NX6 Control Panel Installation Manual

Add to my manuals
48 Pages

advertisement

NX6 Control Panel Installation Manual | Manualzz
NetworX Series
NX-6 CONTROL PANEL
Installation and Startup
© 2002 GE Interlogix
All rights reserved.
Printed in the USA.
These instructions do not purport to cover all details or variations in equipment nor to provide
every possible contingency to be met during installation, operation, and maintenance. If further
information is desired or if particular problems arise that are not covered sufficiently for the
purchaser’s purpose, the matter should be referred to GE Interlogix, Gladewater, Texas, USA.
This document contains proprietary information of GE Interlogix, USA and is furnished to its
customer solely to assist that customer in the installation, testing, operations, and/or
maintenance of the equipment described. This document shall not be reproduced in whole or in
part nor shall its contents be disclosed to any third party without the written approval of GE
Interlogix.
Please refer to the current GE Interlogix product catalog for detailed warranty information.
Main
800-727-2339
Outside the US
903-845-6941
Main Fax
903-845-6811
Web:
www.caddx.com
www.ge-interlogix.com
Technical Support
Tech Support Fax
Sales & Literature
800-727-2339
903-845-8409
800-547-2556
TABLE OF CONTENTS
GENERAL DESCRIPTION............................................................................................... 2
ORDERING INFORMATION ........................................................................................... 2
FEATURE DEFINITIONS................................................................................................ 3
PROGRAMMING THE LED KEYPADS .............................................................................. 8
PROGRAMMING THE NX-6 CONTROL .......................................................................... 10
PROGRAMMING DATA ................................................................................................ 10
LOADING FACTORY DEFAULTS ................................................................................... 12
ENROLLING MODULES AND KEYPADS......................................................................... 12
CONTROL PANEL PROGRAMMING LOCATIONS............................................................ 12
COMMUNICATOR FORMAT SELECTIONS ..................................................................... 13
STANDARD (DEFAULT) ZONE TYPES........................................................................... 18
AUXILIARY OUTPUT EVENT SELECTION ..................................................................... 22
NX-6 PROGRAMMING WORKSHEETS .......................................................................... 29
COMMUNICATOR CODES FOR SLOW SPEED FORMATS ONLY ....................................... 33
APPENDIX 1 REPORTING FIXED CODES IN CONTACT ID AND SIA .............................. 37
APPENDIX 2 REPORTING ZONE CODES IN SIA OR CONTACT ID ................................. 38
APPENDIX 3 EXPANDER NUMBERS FOR REPORTING EXPANDER TROUBLE ................. 39
NX-6 WIRING DIAGRAM ............................................................................................ 40
TERMINAL DESCRIPTION ........................................................................................... 41
LOCAL TELEPHONE COMPANY INTERFACE INFORMATION .......................................... 42
UNDERWRITERS LABORATORIES INFORMATION ....................................................... 43
NX-6 BOARD INSTALLATION...................................................................................... 44
CE NOTICES ............................................................................................................... 45
SPECIFICATIONS ....................................................................................................... 46
GENERAL DESCRIPTION
The NetworX NX-6 represents a new approach to security systems design. Drawing on our experience in the world
market as the largest exporter of USA manufactured controls, we have developed the most flexible, durable, and userfriendly control ever seen in our industry. Featuring sophisticated software which allows up to 40 users to interface with
16 zones, 2 partitions, and a host of integrated fire, access, verification, and input/output modules, all reported with the
most comprehensive and fast SIA and Contact ID formats. The NetworX design allows a fully loaded system to be
housed in one single metal enclosure, establishing for the first time, a logical solution and design response to modular
systems. Up to 3 modules can be added to expand the capabilities of the NX-6. Warranty information is provided in the
Interlogix Product Catalog.
Part #
Description
NX-6-KIT
Includes NX-6 Control, NX-108E LED Keypad, & 16.5V 40VA Transformer
NX-6
NX-6 Control Only
NX-108E
8 Zone LED Keypad
NX-116E
16 Zone LED Keypad
NX-124E
24 Zone LED Keypad
NX-148E
Alphanumeric LCD Keypad
NX-1192E
192 Zone LCD Keypad
NX-1208E
8 Zone LED Keypad
NX-1248E
48 Zone LCD Keypad
NX-1308E
8 Zone LED Door Design Keypad
NX-1316E
16 Zone LED Door Design Keypad
NX-1324E
24 Zone LED Door Design Keypad
NX-1448E
48 Zone Fixed Language Icon Keypad
NX-200 **
Zone Doubling Kit (Includes 100 3.74k and 100 6.98k resistors)
NX-320E **
Smart Power Supply and Buss Extender
NX-408E #
8 Zone Wireless Expansion Module (UL LISTED PART #60-904)
NX-416E #
16 Zone Wireless Expansion Module (UL LISTED PART #60-904)
NX-508E
Eight Output Module
NX-534E **
Two-Way Listen-In Module
NX-540E**
"Operator II" Telephone Interface Module
NX-591E **
Cellemetry Interface
** These products have not been tested and approved by Underwriters Laboratories, Inc.
# These wireless devices are only UL listed for residential applications.
ORDERING INFORMATION
IMPORTANT NOTES:
1. The maximum number of zones available is 16 regardless of the devices added. Information regarding zone
doubling is located on page 7.
2. The 2-wire smoke option is automatically selected when Zone 7 is programmed as a AFire@ Zone Type. Refer to
the Standard Zone Type chart on page 18. If Zone 7 is used as wireless AFire@ zone, the resistor must be placed
on the 2-wire smoke loop. See diagram and terminal descriptions on pages 40 and 41.
Page 2
FEATURE DEFINITIONS
Abort
If enabled, the NX-6 will wait the programmed number of seconds in location 40 prior to sending an alarm. During this
delay time, the "Cancel" LED will flash. To abort the report, type in a code and press the [Cancel] key. The LED will
extinguish. If the report is not aborted within the allotted time, the LED will extinguish when the report is sent. ADialer
Delay@ must be enabled in the ACharacteristic Select@ of locations 110-149. (Loc. 40 and 110-149, pg. 20 and 28)
AC Fail / Low Battery Report / Warning
The NX-6 can be programmed to report AC failure and/or Low Battery conditions to the central station. It can also be
programmed to sound the keypad immediately upon detection of the condition. The AC failure report/warning can be
delayed. (Loc. 37 and 39, pg. 20)
AC Power / Low Battery Sounder Alert
If enabled, the NX-6 will beep the keypad sounder upon arming or disarming if the AC power is missing or a low battery
has been detected. (Loc. 23, pg. 17)
Arm / Disarm Codes
The NX-6 can have 40 four-digit or six-digit codes to arm/disarm the control. All codes must have the same number of
digits. The factory default for User #1 is [1]-[2]-[3]-[4] when using a 4-digit code, or [1]-[2]-[3]-[4]-[5]-[6] for a 6digit code. This code can then be used to enter the new arm/disarm codes. (Loc. 41, pg. 21)
Automatic Arming
NOTE: This feature must be disabled for UL installations
If programmed, the NX-6 will Auto Arm at a specified time. At that time, the keypad will beep for 50 seconds before the
panel arms. The arming process will be stopped if a code is entered on the keypad. The NX-6 will attempt to arm after
every 45 minutes of inactivity until the next Aopening@ time (loc. 52), or until the system is armed. The 45-minute timer
will be extended when there is activity in the building causing the "Ready" LED to turn off and on. The Auto Arming of a
partition can be programmed to be silent. If closing reports are sent, the user code will be 97. (Loc. 23, and 52-55,
pg. 17 and 23)
Automatic Bypass / Instant Arming
When enabled, the control panel can automatically bypass interior follower zones if an exit is not detected during the
exit delay time. Entry delay zones can also be made instant. (Loc. 23, segments 1 and 3, pg. 17)
Auto Cancel / Abort
If enabled, the Cancel and/or Abort features will be automatic (pressing the Cancel button is not required). The Cancel
and Abort features, in locations 23 and 40 respectively, must be enabled to permit this Auto feature to work. For
proper operation of these features, ADialer Delay@ must be enabled in the ACharacteristic Select@ of locations 110-149
Zone Types. (Loc. 41, pg. 21)
Auto Test
This feature will cause the panel to call the central station to report a communicator test at a specified interval. (Loc.
37 and 51, pg. 19 and 23)
Auxiliary Outputs
The NX-6 has four programmable outputs that can be used to activate relays, LED’s, etc. (Refer to the terminal
descriptions on pg. 41 and loc. 45-50, pg. 21-23)
Auxiliary Power Over-current
The NX-6 will illuminate the "Service" LED on the keypad when too much current is drawn from any device powered by
the system. This condition can be reported to the central station. Power down the system to clear. (Loc. 37, pg. 19)
Box Tamper
The NX-6 has an input for a normally closed tamper switch (see terminal drawing). The Box Tamper can be
programmed to report and/or sound the siren and/or the keypad. These terminals can be enabled or disabled in
programming. (Loc. 37 and 39, pg. 19)
Page 3
Built In Siren Driver
The NX-6 has a built-in 112db siren driver. When desired, this built-in driver can be easily converted to a 1-amp voltage
output through programming. (Loc. 37, pg. 19)
Bypass Toggle
This feature will enable the end user to toggle (turn on or off) the bypass of an interior zone with the system armed by
pressing the [Bypass] key. (Loc. 23, pg. 17)
Call Back
When enabled, the control will use the call back phone number to call the download computer before beginning a
download. (Loc. 21, pg. 16)
Cancel
If enabled, the NX-6 will send a "Cancel" report if when the system is disarmed and the [Cancel] button is pressed
within 5 minutes of an alarm. Once the [Cancel] key is pressed, the "Cancel" LED will illuminate until the central station
acknowledges the "Cancel" report. ADialer Delay@ must be enabled in the ACharacteristic Select@ of locations 110-149.
(Loc. 23, pg. 17)
Code Required Options
The NX-6 can be programmed to require a code for bypassing zones and/or initiating a download using the [r]-[9]-[8]
or [r]-[9]-[9] function. (Loc. 23 and 41, pg. 17 and 21)
Communication Formats
The NX-6 can report in multiple formats. It is recommended that you use Contact ID or SIA formats if possible. If you
wish to report to a pager or in a 4+2 format to a central station, you must program each code to be reported. (Loc.
56-83 and 110-149, pg. 24 - 28)
Cross Zoning
This feature requires two or more trips on a zone or zones programmed as "cross zones" within a specified time before
reporting an alarm. During the time between trips, the NX-6 can be programmed to sound the keypad and/or the siren.
The NX-6 can also be programmed to report an alarm after two or more trips on the same zone. (Loc. 37, 39, 40 and
110-149, pg. 19 - 20, 28)
Dual / Split / Multiple Reports
The NX-6 can send communication reports to three different phone numbers for dual, split or multiple reports selectable
by event or partition. (Loc. 4, 10, and 16, pg. 12-15)
Duress Code
If a duress code is programmed the NX-6 will send a duress signal whenever the panel is armed or disarmed with this
code. If open/close reports are sent, the user code will be 254. (Loc. 44, pg. 21)
Dynamic Battery Test
The NX-6 can be programmed to perform a Dynamic Battery Test for a selected duration the first time the panel is
armed or disarmed every day, as well as when the Test Function [r][4] is performed. If the panel is not armed or
disarmed, it will perform the test at midnight. The NX-6 can also be programmed to perform a missing battery test
every 12 seconds. (Loc. 37 and 40, pg. 19 and 20)
NOTE: This feature must be disabled for UL installations
Entry-Guard
This unique low-level arming mode has been developed to reduce the most common source of false alarms. When
armed in the "Stay" mode, the opening of any zones designated as "Entry Guard" will initiate the keypad sounder and
start the entry delay before creating an alarm. All other zones will function as normal. This arming mode will encourage
system owners to use their system more frequently when the premise is occupied. (Loc. 111-149, pg. 28)
Exit Error
If enabled, the NX-6 will send an "Exit Error Report" if an entry/exit zone is faulted at the instant the exit delay expires.
This report will be sent along with the user number that armed the system, if the panel is not disarmed before the entry
delay expires. The alarm report will also be sent. Even if this feature is not enabled, the siren will sound if any
entry/exit zone is faulted at the instant the exit delay expires. (Loc. 23, pg. 17)
Expander Trouble
The NX-6 will report expander trouble to the central station if enabled. This condition will illuminate the "Service" LED
on the keypad even if not reported. NOTE: The keypads are considered expanders. The number of the expansion
devices reported can be found on page 39. (Loc. 37, pg. 19)
Page 4
Fail to Communicate
The NX-6 will illuminate the "Service" LED if a report fails to reach the central station. If enabled, when the next report
is successfully communicated, a “Fail to Communicate” code will be reported. (Loc. 37, pg. 19)
Fire Alarm Verification
When enabled, the NX-6 will verify a Fire alarm by requiring more than one trip on a smoke detector within a specified
time before creating an alarm. (Loc. 40, pg. 20) This feature is not approved for residential use in California.
NOTE: This feature must be disabled for UL installations
Force Arming
When enabled, the NX-6 can be Force Armed with zones violated. Under this condition, if a force armable zone is not
secure, the "Ready" LED will flash. At the end of the exit delay, these zones will become bypassed. If these zones
become secured any time during the arming cycle, they will be unbypassed and active in the system. If "Bypass
Report" is enabled, the force arming zones can be programmed to report bypass when they are Force Armed (default),
or to not report bypass even if "Bypass Report" is enabled. (Loc. 37, and 111-149, pg. 19 & 28)
NOTE: This feature must be disabled for UL installations
Group Bypass
A designated group of zones can be programmed to bypass by pressing [Bypass]- [0]-[Bypass]- [Bypass] prior to
arming. (Loc. 111-149, pg. 28)
Immediate Restore By Zone
The NX-6 can be programmed to send alarm and restore reports as soon as they occur, or wait until the siren time has
expired. (Loc. 37, pg. 19)
Internal Event Log
Up to 185 events can be stored in memory along with the date and time of the event. These events can later be viewed
through downloading or on an LCD keypad. All reportable events report to the log.
Keypad Activated Panics
The NX-6 has three keypad activated panics that will send reports to the central station: Auxiliary 1 (Fire), Auxiliary 2
(Medical), and Keypad Panic. Auxiliary 1 will activate the steady (Fire) siren, Auxiliary 2 will sound the keypad, and the
Keypad Panic can be programmed to be silent or audible (sound siren). (Loc. 23, pg. 17)
Keypad Sounder Control
The NX-6 can be programmed to sound the keypad sounder for certain events. (Loc. 39, pg. 20)
Keypad Tamper
If enabled, the NX-6 will disable the keypad for 60 seconds and communicate a tamper signal to the central station if 30
keypresses are entered without producing a valid code. (Loc. 23, pg. 17)
Keyswitch Arm/Disarm
Any zone on the NX-6 can be programmed as a keyswitch zone. If this is done, a momentary short on this zone will
arm/disarm the control. If opening/closing reports are sent, the user code will be 99. (See "Default Zone
Configurations", pg. 18)
LED Extinguish
This feature will extinguish all LED=s on the keypad, except the "Power" LED, after 60 seconds without a keypress.
Pressing any numeric key will illuminate all LED=s. (Loc. 23, pg. 17)
Local Programming Lockout
This feature will disable programming of all locations or specified locations from the keypad. (Loc. 21, pg. 16)
Log Full Report
A report can be sent to the central station when the event log is full. (Loc. 37, pg. 19)
Lost Clock Service Light
The NX-6 can be programmed to illuminate the "Service" LED when the internal clock has an invalid time due to power
loss. (Loc. 37, pg. 19)
Manual Test
The NX-6 can be programmed to perform a bell and/or communicator test when [r]-[4] is entered while the system is
in the disarmed state. (Loc. 37, pg. 19)
On-Board Zone Disable
All hardwire zones on the NX-6 panel can be disabled to make a completely wireless alarm system. (Loc. 37, pg. 19)
Page 5
Pager Format
Pager formats are 4+3 or 6+3 depending on the number of digits in the account code. The pager will send in this
format: A123456 ABC@ where 1 and 6 are the account number. For report codes that are not zone or user related, the
AA@ will be the first digit of the report code, AB@ will be a zero (0) as a placeholder, and AC@ will be the second digit of the
code. For all other report codes, the AA@ will be the event code while AB@ and AC@ represent the zone or user ID.
(Format Selection chart on pg. 13)
Partitions
The NX-6 can be partitioned into a maximum of two separate systems with distinct reporting codes, user codes, and
operating features for each system. (Loc. 26 - 28, pg. 19)
Program Code
The factory default for the "Go To Program" code is [9]-[7]-[1]-[3] when using a 4-digit code or, if the 6-digit option is
used, the default is [9]-[7]-[1]-[3]-[0]-[0]. The program code can also be used as an Arm/Disarm code. If used as an
Arm/Disarm code, and open/close reports are sent, the user code will be 255. (Loc. 43, pg. 21)
Quick Arm Feature
The NX-6 has a one button "Quick Arm" feature that can be used to arm the system by pressing the [Exit] key or the
[Stay] key on the keypad. If closing reports are sent, the user code will be 98. (Loc. 23, pg. 17)
Recent Closing
If enabled, the NX-6 will send a "Recent Closing Report" to the central station if an alarm occurs within 5 minutes after
the panel is armed. The user number that armed the system will also be sent. (Loc. 23, pg. 17)
Re-exit
The NX-6 has the ability to restart the exit delay for a quick exit without disarming the system by pressing the [Exit]
key while the system is armed. (Loc. 23, pg. 17)
Shutdown
This mode will cause the keypads to turn off all LED=s, except the "Power" LED, and not accept keypresses. (Loc. 21,
pg. 16)
Siren Blast For Arming
The NX-6 can be programmed to give a one-second siren blast when the panel is armed, at the end of the exit delay, or
when the central station receiver acknowledges the closing report. It can also give one blast for remote (keyswitch)
arming and two blasts for remote disarming. (Loc. 37, pg. 19)
Siren Supervision
The NX-6 has a ASiren Supervision@ circuit that will constantly monitor the siren on the NX-6 and can be programmed to
report if the wires are cut. (Loc. 37, pg. 19)
Silent Exit Option
The exit delay can be silenced by pressing [r]-[Exit] before arming the control panel, or when using the re-exit feature.
The exit delay can also be silenced permanently in all partitions. (Loc. 37, pg. 19)
Start/End Programming and End Downloading
A report can be sent when local programming is started and ended. A report can also be sent when a download session
ends. (Loc. 37, pg. 19)
Starting Zone
This feature is used when the keypad zone LEDs must correspond to different control panel zones. Let=s say you have a
16-zone system with two 8-zone partitions. Each partition can utilize an 8-zone LED keypad by programming the
starting zone in each keypad. In this example, zones 1-8 reside in partition #1, and zones 9-16 reside in partition #2.
The starting zone for partition #1 keypads would be 1 and the starting zone for partition #2 keypads would be 9.
(Programming the LED Keypads, pg. 8)
Swinger Shutdown
NOTE: This
installations.
feature
must
be
disabled
for
UL
This feature allows a zone(s) to be automatically bypassed after a specified number of alarms. When a zone is tripped,
the alarm ‘counter’ reflects “1” in memory. If a new (first) alarm is detected in a different zone, the counter remains at
“1”. If an alarm is detected on a previously tripped zone, the count increments to “2”. The ‘counter’ will increment each
time an alarm is detected on a zone with multiple trips. Bypassing will occur on the zone that causes the count to equal
the number programmed in location 38; the ‘counter’ will reset to zero (0); and begin a new trip count where the next
alarm will set the ‘counter’ to 1. If immediate restore is enabled in location 37, the alarms (and restores, if enabled)
will be sent as they occur. If immediate restore is not enabled, a second or subsequent alarm will not be sent until the
siren times out. (Loc. 37 and 38, pg. 19)
Page 6
Telephone Line Monitor
The NX-6 has a Telephone Line Monitor that monitors the voltage and current of the telephone line for a detection of a
faulted phone line. This condition can also be reported to the central station. If the report is enabled, only the
Telephone Line Restore will be reported. (Loc. 37, 39, and 40, pg. 19-20)
Temporal Siren Disable
NOTE: This feature must NOT be disabled for UL
installations.
If disabled, the Fire siren will be steady and Fire Voltage Out will be the same as Burglary (continuous). If enabled, the
Fire siren will be temporal. (Loc. 37, pg. 19)
Tone Sniff Answering Machine Defeat
If enabled, only one call is required to defeat the answering machine. To use this feature you must have a Hayes 1200
Smart Modem or a Caddx 1200 module. From the computer, call the panel as normal. When the answering machine
answers, the panel will hear the tones from the modem and seize the phone line for a download. (Loc. 21, pg. 16)
Two Call Answering Machine Defeat
If enabled, to defeat an answering machine, two telephone calls must be made to the premises. On the first call, let the
phone ring one or two times. The control panel will detect these rings and start a 45-second timer, during which, the
control panel will answer the next call on the first ring. This is not recommended for commercial applications.
(Loc. 21, pg. 16)
Walk-Test Mode
If enabled, entering [r] [Chime] followed by a user code will allow a walk-through zone test where all zones become
silent and local (non-reporting). Each time a zone is faulted, the zone light on the LED keypad will illuminate and the
chime will sound. The number of the faulted zone(s) will be displayed on the LCD keypad. It will also be entered into
alarm memory and the internal log. To exit at any time during this mode, enter a user code. Otherwise the AWalk-Test
Mode@ will automatically exit after 15 minutes. (Loc. 41, pg. 21)
Wireless Sensor Missing/Low Battery
The NX-6 will send a report to the central station when a wireless sensor has detected a low battery or has not reported
to the receiver. The "Service" LED will illuminate when either condition exists. (Loc. 37, pg. 19)
Zone Bypassed Sounder Alert
If enabled, the NX-6 will beep the keypad sounder upon arming if a zone is bypassed. (Loc. 23, pg. 17)
Zone Doubling
This feature allows you to use the six zones on the panel as twelve normally closed zones. When this feature is used,
zone seven cannot be a two-wire smoke zone, and European double E.O.L. configuration cannot be used. THIS
FEATURE DOES NOT INCREASE THE TOTAL NUMBER OF AVAILABLE ZONES BEYOND 16 INCLUDING
WIRELESS. Zones 7 - 12 should not programmed as AFire@ Zone Types when Zone Doubling is used. If one of the
twelve zones must be a fire zone, it must be one of Zones 1 to 6. The corresponding upper zone will become
unavailable. For example, if Zone 6 is a fire zone, then Zone 12 will not be available. (Loc. 37, pg. 19)
Zone Types
The NX-6 has 20 programmable Zone Types that determine how each zone will function and report. The default Zone
Types are listed on page 18. (Loc. 110-149, pg. 28)
Page 7
PROGRAMMING THE LED KEYPADS
This section describes how to program the address and partition of each keypad as well as the options that are available.
The address of the keypad is important because this is how the panel supervises the keypads. The factory default for the
Master code is [1]-[2]-[3]-[4] when using a 4-digit code or [1]-[2]-[3]-[4]-[5]-[6] for a 6-digit code. The factory
default for the "Go To Program" code is [9]-[7]-[1]-[3] for a 4-digit code or [9]-[7]-[1]-[3]-[0]-[0] for a 6-digit code.
SET STARTING ZONE
(Refer to feature definitions)
Step 1
Enter [r]-[9]-[2] [program code]. The "Service" LED will illuminate steady.
Step 2
Enter the starting zone for this keypad (1-48) followed by [r].
SET KEYPAD OPTIONS
Step 1
Enter [r]-[9]-[3] [program code]. The "Service" LED will flash.
Step 2
LEDs 1-8 can now be toggled on/off to enable/disable the functions in the following chart.
Step 3
After enabling/disabling the desired functions press [r].
LED
KEYPAD FEATURE ENABLED
1
Reserved.
DO NOT PROGRAM THIS AT ALL!
2
Enable Silent Keypad option. Silences the entry/exit sounder & chime only.
3
Enable ADing Dong@ sound for chime - If off, chime will be a single tone. (Loc. 40)
4
Enable Keypress Silence option - silences the pulsing keypad sounder for 5 seconds when a key is pressed.
5
Enable Armed Status Suppression - will not allow the keypad to display faulted or bypassed zones when the system is
armed.
6
Enable Panic, Fire, Medical Beeptone - will sound a short beep to verify that the keypress was accepted.
7
Suppresses the "Service" LED - will not allow the "Service" LED to illuminate for any reason. If there is a system trouble,
pressing [r]-[2] will still show the Service menu. (NOTE: For UL installations, the Service LED shall not be
suppressed.)
8
Enable multi-partition viewing - enables temporary viewing of all partitions by pressing [r]-[1]-[partition number].
SET KEYPAD NUMBER AND PARTITION
Step 1
Enter [r]-[9]-[4]-[program code]. The "Service" LED and the "Instant" LED will flash.
Step 2
Enter the keypad number (1-8).
Step 3
Press [r]. The "Instant" LED will illuminate steady and the "Service" LED will remain flashing.
Step 4
Enter the partition number for the keypad. The keypad will automatically exit this mode now.
SET ELAPSED INCREMENTS SINCE LAST AUTOTEST
Step 1
Enter [r]-[9]-[5]-[program code]. The "Service" LED will flash.
Step 2
Enter [100's digit] -[10's digit]-[1's digit]-[#]
SET SYSTEM DATE
Step 1
Enter [r]-[9]-[6]-[master code]. The "Service" LED will flash.
Step 2
Enter ADay of Week@
1 = Sunday
5 = Thursday
Step 3
2 = Monday
6 = Friday
3 = Tuesday
7 = Saturday
4 = Wednesday
Enter AMonth Code@. This must be two digits, i.e. [month 10's digit]-[month 1's digit].
01 = January
05 = May
09 = September
02 = February
06 = June
10 = October
03 = March
07 = July
11 = November
04 = April
08 = August
12 = December
Step 4
Enter ADay Code@. This must be two digits, i.e. [day 10's digit]- [day 1's digit].
Step 5
Enter AYear Code@. This must be two digits, i.e. [year 10's digit]-[year 1's digit].
Page 8
SET SYSTEM CLOCK
Step 1
Enter [r]-[9]-[7]-[master code]. The "Service" LED will flash.
Step 2
Enter AHour Code@. This must be two digits, i.e. [hour 10's digit]-[hour 1's digit].
Step 3
Enter AMinutes Code@. This must be two digits, i.e. [minutes 10's digit]-[minutes 1's digit].
CHANGING USER CODES
Step 1
Enter [r]-[5]-[master code]. The "Ready" LED will flash.
Step 2
Enter the 2-digit user number (always 2 digits, i.e. "03" for user 3). The "Ready" LED will illuminate
steady.
Step 3
Enter the new user code designated for that individual. The "Ready" LED will flash indicating that the
code was accepted. If it rejects the code, the sounder will beep 3 times. Note for NX1300 Series LED
Keypad: The zone lights will illuminate specifying the first digit of the Auser code@. (Lights 1-8 on = code
is blank; lights 1-8 off = A0"; lights 1 and 8 = A9".) Use the up and down scroll keys to view the next
digit or enter a new 4- or 6-digit Auser code@. While using the scroll keys you can change any digit by
entering a new digit. This will advance you to the next digit.
Step 4
If another user code needs to be programmed, return to step 2.
Step 5
Press [#] while the "Ready" LED is flashing to exit the User Code Programming Mode.
ASSIGNING AUTHORITY LEVEL
Step 1
Enter [r]-[6]-[master code]. The "Ready" LED will flash.
Step 2
Enter [2 digit user number] (always 2 digit such as 03 for user 3). The "Ready" LED will illuminate
steady and the "Instant" LED will flash. Refer to the chart below for the description of each LED. Turn the
LED on for the features that you desire.
LED
ATTRIBUTES IF LED 8 IS OFF
LED
ATTRIBUTES IF LED 8 IS ON
1
Reserved
1
Activate output #1
2
Arm Only
2
Activate output # 2
3
Arm Only After Close Window
3
Activate output # 3
4
Master arm/disarm (can program other codes)
4
Reserved
5
Arm/disarm code
5
Arm/disarm
6
Allowed to bypass zones (see location 23)
6
Bypass Zones
7
Code will send open / close reports
7
Open / Close Reporting
8
If this LED is on, LEDs 1-7 will use the chart to the right
8
If this LED is off, LEDs 1-7 use the chart to the left
Step 3
Enter [r]. The "Instant" LED will illuminate steady. This moves you to the partition enable, which tells
the system what partition this user can arm/disarm.
Step 4
LEDs 1-2 illuminate for each partition that the user has authorization for. To change any of these
numbers, press 1-2 to permit or deny access to the user. Example: If LED #2 is lit, then user has
assigned access to that partition. By pressing the [2] key, the LED will go off indicating the user has
been denied access to that partition.)
Step 5
Enter [r]. This returns you back to step 2 above. At this point you may enter another user number to
assign attributes for. Continue this procedure until you have assigned authority levels to all users.
Step 6
Press [#] key to exit the Assigning Authority Level Program.
NOTE: Any master arm/disarm code can add or change a user code if the master code has access to the
same partitions as the code being added/changed. Consequently, when programming the user codes for a
partitioned system, leave at least one code (can be "Go to Program code" if enabled in location 43) with
access to all partitions or you will not be able to add new users. If you desire the end user to be able to add
new codes, you must remove the partition authority from all blank codes.
[r]-[9]-[8]
[r]-[9]-[9]
Pressing [r]-[9]-[8] while the system is disarmed will cause the control to do a callback for a download.
NOTE: A valid user code may be required after [r]-[9]-[8] if enabled in loc. 41.
Pressing [r]-[9]-[9] while the system is disarmed will cause the control panel to seize the phone line for
a download. NOTE: A valid user code may be required after [r]-[9]-[9] if enabled in loc. 41.
Page 9
PROGRAMMING THE CONTROL
ENTERING THE PROGRAM MODE
To enter the Program Mode, press [r]-[8]. At this time, the five function LEDs (Stay, Chime, Exit, Bypass, & Cancel) will
begin to flash. Next, enter the "Go To Program Code" (FACTORY DEFAULT IS [9]-[7]-[1]-[3]). If the "Go To Program
Code" is valid, the "Service" LED will flash and the five function LEDs will illuminate steady. You are now in the Program
Mode and ready to select the module to program.
SELECTING THE MODULE TO PROGRAM
Since all modules connected to the NX-6 are programmed through the keypad, the module you are programming should
be the first entry. To program the NX-6 Control Panel, enter [0]-[#]. The [0] is the module number of the control and
the [#] is the entry key. Other module entry numbers can be found in their corresponding manuals.
PROGRAMMING A LOCATION
Once the number of the module to be programmed has been entered, the "Armed" LED will illuminate, indicating it is
waiting for a programming location to be entered. Any location can be accessed by directly entering the desired
programming location followed by the pound [#] key. If the location entered is a valid location, the "Armed" LED will
extinguish, the "Ready" LED will illuminate and the binary data for the first segment of this location will be shown by the
zone LED's. While entering new data, the "Ready" LED will begin flashing to indicate a data change in process. The
flashing will continue until the new data is stored by pressing the [r] key. Upon pressing the [r] key, the keypad will
advance to the next segment and display its data. This procedure is repeated until the last segment is reached.
Pressing the [#] key will exit from this location, and the "Armed" LED will illuminate again waiting for a new
programming location to be entered. If the desired location is the next sequential location, press the [POLICE] key. If
the previous location is desired press the [FIRE] key. If the same location is desired press the [MEDIC] key. To review
the data in a location, repeat the above procedure, pressing the [r] key without any numeric data entry. Each time the
[r] key is pressed, the programming data of the next segment will be displayed for review.
EXITING A LOCATION
After the last segment of a location is programmed, press [r] to save the data, exit that location, turn the "Ready" LED
off and the "Armed" LED on. To exit before the last segment, press [#]. As before, you are now ready to enter another
programming location. If an attempt is made to program an invalid entry for a particular segment, the keypad sounder
will emit a triple error beep (beep, beep, beep), and remain in that segment awaiting a valid entry.
EXITING THE PROGRAM MODE
When all the desired changes in programming have been made, press the [Exit] key to exit this programming level, and
go to the "Select a Module To Program" level. If no additional modules are to be programmed, pressing the [Exit] key
again will exit the program mode. If there is a module to be programmed, it may be selected by entering its address
followed by the [#] key (see "Selecting the Module To Program" above). The procedure for programming these devices is
the same as for the control panel, except the locations will be for the module selected.
PROGRAMMING DATA
Programming data is always one of two types. One type of data is numerical and can use values from 0 -15 or 0 -255
depending on the location's segment. The other type of data is a feature selection type. Feature selection data is used to
turn features on or off. Use the following procedures when working with these two data types:
NUMERICAL DATA
Numerical data is programmed by entering a number from 0-255 on the numeric keys of the system keypad. To view
the data in a location, a binary process is used. With this process, the LED=s for zones 1 through 8 are utilized, and the
numeric equivalents of their illuminated LED=s are added together to determine the data in a programming location. The
numeric equivalents of these LED=s are as follows:
Zone 1 LED = 1
Zone 2 LED = 2
Zone 3 LED = 4
Zone 4 LED = 8
Zone 5 LED = 16
Zone 6 LED = 32
Zone 7 LED = 64
Zone 8 LED = 128
Example: If the numerical data to be programmed in a location is "66", press [6]-[6] on the keypad. The LED=s for Zone
2 and Zone 7 will become illuminated indicating 66 is in that location (2 + 64 = 66). Once the data is programmed,
press the [r] key to enter the data and advance to the next segment of that location. After the last segment of a
location is programmed, pressing the [r] key will exit that location, turn the "Ready" LED off and the "Armed" LED on. As
before, you are now ready to enter another programming location. If an attempt is made to program a number too large
for a particular segment, the keypad sounder will emit a triple beep, indicating an error, and remain in that segment
awaiting a valid entry. On the LCD keypad, the number in the location will be displayed. For locations with a maximum
of 15, the hexadecimal equivalent will be displayed in parenthesis. Example: 11 (B) or 14 (E).
Page 10
(PROGRAMMING EXAMPLE TO BE INSERTED HERE.)
Page 11
FEATURE SELECTION DATA
Feature selection data will display the current condition (on or off) of eight features associated with the programming
location and segment selected. Pressing a button on the touchpad (1 thru 8) that corresponds to the "feature number"
within a segment will toggle (on/off) that feature. Pressing any numeric key between [1] and [8] for selection of a
feature, will make the corresponding LED illuminate (feature ON). Press the number again, and the LED will extinguish
(feature OFF). You will see that numerous features can be selected from within one segment. For instance, if all eight
features of a segment are desired, pressing [1]-[2]-[3]-[4]-[5]-[6]-[7]-[8] will turn on LED's 1 thru 8 as you press the
keys, indicating that those features are enabled. LCD Keypad Users Note: The numbers of the enabled features
will be displayed. However, the features not enabled will display a hyphen (-). After the desired setting of
features is selected for this segment, press the [r] key. This will enter the data and automatically advance to the next
segment of the location. When you are in the last segment of a location and press the [r] to enter the data, you will exit
that location. This will now turn the "Ready" LED off and the "Armed" LED on. As before, you are now ready to enter
another programming location.
LOADING FACTORY DEFAULTS
To load the factory defaults, enter the program mode using the procedure on page 10, then type [9]-[1]-[0]-[#]. The
keypad will beep 3 times indicating that the loading is in progress. The loading takes about 6 seconds.
ENROLLING MODULES AND KEYPADS
For supervision purposes, the NX-6 has the ability to automatically find and store in its memory, the presence of all
keypads, zone expanders, wireless receivers, and any other module connected to the data terminal. This allows these
modules to be supervised by the control panel. To enroll the modules, enter the Program Mode of the NX-6 control panel
as described on page 10. When the Program Mode is exited, the NX-6 control will automatically enroll the devices. The
enrolling process takes about 12 seconds, during which time the "Service" LED will illuminate. User codes will not be
accepted during the enrolling process. If a speaker is attached to the NX-6, it will click at this time. If a siren or bell is
attached to the NX-6, it will sound for about 1 second. Once a module is enrolled, if it is not detected by the control, the
"Service" LED will illuminate.
CONTROL PANEL PROGRAMMING LOCATIONS
(Various locations intentionally omitted. Attempts to access these reserved locations will cause the
keypad to sound an error beep.)
LOCATION 0
PROGRAMMING PHONE #1
20 segments, numerical data
The first telephone number is programmed in location 0. A "14" indicates the end of the phone number. Delays of 4
seconds can be programmed at any point in the phone number by programming a "13" in the appropriate segment. If
tone dialing is desired, program a "15" in the segment where tone dialing should begin. If the entire number should be
tone dialing, program a "15" in the first segment. Program an A11" for a Ar@, and a A12" for a A#@.
LOCATION 1
ACCOUNT CODE FOR THE PHONE #1
6 segments, numerical data
The account code sent when Phone #1 is dialed is programmed in location 1. Program a A10" in the segment immediately
after the last digit of the account code. If the account code is 6 digits long, program all 6 segments.
LOCATION 2
COMMUNICATOR FORMAT FOR PHONE #1
1 segment, numerical data
Location 2 contains the communicator format used to transmit to the receiver connected to Phone #1. Consult the
instructions for your central station receiver to determine which format is compatible. Select a format from the list on
the following page. If you require a format other than those listed, review the override options described in location 18,
to build the appropriate format. A "15" must be programmed in location 2 in addition to the entries in location 18 in
order to create a special format. If this location contains a "0", the built-in communicator will be disabled, and the NX-6
will function as a local only control.
Page 12
LOCATION 3
DIAL ATTEMPTS/BACKUP CONTROL PHONE # 1
2 segments, numerical data
Segment 1 Dial attempts: Location 3, Segment 1 is used to enter the number of dial attempts (1 to 15 Attempts)
the communicator will make to Phone #1 before ending the notification process. Factory default is "8" and the
communicator will make eight (8) attempts to the first number.
Segment 2 Phone #1 Backup Control: Programming a "0" in Segment 2 of this location will cause the NX-6 to
make the designated number of attempts to Phone #1 and #2 before setting the "Fail To Communicate" condition and
stop reporting. Programming a "1" in this segment will cause the NX-6 to stop trying to communicate after the
designated number of attempts have been made to Phone #1. If a "2" is programmed in this segment, it will cause the
NX-6 to make the dial attempts in increments of two. The first two attempts will be made to Phone #1, the next two
attempts to Phone #2, then repeating until the total number of attempts designated in Segment 1 is completed.
COMMUNICATOR FORMAT SELECTIONS
DATA
FORMAT
DESCRIPTION
0
Local
Communicator is disabled
1
Universal 4+2
Two digit event code 1800hz transmit 2300hz handshake double round parity 40pps
2
3+1 fast (or 4+1)
One digit event code 1900Hz transmit 1400Hz handshake double round parity 20pps
3
Reserved
Reserved
4
Pager
3 digit event code DTMF transmission
5
3/1 or 4/1 slow
1800hz transmit 2300hz handshake double round parity 20 p.p.s. hex capability
6
3/1 or 4/1 slow
1800hz transmit 1400hz handshake double round parity 20 p.p.s. hex capability
7
3/1 or 4/1 fast
1800hz transmit 2300hz handshake double round parity 40 p.p.s. hex capability
8
3/1 or 4/1 fast
1800hz transmit 1400hz handshake double round parity 40 p.p.s. hex capability
9
3/1 or 4/1 fast with
parity
1800hz transmit 2300hz handshake single round w/parity 40 p.p.s. hex capability
10
3/1 or 4/1 fast with
parity
1800hz transmit 1400hz handshake single round w/parity 40 p.p.s. hex capability
11
4+2 express
Two-digit event code DTMF transmission
12
4+2 fast
Two-digit event code 1900hz transmit 1400hz handshake double round parity 20
p.p.s.
13
Ademco Contact ID
DTMF (see pages 37-38)
14
SIA
FSK (see pages 37-38)
15
Custom format
(See location 18, page 16)
LOCATION 4
EVENTS REPORTED TO PHONE # 1
2 segments, feature selection
Phone #1 has two programming locations that are used to select which events are reported to this phone number.
Location 4 is used to select which events are reported to Phone #1. Location 5 is used to select which partitions are
reported to Phone #1. If dual or split reporting is not desired, location 4 should be used to select all events to Phone
#1 and location 5 should be left at the factory default of "0". If dual or split reporting is desired, and the split is based on
the event type (such as alarm, open/close, etc.), location 4 should be used to select only those events that should be
reported to Phone #1 and location 5 should be left at the factory default of "0". If dual or split reporting is desired, and
the split is based on partition, location 4 should be programmed as a "0" and location 5 should be used to select those
partitions that should be reported to Phone #1. If no events should be reported to Phone #1, both locations should be
programmed as "0" (disabling all options). Use Table 1.1 on page 14 to identify the events to be reported for
Phone #1.
Page 13
Table 1.1
Segment 1
1
2
3
4
5
6
7
8
Segment 2
1
2
3
4
5
6
7&8
LOCATION 5
Alarms and Alarm Restores
Opening and Closings
Zone Bypass and Bypass Restores
Zone Trouble and Trouble Restores
Power Fail, Low Battery, Power Restore, and Low Battery Restore
Bell Cut , Telephone Line Cut, Bell Cut Restore, Telephone Line Restore
Test Reports
Start and End programming, Download complete
Zone and Box Tamper and Tamper Restore
Auxiliary Power Overcurrent and Restore
Wireless Sensor Missing and Restore
Wireless Sensor Low Battery and Restore
Expander Trouble and Restore
Fail To Communicate
Reserved
PARTITIONS REPORTED TO PHONE #1
1 segment, feature selection
Location 5 is used when events to be reported to a phone number are based upon the partition regardless of the event.
Program a A1" for Partition 1, and a A2" for Partition 2. If this location is used, location 4 should be "0".
LOCATION 6
PROGRAMMING PHONE #2
20 segments, numerical data
Phone #2 is programmed in location 6. A "14" indicates the end of the phone number. Delays of four seconds can be
programmed at any point in the phone number by programming a "13" in the appropriate segment. If tone dialing is
desired, program a "15" in the segment where tone dialing should begin. If the entire number should be tone dialing,
program a "15" in the first segment. Program an A11" for a Ar@, and a A12" for a A#@.
LOCATION 7
ACCOUNT CODE FOR THE PHONE #2
6 segments of numerical data
The account code sent when Phone #2 is dialed is programmed in location 7. Program a A10" in the segment
immediately after the last digit of the account code. If the account code is 6 digits long, program all 6 segments. If this
location is left unprogrammed, account code 1 will be used when the second phone number is dialed.
LOCATION 8
COMMUNICATOR FORMAT FOR PHONE # 2
1 segment, numerical data
Location 8 contains the communicator format used to transmit to the receiver connected to Phone #2. Consult the
instruction manual for your central station receiver to determine which format is compatible, and select from the 15
formats listed on page 13. If you require a format other than those listed, review the override options described in
Location 18 to build the appropriate format. A "15" must be programmed in location 8 in addition to the entries in
location 18 in order to create a special format. If this location contains a "0", format 1 will be used when Phone #2 is
dialed.
LOCATION 9
DIAL ATTEMPTS/BACKUP CONTROL PHONE #2
2 segments, numerical data
Segment 1 Dial attempts: Segment 1 of Location 9 is used to enter the number of dial attempts (1 to 15 attempts)
the communicator will make to Phone #2 before ending the notification process. Factory default is "0" and the
communicator will make the same number of attempts as those programmed in location 3.
Segment 2 Phone #2 Backup Control: Programming a "0" in Segment 2 of this location will cause the NX-6 to
make the designated number of attempts to Phone #2 and #1 before setting the "Fail To Communicate" condition and
stop reporting. Programming a "1" in this segment will cause the NX-6 to stop trying to communicate after the
designated number of attempts have been made to Phone #2. If a "2" is programmed in this segment, it will cause the
NX-6 to make the dial attempts in increments of two. The first two attempts will be made to Phone #2, the next two
attempts to Phone #1, then repeating until the total number of attempts designated in Segment 1 is completed.
Page 14
LOCATION 10
EVENTS REPORTED TO PHONE #2
2 segments of feature selection
Phone #2 can be used to back up Phone #1 or for a second receiver to multi-report or split report events. Phone #2 has
two programming locations that are used to select which events are reported to this phone number. Location 10 is used
to select which events are reported to Phone #2, and location 11 is used to select which partitions are reported to Phone
#2. If dual or split reporting is not desired, location 10 and location 11 should be left at the factory default of "0". If
multi-reporting or split reporting is desired, and the split is based on the event type (such as alarm, open close etc.),
location 10 should be used to select only those events that should be reported to Phone #2, and location 11 should be
left at the factory default of "0". If dual or split reporting is desired, and the split is based on partition, then location 10
should be programmed as "0", and location 11 should be used to select those partitions that should be reported to the
Phone #2. If no events should be reported to Phone #2, both locations should be "0". Use Table 1.1 on page 14 to
identify the events to be reported for Phone #2.
LOCATION 11
PARTITIONS REPORTED TO PHONE #2
1 segment, feature selection
Location 11 is used when events to be reported to a phone number are based upon the partition regardless of the event.
Program a A1" for Partition 1 and a A2" for Partition 2. If this location is used, location 10 should be "0".
LOCATION 12
PROGRAMMING PHONE #3
20 segments, numerical data
Phone #3 is programmed in location 12. A "14" indicates the end of the phone number. Delays of four seconds can be
programmed at any point in the phone number by programming a "13" in the appropriate segment. If tone dialing is
desired, program a "15" in the segment where tone dialing should begin. If the entire number should be tone dialing,
program a "15" in the first segment. Program an A11" for a Ar@, and a A12" for a A#@.
LOCATION 13
ACCOUNT CODE FOR PHONE #3
6 segments, numerical data
The account code sent when Phone #3 is dialed is programmed in location 13. Program a A10" in the segment
immediately after the last digit of the account code. If the account code is 6 digits long, program all 6 segments. If
location 6 is left unprogrammed, account code 1 will be used when the Phone #3 is dialed.
LOCATION 14
COMMUNICATOR FORMAT FOR PHONE #3
1 segment, numerical data
Location 14 contains the communicator format used to transmit to the receiver connected to phone #3. Consult the
instruction manual for your central station receiver to determine which format is compatible, and select from the 15
formats listed on page 13. If you require a format other than those listed, review the override options described in
Location 18 to build the appropriate format. A "15" must be programmed in location 14 in addition to the entries in
location 18 to create a special format. If this location contains a "0", format 1 will be used when Phone #3 is dialed.
LOCATION 15
DIAL ATTEMPTS/BACKUP CONTROL PHONE #3
2 segments, numerical data
Segment 1 Dial Attempts: Segment 1 of Location 15 is used to enter the number of dial attempts (1 to 15 attempts)
the communicator will try to Phone #3 before ending the notification process. Factory default is "0" and the
communicator will make the same number of attempts as those programmed in location 3.
Segment 2 Phone # 3 Backup Control: Programming a "0" in Segment 2 of this location will cause the NX-6 to
make the designated number of attempts to Phone #3 and #2 before setting the "Fail To Communicate" condition and
stop reporting. Programming a "1" in this segment will cause the NX-6 to stop trying to communicate after the assigned
number of attempts have been made to Phone #3. If a "2" is programmed in this segment, it will cause the NX-6 to
make the dial attempts in increments of two. The first two attempts will be made to Phone #3, the next two attempts to
Phone #2, repeating until the total number of attempts reflected in Segment 1 is completed.
LOCATION 16
EVENTS REPORTED TO PHONE #3
2 segments, feature selection
Phone #3 can be used for a third receiver to multi-report or split report events. Phone #3 has two programming
locations that are used to select which events are reported to this phone number. Location 16 is used to select which
events are reported to Phone #3, and Location 17 is used to select which partitions are reported to Phone #3. If dual or
split reporting is not desired, locations 16 and 17 should be left at the factory default of "0". If multi-reporting or split
reporting is desired, and the split is based on the event type (such as alarm, open/close, etc.), then location 16 should
be used to select only those events that should be reported to Phone #3 and location 17 should be left at the factory
default of "0". If dual or split reporting is desired, and the split is based on partition, then location 16 should be
programmed to "0" and location 17 should be used to select the partitions that should be reported to Phone #3. If no
events should be reported to Phone #3, both locations should be "0". Use Table 1.1 on page 14 to identify the
events to be reported for Phone #3.
Page 15
LOCATION 17
PARTITIONS REPORTED TO PHONE #3
1 segment, feature selection
Location 17 is used when events to be reported to a phone number are based upon the partition regardless of the event.
Program a A1" for Partition 1, and a A2" for Partition 2. If this location is used, location 16 should be "0".
LOCATION 18
CUSTOM COMMUNICATOR FORMAT
Segment 1
â
ã
ä
å
æ
ç
è
é
On for 1800hz transmit; Off for 1900hz.
On for 2300hz handshake; Off for 1400hz.
On for cksum parity; Off for double round parity.
On for 2 digit event code; Off for 1 digit event code.
Reserved.
Reserved.
On for 20 p.p.s.; Off for 10 or 40 p.p.s.
On for 10 p.p.s.; Off for 20 or 40 p.p.s.
Segment 2
â
ã
ä
å
æ
ç
è
é
On for pager format (no handshake required).
On for 1400/2300 handshake.
Reserved
Reserved.
On for Contact ID.
On for SIA.
On for Contact ID or 4+3.
On for DTMF.
Segments 3 & 4
Reserved.
LOCATION 19
DOWNLOAD ACCESS CODE
See locations 2, 8, & 14
8 segments, numerical data
Location 19 contains the eight-digit access code the NX-6 must receive from the downloading software before the panel
will permit downloading to occur. The factory default code is 84800000.
LOCATION 20
NUMBER OF RINGS TO ANSWER
1 segment, numerical data
Location 20 contains the number of rings to answer for a download. Enter a number from A0" (disabled) to "15". Factory
default is "8" and the NX-6 will answer on 8 rings.
LOCATION 21
DOWNLOAD CONTROL
1 segment, feature selection
Location 21 contains the feature selections for the controlling of download sessions. The following features can be
enabled or disabled using this location. (See the feature definitions beginning on page 3)
,
,
,
,
â
ã
ä
å
æ
ç
è
On enables two call answering machine defeat.
On enables tone sniff answering machine defeat.
On requires call back before download session.
Shutdown.
On locks all local programming.
On locks programming of all locations associated with the communicator.
On locks out download section. (If "On", locations 19 - 22 cannot be viewed from the
keypad; can only be viewed from the keypad when "Off".)
é On enables call back at auto test interval.
, These can only be viewed from the keypad, must be changed through downloading.
LOCATION 22
DOWNLOAD CALL BACK NUMBER
20 segments, numerical data
If a telephone number is programmed into this location, and "Require Callback" is enabled in location 21, the control
panel will hang up for approximately 36 seconds (ensuring that the calling party has disconnected), and then call back.
If tone dialing is desired, program an "15" in the segment where tone dialing should begin. If the entire number should
be tone dialing, program an A15" in the first segment. Four-second delays can be obtained anywhere in the sequence by
programming a "13" in the appropriate delay location. WARNING: THE CALLBACK PHONE NUMBER SHOULD ALWAYS
BE REVIEWED FOR ACCURACY BEFORE DISCONNECTING.
Page 16
LOCATION 23
PARTITION 1
FEATURE AND REPORT SELECTIONS
3 segments, feature selection
Location 23 is used to enable certain features that can be accessed or are visible to the user from the keypad of the
system. In addition, certain communicator reports are enabled in location 23. Each of these features can be enabled by
partition. For additional partition information see locations 88-91 on page 27. If the feature selection location for
any partition is left blank, that partition will use this location for the feature selection. This location contains 3
segments of 8 features each. (See the definitions beginning on page 3.)
Segment 1
Segment 2
Segment 3
LOCATION 24
â
ã
ä
å
æ
ç
è
é
On
On
On
On
On
On
On
On
â
ã
ä
å
æ
ç
è
é
On enables
On enables
On enables
On enables
On enables
On enables
On enables
Reserved.
the LED Extinguish feature.
the Require Code for Bypassing feature.
the Zone Bypassed Sounder Alert feature.
the AC Power/Low Battery Sounder Alert feature.
Bypass toggle.
Silent Auto Arm.
the Automatic Instant feature.
â
ã
ä
å
æ
ç
è
é
On
On
On
On
On
On
On
On
Opening and Closing reports.
Zone Bypass reporting.
Zone Restore reporting.
Zone Trouble reporting.
Zone Tamper reporting.
the Cancel reporting.
the Recent Closing report.
the Exit Error report.
enables
enables
enables
enables
enables
enables
enables
enables
enables
enables
enables
enables
enables
enables
enables
enables
the
the
the
the
the
the
the
the
Quick Arm feature.
Re-exit feature.
Automatic Bypass feature.
Silent Keypad Panic feature (overrides the audible panic selection).
Audible Keypad Panic feature.
Keypad Aux 1 feature (FIRE).
Keypad Aux 2 feature (MEDICAL).
Keypad Multiple Code Attempt Tamper feature.
ENTRY / EXIT TIMERS
4 segments, numerical data
Location 24 is used to program the Entry/Exit times. There are 2 separate Entry/Exit times.
Segment 1
Entry time 1
This is the entry time that will be used when a delay 1 zone type initiates an
entry delay. Valid entries are 10-255 seconds.
Segment 2
Exit time 1
This is the exit time that will be used for all zones designated as delay 1. Valid
entries are 10-255 seconds.
Segment 3
Segment 4
Entry time 2 This is the entry time that will be used when a delay 2 zone type initiates an
entry delay. Valid entries are 10-255 seconds.
Exit time 2
This is the exit time that will be used for all zones designated as delay 2. Valid
entries are 10-255 seconds.
Page 17
STANDARD (Default) ZONE TYPES
Zones can be programmed to be one of twenty different zone types (configurations). Zone Types # 17 - 20 can be used
for wireless or hardwired zones using European double EOL configuration. Table 1.1 lists the standard (default) zone
types. These twenty zone types can be customized by programming locations 110-149.
Table
1.1
"1"
"2"
"3"
"4"
"5"
"6"
"7"
"8"
"9"
"10"
"11"
"12"
"13"
"14"
"15"
"16"
"17"
"18"
"19"
"20"
Page 18
STANDARD ZONE TYPE DESCRIPTIONS
DAY ZONE - Instant when system is armed trouble zone when system is disarmed.
24-HOUR AUDIBLE - Creates an instant yelping siren alarm regardless of the armed state of the control
panel.
ENTRY/EXIT DELAY 1- A trip will start entry delay 1. The lack of a trip during exit delay will enable the
Automatic Bypass or Instant mode if so programmed.
FOLLOWER WITH AUTO- BYPASS DISABLED - This zone will be instant when the system is armed and no
entry or exit delays are being timed. It is delayed during entry and exit delay times. This zone will not
automatically bypass even if enabled in Segment 1 of Location 23.
INTERIOR FOLLOWER WITH AUTO- BYPASS ENABLED - This zone will be instant when the system is
armed and no entry or exit delay is being timed. It is delayed during entry and exit delay times. This zone will
automatically bypass if enabled in Segment 1 of Location 23.
INSTANT - This zone creates an instant alarm whenever it is tripped and the Armed LED is on.
24-HOUR SILENT - Creates an instant silent alarm regardless of the armed state of the control panel. It will
not display on the keypad.
FIRE - This zone will light the Fire LED and sound the temporal siren each time the zone is shorted. It will
also rapidly flash the Fire LED indicating a trouble if the zone is open.
ENTRY/EXIT DELAY 2- A trip will start entry delay 2. The lack of a trip during exit delay will enable the
Automatic Bypass or Instant mode if so programmed.
24 HOUR SILENT SUPERVISED- Creates an instant silent alarm regardless of the armed state of the control
panel. It will display on the keypad.
KEYSWITCH ZONE - This zone type will arm and disarm the partition or partitions of the control panel that it
resides in each time the zone is shorted. Keyswitch arming will report as user #99.
INTERIOR FOLLOWER WITH "CROSS ZONE" ENABLED - This zone will be instant when the system is
armed and no entry or exit delay is being timed. It is delayed during entry and exit delay times. If a "Cross
Zone" is not being timed it will start a "Cross Zone" timer. If a "Cross Zone" is being timed it will create an
instant alarm. This zone will automatically bypass when enabled in Segment 1 of Location 23.
INSTANT ENTRY GUARD - This zone creates an instant alarm whenever it is tripped and the Stay LED is
off. It will start an entry delay time 2 if it is tripped and the system is armed and the Stay LED is on.
ENTRY/EXIT DELAY 1 WITH GROUP BYPASS ENABLED - A trip will start entry delay 1. This zone will
bypass when the "Group Bypass" command is entered at the keypad. The lack of a trip during exit delay will
enable the Automatic Bypass or Instant mode if so programmed.
INTERIOR FOLLOWER WITH GROUP BYPASS ENABLED - This zone will be instant when the system is
armed and no entry or exit delays are being timed. It is delayed during entry/exit delay times. This zone will
bypass when the "Group Bypass" command is entered at the keypad. This zone will automatically bypass if
enabled in Segment 1 of Location 23.
INSTANT WITH GROUP BYPASS ENABLED - This zone creates an instant alarm whenever it is tripped and
the Armed LED is on. This zone will bypass when the "Group Bypass" command is entered at the keypad.
ENTRY/EXIT DELAY 1 WITH TAMPER ENABLED- A trip will start entry delay 1. The lack of a trip during
exit delay will enable the Automatic Bypass or Instant mode if so programmed. This Zone Type can be used
to enable tamper on a wireless transmitter.
INTERIOR FOLLOWER WITH TAMPER AND AUTO-BYPASS ENABLED - This zone will be instant when the
system is armed and no entry or exit delay is being timed. It is delayed during entry and exit delay times.
This zone will automatically bypass if enabled in Segment 1 of Location 23. This zone type can be used to
enable tamper on a wireless transmitter.
INSTANT WITH TAMPER ENABLED - This zone creates an instant alarm whenever it is tripped and the
Armed LED is on. This zone type can be used to enable tamper on a wireless transmitter.
ENTRY/EXIT DELAY 2 WITH TAMPER ENABLED-A trip will start entry delay 2. The lack of a trip during
exit delay will enable the Automatic Bypass or Instant mode if so programmed. This zone type can be used
to enable tamper on a wireless transmitter.
NOTE: To null a zone, program the zone in APartition Select@ as zero (0) in all partitions and do
not use end-of-line resistors.
LOCATION 25
ZONE TYPE FOR ZONES 1-8
8 segments, numerical data
Location 25 contains the zone type (configuration) for zones 1-8. Segment 1 is for zone 1, and Segment 8 is for zone 8.
Default zone types are found in the Table 1.1 on page 18. To customize a zone type, see loc. 110 - 149, page 28.
LOCATION 26
PARTITION SELECT, ZONES 1-8
8 segments, feature selection
Location 26 is used to select the partition(s) that zones 1 - 8 reside in. A zone may reside in any combination of the 2
partitions. If a burglary zone resides in more than 1 partition, it will only be active when all partitions it
resides in are armed. A zone that resides in more than 1 partition will be reported to its lowest partition
number. Location 26 has 8 segments. Segment 1 corresponds to zone 1, and Segment 8 corresponds to zone 8.
Segments 1- 8
â Partition #1
ã Partition #2
LOCATION 27
ZONE TYPE FOR ZONES 9-16
8 segments, numerical data
Location 27 contains the zone type (configuration) for zones 9 -16. Segment 1 is for zone 9, and Segment 8 is for zone
16. Default zone types are found in Table 1.1 on page 18. To customize a zone type, see page 28.
LOCATION 28
PARTITION SELECT, ZONES 9-16
8 segments, feature selection
Location 28 is used to select the partition(s) that zones 9-16 reside in. A zone may reside in any combination of the 2
partitions. If a burglary zone resides in more than 1 partition, it will only be active when all partitions it
resides in are armed. A zone that resides in more than 1 partition will be reported to its lowest partition.
Location 28 has 8 segments. Segment 1 corresponds to zone 9 and Segment 8 corresponds to zone 16.
Segments 1- 8
â Partition #1
ã Partition #2
LOCATION 37
SIREN AND SYSTEM SUPERVISION
5 segments, feature selection
Location 37 is used to enable various system feature and reporting options. (Refer to the feature definitions.)
Segment 1
â
ã
ä
å
æ
ç
è
é
On
On
On
On
On
On
On
On
if
if
if
if
if
if
if
if
Segment 2
â
ã
ä
å
æ
ç
è
é
On
On
On
On
On
On
On
On
if siren driver should be a voltage output. Off if on board siren driver enabled.
if siren sounds for expander trouble (required for UL installations).
for Immediate Restore by Zone.
if Dynamic Battery Test performed at arming. Off if performed at disarming. (Loc. 40)
if Battery Missing Test is performed every 12 seconds.
if Manual Bell Test performed during [r]-[4] test function.
if Manual Communicator Test performed during [r]- [4] test function.
if Box Tamper terminals on the control panel are enabled.
Segment 3
â
ã
ä
å
æ
ç
è
é
On if Box Tamper reporting enabled.
On if AC Fail reporting enabled.
On if Low Battery reporting enabled.
On if Aux. Power Over current reporting enabled.
On if Siren Supervision reporting enabled.
On if Telephone Line Cut reporting enabled.
Reserved.
On if Expander Trouble reporting enabled.
siren
siren
siren
siren
siren
siren
siren
siren
sounds for "Telephone Line Cut" when armed.
sounds for "Telephone Line Cut" when disarmed.
blast at arming.
blast at exit expiration.
blast at closing kissoff.
sounds during a "Cross Zone" verification time.
sounds for a Zone or Box Tamper.
blasts 1 time for keyswitch or wireless arming; 2 times for disarming.
Page 19
Segment 4
â
ã
ä
å
æ
ç
è
é
Segment 5
â On enable Lost Clock service light.
ã On enables Zone Doubling for zones 7 -12 (requires NX-200 Zone Doubling Kit).
ä On disables on-board zones.
å On will allow two trips on same cross-zone to activate an alarm.
æ On will not allow zones that are force armed to report bypass.
ç On enables Silent Exit option.
è Use internal crystal for clock.
é Disable Temporal Siren on Fire. (Note: Must not be disabled for UL listed systems.)
Refer to the feature definitions beginning on page 3.
LOCATION 38
On if Fail To Communicate report enabled.
On if Log Full report enabled.
On if Autotest report enabled.
On if Start/End programming report enabled.
On if End Download report enabled.
On if Sensor Low Battery report enabled.
On if Sensor Missing report enabled.
Reserved.
SWINGER SHUTDOWN COUNT
Location 38 contains the number of trips on a zone before that zone is bypassed automatically. Refer to the feature
definitions beginning on page 3. NOTE: For UL installations, this feature shall be disabled.
LOCATION 39
KEYPAD SOUNDER CONTROL
â
ã
ä
å
æ
ç
è
é
LOCATION 40
On if keypad
On if keypad
On if keypad
On if keypad
On if keypad
On if keypad
Reserved.
On if keypad
sounds
sounds
sounds
sounds
sounds
sounds
1 segment, feature selection
for ATelephone Line Cut@ when the system is armed.
for ATelephone Line Cut@ when disarmed.
upon AC Power Failure.
when a Low Battery is detected.
during Cross Zone trip time.
for zone and box tampers.
sounds for expander trouble (required for UL installations).
SYSTEM TIMERS
10 segments, numerical data
Location 40 contains the duration of various system timing functions. Example: If you desire the duration of the
Dynamic Battery Test to be 30 minutes, you should program [3]-[0]-[r] in segment 1 of this location. The [3]-[0] is the
number of minutes, and the [r] stores the data and moves to the next segment of this location.
Segment
Segment
Segment
Segment
Segment
Segment
Segment
1
2
3
4
5
6
7
Segment 8
Segment 9
Segment 10
Dynamic Battery Test duration (0 - 255 minutes) "0" = no test
AC Fail report delay (0 - 255 minutes)
Power Up Delay (0 - 60 seconds) "0" = no delay
Siren time (1 - 255 minutes)
Telephone Line Cut delay (0 - 255 seconds) "0" = no TLM
Cross Zone time (0 - 255 minutes) "0" = no Cross Zoning
Chime time in 50 mS (1/20th second) increments (0 - 255 mS)
Note: 255 mS = 12 seconds; "0" follows zone, A255" is latched
Dial delay (0 - 255 seconds) 0 = no abort delay
Fire Alarm Verification time (120 - 255 seconds) "0"= no Fire Alarm Verification v
Listen-In time (0 - 255 seconds) " 0" = no Listen-In time
Note: The "Listen-In" feature cannot be enabled for UL Listed systems. The "Dynamic Battery Test" feature
cannot exceed four (4) hours. The dial delay shall be set to -0-.
v This feature is not approved for residential use in California.
Page 20
LOCATION 41
SPECIAL FEATURES
1 segment, feature selection
â On enables the 6-digit code option. If 6-digit option is enabled, all arm/disarm codes and
the "Go To Program Code" are 6 digits. If this option is enabled, the default user #1 code
is [1]-[2]-[3]-[4]-[5]-[6]. NOTE: IF YOU ENABLE THIS OPTION, VERIFY THAT THE
"GO TO PROGRAM CODE" IS A 6-DIGIT CODE BEFORE EXITING PROGRAMMING.
ã On requires code entry for [r]-[9]-[8] ACall back for download@ and [r]-[9]-[9] AAnswer
incoming call for download@ functions.
ä On enables AAuto Cancel/Abort@. Refer to feature definitions beginning on page 3.
å On enables AWalk-Test Mode@. Refer to feature definitions beginning on page 3.
Ò - é Reserved.
LOCATION 42
GO TO PROGRAM CODE
6 segments, numerical data
Location 42 contains the "Go To Program Code". This location contains either a 4 or 6-digit code. If the 6-digit code
option is enabled in Location 41, this code must contain six (6) digits. If this option is not enabled in location 41, the last
2 segments (digits) will be ignored. With the NX-6 disarmed, the "Go To Program Code" can be used to enter the
Program Mode.
LOCATION 43
GO TO PROGRAM CODE PARTITION AND
AUTHORIZATION
2 segments, feature selection
The "Go To Program Code" can be used as a standard arm/disarm code. When using the code to arm or disarm, the user
ID is 255. (This code may not be changed in the Run Mode.)
Segment 1
â
ã
ä
å
æ
ç
è
é
Segment 2
â On enables the "Go To Program Code" for Partition #1.
ã On enables the "Go To Program Code" for Partition #2.
LOCATION 44
Reserved.
On enables "Go To Program Code" as an arm only code.
On enables "Go To Program Code" as an arm only after closing.
On enables "Go To Program Code" as a master arm/disarm code (can change user codes)
On enables "Go To Program Code" as an arm/disarm code.
On enables "Go To Program Code" to bypass zones.
On enables "Go To Program Code" opening and closing reports.
Reserved.
DURESS CODE
6 segments, numerical data
Location 44 contains the "Duress" code. This Location contains either 4 or 6 digits. If the 6-digit code option is enabled
in Location 41, this code must contain six (6) digits. If the 6-digit option is not enabled in location 41, the last 2 digits
will be ignored. If the duress code is programmed, it will work for all partitions.
LOCATION 45
AUXILIARY OUTPUT, PARTITION SELECTION
4 segments, feature selection
Location 45 is used to select which partition(s) the events must occur in before the output will activate. Location 45 has
4 segments. Segment 1 corresponds to Output 1, and Segment 4 corresponds to Output 4.
Segments
1-4
LOCATION 46
â Partition #1
ã Partition #2
AUXILIARY OUTPUT, SPECIAL TIMING
4 segments, feature selection
Location 46 contains special timing feature activation for the four auxiliary outputs. Segment 1 corresponds to Auxiliary
Output 1, Segment 4 corresponds to Auxiliary Output 4.
Segments
1-4
â On if output should be timed in minutes; Off if timed in seconds.
ã On if output should latch; Off if output should be timed.
ä On if output should stop timing upon code entry; Off if the output should continue to time
upon code entry.
å On if output should only activate between the closing and opening time in loc. 52 and 53.
æ On if output should only activate between the opening and closing time in loc. 52 and 53.
ç On if output should be inverted (0 volts going to 12 volts when activated).
è Reserved.
é Reserved.
Page 21
LOCATION 47
AUXILIARY OUTPUT #1, EVENT AND TIME
2 segments, numerical data
Segment 1
Use Table 2.1 to select the event that will activate Auxiliary Output 1.
Segment 2
Program the timing from 0-255 (minutes or seconds, depending on data programmed in
Segment 1, Location 46). Programming a "0" makes the output follow the event.
LOCATION 48
AUXILIARY OUTPUT #2, EVENT AND TIME
2 segments, numerical data
Segment 1
Use Table 2.1 to select the event that will activate Auxiliary Output 2.
Segment 2
Program the timing from 0-255 (minutes or seconds, depending on data programmed in
Segment 2, Location 46). Programming a "0" makes the output follow the event.
LOCATION 49
AUXILIARY OUTPUT #3, EVENT AND TIME
2 segments, numerical data
Segment 1
Use Table 2.1 to select the event that will activate Auxiliary Output 3.
Segment 2
Program the timing from 0-255 (minutes or seconds, depending on data programmed in
Segment 3, Location 46). Programming a "0" makes the output follow the event.
LOCATION 50
AUXILIARY OUTPUT #4, EVENT AND TIME
2 segments, numerical data
Segment 1
Use Table 2.1 to select the event that will activate Auxiliary Output 4.
Segment 2
Program the timing from 0-255 (minutes or seconds, depending on data programmed in
Segment 4, Location 46). Programming a "0" makes the output follow the event.
AUXILIARY OUTPUT EVENT SELECTION
Table 2.1
DATA
0
/
1
/
2
/
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
/
/
/
/
/
/
/
EVENT
Burglary Alarm
Fire Alarm
24 Hour Alarm
DATA
19
20
21
EVENT
Exit
Entry or Exit
Armed State
DATA
38
39
40
Trouble Alarm
Tamper Alarm
Yelping Siren (Burglary)
Temporal Siren (Fire)
Any Siren
22
23
24
25
26
Disarmed State
Ready
Not Ready
Fire
Fire Trouble
41
42
43
44
45
Any Bypass
AC Fail
Low Battery
Duress
Aux 1 Keypad Zone
Aux 2 Keypad Zone
27
28
29
30
31
32
33
34
35
36
37
Chime
Expander Trouble
Dynamic Battery Test Time
Open Period
Closed Period
Listen-In
Line Seizure
Ground Start
Fail To Communicate
Telephone Line Fault
Program Mode
46
/
47
48
/
49 ˜ /
50 ˜ /
51
/
52
53
54
Panic Keypad Zone
Keypad Tamper
Autotest
Alarm Memory
Entry
/
EVENT
Download In Process
Smoke Power
Short
Circuit
(Overcurrent)
Box Tamper
Siren Tamper
Any Open
Any Short
Any Fault (Open/ Short on
Non-Fire Zone)
Any Alarm
Beeping Keypad
Code Entry (See note)
Key FOB Function 1
Key FOB Function 2
Always On
Flashing in Alarm
Armed AWAY
Armed STAY
˜ Events 49 & 50 require NX-408, NX-416, or NX-448 wireless receivers to operate.
/ If set to follow condition, these events will be 1 second.
NOTES: When Event 48 is programmed, it is possible to program a user code's authorization to select which output(s) a
particular code will activate. When LED 8 is on for an authorization, then LEDs 1- 4 correspond to that code activating
outputs 1 - 4 respectively. (See programming the LED keypads on page 8.)
Page 22
LOCATION 51
AUTOTEST CONTROL
4 segments, numerical data
Segment 1
Program a "1" if the interval is to be in hours. Program a "0" if in days. Program a A2" to
suppress the daily test or a A3" to suppress the hourly test if any report has been sent.
Segment 2
Program the Autotest interval from 1-255 hours/days.
Segment 3
Program the Autotest report hour in 24-hour format (if the interval is in hours, this segment is
ignored).
Segment 4
Program the Autotest report time, number of minutes after the hour.
LOCATION 52
OPENING TIME
2 segments, numerical data
Location 52 contains the time in 24 hour format the NX-6 enables codes designated as arm only after closing. This time
is only valid on those days programmed in location 54. Note: Opening time must be earlier than closing time for
Auto Arm, Auxiliary Outputs, or Code Authorization to function properly.
Segment 1
Program the hour of the opening time.
Segment 2
Program the minutes after the hour of the opening time.
LOCATION 53
CLOSING TIME/AUTOMATIC ARMING TIME
2 segments, numerical data
Location 53 contains the time in 24-hour format the NX-6 disables the disarm capability for codes designated as arm only
after closing. This is also the time the Automatic Arming sequence will begin (if enabled in location 55). Note: Opening
time must be earlier than closing time for Auto Arm, Aux. Outputs, or Code Authorization to function properly.
Segment 1
Program the hour of the closing / auto arm time.
Segment 2
Program the minutes after the hour of the closing / auto arm time.
LOCATION 54
DAYS OF WEEK EACH PARTITION IS OPEN
2 segments, feature selection
Location 54 selects which days of the week each partition is open. On these days, Aarm only after close window@ codes
will be able to arm and disarm during open window. NOTE: If any partition is not programmed to be opened and
is programmed to Auto-Arm (Location 55), the NX-6 will try to arm every 45 minutes for the duration of the
closed period. On days not selected here, Aarm only after close window@ codes will not disarm. Segment 1 is for
partition 1, and segment 8 is for partition 8. (See locations 52 and 53 for the opening and closing times for the
open days.)
Segments 1- 2
â Open on Sunday.
ã Open on Monday.
ä Open on Tuesday.
å Open on Wednesday.
æ Open on Thursday.
ç Open on Friday.
è Open on Saturday.
é Reserved.
LOCATION 55
DAYS OF WEEK PARTITIONS WILL AUTO ARM
2 segments, feature selection
Location 55 selects which days each partition will auto arm. Segment 1 is for partition 1, and segment 2 is for partition
2. If a zone is faulted when the panel tries to auto arm, the zone will be bypassed.
Segments 1- 2
â Auto Arming on Sunday.
ã Auto Arming on Monday.
ä Auto Arming on Tuesday.
å Auto Arming on Wednesday.
æ Auto Arming on Thursday.
ç Auto Arming on Friday.
è Auto Arming on Saturday.
é Reserved.
Page 23
SLOW FORMAT COMMUNICATOR CODES
LOCATIONS 56- 83 ARE ONLY USED WHEN REPORTING EVENTS TO A PAGER OR USING A SLOW FORMAT
SUCH AS 4+2. WHEN USING CONTACT ID OR SIA, THERE IS NO NEED TO PROGRAM THESE LOCATIONS.
LOCATION 56
RESTORE
2 segments, numerical data
Location 56 contains the event code for a zone "Restore" for a 4+2 format. The digit programmed in this location will be
sent as the tens digit in place of the alarm event code. The zone ID will always be reported as the ones digit of the
zone number (i.e. 9 for zone 29). Any segment left as "0" will follow the Segment 1 selection.
Segment 1 = Partition #1 Restore Code
Segment 2 = Partition #2 Restore Code
LOCATION 57
BYPASS
2 segments, numerical data
Location 57 contains the event code for a zone "Bypass" for a 4+2 format. The digit programmed in this location will be
sent as the tens digit. The zone ID will always be reported as the ones digit of the zone number (i.e. 9 for zone
29). Any segment left as "0" will follow the Segment 1 selection.
Segment 1 = Partition #1 Bypass Code
Segment 2 = Partition #2 Bypass Code
LOCATION 58
TAMPER
2 segments, numerical data
Location 58 contains the event code for a zone "Tamper" for a 4+2 format. The digit programmed in this location will be
sent as the tens digit. The zone ID will always be reported as the zone number (i.e. 9 for zone 29). Any segment left as
"0" will follow the Segment 1 selection.
Segment 1 = Partition #1 Tamper Code
Segment 2 = Partition #2 Tamper Code
LOCATION 59
TROUBLE
2 segments, numerical data
Location 59 contains the event code for a zone "Trouble" for a 4+2 format. The digit programmed in this location will be
sent as the tens digit. The zone ID will always be reported as the zone number (i.e. 9 for zone 29). Any segment left as
"0" will follow the Segment 1 selection.
Segment 1 = Partition #1 Trouble Code
Segment 2 = Partition #2 Trouble Code
LOCATION 60
SENSOR LOW BATTERY
2 segments, numerical data
Location 60 contains the event code for a zone "Sensor Low Battery" for a 4+2 format. The digit programmed in this
location will be sent as the tens digit.. The zone ID will always be reported as the zone number (i.e. 9 for zone
29). Any segment left as "0" will follow the Segment 1 selection.
Segment 1 = Partition #1 Sensor Low Battery Code
Segment 2 = Partition #2 Sensor Low Battery Code
LOCATION 61
SENSOR MISSING
2 segments, numerical data
Location 61 contains the event code for a zone "Sensor Missing" for a 4+2 format. The digit programmed in this location
will be sent as the tens digit.. The zone ID will always be reported as the zone number (i.e. 9 for zone 29). Any
segment left as "0" will follow the Segment 1 selection.
Segment 1 = Partition #1 Sensor Missing Code
Segment 2 = Partition #2 Sensor Missing Code
LOCATION 62
DURESS
2 segments, numerical data
Location 62 contains the tens and ones digits that will be sent for a 4+2 format if the Duress code is enabled in location
44. Segment 1 contains the tens digit, segment 2 contains the ones digit.
LOCATION 63
KEYPAD AUXILIARY 1
2 segments, numerical data
Location 63 contains the tens and ones digits that will be sent for a 4+2 format if the keypad "Auxiliary 1" (FIRE) is
enabled in the partition feature selection. Segment 1 contains the tens digit, segment 2 contains the ones digit.
LOCATION 64
KEYPAD AUXILIARY 2
2 segments, numerical data
Location 64 contains the tens and ones digits that will be sent for a 4+2 format if the keypad "Auxiliary 2" (MEDICAL) is
enabled in the partition feature selection. Segment 1 contains the tens digit, segment 2 contains the ones digit.
Page 24
LOCATION 65
KEYPAD PANIC
2 segments, numerical data
Location 65 contains the tens and ones digits that will be sent for a 4+2 format if the keypad "Panic" is enabled in the
partition feature selection Segment 1 contains the tens digit, segment 2 contains the ones digit.
LOCATION 66
KEYPAD MULTIPLE CODE ENTRY (TAMPER)
2 segments, numerical data
Location 66 contains the tens and ones digits that will be sent for a 4+2 format if the keypad "Multiple Code Entry"
(Tamper) is enabled in the partition feature selection. Segment 1 contains the tens digit, segment 2 contains the ones
digit.
LOCATION 67
BOX TAMPER & BOX TAMPER RESTORE
4 segments, numerical data
Location 67 contains the tens and ones digits that will be sent for a 4+2 format if the "Box Tamper" feature is enabled in
location 37. Segment 1 contains the tens digit of the "Box Tamper". Segment 2 contains the ones digit of the "Box
Tamper". Segment 3 contains the tens digit of the "Box Tamper Restore". Segment 4 contains the ones digit of the "Box
Tamper Restore".
LOCATION 68
AC FAIL & AC FAIL RESTORE
4 segments, numerical data
Location 68 contains the tens and ones digits for a 4+2 format that will be sent if "AC Fail Reporting" is enabled.
Segment 1 contains the tens digit of the "AC Fail Reporting". Segment 2 contains the ones digit of the "AC Fail
Reporting". Segment 3 contains the tens digit of the "AC Fail Restore". Segment 4 contains the ones digit of the "AC Fail
Restore".
LOCATION 69
LOW BATTERY & LOW BATTERY RESTORE
4 segments, numerical data
Location 69 contains the tens and ones digits for a 4+2 format that will be sent if "Low Battery Reporting" is enabled..
Segment 1 contains the tens digit of the "Low Battery Reporting". Segment 2 contains the ones digit of the "Low Battery
Reporting". Segment 3 contains the tens digit of the "Low Battery Restore". Segment 4 contains the ones digit of the
"Low Battery Restore".
LOCATION 70
AUX POWER OVER-CURRENT & RESTORE
4 segments, numerical data
Location 70 contains the tens and ones digits for a 4+2 format that will be sent if "Aux Power Over-current Reporting" is
enabled. Segment 1 contains the tens digit of the "Aux Power Over-current Reporting". Segment 2 contains the ones
digit of the "Aux Power Over-current Reporting". Segment 3 contains the tens digit of the "Aux Power Over-current
Restore". Segment 4 contains the ones digit of the "Aux Power Over-current Restore".
LOCATION 71
BELL TAMPER & RESTORE
4 segments, numerical data
Location 71 contains the tens and ones digits for a 4+2 format that will be sent if siren supervision reporting is enabled.
Segment 1 contains the tens digit of the "Bell Tamper Reporting". Segment 2 contains the ones digit of the "Bell Tamper
Reporting". Segment 3 contains the tens digit of the "Bell Tamper Restore". Segment 4 contains the ones digit of the
"Bell Tamper Restore".
LOCATION 72
TELEPHONE LINE CUT & RESTORE
4 segments, numerical data
Location 72 contains the tens and ones digits for a 4+2 format that will be sent if "Telephone Line Cut Reporting" is
enabled. Segment 1 contains the tens digit of the "Telephone Line Cut Reporting". Segment 2 contains the ones digit of
the "Telephone Line Cut Reporting". Segment 3 contains the tens digit of the "Telephone Line Cut Restore". Segment 4
contains the ones digit of the "Telephone Line Cut Restore".
LOCATION 74
EXPANDER TROUBLE & RESTORE
4 segments, numerical data
Location 74 contains the tens and ones digits for a 4+2 format that will be sent if "Expander Trouble Reporting" is
enabled. Segment 1 contains the tens digit of the "Expander Trouble Reporting". Segment 2 contains the ones digit of
the "Expander Trouble Reporting". Segment 3 contains the tens digit of the "Expander Trouble Restore". Segment 4
contains the ones digit of the "Expander Trouble Restore".
LOCATION 75
FAIL TO COMMUNICATE
2 segments, numerical data
Location 75 contains the tens and ones digits for a 4+2 format that will be sent if the "Fail To Communicate Reporting" is
enabled. Segment 1 contains the tens digit, segment 2 contains the ones digit.
Page 25
LOCATION 76
LOG FULL
2 segments, numerical data
Location 76 contains the tens and ones digits for a 4+2 format if the "Log Full Reporting" is enabled. Segment 1 contains
the tens digit, segment 2 contains the ones digit.
LOCATION 77
OPENING
2 segments, numerical data
Location 77 contains the tens digit of a 4+2 format if the "Opening Reporting" is enabled. The ones digit is the ones
digit of the user number that did the opening. If the user is greater than 9, the numbers will begin repeating.
If it is required to report openings and closings for more than 9 users, Contact ID or SIA format must be used. Any
segment left as "0" will follow the Segment 1 selection.
Segment 1 = Partition #1 Opening Code
Segment 2 = Partition #2 Opening Code
LOCATION 78
CLOSING
2 segments, numerical data
Location 78 contains the tens digit of a 4+2 format if the "Closing Reporting" is enabled. The ones digit is the ones
digit of the user number that did the closing. If the user is greater than 9, the numbers will begin repeating.
If it is required to report openings and closings for more than 9 users, Contact ID or SIA format must be used. Any
segment left as "0" will follow the Segment 1 selection.
Segment 1 = Partition #1 Closing Code
Segment 2 = Partition #2 Closing Code
LOCATION 79
AUTOTEST
2 segments, numerical data
Location 79 contains the tens and ones digits for a 4+2 format that will be sent if the "Autotest" or "Manual Test" is
enabled. Segment 1 contains the tens digit segment 2 contains the ones digit.
LOCATION 80
RECENT CLOSING & EXIT ERROR
2 segments, numerical data
Location 80 contains the tens digit for a 4+2 format that will be sent if "Recent Closing" and/or "Exit Error Reporting" is
enabled. Segment 1 contains the tens digit for the "Recent Closing Reporting". Segment 2 contains the digit for the
"Exit Error Reporting". The ones digit is the ones digit of the user who closed. If the user number is greater
than 9, the numbers will begin repeating (i.e. 9 for user 29). If it is required to report Recent Closings and Exit
Errors for more than 9 users, Contact ID or SIA format must be used.
LOCATION 81
START & END PROGRAM
4 segments, numerical data
Location 81 contains the tens and ones digits for a 4+2 format that will be sent if "Start / End Programming Reporting" is
enabled. Segment 1 contains the tens digit of the "Start Program Reporting". Segment 2 contains the ones digit of the
"Start Program Reporting". Segment 3 contains the tens digit of the "End Program Reporting". Segment 4 contains the
ones digit of the "End Program Reporting".
LOCATION 82
END DOWNLOAD
4 segments, numerical data
Location 82 contains the tens and ones digits for a 4+2 format that will be sent if "End Downloading Reporting" is
enabled. Segment 1 and 2 are reserved. Segment 3 contains the tens digit of the "End Download Reporting". Segment
4 contains the ones digit of the "End Download Reporting". NOTE: A start download report will be sent to the
internal event log.
LOCATION 83
CANCEL
1 segment, numerical data
Location 83 contains the tens digit for a 4+2 format that will be sent if "Cancel Reporting" is enabled. Segment 1
contains the tens digit for the "Cancel Communicator Reporting". The ones digit is the ones digit of the user who
canceled. If the user number is greater than 9, the numbers will begin repeating (i.e. 9 for user 29). If it is
required to report Cancels for more than 9 users, Contact ID or SIA format must be used.
Page 26
PARTITIONING CODES & FEATURES
LOCATIONS 88-91 ARE FOR PROGRAMMING DIFFERENT ACCOUNT CODES AND/OR FEATURES FOR EACH
PARTITION. IF A LOCATION IS NOT PROGRAMMED, THE FEATURE FOR PARTITION 1 AND ACCOUNT CODE
FOR THE PHONE NUMBER WILL BE USED.
LOCATION 88
ACCOUNT CODE FOR PARTITION 1
6 segments, numerical data
Location 88 contains the account code sent when partition 1 is reported. If location 88 is left unprogrammed (all
A10"s), then the account code corresponding to the phone number dialed will be used. If the account code is
less than six digits, program a A10" in the segment immediately after the last digit of the account code. If the account
code is 6 digits long, program all 6 segments.
LOCATION 89
ACCOUNT CODE FOR PARTITION 2
6 segments, numerical data
Location 89 contains the account code sent when partition 2 is reported. If location 89 is left unprogrammed (all
A10"s), then the account code corresponding to the Phone number dialed will be used. If the account code is
less than six digits, program a A10" in the segment immediately after the last digit of the account code. If the account
code is 6 digits long program all 6 segments.
LOCATION 90
PARTITION 2 FEATURES & REPORTING ENABLE
3 segments, feature selection
Location 90 is used to enable certain features that can be accessed or are visible to the user from the keypad of the
system. In addition, certain communicator reports are enabled in this location. Each of these features can be enabled
by partition. This location contains 3 segments, with eight possible features per segment. Refer to Location 23,
Segments 1,2, and 3 (page 17) for the feature selections. If all segments are blank (nothing enabled), the
features for partition 1 will be used.
LOCATION 91
PARTITION 2 ENTRY EXIT TIMERS
4 segments, numerical data
Location 91 is used to enter in seconds the Entry and Exit times. There are 2 separate entry and exit times. Valid
entries are 10-255 seconds. If all segments are A0", the entry and exit times for partition 1 will be used.
Segment
Segment
Segment
Segment
1
2
3
4
Entry time 1
Exit time 1
Entry time 2
Exit time 2
Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Exit time that will be used for all zones designated as Delay 1.
Entry time that will be used when a Delay 2 zone type initiates an entry delay.
Exit time that will be used for all zones designated as Delay 2.
Page 27
CUSTOMIZING ZONE TYPES (Configuration Groups)
LOCATIONS 110-149 ARE USED TO CHANGE THE ZONE TYPES AS LISTED IN THE TABLE ON PAGE 18.
THESE LOCATIONS ARE CONSIDERED ADVANCED PROGRAMMING AND SHOULD ONLY BE CHANGED WITH
A THOROUGH UNDERSTANDING OF THE OPERATION OF EACH BIT.
LOCATION 110
ZONE TYPE 1 ALARM EVENT CODE
1 segment, numerical data
Location 110 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from
the list on page 38. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number programmed
in this location will be sent as the tens digit. When using 4+2 the digit in location 110 should be from 1-15. The zone ID
for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 111
ZONE TYPE 1 CHARACTERISTICS
3 segments, feature selection
Table 3.1
Segment 1
â
ã
ä
å
æ
ç
è
é
Fire (turn on if this is a fire zone).
24 hour (turn on for non-fire 24 hour zones).
Keyswitch zone. (normally open switch)
Follower (turn on for burglary zones that are Instant during non-entry times).
Delay 1 zone (follows timer 1 entry and exit times).
Delay 2 zone (follows timer 2 entry and exit times).
Interior (turn on if this zone should Automatically Bypass or Bypass for Stay Arming).
Local only (turn on if this zone should not be reported).
Segment 2
â
ã
ä
å
æ
ç
è
é
On
On
On
On
On
On
On
On
Segment 3
â RESERVED
ã On enables Double End Of Line (D.E.O.L.) Tamper zone. Mainly used for tamper on wireless
zones.
ä On enables Trouble Reporting zone. (Day zone and Fire zones)
å On if zone type is a Cross Zone.
æ On enables Dialer Delay zone. (See location 40, page 20)
ç On if zone type will swinger shutdown. (See location 38, page 20)
è On enables Restore reporting.
é On enables Listen-In. (See location 40, page 20)
LOCATION 112 LOCATION 149
will beep the keypad for alarm.
will sound the yelping siren for alarm.
if zone type will sound the temporal siren for alarm.
if zone type will chime.
if zone type can be bypassed.
if zone type is included in the group shunt.
if zone type is force armable.
if zone type is entry guard.
ZONE TYPES 2 THROUGH 20
Locations 112 - 149 contain the remaining 19 Zone Types information. Locations 112 and 113 correspond to Zone Type
2, and Locations 148 and 149 correspond to Zone Type 20. The EVEN numbered locations reflect the Zone Type Alarm
Event Code while the ODD numbered locations designate the Zone Type Characteristics. Use the description found in
Location 110 for programming the Alarm Event Codes, and use Table 3.1 shown above to select the Zone Type
Characteristics. Refer also to the Programming Worksheets.
Page 28
NX-6 PROGRAMMING WORKSHEETS
(- Factory defaults for segments are in bold italics text. Some locations have been intentionally omitted.
Attempts to access these reserved locations will cause the keypad to sound an error beep.)
LOC
PG
0
12
PHONE #1
14-14-14-14-14-14-1414-14-14-14-14-14-1414-14-14-14-14-14
1
12
PHONE #1, ACCOUNT CODE
10 - 10 - 10 - 10 - 10 - 10
2
12
PHONE #1, REPORTING FORMAT
0
__
3
13
8
0
__
__
4
13
PHONE #1, DIAL ATTEMPTS
BACKUP CONTROL
PHONE #1, SELECT EVENTS TO REPORT TO PHONE #1
14
Segment #1
Segment # 2
1 - Alarms and Restores “
1 - Tampers “
2 - Open / Close “
2 - Short Circuit “
3 - Bypass “
3 - Sensor Lost “
4 - Zone Trouble “
4 - Sensor Low Battery “
5 - Power Trouble (AC Fail or Low Battery) “
5 - Expander Trouble “
6 - Siren & Telephone Fault “
6 - Failure to Communicate “
7 - Test Reports “
7 - Reserved
8 - Program, Download, & Log Full “
8 - Reserved
PHONE #1 SELECT WHICH PARTITIONS REPORT TO PHONE #1
6
14
1 - Partition #1 “
2 - Partition #2 “
PHONE #2
7
14
PHONE #2, ACCOUNT CODE
10 - 10 - 10 - 10 - 10 - 10
__ __ __ __ __ __
8
14
PHONE #2, REPORTING FORMAT
0
__
9
14
8
0
__
__
10
15
PHONE #2, DIAL ATTEMPTS
BACKUP CONTROL
PHONE #2, SELECT EVENTS TO REPORT TO PHONE #2
15
Segment #1
Segment # 2
1 - Alarms and Restores “
1 - Tampers “
2 - Open / Close “
2 - Short Circuit “
3 - Bypass “
3 - Sensor Lost “
4 - Zone Trouble “
4 - Sensor Low Battery “
5 - Power Trouble (AC Fail or Low Battery) “
5 - Expander Trouble “
6 - Siren & Telephone Fault “
6 - Failure to Communicate “
7 - Test Reports “
7 - Reserved
8 - Program, Download, & Log Full “
8 - Reserved
PHONE #2 SELECT WHICH PARTITIONS REPORT TO PHONE #2
12
15
1 - Partition #1 “
2 - Partition #2 “
PHONE #3
13
15
PHONE #3, ACCOUNT CODE
14
15
PHONE #3, REPORTING FORMAT
0
__
15
15
PHONE #3, DIAL ATTEMPTS
BACKUP CONTROL
8
0
__
__
5
11
DESCRIPTION
DEFAULT
14-14-14-14-14-14-1414-14-14-14-14-14-1414-14-14-14-14-14
14-14-14-14-14-14-1414-14-14-14-14-14-1414-14-14-14-14-14
10 - 10 - 10 - 10 - 10 - 10
PROGRAMMING DATA
__ __ __ __ __ __ __ __
__ __ __ __ __ __ __ __
__ __ __ __
__ __ __ __ __ __
__ __ __ __ __ __ __ __
__ __ __ __ __ __ __ __
__ __ __ __
__ __ __ __ __ __ __ __
__ __ __ __ __ __ __ __
__ __ __ __
__ __ __ __ __ __
Page 29
LOC
PG
16
15
PHONE #3, SELECT EVENTS TO REPORT TO PHONE #3
16
Segment #1
Segment # 2
1 - Alarms and Restores “
1 - Tampers “
2 - Open / Close “
2 - Short Circuit “
3 - Bypass “
3 - Sensor Lost “
4 - Zone Trouble “
4 - Sensor Low Battery “
5 - Power Trouble (AC Fail or Low Battery) “
5 - Expander Trouble “
6 - Siren & Telephone Fault “
6 - Failure to Communicate “
7 - Test Reports “
7 - Reserved
8 - Program, Download, & Log Full “
8 - Reserved
PHONE #3 SELECT WHICH PARTITIONS REPORT TO PHONE #3
16
1 - Partition #1 “
2 - Partition #2 “
FORMAT OVERRIDE
17
18
DESCRIPTION
Segment #1
19
16
20
16
RINGS TO ANSWER DOWNLOAD
21
16
DOWNLOAD CONTROL
22
16
1 - Enables two call answering machine defeat “
2 - Enables tone sniff answering machine defeat “
3 - Requires callback before downloading “
4 - Shutdown control panel “
5 - Lock out local programming “
6 - Lock out communicator programming “
7 - Lock out download section “
8 - Enables callback at autotest interval “
CALLBACK PHONE NUMBER
23
17
FEATURE SELECTION, PARTITION #1
24
17
-
Segment #1
Quick Arm “
Re-Exit “
Auto Bypass “
Silent Panic “
Audible Panic “
Auxiliary 1 “
Auxiliary 2 “
Multi Keypress Tamper “
19
26
19
Page 30
TURN AON@ FOR:
1 - Pager format (no handshake required) “
2 - 1400/2300 handshake “
3 - Reserved
4 - Reserved
5 - Contact ID “
6 - SIA “
7 - Contact ID or 4+3 “
8 - DTMF “
8-4-8-0-0-0-0-0
__ __ __ __ __ __ __ __
8
__
14-14-14-14-14-14-14-1414-14-14-14-14-14-14-1414-14-14-14
__ __ __ __ __ __ __ __
__ __ __ __ __ __ __ __
__ __ __ __
Segment #2
LED extinguish enable “
Require user code for bypassing zones “
Bypass sounder alert “
AC power/low battery sounder alert “
Enables bypass toggle “
Enables silent auto arm “
Enables automatic instant “
Reserved
Segment #3
Open/Close “
Bypass “
Restore “
Trouble “
Tamper “
Cancel “
Recent Closing “
Exit Error “
ENTRY/EXIT TIMERS, PARTITION 1
Segment
Segment
Segment
Segment
25
PROGRAMMING DATA
Segment #2
TURN AOFF@ FOR:
1900hz “
1400hz “
double round parity “
1 digit code “
Reserved
Reserved
10 or 40 p.p.s. “
20 or 40 p.p.s. “
TURN AON@ FOR:
1 - 1800hz transmit “
2 - 2300hz handshake “
3 - Cksum parity “
4 - 2 digit event code “
5 - Reserved
6 - Reserved
7 - 20 p.p.s. “
8 - 10 p.p.s. “
DOWNLOAD ACCESS CODE
1
2
3
4
5
6
7
8
DEFAULT
#1
#2
#3
#4
(Entry Time #1)
(Exit Time #1)
(Entry Time #2)
(Exit Time #2)
ZONES 1-8, ZONE TYPES
30
60
30
60
__
__
__
__
3-5-6-6-6-6-6-6
__ __ __ __ __ __ __ __
ZONES 1-8, PARTITION SELECTION (Segment 1=Zone 1 thru Segment 8=Zone 8)
Segment #1
1 - Partition #1 “
2 - Partition #2 “
Segment #3
1 - Partition #1 “
2 - Partition #2 “
Segment #5
1 - Partition #1 “
2 - Partition #2 “
Segment #7
1 - Partition #1 “
2 - Partition #2 “
Segment # 2
1 - Partition #1 ‘
2 - Partition #2 ‘
Segment #4
1 - Partition #1 “
2 - Partition #2 “
Segment #6
1 - Partition #1 “
2 - Partition #2 “
Segment #8
1 - Partition #1 “
2 - Partition #2 “
LOC
PG
27
19
ZONES 9-16, ZONE TYPES
28
19
ZONES 9-16, PARTITION SELECTION (Segment 1=Zone 9 thru Segment 8=Zone 16)
37
19
DESCRIPTION
DEFAULT
PROGRAMMING DATA
6-6-6-6-6-6-6-6
__ __ __ __ __ __ __ __
Segment #1
1 - Partition #1 “
2 - Partition #2 “
Segment #3
1 - Partition #1 “
2 - Partition #2 “
Segment #5
1 - Partition #1 “
2 - Partition #2 “
Segment #7
1 - Partition #1 “
2 - Partition #2 “
Segment # 2
1 - Partition #1 ‘
2 - Partition #2 ‘
Segment #4
1 - Partition #1 “
2 - Partition #2 “
Segment #6
1 - Partition #1 “
2 - Partition #2 “
Segment #8
1 - Partition #1 “
2 - Partition #2 “
SIREN AND SYSTEM SUPERVISION
Segment #1
1
2
3
4
5
6
7
8
-
Siren sounds for telephone line cut while armed “
Siren sounds for telephone line cut while disarmed “
Siren blast at arming “
Siren blast at exit delay expiration “
Siren blast at closing kissoff “
Siren sounds during a cross zone verification time “
Siren sounds for a tamper “
Siren blast one time for keyswitch arming, two times for disarming “
Segment #2
1
2
3
4
5
6
7
8
-
Convert siren driver to voltage out “
Siren sounds for expander trouble (required for U.L.) “
Immediate restore by zone “
Dynamic battery test performed upon arming “
Battery missing test performed every 12 seconds “
Manual bell test performed during [r]-[4] test function “
Manual communicator test performed during [r]-[4] test function “
Box tamper enabled. “
Segment #3
1
2
3
4
5
6
7
8
-
Box Tamper report enabled “
AC Fail report enabled “
Low Battery report enabled “
Auxiliary power over current report enabled “
Siren supervision report enabled “
Telephone Line Cut report enabled “
Reserved.
Expander trouble report enabled “
Segment #4
1
2
3
4
5
6
7
8
-
Failure To Communicate report enabled “
Log Full report enabled “
Autotest report enabled “
Start and End Programming report enabled “
End Download report enabled “
Sensor Low Battery report enabled “
Sensor Missing report enabled “
Reserved.
Segment #5
1
2
3
4
5
6
7
8
38
20
-
Lost Clock service LED enable “
Enables Zone Doubling for zones 7-12 (requires NX-200 Zone Doubling Kit) “
Disables on-board zones “
Enables two trips on the same cross-zone to activate the alarm “
Disables bypass reports for force armed zones “
Silent exit “
Clock uses internal crystal “
Disable Temporal Siren on Fire (must NOT disable for UL systems) “
SWINGER SHUTDOWN COUNT
0
_
Page 31
LOC
PG
39
20
DESCRIPTION
DEFAULT
PROGRAMMING DATA
KEYPAD SOUNDER CONTROL
1 - Keypad sounds for Telephone Line Cut when in the Armed state “
2 - Keypad sounds for Telephone Line Cut when in the Disarmed state “
3 - Keypad sounds upon AC Power Failure “
4 - Keypad sounds upon Low Battery Detection “
5 - Keypad sounds during Cross Zone Trip Time “
6 - Keypad sounds for Tamper Alarm “
7 - Reserved.
8 - Keypad sounds for expander trouble (required for UL) “
40
20
SYSTEM TIMERS
Seg #
1 - Dynamic Battery Test duration (0-255 minutes)
2 - AC Failure report delay (0-255 minutes)
3 - Power Up Delay (0-60 seconds)
4 - Siren Time (1-255 minutes)
5 - Telephone Line Cut delay (0-255 seconds)
6 - Cross Zone Time (0-255 minutes)
7 - Chime Time in 50 mS increments (0-255 mS)
8 - Dialer delay ( 0-255 seconds)
9 - Fire Alarm Verification Time (120-255 seconds)
10 - Listen-In Time (0-255 seconds)
41
0
5
0
8
0
5
3
0
0
0
__
__
__
__
__
__
__
__
__
__
21
SPECIAL FEATURES
42
21
1 - Enables 6-digit code option -B all Arm/Disarm/=Go To Program= codes require 6 digits “
2 - Requires valid user code entry for [r]-[9]-[8] and [r]-[9]-[9] functions to work “
3 - Enable Auto Cancel / Abort “
4 - Enable Walk-Test Mode “
5-8 Reserved.
GO TO PROGRAM CODE
9-7-1-3-0-0
43
21
GO TO PROGRAM CODE PARTITION AND AUTHORIZATION
______
Segment #1
1
2
3
4
5
6
7
8
-
Reserved.
Enables "Go
Enables "Go
Enables "Go
Enables "Go
Enables "Go
Enables "Go
Reserved.
To
To
To
To
To
To
Program
Program
Program
Program
Program
Program
Code"
Code"
Code"
Code"
Code"
Code"
as an arm only code “
as an arm only after closing “
as a master arm/disarm code (can change user codes) “
as an arm/disarm code “
to bypass zones “
opening and closing reports “
Segment #2
44
21
45
21
46
21
1 - Enables "Go To Program Code" for partition #1
2 - Enables "Go To Program Code" for partition #2
DURESS CODE
15-15-15-15-15-15
AUXILIARY OUTPUTS 1-4 PARTITION SELECTION
Segment #1
Segment #2
1 - Partition #1 “
1 - Partition #1 “
2 - Partition #2 “
2 - Partition #2 “
AUXILIARY OUTPUTS 1-4 SPECIAL TIMING
(Segment 1 = Aux 1, Segment 4= Aux 4)
Segment #3
1 - Partition #1 “
2 - Partition #2 “
1 - Auxiliary output timed in minutes
2 - Auxiliary output to latch
3 - Auxiliary output to stop timing upon user code entry
4 - Auxiliary output to activate only between closing and opening time
5 - Auxiliary output to activate only between opening and closing time
6 - Invert auxiliary output ( 0 volts going to 12 volts when activated)
7 - Reserved
8 - Reserved
47
22
Segment #4
1 - Partition #1 “
2 - Partition #2 “
Segments
1
2
3
4
“
“
“
“
“
“
“
“
“
“
“
“
“
“
“
“
“
“
AUXILIARY OUTPUT #1, EVENT & TIME
Segment #1: Program the event number for output #1
Segment #2: Program the timing for output #1
Page 32
__ __ __ __ __ __
0=Burglary alarm
10 seconds
___
___
“
“
“
“
“
“
LOC
PG
48
22
DESCRIPTION
Segment #1: Program the event number for output #2
Segment #2: Program the timing for output #2
49
22
22
52
23
AUTOTEST CONTROL
23
Segment #1: Program a "1" if the interval is hours, a "0" if
in days. Program a A2" to suppress the daily test or a A3" to
suppress the hourly test.
Segment #2: Program the autotest interval from 1-255
days or hours.
Segment #3: Program the autotest report in 24-hour time
format.
Segment #4: Program the autotest report time, minutes
after the hour.
OPENING TIME
Segment #1: Program the hour of the opening time
Segment #2: Program the minutes after the hour of the
opening time
53
23
23
DAYS OF THE WEEK EACH PARTITION IS OPEN
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Reserved
55
23
___
___
2= 24 Hour Alarm
10 seconds
___
___
39 - Smoke Power
0=Follow condition
___
___
0
___
24
___
2
___
0
___
8
0
___
___
CLOSING TIME / AUTO ARMING TIME
Segment #1: Program the hour of the closing time / auto
arming time
Segment #2: Program the minutes after hour of closing/
auto arming time
54
1=Fire alarm
10 seconds
AUXILIARY OUTPUT #4, EVENT & TIME
Segment #1: Program the event number for output #4
Segment #2: Program the timing for output #4
51
PROGRAMMING DATA
AUXILIARY OUTPUT #3, EVENT & TIME
Segment #1: Program the event number for output #3
Segment #2: Program the timing for output #3
50
DEFAULT
AUXILIARY OUTPUT #2, EVENT & TIME
DAYS OF THE WEEK EACH PARTITION WILL "AUTO ARM"
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Reserved
20
0
Segments 1 - 2
1
2
3
4
5
6
7
8
Segments 1 - 2
1
2
3
4
5
6
7
8
Partition 1 -2
“
“
“
“
“
“
“
“
“
“
“
“
“
“
Partition 1 -2
“
“
“
“
“
“
“
“
“
“
“
“
“
“
COMMUNICATOR CODES FOR SLOW SPEED FORMATS ONLY
56
24
RESTORE COMMUNICATOR CODE
Segment #1: Partition #1 Restore code
Segment #2: Partition #2 Restore code
57
24
24
24
0
0
___
___
0
0
___
___
0
0
___
___
TAMPER COMMUNICATOR CODE
Segment #1: Partition #1 Tamper Code
Segment #2: Partition #2 Tamper Code
59
___
___
BYPASS COMMUNICATOR CODE
Segment #1: Partition #1 Bypass code
Segment #2: Partition #2 Bypass code
58
14
0
TROUBLE COMMUNICATOR CODE
Segment #1: Partition #1 Trouble Code
Segment #2: Partition #2 Trouble Code
Page 33
LOC
PG
60
24
SENSOR LOW BATTERY COMMUNICATOR CODE
DEFAULT
PROGRAMMING DATA
24
Segment #1: Partition #1 Sensor Low Battery Code
Segment #2: Partition #2 Sensor Low Battery Code
SENSOR MISSING COMMUNICATOR CODE
0
0
___
___
24
Segment #1: Partition #1 Sensor Missing Code
Segment #2: Partition #2 Sensor Missing Code
DURESS
0
0
0-0
___
___
__ __
62
63
64
24
AUXILIARY 1
0-0
__ __
24
AUXILIARY 2
0-0
__ __
65
66
25
KEYPAD PANIC
0-2
__ __
25
KEYPAD MULTIPLE CODE ENTRY TAMPER
0-0
__ __
67
25
BOX TAMPER / BOX TAMPER RESTORE
0-0-0-0
__ __ __ __
68
25
AC FAIL / AC RESTORE
0-0-0-0
__ __ __ __
69
25
LOW BATTERY / LOW BATTERY RESTORE
0-0-0-0
__ __ __ __
70
25
POWER SHORT / POWER SHORT RESTORE
0-0-0-0
__ __ __ __
71
25
BELL TAMPER / BELL TAMPER RESTORE
0-0-0-0
__ __ __ __
72
25
TELEPHONE LINE CUT / TELEPHONE LINE CUT RESTORE
0-0-0-0
__ __ __ __
74
25
EXPANDER TROUBLE / EXPANDER TROUBLE RESTORE
0-0-0-0
__ __ __ __
75
25
FAILURE TO COMMUNICATE
0-0
__ __
76
26
LOG FULL COMMUNICATOR CODE
0-0
__ __
77
26
OPENING COMMUNICATOR CODE
11
0
__
__
26
Segment #1: Partition #1 Opening Code
Segment #2: Partition #2 Opening Code
CLOSING COMMUNICATOR CODE
79
26
Segment #1: Partition #1 Closing Code
Segment #2: Partition #2 Closing Code
AUTOTEST COMMUNICATOR CODE
12
0
0-0
__
__
__ __
80
26
RECENT CLOSING AND EXIT ERROR
0-0
__ __
81
26
START PROGRAMMING / END PROGRAMMING
0-0-0-0
__ __ __ __
82
26
END DOWNLOAD
0-0-0-0
__ __ __ __
83
26
CANCEL COMMUNICATOR CODE
0
__
88
27
PARTITION 1, ACCOUNT CODE
10-10-10-10-10-10
__ __ __ __ __ __
89
27
PARTITION 2, ACCOUNT CODE
10-10-10-10-10-10
__ __ __ __ __ __
90
27
PARTITION 2, FEATURE SELECTION
27
Segment #2
Segment #1
LED extinguish enable “
1 - Quick Arm “
Require user code for bypassing zones “
2 - Re-Exit “
Bypass sounder alert “
3 - Auto Bypass “
AC power/low battery sounder alert “
4 - Silent Panic “
Enables bypass toggle “
5 - Audible Panic “
Enables silent auto arm “
6 - Auxiliary 1 “
Enables automatic instant “
7 - Auxiliary 2 “
8 - Multi Keypress Tamper “ Reserved
PARTITION 2, ENTRY/EXIT TIMERS
61
78
91
DESCRIPTION
Segment
Segment
Segment
Segment
Page 34
#1
#2
#3
#4
(Entry Time #1)
(Exit Time #1)
(Entry Time #2)
(Exit Time #2)
0
0
0
0
Segment #3
Open/Close “
Bypass “
Restore “
Trouble “
Tamper “
Cancel “
Recent Closing “
Exit Error “
__
__
__
__
LOC
PG
DESCRIPTION
DEFAULT
PROGRAMMING DATA
CUSTOMIZING ZONE TYPES (GROUPS)
110
28
ZONE TYPE 1 ALARM EVENT CODE
111
28
ZONE TYPE 1 CHARACTERISTIC SELECTION
8
__
Segment #1
1 - Fire (enable for fire zone) “
2 - 24 Hour (enable for non-fire 24 hour zone) “
3 - Keyswitch zone “
4 - Follower (enable for burg zones that are instant during non-entry times) “
5 - Delay 1 zone (enable to follow Timer #1 Entry/Exit) “
6 - Delay 2 zone (enable to follow Timer #2 Entry/Exit) “
7 - Interior (Enable for auto bypass or stay arming) “
8 - Local Only (enable if zone is not to be reported) “
Segment #2
1 - Keypad audible on alarm “
2 - Yelping siren on alarm “
3 - Temporal siren on alarm “
4 - Chime “
5 - Bypassable “
6 - Group Shunt “
7 - Force armable “
8 - Entry Guard “
Segment #3
1 - Reserved
2 - Double End of Line Tamper zone “
3 - Trouble zone (Day zone) “
4 - Cross Zone “
5 - Dialer Delay zone “
6 - Swinger zone “
7 - Restore reporting “
8 - Listen-In “
THE DEFAULTS LISTED IN THE ODD NUMBERED LOCATIONS BELOW REPRESENT THE THREE SEGMENTS OF EACH OF
THOSE LOCATIONS. USE THE THREE SEGMENT CHARTS FROM TABLE 3.1, PAGE 28 TO UNDERSTAND THESE DEFAULTS.
112
28
ZONE TYPE 2 ALARM EVENT CODE
113
28
ZONE TYPE 2 CHARACTERISTIC SELECT
114
28
ZONE TYPE 3 ALARM EVENT CODE
115
28
ZONE TYPE 3 CHARACTERISTIC SELECT
116
28
ZONE TYPE 4 ALARM EVENT CODE
117
28
ZONE TYPE 4 CHARACTERISTIC SELECT
118
28
ZONE TYPE 5 ALARM EVENT CODE
119
28
ZONE TYPE 5 CHARACTERISTIC SELECT
120
28
ZONE TYPE 6 ALARM EVENT CODE
121
28
ZONE TYPE 6 CHARACTERISTIC SELECT
122
28
ZONE TYPE 7 ALARM EVENT CODE
123
28
ZONE TYPE 7 CHARACTERISTIC SELECT
124
28
ZONE TYPE 8 ALARM EVENT CODE
125
28
ZONE TYPE 8 CHARACTERISTIC SELECT
126
28
ZONE TYPE 9 ALARM EVENT CODE
127
28
ZONE TYPE 9 CHARACTERISTIC SELECT
128
28
ZONE TYPE 10 ALARM EVENT CODE
129
28
ZONE TYPE 10 CHARACTERISTIC SELECT
130
28
ZONE TYPE 11 ALARM EVENT CODE
2
____
2-125-78
_____ _____ _____
7
____
5-1245-5678
_____ _____ _____
5
____
45-125-5678
_____ _____ _____
5
____
457-125-5678
_____ _____ _____
4
____
0-1245-5678
_____ _____ _____
0
____
2-0-78
_____ _____ _____
1
____
1-13-378
_____ _____ _____
7
____
6-1245-5678
_____ _____ _____
2
____
24-5-78
_____ _____ _____
3
____
Page 35
LOC
PG
131
28
ZONE TYPE 11 CHARACTERISTIC SELECT
DESCRIPTION
132
28
ZONE TYPE 12 ALARM EVENT CODE
133
28
ZONE TYPE 12 CHARACTERISTIC SELECT
134
28
ZONE TYPE 13 ALARM EVENT CODE
135
28
ZONE TYPE 13 CHARACTERISTIC SELECT
136
28
ZONE TYPE 14 ALARM EVENT CODE
137
28
ZONE TYPE 14 CHARACTERISTIC SELECT
138
28
ZONE TYPE 15 ALARM EVENT CODE
139
28
ZONE TYPE 15 CHARACTERISTIC SELECT
140
28
ZONE TYPE 16 ALARM EVENT CODE
141
28
ZONE TYPE 16 CHARACTERISTIC SELECT
142
28
ZONE TYPE 17 ALARM EVENT CODE
143
28
ZONE TYPE 17 CHARACTERISTIC SELECT
144
28
ZONE TYPE 18 ALARM EVENT CODE
145
28
ZONE TYPE 18 CHARACTERISTIC SELECT
146
28
ZONE TYPE 19 ALARM EVENT CODE
147
28
ZONE TYPE 19 CHARACTERISTIC SELECT
148
28
ZONE TYPE 20 ALARM EVENT CODE
149
28
ZONE TYPE 20 CHARACTERISTIC SELECT
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16
Page 36
PROGRAMMING DATA
3-0-0
_____ _____ _____
5
____
457-125-45678
_____ _____ _____
4
____
0-12458-5678
_____ _____ _____
7
____
5-12456-5678
_____ _____ _____
5
____
457-1256-5678
_____ _____ _____
4
____
0-12456-5678
_____ _____ _____
7
____
5-1245-25678
_____ _____ _____
5
____
457-125-25678
_____ _____ _____
4
____
0-1245-25678
_____ _____ _____
7
____
6-1245-25678
_____ _____ _____
ZONE DESCRIPTIONS
1
DEFAULT
APPENDIX 1 REPORTING FIXED CODES IN CONTACT ID AND SIA
The table below lists the event codes sent for the following reports (if enabled) when using CONTACT ID or SIA formats.
REPORT
MANUAL TEST
AUTOTEST
OPEN (user number)
CLOSE (user number)
CANCEL (user number)
DOWNLOAD COMPLETE
START PROGRAM
END PROGRAM
RECENT CLOSE (user number)
EXIT ERROR (user number)
EVENT LOG FULL
FAIL TO COMMUNICATE
EXPANDER TROUBLE (device number)
EXPANDER RESTORE (device number)
TELEPHONE FAULT
TELEPHONE RESTORE
SIREN TAMPER (device number)
SIREN RESTORE (device number)
AUX POWER OVER CURRENT (device number)
AUX POWER RESTORE (device number)
LOW BATTERY (device number)
LOW BATTERY RESTORE (device number)
AC FAIL (device number)
AC RESTORE (device number)
BOX TAMPER (device number)
BOX TAMPER RESTORE (device number)
KEYPAD TAMPER
KEYPAD PANIC AUDIBLE
KEYPAD PANIC SILENT
DURESS
KEYPAD AUXILIARY 1
KEYPAD AUXILIARY 2
RF SENSOR LOST (zone number)
RF SENSOR RESTORE (zone number)
SENSOR LOW BATTERY (zone number)
SENSOR BATTERY RESTORE (zone number)
ZONE TROUBLE (zone number)
ZONE TROUBLE RESTORE (zone number)
ZONE TAMPER (zone number)
ZONE TAMPER RESTORE (zone number)
ZONE BYPASS (zone number)
BYPASS RESTORE (zone number)
CONTACT ID
601
602
401
401
406
412
627
628
401
457
605
354
333
333
351
351
321
321
312
312
309
309
301
301
137
137
137
120
121
121
110
100
381
381
384
384
380
380
137
137
570
570
SIA
RX
RP
OP
CL
OC
RS
LB
LX
CR
EE
JL
RT
ET
ER
LT
LR
YA
YH
YP
YQ
YT
YR
AT
AR
TA
TR
TA
PA
HA
HA
FA
MA
*T
*R
XT
XR
*T
*R
TA
TR
*B
*U
* The character transmitted in this slot will be the first character from the event code of the zone
that is bypassed or in trouble. (See locations 110 - 141)
THE NUMBER IN PARENTHESES FOLLOWING THE EVENT IS THE NUMBER THAT WILL BE REPORTED AS THE
ZONE NUMBER. IF THERE ARE NO PARENTHESES, THE ZONE WILL BE A0". SEE PAGE 39 FOR THE DEVICE
NUMBERS.
Page 37
APPENDIX 2 REPORTING ZONE CODES IN SIA OR CONTACT ID
The NX-6 has the ability to report SIA level 1 transmissions to either or both phone numbers. Each report in SIA consists
of an Event Code and a Zone or User ID. The Zone ID will be the zone number that is in alarm. The event code will come
from the chart below and be programmed in the Zone Type event code.
Programmed Event Code
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
SIA Code
HA
FA
PA
BA
BA
BA
UA
BA
BA
UA
HA
MA
PA
TA
RP
GA
KA
WA
QA
SA
ZA
Description
Holdup Alarm
Fire Alarm
Panic Alarm
Burglary Alarm
Burglary Alarm
Burglary Alarm
Untyped Alarm
Burglary Alarm
Burglary Alarm
Untyped Alarm
Holdup Alarm
Medical Alarm
Panic alarm
Tamper Alarm
Periodic Test
Gas Alarm
Heat Alarm
Water Alarm
Emergency Alarm
Sprinkler Alarm
Freeze Alarm
The NX-6 has the ability to report Ademco Contact ID transmissions. Each report in Contact ID consists of an Event Code
and a Zone ID. The zone ID is the zone that created the alarm. The event code will come from the chart below and be
programmed in the Zone Type event code.
Programmed Event Code
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Page 38
Contact ID Code
122
110
120
130
131
132
133
134
135
150
121
100
123
137
602
151
158
154
140
140
159
Description
Silent Panic
Fire Alarm
Panic Alarm
Burglary Alarm
Perimeter Alarm
Interior Alarm
24 Hour Burglary
Entry Alarm
Day/Night Alarm
Non Burglary 24 Hour
Duress Alarm
Medical Alarm
Audible Panic Alarm
Tamper Alarm
Periodic Test
Gas Detected
High Temp
Water Leakage
General Alarm
General Alarm
Low Temp
APPENDIX 3 EXPANDER NUMBERS FOR REPORTING EXPANDER TROUBLE
The tables below list the device numbers that will be reported for trouble conditions.
Device
Device # reported
NX-6 Control Panel
0
NX-534E Two Way Listen In
64
NX-540E NetworX AOperator@
40
NX-591E Cellemetry Interface
76
See page 37 for possible report codes.
KEYPADS
KEYPAD
PARTITION 1
PARTITION 2
1
192
193
2
200
201
3
208
209
4
216
217
5
224
225
6
232
233
7
240
241
8
248
249
REMOTE POWER SUPPLY (NX-320E)
Address & Dip Switch Setting
OUTPUT MODULE (NX-508E)
Address & Dip Switch Setting
84 (All switches off)
88 (Switch 3 on)
24 (Switch 1 & 2 on)
85 (Switch 1 on)
89 (Switch 1 & 3 on)
25 (Switch 3 on)
86 (Switch 2 on)
90 (Switch 2 & 3 on)
26 (Switch 1 & 3 on)
30 (Switch 1 on)
87 (Switch 1 & 2 on)
91 (All switches on)
27 (Switch 2 & 3 on)
31 (Switch 2 on)
28 (Switch 1,2,& 3 on)
29 (All switches off)
WIRELESS RECEIVER (NX-408E, NX-416E, NX-448E)
Dip Switch Setting
32 (Switches 1 & 3 on)
Expander # reported
36 (Switch 1 on)
33 (Switches 2 & 3 on)
37 (Switch 2 on)
34 (Switch 1, 2 & 3 on)
38 (Switches 1 & 2 on)
35 (All switches off)
39 (Switch 3 on)
Page 39
NX-6 WIRING DIAGRAM
Page 40
TERMINAL DESCRIPTION
TERMINAL
R1
DESCRIPTION
House Telephone Ring (Grey)
R
Telephone Ring (Red)
T
Telephone Tip (Green)
T1
EARTH
AC
House Telephone Tip (Brown)
Earth Ground. Connect to a cold water pipe or a 6 to 10 foot driven rod.
AC input. Connect to a 16.5V 25, 40 or 50 VA Class ll U.L. approved transformer.
BELL + &
BELL -
If used as a siren output(default), the speaker rating should be 15 watt at 8 or 16 Ω, or 30/40 watt at 4, 8, or 16
Ω. If voltage output is selected in location 37, this output becomes voltage output, 12VDC, 1 Amp maximum load.
NOTE: A 3.3K resistor may be required across the bell terminals when a 12 VDC siren is used. If no
resistor is used, you may experience voltage leakage into the siren which will cause these devices to
output a small signal.
KP DATA
Connect to the data terminal on the keypads and the expanders. When connecting more than one keypad to the
end of the wire, a higher gauge wire will be required. Maximum number of devices is 8 keypads + 3 other devices.
KP COM
Connect to the Common terminal on the keypads and the expanders.
KP POS
Connect to the Positive terminal on the keypads and the expanders. This terminal and AUX PWR + are limited to 1
amp total current when added together.
COM
AUX PWR+
ZONE 6
COM
ZONE 5
ZONE 4 ZONE 1
Connect negative wire of powered devices such as motion detectors and smoke detectors.
Connect positive wire of all powered devices except smoke detectors and keypads. This terminal and KP POS are
limited to 1 amp total current when added together.
Connect to one side of zone 6 loop. Connect the other side to com terminal. Open or short causes alarm.
Common (-) terminal for zones 5 & 6.
Connect to one side of zone 5 loop. Connect the other side to COM terminal. Open or short causes alarm.
Connect as described for zones 5 & 6. (See the wiring diagram for examples.)
AUX OUT 4
SMOKE +
(ZONE 7)
Smoke detector power 12VDC (for those jurisdictions that allow the Priority zone to be used with smoke detectors).
Current limited to 250 mA when output is positive and 250 microamps when output is negative. This output
defaults to Smoke Power, but can be re-configured. Zone 7 may be used for a 2-wire smoke detector using a
680 Ω E.O.L. resistor. W3 must be removed for 2-wire smoke detector loop. For use as Aux Out 4, W2
must be set. The 2-wire smoke loop cannot be enabled if Zone Doubling is used.
AUX OUT 3 AUX OUT 1
Connect negative lead of low current device [relay, LED (install 1K resistor in series with LED), etc.]. Connect
positive lead of device to AUX PWR +. Current limited to 250 microamps maximum when output is positive and
250 mA when output is negative.
NETWORX KEYPAD WIRING REQUIREMENTS
(NOTE: These numbers are for one keypad at the end of the wire. When connecting more than one device to the end
of the wire, a higher gauge wire will be required.)
WHEN CONNECTED TO NX-6
WHEN CONNECTED TO NX-320
Length in feet
Wire Gauge
Wire Gauge
250
24
22
500
20
18
1000
18
16
1500
16
14
2500
14
12
Page 41
LOCAL TELEPHONE COMPANY INTERFACE INFORMATION
TELEPHONE CONNECTION REQUIREMENTS
Except for telephone company provided ringers, all connections to the telephone network shall be made through
standard plugs and standard telephone company provided jacks or equivalent in such a manner as to allow for immediate
disconnection of the terminal equipment. Standard jacks shall be so arranged that if the plug connected thereto is
withdrawn, no interference to the operation of the equipment at the customers’ premises which remains connected to the
telephone network, shall occur by reason of such withdrawal.
INCIDENCE OF HARM
Should terminal equipment or protective circuitry cause harm to the telephone network, the telephone company shall,
where practical, notify the customer that temporary discontinuance of service may be required. However, where prior
notice is not practical, the telephone company may temporarily discontinue service if such action is deemed reasonable in
the circumstances. In the case of such temporary discontinuance, the telephone company shall promptly notify the
customer who will be given the opportunity to correct the situation. The customer also has the right to bring a complaint
to the FCC if he feels the disconnection is not warranted.
CHANGES IN TELEPHONE COMPANY EQUIPMENT OR FACILITIES
The telephone company may make changes in its communications facilities, equipment, operations, or procedures where
such action is reasonably required and proper in its business. Should any such change render the customers terminal
equipment incompatible with the telephone company facilities, the customer shall be given adequate notice to make
modifications to maintain uninterrupted service.
GENERAL
The FCC prohibits customer provided terminal equipment be connected to party lines.
IMPORTANCE OF THE RINGER EQUIVALENCE NUMBER
The Ringer Equivalence Number (REN) of this device is 0.1B. This number is a representation of the electrical load that it
applies to your telephone line.
MALFUNCTION OF THE EQUIPMENT
In the event that the device should fail to operate properly, the customer shall disconnect the equipment from the
telephone line to determine if it is the customers equipment that is not functioning properly. If the problem is with the
device, the customer shall discontinue use until it is repaired.
EQUIPMENT INFORMATION
MANUFACTURER OF CONNECTING EQUIPMENT: CADDX CONTROLS, INC.
FCC REGISTRATION NUMBER: GCQUSA-25950-AL-E, RINGER EQUIVALENCE: 0.1 B
Page 42
UNDERWRITERS LABORATORIES INFORMATION
The NetworX NX-6 holds the following listings from Underwriters Laboratories (North America & Canada):
Household Burglary (UL1023) (ORD-C1023-1974)
Household Fire (UL985) (CAN/ULC-S545-M89)
Local Grade A Mercantile, Police Station Connect w/Basic Line Security (UL609) (requires NX-003-C
enclosure) (CAN/ULC-S303-M91)
Grade B & C Central Station Burglar Alarm Unit (UL1610) (CAN/ULC-S304-M88)
Home Health Care Signaling (UL1637)
When installing an NX-6 in compliance with Underwriters Laboratories, the following instructions must be observed:
! Initiating and indicating devices must be rated at 11.5 to 12.4 V DC residential, 12.0 V DC commercial.
! When using partitioning in Commercial Burglary applications, the main control must be protected by a 24-hour alarm
circuit.
! Force Arming and Auto Arming shall not be enabled.
! For residential fire applications, the indicating devices shall be a Wheelock 34T-12 or equivalent.
! The "Listen-In" feature shall not be enabled.
! The Siren/Bell Test shall be enabled. The auxiliary outputs controlling the audible device require a minimum cutoff
time of 15 minutes for commercial burglary, 4 minutes for residential applications, or 30 minutes for commercial
burglary for Canada.
! For residential fire installations, the Dynamic Battery Test time cannot exceed four (4) hours.
! Ringback shall be enabled on UL commercial burglary installations.
! On commercial burglary installations, the fire initiating circuits shall not be connected.
! The Entry-Guard feature shall be disabled.
! Swinger Shutdown shall be disabled.
! Group Bypassing shall be disabled.
! Delay before dial seizure shall be set to "0".
! Total current draw from aux power connections at terminal positions POS, AUX PWR, and SMOKE PWR must not
exceed 400 mA.
! Remote Downloading shall not be used on UL listed systems.
! For residential burglary applications, the maximum entry and exit delay times shall be 45 and 60 seconds
respectively. The exit delay time shall not exceed 60 seconds for commercial burglar alarm applications.
! The keyswitch option shall not be used.
! The Telephone Line Monitor shall be enabled.
! The Telephone Line Cut delay shall not exceed 90 seconds.
! 24-hour communicator test transmission is required.
! For 24 hours of standby power using a 7.0 AH battery, limit auxiliary power load to 140 mA.
! For 24 hours of standby power using a 17.2 AH battery, limit auxiliary power load to 400 mA.
! The silent keypad option shall not be enabled.
! UL has only verified compatibility with the following listed DACRs and formats: Sure-Gard SG-MLR2-DG:
2,9,10,12,13,14; Silent Knight 9000 - 2,12; FBI - CP220FBI, 13; and Ademco 685: 2,11,12, and 13.
! For burglary installations, cross-zoned detectors shall overlap 100 percent in the area of coverage and similar
coverage areas must be used. For example, interior protection is cross-zoned with interior protection, and so on.
! Expander trouble must activate the siren (Loc 37, Segment 2, LED 2)
! For UL 1637, expander trouble must activate keypad sounder (Loc 39, Segment 1, LED 8)
! The keypad used with wireless receivers and hardwire expansion must be able to display all zones in the system.
! For Canadian installations, the class II transformer secure tabs shall not be employed.
!
!
!
!
!
!
!
MINIMUM SYSTEM CONFIGURATIONS FOR UL INSTALLATIONS
(Residential Fire, Residential Burglary, Commercial Burglary)
The NetworX NX-6 panel is necessary to initiate Residential and Commercial installations.
At least one compatible keypad is needed for all applications.
At least one bell fixture is required for all applications, except Grade C Central Station. For Grade A Local, the AD1012 bell and Grade A bell housing shall be used.
Commercial UL applications require #NX-003-C metal enclosure. Supplied screws to be used.
A minimum of two (2) keypads are required for Home Health applications and each keypad must be set to a unique
address.
The wireless devices are only UL listed for residential applications.
The DACT shall be enabled for all commercial burglary applications.
Page 43
NX-6 BOARD INSTALLATION
Inside the can, several 2-holed insertion points have been constructed. This allows
for either vertical or horizontal placement of the modules. Notice that each insertion
point has two sizes of holes B a larger hole and a smaller hole.
Diagram 1: The black plastic PCB guides are grooved on one edge where the PC
board will be seated. The end with the half-moon protrusion fits into the larger hole.
The smaller hole is for the screw.
Diagram 2: Place the first black plastic PCB guide in the top insertion point, grooved
edge downward. The half-moon protrusion will be in the large hole. It does not
require force. Insert one of the provided screw into the smaller hole (from inside the
can) to secure it in place. A screwdriver should reach through the notch that runs the
length of the guide to tighten the screw. The second PBC guide should be positioned
opposite the first (grooved edge up) and placed in the lower insertion point, using the
same procedures described above. Once mounted, screw it in securely.
Diagram 3: The PC Board should slide freely in the grooves of both guides.
K
IMPORTANT!
1. If separate power supplies are necessary to accommodate additional devices, safety standards
require that each power supply be prominently marked with adequate instructions for removing all
power from the unit.
2. Dispose of used batteries according to the manufacturer’s instructions and/or local government
authorities.
3. Installation personnel should thoroughly read and understand the installation instructions and the
users manuals for the panel and all the accessories to be included with the system before
attempting to install a security system.
WARNING!
Replace only with Panasonic #LC12V4BP or Yuasa #NP4-12 battery. Observe polarity when installing a
new battery. Installing the battery backwards may cause damage to the panel. There is a risk of
explosion if the battery is replaced with an incorrect type.
NOTE
Electrical codes will vary depending upon the country and city where the system is installed. It is the
installer’s responsibility to ensure that the electrical installation is safe and conforms to all applicable
codes, laws, or regulations. Only qualified persons should connect this device to the mains supply.
Page 44
CE NOTICES
(Applies to products which have the CE mark
attached)
Declaration of Conformity
Manufacturer’s Name:
Manufacturer’s Address:
Caddx Controls
1420 North Main St.
Gladewater TX 75647
EU Representative:
Interlogix Europe
Product Identification
Product:
Model Numbers:
Brand:
NetworX
NX-6
CADDX
R&TTE Directive
See EMC and LVD tests below
EMC Directive
EN50081-1
EN50130-4
EN55022
EN60950
EN61000-3-2
EN61000-3-3
LVD Directive
EN 60950: 1999-4 3rd edition
Means of Conformity
We declare under our sole responsibility that this
product is in conformity with Directive 1999/5/EC
(R&TTE); Directive 73/23/EEC (LVD); and Directive
89/336/EEC (EMC) and based on test results using
(non)-harmonized standards in accordance with the
Directives mentioned.
Additional Tests
This equipment has been tested and found to comply
with the following standards (which are no longer
required for compliance).
Network Compatibility Declaration
We declare under our sole responsibility that this
product is designed to work with the networks in the
countries marked with a check () and may have
interworking problems with the countries that are not
checked. Due to the inherent differences in the
individual PSTNs, certain software settings may need to
be adjusted on a country-to-country basis. If it is
desired to use this equipment on a network other than
the one on which it was originally installed, you should
contact your equipment supplier.
() Austria
(_) Liechtenstein
() Belgium
() Denmark
() Luxembourg
() Netherlands
()
()
()
()
()
()
()
()
()
()
Finland
France
Germany
Greece
Iceland
Norway
Poland
Portugal
Spain
Sweden
() Ireland
() Switzerland
() Italy
() United Kingdom
Telecom Approval Notice
This equipment has been approved in accordance with
the Council Decision 98/482/EC for pan-European,
single terminal connection to the public switched
telephone network (PSTN). However, due to the
differences between the individual PSTNs provided in
different countries, the approval does not, of itself, give
an unconditional assurance of successful operation on
every PSTN network termination point. In the event of
problems, you should contact your equipment supplier
in the first instance.
Electrical Requirements
This device automatically adjusts to voltages within the
range of 230 V 50/60 Hz.
Fuse: Type T 200mA 250 VAC
Page 45
SPECIFICATIONS
OPERATING POWER
16.5 VAC 25, 40, or 50 VA Transformer
AUXILIARY POWER
w/25 VA Transformer
w/40 or 50 VA Transformer
w/NX-320 Power Supply
12 VDC Regulated 500 mA
12 VDC Regulated 1 AMP
12 VDC Regulated 2 AMPS + Panel power
LOOP RESISTANCE
Standard Loop
2-Wire Smokes
300 Ohms Maximum
30 Ohms Maximum
BUILT-IN SIREN DRIVER
2-tone (Temporal and Yelp)
LOOP RESPONSE
500mS
OPERATING TEMPERATURE
32 to 120 degrees F
LED KEYPAD
Current Draw
Zones Normal w/o Sounder
Dimensions
NX-148 LCD KEYPAD
Current Draw
w/o Sounder
Dimensions
130 mA max.
55 mA
6.4" Wide
4.0" High
1.1" Deep
110 mA max.
75 mA
6.4" Wide
5.3" High
1.0" Deep
METAL ENCLOSURE DIMENSION
11.25" Wide
11.25" High
3.50" Deep
SHIPPING WEIGHT
9 lbs.
GE INTERLOGIX
1420 NORTH MAIN STREET
GLADEWATER, TEXAS 75647
TOLL FREE 800-727-2339
FAX 903-845-6811
www.caddx.com
NX-6 INSTALLATION MANUAL
NX6IK02 REV. K (11-20-02)

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Languages