IMO Jaguar VXG Manual

Add to my manuals
297 Pages

advertisement

IMO Jaguar VXG Manual | Manualzz
Instruction Manual
High Performance, Multifunction Inverter
Jaguar VXG
Thank you for purchasing our JAGUAR VXG series of inverters.
• This product is designed to drive a three-phase induction motor. Read through this instruction manual and be familiar with
the handling procedure for correct use.
• Improper handling might result in incorrect operation, a short life, or even a failure of this product as well as the motor.
• Deliver this manual to the end user of this product. Keep this manual in a safe place until this product is discarded.
• For how to use an optional device, refer to the instruction and installation manuals for that optional device.
IMO Precision Controls Ltd
VXG-IM-V1
Copyright © 2009 IMO Precision Controls Ltd.
All rights reserved.
No part of this publication may be reproduced or copied without prior written permission
from IMO Precision Controls Ltd.
All products and company names mentioned in this manual are trademarks or registered
trademarks of their respective holders.
The information contained herein is subject to change without prior notice for improvement.
Preface
Thank you for purchasing our JAGUAR VXG series of inverters.
This product is designed to drive a three-phase induction motor. Read through this instruction manual and be familiar with
proper handling and operation of this product.
Improper handling might result in incorrect operation, a short life, or even a failure of this product as well as the motor.
This instruction manual has been prepared for the inverter versions to be destined for the EU.
Have this manual delivered to the end user of this product. Keep this manual in a safe place until this product is discarded.
Listed below are the other materials related to the use of the JAGUAR VXG. Read them in conjunction with this manual as
necessary.
• JAGUAR VXG User's Manual
• RS-485 Communication User's Manual
These materials are subject to change without notice. Be sure to obtain the latest editions for use.
„ Safety precautions
Read this manual thoroughly before proceeding with installation, connections (wiring), operation, or maintenance and
inspection. Ensure you have sound knowledge of the device and familiarize yourself with all safety information and
precautions before proceeding to operate the inverter.
Safety precautions are classified into the following two categories in this manual.
Failure to heed the information indicated by this symbol may lead to dangerous conditions,
possibly resulting in death or serious bodily injuries.
Failure to heed the information indicated by this symbol may lead to dangerous conditions,
possibly resulting in minor or light bodily injuries and/or substantial property damage.
Failure to heed the information contained under the CAUTION title can also result in serious consequences. These safety
precautions are of utmost importance and must be observed at all times.
Application
• The JAGUAR VXG is designed to drive a three-phase induction motor. Do not use it for single-phase motors or for
other purposes.
Fire or an accident could occur.
• The JAGUAR VXG may not be used for a life-support system or other purposes directly related to the human safety.
• Though the JAGUAR VXG is manufactured under strict quality control, install safety devices for applications where
serious accidents or property damages are foreseen in relation to the failure of it.
An accident could occur.
Installation
• Install the inverter on a base made of metal or other non-flammable material.
Otherwise, a fire could occur.
• Do not place flammable object nearby.
Doing so could cause fire.
• Inverters with a capacity of 30 kW or above, whose protective structure is IP00, involve a possibility that a human body
may touch the live conductors of the main circuit terminal block. Inverters to which an optional DC reactor is connected
also involve the same. Install such inverters in an inaccessible place.
Otherwise, electric shock or injuries could occur.
• Do not support the inverter by its front cover during transportation.
Doing so could cause a drop of the inverter and injuries.
• Prevent lint, paper fibers, sawdust, dust, metallic chips, or other foreign materials from getting into the inverter or from
accumulating on the heat sink.
• When changing the positions of the top and bottom mounting bases, use only the specified screws.
Otherwise, a fire or an accident might result.
• Do not install or operate an inverter that is damaged or lacking parts.
Doing so could cause fire, an accident or injuries.
Wiring
i
• If no zero-phase current (earth leakage current) detective device such as a ground-fault relay is installed in the upstream
power supply line in order to avoid the entire power supply system's shutdown undesirable to factory operation, install
a residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) individually to inverters to
break the individual inverter power supply lines only.
Otherwise, a fire could occur.
• When wiring the inverter to the power source, insert a recommended molded case circuit breaker (MCCB) or
residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) (with overcurrent protection)
in the path of each pair of power lines to inverters. Use the recommended devices within the recommended current
capacity.
• Use wires in the specified size.
• Tighten terminals with specified torque.
Otherwise, a fire could occur.
• When there is more than one combination of an inverter and motor, do not use a multicore cable for the purpose of
handling their wirings together.
• Do not connect a surge killer to the inverter's output (secondary) circuit.
Doing so could cause a fire.
• Be sure to connect an optional DC reactor (DCR) when the capacity of the power supply transformer exceeds 500 kVA
and is 10 times or more the inverter rated capacity.
Otherwise, a fire could occur.
• Ground the inverter in compliance with the national or local electric code.
• Be sure to ground the inverter's grounding terminals G.
Otherwise, an electric shock or a fire could occur.
• Qualified electricians should carry out wiring.
• Be sure to perform wiring after turning the power OFF.
Otherwise, an electric shock could occur.
• Be sure to perform wiring after installing the inverter unit.
Otherwise, an electric shock or injuries could occur.
• Ensure that the number of input phases and the rated voltage of the product match the number of phases and the voltage
of the AC power supply to which the product is to be connected.
Otherwise, a fire or an accident could occur.
• Do not connect the power supply wires to output terminals (U, V, and W).
• When connecting a DC braking resistor (DBR), never connect it to terminals other than terminals P(+) and DB.
Doing so could cause fire or an accident.
• In general, sheaths of the control signal wires are not specifically designed to withstand a high voltage (i.e., reinforced
insulation is not applied). Therefore, if a control signal wire comes into direct contact with a live conductor of the main
circuit, the insulation of the sheath might break down, which would expose the signal wire to a high voltage of the main
circuit. Make sure that the control signal wires will not come into contact with live conductors of the main circuit.
Doing so could cause an accident or an electric shock.
• Before changing the switches or touching the control circuit terminal symbol plate, turn OFF the power and wait at
least five minutes for inverters with a capacity of 22 kW or below, or at least ten minutes for inverters with a
capacity of 30 kW or above. Make sure that the LED monitor and charging lamp are turned OFF. Further, make sure,
using a multimeter or a similar instrument, that the DC link bus voltage between the terminals P(+) and N(-) has
dropped to the safe level (+25 VDC or below).
Otherwise, an electric shock could occur.
• The inverter, motor and wiring generate electric noise. Be careful about malfunction of the nearby sensors and devices.
To prevent them from malfunctioning, implement noise control measures.
Otherwise an accident could occur.
• The leakage current of the EMC filter built-in type of inverters is comparatively large. Be sure to perform protective
grounding.
Otherwise, an electric shock could occur.
ii
Operation
• Be sure to mount the front cover before turning the power ON. Do not remove the cover when the inverter power is ON.
Otherwise, an electric shock could occur.
• Do not operate switches with wet hands.
Doing so could cause electric shock.
• If the auto-reset function has been selected, the inverter may automatically restart and drive the motor depending on the
cause of tripping. Design the machinery or equipment so that human safety is ensured at the time of restarting.
Otherwise, an accident could occur.
• If the stall prevention function (current limiter), automatic deceleration (anti-regenerative control), or overload
prevention control has been selected, the inverter may operate with acceleration/deceleration or frequency different
from the commanded ones. Design the machine so that safety is ensured even in such cases.
key on the keypad is effective only when the keypad operation is enabled with function code F02 (= 0, 2 or 3).
• The
When the keypad operation is disabled, prepare an emergency stop switch separately for safe operations.
Switching the run command source from keypad (local) to external equipment (remote) by turning ON the "Enable
key. To enable the
key for an emergency stop, select the STOP
communications link" command LE disables the
key priority with function code H96 (= 1 or 3).
• If any of the protective functions have been activated, first remove the cause. Then, after checking that the all run
commands are set to OFF, release the alarm. If the alarm is released while any run commands are set to ON, the inverter
may supply the power to the motor, running the motor.
Otherwise, an accident could occur.
• If you enable the "Restart mode after momentary power failure" (Function code F14 = 3 to 5), then the inverter
automatically restarts running the motor when the power is recovered.
Design the machinery or equipment so that human safety is ensured after restarting.
• If the user configures the function codes wrongly without completely understanding this Instruction Manual and the
JAGUAR VXG User's Manual, the motor may rotate with a torque or at a speed not permitted for the machine.
An accident or injuries could occur.
• Even if the inverter has interrupted power to the motor, if the voltage is applied to the main circuit input terminals L1/R,
L2/S and L3/T, voltage may be output to inverter output terminals U, V, and W.
• Even if the run command is set to OFF, voltage is output to inverter output terminals U, V, and W if the servo-lock
command is ON.
• Even if the motor is stopped due to DC braking or preliminary excitation, voltage is output to inverter output terminals
U, V, and W.
An electric shock may occur.
• The inverter can easily accept high-speed operation. When changing the speed setting, carefully check the
specifications of motors or equipment beforehand.
Otherwise, injuries could occur.
• Do not touch the heat sink and braking resistor because they become very hot.
Doing so could cause burns.
• The DC brake function of the inverter does not provide any holding mechanism.
Injuries could occur.
• Ensure safety before modifying the function code settings.
Run commands (e.g., "Run forward" FWD), stop commands (e.g., "Coast to a stop" BX), and frequency change
commands can be assigned to digital input terminals. Depending upon the assignment states of those terminals,
modifying the function code setting may cause a sudden motor start or an abrupt change in speed.
• When the inverter is controlled with the digital input signals, switching run or frequency command sources with the
related terminal commands (e.g., SS1, SS2, SS4, SS8, Hz2/Hz1, Hz/PID, IVS, and LE) may cause a sudden motor start
or an abrupt change in speed.
• Ensure safety before modifying customizable logic related function code settings (U codes and related function codes)
or turning ON the "Cancel customizable logic" terminal command CLC. Depending upon the settings, such
modification or cancellation of the customizable logic may change the operation sequence to cause a sudden motor
start or an unexpected motor operation.
An accident or injuries could occur.
iii
Maintenance and inspection, and parts replacement
• Before proceeding to the maintenance/inspection jobs, turn OFF the power and wait at least five minutes for
inverters with a capacity of 22 kW or below, or at least ten minutes for inverters with a capacity of 30 kW or
above. Make sure that the LED monitor and charging lamp are turned OFF. Further, make sure, using a multimeter or a
similar instrument, that the DC link bus voltage between the terminals P(+) and N(-) has dropped to the safe level (+25
VDC or below).
Otherwise, an electric shock could occur.
• Maintenance, inspection, and parts replacement should be made only by qualified persons.
• Take off the watch, rings and other metallic objects before starting work.
• Use insulated tools.
Otherwise, an electric shock or injuries could occur.
• Never modify the inverter.
Doing so could cause an electric shock or injuries.
Disposal
• Treat the inverter as an industrial waste when disposing of it.
Otherwise injuries could occur.
GENERAL PRECAUTIONS
Drawings in this manual may be illustrated without covers or safety shields for explanation of detail parts. Restore the
covers and shields in the original state and observe the description in the manual before starting operation.
Icons
The following icons are used throughout this manual.
This icon indicates information which, if not heeded, can result in the inverter not operating to full efficiency, as well
as information concerning incorrect operations and settings which can result in accidents.
This icon indicates information that can prove handy when performing certain settings or operations.
This icon indicates a reference to more detailed information.
iv
Conformity to the Low Voltage Directive in the EU
If installed according to the guidelines given below, inverters marked with CE are considered as compliant with the Low
Voltage Directive 2006/95/EC.
Compliance with European Standards
Adjustable speed electrical power drive systems (PDS).
Part 5-1: Safety requirements. Electrical, thermal and energy. EN61800-5-1: 2003
1. The ground terminal G should always be connected to the ground. Do not use only a residual-current-operated
protective device (RCD)/earth leakage circuit breaker (ELCB)* as the sole method of electric shock protection. Be sure
to use ground wires whose size is greater than power supply lines.
*With overcurrent protection.
2. To prevent the risk of hazardous accidents that could be caused by damage of the inverter, install the specified fuses in
the supply side (primary side) according to the following tables.
- Breaking capacity: Min. 10 kA
- Rated voltage: Min. 500 V
Power Nominal
applied
supply
voltage motor
(kW)
Inverter type
Power
supply
voltage
Fuse rating
(A)
Nominal
applied
motor
(kW)
0.4
VXG3A-2
0.75
VXG5A-2
1.5
VXG8A-2
2.2
VXG11A-2
30 (IEC60269-1)
0.4
0.75
1.5
2.2
4.0
5.5
3.7
5.5
VXG18A-2
40 (IEC60269-1)
7.5
VXG46AL-2
11
VXG59AL-2
15
VXG74AL-2
18.5
VXG88AL-2
22
VXG115AL-2
30
VXG146AL-2
37
VXG180AL-2
45
VXG215AL-2
55
VXG283AL-2
75
VXG350AL-2
90
110
VXG400AL-2
10 (IEC60269-1)
15 (IEC60269-1)
CT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
20 (IEC60269-1)
Inverter type
VXG1A5-4E
VXG2A5-4E
VXG4A-4E
VXG5.5A-4E
VXG9A-4E
VXG16A5L-4E
VXG23AL-4E
125 (IEC60269-4)
11
VXG30A5L-4E
160 (IEC60269-4)
15
VXG37AL-4E
160 (IEC60269-4)
18.5
VXG45AL-4E
200 (IEC60269-4)
22
VXG60AL-4E
250 (IEC60269-4)
30
VXG75AL-4E
250 (IEC60269-4)
37
VXG91AL-4E
350 (IEC60269-4)
45
VXG112AL-4E
400 (IEC60269-4)
55
VXG150AL-4E
450 (IEC60269-4)
Three-phase 400 V
VXG30AL-2
7.5
Three-phase 200 V
CT/
VT
mode
500 (IEC60269-4)
75
VXG176AL-4E
90
VXG210AL-4E
110
VXG253AL-4E
132
VXG304AL-4E
160
VXG377AL-4E
200
VXG415AL-4E
220
250
VXG520AL-4E
280
315
355
315
355
400
355
400
450
400
450
VXG650AL-4E
VXG740AL-4E
VXG840AL-4E
VXG960AL-4E
500
VXG1170AL-4E
630
710
v
VXG1370AL-4E
CT/
MT/VT
mode
CT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
MT/VT
CT
MT/VT
CT
MT/VT
CT
MT/VT
CT
MT/VT
CT
MT
VT
CT
MT
VT
CT
MT
VT
CT
MT
VT
CT
MT
VT
CT
VT
CT
VT
Fuse rating
(A)
3 (IEC60269-1)
6 (IEC60269-1)
10 (IEC60269-1)
15 (IEC60269-1)
20 (IEC60269-1)
80 (IEC60269-4)
80 (IEC60269-4)
125 (IEC60269-4)
125 (IEC60269-4)
160 (IEC60269-4)
160 (IEC60269-4)
250 (IEC60269-4)
315 (IEC60269-4)
315 (IEC60269-4)
400 (IEC60269-4)
350 (IEC60269-4)
350 (IEC60269-4)
350 (IEC60269-4)
400 (IEC60269-4)
450 (IEC60269-4)
500 (IEC60269-4)
550 (IEC60269-4)
630 (IEC60269-4)
900 (IEC60269-4)
1250
(IEC60269-4)
2000
(IEC60269-4)
Conformity to the Low Voltage Directive in the EU (Continued)
3. When used with the inverter, a molded case circuit breaker (MCCB), residual-current-operated protective device
(RCD)/earth leakage circuit breaker (ELCB) or magnetic contactor (MC) should conform to the EN or IEC standards.
4. When you use a residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) for protection
from electric shock in direct or indirect contact power lines or nodes, be sure to install type B of RCD/ELCB on the input
(primary) of the inverter if the power supply is three-phase 200/400 V.
5. The inverter should be used in an environment that does not exceed Pollution Degree 2 requirements. If the environment
conforms to Pollution Degree 3 or 4, install the inverter in an enclosure of IP54 or higher.
6. Install the inverter, AC or DC reactor, input or output filter in an enclosure with minimum degree of protection of IP2X
(Top surface of enclosure shall be minimum IP4X when it can be easily accessed), to prevent human body from touching
directly to live parts of these equipment.
7. Do not connect any copper wire directly to grounding terminals. Use crimp terminals with tin or equivalent plating to
connect them.
8. When you use an inverter at an altitude of more than 2000 m, you should apply basic insulation for the control circuits of
the inverter. The inverter cannot be used at altitudes of more than 3000 m.
VXG3A-2
0.75
VXG5A-2
1.5
VXG8A-2
2.2
VXG11A-2
3.7
VXG18A-2
VXG30AL-2
7.5
VXG46AL-2
11
VXG59AL-2
Three--phase 200 V
15
VXG74AL-2
18.5
VXG88AL-2
22
VXG115AL-2
30
VXG146AL-2
37
VXG180AL-2
45
VXG215AL-2
55
VXG283AL-2
75
VXG350AL-2
90
110
VXG400AL-2
5
CT
CT
VT
CT
VT
CT
VT
CT
10
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
15
1
20
1
Aux. fan power
supply [R1, T1]
1
Control circuit
1
5
10
Aux. control power
supply [R0, T0]
W/o
DCR
-
1.5
30
2.5
4
2.5
2.5
30
50
4
6
4
4
6
40
75
6
10
50
100
10
16
75
125
16
25
16
150
25
35
25
10
100
6
1
16
-
25
35
1.5
175
35
50
35
150
200
50
70
50
70
175
250
70
95
70
95
200
300
95
70×2
95
50×2
CT
VT
W/
DCR
20
VT
CT
W/o
DCR
DC reactor
[P1, P(+)] *2
W/
DCR
0.4
5.5
Rated current
Main circuit
Main power
input *2
[L1/R, L2/S, L3/T]
Inverter’s
grounding [ G]
Inverter outputs
[U, V, W] *2
Inverter type
MCCB or
RCD/ELCB *1
Braking resistor
[P(+), DB] *2
Recommended wire size (mm2)
CT/VT mode
Nominal applied motor
Power supply voltage
9. Use wires listed in EN60204 Appendix C.
0.65
to
0.82
2.5
2.5
4
6
250
350
50×2
95×2
70×2
70×2
95×2
95×2
120×2
120×2
150×2
150×2
10
350
400
500
95×2
-
120×2
150×2
-
2.5
-
*1 The frame size and model of the MCCB or RCD/ELCB (with overcurrent protection) will vary, depending on the power transformer capacity.
Refer to the related technical documentation for details.
*2 The recommended wire size for main circuits is for the 70qC 600 V PVC wires used at a surrounding temperature of 40qC.
vi
Conformity to the Low Voltage Directive in the EU (Continued)
VXG1A5-4E
VXG2A5-4E
2.2
VXG5.5A-4E
4.0
5.5
VXG9A-4E
VXG4A-4E
VXG16A5L-4E
7.5
VXG23AL-4E
11
VXG30A5L-4E
15
VXG37AL-4E
18.5
VXG45AL-4E
22
VXG60AL-4E
Three--phase 400 V
30
VXG75AL-4E
37
VXG91AL-4E
45
VXG112AL-4E
55
VXG150AL-4E
75
VXG176AL-4E
90
VXG210AL-4E
110
VXG253AL-4E
132
VXG304AL-4E
160
VXG377AL-4E
200
VXG415AL-4E
VXG520AL-4E
5
CT
VT
CT
VT
CT
1
CT
VT
CT
VT
CT
15
30
2.5
1.5
1.5
20
40
1.5
4
2.5
2.5
30
50
4
6
4
4
10
6
6
60
40
CT
VT
CT
VT
CT
VT
CT
MT/VT
CT
MT/VT
CT
MT/VT
CT
100
16
MT/VT
16
25
16
35
25
125
25
100
150
125
0.65
to
0.82
25
200
35
50
35
35
70
50
70
2.5
1.5
2.5
175
70
70
95
200
95
95
120
250
50×2
4
150
70×2
300
-
70×2
350
185
500
300
MT/VT
CT
10
10
75
CT
-
10
16
50
1
6
75
VT
VT
1
1.5
CT
VT
1
20
VT
Aux. fan power
supply [R1, T1]
1
15
10
Control circuit
5
10
CT
W/o
DCR
Aux. control power
supply [R0, T0]
W/
DCR
Braking resistor
[P(+), DB] *2
W/o
DCR
Main circuit
Main power
input *2
[L1/R, L2/S, L3/T]
Inverter’s
grounding [ G]
DC reactor
[P1, P(+)] *2
Rated current
W/
DCR
0.4
0.75
1.5
220
MCCB or
RCD/ELCB *1
Inverter outputs
[U, V, W] *2
Inverter type
CT/MT/VT mode
Nominal applied motor
Power supply voltage
Recommended wire size (mm2)
CT
70×2
240
300
300
120×2
150×2
150×2
2.5
-
.
*1 The frame size and model of the MCCB or RCD/ELCB (with overcurrent protection) will vary, depending on the power transformer capacity.
Refer to the related technical documentation for details.
*2 The recommended wire size for main circuits is for the 70qC 600 V PVC wires used at a surrounding temperature of 40qC.
vii
Conformity to the Low Voltage Directive in the EU (Continued)
450
MT
VXG840AL-4E
CT
VXG740AL-4E
VT
VXG840AL-4E
MT
VXG960AL-4E
CT
VXG840AL-4E
VT
VXG960AL-4E
VXG1170AL-4E
630
710
VXG1370AL-4E
VT
Braking resistor
[P(+), DB] *2
2.5
300×2
-
240×3
1200
300×2
-
240×3
300×3
300×3
240×4
-
300×3
240×4
CT
CT
2.5
240×2
300×2
VT
VT
0.65
to
0.82
240×2
800
MT
Aux. fan power
supply [R1, T1]
VXG740AL-4E
185×2
Aux. control power
supply [R0, T0]
CT
VT
185×2
240×2
MT
VXG650AL-4E
500
600
CT
VXG740AL-4E
W/o
DCR
185×2
MT
VT
W/
DCR
Control circuit
Three--phase 400 V
400
W/o
DCR
Main circuit
Main power
input *2
[L1/R, L2/S, L3/T]
Inverter’s
grounding [ G]
DC reactor
[P1, P(+)] *2
VXG520AL-4E
VXG650AL-4E
355
Rated current
W/
DCR
280
315
MCCB or
RCD/ELCB *1
Inverter outputs
[U, V, W] *2
250
Inverter type
CT/MT/VT mode
Nominal applied motor
Power supply voltage
Recommended wire size (mm2)
1400
300×4
300×4
300×4
1600
*1 The frame size and model of the MCCB or RCD/ELCB (with overcurrent protection) will vary, depending on the power transformer capacity.
Refer to the related technical documentation for details.
*2 The recommended wire size for main circuits is for the 70qC 600 V PVC wires used at a surrounding temperature of 40qC.
10. The inverter has been tested with IEC61800-5-1 2007 5.2.3.6.3 Short-circuit Current Test under the following
conditions.
Short-circuit current in the supply: 10 kA
Maximum 240 V for 200 V class series with 22 kW or below
Maximum 230 V for 200 V class series with 30 kW or above
Maximum 480 V for 400 V class series
viii
Conformity with UL standards and CSA standards (cUL-listed for Canada)
UL/cUL-listed inverters are subject to the regulations set forth by the UL standards and CSA standards (cUL-listed for
Canada) by installation within precautions listed below.
1. Solid state motor overload protection (motor protection by electronic thermal overload relay) is provided in each model.
Use function codes F10 to F12 to set the protection level.
2. Use Cu wire only.
3. Use Class 1 wire only for control circuits.
4. Short circuit rating
"Suitable For Use On A Circuit Of Delivering Not More Than 100,000 rms Symmetrical Amperes, 240 Volts Maximum
for 200V class input 22 kW or less, 230 Volts maximum for 200V class input 30 kW or above when protected by Class
J Fuses or a Circuit Breaker having an interrupting rating not less than 100,000 rms Symmetrical Amperes, 240 Volts
Maximum." Models FRN; rated for 200V class input.
"Suitable For Use On A Circuit Of Delivering Not More Than 100,000 rms Symmetrical Amperes, 480 Volts Maximum
when protected by Class J Fuses or a Circuit Breaker having an interrupting rating not less than 100,000 rms
Symmetrical Amperes, 480 Volts Maximum." Models VXG; rated for 400V class input.
"Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be
provided in accordance with the National Electrical Code and any additional local codes."
5. Field wiring connections must be made by a UL Listed and CSA Certified closed-loop terminal connector sized for the
wire gauge involved. Connector must be fixed using the crimp tool specified by the connector manufacturer.
6. All circuits with terminals L1/R, L2/S, L3/T, R0, T0, R1, T1 must have a common disconnect and be connected to the
same pole of the disconnect if the terminals are connected to the power supply.
ix
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued)
7. Install UL certified fuses or circuit breaker between the power supply and the inverter, referring to the table below.
VXG18A-2
40
30
60
50
75
75
VXG30AL-2
7.5
VXG46AL-2
11
VXG59AL-2
15
VXG74AL-2
CT
VT
CT
VT
CT
VXG88AL-2
22
CT
CT
VT
CT
VXG115AL-2
150
125
175
150
45
VXG215AL-2
55
VXG283AL-2
75
VXG350AL-2
90
110
CT
VT
CT
VT
CT
VT
VT
400
300
*3
4
(21.2)
-
4
(21.2)
2
(33.6)
3
(26.7)
238.9
(27)
600
400 424.7
(48)
700
500
10.6
(1.2)
*2
*3
-
14
(2.1)
*1
*2
1
(42.4)
1/0
(53.5)
-
*2
*3
-
4/0
(107.2)
2/0×2
(67.4×2)
450
350
4/0
(107.2)
*1
2
(33.6)
-
-
-
6
(13.3)
3
(26.7)
3/0
(85)
500
Aux. fan power supply
8
(8.4)
Aux. control power supply
-
Remarks
12
(3.3)
4
(21.2)
3
(26.7)
119.4
(13.5)
250
12
(3.3)
2/0
(67.4)
200
350
Remarks
*2
2
(33.6)
CT
VT
CT
VXG400AL-2
1
(42.4)
175
VXG146AL-2
VXG180AL-2
3
(26.7)
10.6
(1.2)
250
*1
6
(13.3)
51.3
(5.8)
200
-
-
-
CT
VT
10
(5.3)
14
(2.1)
8
(8.4)
VT
30
37
15.9
(1.8)
VT
VT
18.5
100
10
(5.3)
14
(2.1)
-
30.9
(3.5)
100
14
(2.1)
75qC Cu wire
3.7
14
(2.1)
U, V, W
60qC Cu wire
20
L1/R, L2/S, L3/T
75qC Cu wire
15
30
CT
-
Main terminal
60qC Cu wire
20
VXG11A-2
10.6
(1.2)
Wire size AWG (mm2)
Aux. Fan power supply
Circuit breaker trip size (A)
5
10
2.2
5.5
Three-phase 200 V
10
15
Aux. control power supply
VXG3A-2
0.75 VXG5A-2
1.5 VXG8A-2
Required
torque lb-in
(N‚m)
Main terminal
0.4
Class J fuse size (A)
Inverter type
CT/VT mode
Nominal applied motor
Power supply voltage
3/0×2
(85×2)
3/0×2
(85×2)
4/0×2
(107.2×2)
4/0×2
(107.2×2)
300×2
(152×2)
300×2
(152×2)
*2
*3
*1 No terminal end treatment is required for connection.
*2 Use 75qC Cu wire only.
*3 The wire size of UL Open Type and Enclosed Type are common. Please contact us if UL Open Type exclusive wire is necessary.
x
14
(2.1)
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued)
5.5
VXG16A5L-4E
7.5
VXG23AL-4E
11
VXG30A5L-4E
15
VXG37AL-4E
18.5
VXG45AL-4E
Three-phase 400 V
22
VXG60AL-4E
30
VXG75AL-4E
37
VXG91AL-4E
45
VXG112AL-4E
55
VXG150AL-4E
75
VXG176AL-4E
90
VXG210AL-4E
110
VXG253AL-4E
132
VXG304AL-4E
160
VXG377AL-4E
200
VXG415AL-4E
220
VXG520AL-4E
12
(3.3)
40
10
(5.3)
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
MT/VT
CT
MT/VT
CT
MT/VT
CT
MT/VT
CT
MT/VT
CT
40
60
50
70
60
90
75
100
100
14
(2.1)
14
(2.1)
15.9
(1.8)
30.9
(3.5)
-
-
*1
12
(3.3)
*2
*3
-
8
(8.4)
51.3
(5.8)
6
(13.3)
4
(21.2)
125
10.6
(1.2)
175
6
(13.3)
-
4
(21.2)
2
(33.6)
3
(26.7)
200
1/0
(53.5)
2
(33.6)
350
250
400
300
500
350
2/0
(67.4)
238.9
(27)
1/0×2
(53.5×2)
10.6
(1.2)
424.7
(48)
600
500
700
*2
*3
10
(5.3)
6
(13.3)
14
(2.1)
*1
*2
2
(33.6)
1/0
(53.5)
-
175
200
*1
4
(21.2)
2
(33.6)
250
-
8
(8.4)
6
(13.3)
3
(26.7)
150 119.4
(13.5)
300
Remarks
75qC Cu wire
75qC Cu wire
60qC Cu wire
60qC Cu wire
14
(2.1)
-
125
200
14
(2.1)
U, V, W
-
4/0
(107.2)
*2
*3
-
1/0×2
(53.5×2)
2/0×2
(67.4×2)
3/0×2
(85×2)
3/0×2
(85×2)
4/0×2
(107.2×2)
250×2
(127×2)
250×2
(127×2)
300×2
(152×2)
*2
*3
*1 No terminal end treatment is required for connection.
*2 Use 75qC Cu wire only.
*3 The wire size of UL Open Type and Enclosed Type are common. Please contact us if UL Open Type exclusive wire is necessary.
xi
Aux. fan power supply
30
-
L1/R, L2/S, L3/T
Aux. control power supply
30
10.6
(1.2)
Aux. Fan power supply
CT
Aux. control power supply
10
15
20
5
Main terminal
Remarks
Circuit breaker trip size (A)
CT
3
6
10
15
20
Main terminal
VXG1A5-4E
VXG2A5-4E
VXG4A-4E
VXG5.5A-4E
VXG9A-4E
Wire size AWG (mm2)
Class J fuse size (A)
0.4
0.75
1.5
2.2
4.0
Inverter type
Required
torque lb-in
(N‚m)
CT/MT/VT mode
Nominal applied motor
Power supply voltage
14
(2.1)
*1
*2
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued)
250
600
280
VXG650AL-4E
Three-phase 400 V
315
355
400
450
1000
MT
VXG740AL-4E
CT
VXG650AL-4E
VT
VXG740AL-4E
MT
VXG840AL-4E
CT
VXG740AL-4E
VT
VXG840AL-4E
MT
VXG960AL-4E
CT
VXG840AL-4E
VXG960AL-4E
500
VXG1170AL-4E
630
710
CT
VT
*3
300×2
(152×2)
350×2
(177×2)
400×2
(203×2)
400×2
(203×2)
1200
424.7 10.6 10.6
(48) (1.2) (1.2)
-
500×2
(253×2)
*2
*4
1200
350×3
(177×3)
400×3
(203×3)
2000 1400
500×3
(253×3)
600×3
(304×3)
VT 2200 1600
600×3
(304×3)
500×4
(253×4)
VT
*3
500×2
(253×2)
1600
CT
*2
800
600×2
(304×2)
VT
Remarks
75qC Cu wire
60qC Cu wire
350×2
(177×2)
400×2
(203×2)
300×2
(152×2)
*2
600×2
(304×2)
MT
CT
VXG1370AL-4E
U, V, W
Remarks
300×2
(152×2)
400×2
(203×2)
250×2
(127×2)
VXG520AL-4E
VT
75qC Cu wire
L1/R, L2/S, L3/T
1400
14 14
(2.1) (2.1)
*1
*2 *2
*4
N
*1
*2
*3
*4
Aux. fan power supply
Main terminal
Aux. control power supply
Wire size AWG (mm2)
60qC Cu wire
Aux. Fan power supply
Aux. control power supply
800
Required torque
lb-in (N‚m)
Main terminal
MT
Circuit breaker trip size (A)
Class J fuse size (A)
Inverter type
CT/MT/VT mode
Nominal applied motor
Power supply voltage
No terminal end treatment is required for connection.
Use 75qC Cu wire only.
The wire size of UL Open Type and Enclosed Type are common. Please contact us if UL Open Type exclusive wire is necessary.
It is showing the wire size for UL Open Type.
xii
*1
*2
Table of Contents
5.2 Details of Function Codes ..................................... 5-29
5.2.1 Fundamental Functions .................................. 5-29
5.2.2 E codes (Extension Terminal Functions) ........ 5-67
5.2.3 C codes (Control functions) ............................ 5-92
5.2.4 P codes (Motor 1 Parameters)......................... 5-95
5.2.5 H codes (High Performance Functions).......... 5-99
5.2.6 A codes (Motor 2 Parameters),
b codes (Motor 3 Parameters),
r codes (Motor 4 Parameters) ........................ 5-117
5.2.7 J codes (Application Functions 1) .................5-120
5.2.8 d codes (Application Functions 2) .................5-133
5.2.9 U codes (Application functions 3) .................5-139
5.2.10 y codes (Link Functions) ...............................5-147
Preface
............................................................................... i
„ Safety precautions................................................................. i
Chapter 1 BEFORE USING THE INVERTER .................. 1-1
1.1 Acceptance Inspection ............................................. 1-1
1.2 External View and Terminal Blocks ......................... 1-2
1.3 Precautions for Using Inverters ................................ 1-3
1.3.1 Precautions in introducing inverters .................. 1-3
1.3.2 Precautions in running inverters........................ 1-7
1.3.3 Precautions in using special motors .................. 1-8
Chapter 2 MOUNTING AND WIRING THE
INVERTER ....................................................... 2-1
2.1 Operating Environment ............................................ 2-1
2.2 Installing the Inverter ............................................... 2-1
2.3 Wiring ...................................................................... 2-3
2.3.1 Removing and mounting the front cover and
the wiring guide ................................................ 2-3
2.3.2 Screw specifications and recommended wire
sizes .................................................................. 2-4
2.3.3 Wiring precautions ............................................ 2-7
2.3.4 Wiring of main circuit terminals and grounding
terminals ........................................................... 2-9
2.3.5 Wiring for control circuit terminals ................. 2-16
2.3.6 Setting up the slide switches ........................... 2-23
2.4 Mounting and Connecting a Keypad ...................... 2-25
Chapter 3 OPERATION USING THE KEYPAD
(in the case of remote keypad) ........................... 3-1
3.1 LED Monitor, Keys and LED Indicators on the
Keypad ..................................................................... 3-1
3.2 Overview of Operation Modes ................................. 3-2
3.3 Running Mode ......................................................... 3-3
3.3.1 Monitoring the running status ........................... 3-3
3.3.2 Monitoring light alarms .................................... 3-4
3.4 Programming Mode ................................................. 3-5
3.4.1 Setting up basic function codes quickly
-- Menu #0 "Quick Setup" -- ............................. 3-6
3.4.2 Setting up function codes
-- Menu #1 "Data Setting" -- ............................. 3-7
3.4.3 Checking changed function codes
-- Menu #2 "Data Checking" -- ......................... 3-7
3.4.4 Monitoring the running status
-- Menu #3 "Drive Monitoring" --..................... 3-8
3.4.5 Checking I/O signal status
-- Menu #4 "I/O Checking" -- ......................... 3-11
3.4.6 Reading maintenance information
-- Menu #5 "Maintenance Information" -- ...... 3-14
3.4.7 Reading alarm information
-- Menu #6 "Alarm Information" -- ................. 3-18
3.4.8 Copying data
-- Menu #7 "Data Copying" --......................... 3-20
3.5 Alarm Mode ........................................................... 3-23
3.6 USB Connectivity .................................................. 3-24
Chapter 4 RUNNING THE MOTOR ................................. 4-1
4.1 Running the Motor for a Test ................................... 4-1
4.1.1 Test run procedure............................................. 4-1
4.1.2 Checking prior to powering on ......................... 4-1
4.1.3 Powering ON and checking .............................. 4-2
4.1.4 Switching between CT, MT and VT drive
modes ................................................................ 4-2
4.1.5 Selecting a desired motor drive control ............. 4-3
4.1.6 Function code basic settings < 1 > .................... 4-5
4.1.7 Function code basic settings and tuning < 2 > .. 4-6
4.1.8 Function code basic settings and tuning < 3 > .. 4-8
4.1.9 Function code basic settings < 4 > .................. 4-11
4.1.10 Function code basic settings < 5 > .................. 4-12
4.1.11 Function code basic settings and tuning < 6 > 4-12
4.1.12 Running the inverter for motor operation
check ............................................................... 4-14
4.1.13 Preparation for practical operation .................. 4-16
4.2 Special Operations ................................................. 4-16
4.2.1 Jogging operation ............................................ 4-16
4.2.2 Remote and local modes ................................. 4-16
4.2.3 External run/frequency command ................... 4-17
Chapter 5 FUNCTION CODES............................................ 5-1
5.1 Function Code Tables ............................................... 5-1
Chapter 6 TROUBLESHOOTING .................................... 6-1
6.1 Protective Functions ................................................ 6-1
6.2 Before Proceeding with Troubleshooting ................ 6-3
6.3 If Neither an Alarm Code Nor "Light Alarm"
Indication (ODO) Appears on the LED Monitor ...... 6-4
6.3.1 Abnormal motor operation ............................... 6-4
6.3.2 Problems with inverter settings ........................ 6-9
6.4 If an Alarm Code Appears on the LED Monitor .... 6-10
6.5 If the "Light Alarm" Indication (ODO) Appears
on the LED Monitor .............................................. 6-21
6.6 If an Abnormal Pattern Appears on the LED Monitor
while Neither an Alarm Code nor "Light Alarm"
Indication (ODO) is Displayed............................... 6-22
Chapter 7 MAINTENANCE AND INSPECTION ............ 7-1
7.1 Daily Inspection....................................................... 7-1
7.2 Periodic Inspection .................................................. 7-1
7.3 List of Periodic Replacement Parts .......................... 7-2
7.3.1 Judgment on service life ................................... 7-3
7.4 Measurement of Electrical Amounts in Main
Circuit ...................................................................... 7-5
7.5 Insulation Test ......................................................... 7-6
7.6 IMO Inverter Warranty Statement ........................... 7-7
7.6.1 Terms of IMO 5 year Warranty......................... 7-7
7.6.2 Warranty Restrictions ................................... 7-7
7.6.3 Liability.…………………………………….7-7
Chapter 8 SPECIFICATIONS ........................................... 8-1
8.1 Standard Model (With integral EMC Filter) ........... 8-1
8.1.1 Three-phase 200 V class series ......................... 8-1
8.1.2 Three-phase 400 V class series ......................... 8-2
8.2 Common Specifications ........................................... 8-5
8.3 External Dimensions................................................ 8-7
Chapter 9 CONFORMITY WITH STANDARDS............. 9-1
9.1 Compliance with UL Standards and Canadian
Standards (cUL certification) ................................... 9-1
9.1.1 General ............................................................. 9-1
9.1.2 Considerations when using JAGUAR VXG
in systems to be certified by UL and cUL ........ 9-1
9.2 Compliance with European Standards ..................... 9-1
9.3 Compliance with EMC Standards ............................ 9-1
9.3.1 General ............................................................. 9-1
9.3.2 Recommended installation procedure ............... 9-2
9.3.3 Leakage current of EMC-filter built-in type of
inverters ............................................................ 9-3
9.4 Harmonic Component Regulation in the EU ........... 9-4
9.4.1 General comments ............................................ 9-4
9.4.2 Compliance with the harmonic component
regulation ......................................................... 9-4
9.5 Compliance with the Low Voltage Directive
in the EU.................................................................. 9-4
9.5.1 General ............................................................. 9-4
9.5.2 Points for consideration when using the
JAGUAR VXG series in a system to be certified
by the Low Voltage Directive in the EU ........... 9-4
9.6 Compliance with EN954-1, Category 3 ................... 9-5
9.6.1 General ............................................................. 9-5
9.6.2 EN954-1 ........................................................... 9-5
9.6.3 Notes ................................................................ 9-6
xiii
Chapter 1 BEFORE USING THE INVERTER
1.1 Acceptance Inspection
Unpack the package and check the following:
(1) An inverter and instruction manual (this book) are contained in the package.
• The inverter is not equipped with a keypad when it is shipped. Mount a separately ordered keypad on the
inverter. This manual describes the inverter with a remote keypad. For inverters with a multi-function keypad,
read the Multi-function Keypad Instruction Manual in conjunction with this manual.
• Inverters with a capacity of 55 kW in VT mode and inverters with 75 kW or above require a DC reactor
(DCR) to be connected. Be sure to connect a separately ordered DCR to those inverters.
(2) The inverter has not been damaged during transportation—there should be no dents or parts missing.
(3) The inverter is the type you ordered. You can check the type and specifications on the main nameplate. (Main and sub
nameplates are attached to the inverter and are located as shown on the next page.) For inverters with a capacity of 30 kW
or above, the mass is printed on the main nameplate.
VXG
60AL
VT rating
7.5kW
11kW
15kW
18.5kW
22kW
30kW
37kW
45kW
55kW
75kW
90kW
110kW
132kW
160kW
200kW
220kW
280kW
315kW
355kW
400kW
500kW
630kW
710kW
1A5
2A5
4A
5.5A
9A
16A5L
23AL
30A5L
37AL
45AL
60AL
75AL
91AL
112AL
150AL
176AL
210AL
253AL
304AL
377AL
415AL
520AL
650AL
740AL
840AL
960AL
1170AL
1370AL
Jaguar
CT rating
0.4kW
0.75kW
1.5kW
2.2kW
4.0kW
5.5kW
7.5kW
11kW
15kW
18.5kW
22kW
30kW
37kW
45kW
55kW
75kW
90kW
110kW
132kW
160kW
200kW
220kW
280kW
315kW
355kW
400kW
500kW
630W
-
4
E
E
2
4
Integrated EMC filter
Input voltage 200v/3ph
Input voltage 400v/3ph
㻌
In tables given in this manual, inverter types are denoted as ͆VXG͇
The JAGUAR VXG is available in two or three drive modes depending upon the inverter capacity: Constant Torque (CT) and
Variable Torque (VT) modes or Constant Torque (CT), Medium Torque (MT) and Variable Torque (VT) modes. One of these
modes should be selected to match the load property of your system. Specifications in each mode are printed on the main
nameplate. For details, see Chapter 8 "SPECIFICATIONS."
Constant Torque:
CT mode designed for heavy duty load applications. Overload capability: 150% for 1 min, 200% for 3
s. Continuous ratings = Inverter ratings
Medium Torque:
MT mode designed for medium duty load applications. Overload capability: 150% for 1 min.
Continuous ratings = One rank higher capacity of inverters
Variable Torque:
VT mode designed for light duty load applications. Overload capability: 120% for 1 min. Continuous
ratings = One rank or two ranks higher capacity of inverters
SOURCE:
Number of input phases (three-phase: 3PH), input voltage, input frequency, input current (each for CT, MT
and VT modes)
OUTPUT:
Number of output phases, rated output voltage, output frequency range, rated output capacity, rated output
current, overload capability (each for CT, MT and VT modes)
SCCR:
Short-circuit capacity
MASS:
Mass of the inverter in kilogram (30 kW or above)
SER. No.:
Product number
81A123A0001Z
Serial number of production lot
Production month
1 to 9: January to September
X, Y, or Z: October, November, or December
Production year: Last digit of year
If you suspect the product is not working properly or if you have any questions about your product, contact your IMO
representative.
1-1
Chap. 1
1.2 External View and Terminal Blocks
(1) Outside and inside views
BEFORE USING THE INVERTER
(a) VXG30A5L-4E
(b) VXG520AL-4E
Figure 1.2
Outside and Inside Views of Inverters
(2) Warning plates and label
(a) VXG30A5L-4E
(b) VXG520AL-4E
Figure 1.3
Warning Plates and Label
1-2
1.3 Precautions for Using Inverters
1.3.1 Precautions in introducing inverters
This section provides precautions in introducing inverters, e.g. precautions for installation environment, power supply lines,
wiring, and connection to peripheral equipment. Be sure to observe those precautions.
„ Installation environment
Install the inverter in an environment that satisfies the requirements listed in Table 2.1 in Chapter 2.
IMO strongly recommends installing inverters in a panel for safety reasons, in particular, when installing the ones whose
enclosure rating is IP00.
When installing the inverter in a place out of the specified environmental requirements, it is necessary to derate the inverter
or consider the panel engineering design suitable for the special environment or the panel installation location. For details,
refer to the IMO technical information "Engineering Design of Panels" or consult your IMO representative.
The special environments listed below require using the specially designed panel or considering the panel installation
location.
Environments
Possible problems
Highly concentrated
sulfidizing gas or
other corrosive gases
Corrosive gases cause parts
inside the inverter to corrode,
resulting in an inverter
malfunction.
Any of the following measures may
be necessary.
A lot of conductive
dust or foreign
material (e.g., metal
powders or shavings,
carbon fibers, or
carbon dust)
Entry of conductive dust into
the inverter causes a short
circuit.
Any of the following measures may
be necessary.
A lot of fibrous or
paper dust
Fibrous or paper dust
accumulated on the heat sink
lowers the cooing effect.
Any of the following measures may
be necessary.
Entry of dust into the inverter
causes the electronic circuitry
to malfunction.
Sample measures
- Mount the inverter in a sealed
panel with IP6X or air-purge
mechanism.
- Place the panel in a room free
from influence of the gases.
- Mount the inverter in a sealed
panel.
- Place the panel in a room free
from influence of the conductive
dust.
Applications
Paper manufacturing,
sewage disposal, sludge
treatment, tire
manufacturing, gypsum
manufacturing, metal
processing, and a
particular process in
textile factories.
Wiredrawing machines,
metal processing,
extruding machines,
printing presses,
combustors, and industrial
waste treatment.
Textile manufacturing and
paper manufacturing.
- Mount the inverter in a sealed
panel that shuts out dust.
- Ensure a maintenance space for
periodical cleaning of the heat sink
in panel engineering design.
- Employ external cooling when
mounting the inverter in a panel
for easy maintenance and perform
periodical maintenance.
High humidity or
dew condensation
In an environment where a
humidifier is used or where
the air conditioner is not
equipped with a
dehumidifier, high humidity
or dew condensation results,
which causes a
short-circuiting or
malfunction of electronic
circuitry inside the inverter.
- Put a heating module such as a
space heater in the panel.
Outdoor installation.
Vibration or shock
exceeding the
specified level
If a large vibration or shock
exceeding the specified level
is applied to the inverter, for
example, due to a carrier
running on seam joints of
rails or blasting at a
construction site, the inverter
structure gets damaged.
- Insert shock-absorbing materials
between the mounting base of the
inverter and the panel for safe
mounting.
Installation of an inverter
panel on a carrier or
self-propelled machine.
Halogen compounds such as
methyl bromide used in
fumigation corrodes some
parts inside the inverter.
- When exporting an inverter built
in a panel or equipment, pack
them in a previously fumigated
wooden crate.
- When packing an inverter alone
for export, use a laminated veneer
lumber (LVL).
Exporting.
Fumigation for
export packaging
Film manufacturing line,
pumps and food
processing.
Ventilating fan at a
construction site or a press
machine.
„ Storage environment
The storage environment in which the inverter is stored after purchase is different from the operation environment. For details,
refer to the VXG-MANUAL
1-3
No output circuit filter installed
Output circuit filter installed
Power
input
Max. 5 m
Power
input
Inverter
Motor
Output circuit filter
Inverter
Max. 50 m
Max. 100 m
Motor
Max. 400 m
For an inverter with an output circuit filter installed, the total secondary wiring length should be 400 m or less (100 m or
less under the vector control).
If further longer secondary wiring is required, consult your IMO representative.
(5) Precautions for surge voltage in driving a motor by an inverter (especially for 400 V class, general-purpose motors)
If the motor is driven by a PWM-type inverter, surge voltage generated by switching the inverter component may be
superimposed on the output voltage and may be applied to the motor terminals. Particularly if the wiring length is long,
the surge voltage may deteriorate the insulation resistance of the motor. Implement any of the following measures.
- Use a motor with insulation that withstands the surge voltage.
- Connect a surge suppressor unit at the motor terminal.
- Connect an output circuit filter to the output terminals (secondary circuits) of the inverter.
- Minimize the wiring length between the inverter and motor (10 to 20 m or less).
(6) When an output circuit filter is inserted in the secondary circuit or the wiring between the inverter and the motor is long,
a voltage loss occurs due to reactance of the filter or wiring so that the insufficient voltage may cause output current
oscillation or a lack of motor output torque. To avoid it, select the constant torque load by setting the function code F37
(Load Selection/Auto Torque Boost/Auto Energy Saving Operation 1) to "1" and keep the inverter output voltage at a
higher level by configuring H50/H52 (Non-linear V/f Pattern, Frequency) and H51/H53 (Non-linear V/f Pattern,
Voltage).
„ Precautions for connection of peripheral equipment
(1) Phase-advancing capacitors for power factor correction
Do not mount a phase-advancing capacitor for power factor correction in the inverter's input (primary) or output
(secondary) circuit. Mounting it in the input (primary) circuit takes no effect. To correct the inverter power factor, use an
optional DC reactor (DCR). Mounting it in the output (secondary) circuit causes an overcurrent trip, disabling operation.
An overvoltage trip that occurs when the inverter is stopped or running with a light load is assumed to be due to surge
current generated by open/close of phase-advancing capacitors in the power system. An optional DC/AC reactor
(DCR/ACR) is recommended as a measure to be taken at the inverter side.
Input current to an inverter contains a harmonic component that may affect other motors and phase-advancing capacitors
on the same power supply line. If the harmonic component causes any problems, connect an optional DCR/ACR to the
inverter. In some cases, it is necessary to insert a reactor in series with the phase-advancing capacitors.
(2) Power supply lines (Application of a DC/AC reactor)
Use an optional DC reactor (DCR) when the capacity of the power supply transformer is 500 kVA or more and is 10
times or more the inverter rated capacity or when there are thyristor-driven loads. If no DCR is used, the
percentage-reactance of the power supply decreases, and harmonic components and their peak levels increase. These
factors may break rectifiers or capacitors in the converter section of the inverter, or decrease the capacitance of the
capacitors.
If the input voltage unbalance rate is 2% to 3%, use an optional AC reactor (ACR).
9ROWDJH XQEDODQFH 0D[ YROWDJH 90LQYROWDJH 9
™ ,(& - 7KUHH SKDVH DYHUDJH YROWDJH 9
(3) DC reactor (DCR) for correcting the inverter input power factor (for suppressing harmonics)
To correct the inverter input power factor (to suppress harmonics), use an optional DCR. Using a DCR increases the
reactance of inverter’s power source so as to decrease harmonic components on the power source lines and correct the
power factor of the inverter.
1-4
BEFORE USING THE INVERTER
(1) Route the wiring of the control circuit terminals as far from the wiring of the main circuit as possible. Otherwise electric
noise may cause malfunctions.
(2) Fix the control circuit wires inside the inverter to keep them away from the live parts of the main circuit (such as the
terminal block of the main circuit).
(3) If more than one motor is to be connected to a single inverter, the wiring length should be the sum of the length of the
wires to the motors.
(4) Precautions for high frequency leakage currents
If the wiring distance between an inverter and a motor is long, high frequency currents flowing through stray capacitance
across wires of phases may cause an inverter overheat, overcurrent trip, increase of leakage current, or it may not assure
the accuracy in measuring leakage current. Depending on the operating condition, an excessive leakage current may
damage the inverter.
To avoid the above problems when directly connecting an inverter to a motor, keep the wiring distance 50 m or less for
inverters with a capacity of 3.7 kW or below, and 100 m or less for inverters with a higher capacity.
If the wiring distance longer than the specified above is required, lower the carrier frequency or insert an output circuit
filter as shown below.
When the inverter drives two or more motors connected in parallel (group drive), in particular, using shielded wires, the
stray capacitance to the earth is large, so lower the carrier frequency or insert an output circuit filter.
Chap. 1
„ Wiring precautions
DCR models
Consult IMO
Input power factor
Approx. 90% to 95%
Remarks
The last letter identifies the capacitance.
Consult IMO
Approx. 86% to 90%
Exclusively designed for nominal applied motor of 37 kW
or above.
Select a DCR matching not the inverter but the nominal applied motor. Applicable reactors differ depending
upon the selected CT, MT, or VT mode even on the same type of inverters.
(4) PWM converter for correcting the inverter input power factor
Using a PWM converter (High power-factor, regenerative PWM converter, RHC series) corrects the inverter power factor
up to nearly 100%. When combining an inverter with a PWM converter, disable the main power loss detection by setting
the function code H72 to "0." If the main power loss detection is enabled (H72 = 1 by factory default), the inverter
interprets the main power as being shut down, ignoring an entry of a run command.
(5) Molded case circuit breaker (MCCB) or residual-current-operated protective device (RCD)/earth leakage circuit breaker
(ELCB)
Install a recommended MCCB or RCD/ELCB (with overcurrent protection) in the primary circuit of the inverter to
protect the wiring. Since using an MCCB or RCD/ELCB with a lager capacity than recommended ones breaks the
protective coordination of the power supply system, be sure to select recommended ones. Also select ones with
short-circuit breaking capacity suitable for the power source impedance.
Molded Case Circuit Breaker (MCCB) and
Residual-Current-Operated Protective Device (RCD)/Earth Leakage Circuit Breaker (ELCB)
Nominal
Power
applied
supply
motor
voltage
(kW)
0.4
0.75
1.5
2.2
4.0
5.5
Inverter type
VXG3A-2
VXG5A-2
VXG8A-2
VXG11A-2
VXG18A-2
VXG30AL-2
7.5
VXG46AL-2
11
Three-phase 200 V VXG59AL-2
15
VXG74AL-2
18.5
VXG88AL-2
22
VXG88AL-2
30
VXG146AL-2
37
VXG180AL-2
45
VXG215AL-2
55
VXG283AL-2
75
VXG350AL-2
90
110
VXG400AL-2
CT/
MT/
VT
mode
CT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
Rated current of
MCCB and
RCD/ELCB (A)
w/ DCR w/o DCR
5
5
10
15
10
20
20
30
30
50
Nominal
Power
applied
supply
motor
voltage
(kW)
18.5
Three-phase 400 V
0.4
0.75
1.5
2.2
4.0
5.5
Inverter type
VXG1A5-4E
VXG2A5-4E
VXG4A-4E
VXG5.5A-4E
VXG9A-4E
VXG16A5L-4E
7.5
VXG23AL-4E
11
VXG30A5L-4E
15
VXG37AL-4E
CT/
MT/
VT
mode
VXG60AL-4E
30
VXG75AL-4E
40
75
37
50
100
45
VXG91AL-4E
VXG112AL-4E
75
125
55
VXG150AL-4E
150
75
VXG176AL-4E
100
175
90
VXG210AL-4E
150
200
110
VXG253AL-4E
175
200
250
250
300
350
350
400
132
VXG304AL-4E
160
VXG377AL-4E
200
VXG415AL-4E
220
250
--
VXG650AL-4E
315
Rated current of
MCCB and
RCD/ELCB (A)
w/ DCR w/o DCR
5
5
15
10
15
20
30
20
40
10
VXG520AL-4E
280
350
CT
CT
VT
CT
VT
CT
VT
CT
VXG37AL-4E
22
Nominal
Power
applied
supply
motor
voltage
(kW)
Inverter type
VXG45AL-4E
Three-phase 400 V
355
400
450
VXG740AL-4E
VXG650AL-4E
VXG740AL-4E
VXG840AL-4E
VXG740AL-4E
VXG840AL-4E
VXG960AL-4E
VXG840AL-4E
VXG960AL-4E
500
VXG1170AL-4E
630
30
50
40
60
710
1-5
VXG1370AL-4E
CT/
MT/
VT
mode
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
MT/VT
CT
MT/VT
CT
MT/VT
CT
MT/VT
CT
MT/VT
CT
MT
VT
CT
MT
CT
VT
MT
CT
VT
MT
CT
VT
MT
VT
CT
VT
CT
VT
Rated current of
MCCB and
RCD/ELCB (A)
w/ DCR w/o DCR
40
75
50
100
75
125
100
150
125
200
175
200
250
300
350
500
600
800
1200
1400
1600
--
Otherwise, a fire could occur.
(6) Magnetic contactor (MC) in the inverter input (primary) circuit
Avoid frequent ON/OFF operation of the magnetic contactor (MC) in the input circuit; otherwise, the inverter failure may
/
keys on the
result. If frequent start/stop of the motor is required, use FWD/REV terminal signals or the
inverter's keypad.
The frequency of the MC's ON/OFF should not be more than once per 30 minutes. To assure 10-year or longer service
life of the inverter, it should not be more than once per hour.
• From the system's safety point of view, it is recommended to employ such a sequence that shuts down the
magnetic contactor (MC) in the inverter input circuit with an alarm output signal ALM issued on inverter's
programmable output terminals. The sequence minimizes the secondary damage even if the inverter breaks.
When the sequence is employed, connecting the MC's primary power line to the inverter's auxiliary control
power input makes it possible to monitor the inverter's alarm status on the keypad.
• The breakdown of a braking unit or misconnection of an external braking resistor may trigger that of the
inverter's internal parts (e.g., charging resistor). To avoid such a breakdown linkage, introduce an MC and
configure a sequence that shuts down the MC if a DC link voltage establishment signal is not issued within
three seconds after the MC is switched on.
For the braking transistor built-in type of inverters, assign a transistor error output signal DBAL on inverter's
programmable output terminals to switch off the MC in the input circuit.
(7) Magnetic contactor (MC) in the inverter output (secondary) circuit
If a magnetic contactor (MC) is inserted in the inverter's output (secondary) circuit for switching the motor to a
commercial power or for any other purposes, it should be switched on and off when both the inverter and motor are
completely stopped. This prevents the contact point from getting rough due to a switching arc of the MC. The MC should
not be equipped with any main circuit surge killer.
Applying a commercial power to the inverter's output circuit breaks the inverter. To avoid it, interlock the MC on the
motor's commercial power line with the one in the inverter output circuit so that they are not switched ON at the same
time.
(8) Surge absorber/surge killer
Do not install any surge absorber or surge killer in the inverter's output (secondary) lines.
„ Noise reduction
If noise generated from the inverter affects other devices, or that generated from peripheral equipment causes the inverter to
malfunction, follow the basic measures outlined below.
(1) If noise generated from the inverter affects the other devices through power wires or grounding wires:
- Isolate the grounding terminals of the inverter from those of the other devices.
- Connect a noise filter to the inverter power wires.
- Isolate the power system of the other devices from that of the inverter with an insulated transformer.
- Decrease the inverter's carrier frequency (F26).
(2) If induction or radio noise generated from the inverter affects other devices:
- Isolate the main circuit wires from the control circuit wires and other device wires.
- Put the main circuit wires through a metal conduit pipe, and connect the pipe to the ground near the inverter.
- Install the inverter into the metal panel and connect the whole panel to the ground.
- Connect a noise filter to the inverter's power wires.
- Decrease the inverter's carrier frequency (F26).
(3) When implementing measures against noise generated from peripheral equipment:
- For inverter's control signal wires, use twisted or shielded-twisted wires. When using shielded-twisted wires, connect
the shield of the shielded wires to the common terminals of the control circuit.
- Connect a surge absorber in parallel with magnetic contactor's coils or other solenoids (if any).
1-6
BEFORE USING THE INVERTER
If no zero-phase current (earth leakage current) detective device such as a ground-fault relay is installed in the
upstream power supply line in order to avoid the entire power supply system's shutdown undesirable to factory
operation, install a residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB)
individually to inverters to break the individual inverter power supply lines only.
Chap. 1
„ Leakage current
A high frequency current component generated by insulated gate bipolar transistors (IGBTs) switching on/off inside the
inverter becomes leakage current through stray capacitance of inverter input and output wires or a motor. If any of the
problems listed below occurs, take an appropriate measure against them.
Problem
An earth leakage circuit
breaker* that is connected
to the input (primary) side
has tripped.
*With overcurrent protection
An external thermal relay
was activated.
Measures
1)
2)
3)
4)
Decrease the carrier frequency.
Make the wires between the inverter and motor shorter.
Use an earth leakage circuit breaker with lower sensitivity than the one currently used.
Use an earth leakage circuit breaker that features measures against the high frequency
current component.
1) Decrease the carrier frequency.
2) Increase the current setting of the thermal relay.
3) Use the electronic thermal overload protection built in the inverter, instead of the
external thermal relay.
„ Selecting inverter capacity
(1) To drive a general-purpose motor, select an inverter according to the nominal applied motor rating listed in the standard
specifications table. When high starting torque is required or quick acceleration or deceleration is required, select an
inverter with one rank higher capacity than the standard.
(2) Special motors may have larger rated current than general-purpose ones. In such a case, select an inverter that meets the
following condition.
Inverter rated current > Motor rated current
1.3.2 Precautions in running inverters
Precautions for running inverters to drive motors or motor-driven machinery are described below.
„ Motor temperature
When an inverter is used to run a general-purpose motor, the motor temperature becomes higher than when it is operated with
a commercial power supply. In the low-speed range, the motor cooling effect will be weakened, so decrease the output torque
of the motor when running the inverter in the low-speed range.
„ Motor noise
When a general-purpose motor is driven by an inverter, the noise level is higher than that when it is driven by a commercial
power supply. To reduce noise, raise carrier frequency of the inverter. Operation at 60 Hz or higher can also result in higher
noise level.
„ Machine vibration
When an inverter-driven motor is mounted to a machine, resonance may be caused by the natural frequencies of the
motor-driven machinery. Driving a 2-pole motor at 60 Hz or higher may cause abnormal vibration. If it happens, do any of
the following:
- Consider the use of a rubber coupling or vibration-proof rubber.
- Use the inverter's jump frequency control feature to skip the resonance frequency zone(s).
- Use the vibration suppression related function codes that may be effective. For details, refer to the description of H80 in
Chapter 5 "FUNCTION CODES."
1-7
Chap. 1
1.3.3 Precautions in using special motors
When using special motors, note the followings.
„ Explosion-proof motors
„ Submersible motors and pumps
These motors have a larger rated current than general-purpose motors. Select an inverter whose rated output current is greater
than that of the motor. These motors differ from general-purpose motors in thermal characteristics. Decrease the thermal time
constant of the electronic thermal overload protection to match the motor rating.
„ Brake motors
For motors equipped with parallel-connected brakes, their power supply for braking must be supplied from the inverter input
(primary) circuit. If the power supply for braking is mistakenly connected to the inverter's output (secondary) circuit, the
brake may not work when the inverter output is shut down. Do not use inverters for driving motors equipped with
series-connected brakes.
„ Geared motors
If the power transmission mechanism uses an oil-lubricated gearbox or speed changer/reducer, then continuous operation at
low speed may cause poor lubrication. Avoid such operation.
„ Synchronous motors
It is necessary to take special measures suitable for this motor type. Contact your IMO representative for details.
„ Single-phase motors
Single-phase motors are not suitable for inverter-driven variable speed operation.
„ High-speed motors
If the reference frequency is set to 120 Hz or higher to drive a high-speed motor, test-run the combination of the inverter and
motor beforehand to check it for the safe operation.
1-8
BEFORE USING THE INVERTER
When driving an explosion-proof motor with an inverter, use a combination of a motor and an inverter that has been
approved in advance.
Chapter 2 MOUNTING AND WIRING THE INVERTER
2.1 Operating Environment
Install the inverter in an environment that satisfies the requirements listed in Table 2.1.
Table 2.1
Environmental Requirements
Item
Table 2.2 Output Current Derating
Factor in Relation to Altitude
Specifications
Output current
derating factor
Site location
Indoors
Surrounding/ambient
temperature
Relative humidity
-10 to +50qC (Note 1)
1000 m or lower
1.00
5 to 95% (No condensation)
1000 to 1500 m
0.97
Atmosphere
The inverter must not be exposed to dust, direct sunlight, corrosive
gases, flammable gases, oil mist, vapor or water drops.
Pollution degree 2 (IEC60664-1) (Note 2)
The atmosphere can contain a small amount of salt.
(0.01 mg/cm2 or less per year)
The inverter must not be subjected to sudden changes in
temperature that will cause condensation to form.
1500 to 2000 m
0.95
2000 to 2500 m
0.91
2500 to 3000 m
0.88
Altitude
1,000 m max. (Note 3)
Atmospheric pressure
86 to 106 kPa
55 kW or below (200 V class series)
75 kW or below (400 V class series)
3 mm (Max. amplitude)
2 to less than 9 Hz
9.8 m/s2 9 to less than 20 Hz
2 m/s2 20 to less than 55 Hz
1 m/s2 55 to less than 200 Hz
Vibration
Altitude
75 kW or above (200 V class series)
90 kW or above (400 V class series)
3 mm (Max. amplitude)
2 to less than 9 Hz
2 m/s2 9 to less than 55 Hz
1 m/s2 55 to less than 200 Hz
(Note 1) When inverters are mounted
side-by-side without any clearance between
them (22 kW or below), the surrounding
temperature should be within the range from
-10 to +40qC.
(Note 2) Do not install the inverter in an
environment where it may be exposed to lint,
cotton waste or moist dust or dirt which will
clog the heat sink of the inverter. If the
inverter is to be used in such an environment,
install it in a dustproof panel of your system.
(Note 3) If you use the inverter in an altitude
above 1000 m, you should apply an output
current derating factor as listed in Table 2.2.
2.2 Installing the Inverter
(1) Mounting base
Install the inverter on a base made of metal or other non-flammable material. Do not
mount the inverter upside down or horizontally.
Install the inverter on a base made of metal or other non-flammable material.
Otherwise, a fire could occur.
(2) Clearances
Ensure that the minimum clearances indicated in Figure 2.1 and Table 2.3 are maintained
at all times. When mounting the inverter in the panel of your system, take extra care with
ventilation inside the panel as the surrounding temperature easily rises. Do not install the
inverter in a small panel with poor ventilation.
„ When mounting two or more inverters
When mounting two or more inverters in the same unit or panel, basically lay them out
side by side. When mounting them necessarily one above the other, be sure to separate
them with a partition plate or the like so that any heat radiating from an inverter will not
affect the one/s above.
As long as the surrounding temperature is 40°C or lower, inverters with a capacity of 22
kW or below can be mounted side by side without any clearance between them.
Table 2.3 Clearances
(mm)
A
B
C
Inverter capacity
0.4 to 1.5 kW
50
0
100
2.2 to 22 kW
10
30 to 220 kW
100
50
280 to 630 kW
150
150
C: Space required in front of the inverter unit
2-1
Figure 2.1 Mounting Direction and
Required Clearances
2-2
Figure 2.2
External Cooling
MOUNTING AND WIRING THE INVERTER
Prevent lint, paper fibers, sawdust, dust, metallic chips, or other foreign materials
from getting into the inverter or from accumulating on the heat sink.
Otherwise, a fire or accident could occur.
Chap. 2
„ When employing external cooling
In external cooling, the heat sink, which dissipates about 70% of the total heat (total
loss) generated into air, is situated outside the equipment or the panel. The external
cooling, therefore, significantly reduces heat radiating inside the equipment or panel.
To employ external cooling for inverters with a capacity of 22 kW or below, use the
external cooling attachment option; for those with a capacity of 30 kW or above,
simply change the positions of the mounting bases.
To utilize external cooling for inverters with a capacity of 30 kW or above, change the positions of the top and bottom
mounting bases from the edge to the center of the inverter as shown in Figure 2.3.
Screws differ in size and count for each inverter. Refer to the table below.
Table 2.4
Screw Size, Count and Tightening Torque
Base fixing screw
(Screw size and q'ty)
Inverter type
Case fixing screw
(Screw size and q'ty)
Tightening
torque
(Nxm)
VXG146AL-2/VXG180AL-2
VXG75AL-4E to VXG150AL-4E
M6 u 20
5 pcs for upper side,
3 pcs for lower side
M6 u 20
2 pcs for upper side
5.8
VXG215AL-2/VXG283AL-2
VXG176AL-4E
M6 u 20
M6 u 12
3 pcs each for upper and lower sides 3 pcs for upper side
5.8
VXG350AL-2
VXG210AL-4E/VXG253AL-4E
M5 u12
M5 u 12
7 pcs each for upper and lower sides 7 pcs for upper side
3.5
VXG304AL-4E/VXG377AL-4E
M5 u 16
M5 u 16
7 pcs each for upper and lower sides 7 pcs for upper side
3.5
VXG400AL-2
VXG415AL-4E/VXG520AL-4E
M5 u 16
M5 u 16
8 pcs each for upper and lower sides 8 pcs for upper side
3.5
VXG650AL-4E/VXG740AL-4E
VXG840AL-4E/VXG960AL-4E
M5 u 16
2 pcs each for upper and lower sides
M6 u 20
6 pcs each for upper and lower sides
VXG1170AL-4E/VXG1370AL-4E
M8 u 20
M8 u 20
8 pcs each for upper and lower sides 8 pcs each for upper and lower sides
M5 u 16
2 pcs each for upper and lower sides
M6 u 20
6 pcs each for upper and lower sides
3.5
5.8
13.5
1) Remove all of the base fixing screws and the case fixing screws from the top of the inverter.
2) Move the top mounting base to the center of the inverter and secure it to the case fixing screw holes with the base fixing
screws. (After changing the position of the top mounting base, some screws may be left unused.)
3) Remove the base fixing screws from the bottom of the inverter, move the bottom mounting base to the center of the
inverter, and secure it with the base fixing screws, just as in step 2). (Inverters with a capacity of 220 kW or below have
no case fixing screws on the bottom.)
Figure 2.3
Changing the Positions of the Top and Bottom Mounting Bases
When changing the positions of the top and bottom mounting bases, use only the specified screws.
Otherwise, a fire or accident could occur.
2-3
2.3 Wiring
Follow the procedure below. (In the following description, the inverter has already been installed.)
2.3.1 Removing and mounting the front cover and the wiring guide
Figure 2.4
Removing the Front Cover and the Wiring Guide (VXG30A5L-4E)
(2) For inverters with a capacity of 30 to 630 kW
Loosen the four front cover fixing screws, hold the cover with both hands, slide it upward slightly, and pull it toward you,
as shown below.
After carrying out wiring (see Sections 2.3.2 through 2.3.6), align the screw holes provided in the front cover with the
screws on the inverter case, then put the front cover back into place in the reverse order of removal.
To expose the control printed circuit board (control PCB), open the keypad enclosure.
Tightening torque: 1.8 Nxm (M4)
3.5 Nxm (M5)
Figure 2.5
Removing the Front Cover (VXG75AL-4E)
2-4
MOUNTING AND WIRING THE INVERTER
First loosen the front cover fixing screw, slide the cover downward holding its both sides, tilt it toward you, and then pull
it upward, as shown below.
While pressing the wiring guide upward, pull it out toward you.
After carrying out wiring (see Sections 2.3.2 through 2.3.6), put the wiring guide and the front cover back into place in the
reverse order of removal.
Chap. 2
(1) For inverters with a capacity of 22 kW or below
2.3.2 Screw specifications and recommended wire sizes
(1) Arrangement of main circuit terminals
The tables and figures given below show the screw specifications and wire sizes. Note that the terminal arrangements differ
depending on the inverter types. In each of the figures, two grounding terminals ( G) are not exclusive to the power supply
wiring (primary circuit) or motor wiring (secondary circuit).
Use crimp terminals covered with an insulation sheath or with an insulation tube. The recommended wire sizes for the main
circuits are examples of using a single HIV wire (JIS C3317) (for 75°C) at a surrounding temperature of 50qC.
Table 2.5
Inverter type
Three-phase
200 V
VXG3A-2
VXG5A-2
VXG8A-2
VXG11A-2
VXG18A-2
VXG30AL-2
VXG46AL-2
VXG59AL-2
VXG74AL-2
VXG88AL-2
VXG115AL-2
VXG146AL-2
VXG180AL-2
VXG215AL-2
VXG283AL-2
--VXG350AL-2
--VXG400AL-2
-------
Three-phase
400 V
VXG1A5-4E
VXG2A5-4E
VXG4A-4E
VXG5.5A-4E
Screw Specifications
Refer to:
Screw specifications
Auxiliary control
Auxiliary fan
power input
power input
Main circuit
Grounding terminals
terminals
terminals
terminals
[R0, T0]
[R1, T1]
Tightening
Tightening
Tightening
Tightening
Screw
Screw
Screw
Screw
torque
torque
torque
torque
size
size
size
size
(N·m)
(N·m)
(N·m)
(N·m)
Figure A
M3.5
1.2
M3.5
1.2
Figure B
M4
1.8
M4
1.8
Figure C
M5
3.5
M5
3.5
VXG9A-4E
VXG16A5L-4E
VXG23AL-4E
VXG30A5L-4E
VXG37AL-4E
VXG45AL-4E
VXG60AL-4E
VXG75AL-4E
VXG91AL-4E
VXG112AL-4E
VXG150AL-4E
Figure D
M6
5.8
Figure E
M8
13.5
VXG176AL-4E
Figure F
5.8
M8
13.5
M3.5
M10
VXG210AL-4E
VXG253AL-4E
-VXG304AL-4E
VXG377AL-4E
VXG415AL-4E
VXG520AL-4E
VXG650AL-4E
VXG740AL-4E
VXG840AL-4E
VXG960AL-4E
VXG1170AL-4E
VXG1370AL-4E
M6
--
--
--
--
M3.5
1.2
1.2
27
Figure G
Figure M
Figure H
Figure I
Figure J
M12
48
M10
27
Figure K
Figure L
When the inverter power is ON, a high voltage is applied to the following terminals.
Main circuit terminals: L1/R, L2/S, L3/T, P1, P(+), N(-), DB, U, V, W, R0, T0, R1, T1, AUX-contact (30A, 30B, 30C,
Y5A, Y5C)
Insulation level
Main circuit Enclosure
: Basic insulation (Overvoltage category III, Pollution degree 2)
Main circuit Control circuit : Reinforced insulation (Overvoltage category III, Pollution degree 2)
Relay output Control circuit : Reinforced insulation (Overvoltage category II, Pollution degree 2)
An electric shock may occur.
2-5
Chap. 2
Refer to
* Section
2.3.3 (9).
2-6
MOUNTING AND WIRING THE INVERTER
Grounding terminal for input line, provided
* only
on the EMC filter built-in type
Power supply
voltage
Table 2.6
Nominal
applied
motor
(kW)
Three-phase 200 V
0.4
0.75
1.5
2.2
4.0
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
0.4
0.75
1.5
2.2
4.0
5.5
7.5
11
15
18.5
22
Three-phase 400 V
30
37
45
55
75
90
110
132
160
200
220
250
280
315
355
400
450
500
630
710
Recommended Wire Sizes
Recommended wire size (mm2 )
Main circuit power input
Inverter
Braking
Grounding
DCR
(L1/R, L2/S, L3/T)
output
resistor
[ G]
[P1, P(+)]
[U, V, W]
[P(+), DB]
w/ DCR
w/o DCR
Inverter type
CT mode
VT mode
VXG3A-2
VXG5A-2
VXG8A-2
VXG11A-2
VXG18A-2
VXG30AL-2
-VXG46AL-2
VXG59AL-2
VXG74AL-2
VXG88AL-2
VXG115AL-2
-VXG146AL-2
VXG180AL-2
VXG215AL-2
VXG283AL-2
VXG350AL-2
VXG400AL-2
-VXG1A5-4E
VXG2A5-4E
VXG4A-4E
VXG5.5A-4E
VXG9A-4E
VXG16A5L-4E
VXG23A-4E
-VXG30A5L-4E
VXG37AL-4E
VXG45AL-4E
VXG60AL-4E
-VXG75AL-4E
VXG91AL-4E
VXG112AL-4E
VXG150AL-4E
VXG176AL-4E
VXG210AL-4E
VXG253AL-4E
VXG304AL-4E
VXG377AL-4E
VXG415AL-4E
VXG520AL-4E
--VXG650AL-4E
VXG740AL-4E
VXG840AL-4E
VXG960AL-4E
-VXG1170AL-4E
VXG1370AL-4E
--
------VXG30AL-2
-VXG46AL-2
VXG59AL-2
VXG74AL-2
VXG88AL-2
VXG115AL-2
-VXG146AL-2
VXG180AL-2
VXG215AL-2
VXG283AL-2
VXG350AL-2
VXG400AL-2
------VXG16A5L-4E
VXG23A-4E
-VXG30A5L-4E
VXG37AL-4E
VXG45AL-4E
VXG60AL-4E
-VXG75AL-4E
VXG91AL-4E
VXG112AL-4E
VXG150AL-4E
VXG176AL-4E
VXG210AL-4E
VXG253AL-4E
VXG304AL-4E
VXG377AL-4E
VXG415AL-4E
-VXG520AL-4E
--VXG650AL-4E
VXG740AL-4E
VXG840AL-4E
VXG960AL-4E
VXG1170AL-4E
VXG1370AL-4E
MT mode
---------------------------------------VXG176AL-4E
VXG210AL-4E
VXG253AL-4E
VXG304AL-4E
VXG377AL-4E
VXG415AL-4E
--VXG650AL-4E
VXG740AL-4E
VXG840AL-4E
VXG960AL-4E
----
2.0
2.0
2.0
3.5
3.5
3.5
5.5
5.5
14
14
22
22
38 *2
38 *2
60 *3
38
60
60
100
150 *4
150
200
100
5.5
3.5
5.5
8.0
8.0
14
14
22
38 *2
38
22
-38
2.0
2.0
60
100
150 *4
150
200
2.0
2.0
2.0
2.0
3.5
5.5
2.0
8.0
14
22
38 *2
38
60
100
--
150
200
250
2.0
2.0
3.5
3.5
5.5
5.5
8.0 *5
3.5
5.5
14
14
22
22
8.0
14
22
200
38
--
14
22
38
60
100
60
100
150
200
250
250
150u2
325
325
200u2
250u2
325u2
325u3
250u4
60
150
150
150u2
14
5.5
8.0 *5
100
100
250
5.5
8.0 *5
22
38
38
38
60
3.5
3.5
--
200u2
200u2
250u2
250u2
325u2
325u2
325u3
325u4
325u4
325u3
*2 Use the crimp terminal model No. 38-6 manufactured by JST Mfg. Co., Ltd., or equivalent.
*3 Use the crimp terminal model No. 60-6 manufactured by JST Mfg. Co., Ltd., or equivalent.
*4 When using 150 mm2 wires for main circuit terminals of VXG282AL-2E (VT mode), use CB150-10 crimp terminals designed for low voltage
appliances in JEM1399.
*5 Use the crimp terminal model No. 8-L6 manufactured by JST Mfg. Co., Ltd., or equivalent.
Terminals common to all inverters
Recommended wire size (mm2)
Remarks
Auxiliary control power input terminals R0 and T0
2.0
1.5 kW or above
Auxiliary fan power input terminals R1 and T1
2.0
200 V class series with 37 kW or above and
400 V class series with 75 kW or above
2-7
(2) Arrangement of control circuit terminals (common to all inverter types)
Chap. 2
* Using wires exceeding the recommended sizes may lift the front cover depending upon the
number of wires used, impeding keypad's normal operation.
2.3.3 Wiring precautions
Follow the rules below when performing wiring for the inverter.
(1) Make sure that the source voltage is within the rated voltage range specified on the nameplate.
(2) Be sure to connect the three-phase power wires to the main circuit power input terminals L1/R, L2/S and L3/T of the
inverter. If the power wires are connected to other terminals, the inverter will be damaged when the power is turned ON.
(3) Always connect the grounding terminal to prevent electric shock, fire or other disasters and to reduce electric noise.
(4) Use crimp terminals covered with insulated sleeves for the main circuit terminal wiring to ensure a reliable connection.
(5) Keep the power supply wiring (primary circuit) and motor wiring (secondary circuit) of the main circuit, and control
circuit wiring as far away as possible from each other.
(6) After removing a screw from the main circuit terminal block, be sure to restore the screw even if no wire is connected.
(7) Use the wiring guide to separate wiring. For inverters with a capacity of 3.7 kW or below, the wiring guide separates the
main circuit wires and the control circuit wires. For inverters with a capacity of 5.5 to 22 kW, it separates the upper and
lower main circuit wires, and control circuit wires. Be careful about the wiring order.
VXG9A-4E
VXG30A5-4E
„ Preparing for the wiring guide
Inverters with a capacity of 11 to 22 kW (three-phase 200 V class series) are sometimes lacking in wiring space for main
circuit wires depending upon the wire materials used. To assure a sufficient wiring space, remove the clip-off sections
(see below) as required with a nipper. Note that the enclosure rating of IP20 may not be ensured when the wiring guide
itself is removed to secure a space for thick main circuit wiring.
Before removal of clip-off sections
After removal of clip-off sections
Wiring Guide (VXG37AL-4E)
.
2-8
MOUNTING AND WIRING THE INVERTER
Recommended wire size: 0.65 to 0.82 mm2 (AWG 19 or 18)*
(8) In some types of inverters, the wires from the main circuit terminal block cannot be straight routed. Route such wires as
shown below so that the front cover is set into place.
(9) For inverters with a capacity of 500 kW or 630 kW, two L2/S input terminals are arranged vertically to the terminal
block. When connecting wires to these terminals, use the bolts, washers and nuts that come with the inverter, as shown
below.
• When wiring the inverter to the power source, insert a recommended molded case circuit breaker (MCCB) or
residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) (with overcurrent protection)
in the path of each pair of power lines to inverters. Use the recommended devices within the recommended current
capacity.
• Be sure to use wires in the specified size.
• Tighten terminals with specified torque.
Otherwise, a fire could occur.
• When there is more than one combination of an inverter and motor, do not use a multicore cable for the purpose of
handling their wirings together.
• Do not connect a surge killer to the inverter's output (secondary) circuit.
Doing so could cause a fire.
• Ground the inverter in compliance with the national or local electric code.
• Be sure to ground the inverter's grounding terminals G.
Otherwise, an electric shock or fire could occur.
• Qualified electricians should carry out wiring.
• Be sure to perform wiring after turning the power OFF.
Otherwise, electric shock could occur.
• Be sure to perform wiring after installing the inverter unit.
Otherwise, electric shock or injuries could occur.
• Ensure that the number of input phases and the rated voltage of the product match the number of phases and the
voltage of the AC power supply to which the product is to be connected.
Otherwise, a fire or an accident could occur.
• Do not connect the power source wires to inverter output terminals (U, V, and W).
Doing so could cause fire or an accident.
2-9
2.3.4 Wiring of main circuit terminals and grounding terminals
This section shows connection diagrams with the Enable input function used.
(1) VXGxxx-2 are set in SINK mode input by factory default.
Chap. 2
~CM
~THR
Power supply
200 V class series
200 to 240 V
50/60Hz
400 V class series
380 to 480 V
50/60Hz
MCCBor
RCD/ELCB• 1
·~~
Main circuit
I
Mc· 2
_---'--~OJo L 1/R
:_..----+---kS!Jo L2/S
- Power switching connector
(CN UX).10
Auxiliary control power input •3 [
- Fan power supply switching connector
(CN R)/(CN W)"10
, o
L
0
G
G
0
-------•-•---•-•-------------
Analog input
13
Potentiometer power supply
Voltage input for
frequency setting
0 to +10 VDC
(0 to ±10 VDC)
+10VDC
o , Grounding terminal·?
J
-,I •8
,----;oCc-o-no-tr-colc-c~ir-c-uocit
Contact outputs •g
Alarm output
(for any alarm)
OV
l
12
11
Voltage input for
frequency setting
Oto ±10VDC
l
AX terminal
funct1on
Transistor outputs •g
Current input for
frequency setting
4to20 mADC
Motor overload early warning
Frequency/speed detected
Frequency/speed arrival
Inverter running
Common terminal
0 to 10
VDC
4to 20
mADC
0 to 10
VDC
4to 20
mADC
Digital input •g
Run forward command
Run reverse command t---·/--++--+---:-~"=."C-'=
Digital input common terminal
2
6
iSIOr
OC Reacior
R~ldu!III-<.1UI'Nl'D1~,.,ecl
ptOtKIPo!ld~
ELCEl
MC
MCC9 :
Ea . .
LeaM~il Clirt:UIL S'I'B
~Con~<a~or
SW4.11
,,,---
J £
FM2
SW6•11
-------
meter
i',---
J £
11
~
Analog frequency
11
~
Analog frequency
meter
J Data transmission
X1
Select multi-frequency (0 to 1 step) ,----~-f"'=t-+7-<i~x;;:;--7~;;_----l
Select multi-frequency (0 to 3 step)
X
3
Select multi-frequency (0 to 7 step)
X
4
Select multi-frequency (0 to 15 step)
X
5
SelectACC/DEC time (2 steps)+--- /--++--;;-h-~x"'--~~--"
Select ACC/DEC time (4 steps) 1--- .---++----cHT-<r'x"'---'~~____.
7
Reset alarm +---· /--c+-+-tc-~"--_cr
Digital input common terminal c_---+-+---"'~.::.:..------_j
Dynamic 6r .l(lng F!
FM1
k'M
~Cue CltQill Brna~r
2-10
MOUNTING AND WIRING THE INVERTER
[)B
(2) VXGxxx-4E are set with SOURCE mode input by factory default
~CM
~THR
·~
[)B
MCCBor
RCD/ELCB" 1
Main circuit
I
Mc" 2
~--+-~(9)o L 1/R
Power supply
400 V class series
380 to 480 V
50/60Hz
~-+--f-{O)o L2/S
:..------+----c-\oo) L3/T
Auxiliary control power input *3
[
~----------~~oRO
Auxiliary fan power input "4 [
o TO
- Power switching connector
(CN UX)"10
- Fan power supply switching connector
(CN R)/(CN W)"10
-----~2)
, o
L
0
G
G
0
o , Grounding terminal"?
-----------------------------
J
~~C~o-n~tr~ol~c~ir_c_u~it~l" 8
Analog input
Contact outputs •g
Alarm output
(for any alarm)
Potentiometer power supply
Voltage input for
frequency setting
0 to +10 VDC
(0 to ±10 VDC)
l
Voltage input for
frequency setting
Oto ±10VDC
l
AX terminal
funct1on
Transistor outputs •g
Current input for
frequency setting
4to20 mADC
Motor overload early warning
Frequency/speed detected
Frequency/speed arrival
Inverter running
Common terminal
Oto 10
VDC
4 to20
mADC
Digital input •g
J
SW4*11
0 to 10
VDC
4 to20
mADC
,,,---
FM1
"
!!
J
SW6*11
SW2U
SD
1!
i
Oyt1amic 8«a~W~g Ra:;iSLor
00 Relilefor
f<esll:lual-wrrorrt-operal.td
prot~KWe
MC
MCCB
~
Analog frequency
meter
DX+
RS-485 COM port 2
*11
(TB)
ELCB
•..; ___
~
11
vo:--~-+--..-'D"'X"'-C¢-t---+----+"]
Run reverse command
OCR
ROD
Analog frequency
meter
FM2
Run forward command
DBR
~
11
de'lolle
l:alfi l8Bkil~e OirCIJII flreatier
Magl!le'llCI · COnt~K;tar
MQide.d CaM! Ctrwit llrealler
2-11
r
Data transmission
*1
Install a recommended molded case circuit breaker (MCCB) or residual-current-operated protective device (RCD)/earth leakage circuit
breaker (ELCB) (with overcurrent protection function) in the primary circuit of the inverter to protect wiring. Ensure that the circuit
breaker capacity is equivalent to or lower than the recommended capacity.
The R0 and T0 terminals are provided for inverters with a capacity of 1.5 kW or above.
To retain an alarm output signal ALM issued on inverter's programmable output terminals by the protective function or to keep the
keypad alive even if the main power has shut down, connect these terminals to the power supply lines. Without power supply to these
terminals, the inverter can run.
*4
Normally no need to be connected. Use these terminals when the inverter is equipped with a high power-factor, regenerative PWM
converter (RHC series).
*5
When connecting an optional DC reactor (DCR), remove the jumper bar from the terminals P1 and P(+).
Inverters with a capacity of 55 kW in LD mode and inverters with 75 kW or above require a DCR to be connected. Be sure to connect it
to those inverters.
Use a DCR when the capacity of the power supply transformer exceeds 500 kVA and is 10 times or more the inverter rated capacity, or
when there are thyristor-driven loads in the same power supply line.
*6
Inverters with a capacity of 7.5 kW or below have a built-in braking resistor (DBR) between the terminals P(+) and DB.
*7
A grounding terminal for a motor. Use this terminal if needed.
*8
For control signal wires, use twisted or shielded-twisted wires. When using shielded-twisted wires, connect the shield of them to the
common terminals of the control circuit. To prevent malfunction due to noise, keep the control circuit wiring away from the main circuit
wiring as far as possible (recommended: 10 cm or more). Never install them in the same wire duct. When crossing the control circuit
wiring with the main circuit wiring, set them at right angles.
*9
The connection diagram shows factory default functions assigned to digital input terminals [X1] to [X7], [FWD] and [REV], transistor
output terminals [Y1] to [Y4], and relay contact output terminals [Y5A/C] and [30A/B/C].
When connecting an external braking resistor (DBR), be sure to disconnect the built-in one.
*10 Switching connectors in the main circuits. For details, refer to "
Switching connectors" later in this section.
*11 Slide switches on the control printed circuit board (control PCB). Use these switches to customize the inverter operations. For details,
refer to Section 2.3.6 "Setting up the slide switches."
*12 When using the Enable input function, be sure to remove the jumper wire from terminals [EN] and [PLC]. For opening and closing the
hardware circuit between terminals [EN] and [PLC], use safety components such as safety relays and safety switches that comply with
EN954-1, Category 3 or higher. Be sure to use shielded wires exclusive to terminals [EN] and [PLC]. (Do not put them together with
any other control signal wire in the same shielded core.) Ground the shielding layer. For details, refer to Chapter 9, Section 9.6
"Compliance with EN954-1, Category 3."
When not using the Enable input function, keep the terminals between [EN] and [PLC] short-circuited with the jumper wire (factory
default).
2-12
MOUNTING AND WIRING THE INVERTER
*3
Chap. 2
*2 Install a magnetic contactor (MC) for each inverter to separate the inverter from the power supply, apart from the MCCB or RCD/ELCB,
when necessary.
Connect a surge absorber in parallel when installing a coil such as the MC or solenoid near the inverter.
Primary grounding terminal ( G) for inverter enclosure
Two grounding terminals ( G) are not exclusive to the power supply wiring (primary circuit) or motor wiring (secondary
circuit). Be sure to ground either of the two grounding terminals for safety and noise reduction. The inverter is designed for
use with safety grounding to avoid electric shock, fire and other disasters.
The grounding terminal for inverter enclosure should be grounded as follows:
1) Ground the inverter in compliance with the national or local electric code.
2) Use a thick grounding wire with a large surface area and keep the wiring length as short as possible.
An EMC filter built-in type of inverters with a capacity of 5.5 to 11 kW (both 200 V and 400 V class series) has
three grounding terminals. For effective noise suppression, connect grounding wires to the specified grounding
terminals. (Refer to Chapter 9, Section 9.3.2 "Recommended installation procedure.")
Inverter output terminals U, V, and W and secondary grounding terminals ( G) for motor
Inverter’s output terminals should be connected as follows:
1) Connect the three wires of the 3-phase motor to terminals U, V, and W, aligning the phases each other.
2) Connect the secondary grounding wire to the grounding terminal ( G).
When there is more than one combination of an inverter and motor, do not use a multicore cable for the purpose of
handling their wirings together.
DC reactor terminals P1 and P(+)
Connect a DC reactor (DCR) to these terminals for power factor correction.
1) Remove the jumper bar from terminals P1 and P(+).
2) Connect an optional DCR to those terminals.
• The wiring length should be 10 m or below.
• Do not remove the jumper bar when a DCR is not used.
• Inverters with a capacity of 55 kW in LD mode and inverters with 75 kW or above require a DCR to be
connected. Be sure to connect it to those inverters.
• If a PWM converter is connected to the inverter, no DCR is required.
Be sure to connect an optional DC reactor (DCR) when the capacity of the power supply transformer exceeds 500 kVA
and is 10 times or more the inverter rated capacity.
Otherwise, a fire could occur.
DC braking resistor terminals P(+) and DB (for inverters with a capacity of 22 kW or below)
Braking transistor
Built-in DC braking
resistor (DBR)
0.4 to 7.5
Built-in
Built-in
11 to 22
Built-in
None
Capacity (kW)
Optional devices
External DC braking resistor
(with a larger capacity)
External DC braking resistor
Option mounting
steps required
1), 2), 3)
2), 3)
In inverters with a capacity of 7.5 kW or below, if the capacity of the built-in DC braking resistor (DBR) is insufficient since
the inverter undergoes frequent start/stop or heavy inertial load, mount an optional external DC braking resistor (DBR) with a
larger capacity to increase the braking capability, using the following steps. Before mounting the external DBR, remove the
built-in DBR.
1) For inverters with a capacity of 0.4 to 3.7 kW, disconnect the wiring of the built-in DBR from terminals P(+) and DB; for
inverters with a capacity of 5.5 and 7.5 kW, disconnect the wiring from terminal DB and the internal relay terminal (see
the figure below).
Insulate the terminals of the disconnected wires with insulating tape or other materials.
2-13
2) Connect an optional DBR to terminals P(+) and DB.
The internal relay terminal on inverters with a capacity of 5.5 and 7.5 kW is left unused.
3) Arrange the DBR and inverter so that the wiring length comes to 5 m or less and twist the two DBR wires or route them
together in parallel.
Capacity
(kW)
Braking
transistor
Built-in DC braking
resistor (DBR)
Optional devices
Devices and terminals
30 to 630
None
None
Braking unit
DC braking resistor (DBR)
InverterBraking unit: P(+) and N(-)
Braking unitDBR:
P(+) and DB
1) Connecting an optional braking unit or DC braking resistor (DBR)
For inverters with a capacity of 30 kW or above, both a braking unit and DBR are necessary.
Connect the terminals P(+) and N(-) of a braking unit to those on the inverter. Arrange the inverter and the braking unit
so that the wiring length comes to 5 m or less and twist the two wires or route them together in parallel.
Next, connect the terminals P(+) and DB of a DBR to those on the braking unit. Arrange the braking unit and DBR so
that the wiring length comes to 10 m or less and twist the two wires or route them together in parallel.
For details about the wiring, refer to the Braking Unit Instruction Manual.
2) Connecting other external devices
A DC link bus of other inverter(s) or a PWM converter is connectable to these terminals.
When you need to use the DC link bus terminals P(+) and N(-), consult your Fuji Electric representative.
Switching connectors
„ Power switching connectors (CN UX) (for 400 V class series with 75 kW or above)
The 400 V class series with 75 kW or above is equipped with a set of switching connectors (male) which should be
configured according to the power source voltage and frequency. By factory default, a jumper (female connector) is set to U1.
If the power supply to the main power inputs (L1/R, L2/S, L3/T) or the auxiliary fan power input terminals (R1, T1) matches
the conditions listed below, change the jumper to U2.
For the switching instructions, see Figures 2.6 and 2.7.
(a) VXG176AL-4E to VXG253AL-4E
CN UX (red)
CN UX (red)
Connector configuration
Power source voltage
398 to 440 V/50 Hz, 430 to 480 V/60 Hz
(Factory default)
380 to 398 V/50 Hz
380 to 430 V/60 Hz
(b) VXG304AL-4E to VXG1370AL-4E
CN UX (red)
CN UX (red)
Connector configuration
Power source voltage
398 to 440 V/50 Hz, 430 to 480 V/60 Hz
(Factory default)
380 to 398 V/50 Hz,
380 to 430 V/60 Hz
The allowable power input voltage fluctuation is within -15% to +10% of the power source voltage.
2-14
MOUNTING AND WIRING THE INVERTER
DC link bus terminals P(+) and N(-)
Chap. 2
When connecting a DC braking resistor (DBR), never connect it to terminals other than terminals P(+) and DB.
Otherwise, a fire could occur.
„ Fan power supply switching connectors (CN R and CN W) (for 200 V class series with 37 kW or above and
400 V class series with 75 kW or above)
The standard JAGUAR VXG series accepts DC-linked power input in combination with a PWM converter. The 200 V class
series with 37 kW or above and 400 V class series with 75 kW or above, however, contain AC-driven components such as AC
fans. To supply AC power to those components, exchange the CN R and CN W connectors as shown below and connect the
AC power line to the auxiliary fan power input terminals (R1, T1).
For the switching instructions, see Figures 2.6 and 2.7.
(a) VXG180AL-2 to VXG350AL-2, VXG176AL-4E to VXG253AL-4E
CN R (red)
CN W (white)
CN W (white)
CN R (red)
Connector configuration
When using terminals R1 and T1
• Feeding the DC-linked power
• Combined with a PWM converter
When not using terminal R1 or T1
(Factory default)
Use conditions
b) VXG400AL-2E, VXG304AL-4E to VXG1370AL-4E
Connector configuration
CN R
(red)
CN W
(white)
When not using terminal R1 or T1
(Factory default)
Use conditions
CN W
(white)
CN R
(red)
When using terminals R1 and T1
• Feeding the DC-linked power
• Combined with a PWM converter
.
By factory default, the fan power supply switching connectors CN R and CN W are set on
the FAN and NC positions, respectively. Do not exchange them unless you drive the inverter with a DC-linked
power supply.
Wrong configuration of these switching connectors cannot drive the cooling fans, causing a heat sink overheat alarm
Kor a charger circuit alarm SEI.
„ Location of the switching connectors
The switching connectors are located on the power printed circuit board (power PCB) as shown below.
Keypad enclosure
Power switching
connectors (CN UX)
Fan power
supply switching
connectors
(CN R and
CN W)
Auxiliary fan
power input
terminals
Auxiliary
power input
terminals
Power PCB
Auxiliary fan power input
terminals
Power switching
connectors (CN UX)
Auxiliary power input
terminals
(a) VXG180AL-2 to VXG350AL-2,
VXG176AL-4E to VXG253AL-4E
Figure 2.6
(b) VXG400AL-2,
VXG304AL-4E to VXG1370AL-4E
Location of Switching Connectors and Auxiliary Power Input Terminals
2-15
Fan power
supply
switching
connectors
(CN R and
CN W)
Inserting/Removing the Jumpers
Main circuit power input terminals L1/R, L2/S, and L3/T (three-phase input)
The three-phase input power lines are connected to these terminals.
1) For safety, make sure that the molded case circuit breaker (MCCB) or magnetic contactor (MC) is turned OFF before
wiring the main circuit power input terminals.
2) Connect the main circuit power supply wires (L1/R, L2/S and L3/T) to the input terminals of the inverter via an MCCB
or residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB)*, and an MC if necessary.
It is not necessary to align phases of the power supply wires and the input terminals of the inverter with each other.
* With overcurrent protection
It is recommended to insert a manually operable magnetic contactor (MC) that allows you to disconnect the inverter
from the power supply in an emergency (e.g., when the protective function is activated), preventing a failure or
accident from causing secondary disasters.
To drive the inverter with single-phase input power, consult your IMO representative.
Auxiliary control power input terminals R0 and T0 (for inverters with a capacity of 1.5 kW or above)
In general, the inverter runs normally without power supplied to the auxiliary control power input terminals R0 and T0. If the
inverter main power is shut down, however, no power is supplied to the control circuit so that the inverter cannot issue a
variety of output signals or display on the keypad.
To retain an alarm output signal ALM issued on inverter's programmable output terminals by the protective function or to
keep the keypad alive even if the main power has shut down, connect the auxiliary control power input terminals R0 and T0
to the power supply lines. If a magnetic contactor (MC) is installed in the inverter's primary circuit, connect the primary
circuit of the MC to these terminals R0 and T0.
Terminal rating:
200 to 240 VAC, 50/60 Hz, Maximum current 1.0 A (200 V class series with 22 kW or below)
200 to 230 VAC, 50/60 Hz, Maximum current 1.0 A (200 V class series with 30 kW or above)
380 to 480 VAC, 50/60 Hz, Maximum current 0.5 A (400 V class series)
When introducing a residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB),
connect its output (secondary) side to terminals R0 and T0. Connecting its input (primary) side to those terminals
causes the RCD/ELCB to malfunction since the input power voltage to the inverter is three-phase but the one to
terminals R0 and T0 is single-phase. To avoid such problems, be sure to insert an insulation transformer or auxiliary
B contacts of a magnetic contactor in the location shown in Figure 2.8.
Figure 2.8 Connection Example of Residual-current-operated Protective Device (RCD)/
Earth Leakage Circuit Breaker (ELCB)
2-16
MOUNTING AND WIRING THE INVERTER
Figure 2.7
Chap. 2
To remove each of the jumpers, pinch its upper side between
your fingers, unlock its fastener, and pull it up.
When mounting it, fit the jumper over the connector until it
snaps into place.
When connecting a PWM converter with an inverter, do not connect the power supply line directly to terminals R0
and T0. If a PWM is to be connected, insert an insulation transformer or auxiliary B contacts of a magnetic contactor
at the power supply side.
For connection examples at the PWM converter side, refer to the PWM Converter Instruction Manual.
Figure 2.9
Connection Example of PWM Converter
Auxiliary fan power input terminals R1 and T1
The 200 V class series with 37 kW or above and 400 V class series with 75 kW or above are equipped with terminals R1 and
T1. Only if the inverter works with the DC-linked power input whose source is a PWM converter, these terminals are used to
feed AC power to the fans, while they are not used in any power system of ordinary configuration.
In this case, set up the fan power supply switching connectors (CN R and CN W).
Terminal rating:
200 to 220 VAC/50 Hz, 200 to 230 VAC/60 Hz, Maximum current 1.0 A (200 V class series with 37 kW or above)
380 to 440 VAC/50 Hz, 380 to 480 VAC/60 Hz, Maximum current 1.0 A (400 V class series with 75 kW to 400 kW)
380 to 440 VAC/50 Hz, 380 to 480 VAC/60 Hz, Maximum current 2.0 A (400 V class series with 500 kW and 630 kW)
2.3.5 Wiring for control circuit terminals
In general, the covers of the control signal wires are not specifically designed to withstand a high voltage (i.e., reinforced
insulation is not applied). Therefore, if a control signal wire comes into direct contact with a live conductor of the main
circuit, the insulation of the cover might break down, which would expose the signal wire to a high voltage of the main
circuit. Make sure that the control signal wires will not come into contact with live conductors of the main circuit.
Failure to observe these precautions could cause electric shock or an accident.
Noise may be emitted from the inverter, motor and wires.
Take appropriate measures to prevent the nearby sensors and devices from malfunctioning due to such noise.
An accident could occur.
„ Connecting/disconnecting wires to/from a control circuit terminal
Strip the wire end by 8 to 10 mm as shown below.
Strip length of wire end
8 to 10 mm
Type of screwdriver (tip shape)
Flat (0.6 u 3.5 mm)
For strand wires, the strip length specified above should apply after twisting of them.
If the strip length is out of the specified range, the wire may not be firmly clamped or may be short-circuited with
other wires.
Twist the end of the stripped wires for easy insertion and insert it firmly into the wire inlet on the control circuit terminal.
If the insertion is difficult, hold down the clamp release button on the terminal with a flat screwdriver.
When disconnecting the wires from the terminal, hold down the clamp release button on the terminal with a flat
screwdriver and pull out the wires.
Connecting wire to terminal
Disconnecting wire from terminal
Flat screwdriver
Wires
Wires
Wire inlet
Clamp release button
2-17
Table 2.7 lists the symbols, names and functions of the control circuit terminals. The wiring to the control circuit terminals
differs depending upon the setting of the function codes, which reflects the use of the inverter. Route wires properly to reduce
the influence of noise.
Symbol
Symbols, Names and Functions of the Control Circuit Terminals
Name
Chap. 2
Functions
Power supply
for the
potentiometer
Power supply (+10 VDC) for an external frequency command potentiometer
(Variable resistor: 1 to 5k:)
The potentiometer of 1/2 W rating or more should be connected.
[12]
Analog setting
voltage input
(1) The frequency is commanded according to the external voltage input.
• 0 to r10 VDC/0 to r100% (Normal operation)
• +10 to 0 VDC/0 to 100% (Inverse operation)
(2) In addition to frequency setting, PID command, PID feedback signal, auxiliary
frequency command setting, ratio setting, torque limiter level setting, or analog input
monitor can be assigned to this terminal.
(3) Hardware specifications
• Input impedance: 22k:
• The maximum input is r15 VDC, however, the voltage higher than r10 VDC is
handled as r10 VDC.
• Inputting a bipolar analog voltage (0 to r10 VDC) to terminal [12] requires setting
function code C35 to "0."
[C1]
Analog setting
current input
(1) The frequency is commanded according to the external current input.
• 4 to 20 mA DC/0 to 100% (Normal operation)
• 20 to 4 mA DC/0 to 100 % (Inverse operation)
(2) In addition to frequency setting, PID command, PID feedback signal, auxiliary
frequency command setting, ratio setting, torque limiter level setting, or analog input
monitor can be assigned to this terminal.
(3) Hardware specifications
• Input impedance: 250:
• The maximum input is +30 mA DC, however, the current larger than +20 mA DC
is handled as +20 mA DC.
PTC/NTC
thermistor
input
(1) Connects PTC (Positive Temperature
Coefficient)/NTC (Negative Temperature
Coefficient) thermistor for motor
protection. Ensure that the slide switch
SW5 on the control PCB is turned to the
PTC/NTC position (see Section 2.3.6
"Setting up the slide switches").
The figure shown at the right illustrates
the internal circuit diagram where SW5
(switching the input of terminal [C1]
between C1 and PTC/NTC) is turned to
the PTC/NTC position. For details on
SW5, refer to Section 2.3.6 "Setting up
the slide switches." In this case, you must
change data of the function code H26.
[V2]
[11]
Figure 2.10
Internal Circuit Diagram
(SW5 Selecting PTC/NTC)
Analog setting
voltage input
(1) The frequency is commanded according to the external voltage input.
• 0 to r10 VDC/0 to r100 % (Normal operation)
• +10 to 0 VDC/0 to 100% (Inverse operation)
(2) In addition to frequency setting, PID command, PID feedback signal, auxiliary
frequency command setting, ratio setting, torque limiter level setting, or analog input
monitor can be assigned to this terminal.
(3) Hardware specifications
• Input impedance: 22k:
• The maximum input is r15 VDC, however, the voltage higher than r10 VDC is
handled as r10 VDC.
• Inputting a bipolar analog voltage (0 to r10 VDC) to terminal [V2] requires setting
function code C45 to "0."
Analog
common
Common for analog input/output signals ([13], [12], [C1], [V2], [FM1] and [FM2]).
Isolated from terminals [CM] and [CMY].
2-18
MOUNTING AND WIRING THE INVERTER
[13]
Analog input
Classification
Table 2.7
Classification
Table 2.7
Symbol
Symbols, Names and Functions of the Control Circuit Terminals (Continued)
Name
Functions
- Since low level analog signals are handled, these signals are especially susceptible to the external noise
effects. Route the wiring as short as possible (within 20 m) and use shielded wires. In principle, ground
the shielded sheath of wires; if effects of external inductive noises are considerable, connection to
terminal [11] may be effective. As shown in Figure 2.11, be sure to ground the single end of the shield
to enhance the shield effect.
- Use a twin-contact relay for low level signals if the relay is used in the control circuit. Do not connect
the relay's contact to terminal [11].
- When the inverter is connected to an external device outputting the analog signal, the external device
may malfunction due to electric noise generated by the inverter. If this happens, according to the
circumstances, connect a ferrite core (a toroidal core or equivalent) to the device outputting the analog
signal or connect a capacitor having the good cut-off characteristics for high frequency between control
signal wires as shown in Figure 2.12.
- Do not apply a voltage of +7.5 VDC or higher to terminal [C1]. Doing so could damage the internal
control circuit.
Digital input
Figure 2.11
Connection of Shielded Wire
[X1]
Digital input 1
[X2]
Digital input 2
[X3]
Digital input 3
[X4]
Digital input 4
[X5]
Digital input 5
[X6]
Digital input 6
[X7]
Digital input 7
[FWD]
Run forward
command
[REV]
Run reverse
command
Figure 2.12
Example of Electric Noise Reduction
(1) Various signals such as "Coast to a stop," "Enable external alarm trip," and "Select
multi-frequency" can be assigned to terminals [X1] to [X7], [FWD] and [REV] by
setting function codes E01 to E07, E98, and E99. For details, refer to Chapter 5,
Section 5.2 "Details of Function Codes."
(2) Input mode, i.e. SINK/SOURCE, is changeable by using the slide switch SW1.
(Refer to Section 2.3.6, "Setting up the slide switches.") The factory default for
VXGxxx-2E is SINK, and for VXGxxx-4E, SOURCE.
(3) Switches the logic value (1/0) for ON/OFF of the terminals [X1] to [X7], [FWD], or
[REV]. If the logic value for ON of the terminal [X1] is 1 in the normal logic system,
for example, OFF is 1 in the negative logic system and vice versa.
(4) Digital input terminal [X7] can be defined as a pulse train input terminal with the
function codes.
Maximum wiring length 20 m
Maximum input pulse 30 kHz: When connected to a pulse generator with open
collector transistor output
(Needs a pull-up or pull-down resistor. See notes on
page 2-20.)
100 kHz: When connected to a pulse generator with
complementary transistor output
For the settings of the function codes, refer to JAGUAR VXG User's Manual,
Chapter 5 "FUNCTION CODES."
(Digital input circuit specifications)
Item
Min.
ON level
0V
2V
OFF level
22 V
27 V
Operating voltage
(SOURCE)
ON level
22 V
27 V
OFF level
0V
2V
2.5 mA
5 mA
Operating current at ON
(Input voltage is at 0 V)
(For [X7])
Allowable leakage current at
OFF
Figure 2.13
Digital Input Circuit
2-19
Max.
Operating voltage
(SINK)
(9.7 mA) (16 mA)
0.5 mA
Classification
Table 2.7
Symbol
Name
Functions
Enable input
For details of connection to this terminal and precautions, refer to Chapter 9, Section 9.6
"Compliance with EN954-1, Category 3."
<Terminal [EN] circuit specification>
<Control circuit>
+24 VDC
[PLC]
Item
Photocoupler
[EN]
Operating voltage
(SOURCE)
5.4k:
Min.
Max.
ON level
22 V
27 V
OFF level
0V
2V
5 mA
10 mA
0.5 mA
Operating current at ON
(Input voltage is at 24 V)
Allowable leakage current at OFF
5.4k:
[PLC]
PLC signal
power
(1) Connects to PLC output signal power supply.
Rated voltage: +24 VDC (Allowable range: +22 to +27 VDC), Maximum 100 mA DC
(2) This terminal also supplies a power to the load connected to the transistor output
terminals. Refer to "Transistor output" described later in this table for more.
[CM]
Digital input
common
Two common terminals for digital input signals
These terminals are electrically isolated from the terminals [11]s and [CMY].
„ Using a relay contact to turn [X1] to [X7], [FWD], or [REV] ON or OFF
Figure 2.14 shows two examples of a circuit that uses a relay contact to turn control signal input [X1] to
[X7], [FWD], or [REV] ON or OFF. In circuit (a), the slide switch SW1 has been turned to SINK, whereas
in circuit (b) it has been turned to SOURCE.
Note: To configure this kind of circuit, use a high quality relay.
<Control circuit>
<Control circuit>
[PLC]
SINK
[PLC]
SINK
+24 VDC
+24 VDC
Digital input
[CM]
SOURCE
SOURCE
[X1]㻌 㼠 㼛㻌 [X7],
[FWD], [REV]
[X1] to [X7],
[FWD], [REV]
Photocoupler
[CM]
Photocoupler
[CM]
(a) With the switch turned to SINK
Figure 2.14
(b) With the switch turned to SOURCE
Circuit Configuration Using a Relay Contact
„ Using a programmable logic controller (PLC) to turn [X1] to [X7], [FWD], or [REV] ON or OFF
Figure 2.15 shows two examples of a circuit that uses a programmable logic controller (PLC) to turn
control signal input [X1] to [X7], [FWD], or [REV] ON or OFF. In circuit (a), the slide switch SW1 has
been turned to SINK, whereas in circuit (b) it has been turned to SOURCE.
In circuit (a) below, short-circuiting or opening the transistor's open collector circuit in the PLC using an
external power supply turns ON or OFF control signal [X1] to [X7], [FWD], or [REV]. When using this
type of circuit, observe the following:
- Connect the + node of the external power supply (which should be isolated from the PLC's power) to
terminal [PLC] of the inverter.
- Do not connect terminal [CM] of the inverter to the common terminal of the PLC.
2-20
MOUNTING AND WIRING THE INVERTER
(1) Safety stop function that is compliant with EN954-1, Category 3. This terminal
allows the hardware circuit to stop the inserter's output transistor and coast the motor
to a stop.
(2) This terminal is exclusively used for the source mode input. When it is
short-circuited with terminal [PLC], the Enable input is ON (ready for inverter run);
when it is opened, the inverter coasts the motor to a stop. (This terminal is not
interlocked with the slide switch SW1.)
(3) By factory default, terminals [EN] and [PLC] are short-circuited with each other
using a jumper wire, disabling this function. To enable it, be sure to remove the
jumper wire.
Chap. 2
[EN]
Symbols, Names and Functions of the Control Circuit Terminals (Continued)
Symbol
Symbols, Names and Functions of the Control Circuit Terminals (Continued)
Name
Programmable
logic controller
Functions
Programmable
logic controller
<Control circuit>
SINK
<Control circuit>
[PLC]
SINK
+24 VDC
[PLC]
+24 VDC
Classification
Table 2.7
SOURCE
Digital input
[X1] 㼠 㼛㻌 㼇 X7],
[FWD], [REV]
SOURCE
[X1] to [X7],
[FWD], [REV]
Photocoupler
Photocoupler
[CM]
[CM]
(a) With the switch turned to SINK
Figure 2.15
(b) With the switch turned to SOURCE
Circuit Configuration Using a PLC
For details about the slide switch setting, refer to Section 2.3.6 "Setting up the slide switches."
„ For inputting a pulse train through the digital input terminal [X7]
• Inputting from a pulse generator with an open collector transistor output
Stray capacity on the wiring between the pulse generator and the inverter may disable transmission of the
pulse train. As a countermeasure against this problem, insert a pull-up resistor between the open collector
output signal (terminal [X7]) and the power source terminal (terminal [PLC]) if the switch selects the
SINK mode input; insert a pull-down resistor between the output signal and the digital common terminal
(terminal [CM]) if the switch selects the SOURCE mode input.
A recommended pull-up/down resistor is 1k: 2 W. Check if the pulse train is correctly transmitted
because stray capacity is significantly affected by the wire types and wiring conditions.
[FM1]
[FM2]
Analog
monitor
Both terminals output monitor signals for analog DC voltage (0 to +10 V) or analog DC
current (+4 to +20 mA). The output form (VO/IO) for each of [FM1] and [FM2] can be
switched with the slide switches on the control PCB and the function codes, as listed
below.
Terminal
[FM1]
Analog output
[FM2]
Output form
Terminal function is
Content is
specified by:
Analog DC voltage Analog DC current specified by:
Slide switch SW4
VO1
IO1
Function code
F31
Function code F29
0
1
Slide switch SW6
VO2
IO2
Function code
F35
Function code F32
0
1
The signal content can be selected from the following with function codes F31 and F35.
• Output frequency
• Output current
• Output voltage
• Output torque
• Load factor
• Input power
• PID feedback amount
• Speed (PG feedback value) • DC link bus voltage
• Universal AO
• Motor output
• Calibration
• PID command
• PID output
* Input impedance of the external device: Min. 5k: (at 0 to 10 VDC output)
(While the terminal is outputting 0 to 10 VDC, it is capable of driving up to two analog
voltmeters with 10 k: impedance.)
* Input impedance of the external device: Max. 500: (at 4 to 20 mA DC output)
* Adjustable range of the gain: 0 to 300%
[11]
Analog
common
Two common terminals for analog input and output signals.
These terminals are electrically isolated from terminals [CM] and [CMY].
2-21
Symbol
Symbols, Names and Functions of the Control Circuit Terminals (Continued)
Name
[Y2]
Transistor
output 2
[Y3]
Transistor
output 3
(1) Various signals such as inverter running, speed/freq. arrival and overload early
warning can be assigned to any terminals, [Y1] to [Y4] by setting function code E20
to E24. Refer to Chapter 5, Section 5.2 "Details of Function Codes" for details.
(2) Switches the logic value (1/0) for ON/OFF of the terminals between [Y1] to [Y4],
and [CMY]. If the logic value for ON between [Y1] to [Y4] and [CMY] is 1 in the
normal logic system, for example, OFF is 1 in the negative logic system and vice
versa.
(Transistor output circuit specification)
<Control circuit>
Photocoupler
Operation
voltage
[Y1]
to
[Y4]
31 to 35 V
[CMY]
Transistor output
Figure 2.16
[Y4]
Transistor
output 4
[CMY]
Transistor
output
common
Item
Current
Max.
ON level
2V
OFF level
27 V
Maximum current at ON
50 mA
Leakage current at OFF
0.1 mA
Transistor Output Circuit
Figure 2.17 shows examples of connection between the control circuit and a PLC.
- When a transistor output drives a control relay, connect a surge-absorbing diode
across relay’s coil terminals.
- When any equipment or device connected to the transistor output needs to be
supplied with DC power, feed the power (+24 VDC: allowable range: +22 to
+27 VDC, 100 mA max.) through the [PLC] terminal. Short-circuit between the
terminals [CMY] and [CM] in this case.
Common terminal for transistor output signals
This terminal is electrically isolated from terminals [CM] and [11]s.
„ Connecting programmable logic controller (PLC) to terminal [Y1], [Y2], [Y3] or [Y4]
Figure 2.17 shows two examples of circuit connection between the transistor output of the inverter’s
control circuit and a PLC. In example (a), the input circuit of the PLC serves as a SINK for the control
circuit output, whereas in example (b), it serves as a SOURCE for the output.
<Control circuit>
Programmable
logic controller
C0
Current
Photocoupler
[Y1]
to
[Y4]
[CMY]
SINK input
[Y1]
to
[Y4]
31 to
35 V
+24 VDC
31 to
35 V
Current
+24 VDC
Photocoupler
<Control circuit>
Programmable
logic controller
[CMY]
SOURCE input
C0
(a)
PLC serving as SINK
Figure 2.17
Relay output
[Y5A/C]
General
purpose relay
output
[30A/B/C] Alarm relay
output
(for any
error)
(b)
PLC serving as SOURCE
Connecting PLC to Control Circuit
(1) A general-purpose relay contact output usable as well as the function of the transistor
output terminal [Y1], [Y2], [Y3] or [Y4].
Contact rating: 250 VAC 0.3 A, cos I = 0.3, 48 VDC, 0.5 A
(2) Switching of the normal/negative logic output is applicable to the following two
contact output modes: "Active ON" (Terminals [Y5A] and [Y5C] are closed
(excited) if the signal is active.) and "Active OFF" (Terminals [Y5A] and [Y5C] are
opened (non-excited) if the signal is active while they are normally closed.).
(1) Outputs a contact signal (SPDT) when a protective function has been activated to
stop the motor.
Contact rating: 250 VAC, 0.3A, cos I = 0.3, 48 VDC, 0.5A
(2) Any one of output signals assigned to terminals [Y1] to [Y4] can also be assigned to
this relay contact to use it for signal output.
(3) Switching of the normal/negative logic output is applicable to the following two
contact output modes: "Active ON" (Terminals [30A] and [30C] are closed (excited)
if the signal is active.) and "Active OFF" (Terminals [30A] and [30C] are opened
(non-excited) if the signal is active while they are normally closed.).
2-22
MOUNTING AND WIRING THE INVERTER
Transistor
output 1
Chap. 2
[Y1]
Functions
Voltage
Classification
Table 2.7
Symbol
Symbols, Names and Functions of the Control Circuit Terminals (Continued)
Name
Functions
[DX+]/
[DX-]/
[SD]
RS-485
communications
port 2
(Terminals on
control PCB)
A communications port transmits data through the RS-485 multipoint protocol
between the inverter and a personal computer or other equipment such as a PLC.
(For setting of the terminating resistor, refer to Section 2.3.6 "Setting up the slide
switches.")
RJ-45
connector
for the
keypad
RS-485
communications
port 1
(Standard RJ-45
connector)
(1) Used to connect the inverter with the keypad. The inverter supplies the power to
the keypad through the pins specified below. The extension cable for remote
operation also uses wires connected to these pins for supplying the keypad power.
(2) Remove the keypad from the standard RJ-45 connector and connect the RS-485
communications cable to control the inverter through the PC or PLC
(Programmable Logic Controller). For setting of the terminating resistor, refer to
Section 2.3.6 "Setting up the slide switches."
Communication
Classification
Table 2.7
Figure 2.18
RJ-45 Connector and its Pin Assignment*
* Pins 1, 2, 7, and 8 are exclusively assigned to power lines for the remote
keypad and multi-function keypad, so do not use those pins for any other
equipment.
USB
connector
USB port
(On the keypad)
A USB port connector (mini B) that connects an inverter to a personal computer.
JAGUAR Loader software running on the computer supports editing the function
codes, transferring them to the inverter, verifying them, test-running an inverter and
monitoring the inverter running status.
2-23
Wiring for control circuit terminals
For VXG350AL-2, VXG400AL-2 and VXG304AL-4E to VXG1370AL-4E
Control circuit terminal block
Wiring support
Wiring for control
circuit terminals
Section A
Details of Section A
Left side panel
Wiring for control
circuit terminals
Figure 2.19
Wiring Route and Fixing Position for the Control Circuit Wires
- Route the wiring of the control circuit terminals as far from the wiring of the main circuit as possible.
Otherwise electric noise may cause malfunctions.
- Fix the control circuit wires with a cable tie inside the inverter to keep them away from the live parts of the
main circuit (such as the terminal block of the main circuit).
2.3.6 Setting up the slide switches
Before changing the switches or touching the control circuit terminal symbol plate, turn OFF the power and wait at
least five minutes for inverters with a capacity of 22 kW or below, or at least ten minutes for inverters with a
capacity of 30 kW or above. Make sure that the LED monitor and charging lamp are turned OFF. Further, make sure,
using a multimeter or a similar instrument, that the DC link bus voltage between the terminals P(+) and N(-) has dropped
to the safe level (+25 VDC or below).
An electric shock may result if this warning is not heeded as there may be some residual electric charge in the DC
bus capacitor even after the power has been turned OFF.
Switching the slide switches located on the control PCB allows you to customize the operation mode of the analog output
terminals, digital I/O terminals, and communications ports. The locations of those switches are shown in Figure 2.20.
To access the slide switches, remove the front cover so that you can see the control PCB. For inverters with a capacity of 30
kW or above, open also the keypad enclosure.
For details on how to remove the front cover and how to open and close the keypad enclosure, refer to Section 2.3.1
"Removing and mounting the front cover and the wiring guide."
2-24
MOUNTING AND WIRING THE INVERTER
Cable tie
Chap. 2
(1) As shown in Figure 2.19, route the control circuit wires along the left side panel to the outside of the inverter.
(2) Secure those wires to the wiring support, using a cable tie (e.g., Insulok) with 3.8 mm or less in width and 1.5 mm or less
in thickness.
Table 2.8 lists function of each slide switch.
Table 2.8
Function of Each Slide Switch
Switch
Function
SW1
Switches the service mode of the digital input terminals between SINK and SOURCE.
This switches the input mode of digital input terminals [X1] to [X7], [FWD] and [REV] to be used as
the SINK or SOURCE mode.
The factory default for VXGxxx-2 is SINK, for VXGxxx-4E, SOURCE.
SW2
Switches the terminating resistor of RS-485 communications port on the inverter ON and OFF.
(RS-485 communications port 2, on the control PCB)
If the inverter is connected to the RS-485 communications network as a terminating device, turn SW2
to ON.
SW3
Switches the terminating resistor of RS-485 communications port on the inverter ON and OFF.
(RS-485 communications port 1, for connecting the keypad)
To connect a keypad to the inverter, turn SW3 to OFF. (Factory default)
If the inverter is connected to the RS-485 communications network as a terminating device, turn SW3
to ON.
Switches the output form of analog output terminals [FM1] and [FM2] between voltage and current.
When changing the setting of SW4 and SW6, also change the data of function codes F29 and F32,
respectively.
[FM1]
SW4/SW6
Output form
[FM2]
SW4
F29 data
SW6
F32 data
Voltage output (Factory default)
VO1
0
VO2
0
Current output
IO1
1
IO2
1
Switches the property of the analog input terminal [C1] between analog setting current input, PTC
thermistor input, and NTC thermistor input.
When changing this switch setting, also change the data of function code H26.
SW5
SW5
H26 data
C1
0
PTC thermistor input
PTC/NTC
1 (alarm) or 2 (warning)
NTC thermistor input
PTC/NTC
3
Function
Analog setting current input (Factory default)
Figure 2.20 shows the location of slide switches on the control PCB for the input/output terminal configuration.
Switch Configuration and Factory Defaults
SW1*
SW2
OFF
SW3
SW4/SW6
OFF
VO1/VO2
SW5
C1
Factory
default
SOURCE
SINK
ON
--ON
IO1/IO2
PTC/NTC
* The factory default for VXGxxx-2E is SINK, for VXGxxx-4E, SOURCE.
Figure 2.20 Location of the Slide Switches
on the Control PCB
To move a switch slider, use a tool with a narrow tip (e.g., a tip of tweezers). Be careful not to touch other electronic
parts, etc. If the slider is in an ambiguous position, the circuit is unclear whether it is turned ON or OFF and the
digital input remains in an undefined state. Be sure to place the slider so that it contacts either side of the switch.
2-25
2.4 Mounting and Connecting a Keypad
You can mount a keypad on the panel wall or install one at a remote site (e.g. for operation on hand).
Chap. 2
Mounting a Keypad on the Panel Wall
To mount/install a keypad on a place other than in an inverter, the parts listed below are needed.
Parts name
Model
Remarks
Extension cable (Note 1)
JAGLEAD1M / 2M / 3M
3 types available in length of 1 m, 2 m, and 3 m.
Fixing screw
M3 u † (Note 2)
Two screws needed. Purchase off-the-shelf ones separately.
(Note 1) When using an off-the-shelf LAN cable, use a 10BASE-T/100BASE-TX straight type cable compliant with US
ANSI/TIA/EIA-568A Category 5. (Less than 20m)
Recommended LAN cable
Manufacturer: Sanwa Supply Inc.
Model:
KB-10T5-01K (1 m)
KB-STP-01K: (1 m) (Shielded LAN cable)
(Note 2) When mounting on a panel wall, use the screws with a length suitable for the wall thickness.
(Depth of the screw holes on the keypad is 11 mm.)
„ Removing and mounting a keypad
To remove the keypad, pull it toward you while holding down the hook (pointed by the arrow in Figure 2.22). When
mounting it, put the keypad back into place in the reverse order of removal.
Figure 2.22
Removing a Keypad
2-26
MOUNTING AND WIRING THE INVERTER
Figure 2.21
Chapter 3 OPERATION USING THE KEYPAD (in the case of remote keypad)
3.1 LED Monitor, Keys and LED Indicators on the Keypad
7-segment
LED monitor
LED indicators
UP key
RUN LED
RUN key
Function/
Data key
STOP key
DOWN key
USB port
When using a multi-function keypad instead of a remote keypad, read the Multi-function Keypad Instruction Manual.
Table 3.1 Overview of Keypad Functions
Item
LED Monitor, Keys,
and LED Indicators
Functions
Four-digit, 7-segment LED monitor which displays the followings according to the
operation modes.
„ In Running mode:
Running status information (e.g., output frequency, current,
and voltage)
When a light alarm occurs, ODOis displayed.
„ In Programming mode: Menus, function codes and their data
„ In Alarm mode:
Alarm code, which identifies the alarm factor when the
protective function is activated.
LED
Monitor
Program/Reset key which switches the operation modes of the inverter.
„ In Running mode:
Pressing this key switches the inverter to Programming
mode.
„ In Programming mode: Pressing this key switches the inverter to Running mode.
„ In Alarm mode:
Pressing this key after removing the alarm factor will switch
the inverter to Running mode.
Function/Data key which switches the operations you want to do in each mode as
follows:
„ In Running mode:
Pressing this key switches the information to be displayed
concerning the status of the inverter (output frequency (Hz),
output current (A), output voltage (V), etc.).
When a light alarm is displayed, holding down this key resets
the light alarm and switches back to Running mode.
„ In Programming mode: Pressing this key displays the function code or establishes
and
keys.
the data entered with
„ In Alarm mode:
Pressing this key displays the details of the problem
indicated by the alarm code that has come up on the LED
monitor.
Operation
Keys
RUN key. Press this key to run the motor.
STOP key. Press this key to stop the motor.
㸭
RUN LED
KEYPAD
CONTROL LED
LED
Indicators
Unit LEDs
(3 LEDs)
x10 LED
UP and DOWN keys. Press these keys to select the setting items and change the function
code data displayed on the LED monitor.
Lights when running with a run command entered by the
key, by terminal command
FWD or REV, or through the communications link.
key (F02
Lights when the inverter is ready to run with a run command entered by the
key cannot
= 0, 2, or 3). In Programming and Alarm modes, however, pressing the
run the inverter even if this indicator lights.
These three LED indicators identify the unit of numeral displayed on the LED monitor in
Running mode by combination of lit and unlit states of them.
Unit: Hz, A, kW, r/min and m/min
Refer to Chapter 3, Section 3.3.1 "Monitoring the running status" for details.
While the inverter is in Programming mode, the LEDs of Hz and kW light.
„ Hz † A „ kW
Lights when the data to display exceeds 9999. When this LED lights, the "displayed
value x 10" is the actual value.
Example:
If the LED monitor displays and the x10 LED lights, it means that the actual value
is "1,234 u 10 = 12,340."
3-1
OPERATION USING THE KEYPAD
Program/
Reset key
Chap. 3
As shown at the right, the keypad consists of a four-digit
LED monitor, six keys, and five LED indicators.
The keypad allows you to run and stop the motor,
monitor the running status, specify the function code
data, and monitor I/O signal states, maintenance
information, and alarm information.
Table 3.1 Overview of Keypad Functions (Continued)
LED Monitor, Keys,
and LED Indicators
Item
Functions
The USB port with a mini B connector enables the inverter to connect with a PC with a
USB cable.
USB port
3.2 Overview of Operation Modes
JAGUAR VXG features the following three operation modes.
Table 3.2 Operation Modes
Operation mode
Description
Running mode
After powered ON, the inverter automatically enters this mode.
This mode allows you to specify the reference frequency, PID command value and etc., and run/stop the
motor with the
/
keys.
It is also possible to monitor the running status in real time.
If a light alarm occurs, the ODO appears on the LED monitor.
Programming
mode
This mode allows you to configure function code data and check a variety of information relating to the
inverter status and maintenance.
Alarm mode
If an alarm condition arises, the inverter automatically enters Alarm mode in which you can view the
corresponding alarm code* and its related information on the LED monitor.
* Alarm code: Indicates the cause of the alarm condition. For details, first see Table 6.1 "Abnormal
States Detectable ("Heavy Alarm" and "Light Alarm" Objects)" in Chapter 6, Section 6.1 "Protective
Functions," and then read the troubleshooting of each alarm.
Figure 3.1 shows the status transition of the inverter between these three operation modes.
Power ON
Running mode
Programming mode
Run/Stop of motor
Configuration of function
code data and monitor of
maintenance/alarm info
and various status
Monitor of running status
Detection of
a light alarm
Release of
a light alarm
Run/Stop of motor
Light alarm displayed
+
(Press this key if
an alarm has
occurred.)
Occurrence of
a heavy alarm
Release of
a heavy alarm
Alarm mode
Display of alarm status
Figure 3.1 Status Transition between Operation Modes
Simultaneous keying
Simultaneous keying means pressing two keys at the same time. The simultaneous keying operation is expressed by a
"+" letter between the keys throughout this manual.
For example, the expression "
+
keys" stands for pressing the
3-2
key with the
key held down.
3.3 Running Mode
3.3.1 Monitoring the running status
In Running mode, the fourteen items listed below can be monitored. Immediately after the inverter is turned ON, the monitor
item specified by function code E43 is displayed. Press the
key to switch between these monitor items.
Table 3.3 Monitoring Items
Unit
Meaning of displayed value
*1
Output frequency 1
(before slip
compensation)
Output frequency 2
(after slip
compensation)
Reference
frequency
Motor speed
Load shaft speed
Line speed
Speed (%)
Output current
Output voltage
*2
Calculated torque
„ Hz † A † kW
Hz
Frequency actually being output
(E48 = 0)
„ Hz † A † kW
Hz
Frequency actually being output
(E48 = 1)
„ Hz † A † kW
Hz
Reference frequency being set
(E48 = 2)
„ Hz „ A † kW
r/min
„ Hz „ A † kW r/min
† Hz „ A „ kW m/min
† Hz † A † kW
%
† Hz „ A † kW
X † Hz † A † kW
A
V
† Hz † A † kW
%
† Hz † A „ kW
kW
† Hz † A † kW
*3, *5
† Hz † A † kW
PID output
*3, *4
† Hz † A † kW
%
Load factor
*6
† Hz † A † kW
%
Motor output
*7
† Hz † A „ kW
%
*8
† Hz † A † kW
Torque current
*9
† Hz † A † kW
%
Magnetic flux
command
*9
† Hz † A † kW
%
Input power
PID command
*3, *4
PID feedback amount
Analog input monitor
Input watt-hour
0
† Hz † A † kW
kWh
Output frequency (Hz) ×
120
P01
Output frequency (Hz) u E50
Output frequency (Hz) u E50
Output frequency
x 100
Maximum frequency
Current output from the inverter in RMS
Voltage output from the inverter in RMS
Motor output torque in %
(Calculated value)
Input power to the inverter
PID command/feedback amount
transformed to that of virtual physical
value of the object to be controlled (e.g.
temperature)
Refer to function codes E40 and E41 for
details.
PID output in % as the maximum
frequency (F03) being at 100%
Load factor of the motor in % as the rated
output being at 100%
Motor output in kW
An analog input to the inverter in a format
suitable for a desired scale.
Refer to function codes E40 and E41 for
details.
Torque current command value or
calculated torque current
(E48 = 3)
(E48 = 4)
(E48 = 5)
(E48 = 7)
3
4
8
9
10
12
14
15
16
17
23
Magnetic flux command value
24
Input watt - hour (kWh)
100
25
*1 A value exceeding 9999 cannot be displayed as is on the 4-digit LED monitor screen, so the LED monitor displays one-tenth of the actual
value with the x10 LED lit.
*2 When the LED monitor displays an output voltage, the 7-segment letter u in the lowest digit stands for the unit of the voltage "V."
*3 These PID related items appear only when the inverter drives the motor under the PID control specified by function code J01 (= 1, 2 or 3).
*4 When the LED monitor displays a PID command or its output amount, the dot (decimal point) attached to the lowest digit of the 7-segment
letter blinks.
*5 When the LED monitor displays a PID feedback amount, the dot (decimal point) attached to the lowest digit of the 7-segment letter lights.
*6 When the LED monitor displays a load factor, the 7-segment letter ; in the lowest digit stands for "%."
*7 When the LED monitor displays the motor output, the unit LED indicator "kW" blinks.
*8 The analog input monitor can appear only when the analog input monitor function is assigned to any of the analog input terminals by any of
function codes E61 to E63 (= 20).
*9 appears under the V/f control.
3-3
OPERATION USING THE KEYPAD
Function code E48 specifies what to be displayed on the LED monitor and LED
indicators.
Speed monitor
Function
code data
for E43
Chap. 3
Monitor items
Display
sample on the LED indicator
LED monitor „: ON, †: OFF
Function code E42 (LED display filter) allows you to filter the monitoring signals for the monitor items such as output
frequency and output current. Increase the E42 data if the monitored values are unstable and unreadable due to
fluctuation of load.
3.3.2 Monitoring light alarms
The JAGUAR VXG identifies abnormal states in two categories--Heavy alarm and Light alarm. If the former occurs, the
inverter immediately trips; if the latter occurs, the inverter shows the ODO on the LED monitor and blinks the KEYPAD
CONTROL LED but it continues to run without tripping.
Which abnormal states are categorized as a light alarm ("Light alarm" object) should be defined with function codes H81 and
H82 beforehand.
Assigning the LALM signal to any one of the digital output terminals with any of function codes E20 to E24 and E27 (= 98)
enables the inverter to output the LALM signal on that terminal upon occurrence of a light alarm.
For details of the light alarm objects, refer to Chapter 6 "TROUBLESHOOTING," Table 6.1.
„ How to check a light alarm factor
When a light alarm occurs, ODO appears on the LED monitor. To check the current light alarm factor, enter Programming mode
key and select B on Menu #5 "Maintenance Information."
by pressing the
It is also possible to check the factors of the last three light alarms B (last) to B (3rd last).
For details of the menu transition of the maintenance information, refer to Section 3.4.6 "Reading maintenance information."
„ How to remove the current light alarm
After checking the current light alarm factor, to switch the LED monitor back to the running status display (e.g., output
frequency) from the ODO indication, press the
key in Running mode.
If the light alarm factor has been removed, the KEYPAD CONTROL LED stops blinking and the LALM signal turns OFF. If
not (e.g. DC fan lock), the KEYPAD CONTROL LED continues blinking and the LALM signal remains ON.
3-4
3.4 Programming Mode
The Programming mode provides you with these functions--setting and checking function code data, monitoring maintenance
information and checking input/output (I/O) signal status. The functions can be easily selected with the menu-driven system.
Table 3.4 lists menus available in Programming mode. The leftmost digit (numerals) of each letter string on the LED monitor
indicates the corresponding menu number and the remaining three digits indicate the menu contents.
When the inverter enters Programming mode from the second time on, the menu selected last in Programming mode will be
displayed.
Menu #
1
"Quick Setup"
"Data Setting"
Main functions
Refer to:
IQ
Displays only basic function codes to customize the inverter operation.
Section
3.4.1
IBB
F codes (Fundamental functions)
HBB
E codes
(Extension terminal functions)
FBB
C codes (Control functions)
SBB
P codes (Motor 1 parameters)
KBB
H codes
(High performance functions)
DBB
A codes (Motor 2 parameters)
EBB
b codes (Motor 3 parameters)
UBB
r codes (Motor 4 parameters)
MBB
J codes (Application functions 1)
GBB
d codes (Application functions 2)
XBB
U codes (Application functions 3)
\BB
y codes (Link functions)
Selecting each of these
function codes enables its data
to be displayed/changed.
Section
3.4.2
RBB
o codes (Optional functions) (Note)
Section
3.4.3
2
"Data Checking"
UHS
Displays only function codes that have been changed from their
factory defaults. You can refer to or change those function code data.
3
"Drive
Monitoring"
RSH
Displays the running information required for maintenance or test
running.
Section
3.4.4
4
"I/O Checking"
LBR
Displays external interface information.
Section
3.4.5
5
"Maintenance
Information"
FKH
Displays maintenance information including cumulative run time.
Section
3.4.6
6
"Alarm
Information"
DO
Displays the recent four alarm codes. You can refer to the running
information at the time when the alarm occurred.
Section
3.4.7
Allows you to read or write function code data, as well as verifying it.
7
"Data Copying"
FS\
Saving the function code data of the currently running inverter into the
keypad and connecting it to a PC running JAGUAR Loader enables
data checking on the PC.
Section
3.4.8
(Note) The o codes are displayed only when the corresponding option is mounted. For details, refer to the Instruction Manual
for the corresponding option.
3-5
OPERATION USING THE KEYPAD
0
Menu
Chap. 3
Table 3.4 Menus Available in Programming Mode
LED monitor
shows:
„ Selecting menus to display
The menu-driven system allows you to cycle through menus. To cycle through necessary menus only for simple operation, use
function code E52 that provides a choice of three display modes as listed below.
The factory default (E52 = 0) is to display only three menus--Menu #0 "Quick Setup," Menu #1 "Data Setting" and Menu #7
"Data Copying," allowing no switching to any other menu.
Table 3.5 Keypad Display Mode Selection – Function Code E52
Data for E52
Mode
Menus selectable
0
Function code data editing mode (factory default)
Menu #0 "Quick Setup"
Menu #1 "Data Setting"
Menu #7 "Data Copying"
1
Function code data check mode
Menu #2 "Data Checking"
Menu #7 "Data Copying"
2
Full-menu mode
Menus #0 through #7
Press the
key to enter Programming mode and display menus. While cycling through the menus with the
/
key, select the desired menu item with the
key. Once the entire menu has been cycled through, the display returns
to the first menu item.
3.4.1 Setting up basic function codes quickly -- Menu #0 "Quick Setup" --
Menu #0 "Quick Setup" in Programming mode allows you to quickly display and set up a basic set of function codes specified
in Chapter 5, Section 5.1, "Function Code Tables."
To use Menu #0 "Quick Setup," you need to set function code E52 to "0" (Function code data editing mode) or "2" (Full-menu
mode).
The predefined set of function codes that are subject to quick setup are held in the inverter.
Figure 3.2 shows the menu transition in Menu #0 "Quick Setup" and function code data changing procedure.
Figure 3.2 Menu Transition in Menu #0 "Quick Setup" and Function Code Data Changing Procedure
3-6
Basic key operation
This section gives a description of the basic key operation in "Quick Setup," following the example of the function code data
changing procedure shown in Figure 3.2.
This example shows you how to change function code F01 data (Frequency command source) from the factory default "
keys on keypad (F01 = 0)" to "Current input to terminal [C1] (C1 function) (4 to 20 mA DC) (F01 = 2)."
/
It is possible to change or add function code items subject to quick setup. For details, consult your Fuji Electric
representatives.
3.4.2 Setting up function codes -- Menu #1 "Data Setting" --
Menu #1 "Data Setting" (IBB through\BB) in Programming mode allows you to set up all function codes.
To set function codes in this menu, it is necessary to set function code E52 to "0" (Function code data editing mode) or "2"
(Full-menu mode).
The menu transition in Menu #1 "Data Setting" is just like that in Menu #0 "Quick Setup."
Basic key operation
The basic key operation in Menu #1 "Data Setting" is just like that in Menu #0 "Quick Setup."
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears.
and
keys to display the desired function code group from the choices IBB through \BB.
(2) Use the
key to proceed to the list of function codes for the selected function code group.
(3) Press the
(4) Use the
and
keys to display the desired function code, then press the
key.
The data of this function code appears.
(5) Change the function code data using the
and
keys.
(6) Press the
key to establish the function code data.
The VDXH appears and the data will be saved in the memory inside the inverter. The display will return to the function code
list, then move to the next function code.
Pressing the
key instead of the
key cancels the change made to the data. The data reverts to the previous value, the
display returns to the function code list, and the original function code reappears.
key to return to the menu from the function code list.
(7) Press the
3.4.3 Checking changed function codes -- Menu #2 "Data Checking" --
Menu #2 "Data Checking" in Programming mode allows you to check function codes that have been changed. Only the
function codes whose data has been changed from the factory defaults are displayed on the LED monitor. You can refer to the
function code data and change it again if necessary. To check function codes in Menu #2 "Data Checking," it is necessary to set
function code E52 to "1" (Function code data check mode) or "2" (Full-menu mode).
The menu transition in Menu #2 "Data Checking" is just like that in Menu #0 "Quick Setup."
3-7
OPERATION USING THE KEYPAD
Cursor movement
You can move the cursor when changing function code data by holding down the
key for 1 second or longer in the
same way as with the frequency settings. This action is called "Cursor movement."
Chap. 3
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears. (In this example, IQ is displayed.)
(2) If anything other than IQ is displayed, use the
and
keys to display IQ.
key to proceed to the list of function codes.
(3) Press the
(4) Use the
and
keys to display the desired function code (I in this example), then press the
key.
The data of this function code appears. (In this example, data of I appears.)
and
keys. (In this example, press the
key two times to change data to
(5) Change the function code data using the
.)
(6) Press the
key to establish the function code data.
The VDXH appears and the data will be saved in the memory inside the inverter. The display will return to the function code
list, then move to the next function code. (In this example,I .)
Pressing the
key instead of the
key cancels the change made to the data. The data reverts to the previous value, the
display returns to the function code list, and the original function code reappears.
(7) Press the
key to return to the menu from the function code list.
3.4.4 Monitoring the running status -- Menu #3 "Drive Monitoring" --
Menu #3 "Drive Monitoring" is used to monitor the running status during maintenance and trial running. The display items for
"Drive Monitoring" are listed in Table 3.6. Figure 3.3 shows the menu transition in Menu #3 "Drive Monitoring."
Figure 3.3 Menu Transition in Menu #3 "Drive Monitoring"
Basic key operation
To monitor the running status in "Drive monitoring," set function code E52 to "2" (Full-menu mode) beforehand.
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears. (In this example, IQ is displayed.)
(2) Use the
and
keys to display "Drive Monitoring" (RSH).
(3) Press the
key to proceed to a list of monitoring items (e.g. B).
(4) Use the
and
keys to display the desired monitoring item, then press the
key.
The running status information for the selected item appears.
(5) Press the
key to return to the list of monitoring items. Press the
key again to return to the menu.
3-8
Table 3.6 "Drive Monitoring" Display Items
LED monitor
shows:
Item
Unit
Description
Output frequency
Hz
Output frequency before slip compensation
B
Output frequency
Hz
Output frequency after slip compensation
B
Output current
A
Output current
B
Output voltage
V
Output voltage
B
Calculated torque
%
Calculated output torque of the motor in %
B
Reference frequency
Hz
Frequency specified by a frequency command
B
Rotational direction
N/A
I: forward, U: reverse, : stop
B
Running status
N/A
B
Motor speed
r/min
B
Load shaft speed
PID command value
Rotational direction being outputted
Running status in 4-digit hexadecimal format
Refer to "„ Displaying running status (B ) and running status 2 (B )" on
the next page.
120
Display value = (Output frequency Hz) u
(No. of poles)
If the value is 10000 or lager, the x10 LED turns ON and the LED monitor
shows one-tenth of the value.
r/min
Display value = (Output frequency Hz) u (Function code E50: Coefficient for
speed indication)
If the value is 10000 or lager, the x10 LED turns ON and the LED monitor
shows one-tenth of the value.
N/A
Virtual physical value (e.g., temperature or pressure) of the object to be
controlled, which is converted from the PID command value using function
code E40 and E41 data (PID display coefficients A and B)
Display value = (PID command value) u (Coefficient A - B) + B
If PID control is disabled, "" appears.
B
PID feedback
amount
B
Torque limit value
%
Virtual physical value (e.g., temperature or pressure) of the object to be
controlled, which is converted from the PID feedback amount using function
code E40 and E41 data (PID display coefficients A and B)
Display value = (PID feedback amount) u (Coefficient A - B) + B
If PID control is disabled, "" appears.
Driving torque limit value A (based on motor rated torque)
B
Torque limit value
%
Braking torque limit value B (based on motor rated torque)
B
Ratio setting
B
Line speed
B
(Not used.)
B
(Not used.)
B
(Not used.)
B
(Not used.)
B
(Not used.)
N/A
When this setting is 100%, the LED monitor shows 1.00 time of the value to
be displayed. If no ratio setting is selected, "" appears.
Display value = (Output frequency Hz) u (Function code E50: Coefficient for
speed indication)
m/min
If the value is 10000 or lager, the x10 LED turns ON and the LED monitor
shows one-tenth of the value.
%
B
PID output value
%
B
Flux command value
%
PID output value in %. (100% at the maximum frequency)
If PID control is disabled, "" appears.
Flux command value in %.
Running status 2 in 4-digit hexadecimal format
Refer to "„ Displaying running status (B ) and running status 2 (B)" on
the next page.
B
Running status 2
B
Motor temperature
ºC
B
(Not used.)
B
(Not used.)
B
B
Current position
pulse, 4-multiplied
Position deviation
pulse, 4-multiplied
N/A
Temperature detected by the NTC thermistor built in the motor
If the NTC thermistor connectivity is disabled, "" appears.
pulse
Current position pulse for positioning control (servo lock)
pulse
Position deviation pulse for positioning control (servo lock)
3-9
OPERATION USING THE KEYPAD
B
Chap. 3
B
„ Displaying running status (B ) and running status 2 (B )
To display the running status and running status 2 in 4-digit hexadecimal format, each state has been assigned to bits 0 to 15 as
listed in Tables 3.7 and 3.8. Table 3.9 shows the relationship between each of the status assignments and the LED monitor
display.
Table 3.10 gives the conversion table from 4-bit binary to hexadecimal.
Table 3.7 Running Status (B ) Bit Assignment
Bit
Notation
15
BUSY
14
WR
13
Content
Bit
Notation
"1" when function code data is being
written.
7
VL
Always "0."
6
TL
Content
"1" under voltage limiting control.
"1" under torque limiting control.
Always "0."
5
NUV
"1" when the DC link bus voltage is higher
than the undervoltage level.
"1" when communication is enabled (when
ready for run and frequency commands via
communications link).
4
BRK
"1" during braking.
3
INT
"1" when the inverter output is shut down.
12
RL
11
ALM
"1" when an alarm has occurred.
10
DEC
"1" during deceleration.
2
EXT
"1" during DC braking.
9
ACC
"1" during acceleration.
1
REV
"1" during running in the reverse direction.
8
IL
"1" under current limiting control.
0
FWD
"1" during running in the forward direction.
Table 3.8 Running Status 2 (B ) Bit Assignment
Bit
Notation
Content
Bit
Notation
15
7
Speed limiting (under torque control)
14
6
(Not used.)
13
5
12
4
Motor selection
00: Motor 1
01: Motor 2
10: Motor 3
11: Motor 4
11
3
10
2
9
1
0
(Not used.)
8
Content
Inverter drive control
0000: V/f control with slip compensation
inactive
0001: Dynamic torque vector control
0010: V/f control with slip compensation
active
0011: V/f control with speed sensor
0100: Dynamic vector control with
speed sensor
0101: Vector control without speed sensor
0110: Vector control with speed sensor
1010: Torque control
(Vector control without speed
sensor)
1011: Torque control
(Vector control with speed sensor)
Table 3.9 Running Status Display
LED No.
Bit
Notation
Example
Binary
LED4
15
14
13
BUSY WR
1
0
LED3
12
RL
0
11
10
9
ALM DEC ACC
0
0
0
1
Hexadecimal on
the LED
monitor
LED2
8
7
IL
VL
1
0
6
5
4
3
2
1
0
TL NUV BRK INT EXT REV FWD
0
1
3-10
LED1
0
0
0
0
1
„ Hexadecimal expression
A 4-bit binary number can be expressed in hexadecimal (1 hexadecimal digit). Table 3.10 shows the correspondence between
the two notations. The hexadecimals are shown as they appear on the LED monitor.
Table 3.10 Binary and Hexadecimal Conversion
Binary
Hexadecimal
Binary
Hexadecimal
0
0
1
0
0
0
0
0
0
1
1
0
0
1
0
0
1
0
1
0
1
0
D
0
0
1
1
1
0
1
1
E
0
1
0
0
1
1
0
0
F
0
1
0
1
1
1
0
1
G
0
1
1
0
1
1
1
0
H
0
1
1
1
1
1
1
1
I
3.4.5 Checking I/O signal status -- Menu #4 "I/O Checking" --
Using Menu #4 "I/O Checking" displays the I/O status of external signals including digital and analog I/O signals without using
a measuring instrument. Table 3.11 lists check items available. The menu transition in Menu #4 "I/O Checking" is shown in
Figure 3.4.
Figure 3.4 Menu Transition in Menu #4 "I/O Checking"
3-11
OPERATION USING THE KEYPAD
0
Chap. 3
0
Basic key operation
To check the status of the I/O signals, set function code E52 to "2" (Full-menu mode) beforehand.
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears.
(2) Use the
and
keys to display "I/O Checking" (LBR).
(3) Press the
key to proceed to a list of I/O check items (e.g. B).
(4) Use the
and
keys to display the desired I/O check item, then press the
key.
The corresponding I/O check data appears. For the item B or B, using the
and
keys switches the display
method between the segment display (for external signal information in Table 3.12) and hexadecimal display (for I/O signal
status in Table 3.13).
(5) Press the
key to return to the list of I/O check items. Press the
key again to return to the menu.
Table 3.11 I/O Check Items
LED monitor
shows:
Item
Description
B
I/O signals on the control circuit
terminals
Shows the ON/OFF state of the digital I/O terminals. Refer to
"„ Displaying control I/O signal terminals" on the next page for
details.
B
I/O signals on the control circuit
terminals under communications
control
Shows the ON/OFF state of the digital I/O terminals that received a
command via RS-485 and optional communications. Refer to
"„ Displaying control I/O signal terminals" and
"„ Displaying control I/O signal terminals under communications
control" on the following pages for details.
B
Input voltage on terminal [12]
Shows the input voltage on terminal [12] in volts (V).
B
Input current on terminal [C1]
Shows the input current on terminal [C1] in milliamperes (mA).
B
Output voltage on terminal [FM1]
Shows the output voltage on terminal [FM1] in volts (V).
B
Output voltage on terminal [FM2]
Shows the output voltage on terminal [FM2] in volts (V).
B
Input voltage on terminal [V2]
Shows the input voltage on terminal [V2] in volts (V).
B
Output current on terminal [FM1]
Shows the output current on terminal [FM1] in milliamperes (mA).
B
Output current on terminal [FM2]
Shows the output current on terminal [FM2] in milliamperes (mA).
B
Shows the ON/OFF state of the digital I/O terminals on the digital input
Option control circuit terminal
and output interface cards (options). Refer to "„ Displaying control I/O
(I/O)
signal terminals on options" on page 3-14 for details.
B
Terminal [X7] pulse input monitor
Shows the pulse rate of the pulse train signal on terminal [X7].
B
PG pulse rate
(A/B phase signal from the
reference PG)
Shows the pulse rate (p/s) of the A/B phase signal fed back from the
reference PG.
B
PG pulse rate
(Z phase signal from the reference
PG)
Shows the pulse rate (p/s) of the Z phase signal fed back from the
reference PG.
B
PG pulse rate
(A/B phase signal from the slave
PG)
Shows the pulse rate (p/s) of the A/B phase signal fed back from the
slave PG.
B
PG pulse rate
(Z phase signal from the slave PG)
Shows the pulse rate (p/s) of the Z phase signal fed back from the slave
PG.
B
(Not used.)
B
Input voltage on terminal [32]
Shows the input voltage on terminal [32] on the analog interface card
(option) in volts (V).
B
Input current on terminal [C2]
Shows the input current on terminal [C2] on the analog interface card
(option) in milliamperes (mA).
B
Output voltage on terminal [AO]
Shows the output voltage on terminal [AO] on the analog interface card
(option) in volts (V).
B
Output current on terminal [CS]
Shows the output current on terminal [CS] on the analog interface card
(option) in milliamperes (mA).
B
Customizable logic timer monitor
Monitors the timer or counter value in the customizable logic
specified by U91.
3-12
„ Displaying control I/O signal terminals
The status of control I/O signal terminals may be displayed with ON/OFF of the LED segment or in hexadecimal.
• Displaying the I/O signal status with ON/OFF of each LED segment
If all terminal signals are OFF (open), segments "g" on all of LED1 to LED4 will light ("– – – –").
OPERATION USING THE KEYPAD
Table 3.12 Segment Display for External Signal Information
Segment
LED4
LED3
LED2
LED1
a
30A/B/C
Y1-CMY
X7
FWD
b
Y2-CMY
REV
c
Y3-CMY
X1
d
Y4-CMY
EN
X2
e
Y5A-Y5C
X3
f
(XF) *
X4
g
(XR) *
X5
dp
(RST) *
X6
—: No corresponding control circuit terminal exists
* (XF), (XR), and (RST) are assigned for communications control. Refer to "„ Displaying control I/O signal terminals under
communications control" on the next page.
• Displaying I/O signal status in hexadecimal
Each I/O terminal is assigned to bit 15 through bit 0 as shown in Table 3.13. An unassigned bit is interpreted as "0." Allocated
bit data is displayed on the LED monitor as four hexadecimal digits ( to I each).
On the JAGUAR VXG, digital input terminals [FWD] and [REV] are assigned to bits 0 and 1, respectively. Terminals [X1]
through [X7] are assigned to bits 2 through 10. The bit is set to "1" when the corresponding input terminal is short-circuited
(ON), and it is set to "0" when the terminal is open (OFF). For example, when [FWD] and [X1] are ON (short-circuited) and all
the others are OFF (open), is displayed on LED4 to LED1.
Digital output terminals [Y1] through [Y4] are assigned to bits 0 through 3. Each bit is set to "1" when the output terminal [Y1],
[Y2], [Y3] or [Y4] is short-circuited with [CMY] (ON), and "0" when it is open (OFF).
The status of the relay contact output terminal [Y5A/C] is assigned to bit 4. It is set to "1" when the circuit between output
terminals [Y5A] and [Y5C] is closed. The status of the relay contact output terminals [30A/B/C] is assigned to bit 8. It is set to
"1" when the circuit between output terminals [30A] and [30C] is closed, and "0" when the circuit between [30A] and [30C] is
open.
For example, if [Y1] is ON, [Y2] through [Y4] are OFF, the circuit between [Y5A] and [Y5C] is open, and the circuit between
[30A] and [30C] is closed, then " " is displayed on the LED4 through LED1.
Table 3.13 presents bit assignment and an example of corresponding hexadecimal display on the 7-segment LED.
Table 3.13 Segment Display for I/O Signal Status in Hexadecimal (Example)
LED No.
Bit
LED4
15
14
LED3
13
Input terminal (RST)* (XR)* (XF)*
Output terminal
Example
Binary
12
11
10
9
-
EN
-
LED2
LED1
8
7
6
5
4
3
2
-
X7
X6
X5
X4
X3
X2
X1
-
-
-
Y5A/C Y4
Y3
Y2
Y1
0
0
0
1
0
1
-
-
-
-
-
-
-
30A/
B/C
0
0
0
0
0
0
0
0
0
0
1
0
REV FWD
Hexadecimal on
the LED
monitor
– No corresponding control circuit terminal exists.
* (XF), (XR), and (RST) are assigned for communications control. Refer to "„ Displaying control I/O signal terminals under
communications control" on the next page.
3-13
Chap. 3
As shown in Table 3.12 and the figure below, each of segments "a" to "dp" on LED1 and LED2 lights when the corresponding
digital input terminal circuit ([FWD], [REV], [X1] to [X7]) is closed; it goes OFF when it is open. Each of segments "a" to "e"
on LED3 lights when the circuit between output terminal [Y1], [Y2], [Y3] or [Y4] and terminal [CMY] or between terminals
[Y5A] and [Y5C] is closed, respectively; it goes OFF when the circuit is open. Segment "a" on LED4 is for terminals
[30A/B/C] and lights when the circuit between terminals [30C] and [30A] is short-circuited (ON) and goes OFF when it is
open.
„ Displaying control I/O signal terminals under communications control
Under communications control, input commands (function code S06) sent via RS-485 or other optional communications can be
displayed in two ways: "with ON/OFF of each LED segment" and "in hexadecimal." The content to be displayed is basically the
same as that for the control I/O signal terminal status display; however, (XF), (XR), and (RST) are added as inputs. Note that
under communications control, the I/O display is in normal logic (using the original signals not inverted)
For details about input commands sent through the communications link, refer to the RS-485 Communication User's
Manual and the instruction manual of communication-related options as well.
„ Displaying control I/O signal terminals on options
The LED monitor can also show the signal status of the terminals on the optional digital input and output interface cards, just
like the signal status of the control circuit terminals.
Table 3.14 lists the assignment of digital I/O signals to the LED segments.
Table 3.14 Segment Display for External Signal Information
LED No.
Segment
LED4
LED3
LED2
LED1
a
O1
I9
I1
b
O2
I10
I2
c
O3
I11
I3
d
O4
I12
I4
e
O5
I13
I5
f
O6
I14
I6
g
O7
I15
I7
dp
O8
I16
I8
LED4
LED3
LED2
15
14
13
12
11
10
9
8
Input terminal
I16
I15
I14
I13
I12
I11
I10
I9
I8
I7
I6
I5
I4
I3
I2
I1
-
-
-
-
-
-
-
-
O8
O7
O6
O5
O4
O3
O2
O1
Output terminal
7
6
5
LED1
Bit
4
3
2
1
0
3.4.6 Reading maintenance information -- Menu #5 "Maintenance Information" --
Menu #5 "Maintenance Information" (FKH) contains information necessary for performing maintenance on the inverter. The
menu transition in Menu #5 "Maintenance Information" is just like that in Menu #3 "Drive Monitoring." (Refer to Section
3.4.4.)
Basic key operation
To view the maintenance information, set function code E52 to "2" (Full-menu mode) beforehand.
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears.
(2) Use the
and
keys to display "Maintenance Information" (FKH).
(3) Press the
key to proceed to the list of maintenance items (e.g. B).
and
keys to display the desired maintenance item, then press the
key.
(4) Use the
The data of the corresponding maintenance item appears.
(5) Press the
key to return to the list of maintenance items. Press the
key again to return to the menu.
3-14
Chapter 3 OPERATION USING THE KEYPAD (in the case of remote keypad)
3.1 LED Monitor, Keys and LED Indicators on the Keypad
7-segment
LED monitor
LED indicators
UP key
RUN LED
RUN key
Function/
Data key
STOP key
DOWN key
USB port
When using a multi-function keypad instead of a remote keypad, read the Multi-function Keypad Instruction Manual.
Table 3.1 Overview of Keypad Functions
Item
LED Monitor, Keys,
and LED Indicators
Functions
Four-digit, 7-segment LED monitor which displays the followings according to the
operation modes.
„ In Running mode:
Running status information (e.g., output frequency, current,
and voltage)
When a light alarm occurs, ODOis displayed.
„ In Programming mode: Menus, function codes and their data
„ In Alarm mode:
Alarm code, which identifies the alarm factor when the
protective function is activated.
LED
Monitor
Program/Reset key which switches the operation modes of the inverter.
„ In Running mode:
Pressing this key switches the inverter to Programming
mode.
„ In Programming mode: Pressing this key switches the inverter to Running mode.
„ In Alarm mode:
Pressing this key after removing the alarm factor will switch
the inverter to Running mode.
Function/Data key which switches the operations you want to do in each mode as
follows:
„ In Running mode:
Pressing this key switches the information to be displayed
concerning the status of the inverter (output frequency (Hz),
output current (A), output voltage (V), etc.).
When a light alarm is displayed, holding down this key resets
the light alarm and switches back to Running mode.
„ In Programming mode: Pressing this key displays the function code or establishes
and
keys.
the data entered with
„ In Alarm mode:
Pressing this key displays the details of the problem
indicated by the alarm code that has come up on the LED
monitor.
Operation
Keys
RUN key. Press this key to run the motor.
STOP key. Press this key to stop the motor.
㸭
RUN LED
KEYPAD
CONTROL LED
LED
Indicators
Unit LEDs
(3 LEDs)
x10 LED
UP and DOWN keys. Press these keys to select the setting items and change the function
code data displayed on the LED monitor.
Lights when running with a run command entered by the
key, by terminal command
FWD or REV, or through the communications link.
key (F02
Lights when the inverter is ready to run with a run command entered by the
key cannot
= 0, 2, or 3). In Programming and Alarm modes, however, pressing the
run the inverter even if this indicator lights.
These three LED indicators identify the unit of numeral displayed on the LED monitor in
Running mode by combination of lit and unlit states of them.
Unit: Hz, A, kW, r/min and m/min
Refer to Chapter 3, Section 3.3.1 "Monitoring the running status" for details.
While the inverter is in Programming mode, the LEDs of Hz and kW light.
„ Hz † A „ kW
Lights when the data to display exceeds 9999. When this LED lights, the "displayed
value x 10" is the actual value.
Example:
If the LED monitor displays and the x10 LED lights, it means that the actual value
is "1,234 u 10 = 12,340."
3-1
OPERATION USING THE KEYPAD
Program/
Reset key
Chap. 3
As shown at the right, the keypad consists of a four-digit
LED monitor, six keys, and five LED indicators.
The keypad allows you to run and stop the motor,
monitor the running status, specify the function code
data, and monitor I/O signal states, maintenance
information, and alarm information.
Table 3.1 Overview of Keypad Functions (Continued)
LED Monitor, Keys,
and LED Indicators
Item
Functions
The USB port with a mini B connector enables the inverter to connect with a PC with a
USB cable.
USB port
3.2 Overview of Operation Modes
JAGUAR VXG features the following three operation modes.
Table 3.2 Operation Modes
Operation mode
Description
Running mode
After powered ON, the inverter automatically enters this mode.
This mode allows you to specify the reference frequency, PID command value and etc., and run/stop the
motor with the
/
keys.
It is also possible to monitor the running status in real time.
If a light alarm occurs, the ODO appears on the LED monitor.
Programming
mode
This mode allows you to configure function code data and check a variety of information relating to the
inverter status and maintenance.
Alarm mode
If an alarm condition arises, the inverter automatically enters Alarm mode in which you can view the
corresponding alarm code* and its related information on the LED monitor.
* Alarm code: Indicates the cause of the alarm condition. For details, first see Table 6.1 "Abnormal
States Detectable ("Heavy Alarm" and "Light Alarm" Objects)" in Chapter 6, Section 6.1 "Protective
Functions," and then read the troubleshooting of each alarm.
Figure 3.1 shows the status transition of the inverter between these three operation modes.
Power ON
Running mode
Programming mode
Run/Stop of motor
Configuration of function
code data and monitor of
maintenance/alarm info
and various status
Monitor of running status
Detection of
a light alarm
Release of
a light alarm
Run/Stop of motor
Light alarm displayed
+
(Press this key if
an alarm has
occurred.)
Occurrence of
a heavy alarm
Release of
a heavy alarm
Alarm mode
Display of alarm status
Figure 3.1 Status Transition between Operation Modes
Simultaneous keying
Simultaneous keying means pressing two keys at the same time. The simultaneous keying operation is expressed by a
"+" letter between the keys throughout this manual.
For example, the expression "
+
keys" stands for pressing the
3-2
key with the
key held down.
3.3 Running Mode
3.3.1 Monitoring the running status
In Running mode, the fourteen items listed below can be monitored. Immediately after the inverter is turned ON, the monitor
item specified by function code E43 is displayed. Press the
key to switch between these monitor items.
Table 3.3 Monitoring Items
Unit
Meaning of displayed value
*1
Output frequency 1
(before slip
compensation)
Output frequency 2
(after slip
compensation)
Reference
frequency
Motor speed
Load shaft speed
Line speed
Speed (%)
Output current
Output voltage
*2
Calculated torque
„ Hz † A † kW
Hz
Frequency actually being output
(E48 = 0)
„ Hz † A † kW
Hz
Frequency actually being output
(E48 = 1)
„ Hz † A † kW
Hz
Reference frequency being set
(E48 = 2)
„ Hz „ A † kW
r/min
„ Hz „ A † kW r/min
† Hz „ A „ kW m/min
† Hz † A † kW
%
† Hz „ A † kW
X † Hz † A † kW
A
V
† Hz † A † kW
%
† Hz † A „ kW
kW
† Hz † A † kW
*3, *5
† Hz † A † kW
PID output
*3, *4
† Hz † A † kW
%
Load factor
*6
† Hz † A † kW
%
Motor output
*7
† Hz † A „ kW
%
*8
† Hz † A † kW
Torque current
*9
† Hz † A † kW
%
Magnetic flux
command
*9
† Hz † A † kW
%
Input power
PID command
*3, *4
PID feedback amount
Analog input monitor
Input watt-hour
0
† Hz † A † kW
kWh
Output frequency (Hz) ×
120
P01
Output frequency (Hz) u E50
Output frequency (Hz) u E50
Output frequency
x 100
Maximum frequency
Current output from the inverter in RMS
Voltage output from the inverter in RMS
Motor output torque in %
(Calculated value)
Input power to the inverter
PID command/feedback amount
transformed to that of virtual physical
value of the object to be controlled (e.g.
temperature)
Refer to function codes E40 and E41 for
details.
PID output in % as the maximum
frequency (F03) being at 100%
Load factor of the motor in % as the rated
output being at 100%
Motor output in kW
An analog input to the inverter in a format
suitable for a desired scale.
Refer to function codes E40 and E41 for
details.
Torque current command value or
calculated torque current
(E48 = 3)
(E48 = 4)
(E48 = 5)
(E48 = 7)
3
4
8
9
10
12
14
15
16
17
23
Magnetic flux command value
24
Input watt - hour (kWh)
100
25
*1 A value exceeding 9999 cannot be displayed as is on the 4-digit LED monitor screen, so the LED monitor displays one-tenth of the actual
value with the x10 LED lit.
*2 When the LED monitor displays an output voltage, the 7-segment letter u in the lowest digit stands for the unit of the voltage "V."
*3 These PID related items appear only when the inverter drives the motor under the PID control specified by function code J01 (= 1, 2 or 3).
*4 When the LED monitor displays a PID command or its output amount, the dot (decimal point) attached to the lowest digit of the 7-segment
letter blinks.
*5 When the LED monitor displays a PID feedback amount, the dot (decimal point) attached to the lowest digit of the 7-segment letter lights.
*6 When the LED monitor displays a load factor, the 7-segment letter ; in the lowest digit stands for "%."
*7 When the LED monitor displays the motor output, the unit LED indicator "kW" blinks.
*8 The analog input monitor can appear only when the analog input monitor function is assigned to any of the analog input terminals by any of
function codes E61 to E63 (= 20).
*9 appears under the V/f control.
3-3
OPERATION USING THE KEYPAD
Function code E48 specifies what to be displayed on the LED monitor and LED
indicators.
Speed monitor
Function
code data
for E43
Chap. 3
Monitor items
Display
sample on the LED indicator
LED monitor „: ON, †: OFF
Function code E42 (LED display filter) allows you to filter the monitoring signals for the monitor items such as output
frequency and output current. Increase the E42 data if the monitored values are unstable and unreadable due to
fluctuation of load.
3.3.2 Monitoring light alarms
The JAGUAR VXG identifies abnormal states in two categories--Heavy alarm and Light alarm. If the former occurs, the
inverter immediately trips; if the latter occurs, the inverter shows the ODO on the LED monitor and blinks the KEYPAD
CONTROL LED but it continues to run without tripping.
Which abnormal states are categorized as a light alarm ("Light alarm" object) should be defined with function codes H81 and
H82 beforehand.
Assigning the LALM signal to any one of the digital output terminals with any of function codes E20 to E24 and E27 (= 98)
enables the inverter to output the LALM signal on that terminal upon occurrence of a light alarm.
For details of the light alarm objects, refer to Chapter 6 "TROUBLESHOOTING," Table 6.1.
„ How to check a light alarm factor
When a light alarm occurs, ODO appears on the LED monitor. To check the current light alarm factor, enter Programming mode
key and select B on Menu #5 "Maintenance Information."
by pressing the
It is also possible to check the factors of the last three light alarms B (last) to B (3rd last).
For details of the menu transition of the maintenance information, refer to Section 3.4.6 "Reading maintenance information."
„ How to remove the current light alarm
After checking the current light alarm factor, to switch the LED monitor back to the running status display (e.g., output
frequency) from the ODO indication, press the
key in Running mode.
If the light alarm factor has been removed, the KEYPAD CONTROL LED stops blinking and the LALM signal turns OFF. If
not (e.g. DC fan lock), the KEYPAD CONTROL LED continues blinking and the LALM signal remains ON.
3-4
3.4 Programming Mode
The Programming mode provides you with these functions--setting and checking function code data, monitoring maintenance
information and checking input/output (I/O) signal status. The functions can be easily selected with the menu-driven system.
Table 3.4 lists menus available in Programming mode. The leftmost digit (numerals) of each letter string on the LED monitor
indicates the corresponding menu number and the remaining three digits indicate the menu contents.
When the inverter enters Programming mode from the second time on, the menu selected last in Programming mode will be
displayed.
Menu #
1
"Quick Setup"
"Data Setting"
Main functions
Refer to:
IQ
Displays only basic function codes to customize the inverter operation.
Section
3.4.1
IBB
F codes (Fundamental functions)
HBB
E codes
(Extension terminal functions)
FBB
C codes (Control functions)
SBB
P codes (Motor 1 parameters)
KBB
H codes
(High performance functions)
DBB
A codes (Motor 2 parameters)
EBB
b codes (Motor 3 parameters)
UBB
r codes (Motor 4 parameters)
MBB
J codes (Application functions 1)
GBB
d codes (Application functions 2)
XBB
U codes (Application functions 3)
\BB
y codes (Link functions)
Selecting each of these
function codes enables its data
to be displayed/changed.
Section
3.4.2
RBB
o codes (Optional functions) (Note)
Section
3.4.3
2
"Data Checking"
UHS
Displays only function codes that have been changed from their
factory defaults. You can refer to or change those function code data.
3
"Drive
Monitoring"
RSH
Displays the running information required for maintenance or test
running.
Section
3.4.4
4
"I/O Checking"
LBR
Displays external interface information.
Section
3.4.5
5
"Maintenance
Information"
FKH
Displays maintenance information including cumulative run time.
Section
3.4.6
6
"Alarm
Information"
DO
Displays the recent four alarm codes. You can refer to the running
information at the time when the alarm occurred.
Section
3.4.7
Allows you to read or write function code data, as well as verifying it.
7
"Data Copying"
FS\
Saving the function code data of the currently running inverter into the
keypad and connecting it to a PC running JAGUAR Loader enables
data checking on the PC.
Section
3.4.8
(Note) The o codes are displayed only when the corresponding option is mounted. For details, refer to the Instruction Manual
for the corresponding option.
3-5
OPERATION USING THE KEYPAD
0
Menu
Chap. 3
Table 3.4 Menus Available in Programming Mode
LED monitor
shows:
„ Selecting menus to display
The menu-driven system allows you to cycle through menus. To cycle through necessary menus only for simple operation, use
function code E52 that provides a choice of three display modes as listed below.
The factory default (E52 = 0) is to display only three menus--Menu #0 "Quick Setup," Menu #1 "Data Setting" and Menu #7
"Data Copying," allowing no switching to any other menu.
Table 3.5 Keypad Display Mode Selection – Function Code E52
Data for E52
Mode
Menus selectable
0
Function code data editing mode (factory default)
Menu #0 "Quick Setup"
Menu #1 "Data Setting"
Menu #7 "Data Copying"
1
Function code data check mode
Menu #2 "Data Checking"
Menu #7 "Data Copying"
2
Full-menu mode
Menus #0 through #7
Press the
key to enter Programming mode and display menus. While cycling through the menus with the
/
key, select the desired menu item with the
key. Once the entire menu has been cycled through, the display returns
to the first menu item.
3.4.1 Setting up basic function codes quickly -- Menu #0 "Quick Setup" --
Menu #0 "Quick Setup" in Programming mode allows you to quickly display and set up a basic set of function codes specified
in Chapter 5, Section 5.1, "Function Code Tables."
To use Menu #0 "Quick Setup," you need to set function code E52 to "0" (Function code data editing mode) or "2" (Full-menu
mode).
The predefined set of function codes that are subject to quick setup are held in the inverter.
Figure 3.2 shows the menu transition in Menu #0 "Quick Setup" and function code data changing procedure.
Figure 3.2 Menu Transition in Menu #0 "Quick Setup" and Function Code Data Changing Procedure
3-6
Basic key operation
This section gives a description of the basic key operation in "Quick Setup," following the example of the function code data
changing procedure shown in Figure 3.2.
This example shows you how to change function code F01 data (Frequency command source) from the factory default "
keys on keypad (F01 = 0)" to "Current input to terminal [C1] (C1 function) (4 to 20 mA DC) (F01 = 2)."
/
It is possible to change or add function code items subject to quick setup. For details, consult your Fuji Electric
representatives.
3.4.2 Setting up function codes -- Menu #1 "Data Setting" --
Menu #1 "Data Setting" (IBB through\BB) in Programming mode allows you to set up all function codes.
To set function codes in this menu, it is necessary to set function code E52 to "0" (Function code data editing mode) or "2"
(Full-menu mode).
The menu transition in Menu #1 "Data Setting" is just like that in Menu #0 "Quick Setup."
Basic key operation
The basic key operation in Menu #1 "Data Setting" is just like that in Menu #0 "Quick Setup."
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears.
and
keys to display the desired function code group from the choices IBB through \BB.
(2) Use the
key to proceed to the list of function codes for the selected function code group.
(3) Press the
(4) Use the
and
keys to display the desired function code, then press the
key.
The data of this function code appears.
(5) Change the function code data using the
and
keys.
(6) Press the
key to establish the function code data.
The VDXH appears and the data will be saved in the memory inside the inverter. The display will return to the function code
list, then move to the next function code.
Pressing the
key instead of the
key cancels the change made to the data. The data reverts to the previous value, the
display returns to the function code list, and the original function code reappears.
key to return to the menu from the function code list.
(7) Press the
3.4.3 Checking changed function codes -- Menu #2 "Data Checking" --
Menu #2 "Data Checking" in Programming mode allows you to check function codes that have been changed. Only the
function codes whose data has been changed from the factory defaults are displayed on the LED monitor. You can refer to the
function code data and change it again if necessary. To check function codes in Menu #2 "Data Checking," it is necessary to set
function code E52 to "1" (Function code data check mode) or "2" (Full-menu mode).
The menu transition in Menu #2 "Data Checking" is just like that in Menu #0 "Quick Setup."
3-7
OPERATION USING THE KEYPAD
Cursor movement
You can move the cursor when changing function code data by holding down the
key for 1 second or longer in the
same way as with the frequency settings. This action is called "Cursor movement."
Chap. 3
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears. (In this example, IQ is displayed.)
(2) If anything other than IQ is displayed, use the
and
keys to display IQ.
key to proceed to the list of function codes.
(3) Press the
(4) Use the
and
keys to display the desired function code (I in this example), then press the
key.
The data of this function code appears. (In this example, data of I appears.)
and
keys. (In this example, press the
key two times to change data to
(5) Change the function code data using the
.)
(6) Press the
key to establish the function code data.
The VDXH appears and the data will be saved in the memory inside the inverter. The display will return to the function code
list, then move to the next function code. (In this example,I .)
Pressing the
key instead of the
key cancels the change made to the data. The data reverts to the previous value, the
display returns to the function code list, and the original function code reappears.
(7) Press the
key to return to the menu from the function code list.
3.4.4 Monitoring the running status -- Menu #3 "Drive Monitoring" --
Menu #3 "Drive Monitoring" is used to monitor the running status during maintenance and trial running. The display items for
"Drive Monitoring" are listed in Table 3.6. Figure 3.3 shows the menu transition in Menu #3 "Drive Monitoring."
Figure 3.3 Menu Transition in Menu #3 "Drive Monitoring"
Basic key operation
To monitor the running status in "Drive monitoring," set function code E52 to "2" (Full-menu mode) beforehand.
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears. (In this example, IQ is displayed.)
(2) Use the
and
keys to display "Drive Monitoring" (RSH).
(3) Press the
key to proceed to a list of monitoring items (e.g. B).
(4) Use the
and
keys to display the desired monitoring item, then press the
key.
The running status information for the selected item appears.
(5) Press the
key to return to the list of monitoring items. Press the
key again to return to the menu.
3-8
Table 3.6 "Drive Monitoring" Display Items
LED monitor
shows:
Item
Unit
Description
Output frequency
Hz
Output frequency before slip compensation
B
Output frequency
Hz
Output frequency after slip compensation
B
Output current
A
Output current
B
Output voltage
V
Output voltage
B
Calculated torque
%
Calculated output torque of the motor in %
B
Reference frequency
Hz
Frequency specified by a frequency command
B
Rotational direction
N/A
I: forward, U: reverse, : stop
B
Running status
N/A
B
Motor speed
r/min
B
Load shaft speed
PID command value
Rotational direction being outputted
Running status in 4-digit hexadecimal format
Refer to "„ Displaying running status (B ) and running status 2 (B )" on
the next page.
120
Display value = (Output frequency Hz) u
(No. of poles)
If the value is 10000 or lager, the x10 LED turns ON and the LED monitor
shows one-tenth of the value.
r/min
Display value = (Output frequency Hz) u (Function code E50: Coefficient for
speed indication)
If the value is 10000 or lager, the x10 LED turns ON and the LED monitor
shows one-tenth of the value.
N/A
Virtual physical value (e.g., temperature or pressure) of the object to be
controlled, which is converted from the PID command value using function
code E40 and E41 data (PID display coefficients A and B)
Display value = (PID command value) u (Coefficient A - B) + B
If PID control is disabled, "" appears.
B
PID feedback
amount
B
Torque limit value
%
Virtual physical value (e.g., temperature or pressure) of the object to be
controlled, which is converted from the PID feedback amount using function
code E40 and E41 data (PID display coefficients A and B)
Display value = (PID feedback amount) u (Coefficient A - B) + B
If PID control is disabled, "" appears.
Driving torque limit value A (based on motor rated torque)
B
Torque limit value
%
Braking torque limit value B (based on motor rated torque)
B
Ratio setting
B
Line speed
B
(Not used.)
B
(Not used.)
B
(Not used.)
B
(Not used.)
B
(Not used.)
N/A
When this setting is 100%, the LED monitor shows 1.00 time of the value to
be displayed. If no ratio setting is selected, "" appears.
Display value = (Output frequency Hz) u (Function code E50: Coefficient for
speed indication)
m/min
If the value is 10000 or lager, the x10 LED turns ON and the LED monitor
shows one-tenth of the value.
%
B
PID output value
%
B
Flux command value
%
PID output value in %. (100% at the maximum frequency)
If PID control is disabled, "" appears.
Flux command value in %.
Running status 2 in 4-digit hexadecimal format
Refer to "„ Displaying running status (B ) and running status 2 (B)" on
the next page.
B
Running status 2
B
Motor temperature
ºC
B
(Not used.)
B
(Not used.)
B
B
Current position
pulse, 4-multiplied
Position deviation
pulse, 4-multiplied
N/A
Temperature detected by the NTC thermistor built in the motor
If the NTC thermistor connectivity is disabled, "" appears.
pulse
Current position pulse for positioning control (servo lock)
pulse
Position deviation pulse for positioning control (servo lock)
3-9
OPERATION USING THE KEYPAD
B
Chap. 3
B
„ Displaying running status (B ) and running status 2 (B )
To display the running status and running status 2 in 4-digit hexadecimal format, each state has been assigned to bits 0 to 15 as
listed in Tables 3.7 and 3.8. Table 3.9 shows the relationship between each of the status assignments and the LED monitor
display.
Table 3.10 gives the conversion table from 4-bit binary to hexadecimal.
Table 3.7 Running Status (B ) Bit Assignment
Bit
Notation
15
BUSY
14
WR
13
Content
Bit
Notation
"1" when function code data is being
written.
7
VL
Always "0."
6
TL
Content
"1" under voltage limiting control.
"1" under torque limiting control.
Always "0."
5
NUV
"1" when the DC link bus voltage is higher
than the undervoltage level.
"1" when communication is enabled (when
ready for run and frequency commands via
communications link).
4
BRK
"1" during braking.
3
INT
"1" when the inverter output is shut down.
12
RL
11
ALM
"1" when an alarm has occurred.
10
DEC
"1" during deceleration.
2
EXT
"1" during DC braking.
9
ACC
"1" during acceleration.
1
REV
"1" during running in the reverse direction.
8
IL
"1" under current limiting control.
0
FWD
"1" during running in the forward direction.
Table 3.8 Running Status 2 (B ) Bit Assignment
Bit
Notation
Content
Bit
Notation
15
7
Speed limiting (under torque control)
14
6
(Not used.)
13
5
12
4
Motor selection
00: Motor 1
01: Motor 2
10: Motor 3
11: Motor 4
11
3
10
2
9
1
0
(Not used.)
8
Content
Inverter drive control
0000: V/f control with slip compensation
inactive
0001: Dynamic torque vector control
0010: V/f control with slip compensation
active
0011: V/f control with speed sensor
0100: Dynamic vector control with
speed sensor
0101: Vector control without speed sensor
0110: Vector control with speed sensor
1010: Torque control
(Vector control without speed
sensor)
1011: Torque control
(Vector control with speed sensor)
Table 3.9 Running Status Display
LED No.
Bit
Notation
Example
Binary
LED4
15
14
13
BUSY WR
1
0
LED3
12
RL
0
11
10
9
ALM DEC ACC
0
0
0
1
Hexadecimal on
the LED
monitor
LED2
8
7
IL
VL
1
0
6
5
4
3
2
1
0
TL NUV BRK INT EXT REV FWD
0
1
3-10
LED1
0
0
0
0
1
„ Hexadecimal expression
A 4-bit binary number can be expressed in hexadecimal (1 hexadecimal digit). Table 3.10 shows the correspondence between
the two notations. The hexadecimals are shown as they appear on the LED monitor.
Table 3.10 Binary and Hexadecimal Conversion
Binary
Hexadecimal
Binary
Hexadecimal
0
0
1
0
0
0
0
0
0
1
1
0
0
1
0
0
1
0
1
0
1
0
D
0
0
1
1
1
0
1
1
E
0
1
0
0
1
1
0
0
F
0
1
0
1
1
1
0
1
G
0
1
1
0
1
1
1
0
H
0
1
1
1
1
1
1
1
I
3.4.5 Checking I/O signal status -- Menu #4 "I/O Checking" --
Using Menu #4 "I/O Checking" displays the I/O status of external signals including digital and analog I/O signals without using
a measuring instrument. Table 3.11 lists check items available. The menu transition in Menu #4 "I/O Checking" is shown in
Figure 3.4.
Figure 3.4 Menu Transition in Menu #4 "I/O Checking"
3-11
OPERATION USING THE KEYPAD
0
Chap. 3
0
Basic key operation
To check the status of the I/O signals, set function code E52 to "2" (Full-menu mode) beforehand.
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears.
(2) Use the
and
keys to display "I/O Checking" (LBR).
(3) Press the
key to proceed to a list of I/O check items (e.g. B).
(4) Use the
and
keys to display the desired I/O check item, then press the
key.
The corresponding I/O check data appears. For the item B or B, using the
and
keys switches the display
method between the segment display (for external signal information in Table 3.12) and hexadecimal display (for I/O signal
status in Table 3.13).
(5) Press the
key to return to the list of I/O check items. Press the
key again to return to the menu.
Table 3.11 I/O Check Items
LED monitor
shows:
Item
Description
B
I/O signals on the control circuit
terminals
Shows the ON/OFF state of the digital I/O terminals. Refer to
"„ Displaying control I/O signal terminals" on the next page for
details.
B
I/O signals on the control circuit
terminals under communications
control
Shows the ON/OFF state of the digital I/O terminals that received a
command via RS-485 and optional communications. Refer to
"„ Displaying control I/O signal terminals" and
"„ Displaying control I/O signal terminals under communications
control" on the following pages for details.
B
Input voltage on terminal [12]
Shows the input voltage on terminal [12] in volts (V).
B
Input current on terminal [C1]
Shows the input current on terminal [C1] in milliamperes (mA).
B
Output voltage on terminal [FM1]
Shows the output voltage on terminal [FM1] in volts (V).
B
Output voltage on terminal [FM2]
Shows the output voltage on terminal [FM2] in volts (V).
B
Input voltage on terminal [V2]
Shows the input voltage on terminal [V2] in volts (V).
B
Output current on terminal [FM1]
Shows the output current on terminal [FM1] in milliamperes (mA).
B
Output current on terminal [FM2]
Shows the output current on terminal [FM2] in milliamperes (mA).
B
Shows the ON/OFF state of the digital I/O terminals on the digital input
Option control circuit terminal
and output interface cards (options). Refer to "„ Displaying control I/O
(I/O)
signal terminals on options" on page 3-14 for details.
B
Terminal [X7] pulse input monitor
Shows the pulse rate of the pulse train signal on terminal [X7].
B
PG pulse rate
(A/B phase signal from the
reference PG)
Shows the pulse rate (p/s) of the A/B phase signal fed back from the
reference PG.
B
PG pulse rate
(Z phase signal from the reference
PG)
Shows the pulse rate (p/s) of the Z phase signal fed back from the
reference PG.
B
PG pulse rate
(A/B phase signal from the slave
PG)
Shows the pulse rate (p/s) of the A/B phase signal fed back from the
slave PG.
B
PG pulse rate
(Z phase signal from the slave PG)
Shows the pulse rate (p/s) of the Z phase signal fed back from the slave
PG.
B
(Not used.)
B
Input voltage on terminal [32]
Shows the input voltage on terminal [32] on the analog interface card
(option) in volts (V).
B
Input current on terminal [C2]
Shows the input current on terminal [C2] on the analog interface card
(option) in milliamperes (mA).
B
Output voltage on terminal [AO]
Shows the output voltage on terminal [AO] on the analog interface card
(option) in volts (V).
B
Output current on terminal [CS]
Shows the output current on terminal [CS] on the analog interface card
(option) in milliamperes (mA).
B
Customizable logic timer monitor
Monitors the timer or counter value in the customizable logic
specified by U91.
3-12
„ Displaying control I/O signal terminals
The status of control I/O signal terminals may be displayed with ON/OFF of the LED segment or in hexadecimal.
• Displaying the I/O signal status with ON/OFF of each LED segment
If all terminal signals are OFF (open), segments "g" on all of LED1 to LED4 will light ("– – – –").
OPERATION USING THE KEYPAD
Table 3.12 Segment Display for External Signal Information
Segment
LED4
LED3
LED2
LED1
a
30A/B/C
Y1-CMY
X7
FWD
b
Y2-CMY
REV
c
Y3-CMY
X1
d
Y4-CMY
EN
X2
e
Y5A-Y5C
X3
f
(XF) *
X4
g
(XR) *
X5
dp
(RST) *
X6
—: No corresponding control circuit terminal exists
* (XF), (XR), and (RST) are assigned for communications control. Refer to "„ Displaying control I/O signal terminals under
communications control" on the next page.
• Displaying I/O signal status in hexadecimal
Each I/O terminal is assigned to bit 15 through bit 0 as shown in Table 3.13. An unassigned bit is interpreted as "0." Allocated
bit data is displayed on the LED monitor as four hexadecimal digits ( to I each).
On the JAGUAR VXG, digital input terminals [FWD] and [REV] are assigned to bits 0 and 1, respectively. Terminals [X1]
through [X7] are assigned to bits 2 through 10. The bit is set to "1" when the corresponding input terminal is short-circuited
(ON), and it is set to "0" when the terminal is open (OFF). For example, when [FWD] and [X1] are ON (short-circuited) and all
the others are OFF (open), is displayed on LED4 to LED1.
Digital output terminals [Y1] through [Y4] are assigned to bits 0 through 3. Each bit is set to "1" when the output terminal [Y1],
[Y2], [Y3] or [Y4] is short-circuited with [CMY] (ON), and "0" when it is open (OFF).
The status of the relay contact output terminal [Y5A/C] is assigned to bit 4. It is set to "1" when the circuit between output
terminals [Y5A] and [Y5C] is closed. The status of the relay contact output terminals [30A/B/C] is assigned to bit 8. It is set to
"1" when the circuit between output terminals [30A] and [30C] is closed, and "0" when the circuit between [30A] and [30C] is
open.
For example, if [Y1] is ON, [Y2] through [Y4] are OFF, the circuit between [Y5A] and [Y5C] is open, and the circuit between
[30A] and [30C] is closed, then " " is displayed on the LED4 through LED1.
Table 3.13 presents bit assignment and an example of corresponding hexadecimal display on the 7-segment LED.
Table 3.13 Segment Display for I/O Signal Status in Hexadecimal (Example)
LED No.
Bit
LED4
15
14
LED3
13
Input terminal (RST)* (XR)* (XF)*
Output terminal
Example
Binary
12
11
10
9
-
EN
-
LED2
LED1
8
7
6
5
4
3
2
-
X7
X6
X5
X4
X3
X2
X1
-
-
-
Y5A/C Y4
Y3
Y2
Y1
0
0
0
1
0
1
-
-
-
-
-
-
-
30A/
B/C
0
0
0
0
0
0
0
0
0
0
1
0
REV FWD
Hexadecimal on
the LED
monitor
– No corresponding control circuit terminal exists.
* (XF), (XR), and (RST) are assigned for communications control. Refer to "„ Displaying control I/O signal terminals under
communications control" on the next page.
3-13
Chap. 3
As shown in Table 3.12 and the figure below, each of segments "a" to "dp" on LED1 and LED2 lights when the corresponding
digital input terminal circuit ([FWD], [REV], [X1] to [X7]) is closed; it goes OFF when it is open. Each of segments "a" to "e"
on LED3 lights when the circuit between output terminal [Y1], [Y2], [Y3] or [Y4] and terminal [CMY] or between terminals
[Y5A] and [Y5C] is closed, respectively; it goes OFF when the circuit is open. Segment "a" on LED4 is for terminals
[30A/B/C] and lights when the circuit between terminals [30C] and [30A] is short-circuited (ON) and goes OFF when it is
open.
„ Displaying control I/O signal terminals under communications control
Under communications control, input commands (function code S06) sent via RS-485 or other optional communications can be
displayed in two ways: "with ON/OFF of each LED segment" and "in hexadecimal." The content to be displayed is basically the
same as that for the control I/O signal terminal status display; however, (XF), (XR), and (RST) are added as inputs. Note that
under communications control, the I/O display is in normal logic (using the original signals not inverted)
For details about input commands sent through the communications link, refer to the RS-485 Communication User's
Manual and the instruction manual of communication-related options as well.
„ Displaying control I/O signal terminals on options
The LED monitor can also show the signal status of the terminals on the optional digital input and output interface cards, just
like the signal status of the control circuit terminals.
Table 3.14 lists the assignment of digital I/O signals to the LED segments.
Table 3.14 Segment Display for External Signal Information
LED No.
Segment
LED4
LED3
LED2
LED1
a
O1
I9
I1
b
O2
I10
I2
c
O3
I11
I3
d
O4
I12
I4
e
O5
I13
I5
f
O6
I14
I6
g
O7
I15
I7
dp
O8
I16
I8
LED4
LED3
LED2
15
14
13
12
11
10
9
8
Input terminal
I16
I15
I14
I13
I12
I11
I10
I9
I8
I7
I6
I5
I4
I3
I2
I1
-
-
-
-
-
-
-
-
O8
O7
O6
O5
O4
O3
O2
O1
Output terminal
7
6
5
LED1
Bit
4
3
2
1
0
3.4.6 Reading maintenance information -- Menu #5 "Maintenance Information" --
Menu #5 "Maintenance Information" (FKH) contains information necessary for performing maintenance on the inverter. The
menu transition in Menu #5 "Maintenance Information" is just like that in Menu #3 "Drive Monitoring." (Refer to Section
3.4.4.)
Basic key operation
To view the maintenance information, set function code E52 to "2" (Full-menu mode) beforehand.
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears.
(2) Use the
and
keys to display "Maintenance Information" (FKH).
(3) Press the
key to proceed to the list of maintenance items (e.g. B).
and
keys to display the desired maintenance item, then press the
key.
(4) Use the
The data of the corresponding maintenance item appears.
(5) Press the
key to return to the list of maintenance items. Press the
key again to return to the menu.
3-14
Table 3.15 Display Items in "Maintenance Information"
LED Monitor
shows:
Item
Description
B
DC link bus voltage
Shows the DC link bus voltage of the inverter main circuit.
Unit: V (volts)
B
Max. temperature inside the
inverter
Shows the maximum temperature inside the inverter for every hour.
Unit: qC (Temperatures below 20qC are displayed as 20qC.)
B
Max. temperature of heat sink
Shows the maximum temperature of the heat sink for every hour.
Unit: qC (Temperatures below 20qC are displayed as 20qC.)
B
Max. effective output current
Shows the maximum current in RMS for every hour.
Unit: A (amperes)
B
Capacitance of the DC link bus
capacitor
Shows the current capacitance of the DC link bus capacitor (reservoir
capacitor) in %, based on the capacitance when shipping as 100%. Refer
to Chapter 7 "MAINTENANCE AND INSPECTION" for details.
Unit: %
B
Cumulative run time of
electrolytic
capacitors on the printed circuit
boards
Shows the content of the cumulative run time counter of the electrolytic
capacitors on the printed circuit boards, which is calculated by
multiplying the cumulative run time count by the coefficient based on the
surrounding temperature condition.
Counter range: 0 to 99,990 hours
Display range: to The x10 LED turns ON.
Actual cumulative run time of electrolytic capacitors on
the printed circuit boards (hours) = Displayed value x 10
When the count exceeds 99,990 the counter stops and the LED monitor
sticks to .
B
Cumulative run time of the
cooling fan
Shows the content of the cumulative run time counter of the cooling fan.
This counter does not work when the cooling fan ON/OFF control
(function code H06) is enabled and the fan stops.
The display method is the same as for Babove.
Number of startups
Shows the content of the motor 1 startup counter (i.e., the number of run
commands issued).
Counter range: 0 to 65,530 times
Display range: to If the count exceeds 10,000, the x10 LED turns ON and
the LED monitor shows one-tenth of the value.
When the count exceeds 65,530, the counter will be reset to "0" and start
over again.
Input watt-hour
Shows the input watt-hour of the inverter.
Display range: to Input watt-hour = Displayed value u 100 kWh
To reset the integrated input watt-hour and its data, set function code E51
to "0.000." When the input watt-hour exceeds 999,900 kWh, the counter
will be reset to "0."
Input watt-hour data
Shows the value expressed by "input watt-hour (kWh) × E51 (whose data
range is 0.000 to 9,999)."
Unit: None.(Display range: to . The data cannot exceed 9999.
(It will be fixed at 9,999 once the calculated value exceeds 9999.))
Depending on the value of integrated input watt-hour data, the decimal
point on the LED monitor shifts to show it within the LED monitors’
resolution.
To reset the integrated input watt-hour data, set function code E51 to
"0.000."
B
B
B
3-15
OPERATION USING THE KEYPAD
Cumulative run time
Chap. 3
B
Shows the content of the cumulative power-ON time counter of the
inverter.
Counter range: 0 to 65,535 hours
Display: Upper 2 digits and lower 3 digits are displayed alternately.
œ K (535 hours)
Example:
œ K (65,535 hours)
The lower 3 digits are displayed with K (hour).
When the count exceeds 65,535, the counter will be reset to "0" and start
over again.
Table 3.15 Display Items in "Maintenance Information" (Continued)
LED Monitor
shows:
Item
Description
B
Number of RS-485
communications errors
(COM port 1)
Shows the total number of errors that have occurred in RS-485
communication (COM port 1, connection to keypad) after the power is
turned ON.
Once the count exceeds 9999, the counter will be reset to "0."
B
Content of RS-485
communications error
(COM port 1)
Shows the latest error that has occurred in RS-485 communication (COM
port 1) in decimal.
For error contents, refer to the RS-485 Communication User’s Manual.
B
Number of option errors 1
Shows the total number of errors that have occurred in the option being
connected to the A-port. Once the count exceeds 9999, the counter will be
reset to "0."
B
Inverter's ROM version
Shows the inverter's ROM version as a 4-digit code.
B
Keypad's ROM
version
Shows the keypad's ROM version as a 4-digit code.
B
Number of RS-485
communications errors
(COM port 2)
Shows the total number of errors that have occurred in RS-485
communication (COM port 2, connection to terminal block) after the
power is turned ON.
Once the count exceeds 9999, the counter will be reset to "0."
B
Content of RS-485
communications error
(COM port 2)
Shows the latest error that has occurred in RS-485 communication (COM
port 2, connection to terminal block) in decimal.
For error contents, refer to the RS-485 Communication User’s Manual.
B
Option's ROM version 1
Shows the ROM version of the option to be connected to A-port as a
4-digit code.
If the option has no ROM, "" appears on the LED monitor.
B
Option's ROM version 2
Shows the ROM version of the option to be connected to B-port as a
4-digit code.
If the option has no ROM, "" appears on the LED monitor.
B
Option's ROM version 3
Shows the ROM version of the option to be connected to C-port as a
4-digit code.
If the option has no ROM, "" appears on the LED monitor.
Shows the content of the cumulative power-ON time counter of motor 1.
Counter range: 0 to 99,990 hours
The x10 LED turns ON.
Display range: to Actual cumulative motor run time (hours) = Displayed
value x 10
When the count exceeds 99,990, the counter will be reset to "0" and start
over again.
B
Cumulative run time of motor 1
B
Temperature inside the inverter
(real-time value)
Shows the current temperature inside the inverter.
Unit: qC
B
Temperature of heat sink
(real-time value)
Shows the current temperature of the heat sink inside the inverter.
Unit: qC
B
Shows the cumulative time during which a voltage is applied to the DC
link bus capacitor.
Lifetime of DC link bus capacitor When the main power is shut down, the inverter automatically measures
the discharging time of the DC link bus capacitor and corrects the elapsed
(elapsed hours)
time.
The display method is the same as for Babove.
B
Shows the remaining lifetime of the DC link bus capacitor, which is
Lifetime of DC link bus capacitor estimated by subtracting the elapsed time from the lifetime (10 years).
(remaining hours)
The display method is the same as for Babove.
B
Cumulative run time of motor 2
Shows the content of the cumulative power-ON time counter of motor 2.
The display method is the same as for Babove.
B
Cumulative run time of motor 3
Shows the content of the cumulative power-ON time counter of motor 3.
The display method is the same as for Babove.
3-16
Table 3.15 Display Items in "Maintenance Information" (Continued)
LED Monitor
shows:
Item
Description
B
Remaining time before the next
motor 1 maintenance
Shows the time remaining before the next maintenance, which is
estimated by subtracting the cumulative run time of motor 1 from the
maintenance interval specified by H78. (This function applies to motor 1
only.)
The x10 LED turns ON.
Display range: to Time remaining before the next maintenance (hour) =
Displayed value u 10
B
Number of startups 2
Shows the content of the motor 2 startup counter (i.e., the number of run
commands issued).
The display method is the same as for Babove.
B
Number of startups 3
Shows the content of the motor 3 startup counter (i.e., the number of run
commands issued).
The display method is the same as for Babove.
B
Number of startups 4
Shows the content of the motor 4 startup counter (i.e., the number of run
commands issued).
The display method is the same as for Babove.
B
Remaining startup times before
the next maintenance 1
Shows the startup times remaining before the next maintenance, which is
estimated by subtracting the number of startups from the preset startup
count for maintenance specified by H79. (This function applies to motor 1
only.)
The display method is the same as for Babove.
B
Light alarm factor (Latest)
Shows the factor of the latest light alarm as an alarm code.
For details, refer to Chapter 6, Section 6.1 "Protective Functions."
B
Light alarm factor (Last)
Shows the factor of the last light alarm as an alarm code.
For details, refer to Chapter 6, Section 6.1 "Protective Functions."
B
Light alarm factor (2nd last)
Shows the factor of the 2nd last light alarm as an alarm code.
For details, refer to Chapter 6, Section 6.1 "Protective Functions."
B
Light alarm factor (3rd last)
Shows the factor of the 3rd last light alarm as an alarm code.
For details, refer to Chapter 6, Section 6.1 "Protective Functions."
B
Option error factor 1
Shows the factor of the error that has occurred in the option being
connected to the A-port.
B
Number of option errors 2
Shows the total number of errors that have occurred in the option being
connected to the B-port.
Once the count exceeds 9999, the counter will be reset to "0."
B
Option error factor 2
Shows the factor of the error that has occurred in the option being
connected to the B-port.
B
Number of option errors 3
Shows the total number of errors that have occurred in the option being
connected to the C-port.
Once the count exceeds 9999, the counter will be reset to "0."
B
Option error factor 3
Shows the factor of the error that has occurred in the option being
connected to the C-port.
3-17
OPERATION USING THE KEYPAD
Shows the content of the cumulative power-ON time counter of motor 4.
The display method is the same as for Babove.
Chap. 3
Cumulative run time of motor 4
B
3.4.7 Reading alarm information -- Menu #6 "Alarm Information" --
Menu #6 "Alarm Information" shows the causes of the past 4 alarms in alarm code. Further, it is also possible to display alarm
information that indicates the status of the inverter when the alarm occurred. Figure 3.5 shows the menu transition in Menu #6
"Alarm Information" and Table 3.16 lists the details of the alarm information.
Figure 3.5 Menu Transition in Menu #6 "Alarm Information"
Basic key operation
To view the alarm information, set function code E52 to "2" (Full-menu mode) beforehand.
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears.
and
keys to display "Alarm Information" (DO).
(2) Use the
(3) Press the
key to proceed to a list of alarm codes (e.g. O).
In the list of alarm codes, the alarm information for the last 4 alarms is saved as an alarm history.
(4) Each time the
or
key is pressed, the last 4 alarms are displayed beginning with the most recent one in the order of ,
, and (5) Press the
key with an alarm code being displayed.
The item number (e.g. B) and the inverter status information (e.g. Output frequency) at the time of the alarm occurrence
alternately appear at approx. 1-second intervals.
Pressing the
and
keys displays other item numbers (e.g. B) and the status information (e.g. Output current) for
that alarm code.
(6) Press the
key to return to the list of alarm codes. Press the
key again to return to the menu.
3-18
Table 3.16 Display Items in "Alarm Information"
LED monitor
shows:
(item No.)
Item
Description
Output frequency before slip compensation
B
Output current
Output current
B
Output voltage
Output voltage
B
Calculated torque
Calculated motor output torque
B
Reference frequency
Frequency specified by frequency command
B
Rotational direction
Shows the rotational direction currently specified.
I: forward, U: reverse, : stop
B
Running status
Running status as four hexadecimal digits.
Refer to "„ Displaying running status (B ) and running status 2 (B )"
in Section 3.4.4.
Cumulative run time
Shows the content of the cumulative power-ON time counter of the
inverter.
Counter range: 0 to 65,535 hours
Display: Upper 2 digits and lower 3 digits are displayed alternately.
œ K (535 hours)
Example:
œ K (65,535 hours)
The lower 3 digits are displayed with K (hour).
When the count exceeds 65,535, the counter will be reset to "0" and start
over again.
B
No. of startups
Shows the content of the motor startup counter (i.e., the number of run
commands issued).
Counter range: 0 to 65,530 times
Display range: to If the count exceeds 10,000, the x10 LED turns ON and
the LED monitor shows one-tenth of the value.
When the count exceeds 65,530, the counter will be reset to "0" and start
over again.
B
DC link bus voltage
Shows the DC link bus voltage of the inverter main circuit.
Unit: V (volts)
B
Temperature inside the inverter
Shows the temperature inside the inverter.
Unit: qC
B
Max. temperature of heat sink
Shows the temperature of the heat sink.
Unit: qC
B
Terminal I/O signal status
(displayed with the ON/OFF of
LED segments)
B
Terminal input signal status
(in hexadecimal)
B
Terminal output signal status
(in hexadecimal)
B
No. of consecutive occurrences
Shows the number of times the same alarm occurs consecutively.
B
Multiple alarm 1
Simultaneously occurring alarm code (1)
("" is displayed if no alarm has occurred.)
B
Multiple alarm 2
Simultaneously occurring alarm code (2)
("" is displayed if no alarm has occurred.)
B
Terminal I/O signal status under
communications control
(displayed with the ON/OFF of
LED segments)
B
B
Shows the ON/OFF state of the digital I/O terminals. Refer to
"„ Displaying control I/O signal terminals" in Section 3.4.5 "Checking
I/O signal status" for details.
Shows the ON/OFF state of the digital I/O terminals under RS-485
Terminal input signal status under communications control. Refer to "„ Displaying control I/O signal
communications control
terminals under communications control" in Section 3.4.5 "Checking I/O
(in hexadecimal)
signal status" for details.
B
Terminal output signal status
under communications control
(in hexadecimal)
B
Error sub code
Secondary error code for the alarm.
3-19
OPERATION USING THE KEYPAD
Output frequency
Chap. 3
B
Table 3.16 Display Items in "Alarm Information" (Continued)
LED monitor
shows:
(item No.)
Item
Description
B
Running status 2
Running status 2 as four hexadecimal digits.
Refer to "„ Displaying running status (B ) and running status 2
(B )" in Section 3.4.4.
B
Speed detected value
Speed detected value.
When the same alarm occurs repeatedly in succession, the alarm information for the first and the most recent
occurrences will be preserved and the information for other occurrences in-between will be discarded. The number of
consecutive occurrences will be preserved as the first alarm information.
3.4.8 Copying data -- Menu #7 "Data Copying" --
Menu #7 "Data Copying" is used to read function code data out of an inverter for storing it in the keypad or writing it into
another inverter. It is also used to verify the function code data stored in the keypad with the one configured in the inverter. The
keypad serves as a temporary storage media.
In addition, using Menu #7 allows you to store the running status information in the keypad, detach the keypad from the inverter,
connect it to a PC running JAGUAR Loader at an office or off-site place, and check the inverter running status without
removing the inverter itself.
To store the inverter running status information into the keypad, use "Read data" (UHDG ) or "Read inverter running information"
(FKHF ) function. For details on how to connect the keypad to a PC and check the inverter running status information stored in
the keypad, refer to the JAGUAR Loader Instruction Manual.
Figure 3.6 shows the menu transition in Menu #7 "Data Copying." The keypad can hold function code data for a single inverter.
Figure 3.6 Menu Transition in Menu #7 "Data Copying"
3-20
Basic keying operation
Table 3.17 List of Data Copying Functions
Display on
LED Monitor
Function
Description
UHDG
Read data
Reads the function code data out of the inverter’s memory and stores it into the keypad
memory.
Also reads out inverter’s current running status information which can be checked by
JAGUAR Loader, such as information of I/O, system, alarm, and running status.
Pressing the
key during a read operation (when UHDGis blinking) immediately aborts the
operation and displays HUU (blinking).
If this happens, the entire contents of the memory of the keypad will be completely cleared.
FRS\
Write data
Writes data stored in the keypad memory into the inverter’s memory.
key during a write operation (when FRS\ is blinking), the write operation
If you press the
that is under way will be aborted and HUUwill appear (blinking). If this happens, the contents
of the inverter’s memory (i.e., function code data) have been partly updated and remain partly
old. Therefore, do not operate the inverter. Instead, perform initialization or rewrite the entire
data.
If this function does not work, refer to "„ If data copying does not work" on page 3-22.
XHUL
Verify data
Verifies (collates) the data stored in the keypad memory with that in the inverter's memory.
If any mismatch is detected, the verify operation will be aborted, with the function code in
disagreement displayed blinking. Pressing the
key again causes the verification to continue
from the next function code.
key during a verify operation (when XHULis blinking) immediately aborts the
Pressing the
operation and displays HUU(blinking).
HUUappears blinking also when the keypad does not contain any valid data.
SUR7
Enable Data
protection
Enables the Data protection of data stored in the keypad’s memory.
In this state, you cannot read any data stored in the inverter’s memory, but can write data into
the memory and verify data in the memory.
key the inverter immediately displays HUU.
Upon pressing the
FKHF
Read inverter Reads out inverter’s current running status information that can be checked by JAGUAR
running
Loader, such as information of I/O, system, alarm, and running status, excluding function
information
code data.
Use this command when the function code data saved in the PC should not be overwritten and
it is necessary to keep the previous data.
Pressing the
key during a read operation (FKHF blinking) immediately aborts the operation
and displays HUU (blinking).
To get out of the error state indicated by a blinking HUU or FSHU, press the
3-21
key.
OPERATION USING THE KEYPAD
Table 3.17 below lists details of the data copying functions.
Chap. 3
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears.
and
keys to display "Data Copying" (
FS\).
(2) Use the
(3) Press the
key to proceed to the list of data copying functions (e.g. UHDG).
(4) Use the
and
keys to select the desired function, then press the
key to execute the selected function. (e.g. UHDG
will blink.)
(5) When the selected function has been completed, HQGappears. Press the
key to return to the list of data copying functions.
key again to return to the menu.
Press the
„ Data
protection
You can protect data saved in the keypad from unexpected modifications. Enabling the data protection that was disabled
changes the display UHDG on the "Data Copying" function list to SUR7, and disables to read data from the inverter.
To enable or disable the data protection, follow the next steps.
(1) Select the "Data Copying" (FS\ ) on the function selection menu in Programming mode.
key down for at least 5 seconds alternates data protection status between
(2) When the FS\ is displayed, holding the
enabled or disabled.
For switching the data protection status, be sure to hold the
key down for at least 5 seconds. Once the key is
key to go back to the FS\display and perform the keying operation again.
released within 5 seconds, press the
• Enabling the disabled data protection
Hold
key down
for at least 5 seconds.
㻓 㼏㼜㼥
(Displayed item changes.)
㼞 㼑㼍㼐
While FS\ is displayed, holding down the
SUR7 , enabling the data protection.
䋻
㼜㼞 㼛㼀
key for at least 5 seconds shows UHDG for 5 seconds and then switches to
• Disabling the enabled data protection
Hold
key down
for at least 5 seconds.
㻓 㼏㼜㼥
While FS\ is displayed, holding down the
disabling the data protection.
(Displayed item changes.)
㼜㼞 㼛㼀 䋻 㼞 㼑㼍㼐
key for at least 5 seconds shows SUR7 for 5 seconds and then switches to UHDG,
The followings are restrictions and special notes concerning "Data Copying."
„ If data copying does not work
Check whether HUUor FSHUis blinking.
(1) If HUU is blinking (a write error), any of the following problems has arisen:
• No data exists in the keypad memory. (No data read operation has been performed since shipment, or a data read
operation has been aborted.)
• Data stored in the keypad memory contains any error.
• The models of copy source and destination inverters are different.
• A data write operation has been performed while the inverter is running.
• The copy destination inverter is data-protected. (function code F00 = 1)
• In the copy destination inverter, the "Enable write from keypad" command WE-KP is OFF.
• A data read operation has been performed for the inverter whose data protection was enabled.
(2) If FSHU is blinking, any of the following problems has arisen:
• The function codes stored in the keypad and ones registered in the inverter are not compatible with each other. (Either of
the two may have been revised or upgraded in a non-standard or incompatible manner. Consult your IMO representative.)
3-22
3.5 Alarm Mode
If an abnormal condition arises, the protective function is invoked and issues an alarm, then the inverter automatically enters
Alarm mode. At the same time, an alarm code appears on the LED monitor.
„ Releasing the alarm and switching to Running mode
„ Displaying the alarm history
„ Displaying the status of inverter at the time of alarm
When the alarm code is displayed, you may check various running status information (output frequency and output current,
etc.) by pressing the
key. The item number and data for each running information will be displayed alternately.
Further, you can view various pieces of information on the running status of the inverter using the
/
key. The information
displayed is the same as for Menu #6 "Alarm Information" in Programming mode. Refer to Table 3.16 in Section 3.4.7,
"Reading alarm information."
Pressing the
key while the running status information is displayed returns to the alarm code display.
When the running status information is displayed after removal of the alarm cause, pressing the
key twice returns
㻌 to the alarm code display and releases the inverter from the alarm state. This means that the motor starts running if a
run command has been received by this time.
„ Switching to Programming mode
You can also switch to Programming mode by pressing "
the function code data.
+
keys" simultaneously with the alarm displayed, and modify
Figure 3.7 summarizes the possible transitions between different menu items.
Figure 3.7 Menu Transition in Alarm Mode
3-23
OPERATION USING THE KEYPAD
It is possible to display the most recent 3 alarm codes in addition to the one currently displayed. Previous alarm codes can be
displayed by pressing the
/
key while the current alarm code is displayed.
Chap. 3
Remove the cause of the alarm and press the
key to release the alarm and return to Running mode. The alarm can be
key only when the alarm code is displayed.
removed using the
3.6 USB Connectivity
The keypad has a USB port (mini B connector) on its face. To connect a USB cable, open the USB port cover as shown below.
Connecting the inverter to a PC with a USB cable enables remote control from IMO Loader. On the PC running IMO Loader, it
is possible to edit, check, manage, and monitor the function code data in real-time, to start or stop the inverter, and to monitor
the running or alarm status of the inverter.
For the instructions on how to use the IMO Loader, refer to the IMO Loader Instruction Manual.
In addition, using the keypad as a temporary storage media allows you to store the running status information in the keypad,
detach the keypad from the inverter, connect it to a PC running IMO Loader at an office or off-site place.
For details on how to store data into the keypad, refer to Section 3.4.8 "Copying data."
3-24
Chapter 4 RUNNING THE MOTOR
4.1 Running the Motor for a Test
4.1.1 Test run procedure
Make a test run of the motor using the flowchart given below.
This chapter describes the test run procedure with motor 1 dedicated function codes that are marked with an asterisk (*). For
motors 2 to 4, replace those asterisked function codes with respective motor dedicated ones. (Refer to Chapter 5, Table 5.5.)
For the function codes dedicated to motors 2 to 4, see Chapter 5 "FUNCTION CODES."
Chap. 4
RUNNING THE MOTOR
Figure 4.1 Test Run Procedure
4.1.2 Checking prior to powering on
Check the following before powering on the inverter.
(1) Check that the wiring is correct.
Especially check the wiring to the inverter input terminals L1/R, L2/S and L3/T and output terminals U, V, and W. Also
check that the grounding wires are connected to the grounding terminals ( G) correctly. See Figure 4.2.
• Never connect power supply wires to the inverter output terminals U, V, and W. Doing so and turning the power ON breaks
the inverter.
• Be sure to connect the grounding wires of the inverter and the motor to the ground electrodes.
Otherwise, an electric shock could occur.
(2) Check the control circuit terminals and main circuit terminals for short circuits or ground faults.
4-1
(3) Check for loose terminals, connectors and screws.
(4) Check that the motor is separated from mechanical equipment.
(5) Make sure that all switches of devices connected to the inverter
are turned OFF. Powering on the inverter with any of those
switches being ON may cause an unexpected motor operation.
(6) Check that safety measures are taken against runaway of the
equipment, e.g., a defense to prevent people from access to the
equipment.
Figure 4.2 Connection of Main Circuit Terminals
4.1.3 Powering ON and checking
• Be sure to mount the front cover before turning the power ON. Do not remove the cover when the inverter power is ON.
• Do not operate switches with wet hands.
Otherwise, an electric shock could occur.
Turn the power ON and check the following points. The following
is a case when no function code data is changed from the factory
defaults.
(1) Check that the LED monitor displays (indicating that the
reference frequency is 0 Hz) that is blinking. (See Figure 4.3.)
If the LED monitor displays any number except , press
/
key to set .
(2) Check that the built-in cooling fans rotate.
(Inverters with a capacity of 1.5 kW or below are not equipped
with a cooling fan.)
Figure 4.3
Display of the LED Monitor after Power-on
4.1.4 Switching between CT, MT and VT drive modes
The JAGUAR VXG series of inverters is applicable to three ratings--high duty (CT) for heavy load applications, medium duty
(MT) for medium load ones, and low duty (VT) for light load ones. (The MT mode is available for three phase 400 V class
series of inverters with a capacity of 90 kW or above.)
Continuous rated current level
Overload
capability
Maximum
frequency
Constant
Torque
Capable of driving a motor whose capacity is the
same as the inverter's one.
150% for 1 min.
200% for 3 s
500 Hz
MT (Medium
Duty) mode
Medium
Torque
Capable of driving a motor whose capacity is one
rank higher than the inverter's one.
150% for 1 min.
120 Hz
VT (Low Duty)
mode
Variable
Torque
Capable of driving a motor whose capacity is one
or two ranks higher than the inverter's one.
120% for 1 min.
120 Hz
F80
data
Drive mode
0
CT (High Duty)
mode
2
1
Application
The MT-/VT-mode inverter brings out the continuous rated current level which enables the inverter to drive a motor with one or
two ranks higher capacity, but its overload capability (%) against the continuous current level decreases. For the rated current
level, see Chapter 8 "SPECIFICATIONS."
Some versions of the optional multi-function keypad (OP-KP-LCD) do not display the content of the function code F80
when the data is "2," so "2: ---" appears instead of "2: Medium T." However, the function code data can be configured
normally.
4-2
The MT-/VT-mode inverter is subject to restrictions on the function code data setting range and internal processing as listed
below.
Function
codes
F21*
F26
CT mode
Name
Setting range:
0 to 100%
Motor sound
(Carrier
frequency)
Setting range:
0.75 to 16 kHz
(0.4 to 55 kW)
0.75 to 10 kHz
(75 to 400 kW)
Setting range:
0.75 to 16 kHz
(5.5 to 18.5 kW)
Setting range:
0.75 to 2 kHz
(90 to 400 kW)
F03*
Maximum
frequency
Current
indication and
output
0.75 to 10 kHz
(22 to 55 kW)
0.75 to 6 kHz
(75 to 500 kW)
0.75 to 4 kHz
(630 kW)
In the MT/VT mode, a value out
of the range, if specified,
automatically changes to the
maximum value allowable in the
VT mode.
Switching the drive mode
between CT, MT and VT with
Initial value: 160% Initial value: 145% Initial value: 130% function code F80 automatically
initializes the F44 data to the
value specified at left.
In the MT/VT mode, if the
Setting range:
maximum frequency exceeds
25 to 500 Hz
Setting range: 25 to 500 Hz
120 Hz, the actual output
Upper
limit:
120
Hz
Upper limit:
frequency is internally limited to
500 Hz
120 Hz.
Based on the rated Based on the rated Based on the rated
current level for
current level for
current level for
VT mode
MT mode
CT mode
Switching to the MT/VT mode does not automatically change the motor rated capacity (P02*) to the one for the motor with one
rank higher capacity, so configure the P02* data to match the applied motor rating as required.
4.1.5 Selecting a desired motor drive control
The JAGUAR VXG supports the following motor drive control.
F42*
data
0
1
2
3
4
5
6
Drive control
V/f control
with slip compensation inactive
Dynamic torque vector control
V/f control
with slip compensation active
V/f control
with speed sensor
Dynamic torque vector control
with speed sensor
Vector control
without speed sensor
Vector control
with speed sensor
Basic
control
Speed
feedback
Drive control
class
Speed control
Frequency control
Disable
V/f
V/f
control
Enable
Vector
control
PG V/f
Estimated
speed
w/o PG
Enable
w/ PG
Frequency control
with slip compensation
Other
restrictions
Frequency control
with automatic speed
regulator (ASR)
Maximum
frequency:
200 Hz
Speed control
with automatic speed
regulator (ASR)
Maximum
frequency:
120 Hz
Not available
for MT-mode
inverters.
Maximum
frequency:
200 Hz
„ V/f control with slip compensation inactive
Under this control, the inverter controls a motor with the voltage and frequency according to the V/f pattern specified by
function codes. This control disables all automatically controlled features such as the slip compensation, so no unpredictable
output fluctuation results, enabling stable operation with constant output frequency.
„ V/f control with slip compensation active
Applying any load to an induction motor causes a rotational slip due to the motor characteristics, decreasing the motor rotation.
The inverter’s slip compensation function first presumes the slip value of the motor based on the motor torque generated and
raises the output frequency to compensate for the decrease in motor rotation. This prevents the motor from decreasing the
rotation due to the slip.
That is, this function is effective for improving the motor speed control accuracy.
The compensation value is specified by combination of function codes P12* (Rated slip frequency), P09* (Slip compensation
gain for driving) and P11* (Slip compensation gain for braking).
4-3
RUNNING THE MOTOR
Current limiter
(Level)
Remarks
Setting range: 0 to 80%
0.75 to 6 kHz
(500 and 630 kW)
F44
VT mode
Chap. 4
DC braking
(Braking level)
MT mode
H68* enables or disables the slip compensation function according to the motor driving conditions.
H68* data
0
1
2
3
Motor driving conditions
Accl/Decel
Constant speed
Enable
Enable
Disable
Enable
Enable
Enable
Disable
Enable
Motor driving frequency zone
Base frequency or below Above the base frequency
Enable
Enable
Enable
Enable
Enable
Disable
Enable
Disable
„ Dynamic torque vector control
To get the maximal torque out of a motor, this control calculates the motor torque for the load applied and uses it to optimize the
voltage and current vector output.
Selecting this control automatically enables the auto torque boost and slip compensation function.
This control is effective for improving the system response to external disturbances such as load fluctuations, and the motor
speed control accuracy.
Note that the inverter may not respond to a rapid load fluctuation since this control is an open-loop V/f control that does not
perform the current control, unlike the vector control. The advantages of this control include larger maximum torque per output
current than that the vector control.
„ V/f control with speed sensor
Applying any load to an induction motor causes a rotational slip due to the motor characteristics, decreasing the motor rotation.
Under V/f control with speed sensor, the inverter detects the motor rotation using the encoder mounted on the motor shaft and
compensates for the decrease in slip frequency by the PI control to match the motor rotation with the commanded speed. This
improves the motor speed control accuracy.
„ Dynamic torque vector control with speed sensor
The difference from the "V/f control with speed sensor" stated above is to calculate the motor torque for the load applied and
use it to optimize the voltage and current vector output for getting the maximal torque out of a motor.
This control is effective for improving the system response to external disturbances such as load fluctuations, and the motor
speed control accuracy.
„ Vector control without speed sensor
This control estimates the motor speed based on the inverter's output voltage and current to use the estimated speed for speed
control. In addition, it decomposes the motor drive current into the exciting and torque current components, and controls each
of those components in vector. No PG (pulse generator) interface card is required. It is possible to obtain the desired response
by adjusting the control constants (PI constants) using the speed regulator (PI controller).
Since this control controls the motor current, it is necessary to secure some voltage margin between the voltage that the inverter
can output and the induced voltage of the motor, by keeping the former lower than the latter.
Although the voltage of the general-purpose motor has usually been adjusted to match the commercial power, keeping the
motor terminal voltage low is necessary in order to secure the voltage margin. If the motor is driven under this control with the
motor terminal voltage being kept low, however, the rated torque cannot be obtained even when the rated current originally
specified for the motor is applied. To secure the rated torque, therefore, it is necessary to use a motor with higher rated current.
(This also applies to the vector control with speed sensor.)
This control is not available for MT-mode inverters, so do not set F42 data to "5" for those inverters.
„ Vector control with speed sensor
This control requires an optional PG (pulse generator) and an optional PG interface card to be mounted on a motor shaft and an
inverter, respectively. The inverter detects the motor's rotational position and speed from PG feedback signals and uses them for
speed control. In addition, it decomposes the motor drive current into the exciting and torque current components, and controls
each of components in vector.
The desired response can be obtained by adjusting the control constants (PI constants) and using the speed regulator (PI
controller). This control enables the speed control with higher accuracy and quicker response than the vector control without
speed sensor.
Since slip compensation, dynamic torque vector control, and vector control with/without speed sensor use motor
parameters, the following conditions should be satisfied; otherwise, full control performance may not be obtained.
• A single motor should be controlled per inverter.
• Motor parameters P02*, P03*, P06* to P23*, P55* and P56* should be properly configured or auto-tuning (P04*)
should be performed.
• The capacity of the motor to be controlled should be two or more ranks lower than that of the inverter under the
dynamic torque vector control; it should be the same as that of the inverter under the vector control with/without
speed sensor. Otherwise, the inverter may not control the motor due to decrease of the current detection resolution.
• The wiring distance between the inverter and motor should be 50 m or less. If it is longer, the inverter may not
control the motor due to leakage current flowing through stray capacitance to the ground or between wires.
Especially, small capacity inverters whose rated current is also small may be unable to control the motor correctly
even when the wiring is less than 50 m. In that case, make the wiring length as short as possible or use a wire with
small stray capacitance (e.g., loosely-bundled cable) to minimize the stray capacitance.
4-4
„ Performance comparison for drive controls (summary)
Each drive control has advantages and disadvantages. The table below compares the drive controls, showing their relative
performance in each characteristic.
Select the one that shows high performance in the characteristics that are important in your machinery. In rare cases, the
performance shown below may not be obtained due to various conditions including motor characteristics or mechanical rigidity.
The final performance should be determined by adjusting the speed control system or other elements with the inverter being
connected to the machinery (load). If you have any questions, contact your IMO representative.
Output
frequency
stability
Speed
control
accuracy
Speed
control
response
0
V/f control with slip
compensation inactive
‫۔‬
‫۔‬
‫ڹ‬
‫ڹ‬
‫ڹ‬
‫ڹ‬
‫ڸ‬
‫ڹ‬
1
2
3
4
Dynamic torque
vector control
V/f control with slip
compensation active
V/f control with speed
sensor
Dynamic torque
vector control with
speed sensor
Maximum
Load
torque
disturbance
Current
control
Torque
accuracy
‫ڹ‬
‫۔‬
‫ڹ‬
‫ۑ‬
‫ڸ‬
‫۔‬
‫ڹ‬
‫ڹ‬
‫۔‬
‫ۑ‬
‫۔‬
‫ڹ‬
‫ڹ‬
‫ڹ‬
‫۔‬
‫ۑ‬
‫۔‬
‫ڹ‬
‫ۑ‬
5
Vector control without
speed sensor
‫ڹ‬
‫ۑ‬
‫ۑ‬
‫ڹ‬
‫ۑ‬
‫۔‬
‫ۑ‬
6
Vector control with
speed sensor
‫ڹ‬
‫۔‬
‫۔‬
‫ڹ‬
‫۔‬
‫۔‬
‫۔‬
Relative performance symbols ‫۔‬: Excellent, ‫ۑ‬: Good, ‫ڹ‬: Effective, ‫ڸ‬: Less effective, : Not effective
4.1.6 Function code basic settings < 1 >
Driving a general-purpose motor under the V/f control (F42* = 0 or 2) or dynamic torque vector control (F42* = 1) requires
configuring the following basic function codes. (Refer to Figure 4.1 on page 4-1.)
Select standard 8- or 6-series motors with the function code P99*.
Configure the function codes listed below according to the motor ratings and your machinery design values. For the motor
ratings, check the ratings printed on the motor's nameplate. For your machinery design values, ask system designers about
them.
For details on how to modify the function code data, see Chapter 3, Section 3.4.2 "Setting up function codes -- Menu #1
"Data Setting" --."
Function
code
I *
I *
Name
Base frequency 1
Rated voltage at base
frequency 1
Function code data
Motor ratings
(printed on the nameplate of the
motor)
S *
Motor 1 selection
0: Motor characteristics 0
Standard motors
3: Motor characteristics 3
Standard motors
S *
Motor 1
(Rated capacity)
Capacity of motor connected
I *
Maximum frequency 1
I Acceleration time 1
I Deceleration time 1
(Note)
(Note)
Factory default
VXGxxx-2E
VXGxxx-4E
200 V class series:
400 V class series:
60.0 (Hz)
50.0 (Hz)
200 V class series:
220 (V)
(Note) For a test-driving of the motor,
increase values so that they are longer
than your machinery design values. If
the specified time is short, the inverter
may not run the motor properly.
400 (V)
0: Motor characteristics 0
Standard motors
Nominal applied motor capacity
200 V class series:
Machinery design values
400 V class series:
60.0 (Hz)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
400 V class series:
50.0 (Hz)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
After the above configuration, initialize motor 1 with the function code (H03 = 2). It automatically updates the motor
parameters P01*, P03*, P06* to P23*, P53* to P56*, and H46.
4-5
RUNNING THE MOTOR
Drive control
Chap. 4
F42*
data
When accessing the function code P02*, take into account that changing the P02* data automatically updates the data
of the function codes P03*, P06* to P23*, P53* to P56*, and H46.
The motor rating should be specified properly when performing auto-torque boost, torque calculation monitoring,
auto energy saving, torque limiting, automatic deceleration (anti-regenerative control), auto search for idling motor
speed, slip compensation, torque vector control, droop control, or overload stop.
In any of the following cases, the full control performance may not be obtained from the inverter because the motor
parameters differ from the factory defaults, so perform auto-tuning. (Refer to Section 4.1.7.)
• The motor to be driven is not a IMO product or is a non-standard product.
• The wiring distance between the inverter and the motor is too long (generally 20 m or more).
• A reactor is inserted between the inverter and the motor.
4.1.7 Function code basic settings and tuning < 2 >
Under the V/f control (F42* = 0 or 2) or dynamic torque vector control (F42* = 1), any of the following cases requires
configuring the basic function codes given below and auto-tuning. (Refer to Figure 4.1 on page 4-1.)
- Driving a non-standard motor
- Driving a general-purpose motor, provided that the wiring distance between the inverter and motor is long or a reactor is
connected
Configure the function codes listed below according to the motor ratings and your machinery design values. For the motor
ratings, check the ratings printed on the motor's nameplate. For your machinery design values, ask system designers about
them.
For details on how to modify the function code data, see Chapter 3, Section 3.4.2 "Setting up function codes -- Menu #1
"Data Setting" --."
Function
code
Name
I *
Base frequency 1
I *
S *
Rated voltage
at base frequency 1
Motor 1
(Rated capacity)
Motor 1
(Rated current)
I *
Maximum frequency 1
S *
I I Acceleration time 1
(Note)
Deceleration time 1
(Note)
Function code data
Factory default
VXGxxx-2E
200 V class series:
Motor ratings
(printed on the nameplate of the
motor)
VXGxxx-4E
400 V class series:
60.0 (Hz)
50.0 (Hz)
200 V class series:
400 V class series:
220 (V)
400 (V)
Nominal applied motor capacity
Rated current of nominal applied motor
200 V class series:
Machinery design values
(Note) For a test-driving of the motor,
increase values so that they are longer
than your machinery design values. If
the specified time is short, the inverter
may not run the motor properly.
60.0 (Hz)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
400 V class series:
50.0 (Hz)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
When accessing the function code P02*, take into account that changing the P02* data automatically updates the data
of the function codes P03*, P06* to P23*, P53* to P56*, and H46.
4-6
„ Tuning procedure
(1) Selection of tuning type
Check the situation of the machinery and select "Tuning with the motor stopped (P04* = 1)" or "Tuning with the motor running
(P04* = 2)." For the latter tuning, adjust the acceleration and deceleration times (F07 and F08) and specify the rotation direction
that matches the actual rotation direction of the machinery.
1
Tune while
the motor
stops
2
No-load current (P06*)
Primary resistance (%R1) (P07*)
Tune while Leakage reactance (%X) (P08*)
the motor is Rated slip frequency (P12*)
rotating
Magnetic saturation factors 1 to 5
under V/f
Magnetic saturation extension factors
control
"a" to "c" (P16* to P23*)
%X correction factor 1 and 2 (P53* and P54*)
Motor parameters subjected to tuning
Tuning
Primary resistance (%R1) (P07*)
Tuning with the motor
Leakage reactance (%X) (P08*)
stopped.
Rated slip frequency (P12*)
%X correction factor 1 and 2 (P53* and P54*)
Select under the
following conditions
Cannot rotate the motor.
Tuning the %R1 and %X,
with the motor stopped.
Can rotate the motor,
Tuning the no-load current provided that it is safe.
and magnetic saturation
Note that little load
factor, with the motor
should be applied
running at 50% of the base during tuning. Tuning
frequency.
with load applied
decreases the tuning
Tuning the rated slip
frequency, with the motor accuracy.
stopped.
The tuning results of motor parameters will be automatically saved into their respective function codes. If P04* tuning is
performed, for instance, the tuning results will be saved into P* codes (Motor 1* parameters).
(2) Preparation of machinery
Perform appropriate preparations on the motor and its load, such as disengaging the coupling from the motor and deactivating
the safety devices.
(3) Tuning
Set function code P04* to "1" or "2" and press the
key. (The blinking of or on the LED monitor will slow down.)
Enter a run command. The factory default is "
key on the keypad for forward rotation." To switch to reverse rotation
or to select the terminal signal FWD or REV as a run command, change the data of function code F02.
The moment a run command is entered, the display of or lights up, and tuning starts with the motor stopped.
(Maximum tuning time: Approx. 40 to 80 s.)
If P04* = 2, after the tuning in above, the motor is accelerated to approximately 50% of the base frequency and then
tuning starts. Upon completion of measurements, the motor decelerates to a stop.
(Estimated tuning time: Acceleration time + 20 to 75 s + Deceleration time)
If P04* = 2, after the motor decelerates to a stop in above, tuning continues with the motor stopped.
(Maximum tuning time: Approx. 40 to 80 s.)
If the terminal signal FWD or REV is selected as a run command (F02 = 1), HQG appears upon completion of the
measurements. Turning the run command OFF completes the tuning.
If the run command has been given through the keypad or the communications link, it automatically turns OFF upon
completion of the measurements, which completes the tuning.
Upon completion of the tuning, the subsequent function code P06* appears on the keypad.
„ Tuning errors
Improper tuning would negatively affect the operation performance and, in the worst case, could even cause hunting or
deteriorate precision. Therefore, if the inverter finds any abnormality in the tuning results or any error in the tuning process, it
displays HU and discards the tuning data.
Listed below are possible causes that trigger tuning errors.
Possible tuning error causes
Details
Error in tuning results
- An interphase voltage unbalance or output phase loss has been detected.
- Tuning has resulted in an abnormally high or low value of a parameter due to the output
circuit opened.
Output current error
An abnormally high current has flown during tuning.
Sequence error
During tuning, a run command has been turned OFF, or STOP (Force to stop), BX (Coast to
a stop), DWP (Protect from dew condensation), or other similar terminal command has been
received.
Error due to limitation
- During tuning, any of the operation limiters has been activated.
- The maximum frequency or the frequency limiter (high) has limited tuning operation.
Other errors
An undervoltage or any other alarm has occurred.
If any of these errors occurs, remove the error cause and perform tuning again, or consult your IMO representative.
4-7
RUNNING THE MOTOR
Tuning type
Chap. 4
P04*
data
If a filter other than the IMO optional output filter is connected to the inverter's output (secondary) circuit, the tuning
result cannot be assured. When replacing the inverter connected with such a filter, make a note of the old inverter’s
settings for the primary resistance %R1, leakage reactance %X, no-load current, and rated slip frequency, and specify
those values to the new inverter’s function codes.
Vibration that may occur when the motor's coupling is elastic can be regarded as normal vibration due to the output
voltage pattern applied in tuning. The tuning does not always result in an error; however, run the motor and check its
running state.
4.1.8 Function code basic settings and tuning < 3 >
Driving a motor under vector control without speed sensor (F42* = 5) requires auto-tuning, regardless of the motor type. (Refer
to Figure 4.1 on page 4-1.)
Configure the function codes listed below according to the motor ratings and your machinery design values. For the motor
ratings, check the ratings printed on the motor's nameplate. For your machinery design values, ask system designers about
them.
For details on how to modify the function code data, see Chapter 3, Section 3.4.2 "Setting up function codes -- Menu #1
"Data Setting" --."
Function
code
I *
Name
S *
I *
Maximum frequency 1
I Acceleration time 1
S *
Motor ratings
(printed on the nameplate of the
motor)
Deceleration time 1
(Note)
400 V class series:
60.0 (Hz)
50.0 (Hz)
200 V class series:
400 V class series:
220 (V)
400 (V)
Nominal applied motor capacity
Rated current of nominal applied motor
200 V class series:
Machinery design values
60.0 (Hz)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
(Note) For a test-driving of the motor,
increase values so that they are longer
than your machinery design values. If
the specified time is short, the inverter
may not run the motor properly.
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
(Note)
I Factory default
VXGxxx-2E
VXGxxx-4E
200 V class series:
Base frequency 1
Rated voltage
at base frequency 1
Motor 1
(Rated capacity)
Motor 1
(Rated current)
I *
Function code data
400 V class series:
50.0 (Hz)
• When accessing the function code P02*, take into account that changing the P02* data automatically updates the
data of the function codes P03*, P06* to P23*, P53* to P56*, and H46.
• Specify the rated voltage at base frequency (F05) at the normal value, although the inverter controls the motor
keeping the rated voltage (rated voltage at base frequency) low under vector control without speed sensor. After
the auto-tuning, the inverter automatically reduces the rated voltage at base frequency.
• Vector control without speed sensor is not available for MT-mode inverters.
Function
code
Name
Function code data
Factory default
VXGxxx-2E
VXGxxx-4E
S *
Motor 1 selection
2: Motor characteristics 2
(VG motors)
0: Motor characteristics 0
S *
Motor 1
(Rated capacity)
Same as that of the applied motor
capacity
Nominal applied motor capacity
I *
Maximum frequency 1
I Acceleration time 1
I 200 V class series:
Machinery design values
60.0 (Hz)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
(Note) For a test-driving of the motor,
increase values so that they are longer
than your machinery design values. If
the specified time is short, the inverter
may not run the motor properly.
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
(Note)
Deceleration time 1
(Note)
400 V class series:
50.0 (Hz)
Initializing the motor 1 parameters with the function code (H03=2) automatically updates the data of function codes
P03*, P06* to P23*, P53* to P56*, and H46. After that, perform the auto-tuning.
4-8
„ Tuning procedure
(1) Selection of tuning type
Check the machinery conditions and perform the "tuning while the motor is rotating under vector control" (P04*=3). Adjust the
acceleration and deceleration times (F07 and F08) in view of the motor rotation. And specify the rotation direction that matches
the actual rotation direction of the machinery.
If the "tuning while the motor is rotating under vector control (P04*=3)" cannot be selected due to restrictions on the
machinery, refer to the "„ If tuning while the motor is rotating cannot be selected" below.
Drive control abbreviation: "V/f" (V/f control), "w/o PG" (vector control without speed sensor),
and "w/ PG" (vector control with speed sensor)
Tuning type
Primary resistance (%R1) (P07*)
Leakage reactance (%X) (P08*) Tuning with the motor
Rated slip frequency (P12*)
stopped.
%X correction factor 1 and 2
(P53* and P54*)
No-load current (P06*)
Primary resistance (%R1) (P07*)
Leakage reactance (%X) (P08*)
Tune while
Rated slip frequency (P12*)
the motor is
2
rotating under Magnetic saturation factors 1 to 5
Magnetic saturation extension
V/f control
factors "a" to "c" (P16* to P23*)
%X correction factor 1 and 2
(P53* and P54*)
3
Tuning
No-load current (P06*)
Primary resistance (%R1) (P07*)
Leakage reactance (%X) (P08*)
Tune while
Rated slip frequency (P12*)
the motor is
rotating under Magnetic saturation factors 1 to 5
vector control Magnetic saturation extension
factors "a" to "c" (P16* to P23*)
%X correction factor 1 and 2
(P53* and P54*)
Tuning the %R1 and %X,
with the motor stopped.
Tuning the no-load current
and magnetic saturation
factor, with the motor
running at 50% of the base
frequency.
Drive control
Select under the
following conditions V/f w/o w/
PG PG
Cannot rotate the
motor.
Y
Y* Y*
Can rotate the motor,
provided that it is safe.
Note that little load
should be applied
Y
during tuning. Tuning
with load applied
decreases the tuning
accuracy.
N
N
Can rotate the motor,
provided that it is safe.
Note that little load
Tuning the no-load current should be applied
N
during tuning. Tuning
and magnetic saturation
with load applied
factor, with the motor
running at 50% of the base decreases the tuning
accuracy.
frequency twice.
Y
Y
Tuning the rated slip
frequency again, with the
motor stopped.
Tuning the %R1, %X and
rated slip frequency, with
the motor stopped.
Y: Tuning available unconditionally
Y*: Tuning available conditionally
N: Tuning not available
The tuning results of motor parameters will be automatically saved into their respective function codes. If P04* tuning is
performed, for instance, the tuning results will be saved into P* codes (Motor 1* parameters).
(2) Preparation of machinery
Perform appropriate preparations on the motor and its load, such as disengaging the coupling from the motor and deactivating
the safety devices.
(3) Tuning (Tune while the motor is rotating under vector control)
Set function code P04* to "3" and press the
key. (The blinking of on the LED monitor will slow down.)
Enter a run command. The factory default is "
key on the keypad for forward rotation." To switch to reverse rotation
or to select the terminal signal FWD or REV as a run command, change the data of function code F02.
The moment a run command is entered, the display of lights up, and tuning starts with the motor stopped.
(Maximum tuning time: Approx. 40 to 75 s.)
Next, the motor is accelerated to approximately 50% of the base frequency and then tuning starts. Upon completion of
measurements, the motor decelerates to a stop.
(Estimated tuning time: Acceleration time + 20 to 75 s + Deceleration time)
After the motor decelerates to a stop in above, tuning continues with the motor stopped.
(Maximum tuning time: Approx. 20 to 35 s.)
The motor is again accelerated to approximately 50% of the base frequency and then tuning starts. Upon completion of
measurements, the motor decelerates to a stop.
(Estimated tuning time: Acceleration time + 20 to 160 s + Deceleration time)
After the motor decelerates to a stop in above, tuning continues with the motor stopped.
(Maximum tuning time: Approx. 20 to 30 s.)
If the terminal signal FWD or REV is selected as a run command (F02 = 1), HQG appears upon completion of the
measurements. Turning the run command OFF completes the tuning.
If the run command has been given through the keypad or the communications link, it automatically turns OFF upon
completion of the measurements, which completes the tuning.
4-9
RUNNING THE MOTOR
Tune while
1 the motor
stops
Motor parameters
subjected to tuning
Chap. 4
P04*
data
Upon completion of the tuning, the subsequent function code P06* appears on the keypad.
Approx. 50% of the base frequency
e
ACC
f
DEC
g
ACC
h
DEC
i
Tuning operation
The default value of the speed regulator is set low to prevent your system from oscillation (hunting). However,
hunting may occur during tuning due to machinery-related conditions, causing a tuning error (HU ) or a speed
mismatch error (HUH ). If a tuning error (HU ) occurs, reduce the gain for the speed regulator; if a speed mismatch error
(HUH ) occurs, cancel the speed mismatch detection function (d23=0). After that, perform tuning again.
„ If tuning while the motor is rotating cannot be selected
If the "tuning while the motor is rotating under vector control (P04*=3)" cannot be selected due to restrictions on the machinery,
perform the "tuning with the motor stops (P04*=1)" by following the procedure below. Compared to the former tuning, the
latter may show rather inferior performance in the speed control accuracy or stability, perform sufficient tests beforehand by
connecting the motor with the machinery.
(1) For motors whose motor ratings are unknown such as ones made by other manufacturers
Specify the F04*, F05*, P02*, and P03* data according to the motor rated values printed on the motor 's nameplate.
Specify motor parameters (the data of P06*, P16* to P23*) by obtaining the appropriate values on the datasheet issued
from the motor manufacturer.
For details of conversion from data on the datasheet into ones to be entered as function code data, contact your IMO
representative.
Perform the "tuning with the motor stops (P04*=1)."
(2) Tuning (Tune while the motor stops)
Set function code P04* to "1" and press the
key. (The blinking of on the LED monitor will slow down.)
Enter a run command. The factory default is "
key on the keypad for forward rotation." To select the terminal signal
FWD or REV as a run command, change the data of function code F02.
The moment a run command is entered, the display of lights up, and tuning starts with the motor stopped.
(Maximum tuning time: Approx. 40 s.)
If the terminal signal FWD or REV is selected as a run command (F02 = 1), HQG appears upon completion of the
measurements. Turning the run command OFF completes the tuning.
If the run command has been given through the keypad or the communications link, it automatically turns OFF upon
completion of the measurements, which completes the tuning.
Upon completion of the tuning, the subsequent function code P06* appears on the keypad.
„ Tuning errors
Improper tuning would negatively affect the operation performance and, in the worst case, could even cause hunting or
deteriorate precision. Therefore, if the inverter finds any abnormality in the tuning results or any error in the tuning process, it
displays HU and discards the tuning data.
Listed below are possible causes that trigger tuning errors.
Possible tuning error causes
Details
Error in tuning results
- An interphase voltage unbalance or output phase loss has been detected.
- Tuning has resulted in an abnormally high or low value of a parameter due to the output
circuit opened.
Output current error
An abnormally high current has flown during tuning.
Sequence error
During tuning, a run command has been turned OFF, or STOP (Force to stop), BX (Coast to
a stop), DWP (Protect from dew condensation), or other similar terminal command has been
received.
Error due to limitation
- During tuning, any of the operation limiters has been activated.
- The maximum frequency or the frequency limiter (high) has limited tuning operation.
Other errors
An undervoltage or any other alarm has occurred.
If any of these errors occurs, remove the error cause and perform tuning again, or consult your IMO representative.
4-10
If a filter other than the IMO optional output filter is connected to the inverter's output (secondary) circuit, the tuning
result cannot be assured. When replacing the inverter connected with such a filter, make a note of the old inverter’s
settings for the primary resistance %R1, leakage reactance %X, no-load current, and rated slip frequency, and specify
those values to the new inverter’s function codes.
Vibration that may occur when the motor's coupling is elastic can be regarded as normal vibration due to the output
voltage pattern applied in tuning. The tuning does not always result in an error; however, run the motor and check its
running state.
4.1.9 Function code basic settings < 4 >
"Data Setting" --."
Chap. 4
For details on how to modify the function code data, see Chapter 3, Section 3.4.2 "Setting up function codes -- Menu #1
Name
S *
Motor 1 selection
S *
Motor 1
(Rated capacity)
K Thermistor (for motor)
(Mode selection)
Function code data
2: Motor characteristics 2
(VG motors)
Same as that of the applied motor
capacity
3: Enable (when NTC thermistor)
Also turn SW5 on the control
printed circuit board to the
PTC/NTC side.
Factory default
VXGxxx-2E
VXGxxx-4E
0: Motor characteristics 0
(standard motors)
Nominal applied motor capacity
0: Disable
G Feedback input
2: A/B phase with 90 degree phase 2: A/B phase
(Pulse input format)
shift
Feedback input
0400 (1024)
(Encoder pulse resolution) 0400 (1024)
I *
Maximum frequency 1
G Acceleration time 1
I 200 V class series:
I (Note)
I *
Electric thermal overload
protection for motor 1
(Overload detection level)
50.0 (Hz)
Machinery design values
(Note) For a test-driving of the motor,
increase values so that they are longer
than your machinery design values. If
the specified time is short, the inverter
may not run the motor properly.
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
0.00: Disable
Depending upon the inverter capacity
(Note)
Deceleration time 1
400 V class series:
60.0 (Hz)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
After the above configuration, initialize motor 1 with the function code (H03 = 2). It automatically updates the data of the
function codes F04*, F05*, P01*, P03*, P06* to P23*, P53* to P56*, and H46.
When accessing the function code P02*, take into account that changing the P02* data automatically updates the data
of the function codes F04*, F05*, P03*, P06* to P23*, P53* to P56*, and H46.
4-11
RUNNING THE MOTOR
Function
code
4.1.10 Function code basic settings < 5 >
Select standard motors with the function code P99*.
Configure the function codes listed below according to the motor ratings and your machinery design values. For the motor
ratings, check the ratings printed on the motor's nameplate. For your machinery design values, ask system designers about
them.
For details on how to modify the function code data, see Chapter 3, Section 3.4.2 "Setting up function codes -- Menu #1
"Data Setting" --."
Function
code
Name
I * Base frequency 1
Rated voltage at base
I *
frequency 1
S * Motor 1 selection
S *
Motor 1
(Rated capacity)
Acceleration time 1
I Deceleration time 1
G G G (Note)
(Note)
200 V class series:
Motor ratings
(printed on the nameplate of the
motor)
400 V class series:
60.0 (Hz)
50.0 (Hz)
200 V class series:
400 V class series:
220 (V)
400 (V)
0: Motor characteristics 0
Standard motors
3: Motor characteristics 3
Standard motors
0: Motor characteristics 0
(standard motors)
Capacity of motor connected
Nominal applied motor capacity
200 V class series:
I * Maximum frequency 1
I Factory default
VXGxxx-2E
VXGxxx-4E
Function code data
Machinery design values
(Note) For a test-driving of the motor,
increase values so that they are longer
than your machinery design values. If
the specified time is short, the inverter
may not run the motor properly.
Pulse count of the target motor
Feedback input
encoder
(Encoder pulse resolution)
0400 hex. / 1024 P/R
Reduction ratio between the motor
Feedback input
and the encoder
(Pulse count factor 1)
Motor speed =
Feedback input
Encoder speed u (d17) / (d16)
(Pulse count factor 2)
60.0 (Hz)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
400 V class series:
50.0 (Hz)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
0400 (hex.)
1
1
After the above configuration, initialize motor 1 with the function code (H03 = 2). It automatically updates the motor
parameters P01*, P03*, P06* to P23*, P53* to P56*, and H46.
When accessing the function code P02*, take into account that changing the P02* data automatically updates the data
of the function codes P03*, P06* to P23*, P53* to P56*, and H46.
The motor rating should be specified properly when performing auto-torque boost, torque calculation monitoring,
auto energy saving, torque limiting, automatic deceleration (anti-regenerative control), auto search for idling motor
speed, slip compensation, torque vector control, droop control, or overload stop.
In any of the following cases, the full control performance may not be obtained from the inverter because the motor
parameters differ from the factory defaults, so perform auto-tuning. (Refer to Section 4.1.7.)
• The motor to be driven is a non-standard product.
• The wiring distance between the inverter and the motor is too long (generally 20 m or more).
• A reactor is inserted between the inverter and the motor.
4.1.11 Function code basic settings and tuning < 6 >
Under V/f control with speed sensor (F42* = 3) or dynamic torque vector control with speed sensor (F42* = 4), any of the
following cases requires configuring the basic function codes given below and auto-tuning. (Refer to Figure 4.1 on page 4-1.)
- Driving a non-standard motor.
- Driving a general-purpose motor, provided that the wiring distance between the inverter and motor is long or a reactor is
connected
Configure the function codes listed below according to the motor ratings and your machinery design values. For the motor
ratings, check the ratings printed on the motor's nameplate. For your machinery design values, ask system designers about
them.
For details on how to modify the function code data, see Chapter 3, Section 3.4.2 "Setting up function codes -- Menu #1
"Data Setting" --."
4-12
Function
code
Name
Base frequency 1
I *
S *
Rated voltage
at base frequency 1
Motor 1
(Rated capacity)
Motor 1
(Rated current)
I *
Maximum frequency 1
I G G G (Note)
Deceleration time 1
(Note)
Feedback input
(Encoder pulse
resolution)
Feedback input
(Pulse count factor 1)
Feedback input
(Pulse count factor 2)
VXGxxx-4E
400 V class series:
200 V class series:
Motor ratings
(printed on the nameplate of the
motor)
60.0 (Hz)
50.0 (Hz)
200 V class series:
400 V class series:
220 (V)
400 (V)
Nominal applied motor capacity
Rated current of nominal applied motor
400 V class series:
200 V class series:
Machinery design values
(Note) For a test-driving of the motor,
increase values so that they are longer
than your machinery design values. If
the specified time is short, the inverter
may not run the motor properly.
Pulse count of the target motor
encoder
0400 hex. / 1024 P/R
Reduction ratio between the motor
and the encoder
Motor speed =
Encoder speed u (d17) / (d16)
60.0 (Hz)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
50.0 (Hz)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
0400 (hex.)
1
1
When accessing the function code P02*, take into account that changing the P02* data automatically updates the data
of the function codes P03*, P06* to P23*, P53* to P56*, and H46.
„ Tuning procedure
(1) Selection of tuning type
Check the situation of the machinery and select "Tuning with the motor stopped (P04* = 1)" or "Tuning with the motor running
(P04* = 2)." For the latter tuning, adjust the acceleration and deceleration times (F07 and F08) and specify the rotation direction
that matches the actual rotation direction of the machinery.
P04*
data
Tuning type
1
Tune while
the motor
stops
2
No-load current (P06*)
Primary resistance (%R1) (P07*)
Tune while Leakage reactance (%X) (P08*)
the motor is Rated slip frequency (P12*)
rotating
Magnetic saturation factors 1 to 5
under V/f
Magnetic saturation extension factors
control
"a" to "c" (P16* to P23*)
%X correction factor 1 and 2 (P53* and P54*)
Motor parameters subjected to tuning
Tuning
Primary resistance (%R1) (P07*)
Tuning with the motor
Leakage reactance (%X) (P08*)
stopped.
Rated slip frequency (P12*)
%X correction factor 1 and 2 (P53* and P54*)
Tuning the %R1 and %X,
with the motor stopped.
Tuning the no-load current
and magnetic saturation
factor, with the motor
running at 50% of the base
frequency.
Tuning the rated slip
frequency, with the motor
stopped.
Select under the
following conditions
Cannot rotate the motor.
Can rotate the motor,
provided that it is safe.
Note that little load
should be applied
during tuning. Tuning
with load applied
decreases the tuning
accuracy.
The tuning results of motor parameters will be automatically saved into their respective function codes. If P04* tuning is
performed, for instance, the tuning results will be saved into P* codes (Motor 1* parameters).
(2) Preparation of machinery
Perform appropriate preparations on the motor and its load, such as disengaging the coupling from the motor and deactivating
the safety devices.
4-13
RUNNING THE MOTOR
I Acceleration time 1
VXGxxx-2E
Chap. 4
I *
S *
Factory default
Function code data
(3) Tuning
Set function code P04* to "1" or "2" and press the
key. (The blinking of or on the LED monitor will slow down.)
Enter a run command. The factory default is "
key on the keypad for forward rotation." To switch to reverse rotation
or to select the terminal signal FWD or REV as a run command, change the data of function code F02.
The moment a run command is entered, the display of or lights up, and tuning starts with the motor stopped.
(Maximum tuning time: Approx. 40 to 80 s.)
If P04* = 2, after the tuning in above, the motor is accelerated to approximately 50% of the base frequency and then
tuning starts. Upon completion of measurements, the motor decelerates to a stop.
(Estimated tuning time: Acceleration time + 20 to 75 s + Deceleration time)
If P04* = 2, after the motor decelerates to a stop in above, tuning continues with the motor stopped.
(Maximum tuning time: Approx. 40 to 80 s.)
If the terminal signal FWD or REV is selected as a run command (F02 = 1), HQG appears upon completion of the
measurements. Turning the run command OFF completes the tuning.
If the run command has been given through the keypad or the communications link, it automatically turns OFF upon
completion of the measurements, which completes the tuning.
Upon completion of the tuning, the subsequent function code P06* appears on the keypad.
„ Tuning errors
Improper tuning would negatively affect the operation performance and, in the worst case, could even cause hunting or
deteriorate precision. Therefore, if the inverter finds any abnormality in the tuning results or any error in the tuning process, it
displays HU and discards the tuning data.
Listed below are possible causes that trigger tuning errors.
Possible tuning error causes
Details
Error in tuning results
- An interphase voltage unbalance or output phase loss has been detected.
- Tuning has resulted in an abnormally high or low value of a parameter due to the output
circuit opened.
Output current error
An abnormally high current has flown during tuning.
Sequence error
During tuning, a run command has been turned OFF, or STOP (Force to stop), BX (Coast to
a stop), DWP (Protect from dew condensation), or other similar terminal command has been
received.
Error due to limitation
- During tuning, any of the operation limiters has been activated.
- The maximum frequency or the frequency limiter (high) has limited tuning operation.
Other errors
An undervoltage or any other alarm has occurred.
If any of these errors occurs, remove the error cause and perform tuning again, or consult your IMO representative.
If a filter other than the IMO optional output filter is connected to the inverter's output (secondary) circuit, the tuning
result cannot be assured. When replacing the inverter connected with such a filter, make a note of the old inverter’s
settings for the primary resistance %R1, leakage reactance %X, no-load current, and rated slip frequency, and specify
those values to the new inverter’s function codes.
Vibration that may occur when the motor's coupling is elastic can be regarded as normal vibration due to the output
voltage pattern applied in tuning. The tuning does not always result in an error; however, run the motor and check its
running state.
4.1.12 Running the inverter for motor operation check
If the user configures the function codes wrongly without completely understanding this Instruction Manual and the
JAGUAR VXG User's Manual, the motor may rotate with a torque or at a speed not permitted for the machine.
Accident or injury may result.
After completion of preparations for a test run as described above, start running the inverter for motor operation check using the
following procedure.
If any abnormality is found in the inverter or motor, immediately stop operation and investigate the cause referring to
Chapter 6, "TROUBLESHOOTING."
4-14
-------------------------------------------------------------- Test Run Procedure -------------------------------------------------------------(1) Turn the power ON and check that the reference frequency Hz is blinking on the LED monitor.
(2) Set a low reference frequency such as 5 Hz, using
/
keys. (Check that the frequency is blinking on the LED monitor.)
key to start running the motor in the forward direction. (Check that the reference frequency is displayed on the
(3) Press the
LED monitor.)
key.
(4) To stop the motor, press the
Chap. 4
< Check points during a test run >
• Check that the motor is running in the forward direction.
• Check for smooth rotation without motor humming or excessive vibration.
• Check for smooth acceleration and deceleration.
key again to start driving the motor, then increase the reference frequency using
When no abnormality is found, press the
keys. Check the above points again.
/
If any problem is found, modify the function code data again as described below.
< Modification of motor control function code data >
Modifying the current function code data sometimes can solve an insufficient torque or overcurrent incident. The table below
lists the major function codes to be accessed. For details, see Chapter 5 "FUNCTION CODES" and Chapter 6
"TROUBLESHOOTING."
Function
code
Name
Modification key points
Drive control
PG w/o w/
V/f
V/f PG PG
I Acceleration time 1
If the current limiter is activated due to a short acceleration time
and large drive current, prolong the acceleration time.
Y
Y
Y
Y
I Deceleration time 1
If an overvoltage trip occurs due to a short deceleration time,
prolong the deceleration time.
Y
Y
Y
Y
I *
Torque boost 1
If the starting motor torque is deficient, increase the torque boost.
If the motor with no load is overexcited, decrease the torque boost.
Y
Y
N
N
I Current limiter
(Mode selection)
If the stall prevention function is activated by the current limiter
during acceleration or deceleration, increase the operation level.
Y
Y
N
N
S *
Motor 1
(Slip compensation
gain for driving)
For excessive slip compensation during driving, decrease the gain;
for insufficient one, increase the gain.
Y
N
Y
N
S *
Motor 1
(Slip compensation
gain for braking)
For excessive slip compensation during braking, decrease the gain;
for insufficient one, increase the gain.
Y
N
Y
N
K *
Output current
fluctuation damping
gain 1 (For motor 1)
If the motor vibrates due to current fluctuation, increase the
suppression gain.
Y
Y
N
N
Y: Modification effective N: Modification ineffective
If any problem persists under V/f control with speed sensor, dynamic torque vector control with speed sensor, or vector control
with/without speed sensor, modify the following function code data.
The drive controls mentioned above use a PI controller for speed control. The PI constants are sometimes required to be
modified because of the load inertia. The table below lists the main modification items. For details, see Chapter 5 "FUNCTION
CODES" and Chapter 6 "TROUBLESHOOTING."
Function
code
Name
Modification key points
Speed control 1
If an excessive overshoot occurs for a speed command change, increase the filter
constant.
Speed control 1
If ripples are superimposed on the speed detection signal so that the speed control
gain cannot be increased, increase the filter constant to obtain a larger gain.
Speed control 1
If hunting is caused in the motor speed control, decrease the gain.
If the motor response is slow, increase the gain.
G * (Speed command filter)
G * (Speed detection filter)
G * P (Gain)
Speed control 1
G * I (Integral time)
If the motor response is slow, decrease the integral time.
4-15
RUNNING THE MOTOR
Depending on the settings of function codes, the motor speed may rise to an unexpectedly high and dangerous
level, particularly, under vector control with/without speed sensor. To avoid such an event, the speed limiting
function is provided.
If the user is unfamiliar with the function code settings (e.g., when the user starts up the inverter for the first time),
it is recommended that the frequency limiter (high) (F15) and the torque control (speed limit 1/2) (d32/d33) be
used. At the startup of the inverter, to ensure safer operation, specify small values to those function codes at first
and gradually increase them while checking the actual operation.
The speed limiting function serves as an overspeed level barrier, or as a speed limiter under torque control. For
details of the speed limiting function, refer to the JAGUAR VXG User's Manual.
-------------------------------------------------------------------------------------------------------------------------------------------------------
4.1.13 Preparation for practical operation
After verifying normal motor running with the inverter in a test run, connect the motor with the machinery and perform wiring
for practical operation.
(1) Configure the application related function codes that operate the machinery.
(2) Check interfacing with the peripheral circuits.
1) Mock alarm
keys" on the keypad for 5 seconds or more and check the alarm
Generate a mock alarm by pressing the " +
sequence. The inverter should stop and issue an alarm output signal (for any fault).
2) Judgment on the life of the DC link bus capacitor
When the multi-function keypad is used, it is necessary to set up the judgment reference level to be applied for the
judgment on the life of the DC link bus capacitor.
When the remote keypad is used, the same setting-up is also necessary in order to judge the life of the DC link bus
capacitor under the practical operating conditions.
For details, refer to Chapter 7 "MAINTENANCE AND INSPECTION."
3) I/O checking
Check interfacing with peripherals using Menu #4 "I/O Checking" on the keypad in Programming mode. For details,
refer to Chapter 3 "OPERATION USING THE KEYPAD."
4) Analog input adjustment
Adjust the analog inputs on terminals [12], [C1] and [V2] using the function codes related to the offset, filter and gain
that minimize analog input errors. For details, refer to Chapter 5 "FUNCTION CODES."
5) Calibrating the [FM] output
Calibrate the full scale of the analog meter connected to the terminals [FM1] and [FM2], using the reference voltage
equivalent to +10 VDC. To output the reference voltage, it is necessary to select the analog output test with the function
code (F31/F35 = 14).
6) Clearing the alarm history
Clear the alarm history saved during the system setup with the function code (H97 = 1).
Depending upon the situation of the practical operation, it may become necessary to modify the settings of the torque
boost (F09*), acceleration/deceleration times (F07/F08), and the PI controller for speed control under the vector
control. Confirm the function code data and modify them properly.
4.2 Special Operations
4.2.1 Jogging operation
This section provides the procedure for jogging the motor.
(1) Making the inverter ready to jog with the steps below. The LED monitor should display MRJ .
• Switch the inverter to Running mode (see page 3-2).
keys" simultaneously. The LED monitor displays the jogging frequency for approximately one
• Press the " +
second and then returns to MRJ again.
• Function code C20 specifies the jogging frequency. H54 and H55 specify the acceleration and deceleration
times, respectively. These three function codes are exclusive to jogging operation.
• Using the input terminal command "Ready for jogging" JOG switches between the normal operation state and
ready-to-jog state.
• Switching between the normal operation state and ready-to-jog state with the " +
keys" is possible only
when the inverter is stopped.
(2) Jogging the motor.
key during which the motor continues jogging. To decelerate to stop the motor, release the key.
Hold down the
(3) Exiting the ready-to-jog state and returning to the normal operation state.
keys" simultaneously.
Press the " +
4.2.2 Remote and local modes
The inverter is available in either remote or local mode. In the remote mode that applies to ordinary operation, the inverter is
driven under the control of the data settings stored in the inverter, whereas in the local mode that applies to maintenance
operation, it is separated from the control system and is driven manually under the control of the keypad.
• Remote mode: Run and frequency commands are selected by function codes or source switching signals except "Select
local (keypad) operation" LOC.
• Local mode: The command source is the keypad, regardless of the settings specified by function codes. The keypad takes
precedence over the settings specified by communications link operation signals.
4-16
Run commands from the keypad in the local mode
The table below shows the input procedures of run commands from the keypad in the local mode.
When F02 data (run command) is:
Input procedures of run commands from keypad
0: Enable
/
keys on keypad
(Motor rotational direction from digital
terminals [FWD]/[REV])
key runs the motor in the direction specified by command
Pressing the
FWD or REV assigned to terminal [FWD] or [REV], respectively.
Pressing the
key stops the motor.
1: Enable terminal command FWD/REV
Pressing the
key runs the motor in the forward direction only. Pressing
key stops the motor.
the
/
keys on keypad (Forward)
3: Enable
/
keys on keypad (Reverse)
No specification of the motor rotational direction is required.
Pressing the
key runs the motor in the reverse direction only. Pressing
the
key stops the motor.
No specification of the motor rotational direction is required.
The remote and local modes can be switched by a digital input signal provided from the outside of the inverter.
To enable the switching, you need to assign LOC as a digital input signal to any of terminals [X1] to [X7] by setting "35" to any
of E01 to E07, E98 and E99.
Switching from remote to local mode automatically inherits the frequency settings used in remote mode. If the motor is running
at the time of the switching from remote to local, the run command will be automatically turned ON so that all the necessary
data settings will be carried over. If, however, there is a discrepancy between the settings used in remote mode and ones made
on the keypad (e.g., switching from the reverse rotation in remote mode to the forward rotation only in local mode), the inverter
automatically stops.
The transition paths between remote and local modes depend on the current mode and the value (ON/OFF) of LOC, as shown in
the status transition diagram given below. Also, refer to above table for details.
Transition between Remote and Local Modes by LOC
4.2.3 External run/frequency command
By factory default, run and frequency commands are sourced from the keypad. This section provides other external command
source samples--an external frequency command potentiometer (variable resistor) as a frequency command source and external
run switches as run forward/reverse command sources.
Set up those external sources using the following procedure.
(1) Configure the function codes as listed below.
Function code
Name
Data
Factory default
I Frequency command 1
1:
Analog voltage input to terminal [12]
0
I Operation method
1:
External digital input signal
2
H Terminal [FWD] function
98: Run forward command FWD
98
H Terminal [REV] function
99: Run reverse command REV
99
If terminal [FWD] and [REV] are ON, the F02 data cannot be changed. First turn those terminals OFF and then
change the F02 data.
(2) Wire the external frequency command potentiometer to terminals across [13], [12], and [11].
(3) Connect the run forward switch between terminals [FWD] and [CM] and the run reverse switch between [REV] and [CM].
(4) To start running the inverter, rotate the potentiometer to give a voltage to terminal [12] and then turn the run forward or
reverse switch ON (short-circuit).
For precautions in wiring, refer to Chapter 2 "MOUNTING AND WIRING THE INVERTER."
4-17
RUNNING THE MOTOR
Switching between remote and local modes
Chap. 4
2: Enable
Chapter 5 FUNCTION CODES
5.1 Function Code Tables
Function codes enable the JAGUAR VXG series of inverters to be set up to match your system requirements.
Each function code consists of a 3-letter alphanumeric string. The first letter is an alphabet that identifies its group and the
following two letters are numerals that identify each individual code in the group. The function codes are classified into 13
groups: Fundamental Functions (F codes), Extension Terminal Functions (E codes), Control Functions (C codes), Motor 1
Parameters (P codes), High Performance Functions (H codes), Motor 2, 3 and 4 Parameters (A, b and r codes), Application
Functions 1, 2, and 3 (J, d, and U codes), Link Functions (y codes) and Option Functions (o codes). To determine the
property of each function code, set data to the function code.
This manual does not contain the descriptions of Option Function (o codes). For Option Function (o codes), refer to the
instruction manual for each option.
The following descriptions supplement those given in the function code tables on the following pages.
„ Changing, validating, and saving function code data when the inverter is running
Function codes are indicated by the following based on whether they can be changed or not when the inverter is running:
Notation
Change when running
Y*
Possible
Y
Possible
N
Impossible
Validating and saving function code data
and
keys, the
If the data of the codes marked with Y* is changed with
change will immediately take effect; however, the change is not saved into the
inverter's memory. To save the change, press the
key. If you press the
key
key to exit the current state, then the changed data will be
without pressing the
discarded and the previous data will take effect for the inverter operation.
Even if the data of the codes marked with Y is changed with
and
keys,
key will make the change take
the change will not take effect. Pressing the
effect and save it into the inverter's memory.
—
„ Copying data
The keypad is capable of copying of the function code data stored in the inverter's memory into the keypad's memory (refer
to Menu #7 "Data copying" in Programming mode). With this feature, you can easily transfer the data saved in a source
inverter to other destination inverters.
If the specifications of the source and destination inverters differ, some code data may not be copied to ensure safe operation
of your power system. Whether data will be copied or not is detailed with the following symbols in the "Data copying"
column of the function code tables given on the following pages.
Y:
Will be copied unconditionally.
Y1: Will not be copied if the rated capacity differs from the source inverter.
Y2: Will not be copied if the rated input voltage differs from the source inverter.
N:
Will not be copied. (The function code marked with "N" is not subject to the Verify operation, either.)
For details of copying operation, refer to Chapter 3, Section 3.4.8.
„ Using negative logic for programmable I/O terminals
The negative logic signaling system can be used for the programmable, digital input and output terminals by setting the
function code data specifying the properties for those terminals. Negative logic refers to the inverted ON/OFF (logical value
1 (true)/0 (false)) state of input or output signal. An active-ON signal (the function takes effect if the terminal is
short-circuited.) in the normal logic system is functionally equivalent to active-OFF signal (the function takes effect if the
terminal is opened.) in the negative logic system. Active-ON signals can be switched to active-OFF signals, and vice versa,
with the function code data setting, except some signals.
To set the negative logic system for an input or output terminal, enter data of 1000s (by adding 1000 to the data for the
normal logic) in the corresponding function code.
Example: "Coast to a stop" command BX assigned to any of digital input terminals [X1] to [X7] using any of function codes
E01 through E07
Function code data
7
1007
Description
Turning BX ON causes the motor to coast to a stop. (Active-ON)
Turning BX OFF causes the motor to coast to a stop. (Active-OFF)
5-1
„ Drive control
The JAGUAR VXG runs under any of the following drive controls. Some function codes apply exclusively to the specific
drive control, which is indicated by letters Y (Applicable) and N (Not applicable) in the "Drive control" column in the
function code tables given on the following pages.
Abbreviation in "Drive control" column
in function code tables
Control target (H18)
V/f control
Dynamic torque vector control
V/f
PG V/f
w/o PG
Speed
(Frequency for V/f
and PG V/f)
w/ PG
Torque control
Drive control (F42)
V/f control with speed sensor
Dynamic torque vector control with speed sensor
Vector control without speed sensor
Vector control with speed sensor
Vector control without speed sensor
Vector control with speed sensor
Torque
5-2
FUNCTION CODES
The JAGUAR VXG is a general-purpose inverter whose operation is customized by frequency-basis function codes,
like conventional inverters. Under the speed-basis drive control, however, the control target is a motor speed, not a
frequency, so convert the frequency to the motor speed according to the following expression.
Motor speed (r/min) = 120 u Frequency (Hz) y Number of poles
Chap. 5
For details about the drive control, refer to "Function code F42 (Drive Control Selection 1)."
The following tables list the function codes available for the JAGUAR VXG series of inverters.
Name
F00 Data Protection
F01 Frequency Command 1
F02 Operation Method
F03 Maximum Frequency 1
F04 Base Frequency 1
F05 Rated Voltage at Base Frequency 1
F06 Maximum Output Voltage 1
F07 Acceleration Time 1
F08 Deceleration Time 1
F09 Torque Boost 1
F10 Electronic Thermal Overload
Protection for Motor 1
(Select motor characteristics)
F11
(Overload detection level)
F12
(Thermal time constant)
F14 Restart Mode after Momentary
Power Failure
(Mode selection)
F15 Frequency Limiter
(High)
F16
(Low)
F18 Bias
(Frequency command 1)
F20 DC Braking 1
(Braking starting frequency)
F21
(Braking level)
F22
(Braking time)
F23 Starting Frequency 1
F24
(Holding time)
F25 Stop Frequency
Data setting range
0: Disable both data protection and digital reference
protection
1: Enable data protection and disable digital reference
protection
2: Disable data protection and enable digital reference
protection
3: Enable both data protection and digital reference
protection
0:
/
keys on keypad
1: Voltage input to terminal [12] (-10 to +10 VDC)
2: Current input to terminal [C1] (4 to 20 mA DC)
3: Sum of voltage and current inputs to terminals [12] and
[C1]
5: Voltage input to terminal [V2] (0 to 10 VDC)
7: Terminal command UP/DOWN control
8:
/
keys on keypad
(balanceless-bumpless switching available)
11: Digital input interface card (option)
12: Pulse train input
0: RUN/STOP keys on keypad (Motor rotational direction
specified by terminal command FWD/REV)
1: Terminal command FWD or REV
2: RUN/STOP keys on keypad (forward)
3: RUN/STOP keys on keypad (reverse)
25.0 to 500.0 Hz
25.0 to 500.0 Hz
0: Output a voltage in proportion to input
voltage
80 to 240 V: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500 V: Output an AVR-controlled voltage
(for 400 V class series)
80 to 240 V: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500 V: Output an AVR-controlled voltage
(for 400 V class series)
0.00 to 6000 s
Note: Entering 0.00 cancels the acceleration time, requiring
external soft-start.
0.0% to 20.0% (percentage with respect to "Rated Voltage
at Base Frequency 1")
1: For a general-purpose motor with shaft-driven cooling
fan
2: For an inverter-driven motor, non-ventilated motor, or
motor with separately powered cooling fan
0.00: Disable
1% to 135% of the rated current (allowable continuous drive
current) of the motor
0.5 to 75.0 min
0: Trip immediately
1: Trip after a recovery from power failure
2: Trip after decelerate-to-stop
3: Continue to run, for heavy inertia or general loads
4: Restart at the frequency at which the power failure
occurred, for general loads
5: Restart at the starting frequency
0.0 to 500.0 Hz
0.0 to 500.0 Hz
-100.00% to 100.00%
Data
copying
Code
Change when
running
F codes: Fundamental Functions
Default
setting
Y
Y
0
Y
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
N
N
Y
2
Y
Y
Y
Y
Y
5-35
N
Y
*1
Y
Y
Y
Y
Y
5-36
N
Y
50.0
Y
Y
Y
Y
Y
N
Y2
*1
Y
Y
Y
Y
Y
N
Y2
*1
Y
Y
N
N
Y
Drive control
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
5-29
Y
Y
*2
Y
Y
Y
Y
N
Y
Y
*2
Y
Y
Y
Y
N
Y
Y
*3
Y
Y
N
N
N
5-40
5-55
Y
Y
1
Y
Y
Y
Y
Y
5-41
Y
Y1 Y2
*4
Y
Y
Y
Y
Y
Y
Y
*5
Y
Y
Y
Y
Y
Y
Y
1
Y
Y
Y
Y
N
5-43
Y
Y
70.0
Y
Y
Y
Y
N
5-49
Y
Y
0.0
Y
Y
Y
Y
N
Y*
Y
0.00
Y
Y
Y
Y
N
5-29
5-49
0.0 to 60.0 Hz
Y
Y
0.0
Y
Y
Y
Y
N
5-49
0% to 100% (CT mode), 0% to 80% (MT/VT mode)
0.00 (Disable); 0.01 to 30.00 s
0.0 to 60.0 Hz
0.00 to 10.00 s
0.0 to 60.0 Hz
Y
Y
0
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.5
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.2
Y
Y
Y
Y
N
The shaded function codes (
) are applicable to the quick setup.
*1 The factory default differs depending upon the shipping destination. See Table A.
*2 6.00 s for inverters with a capacity of 22 kW or below; 20.00 s for those with 30 kW or above
*3 The factory default differs depending upon the inverter's capacity. See Table B.
*4 The motor rated current is automatically set. See Table C (function code P03).
*5 5.0 min for inverters with a capacity of 22 kW or below; 10.0 min for those with 30 kW or above
5-3
5-38
5-51
Change when
running
Data
copying
F26 Motor Sound
Y
Y
2
(Asia)
15
(EU)
Y
Y
Y
Y
Y
F27
Y
Y
0
Y
Y
N
N
Y
Y
Y
0
Y
Y
Y
Y
Y
Y*
Y
100
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y*
Y
100
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
N
Y
1
Y
Y
N
Y
N
Code
F29
F30
F31
F37
F38
F39
F40
F41
F42
F43
F44
F50
F51
F52
F80
(Carrier frequency) 0.75 to 16 kHz (CT-mode inverters with 55 kW or below
and VT-mode ones with 18.5 kW or below
0.75 to 10 kHz (CT-mode inverters with 75 to 400 kW and
VT-mode ones with 22 to 55 kW)
0.75 to 6 kHz (CT-mode inverters with 500 and 630 kW
and VT-mode ones with 75 to 500 kW)
0.75 to 4 kHz (VT-mode inverters with 630 kW)
0.75 to 2 kHz (MT-mode inverters with 90 to 400 kW)
(Tone) 0: Level 0 (Inactive)
1: Level 1
2: Level 2
3: Level 3
Analog Output [FM1]
0: Output in voltage (0 to 10 VDC)
(Mode selection) 1: Output in current (4 to 20 mA DC)
(Voltage adjustment) 0% to 300%
(Function) Select a function to be monitored from the followings.
0: Output frequency 1 (before slip compensation)
1: Output frequency 2 (after slip compensation)
2: Output current
3: Output voltage
4: Output torque
5: Load factor
6: Input power
7: PID feedback amount
8: PG feedback value
9: DC link bus voltage
10: Universal AO
13: Motor output
14: Calibration (+)
15: PID command (SV)
16: PID output (MV)
Analog Output [FM2]
0: Output in voltage (0 to 10 VDC)
(Mode selection) 1: Output in current (4 to 20 mA DC)
(Voltage adjustment) 0% to 300%
(Function) Select a function to be monitored from the followings.
0: Output frequency 1 (before slip compensation)
1: Output frequency 2 (after slip compensation)
2: Output current
3: Output voltage
4: Output torque
5: Load factor
6: Input power
7: PID feedback amount
8: PG feedback value
9: DC link bus voltage
10: Universal AO
13: Motor output
14: Calibration
15: PID command (SV)
16: PID output (MV)
Load Selection/
0: Variable torque load
Auto Torque Boost/
1: Constant torque load
Auto Energy Saving Operation 1
2: Auto torque boost
3: Auto energy saving
(Variable torque load during ACC/DEC)
4: Auto energy saving
(Constant torque load during ACC/DEC)
5: Auto energy saving
(Auto torque boost during ACC/DEC)
Stop Frequency
(Detection mode) 0: Detected speed
1: Reference speed
(Holding Time) 0.00 to 10.00 s
Torque Limiter 1-1
-300% to 300%; 999 (Disable)
1-2
-300% to 300%; 999 (Disable)
Drive Control Selection 1
0: V/f control with slip compensation inactive
1: Dynamic torque vector control
2: V/f control with slip compensation active
3: V/f control with speed sensor
4: Dynamic torque vector control with speed sensor
5: Vector control without speed sensor
6: Vector control with speed sensor
Current Limiter
(Mode selection) 0: Disable (No current limiter works.)
1: Enable at constant speed (Disable during ACC/DEC)
2: Enable during ACC/constant speed operation
(Level) 20% to 200% (The data is interpreted as the rated output
current of the inverter for 100%.)
Electronic Thermal Overload
0 (Braking resistor built-in type), 1 to 9000 kWs,
Protection for Braking Resistor
OFF (Disable)
(Discharging capability)
(Allowable average loss) 0.001 to 99.99 kW
(Resistance) 0.01 to 999
Switching between CT, MT and VT
0: CT (Constant Torque) mode
drive modes
1: VT (Variable Torque) mode
2: MT (Medium Torque) mode
The shaded function codes (
) are applicable to the quick setup.
*6 0 for inverters with a capacity of 7.5 kW or below; OFF for those with 11 kW or above
5-4
Drive control
Default
setting
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
5-53
5-54
FUNCTION CODES
F34
F35
Data setting range
Chap. 5
F32
Name
5-55
F codes
E codes
C codes
N
Y
0
N
N
N
Y
N
5-51
Y
Y
0.00
Y
Y
Y
Y
N
5-57
5-57
P codes
5-62
H codes
Y
Y
999
Y
Y
Y
Y
Y
Y
Y
999
Y
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
Y
A codes
b codes
Y
Y
2
Y
Y
N
N
N
Y
Y
160
Y
Y
N
N
N
Y
Y1 Y2
*6
Y
Y
Y
Y
Y
Y
Y1 Y2 0.001
Y
Y
Y
Y
Y
Y
Y1 Y2
0.01
Y
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
Y
5-64
r codes
J codes
d codes
U codes
5-66
y codes
E01
E02
E03
E04
E05
E06
E07
E10
E11
E12
E13
E14
E15
Name
Terminal [X1] Function
Terminal [X2] Function
Terminal [X3] Function
Terminal [X4] Function
Terminal [X5] Function
Terminal [X6] Function
Terminal [X7] Function
Acceleration Time 2
Deceleration Time 2
Acceleration Time 3
Deceleration Time 3
Acceleration Time 4
Deceleration Time 4
Data setting range
Selecting function code data assigns the corresponding
function to terminals [X1] to [X7] as listed below.
0 (1000): Select multi-frequency (0 to 1 steps)
(SS1)
1 (1001): Select multi-frequency (0 to 3 steps)
(SS2)
2 (1002): Select multi-frequency (0 to 7 steps)
(SS4)
3 (1003): Select multi-frequency (0 to 15 steps)
(SS8)
4 (1004): Select ACC/DEC time (2 steps)
(RT1)
5 (1005): Select ACC/DEC time (4 steps)
(RT2)
6 (1006): Enable 3-wire operation
(HLD)
7 (1007): Coast to a stop
(BX)
8 (1008): Reset alarm
(RST)
9 (1009): Enable external alarm trip
(THR)
(9 = Active OFF, 1009 = Active ON)
10 (1010): Ready for jogging
(JOG)
11 (1011): Select frequency command 2/1
(Hz2/Hz1)
12 (1012): Select motor 2
(M2)
13:
Enable DC braking
(DCBRK)
14 (1014): Select torque limiter level 2/1
(TL2/TL1)
15:
Switch to commercial power (50 Hz)
(SW50)
16:
Switch to commercial power (60 Hz)
(SW60)
17 (1017): UP (Increase output frequency)
(UP)
18 (1018): DOWN (Decrease output frequency) (DOWN)
19 (1019): Enable data change with keypad
(WE-KP)
20 (1020): Cancel PID control
(Hz/PID)
21 (1021): Switch normal/inverse operation
(IVS)
22 (1022): Interlock
(IL)
23 (1023): Cancel torque control
(Hz/TRQ)
24 (1024): Enable communications link via
RS-485 or fieldbus (option)
(LE)
25 (1025): Universal DI
(U-DI)
26 (1026): Enable auto search for idling motor
speed at starting
(STM)
30 (1030): Force to stop
(STOP)
((30 = Active OFF, 1030 = Active ON)
32 (1032): Pre-excitation
(EXITE)
33 (1033): Reset PID integral and differential
components
(PID-RST)
34 (1034): Hold PID integral component
(PID-HLD)
35 (1035): Select local (keypad) operation
(LOC)
36 (1036): Select motor 3
(M3)
37 (1037): Select motor 4
(M4)
39:
Protect motor from dew condensation
(DWP)
40:
Enable integrated sequence to switch
to commercial power (50 Hz)
(ISW50)
41:
Enable integrated sequence to switch
to commercial power (60 Hz)
(ISW60)
47 (1047): Servo-lock command
(LOCK)
48:
Pulse train input (available only on
terminal [X7] (E07))
(PIN)
49 (1049): Pulse train sign (available on terminals
except [X7] (E01 to E06))
(SIGN)
70 (1070): Cancel constant peripheral speed
control
(Hz/LSC)
71 (1071): Hold the constant peripheral speed
control frequency in the memory
(LSC-HLD)
72 (1072): Count the run time of commercial
power-driven motor 1
(CRUN-M1)
73 (1073): Count the run time of commercial
power-driven motor 2
(CRUN-M2)
74 (1074): Count the run time of commercial
power-driven motor 3
(CRUN-M3)
75 (1075): Count the run time of commercial
power-driven motor 4
(CRUN-M4)
76 (1076): Select droop control
(DROOP)
77 (1077): Cancel PG alarm
(PG-CCL)
80 (1080): Cancel customizable logic
(CLC)
81 (1081): Clear all customizable logic timers
(CLTC)
100:
No function assigned
(NONE)
Setting the value in parentheses ( ) shown above assigns a
negative logic input to a terminal.
0.00 to 6000 s
Note: Entering 0.00 cancels the acceleration time, requiring
external soft-start and -stop.
*2 6.00 s for inverters with a capacity of 22 kW or below; 20.00 s for those with 30 kW or above
5-5
Data copying
Code
Change when
running
E codes: Extension Terminal Functions
Drive control
Default
setting
V/f
PG
V/f
Refer
to
w/o w/ Torque page:
PG PG control
5-67
N
Y
0
Y
Y
Y
Y
N
N
Y
1
Y
Y
Y
Y
N
N
Y
2
Y
Y
Y
Y
N
N
Y
3
Y
Y
Y
Y
N
N
Y
4
Y
Y
Y
Y
N
N
Y
5
Y
Y
Y
Y
N
N
Y
8
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
N
N
N
Y
Y
N
N
N
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
N
N
N
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
N
N
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
N
N
Y
Y
N
N
N
N
N
N
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
N
N
Y
Y
Y
N
N
Y
Y
Y
N
N
Y
Y
Y
N
N
Y
Y
Y
Y
Y
N
N
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
*2
Y
Y
Y
Y
N
5-38
Y
Y
*2
Y
Y
Y
Y
N
5-77
Y
Y
*2
Y
Y
Y
Y
N
Y
Y
*2
Y
Y
Y
Y
N
Y
Y
*2
Y
Y
Y
Y
N
Y
Y
*2
Y
Y
Y
Y
N
Name
E16 Torque Limiter 2-1
E17 Torque Limiter 2-2
E20
E21
E22
E23
E24
E27
Terminal [Y1] Function
Terminal [Y2] Function
Terminal [Y3] Function
Terminal [Y4] Function
Terminal [Y5A/C] Function
Terminal [30A/B/C] Function
(Relay output)
Data setting range
5-6
Y
Y
999
Y
Y
Y
Y
Y
Y
Y
999
Y
Y
Y
Y
Y
Drive control
V/f
PG
V/f
Refer to
page:
w/o w/ Torque
PG PG control
5-57
5-77
5-77
N
Y
0
Y
Y
Y
Y
Y
N
Y
1
Y
Y
Y
Y
N
N
Y
2
Y
Y
Y
Y
Y
N
Y
7
Y
Y
Y
Y
Y
N
Y
15
Y
Y
Y
Y
Y
N
Y
99
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
N
N
Y
Y
N
N
N
Y
Y
N
N
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
E codes
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
C codes
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
P codes
N
Y
Y
Y
Y
H codes
N
Y
Y
Y
N
FUNCTION CODES
Setting the value in parentheses ( ) shown above assigns
a negative logic output to a terminal.
Default
setting
Chap. 5
-300% to 300%; 999 (Disable)
-300% to 300%; 999 (Disable)
Selecting function code data assigns the corresponding
function to terminals [Y1] to [Y5A/C] and [30A/B/C] as
listed below.
0 (1000): Inverter running
(RUN)
1 (1001): Frequency (speed) arrival signal
(FAR)
2 (1002): Frequency (speed) detected
(FDT)
3 (1003): Undervoltage detected (Inverter stopped) (LU)
4 (1004): Torque polarity detected
(B/D)
5 (1005): Inverter output limiting
(IOL)
6 (1006): Auto-restarting after momentary power
failure
(IPF)
7 (1007): Motor overload early warning
(OL)
8 (1008): Keypad operation enabled
(KP)
10 (1010): Inverter ready to run
(RDY)
11:
Switch motor drive source between
commercial power and inverter output
(For MC on commercial line)
(SW88)
12:
Switch motor drive source between
commercial power and inverter output
(For secondary side)
(SW52-2)
13:
Switch motor drive source between
commercial power and inverter output
(For primary side)
(SW52-1)
15 (1015): Select AX terminal function
(For MC on primary side)
(AX)
22 (1022): Inverter output limiting with delay
(IOL2)
25 (1025): Cooling fan in operation
(FAN)
26 (1026): Auto-resetting
(TRY)
27 (1027): Universal DO
(U-DO)
28 (1028): Heat sink overheat early warning
(OH)
30 (1030): Lifetime alarm
(LIFE)
31 (1031): Frequency (speed) detected 2
(FDT2)
33 (1033): Reference loss detected
(REF OFF)
35 (1035): Inverter output on
(RUN2)
36 (1036): Overload prevention control
(OLP)
37 (1037): Current detected
(ID)
38 (1038): Current detected 2
(ID2)
39 (1039): Current detected 3
(ID3)
41 (1041): Low current detected
(IDL)
42 (1042): PID alarm
(PID-ALM)
43 (1043): Under PID control
(PID-CTL)
44 (1044): Motor stopped due to slow
flowrate under PID control
(PID-STP)
45 (1045): Low output torque detected
(U-TL)
46 (1046): Torque detected 1
(TD1)
47 (1047): Torque detected 2
(TD2)
48 (1048): Motor 1 selected
(SWM1)
49 (1049): Motor 2 selected
(SWM2)
50 (1050): Motor 3 selected
(SWM3)
51 (1051): Motor 4 selected
(SWM4)
52 (1052): Running forward
(FRUN)
53 (1053): Running reverse
(RRUN)
54 (1054): In remote operation
(RMT)
56 (1056): Motor overheat detected by thermistor (THM)
57 (1057): Brake signal
(BRKS)
58 (1058): Frequency (speed) detected 3
(FDT3)
59 (1059): Terminal [C1] wire break
(C1OFF)
70 (1070): Speed valid
(DNZS)
71 (1071): Speed agreement
(DSAG)
72 (1072): Frequency (speed) arrival signal 3
(FAR3)
76 (1076): PG error detected
(PG-ERR)
82 (1082): Positioning completion signal
(PSET)
84 (1084): Maintenance timer
(MNT)
98 (1098): Light alarm
(L-ALM)
99 (1099): Alarm output (for any alarm)
(ALM)
101 (1101): Enable circuit failure detected
(DECF)
102 (1102): Enable input OFF
(EN OFF)
105 (1105): Braking transistor broken
(DBAL)
111 (1111): Customizable logic output signal 1
(CLO1)
112 (1112): Customizable logic output signal 2
(CLO2)
113 (1113): Customizable logic output signal 3
(CLO3)
114 (1114): Customizable logic output signal 4
(CLO4)
115 (1115): Customizable logic output signal 5
(CLO5)
Data copying
Code
Change when
running
F codes
Y
Y
Y
Y
N
N
Y
Y
Y
N
N
N
N
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
d codes
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
U codes
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
y codes
A codes
b codes
r codes
J codes
Data copying
Change when
running
Default
setting
E30 Frequency Arrival (Hysteresis width)
E31 Frequency Detection 1
(Level)
E32
(Hysteresis width)
E34 Overload Early Warning/Current
Detection
(Level)
E35
(Timer)
E36 Frequency Detection 2
(Level)
0.0 to 10.0 Hz
0.0 to 500.0 Hz
0.0 to 500.0 Hz
0.00 (Disable); Current value of 1% to 200% of the inverter
rated current
0.01 to 600.00s
0.0 to 500.0 Hz
Y
Y
2.5
Y
Y
Y
Y
N
Y
Y
*1
Y
Y
Y
Y
N
Y
Y
1.0
Y
Y
Y
Y
N
Y
Y1 Y2
*4
Y
Y
Y
Y
Y
Y
Y
10.00
Y
Y
Y
Y
Y
Y
Y
*1
Y
Y
Y
Y
Y
5-82
5-83
E37 Current Detection 2/
Low Current Detection
(Level)
E38
(Timer)
E40 PID Display Coefficient A
E41 PID Display Coefficient B
E42 LED Display Filter
E43 LED Monitor
(Item selection)
0.00 (Disable); Current value of 1% to 200% of the inverter
rated current
0.01 to 600.00 s
-999 to 0.00 to 9990
-999 to 0.00 to 9990
0.0 to 5.0 s
0: Speed monitor (select by E48)
3: Output current
4: Output voltage
8: Calculated torque
9: Input power
10: PID command
12: PID feedback amount
14: PID output
15: Load factor
16: Motor output
17: Analog input
23: Torque current (%)
24: Magnetic flux command (%)
25: Input watt-hour
0: Specified value
1: Output value
0: Running status, rotational direction and operation guide
1: Bar charts for output frequency, current and calculated
torque
Multi-function keypad (option)
Type: OP-KP-LCD
0: Japanese
1: English
2: German
3: French
4: Spanish
5: Italian
0 (Low) to 10 (High)
0: Output frequency 1 (Before slip compensation)
1: Output frequency 2 (After slip compensation)
2: Reference frequency
3: Motor speed in r/min
4: Load shaft speed in r/min
5: Line speed in m/min
7: Display speed in %
0.01 to 200.00
0.000 (Cancel/reset), 0.001 to 9999
Y
Y1 Y2
*4
Y
Y
Y
Y
Y
5-83
Y
Y
10.00
Y
Y
Y
Y
Y
Y
Y
100
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.5
Y
Y
Y
Y
Y
5-85
Y
Y
0
Y
Y
Y
Y
Y
5-86
5-87
Code
Name
E44
(Display when stopped)
E45 LCD Monitor
(Item selection)
E46
(Language selection)
E47
E48 LED Monitor
(Contrast control)
(Speed monitor item)
Data setting range
Drive control
V/f
PG
V/f
Refer to
page:
w/o w/ Torque
PG PG control
5-82
5-83
5-84
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
1
Y
Y
Y
Y
Y
Y
Y
5
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
5-86
5-88
5-88
5-88
E50 Coefficient for Speed Indication
E51 Display Coefficient for Input
Watt-hour Data
E52 Keypad
(Menu display mode) 0: Function code data editing mode (Menus #0, #1, and
#7)
1: Function code data check mode (Menu #2 and #7)
2: Full-menu mode
E54 Frequency Detection 3
(Level) 0.0 to 500.0 Hz
Y
Y
30.00
Y
Y
Y
Y
Y
Y
Y
0.010
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
*1
Y
Y
Y
Y
Y
5-82
5-89
E55 Current Detection 3
Y
Y1 Y2
*4
Y
Y
Y
Y
Y
5-83
5-89
Y
E56
E61
E62
E63
E64
E65
E78
E79
E80
E81
(Level) 0.00 (Disable);
Current value of 1% to 200% of the inverter rated current
(Timer) 0.01 to 600.00 s
Terminal [12] Extended Function
0: None
1: Auxiliary frequency command 1
Terminal [C1] Extended Function
2: Auxiliary frequency command 2
Terminal [V2] Extended Function
3: PID command 1
5: PID feedback amount
6: Ratio setting
7: Analog torque limit value A
8: Analog torque limit value B
10: Torque command
11: Torque current command
20: Analog input monitor
Saving of Digital Reference
0: Automatic saving (when main power is turned OFF)
Frequency
key
1: Saving by pressing
Reference Loss Detection
0: Decelerate to stop, 20% to 120%, 999: Disable
Torque Detection 1
(Level) 0% to 300%
(Timer) 0.01 to 600.00 s
Torque Detection 2/
0% to 300%
Low Torque Detection
(Level)
(Timer) 0.01 to 600.00 s
The shaded function codes (
) are applicable to the quick setup.
*1 The factory default differs depending upon the shipping destination. See Table A.
*4 The motor rated current is automatically set. See Table C (function code P03).
5-7
Y
Y
10.00
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
Y
Y
Y
1
Y
Y
Y
Y
Y
Y
Y
999
Y
Y
Y
Y
Y
Y
Y
100
Y
Y
Y
Y
Y
Y
Y
10.00
Y
Y
Y
Y
Y
Y
Y
20
Y
Y
Y
Y
Y
Y
Y
20.00
Y
Y
Y
Y
Y
5-90
5-91
Name
E98 Terminal [FWD] Function
E99 Terminal [REV] Function
Data setting range
98:
Run forward
99:
Run reverse
100:
No function assigned
V/f
Refer to
page:
PG w/o w/ Torque
V/f PG PG control
5-67
5-92
N
Y
98
Y
Y
Y
Y
N
N
Y
99
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
N
N
N
Y
Y
N
N
N
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
N
N
N
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
N
N
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
N
N
Y
Y
N
N
N
N
N
N
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
N
F codes
E codes
Y
Y
N
N
Y
Y
Y
N
N
Y
Y
Y
N
N
Y
Y
Y
N
N
Y
Y
Y
Y
Y
N
N
Y
N
Y
Y
Y
Y
Y
Y
Y
C codes
P codes
Y
Y
Y
Y
Y
(FWD)
Y
Y
Y
Y
Y
(REV)
Y
Y
Y
Y
Y
(NONE)
Y
Y
Y
Y
Y
Setting the value in parentheses ( ) shown above assigns a
negative logic input to a terminal.
FUNCTION CODES
25 (1025): Universal DI
(U-DI)
26 (1026): Enable auto search for idling motor
speed at starting
(STM)
30 (1030): Force to stop
(STOP)
((30 = Active OFF, 1030 = Active ON)
32 (1032): Pre-excitation
(EXITE)
33 (1033): Reset PID integral and differential
components
(PID-RST)
34 (1034): Hold PID integral component
(PID-HLD)
35 (1035): Select local (keypad) operation
(LOC)
36 (1036): Select motor 3
(M3)
37 (1037): Select motor 4
(M4)
39:
Protect motor from dew condensation
(DWP)
40:
Enable integrated sequence to switch
to commercial power (50 Hz)
(ISW50)
41:
Enable integrated sequence to switch
to commercial power (60 Hz)
(ISW60)
47 (1047): Servo-lock command
(LOCK)
49 (1049): Pulse train sign
(SIGN)
70 (1070): Cancel constant peripheral speed
control
(Hz/LSC)
71 (1071): Hold the constant peripheral speed
control frequency in the memory
(LSC-HLD)
72 (1072): Count the run time of commercial
power-driven motor 1
(CRUN-M1)
73 (1073): Count the run time of commercial
power-driven motor 2
(CRUN-M2)
74 (1074): Count the run time of commercial
power-driven motor 3
(CRUN-M3)
75 (1075): Count the run time of commercial
power-driven motor 4
(CRUN-M4)
76 (1076): Select droop control
(DROOP)
77 (1077): Cancel PG alarm
(PG-CCL)
80 (1080): Cancel customizable logic
(CLC)
81 (1081): Clear all customizable logic timers
(CLTC)
Drive control
Default
setting
Chap. 5
Selecting function code data assigns the corresponding
function to terminals [FWD] and [REV] as listed below.
0 (1000): Select multi-frequency (0 to 1 steps)
(SS1)
1 (1001): Select multi-frequency (0 to 3 steps)
(SS2)
2 (1002): Select multi-frequency (0 to 7 steps)
(SS4)
3 (1003): Select multi-frequency (0 to 15 steps)
(SS8)
4 (1004): Select ACC/DEC time (2 steps)
(RT1)
5 (1005): Select ACC/DEC time (4 steps)
(RT2)
6 (1006): Enable 3-wire operation
(HLD)
7 (1007): Coast to a stop
(BX)
8 (1008): Reset alarm
(RST)
9 (1009): Enable external alarm trip
(THR)
(9 = Active OFF, 1009 = Active ON)
10 (1010): Ready for jogging
(JOG)
11 (1011): Select frequency command 2/1
(Hz2/Hz1)
12 (1012): Select motor 2
(M2)
13:
Enable DC braking
(DCBRK)
14 (1014): Select torque limiter level 2/1
(TL2/TL1)
15:
Switch to commercial power (50 Hz)
(SW50)
16:
Switch to commercial power (60 Hz)
(SW60)
17 (1017): UP (Increase output frequency)
(UP)
18 (1018): DOWN (Decrease output frequency) (DOWN)
19 (1019): Enable data change with keypad
(WE-KP)
20 (1020): Cancel PID control
(Hz/PID)
21 (1021): Switch normal/inverse operation
(IVS)
22 (1022): Interlock
(IL)
23 (1023): Cancel torque control
(Hz/TRQ)
24 (1024): Enable communications link via RS-485
or fieldbus
(LE)
Data copying
Code
Change when
running
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-8
C01
C02
C03
C04
C05
C06
C07
C08
C09
C10
C11
C12
C13
C14
C15
C16
C17
C18
C19
C20
C30
Name
Jump Frequency 1
2
3
(Hysteresis width)
Multi-frequency 1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Jogging Frequency
Frequency Command 2
C31 Analog Input Adjustment for [12]
(Offset)
C32
(Gain)
C33
(Filter time constant)
C34
(Gain base point)
C35
(Polarity)
C36 Analog Input Adjustment for [C1]
(Offset)
C37
(Gain)
C38
(Filter time constant)
C39
(Gain base point)
C41 Analog Input Adjustment for [V2]
(Offset)
C42
(Gain)
C43
(Filter time constant)
C44
(Gain base point)
C45
(Polarity)
C50 Bias (Frequency command 1)
(Bias base point)
C51 Bias (PID command 1) (Bias value)
C52
(Bias base point)
C53 Selection of Normal/Inverse
Operation (Frequency command 1)
Data setting range
0.0 to 500.0 Hz
0.0 to 30.0 Hz
0.00 to 500.00 Hz
0.00 to 500.00 Hz
0: Enable
/
keys on the keypad
1: Voltage input to terminal [12] (-10 to +10 VDC)
2: Current input to terminal [C1] (4 to 20 mA DC)
3: Sum of voltage and current inputs to terminals [12]
and [C1]
5: Voltage input to terminal [V2] (0 to 10 VDC)
7: Terminal command UP/DOWN control
/
keys on the keypad
8: Enable
(balanceless-bumpless switching available)
11: Digital input interface card (option)
12: Pulse train input
-5.0% to 5.0%
0.00% to 200.00%
0.00 to 5.00 s
0.00% to 100.00%
0: Bipolar 1: Unipolar
-5.0% to 5.0%
Data copying
Code
Change when
running
C codes: Control Functions of Frequency
Drive control
Default
setting
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
Y
Y
0.0
Y
Y
Y
Y
N
Y
Y
0.0
Y
Y
Y
Y
N
5-92
Y
Y
0.0
Y
Y
Y
Y
N
Y
Y
3.0
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
5-93
N
Y
2
Y
Y
Y
Y
N
5-29
5-94
Y*
Y
0.0
Y
Y
Y
Y
Y
5-94
Y*
Y
100.00
Y
Y
Y
Y
Y
Y
Y
0.05
Y
Y
Y
Y
Y
Y*
Y
100.00
Y
Y
Y
Y
Y
N
Y
1
Y
Y
Y
Y
Y
Y*
Y
0.0
Y
Y
Y
Y
Y
0.00% to 200.00%
0.00 to 5.00s
0.00% to 100.00%
-5.0% to 5.0%
Y*
Y
100.00
Y
Y
Y
Y
Y
Y
Y
0.05
Y
Y
Y
Y
Y
Y*
Y
100.00
Y
Y
Y
Y
Y
Y*
Y
0.0
Y
Y
Y
Y
Y
0.00% to 200.00%
0.00 to 5.00 s
0.00% to 100.00%
0: Bipolar 1: Unipolar
0.00% to 100.00%
Y*
Y
100.00
Y
Y
Y
Y
Y
Y
Y
0.05
Y
Y
Y
Y
Y
Y*
Y
100.00
Y
Y
Y
Y
Y
N
Y
1
Y
Y
Y
Y
Y
Y*
Y
0.00
Y
Y
Y
Y
Y
5-29
5-95
5-95
-100.00% to 100.00%
0.00% to 100.00%
0: Normal operation
1: Inverse operation
5-9
Y*
Y
0.00
Y
Y
Y
Y
Y
Y*
Y
0.00
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
5-67
5-95
Change when
running
Data copying
P codes: Motor 1 Parameters
P01 Motor 1
P02
N
Y1 Y2
4
Y
Y
Y
Y
Y
5-95
N
Y1 Y2
*7
Y
Y
Y
Y
Y
5-96
P03
P04
N
Y1 Y2
*7
Y
Y
Y
Y
Y
N
N
0
Y
Y
Y
Y
Y
Code
P23
P53
P54
P55
P56
P57
P99
(No. of poles) 2 to 22 poles
(Rated capacity) 0.01 to 1000 kW (when P99 = 0, 2, 3 or 4)
0.01 to 1000 HP (when P99 = 1)
(Rated current) 0.00 to 2000 A
(Auto-tuning) 0: Disable
1: Tune while the motor stops. (%R1, %X and rated slip
frequency)
2: Tune while the motor is rotating under V/f control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c")
3: Tune while the motor is rotating under vector control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c." Available when
the vector control is enabled.)
(No-load current) 0.00 to 2000 A
(%R1) 0.00% to 50.00%
(%X) 0.00% to 50.00%
(Slip compensation gain for driving) 0.0% to 200.0%
(Slip compensation response time) 0.01 to 10.00 s
(Slip compensation gain for braking) 0.0% to 200.0%
(Rated slip frequency) 0.00 to 15.00 Hz
(Iron loss factor 1) 0.00% to 20.00%
(Iron loss factor 2) 0.00% to 20.00%
(Iron loss factor 3) 0.00% to 20.00%
(Magnetic saturation factor 1) 0.0% to 300.0%
(Magnetic saturation factor 2) 0.0% to 300.0%
(Magnetic saturation factor 3) 0.0% to 300.0%
(Magnetic saturation factor 4) 0.0% to 300.0%
(Magnetic saturation factor 5) 0.0% to 300.0%
(Magnetic saturation extension 0.0% to 300.0%
factor "a")
(Magnetic saturation extension 0.0% to 300.0%
factor "b")
(Magnetic saturation extension 0.0% to 300.0%
factor "c")
(%X correction factor 1) 0% to 300%
(%X correction factor 2) 0% to 300%
(Torque current under vector control) 0.00 to 2000 A
(Induced voltage factor under 50% to 100%
vector control)
Reserved *9
0.000 to 20.000 s
Motor 1 Selection
0: Motor characteristics 0 (standard motors)
1: Motor characteristics 1 (HP rating motors)
2: Motor characteristics 2 (Not used)
3: Motor characteristics 3 (Not used)
4: Other motors
Drive control
Default
setting
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
N
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y*
Y
100.0
Y
Y
Y
Y
N
Y
Y1 Y2
0.12
Y
Y
N
N
N
Y*
Y
100.0
Y
Y
Y
Y
N
5-97
N
Y1 Y2
*7
Y
Y
Y
Y
N
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
5-98
Y
Y1 Y2
0.00
Y
Y
Y
Y
Y
Y
Y1 Y2
0.00
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
100
Y
Y
Y
Y
Y
Y
Y1 Y2
100
Y
Y
Y
Y
Y
N
Y1 Y2
*7
N
N
Y
Y
Y
N
Y1 Y2
85
N
N
Y
Y
Y
Y
Y1 Y2
*7
-
-
-
-
Y
N
Y1 Y2
0
Y
Y
Y
Y
Y
5-98
FUNCTION CODES
P22
Data setting range
Chap. 5
P06
P07
P08
P09
P10
P11
P12
P13
P14
P15
P16
P17
P18
P19
P20
P21
Name
F codes
Name
Data setting range
H03 Data Initialization
H04
H05
H06
H07
H08
0: Disable initialization
1: Initialize all function code data to the factory defaults
2: Initialize motor 1 parameters
3: Initialize motor 2 parameters
4: Initialize motor 3 parameters
5: Initialize motor 4 parameters
Auto-reset
(Times) 0: Disable; 1 to 10
(Reset interval) 0.5 to 20.0 s
Cooling Fan ON/OFF Control
0: Disable (Always in operation)
1: Enable (ON/OFF controllable)
Acceleration/Deceleration Pattern
0: Linear
1: S-curve (Weak)
2: S-curve (Arbitrary, according to H57 to H60 data)
3: Curvilinear
Rotational Direction Limitation
0: Disable
1: Enable (Reverse rotation inhibited)
2: Enable (Forward rotation inhibited)
Data
copying
Code
Change when
running
H codes: High Performance Functions
Default
setting
N
N
0
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
Y
Y
Y
Y
Y
5-99
C codes
P codes
H codes
A codes
Y
Y
Y
Y
Y
Y
0
5.0
0
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
N
b codes
5-100
r codes
5-38
5-101
J codes
d codes
N
Y
0
Y
The shaded function codes (
) are applicable to the quick setup.
*7 The motor parameters are automatically set, depending upon the inverter's capacity and shipping destination. See Table C.
*9 These function codes are reserved for particular manufacturers. Unless otherwise specified, do not access these function codes.
5-10
E codes
Drive control
Y
Y
Y
N
5-101
U codes
y codes
Change when
running
Data
copying
Default
setting
H09 Starting Mode
N
Y
0
Y
Y
N
N
N
5-101
H11
H12
Y
Y
Y
Y
0
1
Y
Y
Y
Y
Y
N
Y
N
N
N
5-102
5-64
5-102
Y
Y1 Y2
*3
Y
Y
Y
Y
N
5-43
5-102
Y
Y
999
Y
Y
Y
N
N
Y
Y2
235
470
Y
Y
Y
Y
N
Y
Y
999
Y
Y
Y
Y
N
N
Y
0
N
N
Y
Y
Y
5-103
Y
Y
0
Y
Y
Y
Y
Y
5-104
Y
Y
0.35
Y
Y
Y
Y
Y
Y
Y
0.0
Y
Y
Y
Y
N
Y
Y
0
Y
Y
Y
Y
Y
Y
N
-
Y
Y
Y
Y
Y
Y
N
-
Y
Y
Y
Y
Y
Y
N
-
Y
Y
Y
Y
Y
5-108
Y
N
0
Y
Y
Y
Y
Y
5-109
Y
Y1 Y2
*7
Y
Y
Y
N
Y
5-101
5-109
Y
N
-
Y
Y
Y
Y
Y
5-107
5-109
Y
N
-
Y
Y
Y
Y
Y
Y
Y
0.0
Y
Y
Y
Y
Y
N
Y
*8
Y
Y
N
N
N
5-36
N
Y2
*8
Y
Y
N
N
N
5-109
N
Y
0.0
Y
Y
N
N
N
N
Y2
0
Y
Y
N
N
N
Y
Y
*2
Y
Y
Y
Y
N
5-38
Y
Y
*2
Y
Y
Y
Y
N
5-109
Y
Y
*2
Y
Y
Y
Y
N
Y
Y
10
Y
Y
Y
Y
N
Y
Y
10
Y
Y
Y
Y
N
Y
Y
10
Y
Y
Y
Y
N
Y
Y
10
Y
Y
Y
Y
N
Code
H13
H14
H15
H16
H18
H26
H27
H28
H30
H42
H43
H44
H45
H46
H47
H48
H49
H50
H51
H52
H53
H54
H55
H56
H57
H58
H59
H60
*2
*3
*7
*8
Name
Data setting range
(Auto search) 0: Disable
1: Enable (At restart after momentary power failure)
2: Enable (At restart after momentary power failure and at
normal start)
Deceleration Mode
0: Normal deceleration 1: Coast-to-stop
Instantaneous Overcurrent Limiting 0: Disable
(Mode selection) 1: Enable
Restart Mode after Momentary
0.1 to 10.0 s
Power Failure
(Restart time)
(Frequency fall rate) 0.00: Deceleration time selected by F08,
0.01 to 100.00 Hz/s, 999: Follow the current limit command
(Continuous running level) 200 to 300 V for 200 V class series
400 to 600 V for 400 V class series
(Allowable momentary power 0.0 to 30.0 s
failure time) 999: Automatically determined by inverter
Torque Limiter
(Mode selection) 0: Disable (Speed control)
2: Enable (Torque current command)
3: Enable (Torque command)
Thermistor (for motor)
0: Disable
(Mode selection) 1: PTC (The inverter immediately trips with K
displayed.)
2: PTC (The inverter issues output signal THM and
continues to run.)
3: NTC (When connected)
(Level) 0.00 to 5.00 V
Droop Control
-60.0 to 0.0 Hz
Communications Link Function
Frequency command
Run command
(Mode selection) 0: F01/C30
F02
1: RS-485 (Port 1)
F02
2: F01/C30
RS-485 (Port 1)
3: RS-485 (Port 1)
RS-485 (Port 1)
4: RS-485 (Port 2)
F02
5: RS-485 (Port 2)
RS-485 (Port 1)
6: F01/C30
RS-485 (Port 2)
7: RS-485 (Port 1)
RS-485 (Port 2)
8: RS-485 (Port 2)
RS-485 (Port 2)
Capacitance of DC Link Bus
Indication for replacement of DC link bus capacitor
Capacitor
0000 to FFFF (hex.)
Cumulative Run Time of Cooling Fan Indication for replacement of cooling fan
(in units of 10 hours)
Startup Counter for Motor 1
Indication of cumulative startup count
0000 to FFFF (hex.)
Mock Alarm
0: Disable
1: Enable (Once a mock alarm occurs, the data
automatically returns to 0.)
Starting Mode
0.1 to 10.0 s
(Auto search delay time 2)
Initial Capacitance of DC Link Bus
Indication for replacement of DC link bus capacitor
Capacitor
0000 to FFFF (hex.)
Cumulative Run Time of Capacitors Indication for replacement of capacitors
on Printed Circuit Boards
(The cumulative run time can be modified or reset in units
of 10 hours.)
Starting Mode
0.0 to 10.0 s
(Auto search delay time 1)
Non-linear V/f Pattern 1 (Frequency) 0.0: Cancel, 0.1 to 500.0 Hz
(Voltage) 0 to 240: Output an AVR-controlled voltage
(for 200 V class series)
0 to 500: Output an AVR-controlled voltage
(for 400 V class series)
Non-linear V/f Pattern 2 (Frequency) 0.0: Cancel, 0.1 to 500.0 Hz
(Voltage) 0 to 240: Output an AVR-controlled voltage
(for 200 V class series)
0 to 500: Output an AVR-controlled voltage
(for 400 V class series)
Acceleration Time
(Jogging) 0.00 to 6000 s
Deceleration Time
(Jogging) 0.00 to 6000 s
Deceleration Time for Forced Stop
0.00 to 6000 s
1st S-curve acceleration range
0% to 100%
(Leading edge)
2nd S-curve acceleration range
0% to 100%
(Trailing edge)
1st S-curve deceleration range
0% to 100%
(Leading edge)
2nd S-curve deceleration range
0% to 100%
(Trailing edge)
Drive control
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
5-105
5-107
5-101
5-109
6.00 s for inverters with a capacity of 22 kW or below; 20.00 s for those with 30 kW or above
The factory default differs depending upon the inverter's capacity. See Table B.
The motor parameters are automatically set, depending upon the inverter's capacity and shipping destination. See Table C.
The factory default differs depending upon the inverter's capacity. See the table under "„ Non-linear V/f Patterns 1, 2 and 3 for Voltage" in the description
of F04.
5-11
Data setting range
Default
setting
N
Y
1
Y
Y
Y
Y
N
5-29
5-109
Y
Y
0
Y
Y
Y
Y
N
5-49
5-109
Y
Y
1.6
Y
Y
N
N
N
5-109
N
Y
0.0
Y
Y
N
N
N
5-36
N
Y2
0
Y
Y
N
N
N
5-109
Y
Y
0
Y
Y
N
Y
N
5-55
5-109
N
Y
0
Y
Y
N
N
N
5-62
5-109
Y
Y
0
Y
Y
Y
Y
N
5-109
Y
Y
999
Y
Y
Y
Y
N
5-110
Y
Y
0
Y
Y
N
N
N
Y
Y
1
Y
Y
Y
Y
Y
5-111
N
Y
0
Y
Y
Y
Y
Y
5-57
5-111
N
Y
1
N
N
Y
Y
Y
N
Y
0
N
N
Y
Y
Y
Y
Y
5.0
Y
Y
N
N
N
5-109
5-111
Y
N
-
Y
Y
Y
Y
Y
5-111
Y
N
8760
Y
Y
Y
Y
Y
5-108
Y
N
0
Y
Y
Y
Y
Y
5-111
Y
Y
0.20
*10
Y
Y
N
N
Y
5-111
Y
Y
0
Y
Y
Y
Y
Y
5-112
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
100
N
N
Y
Y
Y
Y
Y
0.00
N
N
Y
Y
Y
Y
Y1Y2
-
-
-
-
-
Drive control
V/f
Y
Y
25.0
-
-
-
-
-
Y
N
0
-
-
-
-
-
Y
Y
0
-
-
-
-
-
Y
Y
0
-
-
-
-
-
Y
Y
0.0
Y
Y
Y
Y
N
Y
Y1Y2
999
Y
Y
Y
Y
Y
Y1Y2
999
Y
Y
Y
Y
N
N
-
Y
Y
Y
Y
Y
1
Y
Y
Y
Y
0
Y
Y
*9 These function codes are reserved for particular manufacturers. Unless otherwise specified, do not access these function codes.
*10 0.10 for 200 V class series of inverters with a capacity of 37 kW or above.
*11 2 for 200 V class series of inverters with a capacity of 37 kW or above.
5-12
FUNCTION CODES
0 *11
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
Chap. 5
H61 UP/DOWN Control
0: 0.00 Hz
(Initial frequency setting) 1: Last UP/DOWN command value on releasing the run
command
H63 Low Limiter
(Mode selection) 0: Limit by F16 (Frequency limiter: Low) and continue to
run
1: If the output frequency lowers below the one limited by
F16 (Frequency limiter: Low), decelerate to stop the
motor.
H64
(Lower limiting frequency) 0.0: Depends on F16 (Frequency limiter, Low)
0.1 to 60.0 Hz
H65 Non-linear V/f Pattern 3 (Frequency) 0.0: Cancel, 0.1 to 500.0 Hz
H66
(Voltage) 0 to 240: Output an AVR-controlled voltage
(for 200 V class series)
0 to 500: Output an AVR-controlled voltage
(for 400 V class series)
H67 Auto Energy Saving Operation
0: Enable during running at constant speed
(Mode selection) 1: Enable in all modes
H68 Slip Compensation 1
0: Enable during ACC/DEC and at base frequency or
(Operating conditions)
above
1: Disable during ACC/DEC and enable at base frequency
or above
2: Enable during ACC/DEC and disable at base frequency
or above
3: Disable during ACC/DEC and at base frequency or
above
H69 Automatic Deceleration
0: Disable
(Mode selection) 2: Torque limit control with Force-to-stop if actual
deceleration time exceeds three times the specified one
3: DC link bus voltage control with Force-to-stop if actual
deceleration time exceeds three times the specified one
4: Torque limit control with Force-to-stop disabled
5: DC link bus voltage control with Force-to-stop disabled
H70 Overload Prevention Control
0.00: Follow the deceleration time selected
0.01 to 100.0 Hz/s
999: Cancel
H71 Deceleration Characteristics
0: Disable
1: Enable
H72 Main Power Down Detection
0: Disable
1: Enable
(Mode selection)
H73 Torque Limiter
0: Enable during ACC/DEC and running at constant speed
(Operating conditions) 1: Disable during ACC/DEC and enable during running at
constant speed
2: Enable during ACC/DEC and disable during running at
constant speed
H74
(Control target) 0: Motor-generating torque limit
1: Torque current limit
2: Output power limit
H75
(Target quadrants) 0: Drive/brake
1: Same for all four quadrants
2: Upper/lower limits
H76
(Frequency increment limit 0.0 to 500.0 Hz
for braking)
H77 Service Life of DC Link Bus
0 to 8760 (in units of 10 hours)
Capacitor
(Remaining time)
H78 Maintenance Interval (M1)
0: Disable; 1 to 9999 (in units of 10 hours)
H79 Preset Startup Count for
0000: Disable; 0001 to FFFF (hex.)
Maintenance (M1)
H80 Output Current Fluctuation Damping 0.00 to 0.40
Gain for Motor 1
H81 Light Alarm Selection 1
0000 to FFFF (hex.)
H82 Light Alarm Selection 2
0000 to FFFF (hex.)
H84 Pre-excitation
(Initial level) 100% to 400%
H85
(Time) 0.00: Disable; 0.01 to 30.00 s
H86 Reserved *9
0 to 2
H87 Reserved *9
25.0 to 500.0 Hz
H88 Reserved *9
0 to 3; 999
H89 Reserved *9
0, 1
H90 Reserved *9
0, 1
H91 PID Feedback Wire Break Detection 0.0: Disable alarm detection
0.1 to 60.0 s
H92 Continuity of Running
(P) 0.000 to 10.000 times; 999
H93
(I) 0.010 to 10.000 s; 999
H94 Cumulative Motor Run Time 1
0 to 9999 (The cumulative run time can be modified or reset
in units of 10 hours.)
H95 DC Braking
0: Slow
(Braking response mode) 1: Quick
H96 STOP Key Priority/
Data STOP key priority
Start check function
Start Check Function
0:
Disable
Disable
1:
Enable
Disable
2:
Disable
Enable
3:
Enable
Enable
Data
copying
Name
Change when
running
Code
F codes
E codes
C codes
5-114
P codes
H codes
A codes
5-115
b codes
N
5-43
N
5-115
r codes
Y
Y
5-108
5-115
J codes
N
N
N
5-49
5-115
d codes
Y
Y
Y
5-115
U codes
y codes
H97 Clear Alarm Data
0: Disable
1: Enable (Setting "1" clears alarm data and then returns to
"0.")
H98 Protection/Maintenance Function
0 to 255: Display data in decimal format
(Mode selection) Bit 0: Lower the carrier frequency automatically
(0: Disabled; 1: Enabled)
Bit 1: Detect input phase loss
(0: Disabled; 1: Enabled)
Bit 2: Detect output phase loss (0: Disabled; 1: Enabled)
Bit 3: Select life judgment threshold of DC link bus
capacitor
(0: Factory default level; 1: User setup level)
Bit 4: Judge the life of DC link bus capacitor
(0: Disabled; 1: Enabled)
Bit 5: Detect DC fan lock
(0: Enabled; 1: Disabled)
Bit 6: Detect braking transistor error
(for 22 kW or below)
(0: Disabled; 1: Enabled)
Bit 7: Switch IP20/IP40 enclosure
(0: IP20; 1: IP40)
Data
copying
Data setting range
Default
setting
Y
N
0
Y
Y
Y
Y
Y
Y
Y
83
Y
Y
Y
Y
Y
Data copying
Name
Change when
running
Code
Change when
running
Default
setting
Drive control
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
5-115
A codes: Motor 2 Parameters
Code
Name
Data setting range
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
A01 Maximum Frequency 2
A02 Base Frequency 2
A03 Rated Voltage at Base Frequency 2
N
Y
*1
Y
Y
Y
Y
Y
N
Y
50.0
Y
Y
Y
Y
Y
N
Y2
*1
Y
Y
Y
Y
Y
A04
N
Y2
*1
Y
Y
N
N
Y
Y
Y
*3
Y
Y
N
N
N
Y
Y
1
Y
Y
Y
Y
Y
Y
Y1 Y2
*4
Y
Y
Y
Y
Y
Y
Y
*5
Y
Y
Y
Y
Y
Y
Y
0.0
Y
Y
Y
Y
N
Y
Y
0
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.5
Y
Y
Y
Y
N
N
Y
1
Y
Y
N
Y
N
N
Y
0
Y
Y
Y
Y
Y
N
Y1 Y2
4
Y
Y
Y
Y
Y
N
Y1 Y2
*7
Y
Y
Y
Y
Y
N
Y1 Y2
*7
Y
Y
Y
Y
Y
A05
A06
A07
A08
A09
A10
A11
A12
A13
A14
A15
A16
A17
*1
*3
*4
*5
*7
25.0 to 500.0 Hz
25.0 to 500.0 Hz
0: Output a voltage in proportion to input voltage
80 to 240: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500: Output an AVR-controlled voltage
(for 400 V class series)
Maximum Output Voltage 2
80 to 240: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500: Output an AVR-controlled voltage
(for 400 V class series)
Torque Boost 2
0.0% to 20.0%
(percentage with respect to "A03: Rated Voltage at Base
Frequency 2")
Electronic Thermal Overload
1: For a general-purpose motor with shaft-driven cooling
Protection for Motor 2
fan
(Select motor characteristics) 2: For an inverter-driven motor, non-ventilated motor, or
motor with separately powered cooling fan
(Overload detection level) 0.00: Disable
1% to 135% of the rated current (allowable continuous drive
current) of the motor
(Thermal time constant) 0.5 to 75.0 min
DC Braking 2
0.0 to 60.0 Hz
(Braking starting frequency)
(Braking level) 0% to 100% (CT mode), 0% to 80% (MT/VT mode)
(Braking time) 0.00: Disable; 0.01 to 30.00 s
Starting Frequency 2
0.0 to 60.0 Hz
Load Selection/
0: Variable torque load
Auto Torque Boost
1: Constant torque load
Auto Energy Saving Operation 2
2: Auto-torque boost
3: Auto-energy saving operation
(Variable torque load during ACC/DEC)
4: Auto-energy saving operation
(Constant torque load during ACC/DEC)
5: Auto-energy saving operation
(Auto-torque boost during ACC/DEC)
Drive Control Selection 2
0: V/f control with slip compensation inactive
1: Dynamic torque vector control
2: V/f control with slip compensation active
3: V/f control with speed sensor
4: Dynamic torque vector control with speed sensor
5: Vector control without speed sensor
6: Vector control with speed sensor
Motor 2
(No. of poles) 2 to 22 poles
(Rated capacity) 0.01 to 1000 kW (when A39 = 0, 2. 3 or 4)
0.01 to 1000 HP (when A39 = 1)
(Rated current) 0.00 to 2000 A
Drive control
The factory default differs depending upon the shipping destination. See Table A.
The factory default differs depending upon the inverter's capacity. See Table B.
The motor rated current is automatically set. See Table C (function code P03).
5.0 min for inverters with a capacity of 22 kW or below; 10.0 min for those with 30 kW or above
The motor parameters are automatically set, depending upon the inverter's capacity and shipping destination. See Table C.
5-13
Change when
running
Data copying
Default
setting
A18 Motor 2
N
N
0
A20
A21
A22
A23
A24
A25
A26
A27
A28
A29
A30
A31
A32
A33
A34
A35
N
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Code
A39
A40
A41
A42
A43
A44
A45
A46
A48
A49
A50
A51
A52
A53
A54
A55
A56
A57
(Auto-tuning) 0: Disable
1: Tune while the motor stops. (%R1, %X and rated slip
frequency)
2: Tune while the motor is rotating under V/f control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c")
3: Tune while the motor is rotating under vector control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c." Available when
the vector control is enabled.
(No-load current) 0.00 to 2000 A
(%R1) 0.00% to 50.00%
(%X) 0.00% to 50.00%
(Slip compensation gain for driving) 0.0% to 200.0%
(Slip compensation response time) 0.01 to 10.00s
(Slip compensation gain for braking) 0.0% to 200.0%
(Rated slip frequency) 0.00 to 15.00 Hz
(Iron loss factor 1) 0.00% to 20.00%
(Iron loss factor 2) 0.00% to 20.00%
(Iron loss factor 3) 0.00% to 20.00%
(Magnetic saturation factor 1) 0.0% to 300.0%
(Magnetic saturation factor 2) 0.0% to 300.0%
(Magnetic saturation factor 3) 0.0% to 300.0%
(Magnetic saturation factor 4) 0.0% to 300.0%
(Magnetic saturation factor 5) 0.0% to 300.0%
(Magnetic saturation extension 0.0% to 300.0%
factor "a")
(Magnetic saturation extension 0.0% to 300.0%
factor "b")
(Magnetic saturation extension 0.0% to 300.0%
factor "c")
Motor 2 Selection
0: Motor characteristics 0 (Standard motors)
1: Motor characteristics 1 (HP rating motors)
2: Motor characteristics 2 (Not used)
3: Motor characteristics 3 (Not used)
4: Other motors
Slip Compensation 2
0: Enable during ACC/DEC and at base frequency or
(Operating conditions)
above
1: Disable during ACC/DEC and enable at base frequency
or above
2: Enable during ACC/DEC and disable at base frequency
or above
3: Disable during ACC/DEC and at base frequency or
above
Output Current Fluctuation Damping 0.00 to 0.40
Gain for Motor 2
Motor/Parameter Switching 2
0: Motor (Switch to the 2nd motor)
(Mode selection) 1: Parameter (Switch to particular A codes)
Speed Control 2
0.000 to 5.000 s
(Speed command filter)
(Speed detection filter) 0.000 to 0.100 s
P (Gain) 0.1 to 200.0 times
I (Integral time) 0.001 to 9.999 s
(Output filter) 0.000 to 0.100 s
(Notch filter resonance frequency) 1 to 200 Hz
(Notch filter attenuation level) 0 to 20 dB
Cumulative Motor Run Time 2
0 to 9999 (The cumulative run time can be modified or reset
in units of 10 hours.)
Startup Counter for Motor 2
Indication of cumulative startup count
0000 to FFFF (hex.)
Motor 2
(%X correction factor 1) 0% to 300%
(%X correction factor 2) 0% to 300%
(Torque current under vector control) 0.00 to 2000 A
(Induced voltage factor under 50 to 100
vector control)
Reserved *9
0.000 to 20.000 s
Drive control
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y*
Y
100.0
Y
Y
Y
Y
N
Y
Y1 Y2
0.12
Y
Y
N
N
N
Y*
Y
100.0
Y
Y
Y
Y
N
N
N
Y1 Y2
*7
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
0.00
Y
Y
Y
Y
Y
Y
Y1 Y2
0.00
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
N
Y1 Y2
0
Y
Y
Y
Y
Y
N
Y
0
Y
Y
N
N
N
Y
Y
0.20
Y
Y
N
N
N
N
Y
0
Y
Y
Y
Y
Y
5-117
Y
Y
0.020
N
Y
Y
Y
N
Y*
Y
0.005
N
Y
Y
Y
N
Y*
Y
10.0
N
Y
Y
Y
N
Y*
Y
0.100
N
Y
Y
Y
N
Y
Y
0.002
N
Y
Y
Y
N
Y
Y
200
N
N
N
Y
N
Y
Y
0
N
N
N
Y
N
N
N
-
Y
Y
Y
Y
Y
Y
N
-
Y
Y
Y
Y
Y
Y
Y1 Y2
100
Y
Y
Y
Y
Y
Y
Y1 Y2
100
Y
Y
Y
Y
Y
N
Y1 Y2
*7
N
N
Y
Y
Y
N
Y1 Y2
85
N
N
Y
Y
Y
Y
Y1 Y2
*7
-
-
-
-
-
*7 The motor parameters are automatically set, depending upon the inverter's capacity and shipping destination. See Table C.
*9 These function codes are reserved for particular manufacturers. Unless otherwise specified, do not access these function codes.
FUNCTION CODES
A37
Data setting range
Chap. 5
A36
Name
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-14
Name
Data setting range
Drive control
Default
setting
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
b01 Maximum Frequency 3
b02 Base Frequency 3
b03 Rated Voltage at Base Frequency 3
N
Y
*1
Y
Y
Y
Y
Y
N
Y
50.0
Y
Y
Y
Y
Y
N
Y2
*1
Y
Y
Y
Y
Y
b04
N
Y2
*1
Y
Y
N
N
Y
Y
Y
*3
Y
Y
N
N
N
Y
Y
1
Y
Y
Y
Y
Y
Y
Y1 Y2
*4
Y
Y
Y
Y
Y
Y
Y
*5
Y
Y
Y
Y
Y
Y
Y
0.0
Y
Y
Y
Y
N
Y
Y
0
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.5
Y
Y
Y
Y
N
N
Y
1
Y
Y
N
Y
N
N
Y
0
Y
Y
Y
Y
Y
N
Y1 Y2
4
Y
Y
Y
Y
Y
N
Y1 Y2
*7
Y
Y
Y
Y
Y
N
Y1 Y2
*7
Y
Y
Y
Y
Y
N
N
0
Y
Y
Y
Y
Y
b05
b06
b07
b08
b09
b10
b11
b12
b13
b14
b15
b16
b17
b18
b20
b21
b22
b23
b24
b25
b26
b27
b28
b29
b30
b31
b32
b33
b34
*1
*3
*4
*5
*7
25.0 to 500.0 Hz
25.0 to 500.0 Hz
0: Output a voltage in proportion to input voltage
80 to 240: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500: Output an AVR-controlled voltage
(for 400 V class series)
Maximum Output Voltage 3
80 to 240: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500: Output an AVR-controlled voltage
(for 400 V class series)
Torque Boost 3
0.0% to 20.0%
(percentage with respect to "b03: Rated Voltage at Base
Frequency 3")
Electric Thermal Overload
1: For a general-purpose motor with shaft-driven cooling
Protection for Motor 3
fan
(Select motor characteristics) 2: For an inverter-driven motor, non-ventilated motor, or
motor with separately powered cooling fan
(Overload detection level) 0.00: Disable
1% to 135% of the rated current (allowable continuous drive
current) of the motor
(Thermal time constant) 0.5 to 75.0 min
DC Braking 3
0.0 to 60.0 Hz
(Braking starting frequency)
(Braking level) 0% to 100% (CT mode), 0% to 80% (MT/VT mode)
(Braking time) 0.00: Disable; 0.01 to 30.00 s
Starting Frequency 3
0.0 to 60.0 Hz
Load Selection/
0: Variable torque load
Auto Torque Boost/
1: Constant torque load
Auto Energy Saving Operation 3
2: Auto-torque boost
3: Auto-energy saving operation
(Variable torque load during ACC/DEC)
4: Auto-energy saving operation
(Constant torque load during ACC/DEC)
5: Auto-energy saving operation
(Auto-torque boost during ACC/DEC)
Drive Control Selection 3
0: V/f control with slip compensation inactive
1: Dynamic torque vector control
2: V/f control with slip compensation active
3: V/f control with speed sensor
4: Dynamic torque vector control with speed sensor
5: Vector control without speed sensor
6: Vector control with speed sensor
Motor 3
(No. of poles) 2 to 22 poles
(Rated capacity) 0.01 to 1000 kW (when b39 = 0, 2, 3 or 4)
0.01 to 1000 HP (when b39 = 1)
(Rated current) 0.00 to 2000 A
(Auto-tuning) 0: Disable
1: Tune while the motor stops. (%R1, %X and rated slip
frequency)
2: Tune while the motor is rotating under V/f control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c")
3: Tune while the motor is rotating under vector control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c." Available when
the vector control is enabled.)
(No-load current) 0.00 to 2000 A
(%R1) 0.00% to 50.00%
(%X) 0.00% to 50.00%
(Slip compensation gain for driving) 0.0% to 200.0%
(Slip compensation response time) 0.01 to 10.00 s
(Slip compensation gain for braking) 0.0% to 200.0%
(Rated slip frequency) 0.00 to 15.00 Hz
(Iron loss factor 1) 0.00% to 20.00%
(Iron loss factor 2) 0.00% to 20.00%
(Iron loss factor 3) 0.00% to 20.00%
(Magnetic saturation factor 1) 0.0% to 300.0%
(Magnetic saturation factor 2) 0.0% to 300.0%
(Magnetic saturation factor 3) 0.0% to 300.0%
(Magnetic saturation factor 4) 0.0% to 300.0%
(Magnetic saturation factor 5) 0.0% to 300.0%
Data copying
Code
Change when
running
b codes: Motor 3 Parameters
N
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y*
Y
100.0
Y
Y
Y
Y
N
Y
Y1 Y2
0.12
Y
Y
N
N
N
Y*
Y
100.0
Y
Y
Y
Y
N
N
N
Y1 Y2
*7
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
0.00
Y
Y
Y
Y
Y
Y
Y1 Y2
0.00
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
The factory default differs depending upon the shipping destination. See Table A.
The factory default differs depending upon the inverter's capacity. See Table B.
The motor rated current is automatically set. See Table C (function code P03).
5.0 min for inverters with a capacity of 22 kW or below; 10.0 min for those with 30 kW or above
The motor parameters are automatically set, depending upon the inverter's capacity and shipping destination. See Table C.
5-15
Change when
running
Data copying
Default
setting
0.0% to 300.0%
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
0.0% to 300.0%
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
0.0% to 300.0%
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
0:
1:
2:
3:
4:
0:
N
Y1 Y2
0
Y
Y
Y
Y
Y
N
Y
0
Y
Y
N
N
N
Y
Y
0.20
Y
Y
N
N
N
N
Y
0
Y
Y
Y
Y
Y
5-117
Y
Y
0.020
N
Y
Y
Y
N
Y*
Y
0.005
N
Y
Y
Y
N
Y*
Y
10.0
N
Y
Y
Y
N
Y*
Y
0.100
N
Y
Y
Y
N
Y
Y
0.002
N
Y
Y
Y
N
Y
Y
200
N
N
N
Y
N
b40
b43
b44
b45
b46
b48
b49
b50
b51
b52
b53
b54
b55
b56
b57
Y
Y
0
N
N
N
Y
N
N
N
-
Y
Y
Y
Y
Y
Y
N
-
Y
Y
Y
Y
Y
Y
Y1 Y2
100
Y
Y
Y
Y
Y
Y
Y1 Y2
100
Y
Y
Y
Y
Y
N
Y1 Y2
*7
N
N
Y
Y
Y
N
Y1 Y2
85
N
N
Y
Y
Y
Y
Y1 Y2
*7
-
-
-
-
-
Default
setting
FUNCTION CODES
b42
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
Chap. 5
b41
Motor characteristics 0 (Standard motors)
Motor characteristics 1 (HP rating motors)
Motor characteristics 2 (Not used)
Motor characteristics 3 (Not used)
Other motors
Slip Compensation 3
Enable during ACC/DEC and at base frequency or
(Operating conditions)
above
1: Disable during ACC/DEC and enable at base frequency
or above
2: Enable during ACC/DEC and disable at base frequency
or above
3: Disable during ACC/DEC and at base frequency or
above
Output Current Fluctuation Damping 0.00 to 0.40
Gain for Motor 3
Motor/Parameter Switching 3
0: Motor (Switch to the 3rd motor)
(Mode selection) 1: Parameter (Switch to particular b codes)
Speed Control 3
0.000 to 5.000 s
(Speed command filter)
(Speed detection filter) 0.000 to 0.100 s
P (Gain) 0.1 to 200.0 times
I (Integral time) 0.001 to 9.999 s
(Output filter) 0.000 to 0.100 s
(Notch filter resonance frequency) 1 to 200 Hz
(Notch filter attenuation level) 0 to 20 dB
Cumulative Motor Run Time 3
0 to 9999 (The cumulative run time can be modified or reset
in units of 10 hours.)
Startup Counter for Motor 3
Indication of cumulative startup count
0000 to FFFF (hex.)
Motor 3
(%X correction factor 1) 0% to 300%
(%X correction factor 2) 0% to 300%
(Torque current under vector control) 0.00 to 2000 A
(Induced voltage factor under 50 to 100
vector control)
Reserved *9
0.000 to 20.000 s
Drive control
Data copying
b35 Motor 3
(Magnetic saturation extension
factor "a")
b36
(Magnetic saturation extension
factor "b")
b37
(Magnetic saturation extension
factor "c")
b39 Motor 3 Selection
Data setting range
Change when
running
Name
r codes: Motor 4 Parameters
Code
Name
Data setting range
r01 Maximum Frequency 4
r02 Base Frequency 4
r03 Rated Voltage at Base Frequency 4
r04
r05
r06
r07
r08
*1
*3
*4
*5
*7
*9
25.0 to 500.0 Hz
25.0 to 500.0 Hz
0: Output a voltage in proportion to input voltage
80 to 240: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500: Output an AVR-controlled voltage
(for 400 V class series)
Maximum Output Voltage 4
80 to 240: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500: Output an AVR-controlled voltage
(for 400 V class series)
Torque Boost 4
0.0% to 20.0%
(percentage with respect to "r03: Rated Voltage at Base
Frequency 4")
Electronic Thermal Overload
1: For a general-purpose motor with shaft-driven cooling
Protection for Motor 4
fan
(Select motor characteristics) 2: For an inverter-driven motor, non-ventilate*d motor, or
motor with separately powered cooling fan
(Overload detection level) 0.00: Disable
1% to 135% of the rated current (allowable continuous drive
current) of the motor
(Thermal time constant) 0.5 to 75.0 min
Drive control
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
N
Y
*1
Y
Y
Y
Y
Y
N
Y
50.0
Y
Y
Y
Y
Y
N
Y2
*1
Y
Y
Y
Y
Y
F codes
E codes
C codes
N
Y2
*1
Y
Y
N
N
Y
P codes
Y
Y
*3
Y
Y
N
N
N
Y
Y
1
Y
Y
Y
Y
Y
H codes
A codes
b codes
Y
Y1 Y2
*4
Y
Y
Y
Y
Y
Y
Y
*5
Y
Y
Y
Y
Y
r codes
J codes
The factory default differs depending upon the shipping destination. See Table A.
The factory default differs depending upon the inverter's capacity. See Table B.
The motor rated current is automatically set. See Table C (function code P03).
5.0 min for inverters with a capacity of 22 kW or below; 10.0 min for those with 30 kW or above
The motor parameters are automatically set, depending upon the inverter's capacity and shipping destination. See Table C.
These function codes are reserved for particular manufacturers. Unless otherwise specified, do not access these function codes.
5-16
d codes
U codes
y codes
r20
r21
r22
r23
r24
r25
r26
r27
r28
r29
r30
r31
r32
r33
r34
r35
0% to 100% (CT mode), 0% to 80% (MT/VT mode)
0.00: Disable; 0.01 to 30.00 s
0.0 to 60.0 Hz
0: Variable torque load
1: Constant torque load
2: Auto-torque boost
3: Auto-energy saving operation
(Variable torque load during ACC/DEC)
4: Auto-energy saving operation
(Constant torque load during ACC/DEC)
5: Auto-energy saving operation
(Auto-torque boost during ACC/DEC)
0: V/f control with slip compensation inactive
1: Dynamic torque vector control
2: V/f control with slip compensation active
3: V/f control with speed sensor
4: Dynamic torque vector control with speed sensor
5: Vector control without speed sensor
6: Vector control with speed sensor
2 to 22 poles
0.01 to 1000 kW (when r39 = 0, 2, 3 or 4)
0.01 to 1000 HP (when r39 = 1)
0.00 to 2000 A
0: Disable
1: Tune while the motor stops. (%R1, %X and rated slip
frequency)
2: Tune while the motor is rotating under V/f control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c")
3: Tune while the motor is rotating under vector control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c." Available when
the vector control is enabled.)
0.00 to 2000 A
0.00% to 50.00%
0.00% to 50.00%
0.0% to 200.0%
0.01 to 10.00 s
0.0% to 200.0%
0.00 to 15.00 Hz
0.00% to 20.00%
0.00% to 20.00%
0.00% to 20.00%
0.0% to 300.0%
0.0% to 300.0%
0.0% to 300.0%
0.0% to 300.0%
0.0% to 300.0%
0.0% to 300.0%
Y
Y
(No. of poles)
(Rated capacity)
(Rated current)
(Auto-tuning)
(No-load current)
(%R1)
(%X)
(Slip compensation gain for driving)
(Slip compensation response time)
(Slip compensation gain for braking)
(Rated slip frequency)
(Iron loss factor 1)
(Iron loss factor 2)
(Iron loss factor 3)
(Magnetic saturation factor 1)
(Magnetic saturation factor 2)
(Magnetic saturation factor 3)
(Magnetic saturation factor 4)
(Magnetic saturation factor 5)
(Magnetic saturation extension
factor "a")
r36
(Magnetic saturation extension 0.0% to 300.0%
factor "b")
r37
(Magnetic saturation extension 0.0% to 300.0%
factor "c")
r39 Motor 4 Selection
0: Motor characteristics 0 (Standard motors)
1: Motor characteristics 1 (HP rating motors)
2: Motor characteristics 2 (Not used)
3: Motor characteristics 3 (Not used)
4: Other motors
r40 Slip Compensation 4
0: Enable during ACC/DEC and at base frequency or above
(Operating conditions) 1: Disable during ACC/DEC and enable at base frequency
or above
2: Enable during ACC/DEC and disable at base frequency
or above
3: Disable during ACC/DEC and at base frequency or
above
r41 Output Current Fluctuation Damping 0.00 to 0.40
Gain for Motor 4
r42 Motor/Parameter Switching 4
0: Motor (Switch to the 4th motor)
(Mode selection) 1: Parameter (Switch to particular r codes)
Data copying
Y
Data setting range
r14 Drive Control Selection 4
r17
r18
0.0 to 60.0 Hz
Name
r09 DC Braking 4
(Braking starting frequency)
r10
(Braking level)
r11
(Braking time)
r12 Starting Frequency 4
r13 Load Selection/
Auto Torque Boost/
Auto Energy Saving Operation 4
r15 Motor 4
r16
Change when
running
Code
Default
setting
Y
0.0
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
N
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.5
Y
Y
Y
Y
N
N
Y
1
Y
Y
N
Y
N
N
Y
0
Y
Y
Y
Y
Y
N
Y1 Y2
4
Y
Y
Y
Y
Y
N
Y1 Y2
*7
Y
Y
Y
Y
Y
N
Y1 Y2
*7
Y
Y
Y
Y
Y
N
N
0
Y
Y
Y
Y
Y
Drive control
V/f
N
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y*
Y
100.0
Y
Y
Y
Y
N
Y
Y1 Y2
0.12
Y
Y
N
N
N
Y*
Y
100.0
Y
Y
Y
Y
N
N
N
Y1 Y2
*7
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
0.00
Y
Y
Y
Y
Y
Y
Y1 Y2
0.00
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
Y
Y1 Y2
*7
Y
Y
Y
Y
Y
N
Y1 Y2
0
Y
Y
Y
Y
Y
N
Y
0
Y
Y
N
N
N
Y
Y
0.20
Y
Y
N
N
N
N
Y
0
Y
Y
Y
Y
Y
*7 The motor parameters are automatically set, depending upon the inverter's capacity and shipping destination. See Table C.
5-17
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
5-117
Data copying
Code
Change when
running
Default
setting
0.000 to 5.000 s
Y
Y
0.020
0.000 to 0.100 s
0.1 to 200.0 times
0.001 to 9.999 s
0.000 to 0.100 s
1 to 200 Hz
0 to 20 dB
0 to 9999 (The cumulative run time can be modified or reset
in units of 10 hours.)
Indication of cumulative startup count
0000 to FFFF (hex.)
0% to 300%
0% to 300%
0.00 to 2000 A
50 to 100
Y*
Y
0.005
N
Y
Y
Y
N
Y*
Y
10.0
N
Y
Y
Y
N
Y*
Y
0.100
N
Y
Y
Y
N
Y
Y
0.002
N
Y
Y
Y
N
Y
Y
200
N
N
N
Y
N
Y
Y
0
N
N
N
Y
N
N
N
-
Y
Y
Y
Y
Y
Y
N
-
Y
Y
Y
Y
Y
Y
Y1 Y2
100
Y
Y
Y
Y
Y
Y
Y1 Y2
100
Y
Y
Y
Y
Y
N
Y1 Y2
*7
N
N
Y
Y
Y
N
Y1 Y2
85
N
N
Y
Y
Y
Y
Y1 Y2
*7
-
-
-
-
-
Name
r43 Speed Control 4
(Speed command filter)
r44
(Speed detection filter)
r45
P (Gain)
r46
I (Integral time)
r48
(Output filter)
r49
(Notch filter resonance frequency)
r50
(Notch filter attenuation level)
r51 Cumulative Motor Run Time 4
r52 Startup Counter for Motor 4
Data setting range
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
N
Y
Y
Y
N
Chap. 5
r53 Motor 4
(%X correction factor 1)
r54
(%X correction factor 2)
r55 (Torque current under vector control)
r56
(Induced voltage factor under
vector control)
r57 Reserved *9
0.000 to 20.000 s
Drive control
J01 PID Control
J02
J03
J04
J05
J06
J08
J09
J10
J11
Data setting range
(Mode selection) 0:
1:
2:
3:
(Remote command SV) 0:
1:
P (Gain)
I (Integral time)
D (Differential time)
(Feedback filter)
(Pressurization starting frequency)
(Pressurizing time)
(Anti reset windup)
(Select alarm output)
Disable
Enable (Process control, normal operation)
Enable (Process control, inverse operation)
Enable (Dancer control)
/
keys on keypad
PID command 1
(Analog input terminals [12], [C1], and [V2])
3: UP/DOWN
4: Command via communications link
0.000 to 30.000 times
0.0 to 3600.0 s
0.00 to 600.00 s
0.0 to 900.0 s
0.0 to 500.0 Hz
0 to 60 s
0% to 200%
0: Absolute-value alarm
1: Absolute-value alarm (with Hold)
2: Absolute-value alarm (with Latch)
3: Absolute-value alarm (with Hold and Latch)
4: Deviation alarm
5: Deviation alarm (with Hold)
6: Deviation alarm (with Latch)
7: Deviation alarm (with Hold and Latch)
-100% to 100%
-100% to 100%
0.0: Disable; 1.0 to 500.0 Hz
0 to 60 s
0.0 to 500.0 Hz
-150% to 150%; 999: Depends on setting of F15
-150% to 150%; 999: Depends on setting of F16
1% to 50%
J12
(Upper level alarm (AH))
J13
(Lower level alarm (AL))
J15
(Stop frequency for slow flowrate)
J16
(Slow flowrate level stop latency)
J17
(Starting frequency)
J18
(Upper limit of PID process output)
J19
(Lower limit of PID process output)
J21 Dew Condensation Prevention
(Duty)
J22 Commercial Power Switching
0: Keep inverter operation (Stop due to alarm)
Sequence
1: Automatically switch to commercial-power operation
J56 PID Control (Speed command filter) 0.00 to 5.00 s
J57
(Dancer reference position) -100% to 0% to 100%
J58
(Detection width of dancer 0: Disable switching PID constant
position deviation) 1% to 100% (Manually set value)
J59
P (Gain) 2 0.000 to 30.000 times
J60
I (Integral time) 2 0.0 to 3600.0 s
J61
D (Differential time) 3 0.00 to 600.00 s
J62
(PID control block selection) 0 to 3
bit 0: PID output polarity
0: Plus (add), 1: Minus (subtract)
bit 1: Select compensation factor for PID output
0 = Ratio (relative to the main setting)
1 = Speed command (relative to maximum frequency)
Data copying
Name
Change when
running
Code
Default
setting
N
Y
0
Y
Y
Y
Y
N
5-120
N
Y
0
Y
Y
Y
Y
N
5-121
Y
Y
0.100
Y
Y
Y
Y
N
5-124
Y
Y
0.0
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
Y
Y
0.5
Y
Y
Y
Y
N
Y
Y
0.0
Y
Y
Y
Y
N
Y
Y
0
Y
Y
Y
Y
N
Y
Y
200
Y
Y
Y
Y
N
Y
Y
0
Y
Y
Y
Y
N
Y
Y
100
Y
Y
Y
Y
N
Y
Y
0
Y
Y
Y
Y
N
Y
Y
0.0
Y
Y
Y
Y
N
5-126
5-128
C codes
5-128
P codes
Drive control
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
5-126
5-127
F codes
Y
Y
30
Y
Y
Y
Y
N
Y
Y
0.0
Y
Y
Y
Y
N
E codes
Y
Y
999
Y
Y
Y
Y
N
Y
Y
999
Y
Y
Y
Y
N
Y
Y
1
Y
Y
Y
Y
Y
N
Y
0
Y
Y
N
N
Y
5-67
5-129
Y
Y
0.10
Y
Y
Y
Y
N
5-129
Y
Y
0
Y
Y
Y
Y
N
Y
Y
0
Y
Y
Y
Y
N
Y
Y
0.100
Y
Y
Y
Y
N
Y
Y
0.0
Y
Y
Y
Y
N
Y
Y
0.00
Y
Y
Y
Y
N
N
Y
0
Y
Y
Y
Y
N
H codes
A codes
b codes
r codes
*7 The motor parameters are automatically set, depending upon the inverter's capacity and shipping destination. See Table C.
*9 These function codes are reserved for particular manufacturers. Unless otherwise specified, do not access these function codes.
5-18
FUNCTION CODES
J codes: Application Functions 1
J codes
d codes
U codes
y codes
Data setting range
J68 Brake Signal
(Brake-OFF current) 0% to 300%
J69
(Brake-OFF frequency/speed) 0.0 to 25.0 Hz
J70
(Brake-OFF timer) 0.0 to 5.0 s
J71
(Brake-ON frequency/speed) 0.0 to 25.0 Hz
J72
(Brake-ON timer) 0.0 to 5.0 s
J95
(Brake-OFF torque) 0% to 300%
J96
(Speed selection) 0: Detected speed
J97 Servo-lock
(Gain) 0.00 to 10.00 times
J98
(Completion timer) 0.000 to 1.000 s
J99
(Completion range) 0 to 9999 pulses
1: Reference speed
Data copying
Name
Change when
running
Code
Default
setting
Y
Y
100
Y
Y
Y
Y
N
Y
Y
1.0
Y
Y
N
N
N
Y
Y
1.0
Y
Y
Y
Y
N
Y
Y
1.0
Y
Y
N
N
N
Y
Y
1.0
Y
Y
Y
Y
N
Y
Y
100
N
N
Y
Y
N
Drive control
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
Y
Y
0
N
N
Y
Y
N
Y*
Y
0.10
N
N
N
Y
N
Y
Y
0.100
N
N
N
Y
N
Y
Y
10
N
N
N
Y
N
5-129
5-131
d16
d17
d21
d22
d23
d24
d25
Default
setting
0.000 to 5.000 s
Y
Y
0.020
N
Y
Y
Y
N
0.000 to 0.100 s
0.1 to 200.0 times
0.001 to 9.999 s
0.000 to 0.100 s
1 to 200 Hz
0 to 20 dB
0.000 to 5.000 s
Y*
Y
0.005
N
Y
Y
Y
N
Y*
Y
10.0
N
Y
Y
Y
N
Y*
Y
0.100
N
Y
Y
Y
N
Y
Y
0.002
N
Y
Y
Y
N
Y
Y
200
N
N
N
Y
N
Y
Y
0
N
N
N
Y
N
Y
Y
0.020
N
Y
Y
Y
N
Y*
Y
0.005
N
Y
Y
Y
N
Y*
Y
10.0
N
Y
Y
Y
N
Y*
Y
0.100
N
Y
Y
Y
N
Name
d01 Speed Control 1
(Speed command filter)
d02
(Speed detection filter)
d03
P (Gain)
d04
I (Integral time)
d06
(Output filter)
d07
(Notch filter resonance frequency)
d08
(Notch filter attenuation level)
d09 Speed Control (Jogging)
(Speed command filter)
d10
(Speed detection filter)
d11
P (Gain)
d12
I (Integral time)
d13
(Output filter)
d14 Feedback Input
(Pulse input format)
d15
Data copying
Code
Change when
running
d codes: Application Functions 2
Data setting range
0.000 to 0.100 s
0.1 to 200.0 times
0.001 to 9.999 s
0.000 to 0.100 s
0: Pulse train sign/Pulse train input
1: Forward rotation pulse/Reverse rotation pulse
2: A/B phase with 90 degree phase shift
(Encoder pulse resolution) 0014 to EA60 (hex.)
(20 to 60000 pulses)
(Pulse count factor 1) 1 to 9999
(Pulse count factor 2) 1 to 9999
Speed Agreement/PG Error
0.0% to 50.0%
(Hysteresis width)
(Detection timer) 0.00 to 10.00 s
PG Error Processing
0: Continue to run
1: Stop running with alarm 1
2: Stop running with alarm 2
Zero Speed Control
0: Not permit at startup
1: Permit at startup
ASR Switching Time
0.000 to 1.000 s
d32 Torque Control
(Speed limit 1) 0 to 110 %
d33
(Speed limit 2) 0 to 110 %
d41 Application-defined Control
0: Disable (Ordinary control)
1: Enable㸦Constant peripheral speed control㸧
d51 Reserved *9
0 to 500
d52 Reserved *9
0 to 500
d53 Reserved *9
0 to 500
d54 Reserved *9
0 to 500
d55 Reserved *9
0, 1
d59 Command (Pulse Rate Input)
0: Pulse train sign/Pulse train input
(Pulse input format) 1: Forward rotation pulse/Reverse rotation pulse
2: A/B phase with 90 degree phase shift
d61
(Filter time constant) 0.000 to 5.000 s
d62
(Pulse count factor 1) 1 to 9999
d63
(Pulse count factor 2) 1 to 9999
d67 Starting Mode (Auto search)
0: Disable
1: Enable (At restart after momentary power failure)
2: Enable (At restart after momentary power failure and at
normal start)
d68 Reserved *9
0.0 to 10.0 Hz
d69 Reserved *9
30.0 to 100.0 Hz
d70 Speed Control Limiter
0.00 to 100.00%
d99 Reserved *9
0 to 3
Drive control
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
Y
Y
0.002
N
Y
Y
Y
N
N
Y
2
N
Y
N
Y
Y
N
Y
0400
(1024)
N
Y
N
Y
Y
N
Y
1
N
Y
N
Y
Y
N
Y
1
N
Y
N
Y
Y
Y
Y
10.0
N
Y
Y
Y
N
5-134
5-133
5-134
5-135
5-136
Y
Y
0.50
N
Y
Y
Y
N
N
Y
2
N
Y
Y
Y
Y
N
Y
0
N
N
Y
Y
N
5-51
5-136
Y
Y
0.000
N
Y
Y
Y
Y
5-117
5-136
Y
Y
100
N
N
Y
Y
Y
5-103
Y
Y
100
N
N
Y
Y
Y
5-137
N
Y
0
N
Y
N
N
N
5-137
N
Y
*12
-
-
-
-
-
5-139
N
Y
*12
-
-
-
-
-
N
Y
*12
-
-
-
-
-
N
Y
*12
-
-
-
-
-
N
Y
0
-
-
-
-
-
N
Y
0
Y
Y
Y
Y
Y
Y
Y
0.005
Y
Y
Y
Y
Y
N
Y
1
Y
Y
Y
Y
Y
5-29
5-139
N
Y
1
Y
Y
Y
Y
Y
N
Y
2
N
N
Y
N
Y
5-101
N
Y
40
-
-
-
-
-
5-139
Y
Y
30.0
-
-
-
-
-
Y
Y
100.00
N
Y
N
N
N
Y
Y
0
-
-
-
-
-
*9 These function codes are reserved for particular manufacturers. Unless otherwise specified, do not access these function codes.
*12 The factory default differs depending upon the inverter's capacity.
5 for inverters with a capacity of 4.0 kW or below; 10 for those with 5.5 kW to 22 kW; 20 for those with 30 kW or above
5-19
5-133
Name
Data setting range
U00 Customizable Logic (Mode selection) 0: Disable
1: Enable (Customizable logic operation)
Data copying
Code
Change when
running
U codes: Application Functions 3
Default
setting
N
Y
0
Y
Y
Y
Y
Drive control
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
Y
(Input 1) 0 (1000):
Inverter running
(RUN)
N
Y
0
Y
Y
Y
Y
Y
U02 Step 1
(Input 2) 1 (1001):
Frequency (speed) arrival signal
(FAR)
N
Y
0
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
2 (1002):
3 (1003):
4 (1004):
5 (1005):
6 (1006):
Frequency (speed) detected
(FDT)
Undervoltage detected (Inverter stopped) (LU)
Torque polarity detected
(B/D)
Inverter output limiting
(IOL)
Auto-restarting after momentary power
failure
(IPF)
7 (1007): Motor overload early warning
(OL)
8 (1008): Keypad operation enabled
(KP)
10 (1010): Inverter ready to run
(RDY)
Switch motor drive source between
commercial power and inverter output
(For MC on commercial line)
(SW88)
Y
Y
N
N
N
12:
Switch motor drive source between
commercial power and inverter output
(For secondary side)
(SW52-2)
Y
Y
N
N
N
13:
Switch motor drive source between
commercial power and inverter output
(For primary side)
(SW52-1)
Y
Y
N
N
N
(AX)
(IOL2)
(FAN)
(TRY)
(OH)
(LIFE)
(FDT2)
(REF OFF)
(RUN2)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
(OLP)
Y
Y
Y
Y
N
(ID)
(ID2)
(ID3)
(IDL)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
42 (1042): PID alarm
(PID-ALM)
Y
Y
Y
Y
N
43 (1043): Under PID control
(PID-CTL)
Y
Y
Y
Y
N
44 (1044): Motor stopped due to slow
flowrate under PID control
(PID-STP)
15 (1015): Select AX terminal function
(For MC on primary side)
22 (1022): Inverter output limiting with delay
25 (1025): Cooling fan in operation
26 (1026): Auto-resetting
28 (1028): Heat sink overheat early warning
30 (1030): Lifetime alarm
31 (1031): Frequency (speed) detected 2
33 (1033): Reference loss detected
35 (1035): Inverter output on
36 (1036): Overload prevention control
37 (1037):
38 (1038):
39 (1039):
41 (1041):
Current detected
Current detected 2
Current detected 3
Low current detected
Y
Y
Y
Y
N
(U-TL)
(TD1)
(TD2)
(SWM1)
(SWM2)
(SWM3)
(SWM4)
(FRUN)
(RRUN)
(RMT)
(THM)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
(BRKS)
Y
Y
Y
Y
N
(FDT3)
(C1OFF)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
70 (1070): Speed valid
(DNZS)
N
Y
Y
Y
Y
71 (1071): Speed agreement
(DSAG)
N
Y
Y
Y
N
45 (1045):
46 (1046):
47 (1047):
48 (1048):
49 (1049):
50 (1050):
51 (1051):
52 (1052):
53 (1053):
54 (1054):
56 (1056):
Low output torque detected
Torque detected 1
Torque detected 2
Motor 1 selected
Motor 2 selected
Motor 3 selected
Motor 4 selected
Running forward
Running reverse
In remote operation
Motor overheat detected by thermistor
57 (1057): Brake signal
58 (1058): Frequency (speed) detected 3
59 (1059): Terminal [C1] wire break
72 (1072): Frequency (speed) arrival signal 3
76 (1076): PG error detected
82 (1082): Positioning completion signal
84 (1084): Maintenance timer
98 (1098): Light alarm
99 (1099): Alarm output (for any alarm)
101 (1101): Enable circuit failure detected
102 (1102): Enable input OFF
105 (1105): Braking transistor broken
2001 (3001): Output of step 1
2002 (3002): Output of step 2
2003 (3003): Output of step 3
2004 (3004): Output of step 4
2005 (3005): Output of step 5
2006 (3006): Output of step 6
2007 (3007): Output of step 7
5-20
(FAR3)
Y
Y
Y
Y
N
(PG-ERR)
N
Y
Y
Y
N
(PSET)
N
N
N
Y
N
(MNT)
(L-ALM)
(ALM)
(DECF)
(EN OFF)
(DBAL)
(SO01)
(SO02)
(SO03)
(SO04)
(SO05)
(SO06)
(SO07)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
FUNCTION CODES
11:
Chap. 5
U01 Customizable Logic:
5-139
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Data setting range
2008 (3008):
2009 (3009):
2010 (3010):
4001 (5001):
4002 (5002):
4003 (5003):
4004 (5004):
4005 (5005):
4006 (5006):
4007 (5007):
4010 (5010):
4011 (5011):
6000 (7000):
6001 (7001):
6002 (7002):
6003 (7003):
6004 (7004):
6005 (7005):
6006 (7006):
6007 (7007):
Data copying
Name
Change when
running
Code
Drive control
Default
setting
V/f
Output of step 8
(SO08)
Output of step 9
(SO09)
Output of step 10
(SO10)
Terminal [X1] input signal
(X1)
Terminal [X2] input signal
(X2)
Terminal [X3] input signal
(X3)
Terminal [X4] input signal
(X4)
Terminal [X5] input signal
(X5)
Terminal [X6] input signal
(X6)
Terminal [X7] input signal
(X7)
Terminal [FWD] input signal
(FWD)
Terminal [REV] input signal
(REV)
Final run command
(FL_RUN)
Final FWD run command
(FL_FWD)
Final REV run command
(FL_REV)
During acceleration
(DACC)
During deceleration
(DDEC)
Under anti-regenerative control
(REGA)
Within dancer reference position (DR_REF)
Alarm factor presence
(ALM_ACT)
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Setting the value in parentheses ( ) shown above assigns a
negative logic output to a terminal. (True if OFF.)
U03
(Logic circuit) 0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
11:
12:
13:
U04
U05
U06 Customizable Logic:
U07 Step 2
(Type of timer) 0:
1:
2:
3:
4:
5:
No function assigned
Through output + General-purpose timer
ANDing + General-purpose timer
ORing + General-purpose timer
XORing + General-purpose timer
Set priority flip-flop + General-purpose timer
Reset priority flip-flop + General-purpose timer
Rising edge detector + General-purpose timer
Failing edge detector + General-purpose timer
Rising and failing edge detector + General-purpose
timer
Input hold + General-purpose timer
Increment counter
Decrement counter
Timer with reset input
N
Y
0
Y
Y
Y
Y
Y
No timer
On-delay timer
Off-delay timer
Pulses
Retriggerable timer
Pulse train output
N
Y
0
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
(Timer) 0.00 to 600.00
N
Y
0.00
(Input 1) See U01.
N
Y
0
See U01.
(Input 2) See U02.
N
Y
0
U08
(Logic circuit) See U03.
N
Y
0
Y
Y
Y
Y
Y
U09
(Type of timer) See U04.
N
Y
0
Y
Y
Y
Y
Y
U10
(Timer) See U05.
N
Y
0.00
Y
Y
Y
Y
Y
(Input 1) See U01.
N
Y
0
U11 Customizable Logic:
U12 Step 3
See U02.
See U01.
(Input 2) See U02.
N
Y
0
U13
(Logic circuit) See U03.
N
Y
0
Y
Y
Y
Y
Y
U14
(Type of timer) See U04.
N
Y
0
Y
Y
Y
Y
Y
U15
(Timer) See U05.
N
Y
0.00
Y
Y
Y
Y
Y
(Input 1) See U01.
N
Y
0
U16 Customizable Logic:
U17 Step 4
See U02.
See U01.
(Input 2) See U02.
N
Y
0
U18
(Logic circuit) See U03.
N
Y
0
Y
Y
Y
Y
Y
U19
(Type of timer) See U04.
N
Y
0
Y
Y
Y
Y
Y
U20
(Timer) See U05.
N
Y
0.00
Y
Y
Y
Y
Y
(Input 1) See U01.
N
Y
0
U21 Customizable Logic:
U22 Step 5
See U02.
See U01.
(Input 2) See U02.
N
Y
0
U23
(Logic circuit) See U03.
N
Y
0
Y
Y
Y
Y
Y
U24
(Type of timer) See U04.
N
Y
0
Y
Y
Y
Y
Y
U25
(Timer) See U05.
N
Y
0.00
Y
Y
Y
Y
Y
5-21
See U02.
5-139
Change when
running
Data copying
U26 Customizable Logic:
(Input 1) See U01.
N
Y
0
See U01.
U27 Step 6
(Input 2) See U02.
N
Y
0
See U02.
U28
(Logic circuit) See U03.
N
Y
0
Y
Y
Y
Y
Y
U29
(Type of timer) See U04.
N
Y
0
Y
Y
Y
Y
Y
U30
(Timer) See U05.
N
Y
0.00
Y
Y
Y
Y
Y
(Input 1) See U01.
N
Y
0
Code
Name
U31 Customizable Logic:
U32 Step 7
Data setting range
Drive control
Default
setting
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
5-139
See U01.
(Input 2) See U02.
N
Y
0
U33
(Logic circuit) See U03.
N
Y
0
Y
Y
Y
Y
Y
U34
(Type of timer) See U04.
N
Y
0
Y
Y
Y
Y
Y
U35
(Timer) See U05.
N
Y
0.00
Y
Y
Y
Y
Y
(Input 1) See U01.
N
Y
0
U36 Customizable Logic:
U37 Step 8
See U02.
See U01.
(Input 2) See U02.
N
Y
0
U38
(Logic circuit) See U03.
N
Y
0
Y
Y
Y
Y
Y
U39
(Type of timer) See U04.
N
Y
0
Y
Y
Y
Y
Y
U40
(Timer) See U05.
N
Y
0.00
Y
Y
Y
Y
Y
(Input 1) See U01.
N
Y
0
U42 Step 9
See U01.
N
Y
0
(Logic circuit) See U03.
N
Y
0
Y
Y
Y
Y
Y
U44
(Type of timer) See U04.
N
Y
0
Y
Y
Y
Y
Y
U45
(Timer) See U05.
N
Y
0.00
Y
Y
Y
Y
Y
(Input 1) See U01.
N
Y
0
U46 Customizable Logic:
U47 Step 10
See U02.
See U01.
(Input 2) See U02.
N
Y
0
U48
(Logic circuit) See U03.
N
Y
0
Y
Y
Y
Y
Y
U49
(Type of timer) See U04.
N
Y
0
Y
Y
Y
Y
Y
U50
(Timer) See U05.
N
Y
0.00
Y
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
Y
N
Y
0
Y
Y
Y
Y
Y
N
Y
100
Y
Y
Y
Y
N
Y
Y
Y
Y
N
U71 Customizable Logic Output Signal 1 0: Disable
(Output selection) 1: Step 1 output
U72 Customizable Logic Output Signal 2 2: Step 2 output
U73 Customizable Logic Output Signal 3 3: Step 3 output
U74 Customizable Logic Output Signal 4 4: Step 4 output
U75 Customizable Logic Output Signal 5 5: Step 5 output
6: Step 6 output
7: Step 7 output
8: Step 8 output
9: Step 1 output
10: Step 10 output
(SO01)
(SO02)
(SO03)
(SO04)
(SO05)
(SO06)
(SO07)
(SO08)
(SO09)
(SO10)
See U02.
FUNCTION CODES
(Input 2) See U02.
U43
Chap. 5
U41 Customizable Logic:
See U02.
U81 Customizable Logic Output Signal 1 0 (1000):
(Function selection) 1 (1001):
Select multi-frequency (0 to 1 steps)
(SS1)
Select multi-frequency (0 to 3 steps)
(SS2)
U82 Customizable Logic Output Signal 2
2 (1002):
Select multi-frequency (0 to 7 steps)
(SS4)
N
Y
100
Y
Y
Y
Y
N
U83 Customizable Logic Output Signal 3
3 (1003):
Select multi-frequency (0 to 15 steps)
(SS8)
N
Y
100
Y
Y
Y
Y
N
U84 Customizable Logic Output Signal 4
4 (1004):
Select ACC/DEC time (2 steps)
(RT1)
N
Y
100
Y
Y
Y
Y
N
U85 Customizable Logic Output Signal 5
5 (1005):
Select ACC/DEC time (4 steps)
(RT2)
N
Y
100
Y
Y
Y
Y
N
6 (1006):
7 (1007):
8 (1008):
9 (1009):
Enable 3-wire operation
Coast to a stop
Reset alarm
Enable external alarm trip
(9 = Active OFF, 1009 = Active ON)
(HLD)
(BX)
(RST)
(THR)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
F codes
E codes
10 (1010): Ready for jogging
11 (1011): Select frequency command 2/1
12 (1012): Select motor 2
13:
Enable DC braking
14 (1014): Select torque limiter level 2/1
(JOG)
Y
Y
Y
Y
N
(Hz2/Hz1)
Y
Y
Y
Y
N
(M2)
Y
Y
Y
Y
Y
(DCBRK)
Y
Y
Y
Y
N
(TL2/TL1)
Y
Y
Y
Y
Y
15:
Switch to commercial power (50 Hz)
(SW50)
Y
Y
N
N
N
16:
Switch to commercial power (60 Hz)
(SW60)
Y
Y
N
N
N
(UP)
Y
Y
Y
Y
N
18 (1018): DOWN (Decrease output frequency)
(DOWN)
Y
Y
Y
Y
N
20 (1020): Cancel PID control
(Hz/PID)
Y
Y
Y
Y
N
(IVS)
Y
Y
Y
Y
N
(IL)
Y
Y
Y
Y
Y
(Hz/TRQ)
N
N
N
N
Y
24 (1024): Enable communications link via RS-485
or fieldbus
(LE)
25 (1025): Universal DI
(U-DI)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
(STM)
Y
Y
Y
N
Y
(STOP)
Y
Y
Y
Y
Y
17 (1017): UP (Increase output frequency)
21 (1021): Switch normal/inverse operation
22 (1022): Interlock
23 (1023): Cancel torque control
26 (1026): Enable auto search for idling motor
speed at starting
30 (1030): Force to stop
(30 = Active OFF, 1030 = Active ON)
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-22
Name
Data setting range
Data copying
Code
Change when
running
Drive control
Default
setting
V/f
32 (1032): Pre-excitation
(EXITE)
33 (1033): Reset PID integral and differential
components
(PID-RST)
34 (1034): Hold PID integral component
(PID-HLD)
35 (1035): Select local (keypad) operation
(LOC)
36 (1036): Select motor 3
(M3)
37 (1037): Select motor 4
(M4)
39:
Protect motor from dew condensation
(DWP)
40:
Enable integrated sequence to switch
to commercial power (50 Hz)
(ISW50)
41:
Enable integrated sequence to switch
to commercial power (60 Hz)
(ISW60)
47 (1047): Servo-lock command
(LOCK)
49 (1049): Pulse train sign
(SIGN)
70 (1070): Cancel constant peripheral speed
control
(Hz/LSC)
71 (1071): Hold the constant peripheral speed
control frequency in the memory
(LSC-HLD)
72 (1072): Count the run time of commercial
power-driven motor 1
(CRUN-M1)
73 (1073): Count the run time of commercial
power-driven motor 2
(CRUN-M2)
74 (1074): Count the run time of commercial
power-driven motor 3
(CRUN-M3)
75 (1075): Count the run time of commercial
power-driven motor 4
(CRUN-M4)
76 (1076): Select droop control
(DROOP)
77 (1077): Cancel PG alarm
(PG-CCL)
81 (1081): Clear all customizable logic timers
(CLTC)
98:
Run forward
(FWD)
99:
Run reverse
(REV)
100:
No function assigned
(NONE)
Setting the value of 1000s in parentheses ( ) shown above
assigns a negative logic input to a terminal.
U91 Customizable Logic Timer Monitor
1: Step 1
(Step selection) 2: Step 2
3: Step 3
4: Step 4
5: Step 5
6: Step 6
7: Step 7
8: Step 8
9: Step 9
10: Step 10
N
Y
1
Refer
to
PG w/o w/
Torque page:
V/f PG PG
N
N
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
N
N
Y
Y
N
N
N
N
N
N
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
N
Y
Y
N
N
Y
Y
Y
N
N
Y
Y
Y
N
N
Y
Y
Y
N
N
Y
Y
Y
Y
Y
N
N
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
5-139
Name
Data setting range
y01 RS-485 Communication 1
1 to 255
(Station address)
y02
(Communications error processing) 0: Immediately trip with alarm HU
1: Trip with alarm HU after running for the period specified
by timer y03
2: Retry during the period specified by timer y03. If the retry
fails, trip with alarm HU.
If it succeeds, continue to run.
3: Continue to run
y03
(Timer) 0.0 to 60.0 s
y04
(Baud rate) 0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
y05
(Data length) 0: 8 bits
1: 7 bits
y06
(Parity check) 0: None (2 stop bits)
1: Even parity (1 stop bit)
2: Odd parity (1 stop bit)
3: None (1 stop bit)
y07
(Stop bits) 0: 2 bits
1: 1 bit
5-23
Data copying
Code
Change when
running
y codes: LINK Functions
Default
setting
N
Y
1
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
2.0
Y
Y
Y
Y
Y
Y
Y
3
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Drive control
V/f
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
5-147
Data setting range
Default
setting
Y
Y
0
Y
Y
0.01
Y
Y
Y
Y
Y
Y
Y
1
Y
Y
Y
Y
Y
N
Y
1
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
2.0
Y
Y
Y
Y
Y
Y
Y
3
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
0.01
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
Y
Y
0
Y
Y
Y
Y
Y
5-149
Y
Y
0
Y
Y
Y
Y
Y
5-105
5-149
Y
N
0
Y
Y
Y
Y
Y
5-149
Drive control
V/f
Y
Refer
to
PG w/o w/ Torque page:
V/f PG PG control
Y
Y
Y
Y
5-147
Chap. 5
FUNCTION CODES
y08 RS-485 Communication 1
0: No detection; 1 to 60 s
(No-response error detection time)
y09
(Response interval) 0.00 to 1.00 s
y10
(Protocol selection) 0: Modbus RTU protocol
1: JAGUAR Loader protocol
2: General-purpose inverter protocol
y11 RS-485 Communication 2
1 to 255
(Station address)
y12
(Communications error processing) 0: Immediately trip with alarm HUS
1: Trip with alarm HUS after running for the period specified
by timer y13
2: Retry during the period specified by timer y13. If the retry
fails, trip with alarm HUS. If it succeeds, continue to run.
3: Continue to run
y13
(Timer) 0.0 to 60.0 s
y14
(Baud rate) 0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
y15
(Data length) 0: 8 bits
1: 7 bits
y16
(Parity check) 0: None (2 stop bits)
1: Even parity (1 stop bit)
2: Odd parity (1 stop bit)
3: None (1 stop bit)
y17
(Stop bits) 0: 2 bits
1: 1 bit
y18
(No-response error detection time) 0: No detection; 1 to 60 s
y19
(Response interval) 0.00 to 1.00 s
y20
(Protocol selection) 0: Modbus RTU protocol
2: IMO general-purpose inverter protocol
y97 Communication Data Storage
0: Save into nonvolatile storage (Rewritable times limited)
Selection
1: Write into temporary storage (Rewritable times unlimited)
2: Save all data from temporary storage to nonvolatile one
(After saving data, the y97 data automatically returns to
"1.")
y98 Bus Link Function (Mode selection)
Frequency command
Run command
0: Follow H30 data
Follow H30 data
1: Via fieldbus option
Follow H30 data
2: Follow H30 data
Via fieldbus option
3: Via fieldbus option
Via fieldbus option
y99 Loader Link Function
Frequency command
Run command
(Mode selection) 0: Follow H30 and y98 data
Follow H30 and y98 data
1: Via RS-485 link
Follow H30 and y98 data
(JAGUAR Loader)
2: Follow H30 and y98 data
Via RS-485 link
(JAGUAR Loader)
3: Via RS-485 link
Via RS-485 link
(JAGUAR Loader)
(JAGUAR Loader)
Data copying
Name
Change when
running
Code
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-24
Table A Factory Default According to Shipping Destination
Shipping destination
Function code
EU
Name
F03, A01, b01, r01
E31, E36, E54
Maximum frequency
Frequency detection (Level)
F05, A03, b03, r03
F06, A04, b04, r04
Rated voltage at base frequency
Maximum output voltage
VXGxxx-2E
VXGxxx-4E
200 V class series
400 V class series
60.0 Hz
50.0 Hz
220 V
400 V
.
Table B
Inverter
capacity
(kW)
Torque boost 1 to 4
F09/A05/b05/r05
0.4
7.1
Factory Defaults Depending upon Inverter Capacity
Auto-restart after
momentary power failure
H13
Inverter
capacity
(kW)
75
0.5
110
4.0
5.5
132
5.5
4.9
160
7.5
4.4
200
11
3.5
220
15
2.8
18.5
22
2.2
45
2.0
0.0
2.5
280
315
1.0
355
30
37
1.5
90
6.8
2.2
Auto-restart after
momentary power failure
H13
55
0.75
1.5
Torque boost 1 to 4
F09/A05/b05/r05
4.0
400
500
0.0
1.5
630
5-25
5.0
Rated
No-load
current
cun~ent
(A)
(A)
P02
--
P03
%Rl
%X
P08
Magnetic Magnetic Magnetic
Rated
Magnetic Magnetic Magnetic Magnetic Magnetic
saturation saturation saturation
Iron loss
slip
saturation saturation saturation saturation saturation
factor 1
extension extension extension
frequency
factor I
factor 2
factor 3 factor4
factor 5
(%)
factor "a" factor "b'' factor "c"
(Hz)
(%)
(%)
(%)
(%)
(%)
(%)
(%)
(%)
0.37
11.40
9.71
Pl2
Pl3
Pl6
Pl7
PIS
Pl9
P20
P21
P22
P23
1.77
14.00
93.8
87.5
75 .0
62.5
50.0
106.3
112.5
118.8
0.10 to 0.19
0.1
0.62
0.50
10.74
10.50
0.20 to 0.39
0.2
1.18
0.97
10.69
10.66
0.40 to 0.74
0.4
2.10
1.52
8.47
11.34
2.40
0.75tol.49
0.75
3.29
2.11
7.20
8.94
2.33
1.50 to2.19
1.5
5.56
2.76
5.43
9.29
2.00
2.20 to 3.69
2.2
8.39
4.45
5.37
9.09
1.80
3.70 to 5.49
3.7
13.67
7.03
4.80
9.32
1.93
5.50 to 7.49
5.5
20.50
10.08
4.37
11.85
7.50 to 10.99
7.5
26.41
11.46
3.73
12.15
P55
0.19
P57
H46
1.77
14.00
93.3
86.1
74.4
63.6
50.7
108.8
118.7
129.6
0.31
0.024
2.33
12.60
89.7
81.9
66.9
54.5
43.3
111.0
129.3
148.4
0.62
0.023
9.88
88.7
81.3
67 .0
55.2
43.8
112.1
126.5
144.3
1.23
0.027
7.40
88.3
77.7
62.6
51.8
41.1
112.4
129.2
148.4
2.32
0.033
5.85
92.1
82.8
71.1
58.1
46.2
111.4
126.1
143.9
4.63
0.061
5.91
85.1
74.6
61.7
50.3
39.8
115.7
133.5
150.6
6.79
0.051
0.6
5.24
86.0
76.9
61.3
49.5
39.1
115.6
133.2
154.1
11.42
0.063
0.8
1.40
4.75
88.6
79.2
64.9
52.7
41.8
114.3
133.1
155.6
16.98
0.082
1.0
1.57
4.03
87.7
80.0
67. 1
56.1
45.6
111.7
128.4
149.2
23.16
0.095
1.2
1.3
0.027
11.00to 14.99
11
38.24
16.23
3.13
12.49
1.07
3.92
91.3
83.3
69.9
58.0
47.0
114.1
130.2
147.9
33.96
0.133
15.00 to 18.49
15
50.05
18.33
2.69
13.54
1.13
3.32
90.5
83.5
72.1
60.7
49.5
109.0
121.3
137.8
46.31
0.151
18.50 to 21.99
18.5
60.96
19.62
2.42
13.71
0.87
3.34
90.7
83.0
70.7
59.9
48.7
112.1
127.9
147.5
57.12
0.220
22.00 to 29.99
22
70.97
23.01
2.23
13.24
0.90
3.28
89.7
81.3
68 .9
59.1
48.4
114.1
130.2
151.8
67.92
0.228
97.38
92.62
0.202
0.5
2.0
30.00 to 36.99
30
35.66
2.18
12.38
0.80
3.10
90.2
81.6
68 .7
57.2
45.8
114.8
132.3
153.9
37.00 to 44.99
37
118.2
38.04
2.28
13.56
0.80
2.30
88.7
78.9
65.4
54.2
43.4
112.2
126.4
143.6
114.2
0.250
2.3
45.00 to 54.99
45
141.9
43.54
2.09
13.36
0.80
2.18
89.0
79.7
66.8
55.4
44.4
112.3
126.0
141.8
138.9
0.272
55.00 to 74.99
55
172.8
53.72
1.94
13.39
0.94
2.45
89.2
79.3
64.7
53.6
43.1
117.2
136.2
157.8
169.8
0.267
75.00 to 89.99
75
236.5
76.27
1.64
13.97
0.80
2.33
88.1
78.0
64.3
54.2
42.9
114.9
129.8
144.6
231.6
0.292
2.8
90.00 to 109.9
90
282.0
90.93
1.43
13.26
0.80
2.31
88.8
79.0
65 .0
54.0
44.0
115.0
130.0
145.0
277.9
0.310
3.2
110.0 or above
110
342.0
83.60
1.65
17.25
0.66
1.73
90.5
82.6
70.7
58.7
47.8
112.2
126.1
142.4
339.6
0.378
3.5
2.5
2.6
Motor Parameters
0.40
vector
control
(A)
For
Starting
particular
mode
manufac- (Auto search
turers
delay time 2)
Table C
P07
0.06
5-26
P06
0.01 to 0.09
Torque
current
under
The tables given below list the function codes dedicated to motor 1. For motors 2 to 4, replace the function codes with the
ones dedicated to the respective motor.
Nominal
applied
motor
(kW)
Three-phase 200 V class series for VXGxxx-2E
Motor
capacity
(kW)
Chap. 5
FUNCTION CODES
P02
0.0 1 to 0.09
Nominal
applied
motor
(kW)
Rated
No-load
current
current
(A)
(A)
--
P03
0 .06
0.23
%R1
%X
Magnetic Magnetic
Rated
Magnetic Magnetic M agnetic Magnetic Magnetic
saturation saturation
!ron loss
saturation saturation saturation saturation saturation
slip
factor 1
extension extension
factor 5
frequency
factor 1 factor 2 factor 3 factor 4
factor ''a'' factor "b"
(%)
(Hz)
(%)
(%)
(%)
(%)
(%)
(%)
(%)
Magnetic
saturation
extension
factor "c"
(%)
Torque
current
under
vector
control
(A)
P55
For
Starting mode
particular
(Auto search
manufacdelay time 2)
turers
P06
P07
P08
P12
P13
P16
P17
P18
P19
P20
P21
P22
P23
0.2 1
13 .90
11.84
1.77
14.00
93 .8
87.5
75.0
62 .5
50.0
106.3
112.5
118.8
0.1 0
0.027
P57
0.024
H46
0 .1
0.35
0.28
12.49
12.21
1.77
14.00
93 .3
86.1
74.4
63 .6
50.7
108.8
118 .7
129.6
0.16
0.20 to 0.39
0.2
0.66
0.55
12.67
12.64
2.33
12.60
89.7
81.9
66.9
54.5
43.3
111.0
129.3
148.4
0.33
0.026
0.40 to 0.74
0.4
1.1 5
0.86
9.83
13. 17
2.40
9.88
88.7
81.3
67.0
55.2
43.8
11 2.1
126.5
144.3
0.65
0.029
0.75 to 1.49
0.75
1.79
1.19
8.31
10.31
2.33
7.40
88.3
77.7
62.6
51.8
41.1
112.4
129.2
148.4
1.23
0.032
1.50to 2.1 9
1.5
3.04
!.57
6.1 9
10.60
2.00
5. 85
92.1
82.8
7 1.1
58.1
46.2
111.4
126 .1
143.9
2.46
0.06 1
2.20 to 3.69
2.2
4.53
2.52
6.1 5
10.41
1.80
5.9 1
85 .1
74.6
6 1.7
50.3
39.8
11 5.7
133 .5
150.6
3.60
0.05 1
0.6
3.70 to 5.49
3.7
7.37
3.98
5.48
10.66
1.93
5.24
86.0
76.9
61.3
49.5
39.1
115.6
133.2
154.1
6.06
0.063
0.8
5.50 to 7.49
5.5
11.28
5.71
4.99
13. 53
1.40
4.75
88.6
79.2
64.9
52.7
4 1. 8
11 4.3
133 .1
155.6
9.00
0.088
1.0
7.50 to 10.99
7.5
14.1 8
6.48
4.24
13.84
!.57
4.03
87.7
80.0
67.1
56. 1
45.6
111 .7
128.4
149.2
12.28
0.095
1.2
1.3
11
20.52
9.18
3.56
14.21
1.07
3.92
91.3
83.3
69.9
58.0
47.0
114.1
130.2
147.9
18.00
0.132
15.00 to 18.49
15
26.79
10.38
3.05
15.37
1.1 3
3.32
90.5
83.5
72. 1
60.7
49.5
109.0
12 1.3
137.8
24. 55
0.1 5 1
2.0
5-27
18.50 to 21.99
18.5
33.03
11.10
2.73
15.52
0.87
3.34
90.7
83 .0
70.7
59.9
48.7
112.1
127 .9
147.5
30.28
0.243
22 .00 to 29.99
22
37.90
13.07
2.53
14.99
0.90
3.28
89. 7
8 1.3
68.9
59.1
48.4
114.1
130.2
151.8
36.01
0. 22 8
30.00 to 36.99
30
52.59
20.23
2.48
14.04
0.80
3. 10
90.2
8 1.6
68. 7
57.2
45.8
114.8
132.3
153.9
49. 10
0.202
2.3
37.00 to 44.99
37
63.16
21.58
2.58
15.37
0.80
2.30
88.7
78.9
65.4
54.2
43.4
112.2
126.4
143.6
60.56
0.250
2.5
45.00 to 54.99
45
75.73
24. 69
2.37
15.12
0.80
2. 18
89.0
79.7
66.8
55.4
44.4
11 2.3
126 .0
14 1.8
73.65
0.272
2. 5
55.00 to 74.99
55
92 .26
30.40
2.20
15.1 6
0.94
2.45
89.2
79.3
64.7
53.6
43. 1
11 7.2
136.2
157.8
90. 02
0.267
2.6
75.00 to 89.99
75
126.3
43.16
1.85
15.82
0.80
2.33
88.1
78.0
64.3
54.2
42.9
114.9
129.8
144.6
122.8
0.292
2.8
90.00 to 109.9
90
150.5
51.46
1.62
15.00
0.80
2.3 1
88.8
79.0
65.0
54.0
44.0
11 5.0
130.0
145.0
147.3
0.3 10
3.2
110.0to 131.9
110
182.0
47.31
1.86
19.47
0.66
1.73
90.5
82 .6
70.7
58.7
47 .8
112.2
126.1
142.4
180.0
0.378
3.5
132.0 to 159.9
132
217.0
59.76
1.63
17.65
0.66
1.80
90.3
81.9
69.8
57.8
46.6
112.9
127.6
144.8
204.0
0.394
4.1
4.5
160.0 to 199.9
160
263.2
66.92
1.57
18.40
0.66
1.50
92.2
84.8
71.1
58.6
46.9
11 4.6
130.5
148.0
247.3
0.482
200.0 to 219.9
200
324.0
74.18
1.46
18.66
0.66
1.36
91.9
85.5
72.3
60.0
47.6
109.8
122.7
136.4
309.2
0.534
220.0 to 249.9
220
352.9
74.49
1.49
19.48
0.58
1.25
93 .1
86.1
72.9
60.8
48.6
108.7
11 8.8
130.9
340.1
0.56 1
250.0 to 279.9
250
40 1.4
91.20
1.30
17.60
0.54
1.33
92.2
84.9
72.7
60.5
109.9
122 .2
137.8
386.5
0.57 1
5.0
280.0 to 314.9
280
446.7
97.21
1.27
17.88
0.54
1.27
432.8
0.589
5.5
31 5.0 to 354.9
3 15
503.3
124.5
0.78
15.56
0.45
1.81
486.9
0.862
355.0 to 399.9
355
561.3
136.9
0.77
15.30
0.43
1.77
548.8
0.89 1
400.0 to 449.9
400
650.3
207.5
0.58
14.66
0.29
!.58
618.3
0.683
450.0 to 499 .9
450
749.3
0.45
12.22
0.23
1.84
695.6
0.694
500.0 to 559.9
500
811.4
0.48
11 .59
0.18
1.80
772.9
560.0 to 629.9
560
911.9
0.53
13.03
0.20
1.61
865.6
630.0 to 709 .9
630
I 02 1.0
368.3
0.43
11.03
0. 17
1.29
710.0 or above
710
1114.0
300.8
0.50
13.65
0.21
0.97
280.1
92.7
85.6
72.9
60.9
48.9
109.3
120.2
133.5
973 .8
1098
1.393
1.395
1.560
4.7
5.6
7.5
9.8
10.5
Motor Parameters (Continued)
11.00to 14.99
0.5
Table C
0.10 to 0.19
Three-phase 400 V class series for VXGxxx-4E
M otor
capacity
(kW)
Nominal
applied
motor
(kW)
Rated
current
(A)
No-load
current
(A)
P02
--
P03
P06
%R1
%X
Magnetic Magn etic M agnetic
Rated
Magnetic Magnetic Magnetic Magnetic Magnetic
Iron loss
saturation saturation saturation
slip
saturation saturation saturation saturation saturation
extension extension extension
factor 1
frequency
factor 1 factor 2
factor 3
factor 4
factor 5
factor "a" factor "b" factor "c"
(%)
(%)
(%)
(Hz)
(%)
(%)
(%)
(%)
(%)
(%)
Torque
current
under
vector
control
(A)
P55
For
Starting mode
particular
(Auto search
manufacdelay time 2)
turers
P07
P08
Pl2
P13
Pl6
P17
PIS
P19
P20
P21
P22
P23
O.oJ to 0.09
0.06
0.22
0.20
13.79
11.75
1.77
14.00
93.8
87.5
75.0
62.5
50.0
106.3
112.5
118.8
0.10
0.027
P57
0.024
H46
0. 1
0.35
0.27
12.96
12.67
1. 77
14.00
93 .3
86 .1
74.4
63.6
50.7
108.8
118 .7
129.6
0. 17
0.2
0.65
0.53
12 .95
12.92
2.33
12.60
89.7
81.9
66 .9
54.5
43 .3
111.0
129.3
148.4
0.34
0.026
0.40 to 0. 74
0.4
1.1 5
0. 83
10.20
13.66
2.40
9.88
88 .7
8 1.3
67 .0
55.2
43.8
112. 1
126.5
144.3
0.68
0.029
0.75to 1.49
0.75
1.80
1.1 5
8.67
10.76
2.33
7.40
88.3
77.7
62.6
5 1.8
41.1
112.4
129.2
148.4
1.27
0.032
1.50 to 2.19
1.5
3.10
1.51
6.55
11.21
2.00
5.85
92.1
82.8
71.1
58.1
46.2
111.4
126.1
143.9
2.55
0.061
2.20 to 3.69
2.2
4.60
2.43
6.48
10.97
1.80
5.9 1
85 .1
74.6
6 1. 7
50.3
39.8
115.7
133 .5
150.6
3.74
0.05 1
0.6
3 .70 to 5.49
4.0
7.50
3.84
5.79
11.25
1.93
5.24
86.0
76 .9
6 1.3
49.5
39.1
11 5.6
133.2
154.1
6.2 8
0.063
0.8
5.50 to 7.49
5.5
11.50
5.50
5.28
14.31
1.40
4.75
88.6
79.2
64.9
52.7
41.8
114.3
133.1
155.6
9.34
0.088
1.0
7.50to 10.99
7.5
14.50
6.25
4.50
14.68
1.57
4.03
87.7
80.0
67.1
56. 1
45.6
111.7
128.4
149.2
12.74
0.095
1.2
1.3
II
2 1.00
8.85
3.78
15.09
1. 07
3.92
9 1.3
83 .3
69.9
58.0
47.0
114.1
130 .2
147.9
18.68
0.132
15.00to 18.49
15
27.50
10.00
3.25
16.37
1.13
3.32
90.5
83.5
72.1
60.7
49.5
109.0
121.3
137.8
25.47
0.151
18.50 to 21.99
18.5
34.00
10.70
2.92
16.58
0.87
3.34
90.7
83 .0
70.7
59.9
48.7
112.1
127.9
147.5
31.41
0.243
22.00 to 29.99
22
39.00
12.60
2.70
16.00
0.90
3.28
89.7
81.3
68 .9
59 .1
48.4
114.1
130.2
151.8
37.36
0.228
2.0
30
54.00
19.50
2.64
14.96
0. 80
3.10
90. 2
8 1.6
68 .7
57.2
45. 8
114.8
132.3
153.9
50.94
0. 202
2.3
37
65.00
20.80
2.76
16.4 1
0.80
2.30
88.7
78.9
65 .4
54.2
43.4
112.2
126.4
14 3.6
62.83
0.250
2.5
45.00 to 54.99
45
78.00
23.80
2.53
16.16
0.80
2.18
89.0
79.7
66.8
55.4
44.4
112.3
126.0
141.8
76.41
0.272
1.0
55 .00 to 74.99
55
95.00
29.30
2.35
16.20
0.94
2.45
89.2
79 .3
64 .7
53.6
43.1
11 7.2
136.2
157.8
93.39
0.26 7
2.6
75 .00 to 89.99
75
130.0
4 1.60
1.98
16.89
0.80
2.33
88. 1
78.0
64.3
54.2
42.9
114.9
129.8
144.6
127 .4
0.292
2.8
90.00 to 109.9
90
155.0
49.60
1.73
16.03
0.80
2.31
88.8
79.0
65.0
54.0
44.0
115.0
130.0
145.0
152.8
0.310
3.2
II 0.0 or 131.9
11 0
188.0
45 .60
1.99
20.86
0.66
1. 73
90.5
82 .6
70.7
58.7
47 .8
11 2.2
126.1
142.4
186.8
0.378
3.5
132. 0 to 159.9
132
224.0
57.6
1.75
18.90
0.66
1.80
90.3
81.9
69.8
57.8
46. 6
11 2.9
127.6
144.8
2 11.7
0.394
4. 1
4.5
160.0 to 199.9
160
272.0
64.5
1.68
19.73
0.66
1.50
92.2
84.8
71.1
58.6
46.9
114.6
130.5
148.0
256.6
0.482
200.0 to 2 19.9
200
33 5.0
7 1.5
1.57
20.02
0.66
1.36
9 1. 9
85 .5
72.3
60.0
47.6
109.8
122.7
136.4
320.8
0.534
220.0 to 249.9
220
365.0
71.8
1.60
20.90
0.58
1.25
93 .1
86.1
72.9
60 .8
48 .6
108.7
118 .8
130.9
352.8
0.561
92 .2
84.9
72. 7
60.5
109 .9
122 .2
137.8
4.7
250.0 to 2 79.9
250
415.0
87.9
1.39
18.88
0.54
1.33
400.9
0.571
5.0
280.0 to 3 14.9
280
462.0
93.7
1.36
19. 18
0.54
1.27
449. 1
0.589
5.5
315.0 to 354.9
315
520.0
120.0
0.84
16.68
0.45
1.81
505.2
0.862
355.0 to 399.9
355
580.0
132.0
0.83
16.40
0.43
1. 77
569.3
0.89 1
400.0 to 449.9
400
670.0
200.0
0.62
15.67
0.29
1.58
450.0 to 499.9
450
770.0
270.0
0.48
13.03
0.23
1.84
92.7
85.6
72.9
60.9
48.9
109.3
120.2
133.5
64 1.5
0.683
721.7
0.694
500.0 to 559.9
500
835.0
270.0
0.5 1
12.38
0.18
1.80
80 1.9
560.0 to 629.9
56 0
940.0
270.0
0.57
13.94
0.20
1.6 1
898. 1
630.0 to 709.9
630
1050.0
355.0
0.46
11.77
0.17
1.29
1010
7 10.0 or above
7 10
1150.0
290.0
0.54
14.62
0.2 1
0.97
1139
Chap. 5
FUNCTION CODES
5-28
30.00 to 36.99
37.00 to 44.99
5.6
7.5
9.8
1.393
1.560
10.5
Motor Parameters (Continued)
11.00 to 14.99
0.5
Table C
0 .1 0 to 0. 19
0.20 to 0.39
Three-phase 400 V class series for VXGxxx-4E
Motor
capacity
(kW)
5.2 Details of Function Codes
This section provides the details of the function codes. The descriptions are, in principle, arranged in the order of function
code groups and in numerical order. However, highly relevant function codes are collectively described where one of them
first appears.
5.2.1 Fundamental Functions
F00
Data Protection
F00 specifies whether to protect function code data (except F00) and digital reference data (such as frequency command
/
keys on the keypad.
and PID command) from accidentally getting changed by pressing the
Changing function code data
From the keypad
Via communications link
Allowed
Allowed
Not allowed *
Allowed
Data for F00
0
1
2
3
Allowed
Not allowed *
Allowed
Allowed
Changing digital reference data
with the
/
keys
Allowed
Allowed
Not allowed
Not allowed
*Only F00 data can be modified with the keypad, while all other function codes cannot.
To change F00 data, simultaneous keying of "
+
" (from 0 to 1) or "
+
" (from 1 to 0) keys is required.
For similar purposes, WE-KP, a signal enabling editing of function code data from the keypad is provided as a terminal
command for digital input terminals. (Refer to the descriptions of E01 through E07, data = 19)
The relationship between the terminal command WE-KP and F00 data are as shown below.
WE-KP
OFF
ON
Changing function code data
From the keypad
Via communications link
Not allowed
Follow the F00 setting
Allowed
• If you mistakenly assign the terminal command WE-KP, you no longer edit or modify function code data. In
such a case, temporarily turn this WE-KP-assigned terminal ON and reassign the WE-KP to a correct
command.
• WE-KP is only a signal that allows you to change function code data, so it does not protect the frequency
settings or PID speed command specified by the
and
keys.
Even when F00 = 1 or 3, function code data can be changed via the communications link.
F01
Frequency Command 1
F18 (Bias, Frequency command 1)
C31 to C35 (Analog Input Adjustment for [12])
C41 to C45 (Analog Input Adjustment for [V2])
H61 (UP/DOWN Control, Initial frequency setting)
C30 (Frequency Command 2)
C36 to C39 (Analog Input Adjustment for [C1])
C50 (Bias (Frequency command 1), Bias base point)
d59, d61 to d63 (Command (Pulse Rate Input))
F01 or C30 sets the command source that specifies reference frequency 1 or reference frequency 2, respectively.
Data for
F01, C30
0
1
2
3
5
7
8
11
12
Function
Refer to
Enable
/
keys on the keypad.
Enable the voltage input to terminal [12] (0 to r10 VDC, maximum frequency obtained at r10
VDC).
Enable the current input to terminal [C1] (+4 to +20 mA DC, maximum frequency obtained at +20
mA DC). (SW5 on the control PCB should be turned to the C1 side (factory default).)
Enable the sum of voltage (0 to r10 VDC) and current inputs (+4 to +20 mA DC) given to terminals
[12] and [C1], respectively. See the two items listed above for the setting range and the value
required for maximum frequencies. (SW5 on the control PCB should be turned to the C1 side
(factory default).)
Note: If the sum exceeds the maximum frequency (F03), the maximum frequency will apply.
Enable the voltage input to terminal [V2] (0 to ±10 VDC, maximum frequency obtained at ±10
VDC). (SW5 on the control circuit board should be turned to the V2 position (factory default).)
Enable UP and DOWN commands assigned to the digital input terminals.
The UP command (any of E01 to E07 = 17) and DOWN command (any of E01 to E07 = 18) should
be assigned to any of digital input terminals [X1] to [X7].
For details, refer to the descriptions of E01 through E07.
Enable
/
keys on the keypad (balanceless-bumpless switching available).
Enable a digital input interface card (option).
(For details, refer to the Digital Input Interface Card Instruction Manual.)
Enable the "Pulse train input" PIN command assigned to digital input terminal [X7] (E07 = 48), or a
PG interface card (option).
[1]
5-29
[2]
[3]
[1]
㸫
[4]
„ Setting up a reference frequency
[ 1 ] Using the keypad (F01 = 0 (factory default) or 8)
(1) Set F01 data to "0" or "8." This can be done only when the inverter is in Running mode.
(2) Press the
/
key to display the current reference frequency. The lowest digit on the LED monitor will blink.
/
key again. To save the new setting into the inverter's
(3) To change the reference frequency, press the
memory, press the
key (when E64 = 1 (factory default)). When the power is turned ON next time, the new
setting will be used as an initial reference frequency.
When any analog input (voltage input to terminals [12] and [V2], or current input to terminal [C1]) is selected by F01, it
is possible to arbitrarily specify the reference frequency by multiplying the gain and adding the bias. The polarity can be
selected and the filter time constant and offset can be adjusted.
FUNCTION CODES
[ 2 ] Using analog input (F01 = 1 to 3, or 5)
Chap. 5
key described above, auto-saving is also available (when E64 = 0).
• In addition to the saving with the
• If you have set F01 data to "0" or "8," but have selected a frequency command source other than
frequency command 1 (i.e., frequency command 2, frequency command via communication, or
multi-frequency command), then the
and
keys are disabled to change the current frequency
command even in Running mode. Pressing either of these keys just displays the current reference
frequency.
• When you start specifying the reference frequency or any other parameter with the
/
key, the
least significant digit on the display blinks; that is, the cursor lies in the least significant digit. Holding
down the
/
key changes data in the least significant digit and generates a carry, while the cursor
remains in the least significant digit.
• While the least significant digit is blinking by pressing the
/
key, holding down the
key for
more than 1 second moves the cursor from the least significant digit to the most significant digit. Further
holding it down moves the cursor to the next lower digit. This cursor movement allows you to easily
move the cursor to the desired digit and change the data in higher digits.
• Setting F01 data to "8" enables the balanceless-bumpless switching. When the frequency command
source is switched to the keypad from any other source, the inverter inherits the current frequency that
has applied before switching, providing smooth switching and shockless running.
Adjustable elements of frequency command 1
Bias
Data for
F01
Input terminal
1
[12]
2
[C1]
3
[12] + [C1]
(Sum of the two values)
5
[V2]
Input range
0 to +10 V,
-10 to +10V
4 to 20 mA
0 to +10 V,
-10 to +10 V
4 to 20 mA
0 to +10 V,
-10 to +10 V
Gain
Filter
time
Offset
constant
Gain
Base
point
Polarity
C50
C32
C34
C35
C33
C31
F18
C50
C37
C39
-
C38
C36
F18
C50
C32
C34
C35
C33
C31
F18
C50
C37
C39
-
C38
C36
F18
C50
C42
C44
C45
C43
C41
Bias
Base
point
F18
F codes
„ Offset (C31, C36, C41)
C31, C36 or C41 specifies an offset for analog input voltage or current. The offset also applies to signals sent from the
external equipment.
„ Filter time constant (C33, C38, C43)
C33, C38, or C43 specifies a filter time constant for analog input voltage or current. Choose an appropriate value for the
time constant taking into account the response speed of the mechanical system since a large time constant slows down
the response. When the input voltage fluctuates due to noise, specify a larger time constant.
„ Polarity (C35, C45)
C35 or C45 specifies the input range for analog input voltage.
E codes
C codes
P codes
H codes
A codes
b codes
r codes
Data for C35/C45
Terminal input specifications
0
-10 to +10 VDC
J codes
1
0 to +10 VDC (negative value of voltage is regarded as 0 V)
d codes
U codes
y codes
5-30
„ Gain and bias
If F01 = 3 (the sum of [12] + [C1] is enabled), the bias and gain are independently applied to each of the
voltage and current inputs given to terminals [12] and [C1], and the sum of the two values is applied as the
reference frequency.
In the case of unipolar input (terminal [12] with C35 = 1, terminal [C1], terminal [V2] with C45 = 1)
As shown in the graph above, the relationship between the analog input and the reference frequency specified by
frequency command 1 can arbitrarily be determined by points "A" and "B." Point "A" is defined by the combination of
the bias (F18) and its base point (C50); Point "B," by the combination of the gain (C32, C37 or C42) and its base point
(C34, C39 or C44).
The combination of C32 and C34 applies to terminal [12], that of C37 and C39, to [C1] (C1 function), and that of C42
and C44, to [C1] (V2 function).
Configure the bias (F18) and gain (C32, C37 or C42), assuming the maximum frequency as 100%, and the bias base
point (C50) and gain base point (C34, C39 or C44), assuming the full scale (10 VDC or 20 mA DC) of analog input as
100%.
• The analog input less than the bias base point (C50) is limited by the bias value (F18).
• Specifying that the data of the bias base point (C50) is equal to or greater than that of each gain base point
(C34, C39 or C44) will be interpreted as invalid, so the inverter will reset the reference frequency to 0 Hz.
Example: Setting the bias, gain and their base points when the reference frequency 0 to 60 Hz follows the analog input
of 1 to 5 VDC to terminal [12] (in frequency command 1).
(Point A)
To set the reference frequency to 0 Hz for an analog input being at 1 V, set the bias to 0% (F18 = 0). Since 1 V is the
bias base point and it is equal to 10% of 10 V (full scale of terminal [12]), set the bias base point to 10% (C50 = 10).
(Point B)
To make the maximum frequency equal to the reference frequency for an analog input being at 5 V, set the gain to
100% (C32 = 100). Since 5 V is the gain base point and it is equal to 50% of 10 V (full scale of terminal [12]), set the
gain base point to 50% (C34 = 50).
The setting procedure for specifying a gain or bias alone without changing any base points is the same as that
of IMO standard inverters of VXM & VXSM series, etc.
5-31
In the case of bipolar input (terminal [12] with C35 = 0, terminal [V2] with C45 = 0)
Setting C35 and C45 data to "0" enables terminal [12] and [V2] to be used for bipolar input (-10 V to +10 V)
respectively.
When both F18 (Bias) and C50 (Bias base point) are set to "0," the negative and positive voltage inputs produce
reference frequencies symmetric about the origin point as shown below.
Chap. 5
Configuring F18 (Bias) and C50 (Bias base point) to specify an arbitrary value (Points A1, A2, and A3) gives
FUNCTION CODES
the bias as shown below.
A reference frequency can be specified not only with the frequency (Hz) but also with other menu items,
depending on the setting of function code E48 (= 3 to 5, or 7).
[ 3 ] Using digital input signals UP/DOWN (F01 = 7)
When the UP/DOWN control is selected for frequency setting with a run command ON, turning the terminal command
UP or DOWN ON causes the output frequency to increase or decrease, respectively, within the range from 0 Hz to the
maximum frequency as listed below.
To enable the UP/DOWN control for frequency setting, it is necessary to set F01 data to "7" and assign the UP and
DOWN commands to any of digital input terminals [X1] to [X7], [FWD] and [REV] with any of E01 to E07 (data = 17
or 18).
UP
Data = 17
OFF
ON
OFF
ON
DOWN
Data = 18
OFF
OFF
ON
ON
Function
Keep the current output frequency.
Increase the output frequency with the acceleration time currently specified.
Decrease the output frequency with the deceleration time currently specified.
Keep the current output frequency.
„ Specifying the initial value for the UP/DOWN control
Specify the initial value to start the UP/DOWN control.
Data for H61
Initial value to start the UP/DOWN control
0
Mode fixing the value at "0":
The inverter automatically clears the value to "0" when restarted (including powered ON).
Speed up by the UP command.
1
Mode holding the final output frequency in the previous UP/DOWN control:
The inverter internally holds the last output frequency set by the UP/DOWN control and
applies the held frequency at the next restart (including powering ON).
At the time of restart, if an UP or DOWN terminal command is entered before the internal frequency reaches
the output frequency saved in the memory, the inverter saves the current output frequency into the memory and
starts the UP/DOWN control with the new frequency.
Pressing one of these keys overwrites the frequency held in the inverter.
5-32
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Initial frequency for the UP/DOWN control when the frequency command source is switched
When the frequency command source is switched to the UP/DOWN control from other sources, the initial frequency for
the UP/DOWN control is as listed below:
Frequency command source
Switching command
Initial frequency for UP/DOWN control
H61 = 0
H61 = 1
Other than UP/DOWN
(F01, C30)
Select frequency
command 2/1 (Hz2/Hz1)
Reference frequency given by the frequency
command source used just before switching
PID control
Cancel PID control (Hz/PID)
Reference frequency given by PID control (PID
controller output)
Multi-frequency
Select multi-frequency
(SS1, SS2, SS4 and SS8)
Communications link
Enable communications link
via RS-485 or fieldbus (LE)
Reference frequency
given by the frequency
command source used
just before switching
Reference frequency at
the time of previous
UP/DOWN control
[ 4 ] Using pulse train input (F01 = 12)
„ Selecting the pulse train input format (d59)
A pulse train in the format selected by the function code d59 can give a frequency command to the inverter. Three types
of formats are available; the pulse train sign/pulse train input, the forward rotation pulse/reverse rotation pulse, and the
A and B phases with 90 degree phase difference. If no optional PG interface card is mounted, the inverter ignores the
setting of the function code d59 and accepts only the pulse train sign/pulse train input.
The table below lists pulse train formats and their operations.
Pulse train input format
selected by d59
Operation overview
0: Pulse train sign/
Pulse train input
Frequency/speed command according to the pulse train rate is given to the inverter.
The pulse train sign specifies the polarity of the frequency/speed command.
x For the inverter without an optional PG interface card
Pulse train input: PIN assigned to the digital terminal [X7] (data = 48)
Pulse train sign: SIGN assigned to a digital terminal other than [X7] (data = 49)
If no SIGN is assigned, polarity of any pulse train input is positive.
1: Forward rotation
pulse/Reverse rotation
pulse
Frequency/speed command according to the pulse train rate is given to the inverter.
The forward rotation pulse gives a frequency/speed command with positive
polarity, and a reverse rotation pulse, with negative polarity.
2: A and B phases with 90
degree phase difference
Pulse trains generated by A and B phases with 90 degree phase difference give a
frequency/speed command based on their pulse rate and the phase difference to an
inverter.
For details of operations using the optional PG interface card, refer to the Instruction Manual for it.
5-33
Pulse train sign/Pulse train input
Chap. 5
Forward rotation pulse/Reverse rotation pulse
FUNCTION CODES
A and B phases with 90 degree phase difference
„ Pulse count factor 1 (d62), Pulse count factor 2 (d63)
For the pulse train input, function codes d62 (Command (Pulse rate input), (Pulse count factor 1)) and d63 (Command
(Pulse rate input), (Pulse count factor 2)) define the relationship between the input pulse rate and the frequency
command (reference).
Frequency reference
f* (Hz)
Pulse count factor 2 (d63)
0
Pulse train input rate
Np (kp/s)
Pulse count factor 1 (d62)
F codes
E codes
Relationship between the Pulse Train Input Rate and Frequency Command (Reference)
C codes
As shown in the figure above, enter the pulse train input rate into function code d62 (Command (Pulse rate input),
(Pulse count factor 1)), and enter the frequency reference defined by d62 into d63 (Command (Pulse rate input), (Pulse
count factor 2)). The relationship between the pulse train input rate (kp/s) inputted to the PIN terminal and the
frequency reference f* (Hz) (or speed command) is given by the expression below.
P codes
H codes
A codes
*
f (Hz) = Np (kp/s) ×
f* (Hz)
Np (kp/s)
Pulse count factor 2 (d63)
Pulse count factor 1 (d62)
: Frequency reference
: Input pulse rate
In the case of A and B phases with 90 degree phase difference, note that the pulse
train rate is not the one 4-multiplied.
b codes
r codes
J codes
d codes
U codes
y codes
5-34
The pulse train sign, forward/reverse rotation pulse, and A/B phase difference define the polarity of the pulse train input.
Combination of the polarity of the pulse train input and the FWD/REV command determines the rotational direction of
the motor. The table below shows the relationship between the polarity of the pulse train input and the motor rotational
direction.
Pulse Train Polarity
Run command
FWD (Run forward command)
REV (Run reverse command)
FWD (Run forward command)
REV (Run reverse command)
Positive (+)
Positive (+)
Negative (-)
Negative (-)
Motor rotational direction
Forward
Reverse
Reverse
Forward
Mounting an optional PG interface card automatically switches the pulse train input source to the card and
disables the input from the terminal [X7].
„ Filter time constant (d61)
d61 specifies a filter time constant for pulse train input. Choose an appropriate value for the time constant taking into
account the response speed of the mechanical system since a large time constant slows down the response. When the
reference frequency fluctuates due to small number of pulses, specify a larger time constant.
Switching frequency command
Using the terminal command Hz2/Hz1 assigned to one of the digital input terminals switches between frequency
command 1 (F01) and frequency command 2 (C30).
For details about Hz2/Hz1, refer to E01 to E07 (data = 11).
Terminal command Hz2/Hz1
OFF
Frequency command source
Follow F01 (Frequency command 1)
ON
Follow C30 (Frequency command 2)
F02
Operation Method
F02 selects the source that specifies a run command.
Data for F02
Run Command
Keypad
(Rotational direction specified by
terminal command)
Description
Enables the
/
keys to run and stop the motor.
The rotational direction of the motor is specified by terminal
command FWD or REV.
External signals
(Digital input terminal commands)
Enables terminal command FWD or REV to run the motor.
2
Keypad
(Forward rotation)
/
keys to run and stop the motor. Note that
Enables
this run command enables only the forward rotation.
There is no need to specify the rotational direction.
3
Keypad
(Reverse rotation)
/
keys to run and stop the motor. Note that
Enables
this run command enables only the reverse rotation.
There is no need to specify the rotational direction.
0
1
• When function code F02 = 0 or 1, the "Run forward" FWD and "Run reverse" REV terminal commands must
be assigned to terminals [FWD] and [REV], respectively.
• When the FWD or REV is ON, the F02 data cannot be changed.
• When changing terminal command assignments to terminals [FWD] and [REV] from commands other than
the FWD and REV to the FWD or REV with F02 being set to "1," be sure to turn the target terminal OFF
beforehand; otherwise, the motor may unintentionally rotate.
„ 3-wire operation with external input signals (digital input terminal commands)
The default setting of the FWD and REV are 2-wire. Assigning the terminal command HLD self-holds the forward
FWD or reverse REV run command, to enable 3-wire inverter operation. Short-circuiting the HLD-assigned terminal
and [CM] (i.e., when HLD is ON) self-holds the first FWD or REV at its rising edge. Turning the HLD OFF releases
the self-holding. When no HLD is assigned, 2-wire operation involving only FWD and REV takes effect.
For details about HLD, refer to E01 to E07 (data = 6).
5-35
In addition to the run command sources described above, higher priority command sources including remote and local
mode (see Section 7.3.6) and communications link are provided. For details, refer to the block diagrams in Chapter 6 in
JAGUAR VXG User's Manual.
Maximum Frequency 1
- Data setting range: 25.0 to 500.0 (Hz)
• For MT- and VT-mode inverters, set the maximum frequency at 120 Hz or below.
• Under vector control with speed sensor, set the maximum frequency at 200 Hz or below, and under vector
control without speed sensor, at 120 Hz or below.
• If a setting exceeding the maximum setting value (e.g., 500 Hz) is made, the reference speed and analog
output (FMA) will be based on the full scale/reference value (10V/500 Hz). However, the frequency is
internally limited. Even if 10 V is inputted, the frequency 500 Hz will be internally limited to 200 Hz.
FUNCTION CODES
F03 specifies the maximum frequency to limit the output frequency. Specifying the maximum frequency exceeding the
rating of the equipment driven by the inverter may cause damage or a dangerous situation. Make sure that the maximum
frequency setting matches the equipment rating.
Chap. 5
F03
The inverter can easily accept high-speed operation. When changing the speed setting, carefully check the
specifications of motors or equipment beforehand.
Otherwise injuries could occur.
Modifying F03 data to allow a higher reference frequency requires also changing F15 data specifying a
frequency limiter (high).
F04 to F05
F06
Base Frequency 1, Rated Voltage at Base Frequency 1
Maximum Output Voltage 1
H50, H51 (Non-linear V/f Pattern 1 (Frequency and Voltage))
H52, H53 (Non-linear V/f Pattern 2 (Frequency and Voltage))
H65, H66 (Non-linear V/f Pattern 3 (Frequency and Voltage))
These function codes specify the base frequency and the voltage at the base frequency essentially required for running
the motor properly. If combined with the related function codes H50 through H53, H65 and H66, these function codes
may profile the non-linear V/f pattern by specifying increase or decrease in voltage at any point on the V/f pattern.
F codes
E codes
The following description includes setups required for the non-linear V/f pattern.
C codes
At high frequencies, the motor impedance may increase, resulting in an insufficient output voltage and a decrease in
output torque. To prevent this problem, use F06 (Maximum Output Voltage 1) to increase the voltage. Note, however,
that the inverter cannot output voltage exceeding its input power voltage.
P codes
V/f point
H codes
Function code
Frequency
Voltage
Maximum frequency
F03
F06
Base frequency
Non-linear V/f pattern 3
Non-linear V/f pattern 2
Non-linear V/f pattern 1
F04
H65
H52
H50
F05
H66
H53
H51
Remarks
The setting of the maximum output voltage is disabled
when the auto torque boost, torque vector control, vector
control without speed sensor, or vector control with speed
sensor is selected.
A codes
b codes
r codes
J codes
Disabled when the auto torque boost, torque vector
control, vector control without speed sensor, or vector
control with speed sensor is selected.
d codes
U codes
y codes
5-36
Examples:
„ Normal (linear) V/f pattern
„ V/f pattern with three non-linear points
Data setting range: 25.0 to 500.0 (Hz)
„ Base Frequency 1 (F04)
Set the rated frequency printed on the nameplate labeled on the motor.
„ Rated Voltage at Base Frequency 1 (F05)
Data setting range: 0: Output a voltage in proportion to input voltage
(The Automatic Voltage Regulator (AVR) is disabled.)
80 to 240 (V): Output an AVR-controlled voltage for 200 V class series
160 to 500 (V): Output an AVR-controlled voltage for 400 V class series
Set "0" or the rated voltage printed on the nameplate labeled on the motor.
- If F05 = 0, the rated voltage at base frequency is determined by the power source of the inverter. The output voltage
will fluctuate in line with the input voltage fluctuation.
- If F05 = an arbitrary value other than 0, the inverter automatically keeps the output voltage constant in line with the
setting. When any of the auto torque boost, auto energy saving, etc. is enabled, the F05 data should be equal to the
rated voltage of the motor.
In vector control, current feedback control is performed. In the current feedback control, the current is
controlled with the difference between the motor induced voltage and the inverter output voltage. For a proper
control, the inverter output voltage should be sufficiently higher than the motor induced voltage. Generally, the
voltage difference is about 20 V for 200 V class series, about 40 V for 400 V class series.
The voltage the inverter can output is at the same level as the inverter input voltage. Configure these voltages
correctly in accordance with the motor specifications.
When enabling the vector control without speed sensor using a general-purpose motor, set the F05 (Rated
Voltage at Base Frequency 1) data at the rated voltage of the motor. The voltage difference described above is
specified by function code P56 (Induced voltage factor under vector control). Generally, there is no need to
modify the initial setting.
5-37
„ Non-linear V/f Patterns 1, 2 and 3 for Frequency (H50, H52 and H65)
Data setting range: 0.0 (cancel); 0.1 to 500.0 (Hz)
Set the frequency component at an arbitrary point in the non-linear V/f pattern.
Setting "0.0" to H50, H52 or H65 disables the non-linear V/f pattern operation.
„ Non-linear V/f Patterns 1, 2 and 3 for Voltage (H51, H53 and H66)
Data setting range: 0 to 240 (V): Output an AVR-controlled voltage for 200 V class series
0 to 500 (V): Output an AVR-controlled voltage for 400 V class series
Sets the voltage component at an arbitrary point in the non-linear V/f pattern.
The factory default values for H50 and H51 differ depending on the inverter capacity.
For inverters with a capacity of 22 kW or below, H50 = 0.0 (Hz) and H51 = 0 (V). For those with a capacity of
30 kW or above, refer to the table below.
EU
VXGxxx-2E
200 V class series
6.0 (Hz)
22 (V)
VXGxxx-4E
400 V class series
5.0 (Hz)
40 (V)
Chap. 5
Destination
Inverter type
Voltage
H50
H51
If F05 (Rated Voltage at Base Frequency 1) is set to "0," settings of H50 through H53, H65, H66 and F06 do
not take effect. (When the non-linear point is below the base frequency, the linear V/f pattern applies; when it
is above, the output voltage is kept constant.)
FUNCTION CODES
„ Maximum Output Voltage 1 (F06)
Data setting range: 80 to 240 (V): Output an AVR-controlled voltage for 200 V class series
160 to 500 (V): Output an AVR-controlled voltage for 400 V class series
Set the voltage for the maximum frequency 1 (F03).
F07, F08
Acceleration Time 1, Deceleration Time 1
E10, E12, E14 (Acceleration Time 2, 3 and 4)
E11, E13, E15 (Deceleration Time 2, 3 and 4)
H07 (Acceleration/Deceleration Pattern)
H56 (Deceleration Time for Forced Stop)
H54, H55 (Acceleration Time/Deceleration Time, Jogging)
H57 to H60 (1st and 2nd S-curve Acceleration/Deceleration Range)
F07 specifies the acceleration time, the length of time the frequency increases from 0 Hz to the maximum frequency.
F08 specifies the deceleration time, the length of time the frequency decreases from the maximum frequency down to 0
Hz.
- Data setting range: 0.00 to 6000 (s)
Under V/f control
F codes
E codes
C codes
P codes
H codes
A codes
Under vector control without speed sensor
b codes
r codes
J codes
d codes
U codes
y codes
5-38
Under vector control with speed sensor
„ Acceleration/deceleration time
Acceleration/
deceleration time
Function code
ACC time DEC time
Acceleration/
deceleration time 1
Acceleration/
deceleration time 2
Acceleration/
deceleration time 3
Acceleration/
deceleration time 4
At jogging
operation
Switching factor of acceleration/deceleration time
( Refer to the descriptions of E01 to E07.)
RT1
RT2
OFF
OFF
E11
OFF
ON
E12
E13
ON
OFF
E14
E15
ON
ON
H54
H55
㸫
H56
F07
F08
E10
At forced stop
The combinations of ON/OFF states of the two
terminal commands RT2 and RT1 offer four
choices of acceleration/deceleration time 1 to 4.
(Data = 4, 5)
If no terminal command is assigned, only the
acceleration/deceleration time 1 (F07/F08) is
effective.
When the terminal command JOG is ON, jogging operation is
possible. (Data = 10)
( Refer to the description of C20.)
When the terminal command STOP is OFF, the motor decelerates
to a stop in accordance with the deceleration time for forced stop
(H56). After the motor stops, the inverter enters the alarm state
with the alarm HU displayed. (Data = 30)
„ Acceleration/Deceleration pattern (H07)
H07 specifies the acceleration and deceleration patterns (patterns to control output frequency).
Data for
H07
0
Acceleration/
deceleration
pattern
Linear
S-curve
(Weak)
1
2
S-curve
(Arbitrary)
Curvilinear
3
Motion
The inverter runs the motor with the constant acceleration and
deceleration.
Weak:
To reduce an impact that
acceleration/deceleration would
The acceleration/deceleration rate
make on the machine, the
to be applied to all of the four
inverter gradually accelerates or
inflection zones is fixed at 5% of
decelerates the motor in both the
the maximum frequency.
starting and ending zones of
Arbitrary:
acceleration or deceleration.
The acceleration/deceleration rate
can be arbitrarily specified for
each of the four inflection zones.
Acceleration/deceleration is linear below the base frequency (constant
torque) but it slows down above the base frequency to maintain a
certain level of load factor (constant output).
This acceleration/deceleration pattern allows the motor to accelerate or
decelerate with the maximum performance of the motor.
Function
code
㸫
㸫
H57
H58
H59
H60
㸫
S-curve acceleration/deceleration
To reduce an impact that acceleration/deceleration would make on the machine, the inverter gradually accelerates or
decelerates the motor in both the starting and ending zones of acceleration or deceleration. Two types of S-curve
acceleration/deceleration rates are available; applying 5% (weak) of the maximum frequency to all of the four inflection
zones, and specifying arbitrary rate for each of the four zones with function codes H57 to H60. The reference
acceleration/deceleration time determines the duration of acceleration/deceleration in the linear period; hence, the actual
acceleration/deceleration time is longer than the reference acceleration/deceleration time.
5-39
Acceleration or deceleration time (s) = (2 u 5/100 + 90/100+ 2 u 5/100) u (reference acceleration or deceleration time)
= 1.1 u (reference acceleration or deceleration time)
<S-curve acceleration/deceleration (arbitrary): when the frequency change is 30% or more of the maximum
frequency--10% at the leading edge and 20% at the trailing edge>
Acceleration or deceleration time (s) = (2 u 10/100 + 70/100 + 2 u 20/100) u (reference acceleration or deceleration time)
= 1.3 u (reference acceleration or deceleration time)
FUNCTION CODES
<S-curve acceleration/deceleration (weak): when the frequency change is 10% or more of the maximum frequency>
Chap. 5
S-curve (Weak)
S-curve (Arbitrary)
Setting range: 0 to 100%
Acceleration
Deceleration
Starting zone
Ending zone
Starting zone
Ending zone
5%
5%
5%
5%
H57
H58
H59
H60
Acceleration rate
Acceleration rate
Deceleration rate
Deceleration rate
for the 1st S-curve for the 2nd S-curve for the 1st S-curve for the 2nd S-curve
(Leading edge)
(Trailing edge)
(Leading edge)
(Trailing edge)
Curvilinear acceleration/deceleration
Acceleration/deceleration is linear below the base frequency (constant torque) but it slows down above the base
frequency to maintain a certain level of load factor (constant output).
This acceleration/deceleration pattern allows the motor to accelerate or decelerate with its maximum performance.
The figures at left show the acceleration characteristics.
Similar characteristics apply to the deceleration.
F codes
E codes
C codes
P codes
H codes
A codes
• If you choose S-curve acceleration/deceleration or curvilinear acceleration/deceleration in Acceleration/
Deceleration Pattern (H07), the actual acceleration/deceleration times are longer than the specified times.
• Specifying an improperly short acceleration/deceleration time may activate the current limiter, torque limiter,
or anti-regenerative control, resulting in a longer acceleration/deceleration time than the specified one.
b codes
r codes
J codes
F09
Torque Boost 1
(Refer to F37.)
d codes
U codes
y codes
5-40
Electronic Thermal Overload Protection for Motor 1
(Select motor characteristics, Overload detection level, and Thermal time constant)
F10 to F12
F10 through F12 specify the thermal characteristics of the motor for its electronic thermal overload protection that is
used to detect overload conditions of the motor.
Upon detection of overload conditions of the motor, the inverter shuts down its output and issues a motor overload
alarm O to protect motor 1.
• Thermal characteristics of the motor specified by F10 and F12 are also used for the overload early warning.
Even if you need only the overload early warning, set these characteristics data to these function codes.
(Refer to the description of E34.)
For motors with PTC thermistor, connecting the PTC thermistor to the terminal [V2] enables the motor
overheat protective function. For details, refer to the description of H26.
„ Select motor characteristics (F10)
F10 selects the cooling mechanism of the motor--shaft-driven or separately powered cooling fan.
Data for F10
1
2
Function
For a general-purpose motor with shaft-driven cooling fan
(The cooling effect will decrease in low frequency operation.)
For an inverter-driven motor, non-ventilated motor, or motor with separately powered cooling fan
(The cooling effect will be kept constant regardless of the output frequency.)
The figure below shows operating characteristics of the electronic thermal overload protection when F10 = 1. The
characteristic factors D1 through D3 as well as their corresponding switching frequencies f2 and f3 vary with the
characteristics of the motor. The tables below list the factors of the motor selected by P99 (Motor 1 Selection).
Cooling Characteristics of Motor with Shaft-driven Cooling Fan
Nominal Applied Motor and Characteristic Factors when P99 (Motor 1 selection) = 0 or 4
Nominal applied
motor (kW)
0.4, 0.75
1.5 to 3.7 (4.0) *
5.5 to 11
15
18.5, 22
30 to 45
55 to 90
110 or above
Thermal time
constant W
(Factory default)
Reference current
for setting the
thermal time
constant (Imax)
Output frequency for motor
characteristic factor
f2
f3
7 Hz
5 min
5 Hz
Allowable
continuous current
u 150%
6 Hz
7 Hz
5 Hz
Base frequency Base frequency
u 33%
u 83%
10 min
Characteristic
factor (%)
D1
D2
D3
75
85
90
85
92
54
51
53
85
85
95
85
100
85
95
85
100
100
100
100
100
95
95
90
* 4.0 kW for the EU.
Nominal Applied Motor and Characteristic Factors when P99 (Motor 1 Selection) = 1 or 3
Nominal applied
motor (kW)
Thermal time
constant W
(Factory default)
0.2 to 22
5 min
30 to 45
55 to 90
110 or above
10 min
Reference current
for setting the
thermal time
constant (Imax)
Output frequency for
motor characteristic factor
f2
f3
Base frequency
u 33%
Allowable
Base frequency
continuous current
u 33%
Base frequency
u 150%
u 83%
Characteristic
factor (%)
D1
D2
D3
69
90
90
54
51
53
85
95
85
95
95
90
If F10 is set to "2," changes of the output frequency do not affect the cooling effect. Therefore, the overload detection
level (F11) remains constant.
5-41
„ Overload detection level (F11)
Data setting range: 1 to 135% of the rated current (allowable continuous drive current) of the inverter
In general, set the F11 data to the allowable continuous current of motor when driven at the base frequency (i.e. 1.0 to
1.1 times of the rated current of the motor.)
To disable the electronic thermal overload protection, set the F11 data to "0.00."
Data setting range: 0.5 to 75.0 (minutes)
„ Thermal time constant (F12)
F12 specifies the thermal time constant of the motor. If the current of 150% of the overload detection level specified by
F11 flows for the time specified by F12, the electronic thermal overload protection becomes activated to detect the
motor overload. The thermal time constant for general-purpose motors including Fuji motors is approx. 5 minutes for
motors of 22 kW or below and 10 minutes for motors of 30 kW or above by factory default.
(Example) When the F12 data is set at 5 minutes
The actual time required for issuing a motor overload alarm tends to be shorter than the specified value, taking into
account the time period from when the output current exceeds the rated current (100%) until it reaches 150% of the
overload detection level.
FUNCTION CODES
Example of Operating Characteristics
Chap. 5
As shown below, the electronic thermal overload protection is activated to detect an alarm condition (alarm code O)
when the output current of 150% of the overload detection level (specified by F11) flows for 5 minutes, and 120% for
approx. 12.5 minutes.
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-42
F14
Restart Mode after Momentary Power Failure (Mode selection)
H13 (Restart Mode after Momentary Power Failure (Restart time))
H14 (Restart Mode after Momentary Power Failure (Frequency fall rate))
H15 (Restart Mode after Momentary Power Failure (Continuous running level))
H16 (Restart Mode after Momentary Power Failure (Allowable momentary power failure time))
H92 (Continuity of running (P))
H93 (Continuity of running (I))
F14 specifies the action to be taken by the inverter such as trip and restart in the event of a momentary power failure.
„ Restart mode after momentary power failure (Mode selection) (F14)
• Under V/f control
Data for F14
0: Trip immediately
1: Trip after recovery
from power failure
Description
Auto search disabled
Auto search enabled
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter issues undervoltage alarm OX and shuts down its
output so that the motor enters a coast-to-stop state.
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter shuts down its output so that the motor enters a
coast-to-stop state, but it does not enter the undervoltage state or issue undervoltage alarm
OX .
The moment the power is restored, an undervoltage alarm OX is issued, while the motor
remains in a coast-to-stop state.
2: Trip after
decelerate-to-stop
As soon as the DC link bus voltage drops below the continuous running level due to a
momentary power failure, decelerate-to-shop control is invoked. Decelerate-to-stop control
regenerates kinetic energy from the load's moment of inertia, slowing down the motor and
continuing the deceleration operation. After decelerate-to-stop operation, an undervoltage
alarm OX is issued.
3: Continue to run
As soon as the DC link bus voltage drops below the continuous running level due to a
(for heavy inertia or momentary power failure, continuous running control is invoked. Continuous running
general loads)
control regenerates kinetic energy from the load’s moment of inertia, continues running, and
waits the recovery of power. When an undervoltage condition is detected due to a lack of
energy to be regenerated, the output frequency at that time is saved, the output of the
inverter is shut down, and the motor enters a coast-to-stop state.
If a run command has been input, restoring
power performs auto search for idling motor
speed and restarts running the motor at the
frequency calculated based on the searched
speed.
This setting is ideal for fan applications with a large moment of inertia.
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter shuts down the output so that the motor enters a
coast-to-stop state.
If a run command has been input,
restoring power restarts the inverter at the
output frequency saved when
undervoltage was detected.
4: Restart at the
frequency at which
the power failure
occurred
(for general loads)
5: Restart at the
starting frequency
If a run command has been input, restoring
power performs auto search for idling motor
speed and restarts running the motor at the
frequency calculated based on the searched
speed.
This setting is ideal for applications with a moment of inertia large enough not to slow down
the motor quickly, such as fans, even after the motor enters a coast-to-stop state upon
occurrence of a momentary power failure.
If a run command has been input,
restoring power restarts the inverter at the
output frequency saved when
undervoltage was detected.
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter shuts down the output so that the motor enters a
coast-to-stop state.
If a run command has been input, restoring
If a run command has been input,
restoring power restarts the inverter at the power performs auto search for idling motor
speed and restarts running the motor at the
starting frequency specified by function
frequency calculated based on the searched
code F23.
speed.
This setting is ideal for heavy load applications such as pumps, having a small moment of
inertia, in which the motor speed quickly goes down to zero as soon as it enters a
coast-to-stop state upon occurrence of a momentary power failure.
Auto search is enabled by turning ON the digital terminal command STM ("Enable auto search for idling motor speed
at starting") or setting the H09 data to "1" or "2."
For details about the digital terminal command STM and auto search, refer to the description of H09 (Starting Mode,
Auto search).
5-43
• Under vector control without speed sensor
Data for F14
0: Trip immediately
1: Trip after recovery
from power failure
2: Trip after
decelerate-to-stop
Auto search enabled
If a run command has been input, restoring
power performs auto search for idling motor
speed and restarts running the motor at the
frequency calculated based on the searched
speed.
5: Restart at the starting As soon as the DC link bus voltage drops below the undervoltage detection level due to a
frequency
momentary power failure, the inverter shuts down the output so that the motor enters a
coast-to-stop state.
If a run command has been input, restoring
If a run command has been input,
power performs auto search for idling motor
restoring power restarts the inverter at
speed and restarts running the motor at the
the starting frequency specified by
frequency calculated based on the searched
function code F23.
speed.
This setting is ideal for heavy load applications such as pumps, having a small moment of
inertia, in which the motor speed quickly goes down to zero as soon as it enters a
coast-to-stop state upon occurrence of a momentary power failure.
If a run command has been input,
restoring power restarts the inverter at
the output frequency saved when
undervoltage was detected.
FUNCTION CODES
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter issues undervoltage alarm OX and shuts down its
output so that the motor enters a coast-to-stop state.
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter shuts down its output so that the motor enters a
coast-to-stop state, but it does not enter the undervoltage state or issue undervoltage alarm
OX .
The moment the power is restored, an undervoltage alarm OX is issued, while the motor
remains in a coast-to-stop state.
As soon as the DC link bus voltage drops below the continuous running level due to a
momentary power failure, decelerate-to-shop control is invoked. Decelerate-to-stop
control regenerates kinetic energy from the load's moment of inertia, slowing down the
motor and continuing the deceleration operation. After decelerate-to-stop operation, an
undervoltage alarm OX is issued.
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter shuts down the output so that the motor enters a
coast-to-stop state.
Even if the F14 data is set to "3," the "Continue to run" function is disabled.
Chap. 5
3: Continue to run
(for heavy inertia or
general loads)
4: Restart at the
frequency at which
the power failure
occurred
(for general loads)
Description
Auto search disabled
Auto search is enabled by turning ON the digital terminal command STM ("Enable auto search for idling motor speed
at starting") or setting the d67 data to "1" or "2."
For details about the digital terminal command STM and auto search, refer to the description of d67 (Starting Mode,
Auto search).
• Under vector control with speed sensor
Data for F14
Description
0: Trip immediately
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter issues undervoltage alarm OX and shuts down its
output so that the motor enters a coast-to-stop state.
1: Trip after recovery
from power failure
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter shuts down its output so that the motor enters a
coast-to-stop state, but it does not enter the undervoltage state or issue undervoltage alarm
OX .
The moment the power is restored, an undervoltage alarm OX is issued, while the motor
remains in a coast-to-stop state.
As soon as the DC link bus voltage drops below the continuous running level due to a
momentary power failure, decelerate-to-shop control is invoked. Decelerate-to-stop
control regenerates kinetic energy from the load's moment of inertia, slowing down the
motor and continuing the deceleration operation. After decelerate-to-stop operation, an
undervoltage alarm OX is issued.
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter shuts down the output so that the motor enters a
coast-to-stop state.
Even if the F14 data is set to "3," the "Continue to run" function is disabled.
If a run command has been input, restoring power restarts the inverter at the motor speed
detected by the speed sensor.
2: Trip after
decelerate-to-stop
3: Continue to run
(for heavy inertia or
general loads)
4: Restart at the
frequency at which
the power failure
occurred
(for general loads)
5: Restart at the starting
frequency
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-44
If you enable the "Restart mode after momentary power failure" (Function code F14 = 3, 4, or 5), the inverter
automatically restarts the motor running when the power is recovered. Design the machinery or equipment so that
human safety is ensured after restarting.
Otherwise an accident could occur.
„ Restart mode after momentary power failure (Basic operation with auto search disabled)
The inverter recognizes a momentary power failure upon detecting the condition that DC link bus voltage goes below
the undervoltage detection level, while the inverter is running. If the load of the motor is light and the duration of the
momentary power failure is extremely short, the voltage drop may not be great enough for a momentary power failure
to be recognized, and the motor may continue to run uninterrupted.
Upon recognizing a momentary power failure, the inverter enters the restart mode (after a recovery from momentary
power failure) and prepares for restart. When power is restored, the inverter goes through an initial charging stage and
enters the ready-to-run state. When a momentary power failure occurs, the power supply voltage for external circuits
such as relay sequence circuits may also drop so as to turn the run command OFF. In consideration of such a situation,
the inverter waits 2 seconds for a run command input after the inverter enters a ready-to-run state. If a run command is
received within 2 seconds, the inverter begins the restart processing in accordance with the F14 data (Mode selection).
If no run command has been received within 2-second wait period, the inverter cancels the restart mode (after a
recovery from momentary power failure) and needs to be started again from the ordinary starting frequency. Therefore,
ensure that a run command is entered within 2 seconds after a recovery of power, or install a mechanical latch relay.
When run commands are entered via the keypad, the above operation is also necessary for the mode (F02 = 0) in which
the rotational direction is determined by the terminal command, FWD or REV. In the modes where the rotational
direction is fixed (F02 = 2 or 3), it is retained inside the inverter so that the restart will begin as soon as the inverter
enters the ready-to-run state.
• When the power is restored, the inverter will wait 2 seconds for input of a run command. However, if the
allowable momentary power failure time (H16) elapses after the power failure was recognized, even within
the 2 seconds, the restart time for a run command is canceled. The inverter will start operation in the normal
starting sequence.
• If the "Coast to a stop" terminal command BX is entered during the power failure, the inverter gets out of the
restart mode and enters the normal running mode. If a run command is entered with power supply applied,
the inverter will start from the normal starting frequency.
• The inverter recognizes a momentary power failure by detecting an undervoltage condition whereby the
voltage of the DC link bus goes below the lower limit. In a configuration where a magnetic contactor is
installed on the output side of the inverter, the inverter may fail to recognize a momentary power failure
because the momentary power failure shuts down the operating power of the magnetic contactor, causing the
contactor circuit to open. When the contactor circuit is open, the inverter is cut off from the motor and load,
and the voltage drop in the DC link bus is not great enough to be recognized as a power failure. In such an
event, restart after a recovery from momentary power failure does not work properly as designed. To solve
this, connect the interlock command IL line to the auxiliary contact of the magnetic contactor, so that a
momentary power failure can sure be detected. For details, refer to the descriptions of E01 through E07.
Function code E01 to E07, data = 22
IL
OFF
ON
Description
No momentary power failure has occurred.
A momentary power failure has occurred. (Restart after a momentary power failure enabled)
During a momentary power failure, the motor slows down. After power is restored, the inverter restarts at the frequency
just before the momentary power failure. Then, the current limiting function works and the output frequency of the
inverter automatically decreases. When the output frequency matches the motor speed, the motor accelerates up to the
original output frequency. See the figure below. In this case, the instantaneous overcurrent limiting must be enabled
(H12 = 1).
5-45
Chap. 5
• Auto-restarting after momentary power failure IPF
„ Restart mode after momentary power failure (Basic operation with auto search enabled)
Auto search for idling motor speed will become unsuccessful if it is done while the motor retains residual voltage. It is,
therefore, necessary to leave the motor for the time (auto search delay time) enough to discharge the residual voltage.
The delay time is specified by H46 (Starting Mode (Auto search delay time 2)).
The inverter will not start unless the time specified by H46 has elapsed, even if the starting conditions are satisfied. (
For details, refer to H09 and d67.)
FUNCTION CODES
This output signal is ON during the period after the occurrence of momentary power failure until the completion of
restart (the output has reached the reference frequency). When the IPF is ON, the motor slows down, so perform
necessary operations. ( For details about IPF, refer to E20 through E24 and E27 (data = 6).)
• To use auto search for idling motor speed, it is necessary to tune the inverter beforehand.
• When the estimated speed exceeds the maximum frequency or the upper limit frequency, the inverter
disables auto search and starts running the motor with the maximum frequency or the upper limit frequency,
whichever is lower.
• During auto search, if an overcurrent or overvoltage trip occurs, the inverter restarts the suspended auto
search.
• Perform auto search at 60 Hz or below.
• Note that auto search may not fully provide the expected/designed performance depending on conditions
including the load, motor parameters, power cable length, and other externally determined events.
„ Restart mode after momentary power failure (Allowable momentary power failure time) (H16)
H16 specifies the maximum allowable duration (0.0 to 30.0 seconds) from an occurrence of a momentary power failure
(undervoltage) until the inverter is to be restarted. Specify the coast-to-stop time which the machine system and facility
can tolerate.
If the power is restored within the specified duration, the inverter restarts in the restart mode specified by F14. If not,
the inverter recognizes that the power has been shut down so that the inverter does not apply the restart mode and starts
normal running.
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-46
If H16 (Allowable momentary power failure time) is set to "999," restart will take place until the DC link bus voltage
drops down to the allowable voltage for restart after a momentary power failure (50 V for 200 V class series and 100 V
for 400 V class series). If the DC link bus voltage drops below the allowable voltage, the inverter recognizes that the
power has been shut down so that it does not restart but starts (normal starting).
Power supply voltage
200 V class series
400 V class series
Allowable voltage for restart after momentary power failure
50 V
100 V
The time required from when the DC link bus voltage drops from the threshold of undervoltage until it reaches
the allowable voltage for restart after a momentary power failure, greatly varies depending on the inverter
capacity, the presence of options, and other factors.
„ Restart mode after momentary power failure (Restart time) (H13)
H13 specifies the time period from momentary power failure occurrence until the inverter reacts for restarting process.
If the inverter starts the motor while motor’s residual voltage is still in a high level, a large inrush current may flow or
an overvoltage alarm may occur due to an occurrence of temporary regeneration. For safety, therefore, it is advisable to
set H13 to a certain level so that the restart will take place only after the residual voltage has dropped to a low level.
Note that even when power is restored, restart will not take place until the restart time (H13) has elapsed.
Factory default: By factory default, H13 is set to the value suitable for the standard motor (see Table B in Section 5.1
"Function Code Tables"). Basically, it is not necessary to change H13 data. However, if the long restart time causes the
flow rate of the pump to overly decrease or causes any other problem, you might as well reduce the setting to about a
half of the default value. In such a case, make sure that no alarm occurs.
Function code H13 (Restart mode after momentary power failure -- Restart time) also applies to the switching
operation between line and inverter (refer to the descriptions of E01 through E07).
5-47
„ Restart mode after momentary power failure (Frequency fall rate) (H14)
During restart after a momentary power failure, if the inverter output frequency and the idling motor speed cannot be
harmonized with each other, an overcurrent will flow, activating the overcurrent limiter. If it happens, the inverter
automatically reduces the output frequency to match the idling motor speed according to the reduction rate (Frequency
fall rate: Hz/s) specified by H14.
Data for H14
0.00
0.01 to 100.00 (Hz/s)
999
Inverter’s action for the output frequency fall
Follow the deceleration time specified
Follow data specified by H14
Follow the setting of the PI controller in the current limiter.
(The PI constant is prefixed inside the inverter.)
If the frequency fall rate is too high, regeneration may take place at the moment the motor rotation matches
the inverter output frequency, causing an overvoltage trip. On the contrary, if the frequency fall rate is too
low, the time required for the output frequency to match the motor speed (duration of current limiting action)
may be prolonged, triggering the inverter overload prevention control.
Chap. 5
„ Restart after momentary power failure (Continuous running level) (H15)
Continuity of running (P and I) (H92, H93)
FUNCTION CODES
• Trip after decelerate-to-stop
If a momentary power failure occurs when F14 is set to "2" (Trip after decelerate-to-stop), the inverter enters the control
sequence of the decelerate-to-stop when the DC link bus voltage drops below the continuous running level specified by
H15.
Under the decelerate-to-stop control, the inverter decelerates its output frequency keeping the DC link bus voltage
constant using the PI processor. P (proportional) and I (integral) components of the PI processor are specified by H92
and H93, respectively.
For normal inverter operation, it is not necessary to modify data of H15, H92 or H93.
• Continue to run
If a momentary power failure occurs when F14 is set to "3" (Continue to run), the inverter enters the control sequence
of the continuous running when the DC link bus voltage drops below the continuous running level specified by H15.
Under the continuous running control, the inverter continues to run keeping the DC link bus voltage constant using the
PI processor.
P (proportional) and I (integral) components of the PI processor are specified by H92 and H93, respectively.
For normal inverter operation, it is not necessary to modify data of H15, H92 or H93.
F codes
Power supply voltage
200 V class series
400 V class series
D
22 kW or below
5V
10 V
30 kW or above
10 V
20 V
E codes
C codes
P codes
H codes
Even if you select "Trip after decelerate-to-stop" or "Continue to run," the inverter may not be able to do so
when the load's inertia is small or the load is heavy, due to undervoltage caused by a control delay. In such a
case, when "Trip after decelerate-to-stop" is selected, the inverter allows the motor to coast to a stop; when
"Continue to run" is selected, the inverter saves the output frequency being applied when the undervoltage
alarm occurred and restarts at the saved frequency after a recovery from the momentary power failure.
When the input power voltage for the inverter is high, setting the continuous running level high makes the
control more stable even if the load's inertia is relatively small. Raising the continuous running level too high,
however, might cause the continuous running control activated even during normal operation.
When the input power voltage for the inverter is extremely low, continuous running control might be activated
even during normal operation, at the beginning of acceleration or at an abrupt change in load. To avoid this,
lower the continuous running level. Lowering it too low, however, might cause undervoltage that results from
voltage drop due to a control delay.
Before you change the continuous running level, make sure that the continuous running control will be
performed properly, by considering the fluctuations of the load and the input voltage.
5-48
A codes
b codes
r codes
J codes
d codes
U codes
y codes
F15, F16
Frequency Limiter (High), Frequency Limiter (Low)
H63 Low Limiter (Mode selection)
„ Frequency Limiter (High and Low) (F15, F16)
Data setting range: 0.0 to 500.0 (Hz)
F15 and F16 specify the upper and lower limits of the output frequency or reference frequency, respectively. The object
to which the limit is applied differs depending on the control system.
Object to which the limit is applied
Frequency Limiter
Frequency Limiter (High)
Frequency Limiter (Low)
F15
F16
V/f control
Vector control without/with speed sensor
Output frequency
Reference frequency
Reference speed (reference frequency)
Reference speed (reference frequency)
When the limit is applied to the reference frequency or reference speed, delayed responses of control may
cause an overshoot or undershoot, and the frequency may temporarily go beyond the limit level.
„ Low Limiter (Mode selection) (H63)
H63 specifies the operation to be carried out when the reference frequency drops below the low level specified by F16,
as follows:
Data for H63
0
1
Operation
The output frequency will be held at the low level specified by F16.
The inverter decelerates to stop the motor.
(H63 = 0)
(H63 = 1)
• When you change the frequency limiter (High) (F15) in order to raise the reference frequency, be sure to
change the maximum frequency (F03) accordingly.
• Maintain the following relationship among the data for frequency control:
F15 > F16, F15 > F23, and F15 > F25
F03 > F16
where, F23 and F25 specify the starting and stop frequencies, respectively.
If you specify any wrong data for these function codes, the inverter may not run the motor at the desired
speed, or cannot start it normally.
F18
Bias (Frequency command 1)
F20 to F22
H95
DC Braking 1 (Braking starting frequency, Braking level, and Braking time)
DC Braking (Braking response mode)
(Refer to F01.)
F20 through F22 specify the DC braking that prevents motor 1 from running by inertia during decelerate-to-stop
operation.
If the motor enters a decelerate-to-stop operation by turning OFF the run command or by decreasing the reference
frequency below the stop frequency, the inverter activates the DC braking by flowing a current at the braking level
(F21) during the braking time (F22) when the output frequency goes down to the DC braking starting frequency (F20).
Setting the braking time to "0.0" (F22 = 0) disables the DC braking.
„ Braking starting frequency (F20)
Data setting range: 0.0 to 60.0 (Hz)
F20 specifies the frequency at which the DC braking starts its operation during motor decelerate-to-stop state.
„ Braking level (F21)
Data setting range: 0 to 100 (%) (0 to 80 (%) for MT/VT-mode inverters)
F21 specifies the output current level to be applied when the DC braking is activated. The function code data should be
set, assuming the rated output current of the inverter as 100%, in increments of 1%.
The inverter rated output current differs between the CT and MT/VT modes.
„ Braking time (F22)
Data setting range: 0.01 to 30.00 (s), 0.00 (Disable)
F22 specifies the braking period that activates DC braking.
5-49
„ Braking response mode (H95)
H95 specifies the DC braking response mode. When vector control without/with speed sensor is selected, the response
is constant.
Data for H95
0
1
Characteristics
Slow response. Slows the rising edge of the current,
thereby preventing reverse rotation at the start of DC
braking.
Quick response. Quickens the rising edge of the
current, thereby accelerating the build-up of the
braking torque.
Note
Insufficient braking torque may result at the
start of DC braking.
Reverse rotation may result depending on the
moment of inertia of the mechanical load and
the coupling mechanism.
Chap. 5
It is also possible to use an external digital input signal as an "Enable DC braking" terminal command DCBRK.
FUNCTION CODES
As long as the DCBRK command is ON, the inverter performs DC braking, regardless of the braking time
specified by F22.
( Refer to E01 through E07, data =13.)
Turning the DCBRK command ON even when the inverter is in a stopped state activates the DC braking. This
feature allows the motor to be excited before starting, resulting in smoother acceleration (quicker build-up of
acceleration torque) (under V/f control).
When vector control without/with speed sensor is selected, use the pre-exciting feature for establishing the
magnetic flux. ( For details, refer to H84.)
In general, DC braking is used to prevent the motor from running by inertia during the stopping process. Under
vector control with speed sensor, however, zero speed control will be more effective for applications where
load is applied to the motor even in a stopped state.
If the zero speed control continues for a long time, the motor may slightly rotate due to a control error. To fix
the motor shaft, use the servo-lock function. ( For details, refer to J97.)
In general, specify data of function code F20 at a value close to the rated slip frequency of motor. If you set it
at an extremely high value, control may become unstable and an overvoltage alarm may result in some cases.
F codes
Even if the motor is stopped by DC braking, voltage is output to inverter output terminals U, V, and W.
An electric shock may occur.
E codes
C codes
P codes
The DC brake function of the inverter does not provide any holding mechanism.
Injuries could occur.
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-50
F23 to F25
Starting Frequency 1, Starting Frequency 1 (Holding time), Stop Frequency
F38 (Stop Frequency (Detection mode)) F39 (Stop Frequency (Holding time))
H92 (Continuity of Running (P)
d24 (Zero Speed Control)
H93 (Continuity of Running (I)
Under V/f control
At the startup of an inverter, the initial output frequency is equal to the starting frequency 1 specified by F23. The
inverter stops its output when the output frequency reaches the stop frequency specified by F25.
Set the starting frequency to a level at which the motor can generate enough torque for startup. Generally, set the
motor's rated slip frequency as the starting frequency.
In addition, F24 specifies the holding time for the starting frequency 1 in order to compensate for the delay time for the
establishment of a magnetic flux in the motor. F39 specifies the holding time for the stop frequency in order to stabilize
the motor speed at the stop of the inverter.
Data setting range: 0.0 to 60.0 (Hz)
„ Starting frequency 1 (F23)
F23 specifies the starting frequency at the startup of an inverter. Under V/f control, even if the starting frequency is set
at 0.0 Hz, the inverter starts at 0.1 Hz.
Data setting range: 0.00 to 10.00 (s)
„ Starting frequency 1 (Holding time) (F24)
F24 specifies the holding time for the starting frequency 1.
Data setting range: 0.0 to 60.0 (Hz)
„ Stop frequency (F25)
F25 specifies the stop frequency at the stop of the inverter. Under V/f control, even if the stop frequency is set at 0.0 Hz,
the inverter stops at 0.1 Hz.
„ Stop frequency (Holding time) (F39)
Data setting range: 0.00 to 10.00 (s)
F39 specifies the holding time for the stop frequency.
If the starting frequency is lower than the stop frequency, the inverter will not output any power as long as the
reference frequency does not exceed the stop frequency.
Under vector control without/with speed sensor
At the startup, the inverter first starts at the “0” speed and accelerates to the starting frequency according to the
specified acceleration time. After holding the starting frequency for the specified period, the inverter again accelerates
to the reference speed according to the specified acceleration time.
The inverter stops its output when the detected speed or reference one (specified by F38) reaches the stop frequency
specified by F25.
In addition, F24 specifies the holding time for the starting frequency 1 in order to compensate for the delay time for the
establishment of a magnetic flux in the motor. F39 specifies the holding time for the stop frequency in order to stabilize
the motor speed at the stop of the inverter.
5-51
„ Starting Frequency 1 (F23)
Data setting range: 0.0 to 60.0 (Hz)
F23 specifies the starting frequency at the startup of an inverter.
„ Starting Frequency 1 (Holding time) (F24)
Data setting range: 0.00 to 10.00 (s)
F24 specifies the holding time for the starting frequency 1.
„ Stop Frequency (F25)
Data setting range: 0.0 to 60.0 (Hz)
F25 specifies the stop frequency at the stop of the inverter.
„ Stop Frequency (Holding time) (F39)
Data setting range: 0.00 to 10.00 (s)
F39 specifies the holding time for the stop frequency.
Data for d24
Zero speed control
Not allowed at startup
1
Allowed at startup
Even setting the speed command at below the starting and stop
frequencies and turning a run command ON does not enable the zero
speed control.
To enable the zero speed control, set the speed command at above the
starting frequency and then start up the inverter again.
Setting the speed command at below the starting and stop frequencies
and turning a run command ON enables the zero speed control.
FUNCTION CODES
0
Descriptions
The table below shows the conditions for zero speed control to be enabled or disabled.
Speed command
At startup
At stop
Below the starting and
stop frequencies
Below the stop frequency
Run command
OFF
ON
ON
OFF
Data for d24
0
1
Chap. 5
„ Zero Speed Control (d24)
To enable zero speed control under vector control with speed sensor, it is necessary to set the speed command
(frequency command) at below the starting and stop frequencies. If the starting and stop frequencies are 0.0 Hz,
however, the zero speed control is enabled only when the speed command is 0.00 Hz. d24 specifies the operation for the
zero speed control at the startup of the inverter.
Operation
Stop (Gate OFF)
Stop (Gate OFF)
Zero speed control
Zero speed control
Stop (Gate OFF)
F codes
E codes
C codes
P codes
„ Stop Frequency (Detection mode) (F38) (Under vector control with speed sensor)
Data setting range: 0 (Detected speed), 1 (Reference speed)
F38 specifies whether the inverter judges when to shutdown its output by the detected speed or reference speed.
Although the inverter generally judges it by the detected speed, if a load exceeding the inverter capability such as
external excess load is applied, the inverter may not stop because the motor may not stop normally and the detected
speed may not reach the stop frequency level. If F38 data is set to "1" (reference speed), the inverter can stop without
fail because the reference speed reaches the stop frequency level even if the detected speed does not.
H codes
A codes
b codes
r codes
J codes
d codes
When such a situation is expected, select the reference speed for the general fail-safe operation.
U codes
y codes
5-52
F26, F27
Motor Sound (Carrier frequency and Tone)
H98 (Protection/Maintenance Function (Mode selection))
„ Motor Sound (Carrier frequency) (F26)
F26 controls the carrier frequency so as to reduce an audible noise generated by the motor or electromagnetic noise
from the inverter itself, and to decrease a leakage current from the main output (secondary) wirings.
Item
Characteristics
0.75
to
16 kHz
0.75
to
10 kHz
0.75
to
6 kHz
0.75
0.75
High
to
to
l
4 kHz
2 kHz
Low
High
l
Low
Large
Low
Low
Low
l
l
l
l
Small
High
High
High
Carrier frequency
Motor sound noise emission
Motor temperature
(due to harmonics components)
Ripples in output current waveform
Leakage current
Electromagnetic noise emission
Inverter loss
Remarks
0.4 to 55 kW (CT mode)
5.5 to 18.5 kW (VT mode)
75 to 400 kW (CT mode)
22 to 55 kW (VT mode)
500 and 630 kW (CT mode)
75 to 500 kW (VT mode)
630 kW (VT mode)
90 to 400 kW (MT mode)
Specifying a too low carrier frequency will cause the output current waveform to have a large amount of
ripples. As a result, the motor loss increases, causing the motor temperature to rise. Furthermore, the large
amount of ripples tends to cause a current limiting alarm. When the carrier frequency is set to 1 kHz or below,
therefore, reduce the load so that the inverter output current comes to be 80% or less of the rated current.
When a high carrier frequency is specified, the temperature of the inverter may rise due to a surrounding
temperature rise or an increase of the load. If it happens, the inverter automatically decreases the carrier
frequency to prevent the inverter overload alarm OX . With consideration for motor noise, the automatic
reduction of carrier frequency can be disabled. Refer to the description of H98.
It is recommended to set the carrier frequency at 5 kHz or above under vector control without/with speed
sensor. DO NOT set it at 1 kHz or below.
„ Motor Sound (Tone) (F27)
F27 changes the motor running sound tone (only for motors under V/f control). This setting is effective when the carrier
frequency specified by function code F26 is 7 kHz or lower. Changing the tone level may reduce the high and harsh
running noise from the motor.
If the tone level is set too high, the output current may become unstable, or mechanical vibration and noise may
increase.
Also, this function code may not be very effective for certain types of motor.
Data for F27
0
1
2
3
Function
Disable (Tone level 0)
Enable (Tone level 1)
Enable (Tone level 2)
Enable (Tone level 3)
5-53
F29 to F31
F32, F34,
F35
Analog Output [FM1] and [FM2] (Mode selection, Voltage adjustment, Function)
These function codes allow terminals [FM1] and [FM2] to output monitored data such as the output frequency and the
output current in an analog DC voltage or current. The magnitude of such analog voltage or current is adjustable.
„ Mode selection (F29 and F32)
F29 and F32 specify the property of the output to terminals [FM1] and [FM2], respectively. You need to set the slide
switches on the control printed circuit board (control PCB). Refer to Chapter 2 "Mounting and Wiring of the Inverter."
Output form
Voltage (0 to +10 VDC)
Current (4 to +20 mA DC)
Terminal [FM1]
Position of slide switch
Data for F29
SW4 on the control PCB
0
VO1
1
IO1
Terminal [FM2]
Position of slide switch
Data for F32
SW6 on the control PCB
0
VO2
1
IO2
„ Voltage adjustment (F30 and F34)
F30 allows you to adjust the output voltage within the range of 0 to 300%.
FUNCTION CODES
connecting an analog, cascade connection of a current output device is not available.
Keep the connection wire length as short as possible.
Chap. 5
The output current is not isolated from analog input, and does not have an isolated power supply. Therefore, if
an electrical potential relationship between the inverter and peripheral equipment has been established, e.g., by
„ Function (F31 and F35)
F31 specifies what is output to analog output terminals [FM1] and [FM2].
Data for
F31/F35
2
Function
(Monitor the following)
Output frequency of the inverter
Output frequency
(before slip compensation) (Equivalent to the motor synchronous
speed)
Output frequency
Output frequency of the inverter
(after slip compensation)
Output current
Output current (RMS) of the inverter
3
Output voltage
Output voltage (RMS) of the inverter
4
Output torque
5
Load factor
Motor shaft torque
Load factor
(Equivalent to the indication of the load
meter)
0
1
[FM1]/[FM2] output
6
Input power
Input power of the inverter
7
PID feedback amount
PG feedback value
(speed)
Feedback amount under PID control
Speed detected through the PG interface,
or estimated speed
8
9
DC link bus voltage
DC link bus voltage of the inverter
10
Universal AO
13
Motor output
Command via communications link
(Refer to the RS-485 Communication
User's Manual.)
Motor output (kW)
14
Calibration
Full scale output of the meter calibration
5-54
Meter scale
(Full scale at 100%)
Maximum frequency (F03)
F codes
Maximum frequency (F03)
Twice the inverter rated current
250 V for 200 V class series,
500 V for 400 V class series
Twice the rated motor torque
E codes
C codes
P codes
H codes
Twice the rated motor load
A codes
Twice the rated output of the
inverter
100% of the feedback amount
Maximum speed as 100%
b codes
r codes
J codes
500 V for 200 V class series,
1000 V for 400 V class series
d codes
20000 as 100%
U codes
Twice the rated motor output
This always outputs the full-scale
(100%).
y codes
Data for
F31/F35
15
Function
Meter scale
(Monitor the following)
(Full scale at 100%)
PID command (SV)
Command value under PID control
100% of the feedback amount
Output level of the PID controller under
16
PID output (MV)
Maximum frequency (F03)
PID control (Frequency command)
If F31/F35 = 16 (PID output), J01 = 3 (Dancer control), and J62 = 2 or 3 (Ratio compensation enabled), the
PID output is equivalent to the ratio against the primary reference frequency and may vary within r300% of
the frequency. The monitor displays the PID output in a converted absolute value. To indicate the value up to
the full-scale of 300%, set F30/F34 data to "33" (%).
[FM1]/[FM2] output
F37
Load Selection/ Auto Torque Boost/ Auto Energy Saving Operation 1
F09 (Torque Boost 1)
H67 (Auto Energy Saving Operation (Mode selection)
F37 specifies V/f pattern, torque boost type, and auto energy saving operation in accordance with the characteristics of
the load.
Specify the torque boost level with F09 in order to assure sufficient starting torque.
Data for F37
0
V/f pattern
Variable torque
V/f pattern
1
2
3
Linear
V/f pattern
Variable torque
V/f pattern
4
5
Linear
V/f pattern
Torque boost
Auto energy saving
Torque boost
specified by F09
Disable
Auto torque boost
Torque boost
specified by F09
Enable
Auto torque boost
Applicable load
Variable torque load
(General-purpose fans and pumps)
Constant torque load
Constant torque load
(To be selected if a motor may be
over-excited at no load.)
Variable torque load
(General-purpose fans and pumps)
Constant torque load
Constant torque load
(To be selected if a motor may be
over-excited at no load.)
If a required "load torque + acceleration toque" is more than 50% of the constant torque, it is recommended to
select the linear V/f pattern (factory default).
• Under the vector control with speed sensor, F37 is used to specify whether the auto energy saving operation
is enabled or disabled. (V/f pattern and torque boost are disabled.)
Data for F37
0 to 2
3 to 5
Operation
Auto energy saving operation OFF
Auto energy saving operation ON
• Under the vector control without speed sensor, both F37 and F09 are disabled. The auto energy saving
operation is also disabled.
„ V/f characteristics
The JAGUAR VXG series of inverters offers a variety of V/f patterns and torque boosts, which include V/f patterns
suitable for variable torque load such as general fans and pumps and for constant torque load (including special pumps
requiring high starting torque). Two types of torque boosts are available: manual and automatic.
Variable torque V/f pattern (F37 = 0)
Linear V/f pattern (F37 = 1)
5-55
When the variable torque V/f pattern is selected (F37 = 0 or 3), the output voltage may be low at a low
frequency zone, resulting in insufficient output torque, depending on the characteristics of the motor and load.
In such a case, it is recommended to increase the output voltage at the low frequency zone using the
non-linear V/f pattern.
Recommended value: H50 = 1/10 of the base frequency
H51 = 1/10 of the voltage at base frequency
• Manual torque boost (F09)
In torque boost using F09, constant voltage is added to the basic V/f pattern, regardless of the load. To secure a
sufficient starting torque, manually adjust the output voltage to optimally match the motor and its load by using F09.
Specify an appropriate level that guarantees smooth start-up and yet does not cause over-excitation at no or light load.
Torque boost per F09 ensures high driving stability since the output voltage remains constant regardless of the load
fluctuation.
Specify the F09 data in percentage to the rated voltage at base frequency 1 (F05). At factory shipment, F09 is preset to a
level that assures approx. 100% of starting torque.
• Specifying a high torque boost level will generate a high torque, but may cause overcurrent due to
over-excitation at no load. If you continue to drive the motor, it may overheat. To avoid such a situation,
adjust torque boost to an appropriate level.
• When the non-linear V/f pattern and the torque boost are used together, the torque boost takes effect below
the frequency on the non-linear V/f pattern’s point.
FUNCTION CODES
Data setting range: 0.0 to 20.0 (%) (100%/Rated voltage at base frequency)
Chap. 5
„ Torque boost
• Auto torque boost
If the auto torque boost is selected, the inverter automatically optimizes the output voltage to fit the motor with its load.
Under light load, the inverter decreases the output voltage to prevent the motor from over-excitation. Under heavy load,
it increases the output voltage to increase the output torque of the motor.
• Since this function relies also on the characteristics of the motor, set the base frequency 1 (F04), the rated
voltage at base frequency 1 (F05), and other pertinent motor parameters (P01 through P03 and P06 through
P99) in line with the motor capacity and characteristics, or else perform auto-tuning (P04).
• When a special motor is driven or the load does not have sufficient rigidity, the maximum torque might
decrease or the motor operation might become unstable. In such cases, do not use auto torque boost but
choose manual torque boost per F09 (F37 = 0 or 1).
F codes
„ Auto energy saving operation (H67)
If the auto energy saving operation is enabled, the inverter automatically controls the supply voltage to the motor to
minimize the total power loss of motor and inverter. (Note that this feature may not be effective depending upon the
motor or load characteristics. Check the advantage of energy saving before you actually apply this feature to your
machinery.)
You can select whether applying this feature to constant speed operation only or applying to constant speed operation
and accelerating/decelerating operation.
Data for H67
0
Auto energy saving operation
Enable only during running at constant speed
Enable during running at constant speed or accelerating/decelerating
1
(Note: For accelerating/decelerating, enable only when the load is light.)
If auto energy saving operation is enabled, the response to a motor speed change from constant speed operation may be
slow. Do not use this feature for such machinery that requires quick acceleration/deceleration.
5-56
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
• Use auto energy saving only where the base frequency is 60 Hz or lower. If the base frequency is set at 60
Hz or higher, you may get a little or no energy saving advantage. The auto energy saving operation is
designed for use with the frequency lower than the base frequency. If the frequency becomes higher than the
base frequency, the auto energy saving operation will be invalid.
• Since this function relies also on the characteristics of the motor, set the base frequency 1 (F04), the rated
voltage at base frequency 1 (F05), and other pertinent motor parameters (P01 through P03 and P06 through
P99) in line with the motor capacity and characteristics, or else perform auto-tuning (P04).
• Under the vector control without speed sensor, the auto energy saving operation is disabled.
F38, F39
Stop frequency (Detection mode, Holding time)
(Refer to F23.)
F40, F41
E16, E17 Torque Limiter 2-1, Torque Limiter 2-2
H73 Torque Limiter (Operating conditions)
H76 Torque Limiter (Frequency increment limit for braking)
Torque Limiter 1-1,
Torque Limiter 1-2
Under V/f control
If the inverter’s output torque exceeds the specified levels of the torque limiters (F40, F41, E16, E17, and E61 to E63),
the inverter controls the output frequency and limits the output torque for preventing a stall.
To use the torque limiters, it is necessary to configure the function codes listed in the table below.
In braking, the inverter increases the output frequency to limit the output torque. Depending on the conditions
during operation, the output frequency could dangerously increase. H76 (Frequency increment limit for
braking) is provided to limit the increasing frequency component.
Related function codes
Function code
Name
F40
Torque Limiter 1-1
V/f control Vector control
Y
Y
F41
Torque Limiter 1-2
Y
Y
E16
E17
H73
H74
H75
Torque Limiter 2-1
Torque Limiter 2-2
Torque Limiter (Operating conditions)
Torque Limiter (Control target)
Torque Limiter (Target quadrants)
Torque Limiter
(Frequency increment limit for braking)
Terminal [12] Extended Function
Terminal [C1] Extended Function
Terminal [V2] Extended Function
Y
Y
Y
N
N
Y
Y
Y
Y
Y
Y
N
Y
Y
H76
E61 to E63
Remarks
7: Analog torque limit value A
8: Analog torque limit value B
„ Torque limit control mode
Torque limit is performed by limiting torque current flowing across the motor.
The graph below shows the relationship between the torque and the output frequency at the constant torque current
limit.
5-57
„ Torque limiter 1-1, 1-2, 2-1 and 2-2 (F40, F41, E16 and E17)
Data setting range: -300 to 300 (%), 999 (Disable)
These function codes specify the operation level at which the torque limiters become activated, as the percentage of the
motor rated torque.
Function code
F40
F41
E16
E17
Name
Torque limiter 1-1
Torque limiter 1-2
Torque limiter 2-1
Torque limiter 2-2
Torque limit feature
Driving torque current limiter 1
Braking torque current limiter 1
Driving torque current limiter 2
Braking torque current limiter 2
Although the data setting range for F40, F41, E16, and E17 is from positive to negative values (–300% to
+300%), specify positive values in practice. If a negative value is specified, the inverter interprets it as an
Data for E61, E62, or E63
Function
7
Analog torque limit value A
8
Analog torque limit value B
Description
Use the analog input as the torque limit value specified by
function code data (= 7 or 8).
Input specifications: 200% / 10 V or 20 mA
If the same setting is made for different terminals, the priority order is E61>E62>E63.
FUNCTION CODES
„ Analog torque limit values (E61 to E63)
The torque limit values can be specified by analog inputs through terminals [12], [C1], and [V2] (voltage or current).
Set E61, E62, and E63 (Terminal [12] Extended Function, Terminal [C1] Extended Function, and Terminal [V2]
Extended Function) as listed below.
Chap. 5
absolute value.
The torque limiter determined depending on the overload current actually limits the torque current output.
Therefore, the torque current output is automatically limited at a value lower than 300%, the maximum setting
value.
„ Torque limiter levels specified via communications link (S10, S11)
The torque limiter levels can be changed via the communications link. Function codes S10 and S11 exclusively
reserved for the communications link respond to function codes F40 and F41.
„ Switching torque limiters
The torque limiters can be switched by the function code setting and the terminal command TL2/TL1 ("Select torque
limiter level 2/1") assigned to any of the digital input terminals.
To assign the TL2/TL1 as the terminal function, set any of E01 through E07 to "14." If no TL2/TL1 is assigned, torque
limiter levels 1-1 and 1-2 (F40 and F41) take effect by default.
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-58
„ Torque limiter (Operating conditions) (H73)
H73 specifies whether the torque limiter is enabled or disabled during acceleration/deceleration and running at constant
speed.
Data for H73
0
1
2
During accelerating/decelerating
Enable
Disable
Enable
During running at constant speed
Enable
Enable
Disable
„ Torque limiter (Frequency increment limit for braking) (H76)
Data setting range: 0.0 to 500.0 (Hz)
H76 specifies the increment limit of the frequency in limiting torque for braking. The factory default is 5.0 Hz. If the
increasing frequency during braking reaches the limit value, the torque limiters no longer function, resulting in an
overvoltage trip. Such a problem may be avoided by increasing the setting of H76.
The torque limiter and current limiter are very similar function each other. If both are activated concurrently,
they may conflict each other and cause hunting in the system. Avoid concurrent activation of these limiters.
Under vector control without/with speed sensor
If the inverter’s output torque exceeds the specified levels of the torque limiters (F40, F41, E16, E17, and E61 to E63),
the inverter controls the speed regulator's output (torque command) in speed control or a torque command in torque
control in order to limit the motor-generating torque.
To use the torque limiters, it is necessary to configure the function codes listed in the table below.
Related function codes
Function code
F40
F41
E16
E17
H73
H74
H75
H76
E61 to E63
Name
V/f control Vector control
Torque Limiter 1-1
Y
Y
Torque Limiter 1-2
Y
Y
Torque Limiter 2-1
Y
Y
Torque Limiter 2-2
Y
Y
Torque Limiter (Operating conditions)
Y
Y
Torque Limiter (Control target)
N
Y
Torque Limiter (Target quadrants)
N
Y
Torque Limiter
Y
N
(Frequency increment limit for braking)
Terminal [12] Extended Function
Terminal [C1] Extended Function
Y
Y
Terminal [V2] Extended Function
Remarks
7: Analog torque limit value A
8: Analog torque limit value B
„ Torque Limiter (Control target) (H74)
Under vector control, the inverter can limit motor-generating torque or output power, as well as a torque current
(default).
Data for H74
0
1
2
Control target
Motor-generating torque limit
Torque current limit
Output power limit
Torque
Torque pattern when the torque
current limit is 100% rating
100% rating
Torque pattern when the
torque limit is 50% rating
Torque pattern when the
power limit is 50% rating
50% rating
Speed
100% rating
200% rating
5-59
„ Torque Limiter (Target quadrants) (H75)
H75 selects the configuration of target quadrants (Drive/brake, Forward/reverse rotation) in which the specified torque
limiter(s) is activated, from "Drive/brake torque limit," "Same torque limit for all four quadrants," and "Upper/lower
torque limits" shown in the table below.
Data for H75
0: Drive/brake
Target quadrants
Torque limiter A applies to driving (both of forward and reverse), and torque limiter B to braking
(both of forward and reverse).
First quadrant:
Forward driving
Second quadrant:
Reverse braking
Torque limiter A
Torque limiter B
Torque limiter B
Torque limiter A
Chap. 5
Fourth quadrant:
Forward braking
Third quadrant:
Reverse driving
Torque limiter A applies to all four quadrants; that is, the same torque limit applies to both driving
and braking in the forward and reverse rotations.
Second quadrant:
Reverse braking
First quadrant:
Forward driving
Torque limiter A
Torque limiter A
Torque limiter A
Torque limiter A
Third quadrant:
Reverse driving
FUNCTION CODES
1: Same for all
four quadrants
Fourth quadrant:
Forward braking
2: Upper/lower
limits
Torque limiter A applies to the upper limit, and torque limiter B to the lower limit.
Depending upon the polarity of torque limiters A and B, the following patterns are available.
Pattern 1
Pattern 2
Pattern 3
Torque limiter A
Positive
Positive
Negative
Torque limiter B
Positive
Negative
Negative
Second quadrant:
Reverse braking
First quadrant:
Forward driving
Second quadrant:
Reverse braking
First quadrant:
Forward driving
Torque limiter A
Torque limiter A
Torque limiter B
Torque limiter B
Third quadrant:
Reverse driving
Fourth quadrant:
Forward braking
Third quadrant:
Reverse driving
Fourth quadrant:
Forward braking
Pattern 2
F codes
E codes
C codes
Pattern 1
P codes
Second quadrant:
Reverse braking
First quadrant:
Forward driving
H codes
A codes
Torque limiter A
b codes
Torque limiter B
Third quadrant:
Reverse driving
Fourth quadrant:
Forward braking
r codes
J codes
Pattern 3
d codes
• If the value of torque limiter A is less than that of torque limiter B, torque limiter A
applies to both the upper and lower limits.
• Selecting the "Upper/lower torque limits" may cause reciprocating oscillation between
the upper and lower limit values, depending upon a small difference between the upper
and lower limits, a slow response from the speed control sequence, and other
conditions.
5-60
U codes
y codes
„ Torque limiter 1-1, 1-2, 2-1 and 2-2 (F40, F41, E16 and E17)
Data setting range: -300 to 300 (%), 999 (Disable)
These function codes specify the operation level at which the torque limiters become activated, as the percentage of the
motor rated torque.
Function code
F40
F41
E16
E17
Name
Torque limiter 1-1
Torque limiter 1-2
Torque limiter 2-1
Torque limiter 2-2
Although the data setting range for F40, F41, E16, and E17 is from positive to negative values (–300% to
+300%), specify positive values in practice except when the "Upper/lower torque limits" (H75 = 2) is selected.
If a negative value is specified, the inverter interprets it as an absolute value.
The torque limiter determined depending on the overload current actually limits the torque current output.
Therefore, the torque current output is automatically limited at a value lower than 300%, the maximum setting
value.
„ Analog torque limit values (E61 to E63)
The torque limit values can be specified by analog inputs through terminals [12], [C1], and [V2] (voltage or current).
Set E61, E62, and E63 (Terminal [12] Extended Function, Terminal [C1] Extended Function, and Terminal [V2]
Extended Function) as listed below.
Data for E61, E62, or E63
Function
7
Analog torque limit value A
8
Analog torque limit value B
Description
Use the analog input as the torque limit value specified by
function code data (= 7 or 8).
Input specifications: 200% / 10 V or 20 mA
If the same setting is made for different terminals, the priority order is E61>E62>E63.
„ Torque limiter levels specified via communications link (S10, S11)
The torque limiter levels can be changed via the communications link. Function codes S10 and S11 exclusively
reserved for the communications link respond to function codes F40 and F41.
„ Switching torque limiters
The torque limiters can be switched by the function code setting and the terminal command TL2/TL1 ("Select torque
limiter level 2/1") assigned to any of the digital input terminals.
To assign the TL2/TL1 as the terminal function, set any of E01 through E07 to "14." If no TL2/TL1 is assigned, torque
limiter levels 1-1 and 1-2 (F40 and F41) take effect by default.
5-61
„ Torque limiter (Operating conditions) (H73)
H73 specifies whether the torque limiter is enabled or disabled during acceleration/deceleration and running at constant
speed.
Data for H73
0
During accelerating/decelerating
Enable
During running at constant speed
Enable
1
2
Disable
Enable
Enable
Disable
The torque limiter and current limiter are very similar function each other. If both are activated concurrently,
they may conflict each other and cause hunting in the system. Avoid concurrent activation of these limiters.
F42
Drive Control Selection 1
H68 (Slip Compensation 1 (Operating conditions))
F42 specifies the motor drive control.
5
6
Speed feedback
Speed control
Frequency control
Disable
V/f control
Frequency control
with slip compensation
Frequency control
with automatic speed
Dynamic torque vector control with speed sensor
regulator (ASR)
Vector control without speed sensor
Estimated speed Speed control
with automatic speed
Vector control
Vector control with speed sensor
Enable
regulator (ASR)
Enable
FUNCTION CODES
4
Basic control
Chap. 5
Data for
Drive control
F42
0
V/f control with slip compensation inactive
Dynamic torque vector control
1
(with slip compensation and auto torque boost)
2
V/f control with slip compensation active
3
V/f control with speed sensor
„ V/f control with slip compensation inactive
Under this control, the inverter controls a motor with the voltage and frequency according to the V/f pattern specified
by function codes. This control disables all automatically controlled features such as the slip compensation, so no
unpredictable output fluctuation, enabling stable operation with constant output frequency.
„ V/f control with slip compensation active
Applying any load to an induction motor causes a rotational slip due to the motor characteristics, decreasing the motor
rotation. The inverter’s slip compensation function first presumes the slip value of the motor based on the motor torque
generated and raises the output frequency to compensate for the decrease in motor rotation. This prevents the motor
from decreasing the rotation due to the slip.
That is, this function is effective for improving the motor speed control accuracy.
P12
Function code
Rated slip frequency
P09
Slip compensation gain for driving
P11
Slip compensation gain for braking
P10
Slip compensation response time
Operation
Specify the rated slip frequency.
Adjust the slip compensation amount for driving.
Slip compensation amount for driving =
Rated slip x Slip compensation gain for driving
Adjust the slip compensation amount for braking.
Slip compensation amount for braking =
Rated slip x Slip compensation gain for braking
Specify the slip compensation response time.
Basically, there is no need to modify the default setting.
To improve the accuracy of slip compensation, perform auto-tuning.
Data for H68
0
1
2
3
Enable
Disable
Enable
Disable
Enable
Enable
Enable
Enable
E codes
C codes
P codes
H codes
H68 enables or disables the slip compensation function according to the motor driving conditions.
Motor driving conditions
Accel/Decel
Constant speed
F codes
A codes
Motor driving frequency zone
Base frequency or below Above the base frequency
Enable
Enable
Enable
Enable
Enable
Enable
Disable
Disable
b codes
r codes
J codes
d codes
U codes
y codes
5-62
„ Dynamic torque vector control
To get the maximal torque out of a motor, this control calculates the motor torque for the load applied and uses it to
optimize the voltage and current vector output.
Selecting this control automatically enables the auto torque boost and slip compensation function.
This control is effective for improving the system response to external disturbances such as load fluctuation, and the
motor speed control accuracy.
Note that the inverter may not respond to a rapid load fluctuation since this control is an open-loop V/f control that does
not perform the current control, unlike the vector control. The advantages of this control include larger maximum
torque per output current than that the vector control.
„ V/f control with speed sensor
Applying any load to an induction motor causes a rotational slip due to the motor characteristics, decreasing the motor
rotation. Under V/f control with speed sensor, the inverter detects the motor rotation using the encoder mounted on the
motor shaft and compensates for the decrease in slip frequency by the PI control to match the motor rotation with the
commanded speed. This improves the motor speed control accuracy.
„ Dynamic torque vector control with speed sensor
The difference from the "V/f control with speed sensor" stated above is to calculate the motor torque for the load
applied and use it to optimize the voltage and current vector output for getting the maximal torque out of a motor.
This control is effective for improving the system response to external disturbances such as load fluctuations, and the
motor speed control accuracy.
„ Vector control without speed sensor
This control estimates the motor speed based on the inverter's output voltage and current to use the estimated speed for
speed control. In addition, it decomposes the motor drive current into the exciting and torque current components, and
controls each of those components in vector. No PG (pulse generator) interface card is required. It is possible to obtain
the desired response by adjusting the control constants (PI constants) using the speed regulator (PI controller).
Since this control controls the motor current, it is necessary to secure some voltage margin between the voltage that the
inverter can output and the induced voltage of the motor, by keeping the former lower than the latter.
Although the voltage of the general-purpose motor has usually been adjusted to match the commercial power, keeping
the motor terminal voltage low is necessary in order to secure the voltage margin. If the motor is driven under this
control with the motor terminal voltage being kept low, however, the rated torque cannot be obtained even when the
rated current originally specified for the motor is applied. To secure the rated torque, therefore, it is necessary to use a
motor with higher rated current. (This also applies to the vector control with speed sensor.)
This control is not available in MT-mode inverters, so do not set F42 data to "5" for those inverters.
„ Vector control with speed sensor
This control requires an optional PG (pulse generator) and an optional PG interface card to be mounted on a motor shaft
and an inverter, respectively. The inverter detects the motor's rotational position and speed from PG feedback signals
and uses them for speed control. In addition, it decomposes the motor drive current into the exciting and torque current
components, and controls each of components in vector.
The desired response can be obtained by adjusting the control constants (PI constants) and using the speed regulator (PI
controller). This control enables the speed control with higher accuracy and quicker response than the vector control
without speed sensor.
Since slip compensation, dynamic torque vector control, and vector control without/with speed sensor use
parameters, the following conditions should be satisfied; otherwise, full control performance may not be
obtained.
• A single motor should be controlled per inverter.
• Motor parameters P02, P03, P06 to P23, P55 and P56 are properly configured. Or, auto-tuning (P04) is
performed.
• The capacity of the motor to be controlled should be two or more ranks lower than that of the inverter under
the dynamic torque vector control; it should be the same as the inverter under the vector control without/with
speed sensor. Otherwise, the inverter may not control the motor due to decrease of the current detection
resolution.
• The wiring distance between the inverter and motor should be 50 m or less. If it is longer, the inverter may not
control the motor due to leakage current flowing through stray capacitance to the ground or between wires.
Especially, small capacity inverters whose rated current is also small may be unable to control the motor
correctly even when the wiring is less than 50 m. In that case, make the wiring length as short as possible or
use a wire with small stray capacitance (e.g., loosely-bundled cable) to minimize the stray capacitance.
motor
5-63
F43, F44
Current Limiter (Mode selection, Level)
H12 (Instantaneous Overcurrent Limiting (Mode selection))
When the output current of the inverter exceeds the level specified by the current limiter (F44), the inverter
automatically manages its output frequency to prevent a stall and limit the output current.
The default setting is 160%, 145% and 130% for CT-, MT- and VT-mode inverters, respectively. (Once the CT, MT, or
VT mode is selected by F80, the current limit for each mode is automatically specified.)
If 160% (145% or 130%) or over of overcurrent instantaneously flows and the output frequency decreases by this
current limit that is undesired, consider increasing the current limit level.
If F43 = 1, the current limiter is enabled only during constant speed operation. If F43 = 2, the current limiter is enabled
during both of acceleration and constant speed operation. Choose F43 = 1 if you need to run the inverter at full
capability during acceleration and to limit the output current during constant speed operation.
„ Mode selection (F43)
F43 selects the motor running state in which the current limiter will be active.
Running states that enable the current limiter
During constant speed
During deceleration
Disable
Disable
Enable
Disable
Enable
Disable
Data setting range: 20 to 200 (%) (in ratio to the inverter rating)
„ Level (F44)
F44 specifies the operation level at which the output current limiter becomes activated, in ratio to the inverter rating.
The inverter's rated current differs depending upon the CT, MT, or VT mode selected.
„ Instantaneous Overcurrent Limiting (Mode selection) (H12)
H12 specifies whether the inverter invokes the current limit processing or enters the overcurrent trip when its output
current exceeds the instantaneous overcurrent limiting level. Under the current limit processing, the inverter
immediately turns OFF its output gate to suppress the further current increase and continues to control the output
frequency.
Data for H12
0
1
FUNCTION CODES
0
1
2
During acceleration
Disable
Disable
Enable
Chap. 5
Data for F43
Function
Disable
An overcurrent trip occurs at the instantaneous overcurrent limiting level.
Enable
If any problem occurs in use of the equipment or machine is expected when the motor torque temporarily drops during
current limiting processing, it is necessary to cause an overcurrent trip (H12 = 0) and actuate a mechanical brake at the
same time.
X
• Since the current limit operation with F43 and F44 is performed by software, it may cause a delay in control.
If you need a quick response current limiting, also enable the instantaneous overcurrent limiting with H12.
• If an excessive load is applied when the current limiter operation level is set extremely low, the inverter will
rapidly lower its output frequency. This may cause an overvoltage trip or dangerous turnover of the motor
rotation due to undershooting. Depending on the load, extremely short acceleration time may activate the
current limiting to suppress the increase of the inverter output frequency, causing the system oscillation
(hunting) or activating the inverter overvoltage trip (alarm
). When specifying the acceleration time,
therefore, you need to take into account machinery characteristics and moment of inertia of the load.
• The torque limiter and current limiter are very similar function each other. If both are activated concurrently,
they may conflict each other and cause hunting in the system. Avoid concurrent activation of these limiters.
• The vector control itself contains the current control system, so it disables the current limiter specified by
F43 and F44, as well as automatically disabling the instantaneous overcurrent limiting (specified by H12).
Accordingly, the inverter causes an overcurrent trip when its output current exceeds the instantaneous
overcurrent limiting level.
F codes
E codes
C codes
P codes
H codes
A codes
b codes
F50 to F52
Electronic Thermal Overload Protection for Braking Resistor
(Discharging capability, Allowable average loss and Resistance)
These function codes specify the electronic thermal overload protection feature for the braking resistor.
Set the discharging capability, allowable average loss and resistance to F50, F51 and F52, respectively. These values
are determined by the inverter and braking resistor models. For the discharging capability, allowable average loss and
resistance, refer to JAGUAR VXG User's Manual, Chapter 4 "SELECTING PERIPHERAL EQUIPMENT." The values
listed in the manual are for standard models and 10% ED models of the braking resistors which IMO can supply. If you
use a braking resistor of other manufacturer, confirm the corresponding values with the manufacturer, and set the
function codes accordingly.
5-64
r codes
J codes
d codes
U codes
y codes
Depending on the thermal marginal characteristics of the braking resistor, the electronic thermal overload
protection feature may act so that the inverter issues the overheat protection alarm GEK even if the actual
temperature rise is not large enough. If it happens, review the relationship between the performance index of
the braking resistor and settings of related function codes.
The standard models of braking resistor can output temperature detection signal for overheat. Assign an
"Enable external alarm trip" terminal command THR to any of digital input terminals [X1] to [X7], [FWD]
and [REV] and connect that terminal and its common terminal to braking resistor's terminals 2 and 1.
Calculating the discharging capability and allowable average loss of the braking resistor and configuring the
function code data
When using any non-Fuji braking resistor, inquire of the resistor manufacturer about the resistor rating and then
configure the related function codes.
The calculation procedures for the discharging capability and allowable average loss of the braking resistor differ
depending on the application of the braking load as shown below.
- Applying braking load during deceleration
In usual deceleration, the braking load decreases as the speed slows down. In the deceleration with constant torque, the
braking load decreases in proportion to the speed. Use Expressions (1) and (3) given below.
- Applying braking load during running at a constant speed
Different from during deceleration, in applications where the braking load is externally applied during running at a
constant speed, the braking load is constant. Use Expressions (2) and (4) given below.
Braking load (kW)
Braking load (kW)
Time
Time
Applying braking load during deceleration
Applying braking load during running at a constant speed
„ Discharging capability (F50)
The discharging capability refers to kWs allowable for a single braking cycle, which is obtained based on the braking
time and the motor rated capacity.
Data for F50
0
1 to 9000
OFF
Function
To be applied to the braking resistor built-in type
1 to 9000 (kWs)
Disable the electronic thermal overload protection
During deceleration:
Discharging capability (kWs) =
Braking time (s) 㽢 Motor rated capacity (kW)
Expression (1)
2
During running at a constant speed:
Discharging capability (kWs) = Braking time (s) u Motor rated capacity (kW)
Expression (2)
When the F50 data is set to "0" (To be applied to the braking resistor built-in type), no specification of the
discharging capability is required.
„ Allowable average loss (F51)
The allowable average loss refers to a tolerance for motor continuous operation, which is obtained based on the %ED
(%) and motor rated capacity (kW).
Data for F51
0.001 to 99.99
Function
0.001 to 99.99 (kW)
During deceleration:
Allowable average loss (kWs) =
%ED(%)
㽢 Motor rated capacity (kW)
100
2
Expression (3)
%ED(%)
㽢 Motor rated capacity (kW)
100
Expression (4)
During constant speed operation:
Allowable average loss (kWs) =
„ Resistance (F52)
F52 specifies the resistance of the braking resistor.
5-65
F80
Switching between CT, MT and VT drive modes
F80 specifies whether to drive the inverter in the Constant Torque (CT), medium Torque (MT) or Variable Torque (VT)
mode.
To change the F80 data, it is necessary to press the"
+
keys" or "
+
keys" (simultaneous keying).
Drive mode
Application
0
CT (High Duty)
mode
(default)
Heavy load
1
VT (Low Duty)
mode
Light load
2
MT (Medium
Duty) mode
Medium load
Overload
capability
Maximum
frequency
150% for 1 min.
200% for 3 s
500 Hz
120% for 1 min.
120 Hz
150% for 1 min.
120 Hz
Continuous current rating level
Capable of driving a motor whose
capacity is the same as the
inverter's
Capable of driving a motor whose
capacity is one or two ranks higher
than the inverter's.
Capable of driving a motor whose
capacity is one rank higher than the
inverter's.
In the MT/VT mode, the continuous current rating allows the inverter to drive a motor with one or two ranks higher
capacity, but the overload capability (%) against the continuous current rating is lower than that of the CT mode. For
the rated current level, see Chapter 8 "SPECIFICATIONS."
Function
codes
Name
CT mode
F21
DC braking 1
Setting range: 0 to
(Braking level) 100%
F26
Setting range:
0.75 to 16 kHz
(0.4 to 55 kW)
0.75 to 10 kHz
(75 to 400 kW)
0.75 to 6 kHz
(500 and 630 kW)
Motor sound
(Carrier
frequency)
F44
Current limiter
Initial value: 160%
(Level)
F03
Maximum
frequency 1
Current
indication and
output
Setting range:
25 to 500 Hz
Upper limit: 500 Hz
Based on the rated
current level for CT
mode
MT mode
VT mode
Remarks
Setting range: 0 to 80%
Setting range:
0.75 to 2 kHz
(90 to 400 kW)
Setting range:
0.75 to 16 kHz
(5.5 to 18.5 kW)
0.75 to 10 kHz
(22 to 55 kW)
0.75 to 6 kHz
(75 to 500 kW)
0.75 to 4 kHz
(630 kW)
In the MT/VT mode, a
value out of the range, if
specified, automatically
changes to the
maximum value
allowable in the MT/VT
mode.
Switching the drive
mode between CT, MT
and VT with function
Initial value: 145% Initial value: 130% code F80 automatically
initializes the F44 data
to the value specified at
left.
In the MT/VT mode, if
the maximum frequency
Setting range: 25 to 500 Hz
exceeds 120 Hz, the
actual output frequency
Upper limit: 120 Hz
is internally limited to
120 Hz.
Based on the rated Based on the rated
current level for
current level for
MT mode
VT mode
Switching to the VT mode does not automatically change the motor rated capacity (P02) to the one for the motor with
one size higher capacity, so configure the P02 data to match the applied motor rating as required.
FUNCTION CODES
The MT- and VT-mode inverters are subject to restrictions on the function code data setting range and internal
processing as listed below.
Chap. 5
Data for
F80
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-66
5.2.2 E codes (Extension Terminal Functions)
E01 to E07 Terminal [X1] to [X7] Function
E98 (Terminal [FWD] Function)
E99 (Terminal [REV] Function)
Function codes E01 to E07, E98 and E99 allow you to assign commands to terminals [X1] to [X7], [FWD], and [REV]
which are general-purpose, programmable, digital input terminals.
These function codes may also switch the logic system between normal and negative to define how the inverter logic
interprets either ON or OFF status of each terminal. The default setting is normal logic system "Active ON." So,
explanations that follow are given in normal logic system "Active ON." The descriptions are, in principle, arranged in
the numerical order of assigned data. However, highly relevant signals are collectively described where one of them
first appears. Refer to the function codes in the "Related function codes" column, if any.
The JAGUAR VXG runs under V/f control, dynamic torque vector control, V/f control with speed sensor, dynamic
torque vector control with speed sensor, vector control without speed sensor, or vector control with speed sensor. Some
function codes apply exclusively to the specific drive control, which is indicated by letters Y (Applicable) and N (Not
applicable) in the "Drive control" column in the table given below. (Refer to page 5-2.)
• Ensure safety before modifying the function code settings.
Run commands (e.g., "Run forward" FWD), stop commands (e.g., "Coast to a stop" BX), and frequency change
commands can be assigned to digital input terminals. Depending upon the assignment states of those terminals,
modifying the function code setting may cause a sudden motor start or an abrupt change in speed.
• When the inverter is controlled with the digital input signals, switching run or frequency command sources with
the related terminal commands (e.g., SS1, SS2, SS4, SS8, Hz2/Hz1, Hz/PID, IVS, and LE) may cause a sudden
motor start or an abrupt change in speed.
An accident or physical injury may result.
Function code data
Active ON Active OFF
Terminal commands assigned
Symbol
0
1
2
3
4
5
6
7
8
1009
1000
1001
1002
1003
1004
1005
1006
1007
1008
9
Select ACC/DEC time (2 steps)
Select ACC/DEC time (4 steps)
Enable 3-wire operation
Coast to a stop
Reset alarm
Enable external alarm trip
SS1
SS2
SS4
SS8
RT1
RT2
HLD
BX
RST
THR
10
1010
Ready for jogging
JOG
11
12
13
1011
1012
Select frequency command 2/1
Select motor 2
Enable DC braking
Hz2/Hz1
M2
DCBRK
14
1014
Select torque limiter level 2/1
TL2/TL1
15
16
17

1017
Switch to commercial power (50 Hz)
Switch to commercial power (60 Hz)
UP (Increase output frequency)
SW50
SW60
UP
18
1018
DOWN (Decrease output frequency)
DOWN
19
1019
Enable data change with keypad
WE-KP
20
1020
Cancel PID control
Hz/PID
21
22
23
1021
1022
1023
Switch normal/inverse operation
Interlock
Cancel torque control
Enable communications link via RS-485
or fieldbus (option)
Universal DI
Enable auto search for idling motor
speed at starting
Force to stop
IVS
IL
Hz/TRQ


24
1024
25
1025
26
1026
1030
30
Select multi-frequency (0 to 15 steps)
5-67
Drive control
Related
PG
w/ Torque function codes
V/f V/f w/o
PG PG control
Y Y Y Y
N
Y Y Y Y
N
C05 to C19
Y Y Y Y
N
Y Y Y Y
N
Y Y Y Y
N F07, F08,
Y Y Y Y
N E10 to E15
Y Y Y Y
Y F02
Y Y Y Y

Y
Y Y Y Y

Y
Y Y Y Y

Y
C20,
Y Y Y Y
N H54, H55,
d09 to d13
Y Y Y Y
N F01, C30
Y A42
Y Y Y Y
Y Y Y Y
N F20 to F22
F40, F41,
Y
Y Y Y Y
E16, E17
Y Y N N
N

N
Y Y N N

Y Y Y Y
N Frequency
command:
F01, C30
Y Y Y Y
N PID command:
J02
Y Y Y Y
Y F00
J01 to J19,
N
Y Y Y Y
J56 to J62
Y Y Y Y
N C53, J01
Y F14
Y Y Y Y
N N N N
Y H18
LE
Y
Y
Y
Y
Y
U-DI
Y
Y
Y
Y
Y
STM
Y
Y
Y
N
Y
H09, d67
STOP
Y
Y
Y
Y
Y
F07, H56
H30, y98

Function code data
Active ON Active OFF
Terminal commands assigned
Symbol
1035
36
37
39
1036
1037
40

41

47
1047
48

49
1049
70
1070
71
1071
72
1072
73
1073
74
1074
75
1075
76
77
1033
34
PID-RST
Y
Y
Y
Y
N
PID-HLD
Y
Y
Y
Y
N
Select local (keypad) operation
LOC
Y
Y
Y
Y
Y
M3
M4
DWP
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
ISW50
Y
Y
N
N
N
ISW60
Y
Y
N
N
N
LOCK
N
N
N
Y
N
PIN
Y
Y
Y
Y
Y
SIGN
Y
Y
Y
Y
Y
Hz/LSC
Y
Y
Y
Y
N
LSC-HLD
Y
Y
Y
Y
N
CRUN-M1
Y
Y
N
N
Y
CRUN-M2
Y
Y
N
N
Y
CRUN-M3
Y
Y
N
N
Y
CRUN-M4
Y
Y
N
N
Y
1076
1077
Select motor 3
Select motor 4
Protect motor from dew condensation
Enable integrated sequence to switch to
commercial power (50 Hz)
Enable integrated sequence to switch to
commercial power (60 Hz)
Servo-lock command
Pulse train input
(available only on terminal [X7])
Pulse train sign
(available on terminals except [X7])
Cancel constant peripheral speed control
Hold the constant peripheral speed
control frequency in the memory
Count the run time of commercial
power-driven motor 1
Count the run time of commercial
power-driven motor 2
Count the run time of commercial
power-driven motor 3
Count the run time of commercial
power-driven motor 4
Select droop control
Cancel PG alarm
DROOP
PG-CCL
Y
N
Y
Y
Y
N
Y
Y
N
Y
80
1080
Cancel customizable logic
CLC
Y
Y
Y
Y
Y
81
1081
CLTC
Y
Y
Y
Y
Y
98

FWD
Y
Y
Y
Y
Y
99

REV
Y
Y
Y
Y
Y
100

Clear all customizable logic timers
Run forward
(Exclusively assigned to [FWD] and
[REV] terminals by E98 and E99)
Run reverse
(Exclusively assigned to [FWD] and
[REV] terminals by E98 and E99)
No function assigned
NONE
Y
Y
Y
Y
Y

J01 to J19,
J56 to J62
(See Section
4.2.2.)
A42, b42
A42, r42
J21
J22
J97 to J99
F01, C30,
d62, d63
d41
H44, H94
FUNCTION CODES
35
1032
33
Chap. 5
EXITE
1034
Pre-excitation
Reset PID integral and differential
components
Hold PID integral component
32
Drive control
Related
PG
w/ Torque function codes
V/f V/f w/o
PG PG control
N N Y
Y
N H84, H85
H28

E01 to E07,
U81 to U85
F02
U81 to U85
Some negative logic (Active OFF) commands cannot be assigned to the functions marked with "" in the
"Active OFF" column.
The "Enable external alarm trip" (data = 1009) and "Force to stop" (data = 1030) are fail-safe terminal
commands. In the case of "Enable external alarm trip," when data = 1009, "Active ON" (alarm is triggered
when ON); when data = 9, "Active OFF" (alarm is triggered when OFF).
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-68
Terminal function assignment and data setting
„ Coast to a stop -- BX (Function code data = 7)
Turning this terminal command ON immediately shuts down the inverter output so that the motor coasts to a stop
without issuing any alarms.
„ Reset alarm -- RST (Function code data = 8)
Turning this terminal command ON clears the ALM state--alarm output (for any fault). Turning it OFF erases the alarm
display and clears the alarm hold state.
When you turn the RST command ON, keep it ON for 10 ms or more. This command should be kept OFF for the
normal inverter operation.
„ Enable external alarm trip -- THR (Function code data = 9)
Turning this terminal command OFF immediately shuts down the inverter output (so that the motor coasts to a stop),
displays the alarm K, and outputs the alarm relay (for any fault) ALM. The THR command is self-held, and is reset
when an alarm reset takes place.
Use this alarm trip command from external equipment when you have to immediately shut down the inverter
output in the event of an abnormal situation in peripheral equipment.
„ Switch to commercial power for 50 Hz or 60 Hz -- SW50 and SW60 (Function code data = 15 and 16)
When an external sequence switches the motor drive power from the commercial line to the inverter, inputting the
terminal command SW50 or SW60 at the specified timing enables the inverter to start running the motor with the
current commercial power frequency, regardless of settings of the reference/output frequency in the inverter. A running
motor driven by commercial power is carried on into inverter operation. This command helps you smoothly switch the
motor drive power source, when the motor is being driven by commercial power, from the commercial power to the
inverter power.
For details, refer to the following table, the operation schemes, and an example of external circuit and its operation time
scheme on the following pages.
Assignment
SW50
SW60
The inverter:
Starts at 50 Hz.
Starts at 60 Hz.
Description
Do not concurrently assign both SW50 and SW60.
5-69
Operation Schemes
• When the motor speed remains almost the same during coast-to-stop:
FUNCTION CODES
• When the motor speed decreases significantly during coast-to-stop (with the current limiter activated):
Chap. 5
• Secure more than 0.1 second after turning ON the "Switch to commercial power" signal before turning ON a
run command.
• Secure more than 0.2 second of an overlapping period with both the "Switch to commercial power" signal
and run command being ON.
• If an alarm has been issued or BX has been ON when the motor drive source is switched from the
commercial power to the inverter, the inverter will not be started at the commercial power frequency and
will remain OFF. After the alarm has been reset or BX turned OFF, operation at the frequency of the
commercial power will not be continued, and the inverter will be started at the ordinary starting frequency.
If you wish to switch the motor drive source from the commercial line to the inverter, be sure to turn BX
OFF before the "Switch to commercial power" signal is turned OFF.
• When switching the motor drive source from the inverter to commercial power, adjust the inverter's
reference frequency at or slightly higher than that of the commercial power frequency beforehand, taking
into consideration the motor speed down during the coast-to-stop period produced by switching.
• Note that when the motor drive source is switched from the inverter to the commercial power, a high inrush
current will be generated, because the phase of the commercial power usually does not match the motor
speed at the switching. Make sure that the power supply and all the peripheral equipment are capable of
withstanding this inrush current.
• If you have enabled "Restart after momentary power failure" (F14 = 3, 4, or 5), keep BX ON during
commercial power driven operation to prevent the inverter from restarting after a momentary power failure.
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-70
Example of Sequence Circuit
Note 1) Emergency switch
Manual switch provided for the event that the motor drive source cannot be switched normally to the
commercial power due to a serious problem of the inverter
Note 2) When any alarm has occurred inside the inverter, the motor drive source will automatically be switched to the
commercial power.
5-71
Example of Operation Time Scheme
Chap. 5
FUNCTION CODES
Alternatively, you may use the integrated sequence by which some of the actions above are automatically
performed by the inverter itself. For details, refer to the description of ISW50 and ISW60.
„ Cancel PID control -- Hz/PID (Function code data = 20)
Turning this terminal command ON disables the PID control.
If the PID control is disabled with this command, the inverter runs the motor with the reference frequency manually set
by any of the multi-frequency, keypad, analog input, etc.
Function
Terminal command Hz/PID
OFF
Enable PID control
ON
Disable PID control/Enable manual frequency settings
( Refer to the descriptions of J01 through J19 and J56 through J62.)
„ Switch normal/inverse operation -- IVS (Function code data = 21)
This terminal command switches the output frequency control between normal (proportional to the input value) and
inverse in analog frequency setting or under PID process control. To select the inverse operation, turn the IVS ON.
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
The normal/inverse switching operation is useful for air-conditioners that require switching between cooling
and heating. In cooling, the speed of the fan motor (output frequency of the inverter) is increased to lower the
temperature. In heating, it is reduced to lower the temperature. This switching is realized by this IVS terminal
command.
5-72
y codes
• When the inverter is driven by an external analog frequency command sources (terminals [12], [C1] and [V2]):
Switching normal/inverse operation can apply only to the analog frequency command sources (terminals [12], [C1] and
[V2]) in frequency command 1 (F01) and does not affect frequency command 2 (C30) or UP/DOWN control.
As listed below, the combination of the "Selection of normal/inverse operation for frequency command 1" (C53) and
the IVS terminal command determines the final operation.
Combination of C53 and IVS
Data for C53
0: Normal operation
1: Inverse operation
IVS
OFF
ON
OFF
ON
Final operation
Normal
Inverse
Inverse
Normal
• When the process control is performed by the PID processor integrated in the inverter:
The terminal command Hz/PID ("Cancel PID control") can switch the PID control between enabled (process is to be
controlled by the PID processor) and disabled (process is to be controlled by the manual frequency setting). In either
case, the combination of the "PID control" (J01) or "Selection of normal/inverse operation for frequency command 1"
(C53) and the terminal command IVS determines the final operation as listed below.
When the PID control is enabled:
The normal/inverse operation selection for the PID processor output (reference frequency) is as follows.
IVS
OFF
ON
OFF
ON
PID control (Mode selection) (J01)
1: Enable (normal operation)
2: Enable (inverse operation)
Final operation
Normal
Inverse
Inverse
Normal
When the PID control is disabled:
The normal/inverse operation selection for the manual reference frequency is as follows.
Selection of normal/inverse operation for frequency
command 1 (C53)
0: Normal operation
1: Inverse operation
IVS
Final operation
–
–
Normal
Inverse
When the process control is performed by the PID control facility integrated in the inverter, the IVS is used
to switch the PID processor output (reference frequency) between normal and inverse, and has no effect on
any normal/inverse operation selection of the manual frequency setting.
Refer to the descriptions of J01 through J19 and J56 through J62.
„ Universal DI -- U-DI (Function code data = 25)
Using U-DI enables the inverter to monitor digital signals sent from the peripheral equipment via an RS-485
communications link or a fieldbus option by feeding those signals to the digital input terminals. Signals assigned to the
universal DI are simply monitored and do not operate the inverter.
For an access to universal DI via the RS-485 or fieldbus communications link, refer to their respective Instruction
Manuals.
„ Force to stop -- STOP (Function code data = 30)
Turning this terminal command OFF causes the motor to decelerate to a stop in accordance with the H56 data
(Deceleration time for forced stop). After the motor stops, the inverter enters the alarm state with the alarm HU
displayed. ( Refer to the description of F07.)
„ Reset PID integral and differential components -- PID-RST (Function code data = 33)
Turning this terminal command ON resets the integral and differential components of the PID processor. ( Refer to
the descriptions of J01 through J19 and J56 through J62.)
„ Hold PID integral component -- PID-HLD (Function code data = 34)
Turning this terminal command ON holds the integral components of the PID processor. ( Refer to the descriptions
of J01 through J19 and J56 through J62.)
5-73
„ Enable integrated sequence to switch to commercial power (50 Hz) and (60 Hz) -- ISW50 and ISW60
(Function code data = 40 and 41)
With the terminal command ISW50 or ISW60 assigned, the inverter controls the magnetic contactor that switches the
motor drive source between the commercial power and the inverter output according to the integrated sequence.
This control is effective when not only ISW50 or ISW60* has been assigned to the input terminal but also the SW88
and SW52-2 signals have been assigned to the output terminals. (It is not essential to assign the SW52-1 signal.)
* The ISW50 or ISW60 should be selected depending upon the frequency of the commercial power; the former for 50
Hz and the latter for 60 Hz.
For details of these commands, refer to the circuit diagrams and timing schemes given below.
Operation
(Switching from commercial power to inverter)
Terminal command assigned
ISW50
Enable integrated sequence to switch to commercial power (50 Hz)
ISW60
Enable integrated sequence to switch to commercial power (60 Hz)
Start at 60 Hz.
Chap. 5
Start at 50 Hz.
Do not assign both ISW50 and ISW60 at the same time. Doing so cannot guarantee the result.
FUNCTION CODES
Circuit Diagram and Configuration
Main Circuit
F codes
E codes
C codes
P codes
H codes
A codes
Configuration of Control Circuit
b codes
Summary of Operation
r codes
Input
ISW50 or ISW60
Run command
OFF
(Commercial power)
ON
OFF
ON
OFF
ON
(Inverter)
Output
(Status signal and magnetic contactor)
SW52-1
SW52-2
SW88
52-1
52-2
88
ON
OFF
OFF
OFF
ON
5-74
ON
OFF
Inverter
operation
J codes
d codes
OFF
U codes
ON
OFF
y codes
Timing Scheme
Switching from inverter operation to commercial-power operation ISW50/ISW60: ON o OFF
(1) The inverter output is shut OFF immediately (Power gate IGBT OFF)
(2) The inverter primary circuit SW52-1 and the inverter secondary side SW52-2 are turned OFF immediately.
(3) If a run command is present after an elapse of t1 (0.2 sec + time specified by H13), the commercial power circuit
SW88 is turned ON.
Switching from commercial-power operation to inverter operation ISW50/ISW60: OFF o ON
(1) The inverter primary circuit SW52-1 is turned ON immediately.
(2) The commercial power circuit SW88 is turned OFF immediately.
(3) After an elapse of t2 (0.2 sec + time required for the main circuit to get ready) from when SW52-1 is turned ON,
the inverter secondary circuit SW52-2 is turned ON.
(4) After an elapse of t3 (0.2 sec + time specified by H13) from when SW52-2 is turned ON, the inverter harmonizes
once the motor that has been freed from the commercial power to the commercial power frequency. Then the motor
returns to the operation driven by the inverter.
t1:
t2:
t3:
0.2 sec + Time specified by H13 (Restart mode after momentary power failure)
0.2 sec + Time required for the main circuit to get ready
0.2 sec + Time specified by H13 (Restart mode after momentary power failure)
Selection of Commercial Power Switching Sequence
J22 specifies whether or not to automatically switch to commercial-power operation when an inverter alarm occurs.
Data for J22
0
1
Sequence (upon occurrence of an alarm)
Keep inverter-operation (Stop due to alarm.)
Automatically switch to commercial-power operation
• The sequence operates normally also even when SW52-1 is not used and the main power of the inverter is
supplied at all times.
• Using SW52-1 requires connecting the input terminals [R0] and [T0] for an auxiliary control power. Without
the connection, turning SW52-1 OFF loses also the control power.
• The sequence operates normally even if an alarm occurs in the inverter except when the inverter itself is
broken. Therefore, for a critical facility, be sure to install an emergency switching circuit outside the inverter.
• Turning ON both the magnetic contactor MC (88) at the commercial-power side and the MC (52-2) at the
inverter output side at the same time supplies main power mistakenly from the output (secondary) side of the
inverter, which may damage the inverter. To prevent it, be sure to set up an interlocking logic outside the
inverter.
5-75
Examples of Sequence Circuits
1) Standard sequence
Chap. 5
FUNCTION CODES
2) Sequence with an emergency switching function
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-76
3) Sequence with an emergency switching function --Part 2 (Automatic switching by the alarm output issued by the
inverter)
„ Cancel PG alarm-- PG-CCL (Function code data = 77)
When this terminal command is ON, the PG wire break alarm is ignored. Use this terminal command when switching
PG wires for switching motors, for example, to prevent it from being detected as PG wire break.
„ Run forward -- FWD (Function code data = 98)
Turning this terminal command ON runs the motor in the forward direction; turning it OFF decelerates it to stop.
This terminal command can be assigned only by E98 or E99.
„ Run reverse -- REV (Function code data = 99)
Turning this terminal command ON runs the motor in the reverse direction; turning it OFF decelerates it to stop.
This terminal command can be assigned only by E98 or E99
E10 to E15 Acceleration Time 2 to 4, Deceleration Time 2 to 4
(Refer to F07.)
E16, E17
(Refer to F40.)
Torque Limiter 2-1, 2-2
E20 to E23 Terminal [Y1] to [Y4] Function
E24, E27
Terminal [Y5A/C] and [30A/B/C] Function (Relay output)
E20 through E24 and E27 assign output signals (listed on the next page) to general-purpose, programmable output
terminals [Y1], [Y2], [Y3], [Y4], [Y5A/C] and [30A/B/C]. These function codes can also switch the logic system
between normal and negative to define the property of those output terminals so that the inverter logic can interpret
either the ON or OFF status of each terminal as active. The factory default settings are "Active ON."
Terminals [Y1], [Y2], [Y3] and [Y4] are transistor outputs and terminals [Y5A/C] and [30A/B/C] are relay contact
outputs. In normal logic, if an alarm occurs, the relay will be energized so that [30A] and [30C] will be closed, and
[30B] and [30C] opened. In negative logic, the relay will be deenergized so that [30A] and [30C] will be opened, and
[30B] and [30C] closed. This may be useful for the implementation of failsafe power systems.
• When a negative logic is employed, all output signals are active (e.g. an alarm would be recognized) while
the inverter is powered OFF. To avoid causing system malfunctions by this, interlock these signals to keep
them ON using an external power supply. Furthermore, the validity of these output signals is not guaranteed
for approximately 1.5 seconds (for 22 kW or below) or 3 seconds (for 30 kW or above) after power- ON, so
introduce such a mechanism that masks them during the transient period.
5-77
• Terminals [Y5A/C] and [30A/B/C] use mechanical contacts that cannot stand frequent ON/OFF switching.
Where frequent ON/OFF switching is anticipated (for example, limiting a current by using signals subjected
to inverter output limit control such as switching to commercial power line or direct-on-line starting), use
transistor outputs [Y1], [Y2], [Y3] and [Y4] instead.
The service life of a relay is approximately 200,000 times if it is switched ON and OFF at one-second
intervals.
The table below lists functions that can be assigned to terminals [Y1], [Y2], [Y3], [Y4], [Y5A/C], and [30A/B/C]. The
descriptions are, in principle, arranged in the numerical order of assigned data. However, highly relevant signals are
collectively described where one of them first appears. Refer to the function codes or signals in the "Related function
codes/signals (data)" column, if any.
The JAGUAR VXG runs under V/f control, dynamic torque vector control, V/f control with speed sensor, dynamic
torque vector control with speed sensor, vector control without speed sensor, or vector control with speed sensor. Some
function codes apply exclusively to the specific drive control, which is indicated by letters Y (Applicable) and N (Not
applicable) in the "Drive control" column in the tables. (Refer to page 5-2.)
Explanations of each function are given in normal logic system "Active ON."
Active ON Active OFF
1000
1001
1002
1003
1004
1005
6
1006
7
1007
8
10
1008
1010
11

12

13

15
1015
22
25
26
27
28
1022
1025
1026
1027
1028
30
1030
31
33
35
36
37
38
39
41
42
43
44
1031
1033
1035
1036
1037
1038
1039
1041
1042
1043
1044
45
46
47
1045
1046
1047
Symbol
Inverter running
Frequency (speed) arrival signal
Frequency (speed) detected
Undervoltage detected (Inverter stopped)
Torque polarity detected
Inverter output limiting
Auto-restarting after momentary power
failure
Motor overload early warning
Keypad operation enabled
Inverter ready to run
Switch motor drive source between
commercial power and inverter output
(For MC on commercial line)
Switch motor drive source between
commercial power and inverter output
(For secondary side)
Switch motor drive source between
commercial power and inverter output
(For primary side)
Select AX terminal function (For MC on
primary side)
Inverter output limiting with delay
Cooling fan in operation
Auto-resetting
Universal DO
Heat sink overheat early warning
Lifetime alarm
RUN
FAR
FDT
LU
B/D
IOL
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
IPF
Y
Y
Y
Y
Y
F14
OL
Y
Y
Y
Y
Y
E34, F10,
F12
KP
RDY
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
SW88
Y
Y
N
N
N
SW52-2
Y
Y
N
N
N
SW52-1
Y
Y
N
N
N
AX
Y
Y
Y
Y
Y
IOL2
FAN
TRY
U-DO
OH
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
LIFE
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
N
N
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Frequency (speed) detected 2
FDT2
Reference loss detected
REF OFF
Inverter output on
RUN2
Overload prevention control
OLP
Current detected
ID
Current detected 2
ID2
Current detected 3
ID3
Low current detected
IDL
PID alarm
PID-ALM
Under PID control
PID-CTL
Motor stopped due to slow flowrate
PID-STP
under PID control
Low output torque detected
U-TL
Torque detected 1
TD1
Torque detected 2
TD2
5-78
Drive control
Related
function
PG
w/o
w/
Torque codes/signals
V/f V/f PG PG
control
(data)

E30
E31, E32



FUNCTION CODES
0
1
2
3
4
5
Functions assigned
Chap. 5
Function code data


E01 to E07
ISW50 (40)
ISW60 (41)
J22

IOL (5)
H06
H04, H05


(See Section
7.3.)
E32, E36
E65
RUN (0)
H70
E34, E35,
E37, E38,
E55, E56
J11 to J13
J01
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
J08, J09
y codes
E78 to E81
Function code data
Drive control
Functions assigned
Active ON Active OFF
Symbol
Related
function
PG w/o w/ Torque codes/signals
V/f
V/f PG PG control
(data)
48
49
50
51
52
53
1048
1049
1050
1051
1052
1053
Motor 1 selected
Motor 2 selected
Motor 3 selected
Motor 4 selected
Running forward
Running reverse
SWM1
SWM2
SWM3
SWM4
FRUN
RRUN
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
54
1054
In remote operation
RMT
Y
Y
Y
Y
Y
56
57
58
59
70
71
72
76
82
1056
1057
1058
1059
1070
1071
1072
1076
1082
Motor overheat detected by thermistor
Brake signal
Frequency (speed) detected 3
Terminal [C1] wire break
Speed valid
Speed agreement
Frequency (speed) arrival signal 3
PG error detected
Positioning completion signal
THM
BRKS
FDT3
C1OFF
DNZS
DSAG
FAR3
PG-ERR
PSET
Y
Y
Y
Y
N
N
Y
N
N
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Y
Y
N
N
N
N
84
1084
Maintenance timer
MNT
Y
Y
Y
Y
Y
98
99
101
102
105
111
112
113
114
115
1098
1099
1101
1102
1105
1111
1112
1113
1114
1115
Light alarm
Alarm output (for any alarm)
Enable circuit failure detected
Enable input OFF
Braking transistor broken
Customizable logic output signal 1
Customizable logic output signal 2
Customizable logic output signal 3
Customizable logic output signal 4
Customizable logic output signal 5
L-ALM
ALM
DECF
EN OFF
DBAL
CLO1
CLO2
CLO3
CLO4
CLO5
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
A42, b42, r42


(See Section
4.2.2.)
H26, H27
J68 to J72
E32, E54

F25, F38
d21, d22
E30
d21 to d23
J97 to J99
H44, H78,
H79
H81, H82



H98
U71 to U75,
U81 to U85
Any negative logic (Active OFF) command cannot be assigned to the functions marked with "" in the
"Active OFF" column.
„ Inverter running -- RUN (Function code data = 0)
Inverter output on -- RUN2 (Function code data = 35)
These output signals tell the external equipment that the inverter is running at a starting frequency or higher.
If assigned in negative logic (Active OFF), these signals can be used to tell the "Inverter being stopped" state.
Output signal
RUN
RUN2
Basic function
These signals come ON when the inverter is running.
Under V/f control:
These signals come ON if the inverter output frequency
exceeds the starting frequency, and go OFF if it drops
below the stop frequency. The RUN signal can also be
used as a "Speed valid" signal DNZS.
Remarks
Goes OFF even during DC braking or
dew condensation prevention.
Comes ON even during DC braking,
pre-exciting, zero speed control, or
dew condensation prevention.
Under vector control, both RUN and RUN2 come ON when zero speed control or servo-lock function is enabled.
„ Undervoltage detected (Inverter stopped) -- LU (Function code data = 3)
This output signal comes ON when the DC link bus voltage of the inverter drops below the specified undervoltage level,
and it goes OFF when the voltage exceeds the level.
This signal is ON also when the undervoltage protective function is activated so that the motor is in an abnormal stop
state (e.g., tripped).
When this signal is ON, a run command is disabled if given.
„ Torque polarity detected -- B/D (Function code data = 4)
The inverter issues the driving or braking polarity signal to this digital output judging from the internally calculated
torque or torque command. This signal goes OFF when the detected torque is a driving one, and it goes ON when it is a
braking one.
5-79
„ Inverter output limiting -- IOL (Function code data = 5)
Inverter output limiting with delay -- IOL2 (Function code data = 22)
The output signal IOL comes ON when the inverter is limiting the output frequency by activating any of the following
actions (minimum width of the output signal: 100 ms). The output signal IOL2 comes ON when any of the following
output limiting operation continues for 20 ms or more.
• Torque limiting (F40, F41, E16 and E17, Maximum internal value)
• Current limiting by software (F43 and F44)
• Instantaneous overcurrent limiting by hardware (H12 = 1)
• Automatic deceleration (Anti-regenerative control) (H69)
When the IOL signal is ON, it may mean that the output frequency may have deviated from the frequency
specified by the frequency command because of this limiting function.
„ Keypad operation enabled -- KP (Function code data = 8)
This output signal comes ON when the
/
keys are specified as the run command source.
FUNCTION CODES
„ Select AX terminal function -- AX (Function code data = 15)
In response to a run command FWD, this output signal controls the magnetic contactor on the commercial-power
supply side. It comes ON when the inverter receives a run command and it goes OFF after the motor decelerates to stop
with a stop command received.
This signal immediately goes OFF upon receipt of a coast-to-stop command or when an alarm occurs.
Chap. 5
„ Inverter ready to run -- RDY (Function code data = 10)
This output signal comes ON when the inverter becomes ready to run by completing hardware preparation (such as
initial charging of DC link bus capacitors and initialization of the control circuit) and no protective functions are
activated.
„ Universal DO -- U-DO (Function code data = 27)
Assigning this output signal to an inverter's output terminal and connecting the terminal to a digital input terminal of
peripheral equipment via the RS-485 communications link or the fieldbus, allows the inverter to send commands to the
peripheral equipment.
The universal DO can also be used as an output signal independent of the inverter operation.
For the procedure for access to Universal DO via the RS-485 communications link or fieldbus, refer to the
respective instruction manual.
„ Heat sink overheat early warning -- OH (Function code data = 28)㻌
This output signal is used to issue a heat sink overheat early warning that enables you to take a corrective action before
an overheat trip K actually happens.
This signal comes ON when the temperature of the heat sink exceeds the "overheat trip temperature minus 5°C," and it
goes OFF when it drops down to the "overheat trip temperature minus 8°C."
This signal comes ON also when the internal air circulation DC fan (45 kW or above for 200 V class series or 75 kW or
above for 400 V class series) has locked.
„ Lifetime alarm -- LIFE (Function code data = 30)
This output signal comes ON when it is judged that the service life of any one of capacitors (DC link bus capacitors and
electrolytic capacitors on the printed circuit boards) and cooling fan has expired.
This signal should be used as a guide for replacement of the capacitors and cooling fan. If this signal comes ON, use the
specified maintenance procedure to check the service life of these parts and determine whether the parts should be
replaced or not. (Refer to Chapter 7, Section 7.3 "List of Periodic Replacement Parts.")
This signal comes ON also when the internal air circulation DC fan (45 kW or above for 200 V class series or 75 kW or
above for 400 V class series) has locked.
5-80
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
„ Under PID control -- PID-CTL (Function code data = 43)
his output signal comes ON when PID control is enabled ("Cancel PID control" (Hz/PID) = OFF) and a run command
is ON. (Refer to the description of J01.)
When PID control is enabled, the inverter may stop due to the slow flowrate stopping function or other
reasons, with the PID-CTL signal being ON. As long as the PID-CTL signal is ON, PID control is effective,
so the inverter may abruptly resume its operation, depending on the feedback value in PID control.
When PID control is enabled, even if the inverter stops its output during operation because of sensor signals or other
reasons, operation will resume automatically. Design your machinery so that safety is ensured even in such cases.
Otherwise, an accident could occur.
„ Running forward -- FRUN (Function code data = 52)
Running reverse -- RRUN (Function code data = 53)
Output signal
FRUN
RRUN
Assigned data
52
53
Running forward
ON
OFF
Running reverse
OFF
ON
Inverter stopped
OFF
OFF
„ In remote operation -- RMT (Function code data = 54)㻌
This output signal comes ON when the inverter switches from local to remote mode.
For details of switching between remote and local modes, refer to Chapter 4, Section 4.2.2 "Remote and local
modes."
„ Terminal [C1] wire break -- C1OFF (Function code data = 59)
This output signal comes ON when the inverter detects that the input current to terminal [C1] drops below 2 mA
interpreting it as the terminal [C1] wire broken.
„ Speed valid -- DNZS (Function code data = 70)
This output signal comes ON when the reference speed or detected one exceeds the stop frequency specified by
function code F25. It goes OFF when the speed is below the stop frequency for 100 ms or longer. Under vector control
with speed sensor, F38 switches the decision criteria between the reference speed and detected one. Under vector
control without speed sensor, the reference speed is used as a decision criteria. ( Refer to the descriptions of F25 and
F38.)
„ Alarm output (for any alarm) -- ALM (Function code data = 99)
This output signal comes ON if any of the protective functions is activated and the inverter enters Alarm mode.
„ Braking transistor broken -- DBAL (Function code data = 105)
If the inverter detects a breakdown of the braking transistor, it issues the braking transistor alarm (GED ) and also the
output signal DBAL. Detection of braking transistor broken can be cancelled by H98.
(200 V class series/ 400 V class series, 22 kW or below) ( Refer to the description of H98.)
Breakdown of the braking transistor could lead to the secondary breakdown of the braking resistor and
inverter’s internal units. Use this output signal DBAL to detect abnormal operation of the built-in braking
transistor and to cut off power to the magnetic contactor in inverter primary circuits, for preventing spread of
the damage.
5-81
E30
Frequency Arrival (Hysteresis width)
Output
signal
Assigned
data
FAR
1
FAR3
72
Operating condition 1
Both signals come ON when the
difference between the output
frequency (estimated/detected speed)
and the reference frequency (reference
speed) comes within the frequency
arrival hysteresis width specified by
E30.
Operating condition 2
FAR always goes OFF when run commands are
OFF or the reference speed is "0."
When run commands are OFF, the reference
speed is regarded as "0," so FAR3 comes ON
when the output frequency (estimated/detected
speed) is within the range of "0 ± the frequency
arrival hysteresis width specified by E30."
- Data setting range: 0.0 to 10.0 (Hz)
The operation timings of each signal are shown below.
Chap. 5
E31, E32
Frequency Detection (Level and Hysteresis width)
E36, E54 (Frequency Detection 2 and 3 (Level))
FUNCTION CODES
When the output frequency exceeds the frequency detection level specified by E31, the FDT signal comes ON; when it
drops below the "Frequency detection level minus Hysteresis width specified by E32," it goes OFF.
Three levels of setting are available with Frequency Detections 2 and 3.
Name
Frequency Detection
Frequency Detection 2
Frequency Detection 3
Output signal
FDT
FDT2
FDT3
Assigned data
2
31
58
Operation level
Range: 0.0 to 500.0 Hz
E31
E36
E54
Hysteresis width
Range: 0.0 to 500.0 Hz
E32
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-82
E34, E35
Overload Early Warning/Current Detection (Level and Timer)
E37, F38 (Current Detection 2/Low Current Detection (Level and Timer))
E55, E56 (Current Detection 3 (Level and Timer))
These function codes define the detection level and time for the "Motor overload early warning" OL, "Current detected"
ID, "Current detected 2" ID2, "Current detected 3" ID3, and "Low current detected" IDL output signals.
Output
signal
Assigned
data
Operation level
Range: See below
Timer
Range: 0.01 to 600.00 s
Motor characteristics
Range: See below
Thermal time constant
Range: 0.5 to 75.0 min
OL
ID
ID2
ID3
IDL
7
37
38
39
41
E34
E34
E37
E55
E37
E35
E38
E56
E38
F10
F12
-
-
- Data setting range
Operation level: 0.00 (Disable), 1 to 200% of inverter rated current
Motor characteristics 1: Enable (For a general-purpose motor with shaft-driven cooling fan)
2: Enable (For an inverter-driven motor, non-ventilated motor, or motor with separately
powered cooling fan)
„ Motor overload early warning signal -- OL
The OL signal is used to detect a symptom of an overload condition (alarm code O) of the motor so that the user can
take an appropriate action before the alarm actually happens.
The OL signal turns ON when the inverter output current exceeds the level specified by E34. In typical cases, set E34
data to 80 to 90% against F11 data (Electronic thermal overload protection for motor 1, Overload detection level).
Specify also the thermal characteristics of the motor with F10 (Select motor characteristics) and F12 (Thermal time
constant).
„ Current detected, Current detected 2 and Current detected 3 -- ID, ID2 and ID3
When the inverter output current exceeds the level specified by E34, E37 or E55 for the period specified by E35, E38 or
E56, the ID, ID2 or ID3 signal turns ON, respectively. When the output current drops below 90% of the rated operation
level, the ID, ID2 or ID3 turns OFF. (The minimum ON-duration is 100 ms.)
„ Low current detected -- IDL
This signal turns ON when the output current drops below the level specified by E37 (Low current detection, Level) for
the period specified by E38 (Timer). When the output current exceeds the "Low current detection level plus 5% of the
inverter rated current," it goes OFF. (The minimum ON-duration is 100 ms.)
E36
Frequency Detection 2
(Refer to E31.)
E37, E38
Current Detection 2/Low Current Detection (Level and Timer)
(Refer to E34.)
5-83
E40, E41
PID Display Coefficient A, B
These function codes specify PID display coefficients A and B to convert a PID command (process command or dancer
position command) and its feedback into mnemonic physical quantities to display.
- Data setting range: -999 to 0.00 to 9990 for PID display coefficients A and B
„ Display coefficients for PID process command and its feedback (J01 = 1 or 2)
E40 specifies coefficient A that determines the display value at 100% of the PID process command or its feedback, and
E41 specifies coefficient B that determines the display value at 0%.
The display value is determined as follows:
Display value = (PID process command or its feedback (%))/100 u (Display coefficient A - B) + B
Chap. 5
Example
Maintaining the pressure around 16 kPa (sensor voltage 3.13 V) while the pressure sensor can detect 0 to 30 kPa over
the output voltage range of 1 to 5 V:
Select terminal [12] as a feedback terminal and set the gain to 200% so that 5 V corresponds to 100%.
The following E40 and E41 settings allow you to monitor or specify the values of the PID process command and its
feedback on the keypad as pressure.
FUNCTION CODES
PID display coefficient A (E40) = 30.0, that determines the display value at 100% of PID process command or its
feedback
PID display coefficient B (E41) = -7.5, that determines the display value at 0% of PID process command or its
feedback
To control the pressure at 16 kPa on the keypad, set the value to 16.0.
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-84
„ Display coefficients for PID dancer position command and its feedback (J01 = 3)
Under the PID dancer control, the PID command and its feedback operate within the range r100%, so specify the value
at +100% of the PID command or its feedback as coefficient A with E40, and the value at -100% as coefficient B with
E41.
If the sensor output is unipolar, the PID dancer control operates within the range from 0 to +100%, so virtually specify
the value at -100% as coefficient B.
That is, suppose "b" = "Display value at 0%," then:
Display coefficient B = 2b - A
For details about the PID control, refer to the description of J01 and later.
For the display method of the PID command and its feedback, refer to the description of E43.
„ Display coefficient for analog input monitor
By inputting analog signals from various sensors such as temperature sensors in air conditioners to the inverter, you can
monitor the state of peripheral devices via the communications link. By using an appropriate display coefficient, you
can also have various values converted into physical values such as temperature and pressure before they are displayed.
To set up the analog input monitor, use function codes E61 through E63. Use E43 to choose the item to be
displayed.
E42
LED Display Filter
E42 specifies a filter time constant to be applied for displaying the output frequency, output current and other running
status monitored on the LED monitor on the keypad. If the display varies unstably so as to be hard to read due to load
fluctuation or other causes, increase this filter time constant.
- Data setting range: 0.0 to 5.0 (s)
5-85
E43
LED Monitor (Item selection)
E48 (LED Monitor (Speed monitor item))
E43 specifies the running status item to be monitored and displayed on the LED monitor.
Specifying the speed monitor with E43 provides a choice of speed-monitoring formats selectable with E48 (LED
Monitor).
Monitor item
Speed monitor
Function
code data
for E43
0
„Hz †A †kW
Hz
Frequency actually being output
(E48 = 0)
„Hz †A †kW
Hz
Frequency actually being output
(E48 = 1)
„Hz †A †kW
Hz
Reference frequency being set
120 „Hz „A †kW r/min Output frequency (Hz) ×
P01
(E48 = 2)
Motor speed
Load shaft
speed
Line speed
„Hz „A †kW r/min Output frequency (Hz) u E50
(E48 = 4)
†Hz „A „kW m/min Output frequency (Hz) u E50
(E48 = 5)
Display speed (%)
†Hz †A †kW
%
X
†Hz „A †kW
†Hz †A †kW
A
V
†Hz †A †kW
%
Input power
†Hz †A „kW
kW
PID command
†Hz †A †kW
㸫
PID feedback amount
†Hz †A †kW
㸫
PID output
†Hz †A †kW
%
Load factor
†Hz †A †kW
%
Motor output
†Hz †A „kW
kW
Output current
Output voltage
Calculated torque
Analog input
Torque current
Magnetic flux
command
Input watt-hour
†Hz †A †kW
㸫
†Hz †A †kW
%
†Hz †A †kW
%
†Hz †A †kW
kWh
Output frequency
u 100 Maximum frequency
Current output from the inverter in RMS
Voltage output from the inverter in RMS
Motor output torque in %
(Calculated value)
Input power to the inverter
PID command/feedback amount
transformed to that of virtual physical
value of the object to be controlled (e.g.
temperature)
Refer to function codes E40 and E41 for
details.
PID output in % as the maximum
frequency (F03) being at 100%
Load factor of the motor in % as the rated
output being at 100%
Motor output in kW
An analog input to the inverter in a format
suitable for a desired scale.
Refer to function codes E40 and E41 for
details.
Torque current command value or
calculated torque current
Magnetic flux command value
(Available only under vector control)
Input watt-hour (kWh)
100
(E48 = 3)
(E48 = 7)
FUNCTION CODES
Chap. 5
Output frequency 1
(before slip
compensation)
Output frequency 2
(after slip
compensation)
Reference frequency
Display
sample on LED indicator
Unit
Meaning of displayed value
the LED
„: on, †: off
monitor
Function code E48 specifies what to be displayed on the LED monitor and LED
indicators.
3
4
8
9
10
12
14
15
16
F codes
E codes
17
C codes
P codes
23
H codes
24
25
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-86
E44
LED Monitor (Display when stopped)
E44 specifies whether the specified value (data = 0) or the output value (data = 1) to be displayed on the LED monitor
of the keypad when the inverter is stopped. The monitored item depends on the E48 (LED monitor, Speed monitor
item) setting as shown below.
Data for
E48
What to be displayed when the inverter stopped
Monitored item
2
3
4
Output frequency 1
(before slip compensation)
Output frequency 2
(after slip compensation)
Reference frequency
Motor speed
Load shaft speed
Reference frequency
Reference motor speed
Reference load shaft speed
E44 = 1 (Output value)
Output frequency 1
(before slip compensation)
Output frequency 2
(after slip compensation)
Reference frequency
Motor speed
Load shaft speed
5
Line speed
Reference line speed
Line speed
7
Display speed (%)
Reference display speed
Display Speed
0
1
E44 = 0 (Specified value)
Reference frequency
Reference frequency
E45
LCD Monitor (Item selection)
E45 specifies the LCD monitor display mode to be applied when the inverter using the multi-function keypad is in
Running mode.
Data for E45
0
1
Function
Running status, rotational direction and operation guide
Bar charts for output frequency, current and calculated torque
Example of display for E45 = 0 (during running)
Example of display for E45 = 1 (during running)
Full-scale values on bar charts
Item displayed
Output frequency
Output current
Calculated torque
Full scale
Maximum frequency (F03)
Inverter rated current u 200%
Motor rated torque u 200%
5-87
E46
LCD Monitor (Language selection)
E46 specifies the language to display on the multi-function keypad as follows:
Data for E46
Language (OP-KP-LCD)
0
1
2
3
4
5
Japanese
English
German
French
Spanish
Italian
E47
LCD Monitor (Contrast control)
Chap. 5
E47 adjusts the contrast of the LCD monitor on the multi-function keypad as follows:
Data for E47
Contrast
0,
1,
2,
3, 4,
5,
6,
7, 8,
Low
9,
10
High
E48
LED Monitor (Speed monitor item)
E50
Coefficient for Speed Indication
(Refer to E43.)
E50 specifies the coefficient that is used when the load shaft speed or line speed is displayed on the LED monitor.
(Refer to the description of E43.)
FUNCTION CODES
Load shaft speed [r/min] = (E50: Coefficient for speed indication) u (Output frequency Hz)
Line speed [m/min]
= (E50: Coefficient for speed indication) u (Output frequency Hz)
- Data setting range: 0.01 to 200.00
E51
Display Coefficient for Input Watt-hour Data
E51 specifies a display coefficient (multiplication factor) for displaying the input watt-hour data (B) in a part of
maintenance information on the keypad.
Input watt-hour data = Display coefficient (E51 data) u Input watt-hour (kWh)
- Data setting range: 0.000 (cancel/reset); 0.001 to 9999
Setting E51 data to 0.000 clears the input watt-hour and its data to "0." After clearing, be sure to restore E51
data to the previous value; otherwise, input watt-hour data will not be accumulated.
E52
F codes
Keypad (Menu display mode)
E52 provides a choice of three menu display modes for the standard keypad as listed below.
Data for E52
0
1
2
Menu display mode
Function code data editing mode
Function code data check mode
Full-menu mode
Menus to be displayed
Menus #0, #1 and #7
Menus #2 and #7
Menus #0 through #7
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-88
The menus available on the standard keypad are described below.
Menu #
0
Menu
LED monitor
shows:
"Quick Setup"
0.Fnc
1,F__
1.E__
1
"Data Setting"
1.C__
1.P__
1.H__
1.A__
1.b__
1.r__
1.j__
1.d__
1.U__
1.Y__
1.o
2
"Data Checking"
2.rEP
3
"Drive Monitoring"
3.oPE
4
"I/O Checking"
4.1_O
5
"Maintenance Information"
5.CHE
6
"Alarm Information"
7
"Data Copying"
6.AL
7.CPY
Main functions
Displays only basic function codes to customize the inverter
operation.
F codes (Fundamental functions)
E codes (Extension terminal functions)
C codes (Control functions)
P codes (Motor 1 parameters)
H codes (High performance functions)
Selecting each of
A codes (Motor 2 parameters)
these function
codes enables its
b codes (Motor 3 parameters)
data to be
r codes (Motor 4 parameters)
displayed/changed.
J codes (Application functions 1)
d codes (Application functions 2)
U codes (Application functions 3)
y codes (Link functions)
o codes (Optional function)
Displays only function codes that have been changed from
their factory defaults. You can refer to or change those
function code data.
Displays the running information required for maintenance or
test running.
Displays external interface information.
Displays maintenance information including cumulative run
time.
Displays the recent four alarm codes. You can refer to the
running information at the time when the alarm occurred.
Allows you to read or write function code data, as well as
verifying it.
For details of each menu item, refer to Chapter 3 "KEYPAD FUNCTIONS."
E54
Frequency Detection 3 (Level)
(Refer to E31.)
E55, E56
Current Detection 3 (Level, Timer)
(Refer to E34.)
5-89
E61 to E63 Terminal [12] Extended Function
Terminal [C1] Extended Function
Terminal [V2] Extended Function
E61, E62, and E63 define the function of the terminals [12], [C1], and [V2], respectively.
There is no need to set up these terminals if they are to be used for frequency command sources.
Data for E61,
E62, or E63
0
Input assigned to
[12], [C1] and [V2]:
None
2
Auxiliary frequency
command 2
3
PID command 1
5
PID feedback amount
6
Ratio setting
7
Analog torque limit value A
8
Analog torque limit value B
10
Torque command
11
Torque current command
20
Analog signal input monitor
FUNCTION CODES
Auxiliary frequency
command 1

Auxiliary frequency input to be added to the reference frequency
given by frequency command 1 (F01). This is not added to any other
reference frequencies given by frequency command 2 and
multi-frequency commands, etc.
Auxiliary frequency input to be added to all reference frequencies
given by frequency command 1, frequency command 2,
multi-frequency commands, etc.
Command sources such as temperature and pressure under PID
control. It is also necessary to configure function code J02.
Feedback amounts such as temperature and pressure under PID
control.
This is used to multiply the final frequency command value by this
value, for use in the constant line speed control by calculating the
winder diameter or in ratio operation with multiple inverters.
This is used when analog inputs are used as torque limiters.
( Refer to F40 (Torque Limiter 1-1).)
This is used when analog inputs are used as torque limiters.
( Refer to F40 (Torque Limiter 1-1).)
Analog inputs to be used as torque commands under torque control.
( Refer to H18 (Torque Limiter).)
Analog inputs to be used as torque current commands under torque
control.
( Refer to H18 (Torque Limiter).)
By inputting analog signals from various sensors such as the
temperature sensors in air conditioners to the inverter, you can
monitor the state of external devices via the communications link.
By using an appropriate display coefficient, you can also have
various values to be converted into physical values such as
temperature and pressure before they are displayed.
Chap. 5
1
Description
If these terminals have been set up to have the same data, the operation priority is given in the following order:
E61 > E62 > E63
E64
Saving of Digital Reference Frequency
E64 specifies how to save the reference frequency specified in digital formats by the
shown below.
Data for E64
0
1
/
keys on the keypad as
E codes
Function
Auto saving when the main power is turned OFF
The reference frequency will be automatically saved when the main power is turned OFF. At the
next power-on, the reference frequency at the time of the previous power-off applies.
Saving by pressing
key
Pressing the
key saves the reference frequency. If the control power is turned OFF without
pressing the
key, the data will be lost. At the next power-ON, the inverter uses the reference
key was pressed last.
frequency saved when the
E65
F codes
Reference Loss Detection (Continuous running frequency)
When the analog frequency command (setting through terminal [12], [C1], or [V2]) has dropped below 10% of the
reference frequency within 400 ms, the inverter presumes that the analog frequency command wire has been broken and
continues its operation at the frequency determined by the ratio specified by E65 to the reference frequency. Refer
to E20 through E24 and E27 (data = 33).
When the frequency command level (in voltage or current) returns to a level higher than that specified by E65, the
inverter presumes that the broken wire has been fixed and continues to run following the frequency command.
5-90
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
In the diagram above, f1 is the level of the analog frequency command sampled at any given time. The sampling is
repeated at regular intervals to continually monitor the wiring connection of the analog frequency command.
- Data setting range: 0 (Decelerate to stop), 20 to 120%, 999 (Disable)
Avoid an abrupt voltage or current change for the analog frequency command. An abrupt change may be
interpreted as a wire break.
Setting E65 data at "999" (Disable) allows the REF OFF signal ("Reference loss detected") to be issued, but
does not allow the reference frequency to change (the inverter runs at the analog frequency command as
specified).
When E65 = "0" or "999," the reference frequency level at which the broken wire is recognized as fixed is "f1
u 0.2."
When E65 = "100" (%) or higher, the reference frequency level at which the wire is recognized as fixed is "f1 u
1."
The reference loss detection is not affected by the setting of analog input adjustment (filter time constants: C33,
C38, and C43)
E78, E79
E80, E81
Torque Detection 1 (Level and Timer)
Torque Detection 2/Low Torque Detection (Level and Timer)
E78 specifies the operation level and E79 specifies the timer, for the output signal TD1. E80 specifies the operation
level and E81 specifies the timer, for the output signal TD2 or U-TL.
Output signal
Assigned data
TD1
TD2
U-TL
46
47
45
Operation level
Range: 0 to 300%
E78
E80
E80
Timer
Range: 0.01 to 600.00 s
E79
E81
E81
„ Torque detected 1 -- TD1, Torque detected 2 -- TD2
The output signal TD1 or TD2 comes ON when the torque value calculated by the inverter or torque command exceeds
the level specified by E78 or E80 (Torque detection (Level)) for the period specified by E79 or E81 (Torque detection
(Timer)), respectively. The signal turns OFF when the calculated torque drops below "the level specified by E78 or E80
minus 5% of the motor rated torque." The minimum ON-duration is 100 ms.
„ Low output torque detected--U-TL
This output signal comes ON when the torque value calculated by the inverter or torque command drops below the level
specified by E80 (Low torque detection (Level)) for the period specified by E81 (Low torque detection (Timer)). The
signal turns OFF when the calculated torque exceeds the "level specified by E80 plus 5% of the motor rated torque."
The minimum ON-duration is 100 ms.
5-91
In the inverter’s low frequency operation, as a substantial error in torque calculation occurs, no low torque can be
detected within the operation range at less than 20% of the base frequency (F04). (In this case, the result of recognition
before entering this operation range is retained.)
The U-TL signal goes off when the inverter is stopped.
E98, E99
(Refer to E01 to E07.)
5.2.3 C codes (Control functions)
C01 to C03 Jump Frequency 1, 2 and 3
C04
Jump Frequency (Hysteresis width)
FUNCTION CODES
Terminal [FWD] Function
Terminal [REV] Function
Chap. 5
Since the motor parameters are used in the calculation of torque, it is recommended that auto-tuning be applied by
function code P04 to achieve higher accuracy.
These function codes enable the inverter to jump over three different points on the output frequency in order to skip
resonance caused by the motor speed and natural frequency of the driven machinery (load).
- While you are increasing the reference frequency, the moment the reference frequency reaches the bottom of the
jump frequency band, the inverter keeps the output at that bottom frequency. When the reference frequency exceeds
the upper limit of the jump frequency band, the internal reference frequency takes on the value of the reference
frequency. When you are decreasing the reference frequency, the situation will be reversed.
- When more than two jump frequency bands overlap, the inverter actually takes the lowest frequency within the
overlapped bands as the bottom frequency and the highest as the upper limit. Refer to the figure on the lower right.
F codes
E codes
„ Jump frequencies 1, 2 and 3 (C01, C02 and C03) Data setting range: 0.0 to 500.0 (Hz)
Specify the center of the jump frequency band. (Setting to 0.0 results in no jump frequency band.)㻌
„ Jump frequency hysteresis width (C04)
Data setting range: 0.0 to 30.0 (Hz)
Specify the jump frequency hysteresis width. (Setting to 0.0 results in no jump frequency band.)㻌
P codes
H codes
A codes
b codes
C05 to C19 Multi-frequency 1 to 15
C codes
r codes
„ These function codes specify 15 frequencies required for driving the motor at frequencies 1 to 15.
Turning terminal commands SS1, SS2, SS4 and SS8 ON/OFF selectively switches the reference frequency of the
inverter in 15 steps. To use these features, you need to assign SS1, SS2, SS4 and SS8 ("Select multi-frequency") to the
digital input terminals with C05 to C19 (data = 0, 1, 2, and 3).
J codes
d codes
U codes
y codes
5-92
„ Multi-frequency 1 to 15 (C05 through C19)
Data setting range: 0.00 to 500.00 (Hz)
The combination of SS1, SS2, SS4 and SS8 and the selected frequencies are as follows.
SS8
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
SS4
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
SS2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
SS1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Selected frequency command
Other than multi-frequency *
C05 (multi-frequency 1)
C06 (multi-frequency 2)
C07 (multi-frequency 3)
C08 (multi-frequency 4)
C09 (multi-frequency 5)
C10 (multi-frequency 6)
C11 (multi-frequency 7)
C12 (multi-frequency 8)
C13 (multi-frequency 9)
C14 (multi-frequency 10)
C15 (multi-frequency 11)
C16 (multi-frequency 12)
C17 (multi-frequency 13)
C18 (multi-frequency 14)
C19 (multi-frequency 15)
* "Other than multi-frequency" includes frequency command 1 (F01), frequency command 2 (C30) and other
command sources except multi-frequency commands.
„ When enabling PID control (J01 = 1, 2, or 3)
Under the PID control, a multi-frequency command can be specified as a preset value (3 different frequencies). It can
also be used for a manual speed command even with the PID control being canceled (Hz/PID = ON) or for a primary
reference frequency under the PID dancer control.
• PID command
SS8
OFF
OFF
ON
ON
SS4
OFF
ON
OFF
ON
SS1, SS2
–
–
–
–
Command
Command specified by J02
Multi-frequency by C08
Multi-frequency by C12
Multi-frequency by C16
C08, C12, and C16 can be specified in increments of 1 Hz. The following gives the conversion formula between the
PID command value and the data to be specified.
Data to be specified = PID command (%) u Maximum frequency (F03) y 100
PID command (%) =
Data to be specified (C08, C12, C16)
Maximum frequency (F03)
u 100
• Manual speed command
SS8, SS4
–
–
–
–
SS2
OFF
OFF
ON
ON
SS1
OFF
ON
OFF
ON
Selected frequency command
Other than multi-frequency
C05 (Multi-frequency 1)
C06 (Multi-frequency 2)
C07 (Multi-frequency 3)
C20
Jogging Frequency
H54, H55 (Acceleration/Deceleration Time, Jogging)
d09 to d13 (Speed Control (Jogging))
To jog or inch the motor for positioning a workpiece, specify the jogging conditions using the jogging-related function
codes (C20, H54, H55, and d09 through d13) beforehand, switch the inverter to the "ready for jogging" state, and then
enter a run command.
„ Switching to the "ready for jogging" state
Turning ON the "Ready for jogging" terminal command JOG (Function code data = 10) readies the inverter for jogging.
• The inverter’s status transition between "ready for jogging" and "normal operation" is possible only when
the inverter is stopped.
• When the run command source is the keypad (F02 = 0, 2 or 3), simultaneous keying "
+
keys" on the
keypad is functionally equivalent to this command. Pressing these keys toggles between the "normal
operation" and "ready for jogging."
5-93
„ Starting jogging operation
key or turning the FWD or REV terminal command ON starts jogging.
Pressing the
key decelerates
key, the inverter jogs only when the
key is held down. Releasing the
In jogging with the
to stop.
To start jogging operation by simultaneously entering the JOG terminal command and a run command (e.g.,
FWD), the input delay time between the two commands should be within 100 ms. If a run command FWD is
entered first, the inverter does not jog the motor but runs it ordinarily until the next input of the JOG.
The jogging conditions should be specified beforehand using the following function codes.
C20
H54
H55
d09
d10
d11
d13
Description
Reference frequency for jogging operation
Acceleration time for jogging operation
Deceleration time for jogging operation
0.000 to 5.000 s
0.000 to 0.100 s
0.1 to 200.0 times
0.001 to 9.999 s
Modification items related to speed control
for jogging operation under vector control
without/with speed sensor
For adjustments, refer to the descriptions of
d01 to d06.
0.000 to 0.100 s
C30
Frequency Command 2
(Refer to F01.)
FUNCTION CODES
d12
Data setting range
0.00 to 500.00 Hz
0.00 to 6000 s
0.00 to 6000 s
Chap. 5
Function code
Jogging Frequency
Acceleration Time (Jogging)
Deceleration Time (Jogging)
Speed Control (Jogging)
(Speed command filter)
Speed Control (Jogging)
(Speed detection filter)
Speed Control (Jogging)
P (Gain)
Speed Control (Jogging)
I (Integral time)
Speed Control (Jogging)
(Output filter)
C31 to C35 Analog Input Adjustment for [12] (Offset, Gain, Filter time constant, Gain base point, Polarity)
C36 to C39 Analog Input Adjustment for [C1] (Offset, Gain, Filter time constant, Gain base point)
C41 to C45 Analog Input Adjustment for [V2] (Offset, Gain, Filter time constant, Gain base point, Polarity)
(For details about the frequency command, refer to F01 (Frequency Command 1).)
Setting up a reference frequency using analog input
You can adjust the gain, polarity, filter time constant, and offset which are applied to analog inputs (voltage inputs to
terminals [12] and [V2], and current input to terminal [C1])
Adjustable items for analog inputs
Input
terminal
Input range
Gain
Gain
Base point
Polarity
Filter time
constant
Offset
[12]
0 to +10 V, -10 to +10 V
C32
C34
C35
C33
C31
[C1]
[V2]
4 to 20 mA
0 to +10 V, -10 to +10 V
C37
C42
C39
C44

C45
C38
C43
C36
C41
„ Offset (C31, C36, C41)
Data setting range: -5.0 to +5.0 (%)
C31, C36 or C41 configures an offset for an analog voltage/current input. The offset also applies to signals sent from
the external equipment.
F codes
E codes
C codes
P codes
„ Filter time constant (C33, C38, C43) Data setting range: 0.00 to 5.00 (s)
C33, C38 or C43 configures a filter time constant for an analog voltage/current input. The larger the time constant, the
slower the response. Specify the proper filter time constant taking into account the response speed of the machine (load).
If the input voltage fluctuates due to line noises, increase the time constant.
H codes
„ Polarity (C35, C45)
C35 and C45 configure the input range for analog input voltage.
b codes
Data for C35 and C45
0
1
Specifications for terminal inputs
-10 to +10 V
0 to +10 V (A minus component of the input will be regarded as 0 VDC.)
A codes
r codes
J codes
d codes
U codes
y codes
5-94
„ Gain
To input bipolar analog voltage (0 to s10 VDC) to terminals [12] and [V2], set C35 and C45 data to "0."
Setting C35 and C45 data to "1" enables the voltage range from 0 to +10 VDC and interprets the negative
polarity input from 0 to -10 VDC as 0 V.
C50
Bias (Frequency command 1) (Bias base point)
C51, C52
Bias (PID command 1) (Bias value and Bias base point)
(Refer to F01.)
These function codes (and the gain-related function codes) specify the gain and bias of the analog PID command 1,
enabling it to define arbitrary relationship between the analog input and PID commands.
The actual setting is the same as that of F18. For details, refer to F18 given in the description of F01.
Gain-related function codes C32, C34, C37, C39, C42, and C44 are shared by frequency commands.
„ Bias value (C51)
„ Bias base point (C52)
C53
Data setting range: -100.00 to 100.00 (%)
Data setting range: 0.00 to 100.00 (%)
Selection of Normal/Inverse Operation (Frequency command 1)
(Refer to E01 to E07.)
5.2.4 P codes (Motor 1 Parameters)
The JAGUAR VXG drives the motor under V/f control, dynamic torque vector control, V/f control with speed sensor,
dynamic torque vector control with speed sensor, vector control without speed sensor, or vector control with speed
sensor, which can be selected with function codes.
To use the integrated automatic control functions such as auto torque boost, torque calculation monitoring, auto-energy
saving operation, torque limiter, automatic deceleration (anti-regenerative control), auto search for idling motor speed,
slip compensation, torque vector control, droop control, and overload stop, it is necessary to build a motor model in the
inverter by specifying proper motor parameters including the motor capacity and rated current.
If the cabling between the inverter and the motor is long (generally, 20 m or longer) or a reactor is inserted between the
motor and the inverter, however, the apparent motor parameters are different from the actual ones, so auto-tuning or
other adjustments are necessary. For the auto-tuning procedure, refer to Chapter 4 "RUNNING THE MOTOR."
When using a motor made by other manufacturers or a non-standard motor, obtain the datasheet of the motor and
specify the motor parameters manually or perform auto-tuning.
To specify the motor parameters correctly, select the motor type with P99 (Motor 1 Selection), specify the motor rated
capacity with P02, and then initialize the motor parameters with H03. This procedure also applies when the inverter is
switched to the MT/VT mode and a motor with one rank higher capacity is used. When switching the motor between
the 1st to 4th motors, specify the corresponding function codes. (Refer to the description of A42.)
The motor parameters to be specified in P13 through P56 (such as iron loss factors and magnetic saturation factors) are
usually not shown on the motor nameplate or in the test report.
If auto-tuning (P04 = 2 or 3) is not performed , it is not necessary to change the motor parameters from the ones for a
standard motor.
P01
Motor 1 (No. of poles)
P01 specifies the number of poles of the motor. Enter the value given on the nameplate of the motor. This setting is
used to display the motor speed on the LED monitor and to control the speed (refer to E43). The following expression is
used for the conversion.
120
Motor speed (r/min) =
u Frequency (Hz)
No. of poles
- Data setting range: 2 to 22 (poles)
5-95
P02
Motor 1 (Rated capacity)
P02 specifies the rated capacity of the motor. Enter the rated value given on the nameplate of the motor.
Data for P02
Unit
Function
kW
When P99 (Motor 1 Selection) = 0, 2, 3 or 4
0.01 to 1000
HP
When P99 (Motor 1 Selection) = 1
When accessing function code P02 with the keypad, take into account that the P02 data automatically updates the data
of function codes P03, P06 through P23, P53 through P56, and H46.
P03
Motor 1 (Rated current)
P03 specifies the rated current of the motor. Enter the rated value given on the nameplate of the motor.
- Data setting range: 0.00 to 2000 (A)
Motor 1 (Auto-tuning)
FUNCTION CODES
The inverter automatically detects the motor parameters and saves them in its internal memory. Basically, it is not
necessary to perform tuning when using a standard motor with a standard connection with the inverter.
There are three types of auto-tuning as listed below. Select appropriate one considering the limitations in your
equipment and control mode.
Data for P04
Auto-tuning
Operation
Motor parameters to be tuned
0
Disable
N/A
N/A
Primary resistance (%R1) (P07)
Tune while the
The inverter performs tuning
Leakage reactance (%X) (P08)
1
Rated slip frequency (P12)
motor stops
while the motor is stopped.
%X correction factors 1 and 2 (P53 and P54)
No-load current (P06)
Primary resistance (%R1) (P07)
After tuning while the motor
Leakage reactance (%X) (P08)
Tune while the
is stopped, the inverter
Rated slip frequency (P12)
2
motor is rotating
performs tuning again, with
Magnetic saturation factors 1 to 5 (P16 to P20)
under V/f control
the motor running at 50% of
Magnetic saturation extension factors "a" to "c"
the base frequency.
(P21 through P23)
%X correction factors 1 and 2 (P53 and P54)
No-load current (P06)
Primary resistance (%R1) (P07)
After tuning while the motor
Tune while the
Leakage reactance (%X) (P08)
is stopped, the inverter
motor is rotating
Rated slip frequency (P12)
3
performs tuning, with the
Magnetic saturation factors 1 to 5 (P16 to P20)
under vector
motor running at 50% of the
Magnetic saturation extension factors "a" to "c"
control
base frequency twice.
(P21 to P23)
%X correction factors 1 and 2 (P53 and P54)
Chap. 5
P04
For details of auto-tuning, refer to Chapter 4, Section 4.1 "Running the Motor for a Test."
In any of the following cases, perform auto-tuning since the motor parameters are different from those of
standard motors so that the best performance cannot be obtained under some controls.
• The motor to be driven is a non-standard motor.
• Cabling between the motor and the inverter is long. (Generally, 20 m or longer)
• A reactor is inserted between the motor and the inverter.
„ Functions that are affected by motor parameters in running capability
Function
Related function codes (representative)
F37
F31, F35
F31, F35
F37
F40, F41
H69
H09
F42
F42
H28
E78 to E81
F42
J95
Auto torque boost
Output torque monitor
Load factor monitor
Auto energy saving operation
Torque limiter
Anti-regenerative control (Automatic deceleration)
Auto search
Slip compensation
Dynamic torque vector control
Droop control
Torque detection
Vector control without/with speed sensor
Brake Signal (Brake-OFF torque)
5-96
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
P06 to P08 Motor 1 (No-load current, %R1 and %X)
P06 through P08 specify no-load current, %R1 and %X, respectively. Obtain the appropriate values from the test report
of the motor or by calling the manufacturer of the motor.
Performing auto-tuning automatically sets these parameters.
„ No-load current (P06)
Enter the value obtained from the motor manufacturer.
„ %R1 (P07)
Enter the value calculated by the following expression.
R1 Cable R1
× 100 (%)
V / ( 3× I )
%R1
where,
R1: Primary resistance of the motor (:)
Cable R1: Resistance of the output cable (:)
V: Rated voltage of the motor (V)
I:
Rated current of the motor (A)
„ %X (P08)
Enter the value calculated by the following expression.
%X
X1 X2 × XM / (X2 XM) Cable X
× 100 (%)
V / ( 3× I )
where,
X1: Primary leakage reactance of the motor (:)
X2: Secondary leakage reactance of the motor (converted to primary) (:)
XM: Exciting reactance of the motor (:)
Cable X: Reactance of the output cable (:)
V: Rated voltage of the motor (V)
I:
Rated current of the motor (A)
For reactance, use the value at the base frequency (F04).
P09 to P11 Motor 1 (Slip compensation gain for driving, Slip compensation response time, and
Slip compensation gain for braking)
P09 and P11 determine the slip compensation amount in % for driving and braking individually and adjust the slip
amount from internal calculation. Specification of 100% fully compensates for the rated slip of the motor. Excessive
compensation (P09, P11 ! 100%) may cause hunting (undesirable oscillation of the system), so carefully check the
operation on the actual machine.
For motors exclusively designed for vector control, the rated slip of the motor for driving or braking is compensated by
P09 or P11, respectively, to improve output torque accuracy.
P10 determines the response time for slip compensation. Basically, there is no need to modify the default setting. If you
need to modify it, consult your IMO representatives.
Function codes
P09
Slip compensation gain for driving
P11
Slip compensation gain for braking
P10
Slip compensation response time
Operation (Slip compensation)
Adjust the slip compensation amount for driving.
Slip compensation amount for driving =
Rated slip x Slip compensation gain for driving
Adjust the slip compensation amount for braking.
Slip compensation amount for braking =
Rated slip x Slip compensation gain for braking
Specify the slip compensation response time. Basically, there is
no need to modify the default setting.
For details about the slip compensation control, refer to the description of F42.
5-97
P12
Motor 1 (Rated slip frequency)
P12 specifies rated slip frequency. Obtain the appropriate values from the test report of the motor or by calling the
manufacturer of the motor. Performing auto-tuning automatically sets these parameters.
• Rated slip frequency: Convert the value obtained from the motor manufacturer to Hz using the following expression
and enter the converted value. (Note: The motor rating given on the nameplate sometimes
shows a larger value.)
(Synchronous speed - Rated speed)
Rated slip frequency (Hz) =
u Base frequency
Synchronous speed
For details about the slip compensation control, refer to the description of F42.
P13 to P15 Motor 1 (Iron loss factors 1 to 3)
These function codes specify the characteristics of the exciting current to generate magnetic flux inside the motor and
the characteristics of the magnetic flux generated.
The combination of P99 (Motor 1 selection) and P02 (Motor 1 rated capacity) data determines the standard value.
Performing auto-tuning while the motor is rotating (P04 = 2 or 3) specifies these factors automatically.
P53, P54
FUNCTION CODES
P16 to P20 Motor 1 (Magnetic saturation factors 1 to 5)
P21 to P23 Motor 1 (Magnetic saturation extension factors "a" to "c")
Chap. 5
P13 to P15 compensates the iron loss caused inside the motor under vector control with speed sensor, in order to
improve the torque control accuracy.
The combination of P99 (Motor 1 selection) and P02 (Motor 1 rated capacity) data determines the standard value.
Basically, there is no need to modify the setting.
Motor 1 (%X correction factors 1 and 2)
P53 and P54 specify the factors to correct fluctuations of leakage reactance (%X).
Basically, there is no need to modify the setting.
P55
Motor 1 (Torque current under vector control)
P55 specifies the rated torque current under vector control without/with speed sensor.
The combination of P99 (Motor 1 selection) and P02 (Motor 1 rated capacity) data determines the standard value.
Basically, there is no need to modify the setting.
P56
Motor 1 (Induced voltage factor under vector control)
P56 specifies the induced voltage factor under vector control without/with speed sensor.
The combination of P99 (Motor 1 Selection) and P02 (Motor 1, Rated capacity) data determines the standard value.
Basically, there is no need to modify the setting.
P99
Motor 1 Selection
F codes
E codes
P99 specifies the motor type to be used.
Data for P99
0
1
2
3
4
C codes
Motor type
Motor characteristics 0 (Standard motors)
Motor characteristics 1 (Not used)
Motor characteristics 2 (Not used)
Motor characteristics 3 (Standard motors)
Other motors
To select the motor drive control or to run the inverter with the integrated automatic control functions such as auto
torque boost and torque calculation monitoring, it is necessary to specify the motor parameters correctly. First select the
motor type with P99 (Motor 1 Selection), next specify the motor rated capacity with P02, and then initialize the motor
parameters with H03. This process automatically configures the related motor parameters (P01, P03, P06 through P23,
P53 through P56, and H46).
The data of F09 (Torque Boost 1), H13 (Restart Mode after Momentary Power Failure (Restart time)), and F11
(Electronic Thermal Overload Protection for Motor 1, Overload detection level) depends on the motor capacity, but the
process stated above does not change them. Specify and adjust the data during a test run if needed.
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-98
5.2.5 H codes (High Performance Functions)
H03
Data Initialization
H03 initializes the current function code data to the factory defaults or initializes the motor parameters.
+
keys or
+
keys (simultaneous keying).
To change the H03 data, it is necessary to press the
Data for H03
0
1
2
3
4
5
Function
Disable initialization (Settings manually made by the user will be retained.)
Initialize all function code data to the factory defaults
Initialize motor 1 parameters in accordance with P02 (Rated capacity) and P99 (Motor 1 selection)
Initialize motor 2 parameters in accordance with A16 (Rated capacity) and A39 (Motor 2 selection)
Initialize motor 3 parameters in accordance with b16 (Rated capacity) and b39 (Motor 3 selection)
Initialize motor 4 parameters in accordance with r16 (Rated capacity) and r39 (Motor 4 selection)
• To initialize the motor parameters, set the related function codes as follows.
Step
Item
Action
(1)
Motor selection
Motor
(rated capacity)
Data
initialization
Selects the motor type
Sets the motor capacity
(kW)
Initialize motor
parameters
If "Data = 0, 1, 3, or 4"
in Step (1)
(2)
(3)
Function code data to
be initialized
1st motor
P99
If "Data = 2" in Step
(1), function codes
listed at the right are
also initialized
Function code
2nd motor
3rd motor
A39
b39
4th motor
r39
P02
A16
b16
r16
H03 = 2
H03 = 3
H03 = 4
H03 = 5
P01, P03,
P06 to P23,
P53 to P56,
H46
A15, A17,
A20 to A37,
A53 to A56
b15, b17,
b20 to b37,
b53 to b56
r15, r17,
r20 to r37,
r53 to r56
F04, F05
A02, A03
b02, b03
r02, r03
• Upon completion of the initialization, the H03 data reverts to "0" (factory default).
• If P02, A16, b16 or r16 data is set to a value other than the nominal applied motor rating, data initialization with H03
internally converts the specified value forcibly to the standard nominal applied motor rating. (Refer to Table C in
Section 5.1 "Function Code Tables."
• Motor parameters to be initialized are for motors listed below under V/f control. When the base frequency, rated
voltage, and the number of poles are different from those of the listed motors, or when non-standard motors are used,
change the rated current data to that printed on the motor nameplate.
Data = 0 or 4
Data = 2
Data = 3
Data = 1
Motor selection
Standard motors
Motors exclusively designed for vector
control
Standard motors
HP rating motors
4 poles
V/f control data
220 V/60 Hz, 415 V/50 Hz (400 V/50 Hz)*
4 poles
/50 Hz,
4 poles
220 V/60 Hz, 415 V/50 Hz (400 V/50 Hz)*
4 poles
230 V/60 Hz, 460 V/60 Hz
/50 Hz
* 400 V/50 Hz for the VXGxxx-4E
When accessing function code P02 with the keypad, take into account that P02 data automatically updates data
of function codes P03, P06 through P23, P53 through P56, and H46. Also, when accessing function code A16,
b16 or r16, data of related function codes for each are automatically updated.
H04, H05
Auto Reset (Times and Reset interval)
H04 and H05 specify the auto-reset function that makes the inverter automatically attempt to reset the tripped state and
restart without issuing an alarm output (for any alarm) even if any protective function subject to reset is activated and
the inverter enters the forced-to-stop state (tripped state).
If the protective function is activated in excess of the times specified by H04, the inverter will issue an alarm output (for
any alarm) and not attempt to auto-reset the tripped state.
Listed below are the protective functions subject to auto-reset.
Protective function
Overcurrent protection
Overvoltage protection
Heat sink overheat
Inverter internal overheat
LED monitor displays:
F, F or F
X, X or X
K
K
Protective function
Motor overheat
Braking resistor overheat
Motor overload
Inverter overload
5-99
LED monitor displays:
K
GEK
O to O
OX
„ Number of reset times (H04) Data setting range: 0 (Disable), 1 to 10 (times)
H04 specifies the number of reset times for the inverter to automatically attempt to escape the tripped state.
If the "auto-reset" function has been specified, the inverter may automatically restart and run the motor stopped due
to a trip fault, depending on the cause of the tripping.
Design the machinery so that human body and peripheral equipment safety is ensured even when the auto-resetting
succeeds.
Otherwise an accident could occur.
„ Reset interval (H05)
Data setting range: 0.5 to 20.0 (s)
H05 specifies the reset interval time between the time when the inverter enters the tripped state and the time when it
issues the reset command to attempt to auto-reset the state. Refer to the timing scheme diagrams below.
Chap. 5
<Operation timing scheme>
• In the figure below, normal operation restarts in the 4-th retry.
FUNCTION CODES
• In the figure below, the inverter failed to restart normal operation within the number of reset times specified by H04
(in this case, 3 times (H04 = 3)), and issued the alarm output (for any alarm) ALM.
F codes
„ Auto-resetting -- TRY (E20 to E24 and E27, data = 26)
This output signal comes ON when auto-resetting (resetting alarms automatically) is in progress.
E codes
C codes
P codes
H06
Cooling Fan ON/OFF Control
H codes
To prolong the service life of the cooling fan and reduce fan noise during running, the cooling fan stops when the
temperature inside the inverter drops below a certain level while the inverter stops. However, since frequent switching
of the cooling fan shortens its service life, the cooling fan keeps running for 10 minutes once started.
H06 specifies whether to keep running the cooling fan all the time or to control its ON/OFF.
Data for H06
0
1
Cooling fan ON/OFF
Disable (Always in operation)
Enable (ON/OFF controllable)
A codes
b codes
r codes
J codes
d codes
„ Cooling fan in operation -- FAN (E20 to E24 and E27, data = 25)
With the cooling fan ON/OFF control enabled (H06 = 1), this output signal is ON when the cooling fan is in operation,
and OFF when it is stopped. This signal can be used to make the cooling system of peripheral equipment interlocked for
an ON/OFF control
5-100
U codes
y codes
H07
Acceleration/Deceleration Pattern
H08
Rotational Direction Limitation
(Refer to F07.)
H08 inhibits the motor from running in an unexpected rotational direction due to miss-operation of run commands,
miss-polarization of frequency commands, or other mistakes.
Data for H08
0
1
2
Function
Disable
Enable (Reverse rotation inhibited)
Enable (Forward rotation inhibited)
Under vector control, some restrictions apply to the speed command. Under vector control without speed sensor, a
speed estimation error caused by a motor constant error or other errors may slightly rotate the motor in the direction
other than the specified one.
H09
d67
Starting Mode (Auto search)
Starting Mode (Auto search)
H49 (Starting Mode, Auto search delay time 1)
H46 (Starting Mode, Auto search delay time 2)
H09 specifies the starting mode--whether to enable the auto search for idling motor speed to run the idling motor
without stopping it.
The auto search can apply to the restart of the inverter after a momentary power failure and the normal startup of the
inverter individually.
If the terminal command STM ("Enable auto search for idling motor speed at starting") is assigned to a digital input
terminal with any of E01 to E07 (data = 26), the combination of the H09 data and the STM command status switches
the starting modes (whether auto search is enabled or disabled). If no STM is assigned, the inverter interprets STM as
being OFF by default.
„ H09/d67 (Starting mode, auto search) and terminal command STM
("Enable auto search for idling motor speed at starting")
The combination of H09/d67 data and the STM status determines whether to perform the auto search as listed below.
Function code
H09
d67
Drive control
V/f control (F42 = 0 to 2)
Vector control with speed sensor (F42 = 5)
Factory default
0: Disable
2: Enable
Data for H09/d67
0: Disable
1: Enable
2: Enable
̿
STM
OFF
OFF
OFF
ON
Auto search for idling motor speed at starting
For restart after momentary
For normal startup
power failure (F14 = 3 to 5)
Disable
Disable
Enable
Disable
Enable
Enable
Enable
Enable
When STM is ON, auto search for idling motor speed at starting is enabled regardless of the H09/d67 setting.
Refer to E01 to E07 (data = 26).
Auto search for idling motor speed
Starting the inverter (with a run command ON, BX OFF, auto-reset, etc.) with STM being ON searches for the idling
motor speed for a maximum of 1.2 seconds to run the idling motor without stopping it. After completion of the auto
search, the inverter accelerates the motor up to the reference frequency according to the frequency command and the
preset acceleration time.
Auto search for idling motor speed to follow
5-101
„ Starting Mode (Auto search delay time 1) (H49)
Data setting range: 0.0 to 10.0 (s)
Auto search for the idling motor speed will become unsuccessful if it is done while the motor retains residual voltage. It
is, therefore, necessary to leave the motor for an enough time for residual voltage to disappear. H49 specifies that time
(0.0 to 10.0 sec.).
At the startup triggered by a run command ON, auto search starts with the delay specified by H49. Using H49, therefore,
eliminates the need of the run command timing control when two inverters share a single motor to drive it alternately,
allow the motor to coast to a stop, and restart it under auto search control at each time of inverter switching
„ Starting Mode (Auto search delay time 2) (H46)
Data setting range: 0.1 to 10.0 (s)
At the restart after a momentary power failure, at the start by turning the terminal command BX ("Coast to a stop") OFF
and ON, or at the restart by auto-reset, the inverter applies the delay time specified by H46. The inverter will not start
unless the time specified by H46 has elapsed, even if the starting conditions are satisfied.
Chap. 5
Under auto search control, the inverter searches the motor speed with the voltage applied at the motor start and the
current flowing in the motor, based on the model built with the motor parameters. Therefore, the search is greatly
influenced by the residual voltage in the motor.
At factory shipment, H46 data is preset to a correct value according to the motor capacity for the general purpose motor,
and basically there is no need to modify the data.
Depending on the motor characteristics, however, it may take time for residual voltage to disappear (due to the
secondary thermal time constant of the motor). In such a case, the inverter starts the motor with the residual voltage
remaining, which will cause an error in the speed search and may result in occurrence of an inrush current or an
overvoltage alarm.
If it happens, increase the value of H46 data and remove the influence of residual voltage. (If possible, it is
recommended to set the value around two times as large as the factory default value allowing a margin.)
FUNCTION CODES
• Be sure to auto-tune the inverter preceding the start of auto search for the idling motor speed.
• When the estimated speed exceeds the maximum frequency or the upper limit frequency, the inverter
disables auto search and starts running the motor with the maximum frequency or the upper limit frequency,
whichever is lower.
• During auto search, if an overcurrent or overvoltage trip occurs, the inverter restarts the suspended auto
search.
• Perform auto search at 60 Hz or below.
• Note that auto search may not fully provide the expected/designed performance depending on conditions
including the load, motor parameters, power cable length, and other externally determined events.
H11
Deceleration Mode
F codes
H11 specifies the deceleration mode to be applied when a run command is turned OFF.
Data for H11
0
1
E codes
Function
Normal deceleration
Coast-to-stop (The inverter immediately shuts down its output, so the motor stops
according to the inertia of the motor and machinery (load) and their kinetic energy losses.)
When reducing the reference frequency, the inverter decelerates the motor according to the deceleration
commands even if H11 = 1 (Coast-to-stop).
C codes
P codes
H codes
A codes
b codes
H12
Instantaneous Overcurrent Limiting (Mode selection)
(Refer to F43.)
r codes
H13, H14
H15, H16
Restart Mode after Momentary Power Failure (Restart time, Frequency fall rate,
Continuous running level, and Allowable momentary power failure time)
J codes
(Refer to F14.)
d codes
U codes
y codes
5-102
H18
Torque Limiter (Mode selection)
d32, d33 (Torque Control, Speed limits 1 and 2)
When "Vector control without speed sensor" or "Vector control with speed sensor" is selected, the inverter can limit the
motor-generating torque according to a torque command sent from external sources.
„ Torque Limiter (Mode selection) (H18)
H18 specifies whether to enable or disable the torque limiter. When the torque limiter is enabled, a torque current
command or torque command can be selected.
Data for H18
Available control
0
Disable (Speed control)
2
Enable (Torque control with torque current command)
3
Enable (Torque control with torque command)
„ Torque Commands
Torque commands can be given as analog voltage input (via terminals [12] and [V2]) or analog current input (via
terminal [C1]), or via the communications link (communication dedicated function codes S02 and S03). 㸦To use
analog voltage/current inputs, it is necessary to set E61 (for terminal [12]), E62 (for terminal [C1]), or E63 (for terminal
[V2]) data to "10" or "11.")
Input
Terminal [12]
(-10 V to 10 V)
Terminal [V2]
(-10 V to 10 V)
Terminal [C1]
(4 to 20 mA)
S02
(-327.68 to 327.67%)
S03
(-327.68 to 327.67%)
Command form
Torque command
Torque current command
Torque command
Torque current command
Torque command
Torque current command
Function code setting
E61 = 10
E61 = 11
E63 = 10
E63 = 11
E62 = 10
E62 = 11
Specifications
Motor rated torque r200% / r10 V
Motor rated torque current r200% / r10V
Motor rated torque r200% / r10V
Motor rated torque current r200% / r10V
Motor rated torque 200% / 20 mA
Motor rated torque current 200% / 20 mA
Torque command

Motor rated torque / r100.00%
Torque current command

Motor rated torque current / r100.00%
„ Polarity of Torque Commands
The polarity of a torque command switches according to the combination of the polarity of an external torque command
and a run command on terminal [FWD] or [REV], as listed below.
Polarity of torque command
Positive
Negative
Run command (ON)
FWD
REV
FWD
REV
Torque polarity
Positive torque (Forward driving/Reverse braking)
Negative torque (Forward braking/Reverse driving)
Negative torque (Forward braking/Reverse driving)
Positive torque(Forward driving/Reverse braking)
„ Cancel torque control -- Hz/TRQ (E01 to E07, data = 23)
When the torque control is enabled (H18 = 2 or 3), assigning the terminal command Hz/TRQ ("Cancel torque control")
to any of the general-purpose digital input terminals (data = 23) enables switching between the speed control and the
torque control.
Cancel torque control signal Hz/TRQ
ON
OFF
Operation
Cancel torque control (Enable speed control)
Enable torque control
„ Torque Control (Speed limits 1 and 2) (d32, d33)
Torque control controls the motor-generating torque, not the speed. The speed is determined secondarily by load torque,
mechanical inertia, and other factors. To prevent a dangerous situation, however, the speed limit functions (d32 and
d33) are provided inside the inverter.
If a regenerative load (which is not generated usually) is generated under droop control, or if function codes
are incorrectly configured, the motor may rotate at an unintended high speed. You can specify the overspeed
level at any value to protect the mechanical system.
• Forward overspeed level = Maximum frequency 1 (F03) x Speed limit 1 (d32) x 120 (%)
• Reverse overspeed level = Maximum frequency 1 (F03) x Speed limit 2 (d33) x 120 (%)
5-103
Running/stopping the motor
Under torque control, the inverter does not control the speed, so it does not perform acceleration or
deceleration by soft-start and stop (acceleration/deceleration time) at the time of startup and stop.
Turning ON a run command starts the inverter to run and outputs the commanded torque. Turning it OFF
stops the inverter so that the motor coasts to a stop.
At the startup in torque control under the "Vector control without speed sensor," the starting operation differs
depending upon whether auto-search is enabled or disabled by d67 as shown below.
Data for d67
0: Disable
1: Enable (At restart after
momentary power failure)
2: Enable (At normal start and
at restart after momentary
power failure)
Operation
At startup, the inverter first starts at zero frequency. Then it accelerates
according to a torque command.
Select this operation for use in which the motor is surely stopped before
startup.
At startup, the inverter searches for idling motor speed and starts
running the motor at the frequency base on the searched speed. Then it
starts torque control.
Chap. 5
H26, H27
Thermistor (for motor) (Mode selection and Level)
„ Thermistor (for motor) (Mode selection) (H26)
H26 selects the function operation mode (protection or alarm) for the PTC/NTC thermistor as shown below.
Data for H26
0
1
2
3
Action
Disable
Enable
When the voltage sensed by PTC thermistor exceeds the detection level, motor protective function
(alarm 0h4 ) is triggered, causing the inverter to enter an alarm stop state.
Enable
When the voltage sensed by the PTC thermistor exceeds the detection level, a motor alarm signal is
output but the inverter continues running. You need to assign the "Motor overheat detected by
thermistor" signal (THM) to one of the digital output terminals beforehand, by which a temperature
alarm condition can be detected by the thermistor (PTC) (E20 to E24 and E27, data = 56).
Enable
If the motor overheats and the temperature exceeds the protection level, the inverter issues the
Motor protection alarm 0h4 and stops the motor.
FUNCTION CODES
These function codes specify the PTC (Positive Temperature Coefficient)/NTC (Negative Temperature Coefficient)
thermistor embedded in the motor. The thermistor is used to protect the motor from overheating or output an alarm
signal.
If H26 data is set to "1" or "2" (PTC thermistor), the inverter monitors the voltage sensed by PTC thermistor and protect
the motor even when any of the 2nd to 4th motors is selected. If H26 data is set to "3" (NTC thermistor) and any of the
2nd to 4th motors is selected, the inverter does not perform these functions.
„ Thermistor (for motor) (Level) (H27)
Data setting range: 0.00 to 5.00 (V)
H27 specifies the detection level (expressed in voltage) for the temperature sensed by the PTC thermistor.
The alarm temperature at which the overheat protection becomes activated depends on the characteristics of the PTC
thermistor. The internal resistance of the thermistor will significantly change at the alarm temperature. The detection
level (voltage) is specified based on the change of the internal resistance.
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
Suppose that the internal resistance of the PTC thermistor at the alarm temperature is Rp, the detection level (voltage)
Vv2 is calculated by the expression below. Set the result Vv2 to function code H27.
VV2
Rp
× 10.5 (V) 27000 Rp
J codes
d codes
U codes
y codes
5-104
Connect the PTC thermistor as shown below. The voltage obtained by dividing the input voltage on terminal [V2] with
a set of internal resistors is compared with the detection level voltage specified by H27.
[13]
Resistor
27k䃈
Motor
<Control circuit>
+10 VDC
(Operation level)
H27
[V2]
Compartor
External
alarm
PTC
thermistor
H26
[11]
0V
When using the terminal [V2] for PTC/NTC thermistor input, also turn SW5 on the control printed circuit
board to the PTC/NTC side. For details, refer to Chapter 2, "SPECIFICATIONS."
H28
Droop Control
In a system in which two or more motors drive single machinery, any speed gap between inverter-driven motors results
in some load unbalance between motors. The droop control allows each inverter to drive the motor with the speed droop
characteristics for increasing its load, eliminating such kind of load unbalance.
- Data setting range: -60.0 to 0.0 (Hz), (0.0: Disable)
„ Select droop control -- DROOP (E01 to E07, data = 76)
This terminal command DROOP is to switch enabling or disabling the droop control.
DROOP
ON
Droop control
Enable
Disable
OFF
To use droop control, be sure to auto-tune the inverter for the motor beforehand.
The droop control under V/f control applies the acceleration/deceleration time to the frequency obtained as a
result of the droop control to prevent the inverter from tripping even at an abrupt change in load. As a result,
reflecting the frequency compensated by the droop control on the motor speed may be delayed due to the
influence of the acceleration/deceleration time specified, which may look as if the droop control is disabled.
By contrast, the vector control without/with speed sensor contains the current control system and the inverter
does not trip even at an abrupt change in load, so the acceleration/deceleration time does not affect the droop
control. It is, therefore, possible to eliminate load unbalance using the droop control even during
accelerating/decelerating.
H30
Communications Link Function (Mode selection)
y98 (Bus Link Function, Mode selection)
Using the RS-485 communications link (standard/option) or fieldbus (option) allows you to issue frequency commands
and run commands from a computer or PLC at a remote location, as well as monitor the inverter running information
and the function code data.
H30 and y98 specify the sources of those commands--"inverter itself" or "computers or PLCs via the RS-485
communications link or fieldbus." H30 is for the RS-485 communications link; y98 for the fieldbus.
5-105
Command sources selectable
Command sources
Description
Sources except RS-485 communications link and fieldbus
Frequency command source: Specified by F01/C30, or multi-frequency command
Run command source: Via the keypad or digital input terminals selected by F02
Inverter itself
RS-485 communications link
(port 1)
RS-485 communications link
(port 2)
Fieldbus (option)
Via the standard RJ-45 port used for connecting a keypad
Via the terminals DX+, DX- and SD on the control PCB
Via fieldbus (option) using FA protocol such as DeviceNet or PROFIBUS-DP
Command sources specified by H30 (Communications link function, Mode selection)
Run command
Inverter itself (F02)
Inverter itself (F02)
RS-485 communications link (port 1)
RS-485 communications link (port 1)
Inverter itself (F02)
RS-485 communications link (port 1)
RS-485 communications link (port 2)
RS-485 communications link (port 2)
RS-485 communications link (port 2)
Command sources specified by y98 (Bus link function, Mode selection)
Data for y98
0
1
2
3
Frequency command
Follow H30 data
Via fieldbus (option)
Follow H30 data
Via fieldbus (option)
Run command
Follow H30 data
Follow H30 data
Via fieldbus (option)
Via fieldbus (option)
FUNCTION CODES
Frequency command
Inverter itself (F01/C30)
RS-485 communications link (port 1)
Inverter itself (F01/C30)
RS-485 communications link (port 1)
RS-485 communications link (port 2)
RS-485 communications link (port 2)
Inverter itself (F01/C30)
RS-485 communications link (port 1)
RS-485 communications link (port 2)
Chap. 5
Data for H30
0
1
2
3
4
5
6
7
8
Combination of command sources
Run command source
Inverter itself
Inverter itself
Via RS-485 communications
link (port 1)
Via RS-485 communications
link (port 2)
Via fieldbus (option)
H30 = 0
y98 = 0
H30 = 2
y98 = 0
H30 = 6
y98 = 0
H30 = 0 (2 or 6)
y98 = 2
Frequency command
Via RS-485
Via RS-485
communications
communications
link (port 1)
link (port 2)
H30 = 1
H30=4
y98 = 0
y98=0
H30 = 3
H30=5
y98 = 0
y98=0
H30 = 7
H30=8
y98 = 0
y98=0
H30 = 1 (3 or 7)
H30 = 4 (5 or 8)
y98 = 2
y98 = 2
Via fieldbus
(option)
H30=0 (1 or 4)
y98=1
H30=2 (3 or 5)
y98=1
H30=6 (7 or 8)
y98=1
H30 = 0 (1 to 8)
y98 = 3
For details, refer to the RS-485 Communication User's Manual or the Field Bus Option Instruction Manual.
When the terminal command LE ("Enable communications link via RS-485 or fieldbus") is assigned to a digital input
terminal, turning LE ON makes the settings of H30 and y98 enabled. When LE is OFF, those settings are disabled so
that both frequency commands and run commands specified from the inverter itself take control. (Refer to the
descriptions of E01 through E07, data = 24.)
No LE assignment is functionally equivalent to the LE being ON.
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-106
H42, H43
H48
Capacitance of DC Link Bus Capacitor, Cumulative Run Time of Cooling Fan
Cumulative Run Time of Capacitors on Printed Circuit Boards
H47 (Initial Capacitance of DC Link Bus Capacitor)
H98 (Protection/Maintenance Function)
„ Life prediction function
The inverter has the life prediction function for some parts which measures the discharging time or counts the voltage
applied time, etc. The function allows you to monitor the current lifetime state on the LED monitor and judge whether
those parts are approaching the end of their service life.
The life prediction function can also issue early warning signals if the lifetime alarm command LIFE is assigned to any
of the digital output terminals by any of E20 through E24 and E27.
For details, refer to Chapter 7, "MAINTENANCE AND INSPECTION."
Function
code
Name
H42
Capacitance of DC link
bus capacitor
H43
Cumulative run time of
cooling fan
H47
Initial capacitance of DC
link bus capacitor
H48
Cumulative run time of
capacitors on printed
circuit boards
Description
Displays the capacitance of DC link bus capacitor (measured value)
• Start of initial capacitance measuring mode under ordinary operating
conditions (0000)
• Measurement failure (0001)
Displays the cumulative run time of cooling fan in units of ten hours.
• Data setting range: 0 to 9999
Displays the initial capacitance of DC link bus capacitor (measured
value)
• Start of initial capacitance measuring mode under ordinary operating
conditions (0000)
• Measurement failure (0001)
Displays the cumulative run time of capacitor on the printed circuit
board in units of ten hours.
• Data setting range: 0 to 9999
When replacing the cooling fan or capacitors on printed circuit boards, it is necessary to clear or modify the data of the
function codes listed above. For details, refer to the documentation for maintenance.
5-107
H44, H78
H79, H94
Startup Counter for Motor 1, Maintenance Interval (M1)
Preset Startup Count for Maintenance (M1), Cumulative Motor Run Time 1
„ Cumulative motor run time 1 (H94)
Operating the keypad can display the cumulative run time of motor 1. This feature is useful for management and
maintenance of the mechanical system. H94 allows you to set the cumulative run time of the motor to the desired value,
which enables setting an arbitrary initial data to determine a parts or inverter replacement timing. Specifying "0" clears
the cumulative run time of the motor.
Even when a motor is driven by commercial power, not by the inverter, it is possible to count the cumulative run time
of the motor by detecting the ON/OFF state of the auxiliary contact of the magnetic contactor for switching to the
commercial power line. To enable this function, assign CRUN-M1 (Commercial power driving status of motor 1,
function code data = 72) to one of the digital input terminals.
• H94 data is in hexadecimal notation. It appears, however, in decimal notation on the keypad.
• Cumulative motor run time 2 through 4 can also be counted by assigning CRUN-M2 through CRUN-M4
(Commercial power driving status of motor 2 through 4, function code data = 73 through 75).
< Biannual maintenance >
2) H79 (Preset startup count for maintenance (M1)) specifies the number of inverter startup times to determine the next
maintenance timing. When the count of the startup counter for motor 1 (H44) reaches the number specified by H79
(Preset startup count for maintenance (M1)), the inverter outputs the maintenance timer signal MNT to remind the
user of the need of system maintenance.
Set the H79 data in hexadecimal. The maximum setting count is 65,535 (FFFF in hexadecimal.)
- Data setting range: 0000 (Disable); 0001 to FFFF (Hexadecimal)
FUNCTION CODES
„ Maintenance timer MNT
1) H78 (Maintenance interval (M1)) specifies the maintenance interval in units of ten hours. When the cumulative
motor run time 1 (H94) reaches the time specified by H78 (Maintenance interval (M1)), the inverter outputs the
maintenance timer signal MNT to remind the user of the need of system maintenance.
The setting is in units of 10 hours. The maximum setting is 9999 × 10 hours.
- Data setting range: 0 (Disable); 1 to 9999 (in units of ten hours)
Chap. 5
„ Startup counter for motor 1 (H44)
H44 counts the number of inverter startups and displays it in hexadecimal format. Check the displayed number on the
maintenance screen of the keypad, and use it as a guide for maintenance timing for parts such as belts. To start the
counting over again, e.g. after a belt replacement, set the H44 data to "0000."
F codes
E codes
< Maintenance every 1,000 times of startups >
C codes
P codes
H codes
A codes
b codes
r codes
J codes
To enable this function, assign the maintenance timer signal MNT to one of the digital output terminals (function
code data = 84).
• After the current setting has expired, set a value for the next maintenance in H78 and press the
key so
that the output signal is reset and counting restarts.
key so
• After the current setting has expired, set a value for the next maintenance in H79 and press the
that the output signal is reset and counting restarts.
This function is exclusively applies to the 1st motor.
5-108
d codes
U codes
y codes
H45
Mock Alarm
H97 (Clear Alarm Data)
H45 causes the inverter to generate a mock alarm in order to check whether external sequences function correctly at the
time of machine setup.
Setting the H45 data to "1" displays mock alarm HUU on the LED monitor. It also issues alarm output (for any alarm)
ALM (if assigned to a digital output terminal by any of E20 to E24 and E27). (Accessing the H45 data requires
key +
key.") After that, the H45 data automatically reverts to "0," allowing you to
simultaneous keying of "
reset the alarm.
Just as data (alarm history and relevant information) of those alarms that could occur in running the inverter, the
inverter saves mock alarm data, enabling you to confirm the mock alarm status.
To clear the mock alarm data, use H97. (Accessing the H97 data requires simultaneous keying of "
key +
key.")
H97 data automatically returns to "0" after clearing the alarm data.
key" on the keypad for 5 seconds or
A mock alarm can be issued also by simultaneous keying of " key +
more.
H46
Starting Mode (Auto search delay time 2)
(Refer to H09.)
H47, H48
Initial Capacitance of DC Link Bus Capacitor
Cumulative Run Time of Capacitors on Printed Circuit Boards
(Refer to H42.)
H50, H51
H52, H53
Non-linear V/f Pattern 1 (Frequency and Voltage)
Non-linear V/f Pattern 2 (Frequency and Voltage)
(Refer to F04.)
H49
Starting Mode (Auto search delay time 1)
(Refer to H09.)
H54, H55
Acceleration Time, Deceleration Time (Jogging)
H56
Deceleration Time for Forced Stop
H57 to H60 1st/2nd S-curve Acceleration/Deceleration Range
(Refer to F07.)
H61
UP/DOWN Control (Initial frequency setting)
(Refer to F01.)
H63
Low Limiter (Mode selection)
(Refer to F15.)
H64
Low Limiter (Lower limiting frequency)
H64 specifies the lower limit of frequency to be applied when the current limiter, torque limiter, automatic deceleration
(anti-regenerative control), or overload prevention control is activated. Normally, it is not necessary to change this data.
- Data setting range: 0.0 to 60.0 (Hz)
H65, H66
Non-linear V/f Pattern 3 (Frequency and Voltage)
(Refer to F04.)
H67
Auto Energy Saving Operation (Mode selection)
(Refer to F37.)
H68
Slip Compensation 1 (Operating conditions)
(Refer to F42.)
H69
Automatic Deceleration (Mode selection)
H76 (Torque Limiter, Frequency increment limit for braking)
H69 enables or disables the anti-regenerative control.
In the inverter not equipped with a PWM converter or braking unit, if the regenerative energy returned exceeds the
inverter's braking capability, an overvoltage trip occurs.
To avoid such an overvoltage trip, enable the automatic deceleration (anti-regenerative control) with this function code,
and the inverter controls the output frequency to keep the braking torque around 0 N·m in both the deceleration and
constant speed running phases.
JAGUAR VXG series of inverters have two braking control modes; torque limit control and DC link bus voltage
control. Understand the feature of each control and select the suitable one.
Control mode
Control process
Operation mode
Features
Torque limit
control
(H69=2 or 4)
DC link bus
voltage control
(H69=3 or 5)
Controls the output frequency
to keep the braking torque at
around "0."
Enabled during acceleration,
running at the constant
speed, and deceleration.
Control the output frequency
to lower the DC link bus
voltage if the voltage exceeds
the limiting level.
Enabled during deceleration.
Disabled during running at
the constant speed.
Quick response.
Causes less overvoltage trip
with heavy impact load.
Shorter deceleration time
by making good use of the
inverter's regenerative
capability.
5-109
In addition, during deceleration triggered by turning the run command OFF, the anti-regenerative control increases the
output frequency so that the inverter may not stop the load depending on the load state (huge moment of inertia, for
example). To avoid that, H69 provides a choice of cancellation of the anti-regenerative control to apply when three
times the specified deceleration time is elapsed, thus decelerating the motor forcibly.
Data for H69
Function
Force-to-stop with actual deceleration time exceeding
three times the specified one
Enable
Enable
Disable
Disable
Control mode
0
2
3
4
5
Disable automatic deceleration
Torque limit control
DC link bus voltage control
Torque limit control
DC link bus voltage control
Chap. 5
FUNCTION CODES
„ Torque Limiter (Frequency increment limit for braking) (H76)
Data setting range: 0.0 to 500.0 (Hz)
Since increasing the output frequency too much in the torque limit control mode is dangerous, the inverter has a torque
limiter (Frequency increment limit for braking) that can be specified by H76. The torque limiter limits the inverter's
output frequency to less than "Reference frequency + H76 setting."
Note that the torque limiter activated restrains the anti-regenerative control, resulting in a trip with an overvoltage alarm
in some cases. Increasing the H76 data makes the anti-regenerative control capability high.
• Enabling the automatic deceleration (anti-regenerative control) may automatically increase the deceleration
time.
• When a braking unit is connected, disable the anti-regenerative control. The automatic deceleration control
may be activated at the same time when a braking unit starts operation, which may make the deceleration
time fluctuate.
• If the set deceleration time is too short, the DC link bus voltage of the inverter rises quickly, and
consequently, the automatic deceleration may not follow the voltage rise. In such a case, specify a longer
deceleration time.
H70
Overload Prevention Control
H70 specifies the decelerating rate of the output frequency to prevent a trip from occurring due to an overload. This
control decreases the output frequency of the inverter before the inverter trips due to a heat sink overheat or inverter
overload (with an alarm indication of K or OX, respectively). It is useful for equipment such as pumps where a
decrease in the output frequency leads to a decrease in the load and it is necessary to keep the motor running even when
the output frequency drops.
Data for H70
0.00
0.01 to 100.0
999
Function
Decelerate the motor by deceleration time 1 (F08) or 2 (E11)
Decelerate the motor by deceleration rate from 0.01 to 100.0 (Hz/s)
Disable overload prevention control
„ Overload prevention control -- OLP (E20 to E24 and E27, data = 36)
This output signal comes ON when the overload prevention control is activated and the output frequency changed.
(Minimum width of the output signal: 100 ms)
In equipment where a decrease in the output frequency does not lead to a decrease in the load, the overload
prevention control is of no use and should not be enabled.
F codes
E codes
C codes
P codes
H71
Deceleration Characteristics
H codes
Setting the H71 data to "1" enables forced brake control. If regenerative energy produced during the deceleration of the
motor and returned to the inverter exceeds the inverter’s braking capability, an overvoltage trip will occur. The forced
brake control increases the motor energy loss during deceleration, increasing the deceleration torque.
Data for H71
0
1
A codes
b codes
Function
r codes
Disable
Enable
J codes
This function is aimed at controlling the torque during deceleration; it has no effect if there is a braking load.
Enabling the automatic deceleration (anti-regenerative control, H69 = 2 or 4) in the torque limit control mode
disables the deceleration characteristics specified by H71.
d codes
U codes
y codes
5-110
H72
Main Power Down Detection (Mode selection)
H72 monitors the inverter alternate-current input power source, and disables the inverter operation if it is not
established.
Data for H72
Function
0
Disable
1
Enable
In cases where the power is supplied via a PWM converter or the inverter is connected via the DC link bus, there is no
alternate-current input. In such cases, set H72 data to "0," otherwise the inverter cannot operate.
If you use a single-phase power supply, contact your IMO representative.
H73 to H75 Torque Limiter (Operating conditions, Control target, and Target quadrants)
(Refer to F40.)
H76
Torque Limiter (Frequency increment limit for braking)
(Refer to H69.)
H77
Service Life of DC Link Bus Capacitor (Remaining time)
H77 displays the remaining time before the service life of DC link bus capacitor expires in units of ten hours.
At the time of a printed circuit board replacement, transfer the service life data of the DC link bus capacitor to the new
board.
- Data setting range: 0 to 8760 (in units of ten hours, 0 to 87,600 hours)
H78, H79
Maintenance Interval (M1), Preset Startup Count for Maintenance (M1)
H80
Output Current Fluctuation Damping Gain for Motor 1
(Refer to H44.)
The inverter output current driving the motor may fluctuate due to the motor characteristics and/or backlash in the
machinery (load). Modifying the H80 data adjusts the controls in order to suppress such fluctuation. However, as
incorrect setting of this gain may cause larger current fluctuation, do not modify the default setting unless it is
necessary.
- Data setting range: 0.00 to 0.40
5-111
H81, H82
Light Alarm Selection 1 and 2
If the inverter detects a minor abnormal state "light alarm", it can continue the current operation without tripping while
displaying the "light alarm" indication ODO on the LED monitor. In addition to the indication ODO, the inverter blinks
the KEYPAD CONTROL LED and outputs the "light alarm" signal L-ALM to a digital output terminal to alert the
peripheral equipment to the occurrence of a light alarm. (To use the L-ALM, it is necessary to assign the signal to any
of the digital output terminals by setting any of function codes E20 through E24 and E27 to "98.")
Select the desired items to be regarded as a light alarm from the following table.
Code
Name
Heat sink overheat
K
External alarm
K
Inverter internal overheat
GEK
Braking resistor overheat
Description
Heat sink temperature increased to the trip level.
An error that has occurred in peripheral equipment turned
the external alarm signal THR ON.
The temperature inside the inverter abnormally has
increased.
Estimated temperature of the coil in the braking resistor
exceeded the allowable level.
Motor temperature calculated with the inverter output
current reached the trip level.
Overload of motor 1 through 4
HU
Option communications error
Communications error between the inverter and an option.
HU
Option error
RS-485 communications error
(COM port 1)
RS-485 communications error
(COM port 2)
An option judged that an error occurred.
HU
HUS
RS-485 communications error between the COM ports 1
and 2.
The deviation of the automatic speed regulator (between the
reference speed and the detected one) is out of the specified
range (d21) for the period specified by d22.
Failure of the air circulation DC fan inside the inverter.
(200 V class: 45 kW or above. 400 V class: 75 kW or
above.)
FUNCTION CODES
O to O
Chap. 5
K
HUH
Speed mismatch or excessive speed
deviation
IDO
DC fan locked
O
Motor overload early warning
K
Heat sink overheat early warning
Early warning before a heat sink overheat trip
OLI
Lifetime alarm
It is judged that the service life of any one of the capacitors
(DC link bus capacitors and electrolytic capacitors on the
printed circuit boards) and cooling fan has expired.
Or, failure of the air circulation DC fan inside the inverter.
(200 V class: 45 kW or above. 400 V class: 75 kW or
above.)
UHI
Reference command loss detected
Analog frequency command was lost.
SLG
PID alarm
X7O
Low torque output
S7F
PTC thermistor activated
The PTC thermistor on the motor detected a temperature.
C codes
U7H
Inverter life (Cumulative run time)
The motor cumulative run time reached the specified level.
P codes
FQ7
Inverter life (Number of startups)
Number of startups reached the specified level.
Early warning before a motor overload
Warning related to PID control (absolute-value alarm or
deviation alarm)
Output torque drops below the low torque detection level
for the specified period.
F codes
E codes
H codes
Set data for selecting "light alarms" in hexadecimal. For details on how to select the codes, refer to the next page.
- Data setting range: 0000 to FFFF (Hexadecimal)
„ Selecting light alarm factors
To set and display the light alarm factors in hexadecimal format, each light alarm factor has been assigned to bits 0 to
15 as listed in Tables 5.1 and 5.2. Set the bit that corresponds to the desired light alarm factor to "1." Table 5.3 shows
the relationship between each of the light alarm factor assignments and the LED monitor display.
Table 5.4 gives the conversion table from 4-bit binary to hexadecimal.
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-112
Table 5.1
Bit
Code
15
14
13
HUS
12
HU
11
10
9
8
HU
HU
Bit
Code
15
14
13
FQ7
12
U7H
11
10
9
8
O
Light Alarm Selection 1 (H81), Bit Assignment of Selectable Factors
Content
RS-485 communications error
(COM port 2)
RS-485 communications error
(COM port 1)
Option error
Option communications error
Overload of motor 4
Table 5.2
Bit
Code
Content
7
6
O
O
Overload of motor 3
Overload of motor 2
5
O
Overload of motor 1
4
GEK
Braking resistor overheated
3
2
1
0
K
K
K
Inverter internal overheat
External alarm
Heat sink overheat
Light Alarm Selection 2 (H82), Bit Assignment of Selectable Factors
Content
Bit
Code
Content
7
6
5
OLI
K
O
Lifetime alarm
Heat sink overheat early warning
Motor overload early warning
4
IDO
DC fan locked
S7F
X7O
SLG
Inverter life (Number of startups)
Inverter life
(Cumulative motor run time)
PTC thermistor activated
Low torque output
PID alarm
3
2
1
UHI
Reference command loss detected
0
HUH
Speed mismatch or excessive speed
deviation
Example
Table 5.3 Display of Light Alarm Factor
(Example) Light alarm factors "RS-485 communications error (COM port 2)," "RS-485 communications error (COM port 1),"
"Option communications error," "Overload of motor 1" and "Heat sink overheat" are selected by H81.
LED No.
Bit
Code
Binary
Hexadecimal
15
0
LED4
LED3
14
13
12
11
10
9
8
7
HUS HU HU HU 2O 2O
0
1
1
0
1
0
0
0
3
LED2
6
5
4
3
O 2O GEK 0
1
0
0
4
2
LED1
2
1
0
K 2K 2K
0
0
1
1
(See Table 5.4.)
Hexadecimal on
the LED
monitor
„ Hexadecimal expression
A 4-bit binary number can be expressed in hexadecimal format (1 hexadecimal digit). The table below shows the
correspondence between the two notations. The hexadecimals are shown as they appear on the LED monitor.
Table 5.4
0
0
0
0
0
0
0
Binary
0
0
0
0
0
1
0
1
1
0
1
0
1
1
Binary and Hexadecimal Conversion
Hexadecimal
0
1
0
1
0
1
0
1
1
1
1
1
1
1
Binary
0
0
0
0
0
1
0
1
1
0
1
0
1
1
Hexadecimal
0
1
0
1
0
1
0
D
E
F
G
H
When the H26 data is set to "1" (PTC (The inverter immediately trips with K displayed)), if the PTC
thermistor is activated, the inverter stops without displaying ODO, blinking the KEYPAD CONTROL LED, or
outputting L-ALM signal, regardless of the assignment of bit 11 (PTC thermistor activated) by H82 (Light
Alarm Selection 2).
„ Light alarm--L-ALM (E20 to E24 and E27, data = 98)
This output signal comes ON when a light alarm occurs.
5-113
H84, H85
Pre-excitation (Initial level, Time)
A motor generates torque with magnetic flux and torque current. Lag elements of the rising edge of magnetic flux
causes a phenomenon in which enough torque is not generated at the moment of the motor start. To obtain enough
torque even at the moment of motor start, enable the pre-excitation with H84 and H85 so that magnetic flux is
established before a motor start.
„ Pre-excitation (Initial level) (H84)
Data setting range: 100 to 400 (%) (Ratio to the motor's no-load current)
H84 specifies the forcing function for the pre-excitation. It is used to shorten the pre-excitation time. Basically, there is
no need to modify the default setting.
„ Pre-excitation (Time) (H85)
Data setting range: 0.00 (Disable), 0.01 to 30.00 (s)
H85 specifies the pre-excitation time before starting operation. When a run command is inputted, the pre-excitation
starts. After the pre-excitation time specified by H85 has elapsed, the inverter judges magnetic flux to have been
established and starts acceleration. Specify H85 data so that enough time is secured for establishing magnetic flux. The
appropriate value for H85 data depends on the motor capacity. Use the default setting value of H13 data as a guide.
Chap. 5
FUNCTION CODES
„ Pre-excitation--EXITE (E01 to E07, data = 32)
When this input signal comes ON, pre-excitation starts. After the delay time for establishing magnetic flux has elapsed,
a run command is inputted. When the run command is inputted, the pre-excitation ends and acceleration starts. Use an
external sequence to control the time for establishing magnetic flux.
F codes
E codes
C codes
P codes
In V/f control (including auto torque boost and torque vector), pre-excitation is disabled. Use the DC braking
or the starting frequency instead.
H codes
A transient phenomenon, which may occur when the amount of mechanical loss is small, may rotate the motor
A codes
mechanical brake or other mechanism to stop the motor.
b codes
㻌
during pre-excitation. If a motor rotation during pre-excitation is not allowed in your system, install a
r codes
Even if the motor is stopped by pre-excitation, voltage is output to inverter's output terminals U, V, and W.
An electric shock may occur.
J codes
d codes
U codes
H86 to H90 Reserved for particular manufacturers
y codes
H86 to H90 are reserved for particular manufacturers. Do not modify the settings.
5-114
H91
PID Feedback Wire Break Detection
Using the terminal [C1] (current input) for PID feedback signal enables wire break detection and alarm (FRI) issuance.
H91 specifies whether the wire break detection is enabled, or the duration of detection. (The inverter judges an input
current to the terminal [C1] below 2 mA as a wire break.)
- Data setting range: 0.0 (Disable alarm detection)
0.1 to 60.0 s (Detect wire break and issue FRI alarm within the time)
H92, H93
Continuity of Running (P and I)
(Refer to F14.)
H94
Cumulative Motor Run Time 1
(Refer to H44.)
H95
DC Braking (Braking response mode)
H96
STOP Key Priority/Start Check Function
(Refer to F20 through F22.)
H96 specifies a functional combination of "STOP key priority" and "Start check function" as listed below.
Data for H96
STOP key priority
Start check function
0
1
2
3
Disable
Enable
Disable
Enable
Disable
Disable
Enable
Enable
„ STOP key priority
Even when run commands are entered from the digital input terminals or via the RS-485 communications link (link
operation), pressing the
key forces the inverter to decelerate and stop the motor. After that, HU appears on the
LED monitor.
„ Start check function
For safety, this function checks whether any run command has been turned ON or not in each of the following
situations. If one has been turned ON, the inverter does not start up but displays alarm code HU on the LED monitor.
• When the power to the inverter is turned ON.
• When the
key is pressed to release an alarm status or when the digital input terminal command RST ("Reset
alarm") is turned ON.
• When the run command source is switched by a digital input terminal command such as LE ("Enable
communications link via RS-485 or fieldbus") or LOC ("Select local (keypad) operation").
H97
Clear Alarm Data
H45 (Mock Alarm)
H97 clears alarm data (alarm history and relevant information) stored in the inverter.
key +
key" is required.
To clear alarm data, simultaneous keying of "
Data for H97
0
1
Function
Disable
Enable (Setting "1" clears alarm data and then returns to "0.")
H98
Protection/Maintenance Function (Mode selection)
H98 specifies whether to enable or disable automatic lowering of carrier frequency, input phase loss protection, output
phase loss protection, judgment threshold on the life of DC link bus capacitor, judgment on the life of DC link bus
capacitor, DC fan lock detection, braking transistor error detection, and IP20/IP40 switching, in combination (Bit 0 to
Bit 7).
Automatic lowering of carrier frequency (Bit 0) (Under V/f control only)
This function should be used for important machinery that requires keeping the inverter running.
Even if a heat sink overheat or overload occurs due to excessive load, abnormal surrounding temperature, or cooling
system failure, enabling this function lowers the carrier frequency to avoid tripping (K, K or OXY). Note that
enabling this function results in increased motor noise.
Input phase loss protection (OLQ) (Bit 1)
Upon detection of an excessive stress inflicted on the apparatus connected to the main circuit due to phase loss or
line-to-line voltage unbalance in the three-phase power supplied to the inverter, this feature stops the inverter and
displays an alarm OLQ.
5-115
In configurations where only a light load is driven or a DC reactor is connected, phase loss or line-to-line
voltage unbalance may not be detected because of the relatively small stress on the apparatus connected to the
main circuit.
Output phase loss protection (SO ) (Bit 2)
Upon detection of phase loss in the output while the inverter is running, this feature stops the inverter and displays an
alarm SO.
Where a magnetic contactor is installed in the inverter output circuit, if the magnetic contactor goes OFF
during operation, all the phases will be lost. In such a case, this protection feature does not work.
Judgment threshold on the life of DC link bus capacitor (Bit 3)
FUNCTION CODES
Judgment on the life of DC link bus capacitor (Bit 4)
Whether the DC link bus capacitor has reached its life is determined by measuring the length of time for discharging
after power OFF. The discharging time is determined by the capacitance of the DC link bus capacitor and the load
inside the inverter. Therefore, if the load inside the inverter fluctuates significantly, the discharging time cannot be
accurately measured, and as a result, it may be mistakenly determined that the life has been reached. To avoid such an
error, you can disable the judgment on the life of the DC link bus capacitor. (Even if it is disabled, the judgment based
on the "ON-time counting" while the voltage is applied to the DC link bus capacitor is continued.) For details, refer to
the description of H42.
Since load may vary significantly in the following cases, disable the judgment on the life during operation. Either
conduct the measurement with the judgment enabled under appropriate conditions during periodical maintenance or
conduct the measurement under the operating conditions matching the actual ones.
• Auxiliary input for control power is used.
• An option card or multi-function keypad is used.
• Another inverter or equipment such as a PWM converter is connected to terminals of the DC link bus.
Chap. 5
Bit 3 is used to select the threshold for judging the life of the DC link bus capacitor--the factory default level or
user-setup level.
If the multi-function keypad is mounted, the inverter does not perform automatic capacitance measurement of
the DC link bus capacitor using the factory default level since the inverter's conditions are different from the
ones applied at shipment. It is, therefore, necessary to select the user-setup level. Using the user-setup level
requires performing the setup procedure for the user ordinary operation beforehand.
( Refer to the description of H42.)
DC fan lock detection (Bit 5) (200 V class series: 45 kW or above, 400 V class series: 75 kW or above)
An inverter of 45 kW or above (200 V class series), or of 75 kW or above (400 V class series) is equipped with the
internal air circulation DC fan. When the inverter detects that the DC fan is locked by a failure or other cause, you can
select either continuing the inverter operation or entering into alarm state.
Entering alarm state: The inverter issues the alarm K and coasts to stop the motor.
Continuing operation: The inverter does not enter the alarm mode, and continues operation of the motor.
Note that, however, the inverter turns ON the OH and LIFE signals on the transistor output terminals whenever the DC
fan lock is detected regardless of your selection.
If the ON/OFF control of the cooling fan is enabled (H06 = 1), the cooling fan may stop depending on
operating condition of the inverter. In this case, the DC fan lock detection feature is considered normal (e.g.;
the cooling fan is normally stopped by the stop fan command.) so that the inverter may turn OFF the LIFE or
OH signal output, or enable to cancel the alarm K , even if the internal air circulation DC fan is locked due
to a failure etc. (When you start the inverter in this state, it automatically issues the run fan command, then the
inverter detects the DC fan lock state, and turn ON the LIFE or OH output or enters the alarm K state.)
F codes
E codes
C codes
Note that, operating the inverter under the condition that the DC fan is locked for long time may shorten the life of
electrolytic capacitors on the PCBs due to local high temperature inside the inverter. Be sure to check with the LIFE
signal etc., and replace the broken fan as soon as possible.
P codes
H codes
Braking transistor error detection (Bit 6) (GED : 22 kW or below)
A codes
Upon detection of a built-in braking transistor error, this feature stops the inverter and displays an alarm GED. Set data of
this bit to "0" when the inverter does not use a braking transistor and there is no need of entering an alarm state.
b codes
r codes
Switch IP20/IP40 enclosure (Bit 7) (for basic type of inverters only)
Mounting an IP40 option to inverters with a capacity of 22 kW or below enables them to conform to IP40. In such a
case, switch Bit 7 to "1" for the protection coordination.
For details, refer to the instruction manual of the IP40 option.
To set data of function code H98, assign the setting of each function to each bit and then convert the 8-bit binary to the
decimal number.
J codes
d codes
U codes
y codes
5-116
Refer to the assignment of each function to each bit and a conversion example below.
Bit
0
Function
Lower the carrier frequency
automatically
Bit data = 0
Bit data = 1
Disable
Enable
Factory default
1: Enable
1
Detect input phase loss
Continue to run
Enter alarm processing
2
Detect output phase loss
Select life judgment threshold
of DC link bus capacitor
Judge the life of DC link bus
capacitor
Continue to run
Enter alarm processing
1: Enter alarm
processing
0: Continue to run
Factory default
User-defined setting
0: Factory default
Disable
Enable
1: Enable
3
4
5
Detect DC fan lock
Enter alarm
processing
Continue to run
6
Detect braking transistor error
Continue to run
Enter alarm processing
7
Switch IP20/IP40 enclosure
IP20
IP40
0: Enter alarm
processing
1: Enter alarm
processing
0: IP20
An example of conversion from binary to decimal (for the number configured by the factory default setting shown
above)
Decimal = Bit 7 u 27 + Bit 6 u 26 + Bit 5 u 25 + Bit 4 u 24 + Bit 3 u 23 + Bit 2 u 22 + Bit 1 u 21 + Bit 0 u 20
= Bit 7 u 128 + Bit 6 u 64 + Bit 5 u 32 + Bit 4 u 16 + Bit 3 u 8 + Bit 2 u 4 + Bit 1 u 2 + Bit 0 u 1
= 0 u 128 + 1 u 64 + 0 u 32 + 1 u 16 + 0 u 8 + 0 u 4 + 1 u 2 + 1 u 1
= 64 + 16 + 2 + 1
= 83
5.2.6 A codes (Motor 2 Parameters), b codes (Motor 3 Parameters), r codes (Motor 4 Parameters)
The JAGUAR VXG can switch control parameters even when it is running so that a single inverter can drive four
motors by switching them or turn the energy saving operation ON or OFF for the setup change (e.g., gear switching)
that causes the moment of inertia of the machinery to change.
Function code
F/E/P and other codes
A codes
b codes
r codes
Motor to drive
Motor 1
Motor 2
Motor 3
Motor 4
Remarks
Including function codes commonly applied to motors 1 to 4.
This manual describes function codes applied to motor 1 only. For ones applied to motors 2 to 4 except A42,
b42, and r42 (Motor/Parameter Switching 2 to 4), refer to the corresponding function codes prepared for
motor 1 in Table 5.5 on the next page.
A42, b42
r42
Motor/Parameter Switching 2, 3, and 4 (Mode selection)
d25 (ASR Switching Time)
The combination of digital input terminal commands M2, M3 and M4 (Select motor 2, 3 and 4) switches between the
1st, 2nd, 3rd and 4th motors as listed below. (Function codes E01 through E07, data = 12, 36, or 37) When the motor is
switched, the function code group with which the inverter drives the motor is also switched to the corresponding one.
At the same time, the inverter outputs the corresponding signal from the "Motor 1 selected" signal SWM1 through the
"Motor 4 selected" signal SWM4 (Function codes E20 through E27 data = 48, 49, 50, or 51) in order to switch the
external switch to that selected motor.
Terminal command
M2
M3
M4
OFF
OFF
OFF
ON
㸫
㸫
OFF
ON
㸫
OFF
OFF
ON
Inverter-driven motor selected
(Function code group enabled)
1st motor (Default codes)
2nd motor (A codes)
3rd motor (b codes)
4th motor (r codes)
SWM1
ON
OFF
OFF
OFF
Output signals
SWM2
SWM3
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
SWM4
OFF
OFF
OFF
ON
A42, b42 or r42 selects whether the combination of terminal commands M2, M3 and M4 switches the actual motors (to
the 2nd, 3rd, and 4th motors) or the particular parameters (A codes, b codes, or r codes).
Data for
A42, b42 or r42
Function
0
Motor (Switch to the 2nd, 3rd or 4th motor)
1
Parameter (Switch to particular A codes, b codes or r codes)
Switching is possible:
Only when the inverter is stopped
(all run commands are OFF).
Even when the inverter is running.
From the point of view of signal timing, a combination of M2, M3 and M4 must be determined at least 2 ms
before the signal of a run command is established.
5-117
If A42, b42 or r42 is set to "0" (Motor (Switch to the 2nd, 3rd or 4th motor)), the combination of M2, M3 and M4
switches the motor to any of the 2nd to 4th motors and also switches the function code group enabled to the one
corresponding to the selected motor, as listed in Table 5.5. Note that, however, the functions listed in Table 5.6 are
unavailable when any of the 2nd to 4th motors are selected.
If A42, b42 or r42 is set to "1" (Parameter (Switch to particular A codes, b codes or r codes)), the combination of M2,
M3 and M4 switches the particular parameters marked with Y in the "Object of parameter switching" column in Table
5.5. For other parameters, ones in the 1st motor column remain effective.
Table 5.5
Function Codes to be Switched
Object of
Function code
1st
2nd
3rd
4th parameter
motor motor motor motor switching
Name
Maximum frequency
F03
A01
b01
r01
Base frequency
F04
A02
b02
r02
Rated voltage at base frequency
F05
A03
b03
r03
F06
A04
b04
r04
Torque boost
F09
A05
b05
r05
Electronic thermal overload protection for motor
(Select motor characteristics)
F10
A06
b06
r06
F11
A07
b07
r07
(Thermal time constant)
F12
A08
b08
r08
(Braking starting frequency)
F20
A09
b09
r09
(Braking level)
F21
A10
b10
r10
F22
A11
b11
r11
Starting frequency
(Braking time)
F23
A12
b12
r12
Load selection/ Auto torque boost/ Auto energy saving operation
F37
A13
b13
r13
Drive control selection
F42
A14
b14
r14
P01
A15
b15
r15
Motor
(No. of poles)
(Rated capacity)
P02
A16
b16
r16
(Rated current)
P03
A17
b17
r17
FUNCTION CODES
DC braking
(Overload detection level)
Chap. 5
Maximum output voltage
Y
(Auto-tuning)
P04
A18
b18
r18
(No-load current)
P06
A20
b20
r20
(%R1)
P07
A21
b21
r21
(%X)
P08
A22
b22
r22
(Slip compensation gain for driving)
P09
A23
b23
r23
Y
(Slip compensation response time)
P10
A24
b24
r24
Y
Y
(Slip compensation gain for braking)
P11
A25
b25
r25
(Rated slip frequency)
P12
A26
b26
r26
(Iron loss factor 1)
P13
A27
b27
r27
(Iron loss factor 2)
P14
A28
b28
r28
F codes
E codes
(Iron loss factor 3)
P15
A29
b29
r29
(Magnetic saturation factor 1)
P16
A30
b30
r30
(Magnetic saturation factor 2)
P17
A31
b31
r31
P codes
(Magnetic saturation factor 3)
P18
A32
b32
r32
H codes
(Magnetic saturation factor 4)
P19
A33
b33
r33
(Magnetic saturation factor 5)
P20
A34
b34
r34
C codes
A codes
(Magnetic saturation extension factor "a")
P21
A35
b35
r35
(Magnetic saturation extension factor "b")
P22
A36
b36
r36
(Magnetic saturation extension factor "c")
P23
A37
b37
r37
P99
A39
b39
r39
H68
A40
b40
r40
Y
H80
A41
b41
r41
Y
Motor selection
Slip compensation
(Operating conditions)
Output current fluctuation damping gain for motor
b codes
r codes
J codes
d codes
U codes
y codes
5-118
Table 5.5
Function Codes to be Switched (Continued)
Object of
Function code
1st
2nd
3rd
4th parameter
motor motor motor motor switching
Name
Speed control
(Speed command filter)
d01
A43
b43
r43
Y
(Speed detection filter)
d02
A44
b44
r44
Y
P (Gain)
d03
A45
b45
r45
Y
I (Integral time)
d04
A46
b46
r46
Y
(Output filter)
d06
A48
b48
r48
Y
(Notch filter resonance frequency)
d07
A49
b49
r49
(Notch filter attenuation level)
d08
A50
b50
r50
Reserved
d51
d52
d53
d54
Cumulative motor run time
H94
A51
b51
r51
H44
A52
b52
r52
P53
A53
b53
r53
Startup counter for motor
Motor
(%X correction factor 1)
(%X correction factor 2)
P54
A54
b54
r54
(Torque current under vector control)
P55
A55
b55
r55
(Induced voltage factor under vector control)
P56
A56
b56
r56
d57
A57
b57
r57
Reserved
Table 5.6
Name
Non-linear V/f pattern
Starting frequency 1 (Holding time)
Stop frequency (Holding time)
Overload early warning/Current
detection
Droop control
UP/DOWN control
(Initial frequency setting)
PID control
Dew condensation prevention
Brake signal
Current limiter
Rotational direction limitation
Pre-excitation
Maintenance Interval/ Preset Startup
Count for Maintenance
NTC thermistor
Function Codes Unavailable for the 2nd to 4th Motors
Function codes
H50 to H53, H65, H66
F24
F39
Operation in 2nd to 4th motors
Disabled
Disabled
Disabled
E34, E35
Disabled
H28
Disabled
H61
Fixed at the initial setting (0 Hz)
J01 to J06, J08 to J13, J15 to J19,
J56 to J62, E40, E41, H91
J21, F21, F22
J68 to J72, J95, J96
F43, F44
H08
H84, H85
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
H78, H79
Disabled
H26, H27
Disabled
„ ASR Switching Time (d25)
Data setting range: 0.000 to 1.000 (s)
Parameter switching is possible even during operation. For example, speed control P (Gain) and I (Integral time) listed
in Table 5.5 can be switched.
Switching these parameters during operation may cause an abrupt change of torque and result in a mechanical shock,
depending on the driving condition of the load.
To reduce such a mechanical shock, the inverter decreases the abrupt torque change using the ramp function of ASR
Switching Time (d25).
5-119
5.2.7 J codes (Application Functions 1)
J01
PID Control (Mode selection)
Under PID control, the inverter detects the state of a control target object with a sensor or the similar device and
compares it with the commanded value (e.g., temperature control command). If there is any deviation between them, the
PID control operates so as to minimize it. That is, it is a closed loop feedback system that matches controlled variable
(feedback amount). The PID control expands the application area of the inverter to the process control (e.g., flow
control, pressure control, and temperature control) and the speed control (e.g., dancer control).
If PID control is enabled (J01 = 1, 2 or 3), the frequency control of the inverter is switched from the drive frequency
command generator block to the PID command generator block.
„ Mode Selection (J01)
J01 selects the PID control mode.
Data for J01
Disable
Enable (Process control, normal operation)
Enable (Process control, inverse operation)
Enable (Dancer control)
Chap. 5
0
1
2
3
Function
FUNCTION CODES
PID process control block diagram
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
PID dancer control block diagram
Using J01 enables switching between normal and inverse operations against the PID control output, so you can specify
an increase/decrease of the motor rotating speed to the difference (error component) between the commanded (input)
and feedback amounts, making it possible to apply the inverter to air conditioners. The terminal command IVS can also
switch operation between normal and inverse.
For details about the switching of normal/inverse operation, refer to the description of Switch normal/inverse
operation IVS (E01 to E07, data = 21).
5-120
d codes
U codes
y codes
PID Control (Remote command SV)
J02
J02 sets the source that specifies the command value (SV) under PID control.
Data for J02
Function
Keypad
/
keys on the keypad.
Specify the PID command by using the
PID command 1 (Analog input: Terminals [12], [C1] and [V2])
Voltage input to the terminal [12] (0 to r10 VDC, 100% PID command/ r10 VDC)
Current input to the terminal [C1] (4 to 20 mA DC, 100% PID command/ 20 mA DC
Voltage input to the terminal [V2] (0 to r10 VDC, 100% PID command/ r10 VDC)
Terminal command UP/DOWN
Using the UP or DOWN command in conjunction with PID display coefficients (specified by E40
and E41) with which the command value is transformed to virtual physical value etc., you can
specify 0 to 100% of the PID command (r 100% for PID dancer control).
Command via communications link
Use function code S13 that specifies the communications-linked PID command. The transmission
data of 20000 (decimal) is equal to 100% (maximum frequency) of the PID command.
0
1
3
4
[ 1 ] PID command with the
/
keys on the keypad (J02 = 0, factory default)
Using the
/
keys on the keypad in conjunction with PID display coefficients (specified by E40 and E41), you
can specify 0 to 100% of the PID command (±100% for PID dancer control) in an easy-to-understand converted
command format. For details of operation, refer to JAGUAR VXG User's Manual, Chapter 7, Section 7.3.3 "Setting up
frequency and PID commands."
[ 2 ] PID command by analog inputs (J02 = 1)
When any analog input (voltage input to terminals [12] and [V2], or current input to terminal [C1]) for PID command 1
(J02 = 1) is used, it is possible to arbitrary specify the PID command by multiplying the gain and adding the bias. The
polarity can be selected and the filter time constant and offset can be adjusted. In addition to J02 setting, it is necessary
to select PID command 1 for analog input (specified by any of E61 to E63, function code data = 3). For details, refer to
the descriptions of E61 to E63.
Adjustable elements of PID command
Bias
Input
terminal
[12]
[C1]
[V2]
Input range
0 to +10 V, -10 to +10V
4 to 20 mA
0 to +10 V, -10 to +10 V
Gain
Bias
Base
point
Gain
Base
point
Polarity
Filter time
constant
Offset
C51
C52
C32
C37
C42
C34
C39
C44
C35
C45
C33
C38
C43
C31
C36
C41
„ Offset (C31, C36, C41)
C31, C36 or C41 configures an offset for an analog voltage/current input. The offset also applies to signals sent from
the external equipment.
„ Filter time constant (C33, C38, C43)
C33, C38, and C43 provide the filter time constants for the voltage and current of the analog input. Choose appropriate
values for the time constants considering the response speed of the mechanical system, as large time constants slow
down the response. If the input voltage fluctuates because of noise, specify large time constants.
„ Polarity (C35, C45)
C35 and C45 specify the input range for analog input voltage.
Data for C35 and C45
0
1
Terminal input specifications
-10 to +10 V
0 to +10 V (negative value of voltage is regarded as 0 V)
5-121
„ Gain and bias
(Example) Mapping the range of 1 through 5 V at terminal [12] to 0 through 100%
Chap. 5
[ 3 ] PID command with UP/DOWN control (J02 = 3)
When the UP/DOWN control is selected as a PID speed command, turning the terminal command UP or DOWN ON
causes the PID speed command to change within the range from 0 to 100%.
The PID speed command can be specified in mnemonic physical quantities (such as temperature or pressure) with the
PID display coefficients (E40, E41).
To select the UP/DOWN control as a PID speed command, the UP and DOWN should be assigned to the digital input
terminals [X1] to [X7]. ( E01 to E07, data = 17, 18)
UP
Data = 17
OFF
ON
OFF
ON
DOWN
Data = 18
OFF
OFF
ON
ON
FUNCTION CODES
Function
Retain PID speed command value.
Increase PID speed command value at a rate between 0.1%/0.1 s and 1%/0.1 s.
Decrease PID speed command value at a rate between 0.1%/0.1 s and 1%/0.1 s.
Retain PID speed command value.
The inverter internally holds the PID command value set by the UP/DOWN control and applies the held value
at the next restart (including powering ON).
[ 4 ] PID command via communications link (J02 = 4)
Use function code S13 that specifies the communications-linked PID command. The transmission data of 20000
(decimal) is equal to 100% (maximum frequency) of the PID command. For details of the communications format, refer
to the RS-485 Communication User's Manual.
• Other than the remote command selection by J02, the multi-frequency 4, 8 or 12 (specified by C08, C12 or
C16, respectively) specified by terminal commands SS4 and SS8 can also be selected as a preset value for
the PID command.
Calculate the setting data of the PID command using the expression below.
Preset multi-frequency
u 100
Maximum frequency
• In dancer control (J01 = 3), the setting from the keypad interlocks with data of J57 (PID control: Dancer
reference position), and is saved as function code data.
PID command data (%) =
Selecting Feedback Terminals
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
For feedback control, determine the connection terminal according to the type of the sensor output.
• If the sensor is a current output type, use the current input terminal [C1] of the inverter.
• If the sensor is a voltage output type, use the voltage input terminal [12] of the inverter, or switch over the terminal
[V2] to the voltage input terminal and use it.
For details, refer to the descriptions of E61 through E63.
5-122
J codes
d codes
U codes
y codes
Application example: Process control (for air conditioners, fans and pumps)
The operating range for PID process control is internally controlled as 0% through 100%. For the given feedback input,
determine the operating range to be controlled by means of gain adjustment.
Example: When the output level of the external sensor is within the range of 1 to 5 V:
• Use terminal [12] since the connection terminal is for voltage input.
• Set the gain (C32 for analog input adjustment) at 200% in order to make the maximum value (5 V) of the external
sensor's output correspond to 100%. Note that the input specification for terminal [12] is 0 to 10 V corresponding to 0
to 100%; thus, a gain factor of 200% (= 10 V y 5 V u 100) should be specified. Note also that any bias setting does
not apply to feedback control.
Application examples: Dancer control (for winders)
Example 1. When the output level of the external sensor is r7 VDC:
• Use terminal [12] since the voltage input is of bipolar.
• When the external sensor's output is of bipolar, the inverter controls the speed within the range of r100%. To convert
the output r7 VDC to r100%, set the gain (C32 for analog input adjustment) at 143% as calculated below.
10 V
| 143%
7V
Example 2. When the output level of the external sensor is 0 to 10 VDC:
• Use terminal [12] since the connection terminal is for voltage input.
• When the external sensor's output is of unipolar, the inverter controls the speed within the range of 0 to 100%.
In this example, it is recommended that the dancer reference position be set around the +5 V (50%) point.
PID Display Coefficient and Monitoring
To monitor the PID command and its feedback value, set the display coefficient to convert the values into
easy-to-understand mnemonic physical quantities, such as temperature.
Refer to function codes E40 and E41 for details on display coefficients, and to E43 for details on monitoring.
5-123
J03 to J06
PID Control (P (Gain), I (Integral time), D (Differential time), Feedback filter)
„ P gain (J03)
Data setting range: 0.000 to 30.000 (times)
J03 specifies the gain for the PID processor.
P (Proportional) action
An operation in which the MV (manipulated value: output frequency) is proportional to the deviation is called P action,
which outputs the MV in proportion to deviation. However, the MV alone cannot eliminate deviation.
Gain is data that determines the system response level against the deviation in P action. An increase in gain speeds up
response, but an excessive gain may oscillate the inverter output. A decrease in gain delays response, but it stabilizes
the inverter output.
Chap. 5
I (Integral) action
FUNCTION CODES
„ I integral time (J04)
Data setting range: 0.0 to 3600.0 (s), 0.0 means that the integral component is ineffective.
J04 specifies the integral time for the PID processor.
An operation in which the change rate of the MV (manipulated value: output frequency) is proportional to the integral
value of deviation is called I action, which outputs the MV that integrates the deviation. Therefore, I action is effective
in bringing the feedback amount close to the commanded value. For the system whose deviation rapidly changes,
however, this action cannot make it react quickly.
The effectiveness of I action is expressed by integral time as parameter, that is J04 data. The longer the integral time,
the slower the response. The reaction to the external disturbance also becomes slow. The shorter the integral time, the
faster the response. Setting too short integral time, however, makes the inverter output tend to oscillate against the
external disturbance.
F codes
„ D differential time (J05)
Data setting range: 0.00 to 600.00 (s), 0.00 means that the differential component is ineffective.
J05 specifies the differential time for the PID processor.
D (Differential) action
E codes
C codes
P codes
H codes
An operation in which the MV (manipulated value: output frequency) is proportional to the differential value of the
deviation is called D action, which outputs the MV that differentiates the deviation. D action makes the inverter quickly
react to a rapid change of deviation.
The effectiveness of D action is expressed by differential time as parameter, that is J05 data. Setting a long differential
time will quickly suppress oscillation caused by P action when a deviation occurs. Too long differential time makes the
inverter output oscillation more. Setting short differential time will weakens the suppression effect when the deviation
occurs.
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-124
The combined uses of P, I, and D actions are described below.
(1) PI control
PI control, which is a combination of P and I actions, is generally used to minimize the remaining deviation caused by P
action. PI control always acts to minimize the deviation even if a commanded value changes or external disturbance
steadily occurs. However, the longer the integral time, the slower the system response to quick-changed control.
P action can be used alone for loads with very large part of integral components.
(2) PD control
In PD control, the moment that a deviation occurs, the control rapidly generates greater MV (manipulated value) than
that generated by D action alone, to suppress the deviation increase. When the deviation becomes small, the behavior of
P action becomes small.
A load including the integral component in the controlled system may oscillate due to the action of the integral
component if P action alone is applied. In such a case, use PD control to reduce the oscillation caused by P action, for
keeping the system stable. That is, PD control is applied to a system that does not contain any damping actions in its
process.
(3) PID control
PID control is implemented by combining P action with the deviation suppression of I action and the oscillation
suppression of D action. PID control features minimal control deviation, high precision and high stability.
In particular, PID control is effective to a system that has a long response time to the occurrence of deviation.
Follow the procedure below to set data to PID control function codes.
It is highly recommended that you adjust the PID control value while monitoring the system response waveform with an
oscilloscope or equivalent. Repeat the following procedure to determine the optimal solution for each system.
- Increase the data of J03 (PID control P (Gain)) within the range where the feedback signal does not oscillate.
- Decrease the data of J04 (PID control I (Integral time)) within the range where the feedback signal does not oscillate.
- Increase the data of J05 (PID control D (Differential time)) within the range where the feedback signal does not
oscillate.
Refining the system response waveforms is shown below.
1) Suppressing overshoot
Increase the data of J04 (Integral time) and decrease that of J05 (Differential time.)
2) Quick stabilizing (moderate overshoot allowable)
Decrease the data of J03 (Gain) and increase that of J05 (Differential time).
3) Suppressing oscillation whose period is longer than the integral time specified by J04
Increase the data of J04 (Integral time).
4) Suppressing oscillation whose period is approximately the same as the time specified by J05 (Differential time)
Decrease the data of J05 (Differential time).
Decrease the data of J03 (Gain), if the oscillation cannot be suppressed even though the differential time is set at 0
sec.
5-125
„ Feedback filter (J06)
Data setting range: 0.0 to 900.0 (s)
J06 specifies the time constant of the filter for feedback signals under PID control. (This setting is used to stabilize the
PID control loop. Setting too long a time constant makes the system response slow.)
To specify the filter for feedback signals finely under PID dancer control, apply filter time constants for analog
input (C33, C38 and C43).
J08, J09
PID Control (Pressurization starting frequency, pressurizing time)
J15 (PID Control, Stop frequency for slow flowrate)
J16 (PID Control, Slow flowrate level stop latency)
J17 (PID Control, Starting frequency)
„ PID control (Slow flowrate level stop latency) (J16) Data setting range: 0 to 60 (s)
J16 specifies the period from when the PID output drops below the frequency specified by J15 until the inverter starts
deceleration to stop.
„ PID control (Starting frequency) (J17)
Data setting range: 0.0 to 500.0 (Hz)
J17 specifies the starting frequency. Set J17 to a frequency higher than the stop frequency for slow flowrate (J15). If the
specified starting frequency is lower than the stop frequency for slow flowrate, the latter stop frequency is ignored; the
slow flowrate stopping function is triggered when the output of the PID processor drops below the specified starting
frequency.
FUNCTION CODES
„ PID control (Stop frequency for slow flowrate) (J15) Data setting range: 0.0 (Disable), 1.0 to 500.0 (Hz)
J15 specifies the frequency which triggers slow flowrate stop of inverter.
Chap. 5
Slow flowrate stopping function (J15 to J17)
J15 to J17 configure the slow flowrate stopping function in pump control, a function that stops the inverter when the
discharge pressure rises, causing the volume of water to decrease.
When the discharge pressure has increased, decreasing the reference frequency (output of the PID processor) below the
stop frequency for slow flowrate level (J15) for the period of slow flowrate level stop latency (J16), the inverter
decelerates to stop, while PID control itself continues to operate. When the discharge pressure decreases, increasing the
reference frequency (output of the PID processor) above the starting frequency (J17), the inverter resumes operation.
„ Assignment of PID-STP ("Motor stopped due to slow flowrate under PID control")
(E20 to E24 and E27, data = 44)
Assigning the digital output signal PID-STP to any of the programmable, output terminals with any of E20 through E24
and E27 (data = 44) enables the signal to output when the inverter stops due to the slow flowrate stopping function
under PID control.
For the slow flowrate stopping function, see the chart below.
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
Pressurization before slow flowrate stopping (J08 and J09)
Specifying J08 (Pressurization starting frequency) and J09 (Pressurizing time) enables pressurization control when the
frequency drops below the level specified by J15 (Stop frequency for slow flowrate) for the period specified by J16.
During the pressurization, the PID control is in the hold state.
This function prolongs the stopping time of equipment with a bladder tank by pressurizing immediately before the
frequency drops below the level at which the inverter stops the motor, thus enabling energy saving operation.
Because the pressurization starting frequency (J08) can be specified with a parameter, pressurization setting suitable for
the equipment is possible.
5-126
d codes
U codes
y codes
For the pressurization control, see the chart below.
J10
PID Control (Anti reset windup
J10 suppresses overshoot in control with the PID processor. As long as the deviation between the feedback and the PID
command is beyond the preset range, the integrator holds its value and does not perform integration operation.
- Data setting range: 0 to 200 (%)
J11 to J13
PID Control (Select alarm output, Upper level alarm (AH) and Lower level alarm (AL))
The inverter can output two types of alarm signals (absolute-value and deviation alarms) associated with PID control if
the digital output signal PID-ALM is assigned to any of the programmable, output terminals with any of E20 through
E24 and E27 (data = 42).
J11 specifies the alarm output types. J12 and J13 specify the upper and lower limits for alarms.
„ Select alarm output (J11)
J11 specifies one of the following alarms available.
Data for J11
Alarm
Description
0
Absolute-value alarm
While PV < AL or AH < PV, PID-ALM is ON.
1
2
3
Same as above (with Hold)
Same as above (with Latch)
Same as above (with Hold and Latch)
4
Absolute-value alarm (with Hold)
Absolute-value alarm (with Latch)
Absolute-value alarm (with Hold and
Latch)
Deviation alarm
5
6
7
Deviation alarm (with Hold)
Deviation alarm (with Latch)
Deviation alarm (with Hold and Latch)
Same as above (with Hold)
Same as above (with Latch)
Same as above (with Hold and Latch)
While PV < SV - AL or SV + AH < PV, PID-ALM is ON.
SV: PID process command PV: PID feedback amount
5-127
Hold:
During the power-on sequence, the alarm output is kept OFF (disabled) even when the monitored quantity is
within the alarm range. Once it goes out of the alarm range, and comes into the alarm range again, the alarm is
enabled.
Latch:
Once the monitored quantity comes into the alarm range and the alarm is turned ON, the alarm will remain
ON even if it goes out of the alarm range. To release the latch, perform a reset by using the
key or turning
the terminal command RST ON. Resetting can be done by the same way as resetting an alarm.
„ Upper level alarm (AH) (J12)
J12 specifies the upper limit of the alarm (AH) in percentage (%) of the feedback amount.
„ Lower level alarm (AL) (J13)
J13 specifies the lower limit of the alarm (AL) in percentage (%) of the feedback amount.
The value displayed (%) is the ratio of the upper/lower limit to the full scale (10 V or 20 mA) of the feedback
amount (in the case of a gain of 100%).
Alarm
ON when AH < PV
ON when PV < AL
ON when SV + AH < PV
ON when PV < SV - AL
ON when |SV - PV| > AL
Absolute-value alarm
Deviation alarm
J13 (AL) = 0
J12 (AH) = 100%
J13 (AL) = 100%
J12 (AH) = 100%
J13 (AL) = J12 (AH)
ON when SV - AL < PV < SV + AL
Deviation alarm
ON when AL < PV < AH
Absolute-value alarm
ON when SV - AL < PV < SV + AH
Deviation alarm
A negative logic signal
should be assigned to
PID-ALM.
FUNCTION CODES
Upper limit (absolute)
Lower limit (absolute)
Upper limit (deviation)
Lower limit (deviation)
Upper/lower limit
(deviation)
Upper/lower range limit
(deviation)
Upper/lower range limit
(absolute)
Upper/lower range limit
(deviation)
How to handle the alarm:
Select alarm output (J11)
Parameter setting
Description
Chap. 5
Upper level alarm (AH) and lower level alarm (AL) also apply to the following alarms.
J15 to J17
PID Control (Stop frequency for slow flowrate, Slow flowrate level stop latency and
Starting frequency)
(Refer to J08.)
J18, J19
PID Control (Upper limit of PID process output, Lower limit of PID process output)
The upper and lower limiters can be specified to the PID output, exclusively used for PID control. The settings are
ignored when PID cancel is enabled and the inverter is operated at the reference frequency previously specified.
( E01 to E07, data = 20)
„ PID Control (Upper limit of PID process output) (J18)
J18 specifies the upper limit of the PID processor output limiter in %. If you specify "999," the setting of the frequency
limiter (High) (F15) will serve as the upper limit.
„ PID Control (Lower limit of PID process output) (J19)
J19 specifies the lower limit of the PID processor output limiter in %. If you specify "999," the setting of the frequency
limiter (Low) (F16) will serve as the lower limit.
F codes
E codes
C codes
P codes
H codes
J21
Dew Condensation Prevention (Duty)
A codes
When the inverter is stopped, dew condensation on the motor can be prevented, by feeding DC power to the motor at
regular intervals to keep the temperature of the motor above a certain level.
„ Enabling Dew Condensation Prevention
To utilize this feature, you need to assign the terminal command DWP ("Protect motor from dew condensation") to one
of the general-purpose digital input terminals. ( E01 to E07, data = 39)
b codes
r codes
J codes
d codes
U codes
y codes
5-128
„ Dew Condensation Prevention (Duty) (J21)
The magnitude of the DC power applied to the motor is the same as the setting of F21 (DC braking 1, Braking level)
and its duration of each interval is the same as the setting of F22 (DC braking 1, Braking time). Interval T is determined
so that the ratio of the duration of the DC power to T is the value (Duty) set for J21.
Duty for condensation prevention (J21)
F22
× 100 (%)
T
Condensation Prevention Cycle
J22
Commercial Power Switching Sequence
J56
PID Control (Speed command filter)
J57
PID Control (Dancer reference position)
(Refer to E01 through E07.)
J57 specifies the dancer reference position in the range of -100% to +100% for dancer control.
If J02 = 0 (keypad), this function code is enabled as the dancer reference position.
/
keys. If it is modified, the new command value is
It is also possible to modify the PID command with the
saved as J57 data.
For the setting procedure of the PID command, refer to the JAGUAR VXG User's Manual, Chapter 7, Section 7.3.3
"Setting up frequency and PID commands."
J58
J59 to J61
PID Control (Detection width of dancer position deviation)
PID Control (P (Gain) 2, I (Integral time) 2 and D (Differential time) 2)
The moment the feedback value of dancer roll position comes into the range of "the dancer reference position r
detection width of dancer position deviation (J58)," the inverter switches PID constants from the combination of J03,
J04 and J05 to that of J59, J60 and J61, respectively in its PID processor. Giving a boost to the system response by
raising the P gain may improve the system performance in the dancer roll positioning accuracy.
„ Detection width of dancer position deviation (J58)
J58 specifies the bandwidth in the range of 1 to 100%. Specifying "0" does not switch PID constants.
„ P (Gain) 2 (J59)
Data setting range: 0.000 to 30.000 (times)
„ I (Integral time) 2 (J60)
Data setting range: 0.0 to 3600.0 (s)
„ D (Differential time) 2 (J61)
Data setting range: 0.00 to 600.00 (s)
Descriptions for J59, J60, and J61 are the same as those of PID control P (Gain) (J03), I (Integral time) (J04), and D
(Differential time) (J05), respectively.
J62
PID Control (PID control block selection)
J62 allows you to select either adding or subtracting the PID dancer processor output to or from the primary speed
command. Also, it allows you to select either controlling the PID dancer processor output by the ratio (%) against the
primary speed command or compensating the primary speed command by the absolute value (Hz).
Decimal
0
1
2
3
Data for J62
Bit 1
0
0
1
1
Bit 0
0
1
0
1
Control value type
Absolute value (Hz)
Absolute value (Hz)
Ratio (%)
Ratio (%)
Control function
Operation for the primary speed command
Addition
Subtraction
Addition
Subtraction
J68 to J70
J71, J72
J95, J96
Brake Signal (Brake-OFF current, Brake-OFF frequency/speed and Brake-OFF timer)
Brake Signal (Brake-ON frequency/speed and Brake-ON timer)
Brake Signal (Brake-OFF torque and Speed selection)
These function codes are for the brake releasing/turning-on signals of vertical carrier machines.
It is possible to set the conditions of the brake releasing/turning-on signals (current, frequency or torque) so that a
hoisted load does not fall down at the start or stop of the operation, or so that the load applied to the brake is reduced.
5-129
„ Brake signal -- BRKS (E20 to E24 and E27, data = 57)
This signal outputs a brake control command that releases or activates the brake.
Releasing the Brake
When any of the inverter output current, output frequency, or torque command value exceeds the specified level of the
brake signal (J68/J69/J95) for the period specified by J70 (Brake signal (Brake-OFF timer)), the inverter judges that
required motor torque is generated and turns the signal BRKS ON for releasing the brake.
This prevents a hoisted load from falling down due to an insufficient torque when the brake is released.
Function code
Name
Data setting range
0% to 300%:
Set it putting the inverter rated current at
100%.
Brake-OFF current
J69
Brake-OFF frequency/speed
0.0 to 25.0 Hz
J70
Brake-OFF timer
0.0 to 5.0 s
J95
Brake-OFF torque
0% to 300%
See Note below.
Available only under
V/f control.
Available only under
vector control.
The inverter rated current differs depending upon the drive mode selected (CT, MT or VT).
When the run command is OFF and the output frequency drops below the level specified by J71 (Brake signal
(Brake-ON frequency/speed)) and stays below the level for the period specified by J72 (Brake signal (Brake-ON timer)),
the inverter judges that the motor rotation is below a certain level and turns the signal BRKS OFF for activating the
brake.
Under vector control, when the reference speed or the detected one drops below the level of the stop frequency
specified by F25 (Stop frequency) and stays below the level for the period specified by J72 (Brake signal (Brake-ON
timer)), the inverter judges that the motor rotation is below a certain level and turns the signal BRKS OFF for activating
the brake.
FUNCTION CODES
Turning the Brake ON
Chap. 5
J68
Remarks
This operation reduces the load applied to the brake, extending lifetime of the brake.
Function code
Name
J71
Brake-ON frequency/speed
0.0 to 25.0 Hz
J72
Brake-ON timer
0.0 to 5.0 s
Speed selection
0: Detected speed
1: Reference speed
Speed selection under vector control.
J96
Data setting range
Remarks
Available only under V/f
control.
Available only under vector
control.
When vector control without
speed sensor is selected, set
to "1: Reference speed."
• The brake signal control is only applicable to the 1st motor. If the motor switching function selects any of the
2nd to 4th motor, the brake signal remains ON.
• If the inverter is shut down due to an occurrence of alarm state or by the terminal command BX ("Coast to a
stop"), the brake signal is turned ON immediately.
F codes
E codes
Operation time chart under V/f control
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-130
Operation time chart under vector control without speed sensor
Operation time chart under vector control with speed sensor
• If the zero speed control is enabled under vector control, set J95 (Brake-OFF torque) at 0%.
• After releasing the brake (BRKS ON), operating for a while, and then activating the brake (BRKS OFF) to
stop the motor, if you want to release the brake (BRKS ON), turn the inverter's run command OFF and then
ON.
J97 to J99
Servo-lock (Gain, Completion timer, Completion width)
Servo-lock
This function servo-locks the inverter to hold the motor within the positioning completion range specified by J99 for the
period specified by J98 even if an external force applies to the load.
When the inverter is servo-locked, it keeps the output frequency low; therefore, use the inverter under the
following specified thermal restriction: Output current within the range of 150% of the rated current for 3
seconds and 80% for continuous operation. (Note that under the restriction, the inverter automatically limits
the carrier frequency under 5 kHz.)
Servo-lock starting conditions
Servo-lock control starts when the following conditions are met:
F38 = 0 (Use detected speed as a decision criteria)
F38 = 1 (Use reference speed as a decision criteria)
1
2
3
Run command OFF, or Reference frequency < Stop frequency (F25)
LOCK ("Servo-lock command") ON
(Assignment of LOCK (Function code data = 47))
The detected speed is less than stop frequency (F25).
5-131
The reference speed is less than stop frequency (F25).
Operation examples
Detected speed (F38=0)
Reference speed (F38=1)
Stop frequency (F25)
FWD/REV
LOCK
Control status
OFF
ON
OFF
Not defined
Gate
OFF
ON
Servo-lock
Speed control
OFF
Servo-lock
Not defined
ON
OFF
Chap. 5
Typical Control Sequence of Servo-lock
Specifying servo-lock control
„ Positioning completion signal -- PSET (Function code data = 82), Servo-lock (Completion timer) (J98),
and Servo-lock (Completion range) (J99)
This output signal comes ON when the inverter has been servo-locked so that the motor is held within the positioning
completion range specified by J99 for the period specified by J98.
FUNCTION CODES
When the servo-lock command is ON, the inverter keeps on outputting voltage on output terminals [U], [V] and [W]
even if a run command is OFF and the motor seems to stop.
An electric shock may occur.
„ Servo-lock (Gain) (J97)
J97 specifies the gain of the servo-lock positioning device to adjust the stop behavior and shaft holding torque.
J97
Stop behavior
Small
Response slow, but smooth
Shaft holding torque
Small
l
l
l
Large
Response quick, but hunting large
Large
Monitor for servo-lock control
Monitor item
Current position
Positioning error
LED monitor
Operation monitor: B
The upper and lower digits
appear alternately.
Operation monitor: B
The upper and lower digits
appear alternately.
Function code
Current position pulse
Upper digit: Z90
Lower digit: Z91
Positioning error pulse
Upper digit: Z94
Lower digit: Z95
Remarks
Only when the positioning device is
in operation (positioning control is
active), the LED monitor displays
these data. When it is not in
operation, the monitor is
zero-cleared.
The values on the LED monitor appear based on PG pulses 4-multiplied. Under servo-lock, no current positioning
pulses or positioning error pulses are displayed on the LED monitor.
F codes
E codes
C codes
P codes
Notes for using servo-lock
(1) Positioning control errorHUR
If a positioning error exceeds the value equivalent to four rotations of the motor shaft when the inverter is
servo-locked, the inverter issues a positioning control error signal HUR.
H codes
(2) Stop frequency (F25) under servo-lock
Since servo-lock starts when the output frequency is below the stop frequency (F25), it is necessary to specify such
F25 data that does not trigger HUR (that is, specify the value equivalent to less than 4 rotations of the motor shaft).
Stop frequency (F25) (4 u Gain (J97) u Maximum frequency)
b codes
(Example) When Gain (J97) = 0.01 and Maximum frequency (F03) = 60 Hz, specify F25 data 2.4 Hz.
(3) Enabling the servo-lock control disables the following:
• Operation controlled with a stop frequency
• Rotation direction limitation
A codes
r codes
J codes
d codes
U codes
y codes
5-132
5.2.8 d codes (Application Functions 2)
d01 to d04
d06
Speed Control 1 (Speed command filter, Speed detection filter, P (Gain) and I (Integral time))
Speed Control 1 (Output filter)
These function codes control the speed control sequence for normal operations. For application of each function code,
refer to the figure below and the subsequent descriptions.
Block diagram of the speed control sequence
„ Speed command filter (d01)
Data setting range: 0.000 to 5.000 (s)
d01 specifies a time constant determining the first order delay of the speed command filter.
Modify this data when an excessive overshoot occurs against the speed command change.
Increasing the filter time constant stabilizes the speed command and reduces overshoot against the speed command
change, but it slows the response speed of the inverter.
„ Speed detection filter (d02)
Data setting range: 0.000 to 0.100 (s)
Modify this data when the control target (machinery) is oscillatory due to deflection of a drive belt or other causes so
that ripples (oscillatory components) are superimposed on the detected speed, causing hunting (undesirable oscillation
of the system) and blocking the PI processor gain from increasing (resulting in a slow response speed of the inverter). In
addition, if the lower encoder (PG) resolution makes the system oscillatory, try to modify this data.
Increasing the time constant stabilizes the detected speed and raises the PI processor gain even with ripples
superimposed on the detected speed. However, the detected speed itself delays, resulting in a slower speed response,
larger overshoot, or hunting.
„ P gain (d03)
Data setting range: 0.1 to 200.0 (times)
Data setting range: 0.001 to 9.999 (s)
I integral time (d04)
d03 and d04 specify the gain and integral time of the speed regulator (PI processor), respectively.
P gain
Definition of "P gain = 1.0" is that the torque command is 100% (100% torque output of each inverter capacity) when
the speed deviation (reference speed – actual speed) is 100% (equivalent to the maximum speed).
Determine the P gain according to moment of inertia of machinery loaded to the motor output shaft. Larger moment of
inertia needs larger P gain to keep the flat response in whole operations.
Specifying a larger P gain improves the quickness of control response, but may cause a motor speed overshooting or
hunting (undesirable oscillation of the system). Moreover, mechanical resonance or vibration sound on the machine or
motor could occur due to excessively amplified noises. If it happens, decreasing P gain will reduce the amplitude of the
resonance/vibration. A too small P gain results in a slow inverter response and a speed fluctuation in low frequency,
which may prolong the time required for stabilizing the motor speed.
Integral time
Specifying a shorter integral time shortens the time needed to compensate the speed deviation, resulting in quick
response in speed. Specify a short integral time if quick arrival to the target speed is necessary and a slight overshooting
in the control is allowed; specify a long time if any overshooting is not allowed and taking longer time is allowed.
If a mechanical resonance occurs and the motor or gears sound abnormally, setting a longer integral time can transfer
the resonance point to the low frequency zone and suppress the resonance in the high frequency zone.
„ Output Filter (d06)
Data setting range: 0.000 to 0.100 (s)
d06 specifies the time constant for the first order delay of the speed controller output filter.
Use this function code when setting of the P gain and/or integral time cannot control mechanical resonance such as
hunting or vibration. Generally, setting a larger value to this time constant decreases the amplitude of resonance;
however, a too long time constant may make the system unstable.
5-133
d07
d08
Speed Control 1 (Notch filter resonance frequency)
Speed Control 1 (Notch filter attenuation level)
A49, b49, r49 (Speed control 2 to 4, Notch filter resonance frequency)
A50, b50, r50 (Speed control 2 to 4, Notch filter attenuation level)
These function codes specify speed control using notch filters. The notch filters make it possible to decrease the speed
loop gain only in the vicinity of the predetermined resonance points, suppressing the mechanical resonance.
The notch filters are available only under "vector control with speed sensor."
Setting the speed loop gain at a high level in order to obtain quicker speed response may cause mechanical resonance. If
it happens, decreasing the speed loop gain is required to slow the speed response as a whole. In such a case, using the
notch filters makes it possible to decrease the speed loop gain only in the vicinity of the predetermined resonance points
and set the speed loop gain at a high level in other resonance points, enabling a quicker speed response as a whole.
The following four types of notch filters can be specified.
Function code
Notch filter 1
d08
A50
b49
Notch filter 3
b50
r49
Notch filter 4
r50
Unit
1 to 200
Hz
200
0 to 20
dB
0 (Disable)
1 to 200
Hz
200
0 to 20
dB
0 (Disable)
1 to 200
Hz
200
0 to 20
dB
0 (Disable)
1 to 200
Hz
200
0 to 20
dB
0 (Disable)
Speed control 1
(Notch filter resonance frequency)
Speed control 1
(Notch filter attenuation level)
Speed control 2
(Notch filter resonance frequency)
Speed control 2
(Notch filter attenuation level)
Speed control 3
(Notch filter resonance frequency)
Speed control 3
(Notch filter attenuation level)
Speed control 4
(Notch filter resonance frequency)
Speed control 4
(Notch filter attenuation level)
Default setting
FUNCTION CODES
A49
Notch filter 2
Data setting range
Chap. 5
d07
Name
Setting the notch filter attenuation level to "0" (dB) disables the corresponding notch filter.
It is possible to apply all of the four notch filters to the 1st motor or apply each notch filter to each of the 1st to 4th
motors.
Requisite for use of notch filters
M2, M3, and M4 ("Select motor 2, 3, and
4") are not in use.
(E01 to E07, E98, E99 z 12, 36, 37)
All of the three "Motor/Parameter
Switching" items are set to "Parameter."
(A42, b42, r42 = 1)
Other than the above
Notch filter 1
Notch filter 2
Notch filter 3
Notch filter 4
d07 and d08
A49 and A50
b49 and b50
r49 and r50
All of the four notch filters apply to the 1st motor.
F codes
To the 1st motor To the 2nd motor To the 3rd motor To the 4th motor
E codes
d09, d10
d11 to d13
Speed Control (Jogging) (Speed command filter and Speed detection filter)
(P (Gain), I (Integral time) and Output filter)
C codes
(Refer to d01.)
These function codes control the speed control sequence for jogging operations.
P codes
H codes
The block diagrams and function codes related to jogging operations are the same as for normal operations.
Since this speed control sequence is exclusive to jogging operations, specify these function codes to obtain higher speed
response than that of normal operations for smooth jogging operations.
For details, refer to the corresponding descriptions (d01 to d04 and d06) about the speed control sequence for normal
operations.
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-134
d14 to d17
Feedback Input (Pulse input format, Encoder pulse resolution,
Pulse count factor 1 and Pulse count factor 2)
These function codes specify the speed feedback input under vector control with speed sensor.
„ Feedback Input, Pulse input format (d14)
d14 specifies the speed feedback input format.
Data for d14
Pulse input mode
0
Pulse train sign/Pulse train input
Remarks
1
Forward rotation pulse/
Reverse rotation pulse
Set the d14 data to "2" for Fuji motors exclusively designed
for vector control.
2
A and B phases with 90 degree
phase difference
„ Feedback Input, Encoder pulse resolution (d15)
Data setting range: 0014 to EA60 (in hex.)
d15 specifies the pulse resolution (P/R) of the speed feedback encoder. (20 to 60000 P/R in decimal.)
„ Feedback Input, Pulse count factor 1 (d16) and Pulse count factor 2 (d17)
Data setting range: 1 to 9999
d16 and d17 specify the factors to convert the speed feedback input pulse rate into the motor shaft speed (r/min).
Specify the data according to the transmission ratios of the pulley and gear train as shown below.
An Example of a Closed Loop Speed Control System (Conveyor)
Listed below are expressions for conversion between a speed feedback input pulse rate and motor shaft speed.
Motor shaft speed =
Pulse count factor 2 (d17)
u Encoder shaft speed
Pulse count factor 1 (d16)
Pulse count factor 2 (d17)
b
=
Pulse count factor 1 (d16)
a
u
d
c
u
c
Pulse count factor 1 (d16)
=
a
Pulse count factor 2 (d17)
=
b u d
5-135
When enabling the vector control with speed sensor, mount the sensor encoder on the motor output shaft
directly, or on a shaft with the rigidity equivalent to the motor output shaft. A backlash or deflection being on
the mounting shaft could interfere with normal control.
d21, d22
d23
Speed Agreement/PG Error (Hysteresis width and Detection timer)
PG Error Processing
These function codes specify the detection levels of the speed agreement signal DSAG and PG error detected signal
PG-ERR.
Speed agreement signal DSAG (E20 to E24 and E27, data = 71)
„ Speed Agreement/PG Error (Hysteresis width) (d21)
PG Error Processing (d23)
Data for d23
Function
0
Continue to run
1
Stop running with alarm 1 (HUH )
2
Stop running with alarm 2 (HUH )
FUNCTION CODES
PG error detected signal PG-ERR (E20 to E24 and E27, data = 76)
„ Speed Agreement/PG Error (Hysteresis width (d21)
Data setting range: 0.0 to 50.0%,
100% at the maximum speed
(Detection timer) (d22)
Data setting range: 0.00 to 10.00 (s)
Chap. 5
Data setting range: 0.0 to 50.0%,
100% at the maximum speed
(Detection timer) (d22)
Data setting range: 0.00 to 10.00 (s)
If the speed regulator's deviation (between the reference speed and detected one) is within the specified range (d21), the
signal DSAG turns ON. If the deviation is out of the specified range (d21) for the period specified by d22, the signal
turns OFF. This signal allows the user to check whether the speed regulator works properly or not.
If the deviation (between the reference speed and detected one) is out of the specified range (d21) for the period
specified by d22, the inverter judges it as a PG error.
Data setting for d23, however, defines the detection conditions and the error processing after the error detection.
Data for d23
Detection condition
Processing after error detection
0
When the inverter cannot follow the speed
command (even after the soft-starting) due to a
heavy overload or the like, and the detected speed
is slow against the reference speed, the inverter
does not interpret this situation as a PG error.
The inverter interprets the situation above as a PG
error.
The inverter outputs the PG error
detected signal PG-ERR and continues to
run.
The inverter enters the coast-to-stop state
outputting the HUH alarm, and also outputs
the PG error detected signal PG-ERR.
1
2
Enabling an operation limiting function such as the torque limit and droop control will increase the deviation
caused by a huge gap between the reference speed and actual one. In this case, the inverter may trip
interpreting this situation as a PG error, depending on the running status. To avoid this incident, set the d23
data to "0: Continue to run" to prevent the inverter from tripping even if any of those limiting functions is
activated.
F codes
E codes
d24
Zero Speed Control
(Refer to F23.)
C codes
P codes
d25
ASR Switching Time
(Refer to A42.)
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-136
d32, d33
Torque Control (Speed limit 1 and Speed limit 2)
d41
Application-Defined Control
(Refer to H18.)
The constant peripheral speed control is available as an application, which suppresses an increase in peripheral speed
(line speed) resulting from the increasing radius of the take-up roll in a winder system.
In a winder system (e.g., roving frames, wiredrawing machines), if the inverter continues to run the motor at a constant
speed, the take-up roll gets bigger with materials (roving, wire, etc.) and its radius increases so that the winding speed
of the take-up roll increases.
Under the application-defined control, to keep the peripheral speed (winding speed) constant, the inverter detects the
winding speed using an encoder and controls the motor rotation according to the encoder feedback.
„ Application-Defined Control (d41)
d41 specifies whether to enable or disable the constant peripheral speed control.
Data for d41
Function
0
Disable (Ordinary control)
1
Enable (Constant peripheral speed control)
Note: This control is valid only when "V/f control with speed sensor" or "Dynamic torque vector
control with speed sensor" is selected with F42, A14, b14, or r14 (data = 3 or 4).
Mechanical configuration of a winder system and function code settings
Shown below is a typical mechanical configuration of a winder system for which it is necessary to configure the
function codes as listed below.
Winder
(The radius of the take-up roll increases
as the roll rotates.)
Speed 䡒
Radius of take-up roll (r1)
Drum
Speed v
in winding direction
㼎
㼍
Inverter
Reduction ratio a:b
(When the motor shaft
rotates “b” times, the takeup roll shaft rotates “a”
Speed detector
times.)
radius r2
Motor
㼁, 㼂, 㼃
R, S, T
c
d
Encoder
I/F card
Reduction ratio c䠖d
(When the speed detector shaft
rotates “d” times, the encoder
shaft rotates “c” times.)
㻱㼚㼏㼛㼐㼑㼞
A/B phase or B phase
- Speed reduction ratio between motor shaft and take-up roll shaft a : b
- Speed reduction ratio between speed detector shaft and encoder shaft c : d
- Radius of take-up roll before winding r1 (m)
- Radius of speed detector r2 (m)
Setting the Reduction Ratio
Function code
Name
Settings
d15
Encoder pulse resolution
Encoder pulse resolution (P/R) to be set in hexadecimal
d16
Pulse count factor 1
Speed reduction ratio of the whole machinery (load)
d17
Pulse count factor 2
K2
K1
r2 b d
u u
r1 a c
d17/d16
d16: Denominator factor for the speed reduction ratio (K1 = r1 u a u c)
d17: Numerator factor for the speed reduction ratio (K2 = r2 u b u d)
5-137
„ Peripheral speed (line speed) command
Under constant peripheral speed control, speed commands should be given as peripheral speed (line speed) ones.
Setting with digital inputs
To digitally specify a peripheral speed (line speed) in m/min, make the following settings.
Function code
Name
Settings
E48
LED monitor
E50
Coefficient for speed indication
5: Line speed in m/min
Ks
240 u a u r1
pub
Where
V: Peripheral speed (Line speed) (m/min)
fmax: Maximum frequency 1 (F03)
FUNCTION CODES
Setting with analog inputs
To specify a peripheral speed (line speed) using analog inputs, set an analog input (0 to 100%) based on the following
equation.
p u b u 100
Analog input (%) =
uV
240S u r1 u a u fmax
Chap. 5
Ks: Coefficient for speed indication (E50)
p: Number of motor poles
a, b: Components of speed reduction ratio between motor shaft and
take-up roll shaft (When the motor shaft rotates "b" times, the
take-up roll shaft rotates "a" times.)
r1: Radius of take-up roll before winding (initial value) (m)
„ Adjustment
Like usual speed controls, it is necessary to adjust the speed command filter, speed detection filter, P gain, and integral
time in the speed control sequence that controls the peripheral speed at a constant level.
Function code
Name
Key points
d01
Speed control
(Speed command filter)
If an excessive overshoot occurs for a speed command change,
increase the filter constant.
d02
Speed control
(Speed detection filter)
If ripples are superimposed on the speed detection signal so that the
speed control gain cannot be increased, increase the filter constant to
obtain a larger gain.
d03
Speed control P
(Gain)
If hunting is caused in the motor speed control, decrease the gain.
If the motor response is slow, increase the gain.
d04
Speed control I
(Integral time)
If the motor response is slow, decrease the integral time.
F codes
„ Cancel constant peripheral speed control Hz/LSC (Function code E01 to E07, data = 70)
Turning ON Hz/LSC cancels the constant peripheral speed control. This disables the frequency compensation of PI
operation, resulting in no compensation for a take-up roll getting bigger and an increase in the winding speed.
Use this signal to temporarily interrupt the control for repairing a thread break, for example.
Hz/LSC
OFF
ON
Function
Enable constant peripheral speed control (depending on d41 setting)
Cancel constant peripheral speed control (V/f control, without compensation for a take-up roll
getting bigger)
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
5-138
„ Hold the constant peripheral speed control frequency in the memory LSC-HLD
(Function code E01 to E07, data = 71)
If this signal is ON under constant peripheral speed control, stopping the inverter (including an occurrence of an alarm
and a coast-to-stop command) or turning OFF Hz/LSC saves the current frequency command compensating for a
take-up roll getting bigger, in the memory. At the time of restart, the saved frequency command applies and the inverter
keeps the peripheral speed constant.
LSC-HLD
OFF
ON
Function
Disable (no saving operation)
Enable (Saving the frequency command compensating for a take-up roll getting bigger)
Shutting down the inverter power during an operation stop loses the frequency compensation data saved in the
memory. At the time of restart, therefore, the inverter runs at the frequency without compensation so that a
large overshoot may occur.
d51 to d55
d68, d69, d99
Reserved for particular manufacturers
These function codes d51 to d55, d68, d69 and d99 are displayed, but they are reserved for particular manufacturers.
Unless otherwise specified, do not access these function codes.
d59, d61
d62, d63
Command (Pulse Rate Input)
(Pulse input format, Filter time constant, Pulse count factor 1 and Pulse count factor 2)
(Refer to F01.)
d70
Speed Control Limiter
d70 specifies a limiter for the PI value output calculated in speed control sequence under V/f control with speed sensor
or dynamic torque vector control with speed sensor.
A PI value output is within the "slip frequency u maximum torque (%)" in a normally controlled state.
If an abnormal state such as a temporary overload arises, the PI value output greatly fluctuates and it may take a long
time for the PI value output to return to the normal level. To suppress such abnormal operation, the PI value output can
be limited with d70.
Data setting range: 0 to 100 (%) (assuming the maximum frequency as 100%)
5.2.9 U codes (Application functions 3)
U00
U01 to U50
U71 to U75
U81 to U85
U91
Customizable Logic (Mode selection)
Customizable Logic: Step 1 to 10 (Setting)
Customizable Logic Output Signal 1 to 5 (Output selection)
Customizable Logic Output Signal 1 to 5 (Function selection)
Customizable Logic Timer Monitor (Step selection)
The customizable logic function allows the user to form a logic circuit for digital input/output signals, modify them
arbitrarily, and configure a simple relay sequence inside the inverter.
In a customizable logic, one step (component) is composed of "2 inputs and 1 output + logical operation (including
timer)" and a total of ten steps can be used to configure a sequence.
„ Specifications
Item
Input signal
Operation block
Output signal
Number of steps
Customizable logic output signal
Customizable logic processing time
Specifications
2 inputs
Logical operation, counter, etc.: 13 types
Timer: 5 types
1 output
10 steps
5 outputs
2 ms
5-139
„ Block diagram
Chap. 5
FUNCTION CODES
„ Customizable Logic (Mode selection) (U00)
U00 specifies whether to enable the sequence configured by the customizable logic function or disable it to operate the
inverter only by input terminal signals and others.
Data for U00
F codes
E codes
Function
C codes
0
Disable
1
Enable (Customizable logic operation)
P codes
„ Customizable Logic (Setting) (U01 to U50)
In a customizable logic, one step is composed of the components shown in the following block diagram.
Input 1
Input 2
Logic circuit
General-purpose
timer
H codes
A codes
b codes
Output
r codes
Timer
J codes
d codes
U codes
y codes
5-140
Function codes for each step
Step No.
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Step 8
Step 9
Step 10
Input 1
U01
U06
U11
U16
U21
U26
U31
U36
U41
U46
Input 2
Logic circuit
General-purpose
timer
U04
U09
U14
U19
U24
U29
U34
U39
U44
U49
Timer
Output (Note)
SO01
SO02
SO03
SO04
SO05
SO06
SO07
SO08
SO09
SO10
(Note) These items shown in this column are output signals, not function codes.
U02
U07
U12
U17
U22
U27
U32
U37
U42
U47
U03
U08
U13
U18
U23
U28
U33
U38
U43
U48
U05
U10
U15
U20
U25
U30
U35
U40
U45
U50
„ Inputs 1 and 2 (U01, U02, etc.)
The following signals are available as input signals.
Data
Selectable Signals
0000 (1000)
|
0105 (1105)
General-purpose output signals
(Same as the ones specified by E20): RUN (Inverter running), FAR (Frequency (speed)
arrival signal), FDT (Frequency (speed) detected), LU (Undervoltage detected (Inverter
stopped)), B/D (Torque polarity detected), and other signals.
Note: 27 (Universal DO) is not available.
2001 (3001)
Output of step 1
SO01
2002 (3002)
Output of step 2
SO02
2003 (3003)
Output of step 3
SO03
2004 (3004)
Output of step 4
SO04
2005 (3005)
Output of step 5
SO05
2006 (3006)
Output of step 6
SO06
2007 (3007)
Output of step 7
SO07
2008 (3008)
Output of step 8
SO08
2009 (3009)
Output of step 9
SO09
2010 (3010)
Output of step 10
SO10
4001 (5001)
Terminal [X1] input signal
X1
4002 (5002)
Terminal [X2] input signal
X2
4003 (5003)
Terminal [X3] input signal
X3
4004 (5004)
Terminal [X4] input signal
X4
4005 (5005)
Terminal [X5] input signal
X5
4006 (5006)
Terminal [X6] input signal
X6
4007 (5007)
Terminal [X7] input signal
X7
4010 (5010)
Terminal [FWD] input signal
FWD
4011 (5011)
Terminal [REV] input signal
REV
6000 (7000)
Final run command
FL_RUN
(ON when "frequency command z 0" and a run command is given)
6001 (7001)
Final FWD run command
FL_FWD
(ON when "frequency command z 0" and a run forward command is given)
Final REV run command
FL_REV
(ON when "frequency command z 0" and a run reverse command is given)
During acceleration
DACC
(ON during acceleration)
6002 (7002)
6003 (7003)
6004 (7004)
6005 (7005)
6006 (7006)
6007 (7007)
During deceleration
DDEC
(ON during deceleration)
Under anti-regenerative control
REGA
(ON under anti-regenerative control)
Within dancer reference position
DR_REF
(ON when the dancer roll position is within the reference range)
Alarm factor presence
(ON when there is no alarm factor)
5-141
ALM_ACT
„ Logic circuit (U03, etc.)
Any of the following functions is selectable as a logic circuit (with general-purpose timer).
Data
Function
Description
0
No function assigned
Output is always OFF.
1
Through output + General-purpose timer
Only a general-purpose timer. No logic circuit exists.
2
ANDing + General-purpose timer
3
4
5
6
9
10
11
Increment counter
12
Decrement counter
13
Timer with reset input
FUNCTION CODES
8
Chap. 5
7
AND circuit with 2 inputs and 1 output, plus general-purpose
timer.
ORing + General-purpose timer
OR circuit with 2 inputs and 1 output, plus general-purpose
timer.
XORing + General-purpose timer
XOR circuit with 2 inputs and 1 output, plus general-purpose
timer.
Set priority flip-flop + General-purpose
Set priority flip-flop with 2 inputs and 1 output, plus
general-purpose timer.
timer
Reset priority flip-flop + General-purpose Reset priority flip-flop with 2 inputs and 1 output, plus
general-purpose timer.
timer
Rising edge detector + General-purpose
Rising edge detector with 1 input and 1 output, plus
timer
general-purpose timer.
This detects the rising edge of an input signal and outputs the ON
signal for 2 ms.
Falling edge detector + General-purpose Falling edge detector with 1 input and 1 output, plus
timer
general-purpose timer.
This detects the falling edge of an input signal and outputs the
ON signal for 2 ms.
Rising and falling edge detector +
Rising and falling edge detector with 1 input and 1 output, plus
General-purpose timer
general-purpose timer.
This detects the falling and rising edges (both) of an input signal
and outputs the ON signal for 2 ms.
Input hold + General-purpose timer
Hold function of previous values of 2 inputs and 1 output, plus
general-purpose timer.
If the hold control signal is OFF, the logic circuit outputs input
signals; if it is ON, the logic circuit retains the previous values of
input signals.
Increment counter with reset input.
By the rising edge of an input signal, the logic circuit increments
the counter value by one. When the counter value reaches the
target one, the output signal turns ON.
Turning the reset signal ON resets the counter to zero.
Decrement counter with reset input.
By the rising edge of an input signal, the logic circuit decrements
the counter value by one. When the counter value reaches zero,
the output signal turns ON.
Turning the reset signal ON resets the counter to the initial value.
Timer output with reset input.
If an input signal turns ON, the output signal turns ON and the
timer starts. When the period specified by the timer has elapsed,
the output signal turns OFF, regardless of the input signal state.
Turning the reset signal ON resets the current timer value to zero
and turns the output OFF.
F codes
E codes
C codes
P codes
The block diagrams for individual functions are given below.
(1) Through output
H codes
(2) AND
(3) OR
Input 1
Input 1
A codes
General-purpose timer
Input 1
Output
b codes
General-purpose timer
General-purpose timer
r codes
Output
Output
J codes
Input 2
Input 2
Input 2
d codes
U codes
y codes
5-142
(4) XOR
(5) Set priority flip-flop
Input 1
Input 1
General-purpose timer
General-purpose timer
Flip-flop
Output
Previous
output
Output
Remarks
OFF
OFF
Hold previous
value
ON
ON
ON
㸫
OFF
㸫
㸫
ON
Input 1 Input 2
Q
S
R
Output
OFF
OFF
Input 2
Input 2
ON
Set priority
(6) Reset priority flip-flop
Input 1
General-purpose timer
Flip-flop
Output
S
Previous
output
Output
OFF
OFF
Input 1
Input 2
OFF
OFF
ON
ON
㸫
ON
㸫
OFF
ON
OFF
㸫
ON
Remarks
Q
R
Input 2
Hold previous
value
Reset priority
(7) Rising edge detection
Rising edge detection
(8) Falling edge detection
General-purpose timer
Falling edge detection General-purpose timer
Output
Input 1
(9) Both edges detection
Input 1
Input 2
Both edges detection
General-purpose timer
Output
Input 1
Output
Input 2
Input 2
(10) Hold
(11) Increment counter
Output
Input 1
Output
=0
Decrement counter
Increment counter
General-purpose timer
Input 1
(12) Decrement counter
Output
Input 1
=1
Clear counter
Initialize the
counter
Input 2
Input 2
Input 2
(13) Timer with reset input
ON timer
Input 1
OFF
ON
OFF
Output
Input 1
Output
OFF
ON
OFF
Input 2
Reset
ON
OFF
ON
Input 2
Timer
Timer period
5-143
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
„ General-purpose timer (U04, etc.)
The table below lists the general-purpose timers available.
Function
No timer
On-delay timer
Description
2
Off-delay timer
3
Pulses (1 shot)
4
Retriggerable timer
5
Pulse train output
Turning an input signal ON starts the on-delay timer. When the period specified by
the timer has elapsed, an output signal turns ON.
Turning the input signal OFF turns the output signal OFF.
Turning an input signal ON turns an output signal ON.
Turning the input signal OFF starts the off-delay timer. When the period specified
by the timer has elapsed, the output signal turns OFF.
Turning an input signal ON issues a one-shot pulse whose length is specified by
the timer.
Turning an input signal ON issues a one-shot pulse whose length is specified by
the timer.
If an input signal is turned ON again during the preceding one-shot pulse length,
however, the logic circuit issues another one-shot pulse.
If an input signal turns ON, the logic circuit issues the ON and OFF pulses (whose
lengths are specified by the timer) alternately and repeatedly. This function is used
to flash a luminescent device.
Chap. 5
Data
0
1
(1) On-delay timer
Input
OFF
(2) Off-delay timer
ON
OFF
Output
FUNCTION CODES
The operation schemes for individual timers are shown below.
OFF
ON
ON
OFF
Input
OFF
Output
Timer
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
Timer
Timer period
Timer period
(3) Pulses (1 shot)
Input
Output
OFF
(4) Retriggerable timer
ON
OFF
ON
OFF
OFF
Input
OFF
ON
Output
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
ON
ON
OFF
OFF
Timer
Timer
㻝㻜㻚 period
㻜㻜⛊
Timer
Timer period
Less than
Timer period
timer period
F codes
E codes
(5) Pulse train output
C codes
Input
Output
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
P codes
ON
H codes
A codes
b codes
Timer
Timer period
r codes
„ Timer (U05, etc.)
J codes
U05 and other related function codes specify the general-purpose timer period or the increment/decrement counter
value.
d codes
Data
0.00 to 600.00
Function
Description
Timer period
The period is specified by seconds.
Counter value
The specified value is multiplied by 100 times. (If 0.01 is specified, it is
converted to 1.)
5-144
U codes
y codes
„ Output signals
In a customizable logic, outputs from steps 1 to 10 are issued to SO01 to SO10, respectively.
Those outputs SO01 to SO10 differ in configuration depending upon the connection destination, as listed below. (To
relay those outputs to any function other than the customizable logic, route them via customizable logic outputs CL01
to CL05.)
If the connection destination is:
Configuration
Function codes
Customizable logic input
Select one of the internal step output signals SO01 to SO10
in customizable logic input setting.
U01, U02, etc.
Input to the inverter's sequence
processor
(e.g., "Select multi-frequency" SS1,
"Run forward" FWD)
Select one of the internal step output signals SO01 to SO10
to be connected to customizable logic output signals 1 to 5
(CLO1 to CLO5).
U71 to U75
Select an inverter's sequence processor input function to
which one of the customizable logic output signals 1 to 5
(CLO1 to CLO5) is to be connected. (Same as in E01)
U81 to U85
Select one of the internal step output signals SO01 to SO10
to be connected to customizable logic output signals 1 to 5
(CLO1 to CLO5).
U71 to U75
To specify a general-purpose digital output function (on Y
terminals) to which one of the customizable logic output
signals 1 to 5 (CLO1 to CLO5) is to be connected, select
one of CLO1 to CLO5 by specifying the general-purpose
digital output function on any Y terminal.
E20 to E24, E27
General-purpose digital output
(Y terminals)
General-purpose digital outputs (on Y terminals) are updated every 5 ms. To securely output a customizable
logic signal via Y terminals, include on- or off-delay timers in the customizable logic. Otherwise, short ON
or OFF signals may not be reflected on those terminals.
Function
code
U71
Name
Data setting range
Customizable logic output signal 1
(Output selection)
0: Disable
1: Step 1 output
2: Step 2 output
3: Step 3 output
4: Step 4 output
5: Step 5 output
6: Step 6 output
7: Step 7 output
8: Step 8 output
9: Step 9 output
10: Step 10 output
SO01
SO02
SO03
SO04
SO05
SO06
SO07
SO08
SO09
SO10
Default
setting
0
U72
Customizable logic output signal 2
(Output selection)
U73
Customizable logic output signal 3
(Output selection)
U74
Customizable logic output signal 4
(Output selection)
U75
Customizable logic output signal 5
(Output selection)
U81
Customizable logic output signal 1
(Function selection)
U82
Customizable logic output signal 2
(Function selection)
U83
Customizable logic output signal 3
(Function selection)
U84
Customizable logic output signal 4
(Function selection)
100
U85
Customizable logic output signal 5
(Function selection)
100
0 to 100, 1000 to 1081
Same as data of E98/E99, except the
following.
19 (1019): Enable data change with keypad
(data can be modified)
80 (1080): Cancel customizable logic
5-145
0
0
0
0
100
100
100
„ Notes for using a customizable logic
A customizable logic performs processing every 2 ms in the following sequence.
(1) At the start of processing, the customizable logic latches all of the external input signals entered to steps 1 to 10 to
ensure simultaneity.
(2) Logical operations are performed in the order of steps 1 to 10.
(3) If an output of a particular step applies to an input at the next step, the output of the step having processing priority
can be used in the same processing.
(4) The customizable logic updates all of the five output signals at the same time.
Chap. 5
When configuring a logic circuit, take into account the processing order of the customizable logic. Otherwise, a delay in
processing of logical operation leads to a signal delay problem, resulting in no expected output, slow processing, or a
hazard signal issued.
An accident or injuries could occur.
„ Customizable logic timer monitor (Step selection) (U91)
FUNCTION CODES
Ensure safety before modifying customizable logic related function code settings (U codes and related function
codes) or turning ON the "Cancel customizable logic" terminal command CLC. Depending upon the settings, such
modification or cancellation of the customizable logic may change the operation sequence to cause a sudden motor
start or an unexpected motor operation.
The contents of the timer in a customizable logic can be monitored using the monitor-related function code or the
keypad.
Selecting a timer to be monitored
Function code
Function
U91
1 to 10: Specifies the step number whose timer or counter is to be
monitored
Remarks
Monitoring
Monitored by:
Related function code and LED monitor display
Communications link
Keypad
X90 Customizable logic (Timer monitor)
I/O checking: B㸽
Monitored item
Timer or counter value specified by
U91 (dedicated to monitoring)
„ Cancel customizable logic CLC (E01 to E07, data = 80)
This terminal command can disable the customizable logic temporarily. This terminal command is used to run the
inverter without using the customizable logic circuit or timers for maintenance or other purposes.
CLC
Function
OFF
Enable customizable logic (Depends on the U00 setting)
ON
Disable customizable logic
F codes
E codes
C codes
P codes
Before changing the setting of CLC, ensure safety. Turning CLC ON disables the sequence of the
customizable logic, causing a sudden motor start depending upon the settings.
„ Clear all customizable logic timers CLTC (E01 to E07, data = 81)
Assigning CLTC to any of the general-purpose digital input terminals and turning it ON resets all of the
general-purpose timers and counters in the customizable logic. This terminal command is used when the timings
between the external sequence and the internal customizable logic do not match due to a momentary power failure or
other reasons so that resetting and restarting the system is required.
CLTC
H codes
A codes
b codes
r codes
J codes
Function
d codes
OFF
Ordinary operation
ON
Reset all of the general-purpose timers and counters in the customizable logic.
(To operate the timers and counters again, revert CLTC to OFF.)
U codes
y codes
5-146
5.2.10
y codes (Link Functions)
y01 to y20
RS-485 Communication 1 and 2
Up to two ports of RS-485 communications link are available as listed below.
Port
Route
Function code
Port 1
RS-485 communications link
(via the RJ-45 connector prepared for keypad connection)
y01 through y10
RS-485 communications link
(via terminals DX+, DX- and SD on the control PCB)
Port 2
y11 through y20
Applicable equipment
Standard keypad
JAGUAR Loader
Host equipment
Host equipment
To connect any of the applicable devices, follow the procedures shown below.
(1) Standard keypad
The standard keypad allows you to run and monitor the inverter.
There is no need to set the y codes.
(2) JAGUAR Loader
Connecting your computer running JAGUAR Loader to the inverter via RS-485 communication (port 1), you can
monitor the inverter’s running status information, edit function codes, and test-run the inverters.
For the setting of y codes, refer to the descriptions of y01 to y10.
JAGUAR VXG series of inverters has a USB port on the keypad.
To use the JAGUAR Loader via the USB port, simply set the station address (y01) to "1" (factory default).
(3) Host equipment
The inverter can be managed and monitored by connecting host equipment such as a PC and PLC to the inverter.
Modbus RTU* and general-purpose inverter protocol are available for communications protocols.
* Modbus RTU is a protocol established by Modicon, Inc.
For details, refer to the RS-485 Communication User's Manual.
„ Station address (y01 for port 1 and y11 for port 2)
y01 or y11 specifies the station address for the RS-485 communications link. The table below lists the protocols and the
station address setting ranges.
Protocol
Modbus RTU protocol
JAGUAR Loader protocol
General-purpose inverter protocol
Station address
1 to 247
1 to 255
1 to 31
Broadcast address
0
None
99
- If any wrong address beyond the above range is specified, no response is returned since the inverter will be unable to
receive any enquiries except the broadcast message.
- To use JAGUAR Loader via the RS-485 communications link (port 1), set the station address that matches the
connected computer.
„ Communications error processing (y02 for port 1 and y12 for port 2)
y02 or y12 specifies the error processing to be performed if an RS-485 communications error occurs.
RS-485 communications errors include logical errors (such as address error, parity error, framing error), transmission
protocol error, and physical errors (such as no-response error specified by y08 and y18). The inverter can recognize
such an error only when it is configured with a run or frequency command sourced through the RS-485 communications
link and it is running. If none of run and frequency commands is sourced through the RS-485 communications link or
the inverter is not running, the inverter does not recognize any error occurrence.
Data for y02, y12
0
1
2
3
Function
Immediately trip, displaying an RS-485 communications error (HU for y02 and HUS for
y12). (The inverter stops with alarm issue.)
Run during the period specified by the error processing timer (y03, y13), display an RS-485
communications error (HU for y02 and HUS for y12), and then stop operation. (The
inverter stops with alarm issue.)
Retry communication during the period specified by the error processing timer (y03, y13).
If a communications link is recovered, continue operation. Otherwise, display an RS-485
communications error (HU for y02 and HUS for y12) and stop operation. (The inverter stops
with alarm issue.)
Continue to run even when a communications error occurs.
For details, refer to the RS-485 Communication User's Manual.
5-147
„ Timer (y03 for port 1 and y13 for port 2)
Data setting range: 0.0 to 60.0 (s)
y03 or y13 specifies an error processing timer. If the timer count has elapsed due to no response from the other end
when a query has been issued, the inverter interprets it as an error occurrence. See the "No-response error detection time
(y08, y18)" given on the next page.
„ Baud rate (y04 for port 1 and y14 for port 2)
y04 or y14 specifies the transmission speed for RS-485
communication.
For JAGUAR Loader (via the RS-485 communications link),
specify the transmission speed that matches the connected
computer.
„ Data length (y05 for port 1 and y15 for port 2)
y05 or y15 specifies the character length for RS-485
communication.
For JAGUAR Loader (via the RS-485 communications link),
no setting is required since Loader automatically sets 8 bits.
(The same applies to the Modbus RTU protocol.)
Data for y05 and y15
0
1
Data length
8 bits
7 bits
„ Parity check (y06 for port 1 and y16 for port 2)
y06 or y16 specifies the property of the parity bit.
For JAGUAR Loader, no setting is required since Loader
automatically sets the even parity.
Data for y06 and y16
Parity
None
(2 stop bits for Modbus RTU)
Even parity
(1 stop bit for Modbus RTU)
Odd parity
(1 stop bit for Modbus RTU)
None
(1 stop bit for Modbus RTU)
0
1
2
3
„ Stop bits (y07 for port 1 and y17 for port 2)
y07 or y17 specifies the number of stop bits.
For JAGUAR Loader, no setting is required since Loader
automatically sets 1 bit.
For the Modbus RTU protocol, no setting is required since
the stop bits are automatically determined associated with the
property of parity bits.
Data for y07 and y17
0
1
FUNCTION CODES
Transmission speed (bps)
2400
4800
9600
19200
38400
Chap. 5
Data for y04 and y14
0
1
2
3
4
Stop bit(s)
2 bits
1 bit
„ No-response error detection time (y08 for port 1 and y18 for port 2)
y08 or y18 specifies the time interval from when the inverter
detects no access until it enters communications error alarm
mode due to network failure and processes the
communications error. This applies to a mechanical system
that always accesses its station within a predetermined
interval during communications using the RS-485
communications link.
For the processing of communications errors, refer to y02
and y12.
Data for y08 and y18
0
1 to 60
Function
No detection
1 to 60 s
F codes
E codes
C codes
„ Response interval (y09 for port 1 and y19 for port 2)
Data setting range: 0.00 to 1.00 (s)
y09 or y19 specifies the latency time after the end of receiving a query sent from the host equipment (such as a
computer or PLC) until the start of sending the response. This function allows using equipment whose response time is
slow while a network requires quick response, enabling the inverter to send a response timely by the latency time
setting.
P codes
H codes
A codes
b codes
r codes
T1 = Response interval + D
where D is the processing time inside the inverter. This time may vary depending on the processing status and the
command processed in the inverter.
For details, refer to the RS-485 Communication User's Manual.
When setting the inverter with JAGUAR Loader via the RS-485 communications link, pay sufficient attention
to the performance and/or configuration of the PC and protocol converter such as RS-485RS-232C converter.
Note that some protocol converters monitor the communications status and switch the sending/receiving of
transmission data by a timer.
5-148
J codes
d codes
U codes
y codes
„ Protocol selection (y10 for port 1)
y10 specifies the communications protocol for port 1.
For JAGUAR Loader (via the RS-485 communications
link), only y10 can be used for protocol selection. Set the
y10 data at "1."
„ Protocol selection (y20 for port 2)
y20 specifies the communications protocol for port 2.
Data for y10
0
1
2
Protocol
Modbus RTU protocol
JAGUAR Loader protocol
General-purpose inverter protocol
Data for y20
0
2
Protocol
Modbus RTU protocol
General-purpose inverter protocol
y97
Communication Data Storage Selection
A nonvolatile storage in the inverter has a limited number of rewritable times (100,000 to 1,000,000 times). Saving data
into the storage so many times unnecessarily will no longer allow the storage to save data, causing memory errors.
For frequent data writing via the communications link, therefore, a temporary storage is provided instead of the
nonvolatile storage. To use the temporary storage, set the y97 data at "1." Using the temporary storage reduces the
number of data writing times into the nonvolatile storage, preventing memory errors.
Setting the y97 data at "2" saves all data written in the temporary storage into the nonvolatile one.
Changing the y97 data requires simultaneous keying of
Data for y97
0
1
2
and
/
keys.
Function
Save into nonvolatile storage (Rewritable times limited)
Write into temporary storage (Rewritable times unlimited)
Save all data from temporary storage to nonvolatile one
(After saving data, the data automatically returns to "1.")
y98
Bus Link Function (Mode selection)
y99
Loader Link Function (Mode selection)
(Refer to H30.)
This is a link switching function for JAGUAR Loader. Rewriting the data of y99 to enable RS-485 communications
from Loader helps Loader send the inverter the frequency and/or run commands. Since the data to be set in the function
code of the inverter is automatically set by Loader, no keypad operation is required.
While Loader is selected as the source of the run command, if the computer runs out of control and cannot be stopped
by a stop command sent from Loader, disconnect the RS-485 communications cable from the port 1 or the USB cable,
connect a keypad instead, and reset the y99 data to "0." This setting "0" in y99 means that the run and frequency
command source specified by function code H30 takes place instead of JAGUAR Loader.
Note that the inverter cannot save the setting of y99. When power is turned off, the data in y99 is lost (y99 is reset to
"0").
Data for y99
0
1
2
3
Function
Frequency command
Follow H30 and y98 data
Via RS-485 link (JAGUAR Loader)
Follow H30 and y98 data
Via RS-485 link (JAGUAR Loader)
5-149
Run command
Follow H30 and y98 data
Follow H30 and y98 data
Via RS-485 link (JAGUAR Loader)
Via RS-485 link (JAGUAR Loader)
Chapter 6 TROUBLESHOOTING
6.1 Protective Functions
The JAGUAR VXG series of inverters has various protective functions as listed below to prevent the system from going down
and reduce system downtime. The protective functions marked with an asterisk (*) in the table are disabled by default. Enable
them according to your needs.
The protective functions include, for example, the "heavy alarm" detection function which, upon detection of an abnormal state,
displays the alarm code on the LED monitor and causes the inverter to trip, the "light alarm" detection function which displays
the alarm code but lets the inverter continue the current operation, and other warning signal output functions.
If any problem arises, understand the protective functions listed below and follow the procedures given in Sections 6.2 and
onwards for troubleshooting.
Related
function code
"Heavy alarm" detection
This function detects an abnormal state, displays the corresponding alarm code,
and causes the inverter to trip. The "heavy alarm" codes are check-marked in the
"Heavy alarm" object column in Table 6.1. For details of each alarm code, see the
corresponding item in the troubleshooting.
The inverter retains the last four alarm codes and their factors together with their
running information applied when the alarm occurred, so it can display them.
H98
"Light alarm" detection*
This function detects an abnormal state categorized as a "light alarm," displays
ODO and lets the inverter continue the current operation without tripping.
It is possible to define which abnormal states should be categorized as a "light
alarm" using function codes H81 and H82. The "light alarm" codes are
check-marked in the "Light alarm" object column in Table 6.1.
For how to check and release light alarms, see Section 6.5 "If the "Light Alarm"
Indication (ODO) Appears on the LED Monitor."
H81
H82
Stall prevention
When the output current exceeds the current limiter level (F44) during
acceleration/ deceleration or constant speed running, this function decreases the
output frequency to avoid an overcurrent trip.
F44
Overload prevention
control*
Before the inverter trips due to a heat sink overheat (K) or inverter overload
(OX ), this function decreases the output frequency to reduce the load.
H70
Automatic deceleration*
(Anti-regenerative
control)
If regenerative energy returned exceeds the inverter's braking capability, this
function automatically increases the deceleration time or controls the output
frequency to avoid an overvoltage trip.
H69
Deceleration
characteristics*
(Excessive regenerative
energy proof braking
capability)
During deceleration, this function increases the motor energy loss and decreases
the regenerative energy returned to avoid an overvoltage trip (X ).
Chap. 6
Description
Protective function
This function detects a reference frequency loss (due to a broken wire, etc.),
Reference loss detection* continues the inverter operation at the specified frequency, and issues the
"Command loss detected" signal REF OFF.
E65
Automatic lowering of
carrier frequency
Before the inverter trips due to an abnormal surrounding temperature or output
current, this function automatically lowers the carrier frequency to avoid a trip.
H98
Dew condensation
prevention*
Even when the inverter is in stopped state, this function feeds DC current across
the motor at certain intervals to raise the motor temperature for preventing dew
condensation.
J21
Motor overload early
warning*
When the inverter output current has exceeded the specified level, this function
issues the "Motor overload early warning" signal OL before the thermal overload
protection function causes the inverter to trip for motor protection. This function
exclusively applies to the 1st motor.
E34
E35
Auto-reset*
When the inverter has stopped because of a trip, this function allows the inverter
to automatically reset and restart itself. (The number of retries and the latency
between stop and reset can be specified.)
H04
H05
Forced stop*
Upon receipt of the "Force to stop" terminal command STOP, this function
interrupts the run and other commands currently applied in order to forcedly
decelerate the inverter to a stop.
H56
Surge protection
This function protects the inverter from a surge voltage invaded between main
circuit power lines and the ground.
6-1
--
TROUBLESHOOTING
H71
Table 6.1 Abnormal States Detectable ("Heavy Alarm" and "Light Alarm" Objects)
Code
"Heavy alarm" "Light alarm"
objects
objects
Name
Remarks
Ref.
page
30 kW or above
6-10
Instantaneous overcurrent
—
--
HI
Ground fault
—
--
X, X, X
Overvoltage
—
--
6-10
OX
Undervoltage
—
--
6-11
OLQ
Input phase loss
—
--
6-11
SO
Output phase loss
—
--
6-12
K
Heat sink overheat
—
—
6-12
K
External alarm
—
—
6-13
K
Inverter internal overheat
—
—
6-13
K
Motor protection (PTC/NTC thermistor)
—
--
GEK
Braking resistor overheat
—
—
IX
Fuse blown
—
--
SEI
Charger circuit fault
—
--
F, F, F
6-10
6-13
22 kW or below
200 V class series
with 75 kW or above,
400 V class series
with 90 kW or above
200 V class series
with 37 kW or above,
400 V class series
with 75 kW or above
6-14
6-14
6-14
Overload of motor 1 through 4
—
—
6-14
OX
Inverter overload
—
--
6-15
Overspeed
—
--
6-15
SJ
PG wire break
—
--
6-16
HU
Memory error
—
--
6-16
HU
Keypad communications error
—
--
6-16
HU
CPU error
—
--
6-17
HU
Option communications error
—
—
6-17
HU
Option error
—
—
6-17
HU
Operation protection
—
--
6-17
HU
Tuning error
—
--
6-17
HU
HUS
RS-485 communications error (COM port 1)
RS-485 communications error (COM port 2)
—
—
6-18
HUI
Data saving error during undervoltage
—
--
O to O
6-18
200 V class series
with 37 kW or above,
400 V class series
with 45 kW or above
HUK
Hardware error
—
HUH
Speed mismatch or excessive speed deviation
—
—
6-19
QUE
NTC wire break error
—
--
6-20
HUU
Mock alarm
—
--
6-20
FRI
PID feedback wire break
—
—
6-20
GED
Braking transistor broken
—
--
6-20
HUR
Positioning control error
—
--
6-20
HFI
Enable circuit failure
—
--
6-21
ODO
Light alarm
--
--
--
6-19
-200 V class series
with 45 kW or above,
400 V class series
with 75 kW or above
--
—
Motor overload early warning
--
—
--
Heat sink overheat early warning
--
—
--
OLI
Lifetime alarm
--
—
--
UHI
Reference command loss detected
--
—
--
SLG
PID alarm
--
—
--
X7O
Low torque output
--
—
--
S7F
PTC thermistor activated
--
—
--
U7H
Inverter life (Motor cumulative run time)
--
—
--
FQ7
Inverter life (Number of startups)
--
—
--
IDO
DC fan locked
O
K
6-2
--
6.2 Before Proceeding with Troubleshooting
If any of the protective functions has been activated, first remove the cause. Then, after checking that the all run commands
are set to OFF, release the alarm. If the alarm is released while any run commands are set to ON, the inverter may supply the
power to the motor, running the motor.
Injury may occur.
- Even if the inverter has interrupted power to the motor, if the voltage is applied to the main circuit input terminals L1/R,
L2/S and L3/T, voltage may be output to inverter output terminals U, V, and W.
- Turn OFF the power and wait at least five minutes for inverters with a capacity of 22 kW or below, or at least ten
minutes for inverters with a capacity of 30 kW or above. Make sure that the LED monitor and charging lamp are
turned OFF. Further, make sure, using a multimeter or a similar instrument, that the DC link bus voltage between the
terminals P (+) and N (-) has dropped to the safe level (+25 VDC or below).
Electric shock may occur.
Follow the procedure below to solve problems.
Problems with inverter settings
[1] Nothing appears on the LED monitor.
[2] The desired menu is not displayed.
[3] Data of function codes cannot be changed.
z If an alarm code appears on the LED monitor
TROUBLESHOOTING
Abnormal motor operation
Go to Section 6.3.1.
[1] The motor does not rotate.
[2] The motor rotates, but the speed does not increase.
[3] The motor runs in the opposite direction to the command.
[4] Speed fluctuation or current oscillation (e.g., hunting) occurs during
running at constant speed.
[5] Grating sound is heard from the motor or the motor sound fluctuates.
[6] The motor does not accelerate or decelerate within the specified time.
[7] The motor does not restart even after the power recovers from a
momentary power failure.
[8] The motor abnormally heats up.
[9] The motor does not run as expected.
Chap. 6
(1) First, check that the inverter is correctly wired, referring to Chapter 2, Section 2.3.4 "Wiring of main circuit terminals and
grounding terminals."
(2) Check whether an alarm code or the "light alarm" indication (ODO) is displayed on the LED monitor.
z If neither an alarm code nor "light alarm" indication (ODO) appears on the LED monitor
Go to Section 6.3.2.
Go to Section 6.4.
z If the "light alarm" indication (ODO) appears on the LED monitor
Go to Section 6.5.
z If an abnormal pattern appears on the LED monitor
while neither an alarm code nor "light alarm" indication (ODO) is displayed
Go to Section 6.6.
If any problems persist after the above recovery procedure, contact your IMO representative.
Formatted: Bullets and Numbering
6-3
6.26.3 If Neither an Alarm Code Nor "Light Alarm" Indication (ODO) Appears on the LED
Monitor
This section describes the troubleshooting procedure based on function codes dedicated to motor 1 which are marked with an
asterisk (*). For motors 2 to 4, replace those asterisked function codes with respective motor dedicated ones (refer to Chapter 5,
Table 5.5).
For the function codes dedicated to motors 2 to 4, see Chapter 5 "FUNCTION CODES."
6.3.1 Abnormal motor operation
[ 1 ] The motor does not rotate.
Possible Causes
What to Check and Suggested Measures
(1) No power supplied to the
inverter.
Check the input voltage and interphase voltage unbalance.
Î Turn ON a molded case circuit breaker (MCCB), a residual-currentoperated protective device (RCD)/earth leakage circuit breaker (ELCB) (with
overcurrent protection) or a magnetic contactor (MC).
Î Check for voltage drop, phase loss, poor connections, or poor contacts, and fix
them if necessary.
Î If only the auxiliary control power input is supplied, also supply the main power
to the inverter.
(2) No run forward/reverse
command was inputted, or both
the commands were inputted
simultaneously (external signal
operation).
Check the input status of the forward/reverse command with Menu #4 "I/O
Checking" using the keypad.
Î Input a run command.
Î Set either the forward or reverse operation command to off if both commands
are being inputted.
Î Correct the run command source. (Set F02 data to "1.")
Î Correct the assignment of commands FWD and REV with function codes E98
and E99.
Î Connect the external circuit wires to control circuit terminals [FWD] and [REV]
correctly.
Î Make sure that the sink/source slide switch (SW1) on the control printed circuit
board (control PCB) is properly configured.
(3) No Enable input
Check the input status of terminal [EN] with Menu #4 "I/O Checking" using the
keypad.
Î Correct the external circuit wiring to control circuit terminal [EN].
(4) No rotation direction command
(keypad operation).
Check the input status of the forward/reverse rotation direction command with
Menu #4 "I/O Checking" using the keypad.
Î Input the rotation direction (F02 = 0), or select the keypad operation with which
the rotation direction is fixed (F02 = 2 or 3).
(5) The inverter could not accept
any run commands from the
keypad since it was in
Programming mode.
Check which operation mode the inverter is in, using the keypad.
Î Shift the operation mode to Running mode and enter a run command.
(6) A run command with higher
priority than the one attempted
was active, and the run
command was stopped.
Referring to the block diagram of the frequency command block (refer to the
JAGUAR VXG User's Manual, Chapter 6), check the higher priority run command
with Menu #2 "Data Checking" and Menu #4 "I/O Checking" using the keypad.
Î Correct any incorrect function code data settings (in H30, y98, etc.) or cancel the
higher priority run command.
(7) No analog frequency command
input.
Check whether the analog frequency command (reference frequency) is correctly
inputted, using Menu #4 "I/O Checking" on the keypad.
Î Connect the external circuit wires to terminals [13], [12], [11], [C1], and [V2]
correctly.
Î When terminal [C1] is used, check the slider position of terminal [C1] property
switch (SW5) and the setting of the thermistor mode selection (H26).
(8) The reference frequency was
below the starting or stop
frequency.
Check that a reference frequency has been entered correctly, using Menu #4 "I/O
Checking" on the keypad.
Î Set the reference frequency at the same or higher than that of the starting and
stop frequencies (F23* and F25).
Î Reconsider the starting and stop frequencies (F23* and F25), and if necessary,
change them to the lower values.
Î Inspect the external frequency command potentiometers, signal converters,
switches, and relay contacts. Replace any ones that are faulty.
Î Connect the external circuit wires to terminals [13], [12], [11], [C1], and [V2]
correctly.
6-4
Possible Causes
What to Check and Suggested Measures
(9) A frequency command with
higher priority than the one
attempted was active.
Check the higher priority run command with Menu #2 "Data Checking" and Menu
#4 "I/O Checking" using the keypad, referring to the block diagram of the frequency
command block (refer to the JAGUAR VXG User's Manual, Chapter 6).
Î Correct any incorrect function code data (e.g. cancel the higher priority run
command).
(10) The upper and lower
frequencies for the frequency
limiters were set incorrectly.
Check the data of function codes F15 (Frequency limiter (High)) and F16
(Frequency limiter (Low)).
Î Change the settings of F15 and F16 to the correct ones.
(11) The coast-to-stop command
was effective.
Check the data of function codes E01 through E07, E98, and E99 and the input
signal status, using Menu #4 "I/O Checking" on the keypad.
Î Release the coast-to-stop command setting.
(12) Broken wires, incorrect
connection or poor contact with
the motor.
Check the wiring (Measure the output current).
Î Repair the wires to the motor, or replace them.
(13) Overload
Measure the output current.
Î Reduce the load (In winter, the load tends to increase.)
(14) Torque generated by the motor
was insufficient.
Check that the motor starts running if the value of torque boost (F09*) is increased.
Î Increase the value of torque boost (F09*) and try to run the motor.
Î Change the V/f pattern to match the motor's characteristics.
Check that the motor switching signal (selecting motor 1, 2, 3 or 4) is correct and the
data of function codes matches each motor.
Î Correct the motor switching signal.
Î Modify the function code data to match the connected motor.
Check whether the reference frequency is below the slip-compensated frequency of
the motor.
Î Change the reference frequency so that it becomes higher than the
slip-compensated frequency of the motor.
(15) Wrong connection or poor
contact of DC reactor (DCR)
Check the wiring.
Inverters with a capacity of 55 kW in VT mode and inverters with 75 kW or above
require a DCR to be connected. Without a DCR, these inverters cannot run.
Î Connect the DCR correctly. Repair or replace DCR wires.
[ 2 ] The motor rotates, but the speed does not increase.
Possible Causes
What to Check and Suggested Measures
(1) The maximum frequency
currently specified was too low.
Check the data of function code F03* (Maximum frequency).
Î Correct the F03* data.
(2) The data of frequency limiter
(High) currently specified was
too low.
Check the data of function code F15 (Frequency limiter (High)).
Î Correct the F15 data.
(3) The reference frequency
currently specified was too low.
Check that the reference frequency has been entered correctly, using Menu #4 "I/O
Checking" on the keypad.
Î Increase the reference frequency.
Î Inspect the external frequency command potentiometers, signal converters,
switches, and relay contacts. Replace any ones that are faulty.
Î Connect the external circuit wires to terminals [13], [12], [11], [C1], and [V2]
correctly.
(4) A frequency command (e.g.,
multi-frequency or via
communications) with higher
priority than the one attempted
was active and its reference
frequency was too low.
Check the data of the relevant function codes and what frequency commands are
being received, through Menu #1 "Data Setting," Menu #2 "Data Checking" and
Menu #4 "I/O Checking," on the keypad by referring to the block diagram of the
frequency command (refer to the JAGUAR VXG User's Manual, Chapter 6).
Î Correct any incorrect data of function codes (e.g. cancel the higher priority
frequency command).
(5) The acceleration time was too
long or too short.
Check the data of function codes F07, E10, E12, and E14 (Acceleration time).
Î Change the acceleration time to match the load.
6-5
TROUBLESHOOTING
Check the data of function codes F04*, F05*, H50, H51, H52, H53, H65, and H66.
Chap. 6
Check whether any mechanical brake is activated.
Î Release the mechanical brake, if any.
Possible Causes
What to Check and Suggested Measures
(6) Overload.
Measure the output current.
Î Reduce the load.
Check whether any mechanical brake is activated.
Î Release the mechanical brake.
(7) Function code settings do not
agree with the motor
characteristics.
If auto-torque boost or auto-energy saving operation is specified, check whether the
data of P02*, P03*, P06*, P07*, and P08* agree with the parameters of the motor.
Î Perform auto-tuning of the inverter for the motor to be used.
(8) The output frequency does not
increase due to the current
limiter operation.
Make sure that F43 (Current limiter (Mode selection)) is set to "2" and check the
data of F44 (Current limiter (Level)).
Î Correct the F44 data. Or, if the current limiter operation is not needed, set F43 to
"0" (disabled).
Decrease the value of torque boost (F09*), then run the motor again and check if the
speed increases.
Î Adjust the value of the torque boost (F09*).
Check the data of function codes F04*, F05*, H50, H51, H52, H53, H65, and H66 to
ensure that the V/f pattern setting is right.
Î Match the V/f pattern setting with the motor ratings.
(9) The output frequency does not
Check whether data of torque limiter related function codes (F40, F41, E16 and
increase due to the torque limiter E17) is correctly configured and the "Select torque limiter level" terminal command
operation.
TL2/TL1 is correct.
Î Correct data of F40, F41, E16 and E17 or reset them to the factory defaults
(disable).
Î Set the TL2/TL1 correctly.
(10) Bias and gain incorrectly
specified.
Check the data of function codes F18, C50, C32, C34, C37, C39, C42, and C44.
Î Readjust the bias and gain to appropriate values.
[ 3 ] The motor runs in the opposite direction to the command.
Possible Causes
What to Check and Suggested Measures
(1) Wiring to the motor is
incorrect.
Check the wiring to the motor.
Î Connect terminals U, V, and W of the inverter to the U, V, and W terminals of the
motor, respectively.
(2) Incorrect connection and
settings for run commands and
rotation direction commands
FWD and REV.
Check the data of function codes E98 and E99 and the connection to terminals
[FWD] and [REV].
Î Correct the data of the function codes and the connection.
(3) A run command (with fixed
rotational direction) from the
keypad is active, but the
rotational direction setting is
incorrect.
Check the data of function code F02 (Run command).
Î Change the data of function code F02 to "2:
/
or "3:
/
keys on keypad (reverse)."
(4) The rotation direction
specification of the motor is
opposite to that of the inverter.
The rotation direction of IEC-compliant motors is opposite to that of incompliant
motors.
Î Switch the FWD/REV signal setting.
keys on keypad (forward)"
[ 4 ] Speed fluctuation or current oscillation (e.g., hunting) occurs during running at constant speed.
Possible Causes
What to Check and Suggested Measures
(1) The frequency command
fluctuates.
Check the signals for the frequency command with Menu #4 "I/O Checking" using
the keypad.
Î Increase the filter constants (C33, C38, and C43) for the frequency command.
(2) An external potentiometer is
used for frequency setting.
Check that there is no noise in the control signal wires from external sources.
Î Isolate the control signal wires from the main circuit wires as far as possible.
Î Use shielded or twisted wires for control signals.
Check whether the external frequency command potentiometer is malfunctioning
due to noise from the inverter.
Î Connect a capacitor to the output terminal of the potentiometer or set a ferrite
core on the signal wire. (Refer to Chapter 2.)
(3) Frequency switching or
multi-frequency command was
enabled.
Check whether the relay signal for switching the frequency command is chattering.
Î If the relay contact is defective, replace the relay.
6-6
Possible Causes
What to Check and Suggested Measures
(4) The wiring length between the
inverter and the motor is too
long.
Check whether auto-torque boost, auto-energy saving operation, or dynamic torque
vector control is enabled.
Î Perform auto-tuning of the inverter for every motor to be used.
Î Disable the automatic control systems by setting F37* to "1" (Constant torque
load) and F42* to "0" (V/f control with slip compensation active), then check
that the motor vibration stops.
Î Make the output wires as short as possible.
(5) The machinery is hunting due
to vibration caused by low
rigidity of the load. Or the
current is irregularly oscillating
due to special motor
parameters.
Once disable all the automatic control systems such as auto torque boost, auto
energy saving operation, overload prevention control, current limiter, torque limiter,
automatic deceleration (anti-regenerative control), auto search for idling motor
speed, slip compensation, dynamic torque vector control, droop control, overload
stop function, speed control, online tuning, notch filter, observer, and then check that
the motor vibration comes to a stop.
Î Disable the functions causing the vibration.
Î Readjust the output current fluctuation damping gain (H80*).
Î Readjust the speed control systems. (d01* through d06*)
Chap. 6
Check that the motor vibration is suppressed if you decrease the level of F26 (Motor
sound (Carrier frequency)) or set F27 (Motor sound (Tone)) to "0."
Î Decrease the carrier frequency (F26) or set the tone to "0" (F27 = 0).
[ 5 ] Grating sound is heard from the motor or the motor sound fluctuates.
What to Check and Suggested Measures
(1) The specified carrier frequency
is too low.
Check the data of function codes F26 (Motor sound (Carrier frequency)) and F27
(Motor sound (Tone)).
Î Increase the carrier frequency (F26).
Î Change the setting of F27 to appropriate value.
(2) The surrounding temperature
of the inverter was too high
(when automatic lowering of
the carrier frequency was
enabled by H98).
Measure the temperature inside the panel where the inverter is mounted.
Î If it is over 40qC, lower it by improving the ventilation.
Î Lower the temperature of the inverter by reducing the load. (For fans or pumps,
decrease the frequency limiter value (F15).)
(3) Resonance with the load.
Check the machinery mounting accuracy or check whether there is resonance with
the mounting base.
Î Disconnect the motor from the machinery and run it alone, then find where the
resonance comes from. Upon locating the cause, improve the characteristics of
the source of the resonance.
Î Adjust the settings of C01 (Jump frequency 1) to C04 (Jump frequency
(Hysteresis width)) so as to avoid continuous running in the frequency range
causing resonance.
Î Enable the speed control (notch filter) (d07*, d08*) and the observer (d18 to
d20) to suppress vibration. (Depending on the characteristics of the load, this
may take no effect.)
Note: If you disable H98, an K, K, orOXalarmmayoccur.
[ 6 ] The motor does not accelerate or decelerate within the specified time.
Possible Causes
What to Check and Suggested Measures
(1) The inverter runs the motor
with S-curve or curvilinear
pattern.
Check the data of function code H07 (Acceleration/deceleration pattern).
Î Select the linear pattern (H07 = 0).
Î Shorten the acceleration/deceleration time (F07, F08, E10 through E15).
(2) The current limiting operation
prevented the output frequency
from increasing (during
acceleration).
Make sure that F43 (Current limiter (Mode selection)) is set to "2: Enable during
acceleration and at constant speed," then check that the setting of F44 (Current
limiter (Level)) is reasonable.
Î Readjust the setting of F44 to appropriate value, or disable the function of
current limiter with F43.
Î Increase the acceleration/deceleration time (F07, F08, E10 through E15).
(3) The automatic deceleration
(Anti-regenerative control) is
enabled during deceleration.
Check the data of function code H69 (Automatic deceleration (Mode selection)).
Î Increase the deceleration time (F08, E11, E13, and E15).
(4) Overload.
Measure the output current.
Î Reduce the load (For fans or pumps, decrease the frequency limiter value
(F15).) (In winter, the load tends to increase.)
6-7
TROUBLESHOOTING
Possible Causes
Possible Causes
What to Check and Suggested Measures
(5) Torque generated by the motor
was insufficient.
Check that the motor starts running if the value of the torque boost (F09*) is
increased.
Î Increase the value of the torque boost (F09*).
(6) An external potentiometer is
used for frequency setting.
Check that there is no noise in the control signal wires from external sources.
Î Isolate the control signal wires from the main circuit wires as far as possible.
Î Use shielded or twisted wires for control signals.
Î Connect a capacitor to the output terminal of the external frequency command
potentiometer or set a ferrite core on the signal wire. (Refer to Chapter 2.)
(7) The output frequency is limited
by the torque limiter.
Check whether data of torque limiter related function codes (F40, F41, E16 and
E17) is correctly configured and the TL2/TL1 terminal command ("Select torque
limiter level 2/1") is correct.
Î Correct the data of F40, F41, E16 and E17 or reset them to the factory defaults.
Î Set the TL2/TL1 correctly.
Î Increase the acceleration/deceleration time (F07, F08, E10 through E15).
(8) The specified acceleration or
deceleration time was
incorrect.
Check the terminal commands RT1 and RT2 for acceleration/deceleration times.
Î Correct the RT1 and RT2 settings.
[ 7 ] The motor does not restart even after the power recovers from a momentary power failure.
Possible Causes
What to Check and Suggested Measures
(1) The data of function code F14
is either "0," "1," or "2."
Check if an undervoltage trip (OX) occurs.
Î Change the data of function code F14 (Restart mode after momentary power
failure (Mode selection)) to "3," "4," or "5."
(2) The run command remains
OFF even after the power has
been restored.
Check the input signal with Menu #4 "I/O Checking" using the keypad.
Î Check the power recovery sequence with an external circuit. If necessary,
consider the use of a relay that can keep the run command ON.
In 3-wire operation, the power to the control printed circuit board (control PCB) has
been shut down once because of a long momentary power failure time, or the
"Enable 3-wire operation" signal HOLD has been turned OFF once.
Î Change the design or the setting so that a run command can be issued again
within 2 seconds after the power has been restored.
[ 8 ] The motor abnormally heats up.
Possible Causes
What to Check and Suggested Measures
(1) Excessive torque boost
specified.
Check whether decreasing the torque boost (F09*) decreases the output current but
does not stall the motor.
Î If no stall occurs, decrease the torque boost (F09*).
(2) Continuous running in
extremely slow speed.
Check the running speed of the inverter.
Î Change the speed setting or replace the motor with a motor exclusively designed
for inverters.
(3) Overload.
Measure the inverter output current.
Î Reduce the load (For fans or pumps, decrease the frequency limiter value
(F15).) (In winter, the load tends to increase.)
[ 9 ] The motor does not run as expected.
Possible Causes
What to Check and Suggested Measures
(1) Incorrect setting of function
code data.
Check that function codes are correctly configured and no unnecessary
configuration has been done.
Î Configure all the function codes correctly.
Make a note of function code data currently configured and then initialize all
function code data using H03.
Î After the above process, reconfigure function codes one by one, checking the
running status of the motor.
6-8
6.3.2 Problems with inverter settings
[ 1 ] Nothing appears on the LED monitor.
Possible Causes
What to Check and Suggested Measures
(1) No power (neither main power
nor auxiliary control power)
supplied to the inverter.
Check the input voltage and interphase voltage unbalance.
Î Turn ON a molded case circuit breaker (MCCB), a residual-currentoperated protective device (RCD)/earth leakage circuit breaker (ELCB) (with
overcurrent protection) or a magnetic contactor (MC).
Î Check for voltage drop, phase loss, poor connections, or poor contacts and fix
them if necessary.
(2) The power for the control PCB
did not reach a sufficiently high
level.
Check if the jumper bar has been removed between terminals P1 and P(+) or if there
is a poor contact between the jumper bar and those terminals.
Î Mount a jumper bar or a DC reactor between terminals P1 and
P(+). For poor contact, tighten up the screws.
(3) The keypad was not properly
connected to the inverter.
Check whether the keypad is properly connected to the inverter.
Î Remove the keypad, put it back, and see whether the problem recurs.
Î Replace the keypad with another one and check whether the problem recurs.
Possible Causes
Check and Measures
(1) The menu display mode is not
selected appropriately.
Check the data of function code E52 (Keypad (Menu display mode)).
Î Change the E52 data so that the desired menu appears.
[ 3 ] Data of function codes cannot be changed.
Possible Causes
What to Check and Suggested Measures
(1) An attempt was made to change
function code data that cannot
be changed when the inverter is
running.
Check if the inverter is running with Menu #3 "Drive Monitoring" using the keypad
and then confirm whether the data of the function codes can be changed when the
motor is running by referring to the function code tables.
Î Stop the motor then change the data of the function codes.
(2) The data of the function codes
is protected.
Check the data of function code F00 (Data Protection).
Î Change the F00 data from "Enable data protection" (1 or 3) to "Disable data
protection" (0 or 2).
(3) The WE-KP terminal
command ("Enable data change
with keypad") is not entered,
though it has been assigned to a
digital input terminal.
Check the data of function codes E01 through E07, E98 and E99 and the input signal
status with Menu #4 "I/O Checking" using the keypad.
Î Input a WE-KP command through a digital input terminal.
(4) The
Check whether you have pressed the
key after changing the function code data.
Î Press the
key after changing the function code data.
Î Check that VDXH is displayed on the LED monitor.
key was not pressed.
(5) The data of function codes F02,
E01 through E07, E98, and E99
cannot be changed.
Either one of the FWD and REV terminal commands is turned ON.
Î Turn OFF both FWD and REV.
(6) The function code(s) to be
changed does not appear.
If Menu #0 "Quick Setup" (R)QF) is selected, only the particular function codes
appear.
Î With Menu #0 "Quick Setup" ()QF) being selected, press the
key to call up
the desired menu from )BB to \BB. Then select the desired function code
and change its data. For details, refer to Chapter 3, Table 3.4 "Menus Available
in Programming Mode."
TROUBLESHOOTING
[ 2 ] The desired menu is not displayed.
Chap. 6
When running the inverter remotely, ensure that the extension cable is securely
connected both to the keypad and to the inverter.
Î Disconnect the cable, reconnect it, and see whether the problem recurs.
Î Replace the keypad with another one and check whether the problem per recurs.
Formatted: Bullets and Numbering
6-9
6.36.4
If an Alarm Code Appears on the LED Monitor
[ 1 ] FQ Instantaneous overcurrent
Problem
The inverter momentary output current exceeded the overcurrent level.
F Overcurrent occurred during acceleration.
F Overcurrent occurred during deceleration.
F Overcurrent occurred during running at a constant speed.
Possible Causes
What to Check and Suggested Measures
(1) The inverter output lines were
short-circuited.
Disconnect the wiring from the inverter output terminals ([U], [V] and [W]) and
measure the interphase resistance of the motor wiring. Check if the resistance is too
low.
Î Remove the short-circuited part (including replacement of the wires, relay
terminals and motor).
(2) Ground faults have occurred at
the inverter output lines.
Disconnect the wiring from the output terminals ([U], [V] and [W]) and perform a
Megger test.
Î Remove the grounded parts (including replacement of the wires, relay terminals
and motor).
(3) Overload.
Measure the motor current with a measuring device to trace the current trend. Then,
use this data to judge if the trend is over the calculated load value for your system
design.
ÎIf the load is too heavy, reduce it or increase the inverter capacity.
Trace the current trend and check if there are any sudden changes in the current.
Î If there are any sudden changes, make the load fluctuation smaller or increase
the inverter capacity.
Î Enable instantaneous overcurrent limiting (H12 = 1).
(4) Excessive torque boost
specified.
(when F37* = 0, 1, 3, or 4)
Check whether decreasing the torque boost (F09*) decreases the output current but
does not stall the motor.
Î If no stall occurs, decrease the torque boost (F09*).
(5) The acceleration/ deceleration
time was too short.
Check that the motor generates enough torque required during
acceleration/deceleration. That torque is calculated from the moment of inertia for
the load and the acceleration/deceleration time.
Î Increase the acceleration/deceleration time (F07, F08, E10 through E15, and
H56).
Î Enable the current limiter (F43) and torque limiter (F40, F41, E16, and E17).
Î Increase the inverter capacity.
(6) Malfunction caused by noise.
Check if noise control measures are appropriate (e.g., correct grounding and routing
of control and main circuit wires).
Î Implement noise control measures. For details, refer to the JAGUAR VXG
User's Manual, "Appendix A."
Î Enable the Auto-reset (H04).
Î Connect a surge absorber to magnetic contactor's coils or other solenoids (if
any) causing noise.
[ 2 ] HI Ground fault
Problem
A ground fault current flew from the output terminal of the inverter.
Possible Causes
What to Check and Suggested Measures
(1) Inverter output terminal(s)
grounded (ground fault).
Disconnect the wiring from the output terminals ([U], [V], and [W]) and perform a
Megger test.
Î Remove the grounded parts (including replacement of the wires, relay terminals
and motor).
[ 3 ] XQ Overvoltage
Problem
The DC link bus voltage was over the detection level of overvoltage.
X Overvoltage occurred during acceleration.
X Overvoltage occurred during deceleration.
X Overvoltage occurred during running at constant speed.
Possible Causes
What to Check and Suggested Measures
(1) The power supply voltage
exceeded the inverter's
specification range.
Measure the input voltage.
Î Decrease the voltage to within the specified range.
6-10
In the same power line, if a phase-advancing capacitor is turned ON/OFF or a
thyristor converter is activated, a surge (momentary large increase in the voltage or
current) may be caused in the input power.
Î Install a DC reactor.
(3) The deceleration time was too
short for the moment of inertia
for load.
Recalculate the deceleration torque based on the moment of inertia for the load and
the deceleration time.
Î Increase the deceleration time (F08, E11, E13, E15, and H56).
Î Enable the automatic deceleration (anti-regenerative control) (H69), or
deceleration characteristics (H71).
Î Enable torque limiter (F40, F41, E16, E17, and H73).
Î Set the rated voltage (at base frequency) (F05*) to "0" to improve the braking
capability.
Î Consider the use of a braking resistor.
(4) The acceleration time was too
short.
Check if the overvoltage alarm occurs after rapid acceleration.
Î Increase the acceleration time (F07, E10, E12, and E14).
Î Select the S-curve pattern (H07).
Î Consider the use of a braking resistor.
(5) Braking load was too heavy.
Compare the braking torque of the load with that of the inverter.
Î Set the rated voltage (at base frequency) (F05*) to "0" to improve the braking
capability.
Î Consider the use of a braking resistor.
(6) Malfunction caused by noise.
Check if the DC link bus voltage was below the protective level when the
overvoltage alarm occurred.
Î Implement noise control measures. For details, refer to the JAGUAR VXG
User's Manual, "Appendix A."
Î Enable the auto-reset (H04).
Î Connect a surge absorber to magnetic contactor's coils or other solenoids (if
any) causing noise.
[ 4 ] OX Undervoltage
Problem
DC link bus voltage has dropped below the undervoltage detection level.
Possible Causes
What to Check and Suggested Measures
(1) A momentary power failure
occurred.
Î Release the alarm.
Î If you want to restart running the motor without treating this condition as an
alarm, set F14 to "3," "4," or "5," depending on the load type.
(2) The power to the inverter was
switched back to ON too soon
(when F14 = 1).
Check if the power to the inverter was switched back to ON while the control power
was still alive. (Check whether the LEDs on the keypad light.)
Î Turn the power ON again after all LEDs on the keypad go off.
(3) The power supply voltage did
not reach the inverter's
specification range.
Measure the input voltage.
Î Increase the voltage to within the specified range.
(4) Peripheral equipment for the
power circuit malfunctioned, or
the connection was incorrect.
Measure the input voltage to find which peripheral equipment malfunctioned or
which connection is incorrect.
Î Replace any faulty peripheral equipment, or correct any incorrect connections.
(5) Any other loads connected to
the same power supply has
required a large starting
current, causing a temporary
voltage drop.
Measure the input voltage and check the voltage fluctuation.
Î Reconsider the power supply system configuration.
(6) Inverter's inrush current caused
the power voltage drop because
the power supply transformer
capacity was insufficient.
Check if the alarm occurs when a molded case circuit breaker (MCCB),
residual-current-operated protective device (RCD)/earth leakage circuit breaker
(ELCB) (with overcurrent protection) or magnetic contactor (MC) is turned ON.
ÎReconsider the capacity of the power supply transformer.
[ 5 ] OLQ Input phase loss
Problem
Input phase loss occurred, or interphase voltage unbalance rate was large.
Possible Causes
What to Check and Suggested Measures
(1) Breaks in wiring to the main
power input terminals.
Measure the input voltage.
Î Repair or replace the main circuit power input wires or input devices (MCCB,
MC, etc.).
6-11
TROUBLESHOOTING
What to Check and Suggested Measures
(2) A surge current entered the
input power supply.
Chap. 6
Possible Causes
Possible Causes
What to Check and Suggested Measures
(2) The screws on the main power
input terminals are loosely
tightened.
Check if the screws on the main power input terminals have become loose.
Î Tighten the terminal screws to the recommended torque.
(3) Interphase voltage unbalance
between three phases was too
large.
Measure the input voltage.
Î Connect an AC reactor (ACR) to lower the voltage unbalance between input
phases.
Î Increase the inverter capacity.
(4) Overload cyclically occurred.
Measure the ripple wave of the DC link bus voltage.
Î If the ripple is large, increase the inverter capacity.
(5) Single-phase voltage was input
to the three-phase input
inverter.
Check the inverter type.
Î Apply three-phase power. The JAGUAR VXG of three-phase input cannot be
driven by single-phase power.
The input phase loss protection can be disabled with the function code H98 (Protection/Maintenance Function).
[ 6 ] SO Output phase loss
Problem
Output phase loss occurred.
Possible Causes
What to Check and Suggested Measures
(1) Inverter output wires are
broken.
Measure the output current.
Î Replace the output wires.
(2) The motor winding is broken.
Measure the output current.
Î Replace the motor.
(3) The terminal screws for
inverter output were not tight
enough.
Check if any screws on the inverter output terminals have become loose.
Î Tighten the terminal screws to the recommended torque.
(4) A single-phase motor has been
connected.
Î Single-phase motors cannot be used. Note that the JAGUAR VXG only drives
three-phase induction motors.
[ 7 ] K Heat sink overheat
Problem
Temperature around heat sink has risen abnormally.
Possible Causes
What to Check and Suggested Measures
(1) Temperature around the
inverter exceeded the inverter's
specification range.
Measure the temperature around the inverter.
Î Lower the temperature around the inverter (e.g., ventilate the panel where the
inverter is mounted).
(2) Ventilation path is blocked.
Check if there is sufficient clearance around the inverter.
Î Change the mounting place to ensure the clearance.
Check if the heat sink is not clogged.
Î Clean the heat sink.
(3) Cooling fan's airflow volume
decreased due to the service life
expired or failure.
Check the cumulative run time of the cooling fan. Refer to Chapter 3, Section 3.4.6
"Reading maintenance information – Menu #5 "Maintenance Information"."
Î Replace the cooling fan.
Visually check whether the cooling fan rotates normally.
Î Replace the cooling fan.
Three-phase 200 V class series inverters with 37 kW or above and three-phase 400 V
class series with 75 kW or above are equipped with not only a cooling fan for heat
sink but also an internal air circulation fan. Check the following.
Î Check the connection of the fan power switching connectors "CN R" and
"CN W."
Î Correct the connection. (Refer to "h Switching connectors" in Chapter 2,
Section 2.3.4 "Wiring of main circuit terminals and grounding terminals".
(4) Overload.
Measure the output current.
Î Reduce the load (e.g. Use the heat sink overheat early warning (E01 through
E07) or the overload early warning (E34) and reduce the load before the
overload protection is activated.).
Î Decease the motor sound (carrier frequency) (F26).
Î Enable the overload prevention control (H70).
6-12
[ 8 ] K External alarm
Problem
External alarm was inputted (THR).
(when the "Enable external alarm trip" THR has been assigned to any of digital input terminals)
Possible Causes
What to Check and Suggested Measures
(1) An alarm function of external
equipment was activated.
Check the operation of external equipment.
Î Remove the cause of the alarm that occurred.
(2) Wrong connection or poor
contact in external alarm signal
wiring.
Check if the external alarm signal wiring is correctly connected to the terminal to
which the "Enable external alarm trip" terminal command THR has been assigned
(Any of E01 through E07, E98, and E99 should be set to "9.").
Î Connect the external alarm signal wire correctly.
(3) Incorrect setting of function
code data.
Check whether the "Enable external alarm trip" terminal command THR has been
assigned to an unavailable terminal (with E01 through E07, E98, or E99).
Î Correct the assignment.
Check whether the normal/negative logic of the external signal matches that of the
THR command specified by any of E01 through E07, E98, and E99.
Î Ensure the matching of the normal/negative logic.
Problem
Temperature inside the inverter has exceeded the allowable limit.
What to Check and Suggested Measures
Measure the surrounding temperature.
Î Lower the temperature around the inverter (e.g., ventilate the panel where the
inverter is mounted).
[ 10 ] K Motor protection (PTC/NTC thermistor)
Problem
Temperature of the motor has risen abnormally.
Possible Causes
What to Check and Suggested Measures
(1) The temperature around the
motor exceeded the motor's
specification range.
Measure the temperature around the motor.
Î Lower the temperature.
(2) Cooling system for the motor
defective.
Check if the cooling system of the motor is operating normally.
Î Repair or replace the cooling system of the motor.
(3) Overload.
Measure the output current.
Î Reduce the load (e.g. Use the heat sink overheat early warning (E01 through
E07) or the overload early warning (E34) and reduce the load before the
overload protection is activated.). (In winter, the load tends to increase.)
Î Lower the temperature around the motor.
Î Increase the motor sound (Carrier frequency) (F26).
(4) The activation level (H27) of
the PTC thermistor for motor
overheat protection was set
inadequately.
Check the PTC thermistor specifications and recalculate the detection voltage.
Î Modify the data of function code H27.
(5) Settings for the PTC/NTC
thermistor are improper.
Check the setting of the thermistor mode selection (H26) and the slider position of
terminal [C1] property switch SW5.
Î Change the H26 data in accordance with the thermistor used and set the SW5 to
the PTC/NTC position.
(6) Excessive torque boost
specified. (F09*)
Check whether decreasing the torque boost (F09*) does not stall the motor.
Î If no stall occurs, decrease the F09* data.
(7) The V/f pattern did not match
the motor.
Check if the base frequency (F04*) and the rated voltage at base frequency (F05*)
match the values on the motor's nameplate.
Î Match the function code data with the values on the motor's nameplate.
(8) Incorrect setting of function
code data.
Although no PTC/NTC thermistor is used, the thermistor mode is enabled (H26).
Î Set the H26 data to "0" (Disable).
6-13
TROUBLESHOOTING
Possible Causes
(1) The surrounding temperature
exceeded the inverter's
specification limit.
Chap. 6
[ 9 ] K Inverter internal overheat
[ 11 ] GEK Braking resistor overheated
Problem
The electronic thermal protection for the braking resistor has been activated.
Possible Causes
What to Check and Suggested Measures
(1) Braking load is too heavy.
Reconsider the relationship between the braking load estimated and the real load.
Î Lower the real braking load.
Î Review the selection of the braking resistor and increase the braking capability
(Modification of related function code data (F50, F51, and F52) is also
required.)
(2) Specified deceleration time is
too short.
Recalculate the deceleration torque and time needed for the load currently applied,
based on a moment of inertia for the load and the deceleration time.
Î Increase the deceleration time (F08, E11, E13, E15, and H56).
Î Review the selection of the braking resistor and increase the braking capability.
(Modification of related function code data (F50, F51, and F52) is also
required.)
(3) Incorrect setting of function
code data F50, F51, and F52.
Recheck the specifications of the braking resistor.
Î Review data of function codes F50, F51, and F52, then modify them.
Note: The inverter issues an overheat alarm of the braking resistor by monitoring the magnitude of the braking load, not by
measuring its surface temperature.
When the braking resistor is frequently used so as to exceed the settings made by function codes F50, F51, and F52, therefore,
the inverter issues an overheat alarm even if the surface temperature of the braking resistor does not rise. To squeeze out full
performance of the braking resistor, configure function codes F50, F51, and F52 while actually measuring the surface
temperature of the braking resistor.
[ 12 ] IXV Fuse blown
Problem
The fuse inside the inverter blew.
Possible Causes
What to Check and Suggested Measures
(1) The fuse blew due to
short-circuiting inside the
inverter.
Check whether there has been any excess surge or noise coming from outside.
Î Take measures against surges and noise.
Î Have the inverter repaired.
[ 13 ] SEI Charger circuit fault
Problem
The magnetic contactor for short-circuiting the charging resistor failed to work.
Possible Causes
What to Check and Suggested Measures
(1) The control power was not
supplied to the magnetic
contactor intended for
short-circuiting the charging
resistor.
Check that, in normal connection of the main circuit (not a connection via the DC
link bus), the connector (CN R) on the power printed circuit board (power PCB) is
not inserted to NC .
Î Insert the connector (CN R) to FAN .
Check whether you quickly turned the circuit breaker ON and OFF to confirm safety
after cabling/wiring.
Î Wait until the DC link bus voltage has dropped to a sufficiently low level and
then release the current alarm. After that, turn ON the power again. (Do not turn
the circuit breaker ON and OFF quickly.)
(Turning ON the circuit breaker supplies power to the control circuit to the
operation level (lighting the LEDs on the keypad) in a short period. Immediately
turning it OFF even retains the control circuit power for a time, while it shuts
down the power to the magnetic contactor intended for short-circuiting the
charging resistor since the contactor is directly powered from the main power.
Under such conditions, the control circuit can issue a turn-on command to the
magnetic contactor, but the contactor not powered can produce nothing. This
state is regarded as abnormal, causing an alarm.)
[ 14 ] OQ Overload of motor 1 through 4
Problem
Electronic thermal protection for motor 1, 2, 3, or 4 activated.
O Motor 1 overload
O Motor 2 overload
O Motor 3 overload
O Motor 4 overload
Possible Causes
What to Check and Suggested Measures
(1) The electronic thermal
characteristics do not match the
motor overload characteristics.
Check the motor characteristics.
Î Reconsider the data of function codes (P99*, F10* and F12*).
Î Use an external thermal relay.
6-14
Possible Causes
What to Check and Suggested Measures
(2) Activation level for the
electronic thermal protection
was inadequate.
Check the continuous allowable current of the motor.
Î Reconsider and change the data of function code F11*.
(3) The specified acceleration/
deceleration time was too short.
Recalculate the acceleration/deceleration torque and time needed for the load, based
on the moment of inertia for the load and the acceleration/deceleration time.
Î Increase the acceleration/ deceleration time (F07, F08, E10 through E15, and
H56).
(4) Overload.
Measure the output current.
Î Reduce the load (e.g. Use the overload early warning (E34) and reduce the load
before the overload protection is activated.). (In winter, the load tends to
increase.)
(5) Excessive torque boost
specified (F09*)
Check whether decreasing the torque boost (F09*) does not stall the motor.
Î If no stall occurs, decrease the F09* data.
[ 15 ] OX Inverter overload
Problem
Temperature inside inverter has risen abnormally.
Measure the temperature around the inverter.
Î Lower the temperature (e.g., ventilate the panel where the inverter is mounted).
(2) Excessive torque boost
specified (F09*)
Check whether decreasing the torque boost (F09*) does not stall the motor.
Î If no stall occurs, decrease the F09* data.
(3) The specified acceleration/
deceleration time was too short.
Recalculate the acceleration/deceleration torque and time needed for the load, based
on the moment of inertia for the load and the acceleration/deceleration time.
Î Increase the acceleration/deceleration time (F07, F08, E10 through E15, and
H56).
(4) Overload.
Measure the output current.
Î Reduce the load (e.g., Use the overload early warning (E34) and reduce the load
before the overload protection is activated.). (In winter, the load tends to
increase.).
Î Decrease the motor sound (Carrier frequency) (F26).
Î Enable overload prevention control (H70).
(5) Ventilation paths are blocked.
Check if there is sufficient clearance around the inverter.
Î Change the mounting place to ensure the clearance.
Check if the heat sink is not clogged.
Î Clean the heat sink.
(6) Cooling fan's airflow volume
decreased due to the service life
expired or failure.
Check the cumulative run time of the cooling fan. Refer to Chapter 3, Section 3.4.6
"Reading maintenance information – Menu #5 "Maintenance Information"."
Î Replace the cooling fan.
Visually check that the cooling fan rotates normally.
Î Replace the cooling fan.
(7) The wires to the motor are too
long, causing a large leakage
current from them.
Measure the leakage current.
Î Insert an output circuit filter (OFL).
[ 16 ] Overspeed
Problem
The motor rotates in an excessive speed (Motor speed t (F03 data) u (d32 data, d33 data) u 1.2)
Possible Causes
What to Check and Suggested Measures
(1) Incorrect setting of function
code data.
Check the motor parameter "Number of poles" (P01*).
Î Specify the P01* data in accordance with the motor to be used.
Check the maximum frequency setting (F03*).
Î Specify the F03* data in accordance with the output frequency.
Check the setting of speed limit function (d32 and d33).
Î Disable the speed limit function (d32 and d33).
(2) Insufficient gain of the speed
controller.
Check whether the actual speed overshoots the commanded one in higher speed
operation.
Î Increase the speed controller gain (d03*.)
(Depending on the situations, reconsider the setting of the filter constant or the
integral time.)
6-15
TROUBLESHOOTING
What to Check and Suggested Measures
(1) Temperature around the
inverter exceeded the inverter's
specification range.
Chap. 6
Possible Causes
Possible Causes
What to Check and Suggested Measures
(3) Noises superimposed on the
PG wire.
Check whether appropriate noise control measures have been implemented (e.g.,
correct grounding and routing of signal wires and main circuit wires).
Î Implement noise control measures. For details, refer to the JAGUAR VXG
User's Manual, "Appendix A."
[ 17 ] SJ PG wire break
Problem
The pulse generator (PG) wire has been broken somewhere in the circuit.
Possible Causes
What to Check and Suggested Measures
(1) The wire between the pulse
generator (PG) and the option
card has been broken.
Check whether the pulse generator (PG) is correctly connected to the option card or
any wire is broken.
Î Check whether the PG is connected correctly. Or, tighten up the related terminal
screws.
Î Check whether any joint or connecting part bites the wire sheath.
Î Replace the wire.
(2) PG related circuit affected by
strong electrical noise.
Check if appropriate noise control measures have been implemented (e.g., correct
grounding and routing of signal wires, communication cables, and main circuit
wires).
Î Implement noise control measures.
Î Separate the signal wires from the main power wires as far as possible.
[ 18 ] HU Memory error
Problem
Error occurred in writing the data to the memory in the inverter.
Possible Causes
What to Check and Suggested Measures
(1) When writing data (especially
initializing or copying data),
the inverter was shut down so
that the voltage to the control
PCB has dropped.
Initialize the function code data with H03 (= 1). After initialization, check if
pressing the
key releases the alarm.
Î Revert the initialized function code data to their previous settings, then restart
the operation.
(2) Inverter affected by strong
electrical noise when writing
data (especially initializing or
copying data).
Check if appropriate noise control measures have been implemented (e.g., correct
grounding and routing of control and main circuit wires). Also, perform the same
check as described in (1) above.
Î Implement noise control measures. Revert the initialized function code data to
their previous settings, then restart the operation.
(3) The control PCB failed.
Initialize the function code data by setting H03 to "1," then reset the alarm by
pressing the
key and check that the alarm goes on.
Î The control PCB (on which the CPU is mounted) is defective. Contact your
IMO representative.
[ 19 ] HU Keypad communications error
Problem
A communications error occurred between the remote keypad or the multi-function keypad and the inverter.
Possible Causes
What to Check and Suggested Measures
(1) Broken communications cable
or poor contact.
Check continuity of the cable, contacts and connections.
Î Re-insert the connector firmly.
Î Replace the cable.
(2) Connecting many control wires
hinders the front cover from
being mounted, lifting the
keypad.
Check the mounting condition of the front cover.
Î Use wires of the recommended size (0.65 to 0.82 mm2) for wiring.
Î Change the wiring layout inside the unit so that the front cover can be mounted
firmly.
(3) Inverter affected by strong
electrical noise.
Check if appropriate noise control measures have been implemented (e.g., correct
grounding and routing of communication cables and main circuit wires).
Î Implement noise control measures.
For details, refer to the JAGUAR VXG User's Manual, "Appendix A."
(4) A keypad failure occurred.
Replace the keypad with another one and check whether a keypad communications
error (HU ) occurs.
Î Replace the keypad.
6-16
[ 20 ] HU CPU error
Problem
A CPU error (e.g. erratic CPU operation) occurred.
Possible Causes
What to Check and Suggested Measures
(1) Inverter affected by strong
electrical noise.
Check if appropriate noise control measures have been implemented (e.g. correct
grounding and routing of signal wires, communications cables, and main circuit
wires).
Î Implement noise control measures.
[ 21 ] HU Option communications error
Problem
A communications error occurred between the option card and the inverter.
What to Check and Suggested Measures
(1) There was a problem with the
connection between the option
card and the inverter.
Check whether the connector on the option card is properly engaged with that of the
inverter.
Î Reload the option card into the inverter.
(2) Strong electrical noise.
Check whether appropriate noise control measures have been implemented (e.g.
correct grounding and routing of signal wires, communications cables, and main
circuit wires).
Î Implement noise control measures.
[ 22 ] HU Option error
[ 23 ] HU Operation protection
Problem
An incorrect operation was attempted.
Possible Causes
What to Check and Suggested Measures
(1) The
key was pressed when
H96 = 1 or 3.
Check that the
key was pressed when a run command had been entered from the
input terminal or through the communications port.
Î If this was not intended, check the setting of H96.
(2) The start check function was
activated when H96 = 2 or 3.
Check that any of the following operations has been performed with a run command
being entered.
- Turning the power ON
- Releasing the alarm
- Switching the enable communications link LE operation
Î Review the running sequence to avoid input of a Run command when this error
occurs.
If this was not intended, check the setting of H96.
(Turn the run command OFF before releasing the alarm.)
(3) The forced stop digital input
STOP was turned OFF.
Check that turning the STOP OFF decelerated the inverter to stop.
Î If this was not intended, check the settings of E01 through E07 for terminals
[X1] through [X7].
[ 24 ] HU Tuning error
Problem
Auto-tuning failed.
Possible Causes
What to Check and Suggested Measures
(1) A phase was missing (There
was a phase loss) in the
connection between the
inverter and the motor.
Î Properly connect the motor to the inverter.
(2) V/f or the rated current of the
motor was not properly set.
Check whether the data of function codes (F04*, F05*, H50 through H53, H65,
H66, P02*, and P03*) matches the motor specifications.
(3) The wiring length between the
inverter and the motor was too
long.
Check whether the wiring length between the inverter and the motor exceeds 50 m.
(Small capacity inverters are greatly affected by the wiring length.)
Î Review, and if necessary, change the layout of the inverter and the motor to
shorten the connection wire. Alternatively, minimize the wiring length without
changing the layout.
Î Disable both auto-tuning and auto-torque boost (set data of F37* to "1").
6-17
TROUBLESHOOTING
An error detected by the option card. Refer to the instruction manual of the option card for details.
Chap. 6
Possible Causes
Possible Causes
What to Check and Suggested Measures
(4) The rated capacity of the motor
was significantly different from
that of the inverter.
Check whether the rated capacity of the motor is three or more ranks lower, or two or
more ranks higher than that of the inverter.
Î Replace the inverter with one with an appropriate capacity.
Î Manually specify the values for the motor parameters P06*, P07*, and P08*.
Î Disable both auto-tuning and auto-torque boost (set data of F37* to "1").
(5) The motor was a special type
such as a high-speed motor.
Î Disable both auto-tuning and auto-torque boost (set data of F37* to "1").
(6) A tuning operation involving
motor rotation (P04* = 2 or 3)
was attempted while the brake
was applied to the motor.
Î Specify the tuning that does not involve the motor rotation (P04* = 1).
Î Release the brake before tuning that involves the motor rotation (P04* = 2 or 3).
For details of tuning errors, refer to Chapter 4, Section 4.1.7 "Function code basic settings and tuning < 2 >, „ Tuning
errors."
Preparation before running the motor for a test – Setting function code data."
[ 25 ] HU RS-485 communications error (COM port 1)
HUS RS-485 communications error (COM port 2)
Problem
A communications error occurred during RS-485 communications.
Possible Causes
What to Check and Suggested Measures
(1) Communications conditions of
the inverter do not match that
of the host equipment.
Compare the settings of the y codes (y01 to y10, y11 to y20) with those of the host
equipment.
Î Correct any settings that differ.
(2) Even though no-response error
detection time (y08, y18) has
been set, communications is
not performed within the
specified cycle.
Check the host equipment.
Î Change the settings of host equipment software or disable the no-response error
detection (y08, y18 = 0).
(3) The host equipment did not
operate due to defective
software, settings, or defective
hardware.
Check the host equipment (e.g., PLCs and personal computers).
Î Remove the cause of the equipment error.
(4) The RS-485 converter did not
operate due to incorrect
connections and settings, or
defective hardware.
Check the RS-485 converter (e.g., check for poor contact).
Î Change the various RS-485 converter settings, reconnect the wires, or replace
hardware with recommended devices as appropriate.
(5) Broken communications cable
or poor contact.
Check the continuity of the cables, contacts and connections.
Î Replace the cable.
(6) Inverter affected by strong
electrical noise.
Check if appropriate noise control measures have been implemented (e.g., correct
grounding and routing of communications cables and main circuit wires).
Î Implement noise control measures.
Î Implement noise reduction measures on the host side.
Î Replace the RS-485 converter with a recommended insulated one.
(7) Terminating resistor not
properly configured.
Check that the inverter serves as a terminating device in the network.
Î Configure the terminating resistor switch(es) (SW2/SW3) for RS-485
communication correctly. (That is, turn the switch(es) to ON.)
[ 26 ] HUI Data saving error during undervoltage
Problem
The inverter failed to save data such as the frequency commands and PID commands (which are specified through
the keypad), or the output frequencies modified by the UP/DOWN terminal commands when the power was turned
OFF.
Possible Causes
What to Check and Suggested Measures
(1) During data saving performed
when the power was turned
OFF, the voltage fed to the
control PCB dropped in an
abnormally short period due to
the rapid discharge of the DC
link bus.
Check how long it takes for the DC link bus voltage to drop to the preset voltage
when the power is turned OFF.
Î Remove whatever is causing the rapid discharge of the DC link bus voltage.
After pressing the
key and releasing the alarm, return the data of the relevant
function codes (such as the frequency commands and PID commands (specified
through the keypad) or the output frequencies modified by the UP/DOWN
terminal commands) back to the original values and then restart the operation.
6-18
Possible Causes
What to Check and Suggested Measures
(2) Inverter operation affected by
strong electrical noise when the
power was turned OFF.
Check if appropriate noise control measures have been implemented (e.g., correct
grounding and routing of control and main circuit wires).
key and releasing the
Î Implement noise control measures. After pressing the
alarm, return the data of the relevant function codes (such as the frequency
commands and PID commands (specified through the keypad) or the output
frequencies modified by the UP/DOWN terminal commands) back to the
original values and then restart the operation.
(3) The control circuit failed.
Check if HUI occurs each time the power is turned ON.
Î The control PCB (on which the CPU is mounted) is defective. Contact your
IMO representative.
[ 27 ] HUK Hardware error
Problem
The LSI on the power printed circuit board malfunctions.
It is necessary to set the inverter capacity correctly.
Î Contact your IMO representative.
(2) Data stored in the power
printed circuit board memory is
corrupted.
It is necessary to replace the power printed circuit board.
Î Contact your IMO representative.
(3) The control printed circuit
board is misconnected to the
power printed circuit board.
It is necessary to replace the power or control printed circuit board.
Î Contact your IMO representative.
[ 28 ] HUH Speed mismatch or excessive speed deviation
Problem
An excessive deviation appears between the speed command and the detected speed.
Possible Causes
What to Check and Suggested Measures
(1) Incorrect setting of function
code data.
Check the following function code data; P01* (Motor (No. of poles)), d15
(Feedback encoder pulse count/rev), and d16 and d17 (Feedback pulse correction
factor 1 and 2).
Î Specify data of function codes P01*, d15, d16, and d17 in accordance with the
motor and PG.
(2) Overload.
Measure the inverter output current.
Î Reduce the load.
Check whether any mechanical brake is working.
Î Release the mechanical brake.
(3) The motor speed does not rise
due to the current limiter
operation.
Check the data of function code F44 (Current limiter (Level)).
Î Change the F44 data correctly. Or, set the F43 data to "0" (Disable) if the current
limiter operation is not needed.
Check the data of function codes F04*, F05*, and P01* through P12* to ensure that
the V/f pattern setting is right.
Î Match the V/f pattern setting with the motor ratings.
Î Change the function code data in accordance with the motor parameters.
(4) Function code settings do not
match the motor
characteristics.
Check whether the data of P01*, P02*, P03*, P06*, P07*, P08*, P09*, P10* and
P12* match the parameters of the motor.
Î Perform auto-tuning of the inverter, using the function code P04*.
(5) Wrong wiring between the
pulse generator (PG) and the
inverter.
Check the wiring between the PG and the inverter.
Î Correct the wiring.
(6) Wiring to the motor is
incorrect.
Check the wiring to the motor.
Î Connect the inverter output terminals U, V, and W to the motor input terminals
U, V, and W, respectively.
Check that the relationships between the PG feedback signal and the run command
are as follows:
x For the FWD command: the B phase pulse is in the High level at rising edge of the
A phase pulse
x For the REV command: the B phase pulse is in the Low level at rising edge of the
A phase pulse
Î If the relationship is wrong, interchange the A and B phase wires.
6-19
TROUBLESHOOTING
What to Check and Suggested Measures
(1) The inverter capacity setting on
the control printed circuit board
is wrong.
Chap. 6
Possible Causes
Possible Causes
What to Check and Suggested Measures
(7) The motor speed does not rise
due to the torque limiter
operation.
Check the data of F40 (Torque limiter 1-1).
Î Correct the F40 data. Or, set the F40 data to "999" (Disable) if the torque limiter
operation is not needed.
[ 29 ] QUE NTC wire break error
Problem
A wire break is found in the NTC thermistor detection circuit.
Possible Causes
What to Check and Suggested Measures
(1) The NTC thermistor cable is
broken.
Check whether the motor cable is broken.
Î Replace the motor cable.
(2) The temperature around the
motor is extremely low (lower
than -30qC).
Measure the temperature around the motor.
Î Reconsider the use environment of the motor.
(3) The NTC thermistor is broken.
Measure the resistance of the NTC thermistor.
Î Replace the motor.
[ 30 ] HUU Mock alarm
Problem
The LED displays the alarm HUU.
Possible Causes
What to Check and Suggested Measures
(1) The
+
keys were held
down for more than 5 seconds.
Î To escape from this alarm state, press the
key.
[ 31 ] FRI PID feedback wire break
Problem
The PID feedback wire is broken.
Possible Causes
What to Check and Suggested Measures
(1) The PID feedback signal wire
is broken.
Check whether the PID feedback signal wires are connected correctly.
Î Check whether the PID feedback signal wires are connected correctly. Or,
tighten up the related terminal screws.
Î Check whether any contact part bites the wire sheath.
(2) PID feedback related circuit
affected by strong electrical
noise.
Check if appropriate noise control measures have been implemented (e.g., correct
grounding and routing of signal wires, communication cables, and main circuit
wires).
Î Implement noise control measures.
Î Separate the signal wires from the main power wires as far as possible.
[ 32 ] GED Braking transistor error
Problem
A braking transistor error is detected.
Possible Causes
What to Check and Suggested Measures
(1) The braking transistor is
broken.
Check whether resistance of the braking resistor is correct or there is a
misconnection of the resistor.
Î Consult your IMO representative for repair.
[ 33 ] HUR Positioning control error
Problem
An excessive positioning deviation has occurred when the servo-lock function was activated.
Possible Causes
What to Check and Suggested Measures
(1) Insufficient gain in positioning
control system
Readjust the settings of J97 (Servo-lock (Gain)) and d03 (Speed control 1 P (Gain)).
(2) Incorrect control completion
width
Check whether the setting of J99 (Servo-lock (Completion width)) is correct.
Î Correct the setting of J99.
6-20
[ 34 ] HFI Enable circuit failure
Problem
The circuit that detects the status of the enable circuit (safety stop circuit) is broken.
Possible Causes
What to Check and Suggested Measures
(1) Circuit related to the Enable
circuit affected by strong
electrical noise.
Check if appropriate noise control measures have been implemented (e.g., correct
grounding and routing of signal wires, communication cables, and main circuit
wires).
Î Implement noise control measures.
Î Separate the signal wires from the main power wires as far as possible.
The "Reset alarm" terminal command RST cannot reset this alarm HFI. If even a power-off reset cannot restore the
inverter state, the inverter needs to be repaired.
6.5 If the "Light Alarm" Indication (ODO) Appears on the LED Monitor
Function codes H81 and H82 specify which alarms should be categorized as "light alarm." The available "light alarm" codes are
check-marked in the "Light alarm" object column in Table 6.1.
„ Displaying the light alarm factor
key to enter Programming mode.
1) Press the
2) Check the light alarm factor in B (Light alarm factor (latest)) under Menu #5 "Maintenance Information" in
Programming mode. The light alarm factor is displayed in alarm codes. For details about the alarm codes, see Table 6.1
"Abnormal States Detectable ("Heavy alarm" and "Light alarm" objects)."
For details about the menu transition in Menu #5 "Maintenance Information", see Chapter 3, Section 3.4.6 "Reading
maintenance information – Menu #5 "Maintenance Information." It is possible to display the factors of most recent 3
light alarms in B (Light alarm factor (last)) to B (Light alarm factor (3rd last)).
„ Switching the LED monitor from the light alarm to normal display
If it is necessary to return the LED monitor to the normal display state (showing the running status such as reference frequency)
before the light alarm factor is removed (e.g., when it takes a long time to remove the light alarm factor), follow the steps below.
1) Press the
key to return the LED monitor to the light alarm indication (ODO).
2) With ODO being displayed, press the
key. The LED monitor returns to the normal display state while the KEYPAD
CONTROL LED continues blinking.
„ Releasing the light alarm
1) Remove the light alarm factor that has been checked in B (Light alarm factor (latest)) under Menu #5 "Maintenance
Information" in Programming mode, in accordance with the troubleshooting procedure. The reference page for the
troubleshooting corresponding to each light alarm factor is shown in "Ref. page" column in Table 6.1.
2) Once the light alarm factor is removed, the "light alarm" indication ODO on the LED monitor disappears and the KEYPAD
CONTROL LED stops blinking. If the KEYPAD CONTROL LED continues blinking, it means that any light alarm factor
has not completely been removed and the inverter is still in the light alarm status. Proceed to other troubleshooting
procedures.
When all of the light alarm factors have been removed, the digital output L-ALM is also turned OFF automatically.
6-21
TROUBLESHOOTING
To display the "light alarm" factor and escape from the light alarm state, follow the instructions below.
Chap. 6
If the inverter detects a minor abnormal state "light alarm", it can continue the current operation without tripping while
displaying the "light alarm" indication ODO on the LED monitor. In addition to the indication ODO, the inverter blinks the
KEYPAD CONTROL LED and outputs the "light alarm" signal L-ALM to a digital output terminal to alert the peripheral
equipment to the occurrence of a light alarm. (To use the L-ALM, it is necessary to assign the signal to any of the digital output
terminals by setting any of function codes E20 through E24 and E27 to "98.")
6.6 If an Abnormal Pattern Appears on the LED Monitor while Neither an Alarm Code nor "Light
Alarm" Indication (ODO) is Displayed
[ 1 ] – – – – (center bar) appears
Problem
A center bar (– – – –) appeared on the LED monitor.
Possible Causes
What to Check and Suggested Measures
(1) When PID control had been
disabled (J01 = 0), you changed
E43 (LED Monitor (Item
selection)) to 10 or 12.
With the PID being enabled
(J01 = 1, 2, or 3), you disabled
PID control (J01 = 0) when the
LED monitor had been set to
display the PID command or
PID feedback amount by
pressing the
key.
Make sure that when you wish to view other monitor items, E43 is not set to "10:
PID command" or "12: PID feedback amount."
Î Set E43 to a value other than "10" or "12."
(2) The keypad was poorly
connected.
Prior to proceed, check that pressing the
key does not change the display on the
LED monitor.
Check continuity of the extension cable for the keypad used in remote operation.
Î Replace the cable.
Make sure that when you wish to view a PID command or a PID feedback amount,
J01 (PID control) is not set to "0: Disable."
Î Set J01 to "1: Enable (Process control normal operation)," "2: Enable (Process
control inverse operation)," or "3: Enable (Dancer control)."
[ 2 ] _ _ _ _ (under bar) appears
Problem
key or entered a run forward command FWD or a run reverse command REV, the
Although you pressed the
motor did not start and an under bar ( _ _ _ _ ) appeared on the LED monitor.
Possible Causes
What to Check and Suggested Measures
(1) The voltage of the DC link bus
was low.
Select B under Menu #5 "Maintenance Information" in Programming mode on
the keypad, then check the voltage of the DC link bus which should be: 200 VDC or
below for three-phase 200 V class series, and 400 VDC or below for three-phase 400
V class series.
Î Connect the inverter to a power supply that meets its input specifications.
(2) The main power is not ON,
while the auxiliary input power
to the control circuit is
supplied.
Check whether the main power is turned ON.
Î Turn the main power ON.
(3) Although power is supplied not
via the commercial power line
but via the DC link bus, the
main power down detection is
enabled (H72 = 1).
Check the connection to the main power and check if the H72 data is set to "1"
(factory default).
Î Correct the H72 data.
[3]
appears
Problem
Parentheses (
) appeared on the LED monitor during speed monitoring on the keypad.
Possible Causes
What to Check and Suggested Measures
(1) The display data overflows the
LED monitor.
Check whether the product of the output frequency and the display coefficient (E50)
exceeds 99999.
Î Correct the E50 data.
6-22
Chapter 7 MAINTENANCE AND INSPECTION
Perform daily and periodic inspections to avoid trouble and keep reliable operation of the inverter for a long time. When
performing inspections, follow the instructions given in this chapter.
• Before proceeding to the maintenance/inspection jobs, turn OFF the power and wait at least five minutes for
inverters with a capacity of 22 kW or below, or at least ten minutes for inverters with a capacity of 30 kW or
above. Make sure that the LED monitor and charging lamp are turned OFF. Further, make sure, using a multimeter or a
similar instrument, that the DC link bus voltage between the terminals P(+) and N(-) has dropped to the safe level (+25
VDC or below).
Electric shock may occur.
•
•
•
•
Maintenance, inspection, and parts replacement should be made only by authorized persons.
Take off the watch, rings and other metallic objects before starting work.
Use insulated tools.
Never modify the inverter.
Electric shock or injuries could occur.
7.1 Daily Inspection
Visually inspect the inverter for operation errors from the outside without removing the covers when the inverter is ON or
operating.
7.2 Periodic Inspection
Perform periodic inspections according to the items listed in Table 7.1. Before performing periodic inspections, be sure to stop
the motor and remove the front cover with the inverter power OFF.
Table 7.1 List of Periodic Inspections
Check part
Environment
Input voltage
Keypad
Check item
How to inspect
Evaluation criteria
1) Check the surrounding temperature,
humidity, vibration and atmosphere
(dust, gas, oil mist, or water drops).
2) Check that tools or other foreign
materials or dangerous objects are not
left around the equipment.
1) Check visually or
measure using apparatus.
1) The standard
specifications must be
satisfied.
2) No foreign or
dangerous objects are
left.
Check that the input voltages of the main
and control circuit are correct.
Measure the input voltages
The standard specifications
using a multimeter or the like. must be satisfied.
1), 2)
Visual inspection
1), 2)
The display can be read
and there is no fault.
1) Visual or auditory
inspection
2) Retighten.
3), 4), 5)
Visual inspection
1), 2), 3), 4), 5)
No abnormalities
1) Check that bolts and screws are tight
and not missing.
2) Check the devices and insulators for
deformation, cracks, breakage and
discoloration caused by overheat or
deterioration.
3) Check for contamination or
accumulation of dust or dirt.
1) Retighten.
1), 2), 3)
No abnormalities
1) Check conductors for discoloration and
distortion caused by overheat.
2) Check the sheath of the wires for cracks
and discoloration.
1), 2)
Visual inspection
1) Check that the display is clear.
2) Check that there is no missing part in
the displayed characters.
Structure such as Check for:
frame and cover 1) Abnormal noise or excessive vibration
2) Loose bolts (at clamp sections).
3) Deformation and breakage
4) Discoloration caused by overheat
5) Contamination and accumulation of
dust or dirt
Main circuit
Common
Conductors
and wires
2) Visual inspection
2), 3)
Visual inspection
7-1
1), 2)
No abnormalities
MAINTENANCE AND INSPECTION
Check that the expected performance (satisfying the standard specification) is obtained.
Check that the surrounding environment satisfies the requirements given in Chapter 2, Section 2.1 "Operating Environment."
Check that the LED monitor on the keypad displays normally.
Check for abnormal noise, odor, or excessive vibration.
Check for traces of overheat, discoloration and other defects.
Chap. 7
-
Table 7.1 List of Periodic Inspections (Continued)
Check part
Terminal
blocks
Main circuit
Braking
resistor
DC link bus
capacitor
Check item
How to inspect
Check that the terminal blocks are not
damaged.
Visual inspection
Control circuit
No abnormalities
1) Check for abnormal odor or cracks in
insulators caused by overheat.
2) Check for wire breakage.
1) Olfactory and visual
inspection
2) Check the wires visually,
or disconnect either wire
and measure the
conductivity with a
multimeter.
1) No abnormalities
1) Check for electrolyte leakage,
discoloration, cracks and swelling of
the casing.
2) Check that the safety valve does not
protrude remarkably.
3) Measure the capacitance if necessary.
1), 2)
Visual inspection
3) Measure the discharge
time with capacitance
probe.
1), 2)
No abnormalities
3) The discharge time
should not be shorter
than the one specified
by the replacement
manual.
Transformer Check for abnormal roaring noise and odor. Auditory, visual, and
olfactory inspection
and reactor
Cooling system
Evaluation criteria
2) Within ±10% of the
resistance of the
braking resistor
No abnormalities
Magnetic
contactor
and relay
1) Check for chatters during operation.
2) Check that contact surface is not rough.
1) Auditory inspection
2) Visual inspection
1), 2)
No abnormalities
Printed
circuit
board
1) Check for loose screws and connectors.
2) Check for odor and discoloration.
3) Check for cracks, breakage,
deformation and remarkable rust.
4) Check the capacitors for electrolyte
leaks and deformation.
1) Retighten.
2) Olfactory and visual
inspection
3), 4)
Visual inspection
1), 2), 3), 4)
No abnormalities
Cooling fan
1) Check for abnormal noise and
excessive vibration.
2) Check for loose bolts.
3) Check for discoloration caused by
overheat.
1) Auditory and visual
inspection, or turn
manually (be sure to turn
the power OFF).
2) Retighten.
3) Visual inspection
1) Smooth rotation
2), 3)
No abnormalities
Ventilation
path
Check the heat sink, intake and exhaust
ports for clogging and foreign materials.
Visual inspection
No abnormalities
Remove dust accumulating on the inverter with a vacuum cleaner. If the inverter is stained, wipe it off with a chemically neutral
cloth.
7.3 List of Periodic Replacement Parts
Each part of the inverter has its own service life that will vary according to the environmental and operating conditions. It is
recommended that the following parts be replaced at the specified intervals.
When the replacement is necessary, consult your IMO representative.
Table 7.2 Replacement Parts
Part name
DC link bus capacitor
Standard replacement intervals (See Note below.)
10 years
Electrolytic capacitors on printed circuit boards
10 years
Cooling fans
10 years
Fuse
10 years (90 kW or above)
(Note) These replacement intervals are based on the inverter's service life estimated at a surrounding temperature of 40qC at
100% (CT-mode inverters) or 80% (MT/VT-mode inverters) of full load. In environments with a surrounding
temperature above 40qC or a large amount of dust or dirt, the replacement intervals may be shorter.
Standard replacement intervals mentioned above are only a guide for replacement, not a guaranteed service life.
7-2
7.3.1 Judgment on service life
The inverter has the life prediction function for some parts which measures the discharging time or counts the voltage applied
time, etc. The function allows you to monitor the current lifetime state on the LED monitor and judge whether those parts are
approaching the end of their service life.
The life prediction function can also issue early warning signals if the life time alarm command LIFE is assigned to any of the
digital output terminals. (Refer to "[ 3 ] Early warning of lifetime alarm" later in this section.)
Table 7.3 lists the parts whose service life can be predicted and details the life prediction function. The predicted values should
be used only as a guide since the actual service life is influenced by the surrounding temperature and other usage environments.
Table 7.3 Life Prediction
Object of life
prediction
DC link bus
capacitor
Prediction function
Measurement of discharging time
Measures the discharging time of
the DC link bus capacitor when
the main power is shut down and
calculates the capacitance.
End-of-life criteria
Prediction timing On the LED monitor
85% or lower of the initial
B
At periodic
capacitance at shipment
(Capacitance)
inspection
(See "[ 1 ] Measuring the
(H98: Bit 3 = 0)
capacitance of DC link bus
capacitor in comparison with
initial one at shipment" on page
7-4.)
During ordinary B
operation
(Elapsed time)
Electrolytic
capacitors on
printed circuit
boards
Counts the time elapsed when the Exceeding 87,600 hours
voltage is applied to the
(10 years)
capacitors, while correcting it
according to the surrounding
temperature.
During ordinary B
(Cumulative run time)
operation
Cooling fans
Counts the run time of the cooling Exceeding 87,600 hours
fans.
(10 years)
During ordinary B
operation
(Cumulative run time)
B
(Time remaining
before the end of life)
„ Notes for the judgment on the service life of the DC link bus capacitor
The service life of the DC link bus capacitor can be judged by the "measurement of discharging time" (c to f) or "ON-time
counting" (g).
c The discharging time of the DC link bus capacitor depends largely on the inverter's internal load conditions, e.g. options
attached or ON/OFF of digital I/O signals. If actual load conditions are so different from the ones at which the
initial/reference capacitance is measured that the measurement result falls out of the accuracy level required, then the
inverter does not perform measuring.
The
capacitance measuring conditions at shipment are extremely restricted--e.g., with the remote keypad mounted and all
d
input terminals being OFF--in order to stabilize the load and measure the capacitance accurately. Those conditions are,
therefore, different from the actual operating conditions in almost all cases. If the actual operating conditions are the same
as those at shipment, shutting down the inverter power automatically measures the discharging time; however, if they are
different, no automatic measurement is performed. To perform it, put those conditions back to the factory default ones and
shut down the inverter. For the measuring procedure, see [ 1 ] given on the next page.
e To measure the capacitance of the DC link bus capacitor under ordinary operating conditions when the power is turned
OFF, it is necessary to set up the load conditions for ordinary operation and measure the reference capacitance (initial
setting) when the inverter is introduced. For the reference capacitance setup procedure, see [ 2 ] given on page 7-5.
Performing the setup procedure automatically detects and saves the measuring conditions of the DC link bus capacitor.
Setting bit 3 of H98 data to 0 restores the inverter to the measurement in comparison with the initial capacitance measured
at shipment.
f If the multi-function keypad is mounted, the inverter does not measure the discharging time automatically since the
inverter's conditions are different from the ones applied at shipment. It is, therefore, necessary to perform the setup
procedure mentioned in e above to enable the measurement under ordinary operating conditions.
To make an accurate judgment on the service life of the DC ink bus capacitor (accurate measurement of the capacitance),
select the judgment procedure according to the keypad type and the measuring conditions, following the flowchart given on
the next page.
7-3
MAINTENANCE AND INSPECTION
Exceeding 87,600 hours
ON-time counting
Counts the time elapsed when the (10 years)
voltage is applied to the DC link
bus capacitor, while correcting it
according to the capacitance
measured above.
Chap. 7
85% or lower of the reference During ordinary B
capacitance under ordinary
operation
(Capacitance)
operating conditions at the user (H98: Bit 3 = 1)
site
(See "[ 2 ] Measuring the
capacitance of DC link bus
capacitor under ordinary
operating conditions" on page
7-5.)
Selection of life judgment
threshold of DC link bus capacitor
What keypad type is
mounted on the inverter?
(See f.)
Remote keypad
Modify the measuring
conditions applied at
shipment?
Multi-function keypad
YES
(Setting up the load
conditions in ordinary
operation. See e.)
NO
(Measuring under the
conditions applied at
shipment. See d.)
Measurement under
ordinary operating
conditions when the power
is turned OFF (See [2].)
Comparison with the initial
capacitance at shipment
(See [1].)
g In a machine system where the inverter main power is rarely shut down, the inverter does not measure the discharging time.
For such an inverter, the ON-time counting is provided. The ON-time counting result can be represented as "elapsed
time"(B ) and "time remaining before the end of life" (B ) as shown in Table 7.3, "On the LED monitor."
When the inverter uses an auxiliary control power input, the load conditions widely differ so that the discharging time
cannot be accurately measured. To prevent unintended measuring, the discharging time measurement can be disabled
with the function code H98 (Bit 4 = 0).
[ 1 ] Measuring the capacitance of DC link bus capacitor in comparison with initial one at shipment
When bit 3 of H98 data is 0, the measuring procedure given below measures the capacitance of DC link bus capacitor in
comparison with initial one at shipment when the power is turned OFF. The measuring result can be displayed on the keypad as
a ratio (%) to the initial capacitance.
-------------------------------------------------- Capacitance measuring procedure ------------------------------------------------------1) To ensure validity in the comparative measurement, put the condition of the inverter back to the state at factory shipment.
x Remove the option card (if already in use) from the inverter.
x In case another inverter is connected via the DC link bus to the P(+) and N(-) terminals of the main circuit, disconnect the
wires. (You do not need to disconnect a DC reactor (optional), if any.)
x Disconnect power wires for the auxiliary input to the control circuit (R0, T0).
x Mount the remote keypad on the inverter.
x Turn OFF all the digital input signals fed to terminals [FWD], [REV], and [X1] through [X7] of the control circuit.
x If an external frequency command potentiometer is connected to terminal [13], disconnect it.
x If an external apparatus is attached to terminal [PLC], disconnect it.
x Ensure that transistor output signals ([Y1] to [Y4]) and relay output signals ([Y5A] - [Y5C], and [30A/B/C]) will not be
turned ON.
x Disable the RS-485 communications link.
It is recommended that terminal [EN] be short-circuited for the measurement of the capacitance.
If negative logic is specified for the transistor output and relay output signals, they are considered ON when the
inverter is not running. Specify positive logic for them.
x Keep the surrounding temperature within 25 r10qC.
2)
3)
4)
5)
Turn ON the main circuit power.
Confirm that the cooling fan is rotating and the inverter is in stopped state.
Turn OFF the main circuit power.
The inverter automatically starts the measurement of the capacitance of the DC link bus capacitor. Make sure that " . . . . "
appears on the LED monitor.
If " . . . . " does not appear on the LED monitor, the measurement has not started. Check the conditions listed in 1).
6) After " . . . . " has disappeared from the LED monitor, turn ON the main circuit power again.
7) Select Menu #5 "Maintenance Information" in Programming mode and note the reading (relative capacitance (%) of the DC
link bus capacitor).
-------------------------------------------------------------------------------------------------------------------------------------------------------
7-4
[ 2 ] Measuring the capacitance of the DC link bus capacitor under ordinary operating conditions
When bit 3 of H98 data is 1, the inverter automatically measures the capacitance of the DC link bus capacitor under ordinary
operating conditions when the power is turned OFF. This measurement requires setting up the load conditions for ordinary
operation and measuring the reference capacitance when the inverter is introduced to the practical operation, using the setup
procedure given below.
------------------------------------------------ Reference capacitance setup procedure ---------------------------------------------------1) Set function code H98 (Protection/maintenance function) to enable the user to specify the judgment criteria for the service
life of the DC link bus capacitor (Bit 3 = 1) (refer to function code H98).
2) Turn OFF all run commands.
3) Make the inverter ready to be turned OFF under ordinary operating conditions.
4) Set both function codes H42 (Capacitance of DC link bus capacitor) and H47 (Initial capacitance of DC link bus capacitor)
to "0000."
5) Turn OFF the inverter, and the following operations are automatically performed.
The inverter measures the discharging time of the DC link bus capacitor and saves the result in function code H47 (Initial
capacitance of DC link bus capacitor).
The conditions under which the measurement has been conducted will be automatically collected and saved.
During the measurement, " . . . . " will appear on the LED monitor.
6) Turn ON the inverter again.
Confirm that H42 (Capacitance of DC link bus capacitor) and H47 (Initial capacitance of DC link bus capacitor) hold right
values. Shift to Menu #5 "Maintenance Information" and confirm that the relative capacitance (ratio to full capacitance) is
100%.
The condition given above produces a rather large measurement error. If this mode gives you a lifetime alarm, set H98
(Maintenance operation) back to the default setting (Bit 3 (Select life judgment threshold of DC link bus capacitor) =
0) and conduct the measurement under the condition at the time of factory shipment.
[ 3 ] Early warning of lifetime alarm
For the components listed in Table 7.3, the inverter can issue an early warning of lifetime alarm LIFE at one of the transistor
output terminals ([Y1] to [Y4]) and the relay contact terminals ([Y5A] - [Y5C], and [30A/B/C]) as soon as any of the levels
specified in Table 7.3 has been exceeded.
The early warning signal is also turned ON when a lock condition on the internal air circulation DC fan (provided on 200 V
class series inverters with a capacity of 45 kW or above; on 400 V class series inverters with a capacity of 75 kW or above) has
been detected.
7.4 Measurement of Electrical Amounts in Main Circuit
Because the voltage and current of the power supply (input, primary circuit) of the main circuit of the inverter and those of the
motor (output, secondary circuit) contain harmonic components, the readings may vary with the type of the meter. Use meters
indicated in Table 7.4 when measuring with meters for commercial frequencies.
The power factor cannot be measured by a commercially available power-factor meter that measures the phase difference
between the voltage and current. To obtain the power factor, measure the power, voltage and current on each of the input and
output sides and use the following formula.
„ Three-phase input
Power factor =
Electric power (W)
× 100 %
3 × Voltage (V) × Current (A)
7-5
MAINTENANCE AND INSPECTION
Hereafter, each time the inverter is turned OFF, it automatically measures the discharging time of the DC link bus capacitor if
the above conditions are met. Periodically check the relative capacitance of the DC link bus capacitor (%) with Menu #5
"Maintenance Information" in Programming mode.
Chap. 7
If the measurement has failed, "0001" is entered into both H42 and H47. Remove the factor of the failure and
conduct the measurement again.
-------------------------------------------------------------------------------------------------------------------------------------------------------
Symbol Type of Name Waveform
of meter meter of meter
Item
Table 7.4 Meters for Measurement of Main Circuit
Input (primary) side
Voltage
DC link bus
voltage
(P(+)-N(-))
Output (secondary) side
Current
Voltage
Current
Ammeter
AR, AS, AT
Voltmeter
VR, VS, VT
Wattmeter
WR, WT
Ammeter
AU, AV, AW
Voltmeter
VU, VV, VW
Wattmeter
WU, WW
DC voltmeter V
Moving iron
type
Rectifier or
moving iron
type
Digital
AC power
meter
Digital AC
power meter
Digital AC
power meter
Digital AC
power meter
Moving coil
type




It is not recommended that meters other than a digital AC power meter be used for measuring the output voltage or
output current since they may cause larger measurement errors or, in the worst case, they may be damaged.
Figure 7.1 Connection of Meters
7.5 Insulation Test
Since the inverter has undergone an insulation test before shipment, avoid making a Megger test at the customer's site.
If a Megger test is unavoidable for the main circuit, observe the following instructions; otherwise, the inverter may be damaged.
A withstand voltage test may also damage the inverter if the test procedure is wrong. When the withstand voltage test is
necessary, consult your IMO representative.
(1) Megger test of main circuit
1) Use a 500 VDC Megger and shut off the main power supply without fail before measurement.
2) If the test voltage leaks to the control circuit due to the wiring, disconnect all the wiring from the control circuit.
3) Connect the main circuit terminals with a common line as shown in Figure 7.2.
4) The Megger test must be limited to across the common line of the main circuit and the ground ( ).
5) Value of 5 M: or more displayed on the Megger indicates a correct state. (The value is measured on an inverter alone.)
Figure 7.2 Main Circuit Terminal Connection for Megger Test
(2) Insulation test of control circuit
Do not make a Megger test or withstand voltage test for the control circuit. Use a high resistance range tester for the control
circuit.
1) Disconnect all the external wiring from the control circuit terminals.
2) Perform a continuity test to the ground. One M: or a larger measurement indicates a correct state.
(3) Insulation test of external main circuit and sequence control circuit
Disconnect all the wiring connected to the inverter so that the test voltage is not applied to the inverter.
7-6
7.6 IMO Inverter warranty statement.
7.6.1 Terms of IMO 5 year warranty.
x
x
x
x
x
IMO Jaguar Inverters are covered by a 5 year warranty from date of despatch.
In the event of failure due to faulty components or inferior workmanship, the Inverter will be replaced or repaired free
of charge at IMO’s discretion.
Warranty replacements and repaired units will be despatched free of charge, all costs related to faulty units being
returned to IMO for inspection/repair are the responsibility of the sender.
In circumstances where it is viable for the Inverter to be repaired in situ due to size (>30kw), an Engineer from IMO
or contracted to represent IMO can be supplied. Site visits are chargeable at IMO’s current service rate, any warranty
parts will be replaced free of charge.
All Inverters require a Returns Authorisation reference to be supplied with the Inverter upon returning the drive to
IMO, this reference can be obtained from our website www.imopconline.com by registering and following the returns
instructions.
x
7.6.2 Warranty restrictions.
Incorrect, or unsafe installation.
Poor condition due to abuse, neglect or improper maintenance.
Modifications, repairs performed by anyone other than IMO or without prior written agreement.
Inverter used in incorrect application or used for function other than for which it is designed.
Any alterations, which may invalidate the Inverters CE declaration.
Non IMO options or ancillary devices used.
x
Regardless whether a breakdown occurs during or after the warranty period, IMO shall not be liable for any loss of
opportunity, loss of profits, penalty clauses or damages arising from any special circumstances, secondary damages,
accident compensation to another company, damages to any equipment, or personal injury.
7-7
MAINTENANCE AND INSPECTION
7.6.3 Liability.
Chap. 7
x
x
x
x
x
x
Chapter 8 SPECIFICATIONS
8.1 Standard Model (EMC Filter Built-in Type)
8.1.1 Three-phase 200 V class series
CT (High Duty)-mode inverters for heavy load
Item
Specifications
3A
5A
8A
11A
18A
30AL
46AL
59AL
74AL
Nominal applied motor
*1
(kW)
(Output rating)
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
1.1
1.9
3.0
4.2
6.8
10
14
18
24
28
34
Input power
Output ratings
Type (VXG*****-2)
Rated capacity (kVA)
*2
Rated voltage (V) *3
Rated current (A) *4
5
8
11
18
27
37
45
55
75
90
45
55
68
81
107
131
215
283
346
71
98
116
62
105
Three-phase 200 to 230 V
(with AVR function)
Three-phase 200 to 240 V (with AVR function)
3
30
37
49
63
76
90
119
Overload capability
150%-1 min, 200%-3.0 s
Voltage, frequency
200 to 240 V, 50/60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) *5, Frequency: +5 to -5%
Required capacity
(with DCR) (kVA) *6
0.6
Torque (%)
Braking
88AL 115AL 146AL 180AL 215AL 283AL 350AL 400AL
*7
1.2
2.2
180
200 to 220 V, 50 Hz,
200 to 230 V, 60 Hz
3.1
150%
5.2
7.4
10
15
20
100%
Braking transistor
25
30
40
48
20%
58
10 to 15%
Built-in
Built-in braking resistor
*8
Applicable safety
standards
–
5s
Braking time (s)
Duty cycle (%ED)
EMC filter
DC reactor (DCR)
146
–
5
3
5
3
2
3
2
–
Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.) (EN61800-3:2004)
Option
UL508C, C22.2No.14, EN61800-5-1:2003, EN954-1 Cat.3
IP20, UL open type
Cooling method
Weight / Mass (kg)
Natural cooling
1.8
2.1
3.0
IP00, UL open type
Fan cooling
3.1
3.2
7.0
6.4
10.9
10.9
11.0
25
32
42
43
30AL
46AL
59AL
74AL
–
7.5
11
15
18.5
22
30
37
45
55
75
90
110
–
11
16
20
25
30
43
55
68
81
107
131
158
Rated voltage (V) *3
–
Three-phase 200 to 240 V
(with AVR function)
Rated current (A) *4
–
346
415
Overload capability
–
120%-1 min
Voltage, frequency
–
200 to 240 V, 50/60 Hz
Allowable
voltage/frequency
–
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) *5, Frequency: +5 to -5%
Required capacity
(with DCR) (kVA) *6
–
10
Torque (%)
–
VT (Low Duty)-mode inverters for light load
Item
Specifications
Type (VXG*****-2)
3A
Nominal applied motor
*1
(kW)
(Output rating)
Braking
Input power
Output ratings
Rated capacity (kVA)
*2
*7
Braking transistor
5A
8A
18A
31.8
(29)
46.2
(42)
15
Braking time (s)
Duty cycle (%ED)
59.4
(55)
20
88AL 115AL 146AL 180AL 215AL 283AL 350AL 400AL
Three-phase 200 to 230 V
(with AVR function)
74.8
(68)
88
(80)
115
(107)
146
180
25
30
40
48
58
15%
283
71
98
116
143
7 to 12%
Built-in
–
–
3.7 s
3.4 s
–
–
2.2
1.4
–
Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.)
(EN61800-3:2004)
EMC filter
*8
–
Option
–
UL508C, C22.2No.14, EN61800-5-1:2003, EN954-1 Cat.3
Enclosure (IEC60529)
–
IP20, UL open type
Cooling method
–
Fan cooling
Weight / Mass (kg)
–
6.7
*1
*2
*3
*4
215
200 to 220 V, 50 Hz,
200 to 230 V, 60 Hz
70%
–
Built-in braking resistor
DC reactor (DCR)
Applicable safety
standards
11A
7.0
6.4
IP00, UL open type
10.9
10.9
11.0
25
32
42
43
62
105
4-pole standard motor
Rated capacity is calculated assuming the rated output voltage as 220 V for 200 V class series and 440 V for 400 V class series.
Output voltage cannot exceed the power supply voltage.
To use the inverter with the carrier frequency of 3 kHz or more at the surrounding temperature of 40°C or higher, manage the load so that the current
comes to be within the rated ones enclosed in parentheses ( ) in continuous running.
*5 Voltage unbalance (%) = Max. voltage (V) - Min. voltage (V) × 67 (IEC 61800 - 3)
Three - phase average voltage (V)
If this value is 2 to 3%, use an optional AC reactor (ACR).
*6 Required when a DC reactor (DCR) is used.
*7 Average braking torque for the motor running alone. (It varies with the efficiency of the motor.)
*8 A DC reactor (DCR) is optionally provided. Note that inverters with a capacity of 55 kW in VT mode and inverters with 75 kW or above in all modes
require a DCR to be connected. Be sure to connect it to those inverters.
8-1
SPECIFICATIONS
6.7
Chap. 8
Enclosure (IEC60529)
Three-phase 400 V class series
CT (High Duty)-mode inverters for heavy load
(0.4 to 75 kW)
Item
Specifications
1A5
2A5
4A
5.5A
9A
16A5L
Nominal applied motor
*2
(kW)
(Output rating)
0.4
0.75
1.5
2.2
3.7
(4.0)*1
5.5
7.5
1.1
1.9
2.8
4.1
6.8
10
Input power
Output ratings
Type (VXG*****-4E)
Rated capacity (kVA)
*3
37AL
45AL
60AL
75AL
11
15
18.5
22
30
37
45
55
75
14
18
24
29
34
45
57
69
85
114
18.5
24.5
32
39
45
60
75
91
112
150
Rated voltage (V) *4
Three-phase 380 to 480 V (with AVR function)
Rated current (A)
1.5
Overload capability
150%-1 min, 200%-3.0 s
Voltage, frequency
380 to 480 V, 50/60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) *6, Frequency: +5 to -5%
Required capacity
(with DCR) (kVA) *7
0.6
Torque (%)
Braking
23AL 30A5L
2.5
1.2
4.0
2.1
5.5
13.5
*5
3.2
150%
*8
9.0
91AL 112AL 150AL 176AL
5.2
7.4
10
15
100%
Braking transistor
20
25
30
40
48
20%
5
EMC filter
3
5
3
96
33
42
–
5s
Braking time (s)
Duty cycle (%ED)
71
10 to 15%
Built-in
Built-in braking resistor
58
–
2
3
2
–
Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.) (EN61800-3:2004)
DC reactor (DCR)
*9
Option
Applicable safety
standards
UL508C, C22.2No.14, EN61800-5-1:2003, EN954-1 Cat.3
Enclosure (IEC60529)
IP20, UL open type
Cooling method
Natural cooling
Weight / Mass (kg)
1.8
2.1
IP00, UL open type
Fan cooling
2.7
2.9
3.2
6.8
6.9
6.2
10.5
10.5
11.2
26
27
32
(90 to 630 kW)
Item
Specifications
Type (VXG*****-4E)
210AL 253AL 304AL 377AL 415AL 520AL 650AL 740AL 840AL 960AL 1170AL 1370AL
Input power
Output ratings
Nominal applied motor
*2
(kW)
(Output rating)
Rated capacity (kVA)
*3
Rated voltage (V) *4
Rated current (A)
110
132
160
200
220
280
315
355
400
500
630
134
160
192
231
287
316
396
445
495
563
731
891
520
585
650
740
960
Three-phase 380 to 480 V (with AVR function)
176
210
253
377
415
1170
150%-1 min, 200%-3.0 s
Voltage, frequency
380 to 440 V, 50 Hz
380 to 480 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) *6, Frequency: +5 to -5%
Required capacity
(with DCR) (kVA) *7
*8
114
199
248
271
347
388
436
489
611
773
–
Braking time (s)
Duty cycle (%ED)
Applicable safety
standards
165
–
Built-in braking resistor
DC reactor (DCR)
140
10 to 15%
Braking transistor
–
EMC filter
Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.) (EN61800-3:2004)
*9
Option
UL508C, C22.2No.14, EN61800-5-1:2003, EN954-1 Cat.3
Enclosure (IEC60529)
IP00, UL open type
Cooling method
Fan cooling
Weight / Mass (kg)
62
*2
*3
*4
*5
304
Overload capability
Torque (%)
Braking
90
64
94
98
129
140
245
245
330
330
530
530
4-pole standard motor
Rated capacity is calculated assuming the rated output voltage as 220 V for 200 V class series and 440 V for 400 V class series.
Output voltage cannot exceed the power supply voltage.
380 to 440 V, 50 Hz; 380 to 480 V, 60 Hz
*6 Voltage unbalance (%) =
Max. voltage (V) - Min. voltage (V)
× 67 (IEC 61800 - 3)
Three - phase average voltage (V)
If this value is 2 to 3%, use an optional AC reactor (ACR).
*7 Required when a DC reactor (DCR) is used.
*8 Average braking torque for the motor running alone. (It varies with the efficiency of the motor.)
*9 A DC reactor (DCR) is optionally provided. Note that inverters with a capacity of 55 kW in VT mode and inverters with 75 kW or above in all modes
require a DCR to be connected. Be sure to connect it to those inverters.
8-2
MT (Medium Duty)-mode inverters for medium load
(90 to 400 kW)
Item
Specifications
Type (VXG*****-4E)
210AL 253AL 304AL 377AL 415AL 520AL 650AL 740AL 840AL 960AL
Input power
Output ratings
Nominal applied motor
(kW)
*1
(Output rating)
Rated capacity (kVA)
*2
132
160
200
220
250
315
355
400
450
160
192
231
287
316
356
445
495
563
640
585
650
740
840
Rated voltage (V) *3
Three-phase 380 to 480 V (with AVR function)
Rated current (A)
210
Overload capability
150%-1 min
Voltage, frequency
380 to 440 V, 50 Hz
380 to 480 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) *4, Frequency: +5 to -5%
Required capacity
(with DCR) (kVA) *5
140
Torque (%)
Braking
110
*6
Braking transistor
165
304
199
377
248
415
271
468
308
388
436
489
547
7 to 12%
–
Built-in braking resistor
Braking time (s)
Duty cycle (%ED)
EMC filter
DC reactor (DCR)
253
–
–
*7
Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.) (EN61800-3:2004)
Option
Applicable safety
standards
UL508C, C22.2No.14, EN61800-5-1:2003, EN954-1 Cat.3
Enclosure (IEC60529)
IP00, UL open type
Cooling method
Weight / Mass (kg)
Fan cooling
62
64
94
98
129
140
245
245
330
330
*1 4-pole standard motor
*2 Rated capacity is calculated assuming the rated output voltage as 220 V for 200 V class series and 440 V for 400 V class series.
*3 Output voltage cannot exceed the power supply voltage.
Max. voltage (V) - Min. voltage (V)
× 67 (IEC 61800 - 3)
Three - phase average voltage (V)
If this value is 2 to 3%, use an optional AC reactor (ACR).
8-3
SPECIFICATIONS
*5 Required when a DC reactor (DCR) is used.
*6 Average braking torque for the motor running alone. (It varies with the efficiency of the motor.)
*7 A DC reactor (DCR) is optionally provided. Note that inverters with a capacity of 55 kW in VT mode and inverters with 75 kW or above in all modes
require a DCR to be connected. Be sure to connect it to those inverters.
Chap. 8
*4 Voltage unbalance (%) =
VT (Low Duty)-mode inverters for light load
(5.5 to 75 kW)
Item
Specifications
Type (VXG*****-4E)
1A5
2A5
Braking
Input power
Output ratings
Nominal applied motor
(kW)
*1
(Output rating)
5.5A
9A
–
Rated capacity (kVA)
–
*2
Rated voltage (V)
4A
16A5L
23AL 30A5L
37AL
45AL
60AL
75AL
91AL 112AL 150AL 176AL
7.5
11
15
18.5
22
30
37
45
55
75
90
12
17
22
28
33
45
57
69
85
114
134
75
91
112
150
176
–
Three-phase 380 to 480 V (with AVR function)
Rated current (A)
–
16.5
Overload capability
–
120%-1 min
Voltage, frequency
–
380 to 480 V, 50/60 Hz
Allowable
voltage/frequency
–
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) *5,
Frequency: +5 to -5%
*3
Required capacity
(with DCR) (kVA)] *6
–
Torque (%)
–
*7
Braking transistor
–
Built-in braking resistor
Braking time (s)
–
Duty cycle (%ED)
EMC filter
DC reactor (DCR)
*8
23
10
15
30.5
20
37
45
60
*4
25
70%
30
40
48
58
15%
71
96
Built-in
–
3.7 s
3.4 s
–
–
2.2
1.4
–
–
Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.)
(EN61800-3:2004)
–
Option
Applicable safety
standards
–
UL508C, C22.2No.14, EN61800-5-1:2003, EN954-1 Cat.3
Enclosure (IEC60529)
–
IP20, UL open type
Cooling method
–
Fan cooling
Weight / Mass (kg)
–
6.8
6.9
6.2
114
7 to 12%
IP00, UL open type
10.5
10.5
11.2
26
27
32
33
42
(90 to 630 kW)
Item
Specifications
Type (VXG*****-4E)
210AL 253AL 304AL 377AL 415AL 520AL 650AL 740AL 840AL 960AL 1170AL
Input power
Output ratings
Nominal applied motor
*1
(kW)
(Output rating)
Rated capacity (kVA)
*2
Rated voltage (V)
110
132
160
200
220
280
355
400
450
500
630
710
160
192
231
287
316
396
495
563
640
731
891
1044
650
740
840
960
1170
Three-phase 380 to 480 V (with AVR function)
Rated current (A)
210
Overload capability
120%-1 min
Voltage, frequency
380 to 440 V, 50 Hz
380 to 480 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) *5, Frequency: +5 to -5%
Required capacity
(with DCR) (kVA) *6
140
Torque (%)
Braking
*3
*7
Braking transistor
Built-in braking resistor
Braking time (s)
165
304
199
377
248
415
271
520
347
436
489
547
611
773
1370
871
7 to 12%
–
–
EMC filter
DC reactor (DCR)
253
–
Duty cycle (%ED)
Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.) (EN61800-3:2004)
*8
Option
Applicable safety
standards
UL508C, C22.2No.14, EN61800-5-1:2003, EN954-1 Cat.3
Enclosure (IEC60529)
IP00, UL open type
Cooling method
Weight / Mass (kg)
Fan cooling
62
64
*1
*2
*3
*4
1370AL
94
98
129
140
245
245
330
330
530
530
4-pole standard motor
Rated capacity is calculated assuming the rated output voltage as 220 V for 200 V class series and 440 V for 400 V class series.
Output voltage cannot exceed the power supply voltage.
380 to 440 V, 50 Hz; 380 to 480 V, 60 Hz
*5 Voltage unbalance (%) =
Max. voltage (V) - Min. voltage (V)
× 67 (IEC 61800 - 3)
Three - phase average voltage (V)
If this value is 2 to 3%, use an optional AC reactor (ACR).
*6 Required when a DC reactor (DCR) is used.
*7 Average braking torque for the motor running alone. (It varies with the efficiency of the motor.)
*8 A DC reactor (DCR) is optionally provided. Note that inverters with a capacity of 55 kW in VT mode and inverters with 75 kW or above in all modes
require a DCR to be connected. Be sure to connect it to those inverters.
8-4
8.2 Common Specifications
Setting range
Item
Explanation
Maximum frequency
25 to 500 Hz (120 Hz for inverters in MT/VT mode)
(120 Hz under vector control without speed sensor)
(200 Hz under V/f control with speed sensor or vector control with speed sensor)
Base frequency
25 to 500 Hz (in conjunction with the maximum frequency)
Starting frequency
0.1 to 60.0 Hz (0.0 Hz under vector control with/without speed sensor)
• 0.75 to 16 kHz (CT mode: 0.4 to 55 kW,
VT mode: 5.5 to 18.5 kW)
• 0.75 to 10 kHz (CT mode: 75 to 400 kW, VT mode: 22 to 55 kW)
• 0.75 to 6 kHz
(CT mode: 500 and 630 kW, VT mode: 75 to 500 kW)
• 0.75 to 4 kHz
(VT mode: 630 kW)
• 0.75 to 2 kHz
(MT mode: 90 to 400 kW)
Note: The carrier frequency may automatically drop depending upon the surrounding temperature
or output current to protect the inverter. (The automatic drop function can be disabled.)
• Analog setting: r0.2% of maximum frequency (at 25 r10qC)
• Keypad setting: r0.01% of maximum frequency (at -10 to +50qC)
• Analog setting: 1/3000 of maximum frequency (1/1500 for V2 input)
• Keypad setting: 0.01 Hz (99.99 Hz or less), 0.1 Hz (100.0 to 500.0 Hz)
• Link operation setting: Selectable from the following two types
- 1/20000 of maximum frequency
- 0.01 Hz (fixed)
Carrier frequency
Setting resolution
Under V/f
control with
speed sensor
Speed
control
range
• 1 : 100 (Minimum speed: Base speed, 4P, 15 to 1500 r/min)
• 1:2
(Constant torque range: Constant output range)
Under dynamic
torque vector
control with
speed sensor
Speed
control
accuracy
• Analog setting: r0.2% of maximum frequency (at 25 r10qC)
• Digital setting: r0.01% of maximum frequency (at -10 to +50qC)
Under
vector control
without speed
sensor
Speed
control
range
• 1 : 200 (Minimum speed: Base speed, 4P, 7.5 to 1500 r/min)
• 1:2
(Constant torque range: Constant output range)
Speed
control
accuracy
• Analog setting: r0.5% of base speed (at 25 r10qC)
• Digital setting: r0.5% of base speed (at -10 to +50qC)
• 1 : 1500
• 1:4
Control method
•
•
•
•
•
V/f characteristics
• Possible to set output voltage at base frequency and at maximum frequency
• AVR control ON/OFF selectable. Non-linear V/f pattern with three arbitrary points.
Torque boost
• Auto torque boost (for constant torque load)
• Manual torque boost: Desired torque boost (0.0 to 20.0%) can be set.
• Select application load with function code F37. (Variable torque load or constant torque load)
Starting torque
22 kW or below: 200% or over, 30 kW or above: 180% or over
Reference frequency: 0.3 Hz with slip compensation and auto torque boost
Start/stop operation
keys), external signals (run forward (run reverse) command, etc.),
• Keypad ( and
Communications link (RS-485/fieldbus (option))
• Remote/local operation
Enable input
(Safety stop function)
Opening the circuit between terminals [EN] and [PLC] stops the inverter's output transistor
(coast-to-stop). (Compliant with EN954-1 Cat.3)
Frequency command
and
keys
• Keypad:
• Analog input (Analog input can be set with external voltage/current input):
0 to r 10 VDC/0 to r 100% (terminals [12], [V2])
+4 to +20 mA DC/0 to 100% (terminal [C1])
• UP/DOWN operation: Multi-frequency (16 steps), 16-bit parallel
• Pulse train input (standard): Pulse input = [X7] terminal,
Rotational direction = One of the digital input terminals
except [X7]
• Link operation: Various buses (option)
• Reference frequency switching, Remote/local mode switching, Auxiliary frequency setting,
Proportional operation setting, and Inverse operation
Acceleration/
deceleration time
0.00 to 6000 s
Linear/S-curve/curvilinear, Acceleration/deceleration time settings 1 to 4 switchable
(Minimum speed: Base speed, 4P, 1 to 1500 r/min, 1024 p/r)
(Constant torque range: Constant output range)
• Analog setting: r0.2% of maximum frequency (at 25 r10qC)
• Digital setting: r0.01% of maximum frequency (at -10 to +50qC)
V/f control
Dynamic torque vector control
V/f control with speed sensor or dynamic torque vector control with speed sensor
Vector control without speed sensor (Not available for MT-mode inverters)
Vector control with speed sensor (with an optional PG interface card mounted)
Item
Explanation
8-5
SPECIFICATIONS
Speed
Under
control
vector control
with speed sensor range
Speed
control
accuracy
Chap. 8
Control
Output frequency
Accuracy (Stability)
Stop control
Auto-restart after
momentary power failure
Hardware current limiter
Torque limiter
Control functions
Run forward command, run reverse command, select multi-frequency, select ACC/DEC time,
enable 3-wire operation, coast to a stop, reset alarm, enable external alarm trip, ready for jogging,
select frequency command 2/1, select motor 1 to 4, enable DC braking, select torque limiter level,
switch to commercial power, UP (increase output frequency), DOWN (decrease output
frequency), enable data change with keypad, cancel PID control, switch normal/inverse operation,
interlock, cancel torque control, enable communications link via RS-485 or fieldbus (option),
universal DI, enable auto search for idling motor speed at starting, force to stop, pre-excitation,
reset PID integral and differential components, hold PID integral component, select local (keypad)
operation, protect the motor from dew condensation, enable internal sequence to commercial lines,
pulse train input, pulse train sign, cancel constant peripheral speed control, hold the constant
peripheral speed control frequency in the memory, switch to commercial power operation, select
droop control, servo-lock command, cancel PG alarm, cancel customizable logic, clear all
customizable logic timers
Transistor output
Inverter running, frequency arrival signal 1/3, frequency detected (3 points), undervoltage
detected (inverter stopped), torque polarity detected, inverter output limiting, auto-restarting after
momentary power failure, motor overload early warning, keypad operation, inverter ready to run,
switch motor power between commercial line and inverter output (inverter
input/output/commercial power), select the AX terminal function (primary side MC), inverter
output limiting with delay, cooling fan in operation, auto-resetting, universal DO, heat sink
overheat early warning, service lifetime alarm, reference loss detected, inverter output on,
overload prevention control, current detected (3 points), low level current detected, PID alarm,
under PID control, PID control stopped due to slow flowrate, low output torque detected, torque
detected (2 points), switched to motor 1 to 4, run forward signal, run reverse signal, inverter in
remote operation, PTC status detection enabled, brake signal, analog frequency reference loss on
the terminal [C1], inverter keeping speed output, speed arrived, PG error detected, maintenance
timer, light alarm, alarm relay contact output (for any fault), braking resistor broken, positioning
completion signal, enable circuit failure detected, customizable logic output signal
Terminals [FM1] and [FM2]:
Output a selected signal with analog DC voltage (0 to +10 V) or analog DC current (4 to 20 mA)
Selectable output signals:
Output frequency (before slip compensation, after slip compensation), output current, output
voltage, output torque, load factor, input power, PID feedback amount, speed (PG feedback value),
DC link bus voltage, universal AO, motor output, calibration, PID command (SV), PID output
(MV)
Speed monitor (reference frequency (Hz), output frequency, motor speed, load shaft speed, line
speed, speed in %)
Output current, output voltage, torque calculation value, input power, PID command value, PID
feedback amount, PID output, load factor, motor output, torque current, flux command, analog
signal input monitor, input watt-hour
Life early warning, cumulative inverter run time, cumulative motor run time, input watt-hour,
number of startups
I/O checking, energy-saving monitor (input power, input power x coefficient (charges for input
power))
Control
Digital input
Analog output
Indication
Running/stopping
Other features
• Running continued at the stop frequency, coast-to-stop, or force to stop.
• DC braking: Braking starting frequency (up to 60 Hz), time (up to 30.0 s), and operation level
(up to 100%)
• Zero speed control (under vector control with speed sensor.)
• Trip immediately, trip after recovery from power failure, trip after deceleration to stop
• Continue to run, restart at the frequency at which the power failure occurred, restart at the
starting frequency, restart after searching for idling motor speed
• Current limiter operation level (20 to 200%)
• Overcurrent limiting by hardware (This can be canceled.)
• Torque limit value (r300%)
• Torque limiter 1/2, torque limiter enabled/disabled, analog torque limit value
• Analog input adjustment (gain/offset/filter time constant), frequency limiter (high and low),
bias frequency, jump frequency, jogging operation, pre-excitation, switch to commercial power,
commercial power switching sequence, cooling fan ON/OFF control, select motor 2 to 4,
protect motor from dew condensation, universal DI, universal DO, universal AO, rotational
direction limitation
• Overload prevention control, auto search, slip compensation, automatic deceleration
(anti-regenerative control), droop control, PID process control, PID dancer control,
Deceleration characteristics (improving braking capability), auto energy saving function
• Auto-tuning (offline)
• Life early warning, cumulative inverter run time, cumulative motor run time
• Light alarm, retry, command loss detection
Trip mode
Trip history: Saves and displays the last 4 trip factors and their detailed description.
Communications
RS-485 COM port 1 (for keypad connection), RS-485 COM port 2 (on terminal block), and USB
port (on the keypad face)
Protection against
momentary power failure
Upon detection of a momentary power failure lasting more than 15 ms, this function stops the
inverter output. If restart after momentary power failure is selected, this function invokes a restart
process if power is restored within a predetermined period (allowable momentary power failure
time).
8-6
8.3 External Dimensions
8.3.1 Standard models
Inverter type
VXG****-2 / 4E
200 V 400 V
0.4
0.4
0.75
0.75
1.5
1.5
2.2
2.2
4.0
4.0
5.5
5.5
7.5
7.5
11
11
15
15
18.5
18.5
22
22
30
30
37
37
45
-
55
45
55
Dimensions (mm)
(Unit: mm)
W
W1 W2
110
96
6
150 136
㸫
220
㸫
280
㸫
315
㸫
355
㸫
400
㸫
500
㸫
630
3
6
19
113
32
400
378
550
530
615
595
675
655
195 105
90
255
140
* Grounding terminal (27.8 u
10
16 mm) for input line,
provided only on the EMC
filter built-in type of 200 V/400
V class series inverters with a
capacity of 5.5 to 11 kW.
10
355 275
740
12
115
270
155
720
750
880
850
285 145 140
360 180
740
710
315 135
4
530 430
1000 970
15
360 180
15.5
180
15
680 290
1400 1370
440 260
6.4
880 260
1000 300
1550 1520
500 313.2 186.8
8-7
SPECIFICATIONS
200
ØA
Chap. 8
160
㸫
145
D3
630 290
132
7
D2
10
-
㸫
D1
238
320 240
90
㸫
D
260
250 226
530 430
90
H2
11
-
110
246
220 196
75
㸫
H1
132
75
㸫
H
Chapter 9 CONFORMITY WITH STANDARDS
9.1 Compliance with UL Standards and Canadian Standards (cUL certification)
9.1.1 General
Originally, the UL standards were established by Underwriters Laboratories, Inc. as private criteria for
inspections/investigations pertaining to fire/accident insurance in the USA. Later, these standards were authorized as the
official standards to protect operators, service personnel and the general populace from fires and other accidents in the USA.
cUL certification means that UL has given certification for products to clear CSA Standards. cUL certified products are
equivalent to those compliant with CSA Standards.
9.1.2 Considerations when using JAGUAR VXG in systems to be certified by UL and cUL
If you want to use the IMO series of inverters as a part of UL Standards or CSA Standards (cUL certified) certified product,
refer to the related guidelines described on pages ix to xii.
9.2 Compliance with European Standards
The CE marking on IMO products indicates that they comply with the essential requirements of the Electromagnetic
Compatibility (EMC) Directive 2004/108/EC and Low Voltage Directive 2006/95/EC which are issued by the Council of the
European Communities
The products comply with the following standards
Basic type
EMC filter built-in type
EMC Directives
Depends upon a filter dedicated to
IMO inverters*
Low Voltage Directive
EN61800-5-1: 2003
Safety Standard
EN954-1: Category 3
EN61800-3 : 2004
Immunity : Second environment (Industrial)
Emission : Category C3
* If connected with an external EMC filter dedicated to IMO inverters, the basic type of inverters that bear a CE marking but
have no built-in EMC filter becomes compliant with these EMC Directives.
9.3 Compliance with EMC Standards
9.3.1 General
The CE marking on inverters does not ensure that the entire equipment including our CE-marked products is compliant with
the EMC Directive. Therefore, CE marking for the equipment shall be the responsibility of the equipment manufacturer. For
this reason, IMO’s CE mark is indicated under the condition that the product shall be used within equipment meeting all
requirements for the relevant Directives. Instrumentation of such equipment shall be the responsibility of the equipment
manufacturer.
Generally, machinery or equipment includes not only our products but other devices as well. Manufacturers, therefore, shall
design the whole system to be compliant with the relevant Directives.
In addition, to satisfy the requirements noted above, use the EMC filter built-in type of inverters or the combination of the
basic type of inverters that have no built-in EMC filter and an external filter (option) dedicated to IMO inverters. In either
case, mount inverters in accordance with the installation procedure given below. To ensure the compliance, it is
recommended that inverters be mounted in a metal panel.
Our EMC compliance test is performed under the following conditions.
Wiring length (of the shielded cable) between the inverter (EMC filter built-in type) and motor: 5m
To use IMO inverters in combination with a PWM converter, the basic type of inverters having no built-in EMC
filter should be used. Use of an EMC filter built-in type may increase heat of capacitors in the inverter, resulting in
a break. In addition, the effect of the EMC filter can no longer be expected.
9-1
CONFORMITY WITH STANDARDS
CAUTION
The EMC filter built-in type of the IMO inverters is categorized as "Category C3" of the EN61800-3. It is not designed for
use in a domestic environment. It may interfere with the operations of home appliances or office equipment due to noise
emitted from it.
Chap. 9
9.3.2 Recommended installation procedure
To make the machinery or equipment fully compliant with the EMC Directive, have certified technicians wire the motor and
inverter in strict accordance with the procedure described below.
„ In the case of EMC filter built-in type of inverter
1) Mount the inverter on a grounded panel or metal plate. Use shielded wires for the motor cable and route the cable as short
as possible. Firmly clamp the shield to the metal plate to ground it. Further, connect the shielding layer electrically to the
grounding terminal of the motor. Separate the input and output wires as far as possible, using wiring guides.
For inverters with a capacity of 5.5 to 11 kW, connect the input grounding wire to the grounding terminal at the front,
left-hand side, and the output grounding wire to that on the main circuit terminal block. (Refer to Figure 9.1.)
Output grounding
Input grounding
Input wires
Output wires
Figure 9.1 Wiring for EMC Filter Built-in Type Inverters with a Capacity of 5.5 to 11 kW
2) For connection to inverter's control terminals and for connection of the RS-485 communication signal cable, use shielded
wires. As with the motor, clamp the shields firmly to a grounded panel.
3) If noise from the inverter exceeds the permissible level, enclose the inverter and its peripherals within a metal panel as
shown in Figure 9.2.
Figure 9.2 Mounting the Inverter in a Metal Panel
„ In case an EMC-compliant filter (optional) is externally used
1) Mount the inverter and the filter on a grounded panel or metal plate. Use shielded wires for the motor cable and route the
cable as short as possible. Firmly clamp the shields to the metal plate to ground them. Further, connect the shielding
layers electrically to the grounding terminal of the motor.
2) For connection to inverter's control terminals and for connection of the RS-485 communication signal cable, use shielded
wires. As with the motor, clamp the shields firmly to a grounded panel.
3) If noise from the inverter exceeds the permissible level, enclose the inverter and its peripherals within a metal panel as
shown in Figure 9.3.
Figure 9.3 Mounting the Inverter with EMC-compliant Filter in a Metal Panel
9-2
9.3.3 Leakage current of EMC-filter built-in type of inverters
An EMC filter uses grounding capacitors for noise suppression which increase leakage current. When using an EMC-filter
built-in type of inverters, therefore, check whether there is no problem with electrical systems.
Three-Phase PDS (Power Drive System) with touch currents t 3.5 mA AC or t 10 mA DC
As the touch current (leakage current) of inverters with EMC-filter is relatively high, it is of essential importance to
always assure a reliable connection to Protective Earth (PE).
In Table 9.1, for the inverter types whose leakage currents are equal to or exceed the critical value of 35 mA AC or 10 mA
DC (IEC 61800-5-1), the minimum cross sectional area of the PE-conductor should be:
- 10 mm2 (Cu-conductors)
- 16 mm2 (Al-conductors)
An electric shock could occur.
Table 9.1 Leakage Current of EMC Filter Built-in Type of Inverters
Input
Power
Three-phase
200 V
*1)
Inverter type *1)
Input
Power
Inverter type *1)
VXG1A5-4E
VXG2A5-4E
VXG4A-4E
VXG5.5A-4E
2
4
Leakage current
(mA)
3
2
VXG9A-4E
23
25
Three-phase
400 V
*2)
4
11
5
*1) Calculated based on these measuring conditions: 240 V, 60 Hz, grounding of a single wire in delta connection, interphase voltage
unbalance ratio 2%.
*2) Calculated based on these measuring conditions: 480 V, 60 Hz, neutral grounding in Y-connection, interphase voltage unbalance ratio
2%.
9-3
CONFORMITY WITH STANDARDS
VXG16A5L-4E
VXG23AL-4E
VXG30A5L-4E
VXG37AL-4E
VXG45AL-4E
VXG60AL-4E
VXG75AL-4E
VXG91AL-4E
VXG112AL-4E
VXG150AL-4E
VXG176AL-4E
VXG210AL-4E
VXG253AL-4E
VXG304AL-4E
VXG377AL-4E
VXG415AL-4E
VXG520AL-4E
VXG650AL-4E
VXG740AL-4E
VXG840AL-4E
VXG960AL-4E
VXG1170AL-4E
VXG1370AL-4E
Chap. 9
VXG3A-2
VXG5A-2
VXG8A-2
VXG11A-2
VXG18A-2
VXG30AL-2
VXG46AL-2
VXG59AL-2
VXG74AL-2
VXG88AL-2
VXG115AL-2
VXG146AL-2
VXG180AL-2
VXG215AL-2
VXG283AL-2
VXG350AL-2
VXG400AL-2
Leakage current
(mA)
9.4 Harmonic Component Regulation in the EU
9.4.1 General comments
When you use general-purpose industrial inverters in the EU, the harmonics emitted from the inverter to power lines are
strictly regulated as stated below.
If an inverter whose rated input is 1 kW or less is connected to public low-voltage power supply, it is regulated by the
harmonics emission regulations from inverters to power lines (with the exception of industrial low-voltage power lines).
Refer to Figure 9.4 below for details.
Figure 9.4 Power Source and Regulation
9.4.2 Compliance with the harmonic component regulation
Table 9.2 Compliance with Harmonic Component Regulation
Power supply voltage
Three-phase 200 V
Three-phase 400 V
Inverter type
w/o DC reactor
w/ DC reactor
Applicable
DC reactor type
VXG3A-2
—*
—*
Consult IMO
VXG5A-2
VXG1A5-4E
—*
—
—*
—
Consult IMO
VXLC0.4
VXG2A5-4E
—
—
VXLC0.75
* When supplying three-phase 200 VAC power stepped down from a three-phase 400 VAC power line using a transformer, the level of
harmonic flow from the 400 VAC line will be regulated.
Note 1) Inverter types marked with — in the table above are compliant with the EN61000-3-2 (+A14), so they may be connected to public
low-voltage power supply unconditionally.
Conditions apply when connecting models marked with "—". To connect them to public low-voltage power supply, you need to
obtain permission from the local electric power supplier. In general, you will need to provide the supplier with the harmonics
current data of the inverter. To obtain the data, contact your IMO representative.
9.5 Compliance with the Low Voltage Directive in the EU
9.5.1 General
General-purpose inverters are regulated by the Low Voltage Directive in the EU. IMO Precision Controls Ltd states that all
our inverters with CE marking are compliant with the Low Voltage Directive.
9.5.2 Points for consideration when using the IMO series in a system to be certified by the Low Voltage
Directive in the EU
If you want to use the IMO series of inverters in systems/equipment in the EU, refer to the guidelines on pages v to viii.
9-4
9.6 Compliance with EN954-1, Category 3
9.6.1 General
In IMO series of inverters, opening the hardware circuit between terminals [EN] and [PLC] stops the output transistor,
coasting the motor to a stop. (EN: Enable input) This is the safety stop function prescribed in EN60204-1, Category 0
(Uncontrolled stop) and compliant with EN954-1, Category 3.
Note: Depending on applications, additional measures may be necessary (for end-user) to apply such as ‘brake function’ to
prevent movement and motor terminal protection against possible electrical hazard(s).
Use of terminals [EN] and [PLC] eliminates the need of external safety circuit breakers while conventional inverters need
those breakers to configure the EN954-1 Category 3 compliant safety system.
9.6.2 EN954-1
Chap. 9
European Standard EN954-1 (Safety of machinery–Safety related parts of control systems) prescribes the basic safety
requirements for machinery categorized according to the requirement level. Category 3 represents the requirements that the
machinery shall be designed with redundancy so that a single fault does not lead to the loss of the safety function. Table 9.3
shows an outline of the category levels and their safety requirements. (For detailed requirements refer to EN 954-1)
Table 9.3
Summary of requirements
System behavior
B
Safety related parts of control systems and/or their safety
devices and their components shall be designed,
constructed, selected, assembled and combined in
accordance with the relevant standards so that they can
withstand the expected influence.
The occurrence of a fault can lead to the
loss of the safety function.
1
Requirements of Category B shall apply.
Well-tried safety principles and well-tried components shall
be used.
The occurrence of a fault can lead to the
loss of the safety function, but the
probability of occurrence is lower than
for Category B.
2
Requirements of Category 1 shall apply.
The occurrence of a fault can lead to the
loss of the safety function between the
checks.
The safety function shall be checked at intervals suitable
for the machinery.
3
Requirements of Category 1 shall apply.
Safety-related parts shall be designed, so that:
- a single fault in any of these parts does not lead to the
loss of the safety function, and
- a single fault is detected whenever reasonably
practicable.
When the single fault occurs, the safety
function is still maintained.
Accumulation of undetected faults can
lead to the loss of the safety function.
4
Requirements of Category 1 shall apply.
Safety-related parts shall be designed, so that a single fault
is detected during or prior to the next demand on the safety
function. If this is not possible, an accumulation of faults
shall not lead to the loss of the safety function.
When faults occur, the safety function is
still maintained.
9-5
CONFORMITY WITH STANDARDS
Category
9.6.3 Notes
(1) Wiring for terminal [EN]
- When using terminal [EN], be sure to remove the short-circuit wire from terminals [EN] and [PLC], which has been
connected at the shipment.
- '[EN] & [PLC]' terminals are safety related wire connections and therefore careful installation practices shall be applied
to ensure no 'short-circuit(s)' can occur to these connections.
- For opening and closing the hardware circuit between terminals [EN] and [PLC], use safety approved components such
as safety switches and safety relays that comply with EN954-1, Category 3 or higher to ensure a complete shutoff.
- Be sure to use shielded wires for connecting terminals [EN] and [PLC] and ground the shielding layer. Do not
connect/mix any other control signal wire within the same shielded core.
- It is the responsibility of the machinery manufacturer to guarantee that a short-circuiting or other fault does not occur in
wiring of external safety components between terminals [EN] and [PLC].
Fault examples:
• Terminals [EN] and [PLC] are short-circuited due to the wiring being caught in the door of the control panel so that a
current continues to flow in terminal [EN] although the safety component is OFF and therefore the safety function
will/may NOT operate
• The wiring is in contact with any other wire so that a current continues to flow in terminal [EN] and therefore the
safety function will/may NOT operate
(2) Other notes
- When configuring the product safety system with this safety stop function, make a risk assessment of not only the
external equipment and wiring connected to terminal [EN] but also the whole system including other equipment,
devices and wiring against the product safety system required by the machinery manufacturer under the manufacturer's
responsibility in order to confirm that the whole system conforms to the product safety system required by the
machinery manufacturer.
In addition, as preventive maintenance, the machinery manufacturer must perform periodical inspections to check that
the product safety system properly functions.
- To make the inverter compliant with EN954-1, Category 3, it is necessary to install the inverter on a control panel with
the enclosure rating of IP54 or above.
This safety stop function coasts the motor to a stop. When a mechanical brake is used to stop or hold the motor for the
sake of the product safety system of whole system, do not use the inverter's control signals such as output from terminal
[Y]. (Using control signals does not satisfy the safety standards because of software intervention.) Use safety
components complying with EN954-1, Category 3 or higher to activate mechanical brakes.
- The safety shutdown circuit between terminal [EN] input section and inverter's output shutdown section is dualconfigured (redundant circuit) so that an occurrence of a single fault does not detract the safety stop function.
If a single fault is detected in the safety shutdown circuit, the inverter coasts the motor to a stop even with the terminal
[EN]-[PLC] state being ON, as well as outputting an alarm to external equipment. (Note that the alarm output function
is not guaranteed to all of single faults.)
- This safety stop function may not completely shut off the power supply to the motor electrically. Before performing
wiring or maintenance jobs, be sure to disconnect/isolate the input power to the inverter and wait at least 5 minutes for
22 kW or below of inverters, and at least 10 minutes for 30 kW or above.
9-6
High Performance, Multifunction Inverter
Jaguar VXG
Instruction Manual
First Edition, December 2009
IMO Precision Controls Ltd
The purpose of this instruction manual is to provide accurate information in handling, setting up and operating of the JAGUAR
VXG series of inverters. Please feel free to send your comments regarding any errors or omissions you may have found, or any
suggestions you may have for generally improving the manual.
In no event will IMO Precision Controls Ltd be liable for any direct or indirect damages resulting from the application of the
information in this manual.
IMO Precision Controls Ltd
1000 North Circular Road, Staples Corner, London, NW2 7JP, United Kingdom.
Phone: +44 (0)20 8452 6444 Fax +44 (0)20 8450 2274
URL http://www.imopconline.com
2009-12 S.Mc (Issue 1)