Amana PTAC Specifications
PTAC Air CondiTioners
And HeAT PumPs
11.7 EER / 3.4 COP
P roduCT s PeCifiCATions
Product Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Quiet operaion: STC of 28
Assembled in the USA for 30 years
Increased dehumidiicaion capacity
100% run-tested at our plant in
Fayeteville, TN, for leaks
7⅝” unit front depth: one of the shallowest
silhouetes in the industry today
Removable condenser shroud allows easy
access to enable regular cleaning of coils
Easy pull-out ilters that are washable and easy to maintain
Filter drier for sealed system refrigerant
7-Buton touch pad provides complete control to guests
for in-room comfort while maintaining energy eiciency
Condensate dispersion system removes condensate
from indoor cooling operaion and evaporates it into
the atmosphere through the condenser
Digismart™ front desk control &
energy management sotware
Room freeze protecion is acivated when
the unit senses temperatures of 40°F or below
Versaile style that blends into any room’s color
scheme and decor
Easy to service with on-board led diagnosics
Digismart™ wireless remote thermostat is available
Remote temperature sensing for guest climate control
Extended heat pump heaing down to as low
as 24°F outdoor ambient temperature
Zero loor clearance allows unit to be installed
lush to a inished loor
30-second fan-of delay
Compressor lock-in prevents compressor short-cycling
Constant fan mode
Hidden venilaion control
High-pressure switch
Control Board
For Sales:
www.knitec.com
(866) 469-7111
sales@knitec.com
First-Year Warranty: Parts & Labor
Second through Fith Year: Parts & Labor on certain sealed system components
Second through Fith Year: on certain funcional parts only
* Complete warranty details available at www.amana-ptac.com.
SS-DPTAC
www.amana-ptac.com
Amana® is a trademark of Maytag Corporaion or its related companies and used under license to Goodman Company, L.P., Houston, Texas.
9/14
Supersedes 8/14
ProduCT sPeCifiCATions
nomenClATure
PTC
07
3
G
35
AXXX
AA
1,2,3
4,5
6
7
8,9
10,11,12,13
14,15
Basic Model Type
Engineering PTC
Standard Cooler PTAC
Major & Minor Revisions
PTH
Standard Heat Pump PTHP
DRY
Dehumid Cooler PTAC
Features Code
A
Cooling Capacity
Standard Model
C
Corrosion Protection (Seacoast)
07
7,000 BTU/h
60 Hz
D
Power Door
09
9,000 BTU/h
60 Hz
F
Fuse Holder (230/208 Only)
10
10,000 BTU/h
50 Hz
H
Hydronic Heat‐Capable
12
12,000 BTU/h
50 or 60 Hz
P
Condensate Pump (PTH Only)
15
15,000 BTU/h
60 Hz
Q
Quiet STC 31 Chassis
17
17,000 BTU/h
60 Hz
R
RF Antenna
V
Power Vent
Rated Voltage
X
placeholder
2
115V, 60 Hz, 1 Ph
W
Hard‐Wired (PTQC)
3
230/208V, 60 Hz, 1 Ph
4
265V, 60 Hz, 1 Ph
Use up to 4 as needed in alphabetical order
5
240/220V, 50 Hz, 1 Ph
Examples:
Design Series
G
PTC123*50AXXX
PTC073*35CRXX
PTC123*50CXXX
PTC073*25CQRW
R‐410A
Heater Size
2
00
No Electric Heat
15
1.5 kW
25
2.5 kW
35
3.5 kW (230/208V)
50
5.0 kW
3.7 kW (265V)
www.amana-ptac.com
SS-DPTAC
ProduCT sPeCifiCATions
ProduCT sPeCifiCATions: PTC models — Cooling/eleCTriC HeAT
230/208 Volts
Model ⁶, ⁸, ⁹
Voltage ³
Capacity (BTU/h)
Amps ¹⁰
Wats ¹⁰
EER
PTC
073G***XXX
PTC
093G***XXX
PTC
123G***XXX
PTC
153G***XXX
PTC
173G***XXX
230 / 208
7,700
3.5
670/660
11.5/11.7
230 / 208
9,000
4.1
805/785
11.2/11.5
230 / 208
11,700 / 11,500
5.6
1135/1105
10.3/10.4
230 / 208
15,000 / 14,700
7.0
1500/1470
10.0/10.0
230 / 208
16400 / 16200
8.4
1740/1720
9.4
4.2
4.9
6.8
8.5
10.2
290
264
290
264
290
264
340
314
340
314
310
282
310
282
310
282
360
332
360
332
65*
1.7
98
113
65*
2.2
102
117
65*
3.6
102
119
65*
4.4
113
130
65*
4.8
113
130
PTC
074G***XXX
PTC
094G***XXX
PTC
124G***XXX
PTC
154G***XXX
265
7,700
3.0
670
11.5
265
9,000
3.6
795
11.3
265
12,000
4.8
1,165
10.3
265
14,800
6.0
1,480
10.0
3.6
4.4
5.9
7.4
290
264
290
264
290
264
340
314
310
282
310
282
310
282
360
332
65*
1.7
98
113
65*
2.2
102
117
65*
3.6
102
119
65*
4.4
113
130
Unit without Electric Heater
Min. Circuit Amps ², ⁴, ¹⁰
CFM (Cool/Wet Coil)
CFM (Dry Coil)
High
Low
High
Low
Venilated Air, CFM (Fan Only)*
Dehumidiicaion (Pints/Hr.)
Net Weight (lbs.)
Ship Weight (lbs.)
265/277 Volts
Model 1, 6, 8
Voltage ¹, ³
Capacity (BTU/h)
Amps ¹⁰
Wats ¹⁰
EER
Unit without Electric Heater
Min. Circuit Amps ², ⁴, ¹⁰
CFM (Cool/Wet Coil)
CFM (Dry Coil)
Venilated Air, CFM (Fan Only)*
Dehumidiicaion (Pints/Hr.)
Net Weight (lbs.)
Ship Weight (lbs.)
High
Low
High
Low
* Actual vent CFM performance will vary due to applicaion and installaion condiions.
Notes
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit PTPWHWK4 and
disconnect switch PSHW04A.
² Minimum Circuit Ampacity (MCA) raings conform to the Naional Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts;
maximum is 292 volts.
⁴ Overcurrent protecion for all units without electric heaters is 15 amps. Overcurrent protecion on 265-volt models must be
cartridge-style ime-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis). See heater performance
⁵ Heaing capacity and eiciency based on unit operaion without condensate pump; unit automaically switches to electric
heat at approximately 24°F outdoor ambient.
⁶ Specify two-digit heater kW size to complete model number.
⁷ R-410A refrigerant used in all systems.
⁸ All units meet or exceed ASHRAE 90.1 standards.
⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protecion. Amps and Wats notaion
refers to compressor only.
SS-DPTAC
www.amana-ptac.com
3
ProduCT sPeCifiCATions
ProduCT sPeCifiCATions: PTH models — Cooling/HeAT PumP/eleCTriC HeAT
Model ¹, 6, 8, 9
Voltage ¹, ³
Capacity (BTU/h)
Amps ¹⁰
PTH073G
**AXXX
PTH093G
**AXXX
PTH123G
**AXXX
PTH153G
**AXXX
PTH074G
**AXXX
PTH094G
**AXXX
PTH124G
**AXXX
PTH154G
**AXXX
230 / 208
230 / 208
230 / 208
230 / 208
265
265
265
265
7,700
9,000
12,000
14,400
7,700
9,100
12,000
14,400
3.9
4.2
5.8
7.0
3.1
3.7
5.0
6.1
Wats ¹⁰
650 / 650
785 / 785
1,120 / 1,120
1,480 / 1,480
650
790
1,120
1,480
EER
11.7 / 11.7
11.5 / 11.5
10.7 / 10.7
9.7 / 9.7
11.7
11.5
10.7
9.7
4.7
5.1
7.1
8.5
3.8
4.5
6.1
7.4
Unit without Electric Heater
Min. Circuit Amps ², ⁴, ¹⁰
CFM (Cool/Wet Coil)
High
340
330
340
390
340
330
340
390
Low
245
245
245
340
245
245
245
340
High
370
360
370
410
370
360
370
410
Low
270
270
270
370
270
270
270
370
Venilated Air, CFM (Fan Only)*
65*
65*
65*
65*
65*
65*
65*
65*
CFM (Dry Coil)
Dehumidiicaion (Pints/Hr.)
1.7
2.2
3.6
4.4
1.7
2.2
3.6
4.4
Net Weight (lbs.)
108
112
115
126
108
112
115
125
Ship Weight (lbs.)
123
127
132
143
123
127
132
142
* Actual vent CFM performance will vary due to applicaion and installaion condiions.
Notes
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum Circuit Ampacity (MCA) raings conform to the Naional Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
³ Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
⁴ Overcurrent protecion for all units without electric heaters is 15 amps. Overcurrent protecion on 265-volt models must be
cartridge-style ime-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
⁵ Heaing capacity and eiciency based on unit operaion without condensate pump; unit automaically switches to electric heat
at approximately 24°F outdoor ambient.
⁶ Specify two-digit heater kW size to complete model number.
⁷ R-410A refrigerant used in all systems.
⁸ All units meet or exceed ASHRAE 90.1 standards.
⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protecion. Amps and Wats notaion refers to compressor only.
4
www.amana-ptac.com
SS-DPTAC
ProduCT sPeCifiCATions
ProduCT sPeCifiCATions: PTC models — Cooling (uniTs for HydroniC HeATing)
Model 5, 6
PTC
072G00XXX
PTC
092G00XXX
115
7000
115
9000
Voltage 2
Capacity (BTU/h)
Amps
6.9
8.3
Wats
EER
585
11.9
795
11.3
CFM (Cool/Wet Coil)
High
Low
8.3
290
264
10.1
290
264
CFM (Dry Coil)
High
Low
310
282
310
282
Venilated Air, (Fan Only)*
65*
65*
Dehumidiicaion (Pints/Hr.)
1.7
2.3
Net Weight (lbs.)
98
102
Ship Weight (lbs.)
113
117
Min. Circuit Amps 1, 3
* Actual vent CFM performance will vary due to applicaion and installaion condiions.
Notes
¹ Minimum Circuit Ampacity (MCA) raings conform to the Naional Electric Code; however, local codes should apply.
2 Minimum voltage on 115-volt models is 109 volts; maximum is 127 volts.
3 Overcurrent protecion for all units without electric heaters is 15 amps.
⁴ R-410A refrigerant used in all systems.
⁵ All units meet or exceed ASHRAE 90.1 standards.
⁶ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
ProduCT sPeCifiCATions: PTC / PTH models — eleCTriC HeAT PerformAnCe
(Primary Heating for PTC Models; Auxiliary Heating for PTH Models; See below for Power Cord Coniguration)
Voltage
Electric
Heater
Size (kW)
No. of
Stages
Nominal Heating (BTU/h)
@ 230V
@ 208V
@ 265V
Total
Watts ⁶
Total
Amps
Min. Circuit MOD ⁴
Ampacity² (amps)
Power
Cord
230/208V
2.5
1
8,500
6,800
--
2,570 / 2,115
11.2 / 10.1
14.1
15
6-15 P
230/208V
3.5
1
12,000
9,900
--
3,570 / 2,935
15.5 / 14.1
19.5
20
6-20 P
230/208V
5
1
17,100
14,000
--
5,070 / 4,160
22.1 / 20.0
27.6
30
6-30 P
265V
2.5
1
--
--
8,500
2,570
9.7
12.2
15
7-20 P
265V
3.7
1
--
--
12,600
3,770
14.2
17.9
20
7-20 P
265V
5
1
--
--
17,100
5,070
19.2
23.9
25
7-30 P
Notes
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum branch circuit ampacity raings conform to the Naional Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts;
maximum is 292 volts.
⁴ Overcurrent protecion for all units without electric heaters is 15 amps. Overcurrent protecion on 265-volt models must be
cartridge-style ime-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
⁵ Heaing capacity and eiciency based on unit operaion without condensate pump; unit automaically switches to electric
heat at approximately 24°F outdoor ambient.
⁶ Total wats for 15,000 BTU/h models; subtract 20 wats for PT07/09/12
⁷ Specify two-digit heater kW size to complete model number.
⁸ R-410A refrigerant used in all systems.
⁹ All units meet or exceed ASHRAE 90.1 standards.
¹⁰ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
SS-DPTAC
www.amana-ptac.com
5
ProduCT sPeCifiCATions
ProduCT sPeCifiCATions: PTH models — reverse-CyCle HeATing PerformAnCe
Heating
Capacity¹
Voltage ¹, ³
BTU/h ⁵
PTH073G
**AXXX
PTH093G
**AXXX
230 / 208
6,800 / 6,800
230 / 208
8,300 / 8,100
PTH123G
**AXXX
PTH153G
**AXXX
230 / 208
230 / 208
11,500 / 11,300 13,800 / 13,600
PTH074G
**AXXX
PTH094G
**AXXX
PTH124G
**AXXX
PTH154G
**AXXX
265
6,800
265
8,300
265
11,400
265
13,700
Amps ¹⁰
3.9
4.2 / 4.2
5.8 / 5.8
7.0 / 7.0
3.1
3.7
5.0
6.1
Wats ¹⁰
585 / 570
715 / 700
1085 /1035
1350 / 1330
570
715
1080
1340
COP ⁵
CFM (Dry)
3.4 / 3.5
370
3.4 / 3.4
360
3.1 / 3.2
370
3.0 / 3.0
410
3.5
370
3.4
360
3.1
370
3.0
410
COP = Coeiciency of Performance; per AHRI Test Procedures, units are rated for capaciies and eiciencies.
Notes
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum branch circuit ampacity raings conform to the Naional Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
⁴ Overcurrent protecion for all units without electric heaters is 15 amps. Overcurrent protecion on 265-volt models must
be cartridge-style ime-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
⁵ Heaing capacity and eiciency based on unit operaion without condensate pump; unit automaically switches to electric
heat at approximately 24°F outdoor ambient.
⁶ Specify two-digit heater kW size to complete model number.
⁷ R-410A refrigerant used in all systems.
⁸ All units meet or exceed ASHRAE 90.1 standards.
⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protecion.
Amps and Wats notaion refers to compressor only.
ConTrACTor's bid sHeeT
Furnish and install air-cooled through-the-wall package terminal air condiioners amd heat pumps (assembled in the USA).
Units are rated in accordance with the ARI (Air Condiioning & Refrigeraion Insitute) Standards 310/380-93, CSA (Canadian
Standards Associaion) EEV ceriicaion programs and listed by U. L. (Underwriters Laboratories).
rATings
Each unit must meet the following speciicaions:
ARI raing of _________BTUH cooling (and _________ BTUH
reverse cycle heaing with a COP of _________ at 47° F O.D.)
Electric resistance heat of _________ BTUH. Total Amp draw
must be of ________ and _________ Wats at _________ volts.
The unit must remove a minimum of _________ pints of
moisture per hour when operated at raing condiions. The EER
must be a minimum of _________ EER.
uniT CHAssis
Each unit must be slide out design shipped with room cabinet
front installed. Unit chassis must have the ability to be installed
with 0 clearance from inished loor. An electrical power cord
must be included with chassis and installed by the manufacturer
to assure proper NEMA 6 or 7 coniguraion and UL-approved
length. Units less than 250 volts must also have a LCDI power cord.
Unit must be tested for conformance to ASTME water iniltraion
speciicaion ASTME 331-86, which ensures no water iniltraion
when tested at 8" rain per hour at 63 mph wind for 15 minutes.
room CAbineT
The monochromaic front of the room cabinet must be able to
be ield-secured to chassis to inhibit tampering. Filter must be
accessible without removing room front. Cabinet depth must
not exceed 7⅝” to minimize unit’s impact on room space.
6
Coils
Unit’s coils must have riled copper tubing expanded into
rippled-edge louvered aluminum ins. Exterior coil must be of
a two-row bent coil design with removable shroud top to allow
easy-access for cleaning of the exterior coil.
HeAT PumPs
Each unit must include a change-over thermistor that senses an
outside ambient switch-over temperature as low as 24°F, lockopen refrigerant reversing valve during heat pump operaion,
temperature-acivated defrost drain and automaic emergency
heat operaion to override the heat pump’s change-over
thermostat and bring on electric resistance heaters in the event
of a sealed system failure. Unit must not operate compressor
and electric heaters simultaneously.
ComPressor
The compressor must be hermeically sealed, internally isolated,
rotary-type and permanently mounted on rubber isolators. No
removal or adjustment of compressor hold-down bolts is to be
required during installaion.
WArrAnTy
The warranty is for Full One Year on the enire unit; Full 2nd through
5th Year on the enire sealed refrigerant system components;
Limited Second through Fith Year on funcional parts only.
www.amana-ptac.com
SS-DPTAC
ProduCT sPeCifiCATions
uniT digiTAl ConTrols
The unit’s control must be completely wired and accessible from
the top of the chassis. Controls shall be a LED touch-pad design
with seven large, easy-to-read and use butons: Heat – Cool –
Of – Fan – Temp+ (plus) – Temp- (minus) and two red sevensegment LED temperature displays. Unit shall have a green
status LED to advise owner of operaional diagnosic messages.
Unit shall have one-buton acivaion via membrane touch-pad.
Unit control board shall have an 18-pin low-voltage connector
to allow for easy connecion to remote wired devices. Unit shall
have two serial-port connectors for easy connecion to wired or
wireless EMS (Energy Management Systems).
Unit must have the ability to easily conigure owner-selectable
and programmable funcions:
• Fan-cycle operaion
• Electronic temperature limiing for cooling
• Electronic temperature limiing for heaing
• Enhanced dehumidiicaion cooling operaion
• Unoccupied 18-hour temperature set-back
• Un-rented temperature set-back
• Muliple unit twinning to one wired thermostat
• Load-shedding operaion
• Front-desk on-of or temperature set-back
Unit must be able to connect to approved remote devices:
• Wired thermostat
• Wired door moion sensor
• Wired room moion sensor
• Wired room-to-room transfer fan
• Front Desk Control
• Future RF wireless communicaions devices
Unit must be able to acquire and display operaional temperature
data from up to six installed thermistors to include:
• IAT—Indoor air temperature (black)
• ICT—Indoor coil temperature (red )
• IDT—Indoor discharge temperature (yellow)
• OCT—Outdoor coil temperature (blue) (heat pumps
& Wireless cooler models)
• OAT— Outdoor Air Temperature (Wireless-ready
models only)
• Orange—Miscellaneous thermistor or analog device (opional)
evAPorATor/Condenser fAns
Direct drive with a permanent, split-capacitor, two-speed
indoor motor. Condensate must be directed onto the back and
sides of the coil to aid in evaporaion and removal.
Air disCHArge
Must be a sloped surface so that obstrucions cannot be placed
on the unit. Discharge condiioned air can be directed into the
room at an angle of 16 or 56 degrees from the verical posiion.
The discharge grille must be of polycarbonate material to resist
bending, cracking, rusing and corrosion.
New installaions typically require a minimum of WS900E wall sleeve and an outdoor grille.
WAll sleeves (Ws900e)
ouTdoor grilles
The wall sleeve must be industry-accepted dimensions:
14⅛” depth x 42” width x 16¹/₁₆” height and constructed of
G90 HDG galvanized steel with a baked corrosion-inhibiing
urethane primer and baked-polyester topcoat enamel.
Sleeve must be insulated and shipped with a weather
resistant rear closure panel installed.
Outdoor grille must be architecturally extruded, louvered
aluminum (AGK01*B), one-piece polymer-blend injecion
molded louver (PGK01*B) or standard stamped aluminum
(SGK**B). All other grilles must be submited to the PTAC
manufacturer for feasibility, airlow characterisics and
compliance with UL regulaions, where necessary.
The opional accessories listed below perform speciic funcions required in some installaions.
CondensATe drAin KiT (dK900d)
PoWer venT & dAmPer
Ataches to the botom of the wall sleeve for direcionalcontrolled internal or external disposal of condensate,
defrost or rain water.
Must be provided to maximize venilaion air intake to up to
approximately 95 CFM. Power vent must be of and damper
door closed when unit fan is de-energized.
sub-bAse KiT (PTsb***e)
fuse Holder (inCluded in 265v CHAssis)
Necessary for UL lising requirements for 265V units (Hard
Wire Kit may be subsituted for Sub-base kit). Opional for
230/208V units. Must be pre-wired to facilitate ield-electrical
connecions and include an NEMA 6 or 7 coniguraion
electrical receptacle. It must have two leveling screws for
sleeve support and accurate unit leveling during installaion.
Locaions for ield installaion of physical disconnect
switches, cartridge-style fuse holders and circuit breakers
must be provided. Side-skirts must be provided with subbases. (PTSB000E Non-Electrical Sub-base available.)
Must be installed either in the unit or the sub-base and must
match the electrical requirements of the chassis.
SS-DPTAC
seCuriTy Key loCKs (Kl03e)
Must be installed to prevent tampering of the unit controls.
Unit room cabinet must also be secured to the chassis with
ield supplied screws. UL-approved for insituional use only.
disConneCT sWiTCH
Power disconnect switch must be installed in sub-base for
use as a physical disconnect, where required by local codes.
www.amana-ptac.com
7
ProduCT sPeCifiCATions
ConTrACTor's bid sHeeT (ConT.)
duCT KiTs (mdK01e, edK02b, TdK02b, PTdK01e, ddK01e)
CirCuiT breAKer KiT
Three kits must be supplied to provide ducted, condiioned
air into a second room: a main duct kit, an extension duct kit
and a terminal duct kit.
Must be installed in sub-base to provide overcurrent
protecion for proper 230/208V amperage. Can also be
used as a physical disconnect where local codes permit for
230/208 voltage.
HydroniC HeAT KiT
Is required for heaing funcions instead of electric resistance
heaters. Unit must retain complete service access with the
kit installed. Proper water or steam valves must be used.
CondensATe removAl PumP (HeAT PumPs only)
Must be installed to assist in removing the condensate
developed by the heat pump operaion and transfer it to the
indoor coil to dissipate into the room, adding humidity to
the room.
HArd Wire KiT
Must be used to permanently wire chassis for hard wire
purposes. (For 265V units, Hard Wire Kit may be subsituted
with Sub-base Kit.)
THermosTATs
A manufacturer-approved manual, auto changeover
or programmable traditionally wired thermostat must
be installed to provide full remote operaion of the chassis.
A Remote Escutcheon Kit must be used to indicate remote
operaion.
monTHly mAinTenAnCe
inTAKe Air filTers
It is extremely important to clean the inlet air ilters once a month (or more oten if operated in dusty or dirty locaions or
condiions) to properly maintain the operaional performance of the PTAC unit. The two intake air ilters (constructed of
durable polypropylene) can be easily inserted into the cabinet front using the cabinet ilter guides. Before cleaning the intake
ilters, turn the unit of by seing the mode switch to the OFF posiion. Filters should be cleaned as required. The following
procedure is used to remove the intake ilters:
1. Facing the unit, pull up on the ilter handles located at the front top of the unit.
2. Pull each ilter upward and remove.
3. Clean ilters with vacuum or with running water. Reverse this procedure to reinstall the ilters.
Note: Accessory ilter kits are available from your sales person. All ilters are permanent and cleanable. Consult your
I&O Manual for other monthly cleaning instrucions.
sPAre filTers
Helps keep dirt and lint out of the air and of the coil,
thus increasing the unit's eiciency. Amana® brand
ilters are easy to remove, wash and replace.
For Sales:
www.knitec.com
(866) 469-7111
sales@knitec.com
rePlACemenT CHArCoAl filTer KiT
Absorbs airborne odors caused by cigarete, pipe
or cigar smoke and odors caused by mold, mildew,
etc. Filters are made of polyester ibers coated with
acivated charcoal and are individually wrapped.
These ilters are permanent and can be washed or
cleaned. Call your Amana® brand PTAC sales person
for details. 10 ilters per pack.
FK10A
10-pack - A Series
FK10B
10-pack - B, C & D Series
FK10E
10-pack - E Series
(requires 2 ilters per
change.)
CFK10A
10-pack - A Series (R-22)
CFK10B
10-pack - B, C & D Series (R-22)
Amana® is a trademark of Maytag Corporaion or its related companies and used under license to Goodman Company, L.P. All rights reserved. Our coninuing commitment to quality products may mean a change in speciicaions without noice. © 2014 • Goodman Company, L.P. • Houston, Texas • Printed in the USA.
8
www.amana-ptac.com
SS-DPTAC