DIRIS A40 DIRIS A41

DIRIS A40 DIRIS A41
Energy management
Network
analysis
L
DIRIS A40
DIRIS A41
DIRIS Am
DIRIS A20
DIRIS A40 / DIRIS A41
Communication interfaces
DIRIS VISION software
CONTROL VISION software
BILLING APPLICATION software
Functions
DIRIS A40 and A41 are multi-function
meter for measuring the extent of
electrical values for all LV/HV networks.
They allow starting from the front panel
to configure and display all the electric
parameters and to exploit the functions
of measurement, metering and energies
management, harmonics analysis, remote
control and control state of control
devices, communication and detection
of high voltages, peaks and voltage
disconnections.
In addition, DIRIS A40 and A41 have
a function for correcting connection errors.
diris_561_b_3_x_cat
Conformity to standards
1 2
3
4
5
6
7
DIRIS A40
1. Backlit LCD display.
2. Direct access key for currents and setup
wiring correction.
3. Direct access key for voltages and frequency.
4. Direct access key for active, reactive,
apparent power and power factor.
5. Direct access key for currents (maximal and
average values) and power.
6. Direct access key for harmonics values.
7. Direct access key for energies and hour run
meter.
• IEC 62053-22 class 0.5 S
• IEC 62053-23 class 2
• IEC 61010-1
• IEC 61000-4-2
• IEC 61000-4-3
• IEC 61000-4-4
• IEC 61000-4-5
• IEC 61000-4-6
• IEC 61000-4-8
• IEC 61000-4-11
• IEC 60068-2-6
• IEC 60068-2-11
• IEC 60068-2-30
• UL 61010-1
• CSA C22.2 No. 61010-1
Applications
RS485
Diris A40
Diris A41
485
Main
meter panel
232
PLC
CON
ciel
de
TRO
on
rvisi
supe
DIR
L VISI
®
IS
et
CO
ON
UN
®
1
®
TIS
B. 54
per phase
curve
Logi
diris_581_a_1_gb_cat
PC Currents
CONTROL VISION software
Using electrical parameters means using
several analogue or digital single-function
products such as ammeters, voltmeters or
wattmeters.
DIRIS A40 and A41, with their six direct
access keys keyboard and LCD display,
allow exploiting all the parameters of a LV
and HV installation. These parameters may
be centralized on a PC or an automaton
through an RS485 link using
JBUS/MODBUS® or PROFIBUS ® DP
protocol. The casing allows the installer
easily fit DIRIS A40 or A41 panel board. To
facilitate and optimize the operator’s work,
DIRIS A40 and A41 use one of the most
functional principles for integrating
communications, metering, harmonics,
analog outputs or even alarm relays.
Simply fit a module on the rear of the
casing to add a function.
Measurement in real effective values
(TRMS) of:
- currents per phase and instantaneous
neutral, average and maximum values
over a programmable period,
- phase-to-neutral and phase-to-phase
voltages, instantaneous, average and
maximum over a programmable period,
- frequency, instantaneous, average and
maximum over a programmable period,
- active power on 4 quadrants (±)
per phase and total in instantaneous,
average and maximal values over
a programmable period,
- reactive power on 4 quadrants (±)
per phase and total in instantaneous,
average and maximal values over
a programmable period,
- apparent power per phase and total
in instantaneous, average and maximal
values over a programmable period,
- power Factor (PF) per phase and total
with inductive or capacitive indication,
- harmonic distortion rate (THD) up to 51
on phase-to-neutral and phase-to-phase
voltages and currents (THD 3U, THD 3V,
THD 3I, THD In).
Metering
• Active power meter on 4 quadrants.
• Reactive power meter on 4 quadrants.
• Apparent power meter.
• Programmable hour run meter.
This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2008 - 2009
SOCOMEC general catalogue
picto_108_a_gb
Services +
Energy management
> Audit
> Setting up
> Training
DIRIS A40 / DIRIS A41
See page IV
Plug-in modules
Pulse outputs
diris_445_a_1_cat
DIRIS® A40
2 pulse outputs able for configuration (type, weight and run) on ± kWh, ± kvarh and kVAh.
Pulse outputs and harmonics
diris_563_a_1_cat
diris_446_a_1_cat
2 pulse outputs able for configuration (type, weight and run) on ± kWh, ± kvarh and kVAh.
Spectral analysis of harmonics by range and by phase for 3I, In, 3V and 3U up to range 25.
RS485 JBUS / MODBUS® communication
diris_447_a_1_cat
RS485 link with JBUS / MODBUS® protocol (speed up to 38400 bauds).
RS485 PROFIBUS® DP communication
DIRIS® A41
diris_699_a_2_cat
RS485 link with PROFIBUS® DP protocol (speed up to 1.5 Mbauds).
2 outputs able for configuration on 3I, In, 3V, 3U, F, ±ΣP, ±ΣQ, ΣS, ΣPFL/C and 30 VDC
power supply.
2 modules may be connected at maximum, that is 4 analogue outputs.
diris_448_a_1_cat
diris_564_a_1_cat
Analogue outputs
2 inputs - 2 outputs
diris_449_a_1_cat
2 outputs assignable for the control of 3I, In, 3V, 3U, F, ±ΣP, ±ΣQ, ΣS, ΣPFL/C, THD 3I,
THD In, THD 3V, THD 3U and of the hour meter (storing of the 3 last alarms) or to the remote
control. 2 inputs for pulses metering. 3 modules may be connected at maximum, that is 6
inputs / outputs.
diris_682_a_1_cat
Memory
• Storing maximum over 62 days of P+, P-, Q+, Q- with an internal or external
synchronisation TOP of 5, 8, 10, 15, 20, 30 and 60 minutes.
• Storing of 10 hour-dated last alarms.
• Storing of minimum and maximum instantaneous last values for 3U, 3V, 3I, In, F, ΣP±,
ΣQ±, ΣS, THD 3U, THD 3V, THD 3I, THD In.
• Storing of 10 last hour-dated (EN 50160 and IEC 61000-4-30):
- voltage dips,
- over voltage,
- voltage cut off.
• Storing of 3U, 3V and F average values based on synchronisation function (maximum 60 days).
diris_718_a
diris_720_a
Accessories
IP65 protection
SOCOMEC general catalogue
Device fitted with 144 x 96 mm cut out plate
This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2008 - 2009
B. 55
Energy management
Network
analysis
L
DIRIS A40
DIRIS A41
DIRIS Am
DIRIS A20
DIRIS A40 / DIRIS A41
Communication interfaces
DIRIS VISION software
CONTROL VISION software
BILLING APPLICATION software
diris_561_b_2_cat
References
DIRIS A40
DIRIS A41
4CT inputs (not UL/CSA)
Basic device
Auxiliary power supply Us
110 … 400 VAC / 120 … 350 VDC (IEC) - 110 … 240 VAC / 120 … 250 VDC (UL/CSA)
12 … 48 VDC (not UL/CSA)
References e HT
4825 0A40
671,00
4825 1A40
842,00
References e HT
4825 0A41
996,00
4825 1A41
1 104,00
Optional plug & display modules
Plug-in modules (1)
Pulse outputs
Pulse outputs and harmonics
RS485 JBUS / MODBUS® communication
Analogue outputs
2 inputs - 2 outputs
RS485 PROFIBUS® DP communication
Memory
4825 0090
4825 0091
4825 0092
4825 0093
4825 0094
4825 0096
4825 0097
82,80
171,00
154,00
103,00
134,00
342,00
325,00
4825 0090
4825 0091
4825 0092
4825 0093
4825 0094
4825 0096
4825 0097
82,80
171,00
154,00
103,00
134,00
342,00
325,00
4825 0089
4825 0088
44,00
0,00
4825 0089
4825 0088
44,00
0,00
Accessories
IP65 protection cover (not UL/CSA)
Fitting kit for 144 x 96 mm cut out (not UL/CSA)
(1) Ease of integration for additional functions (maximum 4 on A40 and 3 on A41) by clutchable modules on the rear of the device, by the user at any moment.
Terminals
diris_569_a_1_x_cat
• DIRIS A40
V1
V2
V3
VN
A U X
S1 S2 S1 S2 S1 S2
I1
I2
S1 - S2: current imputs
AUX: auxiliary power supply Us
V1 - V2 - V3 - VN: voltage inputs
I3
DIRIS A40
V1
V2
V3
VN
A U X
S1 S2 S1 S2 S1 S2 S1 S2
I1
I2
+
diris_572_a_1_x_cat
0V -
1
0n
R = 120 Ω
RS485
• Pulse output module
DIRIS A40 / A41
1
2
3
4
OUT 2
OUT 1
DIRIS A40 / A41
RS485 link
R = 120 Ω: internal resistance for the RS485 link
1 - 2: pulse output no. 1
3 - 4: pulse output no. 2
• 2 inputs / 2 outputs module
• Memory module
9 10 11 12
OUT 1
OUT 2
A-Cd
A-Cd
1 3 14 15 16
-
+
IN 1
-
+
diris_683_a_1_x_cat
diris_571_a_1_x_cat
S1 - S2: current imputs
AUX: auxiliary power supply Us
V1 - V2 - V3 - VN: voltage inputs
IN
DIRIS A41
• Communication module
diris_574_b_1_x_cat
I3
• Analogue output module
diris_573_a_1_x_cat
diris_570_a_1_x_cat
• DIRIS A41
5
6
7
8
+
+
0/4-20 mA 0/4-20 mA
OUT 1
OUT 2
DIRIS A40 / A41
5 - 6: analogue output no. 1
7 - 8: analogue output no. 2
17 18
+
IN
synchro
DIRIS A40 / A41
17 - 18: synchronisation input
IN 2
DIRIS A40 / A41
9 - 10: relay output no. 1
11 - 12: relay output no. 2
13 - 14: opto input no. 1
15 - 16: opto input no. 2
B. 56
This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2008 - 2009
SOCOMEC general catalogue
Energy management
DIRIS A40 / DIRIS A41
Electrical characteristics
Current measurement on insulated inputs (TRMS)
CT primary
CT secondary
Measurement range
Input consumption
Measurement updating period
Accuracy
Sustained overload
Intermittent overload
Auxiliary power supply
10 000 A
1 and 5
0 … 11 kA
≤ 0.1 VA
1s
0.2 %
6A
10 In for 1 s
Voltage measurement (TRMS)
Current-voltage product
10 000 000
10 000 000
Power measurement
Measurement updating period
Accuracy
1s
0.5 %
Power factor measurement
Measurement updating period
Accuracy
1s
0.5 %
Frequency measurement
Measurement range
Measurement updating period
Accuracy
45 … 65 Hz
1s
0.1 %
Energy accuracy
Active (according to IEC 62053-22)
Reactive (according to IEC 62053-23)
SOCOMEC general catalogue
110 … 400 VAC
110 … 240 VAC
± 10 %
120 … 350 VDC / 12 … 48 VDC
120 … 250 VDC
± 20 % / - 6 … + 20 %
50 / 60 Hz
≤ 10 VA
Inputs
Direct measurement between phases (IEC)
18 … 700 VAC
Direct measurement between phases (UL/CSA)
50 … 500 VAC
Direct measurement between phase and neutral (IEC)
11 … 404 VAC
Direct measurement between phase and neutral (UL/CSA)
28 … 288 VAC
VT primary
500 000 VAC
VT secondary
60, 100, 110, 173, 190 VAC
Frequency
50 / 60 Hz
Input consumption
≤ 0.1 VA
Measurement updating period
1s
Accuracy
0.2 %
Sustained overload
760 VAC
Limitation for 1A CT
Limitation for 5A CT
AC voltage (IEC)
AC voltage (UL/CSA)
AC tolerance
DC voltage (IEC)
DC voltage (UL/CSA)
DC tolerance
Frequency
Consumption
Class 0.5 S
Class 2
Number
Power supply
Minimum signal width
Minimum length between 2 impulses
Type
2…6
10 … 30 VDC
10 ms
18 ms
phototransistor
Outputs (alarms / control)
Number of relays
Type
2 ... 6
230 VAC - 5 A - 1150 VA
Outputs (pulsed)
Number of relays
Type
Max. number of operations
2
100 VDC - 0,5 A - 10 VA
≤ 108
Outputs (analogue)
Number of outputs
Type
Range
Charging resistance
Maximum current
2…4
isolated
0 / 4 … 20 mA
600 Ω
30 mA
Communication
Link
Type
Protocol
JBUS / MODBUS® speed
Protocol
PROFIBUS® DP speed
RS485
2 ... 3 wires half duplex
JBUS/MODBUS® in RTU mode
1400 … 38400 bauds
PROFIBUS® DP
9.8 kbauds … 1.5 Mbauds
Operating conditions
Operating temperature
Storage temperature
Relative humidity
This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2008 - 2009
- 10 … + 55 °C
- 20 … + 85 °C
95 %
B. 57
Energy management
Network
analysis
L
DIRIS A40
DIRIS A41
DIRIS Am
DIRIS A20
DIRIS A40 / DIRIS A41
Communication interfaces
DIRIS VISION software
CONTROL VISION software
BILLING APPLICATION software
Overall dimensions
Type
Dimensions W x H x D
Case protection rating
Front protection rating
Display type
Terminal block type
Voltage and other connection section
Current connection section
Weight
92 +- 0,8
0,0
diris_582_b_1_x_cat
96
92 +- 0,8
0,0
panel mounting
96 x 96 x 60 mm
IP30
IP52
LCD
fixed or pull-out
0.2 … 2.5 mm2
0.5 … 6 mm2
400 g
20
60
96
Connections
Recommendation: when disconnecting the DIRIS, the secondaries of each current transformer must be short-circuited.
This operation can be carried out automatically from a product in the SOCOMEC catalogue, PTI, please consult us.
• 3/4 wires with 1 CT
• Single phase
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
N
L1
L2
L3
P1
S1
1
S2
S1
1
1
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
I2
I3
N
L1
L2
L3
P1
diris_393_c_1_gb_cat
diris_392_c_1_gb_cat
1
• Two phases
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
1
S2
P1
S1
1
1
V1 V2 V3 VN
diris_394_c_1_gb_cat
L
Low voltage balanced network for DIRIS A40
S1 S2 S1 S2 S1 S2
I1
I2
I3
L1
L2
S2
1
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
The use of 1 CT reduces by 0.5 % the accuracy of the
phase whose current is determined by vector calculation
• 3/4 wires with 3 CTs
• 3 wires with 2 CTs
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
N
L1
L2
L3
P1
S1
S2
P1
S1
S1
S1
L1
L2
L3
P1
S1
S2
S2
1
1
1
1
1
1
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
diris_396_c_1_gb_cat
diris_395_c_1_gb_cat
S2
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
The use of 2 CTs reduces by 0.5 % the accuracy of the
phase whose current is determined by vector calculation
B. 58
P1
L1
L2
L3
P1
1
1
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
P1
S2
S1
1
• 3 wires with 2 CTs
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
diris_397_c_1_gb_cat
L
Low voltage unbalanced network for DIRIS A40
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
The use of 2 CTs reduces by 0.5 % the accuracy of the
phase whose current is determined by vector calculation
This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2008 - 2009
SOCOMEC general catalogue
Energy management
DIRIS A40 / DIRIS A41
Connections
L
Low voltage unbalanced network for DIRIS A41
• 4 wires with 4 CTs
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
P1
N
L1
L2
L3
S1
P1
S1
S2
P1
S2
S1
diris_575_b_1_gb_cat
1
1
1
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 S1 S2
I1
I2
I3
IN
L
Other information
• Communication via RS485 link
• Voltage transformer connection
for HV networks
• AC & DC auxiliary power supply
110 / 400 VAC (IEC)
120 / 350 VDC (IEC)
L1
L2
L3
110 / 240 VAC (UL/CSA)
120 / 250 VDC (UL/CSA)
or
12-48 VDC (IEC)
+
ON
RS485
V1 V2 V3 N
diris_400_e_1_gb_cat
0V -
diris_399_b_1_x_cat
diris_398_c_1_x_cat
LIYCY-CY
A U X
It is recommended that the auxiliary power supply be
protected by the use of 500 mA gG, BS88 2A gG or 500 mA
CC Class fuses
SOCOMEC general catalogue
This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2008 - 2009
B. 59