

1. Activate the wireless system's TEST mode from the console.

2. Depress and hold the smoke detector's TEST switch and the detector should immediately transmit an alarm signal to the QED control panel.

The built-in horn will start to sound about 2.5 seconds after depressing the button.

3. The wireless system's console should emit at least 3 audible sounds when the alarm transmission is received and will display the transmitting detector's ID number.

4. When the console has received the test signal, release the TEST switch. The horn will immediately stop and a few seconds later the detector's ID number will clear from the console display.

5. If the console does not respond as noted, check the polarity of the batteries and be sure they are fresh. If this is an initial installation, try moving the detector to another location that provides proper reception. Also be sure that the detector's ID has been "enrolled" by the QED control panel (see PROGRAMMING). Then, repeat the test.

6. Turn off the system's TEST mode from the console (security code +

OFF).

MAINTENANCE

ARROW IS ALIGNED

WITH COVER REMOVAL

SLOT WHEN COVER

IS IN POSITION.

REPLACEMENT SCREEN,

ORDER PART NO. RS23

COVER

REMOVAL SLOT

A78-2335-01

Figure 8. Removal of Cover and Screen for Cleaning

I56-918-06

SMOKE DETECTOR LIMITATIONS

• Smoke detectors will not sense a fire if the smoke does not reach the

sensor or if the air temperature does not reach 135° F. In order for a smoke detector to sense smoke, it must be installed in the immediate vicinity of the fire. In addition, smoke from fires in chimneys, in walls, on roofs, in remote parts of the building, or on another level from where the smoke detector is located, may not reach the smoke detector quickly enough for occupants to escape unharmed. For this reason, installer shall install smoke detectors on every level, in every sleeping area, and in every bedroom of the household.

• Smoke detectors may not be heard. The alarm horn in this smoke detector meets or exceeds current Underwriter's Laboratories standards.

However, if the smoke detector is not located in the same room as the occupant, or if it is blocked by a closed door or normal noise, the alarm horn may not be heard. In addition, sound sleepers, or persons who are under the influence of drugs or alcohol may not hear the alarm or be able to react to it. Therefore, locate this smoke detector, which has a sounder rated at 85 dB at 10 feet, on every level, in every sleeping area, and in every bedroom of the household.

• In general, detectors may not always warn you about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.

• Smoke detectors are not fool-proof. Like all electronic devices, smoke detectors have limitations. No type of smoke detector can sense every kind of fire every time. In addition, smoke from slow, smoldering fires rises slowly and may not reach the smoke detector until actual flame breaks out. This type of smoke may not reach the smoke detector in time for occupants to escape unharmed.

• Smoke detectors are not a substitute for life or property insurance.

Though smoke detectors have been responsible for saving many lives, they are not warranted or implied to protect lives or property in the event of a fire.

To keep your equipment in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72, the

National Fire Alarm Code, shall be followed. A preventative maintenance agreement should be arranged through the local manufacturer’s representative. Though smoke detectors are designed for long life, they may fail at any time. Any smoke detector, fire alarm equipment, or any component of that system which fails shall be repaired or replaced as soon as possible.

Where to Install Smoke Detectors

Warning: As a minimum requirement, smoke detectors must be installed in accordance with the National Fire Protection Agency (NFPA)

Standard 72, Chapter 5, which defines the standards for the National

Fire Alarm Code (National Fire Protection Association, Batterymarch

Park, MA 02269-9101). In addition, observe all local and national building and electrical codes.

Recommended Smoke Detector Locations:

DINING ROOM KITCHEN BEDROOM BEDROOM

HORIZONTAL

DISTANCE

FROM PEAK

3 FEET

(.9M)

Figure 4. Recommended smoke detector location in rooms with sloped, gabled or peaked ceilings.

A78-1171-05

Where Smoke Detectors Should NOT Be Installed

• In or near areas where combustion particles are normally present

such as kitchens; in garages where there are particles of combustion in vehicle exhausts; near furnaces, hot water heaters, or gas space

heaters. Install detectors at least 20 feet (6 meters) away from kitchens and other areas where combustion particles are normally present.

• On the ceiling in rooms next to kitchens where there is no transom between the kitchen and these rooms. Instead, install the smoke detector on an inside wall, furthest from the kitchen (See Figure 5). Be sure not to install smoke detectors within 4" of the ceiling or any corner or more than 6" from the ceiling.

AIR INLET

AIR RETURN BATH STOVE

BEDROOM

KITCHEN

CORRECT

INCORRECT

LIVING

ROOM

BEDROOM

Figure 5. Recommended smoke detector locations to avoid air streams with combustion particles

78-1171-06

• In damp or very humid areas, or next to bathrooms with showers.

The moisture in humid air can enter the sensing chamber as water vapor, then cool and condense into droplets that cause a nuisance alarm. Install detectors at least 5 feet (1.5 meters) away from bathrooms.

• In very cold or very hot rooms or areas. Operating temperature of the smoke detector is 40°F to 100°F (4°C to 38°C).

• In dusty, dirty, or insect-infested areas. Dust and dirt can build up on the detector’s sensing chamber and make it overly sensitive, or can block openings to the sensing chamber and keep the detector from sensing smoke.

Near fresh air inlets or returns or excessively drafty areas. Air conditioners, heaters, fans, and fresh air intakes and returns can drive smoke away from smoke detectors, making the detectors less effective.

• In dead air spaces at the top of a peaked ceiling or wall/ceiling intersect.

Dead air may prevent smoke from reaching a detector.

• Near fluorescent light fixtures. Install detectors at least 10 feet

(3 meters) away from such light fixtures.

LIVING ROOM BEDROOM

SMOKE DETECTORS FOR MINIMUM PROTECTION

SMOKE DETECTORS FOR MORE PROTECTION AND

REQUIRED IN NEW CONSTRUCTION

A78-1171-01

Figure 2. Single-floor residence with only one sleeping area

AD300-00-00

FAMILY ROOM KITCHEN DINING

ROOM

BEDROOM

LIVING ROOM

BEDROOM

BEDROOM

SMOKE DETECTORS FOR

MINIMUM PROTECTION

SMOKE DETECTORS FOR

MORE PROTECTION AND

REQUIRED IN NEW CONSTRUCTION

A78-1171-02

Figure 3. Single-floor residence with more than one sleeping area

WHAT TO DO IN CASE OF FIRE

1. DON’T PANIC — escape may depend on clear thinking.

2. Get out of the house following the planned escape routes, if possible.

Do not stop to dress or to collect anything.

3. Open doors carefully only after feeling them to see if they are hot. If a door is hot, do not open it— follow an alternate escape route.

4. Keep close to the floor — smoke and hot gases rise. Breathe through a cloth (wet, if possible) and take short shallow breaths.

5. Keep doors and windows closed unless it is necessary to open them for escape.

6. Meet at your meeting place after leaving your home.

7. Call the local fire department as soon as possible from outside the home.

8. Never re-enter a burning building.

2

For more information about fire safety, contact your local fire depart-

I56-918-06 ment. They can supply more detailed information about making your home as free from fire hazards as possible and about planning for escape in case of fire.

MOUNTING

First, determine the best location for the smoke detector; a location that provides strong wireless transmission paths and proper smoke detection. A GOOD TRANSMISSION PATH MUST BE ESTABLISHED

FROM THE PROPOSED MOUNTING LOCATION BEFORE PERMA-

NENTLY INSTALLING THE DETECTOR. To check, perform the test described in the TESTING TRANSMITTER SIGNAL section of this manual. To mount the detector:

1. Once a suitable location has been determined, install the mounting bracket on the ceiling or on the wall (if local ordinances permit). Use the two screws and anchors provided.

2. Prior to mounting the detector to the mounting bracket, the system must "enroll" the detector's ID. See the PROGRAMMING section for the steps to follow.

3. Turn the detector in a clockwise direction in the mounting bracket until it clicks into place.

4. Test the detector immediately after completing the installation (as described in the TESTING section of this manual) and refer to the QED control system's instructions for additional information concerning the use of wireless smoke detectors.

TAMPER SLOT

(DEPRESS TAB

TO REMOVE

DETECTOR)

TAMPER RESISTANT TAB

(CUT OFF SMALL TAB TO

ACTIVATE TAMPER PROOF

FEATURE)

Figure 6. Detector Mounting Bracket

BRACKET INDICATES

POSITION OF LED WHEN

DETECTOR IS INSTALLED

A78-2333-03

Figure 7. Mount Detector Across Ceiling Panel Support

A78-2620-00

CAUTION

DO NOT attach the detector to removable ceiling panels. Attach the detector across panel support as shown in Figure 7.

TAMPER PROTECTION

This detector has a built-in tamper switch that will cause a CHECK signal to be displayed at the console of the detector if it is removed from its installation bracket. The mounting bracket can also be made tamperproof by breaking off the smaller tab at the scribed line (see Figure 6), thus preventing removal of the detector without a tool. To remove the detector, use a small screwdriver to depress the tamperproof tab and turn the detector counterclockwise.

TESTING

NOTE: Before testing, notify the proper authorities that the smoke detector system is undergoing maintenance and will temporarily be out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.

Detectors must be tested after installation and following periodic maintenance. The 5808 may be tested as follows:

A. TEST SWITCH

1. A recessed test switch is located on the detector housing.

2. Push and hold the recessed test switch with a 0.1" maximum

AD300-00-00 3 diameter tool (an allen wrench or small screwdriver.)

3. The LED on the detector should blink once per second and the horn should sound within 3 seconds.

B. TEST MODULE (Model No. MOD400R)

The MOD400R test module can be used with a DMM or analog voltmeter to check the detector sensitivity as described in the test module’s manual.

C. SMOKE ENTRY TEST

Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through the detector until the unit alarms.

D. DIRECT HEAT METHOD (Hair dryer of 1000-1500 watts)

Direct the heat toward either side thermistor. Be sure to hold the heat source about 12 inches from the detector to avoid damage to the plastic. The detector will reset only after it has time to cool.

Smoke detection testing is recommended for verifying system protection capability.

A detector that fails to activate with any of these tests should first be cleaned as outlined in this manual's MAINTENANCE section. If the detector still fails to activate, return for repair.

Notify the proper authorities that the system is back on line.

TESTING TRANSMITTER SIGNAL

NOTE: Remove battery tab before installation.

This test should be performed before installation to determine a strong communication path with the QED control panel and after installation is complete. Also, the owner/user should test the unit at least weekly.

1. Activate the wireless system's TEST mode from the console.

2. Depress and hold the smoke detector's TEST switch and the detector should immediately transmit an alarm signal to the QED control panel.

The built-in horn will start to sound about 2.5 seconds after depressing the button.

3. The wireless system's console should emit at least 3 audible sounds when the alarm transmission is received and will display the transmitting detector's ID number.

4. When the console has received the test signal, release the TEST switch. The horn will immediately stop and a few seconds later the detector's ID number will clear from the console display.

5. If the console does not respond as noted, check the polarity of the batteries and be sure they are fresh. If this is an initial installation, try moving the detector to another location that provides proper reception. Also be sure that the detector's ID has been "enrolled" by the QED control panel (see PROGRAMMING). Then, repeat the test.

6. Turn off the system's TEST mode from the console (security code +

OFF).

MAINTENANCE

ARROW IS ALIGNED

WITH COVER REMOVAL

SLOT WHEN COVER

IS IN POSITION.

REPLACEMENT SCREEN,

ORDER PART NO. RS23

COVER

REMOVAL SLOT

A78-2335-01

Figure 8. Removal of Cover and Screen for Cleaning

I56-918-06

NOTE: Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and will be out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.

1. Remove the detector cover by placing a small-bladed screwdriver in the cover removal slot and twisting it slightly until the cover can be turned counterclockwise for removal.

2. Remove the screen by pulling it straight out (see Figure 8). Vacuum the screen thoroughly.

3. Clean the black vaned chamber piece by vacuuming or blowing out dust and particles.

4. To reinstall the screen, rotate the screen on the housing until it drops into the alignment slots. Carefully push the screen onto the base, making sure it fits tightly to the chamber. Replacement screens are available (order part number RS23).

5. Replace the cover by rotating it clockwise until it locks in place.

6. Reinstall the detector into the system, enable system operation, and notify the proper authorities that the system is back on line.

In general, detectors cannot be expected to provide warnings for fires resulting from inadequate fire protection practices, violent explosions, escaping gases that ignite, improper storage of flammable liquids like cleaning solvents that ignite, other similar safety hazards, arson, smoking in bed, children playing with matches or lighters, etc. Smoke detectors used in high air velocity conditions may have a delay in alarm due to dilution of smoke densities created by frequent and rapid air exchanges.

Additionally, high air velocity environments may create increased dust contamination, demanding more frequent detector maintenance.

To keep your equipment in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and

NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA

72, the National Fire Alarm Code, shall be followed. A preventative maintenance agreement should be arranged through the local manufacturer’s representative. Though smoke detectors are designed for long life, they may fail at any time. Any smoke detector, fire alarm equipment, or any component of that system which fails shall be repaired or replaced as soon as possible.

WARNING

LIMITATIONS OF SMOKE DETECTORS/TRANSMITTERS action, but will do so only when used in conjunction with an authorized fire alarm system. This detector must be installed in accordance with

NFPA standard 72..... smoke detectors will not work if the power supply is cut off for any reason.

Alarm signal sent by the wireless transmitter in this detector may be blocked or reflected by metal before reaching the alarm receiver. Even if the signal path has been recently checked, blockage can occur if a metal object is moved into the path.

of heat which is needed to drive smoke up to the ceiling where the smoke detector is usually located. For this reason, there may be large delays in detecting a smoldering fire with either an ionization-type detector or a photoelectric-type detector. Either one of them may alarm only after flaming has initiated, which will generate the heat needed to drive the smoke to the ceiling.

Smoke from fires in chimneys, in walls, on roofs, or on the other side of a closed door may not reach the smoke detector and alarm it. A detector cannot quickly detect, or sense at all, a fire developing on another level of a building. Alarm warning devices, such as bell or horns, may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors, or on another level. Persons may not hear a warning device over the noise levels of a radio, air conditioner or other devices, however loud, may not warn hearing-impaired people or waken deep sleepers.

located, a fire within any of these rooms could prevent the QED control from reporting a fire.

and photoelectronic detectors are required to pass fire tests of the flaming and smoldering types. This is to ensure that both can detect a wide range of fires. Ionization detectors offer a broad range of firesensing capability, but they are somewhat better at detecting fastflaming fires than slow-smoldering fires. Photoelectronic detectors sense smoldering fires better than flaming fires, which have little, if any, visible smoke. Because fires develop in different ways, and are often unpredictable in their growth, neither type of detector is always best, and a given detector may not always provide early warning of a specific type of fire.

AD300-00-00 4

Alarm Device Manufacturing Company, a Division of Pittway Corporation

(“Seller”), 165 Eileen Way, Syosset, NY 11791, warrants its security equipment (the “product”) to be free from defects in materials and workmanship for one year from date of original purchase, under normal use and service. Seller’s obligation is limited to repairing or replacing, at its option, free of charge for parts, labor, or transportation, any part proven to be defective in materials or workmanship under normal use and service.

Seller shall have no obligation under this warranty otherwise if the product is altered or improperly repaired or serviced by anyone other than the seller. In case of defect, contact the security professional who installed and maintains your security system or the Seller for product repair.

This one year Limited Warranty is in lieu of all other express warranties, obligations, or liabilities. THERE ARE NO EXPRESS WARRANTIES

WHICH EXTEND BEYOND THE FACE HEREOF. ALL IMPLIED WAR-

RANTIES, OBLIGATIONS, OR LIABILITIES MADE BY SELLER IN

CONNECTION WITH THIS PRODUCT, INCLUDING ANY IMPLIED

WARRANTY OF MERCHANTABILITY, OR FITNESS FOR A PARTICU-

LAR PURPOSE OR OTHERWISE, ARE LIMITED IN DURATION TO A

PERIOD OF ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE.

ANY ACTION OR BREACH OF ANY WARRANTY, INCLUDING BUT

NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY,

MUST BE BROUGHT WITHIN 18 MONTHS OF DATE OF ORIGINAL

PURCHASE. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE

FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR

BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR

IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSO-

EVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER’S

OWN NEGLIGENCE OR FAULT. Some states do not allow limitations on how long an implied warranty lasts or the exclusion of incidental or consequential damages, so above limitation or exclusion may not apply to you.

Seller does not represent that the product may not be compromised or circumvented; that the product will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; or that the product will in all cases provide adequate warning or protection. Buyer understands that a properly installed and maintained alarm my only reduce the risk of a burglary, robbery, or fire occurring without providing an alarm, but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or property loss as a result. CONSEQUENTLY, SELLER

SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROP-

ERTY DAMAGE, OR OTHER LOSS BASED ON A CLAIM THAT THE

PRODUCT FAILED TO GIVE WARNING. However, if seller is held liable, whether directly or indirectly, for any loss or damage arising under this

Limited Warranty or otherwise, regardless of cause or origin, Seller’s maximum liability shall not in any case exceed the purchase price of the product, and shall be the complete and exclusive remedy against Seller.

This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. No increase or alteration, written or verbal, to this warranty is authorized.

I56-918-06

© ADEMCO 1998

Previous Menu

For use with QED control panel ONLY!

Built-in Wireless T ransmitter Installation Instructions

Power Source: Two 3-volt CR123A Lithium Batteries (included). (Replace with Duracell DL123A, Sanyo

CR123A, Panasonic CR123A, ADEMCO 466, or Varta CR123A.)

Maintenance Limits (Maintenance signal is activated at either smoke level):

Height:

Diameter:

Weight:

Operating Ambient Temperature Range:

Operating Humidity Range:

Heat Sensor:

Agency Listings:

Hot Sensitivity: 0.65% ± 0.15% per foot

Cold Sensitivity: less than 6% per foot

2.5 inches (14 cm)

5.5 inches (64 mm)

0.7 lb. (310 g)

4.4° to 37.8° C (40° to 100° F)

5% to 95% Relative Humidity

135° F Fixed Temperature Electronic Thermistors

UL 217; UL 268 – Residential, Commercial Installations

Before installing detectors, please thoroughly read these installation instructions and Manual I56-407, Guide for Proper Use of System Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from

ADEMCO.

NOTICE: This manual should be left with the owner/user of this equipment.

IMPORTANT: This detector must be tested and maintained regularly following

NFPA 72 requirements. The detector should be cleaned at least once a year.

WARNING: Do not use the maintenance signal as an indication that the detector has reached the limits of its nominal sensitivity range. Maintenance only indicates that the detector may need cleaning or can no longer respond to smoke and shall not be used as a sensitivity indicating means.

To replace batteries:

1.

Remove the detector from its mounting plate by twisting the detector counterclockwise. Remove batteries, if replacing, and dispose properly.

2.

Install two new 3-volt CR123A Lithium batteries in the battery compartment. Follow the polarity diagram inside the compartment.

3.

Reinstall the smoke detector onto the mounting plate by turning the detector clockwise.

4. Test the detector as described in the TESTING TRANSMITTER SIG-

NAL section of this manual. The LED should flash about once every 40 seconds to indicate normal operation. If the batteries are not installed correctly, the smoke detector will not operate and the batteries may be damaged. If the detector does not appear to be sending a signal during any of the tests, check for correct battery installation.

GENERAL DESCRIPTION

The 5808 photoelectronic smoke/heat detector with built-in wireless transmitter is intended for use with wireless alarm systems that support QED 5800 series devices. Refer to QED control communicator installation instructions for compatibility. The 5808 smoke/heat detector can be used with 5881 series

(L, M, H) and 5881EH receivers for residential installations. The 5808 smoke/ heat detector can be used with the 5881EH receiver for commercial installations. The transmitter can send alarm, tamper, maintenance (when QED control panels are equipped to process maintenance signals), and battery condition messages to the QED system's receiver. The maintenance signal will either indicate that the photo chamber requires cleaning or that the detector can no longer respond to smoke and may need replacement. Refer to the wireless system's instructions for the maximum number of transmitters that can be supported.

The 5808 sounds its built-in horn when smoke reaches the detector (the

LED also flashes rapidly) or when the air temperature reaches 135° F (the

LED flashes normally, about once every 40 seconds). A message is also sent to the wireless QED control panel and the smoke detector's ID number is displayed at the console. The alarm message is transmitted every 4 seconds until the smoke condition has cleared and the detector has reset.

About 1 second after the horn stops, a RESTORE message is transmitted to the QED control panel and the ID number can be cleared from the panel.

During normal, maintenance, and low battery conditions, the LED flashes approximately once every 40 seconds.

BATTERY INSTALLATION AND REPLACEMENT

The 5808 is powered by two 3-volt CR123A or DL123A Lithium batteries

(included). The detector checks for low batteries at every normal LED flash.

If a low battery is detected, the transmitter sends a low battery message to the QED control panel, which beeps and displays the detector's ID. This condition will exist for a minimum of seven days, and then the detector's horn will "chirp" about every 40 seconds. The batteries should be replaced

BEFORE the chirps begin. BE SURE TO REPLACE BOTH BATTERIES

WITH FRESH ONES.

Indicator Light

Pulsing: Normal/Thermal Alarm

Fast Blink: Smoke Alarm

None: Call for Service

Test Module

Port

Test Switch

Figure 1. 5808 Wireless Smoke/ Heat Detector

A78-2332-01

PROGRAMMING

The smoke detector’s ID must be enrolled in the QED control panel during installation of the system. The QED control panel should be programmed to enroll the 5808 as an “RF” unit (must be programmed as “supervised RF” for UL installations). Put the QED control panel in the program ming mode and perform the following:

With the QED control panel, program the detector as loop 1 and either manually enter the serial number that is on the label of the 5808, or press the test switch to cause a transmission. Additional transmissions will cause the “Confirm” display to appear on the keypad display.

See the QED control unit’s installation instructions for further details.