F-Series TeraFrame

®

Gen 3 Cabinet System

User’s Manual

©2013 Chatsworth Products, Inc. All rights reserved. CPI, CPI Passive Cooling, MegaFrame, Saf-T-Grip,

Seismic Frame, SlimFrame, TeraFrame, GlobalFrame, Cube-iT Plus, Evolution, OnTrac, QuadraRack and Velocity are federally registered trademarks of Chatsworth Products, Inc. eConnect and Simply Efficient are trademarks of Chatsworth Products, Inc.

All other trademarks belong to their respective companies.Rev.3 10/13 MKT-60020-577

Contents  

F-­‐Series  TeraFrame  Gen  3  Cabinet  Overview  ......................................................................................  3

 

Introduction  to  the  F-­‐Series  TeraFrame  Gen  3  Cabinet  ..........................................................................  3

 

Safety  Information  ..................................................................................................................................  3

 

Intended  Use  ..........................................................................................................................................  5

 

Components  of  the  F-­‐Series  TeraFrame  Gen  3  Cabinet  ..........................................................................  6

 

Included  Hardware  .................................................................................................................................  7

 

Tools  Required  ......................................................................................................................................  10

 

Unpacking  .............................................................................................................................................  10

 

Installation  .......................................................................................................................................  12

 

Moving  the  cabinet  ...............................................................................................................................  12

 

Anchoring  the  cabinet  to  the  floor  .......................................................................................................  12

 

Bonding  the  cabinet  to  the  telecommunications  ground  .....................................................................  13

 

Configuring  the  cabinet  ....................................................................................................................  15

 

Removing  and  Installing  the  Front  Door  ...............................................................................................  15

 

Removing  and  Installing  the  Rear  Doors  ...............................................................................................  17

 

Removing  and  Installing  the  Top  Panel  .................................................................................................  18

 

Removing  and  Installing  the  Side  Panels  ..............................................................................................  21

 

Adjusting  the  Equipment  Rails  ..............................................................................................................  24

 

Installing  the  Standard  PDU  Brackets  ...................................................................................................  24

 

Installing  Equipment  .............................................................................................................................  25

 

Cable  Management  ..............................................................................................................................  25

 

Accessories  ......................................................................................................................................  26

 

Cable  Management  ..............................................................................................................................  26

 

Power  Management  .............................................................................................................................  28

 

Thermal  Management  ..........................................................................................................................  29

 

Shelves,  Trays  and  other  accessories  ....................................................................................................  32

 

F-­‐Series  TeraFrame  Gen  3  Cabinet  Overview  

Introduction  to  the  F-­‐Series  TeraFrame  Gen  3  Cabinet  

 

The  F-­‐Series  TeraFrame®  Gen  3  Cabinet  System  from  Chatsworth  Products,  Inc.  (CPI)  has  been   developed  to  meet  a  wide  range  of  application  needs.  The  TeraFrame  is  available  in  multiple  widths,   heights,  and  depths,  allowing  for  precise  alignment  with  the  size  and  capacity  requirements  for  most   installations.      

 

The  F-­‐Series  TeraFrame  Gen  3  cabinet  accessories,  including  cable  management,  power  management,   thermal  management  and  more,  offer  additional  flexibility,  enabling  the  cabinet  to  be  further   configured  to  support  many  different  applications.  

Safety  Information  

 

Keep  a  printed  copy  of  this  User’s  Manual,  especially  the  following  safety  information,  in  or  near  the   cabinet.  

 

 

 

 

 

       WARNINGS:  

• Improper  use  of  this  product  or  failure  to  follow  these  instructions  may  result  in   equipment  damage,  personal  injury,  or  death.  Read  and  understand  all   instructions  for  proper  installation  and  use  of  this  product.  

• Only  trained  service  personnel  or  licensed  electricians  shall  install  the   equipment.  

• Be  sure  to  use  sufficient  personnel  to  safely  remove  the  cabinet  from  the  pallet.  

• Do  not  attempt  to  move  large  cabinets  by  yourself.  Obtain  adequate  assistance   to  stabilize  the  cabinet  during  movement  or  hire  professional  equipment  riggers.  

• Move  cabinets  on  installed  casters  with  extreme  care.  Sudden  stops,  excessive   force,  and  uneven  surfaces  may  cause  the  cabinet  to  overturn.  Move  the  cabinet   with  the  back  as  the  leading  edge.  Never  push  on  the  sides.  

• The  cabinet  shall  be  level,  stable,  bolted  and  appropriately  secured  to  the   building  structure.  Castors  are  only  provided  to  transport  the  cabinet  from  the   receiving  location  to  its  install  location.    

• The  cabinet  shall  be  installed  in  a  Restricted  Access  Location  and  only  used  by   trained  service  personnel.    

• Suitable  for  mounting  on  concrete  or  other  noncombustible  surface  only.    

 

3

Safety  Information  

WARNINGS:  

 

 

 

 

 

 

 

 

 

• Unload  equipment  from  the  cabinet  before  moving  it.  

• Two  or  more  cabinets  can  be  bayed  together  (coupled)  to  enhance  their  stability.  

Each  cabinet  should  be  anchored  to  the  floor.  

• Before  loading  equipment  in  the  cabinet,  be  sure  to  adjust  and  lock  the  leveling  feet   to  level  the  cabinet.  Do  not  use  casters  to  stabilize  the  cabinet;  always  anchor  the   leveling  feet  or  the  cabinet  frame  to  the  floor.  

• Always  load  heavy  equipment,  such  as  a  UPS,  at  the  bottom  of  the  cabinet  first,  and   add  lighter  equipment  on  higher  levels.  

• A  safety  risk  exists  when  equipment  is  mounted  on  a  shelf  installed  more  than  30   inches  (760  mm)  above  the  floor  in  a  cabinet  without  doors  and/or  side  panels.  The   equipment  may  accidentally  slide  or  be  accidentally  pushed  off  the  shelf  and  fall  on   personnel.  When  equipment  is  mounted  on  a  shelf  in  this  condition,  securely  fasten   the  equipment  to  the  shelf  or  cabinet  frame  in  a  manner  that  will  prevent  the   equipment  from  accidentally  sliding  off  the  shelf.  The  following  accessories  may  be   used  to  secure  certain  equipment  on  shelves:  monitor  tie-­‐down  kit  (P/N  11725-­‐701),   seismic  equipment  tie-­‐down  bracket    (P/N  14061-­‐719),  or  equipment  tie-­‐down   bracket  (P/N  16356-­‐719).  

• The  cabinet  can  support  many  system  configurations.  The  amount  of  force  required   to  tip  or  make  the  cabinet  unstable  differs  with  each.  Read  and  follow  your   equipment  manufacturer’s  specific  assembly,  installation,  and  safety  instructions.  

• When  servicing  slide-­‐mounted  equipment  such  as  servers:  

-

Secure  all  equipment,  other  than  the  unit  being  serviced,  in  position  to  prevent   it  from  sliding  out  and  destabilizing  the  cabinet.  

- Slowly  extend  only  one  unit  at  a  time.  Extending  multiple  units  may  cause  the   cabinet  to  tip  over.  Rapid  deployment  of  the  unit  could  cause  the  cabinet  to  tip.  

• For  protection  of  the  equipment  and  personnel,  ground  each  cabinet  individually  to   the  Telecommunications  Equipment  Bonding  Conductor  (TEBC)  or  Signal  Reference  

Structure  (SRS).  

• Provide  the  minimum  spacing  between  the  accessories/components  and  the   housing  that  shall  be  maintained  for  safe  operation  of  the  equipment  when  installed   in  accordance  with  the  National  Electric  Code,  ANSI/NFPA  70.  

• As  appropriate,  all  wiring  and  equipment  should  be  installed  in  accordance  with  

NFPA  70,  “National  Electrical  Code,”  and  the  applicable  sections  of  ANSI  C2,  

“National  Electrical  Safety  Code."  

4

Intended  Use  

 

Keep  a  printed  copy  of  the  Preface  of  this  User’s  Manual  in  or  near  the  cabinet.    

 

•  Install  the  cabinet  only  in  a  Restricted  Access  Location,  such  as  a  data  center.  

•  Use  indoors  only,  in  environmentally  controlled  areas;  do  not  use  outdoors,  in  harsh  environments,   or  in  air-­‐handling  spaces.    

•  Use  the  cabinet  for  information  technology  and  telecommunications  equipment,  including  servers   and  peripherals.    

•  Allow  only  qualified  service  personnel  to  use  the  cabinet.    

•  The  cabinets  must  be  anchored  to  the  floor  to  ensure  stability  and  a  safe  working  environment.  

 

 

 

•  The  F-­‐Series  TeraFrame  Gen  3  Cabinet  is  available  with  a  4-­‐slide  or  6-­‐slide  frame.  The  4-­‐slide  frame   has  two  front-­‐to-­‐back  supports  on  each  side.  The  6-­‐slide  frame  has  three  front-­‐to-­‐back  supports  on   each  side.  6-­‐slide  frames  have  higher  load-­‐bearing  capacity.  The  load-­‐bearing  capacity  of  the  F-­‐Series  

TeraFrame  Gen  3  Cabinet  is:    

  4-­‐Slide  

Static:       2,500  lb  (1134  kg)  

 

   

 

6-­‐Slide  

3,000  lb  (1360  kg)  

 

 

 

5

Components  of  the  F-­‐Series  TeraFrame  Gen  3  Cabinet  

1.      Frame  (6-­‐Slide  shown,  4-­‐Slide  available)  

2.      Front  door  

3.      Equipment  mounting  rails  

4.      Standard  top  panel  

5.      Two  Piece  top  panel  

6.      Vertical  Exhaust  Duct  top  panel  

 

7.      Side  panel  (6-­‐Slide  Shown,  4-­‐Slide  available)  

8.      Double  rear  door  

9.      Single  solid  rear  door  

10.  Air  Director  (included  with  duct)  

11.  Bottom  Panel  (included  with  duct)  

12.  Standard  PDU  bracket  

6

 

Included  Hardware  

1. (2)  Keys   x  2  

 

 

 

2. (50)  M6  Cage  Nuts  and  Screws   x  50  

 

  x  50  

 

3. (2)  Standard  PDU  Brackets  +  (4)  M6x16  Screw  and  Front  Mount  Nut   x  2  

  x  4  

 

 

4. (2)  Baying  Brackets,  (4)  M8x16  Hex  Head  Screws,  +  (4)  M8  Hex  Nuts  

 

 

 

 

 

 

  x  2   x  4  

  x  4  

7

5.  (1)  Ground  Terminal  Block  +  (2)  M5x16  Bolt  +  (2)  M5  Hex  Nut  +  Antioxidant  Compound   x  1  

 

 

 

 

6. (1)  Label  Holder   x  2   x  2   x  1  

 

 

7. (1)  Label  Seals  (Black  or  White)   x  1  

 

 

 

 

8

 

 

 

 

8. (4)  Anchor  Brackets  +  (4)  M8x20  Hex  Head  Screws  

Used  to  secure  the  cabinet  to  the  pallet  during  shipping  and  to  the  floor  at  the  jobsite.   x  4  

           

                           

 

 

                           

9. (1)  Shipping  Bracket  

  x  4  

  x  4  

 

Used  for  shipping  only  –  under  the  front  door  to  help  support  and  secure  the  door.  

  x  1  

 

9

 

 

 

 

Getting  Started

 

 

 

Tools  Required  

1. Utility  Knife   a. For  removing  stretch  wrap  from  around  cabinet  

2. 13  mm  Socket  Wrench     a. For  removing  shipping  brackets  securing  cabinet  to  pallet   b. For  adjusting  equipment  mounting  rail   c. For  installing  baying  brackets  

3. 13  mm  Open  End  Wrench   a. For  adjusting  leveling  feet  

4. 8mm  Socket  or  Open  End  Wrench   a. For  installing  ground  terminal  block  

5. #2  Phillips  Screwdriver   a. For  installing  M6  screws  into  cage  nuts  to  secure  equipment  in  mounting  rails   b. For  removing  and  installing  door  hinges   c. For  installation  and  removal  of  PDU  brackets  

6. 5mm  Ball  Hex  Driver  with  12”L  (300  mm)  shaft  (CPI,  P/N  39150-­‐001,  ordered  separately)   a. For  adjusting  leveling  feet  

 

Unpacking  

 

CAUTION:  The  TeraFrame  cabinet  is  heavy.    Use  a  minimum  of  two  (2)  people  to   unpack  and  remove  the  cabinet  from  the  pallet.  

 

CAUTION: The  TeraFrame  casters  are  for  moving  the  cabinet  short  distances  over   smooth  floor  surfaces  only.    Move  shipping  pallet  as  close  as  possible  to  the  final   installation  location  before  unpacking.    

 

CAUTION: The  TeraFrame  casters  are  not  intended  to  support  cabinet  loads  for   extended  periods  of  time.      Always  level  and  anchor  the  cabinet  after  positioning.      

10

Inspect  the  cabinet  for  damage.    If  any  damage  to  the  cabinet  is  observed,  contact  your  distributor  or  

CPI  Customer  Service.

 

1. Carefully  remove  the  plastic  wrap  surrounding  the  cabinet  using  a  utility  knife.    Be  careful  not  to   allow  the  knife  to  contact  the  cabinet  as  this  may  damage  the  unit.  

2. Remove  the  four  (4)  cardboard  corner  protectors.  

3. Inspect  inside  the  cabinet  to  insure  all  items  are  securely  fastened  to  the  cabinet.    Remove  any   items  that  were  shipped  inside  the  cabinet  but  are  not  fastened  to  the  cabinet.  

4. Remove  the  (4)  anchor  brackets  that  attach  the  cabinet  to  the  pallet  using  a  13  mm  (1/2”)  socket   wrench  and  the  shipping  bracket  under  the  front  door.    

 

ü

 

NOTE:  Do  not  discard  the  (4)  anchor  brackets.    These  brackets  are  used  to  anchor  the   cabinet  to  the  floor.    See  “Anchoring  the  cabinet  to  the  floor”  .  

5. Remove  the  cabinet  from  the  pallet.  

 

RECYCLABLE  MATERIALS:  CPI  uses  only  recyclable  materials  in  all  of  its  cabinet   packaging.    Please  save  packaging  for  later  use  or  dispose  of  properly.    All  wood   components  of  CPI  pallets  have  been  properly  treated  to  comply  with  the  pest-­‐free   certifications  required  by  foreign  countries.  

 

6. If  the  cabinet  is  to  be  reshipped,  save  all  packaging  materials  for  reuse.  

DISCLAIMER:  CPI  is  not  responsible  for  any  damage  to  the  cabinet  or  its  contents  after   the  cabinet  is  repackaged  and  reshipped.  

 

 

   

7. After  the  cabinet  is  unpacked,  check  the  cabinet  and  the  hardware  kit  to  insure  that  all  of  the   components  and  hardware  items  have  been  received  with  the  cabinet.    If  any  components  are   missing  or  damaged,  email  Technical  Support  at  [email protected],  or  call  toll-­‐free  at  

800-­‐834-­‐4969  (US  &  Canada)  Monday  to  Friday,  5  a.m.  to  5  p.m.,  Pacific  Time.  

 

11

Installation  

 

Moving  the  cabinet  

 

CAUTION:  The  F-­‐Series  TeraFrame  Gen  3  Cabinet  ships  on  casters.    Move  the  cabinet   by  pushing  on  the  front  or  the  rear  of  the  cabinet.    Do  not  push  the  cabinet  from  the   sides.  

 

The  TeraFrame  cabinet  has  been  provided  with  four  (4)  casters  to  allow  the  cabinet  to  be  rolled  into  

  position.  

 

Once  the  cabinet  has  been  moved  to  the  final  location,  level  and  anchor  the  cabinet  per  the   instructions  below.    

5mm Ball

Hex Driver Access

13mm Open-Ended

                                                 

Anchoring  the  cabinet  to  the  floor  

 

Insure  that  the  cabinet  has  been  properly  leveled.    All  four  (4)  leveling  feet  should  be  in  firm  contact   with  the  floor  and  the  cabinet  should  not  rock  in  any  direction.    A  level  placed  on  the  cabinet  frame   should  confirm  that  the  cabinet  is  level.    If  the  cabinet  is  not  level,  adjust  the  leveling  feet  with  a  12”  

(300  mm)  long  5mm  hex  ball  driver  (CPI  P/N  39150-­‐001,  ordered  separately)  or  13  mm  open-­‐end   wrench  until  the  cabinet  is  level  and  the  cabinet  will  not  rock  in  any  direction.  

 

F-­‐Series  TeraFrame  Gen  3  Cabinets,  whether  bayed  together  or  standing  alone,  should  be  anchored  to   the  floor.    The  anchor  brackets  that  secured  the  cabinet  to  the  pallet  (shown  on  the  next  page)  are   used  to  anchor  the  cabinet  to  the  floor.    The  brackets  attach  to  the  outside  of  the  frame  (as  they  were   on  the  pallet).    Installation  requires  four  anchors,  either  3/8”  or  M10  hardware.  

12

Anchor  Bracket  

 

 

The  mounting  locations  for  the  anchor  brackets  are  shown  in  the  figure  below.  If  used  as  part  of  an   aisle  containment  solution,  inistall  the  Floor  Seal  Kits  (P/Ns  39208-­‐XXX  and  39209-­‐XXX)  before   attaching  the  anchor  brackets.  

 

 

 

Attach  the  cabinet  to  the  floor  with  3/8”  or  M10  hardware  appropriate  for  your  type  of  flooring.  

Bonding  the  cabinet  to  the  telecommunications  ground  

F-­‐Series  TeraFrame  Gen  3  Cabinets  should  be  bonded  to  the  telecommunications  ground.    The  top   panel,  side  panels,  doors  and  mounting  rails  on  the  TeraFrame  cabinet  are  electrically  bonded  to  the   frame.    A  ground  strap  bonds  the  panels  and  doors  to  the  frame.    In  order  to  bond  the  cabinet  to  the   telecommunications  ground,  use  the  Ground  Terminal  Block  (included)  to  connect  a  bonding  conductor  

  to  the  telecommunications  ground  or  signal  reference  grid.    Remove  the  mask  sticker  at  desired   grounding  location  and  apply  generous  coating  of  gray  antioxidant.  For  top  location,  remove  hole  plug   and  route  wire  through  frame  top  first.    Secure  grounding  wire  to  the  terminal  block.    Attach  the  block   to  the  cabinet  frame  with  an  8  mm  wrench  using  two  M5  bolts  and  nuts.      

13

Baying  cabinets  together

 

F-­‐Series  TeraFrame  Gen  3  Cabinets  can  be  bayed  (fastened)  together  with  solid  side  panels  in  place,   with  a  shared  solid  or  brush  side  panel  between  cabinets,  or  with  no  side  panels,  depending  on   installation  requirements.    Cabinets  must  be  the  same  height  and  depth.  

 

1. Remove  the  hole  plugs  on  top  of  cabinet  frame.  

2. Use  the  supplied  hardware  and  a  13mm  Socket  wrench  to  attach  the  baying  bracket  (included  in   the  hardware  kit)  to  the  first  cabinet.    Make  sure  to  use  the  correct  set  of  holes  for  the  desired   cabinet  spacing  (24”  or  600  mm).    The  24”  spacing  will  center  two  600  mm  wide  cabinets  over  a  24”   access  floor  tile  –  spaces  cabinets  approximately  0.4”  (10  mm)  apart.  The  600  mm  spacing  will  bay   any  two  cabinets  side-­‐by-­‐side.    

600mm

24”

3. Move  the  second  cabinet  so  that  the  cabinets  are  aligned.    This  may  also  require  adjusting  the   leveling  feet  if  the  second  cabinet  was  not  set  at  the  same  level  as  the  first  cabinet.  

4. Use  the  supplied  hardware  to  attach  the  baying  bracket  to  the  second  cabinet.  

5. Repeat  steps  1-­‐4  for  the  other  end  of  the  cabinet.  

14

 

 

Configuring  the  cabinet  

 

The  F-­‐Series  TeraFrame  Gen  3  Cabinet  can  easily  be  configured  for  a  variety  of  applications.    Not  only   can  the  standard  cabinet  components  be  adjusted  or  removed,  but  a  broad  range  of  accessories  can  be  

  installed  to  create  a  cabinet  solution  that  meets  all  the  needs  of  your  installation  requirements.  

 

Removing  and  Installing  the  Front  Door  

 

CAUTION:  To  avoid  personal  injury  and  reduce  the  risk  of  damaging  the  door  or  the   cabinet,  one  person  should  support  the  door  while  another  person  retracts  the  hinge   pins  and  removes  the  door  from  the  frame.  

 

Removing  the  Front  Door:  

1. Open  the  front  door  to  90  degrees  so  that  it  is  perpendicular  to  the  cabinet.  The  door  is   perpendicular  to  the  cabinet  when  it  is  parallel  with  the  side  of  the  cabinet.  

2. Disconnect  the  ground  wire.  

3. While  supporting  the  door,  retract  the  hinge  pin  from  the  upper  hinge.  Note:  the  door,  hinge  pin   and/or  hinge  may  be  damaged  if  the  door  is  not  properly  supported  while  being  removed.  Hold  the   door  so  that  it  does  not  lean.  

4. Lift  the  door  off  the  bottom  hinge  and  move  toward  the  side  of  the  cabinet.  Support  the  door  while   lifting  and  moving  the  door.  The  hinge  is  captive  in  a  pocket  on  the  door.  The  lift  and  move  action   releases  the  hinge  from  the  door.  Note:  you  may  need  to  retract  the  lower  hinge  pin  also.  

5. Once  the  door  is  free  of  the  hinges,  move  the  door  away  from  the  frame.  

4  

3  

               

15

 

 

 

Installing  the  Front  Door:  

1. Hold  the  door  so  that  it  is  perpendicular  to  the  cabinet  and  align  the  hinge  pins  on  the  door  with   the  hinge  barrels  on  the  cabinet.  The  door  is  perpendicular  to  the  cabinet  when  it  is  parallel  with   the  side  of  the  cabinet.  

 

 

 

 

 

 

 

 

2. Lift  the  door  and  move  it  toward  the  hinges.  Align  the  lower  hinge  pin  with  the  lower  hinge  barrel.  

Insert  the  lower  hinge  pin  into  the  lower  hinge  barrel.  Continue  to  support  the  door,  keeping  it   vertical  and  perpendicular  to  the  cabinet  frame.  The  door  must  be  supported  to  prevent  damage  to   the  hinges.  

3. While  supporting  the  door,  retract  the  upper  hinge  pin,  and  then  align  and  release  the  pin  into  the   upper  hinge  barrel.  Check  that  both  hinge  pins  are  inserted  into  the  hinge  barrels  before  releasing   the  door.  Note:  on  tall  cabinets,  you  may  need  to  insert  the  upper  hinge  pin  first.  

 

 

4. Reconnect  the  ground  wire.  

5. Close  the  front  door.  

2  

 

3   4  

16

Removing  and  Installing  the  Rear  Doors  

Removing  the  Rear  Doors:  

1. With  the  doors  closed,  lift  and  remove  the  hinge  pins  from  both  the  upper  and  lower  hinges  on  the   door  that  you  want  to  remove.  

 

2. Partially  open  the  door,  but  not  as  far  as  90  degrees.  

3. Disconnect  the  ground  wire.  

4. Open  the  door  to  exactly  90  degrees  and  pull  the  door  away  from  the  cabinet  frame.  

Installing  the  Rear  Doors:  

1. Hold  the  door  in  a  90  degree  open  position.      

2. Align  the  hinges  on  the  door  with  the  hinges  on  the  frame  and  slide  the  hinges  together.  

 

3. Rotate  the  door  to  the  closed  position.  

4. Insert  the  hinge  pins  (from  the  top  of  the  hinge)  into  both  the  upper  and  lower  door  hinges.    

5. Open  the  door  and  reconnect  the  ground  wire.  

17

Removing  and  Installing  the  Top  Panel  

Removing  the  One-­‐Piece  Top  Panel:  

1. Remove  two  (2)  shipping  brackets  on  top  of  cabinet  using  13mm  socket  wrench.  

2. Open  the  rear  door(s)  of  the  cabinet.  Remove  grounding  wire  from  the  top  panel  (item  1  in  image   next  page).  

3. Depress  and  hold  the  two  (2)  spring  retainers  (item  2  in  image  next  page)  that  hold  the  top  panel  to   the  frame.  

4. Push  up  on  the  top  panel  and  remove.  

 

Installing  the  Top  Panel:  

1. Align  the  front  edge  of  the  top  panel  with  the  frame.  

2. Lower  the  top  panel,  sliding  it  forward  to  make  contact  with  the  front  of  the  frame.  

 

3. Lower  the  back  of  the  top  panel.    Insure  that  the  two  (2)  spring  retainers  have  snapped  in  place  and   secure  the  top  panel  from  lifting.  

4. Reconnect  top  panel  ground  wire.      

18

Removing  the  Two-­‐Piece  Top  Panel:  

1. Open  the  rear  door(s)  of  the  cabinet.  Remove  grounding  wire  from  the  top  panel.  

 

2. Depress  and  hold  the  two  (2)  spring  retainers  that  hold  the  rear  top  panel  to  the  frame.  

 

 

 

3. Push  up  on  the  rear  top  panel  and  remove.  

4. Remove  the  two  (2)  screws  securing  the  front  top  panel  to  the  frame  slides.  

 

 

 

5. Push  up  on  the  front  top  panel  and  remove.  

19

 

Installing  the  Two-­‐Piece  Top  Panel:  

1. Align  the  front  edge  of  the  front  top  panel  with  the  frame.    

 

2. Lower  the  front  top  panel,  sliding  it  forward  to  make  contact  with  the  front  of  the  frame.  

3. Install  two  (2)  screws  to  secure  front  top  panel  to  the  frame  slides.  

4. Lower  the  rear  top  panel,  sliding  it  forward  to  make  contact  with  the  front  top  panel.  

5. Lower  the  back  of  the  rear  top  panel.    Insure  that  the  two  (2)  spring  retainers  have  snapped  in   place  and  secure  the  top  panel  from  lifting.  

6. Reconnect  top  panel  ground  wire.  

 

 

 

 

20

Removing  and  Installing  the  Side  Panels  

Removing  the  Side  Panels  on  6-­‐Slide  Cabinet:  

1. Unlock  the  side  panel  latch  with  the  key  (if  necessary).  

2. Retract  the  side  panel  latch  by  pulling  down  and  allow  the  side  panel  to  tilt  away  from  the  cabinet.  

 

3. Disconnect  the  ground  wire.  

4. Lift  up  on  the  side  panel  and  remove  it  from  the  cabinet.  

Installing  the  Side  Panels  on  6-­‐Slide  Cabinet:  

1. Align  the  side  panel  with  the  cabinet  frame  and  slip  the  side  panel  into  the  side  of  the  frame.    Allow   the  side  panel  to  move  downwards  so  that  the  tabs  on  the  bottom  of  the  panel  engage  the  front-­‐ to-­‐rear  frame  member  below  the  side  panel.  

2. Connect  the  ground  wire.  

3. Rotate  the  side  panel  up  to  meet  the  frame  and  push  until  the  side  panel  latch  engages  the  front-­‐ to-­‐rear  frame  member  above  the  side  panel.  

 

4. Lock  the  side  panel  with  the  key  (if  necessary).  

 

21

 

Removing  the  Side  Panels  on  4-­‐Slide  Cabinet:  

1. Unlock  the  top  side  panel  latch  with  the  key  (if  necessary).  

2. Retract  the  top  side  panel  latch  by  pulling  down  and  allowing  it  to  tilt  away  from  the  cabinet.  

 

3. Disconnect  the  ground  wire  from  the  top  side  panel.  

4. Lift  up  on  the  side  panel  and  remove  it  from  the  cabinet.  

5. Lift  up  on  the  bottom  side  panel  and  remove  it  from  the  cabinet.  

6. Disconnect  the  ground  wire  from  the  bottom  side  panel.  

 

Installing  the  Side  Panels  on  4-­‐Slide  Cabinet:  

1. Align  the  bottom  side  panel  with  the  cabinet  frame  and  slip  the  side  panel  into  the  side  of  the   frame.      

2. Connect  the  ground  wire.  

3. Rotate  the  side  panel  up  to  meet  the  frame  and  slightly  lift  to  engage  the  lower  half  of  the  two  side   panel  catches  on  both  ends  of  the  frame.  

 

22

4. Align  the  top  side  panel  on  the  bottom  side  panel  and  slip  the  side  panel  into  the  side  of  the   frame.  

5. Connect  the  ground  wire.    

6. Rotate  the  top  side  panel  up  to  meet  the  frame  and  slightly  lift  to  engage  the  upper  half  of  the   two  side  panel  catches  on  both  ends  of  the  frame.    The  latch  engages  the  front-­‐to-­‐rear  frame   member  above  the  side  panel.  

 

 

7. Lock  the  side  panel  with  the  key  (if  necessary).  

 

23

 

Adjusting  the  Equipment  Rails  

1. Use  a  13  mm  socket  wrench  to  loosen  (but  do  not  remove)  the  nuts  securing  the  equipment  rail  to   the  frame  in  three  (3)  locations  on  6-­‐Slide  cabinet  or  two  (2)  locations  on  4-­‐Slide  cabinet.  

 

2. Move  the  equipment  rail  forward  or  backward  to  the  desired  location.  

3. Tighten  the  nuts  in  all  three  (3)  locations  on  6-­‐Slide  cabinet  or  two  (2)  locations  on  4-­‐Slide  cabinet.  

 

Markings  are  provided  on  the  frame  to  help  align  the  equipment  rails  so  that  they  are  vertical  as  well   as  in  the  same  location  as  the  rails  on  the  opposite  side  of  the  frame.  

Installing  the  Standard  PDU  Brackets  

1. Choose  the  desired  corner  of  the  cabinet  to  install  the  PDU  Brackets  and  install  cage  nuts  in  square   holes.  

2. Position  PDU  bracket  against  vertical  frame  member  and  install  2  screws  through  holes  into  cage   nuts.    Torque  screws  to  168  in-­‐lb  (19  Nm)  using  a  Phillips  screw  driver.      

3. Repeat  for  second  PDU  Bracket.  

24

Installing  Equipment  

 

The  F-­‐Series  TeraFrame  Gen  3  Cabinet  supports  all  manufacturers’  equipment  that  conforms  to  the  

EIA/ECA-­‐310E  standard.    Most  equipment  attaches  directly  to  the  equipment  mounting  rails;  however,   some  manufacturers  may  provide  brackets  or  slide  assemblies  that  require  additional  installation.  

 

 

Rack-­‐mount  unit  (U)  markings  are  clearly  printed  on  the  equipment  rails  to  simplify  installation  of   components.    Align  equipment  with  the  U  markings  on  each  side  of  the  cabinet  before  securing  the   equipment.  

ü

 

NOTE:  Equipment  rails  should  be  adjusted  to  the  desired  location  (front  to  rear)  prior   to  installing  equipment.    See  “Adjusting  the  Equipment  Rails”  on  page  18.  

 

 

 

The  F-­‐Series  TeraFrame  Gen  3  Cabinet  is  provided  with  hardware  to  secure  equipment  to  the  mounting   rails.    This  hardware  includes  50  sets  of  M6  cage  nuts  and  screws.    Additional  hardware  is  available  for   purchase  (see  “Other  Accessories”  on  page  31).  

Cable  Management  

 

CPI  cable  management  products  provide  the  proper  cable  bend  radii  for  better  data  transmission;   fewer  tangled  cords  and  cable  damage;  and  ease  in  moving,  adding,  and  changing  connections.  The   products  assist  in  complying  with  ANSI/TIA/EIA  installation  of  Category  5/5e/6/6a  and  fiber  cables.  

 

Separate  the  cables  by  type,  gather  into  bundles,  and  fasten  loosely  with  hook  and  loop  fasteners.  CPI  

  offers  Saf-­‐T-­‐Grip  Straps  to  fasten  cable  bundles  (P/N  0200X-­‐series).  

 

See  “Accessories  –  Cable  Management”  on  page  26  for  more  information.  

 

25

 

 

Accessories  

Cable  Management  

Finger  Cable  Manager  no  Cover  

For  23.6”  (600  mm)  wide  cabinets  

Fingers,  attaches  to  equipment  rail  

(Fits  other  width  cabinets  also.)  

Finger  Cable  Manager  with  Cover    

For  27.6”  (700  mm)  wide  cabinets  

Fingers,  Attaches  to  equipment  rail  

Finger  Cable  Manager  with  Cover  

For  31.5”  (800  mm)  wide  cabinets  

Fingers,  Attaches  to  equipment  rail  

42U  x  600    -­‐    39120-­‐X00  

45U  x  600    -­‐    39120-­‐X03  

48U  x  600    -­‐    39120-­‐X06  

52U  x  600    -­‐  39120-­‐X10  

42U  x  700    -­‐    39112-­‐X11  

45U  x  700    -­‐    39112-­‐X14  

48U  x  700    -­‐    39112-­‐X17  

52U  x  700    -­‐    39112-­‐X21  

   42U  x  800    -­‐    39112-­‐X22  

45U  x  800    -­‐    39112-­‐X25  

48U  x  800    -­‐    39112-­‐X28  

52U  x  800    -­‐    39112-­‐X32  

           

39120-XXX

 

39112-XXX

Cable  Lashing  Bracket,  6-­‐Slide  Cabinet  

Two  (2)  half-­‐height  panels  

 

Attaches  to  the  cabinet  frame  

42U    -­‐    39124-­‐X00  

45U    -­‐    39124-­‐X03  

48U    -­‐    39124-­‐X06  

52U    -­‐    39124-­‐X10  

 

 

 

Ring  Cable  Manager,  6-­‐Slide  Cabinet  

For  23.6”  (600  mm)  wide  cabinets  

Two  (2)  half-­‐height  sections  

 

 

 

Ring  Cable  Manager,  6-­‐Slide  Cabinet  

For  27.6”  (700  mm)  wide  cabinets  

Two  (2)  half-­‐height  sections  

42U  x  600    -­‐    39087-­‐X00  

45U  x  600    -­‐    39087-­‐X03  

48U  x  600    -­‐    39087-­‐X06  

52U  x  600    -­‐    39087-­‐X10  

42U  x  700    -­‐    39088-­‐X00  

45U  x  700    -­‐    39088-­‐X03  

48U  x  700    -­‐    39088-­‐X06  

52U  x  700    -­‐    39088-­‐X10  

 

 

 

Ring  Cable  Manager,  6-­‐Slide  Cabinet  

For  31.5”  (800  mm)  wide  cabinets  

Two  (2)  half-­‐height  sections  

42U  x  800    -­‐    39089-­‐X00  

45U  x  800    -­‐    39089-­‐X03  

48U  x  800    -­‐    39089-­‐X06  

52U  x  800    -­‐    39089-­‐X10  

     

X  =  Color  (C=Black,  E=Glacier  White)  –  Other  heights  available.  

26

 

       

Cable  Management  (cont’d)  

Cable  Lashing  Bracket,  4-­‐Slide  Cabinet  

One  (1)  full-­‐height  panel  

 

Attaches  to  the  cabinet  frame  

42U    -­‐    39131-­‐X00  

45U    -­‐    39131-­‐X03  

48U    -­‐    39131-­‐X06  

52U    -­‐    39131-­‐X10  

 

 

Ring  Cable  Manager,  4-­‐Slide  Cabinet  

For  23.6”  (600  mm)  wide  cabinets  

One  (1)  full-­‐height  section  

 

 

Ring  Cable  Manager,  4-­‐Slide  Cabinet  

For  27.6”  (700  mm)  wide  cabinets  

One  (1)  full-­‐height  section  

 

Ring  Cable  Manager,  4-­‐Slide  Cabinet  

For  31.5”  (800  mm)  wide  cabinets  

 

One  (1)  full-­‐height  section  

Cable  Port  Brush  Kit  

Brushes  for  two  (2)  large  cable  knock-­‐outs   in  cabinet  top  panel  

42U  x  600    -­‐    39127-­‐X00  

45U  x  600    -­‐    39127-­‐X03  

48U  x  600    -­‐    39127-­‐X06  

52U  x  600    -­‐    39127-­‐X10  

42U  x  700    -­‐    39128-­‐X00  

45U  x  700    -­‐    39128-­‐X03  

48U  x  700    -­‐    39128-­‐X06  

52U  x  700    -­‐    39128-­‐X10  

42U  x  800    -­‐    39129-­‐X00  

45U  x  800    -­‐    39129-­‐X03  

48U  x  800    -­‐    39129-­‐X06  

52U  x  800    -­‐    39129-­‐X10  

25190-­‐001  

                               

 

 

 

 

 

Front  to  Back  Cable  Manager  

For  27.6”  (700  mm)  &  31.5”  (800  mm)  wide  cabinets   39077-­‐X00  

 

X  =  Color  (C=Black,  E=Glacier  White)  

Other  heights  available.  

27

 

Power  Management  

One  set  of  standard  PDU  brackets  is  included  with  the  F-­‐Series  TeraFrame  Gen  3  Cabinet.    Additional  

PDU  brackets  are  available  as  well  as  a  wide  range  of  power  strips  and  PDU’s,  including  monitored  and  

  switched  versions.  

 

Standard  PDU  Brackets  

Two  (2)  brackets  

Attaches  to  the  cabinet  vertical  frame  member  

39110-­‐701  

 

 

 

 

 

 

 

 

Full  Height  PDU  Bracket  

Two  sizes:  Dual  and  Wide  

Attaches  to  the  cabinet  frame  

Dual  supports  2  x  2.2”W  (51  mm)  PDUs  

 

 

 

Wide  supports  2  x  2.7”W  (69  mm)  PDUs  

Dual,  4.8”  (121  mm)  Wide:  

   42U    -­‐    39086-­‐X00  

   45U    -­‐    39086-­‐X03  

   48U    -­‐    39086-­‐X06  

52U    -­‐    39086-­‐X10  

Wide,  5.8”  (147  mm)  Wide:  

   42U    -­‐    39221-­‐X00  

   45U    -­‐    39221-­‐X03  

   48U    -­‐    39221-­‐X06  

   52U    -­‐    39221-­‐X10  

 

X  =  Color  (C=Black,  E=Glacier  White)  

Other  heights  available.  

28

 

 

Thermal  Management  

 

Vertical  Exhaust  Duct  

Includes  exhaust  duct,  

Extends  14”  –  20”  (356-­‐508  mm)  high  

 

 

Vertical  Exhaust  Duct  

Includes  exhaust  duct,  

 

Extends  20”  –  34”  (508  –  863  mm)  high  

600    -­‐    39177-­‐X00  

700    -­‐    39177-­‐X03  

800    -­‐    39177-­‐X06  

600    -­‐    39177-­‐X01  

700    -­‐    39177-­‐X04  

800    -­‐    39177-­‐X07  

 

 

Vertical  Exhaust  Duct  

Includes  exhaust  duct,  

Extends  34”  –  60”  (863  –  1523  mm)  high  

600    -­‐    39177-­‐X02  

700    -­‐    39177-­‐X05  

800    -­‐    39177-­‐X08  

X  =  Color  (7=Black,  E=Glacier  White)  

 

 

 

 

Side  Panel  with  Brush  Sealed  

Cable  Openings,  6-­‐Slide  Cabinet  

Pair  of  panels  

For  one  side  of  cabinet  

 

 

 

 

 

 

 

Includes  one  (1)  key  

42U  x  800    -­‐    39047-­‐X00  

42U  x  1000    -­‐    39047-­‐X08  

42U  x  1100    -­‐    39047-­‐X12  

42U  x  1200    -­‐    39047-­‐X16  

45U  x  800    -­‐    39047-­‐X51  

45U  x  1000    -­‐    39047-­‐X59  

45U  x  1100    -­‐    39047-­‐X63  

45U  x  1200    -­‐    39047-­‐X67  

48U  x  800    -­‐    39047-­‐XAC  

48U  x  1000    -­‐    39047-­‐XAL  

48U  x  1100    -­‐    39047-­‐XAR  

   48U  x  1200  -­‐    39047-­‐XAW  

52U  x  800    -­‐    39047-­‐XDL  

52U  x  1000    -­‐    39047-­‐XDW  

52U  x  1100    -­‐    39047-­‐XEC  

52U  x  1200    -­‐    39047-­‐XEG  

X  =  Color  (C=Black,  E=Glacier  White)  

Other  sizes  available.  

29

 

 

 

 

 

 

 

Thermal  Management  (cont’d)

 

 

 

 

 

 

 

 

Side  Panel  with  Brush  Sealed  

Cable  Openings,  4-­‐Slide  

Pair  of  panels   for  one  side  of  cabinet  

 

 

 

Includes  one  (1)  key  

42U  x  800    -­‐    39043-­‐X00  

42U  x  1000    -­‐    39043-­‐X08  

42U  x  1100    -­‐    39043-­‐X12  

42U  x  1200    -­‐    39043-­‐X16  

45U  x  800    -­‐    39043-­‐X51  

45U  x  1000    -­‐    39043-­‐X59  

45U  x  1100    -­‐    39043-­‐X63  

45U  x  1200    -­‐    39043-­‐X67  

48U  x  800    -­‐    39043-­‐XAC  

48U  x  1000    -­‐    39043-­‐XAL  

48U  x  1100    -­‐    39043-­‐XAR  

   48U  x  1200  -­‐    39043-­‐XAW  

52U  x  800    -­‐    39043-­‐XDL  

52U  x  1000    -­‐    39043-­‐XDW  

52U  x  1100    -­‐    39043-­‐XEC  

52U  x  1200    -­‐    39043-­‐XEG  

 

Bottom  Panel  with  Brushes  

 

Seals  bottom  of  cabinet  

600  mm  cabinets    -­‐    39132-­‐X00  

700  mm  cabinets    -­‐    39132-­‐X01  

800  mm  cabinets    -­‐    39132-­‐X02  

Airflow  Director  

Use  in  conjunction  with  

Vertical  Exhaust  Duct  

600,  700,  800  mm  cabinets    -­‐    39107-­‐X00  

X  =  Color  (C=Black,  E=Glacier  White)  

Other  Sizes  Available.  

 

 

 

 

 

 

 

 

 

 

 

 

30

Thermal  Management  (cont’d)

 

 

 

 

Air  Dam,  6-­‐Slide  Cabinet  

For  23.6”  (600  mm),  27.6”  (700  mm),       and  31.5”  (800  mm)  wide  cabinets  

Use  with  Bottom  Panel,  p.30,  and    

 

 

 

Snap-­‐In  Filler  Panel,  p.32.  

42U  x  600    -­‐    39085-­‐X00  

45U  x  600    -­‐    39085-­‐X03  

48U  x  600    -­‐    39085-­‐X06  

52U  x  600    -­‐    39085-­‐X10  

42U  x  700    -­‐    39085-­‐X11  

45U  x  700    -­‐    39085-­‐X14  

48U  x  700    -­‐    39085-­‐X17  

52U  x  700    -­‐    39085-­‐X21  

42U  x  800    -­‐    39085-­‐X22

45U  x  800    -­‐    39085-­‐X25  

48U  x  800    -­‐    39085-­‐X28  

52U  x  800    -­‐    39085-­‐X32  

 

 

 

 

Air  Dam,  4-­‐Slide  Cabinet  

For  23.6”  (600  mm),  27.6”  (700  mm),       and  31.5”  (800  mm)  wide  cabinets  

Use  with  Bottom  Panel,  p.30,  and  

 

 

 

Snap-­‐In  Filler  Panel,  p.32.  

42U  x  600    -­‐    39130-­‐X00  

45U  x  600    -­‐    39130-­‐X03  

48U  x  600    -­‐    39130-­‐X06  

52U    x  600  -­‐    39130–X10  

42U  x  700    -­‐    39130-­‐X11  

45U  x  700    -­‐    39130-­‐X14  

48U  x  700    -­‐    39130-­‐X17  

52U  x  700    -­‐    39130-­‐X21  

42U  x  800    -­‐    39130-­‐X22

45U  x  800    -­‐    39130-­‐X25  

48U  x  800    -­‐    39130-­‐X28  

52U  x  800    -­‐    39130-­‐X32  

Baying  Seal  Kit  

Seals  space  between  cabinets  

 

when  bayed  24”  apart  

42U    -­‐    39137-­‐700  

45U    -­‐    39137-­‐703  

48U    -­‐    39137-­‐706  

52U    -­‐    39137-­‐710  

X  =  Color  (C=Black,  E=Glacier  White)  

Other  Sizes  Available.  

31

 

 

 

Snap-­‐In  Grommet  &  Plug  Kit  

For  27.6”  (700  mm)  &  31.5”  (800  mm)  wide  cabinets  

Set  of  8  grommets  that  push     into  equipment  rails  

39133-­‐001  

 

 

 

 

 

 

 

 

 

Snap-­‐In  Filler  Panel  

1U  X19,  Black,  6  EA    -­‐    34537-­‐001  

2U  X19,  Black,  6  EA    -­‐    34538-­‐001  

1U  X19,  Black,  50  EA    -­‐    34537-­‐002  

2U  X19,  Black,  50  EA    -­‐    34538-­‐002  

1U  X19,  Glacier  White,  6  EA    -­‐    34537-­‐E01  

2U  X19,  Glacier  White,  6  EA    -­‐    34538-­‐E01  

1U  X19,  Glacier  White,  50  EA    -­‐    34537-­‐E02  

2U  X19,  Glacier  White,  50  EA    -­‐    34538-­‐E02  

 

Shelves,  Trays  and  other  accessories

Cage  Nuts  &  Screws  

(25)  M6  cage  nuts  and  screws  

12637-­‐001  

Low  Profile  Fixed  Shelf  

1U  x  19”W  

Telescopes  20”-­‐  36”  (510  mm  -­‐  910  mm)  in  depth  

   12610-­‐719  

 

Rack-­‐Mount  Cable  Shelf  

1U  x  19”W   brush  sealed  openings  on  front  for  cable  pass-­‐through  

13517-­‐701  

 

Concrete  Floor  Installation  Kit  

Four  (4)  floor  anchors  

3/8”    -­‐    40604-­‐001  

M10    -­‐    40604-­‐004  