Rheem RLRL-H120DS000 Commercial Package AC Specification

Add to My manuals
68 Pages

advertisement

Rheem RLRL-H120DS000 Commercial Package AC Specification | Manualzz

Air

Package Air Conditioner

RLRL-C/H Series

Rheem Commercial Prestige Series

Package Air Conditioner

RLRL-C Series

With ClearControl

Nominal Sizes 7.5 & 10 Tons [26.4 & 35.2 kW]

ASHRAE 90.1-2007 Compliant Models

RLRL-H Series

With ClearControl

& VFD Technology

Nominal Sizes 7.5 & 10 Tons [26.4 & 35.2 kW]

ASHRAE 90.1-2010 Compliant Models

FORM NO. S11-961 REV. 1

2

Air

Table of Contents

RLRL-C/H Series

TABLE OF CONTENTS

Unit Features & Benefits ..............................................................................3-8

Model Number Identification ............................................................................9

Options ..................................................................................................................10

Selection Procedure ......................................................................................11

General Data

RLRL-C/H Series ..................................................................................12-15

Gross Systems Performance Data

RLRL-C/H Series ......................................................................................16

Airflow Performance

RLRL-C/H Series ..................................................................................17-20

Electrical Data

RLRL-C/H Series ..................................................................................21-24

Units with Heater Kits ..............................................................................25-29

Dimensional Data ....................................................................................30-33

Accessories ............................................................................................34-56

Mechanical Specifications ........................................................................57-62

Wiring Diagrams ......................................................................................63-64

Limited Warranty ..........................................................................................65

Air

Unit Features & Benefits

RLRL-C/H Series

RLRL-C/H STANDARD FEATURES INCLUDE:

• R-410A HFC refrigerant.

• Complete factory charged, wired and run tested.

• Scroll compressors with internal line break overload and high-pressure protection.

• Two stage operation, two independent circuits.

• Convertible airflow–vertical downflow or horizontal sideflow.

• TXV refrigerant metering system on each circuit.

• High Pressure and Low Pressure/Loss of charge protection standard on all models.

• Solid Core liquid line filter drier on each circuit.

• Single slab, single pass designed evaporator and condenser coils facilitate easy cleaning for maintained high efficiencies.

• Cooling operation up to 125 degree F ambient.

• Foil faced insulation encapsulated throughout entire unit minimizes airborne fibers from the air stream.

• Hinged major access door with heavy-duty gasketing, 1/4 turn latches and door retainers.

• Slide Out Indoor fan assembly for added service convenience.

• Powder Paint Finish meets ASTMB117 steel coated on each side for maximum protection. G90 galvanized.

• One piece top cover and one piece base pan with drawn supply and return opening for superior water management.

• Forkable base rails for easy handling and lifting.

• Single point electrical connections.

• Internally sloped slide out condensate pan conforms to

ASHRAE 62 standards.

• High performance belt drive motor with variable pitch pulleys and quick adjust belt system.

• Permanently lubricated evaporator, condenser and gas heat inducer motors.

• Condenser motors are internally protected, totally enclosed with shaft down design.

• 2 inch filter standard with slide out design.

• 24 volt control system with resettable circuit breakers.

• Colored and labeled wiring.

• Copper tube/Aluminum Fin Evaporator coils.

• MicroChannel condenser coil.

• Molded compressor plug.

• Supplemental electric heat provides 100% efficient heating.

• Factory Installed Direct Digital Control (DDC) and sensors which can connect to LonWorks ™ or BACnet ® BAS systems for remote monitoring and control.

• -H models with supply fan Variable Frequency Drive (VFD) meets ASHRAE 90.1-2010 and California Title 24.

3

Air

Unit Features & Benefits

RLRL-C/H Series

1

2

3

4

8

7

5

Rheem Package equipment is designed from the ground up with the latest features and benefits required to compete in today’s market. The clean design stands alone in the industry and is a testament to the quality, reliability, ease of installation and serviceability that goes into each unit. Outwardly, the large Rheem

Commercial Series

label (

1

) identifies the brand to the customer. The sheet-metal cabinet (

2

) uses nothing less than 18gauge material for structural components with an underlying coat of G90. To ensure the leak-proof integrity of these units, the design utilizes a one-piece top with a 1/8" drip lip (

3

),

gasket-protected panels and screws. The Rheem hail guard

(optional) (

4

) is its trademark, and sets the standard for coil protection in the industry. Every Rheem package unit uses the toughest finish in the industry, using electro deposition bakedon enamel tested to withstand a rigorous 1000-hour salt spray test, per ASTM B117.

Anything built to last must start with the right foundation. In this case, the foundation is 14-gauge, commercial-grade, fullperimeter base rails (

5

), which integrate fork slots and rigging holes to save set-up time on the job site. The base pan is stamped, which forms a 1-1/8" flange around the supply and return cover and has eliminated the worry of water entering the conditioned space (

6

). The insulation has been placed on the underside of the basepan, removing areas that would allow for potential moisture accumulation, which can facilitate growth of harmful bacteria. All insulation is secured with both adhesive and mechanical fasteners, and all edges are hidden. The drainpan

(

7

) is made of material that resists the growth of harmful bacteria and is sloped for the latest IAQ benefits. Furthermore, the drain pan slides out for easy cleaning.

6

6

During development, each unit was tested to U.L. 1995, AHRI

340-370 and other Rheem-required reliability tests. Rheem adheres to stringent IS0 9002 quality procedures, and each unit bears the U.L. and AHRI certification labels located on the unit nameplate (

8

). Contractors can rest assured that when a

Rheem package unit arrives at the job, it is ready to go with a factory charge and quality checks.

Access to all major compartments is from the front of the unit, including the filter and electrical compartment, blower compartment, heating section, and outdoor section. Each compartment has 1/4 turn fasteners and hinged access. Each panel is permanently embossed with the compartment name (control/filter access, blower access and electric heat access).

Electrical and filter compartment access is through a large, hinged-access panel. On the outside of the panel is the unit nameplate, which contains the model and serial number, electrical data and other important unit information.

The unit charging chart is located on the inside of the electrical and filter compartment door. Electrical wiring diagrams are found on the control box cover, which allows contractors to

9

move them to more readable locations. To the right of the control box the model and serial number can be found.

Having this information on the inside will assure model iden-

10

tification for the life of the product. The production line quality test assurance label is also placed in this location

(

9

). The two-inch throwaway filters (

10

) are easily removed on a tracked system for easy replacement.

4

Air

Unit Features & Benefits

RLRL-C/H Series

10

7

Inside the control box (

11

), each electrical component is clearly identified with a label that matches the component to the wire diagram for ease of trouble shooting. All wiring is numbered on each end of the termination and color-coded to match the wiring diagram. The control transformer has a low voltage circuit breaker that trips if a low voltage electrical short occurs. There is a blower contactor and compressor for each compressor.

11

As part of the ClearControl ™ system which allows real time monitoring and communication between rooftop units, the

RLRL-C/H Package Air Conditioner has a Rooftop Unit Controller (RTU-C) factory mounted and wired in the control panel.

The RTU-C is a solid-state microprocessor-based control board that provides flexible control and extensive diagnostics for all unit functions.

The RTU-C through proportional/integral control algorithms perform specific unit functions that govern unit operation in response to: zone conditions, system temperatures, system pressures, ambient conditions and

12

electrical inputs. The RTU-C features a 16 x 2 character LCD display and a five-button keypad for local configuration and direct diagnosis of the system. (

12

) New features include a clogged filter switch (CFS), fan proving switch (FPS), return air temperature sensor (RAT), discharge air temperature sensor

(DAT) and outdoor air temperature sensor (OAT). Freeze sensors

(FS) are used in place of freezestats to allow measurement of refrigerant suction line temperatures. The RLRL-C/H Package

Air Conditioner with ClearControl ™ is specifically designed to be applied in four distinct applications:

The RLRL-C/H is compatible with a third party building management system that supports the BACnet Application Specific

Controller device profile, with the use of a field installed BACnet

Communication Module. The BACnet Communication Module plugs onto the unit RTU-C controller and allows communication between ClearControl ™ and the BACnet MSTP network. A zone

sensor, a BACnet network zone sensor, a BACnet thermostat or

DDC controller may be used to send the zone temperature or thermostat demands to the RTU-C. The BACnet Communication

Module is compatible with MSTP EIA-485 daisy chain networks communicating at 38.4 bps. It is compatible with twisted pair, shielded cables.

The RLRL-C/H is compatible with a third party building management system that supports the LonMark Space Comfort Controller (SCC) functional profile or LonMark Discharge Air Controller (DAC) functional profile. This is accomplished with a field installed LonMark communication module. The LonMark Communication Module plugs onto the RTU-C controller and allows communication between ClearControl ™ and a LonWorks Network. A zone sensor, a LonTalk network zone sensor, or a LonTalk thermostat or DDC controller may be used to send the zone temperature or thermostat demands to the RTU-C. The LonMark

Communication Module utilizes an FTT-10A free topology transceiver communicating at 78.8 kbps. It is compatible with Echelon qualified twisted pair cable, Belden 8471 or NEMA Level 4 cables. The Module can communicate up to 1640 ft. with no repeater. The LonWorks limit of 64 nodes per segment applies to this device.

The RLRL-C/H is compatible with a programmable 24 volt thermostat. Connections are made via conventional thermostat screw terminals. Extensive unit status and diagnostics are

displayed on the LCD screen of the RTU-C.

The RLRL-C/H is compatible with a zone sensor and mechanical or solid state time clock connected to the RTU-C. Extensive unit status and diagnostics are displayed on the LCD screen of the RTU-C.

A factory or field installed Comfort Alert ® module is available for power phase-monitoring protection and additional compressor diagnostics. The alarms can be displayed on the RTU-C display, through the (BAS) network, or connected to the “L-Terminal” of a thermostat for notification.

5

Air

Unit Features & Benefits

RLRL-C/H Series

-H models with factory installed supply fan, VFD (Variable Frequency Drive) optimizes energy usage year round by providing a lower speed for first stage cooling operation improving IEER’s by up to 33% over the conventional constant fan system. Furthermore, operating in the constant fan mode at the reduced speed can use as little as

1/8 th of the energy of a conventional constant fan system. Also, by operating at a lower speed on first stage cooling up to 126% more moisture is removed improving comfort during low load operation. The VFD supply fan factory option meet’s California Title 24 and ASHRAE 90.1-2010 requirements for multi blower speed control. VFD also ramps up to the desired speed reducing stress on the supply fan components and reducing the noise from sudden inrush of air. Because the airflow is cut in half during first stage cooling and constant fan operation, noise is much less during these modes of operation.

For added convenience in the field, a factory-installed convenience outlet (

13

) is available.

Low and High voltage can enter either from the side or through the base. Low-voltage connections are made integrated cooling control. The high-voltage connection is terminated at the number 1 compressor contactor. The sug-

13

gested mounting for the field-installed disconnect is on the exterior side of the electrical control box.

To the right of the electrical and filter compartment are the externally mounted gauge ports, which are permanently identified by embossed wording that clearly identifies the compressor circuit, high pressure connection and low pressure connection (

14

). With the gauge

14

ports mounted externally, an accurate diagnostic of system operation can be performed quickly and easily.

The blower compartment is to the right of the gauge ports and can be accessed by 1/4 turn fasteners. To allow easy maintenance of the blower assembly, the entire assembly easily slides out by removing the 3/8" screws from the blower retention bracket. The adjustable motor pulley (

15

) can easily be adjusted by loosening the bolts on either side of the motor mount. Removing the bolts allows for easy removal of the blower pulley

16

by push ing the blower assembly up to loosen the belt. Once the pulley is removed, the motor sheave can

15

be adjusted to the desired number of turns, ranging from 0 to 6 turns open. Where the demands for the job require high static,

Rheem has high-static drives available that deliver nominal airflow up to 2" of static. By referring to the airflow performance tables listed in the installation instructions, proper static pressure and CFM requirements can be dialed in. The scroll housing (

16

)

and blower scroll provide quiet and efficient airflow. The blower sheave is secured by an “H” bushing which firmly secures the pulley to the blower shaft for years of trouble-free operation. The

“H” bushing allows for easy removal of the blower pulley from the shaft, as opposed to the use of a set screw, which can score the shaft, creating burrs that make blower-pulley removal difficult.

6

Air

Unit Features & Benefits

RLRL-C/H Series

Also inside the blower compartment is the low-ambient control

(

17

), low-pressure switch (

18

), high-pressure switch (

19

) and freeze sensor refrigerant safety device (

20

). The low-ambient control allows for operation of the compressor down to 0 degrees ambient temperature by cycling the outdoor fans on high pressure. The high-pressure switch will shut off the compressors if pressures in excess of 610

PSIG are detected, this may occur if the outdoor fan motor fails. The low-pressure switch shuts off the compressors if low pressure is detected due

17

19

18

to loss of charge. The freeze sensor protects the compressor if the evaporator coil gets too cold (below freezing) due to low airflow, and allows monitoring of the suction line temperature on the controller display. Each factory-installed option is brazed into the appropriate high or low side and wired appropriately. Use of polarized plugs and schrader fittings allow for easy field installation.

Inside the blower compartment the interlaced evaporator can also be viewed. The evaporator uses enhanced fin technology for maximum heat transfer. The TXV metering device assures even distribution of refrigerant throughout the evaporator. (Note:

6 ton single stage has an orifice refrigerant control.)

Wiring throughout the unit is neatly bundled and routed.

Where wire harnesses go through the condenser bulkhead or blower deck, a molded wire harness assembly (

20

) provides an air-tight and water-tight

20

seal, and provides strain relief. Care is also taken to tuck raw edges of insulation behind sheet metal to improve indoor air quality.

22

23

27

28

26

25

24

The heating compartment contains the latest electric furnace technology on the market. The 100% efficient electric furnace can be factory-installed or easily field-installed. Built with easeof-installation in mind, the electric furnace is completely wired for slide-in, plug-and-play installation in the field. With choices of up to six kilowatt offerings, the contractor is assured to get the correct amount of heating output to meet the designed heating load.

Power hook-up in the field is easy with single-point wiring to a terminal block (

22

) and a polarized plug for the low-voltage connection (

23

). The electric furnace comes with fuses for the unit (

24

)

and for the electric furnace (

25

), and is UL certified (

26

). The electric heating elements are of a wound-wire construction (

27

)

and isolated with ceramic bushings. The limit switch (

28

)

protects the design from over-temperature conditions. Each electric furnace has the capability to be converted from singlestage operation to two-stage operation by removing a jumper on the low-voltage terminal strip.

7

Air

Unit Features & Benefits

RLRL-C/H Series

The compressor compartment houses the heartbeat of the unit. The scroll compressor (

29

) is known for its long life, and for reliable, quiet, and efficient operation. Each compressor has molded compressor plug eliminating potential for mis wiring. The suction and discharge lines are designed with shock loops (

30

) to

29

absorb the strain and stress that the starting torque, steady state operation, and shut down cycle impose on the refrigerant tubing. Each compressor and circuit is independent for built-in redundancy, and each circuit

31

is clearly marked throughout the system. Each unit has two stages of efficient cooling operation, first stage is approximately

50% of second stage (072 single stage).

Each unit comes standard with filter dryer (

31

). The condenser fan motor (

32

) can easily be accessed and maintained through the compressor compartment. The polarized plug connection allows the motor to be changed quickly and eliminates the need to snake wires through the unit.

The outdoor coil uses the latest enhanced fin design (

33

) for the most effective method of heat transfer. The outdoor coil is protected by optional louvered panels, which allow unobstructed

airflow while protecting the unit from both Mother Nature and vandalism.

Each unit is designed for both downflow or horizontal applications

(

34

) for job configuration flexibility. The return air compartment can also contain an economizer (

35

).

34

Three models exist, two for downflow applications, and one for horizontal applications (A downflow economizer with factory installed

35

smoke detector in the return section is available).

Each unit is pre-wired for the economizer to allow quick plug-in installation. The economizer is also available as a factoryinstalled option. The economizer, which provides free cooling when outdoor conditions are suitable and also provides fresh air to meet local requirements, comes standard with single enthalpy controls. The controls can be upgraded to dual enthalpy easily in the field. The direct drive actuator combined with gear drive dampers has eliminated the need for linkage adjustment in the field. The economizer control has a minimum position setpoint, an outdoor-air setpoint, a mix-air setpoint, and a CO

2 setpoint. Barometric relief is standard on all economizers. Power

Exhaust is easily field-installed. The power exhaust is

35

housed in the barometric relief opening and is easily slipped in with a plug-in assembly. The wire harness to the economizer also has accommodations for a smoke detector.

The damper minimum position, actual damper position, power exhaust on/off setpoint, mixed air temperature limit setpoint and

Demand Controlled Ventilation (DCV) setpoint can be read and adjusted at the unit controller display or remotely through a network connection.

The Space CO

2 level, mixed air temperature, and Economizer

Status (Free Cooling Available, Single or Dual Enthalpy) can be read at the unit controller display or remotely through a network connection. Economizer Faults will trigger a network Alarm and can be read at the unit controller display or remotely through a network connection.

The Rheem roofcurb (

36

) is made for toolless assembly at the jobsite by engaging a pin into the hinged corners of adjacent curb sides, which makes the assembly

36

process quick and easy.

8

Air

Model Number Identification

RLRL-C/H Series

R L R L — C 090 C L 000 X X X

Economizer Option (See Next Page)

Factory Installed Options

(See Next Page)

Electric Heat

000 = No Resistance Heat

010 = 10 kW Resistance Heat

015 = 15 kW Resistance Heat

020 = 20 kW Resistance Heat

030 = 30 kW Resistance Heat

040 = 40 kW Resistance Heat

050 = 50 kW Resistance Heat

Drive Package

L = Belt Drive

M= Belt Drive—High Static

N = Belt Drive—RLRL- C090 Only

R = VFD Belt Drive

S = VFD Belt Drive High Static

T = VFD Belt Drive High Static

(-H 090 only)

Electrical Designation

C = 208-230 V, 3 PH, 60 Hz

D = 460 V, 3 PH, 60 Hz

Y = 575 V, 3 PH, 60 Hz

Cooling Capacity (BTUH) [kW]

090 = 90,000 [26.38]

120 = 120,000 [35.17]

C = ClearControl ™

H = ClearControl ™

(DDC) w/VFD

Design Series

L = R410A

Efficiency Designation

R = Ultra High Efficiency

Product Classification

L = Packaged Air Conditioner–

= Commercial

Tradebrand

R = Rheem Package Air Conditioner

[ ] Designates Metric Conversions

9

Air

Options

RLRL-C/H Series

6 TO 12.5 TON [21.1 TO 44.0 kW]

Option Code

BJ

CZ

JE

AD

AG

AR

JD

“x” indicates factory installed option.

Hail Guard

x x x x

Non-Powered

Convenience Outlet

x x x x

Low Ambient/

Comfort Alert

x x x x

ECONOMIZER SELECTION FOR LRL

7 TO 10 TON [26.4 TO 35.2 kW]

No Economizer

DDC Single Enthalpy Economizer with Barometric Relief

A

H

J

“x” indicates factory installed option.

x x

DDC Single Enthalpy Economizer with

Barometric Relief and Smoke Detector

x

Instructions for Factory Installed Option(s) Selection

Note: Three characters following the model number will be utilized to designate a factory-installed option or combination of options. If no factory option(s) is required, nothing follows the model number.

Step 1. After a basic rooftop model is selected, choose a two-character option code from the FACTORY

INSTALLED OPTION SELECTION TABLE.

Proceed to Step 2.

Step 2. The last option code character is utilized for factory-installed economizers. Choose a character from the FACTORY INSTALLED ECONOMIZER SELECTION TABLE.

Examples:

RLRL-C120CL000 ..............................this unit has no factory installed options.

RLRL-C120CL000ADA ......................this unit is equipped with hail guards.

RLRL-C120CL000JDA ......................this unit is equipped with hail guards, low ambient and comfort alert.

RLRL-C120CL000JDH ......................this unit is equipped as above and includes an Economizer

with single enthalpy sensor and with barometric relief.

RLRL-C120CL000AAJ ......................this unit is equipped with an Economizer with single enthalpy sensor and

barometric relief with smoke detector.

[ ] Designates Metric Conversions

10

To select an RLRL-C/H Cooling and Heating unit to meet a job requirement, follow this procedure, with example, using data supplied in this specification sheet.

1. DETERMINE COOLING AND HEATING REQUIREMENTS

AND SPECIFIC OPERATING CONDITIONS FROM PLANS

AND SPECS.

Example:

Voltage—

Total cooling capacity—

Sensible cooling capacity—

Heating capacity—

*Condenser Entering Air—

208/240V 3 Phase

106,000 BTUH [31.26 kW]

82,000 BTUH [24.03 kW]

150,000 BTUH [43.96 kW]

95°F [35°C] DB

*Evaporator Mixed Air Entering— 65°F [18°C] WB;

*Indoor Air Flow (vertical)—

*External Static Pressure—

78°F [26°C] DB

3600 CFM [1699 L/s]

.40 in. WG

2. SELECT UNIT TO MEET COOLING REQUIREMENTS.

Since total cooling is within the range of a nominal 10 ton

[35.2 kW] unit, enter cooling performance table at 95°F [35°C]

DB condenser inlet air. Interpolate between 63°F [2°C] and

67°F [19°C] to determine total and sensible capacity and power input for 65°F [18°C] WB evap inlet air at 4000 CFM

[1888 L/s] indoor air flow (table basis):

Total Capacity = 118,900 BTUH [34.80 kW]

Sensible Capacity = 99,950 BTUH [29.29 kW]

Power Input (Compressor and Cond. Fans) = 8,950 watts

Use formula [1.10 x CFM x (1 – DR) x (dbE – 80)] in note to determine sensible capacity at 80°F [26.7°C] DB evaporator entering air:

Sensible Capacity = 92,268 BTUH [27.24 kW]

3. CORRECT CAPACITIES OF STEP 2 FOR

ACTUAL AIR FLOW.

Select factors from airflow correction table at 3600 CFM

[1699 L/s] and apply to data obtained in step 2 to obtain gross capacity:

Total Capacity, 118,900 x .98 = 116,522 BTUH [34.15 kW]

Sensible Capacity, 92,268 x .95 = 87,655 BTUH [25.67 kW]

Power Input 11,650 x .99 = 8,861 Watts

These are Gross Capacities, not corrected for blower motor heat or power.

4. DETERMINE BLOWER SPEED AND WATTS TO MEET

SYSTEM DESIGN.

Enter Indoor Blower performance table at 3600 CFM [1699

L/s]. Total ESP (external static pressure) per the spec of .40 in.

includes the system duct and grilles. Add from the table

“Component Air Resistance,” .076 for wet coil, .13 for vertical air flow, for a total selection static pressure of .606 (.6) inches of water, and determine:

RPM = 796

WATTS = 1,650

DRIVE = L (standard 2 H.P. motor)

Air

Selection Procedure

RLRL-C/H Series

5. CALCULATE INDOOR BLOWER BTUH HEAT EFFECT

FROM MOTOR WATTS, STEP 4.

BTUH = 1,650 x 3.412 = 5,630

6. CALCULATE NET COOLING CAPACITIES, EQUAL TO

GROSS CAPACITY, STEP 3, MINUS INDOOR BLOWER

MOTOR HEAT.

Net Total Capacity = 116,522 – 5,630 =

110,892 BTUH [32.5 kW]

Net Sensible Capacity = 87,655 – 5,630 =

82,025 BTUH [24.04 kW]

7. CALCULATE UNIT INPUT AND JOB EER.

Total Power Input = 88,610 (step 3) + 1,650

(step 4) = 10,511 Watts

EER =

Net Total BTUH [kW] (step 6)

=

110,892

Power Input, Watts (above) 10,511

= 10.55

8. SELECT UNIT HEATING CAPACITY.

Units with heater kits section find unit heater kw and convert watts to BTU: add blower BTUH heat effect (step 5).

CC50C Heater Kit kW x 3412 = 163,776 BTUH [48.00 kW]

+ 5,630 BTUH [ 0 1.65 kW]

Heating Capacity= 169,406 BTUH [49.65 kW]

CHOOSE MODEL RLRL-C/H120CL050

*NOTE: These operating conditions are typical of a commercial application in a 95°F/79°F [35°C/26°C] design area with indoor design of 76°F [24°C] DB and 50% RH and 10% ventilation air, with the unit roof mounted and centered on the zone it conditions by ducts.

[ ] Designates Metric Conversions

11

Air

General Data

RLRL-C/H Series

NOM. SIZES 7.5-10 TONS [26.4-35.2 kW] ASHRAE 90.1-2010 COMPLIANT MODELS

Model RLRL- Series

Model RLRL- Series (with VFD)

Cooling Performance 1

Gross Cooling Capacity Btu [kW]

EER/SEER

2

Nominal CFM/AHRI Rated CFM [L/s]

AHRI Net Cooling Capacity Btu [kW]

Net Sensible Capacity Btu [kW]

Net Latent Capacity Btu [kW]

IEER

3

(Standard / VFD)

Net System Power kW

C090CL

H090CR

95,000 [27.83]

13/NA

3000/2600 [1416/1227]

92,000 [26.96]

66,200 [19.4]

25,800 [7.56]

14/15.8

7.04

C090CM

H090CS

95,000 [27.83]

13/NA

3000/2600 [1416/1227]

92,000 [26.96]

66,200 [19.4]

25,800 [7.56]

14/15.8

7.04

C090CN

H090CT

95,000 [27.83]

13/NA

3000/2600 [1416/1227]

92,000 [26.96]

66,200 [19.4]

25,800 [7.56]

14/15.8

7.04

C090DL

H090DR

CONTINUED

95,000 [27.83]

13/NA

3000/2600 [1416/1227]

92,000 [26.96]

66,200 [19.4]

25,800 [7.56]

14/15.8

7.04

Compressor

No./Type

Outdoor Sound Rating (dB) 5

Outdoor Coil—Fin Type

Tube Type

MicroChannel Depth in. [mm]

Face Area sq. ft. [sq. m]

Rows / FPI [FPcm]

Indoor Coil—Fin Type

Tube Type

Tube Size in. [mm]

Face Area sq. ft. [sq. m]

Rows / FPI [FPcm]

Refrigerant Control

Drain Connection No./Size in. [mm]

Outdoor Fan—Type

No. Used/Diameter in. [mm]

Drive Type/No. Speeds

CFM [L/s]

No. Motors/HP

Motor RPM

Indoor Fan—Type

No. Used/Diameter in. [mm]

Drive Type

No. Speeds (Standard / VFD)

No. Motors

Motor HP

Motor RPM

Motor Frame Size

Filter—Type

Furnished

(NO.) Size Recommended in. [mm x mm x mm]

Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g]

Weights

Net Weight lbs. [kg]

Ship Weight lbs. [kg]

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

1 / 23 [9]

Louvered

Rifled

0.375 [9.5]

13.5 [1.25]

3 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single / Multiple

1

2

1725

56

Disposable

Yes

(6)2x18x18 [51x457x457]

105.6/105.6 [2994/2994]

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

1 / 23 [9]

Louvered

Rifled

0.375 [9.5]

13.5 [1.25]

3 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single / Multiple

1

2

1725

56

Disposable

Yes

(6)2x18x18 [51x457x457]

105.6/105.6 [2994/2994]

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

1 / 23 [9]

Louvered

Rifled

0.375 [9.5]

13.5 [1.25]

3 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single / Multiple

1

3

1725

56

Disposable

Yes

(6)2x18x18 [51x457x457]

105.6/105.6 [2994/2994]

1020 [463]

1057 [479]

1020 [463]

1057 [479]

1028 [466]

1065 [483]

1020 [463]

1057 [479]

NOTES:

1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to

⫾20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner

Equipment certification program, which is based on AHRI Standard 340/360.

2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.

3. Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI Standard 340/360.

4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

1 / 23 [9]

Louvered

Rifled

0.375 [9.5]

13.5 [1.25]

3 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single / Multiple

1

2

1725

56

Disposable

Yes

(6)2x18x18 [51x457x457]

105.6/105.6 [2994/2994]

[ ] Designates Metric Conversions

12

Air

General Data

RLRL-C/H Series

NOM. SIZES 7.5-10 TONS [26.4-35.2 kW] ASHRAE 90.1-2010 COMPLIANT MODELS

Model RLRL- Series

Model RLRL- Series (with VFD)

Cooling Performance 1

Gross Cooling Capacity Btu [kW]

EER/SEER

2

Nominal CFM/AHRI Rated CFM [L/s]

AHRI Net Cooling Capacity Btu [kW]

Net Sensible Capacity Btu [kW]

Net Latent Capacity Btu [kW]

IEER

3

(Standard / VFD)

Net System Power kW

Compressor

No./Type

Outdoor Sound Rating (dB) 5

Outdoor Coil—Fin Type

Tube Type

MicroChannel Depth in. [mm]

Face Area sq. ft. [sq. m]

Rows / FPI [FPcm]

Indoor Coil—Fin Type

Tube Type

Tube Size in. [mm]

Face Area sq. ft. [sq. m]

Rows / FPI [FPcm]

Refrigerant Control

Drain Connection No./Size in. [mm]

Outdoor Fan—Type

No. Used/Diameter in. [mm]

Drive Type/No. Speeds

CFM [L/s]

No. Motors/HP

Motor RPM

Indoor Fan—Type

No. Used/Diameter in. [mm]

Drive Type

No. Speeds (Standard / VFD)

No. Motors

Motor HP

Motor RPM

Motor Frame Size

Filter—Type

Furnished

(NO.) Size Recommended in. [mm x mm x mm]

Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g]

C090DM

H090DS

95,000 [27.83]

13/NA

3000/2600 [1416/1227]

92,000 [26.96]

66,200 [19.4]

25,800 [7.56]

14/15.8

7.04

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

1 / 23 [9]

Louvered

Rifled

0.375 [9.5]

13.5 [1.25]

3 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single / Multiple

1

2

1725

56

Disposable

Yes

(6)2x18x18 [51x457x457]

105.6/105.6 [2994/2994]

C090DN

H090DT

95,000 [27.83]

13/NA

3000/2600 [1416/1227]

92,000 [26.96]

66,200 [19.4]

25,800 [7.56]

14/15.8

7.04

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

1 / 23 [9]

Louvered

Rifled

0.375 [9.5]

13.5 [1.25]

3 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single / Multiple

1

3

1725

56

Disposable

Yes

(6)2x18x18 [51x457x457]

105.6/105.6 [2994/2994]

C090YL

95,000 [27.83]

13/NA

3000/2600 [1416/1227]

92,000 [26.96]

66,200 [19.4]

25,800 [7.56]

14

7.04

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

1 / 23 [9]

Louvered

Rifled

0.375 [9.5]

13.5 [1.25]

3 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single

1

2

1725

56

Disposable

Yes

(6)2x18x18 [51x457x457]

105.6/105.6 [2994/2994]

C090YM

CONTINUED

95,000 [27.83]

13/NA

3000/2600 [1416/1227]

92,000 [26.96]

66,200 [19.4]

25,800 [7.56]

14

7.04

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

1 / 23 [9]

Louvered

Rifled

0.375 [9.5]

13.5 [1.25]

3 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single

1

2

1725

56

Disposable

Yes

(6)2x18x18 [51x457x457]

105.6/105.6 [2994/2994]

Weights

Net Weight lbs. [kg]

Ship Weight lbs. [kg]

1020 [463]

1057 [479]

1028 [466]

1065 [483]

1020 [463]

1057 [479]

1020 [463]

1057 [479]

NOTES:

1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to

⫾20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner

Equipment certification program, which is based on AHRI Standard 340/360.

2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.

3. Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI Standard 340/360.

4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.

[ ] Designates Metric Conversions

13

Air

General Data

RLRL-C/H Series

NOM. SIZES 7.5-10 TONS [26.4-35.2 kW] ASHRAE 90.1-2010 COMPLIANT MODELS

Model RLRL- Series

Model RLRL- Series (with VFD)

Cooling Performance 1

Gross Cooling Capacity Btu [kW]

EER/SEER

2

Nominal CFM/AHRI Rated CFM [L/s]

AHRI Net Cooling Capacity Btu [kW]

Net Sensible Capacity Btu [kW]

Net Latent Capacity Btu [kW]

IEER

3

(Standard / VFD)

Net System Power kW

Compressor

No./Type

Outdoor Sound Rating (dB) 5

Outdoor Coil—Fin Type

Tube Type

MicroChannel Depth in. [mm]

Face Area sq. ft. [sq. m]

Rows / FPI [FPcm]

Indoor Coil—Fin Type

Tube Type

Tube Size in. [mm]

Face Area sq. ft. [sq. m]

Rows / FPI [FPcm]

Refrigerant Control

Drain Connection No./Size in. [mm]

Outdoor Fan—Type

No. Used/Diameter in. [mm]

Drive Type/No. Speeds

CFM [L/s]

No. Motors/HP

Motor RPM

Indoor Fan—Type

No. Used/Diameter in. [mm]

Drive Type

No. Speeds (Standard / VFD)

No. Motors

Motor HP

Motor RPM

Motor Frame Size

C090YN

95,000 [27.83]

13/NA

3000/2600 [1416/1227]

92,000 [26.96]

66,200 [19.4]

25,800 [7.56]

14

7.04

C120CL

H120CR

124,000 [36.33]

12.5/NA

4000/3575 [1888/1687]

120,000 [35.16]

87,600 [25.67]

32,400 [9.49]

13.8/15.6

9.62

C120CM

H120CS

124,000 [36.33]

12.5/NA

4000/3575 [1888/1687]

120,000 [35.16]

87,600 [25.67]

32,400 [9.49]

13.8/15.6

9.62

C120DL

H120DR

CONTINUED

124,000 [36.33]

12.5/NA

4000/3575 [1888/1687]

120,000 [35.16]

87,600 [25.67]

32,400 [9.49]

13.8/15.6

9.62

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

1 / 23 [9]

Louvered

Rifled

0.375 [9.5]

13.5 [1.25]

2 / 18 [7]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single

1

3

1725

56

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single / Multiple

1

2

1725

56

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

2 / 23 [9]

Louvered

Rifled

0.375 [9.5]

15.75 [1.46]

4 / 15 [6]

TX Valves

1/1 [25.4]

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

2 / 23 [9]

Louvered

Rifled

0.375 [9.5]

15.8 [1.47]

4 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single / Multiple

1

3

1725

56

Filter—Type

Furnished

(NO.) Size Recommended in. [mm x mm x mm]

Disposable

Yes

(6)2x18x18 [51x457x457]

Disposable

Yes

(3)2x18x18 [51x457x457]

(3)2x18x24 [51x457x610]

153.6/156.8 [4355/4445]

Disposable

Yes

(3)2x18x18 [51x457x457]

(3)2x18x24 [51x457x610]

153.6/156.8 [4355/4445]

Disposable

Yes

(3)2x18x18 [51x457x457]

(3)2x18x24 [51x457x610]

153.6/156.8 [4355/4445]

Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g]

Weights

Net Weight lbs. [kg]

Ship Weight lbs. [kg]

107.5/110.7 [3048/3138]

1028 [466]

1065 [483]

1169 [530]

1206 [547]

1177 [534]

1214 [551]

1169 [530]

1206 [547]

NOTES:

1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to

⫾20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner

Equipment certification program, which is based on AHRI Standard 340/360.

2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.

3. Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI Standard 340/360.

4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

2 / 23 [9]

Louvered

Rifled

0.375 [9.5]

15.75 [1.46]

4 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single / Multiple

1

2

1725

56

[ ] Designates Metric Conversions

14

Air

General Data

RLRL-C/H Series

NOM. SIZES 7.5-10 TONS [26.4-35.2 kW] ASHRAE 90.1-2010 COMPLIANT MODELS

Model RLRL- Series

Model RLRL- Series (with VFD)

Cooling Performance 1

Gross Cooling Capacity Btu [kW]

EER/SEER

2

Nominal CFM/AHRI Rated CFM [L/s]

AHRI Net Cooling Capacity Btu [kW]

Net Sensible Capacity Btu [kW]

Net Latent Capacity Btu [kW]

IEER

3

(Standard / VFD)

Net System Power kW

Compressor

No./Type

Outdoor Sound Rating (dB) 5

Outdoor Coil—Fin Type

Tube Type

MicroChannel Depth in. [mm]

Face Area sq. ft. [sq. m]

Rows / FPI [FPcm]

Indoor Coil—Fin Type

Tube Type

Tube Size in. [mm]

Face Area sq. ft. [sq. m]

Rows / FPI [FPcm]

Refrigerant Control

Drain Connection No./Size in. [mm]

Outdoor Fan—Type

No. Used/Diameter in. [mm]

Drive Type/No. Speeds

CFM [L/s]

No. Motors/HP

Motor RPM

Indoor Fan—Type

No. Used/Diameter in. [mm]

Drive Type

No. Speeds (Standard / VFD)

No. Motors

Motor HP

Motor RPM

Motor Frame Size

Filter—Type

Furnished

(NO.) Size Recommended in. [mm x mm x mm]

C120DM

H120DS

124,000 [36.33]

12.5/NA

4000/3575 [1888/1687]

120,000 [35.16]

87,600 [25.67]

32,400 [9.49]

13.8/15.6

9.62

C120YL

124,000 [36.33]

12.5/NA

4000/3575 [1888/1687]

120,000 [35.16]

87,600 [25.67]

32,400 [9.49]

13.8

9.62

C120YM

124,000 [36.33]

12.5/NA

4000/3575 [1888/1687]

120,000 [35.16]

87,600 [25.67]

32,400 [9.49]

13.8

9.62

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

2 / 23 [9]

Louvered

Rifled

0.375 [9.5]

15.75 [1.46]

4 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single / Multiple

1

3

1725

56

Disposable

Yes

(3)2x18x18 [51x457x457]

(3)2x18x24 [51x457x610]

153.6/156.8 [4355/4445]

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

2 / 23 [9]

Louvered

Rifled

0.375 [9.5]

15.75 [1.46]

4 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single

1

2

1725

56

Disposable

Yes

(3)2x18x18 [51x457x457]

(3)2x18x24 [51x457x610]

153.6/156.8 [4355/4445]

2/Scroll

88

Louvered

MicroChannel

1 [25.4]

27 [2.51]

2 / 23 [9]

Louvered

Rifled

0.375 [9.5]

15.75 [1.46]

4 / 15 [6]

TX Valves

1/1 [25.4]

Propeller

2/24 [609.6]

Direct/1

8000 [3775]

2 at 1/3 HP

1075

FC Centrifugal

1/15x15 [381x381]

Belt (Adjustable)

Single

1

3

1725

56

Disposable

Yes

(3)2x18x18 [51x457x457]

(3)2x18x24 [51x457x610]

153.6/156.8 [4355/4445]

Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g]

Weights

Net Weight lbs. [kg]

Ship Weight lbs. [kg]

1177 [534]

1214 [551]

1169 [530]

1206 [547]

1177 [534]

1214 [551]

NOTES:

1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to

⫾20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner

Equipment certification program, which is based on AHRI Standard 340/360.

2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.

3. Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI Standard 340/360.

4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.

[ ] Designates Metric Conversions

15

Air

Gross Systems Performance Data

RLRL-C/H Series

GROSS SYSTEMS PERFORMANCE DATA—C/H090

E

R

A

T

T

E

M

P

U

R

E

D

O

O

R

O

U

T

B

U

L

B

D

R

Y

°F

[°C]

75

[23.9] wbE

CFM [L/s]

DR

Total BTUH [kW]

Sens BTUH [kW]

Power

80

[26.7]

Total BTUH [kW]

Sens BTUH [kW]

Power

85

[29.4]

90

[32.2]

Total BTUH [kW]

Sens BTUH [kW]

Power

Total BTUH [kW]

Sens BTUH [kW]

Power

95

[35]

100

[37.8]

Total BTUH [kW]

Sens BTUH [kW]

Power

Total BTUH [kW]

Sens BTUH [kW]

Power

105

[40.6]

Total BTUH [kW]

Sens BTUH [kW]

Power

110

[43.3]

Total BTUH [kW]

Sens BTUH [kW]

Power

115

[46.1]

Total BTUH [kW]

Sens BTUH [kW]

Power

3600 [1699]

.0

121.5 [35.6]

82.0 [24.0]

5.2

118.2 [34.6]

80.8 [23.7]

5.5

114.8 [33.6]

79.4 [23.3]

5.8

111.3 [32.6]

77.6 [22.7]

6.2

107.7 [31.6]

75.6 [22.2]

6.6

104.0 [30.5]

73.2 [21.4]

7.0

100.3 [29.4]

70.8 [20.7]

7.4

96.5 [28.3]

67.9 [19.9]

7.9

92.5 [27.1]

64.8 [19.0]

8.4

100.7 [29.5]

57.1 [16.7]

6.3

97.2 [28.5]

55.3 [16.2]

6.7

93.7 [27.5]

53.4 [15.6]

7.2

90.2 [26.4]

51.3 [15.0]

7.6

86.5 [25.3]

48.9 [14.3]

8.1

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

71°F [21.7°C] 67°F [19.4°C]

2600 [1227]

.03

2400 [1133]

.05

3600 [1699]

.0

2600 [1227]

.03

113.6 [33.3]

61.6 [18.0]

5.0

112.0 [32.8]

57.8 [16.9]

5.0

115.0 [33.7]

95.3 [27.9]

5.1

107.5 [31.5]

73.3 [21.5]

5.0

2400 [1133]

.05

106.0 [31.1]

69.2 [20.3]

4.9

110.5 [32.4]

60.8 [17.8]

5.3

107.3 [31.4]

59.8 [17.5]

5.6

104.0 [30.5]

58.5 [17.1]

6.0

108.9 [31.9]

57.1 [16.7]

5.3

105.8 [31.0]

56.2 [16.5]

5.6

102.6 [30.1]

55.1 [16.1]

5.9

111.6 [32.7]

94.0 [27.5]

5.4

108.2 [31.7]

92.6 [27.1]

5.8

104.7 [30.7]

90.8 [26.6]

6.1

104.4 [30.6]

72.5 [21.2]

5.3

101.2 [29.7]

71.5 [20.9]

5.6

97.9 [28.7]

70.2 [20.6]

5.9

102.9 [30.1]

68.5 [20.1]

5.2

99.7 [29.2]

67.5 [19.8]

5.5

96.5 [28.3]

66.3 [19.4]

5.9

99.3 [29.1]

53.7 [15.7]

6.3

95.9 [28.1]

52.1 [15.3]

6.7

92.4 [27.1]

50.2 [14.7]

7.1

88.9 [26.0]

48.2 [14.1]

7.6

85.3 [25.0]

46.0 [13.5]

8.1

101.2 [29.7]

88.9 [26.0]

6.5

97.5 [28.6]

86.6 [25.4]

6.9

93.7 [27.5]

84.0 [24.6]

7.4

89.9 [26.3]

81.1 [23.8]

7.8

86.0 [25.2]

78.1 [22.9]

8.4

94.5 [27.7]

68.7 [20.1]

6.3

91.1 [26.7]

67.0 [19.6]

6.7

87.6 [25.7]

65.1 [19.1]

7.1

84.0 [24.6]

62.9 [18.4]

7.6

80.4 [23.6]

60.6 [17.8]

8.1

93.2 [27.3]

65.0 [19.0]

6.3

89.8 [26.3]

63.3 [18.5]

6.7

86.4 [25.3]

61.6 [18.0]

7.1

82.9 [24.3]

59.6 [17.5]

7.5

79.2 [23.2]

57.3 [16.8]

8.0

3600 [1699]

.0

109.4 [32.1]

105.8 [31.0]

5.1

106.1 [31.1]

104.6 [30.6]

5.4

102.7 [30.1]

102.7 [30.1]

5.7

99.2 [29.1]

99.2 [29.1]

6.1

95.6 [28.0]

95.6 [28.0]

6.5

92.0 [27.0]

92.0 [27.0]

6.9

88.2 [25.8]

88.2 [25.8]

7.3

84.4 [24.7]

84.4 [24.7]

7.8

80.5 [23.6]

80.5 [23.6]

8.3

63°F [17.2°C]

2600 [1227]

.03

102.3 [30.0]

82.6 [24.2]

4.9

99.2 [29.1]

81.8 [24.0]

5.2

96.0 [28.1]

80.8 [23.7]

5.5

92.7 [27.2]

79.5 [23.3]

5.9

89.4 [26.2]

78.1 [22.9]

6.2

85.9 [25.2]

76.3 [22.4]

6.6

82.4 [24.1]

74.4 [21.8]

7.1

78.9 [23.1]

72.3 [21.2]

7.5

75.2 [22.0]

69.9 [20.5]

8.0

2400 [1133]

.05

100.9 [29.6]

78.3 [22.9]

4.9

97.8 [28.7]

77.5 [22.7]

5.2

94.7 [27.7]

76.6 [22.4]

5.5

91.4 [26.8]

75.4 [22.1]

5.8

88.1 [25.8]

74.0 [21.7]

6.2

84.7 [24.8]

72.4 [21.2]

6.6

81.3 [23.8]

70.7 [20.7]

7.0

77.8 [22.8]

68.6 [20.1]

7.5

74.1 [21.7]

66.3 [19.4]

8.0

GROSS SYSTEMS PERFORMANCE DATA—C/H120

E

R

A

T

T

E

M

P

U

R

E

B

U

L

B

D

R

Y

D

O

O

R

O

U

T

°F

[°C]

75

[23.9] wbE

CFM [L/s]

DR

Total BTUH [kW]

Sens BTUH [kW]

Power

80

[26.7]

85

[29.4]

90

[32.2]

95

[35]

100

[37.8]

105

[40.6]

110

[43.3]

115

[46.1]

Total BTUH [kW]

Sens BTUH [kW]

Power

Total BTUH [kW]

Sens BTUH [kW]

Power

Total BTUH [kW]

Sens BTUH [kW]

Power

Total BTUH [kW]

Sens BTUH [kW]

Power

Total BTUH [kW]

Sens BTUH [kW]

Power

Total BTUH [kW]

Sens BTUH [kW]

Power

Total BTUH [kW]

Sens BTUH [kW]

Power

Total BTUH [kW]

Sens BTUH [kW]

Power

DR —Depression ratio dbE —Entering air dry bulb wbE —Entering air wet bulb

4800 [2266]

.0

156.5 [45.9]

105.2 [30.8]

7.1

152.4 [44.7]

103.7 [30.4]

7.5

148.2 [43.4]

101.8 [29.8]

7.9

143.8 [42.1]

99.6 [29.2]

8.3

139.3 [40.8]

97.2 [28.5]

8.8

134.7 [39.5]

94.4 [27.7]

9.3

129.9 [38.1]

91.3 [26.8]

9.8

125.0 [36.6]

87.8 [25.7]

10.4

119.9 [35.1]

84.0 [24.6]

11.0

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

71°F [21.7°C] 67°F [19.4°C]

3575 [1687]

.04

3200 [1510]

.07

4800 [2266]

.0

3575 [1687]

.04

147.3 [43.2]

81.5 [23.9]

6.9

143.5 [42.0]

80.5 [23.6]

7.2

139.5 [40.9]

79.1 [23.2]

7.6

135.4 [39.7]

77.5 [22.7]

8.1

131.2 [38.4]

75.7 [22.2]

8.5

126.8 [37.2]

73.5 [21.5]

9.0

122.3 [35.8]

71.1 [20.8]

9.5

117.6 [34.5]

68.3 [20.0]

10.1

112.9 [33.1]

65.4 [19.2]

10.6

144.5 [42.3]

74.8 [21.9]

6.8

140.7 [41.2]

73.9 [21.7]

7.2

136.8 [40.1]

72.7 [21.3]

7.6

132.8 [38.9]

71.2 [20.9]

8.0

128.7 [37.7]

69.6 [20.4]

8.5

124.4 [36.4]

67.6 [19.8]

8.9

120.0 [35.2]

65.4 [19.2]

9.4

115.4 [33.8]

62.9 [18.4]

10.0

110.7 [32.4]

60.1 [17.6]

10.5

Total —Total capacity x 1000 BTUH

Sens —Sensible capacity x 1000 BTUH

Power —KW input

148.9 [43.6]

123.2 [36.1]

7.0

144.9 [42.5]

121.8 [35.7]

7.3

140.6 [41.2]

119.8 [35.1]

7.8

136.3 [39.9]

117.7 [34.5]

8.2

131.8 [38.6]

115.3 [33.8]

8.7

127.2 [37.3]

112.5 [33.0]

9.2

122.4 [35.9]

109.4 [32.1]

9.7

117.4 [34.4]

105.8 [31.0]

10.3

112.3 [32.9]

102.0 [29.9]

10.9

140.2 [41.1]

97.5 [28.6]

6.8

136.4 [40.0]

96.5 [28.3]

7.1

132.4 [38.8]

95.1 [27.9]

7.5

128.3 [37.6]

93.5 [27.4]

8.0

124.1 [36.4]

91.7 [26.9]

8.4

119.7 [35.1]

89.5 [26.2]

8.9

115.2 [33.8]

87.1 [25.5]

9.4

110.5 [32.4]

84.3 [24.7]

10.0

105.7 [31.0]

81.3 [23.8]

10.5

3200 [1510]

.07

137.5 [40.3]

90.2 [26.4]

6.7

133.8 [39.2]

89.3 [26.2]

7.1

129.9 [38.1]

88.1 [25.8]

7.5

125.9 [36.9]

86.6 [25.4]

7.9

121.7 [35.7]

84.9 [24.9]

8.3

117.4 [34.4]

82.9 [24.3]

8.8

113.0 [33.1]

80.7 [23.6]

9.3

108.4 [31.8]

78.2 [22.9]

9.9

103.7 [30.4]

75.4 [22.1]

10.4

4800 [2266]

.0

142.7 [41.8]

137.2 [40.2]

6.9

138.7 [40.6]

135.8 [39.8]

7.2

134.5 [39.4]

134.1 [39.3]

7.7

130.1 [38.1]

130.1 [38.1]

8.1

125.6 [36.8]

125.6 [36.8]

8.6

121.0 [35.5]

121.0 [35.5]

9.1

116.2 [34.0]

116.2 [34.0]

9.6

111.2 [32.6]

111.2 [32.6]

10.2

106.1 [31.1]

106.1 [31.1]

10.7

63°F [17.2°C]

3575 [1687]

.04

134.4 [39.4]

110.0 [32.2]

6.7

130.5 [38.2]

108.9 [31.9]

7.0

126.6 [37.1]

107.7 [31.6]

7.4

122.5 [35.9]

106.1 [31.1]

7.9

118.2 [34.6]

104.2 [30.5]

8.3

113.9 [33.4]

102.1 [29.9]

8.8

109.4 [32.1]

99.7 [29.2]

9.3

104.7 [30.7]

96.9 [28.4]

9.9

99.9 [29.3]

93.9 [27.5]

10.4

3200 [1510]

.07

131.8 [38.6]

102.1 [29.9]

6.6

128.0 [37.5]

101.2 [29.7]

7.0

124.2 [36.4]

100.1 [29.3]

7.4

120.1 [35.2]

98.6 [28.9]

7.8

116.0 [34.0]

97.0 [28.4]

8.2

111.7 [32.7]

95.0 [27.8]

8.7

107.3 [31.4]

92.8 [27.2]

9.2

102.7 [30.1]

90.3 [26.5]

9.8

98.0 [28.7]

87.5 [25.6]

10.3

NOTES:

➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

[ ] Designates Metric Conversions

16

Air

Airflow Performance

RLRL-C/H Series

17

Air

Airflow Performance

RLRL-C/H Series

18

Air

Airflow Performance

RLRL-C/H Series

19

Air

Airflow Performance

RLRL-C/H Series

20

Air

Electrical Data

RLRL-C/H Series

Unit Operating

Voltage Range

Volts

Minimum Circuit Ampacity

Minimum Overcurrent

Protection Device Size

Maximum Overcurrent

Protection Device Size

No.

Volts

Phase

RPM

HP, Compressor 1

Amps (RLA), Comp. 1

Amps (LRA), Comp. 1

HP, Compressor 2

Amps (RLA), Comp. 2

Amps (LRA), Comp. 2

No.

Volts

Phase

HP

Amps (FLA, each)

Amps (LRA, each)

No.

Volts

Phase

HP

Amps (FLA, each)

Amps (LRA, each)

C090CL

H090CR

187-253

208/230

44/44

50/50

50/50

2

200/240

3

3450

3 1/4

13.6/13.6

83.1/83.1

3 1/4

13.6/13.6

83.1/83.1

2

208/230

1

1/3

2.4/2.4

4.7/4.7

1

208/230

3

2

8/8

56/56

ELECTRICAL DATA – RLRL- SERIES

C090CM

H090CS

C090CN

H090CT

C090DL

H090DR

C090DM

H090DS

187-253

208/230

44/44

187-253

208/230

49/49

414-506

460

21

414-506

460

21

C090DN

H090DT

414-506

460

24

50/50 60/60 25 25 30

50/50

2

200/240

3

3450

3 1/4

13.6/13.6

83.1/83.1

3 1/4

13.6/13.6

83.1/83.1

2

208/230

1

1/3

2.4/2.4

4.7/4.7

1

208/230

3

2

8/8

56/56

60/60

2

200/240

3

3450

3 1/4

13.6/13.6

83.1/83.1

3 1/4

13.6/13.6

83.1/83.1

2

208/230

1

1/3

2.4/2.4

4.7/4.7

1

208/230

3

3

13/13

74.5/74.5

25

1

1/3

1.4

2.4

1

460

3

2

4

28

3 1/4

6.1

41

2

460

2

480

3

3450

3 1/4

6.1

41

25

1

1/3

1.4

2.4

1

460

3

2

4

28

3 1/4

6.1

41

2

460

2

480

3

3450

3 1/4

6.1

41

30

3

3

7

38.1

1

1/3

1.4

2.4

1

460

3 1/4

6.1

41

2

460

2

480

3

3450

3 1/4

6.1

41

C090YL

518-632

575

16

20

20

1

1/3

1

1.5

1

575

3

2

4

19

3 1/4

4.2

33

2

575

2

600

3

3450

3 1/4

4.2

33

C090YN

518-632

575

21

25

25

1

1/3

1

1.5

1

575

3

3

8

20

3 1/4

4.2

33

2

575

2

600

3

3450

3 1/4

4.2

33

C090YM

518-632

575

16

20

20

1

1/3

1

1.5

1

575

3

2

4

19

3 1/4

4.2

33

2

575

2

600

3

3450

3 1/4

4.2

33

21

Air

Electrical Data

RLRL-C/H Series

Unit Operating

Voltage Range

Volts

Minimum Circuit Ampacity

Minimum Overcurrent

Protection Device Size

Maximum Overcurrent

Protection Device Size

No.

Volts

Phase

RPM

HP, Compressor 1

Amps (RLA), Comp. 1

Amps (LRA), Comp. 1

HP, Compressor 2

Amps (RLA), Comp. 2

Amps (LRA), Comp. 2

No.

Volts

Phase

HP

Amps (FLA, each)

Amps (LRA, each)

No.

Volts

Phase

HP

Amps (FLA, each)

Amps (LRA, each)

ELECTRICAL DATA – RLRL- SERIES

C120CL

H120CR

C120CM

H120CS

C120DL

H120DR

187-253 187-253 414-506

208/230

49/49

208/230

54/54

460

23

60/60 60/60 25

60/60

2

200/240

3

3450

4 1/4

15.9/15.9

110/110

4 1/4

15.9/15.9

110/110

2

208/230

1

1/3

2.4/2.4

4.7/4.7

1

208/230

3

2

8/8

56/56

60/60

2

200/240

3

3450

4 1/4

15.9/15.9

110/110

4 1/4

15.9/15.9

110/110

2

208/230

1

1/3

2.4/2.4

4.7/4.7

1

208/230

3

3

13/13

74.5/74.5

25

1.4

2.4

1

460

3

2

4

28

2

480

3

3450

4 1/4

7.1

52

4 1/4

7.1

52

2

460

1

1/3

C120DM

H120DS

414-506

460

26

30

30

1.4

2.4

1

460

3

3

7

38.1

2

480

3

3450

4 1/4

7.1

52

4 1/4

7.1

52

2

460

1

1/3

C120YL

518-632

575

18

20

20

1

1.5

1

575

3

2

4

19

2

575

3

3450

4 1/4

5.1

39.5

4 1/4

5.1

39.5

2

575

1

1/3

C120YM

518-632

575

23

30

30

1

1.5

1

575

3

3

8

20

2

575

3

3450

4 1/4

5.1

39.5

4 1/4

5.1

39.5

2

575

1

1/3

22

Unit Operating

Voltage Range

Volts

Minimum Circuit Ampacity

Minimum Overcurrent

Protection Device Size

Maximum Overcurrent

Protection Device Size

No.

Volts

Phase

RPM

HP, Compressor 1

Amps (RLA), Comp. 1

Amps (LRA), Comp. 1

HP, Compressor 2

Amps (RLA), Comp. 2

Amps (LRA), Comp. 2

No.

Volts

Phase

HP

Amps (FLA, each)

Amps (LRA, each)

No.

Volts

Phase

HP

Amps (FLA, each)

Amps (LRA, each)

Air

Electrical Data

RLRL-C/H Series

ELECTRICAL DATA – RLRL- SERIES

C180CL

H180CR

C180CM

H180CS

C180DL

H180DR

187-253

208/230

75/75

187-253

208/230

79/79

414-506

460

38

90/90 90/90 45

100/100

2

200/230

3

3450

7 1/2

25/25

164/164

7 1/2

25/25

164/164

3

208/230

1

1/3

2.4/2.4

4.7/4.7

1

208/230

3

3

11.5/11.5

74.5/74.5

100/100

2

200/230

3

3450

7 1/2

25/25

164/164

7 1/2

25/25

164/164

3

208/230

1

1/3

2.4/2.4

4.7/4.7

1

208/230

3

5

14.9/14.9

82.6/82.6

50

2

460

3

3450

7 1/2

1/3

1.4

2.1

1

460

3

3

12.8

100

7 1/2

12.8

100

3

460

1

4.6

38.1

C180DM

H180DS

414-506

460

40

45

50

2

460

3

3450

7 1/2

1/3

1.4

2.4

1

460

3

5

12.8

100

7 1/2

12.8

100

3

460

1

6.6

46.3

C180YL

518-632

575

29

35

35

2

575

3

3450

7 1/2

1/3

1

1.8

1

575

3

3

9.6

78

7 1/2

9.6

78

3

575

1

3.5

20

C180YM

518-632

575

30

35

35

2

575

3

3450

7 1/2

1/3

1

1.8

1

575

3

5

9.6

78

7 1/2

9.6

78

3

575

1

5.3

39.4

23

Air

Electrical Data

RLRL-C/H Series

Unit Operating

Voltage Range

Volts

Minimum Circuit Ampacity

Minimum Overcurrent

Protection Device Size

Maximum Overcurrent

Protection Device Size

No.

Volts

Phase

RPM

HP, Compressor 1

Amps (RLA), Comp. 1

Amps (LRA), Comp. 1

HP, Compressor 2

Amps (RLA), Comp. 2

Amps (LRA), Comp. 2

No.

Volts

Phase

HP

Amps (FLA, each)

Amps (LRA, each)

No.

Volts

Phase

HP

Amps (FLA, each)

Amps (LRA, each)

ELECTRICAL DATA – RLRL- SERIES

C240CL

H240CR

C240CM

H240CS

C240DL

H240DR

187-253

208/230

95/95

187-253

208/230

103/103

414-506

460

49

110/110 125/125 60

110/110

2

200/230

3

3450

10

30.1/30.1

225/225

7 1/2

27.6/27.6

191/191

6

208/230

1

1/3

2.4/2.4

4.7/4.7

1

208/230

3

5

14.7/14.7

82.6/82.6

125/125

2

200/230

3

3450

10

30.1/30.1

225/225

7 1/2

27.6/27.6

191/191

6

208/230

1

1/3

2.4/2.4

4.7/4.7

1

208/230

3

7 1/2

23.1/23.1

136/136

60

2

460

3

3450

10

16.7

114

7 1/2

12.8

100

6

460

1

3

5

6.6

46.3

1/3

1.4

2.4

1

460

C240DM

H240DS

414-506

460

52

60

60

2

460

3

3450

10

16.7

114

7 1/2

12.8

100

6

460

1

1/3

1.4

2.4

1

460

3

7 1/2

9.6

67

C240YL

518-632

575

37

40

45

2

575

3

3450

10

12.2

80

7 1/2

9.6

78

6

575

1

3

5

5.3

39.4

1/3

1

1.8

1

575

C240YM

518-632

575

39

45

50

2

575

3

3450

10

12.2

80

7 1/2

9.6

78

6

575

1

1/3

1

1.8

1

575

3

7 1/2

7.8

53.8

24

Air

Electric Heater Kits

RLRL-C/H Series

25

Air

Electric Heater Kits

RLRL-C/H Series

26

Air

Electric Heater Kits

RLRL-C/H Series

27

Air

Electric Heater Kits

RLRL-C/H Series

28

Air

Electric Heater Kits

RLRL-C/H Series

29

Air

Dimensional Data

RLRL-C/H Series

PACKAGE AIR CONDITIONER

[ ] Designates Metric Conversions

30

Illustration

ST-A0715-03-X1

BOTTOM VIEW

Illustration

ST-A0734-03

PACKAGE AIR CONDITIONER

SUPPLY AND RETURN DIMENSIONS FOR HORIZONTAL APPLICATIONS

Air

Dimensional Data

RLRL-C/H Series

*RECOMMENDED DUCT DIMENSIONS ARE 26"

SUPPLY AND RETURN DIMENSIONS FOR DOWNFLOW APPLICATIONS

Illustration

ST-A0736-02-X1

Illustration

ST-A0738-02

[ ] Designates Metric Conversions

31

Air

Dimensional Data

RLRL-C/H Series

PACKAGE AIR CONDITIONER

[ ] Designates Metric Conversions

32

WEIGHTS

Accessory

Economizer

Power Exhaust

Fresh Air Damper (Manual)

Fresh Air Damper (Motorized)

Roof Curb 14"

Roof Curb 24"

Shipping—lbs [kg]

90 [40.82]

44 [19.96]

26 [11.79]

43 [19.50]

90 [40.82]

140 [63.50]

Operating—lbs [kg]

81 [36.70]

42 [19.05]

21 [9.53]

38 [17.24]

85 [38.60]

135 [61.23]

Air

Dimensional Data

RLRL-C/H Series

Capacity Tons [kW]

6-12.5 [21.1-44.0]

Corner Weights by Percentage

A B C D

33% 27% 17% 23%

A074403

Illustration

A074403

CLEARANCES

The following minimum clearances must be observed for proper unit performance and serviceability.

Recommended

Clearance In. [mm]

48 [1219]

18 [457]

18 [457]

18 [457]

60 [1524]

Location

A - Front

B - Condenser Coil

C - Duct Side

*D - Evaporator End

E - Above

*Without Economizer. 48" [1219 mm] With Economizer

[ ] Designates Metric Conversions

33

Air

Accessories

RLRL-C/H Series

FIELD INSTALLED ACCESSORY EQUIPMENT

Thermostats

Electric Heaters

Economizer w/Single Enthalpy

Economizer w/Single Enthalpy and Smoke Dectector

Dual Enthalpy Kit

Horizontal Economizer w/Single Enthalpy

Carbon Dioxide Sensor

Power Exhaust

Manual Fresh Air (Left Panel Mounted)

Manual Fresh Air (Return Panel)

Motorized Fresh Air (Return Panel)

Motor Kit for RXRF-KDA1 (Left Panel Mounted)

Modulating Motor Kit w/position feedback for RXRF-KDA1

Roofcurb, 14"

Roofcurb, 24"

Roofcurb Adapters

Accessory

Concentric Diffuser (Step-Down, 18 x 28)

Concentric Diffuser (Step-Down, 18 x 32)

Concentric Diffuser (Flush, 18 x 28)

Concentric Diffuser (Flush, 18 x 32)

Downflow Adapters (Rect. to Round)

Downflow Adapters (Rect. to Rect., 18 x 28)

Downflow Adapters (Rect. to Rect., 18 x 32)

Low-Ambient Control Kit (1 Per Compressor)

Outdoor Louver Kit

Outdoor Louver Kit

Unwired Convenience Outlet

Comfort Alert (1 per compressor)

BACnet Communication Card

LonWorks Communication Card

NOTES:

➀ Used with RXRN-AA61 and RXRN-AA71 concentric diffusers.

➁ Used with RXRN-AA66 and RXRN-AA76 concentric diffusers.

Model

Number

Shipping

Weight

Lbs. [kg]

Installed

Weight

Lbs. [kg]

See Thermostat Specification Sheet for Details (T11-001)

RXJJ-CC10 (C,D,Y)

RXJJ-CC15 (C,D,Y)

46 [20.9] 0

46 [20.9] 0

36 [16.3]

36 [16.3]

RXJJ-CC20 (C,D,Y)

RXJJ-CC30 (C,D,Y)

RXJJ-CC40 (C,D,Y)

RXJJ-CC50 (C,D,Y)

AXRD-PJCM3

46 [20.9] 0

47 [21.3] 0

49 [22.2] 0

51 [23.1] 0

90 [40.8] 0

91 [41.3] 0

36 [16.3]

37 [16.8]

39 [17.7]

41 [18.6]

81 [36.7]

AXRD-SJCM3

RXRX-AV03

AXRD-RJCM3

RXRX-AR02

RXRX-BFF02 (C,D,Y)

AXRF-KDA1

AXRF-JDA1

AXRF-JDB1

RXRX-AW02

1 [0.5]

94 [42.6]

3 [1.4]

43 [19.5]

38 [17.2]

26 [11.8]

43 [19.5]

35 [15.19]

0

0

0

0

0

0

0

0

82 [37.2]

1 [0.5]

89 [40.4]

2 [1.0]

38 [17.2]

31 [14.0]

21 [9.5]

21 [9.5]

27 [17.7]

RXRX-AW04

RXKG-CAE14

RXKG-CAE24

RXRX-CDCE50

RXRX-CFCE54

RXRX-CFCE56

RXRX-CGCC12

RXRN-AA61

RXRN-AA66

RXRN-AA71

RXRN-AA76

RXMC-CD04

RXMC-CE05

RXMC-CF06

RXRZ-C02

AXRX-AAD02A (7.5 Ton)

AXRX-AAD03A (10 Ton)

RXRX-AN01

RXRX-AZ01

RXRX-AY01

RXRX-AY02

38 [17.2]

3 [1.4]

1 [0.5]

1 [0.5]

0

90 [40.8] 0

140 [63.5] 0

300 [136.1] 0

325 [147.4] 0

350 [158.8] 0

450 [204.1] 0

200 [90.7] 0

247 [112.0] 0

170 [77.1] 0

176 [79.8] 0

15 [6.8] 0

18 [8.2] 0

20 [9.1] 0

3 [1.4] 0

29 [13.1] 0

32 [14.5] 0

2 [1.0] 0

0

0

0

30 [13.6]

85 [38.5]

135 [61.2]

290 [131.5]

315 [142.9]

340 [154.2]

410 [186.0]

185 [83.9]

227 [103.0]

155 [70.3]

161 [73.0]

13 [5.9]

16 [7.3]

18 [8.2]

2 [1.0]

26 [11.8]

28 [12.7]

1.5 [0.7]

2 [0.9]

1 [0.5]

1 [0.5]

[ ] Designates Metric Conversions

Factory

Installation

Available?

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

No

No

No

No

Yes

Yes

Yes

No

No

No

No

Yes

Yes

No

No

No

No

No

No

No

No

No

34

THERMOSTAT

200-Series *

Programmable

300-Series *

Deluxe

Programmable

400-Series *

Special Applications/

Programmable

500-Series *

Communicating/

Programmable

* Photos are representative. Actual models may vary.

For detailed thermostat match-up information, see specification sheet form number T11-001.

Air

Accessories

RLRL-C/H Series

35

Air

Accessories

RLRL-C/H Series

FLUSH MOUNT ROOM TEMPERATURE SENSORS FOR

NETWORKED DDC APPLICATIONS

ROOM TEMPERATURE SENSOR with TIMED OVERRIDE BUTTON

ZNS-101

10k

Ω room temperature sensor transmits room temperature to DDC system. Timed override button allows tenant to change from unoccupied temperature setpoint to occupied temperature setpoint for a preset time.

ROOM TEMPERATURE SENSOR ZNS-102 with TIMED OVERRIDE BUTTON and STATUS INDICATOR

10k

Ω room temperature sensor transmits room temperature to DDC system. Timed override button allows tenant to change from unoccupied temperature setpoint to occupied temperature setpoint for a preset time. Status Indicator Light transmits ALARM flash code to occupied space.

ROOM TEMPERATURE SENSOR ZNS-103 with SETPOINT ADJUSTMENT and TIMED OVERRIDE BUTTON

10k

Ω room temperature sensor with setpoint adjustment transmits room temperature to DDC system along with desired occupied room temperature setpoint. Timed override button allows tenant to change from unoccupied temperature setpoint to occupied temperature setpoint for a preset time.

COMMUNICATION CARDS

Field Installed

BACnet ® COMMUNICATION CARD RXRX-AY01

The field installed BACnet ® Communication Card allows the RTU-C unit controller to communicate with a third party building management system that supports the BACnet Application Specific Controller device profile. The BACnet ® Communication Module plugs onto the unit RTU-C controller and allows communication between the RTU-C and the BACnet MSTP network.

LonWorks ® COMMUNICATION CARD RXRX-AY02

The field installed LonWorks ® Communication Card allows the RTU-C unit controller to communicate with a third party building management system that supports the LonMark Space Comfort Controller

(SCC) functional profile or LonMark Discharge Air Controller (DAC) functional profile. The LonMark

Communication Module plugs onto the RTU-C controller and allows communication between the

RTU-C and a LonWorks Network.

36

ECONOMIZER FOR DOWNFLOW DUCT INSTALLATION

Use to Select Factory Installed Options Only

AXRD-PJCM3—Single Enthalpy (Outdoor) and AXRD-SJCM3 Single Enthalpy with Smoke Detector

RXRX-AV03—Dual Enthalpy Upgrade Kit

RXRX-AR02—Optional Wall-Mounted CO

2

Sensor

Features Honeywell Controls

Available Factory Installed or Field Accessory

Gear Driven Direct Drive Actuator

Fully Modulating (0-100%)

Low Leakage Dampers

Slip-In Design for Easy Installation

Plug-In Polarized 12-pin and 4-pin Electrical Connections

Pre-Configured—No Field Adjustments Necessary

Standard Barometric Relief Damper

Single Enthalpy with Dual Enthalpy Upgrade

Kit Available

CO

2

Input Sensor Available

Field Assembled Hood Ships with Economizer

Economizer Ships Complete for Downflow Duct

Application.

Optional Remote Minimum Position Potentiometer

(270 ohm) (Honeywell #S963B1136) is Available from Prostock.

Field Installed Power Exhaust Available

Prewired for Smoke Detector

If connected to a Building Automation System (BAS), all economizer functions can be viewed on the (BAS) or 16 x 2 LCD screen

If connected to thermostat, all economizer functions can be viewed on 16 x 2 LCD screen

Air

Accessories

RLRL-C/H Series

Illustration

ADS-7949-11

[ ] Designates Metric Conversions

37

Air

Accessories

RLRL-C/H Series

ECONOMIZER FOR HORIZONTAL DUCT INSTALLATION

Field Installed Only

AXRD-RJCM3—Single Enthalpy (Outdoor)

RXRX-AV03—Dual Enthalpy Upgrade Kit

RXRX-AR02—Wall-mounted CO

2

Sensor

Features Honeywell Controls

Available as a Field Installed Accessory Only

Gear Driven Direct Drive Actuator

Fully Modulating (0-100%)

Low Leakage Dampers

Slip-In Design for Easy Installation

Plug-In Polarized 12-pin and 4-pin Electrical

Connections

Pre-Configured—No Field Adjustments Necessary

Standard Barometric Relief Damper

Single Enthalpy with Dual Enthalpy Upgrade

Kit Available

CO

2

Input Sensor Available

Field Assembled Hood Ships with Economizer

Economizer Ships Complete for

Horizontal Duct Application

Optional Remote Minimum Position Potentiometer

(270 ohm) (Honeywell #S963B1136) is Available from Prostock

Field Installed Power Exhaust Available

If connected to a Building Automation System (BAS), all economizer functions can be viewed on the (BAS) or

16 x 2 LCD screen

If connected to thermostat, all economizer functions can be viewed on 16 x 2 LCD screen

[ ] Designates Metric Conversions

38

Air

Accessories

RLRL-C/H Series

POWER EXHAUST KIT FOR AXRD-PJCM3(-), AXRD-RJCM3(-), AXRD-SJCM3

ECONOMIZERS

R XRX-BFF02 (C, D, or Y*)

*Voltage Code

VERTICAL AIRFLOW

Illustration

STA1000-02

HORIZONTAL AIRFLOW

Model No.

No.

of Fans

Volts Phase

RXRX-BFF02C

RXRX-BFF02D

RXRX-BFF02Y

2

2

2

208-230

460

575

NOTES:

➀ Power exhaust is factory set on high speed motor tap.

➁ CFM is per fan at 0" w.c. external static pressure.

1

1

1

HP

(ea.)

0.33

0.33

0.33

Low Speed

CFM [L/s]

2200 [1038]

2200 [1038]

2200 [1038]

RPM

1518

1518

1518

Illustration

STA1000-01

High Speed

CFM [L/s]

RPM

2500 [1179] 1670

2500 [1179]

2500 [1179]

1670

1670

FLA

(ea.)

1.48

0.75

0.81

LRA

(ea.)

3.6

1.8

1.5

[ ] Designates Metric Conversions

39

Air

Accessories

RLRL-C/H Series

FRESH AIR DAMPER

MOTORIZED DAMPER KIT

RXRX-AW02

(Motor Kit for AXRF-KDA1)

RXRX-AW04

(Modulating Motor Kit with position feedback for AXRF-KDA1)

795

1-1

7a

AXRF-KDA1 (Manual)

DOWNFLOW OR

HORIZONTAL APPLICATION

Illustration

ST-A0886-38

Illustration

ST-7951-17

MOTORIZED DAMPER KIT

RXRX-AW02

(Motor Kit for AXRF-KDA1)

RXRX-AW04

(Modulating Motor Kit w/position feedback for AXRF-KDA1)

Features Honeywell Controls

Gear Driven Direct Drive Actuator

Fully Modulating (0-100%)

Low Leakage Dampers

Slip-In Design for Easy Installation

Plug-In Polarized 12-pin and 4-pin Electrical Connections

Pre-Configured—No Field Adjustments Necessary

Addition of Dual Enthalpy Upgrade Kit allows limited economizer function

CO

2

Sensor Input Available for Demand Control Ventilation (DCV)

Optional Remote Minimum Position Potentiometer (270 ohm) (Honeywell #S963B1136) is available from Prostock

All fresh air damper functions can be viewed at the RTU-C unit controller display

If connected to a Building Automation System (BAS), all fresh air damper functions can be viewed on the (BAS)

[ ] Designates Metric Conversions

40

FRESH AIR DAMPER (Cont.)

AXRF-JDA1 (Manual)

AXRF-JDB1 (Motorized)

Air

Accessories

RLRL-C/H Series

DOWNFLOW APPLICATION

Illustration

ADS-7937-58

HORIZONTAL APPLICATION

Illustration

ST-A0901-01

[ ] Designates Metric Conversions

41

Air

Accessories

RLRL-C/H Series

ROOFCURBS (Full Perimeter)

Rheem’s roofcurb design can be utilized on all 7.5-10 ton

[26.4-35.2 kW] RLRL-C/H models.

Two available heights (14" [356 mm] and

24" [610 mm]) for ALL models.

Quick assembly corners for simple and fast assembly.

Opening provided in bottom pan to match the

“Thru the Curb” electrical connection opening provided on the unit base pan.

1" [25 mm] x 4" [102 mm] Nailer provided.

Insulating panels not required because of insulated

outdoor base pan.

Sealing gasket (40' [12.2 m]) provided with Roofcurb.

Packaged for easy field assembly.

Roofcurb Model

RXKG-CAE14

RXKG-CAE24

Height of Curb

14" [356 mm]

24" [610 mm]

ROOFCURB INSTALLATION

Illustration

ST-A0743-02

TYPICAL INSTALLATION

Illustration

ST-A0743-02

Illustration

ST-A0801-17

[ ] Designates Metric Conversions

42

Air

Accessories

RLRL-C/H Series

ROOFCURB ADAPTERS

OLD MODELS

(-)RCF, (-)REF-075/076

(-)RGF-150075, (-)RGF-131076

(-)RGF-201076

(-)RGF-200075

(-)RGG, (-)REG, (-)RCG-075

(-)RGF, (-)REF, (-)RCF-085

(-)RGF, (-)REF, (-)RCF-100

(-)RGG, (-)REG, (-)RCG-100

(-)RGF, (-)REF, (-)RCF-125

(-)PDC-075

(-)PDC-100/101

OLD ROOFCURB

RXRK-E50

RXRK-E54

RXRK-E56

RXPK-C12

ROOFCURB ADAPTER

RXRX-CDCE50

RXRX-CFCE54

RXRX-CFCE56

RXRX-CGCC12

NEW MODELS

(All Share Common Cabinet)

RLRL-C/H090

RLRL-C/H120

NOTE: Ductwork modifications may be necessary if the capacity and/or indoor airflow rate of replacement unit is not equivalent to that of the unit being replaced.

RLRL-C072, C090, C102, C120, C151 fit on same roofcurb as the RLKB-A090, A102, A120, A150, A181, RLMB- A090, A102, A120, A150, RLNB- A090, A102, A120

43

Air

Accessories

RLRL-C/H Series

ROOFCURB ADAPTERS (Cont.)

RXRX-CDCE50

Illustration

ADS-7952-02

Sheet 2

TOP VIEW

Illustration

ADS-7952-02

Sheet 1

[ ] Designates Metric Conversions

44

ROOFCURB ADAPTERS (Cont.)

RXRX-CFCE54

Illustration

ADS-7952-01

Sheet 2

Illustration

ADS-7952-01

Sheet 1

[ ] Designates Metric Conversions

TOP VIEW

Air

Accessories

RLRL-C/H Series

45

Air

Accessories

RLRL-C/H Series

ROOFCURB ADAPTERS (Cont.)

RXRX-CFCE56

Illustration

ADS-7952-03

Sheet 2

TOP VIEW

Illustration

ADS-7952-03

Sheet 1

[ ] Designates Metric Conversions

46

ROOFCURB ADAPTERS (Cont.)

RXRX-CGCC12

Illustration

ADS-7952-04

Sheet 2

Air

Accessories

RLRL-C/H Series

TOP VIEW

Illustration

ADS-7952-04

Sheet 1

[ ] Designates Metric Conversions

47

Air

Accessories

RLRL-C/H Series

CONCENTRIC DIFFUSER APPLICATION

DOWNFLOW TRANSITION DRAWINGS

RXMC-CE05

Used with RXRN-AA61 or RXRN-AA71

Concentric Diffusers.

Illustration

ST-A0840-02

Illustration

ST-A0881-02

[ ] Designates Metric Conversions

48

DOWNFLOW TRANSITION DRAWINGS (Cont.)

RXMC-CF06

Used with RXRN-AA66 or RXRN-AA76

Concentric Diffusers.

Air

Accessories

RLRL-C/H Series

Illustration

ST-A0881-03

[ ] Designates Metric Conversions

49

Air

Accessories

RLRL-C/H Series

DOWNFLOW TRANSITION DRAWINGS (Cont.)

RXMC-CD04

Used with RXRN-FA65 or RXRN-FA75

Concentric Diffusers.

Illustration

ADS-7951-03

[ ] Designates Metric Conversions

795103

50

CONCENTRIC DIFFUSER—STEP DOWN

RXRN-FA65 (7.5 & 8.5 Ton [26.4 & 29.9 kW] Models)

For Use With Downflow Transition (RXMC-CD04) and 20" [508 mm] Round Supply and Return Ducts

All aluminum diffuser with aluminum return air eggcrate.

Built-in anti-sweat gasket.

Molded fiberglass supports.

Built-in hanging supports.

Diffuser box constructed of sheetmetal insulated with

1" [25.4 mm] 1.5 lbs.

[.7 kg] duct liner.

Air

Accessories

RLRL-C/H Series

ENGINEERING DATA

Model No.

Flow Rate

CFM [L/s]

Static Pressure in. w.c. [kPa]

0.17 [0.042]

0.20 [0.050]

Throw

➁ ➂

Feet [m]

24-29 [7.3-8.8] 0

RXRN-FA65

2600 [1227]

2800 [1321]

3000 [1416] 0.25 [0.062]

25-30 [7.6-9.1] 0

27-33 [8.2-10.1]

3200 [1510]

3400 [1604]

0.31 [0.077]

0.37 [0.092]

28-35 [8.5-10.7]

30-37 [9.1-11.3]

NOTES:

➀ All data is based on the air diffusion council guidelines.

➁ Throw data is based on 75 FPM Terminal Velocities using isothermal air.

➂ Throw is based on diffuser blades being directed in a straight pattern.

➃ Actual noise levels may vary due to duct design and do not include transmitted unit noise.

Adequate duct attenuation must be provided to reduce sound output from the unit.

[ ] Designates Metric Conversions

Neck Velocity fpm [m/s]

669 [3.4]

720 [3.7]

772 [3.9]

823 [4.2]

874 [4.4]

Noise Level

(dbA)

20

25

25

25

30

51

Air

Accessories

RLRL-C/H Series

CONCENTRIC DIFFUSER—STEP DOWN

18" x 28" [457.2 x 711.2 mm]

RXRN-AA61 (8.5 & 10 Ton [29.9 kW & 35.2] Models)

For Use With Downflow Transition (RXMC-CE05) and 18" x 28" [457.2 x 711.2 mm]

Supply and Return Ducts

All aluminum diffuser with aluminum return air eggcrate.

Built-in anti-sweat gasket.

Molded fiberglass supports.

Built-in hanging supports.

Diffuser box constructed of sheetmetal

insulated with 1" [25.4 mm] 1.5 lbs.

[.7 kg] duct liner.

Double deflection diffuser with the blades secured by spring steel.

Illustration

ADS-7951-08A

Illustration

ADS-7951-08B

Illustration

ADS-7951-08C

ENGINEERING DATA

Model No.

Flow Rate

CFM [L/s]

Static Pressure in w.c. [kPa]

0.17 [0.042]

0.18 [0.045]

Throw

➁ ➂

Feet [m]

25-33 [7.6-10.1]

RXRN-AA61

3600 [1699]

3800 [1793]

4000 [1888]

4200 [1982]

4400 [2076]

0.21 [0.052]

0.24 [0.060]

0.27 [0.067]

27-35 [8.2-10.7]

29-37 [8.8-11.3]

32-40 [9.8-12.2]

34-42 [10.4-12.8]

NOTES:

➀ All data is based on the air diffusion council guidelines.

➁ Throw data is based on 75 FPM Terminal Velocities using isothermal air.

➂ Throw is based on diffuser blades being directed in a straight pattern.

➃ Actual noise levels may vary due to duct design and do not include transmitted unit noise.

Adequate duct attenuation must be provided to reduce sound output from the unit.

[ ] Designates Metric Conversions

52

Neck Velocity fpm [m/s]

851 [4.3]

898 [4.6]

946 [4.8]

993 [5.0]

1040 [5.3]

Noise Level

(dbA)

30

30

30

30

30

Air

Accessories

RLRL-C/H Series

CONCENTRIC DIFFUSER—STEP DOWN

18" x 32" [457.2 x 813 mm]

RXRN-AA66 (12.5 Ton [44.0 kW] Models)

For Use With Downflow Transition (RXMC-CF06) and 18" x 32" [457.2 x 813 mm]

Supply and Return Ducts

All aluminum diffuser with aluminum return air eggcrate.

Built-in anti-sweat gasket.

Molded fiberglass supports.

Built-in hanging supports.

Diffuser box constructed of sheetmetal insulated with 1" [25.4 mm] 1.5 lbs.

[.7 kg] duct liner.

Double deflection diffuser with the blades secured by spring steel.

Illustration

ADS-7951-09A

Illustration

ADS-7951-09B

Illustration

ADS-7951-09C

ENGINEERING DATA

Model No.

Flow Rate

CFM [L/s]

4600 [2171]

4800 [2265]

5000 [2359]

Static Pressure in w.c. [kPa]

0.31 [0.077]

0.32 [0.080]

0.34 [0.085]

Throw

➁ ➂

Feet [m]

26-31 [7.9-9.4]

27-32 [8.2-9.8]

28-33 [8.5-10.1] RXRN-AA66

5200 [2454] 0.36 [0.090]

5400 [2548] 0.39 [0.097]

NOTES:

➀ All data is based on the air diffusion council guidelines.

➁ Throw data is based on 75 FPM Terminal Velocities using isothermal air.

➂ Throw is based on diffuser blades being directed in a straight pattern.

➃ Actual noise levels may vary due to duct design and do not include transmitted unit noise.

Adequate duct attenuation must be provided to reduce sound output from the unit.

28-34 [8.5-10.4]

29-35 [8.8-10.7]

[ ] Designates Metric Conversions

Neck Velocity fpm [m/s]

841 [4.3]

878 [4.5]

915 [4.6]

951 [4.8]

988 [6.0]

Noise Level

(dbA)

30

30

30

30

30

53

Air

Accessories

RLRL-C/H Series

FLUSH MOUNT CONCENTRIC DIFFUSER—FLUSH

RXRN-FA75 (7.5 & 8.5 Ton [26.4 & 29.9 kW] Models)

For Use With Downflow Transition (RXMC-CD04) and 20" [508 mm] Round Supply and Return Ducts

All aluminum diffuser with aluminum return air eggcrate.

Built-in anti-sweat gasket.

Molded fiberglass supports.

Built-in hanging supports.

Diffuser box constructed of sheetmetal insulated with

1" [25.4 mm] 1.5 lbs.

[.7 kg] duct liner.

Illustration

ADS-5348-04

ENGINEERING DATA

Model No.

Flow Rate

CFM [L/s]

2600 [1227]

2800 [1321]

3000 [1416]

Static Pressure in. w.c. [kPa]

.17 [0.042]

.20 [0.050]

.25 [0.062]

Throw

➁ ➂

Feet [m]

19-24 [5.8-7.3]

20-28 [6.1-8.5]

21-29 [6.4-8.8] RXRN-FA75

3200 [1510] .31 [0.077] 22-29 [6.7-8.8]

3400 [1604] .37 [0.092] 22-30 [6.7-9.1]

NOTES:

➀ All data is based on the air diffusion council guidelines.

➁ Throw data is based on 75 FPM Terminal Velocities using isothermal air.

➂ Throw is based on diffuser blades being directed in a straight pattern.

➃ Actual noise levels may vary due to duct design and do not include transmitted unit noise.

Adequate duct attenuation must be provided to reduce sound output from the unit.

[ ] Designates Metric Conversions

Neck Velocity fpm [m/s]

663 [3.4]

714 [3.6]

765 [3.9]

816 [4.1]

867 [4.4]

Noise Level

(dbA)

30

35

35

40

40

54

Air

Accessories

RLRL-C/H Series

CONCENTRIC DIFFUSER—FLUSH and 18" x 28" [457.2 x 711.2 mm]

RXRN-AA71 (8.5 & 10 Ton [29.9 & 35.2] Models)

For Use With Downflow Transition (RXMC-CE05) and 18" x 28" [457.2 x 711.2 mm]

Supply and Return Ducts

All aluminum diffuser with aluminum return air eggcrate.

Built-in anti-sweat gasket.

Molded fiberglass supports.

Built-in hanging supports.

Diffuser box constructed of sheetmetal insulated with 1" [25.4 mm] 1.5 lbs.

[.7 kg] duct liner.

Illustration

ADS-7951-06A

Illustration

ADS-7951-06B

Illustration

ADS-7951-06C

ENGINEERING DATA

Model No.

Flow Rate

CFM [L/s]

Static Pressure in w.c. [kPa]

0.17 [0.042]

0.18 [0.045]

Throw

➁ ➂

Feet [m]

22-29 [6.7-8.8]

RXRN-AA71

3600 [1699]

3800 [1793]

4000 [1888]

4200 [1982]

4400 [2076]

0.21 [0.052]

0.24 [0.060]

0.27 [0.067]

22-30 [6.7-9.1]

24-33 [7.3-10.1]

26-35 [7.9-10.7]

28-37 [8.5-11.3]

NOTES:

➀ All data is based on the air diffusion council guidelines.

➁ Throw data is based on 75 FPM Terminal Velocities using isothermal air.

➂ Throw is based on diffuser blades being directed in a straight pattern.

➃ Actual noise levels may vary due to duct design and do not include transmitted unit noise.

Adequate duct attenuation must be provided to reduce sound output from the unit.

[ ] Designates Metric Conversions

Neck Velocity fpm [m/s]

844 [4.3]

891 [4.5]

938 [4.8]

985 [5.0]

1032 [5.2]

Noise Level

(dbA)

35

40

40

40

40

55

Air

Accessories

RLRL-C/H Series

CONCENTRIC DIFFUSER—FLUSH

18" x 32" [457.2 x 813 mm]

RXRN-AA76 (12.5 Ton [44.0 kW] Models)

For Use With Downflow Transition (RXMC-CF06) and 18" x 32" [457.2 x 813 mm]

Supply and Return Ducts

All aluminum diffuser with aluminum return air eggcrate.

Built-in anti-sweat gasket.

Molded fiberglass supports.

Built-in hanging supports.

Diffuser box constructed of sheetmetal insulated with 1" [25.4 mm] 1.5 lbs.

[.7 kg] duct liner.

Illustration

ADS-7951-07A

Illustration

ADS-7951-07B

Illustration

ADS-7951-07C

ENGINEERING DATA

Model No.

Flow Rate

CFM [L/s]

4600 [2171]

4800 [2265]

Static Pressure in w.c. [kPa]

0.31 [0.077]

0.32 [0.080]

RXRN-AA76 5000 [2359]

5200 [2454]

0.34 [0.085]

0.36 [0.090]

5400 [2548] 0.39 [0.097]

NOTES:

➀ All data is based on the air diffusion council guidelines.

➁ Throw data is based on 75 FPM Terminal Velocities using isothermal air.

➂ Throw is based on diffuser blades being directed in a straight pattern.

➃ Actual noise levels may vary due to duct design and do not include transmitted unit noise.

Adequate duct attenuation must be provided to reduce sound output from the unit.

Throw

➁ ➂

Feet [m]

25-34 [7.6-10.4]

26-35 [7.9-10.7]

27-36 [8.2-11.0]

30-39 [9.1-11.9]

32-41 [9.8-12.5]

[ ] Designates Metric Conversions

Neck Velocity fpm [m/s]

922 [4.7]

962 [4.9]

1002 [5.1]

1043 [5.3]

1083 [5.5]

Noise Level

(dbA)

40

40

40

45

45

56

Air

Mechanical Specifications

RLRL-C/H Series

GUIDE SPECIFICATIONS – RLRL-C/H090 and 120

You may copy this document directly into your building specification. This specification is written to comply with the 2004 version of the

“master format” as published by the Construction Specification Institute. www.csinet.org.

ELECTRIC HEAT PACKAGED ROOFTOP

HVAC Guide Specifications

Size Range: 6 to 12.5 Nominal Tons

Section Description

23 06 80 Schedules for Decentralized HVAC Equipment

23 06 80.13

Decentralized Unitary HVAC Equipment Schedule

23 06 80.13.A. Rooftop unit schedule

1. Schedule is per the project specification requirements.

23 07 16 HVAC Equipment Insulation

23 07 16.13

Decentralized, Rooftop Units:

1. Interior cabinet surfaces shall be insulated with a minimum 3/4-in. thick, minimum 1-1/2 lb density, flexible fiberglass insulation bonded with a phenolic binder, with aluminum foil facing on the air side.

2. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.

23 09 13 Instrumentation and Control Devices for HVAC

23 09 13.23

Sensors and Transmitters

23 09 13.23.A. Thermostats

1. Thermostat must a. have capability to energize 2 different stages of cooling, and 2 different stages of heating.

b. must include capability for occupancy scheduling.

23 09 23 Direct-digital Control system for HVAC

23 09 23.13

Decentralized, Rooftop Units:

23 09 23.13.A. RTU-C controller

1. Shall be ASHRAE 62-2001 compliant.

2. Shall accept 18-32VAC input power.

3. Shall have an operating temperature range from -40ºF (-40ºC) to 158ºF (70ºC), 10% - 95% RH (non-condensing).

4. Controller shall accept the following inputs: space temperature, setpoint adjustment, outdoor air temperature, indoor air quality, outdoor air enthalpy, fire shutdown, return air enthalpy, fan status, remote time clock/door switch.

5. Shall accept a CO

2 sensor in the conditioned space, and be Demand Control Ventilation (DCV) ready.

6. Shall provide the following outputs: Economizer, fan, cooling stage 1, cooling stage 2, heat stage 1, heat stage 2, exhaust, occupied.

7. Unit shall provide surge protection for the controller through a circuit breaker.

8. Shall have a field installed communication card allowing the unit to be Internet capable, and communicate at a Baud rate of

19.2K or faster

9. Shall have an LED display independently showing the status of activity on the communication bus, and processor operation.

10. Shall have either a field installed BACnet ® plug-in communication card which includes an EIA-485 protocol communication port, or a field installed LonWorks ™ plug-in communications card.

11. Software upgrades will be accomplished by local download. Software upgrades through chip replacements are not allowed.

12. Shall be shock resistant in all planes to 5G peak, 11ms during operation, and 100G peak, 11ms during storage.

13. Shall be vibration resistant in all planes to 1.5G @ 20-300 Hz.

14. Shall support a bus length of 4000 ft max, 60 devices per 1000 ft section, and 1 RS-485 repeater per 1000 ft sections.

23 09 23.13.B. Open protocol, direct digital controller:

1. Shall be ASHRAE 62-2001 compliant.

2. Shall accept 18-30VAC, 50-60Hz, and consumer 15VA or less power.

3. Shall have an operating temperature range from -40ºF (-40ºC) to 130ºF (54ºC), 10% - 90% RH (non-condensing).

4. Shall have either a field installed BACnet ® plug-in communication card which includes an EIA-485 protocol communication port, or a field installed LonWorks ™ plug-in communications card.

5. The BACnet ® plug in communication card shall include built-in protocol for BACNET (MS/TP and PTP modes)

6. The LonWorks

™ plug in communication card shall include the Echelon processor required for all Lon applications.

7. Shall allow access of up to 62 network variables (SNVT). Shall be compatible with all open controllers

8. Baud rate Controller shall be selectable through the EIA-485 protocol communication port.

9. Shall have an LED display independently showing the status of serial communication, running, errors, power, all digital outputs, and all analog inputs.

10. Shall accept the following inputs: space temperature, setpoint adjustment, outdoor air temperature, indoor air quality, outdoor air enthalpy, compressor lock-out, fire shutdown, enthalpy switch, and fan status/filter status/ humidity/ remote occupancy.

11. Shall provide the following outputs: economizer, fan, cooling stage 1, cooling stage 2, heat stage 1, heat stage 2, exhaust.

12. Software upgrades will be accomplished by either local or remote download. No software upgrades through chip replacements are allowed.

57

Air

Mechanical Specifications

RLRL-C/H Series

23 09 33 Electric and Electronic Control System for HVAC

23 09 33.13

Decentralized, Rooftop Units:

23 09 33.13.A. General:

1. Shall be complete with self-contained low-voltage control circuit protected by a resettable circuit breaker on the 24-v transformer side. Transformer shall have 100VA capabilities.

2. Shall utilize color-coded wiring.

3. Shall include a central control terminal board to conveniently and safely provide connection points for vital control functions such as: smoke detectors, phase monitor, economizer, thermostat, DDC control options, loss of charge, freeze sensor, high pressure switches.

4. Unit shall include a minimum of one 10-pin screw terminal connection board for connection of control wiring.

23 09 33.23.B. Safeties:

1. Compressor over-temperature, over current.

2. Loss of charge switch. a. Units with 2 compressors shall have different colored wires for the circuit 1 and circuit 2 low and high pressure switches.

b. Loss of charge switch shall use different color wire than the high pressure switch. The purpose is to assist the installer and service technician to correctly wire and or troubleshoot the rooftop unit.

c. Loss of charge switch shall have a different sized connector than the high pressure switch. They shall physically prevent the cross-wiring of the safety switches between the high and low pressure side of the system.

3. High-pressure switch.

a. Units with 2 compressors shall have different colored wires for the circuit 1 and circuit 2 low and high pressure switches.

b. High pressure switch shall use different color wire than the low pressure switch. The purpose is to assist the installer and service person to correctly wire and or troubleshoot the rooftop unit.

c. High pressure switch shall have a different sized connector than the loss of charge switch. They shall physically prevent the cross-wiring of the safety switches between the high and low pressure side of the system.

4. Freeze protection sensor, evaporator coil.

5. Automatic reset, motor thermal overload protector.

23 09 93 Sequence of Operations for HVAC Controls

23 09 93.13

Decentralized, Rooftop Units:

23 09 93.13

INSERT SEQUENCE OF OPERATION

23 40 13 Panel Air Filters

23 40 13.13

Decentralized, Rooftop Units:

23 40 13.13.A. Standard filter section shall

1. Shall consist of factory-installed, low velocity, throwaway 2-in. thick fiberglass filters of commercially available sizes.

2. Filters shall be accessible through an access panel as described in the unit cabinet section of this specification

23 81 19

(23 81 19.13.H).

Self-Contained Air Conditioners

23 81 19.13

Small-Capacity Self-Contained Air Conditioners

23 81 19.13.A. General

1. Outdoor, rooftop mounted, electrically controlled, heating and cooling unit utilizing a(n) hermetic scroll compressor(s) for cooling duty and heat pump for heating duty.

2. Factory assembled, single-piece heating and cooling rooftop unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, and special features required prior to field start-up.

3. Unit shall use environmentally sound R-410a refrigerant.

4. Unit shall be installed in accordance with the manufacturer’s instructions.

5. Unit must be selected and installed in compliance with local, state, and federal codes.

23 81 19.13.B. Quality Assurance

1. Unit meets ASHRAE 90.1-2004 minimum efficiency requirements.

2. 3 phase units are Energy Star qualified.

3. Unit shall be rated in accordance with AHRI Standards 210/240 and 340/360.

4. Unit shall be designed to conform to ASHRAE 15, 2001.

5. Unit shall be UL-tested and certified in accordance with ANSI Z21.47 Standards and UL-listed and certified under Canadian standards as a total package for safety requirements.

6. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.

7. Unit casing shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen).

8. Unit casing shall be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 5000-hour salt spray.

9. Unit shall be designed in accordance with ISO 9001:2000, and shall be manufactured in a facility registered by ISO 9001:2000.

10. Roof curb shall be designed to conform to NRCA Standards.

11. Unit shall be subjected to a completely automated run test on the assembly line. The data for each unit will be stored at the factory, and must be available upon request.

12. Unit shall be designed in accordance with UL Standard 1995, including tested to withstand rain.

13. Unit shall be constructed to prevent intrusion of snow and tested to prevent snow intrusion into the control box up to 40 mph.

58

Air

Mechanical Specifications

RLRL-C/H Series

23 81 19.13.C. Delivery, Storage, and Handling

1. Unit shall be stored and handled per manufacturer’s recommendations.

2. Lifted by crane requires either shipping top panel or spreader bars.

3. Unit shall only be stored or positioned in the upright position.

23 81 19.13.E. Project Conditions

1. As specified in the contract.

23 81 19.13.F. Operating Characteristics

1. Unit shall be capable of starting and running at 115ºF (46ºC) ambient outdoor temperature, meeting maximum load criteria of

AHRI Standard 210/240 or 340/360 at ± 10% voltage.

2. Compressor with standard controls shall be capable of operation from 40ºF (4ºC) , ambient outdoor temperatures. Accessory low ambient kit is necessary if mechanically cooling at ambient temperatures below 40ºF (4ºC).

3. Unit shall discharge supply air vertically or horizontally as shown on contract drawings.

4. Unit shall be factory configured for vertical supply & return configurations.

5. Unit shall be field convertible from vertical to horizontal configuration.

23 81 19.13.G. Electrical Requirements

1. Main power supply voltage, phase, and frequency must match those required by the manufacturer.

23 81 19.13.H. Unit Cabinet

1. Unit cabinet shall be constructed of galvanized steel, and shall be bonderized and coated with a baked enamel finish on all externally exposed surfaces.

2. Unit cabinet exterior paint shall be: film thickness, (dry) 0.003 inches minimum, gloss (per ASTM D523, 60ºF): 60, Hardness:

H-2H Pencil hardness.

3. Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standards 210/240 or 340/360 minimum exterior sweat criteria. Interior surfaces shall be insulated with a minimum 3/4-in. thick, 1 lb density, flexible fiberglass insulation, aluminum foil-faced on the air side.

4. Base of unit shall have locations for thru-the-base electrical connections (factory installed or field installed), standard.

5. Base Rail a. Unit shall have base rails on all sides.

b. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging.

c. Holes shall be provided in the base rail for moving the rooftop by fork truck.

d. Base rail shall be a minimum of 14 gauge thickness.

6. Condensate pan and connections: a. Shall be a sloped condensate drain pan made of a non-corrosive material.

b. Shall comply with ASHRAE Standard 62. c. Shall use a 1” -11 1/2 NPT drain connection, through the side of the drain pan. Connection shall be made per manufacturer’s recommendations.

7. Top panel: a. Indoor section shall be a single piece top panel.

8. Electrical Connections a. All unit power wiring shall enter unit cabinet at a single, factory-prepared, knockout location.

b. Thru-the-base capability

(1.) Standard unit shall have a thru-the-base electrical location(s) using a raised, embossed portion of the unit basepan.

(2.) No basepan penetration, other than those authorized by the manufacturer, is permitted.

9. Component access panels (standard) a. Cabinet panels shall be easily removable for servicing.

b. Stainless steel metal hinges are standard on all doors.

c. Panels covering control box, indoor fan, indoor fan motor, and electric or gas heater components (where applicable), shall have 1/4 turn latches.

23 81 19.13.J. Coils

1. Standard Aluminum/Copper Coils: on all models.

a. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to seamless internally grooved copper tubes with all joints brazed.

b. Evaporator and Condenser coils shall be leak tested to 150 psig, pressure tested to 550 psig, and qualified to UL 1995 burst test at 2,200 psig.

23 81 19.13.K. Refrigerant Components

1. Refrigerant circuit shall include the following control, safety, and maintenance features: a. Thermal Expansion Valve (TXV) with venturi type distributor except the 072 model which shall use small orifice refrigerant control expansion device.

b. Refrigerant filter drier.

c. External service gauge connections to unit suction and discharge lines.

59

Air

Mechanical Specifications

RLRL-C/H Series

2. Compressors a. Unit shall use one fully hermetic, scroll compressor for each independent refrigeration circuit.

b. Compressor motors shall be cooled by refrigerant gas passing through motor windings.

d. Compressors shall be internally protected from high discharge temperature conditions.

e. Compressors shall be protected from an over-temperature and over-amperage conditions by an internal, motor overload device.

f. Compressor shall be factory mounted on rubber grommets.

g. Compressor motors shall have internal line break thermal, current overload and high pressure differential protection.

h. Crankcase heaters shall not be required for normal operating range.

23 81 19.13.L. Filter Section

1. Filters access is specified in the unit cabinet section of this specification.

2. Filters shall be held in place by a sliding filter tray, facilitating easy removal and installation.

3. Shall consist of factory-installed, low velocity, throw-away 2-in. thick fiberglass filters.

4. Filters shall be standard, commercially available sizes.

5. Filter face velocity shall not exceed 365 fpm at nominal airflows.

23 81 19.13.M. Evaporator Fan and Motor

1. Evaporator fan motor: a. Shall have permanently lubricated bearings.

b. Shall have inherent automatic-reset thermal overload protection or circuit breaker.

c. Shall have a maximum continuous bhp rating for continuous duty operation; no safety factors above that rating shall be required.

2. Belt-driven Evaporator Fan: a. Belt drive shall include an adjustable-pitch motor pulley.

b. Shall use sealed, permanently lubricated ball-bearing type.

c. Blower fan shall be double-inlet type with forward-curved blades.

d. Shall be constructed from steel with a corrosion resistant finish and dynamically balanced.

23 81 19.13.N. Condenser Fans and Motors

1. Condenser fan motors: a. Shall be a totally enclosed motor.

b. Shall use permanently lubricated bearings.

c. Shall have inherent thermal overload protection with an automatic reset feature.

d. Shall use a shaft-down design. Shaft-up designs including those with “rain-slinger devices” shall not be allowed.

2. Condenser Fans: a. Shall be a direct-driven propeller type fan.

b. Shall have aluminum blades riveted to corrosion-resistant steel spiders and shall be dynamically balanced.

23 81 19.13.O. Special Features, Options and Accessories

1. Integrated Economizers: a. Integrated, gear-driven parallel modulating blade design type capable of simultaneous economizer and compressor

operation.

b. Independent modules for vertical or horizontal return configurations shall be available. Vertical return modules shall be available as a factory installed option.

c. Damper blades shall be galvanized steel with metal gears. Plastic or composite blades on intake or return shall not be acceptable.

d. Shall include all hardware and controls to provide free cooling with outdoor air when temperature and/or humidity are below setpoints.

e. Shall be equipped with gear driven dampers for both the outdoor ventilation air and the return air for positive air stream

control.

f. Shall be capable of introducing up to 100% outdoor air.

g. Shall be equipped with a barometric relief damper capable of relieving up to 100% return air.

h. Shall be designed to close damper(s) during loss-of-power situations with spring return built into motor.

i. An outdoor single enthalpy sensor shall be provided as standard. Outdoor air sensor setpoint shall be adjustable and shall range from the enthalpy equivalent of 63°F @ 50% rh to 73°F @ 50% rh. Additional sensor options shall be available as accessories.

j. The economizer controller shall also provide control of an accessory power exhaust unit function. Factory set at 70%, with a range of 0% to 100%.

k. The economizer shall maintain minimum airflow into the building during occupied period and provide design ventilation rate for full occupancy. A remote potentiometer may be used to override the damper setpoint.

l. Dampers shall be completely closed when the unit is in the unoccupied mode.

m. Economizer controller shall accept a 2-10Vdc CO

2 sensor input for IAQ/DCV control. In this mode, dampers shall modulate the outdoor-air damper to provide ventilation based on the sensor input.

60

Air

Mechanical Specifications

RLRL-C/H Series

n. Compressor lockout sensor on the unit controller is factory set at 35°F and is adjustable from 30ºF (-1ºC) to 50ºF (10ºC) and resets the cooling lockout at 5°F (+2.7°C) above the set point..

o. Actuator shall be direct coupled to economizer gear. No linkage arms or control rods shall be acceptable. p. Economizer controller shall provide indications when in free cooling mode, in the DCV mode, or the exhaust fan contact is closed. q. Economizer wire harness will have provision for smoke detector.

2. Two-Position Motorized Damper a. Damper shall be a Two-Position Motorized Damper. Damper travel shall be from the full closed position to the field adjustable %-open setpoint.

b. Damper shall include adjustable damper travel from 25% to 100% (full open).

c. Damper shall include single or dual blade, gear driven dampers and actuator motor. d. Actuator shall be direct coupled to damper gear. No linkage arms or control rods shall be acceptable.

e. Damper will admit up to 100% outdoor air for applicable rooftop units.

f. Damper shall close upon indoor (evaporator) fan shutoff and/or loss of power.

g. The damper actuator shall plug into the rooftop unit’s wiring harness plug. No hard wiring shall be required.

h. Outside air hood shall include aluminum water entrainment filter

3. Manual damper a. Manual damper package shall consist of damper, air inlet screen, and rain hood which can be preset to admit up to 50%

outdoor air for year round ventilation.

4. Head Pressure Control Package a. Controller shall control coil head pressure by condenser-fan cycling.

5. Condenser Coil Hail Guard Assembly a. Shall protect against damage from hail.

b. Shall be louvered design.

6. Convenience Outlet: a. Non-Powered convenience outlet.

(1.) Outlet shall be powered from a separate 115-120v power source.

(2.) A transformer shall not be included.

(3.) Outlet shall be factory-installed and internally mounted with easily accessible 115-v female receptacle.

(4.) Outlet shall include 15 amp GFI receptacles.

(5.) Outlet shall be accessible from outside the unit.

7. Fan/Filter Status Switch: a. Switch shall provide status of indoor evaporator fan (ON/OFF) or filter (CLEAN/DIRTY).

b. Status shall be displayed either over communication bus (when used with direct digital controls) or through the controller

LCD display inside the unit control box.

8. Propeller Power Exhaust: a. Power exhaust shall be used in conjunction with an integrated economizer. b. Independent modules for vertical or horizontal return configurations shall be available.

c. Horizontal power exhaust is shall be mounted in return ductwork.

d. Power exhaust shall be controlled by economizer controller operation. Exhaust fans shall be energized when dampers open past the 0-100% adjustable setpoint on the economizer control.

9. Roof Curbs (Vertical): a. Full perimeter roof curb with exhaust capability providing separate air streams for energy recovery from the exhaust air without supply air contamination.

b. Formed galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight.

c. Permits installation and securing of ductwork to curb prior to mounting unit on the curb.

10. High-Static Indoor Fan Motor(s) and Drive(s): a. High-static motor(s) and drive(s) shall be factory-installed to provide additional performance range.

11. Outdoor Air Enthalpy Sensor: a. The outdoor air enthalpy sensor shall be used to provide single enthalpy control. When used in conjunction with a return air enthalpy sensor, the unit will provide differential enthalpy control. The sensor allows the unit to determine if outside air is suitable for free cooling.

13. Return Air Enthalpy Sensor: a. The return air enthalpy sensor shall be used in conjunction with an outdoor air enthalpy sensor to provide differential enthalpy control.

14. Indoor Air Quality (CO

2

) Sensor: a. Shall be able to provide demand ventilation indoor air quality (IAQ) control.

b. The IAQ sensor shall be available in wall mount with LED display. The setpoint shall have adjustment capability.

61

Air

Mechanical Specifications

RLRL-C/H Series

15. Smoke detectors: a. Shall be a Four-Wire Controller and Detector.

b. Shall be environmental compensated with differential sensing for reliable, stable, and drift-free sensitivity.

c. Shall use magnet-activated test/reset sensor switches.

d. Shall have a recessed momentary switch for testing and resetting the detector.

e. Controller shall include:

(1.) One set of normally open alarm initiation contacts for connection to an initiating device circuit on a fire alarm control panel.

(2.) Two Form-C auxiliary alarm relays for interface with rooftop unit or other equipment.

(3.) One Form-C supervision (trouble) relay to control the operation of the Trouble LED on a remote test/reset station.

(4.) Capable of direct connection to two individual detector modules.

(5.) Can be wired to up to 14 other duct smoke detectors for multiple fan shutdown applications.

16. Electric Heat: a. Heating Section

(1.) Heater element open coil resistance wire, nickel-chrome alloy, strung through ceramic insulators mounted on metal frame. Coil ends are staked and welded to terminal screw slots.

(2.) Heater assemblies are provided with integral fusing for protection of internal heater circuits not exceeding 48 amps each. Auto reset thermo limit controls, magnetic heater contactors (24 v coil) and terminal block all mounted in electric heater control box (minimum 18 ga galvanized steel) attached to end of heater assembly.

62

Air

Wiring Diagrams

RLRL-C/H Series

63

Air

Wiring Diagrams

RLRL-C/H Series

64

Air

Wiring Diagrams

RLRL-C/H Series

65

Air

Wiring Diagrams

RLRL-C/H Series

66

Air

Limited Warranty

RLRL-C/H Series

BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM

YOUR RETAILER.

GENERAL TERMS OF LIMITED WARRANTY*

Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty.

*For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the

Manufacturer for a copy of the product warranty certificate.

Compressor

3 Phase, Commercial Applications ................Five (5) Years

Parts

3 Phase, Commercial Applications..................One (1) Year

67

The new degree of comfort.

In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.

Rheem Heating, Cooling & Water Heating • P.O. Box 17010

Fort Smith, Arkansas 72917 • www.rheem.com

Rheem Canada Ltd./Ltée • 125 Edgeware Road, Unit 1

Brampton, Ontario • L6Y 0P5

PRINTED IN U.S.A 10/12 QG FORM NO. S11-961 REV. 1

advertisement

Key Features

  • 10-ton cooling capacity
  • ClearControl™ technology with VFD
  • ASHRAE 90.1-2010 and California Title 24 compliant
  • Two-stage operation
  • Two independent circuits
  • Convertible airflow
  • Fully factory-charged, wired, and run-tested

Related manuals

Frequently Answers and Questions

What is the cooling capacity of the Rheem RLRL-H120DS000?
The Rheem RLRL-H120DS000 has a cooling capacity of 10 tons.
What type of refrigerant does the Rheem RLRL-H120DS000 use?
The Rheem RLRL-H120DS000 uses R-410A refrigerant.
Is the Rheem RLRL-H120DS000 compliant with ASHRAE 90.1-2010 and California Title 24 standards?
Yes, the Rheem RLRL-H120DS000 is compliant with ASHRAE 90.1-2010 and California Title 24 standards.