Overview
The FDO181C is an optical smoke detector with an optical sensor. It works according
to the principle of forward scattering. The detector reacts extremely sensitively to light
aerosols caused by fire. The increased sensitivity makes possible the early detection of
smoldering and open fires.
Characteristics
– Intelligent detector with built-in CPU, providing advanced distributed intelligence for
optimum reliable detection principle
– Opto-electronic sampling chamber detects fire more reliable and accurate
– Collective detector, no address setting, polarity free connection
– Particularly suited for the early detection of smoke-generating flaming and
smoldering fires
– Resistant to environment and interference factors such as dust, fibers, insects,
humidity, extreme temperatures, corrosive, vapors, vibration, synthetic aerosols.
With immunity against electro-magnetic interference
– Self-test of operating status, when fault occurs or low voltage happens, indicator can
prompt user
– Automatic drift compensation and dust prompt for reducing false alarm because of
dust accumulation
– 360° visible alarm indicator
– Dust cap protects the detector from being contaminated by construction work
Building Technologies
Fire safety and security products
Application
– Communication with FC18 controller via FDCI183 transponder, each FDCI183 can
connect max. 32 collective detectors.
– Communication with BC80 controller via BDS161 transponder, each BDS161 can
connect max. 10 collective detectors.
Indicator
The detector is provided with an internal alarm indicator to show its operating status.
Status
Indicator
Normal
Off
Fault
Flash every 5s
Dust Prompt (Heavy dust) Double flash every 5s
Alarm
Steady on
Installation
 Easy and time-saving mounting
Install the base and finish the wiring during the construction phase.
1. Insert detector into base and turn it clockwisely until positioning pointer on base
align with positioning pointer on detector.(see below)
Uninstallation:
1. Turn it counterclockwisely and pull the detector out of base.
Base
Positioning pointer
Detector
Positioning pointer
After all the construction is finished, the dust cap must be taken away!
No painting!
Dimensions
In:mm (with the base)
2
Building Technologies
Fire safety and security products
A6V10361096_b_en_-07.2012
Connection diagram
Connect to
collective input
module
FDB181C
FDB181C
1a
1b
1a
1b
1a
1b
5
6
5
6
5
6
EOL1.5KE20CA
FDB181C
Maintenance
 Performance test
Recommendation:
– Submit all detectors to an annual visual check. Detectors that are strongly soiled or
mechanically damaged must be replaced.
– Long term backup detectors should be stored with sealed plastic bag.
– Carry out smoke test each year.
Technical data
Operating voltage
Operating current (quiescent)
Activation current
Sensitivity
Operating temperature
Storage temperature
Humidity
Color
Protection category GB4208-93
10 … 28 VDC
0.1 mA
60.0 mA
Standard 2.4%m
–10 ... +50 °C
–20 ... +70 °C
≤96% (40±2 ℃)
White, RAL 9010
IP40
Details for ordering
Type
FDO181C
FDB181C
Material No.
S54320-F11-A2
S54320-F9-A2
A5Q00022000
Part No.
101190982
101190980
100566010
Designation
Collective smoke detector
Collective detector base
FDO181 dust cap
Weight
0.081Kg
0.038Kg
3
Building Technologies
Fire safety and security products
A6V10361096_b_en_-07.2012
Beijing Siemens Cerberus Electronics Limited
No.1,Fengzhidonglu, Xibeiwang, HaiDian District,
Beijing, 100094, China
Tel: +10 6476 8806
Fax: +10 6476 8899
Doc No.
A6V10361096_b_en_--
Edition
07.2012
© Data and design subject to change without notice.
Manual FD18
101190920
Download PDF