6 to 12.5 Tons York Predator ZH/XP

6 to 12.5 Tons York Predator ZH/XP
6 to 12.5 Tons York Predator ZH/XP
have the following available benefits
R-410a Refrigerant
Slide Out Stainless Steel Drain Pan
Stainless Steel Entire Heat Exchanger
Dual Stage Cooling & Heating
Hot Gas Bypass
Slide Out Fan Chassis for easy service
Hinged Filter and Tooless Access Panels
Phase Monitor Protection
Dirty Filter Switch
2” Pleated Filters
CO2 Demand Control Ventilation
BAS Networkable with Free Web Software
Freeze, Hi/Low Pressures, Undervoltage Protections
Smoke Detectors in both Supply and Return
Thermoguard Coating for both Coils and Casing
Modulating Economizer
CFM & VFD Controlled Modulation Plug Fan Power Exhaust
Fully welded IBC Calculated Isolation Curb
Please, call us
Samy Rezine
Karine Leblanc
Maher Syada
Michelle Sangalang
310-420-6767
310-420-7066
626-255-6406
626-854-4613
[email protected]
[email protected]
[email protected]
[email protected]
246824-YTG-D-0806
®
TECHNICAL GUIDE
Description
®
R-410A
ZH/XP SERIES
6-1/2 - 12-1/2 TON
60 Hertz
ASHRAE 90.1 COMPLIANT
YORK® Predator® units are convertible single packages with a
common footprint cabinet and common roof curb for all 6-1/2
through 12-1/2 ton models. All units have two compressors with
independent refrigeration circuits to provide 2 stages of cooling.
The units were designed for light commercial applications and
can be easily installed on a roof curb, slab, or frame.
All Predator® units are self-contained and assembled on rigid
full perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
All units are convertible between side and down airflow.
Independent economizer designs are used on side and down
discharge applications, as well as all tonnage sizes.
Predator® units are available in the following configurations:
cooling only, cooling with electric heat, cooling with gas heat,
heat pump, and heat pump with electric heat. Electric heaters
are available as factory-installed options or field-installed
accessories.
Tested in accordance with:
6-1/2 THROUGH 10 TON
12-1/2 TON
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
246824-YTG-D-0806
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Component Location
Cooling With Gas Heat
[email protected]®FRQWUROERDUG
)LOWHUDFFHVV
'LVFRQQHFWORFDWLRQ
ZVFUHZFRQQHFWRUIRU7VWDW
´WKURZDZD\
ZLULQJDQGQHWZRUNFRQQHFWLRQV RSWLRQDOGLVFRQQHFWVZLWFK
7HUPLQDOEORFNIRU
KLYROWDJHFRQQHFWLRQ
)LOWHUGULHU
VROLGFRUH
&RQGHQVHUVHFWLRQ
6HFRQGPRGHO
QDPHSODWH
LQVLGHKLQJHG
DFFHVVSDQHO
6OLGHRXWPRWRUDQG
EORZHUDVVHPEO\IRU
HDV\DGMXVWPHQW
DQGVHUYLFH
'XDOVWDJH
FRROLQJIRU
PD[LPXP
FRPIRUW
3RZHUYHQWRUPRWRU
&RPSUHVVRU
DFFHVVKLJK
HIILFLHQF\
FRPSUHVVRU
ZFUDQNFDVH
KHDWHU
JDXJHDOXPL
QL]HGVWHHOWXEXODU
KHDWH[FKDQJHUIRU
ORQJOLIHVWDLQOHVV
VWHHORSWLRQ
%DVHUDLOVZIRUNOLIW
VORWVWKUHHVLGHV
DQGOLIWLQJKROHV
7ZRVWDJHJDV
KHDWLQJWRPDLQWDLQ
ZDUPFRPIRUWDEOH
WHPSHUDWXUH
5RRIFXUEVLQHLJKWDQG
IRXUWHHQLQFKKHLJKWV5RRI
FXUEVIRUWUDQVLWLRQLQJIURP
<RUN6XQOLQHŒIRRWSULQWWR
WKH=+6HULHVIRRWSULQWVDUH
DOVRDYDLODEOHILHOGLQVWDOOHG
DFFHVVRU\
2
%HOWGULYH
EORZHUPRWRU
6OLGHRXWGUDLQSDQ
ZLWKVWHHO´137
IHPDOHFRQQHFWLRQ
7RROOHVV
GRRUODWFK
6LGHHQWU\SRZHU
DQGFRQWUROZLULQJ
NQRFNRXWV
,QWHOOLJHQWFRQWURO
ERDUGIRUVDIHDQG
HIILFLHQWRSHUDWLRQ
&RPSUHVVRUDFFHVV
KLJKHIILFLHQF\FRPSUHVVRU
ZFUDQNFDVHKHDWHU
Unitary Products Group
246824-YTG-D-0806
Heat Pump
Simplicity® Control
board w/screw connectors for T-stat wiring and
network connection
Terminal block
for hi-voltage
connection
Disconnect location
(optional disconnect switch)
Filter access
(2” throw-away)
Filter drier (solid core)
Condenser
section
Second Model
Nameplate Inside
Control Door
Slide-out motor and
blower assembly for
easy adjustment and
service.
Dual stage cooling for maximum
comfort (7-1/2 12-1/2 Only)
Compressor #2
Access (High-Eff
Compressor)
Base Rails w/ Forklift Slots (3 Sides)
& Lifting Holes
Belt-drive
blower
motor
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
Sunline™ footprint to the
XP series footprint are also
available (field installed
accessory)
Toolless
Door Latch
Unitary Products Group
Side entry power
and control wiring
knockouts
Compressor #1 Access
(High-Eff Compressor)
Slide-out drain pain
with steel 3/4” NPT,
Female Connection
3
246824-YTG-D-0806
Nomenclature
6.5-12.5 Ton York® Model Number Nomenclature
Z H 090 N10 A 2 A AA 4 0 1 2 4 A
Product Category
Product Style
A = Style A
B = Style B
C = Style C
Z = A/C, Single Pkg., R-410A
X = HP, Single Pkg., R-410A
Product Identifier
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
H = 11.0+ EER A/C
P = 11.0 EER HP
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller, DFS, APS
Nominal Cooling Capacity
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
078 = 6.5 Ton
090 = 7.5 Ton
102 = 8.5 Ton
120 = 10.0 Ton
150 = 12.5 Ton
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated filters
BAS Ready Unit with Belimo Economizer
Shipping Bag
Heat Type and Nominal Heat Capacity
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
C00 = Cooling Only. No heat installed
Product Generation
Gas Heat Options
4 = Fourth Generation
N10 = 100 MBH Output Aluminized Steel
N15 = 150 MBH Output Aluminized Steel
N20 = 200 MBH Output Aluminized Steel
S10 = 100 MBH Output Stainless Steel
S15 = 150 MBH Output Stainless Steel
S20 = 200 MBH Output Stainless Steel
Additional Options
AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
Electric Heat Options
E09 = 9 KW
E18 = 18 KW
E24 = 24 KW
E36 = 36 KW
E54 = 54 KW
RC = Coil Guard, Shipping Bag & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Airflow
A = Std. Motor
B = Std. Motor/Econo./Barometric Relief (Downflow
Only)
C = Std. Motor/Econo./Power Exhaust (Downflow Only)
D = Std. Motor/Motorized Damper (Downflow Only)
E = Std. Motor/Horizontal Economizer (No Baro.)
F = Std. Motor/Slab Econo./Power Exhaust
(Downflow Only)
G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only)
N = Hi Static Mtr.
P = Hi Static Mtr./Econo./Barometric Relief
(Downflow Only)
Q = Hi Static Mtr./Econo./Power Exhaust
(Downflow Only)
R = Hi Static Mtr./Motorized Damper (Downflow Only)
S = Hi Static Mtr./Horizontal Economizer (No Baro.)
T = Hi Static Mtr./Slab Econo./Power Exhaust
(Downflow Only)
U = Hi Static Mtr./Slab Econo./Barometric Relief
(Downflow only)
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
4
Unitary Products Group
246824-YTG-D-0806
Features and Benefits
Standard Features
• High Efficiency – High efficiency units reach as high as
11.5 EER. Gas/electric units have electronic spark ignition
and power vented combustion with steady state efficiencies
of 80%. These efficiencies exceed all legislated minimum
levels and provide low operating costs.
• Service Friendly – The Predator® incorporates a number
of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other
unauthorized persons. It is recommended that the panels
be secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access to
the condenser coils for cleaning or inspection.
Both the unit control board and ignition control board utilize
flash codes to aid in diagnosis of unit malfunctions. Unique
alarm codes quickly identify the source of the unit alarm.
All units use the same standard filter size. This
standardization removes any confusion on which filter
sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit
easy cleaning. The drain pan is accessed by removing the
drain pan cover plate on the rear of the unit. Once the plate is
removed, the drain pan slides out through the rear of the unit.
All Predator® units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
• Environmentally Aware – For improved Indoor Air
Quality, foil faced insulation is used exclusively
throughout the units.
• Balanced Heating – The Predator® offers “Ultimate
Heating Comfort” with a balance between 1st and 2nd stage
gas heating. The first stage of a gas heat Predator® unit
provides 60% of the heating capacity. Balanced heating
allows the unit to better maintain desired temperatures.
• Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two side
duct covers from the outside of the unit and installs them
over the down shot openings. No panel cutting is required.
Convertible airflow design allows maximum field flexibility
and minimum inventory.
• System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frosting
when the economizer operates at low outdoor air
temperatures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and low-
Unitary Products Group
pressure switches. Internal compressor protection is
standard on all compressors. Crankcase heaters are
standard on reciprocating compressors. Scroll compressors
do not require crankcase heaters. Phase Monitors are
standard on units with scroll compressors. This accessory
monitors the incoming power to the unit and protects the
unit from phase loss and reversed phase rotation.
• Advanced Controls - Simplicity® ZH control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
• Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down to
0°F outdoor ambient without additional assistance.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air
temperature is low or when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life,
an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti-short cycle delay can be temporarily
overridden with the push of a button.
• Lead-Lag - An integrated Lead-Lag option allows equal
run time hours on all compressors, thereby extending
the life of all compressors. This option is selectable on
the unit control board.
• Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling
fan delay times are independent of one another. All units
are programmed with default values based upon their
configuration of cooling and heat.
• Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the gas
valve, if applicable, and the temperature limit switch on
gas and electric heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
• Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a “three
times, you’re out” philosophy. The high and lowpressure switches and the freezestats must trip three
times within two hours before the unit control board will
lock out the associated compressor.
• On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and flash
an alarm code on the control board LED. Each high and
low-pressure switch alarm as well as each freezestat
alarm has its own flash code. The control board saves the
five most recent alarms in memory, and these alarms can
be reviewed at any time. Alarms and programmed values
are retained through the loss of power.
• Reliable – From the beginning – All units undergo
computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term – All
Predator® units are painted with a long lasting, powder
paint that stands up over the life of the unit. The paint
used has been proven by a 1000 hour salt spray test.
5
246824-YTG-D-0806
• Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
To further simplify planning and installation, Predator® ZH
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24”
on-center joists or between 48” on-center joists.
The drain pan can be rotated to drain to either the front or
the rear of the unit. Additionally, the drain pan can be
fitted to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
• Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer forklift
access from 3 sides, and rigging holes are available so that
an overhead crane can be used to place the units on a roof.
• Easy Installation – Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the unit.
A clearly identified location is provided to mount a field
supplied electrical disconnect switch. Utility connections can
be made quickly and with a minimum amount of field labor.
All units are shipped with 2” throw-away filters installed.
• Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to handle
most airflow requirements. For high static applications,
factory installed alternate indoor fan motors are available.
With the optional indoor fan motor, all units can supply
nominal airflow at a minimum of 1.5” ESP.
• Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry a 10year warranty.
Factory Installed Options
YORK® offers several equipment options factory installed, for
the Predator® line.
• Optional Factory Installed Economizers - Predator units
offer a variety of optional factory installed economizers
with low leak dampers. The outdoor air enthalpy sensor
enables economizer operation if the outdoor enthalpy is
less than the setpoint of the economizer logic module. See
economizer options section to determine the correct
economizer for your application.
• Downflow Economizer - (With barometric relief) The economizer is provided with a single enthalpy input.
The economizer is 2% low leakage type, and is shipped
installed and wired. The installer needs only to
assemble and mount the outdoor air hood (Provided).
The economizer has spring return, fully modulating
damper actuators and is capable of introducing up to
100% outdoor air. As the outdoor air intake dampers
open, the return air dampers close. The changeover
from mechanical refrigeration to economizer operation is
regulated by the standard single enthalpy input. There is
6
•
•
•
•
an optional input dual dry bulb available. To meet
regulated air standards, the economizer control accepts
an optional CO2 input for demand ventilation. With
single enthalpy input, the economizer control monitors
outdoor air. The dual enthalpy kit provides a second
input used to monitor the return air. With a dual input kit
installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
• Horizontal Economizer - (Without barometric relief) All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizers only.
• BAS Ready Economizer -(With barometric relief) The economizer is provided with a Belimo actuator that
requires a 0-10V DC input from an external source (i.e.,
field installed building automation system controller).
Power exhaust options are available. The economizer is
2% low leakage type with spring return and fully
modulating dampers capable of introducing up to 100%
outside air. Also include 2” pleated filters.
• Slab Economizer for Energy Recovery Ventilators(With barometric relief and Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type, and is shipped
installed and wired. The economizer has spring return,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to
economizer operation is regulated by the standard
single enthalpy input. There is an optional input dual dry
bulb available. To meet regulated air standards, the
economizer control accepts an optional CO2 input for
demand ventilation.With single enthalpy input, the
economizer control monitors outdoor air. The dual
enthalpy kit provides a second input used to monitor the
return air. With a dual input kit installed, the economizer
control compares the values of the two enthalpy or
temperature inputs and positions the dampers to
provide the maximum efficiency possible.
Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer.
Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly
with an outdoor air hood and filters. The outdoor air
dampers open to the preset position when the indoor fan
motor is energized. The damper has a range of 0% to
100% outdoor air entry. Factory installed option or field
installed accessory.
Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
Aluminized Steel Gas Heat Exchanger - For
applications in non-corrosive environments.
Unitary Products Group
246824-YTG-D-0806
• Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
• Stainless Steel Drain Pan - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
• Electric Heaters - The electric heaters range from 9kW to
54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
• Disconnect Switch - For gas heat units and cooling units
with electric heat, a HACR breaker sized to the unit is
provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
• Convenience Outlet - (Non-Powered/Powered) - This
option locates a 120V single-phase GFCI outlet with cover,
on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source and
wiring. The “Powered” option is powered by a stepdown
transformer in the unit. Factory installed option only.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air.
Factory installed smoke detectors in the return air, may be
subjected to freezing temperatures during "off" times due
to out side air infiltration. These smoke detectors have an
operational limit of 32 °F to 131°F. Smoke detectors
installed in areas that could be out side those limitations
will have to be moved to prevent having false alarms.
• Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally, this
kit stops animals and foreign objects from entering the
space between the inner condenser coil and the main
cabinet. This is not a hail guard kit.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
• Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• Hot Gas Bypass - Allows operation during low load
conditions while avoiding coil frosting and damage to
compressor. When suction pressure falls below valve
Unitary Products Group
setpoint, the valve modulates hot gas to the inlet of the
evaporator.
Control Options
• BAS - Building Automation System Controls Simplicity®
INTELLI-Comfort™ Control - The York® Simplicity®
INTELLI-Comfort™ control is factory installed. It includes a
supply air sensor, a return air sensor, and an outside air
sensor. There are provisions for a field installed dirty filter
indicator switch, an air-proving switch, an Outside Air
Humidity sensor, a Return Air Humidity sensor, an Inside
IAQ sensor, and an Outside Air IAQ sensor. Construction
mode operation, 365-day real time clock with 7 day
programming plus holiday scheduling is built-in. Two
different modes of demand ventilation are achieved through
the INTELLI-Comfort™ using CO2 sensors. It uses an
inside CO2 sensor to perform Demand Ventilation. It can
also use an Outside CO2 sensor to perform Differential
Demand Ventilation. It uses a Patented Comfort Ventilation
algorithm to provide comfortable ventilation air
temperature. The patented economizer-loading algorithm
will protect the equipment when harsh operating conditions
exist. Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the onboard connection for hot gas re-heat system. It uses the
INTELLI-Start™ algorithm to maximize energy savings by
recovering the building from the Unoccupied Setpoints to
the Occupied Setpoints just in time for the Occupied Time
Period to begin. The Simplicity® INTELLI-Comfort™
balances space temperature, ventilation air temperature,
CO2 and humidity for ultimate comfort.
• Simplicity® INTELLI-Comfort™ with ModLINC
Control - The York® Simplicity® INTELLI-Comfort™ with
ModLINC control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an
additional control to translate communications from
MODBUS to the BACnet MSTP protocol.
• Novar® BAS Control - The Novar® ETC-3 building
automation system controller is factory installed. Incudes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
• Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air proving switch.
• CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
• Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
Field Installed Accessories
YORK® offers several equipment accessories for field
installation, for the Predator® line.
• Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
7
246824-YTG-D-0806
•
•
•
•
•
•
•
8
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer
control accepts an optional CO2 input for demand
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit provides a
second input used to monitor the return air. With a dual input
kit installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
Horizontal Economizer - (Without barometric relief) All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizer.
Slab Economizer for Energy Recovery Ventilator(Without barometric relief or Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer
control accepts an optional CO2 input for demand
ventilation.With single enthalpy input, the economizer control
monitors outdoor air. The dual enthalpy kit provides a
second input used to monitor the return air. With a dual input
kit installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
You can order 1EH0409 Barometric Relief/FA Hood for
field installations without an ERV.
Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
Power Exhaust - This accessory installs in the unit with a
down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a
horizontal flow application.
Manual Outdoor Air Damper - Like the motorized outdoor
air damper, each manual outdoor air damper includes a
slide-in damper assembly with an outdoor air hood and
filters. Customers have a choice of dampers with ranges of
0% to 100% or 0% to 35% outdoor air entry.
Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
•
•
•
•
•
•
•
•
•
•
•
•
•
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
CO2 Sensor - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
preset limits.
Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be
installed to prevent the flue exhaust from entering nearby
fresh air intakes.
-60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
Gas Heat High Altitude Kit - This kit converts a gas heat
unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and propane.
Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains the
main burner orifices and gas valve replacement springs.
Gas Piping Kit - Contains pipe nipples, fittings and gas cock
required for gas supply connection with external shut off.
Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. Cooling units
include an adapter panel for easy installation of the
electric heaters. Necessary hardware and connectors are
included with the heaters. All heaters are intended for
single point power supply.
Low Limit / Compressor Lockout Kit
• Compressor Lockout (CLO): To prevent mechanical
(compressorized) operation of the unit during cold
outdoor conditions where there is a risk of returning
liquid refrigerant back to the compressors.
• Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing the
units first stage heating means when there is a demand
for cooling during cold outside conditions.
Metal Frame Filter Kit - Metal frame with polyester filter
medium.
• Permanent Filters - Permanent filters are available.
Unitary Products Group
246824-YTG-D-0806
• Roof Curbs - The roof curbs have insulated decks and are
shipped disassembled The roof curbs are available in 8” and
14” heights. For applications with security concerns, burglar
bars are available for the duct openings of the roof curbs.
• Roof Curb Transition - Single Piece Adapter (10” High) Roof curbs for transitioning from Sunline™ units to
Predator® units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
• Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with twostage heat/two-stage cool or two-stage cooling only
thermostats, depending upon unit configuration.
Accessories
Part Number
1RC0470
1RC0471
1RC0472
1BD0408
2TP04520925
2TP04521825
2TP04522425
2TP04523625
2TP04525425
2TP04520946
2TP04521846
2TP04522446
2TP04523646
2TP04525446
2TP04520958
2TP04521858
2TP04522458
2TP04523658
2TP04525458
2TP04540925
2TP04541825
2TP04542425
2TP04543625
2TP04540946
2TP04541846
2TP04542446
2TP04543646
2TP04540958
2TP04541858
2TP04542458
2TP04543658
1FA0413
1FA0414
2MD04702724
2MD04703324
2EE04705424
2EE04705524
2EE04705224
2EE04705624
2PE04703225
2PE04703246
2PE04703258
2EC04700924
1EH0407
1RD0411
1EH0408
1EH0409
2AQ04700424
2AQ04700324
Description
Roof Curb, 8" Height
Roof Curb, 14" Height
Roof Curb, Transition (7.5 T through 12.5 T)
Burglar Bars, Downflow
Electric Heat 9kW 230V
Electric Heat 18kW 230V
Electric Heat 24kW 230V
Electric Heat 36kW 230V
Electric Heat 54kW 230V
Electric Heat 9kW 460V
Electric Heat 18kW 460V
Electric Heat 24kW 460V
Electric Heat 36kW 460V
Electric Heat 54kW 460V
Electric Heat 9kW 575V
Electric Heat 18kW 575V
Electric Heat 24kW 575V
Electric Heat 36kW 575V
Electric Heat 54kW 575V
Electric Heat 9kW 230V, 42" Tall Cabinet
Electric Heat 18kW 230V, 42" Tall Cabinet
Electric Heat 24kW 230V, 42" Tall Cabinet
Electric Heat 36kW 230V, 42" Tall Cabinet
Electric Heat 9kW 460V, 42" Tall Cabinet
Electric Heat 18kW 460V, 42" Tall Cabinet
Electric Heat 24kW 460V, 42" Tall Cabinet
Electric Heat 36kW 460V, 42" Tall Cabinet
Electric Heat 9kW 575V, 42" Tall Cabinet
Electric Heat 18kW 575V, 42" Tall Cabinet
Electric Heat 24kW 575V, 42" Tall Cabinet
Electric Heat 36kW 575V, 42" Tall Cabinet
Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief)
Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)
Economizer, Downflow (Incl. Barometric Relief & All Hoods)
Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief)
Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief)
"Downflow Economizer, Slab type for ERV (no Barometric Relief or FA hood)", 42" Tall Cabinet
Power Exhaust, Downflow, 230V (For Units with Economizer only)
Power Exhaust, Downflow, 460V(For Units with Economizer only)
Power Exhaust, Downflow, 580V (For Units with Economizer only)
Dual Enthalpy Control (Use with Single Enthalpy Economizer)
Hood Kit, Downflow Economizer (Included with all Downflow Economizers)
Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)
Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood)
Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood)
CO2 Detector Unit Mount
CO2 Detector Space Mount
Unitary Products Group
9
246824-YTG-D-0806
Accessories (Continued)
Part Number
2SD04700424
2MK04700624
1CG0419
1CG0420
1CG0424
1CG0425
1CG0427
1CG0428
1HG0411
1HG0415
1GP0405
1NP0442
1HA0442
1HA0443
1FE0412
2BC04700106
2BC04700151
2BC04700154
1FL0402
1FL0423
2DF0401
1FF0410
1FF0411
Description
Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer)
Low Limit / Compressor Lockout Kit
Coil Guard (Electric / Electric & HP models), 8-1/2 and 10 Ton
Coil Guard (Gas / Electric models), 8-1/2 and 10 Ton
Coil Guard (Electric / Electric and HP models), 12-1/2 Ton
Coil Guard (Gas / Electric models), 12-1/2 Ton
Coil Guard (Electric / Electric & HP Models), 6-1/2 and 7-1/2 Ton
Coil Guard (Gas / Electric Models), 6-1/2 and 7-1/2 Ton
Hail Guard Kit
Hail Guard Kit, 42" Tall Cabinet
Gas Piping Kit
Propane Conversion Kit
High Altitude Kit for Natural Gas
High Altitude Kit for Propane
Flue Exhaust Extension Kit
Gas Heat Kit, -60 deg F, 230V
Gas Heat Kit, -60 deg F, 460V
Gas Heat Kit, -60 deg F, 575V
Permanent Filter Kit
Permanent Filter Kit, 42" Tall Cabinet
Dirty Filter Switch
Filter Frame Kit, Metal
Metal Filter Frame Kit, 42" Tall Cabinet
Guide Specifications
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility. YORK®
Predator® units are convertible single packages with a
common footprint cabinet and common roof curb for all 6-1/2
through 12-1/2 ton models. All units have two compressors
with independent R-410a refrigeration circuits to provide 2
stages of cooling. The units were designed for light commercial
applications and can be easily installed on a roof curb, slab, or
frame. All Predator® units are self-contained and assembled
on rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging. Every unit is completely charged
with R-410a, wired, piped, and tested at the factory to provide
a quick and easy field installation. All units are convertible
between side and down airflow. Independent economizer
designs are used on side and down discharge applications, as
well as all tonnage sizes. Predator® units are available in the
following configurations: cooling only, cooling with electric
heat, cooling with gas heat, heat pump, and heat pump with
electric heat. Electric heaters are available as factory-installed
options or field-installed accessories.
DESCRIPTION
Units shall be factory assembled, single package, (Elec/Elec, Gas/
Elec), designed for outdoor installation. They shall have built in
field convertible duct connections for down discharge supply/return
or horizontal discharge supply/return and be available with factory
installed options or field installed accessories. The units shall be
factory wired, piped and charged with R-410a refrigerant and
factory tested prior to shipment. All unit wiring shall be both
10
numbered and color coded. The cooling performance shall be
rated in accordance with DOE and ARI test procedures. Units shall
be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up to
1” thick insulation coated on the airside. Aluminum foil faced
insulation shall be used in the unit’s compartments and be
fastened to prevent insulation from entering the air stream.
Cabinet doors shall be hinged with toolless access for easy
servicing and maintenance. Full perimeter base rails shall be
provided to assure reliable transit of equipment, overhead
rigging, fork truck access and proper sealing on roof curb
applications. Disposable 2” filters shall be furnished and be
accessible through hinged access door. Fan performance
measuring ports shall be provided on the outside of the cabinet
to allow accurate air measurements of evaporator fan
performance without removing panels or creating bypass of the
coils. Condensate pan shall be slide out design, constructed of
a non corrosive material, internally sloped and conforming to
ASHRAE 62-B9 standards. Condensate connection shall be a
minimum of ¾” I.D. female and be rigid mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall not
exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service
Unitary Products Group
246824-YTG-D-0806
factor. Fan wheel shall be double inlet type with forward curve
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
volume. Bearings shall be sealed and permanently lubricated
for longer life and no maintenance. Entire blower assembly and
motor shall be slide out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge air
vertically, have aluminum blades riveted to corrosion resistant
steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently
lubricated bearings internally protected against overload
conditions and staged independently. A cleaning window shall be
provided on two sides of the units for coil cleaning.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or –
10% of the unit nameplate voltage.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.
b. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice
expansion devices.
or
thermally
operated
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
d. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit
Unitary Products Group
should any of the following standard safety devices trip
and shut off compressor:
c. Loss-of-charge/Low-pressure switch.
• High-pressure switch.
• Freeze-protection thermostat, evaporator coil. If any of
the above safety devices trip, an LED (light-emitting
diode) indicator shall flash a diagnostic code that
indicates which safety switch has tripped.
d. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
e. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
f. Unit control board shall have on-board diagnostics and
fault code display.
g. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 ºF.
h. Control board shall monitor each refrigerant safety switch
independently.
i. Control board shall retain last 5 fault codes in nonvolatile memory, which will not be lost in the event of a
power loss.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. The heat exchanger shall
be of the tubular type, constructed of T1-40 aluminized steel for
corrosion resistance and allowing minimum mixed air entering
temperature of 40 ºF. Burners shall be of the in-shot type, constructed of aluminum-coated steel. All gas piping shall enter the
unit cabinet at a single location, through either the side or bottom, without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft pressure sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls. Unit shall have two independent
stages of capacity (60% 1st stage, 100% 2nd stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 9 thru 54 KW, offering two states
of capacity all sizes. The heating section shall have a primary
limit control(s) (automatic reset) to prevent the heating element
system from operating at an excessive temperature. The Heating Section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating Sections shall be
wired for a single point power supply with branch circuit fusing
(where required).
11
246824-YTG-D-0806
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor
temperature, exceeding maximum load criteria of ARI Standard
340/360. The compressor, with standard controls, shall be
capable of operation down to 0 ºF outdoor temperature. Unit
shall be provided with fan time delay to prevent cold air delivery
before heat exchanger warms up. (Gas heat only)
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5 Years,
Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years,
Parts – 1 Year
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be
made available by either/or):
• ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER
– Outdoor and return air dampers that are interlocked and
positioned by a fully-modulating, spring-return damper
actuator. The maximum leakage rate for the outdoor air
intake dampers shall not exceed 2% when dampers are
fully closed and operating against a pressure differential
of 0.5 IWG. A unit-mounted potentiometer shall be
provided to adjust the outdoor and return air damper
assembly to take in outdoor air to meet the minimum
ventilation requirement of the conditioned space during
normal operation. During economizer operation, a mixedair temperature control shall modulate the outdoor and
return air damper assembly to prevent the supply air
temperature from dropping below 55 ºF. Changeover from
compressor to economizer operation shall be provided by
an integral electronic enthalpy control that feeds input into
the basic module. The outdoor intake opening shall be
covered with a rain hood that matches the exterior of the
unit. Water eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
Available with barometric relief or power exhaust.
• MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and
return air dampers that are interlocked and positioned by
a 2-position, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG. A
unit-mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
– regardless of the outdoor air enthalpy. Dampers return
to the fully closed position when the indoor fan motor is
de-energized. Dampers shall fully close on power loss.
12
ADDITIONAL FACTORY INSTALLED OPTIONS
• ALTERNATE INDOOR BLOWER MOTOR – For
applications with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
• CONVENIENCE OUTLET (POWERED/NON-POWERED)–
Unit can be provided with an optional 120VAC GFCI outlet
with cover on the corner of the unit housing the compressors.
• ELECTRIC HEAT - Electric Heaters range from 9 kW to
54 kW and are available in all the voltage options of the
base unit.
• PHASE MONITOR - Designed to prevent damage in outof-phase condition.
• COIL GUARD - Designed to prevent condenser coil
damage.
• BAS CONTROLS - Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
• DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally highpressure drop across the filters.
• BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
• DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest
electric heat available.
• STAINLESS STEEL HEAT EXCHANGER – For
applications in a corrosive environment, this option
provides a full stainless steel heat exchanger assembly.
• SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
• ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
• BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
• PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
• 60ºF GAS HEAT KIT – Provides an electric heat kit for the
gas compartment for use in extreme low ambient
conditions.
• ECONOMIZER (Downflow and Horizontal flow)
• POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
• DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
Unitary Products Group
246824-YTG-D-0806
Physical Data
ZH078-150 Physical Data
Models
Component
ZH078
ZH090
ZH102
ZH120
ZH150
6.5
7.5
8.5
10
12.5
Gross Capacity @ ARI A point (Btu)
79000
93000
106000
126000
156000
ARI net capacity (Btu)
76000
90000
102000
122000
150000
EER
11.4
11.4
11.5
11.5
11.2
SEER
-
-
-
-
-
IPLV
12.7
12.4
12.4
12.1
12.7
Nominal CFM
2600
3000
3400
4000
5000
System power (KW)
6.67
7.90
8.87
10.61
13.40
R-410a
R-410a
R-410a
R-410a
R-410a
System 1
9-4
8-8
11-8
11-8
19-8
System 2
6-0
8-4
11-0
11-8
19-8
Nominal Tonnage
ARI COOLING PERFORMANCE
Refrigerant type
Refrigerant charge (lb-oz)
ARI HEATING PERFORMANCE
Heating model
10
15
10
15
10
Heat input (K Btu)
Heat output (K Btu)
120
180
96
144
120
180
120
180
96
144
96
144
-
-
-
-
-
-
Steady state efficiency (%)
80
80
80
80
80
No. burners
4
6
4
6
No. stages
2
2
2
2
20-50
35-65
15-45
Gas Limit Setting (ºF)
165
165
Gas piping connection (in.)
3/4
3/4
AFUE %
Temperature Rise Range (ºF)
15
15
20
15
20
180
240
180
240
144
192
144
192
-
-
-
-
80
80
80
80
80
4
6
6
8
6
8
2
2
2
2
2
2
30-60
10-40
25-55
20-50
35-65
10-40
25-55
165
165
215
195
195
160
195
160
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
DIMENSIONS (inches)
Length
89
89
89
89
Width
59
59
59
59
59
Height
42
42
50-3/4
50-3/4
50-3/4
900
920
1135
1135
1400
Scroll
Scroll
Scroll
Scroll
Scroll
OPERATING WT. (lbs.)
119-7/16
COMPRESSORS
Type
Quantity
2
2
2
2
2
50 / 100
50 / 100
50 / 100
50 / 100
50 / 100
Face area (Sq. Ft.)
23.8
23.8
29.0
29.0
47.5
Rows
2/1
2
2
2
2
20
20
20
20
15
Unit Capacity Steps (%)
CONDENSER COIL DATA
Fins per inch
Tube diameter (in.)
Circuitry Type
3/8
3/8
3/8
3/8
3/8
Split-face
Split-face
Split-face
Split-face
Split-face
13.2
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.6
10.6
13.2
13.2
Rows
3
3
4
4
4
Fins per inch
15
15
15
15
15
Tube diameter
0.375
0.375
0.375
0.375
0.375
Circuitry Type
Split-face
Split-face
Split-face
Split-face
Split-face
TXV
TXV
TXV
TXV
TXV
Refrigerant control
Unitary Products Group
13
246824-YTG-D-0806
ZH078-150 Physical Data (Continued)
Models
Component
ZH078
ZH090
ZH102
ZH120
ZH150
6.5
7.5
8.5
10
12.5
2
2
2
2
4
Nominal Tonnage
CONDENSER FAN DATA
Quantity
24
24
24
24
24
Type
Fan diameter (Inch)
Prop
Prop
Prop
Prop
Prop
Direct
Drive type
Direct
Direct
Direct
Direct
No. speeds
1
1
1
1
1
Number of motors
2
2
2
2
4
Motor HP each
1/3
1/3
3/4
3/4
1/3
RPM
850
850
1110
1110
850
Nominal total CFM
6800
6800
8800
8800
14000
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
1
1
12 x 12
12 x 12
15 x 15
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK74
AK66
AK69
AK64
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
2
2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
56
56
56
184T
Frame size
FILTERS
Quantity - Size
14
4 - 25 x 16 x 2
4 - 25 x 16 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
Unitary Products Group
246824-YTG-D-0806
XP078-150 Physical Data
Component
Models
XP078
XP090
XP102
XP120
XP150
6.5
7.5
8.5
10
12.5
Gross Capacity @ ARI A point (Btu)
80000
95000
104000
122000
156000
ARI net capacity (Btu)
78000
92000
100000
118000
150000
EER
11.0
11.0
11.0
11.0
11.0
SEER
-
-
-
-
-
IPLV
12.4
12.4
12.4
12.4
11.9
Nominal CFM
2600
3000
3400
4000
5000
System power (KW)
7.10
8.35
9.10
10.70
13.60
R-410a
R-410a
R-410a
R-410a
R-410a
System 1
9-0
9-8
13-8
14-0
16-0
System 2
9-4
9-0
13-0
14-0
16-0
47°F capacity rating (MBH)
78.0
92.0
94.0
110.0
144.0
System power (KW) / COP
6.5 / 3.50
7.6 / 3.50
7.8 / 3.50
9.2 / 3.50
13.2 / 3.20
17°F capacity rating (MBH
48.0
55.0
57.0
66.0
90.0
System power (KW) / COP
6.2 / 2.30
7.0 / 2.30
7.3 / 2.30
8.3 / 2.30
11.9 / 2.20
-
-
-
-
119-7/16
Nominal Tonnage
ARI COOLING PERFORMANCE
Refrigerant type
Refrigerant charge (lb-oz)
ARI HEATING PERFORMANCE
HSPF (Btu/Watts-hr)
DIMENSIONS (inches)
Length
89
89
89
89
Width
59
59
59
59
59
Height
42
42
50-3/4
50-3/4
50-3/4
920
920
1135
1135
1400
Scroll
Scroll
Scroll
Scroll
Scroll
2
2
2
2
2
50 / 100
50 / 100
50 / 100
50 / 100
50 / 100
23.8
23.8
29.0
29.0
47.5
2
2
2
2
2
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
20
20
20
20
15
Tube diameter (in.)
3/8
3/8
3/8
3/8
3/8
Split-face
Split-face
Split-face
Split-face
Split-face
13.2
Circuitry Type
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.6
10.6
13.2
13.2
Rows
3
3
4
4
4
Fins per inch
15
15
15
15
15
Tube diameter
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Split-face
Split-face
Split-face
Split-face
Split-face
TXV
TXV
TXV
TXV
TXV
Refrigerant control
Unitary Products Group
15
246824-YTG-D-0806
XP078-150 Physical Data (Continued)
Models
Component
XP078
XP090
XP102
XP120
XP150
6.5
7.5
8.5
10
12.5
2
2
2
2
4
Nominal Tonnage
CONDENSER FAN DATA
Quantity
24
24
24
24
24
Type
Fan diameter (Inch)
Prop
Prop
Prop
Prop
Prop
Direct
Drive type
Direct
Direct
Direct
Direct
No. speeds
1
1
1
1
1
Number of motors
2
2
2
2
4
Motor HP each
1/3
1/3
1/3
1/3
1/3
RPM
850
850
850
850
850
Nominal total CFM
6800
6800
6800
6800
14000
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
1
1
12 x 12
12 x 12
15 x 15
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK74
AK66
AK69
AK64
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
2
2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
56
56
56
184T
Frame size
FILTERS
Quantity - Size
4 - 25 x 16 x 2
4 - 25 x 16 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
ZH/XP078-150 Unit Limitations
Unit Limitations
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
16
Model
ZH/XP
ZH/XP
ZH/XP
ZH/XP
ZH/XP
Unit Voltage
Applied Voltage
Outdoor DB Temp
Min
Max
208/230-3-60
187
252
Max (°F)
125
460-3-60
432
504
125
125
575-3-60
540
630
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
125
575-3-60
540
630
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
Unitary Products Group
246824-YTG-D-0806
Capacity Performance
ZH078-150 Cooling Capacities
ZH078 (6.5 Ton)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
100.5
91.5
82.5
78.1
104.3
95.0
85.6
81.0
78.6
108.0
98.4
88.7
83.9
81.4
111.8
101.8
91.8
86.8
84.3
104.1
93.8
88.7
86.2
106.3
95.9
90.6
88.1
4.5
4.5
4.4
4.4
4.6
4.5
4.5
4.5
4.5
4.6
4.6
4.5
4.5
4.5
4.6
4.6
4.6
4.5
4.6
4.6
4.6
4.5
4.6
4.6
4.6
4.6
4.6
42.8
53.4
63.9
78.1
46.3
59.4
72.5
81.0
78.6
49.7
65.4
81.1
83.9
81.4
53.2
71.5
89.7
86.8
84.3
76.6
92.8
88.7
86.2
81.7
95.9
90.6
88.1
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
89.1
80.8
72.5
67.9
91.7
83.1
74.6
69.9
72.2
94.2
85.5
76.7
71.8
74.2
96.8
87.8
78.8
73.8
76.3
89.5
80.3
75.2
77.8
91.3
81.9
76.7
79.3
5.9
5.9
5.8
5.8
5.9
5.9
5.8
5.8
5.8
5.9
5.9
5.8
5.8
5.8
5.9
5.9
5.8
5.8
5.8
5.9
5.8
5.8
5.8
5.9
5.8
5.8
5.8
36.5
49.3
62.1
67.9
42.3
55.0
67.7
69.9
72.2
48.2
60.7
73.2
71.8
74.2
54.1
66.4
78.8
73.8
76.3
72.0
80.3
75.2
77.8
77.6
81.9
76.7
79.3
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
33.7
25.9
94.8
5.2
45.6
37.8
30.0
86.2
5.2
57.4
49.6
41.8
34.0
77.5
5.1
72.3
61.3
53.5
45.7
37.9
73.0
5.1
37.5
28.7
98.0
5.2
50.6
41.8
33.0
89.0
5.2
63.7
54.9
46.1
37.3
80.1
5.2
77.1
67.8
59.0
50.2
41.4
75.4
5.1
78.3
69.5
60.7
51.9
43.1
75.4
5.1
41.2
31.4
101.1
5.3
55.6
45.8
36.0
91.9
5.2
70.0
60.2
50.4
40.6
82.7
5.2
81.9
74.3
64.5
54.7
44.9
77.9
5.2
81.3
76.2
66.4
56.5
46.7
77.8
5.2
45.0
34.2
104.3
5.3
60.6
49.8
39.0
94.8
5.2
76.3
65.5
54.6
43.8
85.3
5.2
86.8
80.8
70.0
59.2
48.4
80.3
5.2
84.3
82.8
72.0
61.2
50.4
80.3
5.2
64.8
53.0
41.3
96.8
5.2
81.5
69.7
57.9
46.1
87.1
5.2
88.7
85.7
74.0
62.2
50.4
82.0
5.2
86.2
85.4
73.7
61.9
50.1
82.0
5.2
69.0
56.2
43.5
98.8
5.2
86.6
73.9
61.2
48.4
88.9
5.2
90.6
90.6
77.9
65.2
52.4
83.7
5.2
88.1
88.1
75.3
62.6
49.8
83.7
5.2
95°F
30.3
22.8
82.2
6.9
41.8
34.3
26.7
74.4
6.7
53.3
45.8
38.2
30.7
66.5
6.5
67.9
56.1
48.6
41.0
33.5
62.2
6.5
33.7
25.1
84.5
6.9
46.4
37.7
29.1
76.4
6.7
59.0
50.4
41.7
33.1
68.4
6.5
69.9
61.7
53.1
44.4
35.8
63.9
6.5
70.6
61.9
53.3
44.6
36.0
66.6
6.5
37.1
27.3
86.8
6.9
50.9
41.2
31.4
78.5
6.7
64.7
55.0
45.2
35.4
70.2
6.6
71.8
67.3
57.6
47.8
38.0
65.6
6.5
73.4
67.6
57.8
48.0
38.2
68.4
6.5
40.5
29.6
89.0
6.9
55.5
44.6
33.7
80.5
6.8
70.5
59.6
48.6
37.7
72.0
6.6
73.8
73.0
62.1
51.1
40.2
67.3
6.5
76.3
73.2
62.3
51.4
40.5
70.2
6.5
60.0
47.9
35.8
81.9
6.8
76.0
63.9
51.9
39.8
73.2
6.6
75.2
74.8
62.8
50.7
38.6
68.4
6.5
77.8
76.3
64.2
52.1
40.0
71.4
6.5
64.4
51.1
37.9
83.2
6.8
81.6
68.3
55.1
41.8
74.4
6.6
76.7
76.7
63.5
50.2
37.0
69.5
6.5
79.3
79.3
66.0
52.8
39.5
72.5
6.5
90
39.6
51.3
63.0
73.0
44.3
57.2
70.1
75.4
75.4
49.0
63.1
77.2
77.9
77.8
53.6
68.9
84.2
80.3
80.3
74.3
86.6
82.0
82.0
79.7
88.9
83.7
83.7
31.8
46.5
61.2
62.2
39.9
52.4
64.8
63.9
66.6
48.1
58.2
68.4
65.6
68.4
56.2
64.1
72.0
67.3
70.2
69.4
73.2
68.4
71.4
74.6
74.4
69.5
72.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
32.0
24.3
43.7
36.0
28.4
55.4
47.7
40.0
32.4
70.1
58.7
51.0
43.4
35.6
26.9
48.5
39.7
31.0
61.4
52.6
43.9
35.2
73.5
64.8
56.0
47.3
74.4
65.7
57.0
48.3
39.2
29.4
53.3
43.5
33.7
67.4
57.6
47.8
38.0
76.9
70.8
61.0
51.2
77.4
71.9
62.1
52.3
42.8
31.9
58.1
47.2
36.3
73.4
62.5
51.6
40.8
80.3
76.9
66.0
55.2
80.3
78.0
67.2
56.3
62.4
50.4
38.5
78.7
66.8
54.9
42.9
82.0
80.3
68.4
56.4
82.0
80.8
68.9
57.0
66.7
53.7
40.7
84.1
71.1
58.1
45.1
83.7
83.7
70.7
57.7
83.7
83.7
70.7
57.7
105°F
27.9
20.7
39.2
31.9
24.6
50.4
43.2
35.9
28.6
62.2
51.0
43.7
36.4
31.4
22.8
43.8
35.2
26.7
56.2
47.7
39.1
30.6
63.9
56.3
47.7
39.2
64.8
56.2
47.7
39.1
34.8
25.0
48.4
38.6
28.7
62.0
52.2
42.3
32.5
65.6
61.6
51.7
41.9
67.5
61.5
51.7
41.9
38.2
27.1
53.0
41.9
30.8
67.8
56.7
45.6
34.5
67.3
66.9
55.8
44.7
70.2
66.8
55.7
44.6
57.1
44.9
32.7
71.0
60.8
48.6
36.4
68.4
68.2
56.0
43.8
71.4
69.7
57.5
45.3
61.3
48.0
34.7
74.2
64.9
51.6
38.3
69.5
69.5
56.2
42.9
72.5
72.5
59.2
45.9
65
35.7
38.6
39.5
41.4
42.5
44.3
45.4
44.5
45.1
44.7
44.7
29.1
30.6
30.6
32.1
32.0
33.6
33.5
31.6
33.1
29.6
32.6
17
246824-YTG-D-0806
ZH078 (6.5 Ton)(Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
75.4
68.0
60.5
56.4
77.4
69.7
62.1
57.8
61.0
79.3
71.5
63.7
59.3
62.6
81.3
73.3
65.3
60.8
64.1
74.2
66.1
61.5
64.9
75.1
66.9
62.3
65.7
7.9
7.6
7.3
7.2
7.9
7.6
7.3
7.3
7.2
7.9
7.6
7.3
7.3
7.2
8.0
7.6
7.3
7.3
7.3
7.6
7.3
7.3
7.3
7.6
7.3
7.3
7.3
27.1
43.7
60.2
56.4
37.5
49.7
61.9
57.8
61.0
47.9
55.8
63.6
59.3
62.6
58.4
61.8
65.3
60.8
64.1
66.7
66.1
61.5
64.9
71.5
66.9
62.3
65.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
25.6
18.6
68.5
8.9
36.6
29.6
22.5
61.5
8.4
47.6
40.6
33.5
26.5
54.6
8.0
56.4
45.8
38.8
31.8
24.7
50.6
8.0
29.1
20.6
70.2
8.9
41.2
32.8
24.3
63.0
8.5
53.4
45.0
36.5
28.0
55.9
8.0
57.8
50.8
42.4
33.9
25.4
51.8
8.0
59.0
50.6
42.1
33.6
25.2
55.4
7.9
32.5
22.6
71.9
9.0
45.9
36.0
26.1
64.5
8.5
59.3
49.4
39.5
29.6
57.2
8.0
59.3
55.8
45.9
36.0
26.2
53.1
8.0
61.6
55.5
45.6
35.8
25.9
56.7
8.0
35.9
24.6
73.5
9.0
50.5
39.2
27.9
66.0
8.5
65.1
53.8
42.5
31.2
58.5
8.0
60.8
60.8
49.5
38.2
26.9
54.3
8.0
64.1
60.5
49.2
37.9
26.6
58.1
8.0
54.3
42.0
29.7
66.5
8.5
66.0
57.6
45.3
33.0
59.0
8.0
61.5
61.5
49.2
36.9
24.6
54.7
8.0
64.9
63.1
50.8
38.4
26.1
58.5
8.0
58.2
44.8
31.5
67.0
8.5
66.9
61.5
48.1
34.8
59.4
8.0
62.3
62.3
48.9
35.6
22.2
55.1
8.0
65.7
65.7
52.4
39.0
25.7
58.9
8.0
90
27.1
40.8
54.6
50.6
38.3
47.1
55.9
51.8
55.4
49.4
53.3
57.2
53.1
56.7
60.5
59.5
58.5
54.3
58.1
64.0
59.0
54.7
58.5
67.0
59.4
55.1
58.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
21.3
16.5
34.0
27.2
20.4
44.8
38.0
31.2
24.4
50.6
40.7
33.9
27.1
26.7
18.4
38.7
30.3
21.9
50.7
42.3
33.9
25.5
51.8
45.4
37.0
28.6
53.3
44.9
36.5
28.2
32.1
20.2
43.4
33.4
23.5
56.5
46.6
36.7
26.7
53.1
50.0
40.1
30.2
55.7
49.5
39.6
29.6
37.5
22.1
48.0
36.5
25.0
58.5
50.9
39.4
27.9
54.3
54.3
43.2
31.7
58.1
54.1
42.6
31.1
51.5
39.1
26.6
59.0
54.5
42.0
29.6
54.7
54.7
42.4
30.0
58.5
56.5
44.1
31.6
55.1
41.6
28.2
59.4
58.1
44.7
31.2
55.1
55.1
41.7
28.3
58.9
58.9
45.5
32.1
65
20.3
20.3
19.8
20.2
19.7
20.2
19.6
17.5
19.2
14.9
18.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
18
Unitary Products Group
246824-YTG-D-0806
ZH090 (7.5 Ton)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
119.1
107.7
96.3
91.3
123.0
111.2
99.4
94.2
87.2
126.8
114.7
102.5
97.2
89.9
130.7
118.1
105.6
100.1
92.6
120.9
108.1
102.4
94.9
123.6
110.6
104.8
97.1
5.6
5.5
5.3
5.3
5.6
5.5
5.3
5.3
5.3
5.6
5.5
5.3
5.3
5.3
5.6
5.5
5.3
5.3
5.3
5.8
5.6
5.6
5.6
6.1
6.0
5.9
5.9
50.2
63.0
75.8
91.3
55.4
69.1
82.8
94.2
87.2
60.5
75.2
89.9
97.2
89.9
65.6
81.3
96.9
100.1
92.6
86.4
103.7
102.4
94.9
91.5
110.6
104.8
97.1
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
97.7
90.9
84.2
76.5
101.3
94.3
87.3
79.4
80.8
105.0
97.7
90.4
82.2
83.7
108.6
101.1
93.6
85.1
86.6
101.6
94.1
85.6
87.1
102.2
94.6
86.0
87.5
6.9
6.8
6.8
6.7
6.9
6.8
6.8
6.7
6.7
6.9
6.8
6.8
6.7
6.7
6.9
6.9
6.8
6.8
6.8
6.9
6.8
6.8
6.8
6.9
6.8
6.8
6.8
42.9
55.8
68.7
76.5
48.1
62.3
76.6
79.4
80.8
53.3
68.9
84.4
82.2
83.7
58.4
75.4
92.3
85.1
86.6
81.0
93.4
85.6
87.1
86.6
94.6
86.0
87.5
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
42.2
34.1
108.4
6.2
54.9
46.8
38.7
99.3
6.1
67.7
59.6
51.5
43.4
90.2
6.1
88.6
75.9
67.8
59.7
51.6
83.9
6.0
46.1
36.7
112.2
6.2
59.8
50.5
41.2
102.7
6.1
73.5
64.2
54.9
45.6
93.3
6.1
92.4
81.8
72.5
63.2
53.9
86.8
6.0
87.2
81.7
72.3
63.0
53.7
84.0
6.0
50.0
39.4
115.9
6.2
64.6
54.1
43.6
106.2
6.1
79.3
68.8
58.3
47.7
96.5
6.1
96.3
87.7
77.2
66.6
56.1
89.7
6.0
89.9
87.5
77.0
66.5
55.9
86.8
6.0
53.9
42.1
119.7
6.2
69.5
57.8
46.0
109.6
6.2
85.2
73.4
61.7
49.9
99.6
6.1
100.1 93.6
81.8
70.1
58.3
92.6
6.0
92.6
93.4
81.6
69.9
58.1
89.6
6.0
74.0
61.6
49.2
111.3
6.3
90.7
78.3
65.9
53.5
101.1
6.2
102.4 99.2
86.8
74.4
62.0
94.0
6.2
94.9
95.2
82.9
70.5
58.1
91.0
6.2
78.4
65.4
52.4
112.9
6.5
96.2
83.2
70.2
57.1
102.6
6.4
104.8 104.8 91.7
78.7
65.7
95.4
6.3
97.1
97.1
84.1
71.0
58.0
92.3
6.3
95°F
34.8
26.6
92.8
7.7
47.7
39.5
31.4
85.2
7.7
60.6
52.4
44.3
36.1
77.7
7.6
76.5
64.6
56.4
48.3
40.1
72.0
7.6
38.8
29.4
95.7
7.7
53.0
43.6
34.3
87.9
7.7
67.2
57.9
48.5
39.2
80.1
7.6
79.4
71.3
62.0
52.6
43.3
74.2
7.6
80.8
72.2
62.9
53.5
44.2
75.6
7.6
42.7
32.2
98.5
7.7
58.3
47.8
37.2
90.5
7.7
73.9
63.3
52.8
42.2
82.5
7.6
82.2
78.0
67.5
57.0
46.4
76.4
7.6
83.7
79.1
68.5
58.0
47.4
77.9
7.6
46.7
35.0
101.4
7.7
63.6
51.9
40.1
93.1
7.7
80.5
68.8
57.1
45.3
84.9
7.7
85.1
84.8
73.0
61.3
49.5
78.6
7.6
86.6
85.9
74.1
62.4
50.6
80.1
7.6
68.1
55.2
42.3
93.6
7.7
86.1
73.2
60.3
47.5
85.3
7.7
85.6
85.4
72.5
59.6
46.7
79.0
7.6
87.1
86.7
73.8
60.9
48.1
80.6
7.6
72.6
58.5
44.5
94.2
7.7
91.7
77.6
63.6
49.6
85.8
7.7
86.0
86.0
72.0
58.0
44.0
79.5
7.6
87.5
87.5
73.5
59.5
45.5
81.0
7.6
90
46.6
59.4
72.3
83.9
51.7
65.7
79.7
86.8
84.0
56.9
72.0
87.2
89.7
86.8
62.0
78.3
94.6
92.6
89.6
83.7
98.6
94.0
91.0
89.0
102.6
95.4
92.3
37.6
52.9
68.1
72.0
45.3
59.4
73.5
74.2
75.6
53.0
65.9
78.8
76.4
77.9
60.7
72.4
84.2
78.6
80.1
77.8
85.0
79.0
80.6
83.1
85.8
79.5
81.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
38.5
30.3
51.3
43.2
35.1
64.1
56.0
47.9
39.8
82.5
70.3
62.1
54.0
42.4
33.1
56.4
47.1
37.7
70.4
61.0
51.7
42.4
85.9
76.6
67.2
57.9
84.0
77.0
67.6
58.3
46.3
35.8
61.5
50.9
40.4
76.6
66.1
55.5
45.0
89.3
82.9
72.3
61.8
86.8
83.3
72.7
62.2
50.3
38.5
66.6
54.8
43.1
82.9
71.1
59.4
47.6
92.6
89.2
77.4
65.7
89.6
89.6
77.9
66.1
71.0
58.4
45.8
88.4
75.8
63.1
50.5
94.0
92.3
79.7
67.0
91.0
91.0
78.3
65.7
75.5
62.0
48.5
93.9
80.4
66.9
53.4
95.4
95.4
81.9
68.3
92.3
92.3
78.8
65.3
105°F
32.1
24.0
44.8
36.7
28.7
57.5
49.5
41.4
33.4
72.0
59.4
51.4
43.3
35.9
26.6
50.0
40.7
31.3
64.1
54.8
45.4
36.0
74.2
65.8
56.4
47.0
75.3
66.3
57.0
47.6
39.8
29.1
55.2
44.6
33.9
70.7
60.0
49.4
38.7
76.4
72.1
61.4
50.8
77.7
72.7
62.0
51.4
43.7
31.7
60.5
48.5
36.5
77.3
65.3
53.3
41.3
78.6
78.4
66.5
54.5
80.1
79.1
67.1
55.1
64.7
51.7
38.6
80.8
69.6
56.5
43.5
79.0
79.0
65.9
52.9
80.6
80.1
67.0
54.0
69.0
54.9
40.7
84.4
73.9
59.8
45.6
79.5
79.5
65.4
51.2
81.0
81.0
66.9
52.8
65
45.9
48.6
49.0
51.2
51.7
53.9
54.4
54.4
53.1
54.8
51.8
35.3
37.7
38.2
40.1
40.7
42.5
43.2
39.8
40.9
37.1
38.6
19
246824-YTG-D-0806
ZH090 (7.5 Ton)(Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
88.0
79.6
71.1
67.4
90.0
81.4
72.8
69.0
70.4
92.1
83.3
74.5
70.5
72.0
94.1
85.1
76.1
72.1
73.6
85.6
76.6
72.5
74.0
86.2
77.1
73.0
74.5
8.6
8.5
8.5
8.5
8.6
8.5
8.5
8.5
8.5
8.6
8.5
8.5
8.5
8.5
8.6
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.6
8.5
8.5
8.5
32.3
49.9
67.5
67.4
42.5
56.4
70.4
69.0
70.4
52.7
63.0
73.3
70.5
72.0
63.0
69.5
76.1
72.1
73.6
74.6
76.6
72.5
74.0
79.6
77.1
73.0
74.5
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
29.4
21.4
83.1
9.4
41.9
34.0
26.0
73.9
9.4
54.5
46.5
38.6
30.6
64.6
9.3
67.4
54.3
46.3
38.3
30.4
62.8
9.3
33.1
23.7
84.4
9.4
47.1
37.7
28.3
75.0
9.4
61.0
51.6
42.2
32.9
65.6
9.3
69.0
60.2
50.8
41.4
32.1
63.8
9.3
69.8
60.4
51.0
41.6
32.3
65.2
9.3
36.9
26.1
85.6
9.4
52.2
41.4
30.6
76.1
9.4
67.5
56.7
45.9
35.1
66.5
9.3
70.5
66.2
55.4
44.6
33.8
64.7
9.3
71.7
66.4
55.6
44.8
34.0
66.1
9.3
40.6
28.4
86.9
9.4
57.3
45.1
32.9
77.1
9.4
74.0
61.8
49.6
37.4
67.4
9.3
72.1
72.1
59.9
47.7
35.5
65.6
9.3
73.6
72.3
60.1
47.9
35.7
67.1
9.3
61.4
48.1
34.9
77.7
9.4
75.5
66.0
52.7
39.5
67.8
9.3
72.5
72.5
59.3
46.1
32.9
66.0
9.4
74.0
73.4
60.2
47.0
33.7
67.5
9.4
65.4
51.2
36.9
78.2
9.4
77.1
70.1
55.9
41.7
68.3
9.4
73.0
73.0
58.8
44.5
30.3
66.5
9.4
74.5
74.5
60.3
46.0
31.8
68.0
9.4
90
29.2
46.9
64.6
62.8
41.4
53.5
65.6
63.8
65.2
53.6
60.1
66.5
64.7
66.1
65.9
66.6
67.4
65.6
67.1
71.4
67.8
66.0
67.5
76.2
68.3
66.5
68.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
25.0
18.8
39.1
31.2
23.3
51.5
43.6
35.7
27.8
62.8
49.1
41.2
33.3
30.3
20.9
44.1
34.7
25.3
57.9
48.5
39.1
29.7
63.8
54.7
45.3
35.9
64.3
54.5
45.1
35.7
35.6
23.0
49.1
38.2
27.3
64.3
53.4
42.5
31.6
64.7
60.2
49.3
38.4
65.7
60.0
49.1
38.2
41.0
25.2
54.2
41.7
29.3
67.4
58.3
45.9
33.4
65.6
65.6
53.3
40.9
67.1
65.6
53.1
40.7
58.0
44.6
31.2
67.8
62.3
48.9
35.6
66.0
66.0
52.7
39.3
67.5
66.8
53.4
40.0
61.8
47.5
33.2
68.3
66.4
52.0
37.7
66.5
66.5
52.1
37.8
68.0
68.0
53.6
39.3
65
25.5
26.5
26.3
27.4
27.3
28.4
28.2
25.9
26.6
23.5
24.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
20
Unitary Products Group
246824-YTG-D-0806
ZH102 (8.5 Ton)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
125.2
116.5
107.7
98.3
130.8
121.6
112.5
102.6
100.7
136.3
126.8
117.2
106.9
105.0
141.9
131.9
121.9
111.2
109.3
135.0
124.8
113.8
111.8
138.1
127.6
116.4
114.4
6.6
6.6
6.6
6.6
6.5
6.5
6.5
6.5
6.5
6.3
6.3
6.3
6.3
6.3
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.3
6.2
57.1
70.4
83.6
98.3
62.2
79.3
96.4
102.6
100.7
67.3
88.2
109.2
106.9
105.0
72.4
97.1
121.9
111.2
109.3
123.1
124.8
113.8
111.8
149.0
127.6
116.4
114.4
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
119.8
108.7
97.7
89.1
123.2
111.8
100.4
91.6
93.5
126.5
114.9
103.2
94.1
96.0
129.9
117.9
105.9
96.6
98.6
120.3
108.0
98.6
100.6
122.6
110.1
100.5
102.5
7.3
7.3
7.3
7.2
7.5
7.5
7.5
7.4
7.4
7.6
7.6
7.6
7.5
7.6
7.8
7.8
7.8
7.7
7.7
7.8
7.8
7.7
7.7
7.8
7.8
7.7
7.7
51.2
67.9
84.6
89.1
60.0
75.8
91.7
91.6
93.5
68.7
83.8
98.8
94.1
96.0
77.5
91.7
105.9
96.6
98.6
99.5
108.0
98.6
100.6
107.2
110.1
100.5
102.5
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
45.0
35.0
122.5
7.0
60.4
50.3
40.3
112.6
7.0
75.7
65.6
55.6
45.6
102.7
7.0
97.6
78.5
68.4
58.4
48.4
93.7
6.9
50.6
39.0
127.0
7.0
67.7
56.1
44.5
116.7
7.0
84.8
73.2
61.6
50.0
106.4
7.0
102.2 87.5
75.9
64.3
52.7
97.1
6.9
100.7 89.3
77.7
66.1
54.5
97.1
6.9
56.2
43.0
131.4
7.0
75.0
61.9
48.7
120.8
7.0
93.9
80.7
67.5
54.4
110.2
7.0
106.7 96.5
83.3
70.2
57.0
100.5
6.9
105.0 98.5
85.4
72.2
59.0
100.5
7.0
61.8
47.0
135.9
7.0
82.4
67.6
52.9
124.9
7.0
103.0 88.3
73.5
58.8
113.9
7.0
111.2 105.5 90.8
76.0
61.3
103.9
6.9
109.3 107.7 93.0
78.2
63.5
103.9
7.0
97.7
72.3
46.9
127.6
7.0
115.3 94.3
68.9
43.5
116.4
7.0
113.8 111.0 85.6
60.2
34.8
106.2
7.0
111.8 111.0 85.6
60.3
34.9
106.2
7.0
113.0 76.9
40.9
130.3
7.0
127.6 100.4 64.3
28.3
118.9
7.0
116.4 116.4 80.4
44.3
8.3
108.5
7.0
114.4 114.4 78.3
42.3
6.2
108.5
7.0
95°F
43.5
33.5
112.1
8.4
57.9
47.9
37.9
101.7
8.4
72.4
62.4
52.4
42.4
91.2
8.4
89.1
75.6
65.6
55.6
45.6
83.4
8.3
48.4
36.8
114.7
8.5
64.3
52.7
41.1
104.0
8.5
80.2
68.6
57.0
45.5
93.3
8.5
91.6
83.1
71.6
60.0
48.4
85.3
8.4
93.5
82.0
70.4
58.8
47.3
87.0
8.5
53.3
40.2
117.3
8.6
70.6
57.5
44.3
106.4
8.6
88.0
74.8
61.7
48.5
95.4
8.6
94.1
90.7
77.5
64.4
51.2
87.2
8.6
96.0
89.4
76.3
63.1
50.0
89.0
8.6
58.2
43.5
119.9
8.7
77.0
62.3
47.5
108.8
8.7
95.7
81.0
66.3
51.6
97.6
8.7
96.6
98.2
83.5
68.7
54.0
89.2
8.7
98.6
96.8
82.1
67.4
52.7
91.0
8.7
83.3
67.1
50.9
110.9
8.7
102.9 87.3
71.1
55.0
99.5
8.7
98.6
99.3
83.2
67.0
50.8
91.0
8.6
100.6 99.7
83.5
67.3
51.1
92.8
8.7
89.6
71.9
54.3
113.1
8.7
110.1 93.6
76.0
58.3
101.5
8.7
100.5 100.5 82.9
65.2
47.6
92.8
8.6
102.5 102.5 84.9
67.3
49.6
94.6
8.7
90
54.2
69.1
84.1
93.7
61.1
77.6
94.1
97.1
97.1
68.0
86.0
104.0
100.5
100.5
74.9
94.4
113.9
103.9
103.9
111.3
116.4
106.2
106.2
128.1
118.9
108.5
108.5
45.1
64.7
84.3
83.4
55.9
72.3
88.7
85.3
87.0
66.7
79.9
93.1
87.2
89.0
77.6
87.6
97.6
89.2
91.0
95.1
99.5
91.0
92.8
102.6
101.5
92.8
94.6
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
44.2
34.2
59.1
49.1
39.1
74.0
64.0
54.0
44.0
93.4
77.0
67.0
57.0
49.5
37.9
66.0
54.4
42.8
82.5
70.9
59.3
47.7
96.9
85.3
73.7
62.1
97.1
85.7
74.1
62.5
54.7
41.6
72.8
59.7
46.5
90.9
77.8
64.6
51.4
100.4 93.6
80.4
67.3
100.5 94.0
80.8
67.6
60.0
45.3
79.7
65.0
50.2
99.4
84.6
69.9
55.2
103.9 101.9 87.1
72.4
103.9 102.3 87.5
72.8
90.5
69.7
48.9
109.1 90.8
70.0
49.2
106.2 105.2 84.4
63.6
106.2 105.4 84.6
63.8
101.3 74.4
47.6
118.9 97.0
70.2
43.3
108.5 108.5 81.6
54.8
108.5 108.5 81.6
54.8
105°F
39.9
29.9
54.8
44.8
34.9
69.6
59.7
49.8
39.8
83.4
72.8
62.9
53.0
44.4
33.0
60.8
49.3
37.9
77.2
65.7
54.2
42.8
85.3
80.2
68.7
57.2
87.0
76.8
65.3
53.8
49.0
36.0
66.9
53.9
40.8
84.8
71.7
58.7
45.7
87.2
87.5
74.5
61.4
89.0
83.8
70.8
57.7
53.6
39.0
73.0
58.4
43.8
92.3
77.8
63.2
48.6
89.2
94.8
80.2
65.6
91.0
90.8
76.2
61.6
79.0
63.0
46.9
96.9
83.9
67.8
51.8
91.0
93.8
77.8
61.7
92.8
92.7
76.7
60.6
85.1
67.6
50.1
101.5 90.0
72.5
55.0
92.8
92.8
75.3
57.8
94.6
94.6
77.1
59.6
65
47.0
50.5
50.9
54.1
54.5
57.7
58.1
42.8
43.0
27.9
27.9
43.0
45.7
42.3
48.4
44.7
51.0
47.0
45.7
44.6
40.3
42.2
21
246824-YTG-D-0806
ZH102 (8.5 Ton)(Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
104.5
94.6
84.7
77.6
106.3
96.3
86.2
78.9
80.5
108.2
97.9
87.7
80.3
81.9
110.0
99.6
89.2
81.7
83.3
101.6
91.0
83.3
85.0
103.7
92.9
85.0
86.7
9.5
9.5
9.5
9.5
9.5
9.5
9.6
9.5
9.5
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.7
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
39.0
61.5
83.9
77.6
51.9
68.8
85.7
78.9
80.5
64.8
76.1
87.4
80.3
81.9
77.6
83.4
89.2
81.7
83.3
90.7
91.0
83.3
85.0
97.9
92.9
85.0
86.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
36.3
26.4
96.8
10.6
51.6
41.7
31.8
87.5
10.6
66.9
57.0
47.2
37.3
78.2
10.6
77.6
70.0
60.2
50.3
40.4
71.8
10.6
40.5
29.1
97.9
10.5
57.4
46.0
34.6
88.5
10.6
74.3
62.9
51.4
40.0
79.1
10.6
78.9
77.2
65.8
54.4
43.0
72.6
10.6
80.5
71.6
60.2
48.8
37.4
74.0
10.6
44.7
31.8
99.0
10.5
63.2
50.2
37.3
89.5
10.6
81.6
68.7
55.7
42.8
80.0
10.6
80.3
84.3
71.4
58.5
45.5
73.4
10.6
81.9
78.2
65.3
52.3
39.4
74.9
10.6
48.9
34.5
100.0
10.5
68.9
54.5
40.0
90.4
10.5
89.0
74.5
60.0
45.5
80.8
10.6
81.7
91.5
77.0
62.5
48.1
74.2
10.6
83.3
84.8
70.3
55.9
41.4
75.7
10.5
74.8
58.9
43.0
92.3
10.5
90.9
80.5
64.6
48.7
82.5
10.6
83.3
88.2
72.3
56.4
40.5
75.7
10.5
85.0
85.8
69.9
54.0
38.1
77.2
10.5
80.6
63.2
45.9
94.2
10.5
92.9
86.4
69.1
51.8
84.2
10.6
85.0
85.0
67.7
50.3
33.0
77.3
10.5
86.7
86.7
69.4
52.0
34.7
78.8
10.5
90
38.2
58.2
78.2
71.8
51.4
65.2
79.1
72.6
74.0
64.5
72.3
80.0
73.4
74.9
77.7
79.3
80.8
74.2
75.7
86.3
82.5
75.7
77.2
93.3
84.2
77.3
78.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
30.3
22.9
48.4
38.6
28.8
64.2
54.4
44.6
34.8
71.8
71.8
57.5
47.7
36.5
25.2
53.9
42.6
31.3
71.3
60.0
48.7
37.3
72.6
72.6
62.9
51.6
74.0
66.4
55.0
43.7
42.8
27.6
59.4
46.6
33.8
78.4
65.6
52.8
39.9
73.4
73.4
68.3
55.5
74.9
72.6
59.8
46.9
49.0
30.0
64.9
50.6
36.3
80.8
71.2
56.9
42.5
74.2
74.2
73.8
59.4
75.7
75.7
64.5
50.1
70.5
54.7
39.0
82.5
77.0
61.3
45.5
75.7
75.7
66.9
51.2
77.2
77.2
63.0
47.3
76.1
58.9
41.7
84.2
82.9
65.7
48.5
77.3
77.3
60.1
42.9
78.8
78.8
61.6
44.4
65
37.9
40.3
32.4
42.7
34.1
45.1
35.8
35.4
31.5
25.7
27.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
22
Unitary Products Group
246824-YTG-D-0806
ZH120 (10 Ton)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
156.1
144.0
131.9
117.8
160.9
148.4
136.0
121.5
117.2
165.7
152.9
140.0
125.1
120.7
170.5
157.3
144.1
128.7
124.3
161.7
148.1
132.3
127.8
166.1
152.2
136.0
131.3
7.6
7.5
7.4
7.4
7.6
7.5
7.4
7.4
7.3
7.6
7.5
7.4
7.5
7.3
7.6
7.5
7.4
7.5
7.3
7.5
7.4
7.5
7.3
7.5
7.4
7.5
7.3
68.9
85.7
102.5
117.8
75.6
94.6
113.6
121.5
117.2
82.3
103.4
124.6
125.1
120.7
88.9
112.3
135.7
128.7
124.3
120.9
143.9
132.3
127.8
129.6
152.2
136.0
131.3
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
138.8
128.2
117.6
108.7
142.8
131.9
121.0
111.9
109.1
146.8
135.6
124.4
115.0
112.2
150.8
139.3
127.8
118.2
115.3
142.5
130.7
120.8
117.9
145.6
133.6
123.5
120.5
9.4
9.2
9.1
9.0
9.4
9.3
9.1
9.1
9.2
9.5
9.3
9.2
9.1
9.3
9.6
9.4
9.2
9.2
9.3
9.4
9.3
9.2
9.4
9.5
9.3
9.3
9.4
59.1
78.3
97.5
108.7
66.9
87.2
107.6
111.9
109.1
74.6
96.2
117.7
115.0
112.2
82.4
105.1
127.8
118.2
115.3
113.2
130.7
120.8
117.9
121.3
133.6
123.5
120.5
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
57.2
46.2
147.4
8.5
74.7
63.7
52.6
136.1
8.3
92.2
81.1
70.1
59.1
124.7
8.2
118.1 100.3 89.2
78.2
67.2
113.3
8.2
62.9
50.2
151.8
8.5
81.9
69.2
56.5
140.1
8.4
100.9 88.2
75.5
62.8
128.5
8.3
121.7 109.0 96.3
83.6
70.9
116.7
8.3
117.2 114.2 101.5 88.8
76.1
113.2
8.3
68.6
54.3
156.2
8.6
89.1
74.7
60.4
144.2
8.4
109.6 95.2
80.9
66.5
132.2
8.3
125.2 117.7 103.3 89.0
74.6
120.1
8.3
120.7 123.4 109.0 94.7
80.3
116.5
8.3
74.3
58.3
160.6
8.6
96.3
80.3
64.3
148.3
8.5
118.3 102.3 86.2
70.2
135.9
8.3
128.7 126.4 110.4 94.4
78.4
123.4
8.3
124.3 132.5 116.5 100.5 84.5
119.8
8.3
103.3 85.7
68.1
152.1
8.5
126.8 109.2 91.6
74.0
139.4
8.3
132.3 131.2 113.6 96.0
78.4
126.6
8.4
127.8 131.9 114.3 96.7
79.1
122.8
8.4
110.4 91.2
72.0
155.9
8.5
135.3 116.1 96.9
77.7
142.9
8.4
136.0 136.0 116.8 97.6
78.4
129.8
8.4
131.3 131.3 112.1 92.9
73.7
125.9
8.4
95°F
48.4
37.0
133.4
10.5
66.9
55.5
44.1
122.8
10.4
85.4
74.0
62.6
51.2
112.2
10.3
107.5 89.1
77.7
66.3
54.9
104.1
10.3
53.8
40.7
135.8
10.6
74.1
61.1
48.0
125.0
10.5
94.5
81.4
68.3
55.3
114.1
10.3
111.1 98.0
84.9
71.8
58.7
106.0
10.3
109.1 100.1 87.0
73.9
60.8
103.9
10.4
59.2
44.4
138.1
10.6
81.4
66.6
51.8
127.1
10.5
103.6 88.8
74.0
59.3
116.1
10.4
114.6 106.9 92.1
77.3
62.5
107.8
10.4
112.2 109.2 94.4
79.6
64.8
105.7
10.4
64.6
48.1
140.4
10.7
88.6
72.1
55.7
129.3
10.5
112.7 96.2
79.7
63.3
118.1
10.4
118.2 115.8 99.3
82.8
66.4
109.6
10.4
115.3 118.3 101.8 85.3
68.8
107.5
10.5
95.2
77.3
59.3
132.1
10.6
121.0 103.1 85.1
67.2
120.7
10.4
120.8 119.7 101.7 83.8
65.8
112.1
10.4
117.9 119.4 101.4 83.5
65.5
109.9
10.5
101.9 82.4
63.0
135.0
10.6
129.4 109.9 90.5
71.1
123.4
10.4
123.5 123.5 104.1 84.7
65.3
114.5
10.4
120.5 120.5 101.1 81.7
62.3
112.3
10.5
90
64.0
82.0
100.0
113.3
71.2
90.9
110.6
116.7
113.2
78.5
99.8
121.1
120.1
116.5
85.7
108.7
131.7
123.4
119.8
117.1
137.3
126.6
122.8
125.4
142.9
129.8
125.9
53.7
76.1
98.5
104.1
64.1
84.6
105.0
106.0
103.9
74.5
93.0
111.6
107.8
105.7
84.9
101.5
118.1
109.6
107.5
109.5
120.7
112.1
109.9
117.5
123.4
114.5
112.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
52.8
41.6
70.8
59.6
48.4
88.8
77.6
66.4
55.2
112.8 94.7
83.5
72.2
58.3
45.5
78.0
65.1
52.2
97.7
84.8
71.9
59.0
116.4 103.5 90.6
77.7
113.2 107.1 94.3
81.4
63.9
49.3
85.2
70.7
56.1
106.6 92.0
77.5
62.9
119.9 112.3 97.7
83.2
116.5 116.3 101.7 87.1
69.4
53.2
92.5
76.2
60.0
115.5 99.2
83.0
66.8
123.4 121.1 104.9 88.6
119.8 125.4 109.1 92.9
99.3
81.5
63.7
123.9 106.1 88.4
70.6
126.6 125.4 107.6 89.9
122.8 125.6 107.9 90.1
106.1 86.8
67.5
132.3 113.0 93.7
74.4
129.8 129.8 110.4 91.1
125.9 125.9 106.6 87.3
105°F
46.1
34.9
64.9
53.6
42.4
83.6
72.4
61.1
49.9
103.5 86.7
75.4
64.2
51.1
38.1
71.6
58.6
45.6
92.0
79.0
66.0
53.0
105.6 94.6
81.7
68.7
103.9 94.2
81.2
68.2
56.1
41.3
78.3
63.5
48.7
100.4 85.7
70.9
56.2
107.6 102.6 87.9
73.1
105.7 102.1 87.4
72.6
61.1
44.6
85.0
68.5
51.9
108.9 92.3
75.8
59.3
109.6 110.6 94.1
77.6
107.5 110.1 93.5
77.0
91.5
73.5
55.5
115.1 99.1
81.1
63.1
112.1 112.6 94.6
76.5
109.9 111.2 93.2
75.2
98.0
78.5
59.0
121.3 105.9 86.4
66.9
114.5 114.5 95.0
75.5
112.3 112.3 92.8
73.3
65
61.0
64.8
68.5
68.6
72.6
72.4
76.7
72.1
72.3
71.8
68.0
53.0
55.7
55.2
58.4
57.8
61.0
60.5
58.5
57.2
56.0
53.8
23
246824-YTG-D-0806
ZH120 (10 Ton)(Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
128.1
117.4
106.8
99.5
128.7
118.0
107.3
100.1
98.8
129.4
118.6
107.9
100.6
99.3
130.1
119.3
108.4
101.1
99.8
121.8
110.8
103.3
101.9
124.4
113.1
105.5
104.1
11.7
11.6
11.5
11.6
11.7
11.6
11.5
11.6
11.6
11.7
11.6
11.5
11.6
11.6
11.8
11.7
11.6
11.6
11.6
11.7
11.6
11.6
11.6
11.7
11.6
11.6
11.6
48.4
73.9
99.5
99.5
61.4
81.9
102.5
100.1
98.8
74.3
89.9
105.4
100.6
99.3
87.3
97.9
108.4
101.1
99.8
105.8
110.8
103.3
101.9
113.6
113.1
105.5
104.1
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
43.9
32.8
122.7
12.9
62.8
51.7
40.7
112.1
12.8
81.8
70.7
59.6
48.5
101.4
12.7
99.5
84.3
73.2
62.1
51.0
94.9
12.8
48.4
35.5
121.7
12.9
69.0
56.1
43.2
111.1
12.8
89.5
76.6
63.7
50.8
100.5
12.7
100.1 91.3
78.4
65.5
52.6
94.1
12.8
98.8
88.2
75.3
62.4
49.5
93.6
12.8
53.0
38.3
120.7
12.9
75.2
60.4
45.7
110.2
12.8
97.3
82.6
67.8
53.1
99.6
12.7
100.6 98.4
83.6
68.9
54.2
93.3
12.8
99.3
95.0
80.3
65.6
50.8
92.8
12.8
57.6
41.0
119.7
12.9
81.3
64.8
48.2
109.2
12.8
105.0 88.5
71.9
55.3
98.8
12.7
101.1 105.4 88.9
72.3
55.7
92.6
12.8
99.8 101.9 85.3
68.7
52.2
92.0
12.8
87.7
69.6
51.6
111.5
12.8
109.1 95.2
77.1
59.0
100.8
12.7
103.3 105.5 87.4
69.3
51.3
94.5
12.8
101.9 103.0 84.9
66.9
48.8
94.0
12.8
94.1
74.5
55.0
113.8
12.8
113.1 101.8 82.3
62.7
102.9
12.7
105.5 105.5 85.9
66.4
46.8
96.4
12.8
104.1 104.1 84.6
65.0
45.4
95.9
12.8
90
43.0
71.7
100.5
94.9
58.6
79.2
99.9
94.1
93.6
74.2
86.8
99.3
93.3
92.8
89.8
94.3
98.8
92.6
92.0
102.0
100.8
94.5
94.0
109.8
102.9
96.4
95.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
40.4
30.7
60.8
49.9
38.9
80.0
69.1
58.1
47.2
94.9
82.6
70.9
60.0
45.8
33.0
66.4
53.6
40.8
87.1
74.2
61.4
48.6
94.1
88.0
75.2
62.3
93.6
82.3
69.5
56.7
51.2
35.2
72.0
57.3
42.6
94.1
79.4
64.7
50.0
93.3
93.3
79.4
64.7
92.8
88.0
73.3
58.5
56.6
37.5
77.7
61.1
44.4
98.8
84.6
68.0
51.4
92.6
92.6
83.6
67.0
92.0
92.0
77.1
60.4
83.9
65.8
47.7
100.8 91.2
73.1
55.0
94.5
94.5
80.2
62.1
94.0
94.0
76.7
58.6
90.2
70.6
50.9
102.9 97.8
78.1
58.5
96.4
96.4
76.8
57.2
95.9
95.9
76.3
56.7
65
49.0
49.5
43.8
50.0
43.8
50.4
43.8
44.0
40.4
37.6
37.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
24
Unitary Products Group
246824-YTG-D-0806
ZH150 (12.5 Ton)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
187.0
176.3
165.5
149.3
193.7
182.5
171.4
154.5
155.4
200.3
188.8
177.2
159.8
160.7
207.0
195.1
183.1
165.1
166.0
203.6
191.1
172.4
173.3
212.2
199.1
179.6
180.6
9.5
9.5
9.4
9.2
9.6
9.6
9.5
9.3
9.2
9.7
9.7
9.6
9.3
9.3
9.8
9.8
9.7
9.4
9.4
9.7
9.6
9.4
9.3
9.7
9.6
9.4
9.3
73.2
98.5
123.7
149.3
82.5
110.4
138.3
154.5
155.4
91.7
122.3
152.8
159.8
160.7
101.0
134.2
167.3
165.1
166.0
143.3
183.2
172.4
173.3
152.4
199.1
179.6
180.6
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
178.3
163.6
148.9
136.0
183.6
168.4
153.3
140.1
141.1
188.9
173.3
157.7
144.1
145.2
194.1
178.1
162.1
148.1
149.2
183.1
166.6
152.2
153.4
188.0
171.1
156.3
157.5
11.7
11.6
11.5
11.2
11.8
11.7
11.6
11.3
11.3
12.0
11.8
11.7
11.4
11.4
12.1
11.9
11.8
11.5
11.5
11.9
11.8
11.5
11.5
11.9
11.8
11.5
11.5
76.0
98.8
121.6
136.0
83.7
108.6
133.4
140.1
141.1
91.5
118.3
145.2
144.1
145.2
99.2
128.1
157.0
148.1
149.2
138.0
164.0
152.2
153.4
147.8
171.1
156.3
157.5
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
60.2
47.2
182.7
10.6
85.5
72.4
59.4
169.9
10.5
110.7 97.7
84.7
71.7
157.2
10.4
143.1 119.8 106.8 93.8
80.8
142.6
10.2
67.3
52.2
188.6
10.7
95.2
80.1
64.9
175.5
10.6
123.1 108.0 92.8
77.7
162.3
10.5
150.5 132.4 117.3 102.1 87.0
147.3
10.3
155.4 138.2 123.1 107.9 92.8
148.3
10.3
74.4
57.2
194.6
10.8
105.0 87.7
70.4
181.0
10.7
135.5 118.2 101.0 83.7
167.5
10.6
157.8 145.0 127.7 110.5 93.2
152.0
10.4
160.7 151.3 134.0 116.8 99.5
152.9
10.4
81.6
62.2
200.6
10.9
114.7 95.3
75.9
186.6
10.8
147.9 128.5 109.1 89.7
172.6
10.7
165.1 157.6 138.2 118.8 99.4
156.6
10.5
166.0 164.4 145.0 125.6 106.2
157.6
10.5
122.5 101.8 81.1
193.3
10.8
158.0 137.2 116.5 95.8
178.9
10.7
172.4 168.6 147.9 127.1 106.4
162.3
10.5
173.3 172.5 151.8 131.0 110.3
163.3
10.4
130.3 108.2 86.2
200.1
10.8
168.0 145.9 123.9 101.8
185.1
10.7
179.6 179.6 157.5 135.5 113.4
168.0
10.4
180.6 180.6 158.5 136.5 114.4
169.0
10.4
95°F
62.2
48.4
167.8
13.1
85.0
71.3
57.5
153.7
13.0
107.9 94.1
80.3
66.6
139.7
12.8
136.0 117.1 103.4 89.6
75.8
128.6
12.6
68.2
52.7
172.5
13.2
93.1
77.6
62.1
158.0
13.0
117.9 102.4 86.9
71.4
143.6
12.9
140.1 127.5 112.0 96.5
81.0
132.2
12.7
141.1 128.2 112.7 97.2
81.6
132.5
12.7
74.2
57.0
177.2
13.3
101.1 83.9
66.6
162.3
13.1
128.0 110.7 93.5
76.2
147.5
13.0
144.1 137.8 120.6 103.3 86.1
135.8
12.8
145.2 138.6 121.3 104.1 86.8
136.1
12.8
80.3
61.3
181.9
13.3
109.1 90.1
71.2
166.6
13.2
138.0 119.0 100.0 81.0
151.4
13.1
148.1 148.1 129.2 110.2 91.2
139.4
12.9
149.2 148.9 130.0 111.0 92.0
139.7
12.9
117.4 96.9
76.4
170.9
13.2
148.5 128.0 107.4 86.9
155.3
13.1
152.2 152.2 131.7 111.2 90.7
143.0
12.9
153.4 153.2 132.7 112.2 91.6
143.3
12.9
125.7 103.7 81.6
175.1
13.2
159.0 136.9 114.8 92.8
159.1
13.1
156.3 156.3 134.3 112.2 90.1
146.5
12.9
157.5 157.5 135.4 113.4 91.3
146.8
12.9
90
74.6
98.6
122.7
142.6
83.1
109.5
135.8
147.3
148.3
91.6
120.3
149.0
152.0
152.9
100.1
131.1
162.2
156.6
157.6
140.6
173.6
162.3
163.3
150.1
185.1
168.0
169.0
69.9
94.5
119.1
128.6
79.8
104.4
129.0
132.2
132.5
89.7
114.3
138.9
135.8
136.1
99.7
124.2
148.8
139.4
139.7
133.8
154.0
143.0
143.3
143.4
159.1
146.5
146.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
61.2
47.8
85.2
71.9
58.5
109.3 95.9
82.5
69.1
139.6 118.5 105.1 91.7
67.8
52.4
94.1
78.8
63.5
120.5 105.2 89.9
74.5
145.3 129.9 114.6 99.3
148.3 133.2 117.9 102.5
74.3
57.1
103.0 85.8
68.5
131.7 114.5 97.2
80.0
151.0 141.4 124.2 106.9
152.9 144.9 127.7 110.4
80.9
61.7
111.9 92.7
73.5
143.0 123.8 104.6 85.4
156.6 152.9 133.7 114.5
157.6 156.7 137.5 118.3
120.0 99.4
78.7
153.2 132.6 112.0 91.3
162.3 160.4 139.8 119.2
163.3 162.9 142.2 121.6
128.0 106.0 83.9
163.5 141.4 119.3 97.3
168.0 168.0 145.9 123.8
169.0 169.0 147.0 124.9
105°F
58.4
44.7
80.9
67.2
53.6
103.4 89.7
76.1
62.4
128.6 108.9 95.2
81.5
64.4
48.9
89.0
73.5
58.1
113.6 98.1
82.7
67.2
132.2 119.0 103.6 88.1
132.5 119.2 103.7 88.3
70.4
53.1
97.1
79.8
62.5
123.8 106.5 89.3
72.0
135.8 129.2 112.0 94.7
136.1 129.4 112.1 94.8
76.3
57.3
105.2 86.1
67.0
134.0 114.9 95.9
76.8
139.4 139.4 120.3 101.3
139.7 139.6 120.5 101.4
113.2 92.7
72.1
143.5 123.7 103.1 82.5
143.0 143.0 122.4 101.8
143.3 143.2 122.6 102.0
121.3 99.2
77.1
153.1 132.5 110.4 88.3
146.5 146.5 124.4 102.3
146.8 146.8 124.7 102.7
65
78.3
84.0
87.2
89.6
93.2
95.3
99.1
98.5
101.0
101.8
102.8
67.9
72.7
72.8
77.4
77.6
82.2
82.4
81.2
81.5
80.3
80.6
25
246824-YTG-D-0806
ZH150 (12.5 Ton)(Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
157.3
143.8
130.4
121.2
161.4
147.6
133.8
124.3
123.8
165.5
151.4
137.2
127.5
127.0
169.6
155.1
140.7
130.7
130.2
158.7
143.9
133.7
133.2
162.3
147.2
136.7
136.2
14.5
14.3
14.1
14.0
14.5
14.4
14.2
14.1
14.1
14.6
14.4
14.3
14.1
14.2
14.6
14.5
14.3
14.2
14.2
14.5
14.3
14.2
14.3
14.5
14.4
14.2
14.3
63.8
90.2
116.6
121.2
75.9
100.3
124.6
124.3
123.8
88.0
110.3
132.6
127.5
127.0
100.1
120.4
140.7
130.7
130.2
129.7
143.9
133.7
133.2
139.0
147.2
136.7
136.2
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
54.6
41.0
146.7
15.8
76.7
63.2
49.6
134.0
15.7
98.8
85.3
71.8
58.2
121.2
15.5
121.2 100.6 87.0
73.5
60.0
113.7
15.4
60.5
45.1
150.3
15.9
84.9
69.5
54.1
137.2
15.7
109.2 93.8
78.4
63.0
124.1
15.5
124.3 110.6 95.2
79.8
64.4
116.5
15.4
123.8 110.2 94.8
79.4
63.9
115.2
15.5
66.5
49.2
153.8
15.9
93.0
75.8
58.5
140.4
15.7
119.6 102.3 85.0
67.8
127.0
15.5
127.5 120.6 103.4 86.1
68.8
119.2
15.5
127.0 120.2 102.9 85.6
68.3
117.9
15.5
72.4
53.3
157.3
15.9
101.2 82.1
62.9
143.6
15.7
130.0 110.8 91.7
72.5
129.9
15.6
130.7 130.7 111.5 92.4
73.2
121.9
15.5
130.2 130.2 111.0 91.9
72.7
120.6
15.6
109.1 88.4
67.8
146.5
15.8
138.6 119.4 98.8
78.2
132.5
15.6
133.7 133.7 113.1 92.4
71.8
124.4
15.6
133.2 133.2 112.5 91.9
71.3
123.1
15.6
116.9 94.8
72.7
149.4
15.8
147.2 128.0 105.9 83.8
135.2
15.7
136.7 136.7 114.6 92.5
70.4
126.9
15.6
136.2 136.2 114.1 92.0
69.8
125.5
15.7
90
56.5
85.9
114.1
113.7
72.0
96.1
120.2
116.5
115.2
87.5
106.3
126.4
119.2
117.9
103.1
116.5
129.9
121.9
120.6
125.5
132.5
124.4
123.1
134.6
135.2
126.9
125.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
50.7
37.3
72.5
59.1
45.7
94.3
80.9
67.5
54.1
113.7 92.3
78.9
65.4
56.7
41.3
80.8
65.4
50.0
104.9 89.5
74.2
58.8
116.5 102.2 86.8
71.4
115.2 101.2 85.8
70.5
62.6
45.3
89.0
71.7
54.4
115.4 98.1
80.8
63.5
119.2 112.1 94.8
77.5
117.9 111.0 93.7
76.4
68.5
49.3
97.3
78.0
58.8
126.0 106.7 87.5
68.3
121.9 121.9 102.7 83.5
120.6 120.6 101.5 82.3
104.9 84.2
63.5
132.5 115.2 94.5
73.8
124.4 124.4 103.7 83.1
123.1 123.1 102.5 81.8
112.5 90.3
68.2
135.2 123.6 101.5 79.3
126.9 126.9 104.8 82.6
125.5 125.5 103.4 81.2
65
52.0
56.1
55.1
60.2
59.1
64.2
63.1
62.4
61.1
60.5
59.1
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
26
Unitary Products Group
246824-YTG-D-0806
XP078-150 Cooling Capacities
XP078 (6.5 Ton)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
101.5
92.3
83.1
76.7
105.5
95.9
86.3
79.8
78.2
109.5
99.6
89.6
82.8
81.2
113.6
103.2
92.9
85.8
84.2
105.5
95.0
87.7
86.1
107.8
97.0
89.7
87.9
4.7
4.8
4.9
4.8
4.8
4.8
4.9
4.8
4.8
4.8
4.9
4.9
4.8
4.9
4.8
4.9
5.0
4.9
4.9
4.9
4.9
4.8
4.9
4.8
4.9
4.8
4.8
41.0
52.5
64.0
76.7
45.8
58.9
72.0
79.8
78.2
50.6
65.3
79.9
82.8
81.2
55.4
71.7
87.9
85.8
84.2
76.3
92.5
87.7
86.1
80.9
97.0
89.7
87.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
84.3
77.8
71.3
65.2
88.0
81.2
74.4
68.0
68.8
91.7
84.6
77.5
70.8
71.7
95.3
88.0
80.6
73.7
74.6
90.2
82.6
75.5
76.5
92.4
84.7
77.4
78.3
6.6
6.5
6.4
6.4
6.6
6.4
6.3
6.4
6.4
6.5
6.4
6.3
6.3
6.3
6.5
6.3
6.2
6.3
6.3
6.4
6.3
6.3
6.3
6.4
6.3
6.3
6.3
37.4
48.6
59.9
65.2
42.5
54.7
66.8
68.0
68.8
47.7
60.7
73.7
70.8
71.7
52.9
66.7
80.6
73.7
74.6
71.4
82.6
75.5
76.5
76.1
84.7
77.4
78.3
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
33.6
26.4
92.9
5.7
45.3
38.2
31.1
85.1
5.6
57.1
50.0
42.9
35.8
77.2
5.6
74.1
60.8
53.6
46.5
39.4
71.0
5.6
37.6
29.4
96.8
5.7
50.7
42.5
34.3
88.6
5.6
63.8
55.6
47.4
39.2
80.4
5.6
78.0
67.5
59.3
51.1
42.9
73.9
5.6
78.2
70.1
61.9
53.7
45.5
73.5
5.6
41.6
32.3
100.6
5.7
56.0
46.7
37.4
92.1
5.6
70.4
61.1
51.8
42.6
83.6
5.6
81.9
74.3
65.0
55.7
46.5
76.8
5.6
81.2
77.2
67.9
58.6
49.3
76.5
5.6
45.6
35.3
104.4
5.6
61.3
51.0
40.6
95.6
5.6
77.0
66.7
56.3
46.0
86.8
5.6
85.8
81.1
70.7
60.3
50.0
79.8
5.6
84.2
84.2
73.8
63.5
53.1
79.4
5.6
65.0
53.7
42.5
97.9
5.6
81.6
70.3
59.0
47.8
88.8
5.6
87.7
85.4
74.1
62.8
51.6
81.6
5.6
86.1
86.1
74.8
63.5
52.3
81.3
5.6
68.7
56.5
44.3
100.1
5.6
86.1
73.9
61.7
49.6
90.9
5.6
89.7
89.7
77.5
65.3
53.1
83.5
5.6
87.9
87.9
75.7
63.6
51.4
83.1
5.6
95°F
30.6
23.6
78.5
7.4
41.7
34.7
27.7
72.1
7.3
52.7
45.7
38.7
31.7
65.7
7.2
65.2
56.2
49.2
42.3
35.3
59.9
7.2
34.3
26.1
81.4
7.3
46.5
38.2
30.0
74.8
7.2
58.6
50.4
42.2
33.9
68.2
7.2
68.0
62.1
53.8
45.6
37.4
62.1
7.2
68.8
62.8
54.6
46.4
38.2
64.4
7.2
38.0
28.5
84.3
7.3
51.3
41.8
32.4
77.4
7.2
64.5
55.1
45.6
36.2
70.6
7.1
70.8
67.9
58.4
49.0
39.5
64.3
7.1
71.7
68.7
59.3
49.8
40.4
66.7
7.2
41.6
31.0
87.2
7.2
56.1
45.4
34.7
80.1
7.2
70.5
59.8
49.1
38.5
73.1
7.1
73.7
73.7
63.0
52.3
41.7
66.6
7.1
74.6
74.6
63.9
53.2
42.6
69.0
7.1
59.9
48.4
36.9
81.8
7.2
75.3
63.8
52.3
40.8
74.6
7.1
75.5
75.5
64.0
52.6
41.1
68.0
7.1
76.5
76.5
65.0
53.5
42.0
70.5
7.2
63.8
51.5
39.2
83.5
7.2
80.1
67.8
55.5
43.2
76.2
7.2
77.4
77.4
65.1
52.8
40.5
69.4
7.2
78.3
78.3
66.0
53.7
41.5
72.0
7.2
90
39.2
50.6
62.0
71.0
44.2
56.8
69.4
73.9
73.5
49.2
63.0
76.8
76.8
76.5
54.1
69.2
84.3
79.8
79.4
73.8
87.6
81.6
81.3
78.5
90.9
83.5
83.1
33.1
46.3
59.6
59.9
40.2
52.2
64.1
62.1
64.4
47.4
58.0
68.6
64.3
66.7
54.5
63.8
73.1
66.6
69.0
68.3
74.6
68.0
70.5
72.7
76.2
69.4
72.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
32.1
25.0
43.5
36.4
29.4
54.9
47.8
40.8
33.7
69.6
58.5
51.4
44.4
36.0
27.7
48.6
40.4
32.1
61.2
53.0
44.8
36.5
73.0
64.8
56.6
48.4
73.5
66.5
58.3
50.1
39.8
30.4
53.6
44.3
34.9
67.5
58.1
48.7
39.4
76.4
71.1
61.7
52.4
76.5
72.9
63.6
54.2
43.6
33.1
58.7
48.2
37.7
73.8
63.2
52.7
42.2
79.8
77.4
66.9
56.3
79.4
79.4
68.9
58.4
62.5
51.1
39.7
78.4
67.1
55.7
44.3
81.6
80.4
69.1
57.7
81.3
81.3
69.9
58.5
66.2
54.0
41.8
83.1
70.9
58.6
46.4
83.5
83.5
71.3
59.0
83.1
83.1
70.9
58.7
105°F
28.6
21.6
39.4
32.4
25.4
50.2
43.2
36.2
29.2
59.9
50.6
43.6
36.6
32.1
23.9
44.0
35.8
27.6
55.9
47.7
39.6
31.4
62.1
55.9
47.7
39.6
64.4
58.0
49.8
41.6
35.6
26.2
48.6
39.2
29.9
61.7
52.3
42.9
33.5
64.3
61.2
51.9
42.5
66.7
63.5
54.1
44.8
39.0
28.5
53.2
42.6
32.1
67.4
56.8
46.3
35.7
66.6
66.6
56.0
45.4
69.0
69.0
58.5
47.9
56.9
45.5
34.1
70.6
60.6
49.3
37.9
68.0
68.0
56.6
45.2
70.5
70.5
59.1
47.8
60.5
48.4
36.2
73.9
64.5
52.3
40.1
69.4
69.4
57.2
45.1
72.0
72.0
59.8
47.6
65
37.3
40.2
41.8
43.0
44.8
45.8
47.8
46.3
47.1
46.8
46.4
29.7
31.4
33.5
33.1
35.4
34.8
37.3
33.9
36.4
32.9
35.5
27
246824-YTG-D-0806
XP078 (6.5 Ton)(Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
72.6
66.3
60.1
54.6
74.7
68.3
61.9
56.2
60.0
76.9
70.3
63.7
57.8
61.8
79.0
72.3
65.5
59.4
63.5
73.5
66.6
60.4
64.5
74.7
67.7
61.4
65.6
8.1
8.1
8.0
8.0
8.1
8.0
8.0
7.9
8.0
8.1
8.0
8.0
7.9
8.0
8.0
8.0
7.9
7.9
8.0
8.0
8.0
7.9
8.0
8.1
8.0
8.0
8.0
28.9
44.0
59.2
54.6
38.0
49.6
61.3
56.2
60.0
47.1
55.3
63.4
57.8
61.8
56.2
60.9
65.5
59.4
63.5
65.1
66.6
60.4
64.5
69.4
67.7
61.4
65.6
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
26.6
19.6
66.7
8.9
37.1
30.2
23.2
60.6
8.9
47.6
40.7
33.8
26.8
54.5
8.9
54.6
44.9
38.0
31.0
24.1
49.3
8.8
29.8
21.7
68.1
8.9
41.5
33.4
25.3
61.9
8.8
53.2
45.1
37.0
28.8
55.7
8.8
56.2
49.8
41.6
33.5
25.4
50.3
8.7
60.0
53.1
45.0
36.9
28.8
55.6
8.9
33.1
23.8
69.5
8.8
46.0
36.7
27.4
63.2
8.8
58.8
49.5
40.2
30.9
56.8
8.8
57.8
54.6
45.3
36.0
26.7
51.3
8.7
61.8
58.3
49.0
39.7
30.4
56.8
8.8
36.4
25.9
70.9
8.8
50.4
39.9
29.4
64.4
8.8
64.3
53.9
43.4
32.9
58.0
8.8
59.4
59.4
49.0
38.5
28.0
52.3
8.7
63.5
63.5
53.0
42.5
32.1
57.9
8.8
53.8
42.6
31.3
65.1
8.8
66.0
57.5
46.2
35.0
58.6
8.8
60.4
60.4
49.2
37.9
26.6
52.9
8.7
64.5
64.5
53.3
42.0
30.8
58.6
8.9
57.3
45.3
33.2
65.8
8.9
67.7
61.1
49.1
37.0
59.2
8.9
61.4
61.4
49.4
37.3
25.3
53.4
8.8
65.6
65.6
53.5
41.5
29.5
59.2
8.9
90
29.0
41.7
54.5
49.3
38.6
47.1
55.7
50.3
55.6
48.2
52.5
56.8
51.3
56.8
57.8
57.9
58.0
52.3
57.9
62.0
58.6
52.9
58.6
65.8
59.2
53.4
59.2
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
22.9
17.6
34.8
27.9
21.0
45.1
38.2
31.3
24.4
49.3
39.3
32.3
25.4
27.6
19.5
39.1
31.0
22.9
50.5
42.4
34.4
26.3
50.3
43.6
35.5
27.5
55.6
48.3
40.2
32.2
32.3
21.5
43.3
34.1
24.8
55.9
46.7
37.4
28.2
51.3
48.0
38.7
29.5
56.8
53.1
43.9
34.7
37.1
23.4
47.5
37.2
26.8
58.0
50.9
40.5
30.1
52.3
52.3
42.0
31.6
57.9
57.9
47.6
37.2
50.8
39.7
28.5
58.6
54.3
43.2
32.0
52.9
52.9
41.7
30.6
58.6
58.6
47.4
36.3
54.1
42.2
30.3
59.2
57.8
45.9
33.9
53.4
53.4
41.5
29.6
59.2
59.2
47.3
35.4
65
18.5
19.4
24.1
20.3
25.5
21.2
26.8
19.4
25.1
17.7
23.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
28
Unitary Products Group
246824-YTG-D-0806
XP090 (7.5 Ton)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
117.7
108.9
100.0
94.6
122.0
112.8
103.6
98.0
94.3
126.2
116.7
107.2
101.4
97.6
130.4
120.6
110.7
104.7
100.8
122.0
112.1
106.0
102.1
123.5
113.4
107.2
103.3
5.8
5.7
5.7
5.6
5.8
5.7
5.7
5.6
5.6
5.8
5.8
5.7
5.6
5.6
5.8
5.8
5.7
5.6
5.6
5.8
5.7
5.6
5.7
5.8
5.7
5.7
5.7
48.9
63.3
77.7
94.6
54.1
69.7
85.4
98.0
94.3
59.3
76.2
93.0
101.4
97.6
64.5
82.6
100.7
104.7
100.8
87.6
107.1
106.0
102.1
92.5
113.4
107.2
103.3
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
104.4
95.9
87.4
79.8
107.4
98.7
89.9
82.1
81.9
110.4
101.4
92.4
84.4
84.2
113.4
104.1
94.9
86.7
86.5
104.6
95.3
87.0
86.8
105.0
95.7
87.4
87.2
7.4
7.3
7.2
7.2
7.4
7.3
7.3
7.2
7.2
7.4
7.4
7.3
7.2
7.2
7.5
7.4
7.3
7.2
7.2
7.4
7.3
7.3
7.3
7.4
7.3
7.3
7.3
43.3
57.2
71.0
79.8
47.9
63.0
78.1
82.1
81.9
52.6
68.9
85.2
84.4
84.2
57.3
74.8
92.2
86.7
86.5
80.2
94.0
87.0
86.8
85.7
95.7
87.4
87.2
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
40.3
31.8
111.1
6.6
54.7
46.2
37.6
102.4
6.5
69.2
60.6
52.0
43.4
93.7
6.4
85.6
75.3
66.8
58.2
49.6
87.2
6.4
44.3
34.5
114.7
6.6
59.9
50.1
40.3
105.7
6.5
75.6
65.7
55.9
46.1
96.8
6.5
92.0
81.7
71.9
62.1
52.3
90.1
6.4
94.3
85.9
76.1
66.2
56.4
88.1
6.4
48.2
37.2
118.3
6.6
65.1
54.0
43.0
109.0
6.6
82.0
70.9
59.8
48.8
99.8
6.5
98.3
88.2
77.1
66.0
55.0
92.9
6.4
97.6
92.6
81.5
70.5
59.4
90.9
6.4
52.2
39.9
121.9
6.7
70.3
58.0
45.6
112.3
6.6
88.4
76.1
63.7
51.4
102.8
6.5
104.7 94.6
82.3
69.9
57.6
95.7
6.4
100.8 99.3
87.0
74.7
62.4
93.7
6.4
74.4
61.3
48.1
113.3
6.6
93.5
80.4
67.2
54.1
103.7
6.5
106.0 100.9 87.8
74.6
61.5
96.5
6.5
102.1 101.3 88.2
75.0
61.9
94.4
6.5
78.6
64.6
50.6
114.2
6.6
98.7
84.7
70.7
56.7
104.6
6.5
107.2 107.2 93.3
79.3
65.3
97.3
6.5
103.3 103.3 89.3
75.3
61.3
95.2
6.5
95°F
35.0
26.8
96.3
8.3
48.9
40.7
32.4
88.5
8.2
62.8
54.5
46.3
38.0
80.7
8.1
79.8
67.3
59.0
50.8
42.5
74.7
8.1
38.5
29.1
98.6
8.3
53.6
44.2
34.8
90.6
8.3
68.7
59.3
49.8
40.4
82.6
8.2
82.1
73.1
63.7
54.3
44.8
76.5
8.1
81.9
75.5
66.1
56.7
47.3
76.1
8.1
42.0
31.4
100.9
8.4
58.3
47.7
37.1
92.7
8.3
74.6
64.0
53.4
42.8
84.5
8.2
84.4
78.9
68.4
57.8
47.2
78.2
8.1
84.2
81.6
71.0
60.4
49.8
77.9
8.1
45.5
33.7
103.1
8.4
63.0
51.2
39.5
94.8
8.3
80.5
68.7
57.0
45.2
86.4
8.2
86.7
84.8
73.0
61.3
49.5
80.0
8.2
86.5
87.6
75.8
64.1
52.3
79.6
8.2
67.5
54.7
41.9
94.9
8.3
86.1
73.4
60.6
47.8
86.5
8.2
87.0
86.1
73.3
60.6
47.8
80.1
8.2
86.8
87.4
74.6
61.8
49.1
79.7
8.2
71.9
58.2
44.4
95.0
8.3
91.8
78.0
64.2
50.4
86.6
8.3
87.4
87.4
73.6
59.8
46.0
80.1
8.2
87.2
87.2
73.4
59.6
45.8
79.8
8.2
90
46.1
60.2
74.4
87.2
51.0
66.4
81.7
90.1
88.1
55.9
72.5
89.1
92.9
90.9
60.9
78.7
96.5
95.7
93.7
83.9
100.5
96.5
94.4
89.1
104.6
97.3
95.2
37.8
53.5
69.2
74.7
43.9
59.2
74.5
76.5
76.1
50.1
64.9
79.8
78.2
77.9
56.2
70.6
85.1
80.0
79.6
75.6
85.8
80.1
79.7
80.6
86.6
80.1
79.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
37.7
29.3
51.8
43.4
35.0
66.0
57.6
49.1
40.7
82.7
71.3
62.9
54.5
41.4
31.8
56.8
47.1
37.5
72.1
62.5
52.9
43.3
87.0
77.4
67.8
58.2
88.1
80.7
71.1
61.5
45.1
34.3
61.7
50.9
40.0
78.3
67.4
56.6
45.8
91.4
83.6
72.7
61.9
90.9
87.1
76.3
65.4
48.8
36.8
66.6
54.6
42.6
84.4
72.4
60.4
48.3
95.7
89.7
77.6
65.6
93.7
93.5
81.4
69.4
70.9
58.0
45.0
89.8
76.9
63.9
51.0
96.5
93.5
80.5
67.6
94.4
94.4
81.4
68.4
75.2
61.4
47.5
95.2
81.4
67.5
53.6
97.3
97.3
83.4
69.6
95.2
95.2
81.3
67.5
105°F
31.4
23.4
45.4
37.4
29.3
59.4
51.4
43.4
35.3
74.7
62.6
54.6
46.5
34.7
25.5
50.0
40.8
31.6
65.3
56.1
46.9
37.7
76.5
68.3
59.1
49.9
76.1
69.7
60.5
51.3
38.0
27.6
54.5
44.2
33.8
71.1
60.7
50.4
40.0
78.2
74.0
63.6
53.2
77.9
75.5
65.2
54.8
41.3
29.7
59.1
47.6
36.0
76.9
65.4
53.9
42.3
80.0
79.6
68.1
56.6
79.6
81.3
69.8
58.3
63.1
50.7
38.2
80.8
69.7
57.2
44.7
80.1
79.9
67.4
54.9
79.7
80.6
68.1
55.6
67.2
53.8
40.3
84.6
73.9
60.5
47.1
80.1
80.1
66.7
53.3
79.8
79.8
66.4
52.9
65
46.1
48.6
51.8
51.1
54.6
53.6
57.4
54.6
55.5
55.7
53.6
38.5
40.7
42.1
42.9
44.4
45.1
46.7
42.5
43.1
39.9
39.5
29
246824-YTG-D-0806
XP090 (7.5 Ton)(Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
88.3
81.1
74.0
69.6
89.8
82.6
75.3
70.8
70.3
91.4
84.0
76.6
72.0
71.5
92.9
85.4
77.9
73.3
72.7
85.2
77.7
73.1
72.6
85.0
77.5
72.9
72.4
9.2
9.1
9.1
9.0
9.3
9.2
9.1
9.1
9.1
9.3
9.2
9.1
9.1
9.1
9.3
9.2
9.2
9.1
9.1
9.2
9.2
9.1
9.1
9.3
9.2
9.1
9.1
32.2
49.8
67.3
69.6
39.9
55.3
70.8
70.8
70.3
47.5
60.9
74.3
72.0
71.5
55.1
66.5
77.9
73.3
72.7
71.0
77.7
73.1
72.6
75.5
77.5
72.9
72.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
27.8
20.0
80.3
10.2
41.9
34.1
26.3
73.8
10.1
56.1
48.2
40.4
32.6
67.3
10.0
69.6
57.9
50.1
42.3
34.5
64.5
10.0
30.9
21.9
81.1
10.2
46.4
37.4
28.4
74.5
10.1
61.8
52.9
43.9
34.9
68.0
10.0
70.8
63.4
54.5
45.5
36.5
65.2
10.0
70.3
63.9
54.9
46.0
37.0
64.5
10.0
34.0
23.8
81.9
10.2
50.8
40.6
30.5
75.3
10.1
67.6
57.5
47.3
37.2
68.7
10.1
72.0
69.0
58.8
48.7
38.5
65.9
10.0
71.5
69.5
59.4
49.2
39.1
65.2
10.0
37.0
25.7
82.7
10.2
55.2
43.9
32.6
76.0
10.2
73.4
62.1
50.8
39.5
69.3
10.1
73.3
74.5
63.2
51.9
40.6
66.5
10.1
72.7
75.1
63.8
52.5
41.2
65.9
10.0
58.8
46.6
34.5
75.5
10.2
75.4
65.9
53.8
41.6
68.9
10.1
73.1
73.7
61.5
49.3
37.1
66.1
10.1
72.6
73.7
61.5
49.4
37.2
65.4
10.1
62.4
49.4
36.3
75.0
10.2
77.5
69.8
56.7
43.7
68.4
10.1
72.9
72.9
59.8
46.8
33.7
65.6
10.1
72.4
72.4
59.3
46.2
33.2
65.0
10.1
90
26.0
46.1
65.7
64.5
35.8
51.5
67.2
65.2
64.5
45.6
56.9
68.7
65.9
65.2
55.4
62.4
69.3
66.5
65.9
66.4
68.9
66.1
65.4
70.4
68.4
65.6
65.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
24.0
16.6
38.5
30.9
23.3
52.7
45.1
37.5
29.9
64.5
53.2
45.6
38.0
27.1
18.3
42.7
34.0
25.2
58.4
49.6
40.9
32.1
65.2
58.6
49.9
41.1
64.5
58.1
49.4
40.6
30.2
20.0
47.0
37.1
27.2
64.1
54.2
44.3
34.3
65.9
64.0
54.1
44.1
65.2
63.5
53.6
43.6
33.3
21.7
51.3
40.2
29.1
69.3
58.7
47.7
36.6
66.5
66.5
58.3
47.2
65.9
65.9
57.7
46.7
54.5
42.6
30.7
68.9
62.2
50.3
38.4
66.1
66.1
55.6
43.7
65.4
65.4
55.0
43.1
57.7
45.0
32.3
68.4
65.7
53.0
40.3
65.6
65.6
52.9
40.2
65.0
65.0
52.3
39.6
65
30.4
32.3
31.8
34.2
33.7
36.1
35.6
31.8
31.2
27.5
26.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
30
Unitary Products Group
246824-YTG-D-0806
XP102 (8.5 Ton)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
120.9
113.7
106.4
96.7
126.2
118.6
110.9
100.9
100.3
131.4
123.5
115.5
105.1
104.4
136.7
128.4
120.1
109.3
108.6
132.2
123.6
112.5
111.8
136.0
127.2
115.7
115.0
6.2
6.1
6.0
5.9
6.2
6.1
6.0
6.0
5.9
6.2
6.1
6.0
6.0
6.0
6.2
6.1
6.0
6.0
6.0
6.2
6.1
6.0
6.0
6.3
6.2
6.1
6.1
58.3
69.9
81.4
96.7
62.1
78.1
94.1
100.9
100.3
65.9
86.3
106.8
105.1
104.4
69.7
94.6
119.5
109.3
108.6
101.6
123.3
112.5
111.8
108.6
127.2
115.7
115.0
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
116.2
105.1
94.0
87.9
120.4
108.9
97.4
91.1
91.1
124.5
112.6
100.7
94.2
94.2
128.7
116.4
104.1
97.4
97.4
118.8
106.3
99.4
99.4
121.3
108.4
101.4
101.4
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.7
7.7
7.9
7.9
7.8
7.7
7.7
7.9
7.9
7.9
7.8
7.8
7.9
7.9
7.8
7.8
7.9
7.9
7.8
7.8
46.9
64.7
82.5
87.9
56.5
73.1
89.7
91.1
91.1
66.1
81.5
96.9
94.2
94.2
75.7
89.9
104.1
97.4
97.4
96.9
106.3
99.4
99.4
103.9
108.4
101.4
101.4
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
45.7
36.0
118.6
7.0
60.2
50.5
40.8
109.4
6.9
74.6
65.0
55.3
45.6
100.2
6.9
94.3
79.3
69.6
59.9
50.2
92.3
6.8
51.0
39.8
123.3
7.0
67.0
55.8
44.7
113.7
7.0
83.0
71.8
60.7
49.5
104.2
6.9
99.3
87.7
76.5
65.4
54.3
96.0
6.8
100.5 89.7
78.6
67.5
56.3
95.7
6.8
56.2
43.6
128.0
7.0
73.7
61.2
48.6
118.1
7.0
91.3
78.7
66.1
53.5
108.1
6.9
104.3 96.1
83.5
70.9
58.3
99.6
6.9
104.6 98.3
85.8
73.2
60.6
99.3
6.9
61.5
47.5
132.7
7.1
80.5
66.5
52.5
122.4
7.0
99.6
85.6
71.5
57.5
112.1
7.0
109.3 104.5 90.4
76.4
62.4
103.3
6.9
108.6 106.9 92.9
78.9
64.9
103.0
6.9
86.1
70.7
55.3
125.5
7.1
106.7 91.0
75.5
60.1
115.0
7.0
112.5 110.1 94.7
79.2
63.8
105.9
6.9
111.8 111.0 95.5
80.1
64.7
105.6
6.9
91.8
74.9
58.1
128.6
7.1
113.8 96.4
79.5
62.7
117.8
7.0
115.7 115.7 98.9
82.1
65.2
108.6
7.0
115.0 115.0 98.2
81.4
64.5
108.2
7.0
95°F
39.8
29.8
107.5
8.9
54.7
44.7
34.7
97.2
8.8
69.6
59.6
49.5
39.5
86.8
8.8
87.9
71.6
61.6
51.5
41.5
80.7
8.7
44.9
33.3
111.4
8.9
61.5
49.9
38.3
100.6
8.9
78.1
66.5
54.9
43.3
89.9
8.8
91.1
79.9
68.3
56.7
45.1
83.5
8.7
90.8
79.2
67.6
56.0
44.4
85.1
8.8
50.0
36.8
115.2
9.0
68.3
55.1
41.9
104.0
8.9
86.6
73.4
60.2
47.0
92.9
8.9
94.2
88.2
75.0
61.8
48.6
86.4
8.8
94.1
87.5
74.3
61.0
47.8
88.0
8.8
55.0
40.2
119.0
9.0
75.1
60.3
45.5
107.5
9.0
95.2
80.4
65.6
50.8
96.0
8.9
97.4
96.6
81.8
67.0
52.2
89.2
8.8
97.4
95.7
80.9
66.1
51.3
90.9
8.8
80.7
64.4
48.2
109.5
9.0
101.8 85.9
69.7
53.4
97.8
8.9
99.4
99.0
82.8
66.5
50.3
90.9
8.8
99.4
98.6
82.3
66.1
49.9
92.6
8.8
86.2
68.6
50.9
111.6
9.0
108.4 91.4
73.8
56.1
99.7
8.9
101.4 101.4 83.8
66.1
48.4
92.6
8.9
101.4 101.4 83.8
66.1
48.5
94.4
8.9
90
52.6
67.3
82.0
92.3
59.3
75.6
91.9
96.0
95.7
66.0
83.9
101.8
99.6
99.3
72.7
92.2
111.8
103.3
103.0
99.2
114.8
105.9
105.6
106.2
117.8
108.6
108.2
44.1
62.6
81.1
80.7
56.2
71.1
86.0
83.5
85.1
68.4
79.7
91.0
86.4
88.0
80.5
88.3
96.0
89.2
90.9
95.4
97.8
90.9
92.6
102.5
99.7
92.6
94.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
42.8
32.9
57.4
47.6
37.7
72.1
62.3
52.4
42.5
91.1
75.4
65.6
55.7
47.9
36.6
64.2
52.9
41.5
80.5
69.2
57.8
46.4
95.2
83.8
72.4
61.0
95.7
84.5
73.1
61.7
53.1
40.2
71.0
58.1
45.2
89.0
76.1
63.2
50.3
99.2
92.2
79.3
66.4
99.3
92.9
80.0
67.1
58.3
43.8
77.8
63.4
49.0
97.4
83.0
68.5
54.1
103.3 100.5 86.1
71.7
103.0 101.3 86.9
72.5
83.4
67.6
51.8
104.3 88.4
72.6
56.8
105.9 104.5 88.7
72.9
105.6 104.8 88.9
73.1
89.0
71.8
54.5
111.1 93.9
76.7
59.4
108.6 108.6 91.3
74.1
108.2 108.2 91.0
73.7
105°F
37.9
28.3
52.5
42.4
32.3
67.1
56.5
46.4
36.3
80.7
68.6
58.5
48.4
43.5
31.8
59.4
47.6
35.9
75.2
63.5
51.7
40.0
83.5
77.0
65.3
53.5
85.0
73.3
61.6
49.8
49.2
35.3
66.3
52.9
39.4
83.4
70.4
57.0
43.6
86.4
85.5
72.1
58.7
87.9
81.4
67.9
54.5
54.8
38.8
73.2
58.1
43.0
91.5
77.4
62.3
47.2
89.2
93.9
78.9
63.8
90.9
89.4
74.3
59.2
78.8
62.2
45.6
95.6
82.9
66.3
49.7
90.9
93.3
76.7
60.1
92.6
91.9
75.3
58.7
84.4
66.3
48.2
99.7
88.4
70.3
52.2
92.6
92.6
74.6
56.5
94.4
94.4
76.3
58.2
65
45.9
49.7
50.3
53.5
54.2
57.3
58.1
57.1
57.3
56.8
56.5
38.3
41.8
38.1
45.2
41.1
48.7
44.1
43.5
42.1
38.4
40.1
31
246824-YTG-D-0806
XP102 (8.5 Ton)(Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
98.9
89.2
79.6
73.4
102.3
92.4
82.4
76.0
79.1
105.8
95.5
85.1
78.5
81.8
109.2
98.6
87.9
81.1
84.4
100.3
89.4
82.5
85.9
101.9
90.9
83.9
87.3
10.0
9.9
9.8
9.7
10.0
9.9
9.8
9.8
9.8
10.1
10.0
9.9
9.8
9.8
10.1
10.0
9.9
9.8
9.9
10.0
9.9
9.9
9.9
10.1
10.0
9.9
9.9
41.2
60.4
79.6
73.4
55.9
69.1
82.4
76.0
79.1
70.7
77.9
85.1
78.5
81.8
85.4
86.6
87.9
81.1
84.4
93.9
89.4
82.5
85.9
101.1
90.9
83.9
87.3
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
36.0
26.8
90.2
11.1
50.3
40.1
30.0
81.3
11.0
64.5
53.4
43.3
33.2
72.4
10.9
73.4
65.6
55.4
45.3
35.2
66.2
10.8
42.2
30.3
93.3
11.1
57.3
45.4
33.5
84.1
11.0
72.3
60.5
48.6
36.7
74.9
10.9
76.0
74.1
62.3
50.4
38.5
68.5
10.8
79.1
67.5
55.6
43.7
31.8
73.1
10.8
48.4
33.8
96.4
11.2
64.3
50.6
37.0
86.9
11.0
80.1
67.5
53.8
40.2
77.3
10.9
78.5
82.7
69.1
55.5
41.8
70.7
10.8
81.8
75.3
61.6
48.0
34.4
75.6
10.9
54.6
37.3
99.5
11.2
71.3
55.9
40.5
89.7
11.1
87.9
74.5
59.1
43.7
79.8
10.9
81.1
91.3
75.9
60.6
45.2
73.0
10.9
84.4
83.1
67.7
52.3
37.0
78.0
10.9
76.9
60.0
43.0
91.0
11.1
89.4
79.9
63.0
46.0
81.0
11.0
82.5
87.6
70.7
53.7
36.8
74.0
10.9
85.9
85.2
68.3
51.3
34.4
79.1
10.9
82.6
64.1
45.6
92.3
11.1
90.9
85.4
66.8
48.3
82.1
11.0
83.9
83.9
65.4
46.8
28.3
75.1
10.9
87.3
87.3
68.8
50.3
31.8
80.3
11.0
90
44.1
58.2
72.4
66.2
59.4
67.2
74.9
68.5
73.1
74.8
76.1
77.3
70.7
75.6
90.2
85.0
79.8
73.0
78.0
91.0
81.0
74.0
79.1
92.3
82.1
75.1
80.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
31.8
25.3
48.0
37.8
27.6
62.0
50.4
40.2
30.0
66.2
66.2
52.3
42.2
40.8
28.8
55.1
43.1
31.1
69.4
57.4
45.4
33.4
68.5
68.5
59.2
47.2
73.1
61.6
49.6
37.6
49.9
32.3
62.2
48.4
34.6
76.9
64.5
50.6
36.8
70.7
70.7
66.1
52.3
75.6
69.2
55.3
41.5
58.9
35.9
69.4
53.7
38.0
79.8
71.5
55.8
40.2
73.0
73.0
73.0
57.4
78.0
76.8
61.1
45.5
75.1
57.8
40.5
81.0
76.9
59.6
42.3
74.0
74.0
64.6
47.3
79.1
78.5
61.2
43.9
80.8
61.8
42.9
82.1
82.1
63.4
44.4
75.1
75.1
56.2
37.2
80.3
80.3
61.3
42.4
65
32.0
35.2
25.5
38.5
27.7
41.7
29.8
30.0
26.6
18.3
23.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
32
Unitary Products Group
246824-YTG-D-0806
XP120 (10 Ton)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
132.6
125.0
117.5
105.6
142.4
134.2
126.1
113.4
111.1
152.2
143.4
134.6
121.2
118.8
162.0
152.6
143.2
128.9
126.4
153.5
144.1
129.7
127.1
154.4
145.0
130.4
127.9
6.7
6.9
7.0
6.6
6.8
7.0
7.1
6.7
6.9
6.9
7.1
7.2
6.8
7.0
7.0
7.2
7.3
6.9
7.1
7.0
7.2
6.8
7.0
6.9
7.1
6.6
6.8
57.3
74.4
91.5
105.6
64.4
86.2
108.1
113.4
111.1
71.5
98.1
124.6
121.2
118.8
78.6
109.9
141.1
128.9
126.4
115.1
143.0
129.7
127.1
120.3
145.0
130.4
127.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
129.5
118.6
107.8
101.0
134.9
123.6
112.3
105.3
104.0
140.4
128.6
116.9
109.6
108.2
145.8
133.6
121.4
113.8
112.5
136.1
123.6
115.9
114.5
138.5
125.9
118.0
116.6
9.2
9.1
9.0
9.0
9.2
9.1
9.1
9.0
9.0
9.3
9.2
9.1
9.0
9.1
9.3
9.2
9.1
9.0
9.1
9.2
9.1
9.0
9.1
9.2
9.1
9.0
9.1
54.8
75.0
95.2
101.0
64.6
84.3
103.9
105.3
104.0
74.3
93.5
112.7
109.6
108.2
84.1
102.7
121.4
113.8
112.5
109.7
123.6
115.9
114.5
116.6
125.9
118.0
116.6
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
45.8
36.7
131.0
8.0
65.3
56.2
47.1
121.8
8.0
84.9
75.8
66.7
57.6
112.6
8.0
105.6 91.5
82.4
73.3
64.2
103.3
7.8
52.7
40.9
138.6
8.0
74.5
62.8
51.0
128.9
8.1
96.3
84.6
72.9
61.1
119.2
8.1
113.4 102.2 90.5
78.7
67.0
109.3
7.8
111.1 103.3 91.6
79.9
68.1
107.6
8.0
59.6
45.2
146.3
8.1
83.7
69.3
55.0
136.0
8.1
107.8 93.4
79.1
64.7
125.8
8.1
121.2 112.9 98.5
84.1
69.8
115.4
7.9
118.8 114.1 99.7
85.4
71.0
113.5
8.0
66.5
49.5
153.9
8.2
92.9
75.9
58.9
143.1
8.2
119.3 102.3 85.3
68.3
132.3
8.2
128.9 123.5 106.5 89.5
72.6
121.4
8.0
126.4 124.9 107.9 90.9
73.9
119.4
8.1
97.2
79.4
61.5
144.8
8.1
124.8 107.0 89.1
71.2
133.9
8.1
129.7 127.0 109.1 91.2
73.4
122.8
7.9
127.1 126.4 108.5 90.6
72.7
120.8
8.0
101.6 82.8
64.1
146.5
8.1
130.4 111.6 92.9
74.1
135.4
8.1
130.4 130.4 111.7 92.9
74.2
124.2
7.8
127.9 127.9 109.1 90.3
71.6
122.2
8.0
95°F
45.7
34.2
120.4
10.4
63.5
51.9
40.4
109.9
10.3
81.2
69.7
58.1
46.6
99.5
10.2
101.0 83.6
72.0
60.5
48.9
93.0
10.1
51.2
37.9
125.1
10.4
70.9
57.6
44.3
114.2
10.3
90.6
77.3
63.9
50.6
103.4
10.2
105.3 92.7
79.4
66.0
52.7
96.7
10.2
104.0 92.8
79.5
66.1
52.8
95.6
10.2
56.8
41.6
129.9
10.5
78.4
63.3
48.2
118.6
10.4
100.0 84.9
69.8
54.7
107.3
10.3
109.6 101.8 86.7
71.6
56.5
100.4
10.2
108.2 102.0 86.8
71.7
56.6
99.2
10.3
62.3
45.4
134.6
10.5
85.8
69.0
52.1
122.9
10.5
109.4 92.5
75.6
58.7
111.2
10.4
113.8 111.0 94.1
77.2
60.3
104.0
10.3
112.5 111.1 94.2
77.3
60.4
102.8
10.3
91.5
73.4
55.3
124.7
10.4
116.6 98.5
80.4
62.2
112.9
10.3
115.9 114.5 96.4
78.2
60.1
105.6
10.3
114.5 113.8 95.7
77.6
59.5
104.4
10.3
97.2
77.9
58.5
126.6
10.4
123.8 104.5 85.1
65.7
114.5
10.3
118.0 118.0 98.6
79.3
59.9
107.1
10.2
116.6 116.6 97.2
77.9
58.5
105.9
10.3
90
56.1
74.7
93.4
103.3
64.5
85.2
106.0
109.3
107.6
72.9
95.8
118.6
115.4
113.5
81.3
106.3
131.3
121.4
119.4
112.4
133.3
122.8
120.8
118.5
135.4
124.2
122.2
49.5
71.4
93.2
93.0
63.4
81.3
99.2
96.7
95.6
77.3
91.3
105.2
100.4
99.2
91.2
101.2
111.2
104.0
102.8
107.3
112.9
105.6
104.4
113.4
114.5
107.1
105.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
45.7
35.4
64.4
54.1
43.7
83.0
72.7
62.4
52.1
103.3 87.5
77.2
66.9
52.0
39.4
72.7
60.2
47.7
93.5
80.9
68.4
55.9
109.3 97.4
84.9
72.4
107.6 98.1
85.5
73.0
58.2
43.4
81.0
66.3
51.6
103.9 89.2
74.4
59.7
115.4 107.4 92.6
77.9
113.5 108.0 93.3
78.6
64.4
47.4
89.4
72.4
55.5
114.3 97.4
80.4
63.5
121.4 117.3 100.3 83.4
119.4 118.0 101.0 84.1
94.4
76.4
58.4
120.7 102.7 84.7
66.7
122.8 120.7 102.7 84.7
120.8 120.1 102.1 84.1
99.4
80.3
61.3
127.1 108.1 89.0
69.9
124.2 124.2 105.2 86.1
122.2 122.2 103.2 84.1
105°F
41.8
31.1
59.9
48.4
37.0
78.0
65.7
54.3
42.8
93.0
75.3
63.9
52.4
48.4
34.8
67.7
54.1
40.6
87.1
73.5
59.9
46.3
96.7
84.2
70.6
57.0
95.6
84.7
71.1
57.5
55.0
38.5
75.6
59.8
44.1
96.1
81.2
65.5
49.8
100.4 93.0
77.3
61.6
99.2
93.6
77.9
62.1
61.6
42.1
83.4
65.6
47.7
105.2 89.0
71.2
53.3
104.0 101.9 84.1
66.2
102.8 102.5 84.6
66.8
88.5
69.6
50.8
109.4 94.5
75.7
56.8
105.6 104.5 85.7
66.8
104.4 104.2 85.3
66.5
93.6
73.7
53.8
113.5 100.0 80.1
60.3
107.1 107.1 87.3
67.4
105.9 105.9 86.0
66.1
65
56.6
59.9
60.5
63.1
63.8
66.4
67.2
66.7
66.1
67.0
65.0
41.0
43.4
43.9
45.9
46.4
48.4
49.0
48.0
47.6
47.5
46.3
33
246824-YTG-D-0806
XP120 (10 Ton)(Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
111.3
101.2
91.1
85.0
115.3
104.9
94.4
88.1
87.1
119.4
108.5
97.7
91.2
90.1
123.4
112.2
101.0
94.2
93.2
113.4
102.1
95.3
94.2
114.6
103.2
96.3
95.2
11.5
11.4
11.3
11.2
11.6
11.5
11.4
11.3
11.4
11.7
11.6
11.5
11.4
11.5
11.8
11.7
11.6
11.5
11.5
11.7
11.6
11.5
11.5
11.6
11.5
11.4
11.5
44.2
67.7
91.1
85.0
62.3
78.4
94.4
88.1
87.1
80.3
89.0
97.7
91.2
90.1
98.4
99.7
101.0
94.2
93.2
105.0
102.1
95.3
94.2
110.3
103.2
96.3
95.2
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
37.9
28.1
102.2
12.7
56.3
44.9
33.6
92.5
12.6
74.8
61.8
50.4
39.1
82.8
12.5
85.0
67.1
55.8
44.4
33.0
77.0
12.4
45.5
31.7
105.5
12.8
64.5
50.7
36.8
95.5
12.7
83.5
69.7
55.8
42.0
85.5
12.6
88.1
75.7
61.9
48.0
34.2
79.5
12.5
87.1
76.5
62.7
48.8
35.0
78.6
12.5
53.2
35.3
108.8
12.9
72.7
56.4
40.1
98.5
12.8
92.3
77.6
61.3
45.0
88.1
12.7
91.2
84.3
68.0
51.6
35.3
82.0
12.6
90.1
85.2
68.9
52.6
36.3
81.1
12.7
60.8
38.9
112.1
13.0
80.9
62.2
43.4
101.5
12.9
101.0 85.5
66.7
47.9
90.8
12.9
94.2
92.8
74.1
55.3
36.5
84.4
12.7
93.2
93.8
75.1
56.3
37.5
83.6
12.8
85.4
65.8
46.3
102.1
12.9
102.1 90.5
70.9
51.4
91.4
12.8
95.3
94.6
75.0
55.4
35.8
84.9
12.7
94.2
94.5
74.9
55.4
35.8
84.0
12.7
89.9
69.5
49.1
102.7
12.8
103.2 95.6
75.2
54.8
91.9
12.7
96.3
96.3
75.9
55.5
35.1
85.4
12.6
95.2
95.2
74.8
54.4
34.0
84.5
12.7
90
45.2
64.0
82.8
77.0
65.3
75.4
85.5
79.5
78.6
85.4
86.8
88.1
82.0
81.1
105.5
98.2
90.8
84.4
83.6
102.1
91.4
84.9
84.0
102.7
91.9
85.4
84.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
30.9
25.1
52.7
41.5
30.2
71.8
57.9
46.6
35.3
77.0
58.9
47.6
36.3
42.7
28.6
61.3
47.2
33.1
80.0
65.9
51.8
37.7
79.5
67.2
53.1
39.0
78.6
68.4
54.3
40.2
54.4
32.1
69.9
53.0
36.1
88.1
73.9
57.0
40.1
82.0
75.5
58.6
41.7
81.1
76.8
59.9
43.0
66.1
35.6
78.5
58.8
39.0
90.8
81.9
62.2
42.5
84.4
83.7
64.0
44.3
83.6
83.6
65.5
45.8
82.4
62.1
41.7
91.4
86.5
66.2
45.9
84.9
84.6
64.3
44.0
84.0
84.0
64.6
44.3
86.3
65.4
44.4
91.9
91.1
70.2
49.3
85.4
85.4
64.5
43.6
84.5
84.5
63.6
42.7
65
25.1
24.9
26.1
24.8
26.1
24.6
26.1
23.7
23.9
22.7
21.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
34
Unitary Products Group
246824-YTG-D-0806
XP150 (12.5 Ton)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
163.7
158.9
154.2
145.0
169.7
164.7
159.8
150.3
147.7
175.7
170.5
165.4
155.6
152.9
181.6
176.3
171.0
160.9
158.1
180.7
175.3
164.9
162.0
185.0
179.5
168.8
165.9
9.7
9.5
9.4
9.3
9.7
9.5
9.4
9.3
9.4
9.7
9.5
9.4
9.3
9.4
9.7
9.5
9.4
9.3
9.4
9.6
9.5
9.4
9.4
9.6
9.5
9.4
9.4
70.7
95.0
119.4
145.0
77.1
103.5
129.9
150.3
147.7
83.5
112.0
140.4
155.6
152.9
89.9
120.4
150.9
160.9
158.1
125.2
159.2
164.9
162.0
129.9
167.4
168.8
165.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
155.1
148.5
141.8
133.3
160.4
153.5
146.6
137.8
135.3
165.6
158.5
151.4
142.3
139.8
170.8
163.5
156.2
146.8
144.2
167.7
160.2
150.5
147.9
171.8
164.1
154.2
151.5
11.6
11.5
11.4
11.3
11.6
11.6
11.5
11.3
11.4
11.7
11.7
11.6
11.4
11.5
11.8
11.7
11.7
11.5
11.5
11.7
11.6
11.5
11.5
11.7
11.6
11.5
11.5
64.1
89.6
115.1
133.3
71.2
99.2
127.1
137.8
135.3
78.4
108.8
139.2
142.3
139.8
85.5
118.4
151.3
146.8
144.2
125.0
157.7
150.5
147.9
131.6
164.1
154.2
151.5
Unitary Products Group
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
58.2
45.7
159.4
10.6
82.6
70.1
57.6
153.7
10.5
106.9 94.4
81.9
69.4
148.0
10.4
137.7 121.3 108.8 96.4
83.9
139.1
10.3
63.4
49.7
165.0
10.7
89.8
76.1
62.3
159.1
10.6
116.2 102.4 88.7
75.0
153.2
10.5
145.4 131.7 118.0 104.2 90.5
144.0
10.3
147.7 135.9 122.2 108.4 94.7
141.5
10.4
68.5
53.6
170.6
10.7
97.0
82.0
67.1
164.5
10.6
125.5 110.5 95.5
80.6
158.4
10.5
153.2 142.1 127.1 112.1 97.2
148.9
10.4
152.9 146.6 131.6 116.7 101.7
146.3
10.4
73.7
57.5
176.2
10.7
104.2 88.0
71.8
169.9
10.6
134.7 118.5 102.3 86.1
163.6
10.5
160.9 152.4 136.2 120.0 103.8
153.8
10.4
158.1 157.3 141.1 124.9 108.7
151.2
10.4
108.5 91.8
75.2
174.2
10.6
140.3 123.6 107.0 90.3
167.7
10.6
164.9 160.6 144.0 127.3 110.6
157.7
10.4
162.0 161.6 145.0 128.3 111.6
154.9
10.5
112.8 95.7
78.5
178.4
10.7
145.8 128.7 111.6 94.5
171.8
10.6
168.8 168.8 151.7 134.6 117.5
161.5
10.4
165.9 165.9 148.8 131.7 114.6
158.7
10.5
95°F
51.2
38.3
147.3
13.0
76.7
63.8
51.0
140.1
12.9
102.2 89.4
76.5
63.6
133.0
12.8
131.3 111.2 98.3
85.4
72.6
126.1
12.6
56.6
42.0
152.0
13.0
84.6
70.0
55.4
144.6
12.9
112.5 97.9
83.3
68.7
137.2
12.8
136.5 121.9 107.3 92.7
78.1
130.1
12.7
135.3 121.8 107.2 92.6
78.0
128.0
12.7
62.0
45.7
156.7
13.1
92.4
76.1
59.8
149.0
13.0
122.9 106.5 90.2
73.9
141.4
12.9
141.6 132.6 116.2 99.9
83.6
134.1
12.7
139.8 132.5 116.2 99.8
83.5
131.9
12.8
67.4
49.4
161.3
13.1
100.3 82.3
64.2
153.5
13.0
133.2 115.1 97.1
79.0
145.7
12.9
146.8 143.3 125.2 107.1 89.0
138.1
12.8
144.2 143.2 125.1 107.1 89.0
135.9
12.8
106.2 87.3
68.5
157.5
13.0
141.1 122.2 103.4 84.6
149.5
12.9
150.5 148.7 129.9 111.1 92.2
141.7
12.8
147.9 147.3 128.5 109.7 90.8
139.4
12.8
112.0 92.4
72.8
161.6
13.0
148.9 129.3 109.7 90.1
153.3
12.9
154.2 154.2 134.6 115.0 95.4
145.4
12.8
151.5 151.5 131.9 112.3 92.7
143.0
12.8
90
67.4
92.3
117.2
139.1
74.2
101.3
128.5
144.0
141.5
80.9
110.4
139.8
148.9
146.3
87.7
119.4
151.1
153.8
151.2
125.1
158.4
157.7
154.9
130.7
165.8
161.5
158.7
58.0
86.8
115.6
126.1
67.7
96.2
124.8
130.1
128.0
77.3
105.7
134.0
134.1
131.9
86.9
115.1
143.2
138.1
135.9
122.1
148.3
141.7
139.4
129.1
153.3
145.4
143.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
54.7
42.0
79.6
67.0
54.3
104.6 91.9
79.2
66.5
134.5 116.3 103.6 90.9
60.0
45.8
87.2
73.0
58.9
114.4 100.2 86.0
71.9
140.9 126.8 112.6 98.5
141.5 128.9 114.7 100.5
65.3
49.6
94.7
79.1
63.4
124.2 108.5 92.9
77.2
147.4 137.3 121.7 106.0
146.3 139.6 123.9 108.3
70.6
53.4
102.3 85.1
68.0
134.0 116.8 99.7
82.6
153.8 147.8 130.7 113.6
151.2 150.3 133.1 116.0
107.3 89.6
71.8
140.7 122.9 105.2 87.4
157.7 154.7 136.9 119.2
154.9 154.5 136.7 119.0
112.4 94.0
75.7
147.4 129.0 110.7 92.3
161.5 161.5 143.2 124.8
158.7 158.7 140.3 122.0
105°F
47.7
34.5
73.7
60.6
47.5
99.8
86.7
73.6
60.5
124.4 104.1 91.0
77.9
52.8
37.8
81.3
66.4
51.5
109.9 95.0
80.1
65.2
129.0 114.1 99.1
84.2
128.0 114.9 100.0 85.1
57.9
41.2
88.9
72.2
55.5
120.0 103.3 86.5
69.8
133.5 124.0 107.3 90.6
131.9 125.0 108.2 91.5
63.0
44.5
96.5
78.0
59.5
130.1 111.5 93.0
74.5
138.1 134.0 115.4 96.9
135.9 135.0 116.5 97.9
102.6 83.1
63.5
137.9 118.8 99.3
79.8
141.7 139.7 120.1 100.6
139.4 139.0 119.5 100.0
108.6 88.1
67.6
145.7 126.0 105.5 85.1
145.4 145.4 124.9 104.4
143.0 143.0 122.5 102.1
65
78.2
84.3
86.4
90.4
92.6
96.4
98.9
101.4
101.2
106.4
103.6
64.8
69.3
70.2
73.8
74.8
78.4
79.4
81.1
80.5
83.9
81.6
35
246824-YTG-D-0806
XP150 (12.5 Ton)(Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
139.5
131.8
124.1
118.9
143.6
135.7
127.8
122.4
120.6
147.7
139.6
131.5
125.9
124.1
151.8
143.5
135.1
129.4
127.6
147.4
138.8
133.0
131.0
151.3
142.5
136.5
134.5
14.4
14.2
14.1
14.0
14.4
14.3
14.1
14.0
14.1
14.5
14.3
14.1
14.1
14.1
14.5
14.3
14.2
14.1
14.1
14.4
14.2
14.1
14.1
14.4
14.2
14.2
14.2
52.0
84.1
116.1
118.9
64.1
93.3
122.5
122.4
120.6
76.2
102.5
128.8
125.9
124.1
88.3
111.7
135.1
129.4
127.6
119.1
138.8
133.0
131.0
126.5
142.5
136.5
134.5
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
44.1
30.8
131.7
15.8
70.7
57.4
44.1
123.5
15.6
97.4
84.0
70.7
57.4
115.3
15.4
117.5 97.0
83.7
70.3
57.0
111.7
15.4
48.9
33.7
135.2
15.8
78.1
62.9
47.6
126.8
15.6
107.2 92.0
76.8
61.6
118.4
15.4
121.5 106.2 91.0
75.8
60.6
114.7
15.4
120.6 108.1 92.8
77.6
62.4
113.3
15.4
53.7
36.6
138.8
15.8
85.4
68.3
51.2
130.1
15.6
117.1 100.0 82.9
65.8
121.5
15.4
125.4 115.4 98.3
81.2
64.1
117.8
15.4
124.1 117.4 100.3 83.2
66.1
116.3
15.4
58.5
39.5
142.3
15.9
92.7
73.7
54.8
133.5
15.6
127.0 108.0 89.0
70.0
124.6
15.4
129.4 124.6 105.7 86.7
67.7
120.8
15.4
127.6 126.8 107.8 88.8
69.8
119.2
15.4
98.9
78.8
58.6
137.3
15.7
134.7 115.3 95.2
75.0
128.1
15.5
133.0 130.6 110.4 90.2
70.1
124.2
15.5
131.0 130.7 110.5 90.3
70.1
122.6
15.5
105.2 83.8
62.5
141.1
15.7
142.5 122.7 101.3 80.0
131.7
15.5
136.5 136.5 115.2 93.8
72.5
127.6
15.5
134.5 134.5 113.2 91.8
70.5
126.0
15.5
90
47.4
81.4
115.3
111.7
62.4
90.4
118.4
114.7
113.3
77.3
99.4
121.5
117.8
116.3
92.2
108.4
124.6
120.8
119.2
116.2
128.1
124.2
122.6
123.9
131.7
127.6
126.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
40.6
27.0
67.8
54.2
40.6
95.0
81.4
67.8
54.2
110.5 89.9
76.4
62.8
45.1
29.5
74.8
59.3
43.7
104.6 89.1
73.5
58.0
114.0 98.4
82.9
67.3
113.3 101.2 85.6
70.1
49.6
32.1
81.9
64.4
46.9
114.2 96.7
79.2
61.7
117.4 106.9 89.4
71.9
116.3 109.9 92.4
74.9
54.1
34.6
89.0
69.5
50.0
123.8 104.4 84.9
65.5
120.8 115.3 95.9
76.4
119.2 118.6 99.1
79.7
95.3
74.5
53.7
128.1 111.9 91.0
70.2
124.2 121.5 100.7 79.8
122.6 122.3 101.5 80.6
101.7 79.5
57.3
131.7 119.4 97.2
74.9
127.6 127.6 105.4 83.2
126.0 126.0 103.8 81.6
65
49.2
51.8
54.6
54.4
57.4
57.0
60.2
59.0
59.8
61.0
59.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
XP078-150 Heating Capacities
XP078-150
Size
(Tons)
Model
Air Over Evaporator
Coil
CFM
DB (°F)
55
1950
70
80
55
078
(6.5)
XP
2600
70
80
55
3250
70
80
36
Capacity1 &
kW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
Outdoor Temperature (°F @ 72% RH)
-10
0
10
20
30
40
50
60
18.7
4.8
13.9
5.6
11.6
6.4
21.8
4.2
16.9
5.0
14.7
5.8
22.9
3.9
18.1
4.7
15.8
5.5
29.2
4.9
24.4
5.7
22.1
6.5
32.3
4.3
27.4
5.1
25.2
6.0
33.5
4.0
28.6
4.9
26.3
5.6
39.8
5.1
35.0
5.9
32.6
6.7
42.9
4.5
37.9
5.3
35.8
6.1
44.0
4.2
39.2
5.0
36.9
5.8
50.3
5.2
45.5
6.0
43.2
6.8
53.4
4.6
48.5
5.4
46.3
6.3
54.6
4.3
49.7
5.2
47.4
6.0
60.9
5.4
56.0
6.2
53.7
7.0
64.0
4.8
59.0
5.6
56.8
6.4
65.1
4.5
60.3
5.3
58.0
6.1
71.4
5.5
66.6
6.3
64.3
7.1
74.5
4.9
69.6
5.7
67.4
6.6
75.6
4.6
70.8
5.5
68.5
6.3
81.9
5.7
77.1
6.5
74.8
7.3
85.1
5.1
80.1
5.9
77.9
6.7
86.2
4.8
81.4
5.6
79.0
6.4
92.5
5.8
87.7
6.7
85.3
7.4
95.6
5.2
90.7
6.0
88.5
6.9
96.7
4.9
91.9
5.8
89.6
6.6
Unitary Products Group
246824-YTG-D-0806
XP078-150 (Continued)
Size
(Tons)
Model
Air Over Evaporator
Coil
CFM
DB (°F)
55
2250
70
80
55
090
(7.5)
XP
3000
70
80
55
3750
70
80
55
2550
70
80
55
102
(8.5)
XP
3400
70
80
55
4250
70
80
55
3000
70
80
55
120
(10)
XP
4000
70
80
55
5000
70
80
Unitary Products Group
Capacity1 &
kW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
Outdoor Temperature (°F @ 72% RH)
-10
0
10
20
30
40
50
60
19.0
5.0
14.7
6.1
11.6
6.9
22.0
4.4
17.7
5.4
14.5
6.2
21.7
4.0
17.4
5.0
14.3
5.8
9.4
4.9
12.2
6.1
11.1
6.9
14.9
4.3
17.7
5.6
16.6
6.4
17.2
4.0
20.0
5.2
18.9
6.1
14.5
5.9
11.2
7.0
7.8
7.9
24.6
5.5
21.2
6.7
17.9
7.6
21.2
5.0
17.8
6.2
14.4
7.0
31.5
5.2
27.2
6.3
24.1
7.1
34.4
4.6
30.2
5.6
27.0
6.4
34.2
4.2
29.9
5.2
26.8
6.1
22.3
5.1
25.1
6.3
24.0
7.1
27.8
4.5
30.6
5.8
29.4
6.6
30.1
4.2
32.9
5.4
31.8
6.3
29.4
6.0
26.0
7.2
22.7
8.1
39.5
5.7
36.1
6.8
32.8
7.7
36.0
5.2
32.6
6.3
29.3
7.2
43.9
5.4
39.7
6.5
36.5
7.3
46.9
4.8
42.6
5.8
39.4
6.7
46.6
4.4
42.3
5.4
39.2
6.3
35.1
5.3
37.9
6.5
36.8
7.3
40.6
4.7
43.4
6.0
42.3
6.8
42.9
4.4
45.7
5.6
44.6
6.5
44.3
6.2
40.9
7.4
37.6
8.3
54.3
5.8
51.0
7.0
47.6
7.9
50.9
5.3
47.5
6.5
44.2
7.4
56.4
5.6
52.1
6.7
49.0
7.5
59.3
5.0
55.1
6.0
51.9
6.9
59.1
4.6
54.8
5.6
51.7
6.5
48.0
5.5
50.8
6.7
49.7
7.5
53.5
4.9
56.3
6.2
55.1
7.0
55.8
4.6
58.6
5.9
57.5
6.7
59.1
6.4
55.7
7.5
52.4
8.4
69.2
6.0
65.8
7.2
62.5
8.1
65.8
5.5
62.4
6.6
59.0
7.5
68.8
5.9
64.6
6.9
61.5
7.7
71.8
5.2
67.5
6.3
64.4
7.1
71.5
4.8
67.3
5.8
64.1
6.7
60.8
5.7
63.7
6.9
62.5
7.7
66.3
5.2
69.1
6.4
68.0
7.2
68.6
4.8
71.4
6.1
70.3
6.9
74.0
6.5
70.6
7.7
67.3
8.6
84.1
6.2
80.7
7.3
77.4
8.2
80.6
5.6
77.2
6.8
73.9
7.7
81.3
6.1
77.0
7.1
73.9
7.9
84.2
5.4
80.0
6.5
76.8
7.3
84.0
5.0
79.7
6.0
76.6
6.9
73.7
5.9
76.5
7.1
75.4
7.9
79.2
5.4
82.0
6.6
80.8
7.4
81.5
5.0
84.3
6.3
83.2
7.1
88.9
6.7
85.5
7.9
82.1
8.8
98.9
6.3
95.5
7.5
92.2
8.4
95.5
5.8
92.1
7.0
88.8
7.9
93.8
6.3
89.5
7.3
86.4
8.1
96.7
5.6
92.5
6.7
89.3
7.5
96.5
5.2
92.2
6.3
89.1
7.1
86.5
6.1
89.4
7.3
88.2
8.2
92.0
5.6
94.8
6.8
93.7
7.6
94.3
5.2
97.1
6.5
96.0
7.3
103.7
6.9
100.3
8.0
97.0
8.9
113.8
6.5
110.4
7.6
107.1
8.5
110.3
6.0
107.0
7.1
103.6
8.0
106.2
6.5
101.9
7.5
98.8
8.4
109.2
5.8
104.9
6.9
101.7
7.7
108.9
5.4
104.6
6.5
101.5
7.3
99.4
6.3
102.2
7.5
101.1
8.4
104.9
5.8
107.7
7.0
106.6
7.8
107.2
5.4
110.0
6.7
108.9
7.5
118.6
7.0
115.2
8.2
111.9
9.1
128.7
6.6
125.3
7.8
122.0
8.7
125.2
6.1
121.8
7.3
118.5
8.2
37
246824-YTG-D-0806
XP078-150 (Continued)
Size
(Tons)
Model
Air Over Evaporator
Coil
CFM
DB (°F)
55
3750
70
80
55
150
(12.5)
XP
5000
70
80
55
6250
70
80
Capacity1 &
kW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
Outdoor Temperature (°F @ 72% RH)
-10
0
10
20
30
40
50
60
26.2
8.0
22.8
9.5
19.5
10.7
34.3
7.2
30.9
8.7
27.6
9.9
36.3
6.8
32.9
8.3
29.6
9.5
45.3
8.4
41.9
9.9
38.7
11.1
53.4
7.6
50.1
9.1
46.7
10.3
55.5
7.2
52.0
8.7
48.8
9.9
64.5
8.8
61.0
10.3
57.8
11.5
72.6
8.0
69.2
9.5
65.8
10.7
74.6
7.6
71.1
9.1
67.9
10.3
83.6
9.2
80.2
10.7
76.9
11.9
91.7
8.4
88.3
9.9
85.0
11.1
93.7
8.0
90.3
9.5
87.0
10.7
102.7
9.6
99.3
11.1
96.1
12.3
110.8
8.8
107.5
10.3
104.1
11.5
112.8
8.4
109.4
9.9
106.2
11.1
121.9
10.0
118.4
11.5
115.2
12.7
130.0
9.2
126.6
10.7
123.2
11.9
132.0
8.8
128.5
10.3
125.3
11.5
141.0
10.4
137.6
11.9
134.3
13.1
149.1
9.6
145.7
11.1
142.4
12.3
151.1
9.2
147.7
10.7
144.4
11.9
160.1
10.8
156.7
12.3
153.5
13.5
168.2
10.0
164.8
11.5
161.5
12.7
170.2
9.6
166.8
11.1
163.6
12.3
1. These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh = 3.415 x
kW.
38
Unitary Products Group
246824-YTG-D-0806
Airflow Performance
ZH078-150 Side Duct Application
ZH078 (6.5 Ton)-Side Duct
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
RPM
751
763
776
790
804
819
835
852
869
887
906
925
945
965
987
1008
1030
1053
1076
1100
1124
0.2
W
204
264
327
393
463
537
614
695
780
870
963
1061
1162
1268
1377
1491
1608
1730
1855
1984
2116
RPM
1040
1052
1064
1078
1092
1108
1124
1140
1158
1176
1194
1214
1234
1254
-
1.2
W
999
1059
1123
1189
1259
1332
1409
1491
1576
1665
1759
1856
1958
2063
-
BHP
0.22
0.28
0.35
0.42
0.50
0.58
0.66
0.75
0.84
0.93
1.03
1.14
1.25
1.36
1.48
1.60
1.73
1.86
1.99
2.13
2.27
BHP
1.07
1.14
1.20
1.28
1.35
1.43
1.51
1.60
1.69
1.79
1.89
1.99
2.10
2.21
-
RPM
813
825
838
851
866
881
897
914
931
949
968
987
1007
1027
1048
1070
1092
1115
1138
-
0.4
W
402
462
525
591
661
735
812
893
978
1068
1161
1259
1360
1466
1575
1689
1806
1927
2053
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.43
872
576
0.62
929
0.50
884
636
0.68
941
0.56
897
699
0.75
954
0.63
910
766
0.82
968
0.71
925
836
0.90
982
0.79
940
909
0.98
997
0.87
956
986
1.06
1013
0.96
973
1068
1.15
1030
1.05
990
1153
1.24
1047
1.15
1008
1242
1.33
1065
1.25
1027
1335
1.43
1084
1.35
1046
1433
1.54
1103
1123
1.46
1066
1534
1.65
1086
1640
1.76
1143
1.57
1107
1750
1.88
1165
1.69
1.81
1129
1863
2.00
1186
1.94
1151
1981
2.12
1208
2.07
1174
2102
2.25
2.20
-
0.8
W
731
791
854
921
991
1064
1141
1223
1308
1397
1491
1588
1690
1795
1905
2018
2136
-
BHP
0.78
0.85
0.92
0.99
1.06
1.14
1.22
1.31
1.40
1.50
1.60
1.70
1.81
1.93
2.04
2.17
2.29
-
RPM
985
997
1010
1023
1038
1053
1069
1085
1103
1121
1139
1159
1179
1199
1220
-
1.0
W
871
931
994
1060
1130
1204
1281
1362
1447
1537
1630
1728
1829
1935
2044
-
RPM
1095
1106
1119
1133
1147
1162
1178
1195
1212
1230
1249
1268
1288
-
1.4
W
1120
1181
1244
1310
1380
1453
1530
1612
1697
1786
1880
1977
2079
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
1.20
1150
1238
1.33
1206
1.27
1162
1298
1.39
1218
1.33
1175
1362
1.46
1231
1.41
1188
1428
1.53
1245
1.48
1203
1498
1.61
1259
1274
1.56
1218
1571
1.69
1234
1648
1.77
1290
1.64
1.73
1250
1730
1.86
1307
1.82
1268
1815
1.95
1324
1.92
1286
1904
2.04
1342
2.02
1304
1998
2.14
1361
2.12
1324
2095
2.25
2.23
-
1.8
W
1357
1417
1480
1547
1616
1690
1767
1848
1934
2023
2116
-
BHP
1.46
1.52
1.59
1.66
1.73
1.81
1.90
1.98
2.07
2.17
2.27
-
RPM
1265
1276
1289
1303
1317
1332
1348
1365
1382
1400
-
2.0
W
1480
1541
1604
1670
1740
1813
1891
1972
2057
2147
-
BHP
0.93
1.00
1.07
1.14
1.21
1.29
1.37
1.46
1.55
1.65
1.75
1.85
1.96
2.08
2.19
-
BHP
1.59
1.65
1.72
1.79
1.87
1.95
2.03
2.12
2.21
2.30
-
1. Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
Unitary Products Group
39
246824-YTG-D-0806
ZH090 (7.5 Ton)-Side Duct
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
RPM
751
763
776
790
804
819
835
852
869
887
906
925
945
965
987
1008
1030
1053
1076
1100
1124
1148
1173
1199
1224
1251
1277
1304
0.2
W
204
264
327
393
463
537
614
695
780
870
963
1061
1162
1268
1377
1491
1608
1730
1855
1984
2116
2252
2392
2535
2682
2832
2986
3142
RPM
1040
1052
1064
1078
1092
1108
1124
1140
1158
1176
1194
1214
1234
1254
1275
1297
1319
1341
1364
1388
1412
1437
1462
-
1.2
W
999
1059
1123
1189
1259
1332
1409
1491
1576
1665
1759
1856
1958
2063
2173
2286
2404
2525
2650
2779
2911
3048
3187
-
BHP
0.22
0.28
0.35
0.42
0.50
0.58
0.66
0.75
0.84
0.93
1.03
1.14
1.25
1.36
1.48
1.60
1.73
1.86
1.99
2.13
2.27
2.42
2.57
2.72
2.88
3.04
3.20
3.37
BHP
1.07
1.14
1.20
1.28
1.35
1.43
1.51
1.60
1.69
1.79
1.89
1.99
2.10
2.21
2.33
2.45
2.58
2.71
2.84
2.98
3.12
3.27
3.42
-
RPM
813
825
838
851
866
881
897
914
931
949
968
987
1007
1027
1048
1070
1092
1115
1138
1161
1185
1210
1235
1260
1286
1312
1339
-
0.4
W
402
462
525
591
661
735
812
893
978
1068
1161
1259
1360
1466
1575
1689
1806
1927
2053
2181
2314
2450
2590
2733
2880
3030
3184
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.43
872
576
0.62
929
0.50
884
636
0.68
941
0.56
897
699
0.75
954
0.63
910
766
0.82
968
0.71
925
836
0.90
982
0.79
940
909
0.98
997
0.87
956
986
1.06
1013
0.96
973
1068
1.15
1030
1.05
990
1153
1.24
1047
1.15
1008
1242
1.33
1065
1.25
1027
1335
1.43
1084
1.35
1046
1433
1.54
1103
1.46
1066
1534
1.65
1123
1.57
1086
1640
1.76
1143
1.69
1107
1750
1.88
1165
1.81
1129
1863
2.00
1186
1.94
1151
1981
2.12
1208
1231
2.07
1174
2102
2.25
1197
2227
2.39
1254
2.20
2.34
1221
2356
2.53
1278
2.48
1245
2488
2.67
1302
2.63
1269
2625
2.82
1326
2.78
1294
2764
2.97
1351
2.93
1319
2908
3.12
1377
3.09
1345
3054
3.28
1402
3.25
1371
3204
3.44
3.42
-
0.8
W
731
791
854
921
991
1064
1141
1223
1308
1397
1491
1588
1690
1795
1905
2018
2136
2257
2382
2511
2643
2780
2919
3063
3209
-
BHP
0.78
0.85
0.92
0.99
1.06
1.14
1.22
1.31
1.40
1.50
1.60
1.70
1.81
1.93
2.04
2.17
2.29
2.42
2.56
2.69
2.84
2.98
3.13
3.29
3.44
-
RPM
985
997
1010
1023
1038
1053
1069
1085
1103
1121
1139
1159
1179
1199
1220
1242
1264
1286
1310
1333
1357
1382
1407
1432
-
1.0
W
871
931
994
1060
1130
1204
1281
1362
1447
1537
1630
1728
1829
1935
2044
2158
2275
2397
2522
2651
2783
2919
3059
3202
-
BHP
0.93
1.00
1.07
1.14
1.21
1.29
1.37
1.46
1.55
1.65
1.75
1.85
1.96
2.08
2.19
2.31
2.44
2.57
2.71
2.84
2.99
3.13
3.28
3.44
-
RPM
1095
1106
1119
1133
1147
1162
1178
1195
1212
1230
1249
1268
1288
1309
1330
1351
1374
1396
1419
1443
1467
1491
-
1.4
W
1120
1181
1244
1310
1380
1453
1530
1612
1697
1786
1880
1977
2079
2184
2294
2407
2525
2646
2771
2900
3033
3169
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
1.20
1150
1238
1.33
1206
1.27
1162
1298
1.39
1218
1.33
1175
1362
1.46
1231
1.41
1188
1428
1.53
1245
1.48
1203
1498
1.61
1259
1.56
1218
1571
1.69
1274
1.64
1234
1648
1.77
1290
1.73
1250
1730
1.86
1307
1.82
1268
1815
1.95
1324
1.92
1286
1904
2.04
1342
2.02
1304
1998
2.14
1361
2.12
1324
2095
2.25
1380
1344
2197
2.36
1400
2.23
2.34
1364
2302
2.47
1421
2.46
1385
2412
2.59
1442
2.58
1407
2525
2.71
1463
2.71
1429
2643
2.84
1485
2.84
1451
2764
2.97
1508
2.97
1475
2889
3.10
1531
3.11
1498
3018
3.24
1555
3.25
1522
3150
3.38
3.40
-
1.8
W
1357
1417
1480
1547
1616
1690
1767
1848
1934
2023
2116
2214
2315
2421
2530
2644
2761
2883
3008
3137
-
BHP
1.46
1.52
1.59
1.66
1.73
1.81
1.90
1.98
2.07
2.17
2.27
2.37
2.48
2.60
2.71
2.84
2.96
3.09
3.23
3.37
-
RPM
1265
1276
1289
1303
1317
1332
1348
1365
1382
1400
1419
1438
1458
1479
1500
1521
1544
1566
1589
-
2.0
W
1480
1541
1604
1670
1740
1813
1891
1972
2057
2147
2240
2337
2439
2544
2654
2768
2885
3006
3131
-
BHP
1.59
1.65
1.72
1.79
1.87
1.95
2.03
2.12
2.21
2.30
2.40
2.51
2.62
2.73
2.85
2.97
3.10
3.23
3.36
-
1. Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
40
Unitary Products Group
246824-YTG-D-0806
ZH102 (8.5 Ton)-Side Duct
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
RPM
644
649
654
659
664
670
675
680
686
692
699
706
713
720
728
736
745
754
763
773
783
794
805
816
828
840
852
865
879
892
906
0.2
W
194
250
302
351
398
445
493
541
591
643
698
756
818
882
951
1023
1099
1180
1264
1353
1447
1545
1647
1753
1864
1980
2100
2224
2353
2486
2623
RPM
883
888
893
898
904
909
914
920
925
932
938
945
952
959
967
975
984
993
1002
1012
1022
1033
1044
1055
1067
1079
1092
1105
-
1.2
W
1079
1135
1187
1236
1283
1330
1378
1426
1476
1529
1584
1642
1703
1767
1836
1908
1984
2065
2150
2239
2332
2430
2532
2638
2749
2865
2985
3109
-
BHP
0.21
0.27
0.32
0.38
0.43
0.48
0.53
0.58
0.63
0.69
0.75
0.81
0.88
0.95
1.02
1.10
1.18
1.27
1.36
1.45
1.55
1.66
1.77
1.88
2.00
2.12
2.25
2.39
2.52
2.67
2.81
BHP
1.16
1.22
1.27
1.33
1.38
1.43
1.48
1.53
1.58
1.64
1.70
1.76
1.83
1.90
1.97
2.05
2.13
2.22
2.31
2.40
2.50
2.61
2.72
2.83
2.95
3.07
3.20
3.34
-
RPM
695
701
706
711
716
721
726
732
738
744
750
757
764
772
779
788
796
805
815
824
835
845
856
868
879
891
904
917
930
944
958
0.4
W
389
445
497
546
593
640
688
736
786
839
894
952
1013
1077
1146
1218
1295
1375
1460
1549
1642
1740
1842
1948
2059
2175
2295
2419
2548
2681
2819
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.42
745
573
0.61
793
0.48
750
629
0.67
798
0.53
755
681
0.73
803
0.59
760
730
0.78
808
0.64
765
778
0.83
813
0.69
771
824
0.88
818
0.74
776
872
0.94
824
0.79
781
920
0.99
829
0.84
787
970
1.04
835
0.90
793
1023
1.10
841
0.96
800
1078
1.16
847
1.02
807
1136
1.22
854
1.09
814
1197
1.28
861
1.16
821
1262
1.35
869
1.23
829
1330
1.43
877
1.31
837
1402
1.50
885
1.39
846
1479
1.59
893
1.48
855
1559
1.67
902
1.57
864
1644
1.76
912
1.66
874
1733
1.86
922
1.76
884
1826
1.96
932
1.87
895
1924
2.06
942
953
1.98
906
2026
2.17
965
2.09
917
2133
2.29
929
2244
2.41
976
2.21
2.33
941
2359
2.53
989
2.46
953
2479
2.66
1001
2.60
966
2603
2.79
1014
2.73
980
2732
2.93
1027
2.88
993
2865
3.07
1041
3.02
1007
3003
3.22
1055
0.8
W
748
804
856
905
952
999
1047
1095
1145
1198
1253
1311
1372
1437
1505
1577
1654
1734
1819
1908
2001
2099
2201
2307
2419
2534
2654
2778
2907
3040
3178
BHP
0.80
0.86
0.92
0.97
1.02
1.07
1.12
1.18
1.23
1.28
1.34
1.41
1.47
1.54
1.61
1.69
1.77
1.86
1.95
2.05
2.15
2.25
2.36
2.48
2.59
2.72
2.85
2.98
3.12
3.26
3.41
RPM
839
844
849
854
859
864
870
875
881
887
893
900
907
915
923
931
939
948
958
968
978
988
999
1011
1022
1035
1047
1060
1073
1087
-
1.0
W
916
972
1024
1073
1120
1167
1215
1263
1313
1366
1421
1479
1540
1604
1673
1745
1822
1902
1987
2076
2169
2267
2369
2475
2586
2702
2822
2946
3075
3208
-
BHP
0.98
1.04
1.10
1.15
1.20
1.25
1.30
1.36
1.41
1.47
1.52
1.59
1.65
1.72
1.79
1.87
1.95
2.04
2.13
2.23
2.33
2.43
2.54
2.66
2.77
2.90
3.03
3.16
3.30
3.44
-
RPM
926
932
937
942
947
952
957
963
969
975
981
988
995
1003
1010
1019
1027
1036
1046
1055
1066
1076
1087
1098
1110
1122
1135
-
1.4
W
1239
1295
1347
1396
1443
1490
1538
1586
1636
1689
1744
1802
1863
1928
1996
2068
2145
2225
2310
2399
2492
2590
2692
2798
2910
3025
3145
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
1.33
969
1398
1.50
1010
1.39
974
1454
1.56
1015
1.44
979
1506
1.62
1020
1.50
984
1555
1.67
1025
1.55
989
1603
1.72
1030
1.60
994
1650
1.77
1036
1.65
1000
1697
1.82
1041
1.70
1005
1746
1.87
1047
1.76
1011
1796
1.93
1052
1.81
1017
1848
1.98
1058
1.87
1024
1903
2.04
1065
1.93
1030
1961
2.10
1072
1079
2.00
1037
2022
2.17
1086
2.07
1045
2087
2.24
1053
2155
2.31
1094
2.14
2.22
1061
2227
2.39
1102
1069
2304
2.47
1111
2.30
2.39
1078
2384
2.56
1120
2.48
1088
2469
2.65
1129
2.57
1098
2558
2.74
1139
2.67
1108
2651
2.84
1149
2.78
1118
2749
2.95
1160
2.89
1129
2851
3.06
1171
3.00
1141
2958
3.17
1182
3.12
1152
3069
3.29
3.25
1165
3184
3.42
3.37
-
1.8
W
1559
1615
1667
1716
1763
1810
1858
1906
1956
2008
2063
2121
2182
2247
2316
2388
2464
2545
2629
2718
2812
2909
3012
3118
-
BHP
1.67
1.73
1.79
1.84
1.89
1.94
1.99
2.04
2.10
2.15
2.21
2.28
2.34
2.41
2.48
2.56
2.64
2.73
2.82
2.92
3.02
3.12
3.23
3.35
-
RPM
1051
1056
1061
1066
1071
1076
1082
1087
1093
1099
1106
1112
1119
1127
1135
1143
1152
1161
1170
1180
1190
1200
1211
-
2.0
W
1722
1778
1830
1879
1927
1974
2021
2070
2120
2172
2227
2285
2346
2411
2479
2552
2628
2708
2793
2882
2975
3073
3175
-
BHP
1.85
1.91
1.96
2.02
2.07
2.12
2.17
2.22
2.27
2.33
2.39
2.45
2.52
2.59
2.66
2.74
2.82
2.91
3.00
3.09
3.19
3.30
3.41
-
1. Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
Unitary Products Group
41
246824-YTG-D-0806
ZH120 (10 Ton)-Side Duct
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
RPM
644
649
654
659
664
670
675
680
686
692
699
706
713
720
728
736
745
754
763
773
783
794
805
816
828
840
852
865
879
892
906
0.2
W
194
250
302
351
398
445
493
541
591
643
698
756
818
882
951
1023
1099
1180
1264
1353
1447
1545
1647
1753
1864
1980
2100
2224
2353
2486
2623
RPM
883
888
893
898
904
909
914
920
925
932
938
945
952
959
967
975
984
993
1002
1012
1022
1033
1044
1055
1067
1079
1092
1105
-
1.2
W
1079
1135
1187
1236
1283
1330
1378
1426
1476
1529
1584
1642
1703
1767
1836
1908
1984
2065
2150
2239
2332
2430
2532
2638
2749
2865
2985
3109
-
BHP
0.21
0.27
0.32
0.38
0.43
0.48
0.53
0.58
0.63
0.69
0.75
0.81
0.88
0.95
1.02
1.10
1.18
1.27
1.36
1.45
1.55
1.66
1.77
1.88
2.00
2.12
2.25
2.39
2.52
2.67
2.81
BHP
1.16
1.22
1.27
1.33
1.38
1.43
1.48
1.53
1.58
1.64
1.70
1.76
1.83
1.90
1.97
2.05
2.13
2.22
2.31
2.40
2.50
2.61
2.72
2.83
2.95
3.07
3.20
3.34
-
RPM
695
701
706
711
716
721
726
732
738
744
750
757
764
772
779
788
796
805
815
824
835
845
856
868
879
891
904
917
930
944
958
0.4
W
389
445
497
546
593
640
688
736
786
839
894
952
1013
1077
1146
1218
1295
1375
1460
1549
1642
1740
1842
1948
2059
2175
2295
2419
2548
2681
2819
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.42
745
573
0.61
793
0.48
750
629
0.67
798
0.53
755
681
0.73
803
0.59
760
730
0.78
808
0.64
765
778
0.83
813
0.69
771
824
0.88
818
0.74
776
872
0.94
824
0.79
781
920
0.99
829
0.84
787
970
1.04
835
0.90
793
1023
1.10
841
0.96
800
1078
1.16
847
1.02
807
1136
1.22
854
1.09
814
1197
1.28
861
1.16
821
1262
1.35
869
1.23
829
1330
1.43
877
1.31
837
1402
1.50
885
1.39
846
1479
1.59
893
1.48
855
1559
1.67
902
1.57
864
1644
1.76
912
1.66
874
1733
1.86
922
1.76
884
1826
1.96
932
1.87
895
1924
2.06
942
953
1.98
906
2026
2.17
965
2.09
917
2133
2.29
929
2244
2.41
976
2.21
2.33
941
2359
2.53
989
2.46
953
2479
2.66
1001
2.60
966
2603
2.79
1014
2.73
980
2732
2.93
1027
2.88
993
2865
3.07
1041
3.02
1007
3003
3.22
1055
0.8
W
748
804
856
905
952
999
1047
1095
1145
1198
1253
1311
1372
1437
1505
1577
1654
1734
1819
1908
2001
2099
2201
2307
2419
2534
2654
2778
2907
3040
3178
BHP
0.80
0.86
0.92
0.97
1.02
1.07
1.12
1.18
1.23
1.28
1.34
1.41
1.47
1.54
1.61
1.69
1.77
1.86
1.95
2.05
2.15
2.25
2.36
2.48
2.59
2.72
2.85
2.98
3.12
3.26
3.41
RPM
839
844
849
854
859
864
870
875
881
887
893
900
907
915
923
931
939
948
958
968
978
988
999
1011
1022
1035
1047
1060
1073
1087
-
1.0
W
916
972
1024
1073
1120
1167
1215
1263
1313
1366
1421
1479
1540
1604
1673
1745
1822
1902
1987
2076
2169
2267
2369
2475
2586
2702
2822
2946
3075
3208
-
BHP
0.98
1.04
1.10
1.15
1.20
1.25
1.30
1.36
1.41
1.47
1.52
1.59
1.65
1.72
1.79
1.87
1.95
2.04
2.13
2.23
2.33
2.43
2.54
2.66
2.77
2.90
3.03
3.16
3.30
3.44
-
RPM
926
932
937
942
947
952
957
963
969
975
981
988
995
1003
1010
1019
1027
1036
1046
1055
1066
1076
1087
1098
1110
1122
1135
-
1.4
W
1239
1295
1347
1396
1443
1490
1538
1586
1636
1689
1744
1802
1863
1928
1996
2068
2145
2225
2310
2399
2492
2590
2692
2798
2910
3025
3145
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
1.33
969
1398
1.50
1010
1.39
974
1454
1.56
1015
1.44
979
1506
1.62
1020
1.50
984
1555
1.67
1025
1.55
989
1603
1.72
1030
1.60
994
1650
1.77
1036
1.65
1000
1697
1.82
1041
1.70
1005
1746
1.87
1047
1.76
1011
1796
1.93
1052
1.81
1017
1848
1.98
1058
1.87
1024
1903
2.04
1065
1.93
1030
1961
2.10
1072
1079
2.00
1037
2022
2.17
1086
2.07
1045
2087
2.24
1053
2155
2.31
1094
2.14
1061
2227
2.39
1102
2.22
1069
2304
2.47
1111
2.30
2.39
1078
2384
2.56
1120
2.48
1088
2469
2.65
1129
2.57
1098
2558
2.74
1139
2.67
1108
2651
2.84
1149
2.78
1118
2749
2.95
1160
2.89
1129
2851
3.06
1171
3.00
1141
2958
3.17
1182
3.12
1152
3069
3.29
3.25
1165
3184
3.42
3.37
-
1.8
W
1559
1615
1667
1716
1763
1810
1858
1906
1956
2008
2063
2121
2182
2247
2316
2388
2464
2545
2629
2718
2812
2909
3012
3118
-
BHP
1.67
1.73
1.79
1.84
1.89
1.94
1.99
2.04
2.10
2.15
2.21
2.28
2.34
2.41
2.48
2.56
2.64
2.73
2.82
2.92
3.02
3.12
3.23
3.35
-
RPM
1051
1056
1061
1066
1071
1076
1082
1087
1093
1099
1106
1112
1119
1127
1135
1143
1152
1161
1170
1180
1190
1200
1211
-
2.0
W
1722
1778
1830
1879
1927
1974
2021
2070
2120
2172
2227
2285
2346
2411
2479
2552
2628
2708
2793
2882
2975
3073
3175
-
BHP
1.85
1.91
1.96
2.02
2.07
2.12
2.17
2.22
2.27
2.33
2.39
2.45
2.52
2.59
2.66
2.74
2.82
2.91
3.00
3.09
3.19
3.30
3.41
-
1. Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
42
Unitary Products Group
246824-YTG-D-0806
ZH150 (12.5 Ton)-Side Duct
Air Flow
(CFM)
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
Air Flow
(CFM)
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
RPM
713
720
728
736
745
754
763
773
783
794
805
816
828
840
852
865
879
892
906
921
936
951
966
982
999
1015
1032
1050
1067
1085
1103
0.2
W
818
882
951
1023
1099
1180
1264
1353
1447
1545
1647
1753
1864
1980
2100
2224
2353
2486
2623
2765
2911
3062
3216
3375
3538
3706
3877
4052
4232
4415
4602
RPM
952
959
967
975
984
993
1002
1012
1022
1033
1044
1055
1067
1079
1092
1105
1118
1132
1146
1160
1175
1190
1206
1222
1238
1254
1271
1289
1306
1324
-
1.2
W
1703
1767
1836
1908
1984
2065
2150
2239
2332
2430
2532
2638
2749
2865
2985
3109
3238
3371
3509
3650
3797
3947
4102
4261
4424
4591
4762
4937
5117
5300
-
BHP
0.88
0.95
1.02
1.10
1.18
1.27
1.36
1.45
1.55
1.66
1.77
1.88
2.00
2.12
2.25
2.39
2.52
2.67
2.81
2.97
3.12
3.28
3.45
3.62
3.80
3.98
4.16
4.35
4.54
4.74
4.94
BHP
1.83
1.90
1.97
2.05
2.13
2.22
2.31
2.40
2.50
2.61
2.72
2.83
2.95
3.07
3.20
3.34
3.47
3.62
3.76
3.92
4.07
4.23
4.40
4.57
4.75
4.93
5.11
5.30
5.49
5.69
-
RPM
764
772
779
788
796
805
815
824
835
845
856
868
879
891
904
917
930
944
958
972
987
1002
1018
1034
1050
1067
1084
1101
1119
1137
1155
0.4
W
1013
1077
1146
1218
1295
1375
1460
1549
1642
1740
1842
1948
2059
2175
2295
2419
2548
2681
2819
2960
3107
3257
3412
3571
3734
3901
4072
4247
4427
4610
4797
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
1.09
814
1197
1.28
861
1.16
821
1262
1.35
869
1.23
829
1330
1.43
877
1.31
837
1402
1.50
885
1.39
846
1479
1.59
893
1.48
855
1559
1.67
902
1.57
864
1644
1.76
912
1.66
874
1733
1.86
922
1.76
884
1826
1.96
932
1.87
895
1924
2.06
942
1.98
906
2026
2.17
953
2.09
917
2133
2.29
965
2.21
929
2244
2.41
976
2.33
941
2359
2.53
989
2.46
953
2479
2.66
1001
2.60
966
2603
2.79
1014
2.73
980
2732
2.93
1027
2.88
993
2865
3.07
1041
3.02
1007
3003
3.22
1055
1070
3.18
1022
3144
3.37
1037
3291
3.53
1084
3.33
3.49
1052
3441
3.69
1100
3.66
1067
3596
3.86
1115
3.83
1083
3755
4.03
1131
4.01
1100
3918
4.20
1147
4.18
1116
4085
4.38
1164
4.37
1133
4256
4.57
1181
4.56
1150
4432
4.75
1198
4.75
1168
4611
4.95
1216
4.95
1186
4794
5.14
1234
5.15
1204
4982
5.34
1252
0.8
W
1372
1437
1505
1577
1654
1734
1819
1908
2001
2099
2201
2307
2419
2534
2654
2778
2907
3040
3178
3319
3466
3616
3771
3930
4093
4260
4431
4607
4786
4969
5157
BHP
1.47
1.54
1.61
1.69
1.77
1.86
1.95
2.05
2.15
2.25
2.36
2.48
2.59
2.72
2.85
2.98
3.12
3.26
3.41
3.56
3.72
3.88
4.05
4.22
4.39
4.57
4.75
4.94
5.13
5.33
5.53
RPM
907
915
923
931
939
948
958
968
978
988
999
1011
1022
1035
1047
1060
1073
1087
1101
1116
1130
1146
1161
1177
1193
1210
1227
1244
1262
1280
1298
1.0
W
1540
1604
1673
1745
1822
1902
1987
2076
2169
2267
2369
2475
2586
2702
2822
2946
3075
3208
3346
3487
3634
3784
3939
4098
4261
4428
4599
4774
4954
5137
5324
BHP
1.65
1.72
1.79
1.87
1.95
2.04
2.13
2.23
2.33
2.43
2.54
2.66
2.77
2.90
3.03
3.16
3.30
3.44
3.59
3.74
3.90
4.06
4.23
4.40
4.57
4.75
4.93
5.12
5.31
5.51
5.71
RPM
995
1003
1010
1019
1027
1036
1046
1055
1066
1076
1087
1098
1110
1122
1135
1148
1161
1175
1189
1203
1218
1233
1249
1265
1281
1298
1315
1332
1350
-
1.4
W
1863
1928
1996
2068
2145
2225
2310
2399
2492
2590
2692
2798
2910
3025
3145
3269
3398
3531
3669
3810
3957
4107
4262
4421
4584
4751
4922
5098
5277
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
2.00
1037
2022
2.17
1079
2.07
1045
2087
2.24
1086
2.14
1053
2155
2.31
1094
2.22
1061
2227
2.39
1102
2.30
1069
2304
2.47
1111
2.39
1078
2384
2.56
1120
2.48
1088
2469
2.65
1129
2.57
1098
2558
2.74
1139
2.67
1108
2651
2.84
1149
2.78
1118
2749
2.95
1160
2.89
1129
2851
3.06
1171
3.00
1141
2958
3.17
1182
1194
3.12
1152
3069
3.29
1206
3.25
1165
3184
3.42
1177
3304
3.54
1219
3.37
3.51
1190
3428
3.68
1231
3.65
1203
3557
3.82
1245
3.79
1217
3690
3.96
1258
3.94
1231
3828
4.11
1273
4.09
1246
3970
4.26
1287
4.24
1260
4116
4.42
1302
4.41
1276
4266
4.58
1317
4.57
1291
4421
4.74
1333
4.74
1307
4580
4.91
1348
4.92
1323
4743
5.09
1365
5.10
1340
4910
5.27
1381
5.28
1357
5081
5.45
1398
5.47
1374
5257
5.64
5.66
-
1.8
W
2182
2247
2316
2388
2464
2545
2629
2718
2812
2909
3012
3118
3229
3345
3465
3589
3718
3851
3988
4130
4276
4427
4581
4740
4903
5071
5242
-
BHP
2.34
2.41
2.48
2.56
2.64
2.73
2.82
2.92
3.02
3.12
3.23
3.35
3.46
3.59
3.72
3.85
3.99
4.13
4.28
4.43
4.59
4.75
4.91
5.09
5.26
5.44
5.62
-
RPM
1119
1127
1135
1143
1152
1161
1170
1180
1190
1200
1211
1223
1235
1247
1259
1272
1285
1299
1313
1328
1343
1358
1373
1389
1405
1422
-
2.0
W
2346
2411
2479
2552
2628
2708
2793
2882
2975
3073
3175
3282
3393
3508
3628
3753
3881
4015
4152
4294
4440
4590
4745
4904
5067
5234
-
BHP
2.52
2.59
2.66
2.74
2.82
2.91
3.00
3.09
3.19
3.30
3.41
3.52
3.64
3.76
3.89
4.03
4.16
4.31
4.45
4.61
4.76
4.92
5.09
5.26
5.44
5.62
-
1. Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
Unitary Products Group
43
246824-YTG-D-0806
ZH078-150 Bottom Duct Application
ZH078 (6.5 Ton)-Bottom Duct
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
RPM
775
788
803
820
838
857
878
900
923
946
971
996
1023
1049
1077
1105
1133
1163
1192
-
0.2
W
289
350
416
487
562
642
727
817
912
1012
1118
1229
1345
1466
1591
1722
1858
1999
2144
-
0.4
W
494
556
622
692
767
847
932
1022
1117
1218
1323
1434
1550
1671
1797
1928
2063
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.53
924
673
0.72
998
0.60
937
735
0.79
1011
0.67
952
800
0.86
1026
0.74
968
871
0.93
1042
0.82
986
946
1.01
1060
0.91
1006
1026
1.10
1080
1.00
1027
1111
1.19
1100
1.10
1048
1201
1.29
1122
1.20
1071
1296
1.39
1145
1.31
1095
1396
1.50
1169
1193
1.42
1119
1502
1.61
1145
1613
1.73
1219
1.54
1171
1729
1.85
1245
1.66
1.79
1198
1850
1.98
1272
1.93
1225
1976
2.12
1299
2.07
1253
2106
2.26
2.21
-
0.8
W
832
894
960
1030
1105
1185
1270
1360
1455
1556
1661
1772
1888
2009
2135
-
BHP
0.31
0.38
0.45
0.52
0.60
0.69
0.78
0.88
0.98
1.09
1.20
1.32
1.44
1.57
1.71
1.85
1.99
2.14
2.30
-
RPM
850
863
878
894
913
932
953
974
997
1021
1046
1071
1097
1124
1151
1179
1208
-
RPM
1.8
W
BHP
1384
1397
1412
1429
1447
1466
1487
1509
-
1575
1637
1703
1773
1848
1928
2013
2103
-
1.69
1.76
1.83
1.90
1.98
2.07
2.16
2.26
-
RPM
1.2
W
BHP
Available External Static Pressure - IWG1
1.4
1.6
RPM
W
BHP
RPM
W
BHP
1147
1160
1175
1192
1210
1229
1250
1272
1294
1318
1343
1368
-
1119
1181
1247
1317
1392
1472
1557
1647
1742
1843
1948
2059
-
1.20
1.27
1.34
1.41
1.49
1.58
1.67
1.77
1.87
1.98
2.09
2.21
-
1224
1237
1252
1268
1286
1306
1327
1348
1371
1395
1419
-
1261
1323
1389
1459
1534
1614
1699
1789
1884
1985
2090
-
1.35
1.42
1.49
1.57
1.65
1.73
1.82
1.92
2.02
2.13
2.24
-
1303
1316
1331
1347
1365
1385
1405
1427
1450
1474
-
1411
1473
1538
1609
1684
1764
1849
1939
2034
2134
-
1.51
1.58
1.65
1.73
1.81
1.89
1.98
2.08
2.18
2.29
-
BHP
0.89
0.96
1.03
1.10
1.19
1.27
1.36
1.46
1.56
1.67
1.78
1.90
2.03
2.16
2.29
-
RPM
1072
1085
1100
1116
1134
1154
1174
1196
1219
1243
1267
1293
1319
-
1.0
W
978
1040
1106
1176
1252
1331
1416
1506
1602
1702
1808
1919
2034
-
BHP
1.05
1.12
1.19
1.26
1.34
1.43
1.52
1.62
1.72
1.83
1.94
2.06
2.18
-
1. Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
44
Unitary Products Group
246824-YTG-D-0806
ZH090 (7.5 Ton)-Bottom Duct
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
RPM
775
788
803
820
838
857
878
900
923
946
971
996
1023
1049
1077
1105
1133
1163
1192
1222
1253
1284
1315
1346
1378
-
0.2
W
289
350
416
487
562
642
727
817
912
1012
1118
1229
1345
1466
1591
1722
1858
1999
2144
2294
2448
2607
2771
2938
3110
-
RPM
1147
1160
1175
1192
1210
1229
1250
1272
1294
1318
1343
1368
1394
1421
1448
1476
1505
1534
1564
1594
-
1.2
W
1119
1181
1247
1317
1392
1472
1557
1647
1742
1843
1948
2059
2175
2296
2422
2553
2689
2829
2975
3124
-
BHP
0.31
0.38
0.45
0.52
0.60
0.69
0.78
0.88
0.98
1.09
1.20
1.32
1.44
1.57
1.71
1.85
1.99
2.14
2.30
2.46
2.63
2.80
2.97
3.15
3.34
-
BHP
1.20
1.27
1.34
1.41
1.49
1.58
1.67
1.77
1.87
1.98
2.09
2.21
2.33
2.46
2.60
2.74
2.88
3.04
3.19
3.35
-
RPM
850
863
878
894
913
932
953
974
997
1021
1046
1071
1097
1124
1151
1179
1208
1237
1267
1297
1327
1358
1389
1421
-
0.4
W
494
556
622
692
767
847
932
1022
1117
1218
1323
1434
1550
1671
1797
1928
2063
2204
2349
2499
2654
2813
2976
3144
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.53
924
673
0.72
998
0.60
937
735
0.79
1011
0.67
952
800
0.86
1026
0.74
968
871
0.93
1042
0.82
986
946
1.01
1060
0.91
1006
1026
1.10
1080
1.00
1027
1111
1.19
1100
1.10
1048
1201
1.29
1122
1.20
1071
1296
1.39
1145
1.31
1095
1396
1.50
1169
1.42
1119
1502
1.61
1193
1.54
1145
1613
1.73
1219
1.66
1171
1729
1.85
1245
1.79
1198
1850
1.98
1272
1.93
1225
1976
2.12
1299
1327
2.07
1253
2106
2.26
1282
2242
2.41
1356
2.21
2.36
1311
2383
2.56
1385
2.52
1341
2528
2.71
1414
2.68
1371
2678
2.87
1444
2.85
1401
2832
3.04
1475
3.02
1432
2991
3.21
1506
3.19
1463
3155
3.38
3.37
-
0.8
W
832
894
960
1030
1105
1185
1270
1360
1455
1556
1661
1772
1888
2009
2135
2266
2401
2542
2687
2837
2992
3151
-
BHP
0.89
0.96
1.03
1.10
1.19
1.27
1.36
1.46
1.56
1.67
1.78
1.90
2.03
2.16
2.29
2.43
2.58
2.73
2.88
3.04
3.21
3.38
-
RPM
1072
1085
1100
1116
1134
1154
1174
1196
1219
1243
1267
1293
1319
1346
1373
1401
1430
1459
1489
1519
1549
-
1.0
W
978
1040
1106
1176
1252
1331
1416
1506
1602
1702
1808
1919
2034
2155
2281
2412
2548
2689
2834
2984
3138
-
BHP
1.05
1.12
1.19
1.26
1.34
1.43
1.52
1.62
1.72
1.83
1.94
2.06
2.18
2.31
2.45
2.59
2.73
2.88
3.04
3.20
3.37
-
RPM
1224
1237
1252
1268
1286
1306
1327
1348
1371
1395
1419
1445
1471
1498
1525
1553
1582
1611
1641
-
1.4
W
1261
1323
1389
1459
1534
1614
1699
1789
1884
1985
2090
2201
2317
2438
2564
2695
2830
2971
3116
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
1.35
1303
1411
1.51
1384
1.42
1316
1473
1.58
1397
1.49
1331
1538
1.65
1412
1.57
1347
1609
1.73
1429
1.65
1365
1684
1.81
1447
1.73
1385
1764
1.89
1466
1.82
1405
1849
1.98
1487
1.92
1427
1939
2.08
1509
1532
2.02
1450
2034
2.18
1555
2.13
1474
2134
2.29
1498
2240
2.40
1580
2.24
2.36
1524
2351
2.52
1605
2.49
1550
2467
2.65
1632
2.62
1577
2588
2.78
1658
2.75
1604
2714
2.91
1686
2.89
1632
2844
3.05
1714
3.04
1661
2980
3.20
1742
3.19
1690
3121
3.35
3.34
-
1.8
W
1575
1637
1703
1773
1848
1928
2013
2103
2199
2299
2405
2515
2631
2752
2878
3009
3145
-
BHP
1.69
1.76
1.83
1.90
1.98
2.07
2.16
2.26
2.36
2.47
2.58
2.70
2.82
2.95
3.09
3.23
3.37
-
RPM
1469
1482
1497
1514
1532
1551
1572
1594
1617
1640
1665
1690
1717
1743
1771
1799
-
2.0
W
1762
1824
1889
1960
2035
2115
2200
2290
2385
2485
2591
2702
2818
2939
3065
3196
-
BHP
1.89
1.96
2.03
2.10
2.18
2.27
2.36
2.46
2.56
2.67
2.78
2.90
3.02
3.15
3.29
3.43
-
1. Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
Unitary Products Group
45
246824-YTG-D-0806
ZH102 (8.5 Ton)-Bottom Duct
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
RPM
679
683
688
694
701
709
718
727
737
748
759
770
782
794
806
818
831
844
857
870
883
896
910
923
937
950
964
977
-
0.2
W
202
265
326
388
450
514
580
650
724
801
883
970
1061
1158
1260
1367
1479
1597
1720
1849
1984
2124
2269
2420
2577
2739
2906
3079
-
RPM
937
941
946
952
959
967
976
986
995
1006
1017
1028
1040
1052
1064
1076
1089
1102
1115
1128
1141
-
1.2
W
1432
1495
1557
1618
1680
1744
1811
1881
1954
2032
2114
2200
2292
2388
2490
2597
2710
2828
2951
3080
3214
-
BHP
0.22
0.28
0.35
0.42
0.48
0.55
0.62
0.70
0.78
0.86
0.95
1.04
1.14
1.24
1.35
1.47
1.59
1.71
1.85
1.98
2.13
2.28
2.43
2.60
2.76
2.94
3.12
3.30
-
BHP
1.54
1.60
1.67
1.74
1.80
1.87
1.94
2.02
2.10
2.18
2.27
2.36
2.46
2.56
2.67
2.79
2.91
3.03
3.17
3.30
3.45
-
RPM
743
746
751
758
765
773
781
791
801
811
822
834
845
857
869
882
894
907
920
933
947
960
973
987
1000
1014
1027
-
RPM
977
981
986
992
999
1007
1016
1025
1035
1046
1057
1068
1080
1092
1104
1116
1129
1142
1155
-
0.4
W
453
516
577
638
701
765
831
901
975
1052
1134
1221
1312
1409
1511
1618
1730
1848
1971
2100
2235
2375
2520
2671
2828
2990
3157
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.49
799
700
0.75
849
0.55
803
763
0.82
853
0.62
808
825
0.89
858
0.68
814
886
0.95
864
0.75
821
949
1.02
872
0.82
829
1013
1.09
880
0.89
838
1079
1.16
888
0.97
847
1149
1.23
898
1.05
857
1223
1.31
908
1.13
868
1300
1.39
918
1.22
879
1382
1.48
929
1.31
890
1469
1.58
940
1.41
902
1560
1.67
952
1.51
914
1657
1.78
964
1.62
926
1758
1.89
976
1.74
938
1865
2.00
989
1001
1.86
951
1978
2.12
1014
1.98
964
2096
2.25
977
2219
2.38
1027
2.11
990
2348
2.52
1040
2.25
2.40
1003
2483
2.66
1053
2.55
1016
2623
2.81
1067
2.70
1030
2768
2.97
1080
2.87
1043
2919
3.13
1093
3.03
1057
3076
3.30
3.21
3.39
-
Available External Static Pressure - IWG1
1.4
1.6
W
BHP
RPM
W
1674
1.80
1016
1917
1737
1.86
1020
1980
1799
1.93
1025
2041
1860
2.00
1031
2103
1038
2165
1923
2.06
1046
2229
1987
2.13
1055
2296
2053
2.20
1064
2365
2123
2.28
2196
2.36
1074
2439
2274
2.44
1084
2516
2356
2.53
1095
2598
2442
2.62
1107
2685
2534
2.72
1118
2776
2631
2.82
1130
2873
2732
2.93
1143
2975
2839
3.05
1155
3082
2952
3.17
1168
3194
3070
3.29
3193
3.43
-
BHP
2.06
2.12
2.19
2.26
2.32
2.39
2.46
2.54
2.62
2.70
2.79
2.88
2.98
3.08
3.19
3.31
3.43
-
RPM
1055
1058
1063
1070
1077
1085
1093
1103
1113
1123
1134
1145
1157
1169
1181
-
0.8
W
946
1009
1070
1132
1194
1258
1325
1395
1468
1545
1627
1714
1805
1902
2004
2111
2223
2341
2465
2594
2728
2868
3014
3165
-
BHP
1.01
1.08
1.15
1.21
1.28
1.35
1.42
1.50
1.57
1.66
1.75
1.84
1.94
2.04
2.15
2.26
2.39
2.51
2.64
2.78
2.93
3.08
3.23
3.39
-
1.8
W
2160
2223
2285
2346
2408
2472
2539
2609
2682
2760
2842
2928
3020
3116
3218
-
BHP
2.32
2.39
2.45
2.52
2.58
2.65
2.72
2.80
2.88
2.96
3.05
3.14
3.24
3.34
3.45
-
RPM
895
899
904
910
917
925
934
943
953
964
975
986
998
1010
1022
1034
1047
1060
1073
1086
1099
1112
-
1.0
W
1190
1253
1314
1375
1438
1502
1568
1638
1712
1789
1871
1958
2049
2146
2248
2355
2467
2585
2708
2837
2972
3112
-
BHP
1.28
1.34
1.41
1.48
1.54
1.61
1.68
1.76
1.84
1.92
2.01
2.10
2.20
2.30
2.41
2.53
2.65
2.77
2.91
3.04
3.19
3.34
-
1. Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
46
Unitary Products Group
246824-YTG-D-0806
ZH120 (10 Ton)-Bottom Duct
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
RPM
679
683
688
694
701
709
718
727
737
748
759
770
782
794
806
818
831
844
857
870
883
896
910
923
937
950
964
977
-
0.2
W
202
265
326
388
450
514
580
650
724
801
883
970
1061
1158
1260
1367
1479
1597
1720
1849
1984
2124
2269
2420
2577
2739
2906
3079
-
RPM
937
941
946
952
959
967
976
986
995
1006
1017
1028
1040
1052
1064
1076
1089
1102
1115
1128
1141
-
1.2
W
1432
1495
1557
1618
1680
1744
1811
1881
1954
2032
2114
2200
2292
2388
2490
2597
2710
2828
2951
3080
3214
-
BHP
0.22
0.28
0.35
0.42
0.48
0.55
0.62
0.70
0.78
0.86
0.95
1.04
1.14
1.24
1.35
1.47
1.59
1.71
1.85
1.98
2.13
2.28
2.43
2.60
2.76
2.94
3.12
3.30
-
BHP
1.54
1.60
1.67
1.74
1.80
1.87
1.94
2.02
2.10
2.18
2.27
2.36
2.46
2.56
2.67
2.79
2.91
3.03
3.17
3.30
3.45
-
RPM
743
746
751
758
765
773
781
791
801
811
822
834
845
857
869
882
894
907
920
933
947
960
973
987
1000
1014
1027
-
RPM
977
981
986
992
999
1007
1016
1025
1035
1046
1057
1068
1080
1092
1104
1116
1129
1142
1155
-
0.4
W
453
516
577
638
701
765
831
901
975
1052
1134
1221
1312
1409
1511
1618
1730
1848
1971
2100
2235
2375
2520
2671
2828
2990
3157
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.49
799
700
0.75
849
0.55
803
763
0.82
853
0.62
808
825
0.89
858
0.68
814
886
0.95
864
0.75
821
949
1.02
872
0.82
829
1013
1.09
880
0.89
838
1079
1.16
888
0.97
847
1149
1.23
898
1.05
857
1223
1.31
908
1.13
868
1300
1.39
918
1.22
879
1382
1.48
929
1.31
890
1469
1.58
940
1.41
902
1560
1.67
952
1.51
914
1657
1.78
964
1.62
926
1758
1.89
976
1.74
938
1865
2.00
989
1001
1.86
951
1978
2.12
1014
1.98
964
2096
2.25
977
2219
2.38
1027
2.11
990
2348
2.52
1040
2.25
2.40
1003
2483
2.66
1053
2.55
1016
2623
2.81
1067
2.70
1030
2768
2.97
1080
2.87
1043
2919
3.13
1093
3.03
1057
3076
3.30
3.21
3.39
-
Available External Static Pressure - IWG1
1.4
1.6
W
BHP
RPM
W
1674
1.80
1016
1917
1737
1.86
1020
1980
1799
1.93
1025
2041
1860
2.00
1031
2103
1038
2165
1923
2.06
1046
2229
1987
2.13
1055
2296
2053
2.20
1064
2365
2123
2.28
2196
2.36
1074
2439
2274
2.44
1084
2516
2356
2.53
1095
2598
2442
2.62
1107
2685
2534
2.72
1118
2776
2631
2.82
1130
2873
2732
2.93
1143
2975
2839
3.05
1155
3082
2952
3.17
1168
3194
3070
3.29
3193
3.43
-
BHP
2.06
2.12
2.19
2.26
2.32
2.39
2.46
2.54
2.62
2.70
2.79
2.88
2.98
3.08
3.19
3.31
3.43
-
RPM
1055
1058
1063
1070
1077
1085
1093
1103
1113
1123
1134
1145
1157
1169
1181
-
0.8
W
946
1009
1070
1132
1194
1258
1325
1395
1468
1545
1627
1714
1805
1902
2004
2111
2223
2341
2465
2594
2728
2868
3014
3165
-
BHP
1.01
1.08
1.15
1.21
1.28
1.35
1.42
1.50
1.57
1.66
1.75
1.84
1.94
2.04
2.15
2.26
2.39
2.51
2.64
2.78
2.93
3.08
3.23
3.39
-
1.8
W
2160
2223
2285
2346
2408
2472
2539
2609
2682
2760
2842
2928
3020
3116
3218
-
BHP
2.32
2.39
2.45
2.52
2.58
2.65
2.72
2.80
2.88
2.96
3.05
3.14
3.24
3.34
3.45
-
RPM
895
899
904
910
917
925
934
943
953
964
975
986
998
1010
1022
1034
1047
1060
1073
1086
1099
1112
-
1.0
W
1190
1253
1314
1375
1438
1502
1568
1638
1712
1789
1871
1958
2049
2146
2248
2355
2467
2585
2708
2837
2972
3112
-
BHP
1.28
1.34
1.41
1.48
1.54
1.61
1.68
1.76
1.84
1.92
2.01
2.10
2.20
2.30
2.41
2.53
2.65
2.77
2.91
3.04
3.19
3.34
-
1. Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
Unitary Products Group
47
246824-YTG-D-0806
ZH150 (12.5 Ton)-Bottom Duct
Air Flow
(CFM)
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
Air Flow
(CFM)
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
RPM
782
794
806
818
831
844
857
870
883
896
910
923
937
950
964
977
991
1004
1018
1032
1045
1059
1072
1086
1099
1112
1126
-
0.2
W
1061
1158
1260
1367
1479
1597
1720
1849
1984
2124
2269
2420
2577
2739
2906
3079
3256
3440
3628
3822
4020
4224
4433
4647
4865
5089
5317
-
RPM
1040
1052
1064
1076
1089
1102
1115
1128
1141
1154
1168
1181
1195
1208
1222
1235
1249
1263
1276
1290
1303
-
1.2
W
2292
2388
2490
2597
2710
2828
2951
3080
3214
3354
3500
3651
3807
3969
4136
4309
4487
4670
4859
5052
5251
-
BHP
1.14
1.24
1.35
1.47
1.59
1.71
1.85
1.98
2.13
2.28
2.43
2.60
2.76
2.94
3.12
3.30
3.49
3.69
3.89
4.10
4.31
4.53
4.76
4.99
5.22
5.46
5.70
-
BHP
2.46
2.56
2.67
2.79
2.91
3.03
3.17
3.30
3.45
3.60
3.75
3.92
4.08
4.26
4.44
4.62
4.81
5.01
5.21
5.42
5.63
-
RPM
845
857
869
882
894
907
920
933
947
960
973
987
1000
1014
1027
1041
1054
1068
1082
1095
1109
1122
1136
1149
1163
1176
-
0.4
W
1312
1409
1511
1618
1730
1848
1971
2100
2235
2375
2520
2671
2828
2990
3157
3329
3507
3691
3879
4073
4271
4475
4684
4898
5116
5340
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
1.41
902
1560
1.67
952
1.51
914
1657
1.78
964
1.62
926
1758
1.89
976
1.74
938
1865
2.00
989
1.86
951
1978
2.12
1001
1.98
964
2096
2.25
1014
2.11
977
2219
2.38
1027
2.25
990
2348
2.52
1040
2.40
1003
2483
2.66
1053
2.55
1016
2623
2.81
1067
2.70
1030
2768
2.97
1080
2.87
1043
2919
3.13
1093
1107
3.03
1057
3076
3.30
1070
3237
3.47
1120
3.21
1084
3405
3.65
1134
3.39
3.57
1097
3577
3.84
1148
3.76
1111
3755
4.03
1161
3.96
1124
3939
4.23
1175
4.16
1138
4127
4.43
1188
4.37
1151
4321
4.64
1202
4.58
1165
4519
4.85
1215
4.80
1179
4723
5.07
1229
5.03
1192
4932
5.29
1242
5.25
1205
5146
5.52
5.49
1219
5364
5.75
5.73
-
0.8
W
1805
1902
2004
2111
2223
2341
2465
2594
2728
2868
3014
3165
3321
3483
3650
3823
4001
4184
4372
4566
4765
4969
5177
-
BHP
1.94
2.04
2.15
2.26
2.39
2.51
2.64
2.78
2.93
3.08
3.23
3.39
3.56
3.74
3.92
4.10
4.29
4.49
4.69
4.90
5.11
5.33
5.55
-
RPM
998
1010
1022
1034
1047
1060
1073
1086
1099
1112
1126
1139
1153
1166
1180
1193
1207
1220
1234
1248
1261
1275
-
1.0
W
2049
2146
2248
2355
2467
2585
2708
2837
2972
3112
3257
3408
3565
3727
3894
4066
4244
4428
4616
4810
5008
5212
-
BHP
2.20
2.30
2.41
2.53
2.65
2.77
2.91
3.04
3.19
3.34
3.49
3.66
3.82
4.00
4.18
4.36
4.55
4.75
4.95
5.16
5.37
5.59
-
RPM
1080
1092
1104
1116
1129
1142
1155
1168
1181
1194
1208
1221
1235
1248
1262
1275
1289
1302
1316
1330
-
1.4
W
2534
2631
2732
2839
2952
3070
3193
3322
3457
3597
3742
3893
4049
4211
4379
4551
4729
4912
5101
5295
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
2.72
1118
2776
2.98
1157
2.82
1130
2873
3.08
1169
2.93
1143
2975
3.19
1181
1194
3.05
1155
3082
3.31
1206
3.17
1168
3194
3.43
1180
3312
3.55
1219
3.29
1193
3436
3.69
1232
3.43
3.56
1206
3565
3.82
1245
3.71
1220
3699
3.97
1258
3.86
1233
3839
4.12
1272
4.01
1246
3984
4.27
1285
4.18
1260
4135
4.44
1299
4.34
1273
4292
4.60
1312
4.52
1287
4454
4.78
1326
4.70
1300
4621
4.96
1339
4.88
1314
4794
5.14
1353
5.07
1328
4972
5.33
1366
5.27
1341
5155
5.53
5.47
1355
5343
5.73
5.68
-
1.8
W
3020
3116
3218
3325
3438
3556
3679
3808
3942
4082
4228
4379
4535
4697
4864
5037
5215
-
BHP
3.24
3.34
3.45
3.57
3.69
3.81
3.95
4.09
4.23
4.38
4.54
4.70
4.87
5.04
5.22
5.40
5.59
-
RPM
1197
1209
1221
1234
1246
1259
1272
1285
1298
1312
1325
1339
1352
1366
1379
1393
-
2.0
W
3265
3361
3463
3570
3683
3801
3924
4053
4187
4327
4473
4624
4780
4942
5109
5282
-
BHP
3.50
3.61
3.72
3.83
3.95
4.08
4.21
4.35
4.49
4.64
4.80
4.96
5.13
5.30
5.48
5.67
-
1. Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
48
Unitary Products Group
246824-YTG-D-0806
XP078-150 Side Duct Application
XP078 (6.5 Ton)-Side Duct
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
RPM
751
763
776
790
804
819
835
852
869
887
906
925
945
965
987
1008
1030
1053
1076
1100
1124
0.2
W
204
264
327
393
463
537
614
695
780
870
963
1061
1162
1268
1377
1491
1608
1730
1855
1984
2116
RPM
1040
1052
1064
1078
1092
1108
1124
1140
1158
1176
1194
1214
1234
1254
-
1.2
W
999
1059
1123
1189
1259
1332
1409
1491
1576
1665
1759
1856
1958
2063
-
BHP
0.22
0.28
0.35
0.42
0.50
0.58
0.66
0.75
0.84
0.93
1.03
1.14
1.25
1.36
1.48
1.60
1.73
1.86
1.99
2.13
2.27
BHP
1.07
1.14
1.20
1.28
1.35
1.43
1.51
1.60
1.69
1.79
1.89
1.99
2.10
2.21
-
RPM
813
825
838
851
866
881
897
914
931
949
968
987
1007
1027
1048
1070
1092
1115
1138
-
0.4
W
402
462
525
591
661
735
812
893
978
1068
1161
1259
1360
1466
1575
1689
1806
1927
2053
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.43
872
576
0.62
929
0.50
884
636
0.68
941
0.56
897
699
0.75
954
0.63
910
766
0.82
968
0.71
925
836
0.90
982
0.79
940
909
0.98
997
0.87
956
986
1.06
1013
0.96
973
1068
1.15
1030
1.05
990
1153
1.24
1047
1.15
1008
1242
1.33
1065
1.25
1027
1335
1.43
1084
1.35
1046
1433
1.54
1103
1123
1.46
1066
1534
1.65
1086
1640
1.76
1143
1.57
1.69
1107
1750
1.88
1165
1.81
1129
1863
2.00
1186
1.94
1151
1981
2.12
1208
2.07
1174
2102
2.25
2.20
-
0.8
W
731
791
854
921
991
1064
1141
1223
1308
1397
1491
1588
1690
1795
1905
2018
2136
-
BHP
0.78
0.85
0.92
0.99
1.06
1.14
1.22
1.31
1.40
1.50
1.60
1.70
1.81
1.93
2.04
2.17
2.29
-
RPM
985
997
1010
1023
1038
1053
1069
1085
1103
1121
1139
1159
1179
1199
1220
-
1.0
W
871
931
994
1060
1130
1204
1281
1362
1447
1537
1630
1728
1829
1935
2044
-
RPM
1095
1106
1119
1133
1147
1162
1178
1195
1212
1230
1249
1268
1288
-
1.4
W
1120
1181
1244
1310
1380
1453
1530
1612
1697
1786
1880
1977
2079
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
1.20
1150
1238
1.33
1206
1.27
1162
1298
1.39
1218
1.33
1175
1362
1.46
1231
1.41
1188
1428
1.53
1245
1.48
1203
1498
1.61
1259
1274
1.56
1218
1571
1.69
1234
1648
1.77
1290
1.64
1.73
1250
1730
1.86
1307
1.82
1268
1815
1.95
1324
1.92
1286
1904
2.04
1342
2.02
1304
1998
2.14
1361
2.12
1324
2095
2.25
2.23
-
1.8
W
1357
1417
1480
1547
1616
1690
1767
1848
1934
2023
2116
-
BHP
1.46
1.52
1.59
1.66
1.73
1.81
1.90
1.98
2.07
2.17
2.27
-
RPM
1265
1276
1289
1303
1317
1332
1348
1365
1382
1400
-
2.0
W
1480
1541
1604
1670
1740
1813
1891
1972
2057
2147
-
BHP
0.93
1.00
1.07
1.14
1.21
1.29
1.37
1.46
1.55
1.65
1.75
1.85
1.96
2.08
2.19
-
BHP
1.59
1.65
1.72
1.79
1.87
1.95
2.03
2.12
2.21
2.30
-
1. Blower performance includes 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
Unitary Products Group
49
246824-YTG-D-0806
XP090 (7.5 Ton)-Side Duct
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
RPM
751
763
776
790
804
819
835
852
869
887
906
925
945
965
987
1008
1030
1053
1076
1100
1124
1148
1173
1199
1224
1251
1277
1304
0.2
W
204
264
327
393
463
537
614
695
780
870
963
1061
1162
1268
1377
1491
1608
1730
1855
1984
2116
2252
2392
2535
2682
2832
2986
3142
RPM
1040
1052
1064
1078
1092
1108
1124
1140
1158
1176
1194
1214
1234
1254
1275
1297
1319
1341
1364
1388
1412
1437
1462
-
1.2
W
999
1059
1123
1189
1259
1332
1409
1491
1576
1665
1759
1856
1958
2063
2173
2286
2404
2525
2650
2779
2911
3048
3187
-
BHP
0.22
0.28
0.35
0.42
0.50
0.58
0.66
0.75
0.84
0.93
1.03
1.14
1.25
1.36
1.48
1.60
1.73
1.86
1.99
2.13
2.27
2.42
2.57
2.72
2.88
3.04
3.20
3.37
BHP
1.07
1.14
1.20
1.28
1.35
1.43
1.51
1.60
1.69
1.79
1.89
1.99
2.10
2.21
2.33
2.45
2.58
2.71
2.84
2.98
3.12
3.27
3.42
-
RPM
813
825
838
851
866
881
897
914
931
949
968
987
1007
1027
1048
1070
1092
1115
1138
1161
1185
1210
1235
1260
1286
1312
1339
-
0.4
W
402
462
525
591
661
735
812
893
978
1068
1161
1259
1360
1466
1575
1689
1806
1927
2053
2181
2314
2450
2590
2733
2880
3030
3184
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.43
872
576
0.62
929
0.50
884
636
0.68
941
0.56
897
699
0.75
954
0.63
910
766
0.82
968
0.71
925
836
0.90
982
0.79
940
909
0.98
997
0.87
956
986
1.06
1013
0.96
973
1068
1.15
1030
1.05
990
1153
1.24
1047
1.15
1008
1242
1.33
1065
1.25
1027
1335
1.43
1084
1.35
1046
1433
1.54
1103
1.46
1066
1534
1.65
1123
1.57
1086
1640
1.76
1143
1.69
1107
1750
1.88
1165
1.81
1129
1863
2.00
1186
1.94
1151
1981
2.12
1208
1231
2.07
1174
2102
2.25
1197
2227
2.39
1254
2.20
2.34
1221
2356
2.53
1278
2.48
1245
2488
2.67
1302
2.63
1269
2625
2.82
1326
2.78
1294
2764
2.97
1351
2.93
1319
2908
3.12
1377
3.09
1345
3054
3.28
1402
3.25
1371
3204
3.44
3.42
-
0.8
W
731
791
854
921
991
1064
1141
1223
1308
1397
1491
1588
1690
1795
1905
2018
2136
2257
2382
2511
2643
2780
2919
3063
3209
-
BHP
0.78
0.85
0.92
0.99
1.06
1.14
1.22
1.31
1.40
1.50
1.60
1.70
1.81
1.93
2.04
2.17
2.29
2.42
2.56
2.69
2.84
2.98
3.13
3.29
3.44
-
RPM
985
997
1010
1023
1038
1053
1069
1085
1103
1121
1139
1159
1179
1199
1220
1242
1264
1286
1310
1333
1357
1382
1407
1432
-
1.0
W
871
931
994
1060
1130
1204
1281
1362
1447
1537
1630
1728
1829
1935
2044
2158
2275
2397
2522
2651
2783
2919
3059
3202
-
BHP
0.93
1.00
1.07
1.14
1.21
1.29
1.37
1.46
1.55
1.65
1.75
1.85
1.96
2.08
2.19
2.31
2.44
2.57
2.71
2.84
2.99
3.13
3.28
3.44
-
RPM
1095
1106
1119
1133
1147
1162
1178
1195
1212
1230
1249
1268
1288
1309
1330
1351
1374
1396
1419
1443
1467
1491
-
1.4
W
1120
1181
1244
1310
1380
1453
1530
1612
1697
1786
1880
1977
2079
2184
2294
2407
2525
2646
2771
2900
3033
3169
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
1.20
1150
1238
1.33
1206
1.27
1162
1298
1.39
1218
1.33
1175
1362
1.46
1231
1.41
1188
1428
1.53
1245
1.48
1203
1498
1.61
1259
1.56
1218
1571
1.69
1274
1.64
1234
1648
1.77
1290
1.73
1250
1730
1.86
1307
1.82
1268
1815
1.95
1324
1.92
1286
1904
2.04
1342
2.02
1304
1998
2.14
1361
2.12
1324
2095
2.25
1380
1344
2197
2.36
1400
2.23
2.34
1364
2302
2.47
1421
2.46
1385
2412
2.59
1442
2.58
1407
2525
2.71
1463
2.71
1429
2643
2.84
1485
2.84
1451
2764
2.97
1508
2.97
1475
2889
3.10
1531
3.11
1498
3018
3.24
1555
3.25
1522
3150
3.38
3.40
-
1.8
W
1357
1417
1480
1547
1616
1690
1767
1848
1934
2023
2116
2214
2315
2421
2530
2644
2761
2883
3008
3137
-
BHP
1.46
1.52
1.59
1.66
1.73
1.81
1.90
1.98
2.07
2.17
2.27
2.37
2.48
2.60
2.71
2.84
2.96
3.09
3.23
3.37
-
RPM
1265
1276
1289
1303
1317
1332
1348
1365
1382
1400
1419
1438
1458
1479
1500
1521
1544
1566
1589
-
2.0
W
1480
1541
1604
1670
1740
1813
1891
1972
2057
2147
2240
2337
2439
2544
2654
2768
2885
3006
3131
-
BHP
1.59
1.65
1.72
1.79
1.87
1.95
2.03
2.12
2.21
2.30
2.40
2.51
2.62
2.73
2.85
2.97
3.10
3.23
3.36
-
1. Blower performance includes 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
50
Unitary Products Group
246824-YTG-D-0806
XP102 (8.5 Ton)-Side Duct
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
RPM
644
649
654
659
664
670
675
680
686
692
699
706
713
720
728
736
745
754
763
773
783
794
805
816
828
840
852
865
879
892
906
0.2
W
194
250
302
351
398
445
493
541
591
643
698
756
818
882
951
1023
1099
1180
1264
1353
1447
1545
1647
1753
1864
1980
2100
2224
2353
2486
2623
RPM
883
888
893
898
904
909
914
920
925
932
938
945
952
959
967
975
984
993
1002
1012
1022
1033
1044
1055
1067
1079
1092
1105
-
1.2
W
1079
1135
1187
1236
1283
1330
1378
1426
1476
1529
1584
1642
1703
1767
1836
1908
1984
2065
2150
2239
2332
2430
2532
2638
2749
2865
2985
3109
-
BHP
0.21
0.27
0.32
0.38
0.43
0.48
0.53
0.58
0.63
0.69
0.75
0.81
0.88
0.95
1.02
1.10
1.18
1.27
1.36
1.45
1.55
1.66
1.77
1.88
2.00
2.12
2.25
2.39
2.52
2.67
2.81
BHP
1.16
1.22
1.27
1.33
1.38
1.43
1.48
1.53
1.58
1.64
1.70
1.76
1.83
1.90
1.97
2.05
2.13
2.22
2.31
2.40
2.50
2.61
2.72
2.83
2.95
3.07
3.20
3.34
-
RPM
695
701
706
711
716
721
726
732
738
744
750
757
764
772
779
788
796
805
815
824
835
845
856
868
879
891
904
917
930
944
958
0.4
W
389
445
497
546
593
640
688
736
786
839
894
952
1013
1077
1146
1218
1295
1375
1460
1549
1642
1740
1842
1948
2059
2175
2295
2419
2548
2681
2819
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.42
745
573
0.61
793
0.48
750
629
0.67
798
0.53
755
681
0.73
803
0.59
760
730
0.78
808
0.64
765
778
0.83
813
0.69
771
824
0.88
818
0.74
776
872
0.94
824
0.79
781
920
0.99
829
0.84
787
970
1.04
835
0.90
793
1023
1.10
841
0.96
800
1078
1.16
847
1.02
807
1136
1.22
854
1.09
814
1197
1.28
861
1.16
821
1262
1.35
869
1.23
829
1330
1.43
877
1.31
837
1402
1.50
885
1.39
846
1479
1.59
893
1.48
855
1559
1.67
902
1.57
864
1644
1.76
912
1.66
874
1733
1.86
922
1.76
884
1826
1.96
932
1.87
895
1924
2.06
942
953
1.98
906
2026
2.17
965
2.09
917
2133
2.29
929
2244
2.41
976
2.21
2.33
941
2359
2.53
989
2.46
953
2479
2.66
1001
2.60
966
2603
2.79
1014
2.73
980
2732
2.93
1027
2.88
993
2865
3.07
1041
3.02
1007
3003
3.22
1055
0.8
W
748
804
856
905
952
999
1047
1095
1145
1198
1253
1311
1372
1437
1505
1577
1654
1734
1819
1908
2001
2099
2201
2307
2419
2534
2654
2778
2907
3040
3178
BHP
0.80
0.86
0.92
0.97
1.02
1.07
1.12
1.18
1.23
1.28
1.34
1.41
1.47
1.54
1.61
1.69
1.77
1.86
1.95
2.05
2.15
2.25
2.36
2.48
2.59
2.72
2.85
2.98
3.12
3.26
3.41
RPM
839
844
849
854
859
864
870
875
881
887
893
900
907
915
923
931
939
948
958
968
978
988
999
1011
1022
1035
1047
1060
1073
1087
-
1.0
W
916
972
1024
1073
1120
1167
1215
1263
1313
1366
1421
1479
1540
1604
1673
1745
1822
1902
1987
2076
2169
2267
2369
2475
2586
2702
2822
2946
3075
3208
-
BHP
0.98
1.04
1.10
1.15
1.20
1.25
1.30
1.36
1.41
1.47
1.52
1.59
1.65
1.72
1.79
1.87
1.95
2.04
2.13
2.23
2.33
2.43
2.54
2.66
2.77
2.90
3.03
3.16
3.30
3.44
-
RPM
926
932
937
942
947
952
957
963
969
975
981
988
995
1003
1010
1019
1027
1036
1046
1055
1066
1076
1087
1098
1110
1122
1135
-
1.4
W
1239
1295
1347
1396
1443
1490
1538
1586
1636
1689
1744
1802
1863
1928
1996
2068
2145
2225
2310
2399
2492
2590
2692
2798
2910
3025
3145
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
1.33
969
1398
1.50
1010
1.39
974
1454
1.56
1015
1.44
979
1506
1.62
1020
1.50
984
1555
1.67
1025
1.55
989
1603
1.72
1030
1.60
994
1650
1.77
1036
1.65
1000
1697
1.82
1041
1.70
1005
1746
1.87
1047
1.76
1011
1796
1.93
1052
1.81
1017
1848
1.98
1058
1.87
1024
1903
2.04
1065
1.93
1030
1961
2.10
1072
1079
2.00
1037
2022
2.17
1086
2.07
1045
2087
2.24
1053
2155
2.31
1094
2.14
2.22
1061
2227
2.39
1102
1069
2304
2.47
1111
2.30
2.39
1078
2384
2.56
1120
2.48
1088
2469
2.65
1129
2.57
1098
2558
2.74
1139
2.67
1108
2651
2.84
1149
2.78
1118
2749
2.95
1160
2.89
1129
2851
3.06
1171
3.00
1141
2958
3.17
1182
3.12
1152
3069
3.29
3.25
1165
3184
3.42
3.37
-
1.8
W
1559
1615
1667
1716
1763
1810
1858
1906
1956
2008
2063
2121
2182
2247
2316
2388
2464
2545
2629
2718
2812
2909
3012
3118
-
BHP
1.67
1.73
1.79
1.84
1.89
1.94
1.99
2.04
2.10
2.15
2.21
2.28
2.34
2.41
2.48
2.56
2.64
2.73
2.82
2.92
3.02
3.12
3.23
3.35
-
RPM
1051
1056
1061
1066
1071
1076
1082
1087
1093
1099
1106
1112
1119
1127
1135
1143
1152
1161
1170
1180
1190
1200
1211
-
2.0
W
1722
1778
1830
1879
1927
1974
2021
2070
2120
2172
2227
2285
2346
2411
2479
2552
2628
2708
2793
2882
2975
3073
3175
-
BHP
1.85
1.91
1.96
2.02
2.07
2.12
2.17
2.22
2.27
2.33
2.39
2.45
2.52
2.59
2.66
2.74
2.82
2.91
3.00
3.09
3.19
3.30
3.41
-
1. Blower performance includes 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
Unitary Products Group
51
246824-YTG-D-0806
XP120 (10 Ton)-Side Duct
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
RPM
644
649
654
659
664
670
675
680
686
692
699
706
713
720
728
736
745
754
763
773
783
794
805
816
828
840
852
865
879
892
906
0.2
W
194
250
302
351
398
445
493
541
591
643
698
756
818
882
951
1023
1099
1180
1264
1353
1447
1545
1647
1753
1864
1980
2100
2224
2353
2486
2623
RPM
883
888
893
898
904
909
914
920
925
932
938
945
952
959
967
975
984
993
1002
1012
1022
1033
1044
1055
1067
1079
1092
1105
-
1.2
W
1079
1135
1187
1236
1283
1330
1378
1426
1476
1529
1584
1642
1703
1767
1836
1908
1984
2065
2150
2239
2332
2430
2532
2638
2749
2865
2985
3109
-
BHP
0.21
0.27
0.32
0.38
0.43
0.48
0.53
0.58
0.63
0.69
0.75
0.81
0.88
0.95
1.02
1.10
1.18
1.27
1.36
1.45
1.55
1.66
1.77
1.88
2.00
2.12
2.25
2.39
2.52
2.67
2.81
BHP
1.16
1.22
1.27
1.33
1.38
1.43
1.48
1.53
1.58
1.64
1.70
1.76
1.83
1.90
1.97
2.05
2.13
2.22
2.31
2.40
2.50
2.61
2.72
2.83
2.95
3.07
3.20
3.34
-
RPM
695
701
706
711
716
721
726
732
738
744
750
757
764
772
779
788
796
805
815
824
835
845
856
868
879
891
904
917
930
944
958
0.4
W
389
445
497
546
593
640
688
736
786
839
894
952
1013
1077
1146
1218
1295
1375
1460
1549
1642
1740
1842
1948
2059
2175
2295
2419
2548
2681
2819
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.42
745
573
0.61
793
0.48
750
629
0.67
798
0.53
755
681
0.73
803
0.59
760
730
0.78
808
0.64
765
778
0.83
813
0.69
771
824
0.88
818
0.74
776
872
0.94
824
0.79
781
920
0.99
829
0.84
787
970
1.04
835
0.90
793
1023
1.10
841
0.96
800
1078
1.16
847
1.02
807
1136
1.22
854
1.09
814
1197
1.28
861
1.16
821
1262
1.35
869
1.23
829
1330
1.43
877
1.31
837
1402
1.50
885
1.39
846
1479
1.59
893
1.48
855
1559
1.67
902
1.57
864
1644
1.76
912
1.66
874
1733
1.86
922
1.76
884
1826
1.96
932
1.87
895
1924
2.06
942
953
1.98
906
2026
2.17
965
2.09
917
2133
2.29
929
2244
2.41
976
2.21
2.33
941
2359
2.53
989
2.46
953
2479
2.66
1001
2.60
966
2603
2.79
1014
2.73
980
2732
2.93
1027
2.88
993
2865
3.07
1041
3.02
1007
3003
3.22
1055
0.8
W
748
804
856
905
952
999
1047
1095
1145
1198
1253
1311
1372
1437
1505
1577
1654
1734
1819
1908
2001
2099
2201
2307
2419
2534
2654
2778
2907
3040
3178
BHP
0.80
0.86
0.92
0.97
1.02
1.07
1.12
1.18
1.23
1.28
1.34
1.41
1.47
1.54
1.61
1.69
1.77
1.86
1.95
2.05
2.15
2.25
2.36
2.48
2.59
2.72
2.85
2.98
3.12
3.26
3.41
RPM
839
844
849
854
859
864
870
875
881
887
893
900
907
915
923
931
939
948
958
968
978
988
999
1011
1022
1035
1047
1060
1073
1087
-
1.0
W
916
972
1024
1073
1120
1167
1215
1263
1313
1366
1421
1479
1540
1604
1673
1745
1822
1902
1987
2076
2169
2267
2369
2475
2586
2702
2822
2946
3075
3208
-
BHP
0.98
1.04
1.10
1.15
1.20
1.25
1.30
1.36
1.41
1.47
1.52
1.59
1.65
1.72
1.79
1.87
1.95
2.04
2.13
2.23
2.33
2.43
2.54
2.66
2.77
2.90
3.03
3.16
3.30
3.44
-
RPM
926
932
937
942
947
952
957
963
969
975
981
988
995
1003
1010
1019
1027
1036
1046
1055
1066
1076
1087
1098
1110
1122
1135
-
1.4
W
1239
1295
1347
1396
1443
1490
1538
1586
1636
1689
1744
1802
1863
1928
1996
2068
2145
2225
2310
2399
2492
2590
2692
2798
2910
3025
3145
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
1.33
969
1398
1.50
1010
1.39
974
1454
1.56
1015
1.44
979
1506
1.62
1020
1.50
984
1555
1.67
1025
1.55
989
1603
1.72
1030
1.60
994
1650
1.77
1036
1.65
1000
1697
1.82
1041
1.70
1005
1746
1.87
1047
1.76
1011
1796
1.93
1052
1.81
1017
1848
1.98
1058
1.87
1024
1903
2.04
1065
1.93
1030
1961
2.10
1072
1079
2.00
1037
2022
2.17
1086
2.07
1045
2087
2.24
1053
2155
2.31
1094
2.14
2.22
1061
2227
2.39
1102
1069
2304
2.47
1111
2.30
2.39
1078
2384
2.56
1120
2.48
1088
2469
2.65
1129
2.57
1098
2558
2.74
1139
2.67
1108
2651
2.84
1149
2.78
1118
2749
2.95
1160
2.89
1129
2851
3.06
1171
3.00
1141
2958
3.17
1182
3.12
1152
3069
3.29
3.25
1165
3184
3.42
3.37
-
1.8
W
1559
1615
1667
1716
1763
1810
1858
1906
1956
2008
2063
2121
2182
2247
2316
2388
2464
2545
2629
2718
2812
2909
3012
3118
-
BHP
1.67
1.73
1.79
1.84
1.89
1.94
1.99
2.04
2.10
2.15
2.21
2.28
2.34
2.41
2.48
2.56
2.64
2.73
2.82
2.92
3.02
3.12
3.23
3.35
-
RPM
1051
1056
1061
1066
1071
1076
1082
1087
1093
1099
1106
1112
1119
1127
1135
1143
1152
1161
1170
1180
1190
1200
1211
-
2.0
W
1722
1778
1830
1879
1927
1974
2021
2070
2120
2172
2227
2285
2346
2411
2479
2552
2628
2708
2793
2882
2975
3073
3175
-
BHP
1.85
1.91
1.96
2.02
2.07
2.12
2.17
2.22
2.27
2.33
2.39
2.45
2.52
2.59
2.66
2.74
2.82
2.91
3.00
3.09
3.19
3.30
3.41
-
1. Blower performance includes 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
52
Unitary Products Group
246824-YTG-D-0806
XP150 (12.5 Ton)-Side Duct
Air Flow
(CFM)
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
Air Flow
(CFM)
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
RPM
713
720
728
736
745
754
763
773
783
794
805
816
828
840
852
865
879
892
906
921
936
951
966
982
999
1015
1032
1050
1067
1085
1103
0.2
W
818
882
951
1023
1099
1180
1264
1353
1447
1545
1647
1753
1864
1980
2100
2224
2353
2486
2623
2765
2911
3062
3216
3375
3538
3706
3877
4052
4232
4415
4602
RPM
952
959
967
975
984
993
1002
1012
1022
1033
1044
1055
1067
1079
1092
1105
1118
1132
1146
1160
1175
1190
1206
1222
1238
1254
1271
1289
1306
1324
-
1.2
W
1703
1767
1836
1908
1984
2065
2150
2239
2332
2430
2532
2638
2749
2865
2985
3109
3238
3371
3509
3650
3797
3947
4102
4261
4424
4591
4762
4937
5117
5300
-
BHP
0.88
0.95
1.02
1.10
1.18
1.27
1.36
1.45
1.55
1.66
1.77
1.88
2.00
2.12
2.25
2.39
2.52
2.67
2.81
2.97
3.12
3.28
3.45
3.62
3.80
3.98
4.16
4.35
4.54
4.74
4.94
BHP
1.83
1.90
1.97
2.05
2.13
2.22
2.31
2.40
2.50
2.61
2.72
2.83
2.95
3.07
3.20
3.34
3.47
3.62
3.76
3.92
4.07
4.23
4.40
4.57
4.75
4.93
5.11
5.30
5.49
5.69
-
RPM
764
772
779
788
796
805
815
824
835
845
856
868
879
891
904
917
930
944
958
972
987
1002
1018
1034
1050
1067
1084
1101
1119
1137
1155
0.4
W
1013
1077
1146
1218
1295
1375
1460
1549
1642
1740
1842
1948
2059
2175
2295
2419
2548
2681
2819
2960
3107
3257
3412
3571
3734
3901
4072
4247
4427
4610
4797
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
1.09
814
1197
1.28
861
1.16
821
1262
1.35
869
1.23
829
1330
1.43
877
1.31
837
1402
1.50
885
1.39
846
1479
1.59
893
1.48
855
1559
1.67
902
1.57
864
1644
1.76
912
1.66
874
1733
1.86
922
1.76
884
1826
1.96
932
1.87
895
1924
2.06
942
1.98
906
2026
2.17
953
2.09
917
2133
2.29
965
2.21
929
2244
2.41
976
2.33
941
2359
2.53
989
2.46
953
2479
2.66
1001
2.60
966
2603
2.79
1014
2.73
980
2732
2.93
1027
2.88
993
2865
3.07
1041
3.02
1007
3003
3.22
1055
1070
3.18
1022
3144
3.37
3.33
1037
3291
3.53
1084
3.49
1052
3441
3.69
1100
3.66
1067
3596
3.86
1115
3.83
1083
3755
4.03
1131
4.01
1100
3918
4.20
1147
4.18
1116
4085
4.38
1164
4.37
1133
4256
4.57
1181
4.56
1150
4432
4.75
1198
4.75
1168
4611
4.95
1216
4.95
1186
4794
5.14
1234
5.15
1204
4982
5.34
1252
0.8
W
1372
1437
1505
1577
1654
1734
1819
1908
2001
2099
2201
2307
2419
2534
2654
2778
2907
3040
3178
3319
3466
3616
3771
3930
4093
4260
4431
4607
4786
4969
5157
BHP
1.47
1.54
1.61
1.69
1.77
1.86
1.95
2.05
2.15
2.25
2.36
2.48
2.59
2.72
2.85
2.98
3.12
3.26
3.41
3.56
3.72
3.88
4.05
4.22
4.39
4.57
4.75
4.94
5.13
5.33
5.53
RPM
907
915
923
931
939
948
958
968
978
988
999
1011
1022
1035
1047
1060
1073
1087
1101
1116
1130
1146
1161
1177
1193
1210
1227
1244
1262
1280
1298
1.0
W
1540
1604
1673
1745
1822
1902
1987
2076
2169
2267
2369
2475
2586
2702
2822
2946
3075
3208
3346
3487
3634
3784
3939
4098
4261
4428
4599
4774
4954
5137
5324
BHP
1.65
1.72
1.79
1.87
1.95
2.04
2.13
2.23
2.33
2.43
2.54
2.66
2.77
2.90
3.03
3.16
3.30
3.44
3.59
3.74
3.90
4.06
4.23
4.40
4.57
4.75
4.93
5.12
5.31
5.51
5.71
RPM
995
1003
1010
1019
1027
1036
1046
1055
1066
1076
1087
1098
1110
1122
1135
1148
1161
1175
1189
1203
1218
1233
1249
1265
1281
1298
1315
1332
1350
-
1.4
W
1863
1928
1996
2068
2145
2225
2310
2399
2492
2590
2692
2798
2910
3025
3145
3269
3398
3531
3669
3810
3957
4107
4262
4421
4584
4751
4922
5098
5277
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
2.00
1037
2022
2.17
1079
2.07
1045
2087
2.24
1086
2.14
1053
2155
2.31
1094
2.22
1061
2227
2.39
1102
2.30
1069
2304
2.47
1111
2.39
1078
2384
2.56
1120
2.48
1088
2469
2.65
1129
2.57
1098
2558
2.74
1139
2.67
1108
2651
2.84
1149
2.78
1118
2749
2.95
1160
2.89
1129
2851
3.06
1171
3.00
1141
2958
3.17
1182
1194
3.12
1152
3069
3.29
1206
3.25
1165
3184
3.42
1177
3304
3.54
1219
3.37
3.51
1190
3428
3.68
1231
3.65
1203
3557
3.82
1245
3.79
1217
3690
3.96
1258
3.94
1231
3828
4.11
1273
4.09
1246
3970
4.26
1287
4.24
1260
4116
4.42
1302
4.41
1276
4266
4.58
1317
4.57
1291
4421
4.74
1333
4.74
1307
4580
4.91
1348
4.92
1323
4743
5.09
1365
5.10
1340
4910
5.27
1381
5.28
1357
5081
5.45
1398
5.47
1374
5257
5.64
5.66
-
1.8
W
2182
2247
2316
2388
2464
2545
2629
2718
2812
2909
3012
3118
3229
3345
3465
3589
3718
3851
3988
4130
4276
4427
4581
4740
4903
5071
5242
-
BHP
2.34
2.41
2.48
2.56
2.64
2.73
2.82
2.92
3.02
3.12
3.23
3.35
3.46
3.59
3.72
3.85
3.99
4.13
4.28
4.43
4.59
4.75
4.91
5.09
5.26
5.44
5.62
-
RPM
1119
1127
1135
1143
1152
1161
1170
1180
1190
1200
1211
1223
1235
1247
1259
1272
1285
1299
1313
1328
1343
1358
1373
1389
1405
1422
-
2.0
W
2346
2411
2479
2552
2628
2708
2793
2882
2975
3073
3175
3282
3393
3508
3628
3753
3881
4015
4152
4294
4440
4590
4745
4904
5067
5234
-
BHP
2.52
2.59
2.66
2.74
2.82
2.91
3.00
3.09
3.19
3.30
3.41
3.52
3.64
3.76
3.89
4.03
4.16
4.31
4.45
4.61
4.76
4.92
5.09
5.26
5.44
5.62
-
1. Blower performance includes 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
Unitary Products Group
53
246824-YTG-D-0806
XP078-150 Bottom Duct Application
XP078 (6.5 Ton)-Bottom Duct
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
RPM
775
788
803
820
838
857
878
900
923
946
971
996
1023
1049
1077
1105
1133
1163
1192
-
0.2
W
289
350
416
487
562
642
727
817
912
1012
1118
1229
1345
1466
1591
1722
1858
1999
2144
-
0.4
W
494
556
622
692
767
847
932
1022
1117
1218
1323
1434
1550
1671
1797
1928
2063
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.53
924
673
0.72
998
0.60
937
735
0.79
1011
0.67
952
800
0.86
1026
0.74
968
871
0.93
1042
0.82
986
946
1.01
1060
0.91
1006
1026
1.10
1080
1.00
1027
1111
1.19
1100
1.10
1048
1201
1.29
1122
1.20
1071
1296
1.39
1145
1.31
1095
1396
1.50
1169
1193
1.42
1119
1502
1.61
1145
1613
1.73
1219
1.54
1171
1729
1.85
1245
1.66
1.79
1198
1850
1.98
1272
1.93
1225
1976
2.12
1299
2.07
1253
2106
2.26
2.21
-
0.8
W
832
894
960
1030
1105
1185
1270
1360
1455
1556
1661
1772
1888
2009
2135
-
BHP
0.31
0.38
0.45
0.52
0.60
0.69
0.78
0.88
0.98
1.09
1.20
1.32
1.44
1.57
1.71
1.85
1.99
2.14
2.30
-
RPM
850
863
878
894
913
932
953
974
997
1021
1046
1071
1097
1124
1151
1179
1208
-
RPM
1.8
W
BHP
1384
1397
1412
1429
1447
1466
1487
1509
-
1575
1637
1703
1773
1848
1928
2013
2103
-
1.69
1.76
1.83
1.90
1.98
2.07
2.16
2.26
-
RPM
1.2
W
BHP
Available External Static Pressure - IWG1
1.4
1.6
RPM
W
BHP
RPM
W
BHP
1147
1160
1175
1192
1210
1229
1250
1272
1294
1318
1343
1368
-
1119
1181
1247
1317
1392
1472
1557
1647
1742
1843
1948
2059
-
1.20
1.27
1.34
1.41
1.49
1.58
1.67
1.77
1.87
1.98
2.09
2.21
-
1224
1237
1252
1268
1286
1306
1327
1348
1371
1395
1419
-
1261
1323
1389
1459
1534
1614
1699
1789
1884
1985
2090
-
1.35
1.42
1.49
1.57
1.65
1.73
1.82
1.92
2.02
2.13
2.24
-
1303
1316
1331
1347
1365
1385
1405
1427
1450
1474
-
1411
1473
1538
1609
1684
1764
1849
1939
2034
2134
-
1.51
1.58
1.65
1.73
1.81
1.89
1.98
2.08
2.18
2.29
-
BHP
0.89
0.96
1.03
1.10
1.19
1.27
1.36
1.46
1.56
1.67
1.78
1.90
2.03
2.16
2.29
-
RPM
1072
1085
1100
1116
1134
1154
1174
1196
1219
1243
1267
1293
1319
-
1.0
W
978
1040
1106
1176
1252
1331
1416
1506
1602
1702
1808
1919
2034
-
BHP
1.05
1.12
1.19
1.26
1.34
1.43
1.52
1.62
1.72
1.83
1.94
2.06
2.18
-
1. Blower performance includes 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
54
Unitary Products Group
246824-YTG-D-0806
XP090 (7.5 Ton)-Bottom Duct
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
Air Flow
(CFM)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
RPM
775
788
803
820
838
857
878
900
923
946
971
996
1023
1049
1077
1105
1133
1163
1192
1222
1253
1284
1315
1346
1378
-
0.2
W
289
350
416
487
562
642
727
817
912
1012
1118
1229
1345
1466
1591
1722
1858
1999
2144
2294
2448
2607
2771
2938
3110
-
RPM
1147
1160
1175
1192
1210
1229
1250
1272
1294
1318
1343
1368
1394
1421
1448
1476
1505
1534
1564
1594
-
1.2
W
1119
1181
1247
1317
1392
1472
1557
1647
1742
1843
1948
2059
2175
2296
2422
2553
2689
2829
2975
3124
-
BHP
0.31
0.38
0.45
0.52
0.60
0.69
0.78
0.88
0.98
1.09
1.20
1.32
1.44
1.57
1.71
1.85
1.99
2.14
2.30
2.46
2.63
2.80
2.97
3.15
3.34
-
BHP
1.20
1.27
1.34
1.41
1.49
1.58
1.67
1.77
1.87
1.98
2.09
2.21
2.33
2.46
2.60
2.74
2.88
3.04
3.19
3.35
-
RPM
850
863
878
894
913
932
953
974
997
1021
1046
1071
1097
1124
1151
1179
1208
1237
1267
1297
1327
1358
1389
1421
-
0.4
W
494
556
622
692
767
847
932
1022
1117
1218
1323
1434
1550
1671
1797
1928
2063
2204
2349
2499
2654
2813
2976
3144
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.53
924
673
0.72
998
0.60
937
735
0.79
1011
0.67
952
800
0.86
1026
0.74
968
871
0.93
1042
0.82
986
946
1.01
1060
0.91
1006
1026
1.10
1080
1.00
1027
1111
1.19
1100
1.10
1048
1201
1.29
1122
1.20
1071
1296
1.39
1145
1.31
1095
1396
1.50
1169
1.42
1119
1502
1.61
1193
1.54
1145
1613
1.73
1219
1.66
1171
1729
1.85
1245
1.79
1198
1850
1.98
1272
1.93
1225
1976
2.12
1299
1327
2.07
1253
2106
2.26
1282
2242
2.41
1356
2.21
2.36
1311
2383
2.56
1385
2.52
1341
2528
2.71
1414
2.68
1371
2678
2.87
1444
2.85
1401
2832
3.04
1475
3.02
1432
2991
3.21
1506
3.19
1463
3155
3.38
3.37
-
0.8
W
832
894
960
1030
1105
1185
1270
1360
1455
1556
1661
1772
1888
2009
2135
2266
2401
2542
2687
2837
2992
3151
-
BHP
0.89
0.96
1.03
1.10
1.19
1.27
1.36
1.46
1.56
1.67
1.78
1.90
2.03
2.16
2.29
2.43
2.58
2.73
2.88
3.04
3.21
3.38
-
RPM
1072
1085
1100
1116
1134
1154
1174
1196
1219
1243
1267
1293
1319
1346
1373
1401
1430
1459
1489
1519
1549
-
1.0
W
978
1040
1106
1176
1252
1331
1416
1506
1602
1702
1808
1919
2034
2155
2281
2412
2548
2689
2834
2984
3138
-
BHP
1.05
1.12
1.19
1.26
1.34
1.43
1.52
1.62
1.72
1.83
1.94
2.06
2.18
2.31
2.45
2.59
2.73
2.88
3.04
3.20
3.37
-
RPM
1224
1237
1252
1268
1286
1306
1327
1348
1371
1395
1419
1445
1471
1498
1525
1553
1582
1611
1641
-
1.4
W
1261
1323
1389
1459
1534
1614
1699
1789
1884
1985
2090
2201
2317
2438
2564
2695
2830
2971
3116
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
1.35
1303
1411
1.51
1384
1.42
1316
1473
1.58
1397
1.49
1331
1538
1.65
1412
1.57
1347
1609
1.73
1429
1.65
1365
1684
1.81
1447
1.73
1385
1764
1.89
1466
1.82
1405
1849
1.98
1487
1.92
1427
1939
2.08
1509
1532
2.02
1450
2034
2.18
1555
2.13
1474
2134
2.29
1498
2240
2.40
1580
2.24
2.36
1524
2351
2.52
1605
2.49
1550
2467
2.65
1632
2.62
1577
2588
2.78
1658
2.75
1604
2714
2.91
1686
2.89
1632
2844
3.05
1714
3.04
1661
2980
3.20
1742
3.19
1690
3121
3.35
3.34
-
1.8
W
1575
1637
1703
1773
1848
1928
2013
2103
2199
2299
2405
2515
2631
2752
2878
3009
3145
-
BHP
1.69
1.76
1.83
1.90
1.98
2.07
2.16
2.26
2.36
2.47
2.58
2.70
2.82
2.95
3.09
3.23
3.37
-
RPM
1469
1482
1497
1514
1532
1551
1572
1594
1617
1640
1665
1690
1717
1743
1771
1799
-
2.0
W
1762
1824
1889
1960
2035
2115
2200
2290
2385
2485
2591
2702
2818
2939
3065
3196
-
BHP
1.89
1.96
2.03
2.10
2.18
2.27
2.36
2.46
2.56
2.67
2.78
2.90
3.02
3.15
3.29
3.43
-
1. Blower performance includes 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
Unitary Products Group
55
246824-YTG-D-0806
XP102 (8.5 Ton)-Bottom Duct
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
RPM
679
683
688
694
701
709
718
727
737
748
759
770
782
794
806
818
831
844
857
870
883
896
910
923
937
950
964
977
-
0.2
W
202
265
326
388
450
514
580
650
724
801
883
970
1061
1158
1260
1367
1479
1597
1720
1849
1984
2124
2269
2420
2577
2739
2906
3079
-
RPM
937
941
946
952
959
967
976
986
995
1006
1017
1028
1040
1052
1064
1076
1089
1102
1115
1128
1141
-
1.2
W
1432
1495
1557
1618
1680
1744
1811
1881
1954
2032
2114
2200
2292
2388
2490
2597
2710
2828
2951
3080
3214
-
BHP
0.22
0.28
0.35
0.42
0.48
0.55
0.62
0.70
0.78
0.86
0.95
1.04
1.14
1.24
1.35
1.47
1.59
1.71
1.85
1.98
2.13
2.28
2.43
2.60
2.76
2.94
3.12
3.30
-
BHP
1.54
1.60
1.67
1.74
1.80
1.87
1.94
2.02
2.10
2.18
2.27
2.36
2.46
2.56
2.67
2.79
2.91
3.03
3.17
3.30
3.45
-
RPM
743
746
751
758
765
773
781
791
801
811
822
834
845
857
869
882
894
907
920
933
947
960
973
987
1000
1014
1027
-
RPM
977
981
986
992
999
1007
1016
1025
1035
1046
1057
1068
1080
1092
1104
1116
1129
1142
1155
-
0.4
W
453
516
577
638
701
765
831
901
975
1052
1134
1221
1312
1409
1511
1618
1730
1848
1971
2100
2235
2375
2520
2671
2828
2990
3157
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.49
799
700
0.75
849
0.55
803
763
0.82
853
0.62
808
825
0.89
858
0.68
814
886
0.95
864
0.75
821
949
1.02
872
0.82
829
1013
1.09
880
0.89
838
1079
1.16
888
0.97
847
1149
1.23
898
1.05
857
1223
1.31
908
1.13
868
1300
1.39
918
1.22
879
1382
1.48
929
1.31
890
1469
1.58
940
1.41
902
1560
1.67
952
1.51
914
1657
1.78
964
1.62
926
1758
1.89
976
1.74
938
1865
2.00
989
1001
1.86
951
1978
2.12
1014
1.98
964
2096
2.25
977
2219
2.38
1027
2.11
990
2348
2.52
1040
2.25
2.40
1003
2483
2.66
1053
2.55
1016
2623
2.81
1067
2.70
1030
2768
2.97
1080
2.87
1043
2919
3.13
1093
3.03
1057
3076
3.30
3.21
3.39
-
Available External Static Pressure - IWG1
1.4
1.6
W
BHP
RPM
W
1674
1.80
1016
1917
1737
1.86
1020
1980
1799
1.93
1025
2041
1860
2.00
1031
2103
1038
2165
1923
2.06
1046
2229
1987
2.13
1055
2296
2053
2.20
1064
2365
2123
2.28
2196
2.36
1074
2439
2274
2.44
1084
2516
2356
2.53
1095
2598
2442
2.62
1107
2685
2534
2.72
1118
2776
2631
2.82
1130
2873
2732
2.93
1143
2975
2839
3.05
1155
3082
2952
3.17
1168
3194
3070
3.29
3193
3.43
-
BHP
2.06
2.12
2.19
2.26
2.32
2.39
2.46
2.54
2.62
2.70
2.79
2.88
2.98
3.08
3.19
3.31
3.43
-
RPM
1055
1058
1063
1070
1077
1085
1093
1103
1113
1123
1134
1145
1157
1169
1181
-
0.8
W
946
1009
1070
1132
1194
1258
1325
1395
1468
1545
1627
1714
1805
1902
2004
2111
2223
2341
2465
2594
2728
2868
3014
3165
-
BHP
1.01
1.08
1.15
1.21
1.28
1.35
1.42
1.50
1.57
1.66
1.75
1.84
1.94
2.04
2.15
2.26
2.39
2.51
2.64
2.78
2.93
3.08
3.23
3.39
-
1.8
W
2160
2223
2285
2346
2408
2472
2539
2609
2682
2760
2842
2928
3020
3116
3218
-
BHP
2.32
2.39
2.45
2.52
2.58
2.65
2.72
2.80
2.88
2.96
3.05
3.14
3.24
3.34
3.45
-
RPM
895
899
904
910
917
925
934
943
953
964
975
986
998
1010
1022
1034
1047
1060
1073
1086
1099
1112
-
1.0
W
1190
1253
1314
1375
1438
1502
1568
1638
1712
1789
1871
1958
2049
2146
2248
2355
2467
2585
2708
2837
2972
3112
-
BHP
1.28
1.34
1.41
1.48
1.54
1.61
1.68
1.76
1.84
1.92
2.01
2.10
2.20
2.30
2.41
2.53
2.65
2.77
2.91
3.04
3.19
3.34
-
1. Blower performance includes 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
56
Unitary Products Group
246824-YTG-D-0806
XP120 (10 Ton)-Bottom Duct
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Air Flow
(CFM)
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
RPM
679
683
688
694
701
709
718
727
737
748
759
770
782
794
806
818
831
844
857
870
883
896
910
923
937
950
964
977
-
0.2
W
202
265
326
388
450
514
580
650
724
801
883
970
1061
1158
1260
1367
1479
1597
1720
1849
1984
2124
2269
2420
2577
2739
2906
3079
-
RPM
937
941
946
952
959
967
976
986
995
1006
1017
1028
1040
1052
1064
1076
1089
1102
1115
1128
1141
-
1.2
W
1432
1495
1557
1618
1680
1744
1811
1881
1954
2032
2114
2200
2292
2388
2490
2597
2710
2828
2951
3080
3214
-
BHP
0.22
0.28
0.35
0.42
0.48
0.55
0.62
0.70
0.78
0.86
0.95
1.04
1.14
1.24
1.35
1.47
1.59
1.71
1.85
1.98
2.13
2.28
2.43
2.60
2.76
2.94
3.12
3.30
-
BHP
1.54
1.60
1.67
1.74
1.80
1.87
1.94
2.02
2.10
2.18
2.27
2.36
2.46
2.56
2.67
2.79
2.91
3.03
3.17
3.30
3.45
-
RPM
743
746
751
758
765
773
781
791
801
811
822
834
845
857
869
882
894
907
920
933
947
960
973
987
1000
1014
1027
-
RPM
977
981
986
992
999
1007
1016
1025
1035
1046
1057
1068
1080
1092
1104
1116
1129
1142
1155
-
0.4
W
453
516
577
638
701
765
831
901
975
1052
1134
1221
1312
1409
1511
1618
1730
1848
1971
2100
2235
2375
2520
2671
2828
2990
3157
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
0.49
799
700
0.75
849
0.55
803
763
0.82
853
0.62
808
825
0.89
858
0.68
814
886
0.95
864
0.75
821
949
1.02
872
0.82
829
1013
1.09
880
0.89
838
1079
1.16
888
0.97
847
1149
1.23
898
1.05
857
1223
1.31
908
1.13
868
1300
1.39
918
1.22
879
1382
1.48
929
1.31
890
1469
1.58
940
1.41
902
1560
1.67
952
1.51
914
1657
1.78
964
1.62
926
1758
1.89
976
1.74
938
1865
2.00
989
1001
1.86
951
1978
2.12
1014
1.98
964
2096
2.25
977
2219
2.38
1027
2.11
990
2348
2.52
1040
2.25
2.40
1003
2483
2.66
1053
2.55
1016
2623
2.81
1067
2.70
1030
2768
2.97
1080
2.87
1043
2919
3.13
1093
3.03
1057
3076
3.30
3.21
3.39
-
Available External Static Pressure - IWG1
1.4
1.6
W
BHP
RPM
W
1674
1.80
1016
1917
1737
1.86
1020
1980
1799
1.93
1025
2041
1860
2.00
1031
2103
1038
2165
1923
2.06
1046
2229
1987
2.13
1055
2296
2053
2.20
1064
2365
2123
2.28
2196
2.36
1074
2439
2274
2.44
1084
2516
2356
2.53
1095
2598
2442
2.62
1107
2685
2534
2.72
1118
2776
2631
2.82
1130
2873
2732
2.93
1143
2975
2839
3.05
1155
3082
2952
3.17
1168
3194
3070
3.29
3193
3.43
-
BHP
2.06
2.12
2.19
2.26
2.32
2.39
2.46
2.54
2.62
2.70
2.79
2.88
2.98
3.08
3.19
3.31
3.43
-
RPM
1055
1058
1063
1070
1077
1085
1093
1103
1113
1123
1134
1145
1157
1169
1181
-
0.8
W
946
1009
1070
1132
1194
1258
1325
1395
1468
1545
1627
1714
1805
1902
2004
2111
2223
2341
2465
2594
2728
2868
3014
3165
-
BHP
1.01
1.08
1.15
1.21
1.28
1.35
1.42
1.50
1.57
1.66
1.75
1.84
1.94
2.04
2.15
2.26
2.39
2.51
2.64
2.78
2.93
3.08
3.23
3.39
-
1.8
W
2160
2223
2285
2346
2408
2472
2539
2609
2682
2760
2842
2928
3020
3116
3218
-
BHP
2.32
2.39
2.45
2.52
2.58
2.65
2.72
2.80
2.88
2.96
3.05
3.14
3.24
3.34
3.45
-
RPM
895
899
904
910
917
925
934
943
953
964
975
986
998
1010
1022
1034
1047
1060
1073
1086
1099
1112
-
1.0
W
1190
1253
1314
1375
1438
1502
1568
1638
1712
1789
1871
1958
2049
2146
2248
2355
2467
2585
2708
2837
2972
3112
-
BHP
1.28
1.34
1.41
1.48
1.54
1.61
1.68
1.76
1.84
1.92
2.01
2.10
2.20
2.30
2.41
2.53
2.65
2.77
2.91
3.04
3.19
3.34
-
1. Blower performance includes 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
Unitary Products Group
57
246824-YTG-D-0806
XP150 (12.5 Ton)-Bottom Duct
Air Flow
(CFM)
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
Air Flow
(CFM)
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
RPM
782
794
806
818
831
844
857
870
883
896
910
923
937
950
964
977
991
1004
1018
1032
1045
1059
1072
1086
1099
1112
1126
-
0.2
W
1061
1158
1260
1367
1479
1597
1720
1849
1984
2124
2269
2420
2577
2739
2906
3079
3256
3440
3628
3822
4020
4224
4433
4647
4865
5089
5317
-
RPM
1040
1052
1064
1076
1089
1102
1115
1128
1141
1154
1168
1181
1195
1208
1222
1235
1249
1263
1276
1290
1303
-
1.2
W
2292
2388
2490
2597
2710
2828
2951
3080
3214
3354
3500
3651
3807
3969
4136
4309
4487
4670
4859
5052
5251
-
BHP
1.14
1.24
1.35
1.47
1.59
1.71
1.85
1.98
2.13
2.28
2.43
2.60
2.76
2.94
3.12
3.30
3.49
3.69
3.89
4.10
4.31
4.53
4.76
4.99
5.22
5.46
5.70
-
BHP
2.46
2.56
2.67
2.79
2.91
3.03
3.17
3.30
3.45
3.60
3.75
3.92
4.08
4.26
4.44
4.62
4.81
5.01
5.21
5.42
5.63
-
RPM
845
857
869
882
894
907
920
933
947
960
973
987
1000
1014
1027
1041
1054
1068
1082
1095
1109
1122
1136
1149
1163
1176
-
0.4
W
1312
1409
1511
1618
1730
1848
1971
2100
2235
2375
2520
2671
2828
2990
3157
3329
3507
3691
3879
4073
4271
4475
4684
4898
5116
5340
-
Available External Static Pressure - IWG1
0.6
BHP
RPM
W
BHP
RPM
1.41
902
1560
1.67
952
1.51
914
1657
1.78
964
1.62
926
1758
1.89
976
1.74
938
1865
2.00
989
1.86
951
1978
2.12
1001
1.98
964
2096
2.25
1014
2.11
977
2219
2.38
1027
2.25
990
2348
2.52
1040
2.40
1003
2483
2.66
1053
2.55
1016
2623
2.81
1067
2.70
1030
2768
2.97
1080
2.87
1043
2919
3.13
1093
1107
3.03
1057
3076
3.30
1070
3237
3.47
1120
3.21
1084
3405
3.65
1134
3.39
3.57
1097
3577
3.84
1148
3.76
1111
3755
4.03
1161
3.96
1124
3939
4.23
1175
4.16
1138
4127
4.43
1188
4.37
1151
4321
4.64
1202
4.58
1165
4519
4.85
1215
4.80
1179
4723
5.07
1229
5.03
1192
4932
5.29
1242
5.25
1205
5146
5.52
5.49
1219
5364
5.75
5.73
-
0.8
W
1805
1902
2004
2111
2223
2341
2465
2594
2728
2868
3014
3165
3321
3483
3650
3823
4001
4184
4372
4566
4765
4969
5177
-
BHP
1.94
2.04
2.15
2.26
2.39
2.51
2.64
2.78
2.93
3.08
3.23
3.39
3.56
3.74
3.92
4.10
4.29
4.49
4.69
4.90
5.11
5.33
5.55
-
RPM
998
1010
1022
1034
1047
1060
1073
1086
1099
1112
1126
1139
1153
1166
1180
1193
1207
1220
1234
1248
1261
1275
-
1.0
W
2049
2146
2248
2355
2467
2585
2708
2837
2972
3112
3257
3408
3565
3727
3894
4066
4244
4428
4616
4810
5008
5212
-
BHP
2.20
2.30
2.41
2.53
2.65
2.77
2.91
3.04
3.19
3.34
3.49
3.66
3.82
4.00
4.18
4.36
4.55
4.75
4.95
5.16
5.37
5.59
-
RPM
1080
1092
1104
1116
1129
1142
1155
1168
1181
1194
1208
1221
1235
1248
1262
1275
1289
1302
1316
1330
-
1.4
W
2534
2631
2732
2839
2952
3070
3193
3322
3457
3597
3742
3893
4049
4211
4379
4551
4729
4912
5101
5295
-
Available External Static Pressure - IWG1
1.6
BHP
RPM
W
BHP
RPM
2.72
1118
2776
2.98
1157
2.82
1130
2873
3.08
1169
2.93
1143
2975
3.19
1181
1194
3.05
1155
3082
3.31
1206
3.17
1168
3194
3.43
1180
3312
3.55
1219
3.29
1193
3436
3.69
1232
3.43
3.56
1206
3565
3.82
1245
3.71
1220
3699
3.97
1258
3.86
1233
3839
4.12
1272
4.01
1246
3984
4.27
1285
4.18
1260
4135
4.44
1299
4.34
1273
4292
4.60
1312
4.52
1287
4454
4.78
1326
4.70
1300
4621
4.96
1339
4.88
1314
4794
5.14
1353
5.07
1328
4972
5.33
1366
5.27
1341
5155
5.53
5.47
1355
5343
5.73
5.68
-
1.8
W
3020
3116
3218
3325
3438
3556
3679
3808
3942
4082
4228
4379
4535
4697
4864
5037
5215
-
BHP
3.24
3.34
3.45
3.57
3.69
3.81
3.95
4.09
4.23
4.38
4.54
4.70
4.87
5.04
5.22
5.40
5.59
-
RPM
1197
1209
1221
1234
1246
1259
1272
1285
1298
1312
1325
1339
1352
1366
1379
1393
-
2.0
W
3265
3361
3463
3570
3683
3801
3924
4053
4187
4327
4473
4624
4780
4942
5109
5282
-
BHP
3.50
3.61
3.72
3.83
3.95
4.08
4.21
4.35
4.49
4.64
4.80
4.96
5.13
5.30
5.48
5.67
-
1. Blower performance includes 2" filters. See STATIC RESISTANCE table for additional applications.
High horsepower option required.
58
Unitary Products Group
246824-YTG-D-0806
Additional Static Resistance
Size
(Tons)
Model
078 (6.5)
090 (7.5)
ZH/XP
102 (8.5)
120 (10)
150 (12.5)
ZH/XP
CFM
Cooling Only1
Economizer2 3
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
0.00
-0.01
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
-0.09
-0.09
-0.10
-0.11
0.06
0.07
0.08
0.09
0.11
0.12
0.14
0.16
0.18
0.20
0.23
0.25
0.28
0.30
0.33
0.36
0.39
0.42
0.45
0.48
0.52
0.56
0.60
0.07
0.09
0.11
0.13
0.16
0.18
0.20
0.22
0.24
0.27
0.29
0.31
0.30
0.35
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
0.06
0.07
0.07
0.07
95
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
18
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
Electric Heat kW2
24
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.56
36
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
54
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.62
0.65
1. Add these values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Unitary Products Group
59
246824-YTG-D-0806
Altitude/Temperature Correction Factors
Air
Temp.
40
50
60
70
80
90
100
0
1.060
1.039
1.019
1.000
0.982
0.964
0.946
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
Altitude (Ft.)
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
&RUUHFWLRQ)DFWRU
6HD/HYHO
IW
IW
IW
IW
IW
IW
IW
IW
IW
IW
$LU7HPSHUDWXUHž)
60
Unitary Products Group
246824-YTG-D-0806
Gas Heat Minimum Supply Air
Supply Air (CFM)
Size
(Tons)
Model
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Heat Size
Cooling
10
15
10
15
10
15
15
20
15
20
ZH
ZH
ZH
ZH
ZH
Heating
Min
1950
1950
2250
2250
2550
2550
3000
3000
3750
3750
Max
3250
3250
3750
3750
4250
4250
5000
5000
6250
6250
Min
1950
1950
2250
2250
2550
2550
3000
3000
3750
3750
Max
3250
3250
3750
3750
4250
4250
5000
5000
6250
6250
9
1950
1950
1950
2250
2250
2250
2550
2550
2550
-
Minimum Supply Air (CFM)
Heater kW
18
24
36
1950
1950
1950
1950
1950
1950
1950
1950
1950
2250
2250
2250
2250
2250
2250
2250
2250
2250
2550
2550
2550
2550
2550
2550
2550
2550
2550
3000
3000
3000
3000
3000
3000
3000
3000
3000
3750
3750
3750
3750
3750
3750
3750
3750
3750
Electric Heat Minimum Supply Air
Size
(Tons)
Model
078
(6.5)
ZH/XP
090
(7.5)
ZH/XP
102
(8.5)
ZH/XP
120
(10)
ZH/XP
150
(12.5)
ZH/XP
Voltage
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
54
3500
3000
3500
4000
3750
3750
Indoor Blower Specifications
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Motor
Model
ZH/XP
ZH/XP
ZH/XP
ZH/XP
ZH/XP
HP
RPM
Eff.
SF
1-1/2
2
2
3
2
3
2
3
3
5
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.87
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
Motor Sheave
Blower Sheave
Datum Dia.
Datum Dia.
Frame
Bore (in.) Model
Bore (in.) Model
(in.)
(in.)
56
3.4 - 4.4
7/8
1VM50
7.0
1
AK74
56
3.4 - 4.4
7/8
1VM50
6.2
1
AK66
56
3.4 - 4.4
7/8
1VM50
6.5
1
AK69
56
3.4 - 4.4
7/8
1VM50
6.0
1
AK64
56
3.4 - 4.4
7/8
1VM50
8.5
1
AK89
56
3.4 - 4.4
7/8
1VM50
7.0
1
AK74
56
3.4 - 4.4
7/8
1VM50
8.0
1
AK84
56
3.4 - 4.4
7/8
1VM50
7.0
1
AK74
56
3.4 - 4.4
7/8
1VM50
7.0
1
AK74
184T
4.3 - 5.3
1-1/8
1VP56
6.7
1
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Power Exhaust Specifications
Model
Voltage
2PE04703225
2PE04703246
2PE04703258
208/230-1-60
460-1-60
575-1-60
HP
3/4
3/4
3/4
Motor
RPM1
1075
1075
1050
QTY
1
1
1
LRA
7.8
3.4
2.9
Motor
FLA
5
2.2
1.5
MCA
6.3
2.8
1.9
Fuse Size
10
5
4
CFM @
0.1 ESP
3800
3800
3800
1. Motors are multi-tapped and factory wired for high speed.
Unitary Products Group
61
246824-YTG-D-0806
Electric Heat Multipliers
Voltage
Nominal
kW Capacity Multipliers1
Applied
208
230
460
575
240
480
600
0.75
0.92
0.92
0.92
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Sound Performance
Indoor Sound Power Levels
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Model
CFM
ESP
(IWG)
Blower
RPM
BHP
Sound Rating1
dB (A)
63
Sound Power, dB (10-12) Watts
Octave Band Centerline Frequency (Hz)
125
250
500
1000
2000
4000
8000
ZH/XP
2600
0.6
812
1.14
74
71
73
73
71
69
65
65
60
ZH/XP
3000
0.6
854
1.47
77
74
76
76
74
72
68
68
63
ZH/XP
3400
0.6
872
1.65
80
77
79
79
77
75
71
71
66
ZH/XP
4000
0.6
959
2.29
83
80
82
82
80
78
74
74
69
ZH/XP
5000
0.6
1132
3.74
87
84
86
86
84
82
78
78
73
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.
Outdoor Sound Power Levels
ZH078-150
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Model
Sound Rating1
dB (A)
125
Octave Band Centerline Frequency (Hz)
250
500
1000
2000
4000
8000
ZH
83
88.0
82.5
81.5
78.0
73.0
69.0
62.0
ZH
83
89.5
83.5
82.0
78.0
72.5
68.0
60.5
ZH
90
93.5
92.5
88.0
84.5
79.0
74.5
68.0
ZH
90
94.0
92.0
88.5
84.5
80.0
75.5
68.5
ZH
84
90.0
84.5
81.5
77.5
72.0
68.5
61.5
XP
83
88.0
82.5
81.5
78.0
73.0
69.0
62.0
XP
83
89.5
83.5
82.0
78.0
72.5
68.0
60.5
XP
83
89.0
84.5
81.5
78.0
72.5
68.5
70.5
XP
83
89.5
83.5
81.0
78.0
72.0
68.5
70.5
XP
84
90.0
84.5
81.5
77.5
72.0
68.5
61.5
XP078-150
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
1. Rated in accordance with ARI 270 standard.
62
Unitary Products Group
246824-YTG-D-0806
Electrical Data
ZH078-150 Standard Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
12.8
95.0
20.0
1.5
6.2
5.5
0.0
230
12.8
95.0
20.0
1.5
6.2
5.5
0.0
460
6.4
45.0
10.0
0.8
3.1
2.2
0.0
575
5.4
38.0
8.5
0.6
2.4
1.8
0.0
208
14.7 115.0 23.0
1.5
8.2
5.5
0.0
230
14.7 115.0 23.0
1.5
8.2
5.5
0.0
460
7.7
50.0
12.0
0.8
4.1
2.2
0.0
575
6.4
40.0
10.0
0.6
3.6
1.8
0.0
208
16.0 120.0 25.0
3.5
8.2
5.5
0.0
230
16.0 120.0 25.0
3.5
8.2
5.5
0.0
460
8.3
60.0
13.0
1.6
4.1
2.2
0.0
575
6.7
40.0
10.5
1.3
3.6
1.8
0.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
Stages
Amps
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
38.0
38.0
54.6
70.2
96.2
38.0
38.0
61.9
79.9
110.0
19.1
19.1
30.9
40.0
55.0
15.8
15.8
24.7
31.9
43.9
44.3
44.3
57.1
72.7
98.7
44.3
44.3
64.4
82.4
112.5
23.0
23.0
32.2
41.2
56.2
19.2
19.2
26.2
33.4
45.4
51.2
51.2
57.1
72.7
98.7
51.2
51.2
64.4
82.4
112.5
26.0
26.0
32.2
41.2
56.2
21.3
21.3
26.2
33.4
45.4
43.5
43.5
61.5
77.1
103.1
43.5
43.5
68.8
86.8
116.9
21.3
21.3
33.7
42.7
57.7
17.6
17.6
26.9
34.1
46.1
49.8
49.8
64.0
79.6
105.6
49.8
49.8
71.3
89.3
119.4
25.2
25.2
34.9
44.0
59.0
21.0
21.0
28.4
35.6
47.6
56.7
56.7
64.0
79.6
105.6
56.7
56.7
71.3
89.3
119.4
28.2
28.2
34.9
44.0
59.0
23.1
23.1
28.4
35.6
47.6
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
50
50
50
50
60
70
80
80
100
110
50
50
50
50
70
70
80
90
110
125
25
25
25
25
35
35
40
45
60
60
20
20
20
20
25
30
35
35
45
50
50
60
50
60
60
70
80
80
100
110
50
60
50
60
70
80
90
90
125
125
30
30
30
30
35
35
45
45
60
60
25
25
25
25
30
30
35
40
50
50
60
70
60
70
60
70
80
80
100
110
60
70
60
70
70
80
90
90
125
125
30
35
30
35
35
35
45
45
60
60
25
25
25
25
30
30
35
40
50
50
63
246824-YTG-D-0806
ZH078-150 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
3.5
8.2
5.5
0.0
230
17.9 120.0 28.0
3.5
8.2
5.5
0.0
460
9.6
70.0
15.0
1.6
4.1
2.2
0.0
575
7.4
53.0
11.5
1.3
3.6
1.8
0.0
208
25.0 149.0 35.0
1.5
10.9
5.5
0.0
230
25.0 149.0 35.0
1.5
10.9
5.5
0.0
460
11.8
75.0
16.5
0.8
5.3
2.2
0.0
575
8.6
54.0
12.0
0.6
4.1
1.8
0.0
120
(10)
150
(12.5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
55.5
57.1
72.7
98.7
151.1
55.5
64.4
82.4
112.5
140.2
28.9
32.2
41.2
56.2
70.1
22.9
26.2
33.4
45.4
56.5
73.2
73.2
76.1
102.1
154.5
73.2
73.2
85.8
115.9
143.5
35.1
35.1
42.7
57.7
71.6
25.9
26.8
34.0
46.0
57.1
61.0
64.0
79.6
105.6
158.0
61.0
71.3
89.3
119.4
147.0
31.1
34.9
44.0
59.0
72.8
24.7
28.4
35.6
47.6
58.7
78.7
78.7
83.0
109.0
161.4
78.7
78.7
92.7
122.7
150.4
37.3
37.3
45.5
60.5
74.3
27.7
29.0
36.2
48.3
59.3
1
Model
kW
Stages
Amps
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
70
70
70
70
80
80
100
110
175
175
70
70
70
80
90
90
125
125
150
175
35
40
35
40
45
45
60
60
80
80
30
30
30
30
35
40
50
50
70
70
90
100
90
100
90
100
110
110
175
175
90
100
90
100
90
100
125
125
175
175
45
45
45
45
45
50
60
70
80
80
30
35
30
35
35
40
50
50
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
64
Unitary Products Group
246824-YTG-D-0806
ZH078-150 Alternate Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
12.8
95.0
20.0
1.5
8.2
5.5
0.0
230
12.8
95.0
20.0
1.5
8.2
5.5
0.0
460
6.4
45.0
10.0
0.8
4.1
2.2
0.0
575
5.4
38.0
8.5
0.6
3.6
1.8
0.0
208
14.7 115.0 23.0
1.5
10.9
5.5
0.0
230
14.7 115.0 23.0
1.5
10.9
5.5
0.0
460
7.7
50.0
12.0
0.8
5.3
2.2
0.0
575
6.4
40.0
10.0
0.6
4.1
1.8
0.0
208
16.0 120.0 25.0
3.5
10.9
5.5
0.0
230
16.0 120.0 25.0
3.5
10.9
5.5
0.0
460
8.3
60.0
13.0
1.6
5.3
2.2
0.0
575
6.7
40.0
10.5
1.3
4.1
1.8
0.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
40.0
40.0
57.1
72.7
98.7
40.0
40.0
64.4
82.4
112.5
20.1
20.1
32.2
41.2
56.2
17.0
17.0
26.2
33.4
45.4
47.0
47.0
60.5
76.1
102.1
47.0
47.0
67.8
85.8
115.9
24.2
24.2
33.7
42.7
57.7
19.7
19.7
26.8
34.0
46.0
53.9
53.9
60.5
76.1
102.1
53.9
53.9
67.8
85.8
115.9
27.2
27.2
33.7
42.7
57.7
21.8
21.8
26.8
34.0
46.0
45.5
45.5
64.0
79.6
105.6
45.5
45.5
71.3
89.3
119.4
22.3
22.3
34.9
44.0
59.0
18.8
18.8
28.4
35.6
47.6
52.5
52.5
67.3
83.0
109.0
52.5
52.5
74.6
92.7
122.7
26.4
26.4
36.4
45.5
60.5
21.5
21.5
29.0
36.2
48.3
59.4
59.4
67.3
83.0
109.0
59.4
59.4
74.6
92.7
122.7
29.4
29.4
36.4
45.5
60.5
23.6
23.6
29.0
36.2
48.3
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
50
50
50
60
70
80
80
100
110
50
50
50
50
70
80
90
90
125
125
25
25
25
25
35
35
45
45
60
60
20
20
20
20
30
30
35
40
50
50
60
60
60
60
70
70
80
90
110
110
60
60
60
60
70
80
90
100
125
125
30
30
30
30
35
40
45
50
60
70
25
25
25
25
30
30
35
40
50
50
60
70
60
70
70
70
80
90
110
110
60
70
60
70
70
80
90
100
125
125
35
35
35
35
35
40
45
50
60
70
25
30
25
30
30
30
35
40
50
50
65
246824-YTG-D-0806
ZH078-150 Alternate Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
3.5
10.9
5.5
0.0
230
17.9 120.0 28.0
3.5
10.9
5.5
0.0
460
9.6
70.0
15.0
1.6
5.3
2.2
0.0
575
7.4
53.0
11.5
1.3
4.1
1.8
0.0
208
25.0 149.0 35.0
1.5
16.1
5.5
0.0
230
25.0 149.0 35.0
1.5
16.1
5.5
0.0
460
11.8
75.0
16.5
0.8
8.1
2.2
0.0
575
8.6
54.0
12.0
0.6
6.0
1.8
0.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
58.2
60.5
76.1
102.1
154.5
58.2
67.8
85.8
115.9
143.5
30.1
33.7
42.7
57.7
71.6
23.4
26.8
34.0
46.0
57.1
78.4
78.4
82.6
108.6
161.0
78.4
78.4
92.3
122.4
150.0
37.9
37.9
46.2
61.2
75.1
27.8
29.2
36.4
48.4
59.5
63.7
67.3
83.0
109.0
161.4
63.7
74.6
92.7
122.7
150.4
32.3
36.4
45.5
60.5
74.3
25.2
29.0
36.2
48.3
59.3
83.9
83.9
89.5
115.5
167.9
83.9
83.9
99.2
129.2
156.9
40.1
40.1
49.0
64.0
77.8
29.6
31.4
38.6
50.6
61.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
70
80
80
90
110
110
175
175
70
80
70
80
90
100
125
125
175
175
35
40
35
40
45
50
60
70
80
80
30
30
30
30
35
40
50
50
70
70
100
100
100
100
100
100
110
125
175
175
100
100
100
100
100
100
125
150
175
175
45
50
45
50
50
50
70
70
90
90
35
35
35
35
40
40
50
60
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
66
Unitary Products Group
246824-YTG-D-0806
ZH078-150 Standard Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
12.8
95.0
20.0
1.5
6.2
5.5
10.0
230
12.8
95.0
20.0
1.5
6.2
5.5
10.0
460
6.4
45.0
10.0
0.8
3.1
2.2
5.0
575
5.4
38.0
8.5
0.6
2.4
1.8
4.0
208
14.7 115.0 23.0
1.5
8.2
5.5
10.0
230
14.7 115.0 23.0
1.5
8.2
5.5
10.0
460
7.7
50.0
12.0
0.8
4.1
2.2
5.0
575
6.4
40.0
10.0
0.6
3.6
1.8
4.0
208
16.0 120.0 25.0
3.5
8.2
5.5
10.0
230
16.0 120.0 25.0
3.5
8.2
5.5
10.0
460
8.3
60.0
13.0
1.6
4.1
2.2
5.0
575
6.7
40.0
10.5
1.3
3.6
1.8
4.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
48.0
48.0
67.1
82.7
108.7
48.0
48.0
74.4
92.4
122.5
24.1
24.1
37.2
46.2
61.2
19.8
19.8
29.7
36.9
48.9
54.3
54.3
69.6
85.2
111.2
54.3
54.3
76.9
94.9
125.0
28.0
28.0
38.4
47.5
62.5
23.2
23.2
31.2
38.4
50.4
61.2
61.2
69.6
85.2
111.2
61.2
61.2
76.9
94.9
125.0
31.0
31.0
38.4
47.5
62.5
25.3
25.3
31.2
38.4
50.4
53.5
53.5
74.0
89.6
115.6
53.5
54.2
81.3
99.3
129.4
26.3
26.4
39.9
49.0
64.0
21.6
21.6
31.9
39.1
51.1
59.8
59.8
76.5
92.1
118.1
59.8
59.8
83.8
101.8
131.9
30.2
30.2
41.2
50.2
65.2
25.0
25.0
33.4
40.6
52.6
66.7
66.7
76.5
92.1
118.1
66.7
66.7
83.8
101.8
131.9
33.2
33.2
41.2
50.2
65.2
27.1
27.1
33.4
40.6
52.6
Stages Amps
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
60
60
60
70
80
90
90
110
125
60
60
60
60
80
90
100
100
125
150
30
30
30
30
40
40
50
50
70
70
25
25
25
25
30
35
40
40
50
60
60
70
60
70
70
80
90
100
125
125
60
70
60
70
80
90
100
110
125
150
35
35
35
35
40
45
50
60
70
70
25
30
25
30
35
35
40
45
60
60
70
80
70
80
70
80
90
100
125
125
70
80
70
80
80
90
100
110
125
150
35
40
35
40
40
45
50
60
70
70
30
30
30
30
35
35
40
45
60
60
67
246824-YTG-D-0806
ZH078-150 Standard Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
3.5
8.2
5.5
10.0
230
17.9 120.0 28.0
3.5
8.2
5.5
10.0
460
9.6
70.0
15.0
1.6
4.1
2.2
5.0
575
7.4
53.0
11.5
1.3
3.6
1.8
4.0
208
25.0 149.0 35.0
1.5
10.9
5.5
10.0
230
25.0 149.0 35.0
1.5
10.9
5.5
10.0
460
11.8
75.0
16.5
0.8
5.3
2.2
5.0
575
8.6
54.0
12.0
0.6
4.1
1.8
4.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
65.5
69.6
85.2
111.2
163.6
65.5
76.9
94.9
125.0
152.7
33.9
38.4
47.5
62.5
76.3
26.9
31.2
38.4
50.4
61.5
83.2
83.2
88.6
114.6
167.0
83.2
83.2
98.3
128.4
156.0
40.1
40.1
49.0
64.0
77.8
29.9
31.8
39.0
51.0
62.1
71.0
76.5
92.1
118.1
170.5
71.0
83.8
101.8
131.9
159.5
36.1
41.2
50.2
65.2
79.1
28.7
33.4
40.6
52.6
63.7
88.7
88.7
95.5
121.5
173.9
88.7
88.7
105.2
135.2
162.9
42.3
42.7
51.7
66.7
80.6
31.7
34.0
41.2
53.3
64.3
1
Stages Amps
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
80
80
80
80
90
100
125
125
175
175
80
80
80
90
100
110
125
150
175
175
40
45
40
45
50
60
70
70
90
90
30
35
35
35
40
45
60
60
70
70
100
110
100
110
100
110
125
125
175
175
100
110
100
110
100
110
150
150
175
175
50
50
50
50
50
60
70
70
90
90
35
40
35
40
40
45
60
60
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
68
Unitary Products Group
246824-YTG-D-0806
ZH078-150 Alternate Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
12.8
95.0
20.0
1.5
8.2
5.5
10.0
230
12.8
95.0
20.0
1.5
8.2
5.5
10.0
460
6.4
45.0
10.0
0.8
4.1
2.2
5.0
575
5.4
38.0
8.5
0.6
3.6
1.8
4.0
208
14.7 115.0 23.0
1.5
10.9
5.5
10.0
230
14.7 115.0 23.0
1.5
10.9
5.5
10.0
460
7.7
50.0
12.0
0.8
5.3
2.2
5.0
575
6.4
40.0
10.0
0.6
4.1
1.8
4.0
208
16.0 120.0 25.0
3.5
10.9
5.5
10.0
230
16.0 120.0 25.0
3.5
10.9
5.5
10.0
460
8.3
60.0
13.0
1.6
5.3
2.2
5.0
575
6.7
40.0
10.5
1.3
4.1
1.8
4.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
50.0
50.0
69.6
85.2
111.2
50.0
50.0
76.9
94.9
125.0
25.1
25.1
38.4
47.5
62.5
21.0
21.0
31.2
38.4
50.4
57.0
57.0
73.0
88.6
114.6
57.0
57.0
80.3
98.3
128.4
29.2
29.2
39.9
49.0
64.0
23.7
23.7
31.8
39.0
51.0
63.9
63.9
73.0
88.6
114.6
63.9
63.9
80.3
98.3
128.4
32.2
32.2
39.9
49.0
64.0
25.8
25.8
31.8
39.0
51.0
55.5
55.5
76.5
92.1
118.1
55.5
56.7
83.8
101.8
131.9
27.3
27.7
41.2
50.2
65.2
22.8
22.8
33.4
40.6
52.6
62.5
62.5
79.8
95.5
121.5
62.5
62.5
87.1
105.2
135.2
31.4
31.4
42.7
51.7
66.7
25.5
25.5
34.0
41.2
53.3
69.4
69.4
79.8
95.5
121.5
69.4
69.4
87.1
105.2
135.2
34.4
34.4
42.7
51.7
66.7
27.6
27.6
34.0
41.2
53.3
Stages Amps
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
60
60
60
70
80
90
100
125
125
60
60
60
60
80
90
100
110
125
150
30
30
30
30
40
45
50
60
70
70
25
25
25
25
35
35
40
45
60
60
70
70
70
70
80
80
90
100
125
125
70
70
70
70
90
90
100
110
150
150
35
35
35
35
40
45
50
60
70
70
30
30
30
30
35
35
40
45
60
60
70
80
70
80
80
80
90
100
125
125
70
80
70
80
90
90
100
110
150
150
40
40
40
40
40
45
50
60
70
70
30
30
30
30
35
35
40
45
60
60
69
246824-YTG-D-0806
ZH078-150 Alternate Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
3.5
10.9
5.5
10.0
230
17.9 120.0 28.0
3.5
10.9
5.5
10.0
460
9.6
70.0
15.0
1.6
5.3
2.2
5.0
575
7.4
53.0
11.5
1.3
4.1
1.8
4.0
208
25.0 149.0 35.0
1.5
16.1
5.5
10.0
230
25.0 149.0 35.0
1.5
16.1
5.5
10.0
460
11.8
75.0
16.5
0.8
8.1
2.2
5.0
575
8.6
54.0
12.0
0.6
6.0
1.8
4.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
68.2
73.0
88.6
114.6
167.0
68.2
80.3
98.3
128.4
156.0
35.1
39.9
49.0
64.0
77.8
27.4
31.8
39.0
51.0
62.1
88.4
88.4
95.1
121.1
173.5
88.4
88.4
104.8
134.9
162.5
42.9
43.4
52.5
67.5
81.3
31.8
34.2
41.4
53.4
64.5
73.7
79.8
95.5
121.5
173.9
73.7
87.1
105.2
135.2
162.9
37.3
42.7
51.7
66.7
80.6
29.2
34.0
41.2
53.3
64.3
93.9
93.9
102.0
128.0
180.4
93.9
93.9
111.7
141.7
169.4
45.1
46.2
55.2
70.2
84.1
33.6
36.4
43.6
55.6
66.7
1
Stages Amps
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
80
90
80
90
90
100
125
125
175
175
80
90
90
90
100
110
150
150
175
175
40
45
40
45
50
60
70
70
90
90
30
35
35
35
40
45
60
60
70
70
110
110
110
110
110
110
125
150
175
200
110
110
110
110
110
125
150
150
175
175
50
50
50
50
60
60
70
80
90
90
40
40
40
40
45
45
60
60
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
70
Unitary Products Group
246824-YTG-D-0806
XP078-150 Standard Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
6.2
5.5
0.0
230
14.1
95.0
22.0
1.5
6.2
5.5
0.0
460
6.4
45.0
10.0
0.8
3.1
2.2
0.0
575
5.4
38.0
8.5
0.6
2.4
1.8
0.0
208
15.6
83.1
21.4
1.5
8.2
5.5
0.0
230
15.6
83.1
21.4
1.5
8.2
5.5
0.0
460
6.9
41.0
9.7
0.8
4.1
2.2
0.0
575
5.4
33.0
7.5
0.6
3.6
1.8
0.0
208
16.7 120.0 26.0
1.5
8.2
5.5
0.0
230
16.7 120.0 26.0
1.5
8.2
5.5
0.0
460
8.7
60.0
13.5
0.8
4.1
2.2
0.0
575
6.7
42.0
10.5
0.6
3.6
1.8
0.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
Stages
Amps
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
40.9
64.5
87.8
103.4
129.4
40.9
68.0
95.1
113.1
143.2
19.1
32.6
46.2
55.2
70.2
15.8
26.6
37.4
44.6
56.6
46.3
69.9
93.1
108.8
134.8
46.3
73.4
100.4
118.5
148.5
21.2
34.8
48.3
57.3
72.3
17.0
27.8
38.6
45.8
57.8
48.8
72.4
95.6
111.2
137.3
48.8
75.8
102.9
120.9
151.0
25.3
38.8
52.3
61.4
76.4
19.9
30.7
41.5
48.7
60.8
46.4
70.0
93.3
108.9
134.9
46.4
73.5
100.6
118.6
148.7
21.3
34.8
48.4
57.4
72.4
17.6
28.4
39.2
46.4
58.4
51.8
75.4
98.6
114.3
140.3
51.8
78.9
105.9
124.0
154.0
23.4
37.0
50.5
59.5
74.5
18.8
29.6
40.4
47.6
59.6
54.3
77.9
101.1
116.7
142.8
54.3
81.3
108.4
126.4
156.5
27.5
41.0
54.5
63.6
78.6
21.7
32.5
43.3
50.5
62.6
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
50
60
70
70
90
100
110
110
150
150
50
60
70
80
100
110
125
125
150
150
25
25
35
35
50
50
60
60
80
80
20
20
30
30
40
40
45
50
60
60
60
60
80
80
100
100
110
125
150
150
60
60
80
80
110
110
125
125
150
175
25
30
35
40
50
60
60
60
80
80
20
20
30
30
40
45
50
50
60
60
60
70
80
80
100
110
125
125
150
150
60
70
80
90
110
110
125
150
175
175
30
35
40
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
71
246824-YTG-D-0806
XP078-150 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
1.5
8.2
5.5
0.0
230
17.9 120.0 28.0
1.5
8.2
5.5
0.0
460
9.6
70.0
15.0
0.8
4.1
2.2
0.0
575
7.4
53.0
11.5
0.6
3.6
1.8
0.0
208
23.1 160.0 36.0
1.5
10.9
5.5
0.0
230
23.1 160.0 36.0
1.5
10.9
5.5
0.0
460
12.2
87.0
19.0
0.8
5.3
2.2
0.0
575
8.7
62.0
13.5
0.6
4.1
1.8
0.0
120
(10)
150
(12.5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
51.5
98.3
113.9
140.0
151.1
51.5
105.6
123.6
153.7
153.7
27.3
54.4
63.4
78.4
78.4
21.5
43.1
50.3
62.3
62.3
68.9
115.7
131.3
157.4
157.4
68.9
123.0
141.0
171.1
171.1
36.0
63.0
72.0
87.1
87.1
26.1
47.7
54.9
67.0
67.0
57.0
103.8
119.4
145.5
158.0
57.0
111.1
129.1
159.2
159.2
29.5
56.6
65.6
80.6
80.6
23.3
44.9
52.1
64.1
64.1
74.4
121.2
136.8
162.9
162.9
74.4
128.5
146.5
176.6
176.6
38.2
65.2
74.2
89.3
89.3
27.9
49.5
56.7
68.8
68.8
1
Model
kW
Stages
Amps
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
60
70
100
110
125
125
150
150
175
175
60
70
110
125
125
150
175
175
175
175
35
35
60
60
70
70
80
90
80
90
25
30
45
45
60
60
70
70
70
70
90
90
125
125
150
150
175
175
175
175
90
90
125
150
150
150
175
200
175
200
45
50
70
70
80
80
90
90
90
90
30
35
50
50
60
60
70
70
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
72
Unitary Products Group
246824-YTG-D-0806
XP078-150 Alternate Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
8.2
5.5
0.0
230
14.1
95.0
22.0
1.5
8.2
5.5
0.0
460
6.4
45.0
10.0
0.8
4.1
2.2
0.0
575
5.4
38.0
8.5
0.6
3.6
1.8
0.0
208
15.6
83.1
21.4
1.5
10.9
5.5
0.0
230
15.6
83.1
21.4
1.5
10.9
5.5
0.0
460
6.9
41.0
9.7
0.8
5.3
2.2
0.0
575
5.4
33.0
7.5
0.6
4.1
1.8
0.0
208
16.7 120.0 26.0
1.5
10.9
5.5
0.0
230
16.7 120.0 26.0
1.5
10.9
5.5
0.0
460
8.7
60.0
13.5
0.8
5.3
2.2
0.0
575
6.7
42.0
10.5
0.6
4.1
1.8
0.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
42.9
66.5
89.8
105.4
131.4
42.9
70.0
97.1
115.1
145.2
20.1
33.6
47.2
56.2
71.2
17.0
27.8
38.6
45.8
57.8
49.0
72.6
95.8
111.5
137.5
49.0
76.1
103.1
121.2
151.2
22.4
36.0
49.5
58.5
73.5
17.5
28.3
39.1
46.3
58.3
51.5
75.1
98.3
113.9
140.0
51.5
78.5
105.6
123.6
153.7
26.5
40.0
53.5
62.6
77.6
20.4
31.2
42.0
49.2
61.3
48.4
72.0
95.3
110.9
136.9
48.4
75.5
102.6
120.6
150.7
22.3
35.8
49.4
58.4
73.4
18.8
29.6
40.4
47.6
59.6
54.5
78.1
101.3
117.0
143.0
54.5
81.6
108.6
126.7
156.7
24.6
38.2
51.7
60.7
75.7
19.3
30.1
40.9
48.1
60.1
57.0
80.6
103.8
119.4
145.5
57.0
84.0
111.1
129.1
159.2
28.7
42.2
55.7
64.8
79.8
22.2
33.0
43.8
51.0
63.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
60
70
80
90
100
110
125
150
150
50
60
70
80
100
110
125
125
150
175
25
25
35
40
50
50
60
60
80
80
20
20
30
30
40
45
50
50
60
60
60
70
80
80
100
110
125
125
150
150
60
70
80
90
110
110
125
150
175
175
25
30
40
40
50
60
60
70
80
80
20
20
30
35
40
45
50
50
60
70
60
70
80
90
100
110
125
125
150
150
60
70
80
90
110
125
125
150
175
175
35
35
45
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
73
246824-YTG-D-0806
XP078-150 Alternate Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
1.5
10.9
5.5
0.0
230
17.9 120.0 28.0
1.5
10.9
5.5
0.0
460
9.6
70.0
15.0
0.8
5.3
2.2
0.0
575
7.4
53.0
11.5
0.6
4.1
1.8
0.0
208
23.1 160.0 36.0
1.5
16.1
5.5
0.0
230
23.1 160.0 36.0
1.5
16.1
5.5
0.0
460
12.2
87.0
19.0
0.8
8.1
2.2
0.0
575
8.7
62.0
13.5
0.6
6.0
1.8
0.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
54.2
101.0
116.6
142.7
154.5
54.2
108.3
126.3
156.4
156.4
28.5
55.6
64.6
79.6
79.6
22.0
43.6
50.8
62.8
62.8
74.1
120.9
136.5
162.6
162.6
74.1
128.2
146.2
176.3
176.3
38.8
65.8
74.8
89.9
89.9
28.0
49.6
56.8
68.9
68.9
59.7
106.5
122.1
148.2
161.4
59.7
113.8
131.8
161.9
161.9
30.7
57.8
66.8
81.8
81.8
23.8
45.4
52.6
64.6
64.6
79.6
126.4
142.0
168.1
168.1
79.6
133.7
151.7
181.8
181.8
41.0
68.0
77.0
92.1
92.1
29.8
51.4
58.6
70.7
70.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
70
110
110
125
125
150
150
175
175
70
70
110
125
150
150
175
175
175
175
35
40
60
60
70
70
80
90
80
90
25
30
45
50
60
60
70
70
70
70
90
100
125
150
150
150
175
175
175
175
90
100
150
150
150
175
200
200
200
200
50
50
70
70
80
80
90
100
90
100
35
35
50
60
60
60
70
80
70
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
74
Unitary Products Group
246824-YTG-D-0806
XP078-150 Standard Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
6.2
5.5
10.0
230
14.1
95.0
22.0
1.5
6.2
5.5
10.0
460
6.4
45.0
10.0
0.8
3.1
2.2
5.0
575
5.4
38.0
8.5
0.6
2.4
1.8
4.0
208
15.6
83.1
21.4
1.5
8.2
5.5
10.0
230
15.6
83.1
21.4
1.5
8.2
5.5
10.0
460
6.9
41.0
9.7
0.8
4.1
2.2
5.0
575
5.4
33.0
7.5
0.6
3.6
1.8
4.0
208
16.7 120.0 26.0
1.5
8.2
5.5
10.0
230
16.7 120.0 26.0
1.5
8.2
5.5
10.0
460
8.7
60.0
13.5
0.8
4.1
2.2
5.0
575
6.7
42.0
10.5
0.6
3.6
1.8
4.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
50.9
74.5
97.8
113.4
139.4
50.9
78.0
105.1
123.1
153.2
24.1
37.6
51.2
60.2
75.2
19.8
30.6
41.4
48.6
60.6
56.3
79.9
103.1
118.8
144.8
56.3
83.4
110.4
128.5
158.5
26.2
39.8
53.3
62.3
77.3
21.0
31.8
42.6
49.8
61.8
58.8
82.4
105.6
121.2
147.3
58.8
85.8
112.9
130.9
161.0
30.3
43.8
57.3
66.4
81.4
23.9
34.7
45.5
52.7
64.8
56.4
80.0
103.3
118.9
144.9
56.4
83.5
110.6
128.6
158.7
26.3
39.8
53.4
62.4
77.4
21.6
32.4
43.2
50.4
62.4
61.8
85.4
108.6
124.3
150.3
61.8
88.9
115.9
134.0
164.0
28.4
42.0
55.5
64.5
79.5
22.8
33.6
44.4
51.6
63.6
64.3
87.9
111.1
126.7
152.8
64.3
91.3
118.4
136.4
166.5
32.5
46.0
59.5
68.6
83.6
25.7
36.5
47.3
54.5
66.6
Stages Amps
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
80
80
100
110
125
125
150
150
60
70
80
90
110
125
125
150
175
175
30
30
40
40
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
70
70
90
90
110
110
125
125
150
175
70
70
90
90
125
125
150
150
175
175
30
35
40
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
70
80
90
90
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
35
40
45
50
60
60
70
70
90
90
30
30
35
40
50
50
60
60
70
70
75
246824-YTG-D-0806
XP078-150 Standard Motor - With Powered Convenience Outlet(Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
1.5
8.2
5.5
10.0
230
17.9 120.0 28.0
1.5
8.2
5.5
10.0
460
9.6
70.0
15.0
0.8
4.1
2.2
5.0
575
7.4
53.0
11.5
0.6
3.6
1.8
4.0
208
23.1 160.0 36.0
1.5
10.9
5.5
10.0
230
23.1 160.0 36.0
1.5
10.9
5.5
10.0
460
12.2
87.0
19.0
0.8
5.3
2.2
5.0
575
8.7
62.0
13.5
0.6
4.1
1.8
4.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
61.5
108.3
123.9
150.0
163.6
61.5
115.6
133.6
163.7
163.7
32.3
59.4
68.4
83.4
83.4
25.5
47.1
54.3
66.3
66.3
78.9
125.7
141.3
167.4
167.4
78.9
133.0
151.0
181.1
181.1
41.0
68.0
77.0
92.1
92.1
30.1
51.7
58.9
71.0
71.0
67.0
113.8
129.4
155.5
170.5
67.0
121.1
139.1
169.2
169.2
34.5
61.6
70.6
85.6
85.6
27.3
48.9
56.1
68.1
68.1
84.4
131.2
146.8
172.9
173.9
84.4
138.5
156.5
186.6
186.6
43.2
70.2
79.2
94.3
94.3
31.9
53.5
60.7
72.8
72.8
1
Stages Amps
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
110
125
125
150
150
175
175
175
70
80
125
125
150
150
175
175
175
175
40
40
60
70
70
80
90
90
90
90
30
30
50
50
60
60
70
70
70
70
100
100
150
150
150
150
175
175
175
175
100
100
150
150
175
175
200
200
200
200
50
50
70
80
80
80
100
100
100
100
35
40
60
60
60
70
80
80
80
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
76
Unitary Products Group
246824-YTG-D-0806
XP078-150 Alternate Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
8.2
5.5
10.0
230
14.1
95.0
22.0
1.5
8.2
5.5
10.0
460
6.4
45.0
10.0
0.8
4.1
2.2
5.0
575
5.4
38.0
8.5
0.6
3.6
1.8
4.0
208
15.6
83.1
21.4
1.5
10.9
5.5
10.0
230
15.6
83.1
21.4
1.5
10.9
5.5
10.0
460
6.9
41.0
9.7
0.8
5.3
2.2
5.0
575
5.4
33.0
7.5
0.6
4.1
1.8
4.0
208
16.7 120.0 26.0
1.5
10.9
5.5
10.0
230
16.7 120.0 26.0
1.5
10.9
5.5
10.0
460
8.7
60.0
13.5
0.8
5.3
2.2
5.0
575
6.7
42.0
10.5
0.6
4.1
1.8
4.0
078
(6.5)
090
(7.5)
102
(8.5)
Unitary Products Group
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
6.8
13.5
18.0
25.5
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
–
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
52.9
76.5
99.8
115.4
141.4
52.9
80.0
107.1
125.1
155.2
25.1
38.6
52.2
61.2
76.2
21.0
31.8
42.6
49.8
61.8
59.0
82.6
105.8
121.5
147.5
59.0
86.1
113.1
131.2
161.2
27.4
41.0
54.5
63.5
78.5
21.5
32.3
43.1
50.3
62.3
61.5
85.1
108.3
123.9
150.0
61.5
88.5
115.6
133.6
163.7
31.5
45.0
58.5
67.6
82.6
24.4
35.2
46.0
53.2
65.3
58.4
82.0
105.3
120.9
146.9
58.4
85.5
112.6
130.6
160.7
27.3
40.8
54.4
63.4
78.4
22.8
33.6
44.4
51.6
63.6
64.5
88.1
111.3
127.0
153.0
64.5
91.6
118.6
136.7
166.7
29.6
43.2
56.7
65.7
80.7
23.3
34.1
44.9
52.1
64.1
67.0
90.6
113.8
129.4
155.5
67.0
94.0
121.1
139.1
169.2
33.7
47.2
60.7
69.8
84.8
26.2
37.0
47.8
55.0
67.1
Stages Amps
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
–
18.9
37.5
50.0
70.8
–
22.6
45.2
60.2
85.3
–
11.3
22.6
30.1
42.7
–
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
80
90
100
110
125
125
150
150
60
70
80
90
110
125
150
150
175
175
30
30
40
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
70
80
90
90
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
30
35
45
45
60
60
70
70
80
90
25
25
35
35
45
45
60
60
70
70
70
80
90
100
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
40
40
50
50
60
70
70
70
90
90
30
30
40
40
50
50
60
60
70
70
77
246824-YTG-D-0806
XP078-150 Alternate Motor - With Powered Convenience Outlet(Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
17.9 120.0 28.0
1.5
10.9
5.5
10.0
230
17.9 120.0 28.0
1.5
10.9
5.5
10.0
460
9.6
70.0
15.0
0.8
5.3
2.2
5.0
575
7.4
53.0
11.5
0.6
4.1
1.8
4.0
208
23.1 160.0 36.0
1.5
16.1
5.5
10.0
230
23.1 160.0 36.0
1.5
16.1
5.5
10.0
460
12.2
87.0
19.0
0.8
8.1
2.2
5.0
575
8.7
62.0
13.5
0.6
6.0
1.8
4.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
13.5
18.0
25.5
40.6
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
–
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
64.2
111.0
126.6
152.7
167.0
64.2
118.3
136.3
166.4
166.4
33.5
60.6
69.6
84.6
84.6
26.0
47.6
54.8
66.8
66.8
84.1
130.9
146.5
172.6
173.5
84.1
138.2
156.2
186.3
186.3
43.8
70.8
79.8
94.9
94.9
32.0
53.6
60.8
72.9
72.9
69.7
116.5
132.1
158.2
173.9
69.7
123.8
141.8
171.9
171.9
35.7
62.8
71.8
86.8
86.8
27.8
49.4
56.6
68.6
68.6
89.6
136.4
152.0
178.1
180.4
89.6
143.7
161.7
191.8
191.8
46.0
73.0
82.0
97.1
97.1
33.8
55.4
62.6
74.7
74.7
1
Stages Amps
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
–
37.5
50.0
70.8
112.7
–
45.2
60.2
85.3
135.6
–
22.6
30.1
42.7
67.8
–
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
80
80
125
125
150
150
175
175
175
175
80
80
125
125
150
150
175
175
175
175
40
45
70
70
70
80
90
90
90
90
30
35
50
50
60
60
70
70
70
70
100
110
150
150
150
175
175
200
175
200
100
110
150
150
175
175
200
200
200
200
50
50
80
80
80
90
100
100
100
100
40
40
60
60
70
70
80
80
80
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
78
Unitary Products Group
246824-YTG-D-0806
Weights and Dimensions
ZH/XP078-150 Unit Weights
Unit 4 Point Load Weight
Unit 6 Point Load Weight
FRONT
FRONT
LEFT
LEFT
B
B
A
A
D
C
C
E
F
D
Y
X
FRONT
LEFT
Size
Weight (lbs.)
Center of Gravity
Model
(Tons)
Shipping Operating
X
Y
078
ZH
905
900
38
23
(6.5)
090
ZH
925
920
38
23
(7.5)
102
ZH
1140
1135
38
25.5
(8.5)
120
ZH
1140
1135
38
25.5
(10)
150
ZH
1405
1400
51
25.5
(12.5)
078
XP
925
920
38
23
(6.5)
090
XP
925
920
38
23
(7.5)
102
XP
1140
1135
38
25.5
(8.5)
120
XP
1140
1135
38
25.5
(10)
150
XP
1405
1400
51
25.5
(12.5)
4 Point Load Location (lbs.)
A
B
C
D
Economizer
Power Exhaust
Electric Heat1
Gas Heat2
Unitary Products Group
6 Point Load Location (lbs.)
B
C
D
E
F
201
150
234
315
141
115
95
149
180
221
206
153
240
322
144
117
97
152
184
225
281
209
275
369
197
160
133
175
211
259
281
209
275
369
197
160
133
175
211
259
258
347
456
339
164
198
243
319
260
216
206
153
240
322
144
117
97
152
184
225
206
153
240
322
144
117
97
152
184
225
281
209
275
369
197
160
133
175
211
259
281
209
275
369
197
160
133
175
211
259
258
347
456
339
164
198
243
319
260
216
ZH/XP078-150 Unit Accessory Weights
Unit Accessory
A
Weight (lbs.)
Shipping
Operating
90
85
155
150
80
80
110
110
1. Weight given is for the maximum heater size available
(54KW).
2. Weight given is for the maximum number of tube heat
exchangers available (8 tube).
87
246824-YTG-D-0806
ZH/XP078-150 Unit Dimensions
ZH/XP078-120
ZH/XP150
ZH/XP078-150 Unit Physical Dimensions
Unit Model Number
A
42
42
50 3/4
50 3/4
50 3/4
078
090
102
120
150
Detail A
B
89
89
89
89
119 1/2
17-13/16
E
15 3/16
15 3/16
17 3/16
17 3/16
17 3/16
F
6 3/16
6 3/16
6 3/16
6 3/16
6 3/16
Detail B
Gas Pipe Inlet
5-1/4
Dimension (in.)
C
D
22 1/8
18 3/16
22 1/8
18 3/16
30 3/16
24 3/16
30 3/16
24 3/16
30 3/16
24 3/16
Base
Pan
View of Wall Across from Coil
88
Unitary Products Group
246824-YTG-D-0806
ZH/XP078-150 Unit Clearances
Direction
Top1
Front
Rear
Distance (in.)
72
36
36
Direction
Right
Left
Bottom2
Distance (in.)
12
36
0
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustable floors made from wood or class A, B or C roof covering materials.
ZH/XP078-150 Unit Bottom Duct Openings
ZH/XP078-150 Unit Electrical Entry
'LVFRQQHFW6ZLWK&RYHU
3RZHU(QWU\‘
&RQWURO(QWU\‘
3RZHU(QWU\‘
&RQYHQLHQFH2XWOHW&RYHU
&RQYHQLHQFH2XWOHW
3RZHU(QWU\‘
Unitary Products Group
)5217
89
246824-YTG-D-0806
ZH/XP078-120 Unit Side Duct Openings
'RW3OXJV
$
5HWXUQ
$LU
6XSSO\
$LU
'
%
&
ZH/XP150 Unit Side Duct Openings
'RW3OXJV
$
'
%
&
Side Duct Dimensions
Unit Model Number
078
090
102
120
150
90
A
27 3/4
27 3/4
28 1/4
28 1/4
28 1/4
Dimension (in.)
B
C
12 1/16
27 1/2
12 1/16
27 1/2
18 1/16
28 1/4
18 1/16
28 1/4
18 1/16
28 1/4
D
16
16
18 1/4
18 1/4
18 1/4
Unitary Products Group
Controls
HVAC control just became a
whole lot smarter and easier!
Only York offers the easiest
solution to help you
take control of controls.
®
C
O
N
T
R
O
L
COMFORT
ONLINE ALARMING
NO HASSLE SET-UP
TOTAL HVAC
CONTROL SOLUTIONS
More control for more savings
More compatibility for more flexibility
Cut energy costs, and achieve higher levels of comfort—
automatically with Simplicity® Intelli-Comfort™ controls.
The controls are compatible with the MODBUS protocol,
and are factory-installed on 3- to 25-ton Sunline™ and
Predator® products and Millennium® HA/HB Systems.
More intelligence for more capabilities
Intelli-Comfort controls use intelligent hardware and
software to give you better monitoring, more flexibility in
control set-up, and finer control of every aspect of your
HVAC system. In addition, the more intelligent the control,
the greater savings you will realize through operational
efficiencies and conservation.
More power with less effort
Intelli-Comfort is a control that’s so easy to use that
you actually benefit from the power at your fingertips.
Easier to manage
Intelli-Comfort raises the intelligence of an already
smart Simplicity control.
More control for greater comfort
The flexibility of the Simplicity Intelli-Comfort control
means comfortable, happier, and more productive
occupants—thanks to the ability to optimize temperature,
humidity, and indoor air quality simultaneously.
Put the intelligence of Simplicity Intelli-Comfort controls
to work in your building.
Simplicity Intelli-Comfort controls give you powerful capabilities without complexity. Easy to set-up, program, and use, the controls give you
everything you need to monitor and control Sunline and Predator units. And because they can be connected as your HVAC Energy
Management System you can save even more by making the intelligence of Simplicity Intelli-Comfort part of your building automation strategy.
RELIABILITY
OPEN PROTOCOL
LOW COST
New features for superior
monitoring and control
365-Day Real Time Clock with
automatic Daylight Savings Time adjustment
Occupancy Schedule allowing two different occupied
schedules per day for each of the seven days of the week
20 Holiday Schedules with a length of up to 99 days, each
with flexible start times. You can now choose the time of day
your holiday begins saving energy
Patent Pending Temperature Humidity Algorithm offsets
the operating setpoint based on high humidity in the space—with
programmable limits to control humidity
Energy-Saving Economizer Operation with the flexibility
of using dry bulb, outside enthalpy and differential enthalpy.
Our economizer enthalpy control has setpoints for outside air
temperature, supply air temperature, small space cooling demand,
and large space cooling demand
High and Low Ambient Lockout to lockout cooling below or
heating above a programmable setpoint of outside air temperature
Outside Air CO2 Sensor to close the economizer if CO2 is present
Inside Demand Ventilation using one CO2 sensor or differential
demand ventilation using inside and outside CO2 sensors
IAQ Operation with programmable maximum outside air
damper position
Space Temperature Alarm when temperatures are outside
of program setpoints. Alarm setpoints are user programmable
Unit Monitors Airflow to detect dirty filters and insufficient airflow
Intelligent Recovery brings the space temperature to the
occupied setpoint just before or at the beginning of the first
occupied schedule each day. The control will “learn” and apply
the minimum runtime required to heat or cool the space to
minimize energy use
Comfort Ventilation Control tempers the ventilation air
when heating or cooling is not required, increasing comfort
©2004 York International Corporation.
All rights reserved. Subject to change without notice.
Form 036-12054-001 (0105). Supersedes: Nothing. Printed in USA.
COMMERCIAL ZONING PACKAGE
The Facility Explorer Commercial Zoning Package is a complete, turnkey control system used to improve
occupant comfort in a building (or section of a building) that is conditioned with a packaged rooftop HVAC unit.
It accomplishes this by varying the amount of conditioned air delivered to individual zones and by intelligently
cycling the rooftop unit’s heating and cooling stages to best satisfy all the zone demands.
Manufacturer Independent
The Facility Explorer Commercial Zoning
Package is designed to work with any
standard, packaged HVAC equipment, regardless
of manufacturer. This allows you to apply this control
package to equipment provided by a variety of
suppliers or to equipment that has already been
installed. This flexibility makes the Facility Explorer
Commercial Zoning Package perfectly suited for both
new and retrofit installations.
Affordable Intelligence
The Facility Explorer Commercial Zoning Package
utilizes the distributed application architecture of
the FX16 Master Controller. This feature allows direct
communications to occur between the FX16 and all
the zone controllers. This means that there is no
need for a traditional supervisory class controller to
manage the data sharing. This direct communication
flow allows the FX16 to monitor each zone’s status to
intelligently determine the proper mode of operation
for the rooftop unit.
COMMERCIAL ZONING PACKAGE
Easy Installation
Several pieces of the Facility Explorer Commercial
Zoning Package can be ordered pre-assembled from
the factory to simplify installation:
• Bypass Damper and Actuator Assembly
• Zone Controller and Actuator Assembly (FXZAN)
• FX16 Master Controller with Pre-Downloaded
Zoning Application
• The FX05 Field Controller is combined with an
M9104AGA non-spring return actuator and an
electrical termination wiring block, all in one
packaged assembly
• Perfect for retrofit installations where the zone
damper is already installed
• Zone Controller, Actuator, and Damper Assembly
• FXZAN Zone Controller and Actuator Assembly is
combined with a round or rectangular zone damper
• Perfect for new installations or for retrofit
installations where the zone damper has not yet
been installed
© 2005 Johnson Controls, Inc.
• A round or rectangular bypass damper is combined
with an M910xHGA non-spring return actuator
• FX16 Master Controller can be ordered with the
commercial zoning application pre-downloaded
• Once installed, the FX16 takes care of downloading
the corresponding parts of the zoning application to
each of the zone controllers
• Eliminates the downloading steps from the field
installation and startup
• This provides the possibility (with an onsite Medium
User Interface) to download, configure and
commission the entire system, including the
rooftop, bypass, and all zone controllers without
any software tool
P.O. Box 423, Milwaukee, WI 53201
Printed in USA PUBL-3894
TSS – Single Duct Variable Air Volume Terminal
• An integrated VAV box with direct digital controls
TSS Terminals provide Variable Air Volume (VAV) control
eliminates the coordination and difficulties
beyond the typical single duct box. They are specifically
associated with factory mounting
designed for precise air delivery throughout the entire
operating range, regardless of the installed inlet conditions.
• Downloading of software, setting of parameters,
These units can be ordered with or without a Direct Digital
addressing and testing at the factory reduces
Controller (DDC), which can operate as a stand-alone unit,
startup time and lowers risk
on a Johnson Controls N2 trunk, or on a LON® trunk.
• Superior flow measuring provides for lower
TSS Terminals take advantage of typical benefits provided
minimum cubic feet per minute (CFM) values,
by single duct units, while performing at extremely low
which reduces energy costs and noise while
sound levels. This is critical in today’s buildings where
maintaining comforts in the zone
occupants are placing more emphasis on indoor acoustics.
The TSS Terminal is manufactured and assembled with a
• Installation time can be reduced with the low
multi-point, center-averaging airflow sensor, which
profile compact design and standard metal
provides a signal to the controller enabling it to quietly and
hanging straps
precisely measure airflow.
• Units wired in compliance with all applicable
Bundled with the TSS Terminal is a digital controller from
National Electrical Code (NEC) requirements and
the VAV Modular Assembly (VMA) Series or the LN Series.
tested in accordance with Air Conditioning and
Each model in the VMA1400 Series and the LN Series
Refrigeration Institute (ARI) standard 880
combines a controller, pressure sensor, and actuator
housed in one pre-assembled unit.
• Offers damper stall detection, starved box
detection, actuator motor duty cycle, VAV box
flow test, and other diagnostics on most
models (VMA Series)
TSS – Single Duct Variable Air Volume Terminal
Standard Features
Optional Features
Construction
Construction
• ARI 880 certified and labeled
• 20-gauge galvanized steel construction
• 22-gauge galvanized steel casing and valve
• 3/4” or 1” fiberglass insulation
• G90 galvanized steel
• Scrim-reinforced, foil-faced insulation meeting American
Society for Testing and Materials (ASTM) C1136 for mold,
mildew, and humidity resistance
• 1/2”, 4lb/ft3 skin, dual density fiberglass insulation, glued
and clinch-pinned in place
• 1/2” Elastomeric closed-cell foam insulation
Hot Water Coils
• Double wall construction with 22-gauge liner
• ARI 410 certified and labeled
• Mounting brackets to accept all-thread hanging rods or
wire hangers
• 1-, 2-, 3-, 4-row coils
• Tested at a minimum of 350 psig under water
• Low temperature construction for use in thermal storage
applications, including a thermally isolated primary air
inlet and a composite damper shaft
• Mechanically expanded copper tubes leak tested
to 350 psig air pressure
• Male sweat type water connections
Hot Water Coils
• Low pressure steam coils
Primary Air Valve
• Embossed rigidity rings
• Multi-circuit coils for reduced water pressure drop
• Low-thermal conducting damper shaft with
position indicator
• Opposite hand water connections
• Bottom and top access plates for cleaning
• Mechanical stops for open and closed position
Electrical Components
• Multi-point center-averaging airflow sensor
• Full unit toggle disconnect and inline motor fusing
• Brass balancing tees
• Primary and secondary transformer fusing
• Plenum-rated sensor tubing
Electric Heat
Electrical Components
• Proportional solid state relay (SSR) heater control
• cETL listed for safety compliance
• Mercury contactors
• National Electrical Manufacturers Association (NEMA)
Type 1 wiring enclosure
• Door interlocking disconnect switches
• Disconnect (toggle or door interlocking)
Electric Heat
• ETL listed as an assembly for safety compliance
• Integral electric heat assembly
• Automatic reset primary and back-up secondary
thermal limits
• Pneumatic Electric (PE) switches
• Mercury and magnetic contactors
• Manual reset secondary limit
• 24 volt control transformer
• Single-point power connection
• Special watt densities
• Hinged electrical enclosure
• Finned tubular elements
• Fusing per NEC
Controls
• Airflow switch
• Factory-provided controls
• Ni-chrome elements
• Direct digital controls (DDC) for N2 or LON® networks
• Primary/Secondary power terminations
• Pneumatic controls
• Wiring diagram
© 2005 Johnson Controls, Inc.
P.O. Box 423, Milwaukee, WI 53201
www.johnsoncontrols.com
Printed in USA PUBL-3888
TSL – Single Duct Low Height Variable Air Volume Terminal
• An integrated VAV box with direct digital controls
TSL Terminals provide variable air volume (VAV) control
eliminates the coordination and difficulties
beyond the typical single duct box. They are specifically
associated with factory mounting
designed for precise air delivery throughout the entire
operating range and are only 10” in height, making them
• Downloading of software, setting of parameters,
ideal for shallow or congested ceiling plenum applications.
addressing and testing at the factory reduces
These units can be ordered with or without a Direct Digital
startup time and lowers risk
Controller (DDC), which can operate as a stand-alone unit,
on a Johnson Controls N2 trunk, or on a LON® trunk.
• Superior flow measuring provides for lower
minimum cubic feet per minute (CFM) values,
TSL Terminals take advantage of typical benefits provided
which reduces energy costs and noise while
by single duct units, while performing at extremely low
maintaining comforts in the zone
sound levels. This is critical in today’s buildings where
occupants are placing more emphasis on indoor acoustics.
• Installation time can be reduced with the low
The TSS Terminal is manufactured and assembled with
profile compact design and standard metal
a multi-point, center-averaging airflow sensor, which
hanging straps
provides a signal to the controller enabling it to quietly and
precisely measure airflow.
• Units wired in compliance with all applicable
National Electrical Code (NEC) requirements and
Bundled with the TSL Terminal is a digital controller from
tested in accordance with Air Conditioning and
the VAV Modular Assembly (VMA) Series or the LN Series.
Refrigeration Institute (ARI) standard 880
Each model in the VMA1400 Series and the LN Series
combines a controller, pressure sensor, and actuator
housed in one pre-assembled unit.
TSL – Single Duct Low Height Variable Air Volume Terminal
• Secondary high limit
Standard Features
• Airflow switch
Construction
• ARI 880 certified and labeled
• Single-point power connection
• 20-gauge, galvanized steel casing and valve
• Hinged electrical enclosure door
• G90 galvanized steel construction
• Fusing per NEC
• 1/2", 4 lb/ft3 skin, dual density fiberglass insulation glued
and clinch pinned
Optional Features
• Invertible unit facilitates control installation on the left- or
right-hand side
Construction
Hot Water Coils
• ARI 410 certified and labeled
• Scrim-reinforced, foil-faced insulation meeting American
Society for Testing and Materials (ASTM) C1136 for mold,
mildew, and humidity resistance
• 1-, 2-, 3-, 4-row coils
• 1/2” Elastomeric closed-cell foam insulation
• Left- or right-hand connections
• Double wall construction with a 22-gauge liner
• Tested at a minimum of 450 psig under water and rated
at 300 psig working pressure at 200°F
• Mounting brackets to accept all thread hanging rods or
wire hangers
• Aluminum fin construction with die-formed spacer collars
for uniform spacing
• Discharge sound attenuator (Model TSL-SA)
• Mechanically expanded copper tubes leak tested to 450
psig air pressure and rated at 300 psig working pressure
at 200°F
• Coil access plate for cleaning coil
Hot Water Coil
• Coil circuiting options for reduced water pressure drop
• Right- or left-hand water connections
• Male sweat type water connections
• Bottom and top access plates for cleaning
Primary Air Valve
• 18-gauge, G90 galvanized steel construction
• Steam coils
• Low thermal conductance damper shaft
Electrical Components
• Position indicator on external end of damper shaft
• Toggle disconnect switch
• Mechanical stops for open and closed position
• Primary and secondary transformer fusing
• Multi-point center-averaging airflow sensor
Electric Heat
• Brass balancing tees
• Proportional solid state relay (SSR) heater control
• Plenum-rated sensor tubing
• Mercury contactors (if equipped with a mercury contactor,
the unit cannot be inverted)
Electrical Components
• Door interlocking disconnect switches
• cETL listed for safety compliance with Underwriters
Laboratories Inc.® (UL) 1995
• Disconnect (toggle or door interlocking)
• National Electrical Manufacturers Association (NEMA)
Type 1 wiring enclosure
• Pneumatic Electric (PE) switches
Electric Heat
• Manual reset secondary limit
• Invertible unit facilitates control installation on the left- or
right-hand side (not applicable if equipped with a
mercury contactor)
Controls
• cETL listed as an assembly for safety compliance
• Direct Digital Controls (DDC), for N2 or LON® networks
• Automatic reset primary and back-up secondary
thermal limits
• Pneumatic controls
• Mercury and magnetic contactors
• Factory-provided controls
• Primary auto-reset high limit
© 2005 Johnson Controls, Inc.
P.O. Box 423, Milwaukee, WI 53201
www.johnsoncontrols.com
Printed in USA PUBL-3882
Single Duct Variable Air Volume Terminal (Model TSS)
Unit
Size
6
8
10
12
14
16
22
CFM
200
400
600
800
1100
1500
3000
Bypass
CFM
300
600
900
1200
1800
2200
5400
Dimensions
Weight
18
20
25
30
38
42
72
WxHxL
10” x 10" x 11"
12” x 10” x 11"
14” x 12.5" x 13”
16” x 15" x 13”
20” x 17.5" x 17.5"
24” x 17.5" x 17.5"
34” x 17.5" x 11"
A
6 1/2“
6 1/2“
6 1/2“
6 1/2“
6 1/2“
6 1/2“
8”
I
5 7/8”
7 7/8”
9 7/8”
11 7/8”
13 7/8”
15 7/8”
32 1/4” x 15 7/8”
X
8 3/4”
10 3/4”
12 3/4”
14 3/4”
18 3/4”
22 3/4”
32 3/4”
Y
8 3/4”
8 3/4”
11 1/4”
13 3/4”
16 1/4”
16 1/4”
16 1/4”
Note: All dimensions are in inches with a tolerance of +1/8”. Size 22 has a rectangular inlet collar. CFM based on
1000 FPM (Bypass 1500 FPM) for low to medium pressure applications.
Clearance 24"
Single Duct Variable Air Volume Terminal - Rectangular (Model TSL)
Dimensions
Unit
Bypass
Size
CFM
CFM
A
W
L
X
Weight
10
600
1200
10”
15”
12 1/2”
13 3/4”
26
12
800
1600
14”
19”
12 1/2”
17 3/4”
28
14
1200
2200
20”
25”
16 1/2”
23 3/4”
39
16
1500
3000
26”
31”
16 1/2”
29 3/4”
45
Notes: 1. For dimensional data for unit sizes 6 and 8, refer to the Single Duct Variable
Air Volume Terminal (Model TSS). All dimensions are in inches with a tolerance of +1/8”.
Weights are in pounds. Weights are for the basic unit with the indicated option and
control enclosure. Actual weight varies based on project-specific requirements for unit
options, appurtenances, and controls. 2. Control enclosure is standard with factorymounted electronic controls. 3. Check all national and local codes for required
clearances.
®
TM
UVC for HVAC
Single-Ended, NEMA 4X
Very High Output Germicidal
Light Source for Outdoor A/C Units
Model SEN Series
UVC Emitters™
needed to maintain microbial control. The UVC Emitter, by
contrast, has a 12-month service life – and even after a full
year, it has 2-1/2 times greater output than competitive devices
deliver on Day 1! As a result, only Steril-Aire can ensure the
germicidal performance you need, with no return of microbial
growth, for 3-4 times longer than the competition
Applications
Steril-Aire Single-Ended NEMA 4X (SEN Series)
fixtures combine the externally mounted design of the SE
Series with a weather resistant NEMA 4X fixture. Installed
from the exterior of rooftop A/C units or ductwork, they are
ideal for difficult to access outdoor sites. By creating two 1"
holes in the equipment wall and mounting the fixture, the
devices may be installed vertically or horizontally. Only the
lamp or tube penetrates into the system, while the power
supply remains external. Choose from six tube lengths (16",
20", 24", 30", 36" and 42") and four voltage options (115,
208, 230 or 277 Vac).
Benefits
• Kills or inactivates surface and airborne microorganisms that
contribute to poor IAQ and/or the spread of infectious disease,
including: mold and mold spores, bacteria (including TB,
Legionella, E. coli, Listeria, salmonella and whooping cough);
and viruses (including colds, flu, measles).
• Delivers an average of 5 times the output of competitive UVC
products at HVAC operating temperatures, for 3-4 times
longer life, while providing more reliable germicidal control.
• Uses patented state-of-the-art solid-state electronic power
supply for enhanced reliability and performance.
• Continuously cleans coils, drain pans, plenums and ducts,
eliminating costly cleaning programs and the use of harmful
chemicals and disinfectants.
• Lowers HVAC energy costs by restoring heat transfer and net
cooling capacity.
Steril-Aire’s multi-patented UVC Emitter™ provides the
best and longest-lasting UVC performance available. As
shown in the comparison graph (above), it has been
independently tested to deliver an average of 5 times the
output of other ultraviolet devices under HVAC operating
conditions (45o F @ 550 fpm air velocity).
Competitive UVC lights must be changed every 3-4
months because they quickly lose the output or "killing power"
• Produces no ozone or other secondary contaminants – will not
harm building occupants, equipment or furnishings.
• Offers lowest life-cycle cost of any UVC product. Return on
investment is often less than one year.
• Installs quickly and easily, with no need to open equipment –
ideal for packaged systems and/or ducts.
Model SEN Specifications
The UVC EmitterTM and fixture shall be factory assembled and
tested. They shall consist of a housing, power source, Emitter socket
and Emitter.
The housing shall be constructed of 304 stainless steel and shall be
powder coated to withstand the elements and HVAC environments.
Housing shall be equipped with a bottom side electrical opening to
facilitate wiring fixture to unit power. It shall incorporate all
components into one integral assembly that maximizes integrity and
serviceability. It shall be designed for mounting from outside the
airstream with only the Emitter in the conditioned air. Emitter shall
be held in place and supported in the airstream by a patented integral
collar, o-ring and heavy-duty spring wire fastener. The patented tube
mount section shall allow for quick and easy removal during lamp
replacement. The housing shall include an on-off switch.
The power source shall be a Class P2, electronic rapid start type
with a power factor of >0.95 and a power conversion of >75%. It
shall be available in 115-208/230 and 277 Vac, 50/60 Hertz, and
single phase. It shall be designed to maximize photon production,
irradiance and reliability in cold or moving airstreams of 35-170° F,
100% RH and at up to 2000 fpm velocity. The design shall include
RF and EMI suppression.
The soc ket shall be a Circline® 4 pin type with sufficient wire length
to facilitate service.
The Emitter shall be a very high output, hot cathode, T5 diameter,
Circline® cell-base type that produces a UVC band of 250-260 nm.
Each tube shall be capable of producing the specified output at up to
2000 fpm velocity and temperatures of 35-170° F. It shall produce no
ozone or other secondary contaminants.
Inde pendent testing: The unit shall be tested by an independent test
laboratory in accordance with the general provisions of IES Lighting
Handbook, 1981 Applications Volume, and shall be verified through
independent testing to provide output per 1" arc length of not less
than 10 µW/cm2 at 1 meter in a 400 fpm airstream of 45° F.
This product may be covered by one or more of the following patents, others
pending: 5,334,347/ 5,866,076/ 5,817,276/ 6,372,186/ 6,313,470/ 6,245,293/
6,267,924/ 6,280,686/ 6,423,882.
Unit shall comply with UL Standard 1995 for use in HVAC
equipment and carry the "UL" and "ULC" labels.
Ordering Information
Model No.
Part No.
Description
SEN 1 VO
SEN 1 VO
GTS 16 VO
GTS 20 VO
GTS 24 VO
GTS 30 VO
GTS 36 VO
GTS 42 VO
12001900
12002100
21000100
21000200
21000300
21000400
21000500
21000600
Single-Ended Fixture
Single-Ended Fixture
UVC Emitter
UVC Emitter
UVC Emitter
UVC Emitter
UVC Emitter
UVC Emitter
Length
N/A
N/A
16"
20"
24"
30"
36"
42"
Electrical
Weight
115, 208, 230V: 70-85 watts
277V: 70-85 watts
N/A
N/A
N/A
N/A
N/A
N/A
3.3 lb.
3.3 lb.
0.15 lb.
0.15 lb.
0.20 lb.
0.20 lb.
0.25 lb.
0.25 lb.
Complies with current U.S. and Canadian UL Standards for
use in HVAC equipment.
®
Represented By:
Steril-Aire, Inc.
Corporate Office:
2840 N. Lima Street
Burbank, CA 91504
Telephone: 818-565-1128
Fax: 818-565-1129
Website: www.steril-aire.com
Email: [email protected]
© 2003 Steril-Aire
1109-07/05
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project