9450
Installation and User Guide
Compatible Equipment
9040 Internal Sounder
496326 Issue 1 1 of 6
9450
INTRODUCTION
The 9450 is a fully programmable 3 zone control panel with Entry/Exit, PA and Fire zones. The panel is designed specifically for domestic installations.
The control unit PCB is built into a polycarbonate box with keypad and eight indicator LEDs on the front of the lid.
Scantronic recomend that you use this system for "bell only" installations.
Technical Specification
Dimensions
Weight
Power Supply
h x w x d 163 x 257 x 72mm.
Approx 1.2kg (without stand-by battery).
System Power Supply
Quiescent Panel Power
Battery charging current
Standby Battery
230VAC (Ambient Temp. 20 º C).
500mA max continuous output.
130mA nominal (includes 50mA SAB).
20mA (1.9AH battery fully charged).
12 Volt, 1.9AH rechargeable lead-acid, Gel
Type battery.
Outputs
Bell, Strobe, and O/P are open collector transistor outputs.
Bell
Strobe
AUX (for detectors)
LS
Outputs (2)
340mA (max in alarm).
150mA (max in alarm).
350mA, 12VDC.
100mA (suitable for one 16 Ohm speaker max).
PIR Set Latch and Shock Sensor Reset.
Note: Drawing more than 820mA output current will open the polyswitch fuse and remove all DC power from the panel.
2 of 6 496326 Issue 1
9450
Wiring
Figure 1 shows the layout of the 9450 PCB and its connector.
Figure 1. 9450 PCB Layout
Programming
Initial Start Up
Before applying power to the control panel, ensure that all zone circuits are connected (link out any circuits not used). DO NOT connect the 12V terminal to the external sounder or 12VAUX terminals to the detectors at this stage.
1.
Apply mains to the control panel.
The green power LED lights and the internal sounder will sound. Ignore any other lights.
2.
Key-in the factory default user access code: 1234.
The internal sounder stops. Ignore any other lights.
3.
Key-in 0 then ENTER followed by the factory default engineer access code: 7890.
The Day LED goes off.
4.
Open the control panel lid.
You are now in programming mode.
496326 Issue 1 3 of 6
Changing Default Programming 9450
Changing Default Programming
To change the factory defaults, the panel must be in programming mode.
Then:
1.
Key in a two digit programming command followed by "ENTER". (See
"Engineer Program Command List".)
2.
Key in the correct digit for the option you want, and then press ENTER.
The panel beeps twice to show that it has accepted the command.
The panel gives a single error tone if you enter an incorrect command
(or if you close the lid). Re-enter the correct command.
Engineer Program Command List
To change: Key-in: Followed by: Notes: Defaults
Engineer Code
User Code 1
Zone 2 Entry
Route
Auto Re-Arm
Bell Time
Entry time
20 ENTER new code ENTER 4 digits
21 ENTER new code ENTER 4 digits (see note 1)
36 ENTER 0
1
ENTER
ENTER
40 ENTER 1 ENTER
4 ENTER
Normal Alarm
Entry Route
42
43
ENTER
ENTER
1
2
3
4
ENTER
ENTER
ENTER
ENTER
1 ENTER
2 ENTER
3 ENTER
4 ENTER
Never rearm
Rearm three times
Nil
3 minutes
10 minutes
20 minutes
20 seconds
40 seconds
1.5 minutes
3 minutes
7890
1234 y y
Exit time 44 ENTER 1 ENTER
2 ENTER
3 ENTER
4 ENTER
10 seconds
30 seconds
1 minute
2 minutes y
Walk Test 97 ENTER Trigger detectors. Press OMIT to exit test.
Leave Program 99 ENTER (See note 2.)
Notes:
1. The end user may change the user code.
2. If the internal sounder activates when you use this command then check the lid tamper, bell tamper, and the global zone anti tamper.
y y
4 of 6 496326 Issue 1
9450 Leaving Programming Mode
Leaving Programming Mode
1.
Connect the battery.
2.
Complete the connections between the 12V terminal and the external sounder, and 12VAUX and the detectors.
Note: The SAB module in the external sounder will continue to ring until the hold off supply is connected, or until the bell cover lid tamper switch is closed.
3.
Close the panel lid.
4.
Key in "99 ENTER" to leave programming mode.
You are now in user mode.
To Re-enter Programming Mode
You can re-enter programming mode at any time when the panel is not set or in alarm:
Key-in 0 then ENTER followed by the engineer access code.
Open the control panel lid.
You are now in programming mode.
Restoring Factory Defaults
The control panel can retain all programmed information and access codes if both mains and battery power fail. When power is restored the panel will simply need resetting with the customer or engineer's access code.
If the installer wants to return the panel to the factory default settings, then:
1.
Power down the control panel, mains and battery.
2.
Locate the pair of Molex pins marked 'RST' near the microcontroller.
3.
Place a small screwdriver blade to short between the 'RST' pins.
4.
With the blade still across the pins, apply battery power then mains.
The system loads the factory default user and engineer's access codes, and all the program defaults.
5.
Remove the screwdriver blade.
6.
Key in 1234.
7.
Key in 0 then ENTER followed by 7890.
8.
You must now reprogram as neccessary.
496326 Issue 1 5 of 6
Eningeer Walk Test 9450
Engineer Walk Test
Allows the engineer to test all devices on the system.
1.
Enter programming mode.
2.
Key in "97 ENTER".
The panel gives a continuous tone.
3.
Open and close each detector contact in turn.
When a detector contact is open the panel gives an interrupted tone and flashes the zone LED.
4.
Press OMIT to stop the walk test.
Note that the Engineer's walk test allows you to test all zones including PA zones, zone tampers, and panel and bell tampers. The user's walk test does not allow this.
Set/Unset System
Omit zone/Part Set
Test Bells
Walk Test
Change User code
User Commands
User code
User code + 2 + Omit and/or 3 + Omit
4 + ENTER + User code
The system activates the internal sounder for three seconds, followed by the external sounder for three seconds.
5 + ENTER + User code
Key in User code to end test
6 + ENTER + current user code new user code + ENTER
6 of 6 496326 Issue 1