Haes ECL-2/4 fire alarm panel Installation, Commissioning & Operating Manual
Below you will find brief information for fire alarm panel ECL-2/4. This manual guides you through the process of installing, commissioning, and operating the fire alarm panel ECL-2/4. It covers aspects such as safety precautions, mounting the cabinet, connecting the mains supply and batteries, programming options, and troubleshooting.
Advertisement
Advertisement
EN54 APPROVED 2 - 4 ZONE CONVENTIONAL CONTROL
PANEL
Installation, Commissioning &
Operating Manual
810a/03
Approved Document UI-ECL-01 Issue 6.0
0832
Haes Systems Ltd, Columbia House, Packet Boat Lane, Cowley Peachey, Uxbridge, UB8 2JP
13
Model Number
Eclipse 2-4 zone conventional panel ECL-2/4
CPD Number
0832-CPD-2176
European Standard EN54-2 : 1997 + A1 : 2006
Control and indicating equipment for fi re detection and fi re alarm systems for buildings.
Provided Options (with requirements):
Output to fi re alarm devices, dependency type ‘A’, test condition
European Standard EN54-4 : 1997 + A1 : 2002 + A2 : 2006
Power supply equipment for fi re detection and fi re alarm systems for buildings.
IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID
E.S.D
!
IMPORTANT SAFETY NOTES
ATTENTION
ABOUT THIS PANEL
PRODUCT OVERVIEW
CABINET DETAILS
CIRCUIT BOARDS
MAIN PCB TERMINALS
TECHNICAL SPECIFICATION
POWER SUPPLY MODULE
DESIGN CONSIDERATIONS
SYSTEM DESIGN & PLANNING
GENERAL CONVENTIONAL WIRIING SCHEMATIC
GENERAL TWIN WIRE WIRIING SCHEMATIC
INSTALLATION
SAFETY
ESD PRECAUTIONS
GENERAL
MOUNTING THE CABINET
MAINS CONNECTIONS
CONNECTING THE BATTERIES
SETUP & PROGRAMMING
TWIN WIRE MODE
LEVEL 3 ENGINEERING OPTIONS
ZONE INTERFACE FUNCTION
OPERATING
PANEL CONTROLS & INDICATIONS
DISABLE MODE
TEST MODE
FAULT DIAGNOSIS
FUNCTIONALITY DURING A SYSTEM FAULT
USER INSTRUCTIONS
SERVICE & MAINTENANCE
THE NEED FOR MAINTENANCE
DUTIES OF THE RESPONSIBLE PERSON
ROUTINE MAINTENANCE & TESTING
SCHEDULE OF TESTING LOG BOOK
FALSE ALARMS, FAULTS & ENGINEER VISIT LOG BOOK
Eclipse Installation, Commissioning & Operating Manual
1
CONTENTS
8
8
10
11
12
12
13
13
13
14
15
16
16
17
25
Page
2
5
6
7
2
3
4
32
32
32
32
34
40
26
30
31
31
26
28
29
Approved Document Ref: UI-ECL-01 Issue 6.0
ABOUT THIS PANEL
PRODUCT OVERVIEW
Quiesecent and alarm current details for standby battery calculations
Model
ECL-2
ECL-2 (set to Twin Wire mode)
ECL-4
ECL-4 (set to Twin Wire mode)
Standby Current
75mA
75mA
85mA
85mA
Alarm Current
116mA
134mA
133mA
170mA
Eclipse Installation, Commissioning & Operating Manual
2
Approved Document Ref: UI-ECL-01 Issue 6.0
CABINET
ABOUT THIS PANEL
57mm
80mm
Fire Detection System
260mm
308mm
250mm
300mm
Eclipse Installation, Commissioning & Operating Manual
3
Approved Document Ref: UI-ECL-01 Issue 6.0
ABOUT THIS PANEL
CIRCUIT BOARDS
Eclipse panels comprise of two circuit boards
TPCA01-E2/E4 - 2 or 4 zone Master PCB
PSU
@ + -
28V 0V
+
-
FIRE FAULT
C NC NO C NC NO
FR
FLT
CC
PUL
-OP -OP -IP -IP
SNDR1 SNDR2
+ -
ZONE1 ZONE2 ZONE3 ZONE4
+ + + + + -
TPCA02 - LED Display & Controls PCB
+ -
BATTERY
RESOUND SILENCE RESET
1 2 3 4
ENTER
ON
1 2 3
Eclipse Installation, Commissioning & Operating Manual
4
Approved Document Ref: UI-ECL-01 Issue 6.0
MAIN PCB TERMINALS
Switched -ve inputs
Switched -ve outputs
Max load 40mA
Relay Coil
ABOUT THIS PANEL
PSU
@ + -
28V 0V
+
-
FIRE FAULT
C NC NO C NC NO
FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2
+ -
ZONE1 ZONE2 ZONE3 ZONE4
+ + + + + -
Eclipse Installation, Commissioning & Operating Manual
+ -
BATTERY
5
ON
1 2 3
Approved Document Ref: UI-ECL-01 Issue 6.0
ABOUT THIS PANEL
TECHNICAL SPECIFICATION
Electrical Specifi cation Inputs & Outputs - TPCA01-E2/E4
Cabling Fire resistant screened cable, minimum size 1mm
2
. Max cable length 1Km (20
Ohm). FireBurn, FP200 or equivalent
(max capacitance 1uF, max inductance 1 millihenry).
Terminal capacity
PSU @ output
PSU Input + -
28v+, 0v- power output
Common fi re relay
Common fault relay
Outputs; FR, FLT
Inputs; CC, PUL
SNDR 1 - 2
0.5mm
2 to 2.5mm
2 solid or stranded wire.
Power supply voltage control line.
28vdc supply input. Diode protected for reversal and independent short circuit.
Max current 3 amps.
28vdc supply output for fi re alarm accessory relays etc. Max continuous use = 400mA.
Fire relay contact. Clean C/O.
Max 3A @ 30vdc
Maintained fault relay contact. Clean
C/O. Max 3A @ 30vdc
Switched -ve voltage outputs for relay control.
Switched -ve inputs, connect to 0v to trigger. Max input voltage = 28vdc. Non latching, max resistance 100R.
28vdc polarity reversal monitored sounder outputs to fi re alarm devices.
4K7 Ohm 5% 0.25W EOL resistor.
Zone 1 - 4 Fire alarm zone circuits. Conventionally wired detection circuit or Twin Wire combined detection / sounder circuit.
4K7 Ohm 5% 0.25W EOL resistor.
Suitable cable glands must be used.
For temperature compensation control.
Max input current 3 amps. Input voltage
22vdc to 32vdc.
Fused @ 500mA. Fuse = 500mA resettable fuse.
Unfused
Unfused
Overload voltage protected to 52vdc.
Current limited 680R. Max load = 40mA
Protected via 10K Ohm impedance, 3v6 zener diode.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 0.9A is not exceeded.
Monitoring current limit 50mA, fused
@ 500mA. Typical max load 22 alarm devices @ 18mA each per circuit. Ensure
0.9A is not exceeded.
General Specifi cation
Enclosure
Temperature range
Steel IP30. Epoxy powder coated Interpon Radon, silver grey
-5 deg C to +40 deg C max RH 95%
Number of conventional/Twin Wire detection circuits 2 or 4
Conventional/Twin Wire detector compatibility Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
Eclipse Installation, Commissioning & Operating Manual
6
Approved Document Ref: UI-ECL-01 Issue 6.0
ABOUT THIS PANEL
POWER SUPPLY MODULE
Power Supply Specifi cation
Mains supply
Mains supply fuse
Internal power supply rating
Power supply output voltage
Maximum continuous load for battery standby (ImaxA)
Minimum current drawn by panel
(example)
Maximum ripple
Min/max battery size and type
Battery charging voltage
Battery charging output current
230vac +10% / -15% 50Hz max current
1A
2 Amp (T2A 250V) Not accessible for servicing. Internal to switch mode power unit
1.5 Amps total including battery charging Maximum load shared between outputs
= 0.9A
19.92 - 30.09vdc
Tolerance +/- 0.1%
ImaxA = 575mA ImaxB not specifi ed
4 Zone
I min = 85mA
120 mV p-p
2 x 3.2Ahr 12volt VRLA
Use Yuasa NP range batteries
2 Zone
I min = 75mA
Supply and charger fault monitored
Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval.
Temperature compensated
Battery high impedance fault (Batt Hi Z)
Max current drawn from batteries
27.3 vdc nominal at 20 deg C
1.5A PSU 630mA
Current limited 10 Ohms
Resistance > 1 Ohm
1.5 Amps with main power source disconnected. Battery fuse 3A LBC
20mm.
1 hour reporting time
Eclipse Installation, Commissioning & Operating Manual
7
Approved Document Ref: UI-ECL-01 Issue 6.0
DESIGN CONSIDERATIONS
SYSTEM DESIGN & PLANNING - A few handy tips
This guide is intended as an aid to designers and installers of fi re detection systems. It is NOT to be used as a substitute to BS5839 which should be read in full.
What is a detection zone?
In order to direct those responding to a fi re alarm signal, particularly the fi re service, to the area of a fi re, all buildings, other than very small buildings, need to be divided into detection zones. Detection zones need to be small enough for a fi re to be located quickly.
storey total
2
, each zone should be restricted to a single
• If the total fl oor area of the building is less than 300m
2
a zone may cover more than a single storey
• For voids above or below the fl oor area of a room, these may be included within the same zone of the room, provided that the void and the room constitute a single fi re compartment
• The
2
.
Detectors
• A person searching a zone for a fi re in a non- addressable fi re system should not have to travel more than 60m to identify the source of a fi re
• The sensing element of a smoke detection device should not be less than 25mm and not more than
600mm below ceiling
• The sensing element of a heat detector should not be less than 25mm and not more than 150mm below ceiling
• When mounted on a fl at ceiling, smoke detection devices have an individual coverage of 7.5m radius.
However these radii must overlap to ensure there are no ‘blind spots’. Therefore individual coverage can be represented by a square measuring 10.6m x 10.6m giving an actual coverage of 112m
2
per device
• When mounted on a fl at ceiling, heat detection devices have an individual coverage of 5.3m radius.
However these radii must overlap to ensure there are no ‘blind spots’. Therefore individual coverage can be represented by a square measuring 7.5m x 7.5m giving an actual coverage of 56.3m
2
per device.
Call Points
• A person should not have to travel more than 45m along an escape route to reach a Manual Call Point
(25m if disabled person to operate, or rapid fi re development is likely). Manual Call Points should be sited at all stair wells and exits from the building.
• The frangible element of the manual call point should be positioned 1.4m (+/- 200mm) from the fl oor level. (Unless a wheelchair user is likely to be the fi rst person to raise the alarm).
Sounders
• Sounder device cabling should be arranged so that in the event of a fault, at least one sounder will remain operational during a fi re condition.
• The minimum sound level should be 65dB(A) or 5dB(A) above a background noise which is louder than 60dB(A) (if lasting more than 30 seconds) and at a frequency of between 500Hz and 1000Hz.
The maximum sound level should not be greater than 120dB(A) at any normally accessible point. This may be reduced to 60dB(A) in stairways, enclosures up to 60m
2
and specifi c points of limited extent.
• For areas where people are sleeping, sounder devices should produce a minimum 75dB(A) at the bed-head with all doors shut. In buildings providing sleeping accomodation for a signifi cant number of people, all bedrooms should have both audible and visual alarms.
Eclipse Installation, Commissioning & Operating Manual Approved Document Ref: UI-ECL-01 Issue 6.0
8
DESIGN CONSIDERATIONS
Beacons
• Visual alarms such as beacons, should always be mounted at a minimum height of 2.1m from fl oor level.
General
• Fire Alarm Control Panels should be installed at a location appropriate for staff and fi re fi ghters
• All mains supply isolators must be double pole and suitably marked
• All joints to be fi re resisting, junction boxes to be labelled ‘FIRE ALARM’.
• All cables to be fi re resisting with a minimum cross-sectional area of 1mm
2.
• Cable using trunking as a means of containment must be clipped using fi re resistant supports WITHIN
THE TRUNKING.
• Zone charts should be fi tted in all appropriate locations (adjacent to control equipment and repeaters).
CABLE TYPES & LIMITATIONS
CABLING
CABLE LENGTHS
The maximum recommended cable length for a zone or sounder circuit is 1Km. This, however, is highly dependant on the number and type of devices connected.
If in doubt, cable load and resistance calculations should be undetaken to ensure devices are working within specifi ed limits.
MAINS PROVISION
All system wiring should be installed to meet BS5839 Pt 1 : 2002 and BS7671
(Wiring Regulations). Other national standards of installation should be used where applicable.
Eclipse Installation, Commissioning & Operating Manual Approved Document Ref: UI-ECL-01 Issue 6.0
9
DESIGN CONSIDERATIONS
GENERAL CONVENTIONAL SYSTEM SCHEMATIC
Typical Conventional
Detection Circuit Wiring
4K7 OHM
END OF LINE
RESISTOR
APOLLO S65 BASE
45681-201
-
R
L2
IN
L1
OUT
L1
+
MANUAL CALL POINT
MCP1A-R-470
470
_ _
+ +
1 2 3 4
Typical Conventional Sounder
Circuit Wiring
4K7 OHM
END OF LINE
RESISTOR
APOLLO S65 BASE
45681-201
-
R L2
IN
L1
OUT
L1
APOLLO S65 BASE
45681-201
-
R
L2
IN
L1
OUT
L1
MOTORISED BELL
POLARISED
+VE
-VE
MOTORISED BELL
POLARISED
+VE -VE
+VE
ELECTRONIC SOUNDER
POLARISED
-VE
+VE
ELECTRONIC SOUNDER
POLARISED
-VE
ZONE 1
+ -
Eclipse Installation, Commissioning & Operating Manual
10
SNDR1
+ -
Approved Document Ref: UI-ECL-01 Issue 6.0
DESIGN CONSIDERATIONS
GENERAL TWIN WIRE SYSTEM SCHEMATIC
Typical Twin Wire
Circuit Wiring
4K7 OHM
END OF LINE
RESISTOR
TWIN WIRE CALL POINT
MCP1B-R-TW
470
_ _
+ +
1 2 3 4
MOTORISED BELL
POLARISED
-VE
+VE
+VE
APOLLO TWIN WIRE BASE
45681-206
R+
R-
+
_
-VE
TWIN WIRE CALL POINT
MCP1B-R-TW
470
_ _
+ +
1 2 3 4
APOLLO TWIN WIRE BASE
45681-206
R+
R-
Note:
Zone circuit configuration is set to ‘Conventional’ by default.
‘Twin Wire’ mode must be set using DIL Switch 1 on Main PCB.
-VE
+VE
E
ELECTRONIC SOUNDER
POLARISED
-VE
+VE
1 2 3 4 5 6 7
ON
1 2 3
Note:
On a Twin Wire circuit the sounders are connected in reverse polarity to the detectors and call points
ZONE 1
+ -
Eclipse Installation, Commissioning & Operating Manual
11
Approved Document Ref: UI-ECL-01 Issue 6.0
INSTALLATION
SAFETY
(i) BS 7671 (IEE wiring regulations for electrical installations)
(ii) Codes of Practice
(iii) Statutory requirements
(iv) Any instructions specifi cally advised by the manufacturer
!
This equipment must only be installed and maintained by a suitably skilled and technically competent person.
THIS IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED
Equipment Guarantee
This equipment is not guaranteed unless the complete system is installed and commissioned in accordance with the laid down national standards by an approved and competent person or organisation.
This product has been manufactured in conformance with the requirements of all applicable EU Council
Directives
Eclipse Installation, Commissioning & Operating Manual
12
Approved Document Ref: UI-ECL-01 Issue 6.0
INSTALLATION
ESD PRECAUTION
GENERAL
segregated away from mains voltage.
• Any junction boxes used should be clearly labelled FIRE ALARM.
• Any ancillary devices, e.g. door retaining magnets, must be powered from a separate power source.
• Any coils or solenoids used in the system must be suppressed, to avoid damage to the control equipment.
MOUNTING THE CABINET
Before mounting the cabinet remove the main PCB.
Remove the power supply module connecting wires from the main PCB, taking care to note where to reconnect them. The main PCB can then be carefully pulled off it’s mounting clips.
Secure the cabinet to the wall using the four indented holes in the back box. Ensure the box is mounted level and in a convenient location where it may be easily operated and serviced.
External cables should be glanded via preformed knockouts at the top and rear of the cabinet. Remove any knockouts and ensure the cabinet is clear of swarf etc prior to refi tting the PCB. Always ensure that if a knockout is removed, the hole is fi lled with a good quality cable gland. Any unused knockouts must be securely blanked off.
Knockouts should be removed with a sharp tap at the rim of the knockout using a fl at 6mm broad bladed screwdriver.
Use of excessive force will damage the enclosure around the knockout.
Eclipse Installation, Commissioning & Operating Manual
13
Approved Document Ref: UI-ECL-01 Issue 6.0
INSTALLATION
Typical panel layout
Incoming mains wiring Low voltage detection and sounder circuit wiring
PSU
@ + -
28V 0V
+ C
FIRE
NC NO C
FAULT
NC NO
FR FLT CC PUL
-OP -OP -IP -IP
SNDR1
+ -
SNDR2
+ -
ZONE1
+ -
ZONE2
+ -
ZONE3
+ -
ZONE4
+ -
+ -
BATTERY
ON
1 2 3
12V 3.2Ah VRLA BATTERY
12V 3.2Ah VRLA BATTERY
Drawing shows typical internal layout of the panel cabinet with two 3.2Ah, 12v batteries fi tted
MAINS CONNECTIONS
Do not connect the mains supply to the panel until you are fully conversant with the layout and features of the equipment.
A rating plate is attached to the power supply module describing the nature of the supply permitted.
The incoming mains supply should be brought into the panel via one of the knockouts provided.
A suitable cable gland must be used to secure the outer sheath of the cable used. The earth must fi rst be connected to the primary earth stud (peg) marked with a symbol, using the ring crimp provided.
Suffi cient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while leaving the earth connection intact.
Eclipse Installation, Commissioning & Operating Manual Approved Document Ref: UI-ECL-01 Issue 6.0
14
INSTALLATION
CONNECTING THE BATTERIES
Batteries of even very small capacity are capable of delivering very high currents which can cause fi re or injury, therefore battery connections should be done with caution.
The panel is supplied with battery leads already connected to the battery terminals on the main PCB.
These leads are coloured red for +ve and black for -ve.
2 x 12v batteries should be connected in series using the white jumper lead provided. See diagram.
ON
1 2 3
+ -
BATTERY
To optimise the service life of the batteries, the battery charger output voltage varies with temperature.
-ve +ve
N.B.
In the event of mains failure, the battery charger circuit will protect the batteries from full discharge by disconnecting them when they reach below
19v. When the mains supply is restored the batteries will be automatically reconnected.
12v SLA Battery 12v SLA Battery
NOTE:
If the mains is connected before the batteries, the panel will show a Power Supply fault for up to 1 minute until the monitoring cylce has fi nished polling. This is normal. If the fault doesn’t clear after 1 minute, check connections.
BATTERY CHARGING VOLTAGE CHECKS
The battery charging voltage is factory calibrated to 27.3vdc +/- 0.2v @ 20 o
C. This should not normally require adjustment. Where battery problems are experienced, the following information should be considered.
a) If a battery is disconnected from the charger, no voltage will appear on the output leads or terminals, due to intelligent battery controls.
b) Check the power supply voltage at the 28v & 0v supply output terminals. With the batteries disconnected the voltage should be 27.6vdc +/- 0.2v @ between 11 o
C - 40 o
C.
c) To test the batteries, turn off the mains and see if the system will run on the batteries. Check the battery voltage, should be 26.8v for a good battery or 22v for a fl at battery.
d) The power supply voltage can be adjusted using the potentiometer on the power supply module (see page 7), checking at the 28v & 0v output terminals with a calibrated volt meter. Batteries should be disconnected and the Access Level 3 DIL switch should be set to ‘ON’ (see page 17), which will over ride the temperature compensation controls. Carefully adjust the voltage to 27.6vdc +/- 0.2v. When completed, switch off Access Level 3 DIL switch and re-connect the batteries.
e) When the panel is re-charging a low battery, it should be possible to see the voltage across the batteries increase gradually. If this is not occurring, the batteries or the panel may be faulty.
Eclipse Installation, Commissioning & Operating Manual
15
Approved Document Ref: UI-ECL-01 Issue 6.0
SETUP & PROGRAMMING
TWIN WIRE MODE
What is Twin Wire?
Twin Wire is Haes’ version of what is often referred to as sav wire. The technology enables sounders and beacons to be connected to the same circuit as the detectors and call points. This can result in greatly reduced installation time and cost.
How does it work?
In Twin Wire confi guration the fi re zone circuits reverse polarity in alarm condition to power the sounders and beacons. For this reason the sounders and beacons need to be wired in opposite polarity to the detectors and call points, i.e. zone positive wire connects to detector base and call point positive terminals but sounder and beacon negative terminals.
+ + + +
Zone +ve
4K7 EOL
Resistor
Zone -ve
-
Haes Twin Wire systems require special ‘sav-wire’ detector bases and polarised call points but standard sounders. Most modern, non addressable, low current, polarised sounders, bells and beacons are compatible, Cooper Fulleon, Besson, Klaxon etc.
To set Twin Wire mode, move switch 1 on the 3 way DIL switch located on the main PCB to the ‘ON’ position.
Note: Setting this switch will change ALL zones to
Twin Wire.
1 SNDR2
+ -
ZONE1 ZONE2 ZONE3 ZONE4
+ + + + -
1 2 3 4 5 6 7
ON
1 2 3
ON
1 2 3
ON
1 2 3
Eclipse Installation, Commissioning & Operating Manual
16
Approved Document Ref: UI-ECL-01 Issue 6.0
SETUP & PROGRAMMING
LEVEL 3 ENGINEERING OPTIONS
A series of programmable engineering options are available. These programming modes are initiated by entering a four digit code using buttons 1 - 4 on the keypad followed by the ENTER button.
RESOUND SILENCE RESET
1
Disable
Mode
2 3 4
Test
Mode
Mute
Buzzer
Test
Lamps
ENTER
To access Level 3 options, fi rst set switch 3 on the 3 way DIL switch located on the main PCB to the
‘ON’ position. Then activate the controls by turning the key switch or by entering the four digit code (see
Activate Controls in the OPERATING section).
The ‘Access Level’ indicator will pulse rapidly to signify that Level 3 access is active.
1 SNDR2
+ -
ZONE1 ZONE2 ZONE3 ZONE4
+ + + + -
1 2 3 4 5 6 7
ON
1 2 3
ON
1 2 3
ON
1 2 3
Options
1 1 1 3
Reset all disablements, test modes and parameters back to factory settings.
Enter the above code and press the ENTER button.
Then press the ENTER button again and hold for 3 seconds.
Any disablements or test mode settings will now clear and all engineering option parameters will revert back to factory settings.
The panel will bleep to acknowledge the reset.
1
RESOUND
Disable
Mode
SILENCE
2 3 4
Test
Mode
Mute
Buzzer
Test
Lamps
RESET
ENTER
Eclipse Installation, Commissioning & Operating Manual
17
Approved Document Ref: UI-ECL-01 Issue 6.0
SETUP & PROGRAMMING
2 2 2 4
Set fault buzzer volume.
There are two levels of volume for the internal fault buzzer, high and low.
Enter the above code and press the ENTER button to increase or decrease the fault buzzer tone from the previous level.
RESOUND SILENCE RESET
Setting will change when ENTER button is pressed.
1 2
Disable
Mode
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
When fi nished, enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
2 1 2 3
Set keypad entry code (fi re LED 1 option)
The keypad can be used to activate the panel controls instead of using the key switch. The default code is 1-2-3-4, however, this can be changed. It is also possible to disable the use of a code entry to enable controls, forcing the use of the key switch only.
Enter the above code and press the ENTER button.The Zone Fault/Disabled/Test LEDs will start to rapidly pulse in sequence to show the currently set code. The sequence will be repeated twice after which time the panel will automatically drop out of the set keypad entry mode.
Whilst the current code sequence is being repeated start to enter the new code. Enter the new code slowly and deliberately, one number at a time. The corresponding Zone Fault/Disabled/Test LED will rapidly pulse to confi rm each entry.
Note: Enable Controls codes must always start with a 1 or 2.
When fi nished entering the new four digit code, press the ENTER button. The panel will then confi rm the new code with rapidly pulsing LEDs in sequence, after which time the panel will automatically drop out of the set keypad entry mode.
Changing the keypad code to 1 - 1 - 1 - 1 will disable the use of a keypad to enable controls.
2 1 2 3
Fire LED 2 future option (not in use)
Eclipse Installation, Commissioning & Operating Manual
18
Approved Document Ref: UI-ECL-01 Issue 6.0
SETUP & PROGRAMMING
1 1 1 4
Select sounder resound options for zones.
By default, after an initial fi re condition and the (blue) Silence Alarms button has been activated, any new fi re condition in a different zone will cause the alarms to resound.
It is possible to change this on a zonal basis so that any new alarm in a different zone will not resound the alarms.
Enter the above code and press the ENTER button. The Sounder Status LED will pulse slowly. Zone Fault/
Disabled/Test LEDs will show their current status (see below) with Zone 1 pulsing to indicate it is under selection.
Use Button 1 (Disable Mode) to move to the zone for programming (indicated by a pulsing LED) and press the ENTER button to change the status. Pressing the ENTER button again will toggle the status, indicated by a rapid or slow pulsing LED (see below). Then use Button 1 to move to the next zone. If the zone has been set to not resound alarms, the LED will be off. If kept as default, new fi re condition will resound alarms, then the LED will be on steady.
Rapid Pulse = Zone is under selection and is set to have alarms resound (default).
Slow Pulse = Zone is under selection and has been set to not resound alarms on new fi re condition.
LED Off = Zone has been set to not resound alarms on new fi re condition.
LED On = Zone is set to have alarms resound (default).
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
When fi nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10 seconds and the panel will save the settings and revert back to Level 3 access mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Eclipse Installation, Commissioning & Operating Manual
19
Approved Document Ref: UI-ECL-01 Issue 6.0
SETUP & PROGRAMMING
3 1 2 1
Zone Function Settings
There are 4 functional settings available for each zone. These are as follows:
Fire latching
Normally a zone latches a fi re input signal. This setting allows the panel to clear automatically when a fi re signal is removed. This is useful for interfacing purposes.
Short circuit as alarm (EN54!)
For Older non EN54 or BS5839 compliant systems. This allows a short circuit to activate a fi re rather than a fault condition.
Intrinsically safe operation
This option changes the zone alarm and short circuit thresholds to allow for an MTL 5061 type intrinsically safe barrier to be used in the circuit.
Note: Twin Wire mode is not compatible with intrinsically safe operation.
Detector removal monitoring (EN54!)
The detector removal monitoring can be turned off. For use with older, non compliant detectors.
Enter the above code and press the ENTER button.
RESOUND
The zone 1 fi re LED will light. This indicates setting the above attributes for zone 1.
The amber, fault / disabled / test LEDs will show the current settings for that zone.
1
Disable
Mode
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
Use button 1 to move to the zone that requires editing.
RESOUND
With the required zone for editing LED lit, press the ENTER button to enter ‘editing mode’.
1
Disable
Mode
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
The fi re zone 1 LED will now pulse to indicate the editing of attribute 1 (fi re latching) for the selected zone.
Eclipse Installation, Commissioning & Operating Manual
20
Approved Document Ref: UI-ECL-01 Issue 6.0
SETUP & PROGRAMMING
Use button 1 to scroll to the attribute that requires editing, inidicated by a pulsing fi re LED 1 - 4 as per table below.
Fire LED
(pulsing)
LED 1
Attribute
Fire latching
Amber fault LED
(default setting)
ON
LED 2
Short circuit as fi re
OFF OFF ON
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
LED 3 LED 4
Intrinsically safe operation
Detector removal monitoring
The setting of the attribute is indicated by the amber, fault / disabled / test
LED, ON or OFF.
Use button 2 to switch the attribute ON or OFF, indicated by the amber, fault / disabled / test LED.
Then use button 1 to move to the next attribute if required.
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
RESOUND SILENCE RESET
Press the ENTER button to return back to the zone selection, indicated by a steady zone fi re LED
1
Disable
Mode
2 3 4
Test
Mode
Mute
Buzzer
Test
Lamps
ENTER
When fi nished all the zone function programming, enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Eclipse Installation, Commissioning & Operating Manual
21
Approved Document Ref: UI-ECL-01 Issue 6.0
SETUP & PROGRAMMING
2 1 1 4
Type ‘A’ dependency mode.
Dependency ‘A’ (confi rmation alarm) is a requirement by some monitoring stations and local fi re authoities to reduce the possibility of false alarms.
Dependency ‘A’ zones will apply the following sequence:
Note: 220Ω ‘Evacuate’ call points should be used on such zones to provide an instant un-delayed alarm.
A 470Ω call point will be included in the dependency delay sequence.
By default this is set to ‘off’ for all zones.
To set zones to Type ‘A’ Dependency, enter the above code and press the ENTER button. The Aux Output
Status LED will pulse slowly. Zone Fault/Disabled/Test LEDs will show their current status (see below) with
Zone 1 pulsing to indicate it is under selection.
Use Button 1 (Disable Mode) to move to the zone for programming (indicated by a pulsing LED) and press the ENTER button to change the status. Pressing the ENTER button again will toggle the status, indicated by a rapid or slow pulsing LED (see below). Then use Button 1 to move to the next zone. If the zone has been set to confi rmation alarm mode, the LED will remain on. If kept as standard alarm mode then the
LED will be off.
Slow Pulse = Zone is under selection and is set to standard alarm mode.
Rapid Pulse = Zone is under selection and has been set to confi rmation alarm mode.
LED Off = Zone is set to standard alarm mode.
LED On = Zone has been set to confi rmation alarm mode.
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
When fi nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10 seconds and the panel will save the settings and revert back to Level 3 access mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Eclipse Installation, Commissioning & Operating Manual
22
Approved Document Ref: UI-ECL-01 Issue 6.0
SETUP & PROGRAMMING
2 1 3 4
Dependency mode Twin Wire detector compatibility
If using dependency mode, Eclipse panels are designed to work with the following conventional detectors:-
• Apollo Series 65
• Nittan Evolution Conventional
However, if also using
Twin Wire mode the panels are optimised for use with Apollo Series 65 heads &
Fault/Disabled/Test LED indicating that the compatibility mode is set to on,
Disabled/Test LED.
When fi nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10 seconds and the panel will save the settings and revert back to Level 3 access mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
The above setting is only relevant if you are using Dependency mode & Twin Wire mode but NOT using Apollo Series 65 detectors.
Eclipse Installation, Commissioning & Operating Manual
23
Approved Document Ref: UI-ECL-01 Issue 6.0
SETUP & PROGRAMMING
4 2 4 2
Common fi re outputs cancel on silence alarms
The Common Fire VFCO relay output and the Common Fire switched -ve output, when activated, normally remain until the panel is RESET.
This option changes these outputs to reset on SILENCE ALARMS. This may be useful for panel interlink purposes.
Both outputs can be programmed independently.
RESOUND SILENCE RESET
1 2
Disable
Mode
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
PSU
@ + -
28V 0V
+
-
FIRE FAULT
C NC NO C NC NO
FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
+ + + + + + -
Enter the above code and press the ENTER button.
The red Zone 1 fi re LED will illuminate, this LED represents the Common Fire VFCO relay output.
Pressing Button 1 (Disable Mode) will move to red Zone 2 fi re LED which represents the Common Fire switched -ve output. Subsequent presses will toggle between them.
With the required fi re LED lit press the ENTER button and Zone 1, fi re LED will pulse.
Press button 2 (Test Mode) to alter the status of the output, represented by the Zone 1, Fault/Disabled/
Test LED either off or on.
Off = Output cancels on RESET (factory default)
On = Output cancels on SILENCE ALARMS.
When the output status has been set, press the ENTER button to return to the output selection mode.
When fi nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10 seconds and the panel will save the settings and revert back to Level 3 access mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Eclipse Installation, Commissioning & Operating Manual
24
Approved Document Ref: UI-ECL-01 Issue 6.0
SETUP & PROGRAMMING
4 3 4 4
Conventional Sounder Circuit Functional Options
This option is used to programme each of the conventional sounder circuits on the main circuit board with custom reponses as below.
Enter the above code and press ENTER. Then use button 1 to select the sounder circuit to be programmed (indicated by a steady fi re zone LED) as per table.
LED 1
SNDR1
(Main
LED 2
SNDR2
(Main
With the required sounder LED lit, press the ENTER button. Fire zone LED 1 will now pulse. This indicates setting up function 1 (resets on silence alarms) for the selected
PCB) PCB) circuit. Use button 1 to scroll to the required function, indicated buy pulsing fi re LEDs 1- 4 as per table below.
Fire LED
(pulsing)
LED 1 LED 2 LED 3 LED 4
Use button 2 to change the response to ON or OFF, indicated by the amber fault LEDs.
Function
Resets on
Silence
Alarms
Activates on
Evacuate
Activates on Class
Change
Activates on Alert
Then use button 1 again to scroll to the next function if required.
Amber fault LED
(default setting)
OFF ON OFF OFF
Press the ENTER button to return back to sounder circuit selection, indicated by a steady fi re LED.
ZONE INTERFACE FUNCTION
This is a special setting to confi gure the last zone on the panel, (i.e. zone 2 on the ECL-2 or zone 4 on the
ECL-4), to be used for interconnection from other control panels.
The function is enabled by setting switch 2 on the 3 way DIL switch located on the main PCB to the ‘ON’ position.
1 2 3 4 5 6 7
With switch 2 in the ‘ON’ position, the last zone becomes;
ON
1 2 3
Note:
If the control panel is also set to Twin Wire mode (Switch 1 ‘ON’) and sounders are connected to the interface zone circuit, the following sounder operation will apply:
A fi re (470Ω) signal to the interface zone will
NOT operate the sounders connected to that Twin Wire circuit.
All other conventional (SNDR1 & SNDR2) and Twin Wire zone sounders will operate as normal.
3K3Ω A fi re (470Ω) signal to any other zone will operate
ALL conventional (SNDR1 & SNDR2)
and Twin Wire sounder circuits, including the sounders connected to the interface zone, as normal.
ZONE2 ZONE3 ZONE4
+ + + -
470Ω
C NC NO C NC
NO
Example connection
PANEL 1
FIRE
FAULT
(optional)
PANEL 2
Eclipse Installation, Commissioning & Operating Manual Approved Document Ref: UI-ECL-01 Issue 6.0
25
OPERATING
PANEL CONTROLS & INDICATIONS
Zonal Fire Indicator LEDs
Status Indicator LEDs
Zones In Fault, Zones Disabled or
Zones In Test Indicator LEDs
1
Zones in Fire
2 3
Zone Fault / Disabled / Test
4
RESOUND SILENCE RESET
1 2 3 4
ENTER
Supply Healthy
General Fire
General Fault
General Disablement
Test Mode
Sounder Status
Aux Output Status
Power Supply Fault
System Fault
Access Level
Fire Detection System
8 Button Keypad For Controls
And Programming
Activate Controls Key Switch
Activate Controls
In normal standby mode the keypad controls are inactive to protect from unauthorised operation. Controls can be activated by using the ‘Activate Controls’ key switch or by entering a four digit code using the keypad.
The use of a code entry to activate the controls is enabled by default but can be disabled in the engineering functions.
To activate the controls using the key switch; turn the key clockwise to the ‘On’ position. The ‘Access
Level’ indicator LED will light and all buttons on the keypad will now be operational. To deactivate the controls, turn the key back to the ‘Off’ position and the ‘Access Level’ indicator LED will extinguish.
If the key switch is in the ‘On’ position the keypad will remain active.
NOTE : It is not possible to remove the key in the ‘On’ position.
To activate the controls using the keypad; enter the four digit code using buttons 1 - 4. The factory
default code is 1-2-3-4 but can be changed in the engineering functions. After entering the four digit code press the ‘ENTER’ button. The ‘Access Level’ indicator LED will light and all buttons on the keypad will now be operational.
After activation by code entry, controls will automatically deactivate again after 2 minutes and the panel will return to standby mode.
The test lamps and mute buzzer functions are operational without the need to activate controls.
Eclipse Installation, Commissioning & Operating Manual
26
Approved Document Ref: UI-ECL-01 Issue 6.0
OPERATING
Status LED Indicators
Zones in Fire 1 - 4
Zone Fault/Disabled/Test
1 - 4
Supply Healthy:
General Fire:
General Fault:
General Disablement:
Test Mode:
Sounder Status:
Aux Output Status:
Power Supply Fault:
System Fault:
Access Level:
LED On
N/A
Indicates zone circuit is disabled or in test mode.
Indicates mains and/or battery supply is present.
N/A
N/A
Indicates one or more circuits have been disabled.
Indicates one or more circuits are in test mode
Indicates sounder circuits have been disabled or are in test mode
Indicates auxiliary outputs have been disabled.
N/A
Indicates a system failure, panel not functional.
Indicates controls are active (access level 2).
LED Pulsing
Indicates alarm condition in zone.
Indicates a fault in the zone circuit.
N/A
Indicates panel is in alarm condition.
Indicates one or more faults are present.
Indicates disablement selection mode is active.
Indicates test mode selection is active.
Indicates a fault on one or more sounder circuits.
N/A
Indicates a power supply or battery fault.
Indicates the panel has recovered from a system fault.
Indicates panel is in confi guration mode
(access level 3).
RESOUND SILENCE RESET
Keypad
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
RESOUND (red):
SILENCE (blue):
RESET (green):
1: (Disable Mode)
2: (Test Mode)
3: (Mute Buzzer)
4: (Test Lamps &
Buzzer)
ENTER:
Use to resound the alarms after they have been silenced. Can also be used to invoke full evacuation.
Use to silence the sounders during an alarm condition.
Resets the panel back to standby mode.
With controls inactive, use to initialise code entry mode for activation of controls. With controls active, use to disable zones, sounder circuits or aux outputs (see DISABLE MODE section). Also has the numeric value 1 for code entry.
With controls inactive, use to initialise code entry mode for activation of controls. With controls active, use to put zones or sounders circuits into test mode (see TEST MODE section). Also has the numeric value 2 for code entry.
Mutes the panels internal fi re and fault buzzer. (The buzzer will still blip every 5-6 seconds during a fi re or fault condition). This function is operational without the need to activate controls. Also has the numeric value 3 for code entry.
Use this button to illuminate all LEDs and sound the internal buzzer to check that they are working correctly. This function is operational without the need to activate controls. Also has the numeric value
4 for code entry.
This button is used to confi rm code entries. It can also be used for fault diagnosis (see FAULT
DIAGNOSIS section).
Some buttons have other functions within the engineering facilities. These functions are described in the relevant sections.
Eclipse Installation, Commissioning & Operating Manual Approved Document Ref: UI-ECL-01 Issue 6.0
27
OPERATING
DISABLE MODE
Disable Mode is used to disable or isolate individual zone circuits or all sounder circuits or all auxiliary outputs.
To initialise Disable Mode, fi rstly activate the controls by turning the key switch or by entering the four digit code. Then press and hold the Disable Mode button (1) for 3 seconds.
After 3 seconds the panel will bleep and the General Disablement
LED and Zone 1 Fault/Disabled/Test LED will pulse slowly, indicating that Zone 1 is in disable selection mode.
1
RESOUND
Disable
Mode
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
Pressing the Disable Mode button again will move disable selection mode to Zone 2 and the Zone 2 Fault/
Disabled/Test LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 and 4.
After Zone 4 the next press will move the selection mode to the sounder circuits, indicated by the Sounder
Status LED and then to the Aux outputs, indicated by the Aux Output Status LED. Pressing the button once more will move the selection back to Zone 1 again.
When the desired circuit or output to be disabled is indicated by a slow pulsing LED, use the ENTER button to select it. Once selected the indicator LED will change to a rapid pulse. Pressing ENTER again will toggle the circuit between disabled and enabled. Then use Disable Mode button again to move to the next circuit. Any or all circuits can be disabled simultaneously.
1
RESOUND
2
SILENCE
3 4
RESET
ENTER
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
When all disablements have been set, press and hold the Disable Mode button for 3 seconds again. This will exit the disable selection mode and the panel will return to standby.
All disabled circuits and the General Disablement will now be indicated by a steady LED.
To enable the circuits again, repeat the above process using the Disable Mode button to select the circuit and the ENTER button to remove the disablement.
Tip:
With the controls active, pressing the Disable Mode button briefl y will reveal which circuits are disabled (as opposed to in test mode). This is useful if using Disable Mode and Test Mode at the same time.
Eclipse Installation, Commissioning & Operating Manual
28
Approved Document Ref: UI-ECL-01 Issue 6.0
OPERATING
TEST MODE
Test Mode is used when testing the fi re alarm system. In test mode the devices in the zone(s) in test, detectors and call points etc, can be activated and the panel will automatically reset, enabling the system to be tested by one person. It is possible to test head removal monitoring and to test the system with or without the sounders.
To initialise Test Mode, fi rstly activate the controls by turning the key switch or by entering the four digit code. Then press and hold the Test
Mode button (2) for 3 seconds.
RESOUND SILENCE RESET
1 2 3 4
ENTER
After 3 seconds the panel will bleep and the Test Mode LED and Zone
1 Fault/Disabled/Test LED will pulse slowly, indicating that Zone 1 is
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps in test selection mode. The Sounder Status LED will also be pulsing rapidly, this indicates that the test will be
with sounders. (Test mode without sounders is explained below)
Pressing the Test Mode button again will move test selection mode to Zone 2 and the Zone 2 Fault/
Disabled/Test LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 and 4.
After Zone 4 the next press will move the selection mode to the sounder circuits, indicated by no Zone
Fault/Disabled/Test LEDs on. This position selects whether or not the sounders will ring during test.
Pressing the button once more will move the selection back to Zone 1 again.
When the desired zone to be tested is indicated by a slow pulsing LED, use the ENTER button to select it. Once selected the indicator LED will change to a rapid pulse. Pressing ENTER again will toggle the zone between in and out of test. Then use Test Mode button again to move to the next zone. Any or all zones can be in test mode simultaneously.
RESOUND
1
Disable
Mode
When at the sounder status position, use the ENTER button to toggle between testing with or without sounders. A rapid pulse = with sounders
(default), a slow pulse = without sounders.
SILENCE
2 3 4
Test
Mode
Mute
Buzzer
Test
Lamps
RESET
ENTER
When all zones to be tested have been set, press and hold the Test Mode button for 3 seconds again. This will exit the test selection mode. All zones in test and the Test Mode will now be indicated by a steady LED.
To take zones out of test mode, repeat the above process using the Test Mode button to select the zone and the ENTER button to change the status.
Test Mode With Sounders
Activation of a call point or detector - sounders will pulse twice, device is automatically reset.
Removal of a detector - sounders will pulse once.
Test Mode Without Sounders
Activation of a call point or detector - panel buzzer and LED response only, device is automatically reset.
Tip:
With the controls active, pressing the Test Mode button briefl y will reveal which circuits are in test mode
(as opposed to disabled). This is useful if using Disable Mode and Test Mode at the same time.
Eclipse Installation, Commissioning & Operating Manual
29
Approved Document Ref: UI-ECL-01 Issue 6.0
OPERATING
FAULT DIAGNOSIS
If the panel has detected a fault on the system the General Fault LED will be illuminated and the internal fault buzzer will sound. Secondary LEDs will also be illuminated depending on the location of the fault.
Pressing and holding the ENTER button will reveal more detailed information about the loction and type of fault.
RESOUND
This function will not work if the panel is in a fi re condition. If no faults exist pressing the ENTER button will have no effect.
This function is only operational when controls are not active.
1
Disable
Mode
2
Test
Mode
The following table shows details of the indications in fault diagnosis mode:
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
LED Indicator
& State before pressing ENTER
LED Pulsing after pressing ENTER
Zone 1 Fire LED
(off)
Zone 2 Fire LED
(off)
Zone 1 - 4 Fault/
Disabled/Test LED
(pulsing)
Zone 1 - 4 Fault/
Disabled/Test LED
(steady)
Power Supply
Fault LED (pulsing)
Sounder circuit 1 short circuit
Sounder circuit 2 short circuit
Zone # short circuit
N/A
Mains failure
LED Steady after pressing ENTER
Sounder circuit 1 open circuit
Sounder circuit 2 open circuit
Zone # open circuit
N/A
Battery failure or high impedance
LED Off after pressing ENTER
OK
OK
Voltage fault
Location
Main PCB SNDR 1
Main PCB SNDR 2
(slow pulse)
Zone # detector removed
Zone # disabled or in test mode
Main PCB Zones
1 - 4
Main PCB
Eclipse Installation, Commissioning & Operating Manual
30
Approved Document Ref: UI-ECL-01 Issue 6.0
OPERATING
FUNCTIONALITY DURING A SYSTEM FAULT
A system fault is indicated when a processor controlling a function in the panel has a watchdog time out or processor failure. In the event of a system fault the particular board affected may not be functional. The following indications may be observed.
Display Board
System Fault LED only continous and continous buzzer sound. Display board TPCA02 is halted and no other indication or control is possible. Fault relay and fault output are activated. If a fi re occurs alarm sounders and outputs will still function.
Main Board
System Fault LED continous and General Fault LED pulsing and continous buzzer sound. Main board is halted. Fault relay is activated. No alarms may be activated on the system.
System Fault recovery
System Fault LED pulsing and General Fault LED pulsing along with a pulsed buzzer (fault tone) a system fault has occurred and the affected board has recovered. The indication will remain until the panel is reset.
USER INSTRUCTIONS
If an alarm condition is present YOU MUST FOLLOW YOUR NORMAL FIRE DRILL PROCEDURES.
A responsible person should then:-
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
fi g 1
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
fi g 2
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
fi g 3
ENTER
Eclipse Installation, Commissioning & Operating Manual
31
Approved Document Ref: UI-ECL-01 Issue 6.0
SERVICE & MAINTENANCE
The following section is a summary of the requirements in BS5839 Part 1
For comprehensive information a copy of BS5839 Part 1 can be purchased from the British Standards
Institution via their web site at www.bsi-global.com.
THE NEED FOR MAINTENANCE
Your Fire Alarm System is working 24 hours a day, 365 days a year. The detectors and control & indicating panel are operating continuously and the fi re alarm circuits are constantly monitored.
Legislation such as the Regulatory Reform (Fire Safety) Order 2005 and other legislation protecting both employees and the public require premises operators to conform with standards for Fire Alarm Systems.
It is a requirement of BS 5839 Part 1 that the system is subject to periodic inspection and servicing so that faults are identifi ed, preventive measures can be taken to ensure the continued reliability of the system, false alarm problems are identifi ed and suitably addressed, and the user is made aware of any changes to the building that affect the protection afforded by the system.
The inspection and servicing recommendations in this clause should be carried out by a competent person. A ‘Competent Person’ is a person or fi re alarm servicing organisation with specialist knowledge of fi re detection and fi re alarm systems, including knowledge of the causes of false alarms, suffi cient information regarding the system, and adequate access to spares.
The period between successive inspection and servicing visits should be based upon a risk assessment, taking into account the type of system installed, the environment in which it operates and other factors that may affect the long term operation of the system. The recommended period between successive inspection and servicing visits should not exceed six months. If this recommendation is not implemented, it should be considered that the system is no longer compliant with this part of BS 5839
DUTIES OF THE RESPONSIBLE PERSON
The system user needs to appoint a single, named member of the premises management to supervise all matters pertaining to the fi re detection and fi re alarm system. The role of this person is to ensure that the system is tested and maintained in accordance with the recommendations of BS 5839 Part 1, that appropriate records are kept and that relevant occupants in the protected premises are aware of their roles and responsibilities in connection with the fi re detection and fi re alarm system.
This person also needs to ensure that necessary steps are taken to avoid situations that are detrimental to the standard of protection afforded by the system and to ensure that the level of false alarms is minimized.
ROUTINE MAINTENANCE & TESTING
DAILY
The ‘Responsible Person’ should check the control panel to make sure no faults or pre-alarm conditions are indicated and that the green ‘Supply Healthy’ lamp is lit.
WEEKLY
The Fire Alarm System should be tested on a weekly basis as recommended in BS5839 Part 1 clause 44.2.
Every week a manual call point should be operated during normal working hours. The weekly test should be carried out at approximately the same time each week. Instructions to the occupants should be that they report any instance of poor audibility of the fi re alarm signal.
A different manual call point should be used at the time of every weekly test so that all manual call points in the building are tested in rotation over a prolonged period.
The result of the weekly test and the identity or location of the manual call point used should be recorded in the system log book.
Eclipse Installation, Commissioning & Operating Manual Approved Document Ref: UI-ECL-01 Issue 6.0
32
SERVICE & MAINTENANCE
WEEKLY TEST
The call point test key should be inserted fi rmly and deliberately into the bottom of the manual call point.
Once activated it may be necessary to wait up to four seconds before the alarms sound.
Your manual call points may not be the same as the ones described above. If not please refer to your service and maintenance company for instructions.
Note:
Before testing the fi re alarm system it may be necessary to isolate ancillary outputs.
It is essential that any alarm receiving centre is contacted immediately before and immediately after, the weekly test to ensure that unwanted alarms are avoided and that fi re alarm signals are correctly received at the alarm receiving centre.
PERIODIC INSPECTION & SERVICING
Inspection & servicing should only be carried out by a ‘Competent Person’ who has suffi cient knowledge to check the whole system. This would normally be a qualifi ed electrical contractor or fi re alarm specialist.
Inspection & servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warrant servicing on a more regular basis. The maximum period between inspections must not exceed six months.
Recommendations of BS5839-1 for periodic service visits include:
• Every device on the system should be tested annually. The testing of each device can be split between periodic visits but with a minimum of one detector or call point tested on each circuit, per visit.
• On each visit the ‘Competent Person’ should check the record of false alarms. Any persistent occurrence should be investigated and corrective action taken as appropriate.
• Battery and connections should be examined and load tested to check serviceable condition and that they are not likely to fail before the next service visit.
• All other devices and control & indicating equipment should be checked for correct operation and any faults should be recorded and rectifi ed.
• Details of the service visit must be recorded in the log book
EVERY FOUR YEARS
Renew the sealed lead acid batteries and record the fact in the log book
Eclipse Installation, Commissioning & Operating Manual Approved Document Ref: UI-ECL-01 Issue 6.0
33
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Eclipse Installation, Commissioning & Operating Manual
34
Approved Document Ref: UI-ECL-01 Issue 6.0
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Eclipse Installation, Commissioning & Operating Manual
35
Approved Document Ref: UI-ECL-01 Issue 6.0
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Eclipse Installation, Commissioning & Operating Manual
36
Approved Document Ref: UI-ECL-01 Issue 6.0
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Eclipse Installation, Commissioning & Operating Manual
37
Approved Document Ref: UI-ECL-01 Issue 6.0
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Eclipse Installation, Commissioning & Operating Manual
38
Approved Document Ref: UI-ECL-01 Issue 6.0
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Eclipse Installation, Commissioning & Operating Manual
39
Approved Document Ref: UI-ECL-01 Issue 6.0
FALSE ALARMS, FAULTS & ENGINEERS VISITS
Fault/Reason For
Call-Out
Action Taken Date Work Completed Engineer’s Details
Eclipse Installation, Commissioning & Operating Manual
40
Approved Document Ref: UI-ECL-01 Issue 6.0
FALSE ALARMS, FAULTS & ENGINEERS VISITS
Fault/Reason For
Call-Out
Action Taken Date Work Completed Engineer’s Details
Eclipse Installation, Commissioning & Operating Manual
41
Approved Document Ref: UI-ECL-01 Issue 6.0
FALSE ALARMS, FAULTS & ENGINEERS VISITS
Fault/Reason For
Call-Out
Action Taken Date Work Completed Engineer’s Details
Eclipse Installation, Commissioning & Operating Manual
42
Approved Document Ref: UI-ECL-01 Issue 6.0
USER INSTRUCTIONS
If an alarm condition is present YOU MUST FOLLOW YOUR NORMAL FIRE DRILL PROCEDURES.
A responsible person should then:-
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
fi g 1
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
fi g 2
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
fi g 3
3 4
Mute
Buzzer
Test
Lamps
ENTER
The internal fault buzzer can be silenced by pressing MUTE BUZZER (button 3 on the keypad). DO
NOT RESET THE SYSTEM UNTIL AN ENGINEER HAS INVESTIGATED THE FAULT.
www.haes-systems.com
Advertisement
Key features
- EN54 approved
- 2 or 4 zone conventional control
- Twin Wire support
- Integral power supply
- Battery backup
- Keypad entry code
- Sounder resound options
- Zone function settings
- Dependency mode
- Detector removal monitoring