Steam Sauna ES 1 Unit for 1 Room Steam Generator Installation, operation and maintenance manual
Below you will find brief information for Steam Generator ES 1 Unit for 1 Room. This manual details the installation, operation, and maintenance of this commercial steam generator. This unit is designed for a single steam room and comes with a variety of features including a 24-hour timer, thermostat, and scent dispenser. It is important to follow these instructions for proper operation and maintenance to ensure a safe and enjoyable steam bath experience.
Advertisement
Advertisement
STEAM
MASTER®
1 UNIT FOR 1 ROOM
M
G
IN
M
S
IA
A
IO
IO
O
,
IN
WARRANTY
The manufacturer warrants each part to be free from defects in material and workmanship, in the course of normal use and agrees to repair or exchange any part thereof in which such defects appear, to the satisfaction of the manufacturer. This warranty is applied within the boundaries of the United States or Canada.
The manufacturer’s obligation under this warranty is limited to the repairing or exchanging of any defective part, if that part is returned to the manufacturer. Postage and handling charges to and from Steam Sauna Inc for warranty repairs is to be prepaid by the purchaser. A return authorization number assigned by Steam Sauna Inc is required prior to returning any product for repair. Components returned without a return authorization number will not be repaired or replaced. Any missing parts claim must be made within 48 hours of receiving this product.
This warranty does not cover any related charges for the installation/removal of these products. Warranty service can be obtained by sending your product to Steam Sauna Inc.
Proof of purchase and a serial number of the product will be required before any services are performed. This warranty applied only to the original purchaser.
For all Commercial steam units, the boiling tank is protected by a three-year warranty against corrosion and leakage, and 1 year warranty on all other components from date of purchase (return freight and all “on site” work is purchaser’s obligation).
The warranty is void if a certified plumber, electrician or authorized qualified service representative do not perform the installation and wiring.
This warranty does not apply to any product, which has been repaired or altered in any way, so as in the judgment of the manufacturer to injure the product’s stability or reliability or which has been subjected to misuse, neglect, accident or any use other than steam bath. Neither does this warranty applies to any product connected, installed or adjusted other than in accordance with the manufacturer’s instructions, or if the steam line(s) are restricted in any manner.
The manufacturer will not be liable to you or anyone else for any damages, loss of profits, loss of earnings, loss of business opportunities, personal injury or other loss resulting directly or indirectly from using the equipment or services.
This warranty is in lieu of any other warranties expressed or implied and no representative is authorized to assume for the manufacturer any liability in conjunction with the sale of the manufacturer’s products.
STEAM SAUNA INC
This manual is a comprehensive guide to proper installation, troubleshooting, operation and general care of your STEAMASTER
®
ES Series 1 Unit for 1
Room.
Please familiarize yourself with these contents. This will guide you through the necessary steps to install and operate your Steam Sauna commercial steam generator as easily and conveniently as possible.
TABLE OF CONTENTS
INSTALLATION MANUAL 1 UNIT FOR 1 ROOM
2
INTRODUCTION
SAFETY TIPS
INSTALLATION GUIDE
SHOP DRAWING 1 UNIT FOR 1 ROOM
INSTALLATION INSTRUCTIONS
STEP 1. LOCATING AND INSTALLING THE UNIT
STEP 2. PLUMBING
STEP 3. ELECTRICAL INSTALLATIONS
STEP 4. SCENT DISPENSER (OPTION)
STEP 5. WATER SOFTENER (OPTION)
START UP PROCEDURE
BASIC TROUBLESHOOT GUIDE
OPERATION MANUAL
INTRODUCTION TO STEAM GENERATOR FUNCTIONS
INTRODUCTION TO PROGRAMMING
THERMOSTAT FUNCTIONS AND SET UP
THE 419 CONTROL FUNCTIONS
RANCO ELECTRONIC TEMPERATURE CNOTROL
PROGRAMMING DAILY SCHEDULE FOR THE UNIT
PROGRAMMING INSTRUCTIONS
SPECIFICATION SHEET
MAINTENANCE MANUAL
DRAIN VALVE
WATER SCALE INHIBITOR
WATER INLET VALVE
POWER FLUSH VALVE
THERMOSTAT
16
18
18
19
19
19
23
25
27
4
5
6
8
2
2
3
4
11
12
13
30
31
31
34
35
38
42
1
INSTALLATION MANUAL
COMMERCIAL STEAM GENERATOR
EXECUTIVE SERIES (ES) 1 UNIT FOR 1 ROOM
INTRODUCTION
Steam Sauna manufactures steam generators for any steam bath need. They are the result
of many years of continued research. Our large commercial units are manufactured to rigid quality standard. We also custom build for specialized applications e.g. yachts, Recreational
Vehicles (RV’s), executive fitness rooms etc.
Your Steam Sauna Commercial generator has been factory tested for a minimum of 8 hours and is both C.S.A. approved and U.L. listed. This assures consistent quality and safety control. The ES series steam generators are custom built to your particular requirements; therefore your unit may not be equipped with all the features described in this manual. Contact your manufacturer for additional information or troubleshooting instructions.
SAFETY TIPS
1) Read all instructions in this guide prior to installing your steam generator.
2) Always ground the unit properly.
3) Make sure there are no restrictions in the steam line(s) (existing lines).
4) Never install valves or have other obstructions in the steam lines (e.g. kinks). (new installation)
5) Always turn off the electrical supply and the water before doing any work on the unit.
6) Install the steam heads approximately 6"-12" from the floor. If possible, under the benches or in another location away from peoples feet and legs as they are extremely hot and could cause injury.
7) Always ask qualified trade people to install or service your unit.
2
3
4
INSTALLATION INSTRUCTIONS
All units operate at atmospheric pressure. NEVER install valves or other obstructions in the steam lines To do so may cause damage to the unit, malfunction or personal injury.
Always use copper pipe with copper or brass fittings. The use of black or galvanized pipe will cause staining in the steam room.
Always use qualified trades people for the installation of this unit.
Observe and follow all instruction tags on the machine.
STEP 1. LOCATING AND INSTALLING THE UNIT
1. The commercial steam generator should be located within maximum 50 ft. of the steam room.
2. It must be located in a clean, dry location (e.g. mechanical room). It is not designed to operate in a location that is wet, damp or may get splashed with water or chemicals which could cause a shock hazard and will cause serious damage to the unit voiding all warranties.
3. Before installing the unit, have in mind that you need water line and drain hole close to the unit, also you will need to run power line to the unit.
4. All areas that may be exposed to frost or high temperature must be avoided e.g. attics or unventilated rooms where temperature can reach 120
0
F (50
0
C) or more.
5. The steam unit should be shelf or bench top mounted in an area that allows easy service access. We recommend a shelf height of 36” – 45”. Installation inside the wall or under the ceiling is not recommended.
6. The unit must always be installed on a flat and level surface with the steam outlets and electrical junction box at the top. Do not set the unit into a sealed frame.
7. Face the front (access panel) out from a wall so that it may be readily removed to access the fuses and other components of the unit for maintenance purposes. Allow a minimum of 4” to 8” clearance from the wall on each side of the unit for easy access and ventilation. NEVER mount the unit with one (1) side against a wall.
5
8. Always mount the unit on flat and level surface. Do not set into an external frame.
STEP2. PLUMBING
All units are supplied with factory equipped compression connections and unions. Always use these connectors. Use the following table to select proper copper pipe sizes for different lines, and then follow the instructions on each line connection:
Pipe size
Lines
1”- ¼”
(Also see page 30)
Line
Power
Flush Line
1” ¼” ½”
2-1. INSTALLING THE STEAM LINES
The steam outlets are two 3/4" copper pipe compression fittings on top of the unit, which you will immediately expand into a 1" line. Run the steam lines from the steam outlets to steam rooms. Always install the steam lines so they drain back to the machine and/or to the steam heads. Never have a low spot that will accumulate condensation.
Insulate exposed steam lines with fiberglass insulation to prevent steam heat loss.
Note: In some models it is required to install a different pipe size. Check specification sheet for more details. However, the minimum size 1” is recommended for models up to
ES-24.
Notes:
1. Do not install any restrictions on the steam lines.
2. For steam line runs of 50 ft or more, contact the manufacturer
3. Never use foam type insulation.
2-2. INSTALLING THE DRAIN LINE
The drain valve is located on the front of the unit and has a ¾” fitting. Using an adapter connect a 1” copper pipe to the drain valve. Run this pipe with a down slope to the floor drain, because the drain system is a gravity drain.
6
2-3. WATER INLET LINE
A sediment filter is installed on the ¼” water inlet line. Use a 1/4” tubing and a manual valve to connect it to the ½” water supply line. If you are connecting to a softener or R.O. system, use the instructions included with this equipment to connect into the water supply. Set up the softener according to specific instructions included with it.
Note: Flush the 1/4" feed line to the floor drain or a bucket prior to connecting it to the
unit; otherwise the copper debris will clog the Water Inlet Valve
2-4. POWER FLUSH LINE
The Power Flush solenoid is installed on the ½” line on the front of the unit. Install a manual shut-off valve on the 1/2" copper pipe, and then use a ½” copper pipe to connect it to the water supply, considering the instructions in step 4-5.
Note: Flush the ½’ feed line to floor drain or a bucket prior to connecting it to the unit, otherwise the copper debris will clog the Power flush Valve.
2-5. WATER SUPPLY LINE
On a ½” copper line install a pressure reducer (35-40 PSI) with a pressure gauge and a manual shut-off valve and connect it to the water supply line.
2-6. STEAM HEADS
The steam head(s) should be located in a safe area away from people’s feet and legs.
They should be as close to the floor drain as possible.
The steam head(s) should be placed between 6" to 12" up from the floor with the slotted side facing down. They may be grouped together or spread throughout the room. Never place the steam head(s) high on a wall.
STEP 3. ELECTRICAL INSTALLATIONS
7
Have a qualified electrician to connect the unit to power source. The wattage and voltage are listed on the serial plate on top of the unit. Make sure that your power source voltage and amperage capacities match the unit.
3-1. POWER CONNECTION
You will need a circuit breaker and a disconnect switch and sufficient length of cable to install the power line. Select the appropriate parts according to the electrical specifications of the steam generator and local electrical codes.
Install a circuit breaker in power distribution panel and connect it to main power.
Run a cable from circuit breaker to a disconnect switch that will be installed on the wall beside the steam generator. Connect L1 (red), L2 (black) and/or L3 (blue) wires in the power junction box to the disconnect switch. Connect the ground terminal in the power junction box to the ground. This machine has no neutral connection.
The power to the unit must be uninterrupted on a day-to-day basis. This allows the control board and timer to function properly.
3-2. INSTALLING THE TEMPRATURE SENSOR PROBE IN THE STEAM ROOM
The
Sensor Probe
should be installed into the wall approx. 3-5” above the door and in
opposite
corner of the room from the steam heads. The sensor head must be exposed
into the room from the wall approx. 1" out, and sealed with rubber or silicon gel. It must always have free air flow around it to sense the current temperature and also to prevent sensing radiant wall heat (Above the door is a good location). A guard that allows free airflow may be placed over the probe.
3-3. CONNECTING THE SENSOR PROBE TO THE THERMOSTAT
The sensor probe is supplied with a 6 ft wire. If the distance between the steam room(s) and the thermostat(s) (which is/are installed on the steam generator) is more than that, run a cable from the thermostat to the sensor probe and connect it to the sensor wires. Use the following table to select the proper wire size:
Wire Gauge Maximum Sensor Cable Length feet (meters)
16 AWG 500 (150)
18 AWG 300 (100)
8
20 AWG
22 AWG
3-4. CONTROL OPTIONS
200 (60)
125 (40)
BASED ON THE USER’S REQUIREMENTS THE UNITS ARE DESIGNED WITH DIFFERENT
CONTROL OPTIONS.
Check your unit Work Order Sheet and the parts that are supplied with unit, and then use the proper instruction in this section. Your unit may not have some or all of the options that are described below.
3-4-1. AUTO SHUT OFF TIMER (30 OR 60 MINUTES)
Install the 30 or 60 minutes timer outside the steam room beside the door. Run a cable (2x14 AWG) from this timer to the power junction box on top of the steam generator and connect it to the labeled wires accordingly.
3-4-2. IN ROOM TOUCH TIMER
Install the touch button inside the steam room into the wall, away from steam and water dripping and accessible for users to use as a Start/ Stop button. Seal the flat side on the wall with silicon sealing. Connect the female end of the connector cable to the rear end of the button and run the cable to the black box (touch timer), which is attached to the steam generator by a flexible conduit. Connect the male end of the connector cable to female connector on the box.
9
STEP 4. SCENT DISPENSER (OPTION)
Read the dispenser Instruction manual that is provided with this document separately before installing.
Scent dispenser pumps the fragrance (wintergreen, eucalyptus…) from the bottle into the steam line. Install the scent pump beside the steam generator and connect its adopter to the power source.
The scent tubing starts from the Fragrance Bottle and its black portion will be mounted on the scent pump wheel. Then it ends to the saddle valve, which will tap into the steam line.
4-1. INSTALLATION INSTRUCTION FOR SELF-PIERCING SADDLE VALVE
Assemble valve body as shown in the following sketch, with piercing pin retracted to the top clamp (2) by rotating valve handle counter-clockwise. clamp.
With rubber gasket (3) in fixed position, clamp the entire assembly firmly to the steam pipe outlet using the bolts, nuts and base clamp provided.
Turn the handle clockwise to pierce the steam pipe and close the valve.
To open valve, turn handle counter-clockwise to desired scent flow.
10
Valve pierces its own hole in copper steam line when turned CW. At the end turn CCW to open the hole made.
Steam
Line
5. WATER SOFTNER (OPTION)
Read the water softener manual that is provided with this document separately before installing.
The water softener will purify the water for the boiling cycle, therefore it will be installed only on ¼” water inlet line. Connect the water softener between the manual shut-off valve and the sediment filter -which is factory installed- on ¼” line. This way you can close the valve and remove the water softener for service, without interrupting the steam generator by using a bypass line.
11
START UP PROCEDURE
There is a boiler tank inside the steam generator that is equipped with several heating elements. In the boiling (steaming) cycle, first the tank fills up with water, then the heating elements will power up, and boils the water. Therefore it is crucial to monitor the start up procedure as follows in this section to make sure the heating elements do not energize before filling the tank. After the boiling cycle finished (at the time which is set by timer) the unit will go to cleaning cycle. In this cycle the unit will be filled with pressured water and drained repeatedly for ½ hour.
1. Boiling (steaming) Cycle
Note: Make sure all solenoid coils are properly installed on all external valves before
proceeding with start up.
1. Turn on water supply and check for leaks on all plumbing connections.
2. Turn the timer that is mounted on the front of the unit to the OFF position.
For mechanical timer: Push the manual ON/OFF lever to OFF position.
For digital timer: Press the ENTER (OVERRIDE) button and verify the OFF sign shows up on the display.
3. Hook a clamp AMP Meter to L1 (red) and turn it on to monitor the amperage during the start up cycle. Turn the breaker and the fuse disconnect switch to the ON position.
4. The amperage is less than 1 Amp.
5. The thermostat display will start flashing.
6. Turn the unit “ON” at the Timer.
For mechanical timer: Push the manual ON/OFF lever to ON position.
For digital timer: Press the ENTER (OVERRIDE) button and verify the ON sign shows up on the display.
7. The amperage is less than 1 Amp.
12
8. You will hear a “click” sound inside the unit, which shows that water inlet solenoid is energized. Water will immediately flow into the tank through 1/4" inlet line. You can verify it by touching the ¼” line to feel the water flow. Depending on the water pressure and unit’s model, tank will fill within 2-5 minutes. You will hear another
“click” and the water will stop.
9. Caution: Up to this point the amperage must always stay less than 1 Amp. If you noticed amperage higher than 1 Amp, turn off the breaker immediately and call the manufacturer for further assistance.
10. After 10 seconds, you will hear a bigger “click” sound that indicates the contactors are engaged. The amperage will jump to the 1 st
stage or 2 nd
stage value, depending on your control options. Read your work order sheet to find the nominal current for your unit.
11. If you have optional controls such as 30-minute timer or in-room-touch-timer, turn them ON to elevate to the 2 nd
stage. You will notice that the amperage is even higher than the 1 st
stage.
12. Unit produces steam in 2 to 8 minutes depending on the kW of your unit and the distance between the unit & steam room. Allow the unit to produce steam for ½ hour and observe the temperature in the steam room and compare it with your thermostat settings. See the operating manual for further information.
13
2. Cleaning (Flush) Cycle
The cleaning cycle will start 10 minutes after the boiling cycle is finished according to the daily schedule that is set to the 24h/7day timer. In this cycle the hot water will be drained from the boiler through the drain valve. Then the boiler will be flushed by the water inlet and the power flush valves and drained through the drain valve several times within ½ hour. To start this cycle manually turn the 24h/7day timer
OFF and observe this cycle for a ½ hour period and make sure that during this cycle you will see the change (from open to close or vice versa) of the following solenoid valves at least once:
1. The drain valve: Drains water from the tank. The first drain is hot water and the other drains are cold water. You can check its function by touching the 1” drain line to feel the water flow.
2. The water inlet valve: On ¼” line fills up the tank. You can check its function by touching the ¼” line to feel the water flow.
3. The power flush valve: On ½” line is fills up the tank. You can check its function by touching the ½” line to feel the water flow or use a screwdriver to check the magnetic pull.
14
BASIC TROUBLESHOOTING GUIDE
Unit does not produce steam connected
Water constantly flows out of the steam head
- Water supply valve is closed
- Timer On/Off turned off
- Thermostat not set properly
- Not Connected properly
- Damage in shipping
- Water Inlet Valve on ¼” line is stuck open by copper debris
- Power flush valve is stuck open by copper debris
- No water level signal to control board
- Turn on water supply
- Turn on power. Check circuit breaker
- Turn it on
- Adjust thermostat to desired temperature
- Check wiring and plumbing
- Contact manufacturer
- Turn the power off, if water didn’t stop, open the valve and clean it up
- Open the valve and clean it up
- See maintenance manual
- Install pressure reducer valve (35-40) PSI on water supply line
Thumping noise on water line
allowed pressure on water supply valve
when unit is
- Water pressure higher than the maximum
running
The unit does
- The timer is not set properly
not drain
-See Timer instructions setting
Breaker trips or blows the fuse on disconnector switch
- Short circuit caused by wrong wiring
- Short circuit caused by water leakage
- Heating elements burnt
Unit heats up
- Drain valve is leaking, causing frequent
but does not
flow of cold water into the tank
produce sufficient steam,
-Check the AMP. Rating on the nameplate or your order sheet and change the breaker
- Check your wiring with the electrical diagram provided with your documents
- Check for water leaks, find the source and tighten the fittings
- Check the resistance on heating elements (see maintenance manual)
- Open drain valve (see maintenance manual) and check for pieces of calcium, clean it up
15
sufficient steam, steam room not hot enough
Steam room is too hot
- Water inlet valve stuck open
- Power flush valve stuck open
- Standby timer is off. Only one stage is engaged
- Sensor location is wrong
- Thermostat is not set properly
- Sensor wiring is wrong or sensor failed
- Open water inlet valve
(see maintenance manual) and check for small pieces, clean it up
- Open water inlet valve
(see maintenance manual) and check for small pieces, clean it up
- Turn the timer ON. Also check for proper connection.
- Displace the sensor to correct location (see installation manual)
- Check the thermostat set points and program it properly (see operation manual)
- Check the sensor wiring
(see installation manual)
16
OPERATION MANUAL
COMMERCIAL STEAM GENERATOR
EXECUTIVE SERIES (ES)
INTRODUCTION TO STEAM GENERATOR FUNCTIONS
This unit is designed and manufactured based on your specific requirements. Each steam generator has it own function, which may operate differently from another steam generator. This section explains different functions on steam generators. Your unit may have some of these functions. Read your order sheet to find out which functions your unit has.
REGULAR 2-in-1 SYSTEM
The unit has two heating stages. When the thermostat is calling for heat, both stages get engaged and produce strong steam until the temperature SETPOINT is reached in the steam room. Then one stage, which is controlled by thermostat, goes off and the other stage keeps on producing steam (steady but slow).
SPECIAL 2-in-1 SYSTEM
This system also has two stages, but the thermostat controls each stage individually.
The SETPOINT for the top thermostat is slightly higher than the bottom thermostat.
When the lower SETPOINT in bottom thermostat is reached, one stage goes off, but the other stage keeps on steaming until the higher SETPOINT in top thermostat is reached.
STAND BY SYSTEM
The unit only produces steam on demand. When the user turns on the 30 minute mechanical or Electronic TOUCH timer the unit starts producing strong steam until one of the following happens:
Timer times out (turns off)
Temperature SETPOINT is reached
Then the unit stops producing steam and stands by for the next request. Only the
BINARY SETTING
first heating cycle in the daily schedule will take about 5 minutes longer than the consequent next cycles to produce steam.
17
The thermostat implements two different sets of SETPOINTS to control the temperature in the steam room. The regular SETPOINT is about 117°F (47°C) and the secondary SETPOINT is less than by OFFSET value, 25°F (15°C):
Secondary SETPOINT = Regular SETPOINT – OFFSET Value
= 117°F – 25°F = 92°F
A 30 minutes dial timer or Electronic Touch timer activates the transition from
Regular SETPOINT to Secondary SETPOINT and vice versa.
INTRODUCTION TO PROGRAMMING
The steam generator operates based on the thermostat and the 24h/7day timer setting. The thermostat controls and maintains the desired temperature in the steam room (which can be set by user) and the timer controls the daily operation schedule for the unit (e.g. start time and shut down time). Users according to their desired application can set these controls. The thermostat and timer programming instructions is explained below.
THERMOSTAT FUNCTIONS AND SET UP
Depending on the model and features, the steam generator might be equipped with one or both of the following thermostats, which are fully programmable:
A419 Johnson Controls digital thermostat
RANCO ETC digital thermostat
The programming instructions for both thermostats will be explained in the following sections.
The A419 Control Functions
Setpoint (SP) establishes the temperature value at which the steam is switched on or
off. Setpoint range is –30 to 212°F or –34 to 100°C (in 1-degree increments).
18
Differential (DIF) establishes the difference in temperature between the ON and OFF
cycle. For example if the SP=117°F and the DIF=3 steam stops at 117°F and comes back ON at 113 which is (117-3-1=113). The differential is set relative to Setpoint and may be set from 1 to 30 °F or °C (in 1-degree increments).
Anti-Short Cycle Delay (ASD) establishes the minimum time that the unit stays in
OFF cycle before the next ON-cycle. The ASD does not allow the unit to re-energize until the programmed time delay has elapsed. The delay is activated when the control is first turned on and every time an ON-cycle ends. When the delay is activated, the LCD alternately flashes the sensor current temperature reading and
ASD. The anti-short Cycle Delay range is 0 to 12 minutes (in 1-minute increments).
Temperature Offset (OFS) establishes a secondary Setpoint value that may be
invoked to control the steam or temperature in the room when a 30-minute timer or in-room-touch timer is activated in the steam room. Offset range is 0 to 50 °F or °C
(in 1-degree increments). For example, if OFS=25F and SP=117F, with the timer in
ON position, the unit operates at normal setpoint which is 117; but when the timer turns off, the unit operates at 92F which is (117-25) and the display shows a BIN sign as long as the timer stays “OFF”.
Sensor Failure Operation (SF) establishes how the A419 control’s output-relay
operates the unit in the event of a sensor or sensor wiring failure. The user may select to keep the unit running (SF=1) or to shut it down (SF=0) after the sensor failed. When the control detects a sensor circuit failure, the LCD flashes SF alternately with OP (if the sensor circuit is open), or SH (if the sensor circuit is shorted). Before indicating a failure, the control implements a 1-minute delay, which allows verification of failure condition and avoids nuisance failure indications.
Setpoint
(sp)
Differential
(dif)
Anti-short Cycle
Delay (Asd)
Temperature
Offset
(OFS)
25°F/15°C
Sensor Failure
Operation
(SF)
0 117°F/47°C 1 1
Changing the A419 Control Temperature Units
The A419 control is factory set to display Fahrenheit or Celsius according to the region standards. To change to Celsius, press Up and Down (arrows) simultaneously.
Press them again to display Fahrenheit units. Verify that the control is displaying the desired temperature units before setting the Setpoint.
19
Setting the A419 Control Setpoint Value
To view and adjust Setpoint, follow these steps:
1. Press and hold MENU (about 2 seconds) until the display flashes SP.
2. Press MENU again to display the existing setpoint value.
3. Press Up or Down (arrows) to change the setpoint value.
4. Press MENU again to save the new value. The display returns to the current sensor temperature.
Note: If no setup entry is made for 30 seconds, the control reverts to the (normal)
temperature display.
IMPORTANT: If MENU is not pressed after changing the setpoint value, the control
reverts to the previously programmed setpoint value.
Temperature Offset Indicator
- 10
BIN
° F
♠
Temperature Units Indicator
Operating Mode Indicator
MENU
Liquid Crystal Display
V U
MENU Button
UP Arrow Button
Output Relay Status Indicator LED
Figure1: Liquid crystal display,
Touchpad, and LED indicator
DOWN Arrow Button
Setting the other A419 Control Functions
To set the Differential, Anti-short Cycle Delay, Temperature Offset, or Sensor Failure operation, use the following method.
1. Press and hold MENU until the display changes to flashing SP. (This takes about 2 seconds.)
2. Press Up or Down (arrows) repeatedly until the desired function is displayed.
(See Table 3.)
3. Press MENU to display the function’s current value.
4. Press Up or Down (arrows) until the desired value is reached.
5. Press MENU to save the new value. The display returns to the current sensor temperature.
IMPORTANT: If MENU is not pressed after changing the settings, the new settings
are not saved and the control reverts to the previously programmed setting values.
20
Notes:
If no setup entry is made for 30 seconds, the control reverts to the (normal) temperature display.
Any saved A419 control setting is non-volatile and remains in the control’s memory during power interruptions.
The sum of the Setpoint and Differential values must be within the Setpoint range, or the control may not function properly.
IMPORTANT: Do not set Setpoint and Differential values which (when totaled) fall out of
A419 control’s Setpoint range (-30 to 212°F [-34 to 100°C]). The control will not function properly if these values are outside of the control’s Setpoint range.
Table 1: Display Symbols, Control Function, Ranges, Units, Values, and Factory Settings
Display
Symbols
SP
Control
Function
Setpoint*
DIF
ASD
OFS
SF
F or C
Differential*
Anti-short Cycle
Delay
Temperature
Offset
Sensor Failure
Operation
Temperature
Units
Range – Units/Value
-30 to 212 – °F
(-34 to 100 – °C)
1 to 30 – (°F or °C in 1degree increments)
0 to 12 – (in 1-minute increments)
0 to 50 (°F or °C in 1degree increments)
0 = unit will shut down after sensor failure
1 = unit keeps running after sensor failure
°F (Fahrenheit) or °C
(Celsius)
Factory
Settings
117F
47C
1
1
25F
15C
0
F for USA
C for Canada
21
RANCO ELECTRONIC TEMPERATURE CONTROL
A steam generator with 2-in-1 system has 2 separate stages of heaters. Initially, both stages are energized to raise the temperature in steam room up to the setpoint (S2), then the second stage disengages and only first stage stays on to keep the room full of steam by producing continuous flow of steam (S1). The operator can control the function of both stages by programming ETC thermostat dual setpoints (S1 and S2).
In order to keep the room full of steam, S1 (which controls the first stage) should be set higher than S2; for example if S2 is set at 117°F(47°C), then S1 should be set at
125°F(52°C) or higher.
ETC has seven values that has to be programmed:
Display
Symbols
1
F/C
Description
Fahrenheit or Celsius reading selection on the display
2
3
S1
DIF1
First stage temperature setpoint.
The first stage turns off after reaching to S1.
First stage differential; e.g. the temperature drop by which the first stage turns back to ON state, after reaching to the setpoint(OFF state)
4
C1/H1
First stage Cooling or Heating mode
5
S2
Second stage temperature setpoint. The second stage turns off after reaching to S2.
6
DIF2
Second stage differential; e.g. the temperature drop by which the second stage switches back to ON state, after reaching to the setpoint(OFF state).
7
C2/H2
Second stage Cooling or Heating mode
Range
-30°F to 220°F
1°C to 105°C
1 to 30
-30°F to 220°F
1°C to 105°C
1 to 30
Factory
Default
F for US
C for Canada
125°F
52°C
1
Must be set as H1
117°F
47°C
1
Must be set as H2
22
Programming Steps
1. Press the SET key once to start programming. The display will show current selection for F (Fahrenheit) or C (Celsius). Press © or ª key to toggle between F or C designation.
2. Press the SET key again to access the stage 1 setpoint (S1). The display will show the current value of S1. Press © or ª key to increase or decrease the value of S1. Should be set at 125°F (52°C).
3. Press the SET key again to access the stage 1 differential (DIF1). The display will show the current value of DIF1. Press © or ª key to increase or decrease the value of DIF1. Should be set at 1.
4. Press the SET key again to access the stage 1 cooling or heating mode selection. The display will show the current mode, either C1 for cooling or H1 for heating. Press © or ª key to select H1 for heating mode.
5. Press the SET key again to access the stage 2 setpoint (S2). The display will show the current value of S2. Press © or ª key to increase or decrease the value of S2. It should be set at 117°F (47°C).
6. Press the SET key again to access the stage 2 differential (DIF2). The display will show the current value of DIF2. Press © or ª key to increase or decrease the value of DIF2. It should be set at 1.
7. Press the SET key again to access the stage 2 cooling or heating mode selection. The display will show the current mode, either C2 for cooling or H2 for heating. Press © or ª key to select H2 for heating mode.
8.
Press the SET key once more and programming is complete. The display will show the current steam room temperature, and the stages that are energized, i.e. S1 or S2 or both or none.
Lockout Switch
The ETC is provided with a lockout switch to prevent tampering by unauthorized personnel. When placed in the LOCK position, the keypad is disabled and no changes to the settings can be made.
To access the lockout switch, disconnect the power supply and open the ETC front panel, the lockout switch is located on the inside cover.
23
PROGRAMMING DAILY SCHEDULE FOR THE UNIT
EC7000 TIMER
INTRODUCTION
The EC7000 is a single-channel, electronic timer that controls the unit with a timeof-day schedule. The control may be utilized as a 24-hour or 7-day control. As a 24hour control the same ON/OFF program is utilized each day of the week (Saturday and/or Sunday, or any other day may be skipped). When schedules vary from day to day, the 7-day programming capability allows a different schedule for each day of the week. With 16 setpoints available, these time controls provide programming versatility.
SPECIFICATIONS – PROGRAMMING CAPABILITIES
16 Setpoints – A setpoint defines the type of event (ON or OFF) as well as the time
and day(s) on which the event will occur.
24-Hour or 7-Day programming – Allows the same schedule or a different schedule
for each day of the week.
Selectable Clock Format – 12-hour (AM/PM) or 24-hour format.
Manual Override – Reverses current output state; begins immediately when initiated
and remains until overridden again or until next setpoint is reached.
POWER OUTAGE CARRY-OVER
The program and time-of-day are maintained during a power outage for a minimum of seven (7) days. A built-in special capacitor eliminates the inconvenience of battery replacement.
ENVIRONMENTAL
EC7000 should be mounted indoors in an environment that is free from excessive contaminants such as oil, moisture and dirt. EC7000 is suitable for both indoor and outdoor use.
24
KEYPAD DESCRIPTION
AM TU ON
12:34 y
RUN – Returns timer to the RUN mode.
The timer will only control the load when in the RUN mode.
MODE – Advances from one programming mode to the next. The order
OVR of programming modes is as follows:
Clock Format select, Run, Set Time and
Setpoint Programming. After the last mode, the control will loop back to the
RUN MODE
X
ENTER
Run mode.
X
- Changes the parameter value that currently being programmed.
UNDERSTANDING SETPOINTS
ENTER – In all programming modes, what is shown in the display is what exists in memory. Pressing the Enter key simply advance to the next parameter to be programmed. (i.e. hours to minutes).
Before you begin programming, make sure you understand setpoints. A setpoint defines the type of event – ON or OFF – as well as the time of the event and the day(s) on which the event will occur. For example, to turn the unit ON at 5:00 AM each day of the week, a setpoint like this would be required: ON, 5:00 AM, Mon-Tue-Wed-Thur-
Fri-Sat-Sun. Setpoint programming provides built-in skip-a-day capability; to skip any day(s), simply do not add the day(s) to the setpoint. You must set the timer as it shuts down the boiling cycle for at least 1 hour in any 24 hours period.
As a simple example, consider the following schedule for turning the unit ON and
OFF:
SUN: Unit is OFF.
MON through FRI: Unit is ON at 5:30 AM, OFF at 10:30 PM
SAT: ON at 5:30 AM, OFF at 12:30 PM
Note: When programming, “NO” on the display means no event is required at that setpoint
on that particular day. “YES” means an event is required (either On or OFF) at that setpoint on that day. The sample schedule would be arranged as follows:
1 st
setpoint: SUN: NO, MON through SAT: YES; ON; at 5:30 AM
2 nd
setpoint: SUN: NO, MON through FRI: YES, SAT: NO; OFF; at 10:30 PM
3 rd
setpoint: SUN through FRI: NO, SAT: YES; OFF; at 12:30 PM
Mark your setpoint work sheet as following table and proceed to grogram the unit using the programming instruction.
25
Program
No.
Day of Week Type of Event
1 S (M) (T) (W) (T) (F) (S) ON OFF
2 S (M) (T) (W) (T) (F) S
3 S M T W T
ON OFF
F (S) ON OFF
Time
5:30 AM
10:30 PM
12:30 PM
YOUR SETPOINT WORK SHEET (Mark with your schedule)
Day of Week Type of Event
1 S M T W T F S ON OFF
2 S M T W T F S ON OFF
3 S M T W T F S ON OFF
4 S M T W T F S ON OFF
5 S M T W T F S ON OFF
6 S M T W T F S ON OFF
7 S M T W T F S ON OFF
8 S M T W T F S ON OFF
9 S M T W T F S ON OFF
10 S M T W T F S ON OFF
11 S M T W T F S ON OFF
12 S M T W T F S ON OFF
13 S M T W T F S ON OFF
14 S M T W T F S ON OFF
15 S M T W T F S ON OFF
16 S M T W T F S ON OFF
Time
PROGRAMMING INSTRUCTIONS
These timers initially power up in the Clock Format Select mode. This mode is only accessible once. If the clock format needs to be changed, the timer will have to be reset. To reset the timer, insert a pointed object into the reset hole to the right of the display.
CLOCK FORMAT SELECT mode
STEP KEY
1.
DESCRIPTION
Apply power to timer. Control displays 12 Hr, indicating 12-hour clock format.
2.
X
Toggles between 12 hour (AM/PM) and 24 hour
(17:00 = 5:00 PM) clock formats. Choose the format desired.
3. ENTER Advances to RUN mode.
SET TIME mode
STEP KEY DESCRIPTION
26
1. MODE Advances to SET TIME mode. Control displays time with hours flashing. TOD is also displayed to indicate that Time-of-Day is being set.
2.
X
3. ENTER
4.
X
Advance to current hour.
Minutes begin flashing.
Advance to current minute.
5. ENTER
6.
X mode below.
Day of week begins flashing.
Advance to current day of week. Then go directly to Setpoint Programming
SETPOINT PROMGRAMMING mode
STEP KEY DESCRIPTION
1. MODE mode. The timer displays “1” at bottom of display and “_ _: _ _”. The “1” indicates that the first of 16 setpoints is being programmed. The dashes indicate that this setpoint is clear.
Display shows “SU” and “no”. This indicates that Sunday is not included in the setpoint.
3.
X
Displays toggles between “YES” and “no”. If the event is desired for the particular day select “YES”, if not select “no”
.
Display shows “MO” and “no”. Repeat steps 3 and 4 to select which day(s) to include in the setpoint. After programming Saturday, the display will show the setpoint with the hours flashing. Dashes in the hour location indicate that the setpoint is still clear.
5.
X
Advance to desired hour.
7.
X
Advance to desired minute.
9.
X
Display toggles between ON and OFF event types. Choose the event desired.
10. ENTER additional setpoints. When all setpoints required are programmed, advance to step 11.
11. RUN
Return to the RUN mode when programming is complete.
NOTE: Once programming has been completed through step 11, the display should show
correct Time-of-Day, Day-of-Week and Setpoint status (ON/OFF). If present load status should be an ON event, but shows as an OFF event, press ENTER/OVR to turn load ON and to initiate programmed schedule.
27
TO REVIEW SETPOINTS
STEP KEY
1.
DESCRIPTION
MODE Advances from RUN mode to SET TIME mode (TOD displays)
2. MODE Advances from SET TIME mode to SETPOINT PROGRAMMING mode. The control will display the first setpoint ( 1 displays at bottom). To modify the setpoint, go to step 2 of the SETPOINT PROGRAMMING mode instructions.
3.
4.
X
RUN
Advances through the remaining setpoints.
Returns to RUN mode when done reviewing setpoints.
OVERRIDE
Manual override reverses the current output state. Loads that are ON turn immediately
OFF; loads that are OFF turn immediately ON. The timer displays OVR to indicate that the current load state is the result of an override. The override remains in effect until overridden again or until the next setpoint is reached. To initiate override, press OVR
(ENTER) key while in the RUN mode.
NOTE: After an override has been initiated, the OVR will display until the next programmed
setpoint is reached, even if the timer is overridden again. Display will show if the load is on or off.
28
SPECIFICATION SHEET
STEAMASTER
®
COMMERCIAL STEAM GENERATOR
MODEL CU
1 PHASE
OUTLET
AMPS AMPS
208/240 21 / 18 36 / 32
ES - 7.5
375 7.5
¾"
480/600 9 / 7 16 / 13
208/240 25 / 22
ES - 9
500 9 1"
480/600 11 / 9
ES - 12
750 12 1"
208/240 33 / 29
480/600 14 / 12
44 / 36
19 / 15
58 / 50
ES - 15
1000 15 1"
208/240 42 / 35
480/600 18 / 15
ES - 18
1250 18 1"
208/240 50 / 43
480/600 22 / 18
25 / 20
72 / 63
32 / 25
87 / 75
38 / 30
ES - 21
1500 21 1"
208/240 58 / 51 101 / 88
480/600 25 / 21 44 / 35
ES - 24
1750 24 1"
208/240 67 / 58 116 / 100
480/600 29 / 24 50 / 40
208/240 83 / 72 145 / 125
ES - 30
2000 30 1 -
¼"
480/600 36 / 30 63 / 50
208/240 100 / 87 173 / 150
ES - 36
2250 36 1 -
¼"
ES - 42
ES - 48
ES - 60
2400 42 1 -
2685 48 1 -
3285 60 1 -
¼"
¼"
¼"
480/600 44 / 35
208/240 100 / 87
480/600 51 / 41
208/240 100 / 87
480/600 59 / 47
208/240 100 / 87
480/600 73 / 58
75 / 60
MAX. DIM OPERATING
L X W X H WEIGHT
90 to 105 lb
27"X 9"X 24"
100 to 115 lb
90 to 105 lb
27"X 9"X 24"
100 to 115 lb
95 to 110 lb
27"X 9"X 24"
100 to 115 lb
95 to 110 lb
27"X 9"X 24"
100 to 115 lb
95 to 110 lb
27"X 9"X 24"
100 to 120 lb
95 to 110 lb
27"X 9"X 24"
100 to 120 lb
95 to 110 lb
27"X 9"X 24"
105 to 120 lb
100 to 115 lb
27"X 9"X 24"
110 to 125 lb
32"X 14"X 24"
130 to 150 lb
130 to 150 lb
32"X 14"X 24" 130 to 150 lb
32"X 14"X 24" 130 to 150 lb
32"X 14"X 24" 130 to 150 lb
For room size over the above range, contact manufacturer Toll free: 1 800 354 8462
29
MAINTENANCE MANUAL
DRAIN VALVE
INSTRUCTION FOR CLEANING THE DRAIN VALVE V8043
Removing the Power head
1. Turn off the main power supply to the steam generator to prevent electrical shock or equipment damage.
2. Push the manual opening lever to the “MAN. OPEN” position (see Fig.4-A).
3. Remove the front screw securing the cover to the power head and lift the power head off (see Fig.4-B).
4. Use a flat screwdriver to loosen the 2 screws securing the power head to the valve body and lift power head off the valve body (see Fig.6).
5. Use a 5/16 wrench or ratchet to remove the 4 hex-nut screws securing the adapter plate to the valve body and lift off the adapter plate using a flat screwdriver (see
Fig.5).
Cleaning the Boiler and the Valve Body
Now that the valve is open, you can flush the tank in order to remove any other sediment or calcium pieces inside the boiler. Follow these instructions:
1. Insert the O-ring back on the valve body, and then replace the adapter plate upsidedown, so the ball will stick out of the valve body. This is to open the valve passage, so the sediment will pass through easily.
2. Remove the power head and place it on a location where it is secure from water.
3. Turn on the main power breaker and turn off the front timer after 5 seconds. After 10 minutes the unit will start cleaning cycle, which will continue for 30 minutes.
4. To repeat the cleaning cycle turn on the timer, then turn it off after 5 seconds.
5. After the cleaning cycle finished, turn off the main power to the unit.
6. Remove the adapter plate and clean the valve body of any piece of sediment that is left inside the valve.
Installing the Power Head
1. Insert the O-ring on the valve body, only if you have removed it (see Fig.5).
30
2. Place the metal plate with the rubber plug on top of valve body. Make sure the 3 guide pins on the underside of the metal plate fit into the recesses on the valve body.
3. Secure the metal plate to the valve body with the 4 hex-nut screws (see Fig.5). 2 of the screws have heads with recessed threads to insert screws for mounting the power head, insert them in the larger screw openings.
4. Make sure that the manual opening lever is locked in the “MAN. OPEN” position. Fit the power head onto the valve body, ensuring that the shaft seats correctly (see Fig.6). The power head should be aligned so that the manual opening lever is at the port “A” end of the valve body. Secure the power head to the valve body with the 2 screws.
5.
Replace power head cover and secure it with 1 screw.
6. Turn on the main power and test the unit in both boiling cycle and cleaning cycles.
31
33
34
WATER INLET VALVE 3121 Parker / 32L8DGM Peter Paul
MAINTENANCE
Note: Depending on water conditions and filtration, it may be required to periodically clean and/or replace worn components.
CAUTION: Do not expose plastic or rubber
components to any type of commercial cleaning fluid.
Parts should e cleaned with a mild soap and water solution.
DISASSEMBLY INSTRUCTIONS
(See Figure 1 & Figure 2)
WARNING: Depressurize system and turn off
electrical power to the valve before attempting repair. /
The valves need to be removed from the line for
disassembly or repair.
To remove the coil: Unscrew the nut on top of the sleeve. The enclosure, coil and flux plate or integrated coil may now be removed.
To disassemble the pressure vessel:
Disassembly is best done as follows:
Hold the valve body installed in the system with a channel lock to prevent bending the existing piping.
Placing pliers on the sleeve of the valve in the location shown in Figure 1 turn the sleeve counterclockwise to unscrew the sleeve from the body of the valve. The pliers should be positioned 90º from the centerline of the sleeve to avoid sleeve damage. Extract the plunger
& spring from the sleeve. Wash the sleeve cavity and valve body and remove any sediment or rust.
Replacement parts: When ordering replacement parts, specify valve complete number and voltage as noted on the valve nameplate or label.
CAUTION: Rectified coils:
The 3121 Parker solenoid coil contains solid state components that prevents from reading the actual resistance of the coil. But the 32L8DGM Peter Paul resistance should read about 780 Ohms.
REASSEMBLY INSTRUCTIONS (See Figure 2)
Insert the O-ring seal onto the body and make certain that it seats completely flat inside the body.
Assemble plunger spring to plunger assembly if necessary and insert the plunger into the sleeve assembly with the lower and exposed.
Carefully thread the sleeve assembly with the plunger inside into the body, and tighten the sleeve assembly with a torque of 30 – 40 inch pounds.
Place the flux plate, coil, and enclosure onto the sleeve, and tighten the sleeve assembly with the top nut using a torque of 15 – 30 inch pounds.
35
TROUBLE SHOOTING
PROBLE PROCEDURE
Valve fails to operate
1. Check electrical supply with voltmeter.
Voltage should agree with nameplate or label rating at the valve.
2. Check coil with ohmmeter for shorted or open coil.
3. Verify supply pressure is equal to or less than nameplate rating.
Valve is sluggish or inoperative – electrical supply and pressure check out.
1. Disassemble valve operator (see disassembly instructions). Clean extraneous matter from inside valve – the plunger must be free to move without
External leakage at sleeve to body joint.
Internal leakage at sleeve port or body port, energized or de-energized. binding.
1. Check that sleeve is torqued to the body with 30 – 40 inch pounds and that O-ring seal inside the body is not damaged.
1. Remove sleeve. Examine surface of rubber seals in the bottom and top of the plunger.
Clean or replace plunger as required.
2. Inspect orifices in the body and sleeve for nicks. Damage may require installing a new valve if problem not solved by replacing the plunger.
3. The return spring must not be broken.
36
37
POWER FLUSH VALVE
Depending on service conditions, fluid being used, filtration, and lubrication, it may be required to periodically clean and/or replace worn components. See
Disassembly Instructions.
Caution:
Do not expose plastic or elastomeric materials to any type of commercial cleaning fluid. Parts should be cleaned with a mild soap and water solution.
DISASSEMBLY INSTRUCTIONS
Warning:
Depressurize system and turn off electrical power to the valve before
attempting repair. The valve body need not be removed from the line.
To remove the coil assembly
For both ordinary and hazardous location constructions, unscrew the nut on the top of the coil assembly. The wave washer and coil assembly can now be removed.
To disassemble the pressure vessel
Caution: Do not use a pipe wrench directly on the sleeve tube.
For general cleaning and internal component replacement, there is no reason to remove the sleeve from the valve cover. Unscrew the four (4) cover screws. The diaphragm retainer/plunger assembly, return spring, diaphragm and O-ring can now be removed. On anti water hammer valves the speed control feature can also be removed at this time.
Replacement Parts
When ordering replacement parts kits, specify valve number and voltage from nameplate. Parts kits are available for each valve. Parts included in each kit are marked with an asterisk (*). See exploded views.
38
Reassembly Instructions
Warning:
Valves equipped with Hazardous Location coils must use Hazardous
Location replacement coils only. Verify nameplate data and coil part number before installing the replacement coil.
To reassemble the pressure vessel
Refer to exploded view drawings. Assemble the O-ring into the body groove. For valves with the anti-water hammer feature, replace the O-rings and reassemble the speed control device at this time. Place return spring over plunger and install plunger diaphragm with the diaphragm installed into sleeve cover assembly. Parts must be replaced in the order shown. Tighten screw with a torque of 70-80 in-lbs.
Avoid damaging the main orifice when placing the diaphragm assembly in the valve.
If the sleeve was removed from the cover, tighten the sleeve assembly with an input torque of 260-270 in-lbs.
With the coil assembly repositioned on the sleeve, slide the wave washer over the sleeve and tighten coil assembly nut with an input torque of 43-53 in-lbs.
39
40
POWER FLUSH VALVE TROUBLE SHOOTING
PROBLEM PROCEDURE
Valve fails to operate
Valve is sluggish or inoperative – electrical supply and pressure check out.
1. Check electrical supply with voltmeter. Voltage must agree with nameplate rating.
2. Check coil with ohmmeter for shorted or open coil.
3. Make sure that pressure complied with nameplate rating.
1. Disassemble valve as per the
Disassembly Instructions. Clean out
External leakage at sleeve flange to cover joint. extraneous matter. The plunger must be free to move without binding.
2. Check the diaphragm for tears and for clogged or obstructed bleed hole or pilot orifice. Torn diaphragm must be replaced.
3. Check all springs, if broken, replace.
4. Check that the plunger is attached to the diaphragm assembly.
1. Check that sleeve is torqued to 260 -
270 in-lbs.
1. Check that cover screws are torqued External leakage at flange joint between body and cover. with an input torque of 70-80 in-lbs. If leakage persists replacement of diaphragm assembly or flange O-ring may be required and/or bodies or covers with damaged sealing surfaces may have to be replaced.
External leakage at speed control device. 1. Check O-rings for damage. Replace if necessary.
Internal Leakage 1. Disassemble valve as per the
Disassembly Instructions. Remove extraneous matter. Clean parts in a mild soap and water solution.
2. Examine diaphragm sealing surface for dirt. Remove all foreign particles.
Examine orifice for nicks. Damaged parts must be repaired or replaced.
3. Check plunger return spring. Replace if broken.
41
THERMOSTAT
How to test the Temperature sensor probe on A419 and A319 Johnson
Control Thermostat
1. Using a thermometer take an independent temperature reading at the steam room, where the sensor probe is installed. Find the corresponding resistance value from table.1. Each resistance value corresponds to a temperature value, which is the temperature at the tip of the sensor in the steam room.
2. Using a philips screwdriver remove 4 screws from the front panel of the thermostat.
3. Using a fine flat screwdriver take off the sensor wires:
On A319: from TB3.
On A419: from TB3-2 and TB3-3 pins.
4. Using your Ohmmeter measure the resistance between the sensor wires and compare the reading with the resistance value that you found in step 1 above.
5. If there is a big difference between these values, the sensor is defective and has to be replaced.
6. As a secondary measure, check the continuity on the extension cable from thermostat to sensor, while the sensor is disconnected from the cable. Make sure the cable wires are not short (circuit).
7. As a secondary measure, check the continuity on the extension cable from thermostat to sensor, while the sensor is disconnected from the cable. Make sure the cable wires are not short (circuit).
How to test the sensor probe on ETCDD211000 RANCO Thermostat
1. Follow Step 1. above.
2. Disconnect the sensor wire from the thermostat
3. Follow Step 4, 5 and 6 above.
42
Resistance
A319
Temperature
Fahrenheit Celsius
Resistance
A419
Resistance
ETC. RANCO
52571 -30 -34 650 682800
37116 -20 -29 670 498900
26539 -10 -23 700 347400
19208 0 -18 750 259470
14062 10 -12 780 185190
10408 20 -7 810 141180
7784 30 -1 850 103110
5880 40 4 890 80040
4484 50 10 930 59700
3450 60 16 960 45000
2678 70 21 1000 35820
2095 80 27 1050 27495
1652 90 32 1080 22209
135 220 104 1750 1814
TB3
1
2
3
TB1
Sensor
A419
TB2
Johnson Control
Table.1
Example:
If the sensor temperature in the steam room is 90
0
F/32
0
C and you have an A419 thermostat, you should read 1080 Ohms on your meter.
If you have an A319 thermostat, you should read 1652 Ohms on your meter.
And if you have ETC RANCO, you should read 22209 Ohms on your meter.
43
STEAM SAUNA INC
I S O 9 0 0 1 : 2 0 0 0 C E R T I F I E D
U.S. CANADA
210 South 8 th
Street
Lewiston, NY 14092
1-800-354-8462 1-800-387-0309 www.steam-sauna.com
153 Bridgeland Ave, Unit 13
North York, ON M6A 2Y6 [email protected]

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- 24-hour timer control
- Thermostat for temperature control
- Scent dispenser for aromatherapy
- Adjustable temperature setting
- Automatic drain cycle
- Multiple heating stages
- Safety features for secure operation
- Detailed step-by-step installation guide
- Troubleshooting guide for common issues