Allen-Bradley FLEX I/O Input, Output, and Input/Output Analog Modules Installation Instructions
Allen-Bradley FLEX I/O Input, Output, and Input/Output Analog Modules are designed for use in industrial control systems. They offer various input and output capabilities, including voltage and current, to accommodate diverse applications. This manual explains the safety precautions and procedures for installing these modules in various hazardous and non-hazardous environments. The manual details the module configuration, wiring, and diagnostics, providing users with critical information for successful implementation.
PDF
Document
Advertisement
Advertisement
Installation Instructions FLEX I/O Input, Output and Input/Output Analog Modules ATTENTION Cat. Nos. 1794-IE8, -IE8K, -OE4, -OE4K, and -IE4XOE2 Series B (Modules with a K in the last position of the catalog number are conformally coated to meet noxious gas requirements of ISA/ANSI-71.040 1985 Class G3 Environment.) Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual we use notes to make you aware of safety considerations. Identifies information about practices or circumstances that can cause an WARNING explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION - . '/ 0 + #0 12113*4, /222 - 5406 - #0%0 7.8. 44 - 99- : 7- - 7(#;67 /<2 #0 12</= 6 6* 4>>2*34 +9 6 5 5 9, - - - ! - ? • : • • ' • ' - • * European Zone 2 Hazardous Location Approval IMPORTANT Identifies information that is critical for successful application and understanding of the product. ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you: • identify a hazard • avoid a hazard • recognize the consequence WARNING The following analog input/output modules are European Zone 2 approved: 1794-IE8/B, 1794-IE8K/B, 1794-OE4/B, 1794-OE4K/B and 1794-IE4XOE2/B. !" - #) ' =3%=%#0 "0 #+" 0 # -, - # @7 8- 0A- 6 ' (/B 1B/242 0 # @78- #(<22/4 IMPORTANT WARNING ATTENTION !"#$ %& ' ( ) *' ( ' ( + , O C/ - • - )D • * 0 C/ • #- #8 .<3 0 C/ • - 6* • . 32E 0 C/ Publication 1794-IN100B-EN-P - June 2004 2 '$ North American Hazardous Location Approval The following modules are North American Hazardous Location approved: 1794-IE8/B, 1794-IE8K/B, 1794-OE4/B, 1794-OE4K/B and 1794-IE4XOE2/B. The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux : Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation. Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation. EXPLOSION HAZARD WARNING AVERTISSEMENT ($ 0 #*+(,-',-'.&/0 0*A= 0*31 0FD A3A3*<4+0,*D % 41 ATTENTION RISQUE D’EXPLOSION • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. • Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement. • Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. • Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit. )$ FD : <4+FD, A3 0$ +*D, : AA+, 41 1 #*+(,234-,2354-6 2 • La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2. • Substitution of components may impair suitability for Class I, Division 2. • If this product contains batteries, they must only be changed in an area known to be nonhazardous. • S’assurer que l’environnement est classé non dangereux avant de changer les piles. Installing Your Analog Input/Output Module Channel Input 0 7 1 3 Input 1 2 Input 2 6 Input 3 4 5 Input 4 4>=3 ATTENTION ' + , ' Input 5 Input 6 Input 7 -V dc Common #$ $ '$ ($ )$ 8 +4, +/, A +4>=3* #B,3+4>=3*&#3,<+4>=3* #3$&#/,- ; +A, %% & $ ; . +3, +<, +1, . +>, Connecting Wiring for the Analog Inputs and Outputs #$ 0 % 2*4< +6,4>=3*/*A*A7*A*A7+, 4>=3*( IMPORTANT $ ' =B+A, )B>14 0% +6, +,4>=3*/*A*A7*A*A70 4>=3*(! - +0, Publication 1794-IN100B-EN-P - June 2004 +V dc Power Signal Type Label Marking 1794 -TB2, -TB3, -TB3S, -TB3T, -TB3TS, Input 1794 -TB3, -TB3S 1794 -TB2, TB3, -TB3S Power1 Common Terminal 1794-TB3T, -TB3TS Shield Current I0 A-0 C-35 B-17 B-17 C-39 Voltage V0 A-1 C-36 B-18 B-17 Current I1 A-2 C-37 B-19 B-19 C-40 Voltage V1 A-3 C-38 B-20 B-19 Current I2 A-4 C-39 B-21 B-21 C-41 Voltage V2 A-5 C-40 B-22 B-21 Current I3 A-6 C-41 B-23 B-23 C-42 Voltage V3 A-7 C-42 B-24 B-23 Current I4 A-8 C-43 B-25 B-25 C-43 Voltage V4 A-9 C-44 B-26 B-25 Current I5 A-10 C-45 B-27 B-27 C-44 Voltage V5 A-11 C-46 B-28 B-27 Current I6 A-12 C-47 B-29 B-29 C-45 Voltage V6 A-13 C-48 B-30 B-29 Current I7 A-14 C-49 B-31 B-31 C-46 Voltage V7 A-15 C-50 B-32 B-31 1794-TB2, -TB3, -TB3S - Terminals 16 thru 33 are internally connected in the terminal base unit. 1794-TB3T, -TB3TS - Terminals 16, 17, 19, 21, 23, 25, 27, 29, 31 and 33 are internally connected in the terminal base unit. 1794-TB3, -TB3S - Terminals 34 thru 51 are internally connected in the terminal base unit. 1794-TB3T, -TB3TS - Terminals 34, 35, 50 and 51 are internally connected in the terminal base unit. 1794-TB2 - Terminals 34 and 51 are internally connected in the terminal base unit. 1794-TB3T, -TB3TS - Terminals 39 thru 46 are internally connected to chassis ground. Chassis Ground (Shield) 1 Use when transmitter requires terminal base power. 3 -1 #*+(,234-,2354- -1 #*+(,7(4-,7(5416 I V I 0 1 0 16 34 2 1 17 V I V I 3 2 18 35 4 3 19 36 4 20 37 5 5 21 38 6 6 22 39 V I V I V I 7 7 23 40 i 8 8 24 41 42 10 26 43 T 45 ac or dc 4-W ire Current T ransmitter (External power) 4-W ire Voltage T ransmitter (External power) 13 29 46 14 30 47 48 A 15 31 32 49 33 50 51 0 -15 Input B 16-33 24V Common C 34-51 24V Power 1 #*+(,7(4-,7(54-7 Signal Type Output 0 Current I0 A-0 B-0 C-39 Current I0 Ret A-1 C-1 Voltage V0 A-2 B-2 C-40 Voltage V0 Ret A-3 C-3 Current I1 A-4 B-4 C-41 Current I1 Ret A-5 C-5 Voltage V1 A-6 B-6 C-42 Voltage V1 Ret A-7 C-7 Current I2 A-8 B-8 C-43 Current I2 Ret A-9 C-9 Voltage V2 A-10 B-10 C-44 Voltage V2 Ret A-11 C-11 Current I3 A-12 B-12 C-45 Current I3 Ret A-13 C-13 Voltage V3 A-14 B-14 C-46 Voltage V3 Ret A-15 C-15 1794-TB3, -TB3S - Terminals 16 thru 33 are internally connected in the terminal base unit. 1794-TB3T, -TB3TS - Terminals 16, 17, 19, 21, 23, 25, 27, 29, 31 and 33 are internally connected in the terminal base unit. 1794-TB2 - Terminals 16 and 33 are internally connected in the terminal base unit 1794-TB3, -TB3S - Terminals 34 thru 51 are internally connected in the terminal base unit. 1794-TB3T, -TB3TS - Terminals 34, 35, 50 and 51 are internally connected in the terminal base unit. 1794-TB2 - Terminals 34 and 51 are internally connected in the terminal base unit. 1794-TB3T, -TB3TS - Terminals 39 thru 46 are internally connected to chassis ground. Output 1 Output 2 Output 3 -V dc Common +V dc Power Chassis Ground (Shield) Shield (1794-TB3T, -TB3TS 8 5 10 7 12 9 11 14 33 13 15 51 I + Current Output Device _ I + Voltage _ Output Device + Row B 16, 0, 2, 4, 6, 8, 10, 12, 14, 33 Row C 34, 1, 3, 5, 7, 9, 11, 13, 15, 51 51 I + Voltage _ Output Device + Current only dc only 2-Wire Output 3-Wire Output Device Device 1794-TBN shown dc only 3-Wire Output Device 1 #*+(,2(874-(62 4 7 Signal Type Channel 1794-TBN Channel Output Terminal1 3 Current only 2-Wire Output Device 2-W ire Current T ransmitter (T erminal base powered loop) 1794-TB2, -TB3, -TB3S, -TB3T, -TB3TS 1 6 I + Current Output Device _ (1794-TB3 base shown) Label Marking 4 34 i 3-W ire T ransmitter (T erminal base powered 2 34 T T + ac or dc 12 28 44 T 11 27 33 Even Numbered Terminals 0 thru 14 0 16 V 9 10 11 12 13 14 15 9 25 V I Output Terminal2 1794-TB2, -TB3,-TB3S, -TB3T, -TB3TS 1794 -TB3, -TB3S Input/Output Terminal1 Power Terminal2 1794 -TB2, -TB3, -TB3S Common Terminal 1794-TB3T, -TB3TS Shield Current I0 A-0 C-35 B-17 B-17 C-39 Voltage V0 A-1 C-36 B-18 B-17 Current I1 A-2 C-37 B-19 B-19 C-40 Voltage V1 A-3 C-38 B-20 B-19 Current I2 A-4 C-39 B-21 B-21 C-41 Voltage V2 A-5 C-40 B-22 B-21 Current I3 A-6 C-41 B-23 B-23 C-42 Voltage V3 A-7 C-42 B-24 B-23 Current I0 A-8 C-43 Current RET A-9 Voltage V0 A-10 C-44 Voltage RET A-11 Current I1 A-12 C-45 Current RET A-13 Voltage V1 A-14 C-46 Voltage RET A-15 1794-TB2, -TB3, -TB3S - Terminals 16 thru 33 are internally connected in the terminal base unit. 1794-TB3T, -TB3TS - Terminals 16, 17, 19, 21, 23, 25, 27, 29, 31 and 33 are internally connected in the terminal base unit. 1794-TB3, -TB3S - Terminals 34 thru 51 are internally connected in the terminal base unit. 1794-TB3T, -TB3TS - Terminals 34, 35, 50 and 51 are internally connected in the terminal base unit. 1794-TB2 - Terminals 34 and 51 are internally connected in the terminal base unit. 1794-TB3T, -TB3TS - Terminals 39 thru 46 are internally connected to chassis ground. Input 0 Input 1 Input 2 Input 3 Output 0 Output 1 -V dc Common +V dc Power Chassis Ground (Shield) 1 2 Label Marking A-9, 11, 13 and 15 are internally connected in the module to 24V dc common. Use when transmitter requires terminal base power. -1 #*+(,2(874#*+(,-'-" 1 A-1, 3, 5, 7, 9, 11, 13 and 15 are internally connected in the module to 24V dc common. 2 C-1, 3, 5, 7, 9, 11, 13 and 15 are internally connected in the module to 24V dc common I V I V I V I V 0 0 1 1 17 16 18 35 34 I+ 2 2 3 3 19 36 – Current Input + – ac or dc 4-Wire Current Transmitter 4 4 20 37 5 5 21 38 22 39 I 6 6 23 40 I R V R 7 7 8 8 24 41 25 42 9 10 9 10 26 43 27 44 I R V R 11 11 28 45 12 12 13 14 15 13 29 46 14 30 47 A 15 31 48 32 49 33 50 B 51 C 0 –1 5 16– 33 34– 51 + Voltage – Input + dc only 3-Wire Transmitter I + Current Output Device – Current only 2-Wire Output Device I + Voltage Output Device – + dc only 3-Wire Output Device Publication 1794-IN100B-EN-P - June 2004 4 Input Map (Read) - 1794-IE8, -IE8K Input Map (Read) - 1794-OE4, -OE4K Dec. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Dec. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Oct. 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 Oct. 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 Word 0 S Analog Input Value for Channel 0 Word 0 Not used - set to 0 Word 1 S Analog Input Value for Channel 1 P U W 3 W 2 W 1 W 0 Word 2 S Analog Input Value for Channel 2 Word 3 S Analog Input Value for Channel 3 Word 4 S Analog Input Value for Channel 4 Word 5 S Analog Input Value for Channel 5 Word 6 S Analog Input Value for Channel 6 Word 7 S Analog Input Value for Channel 7 Word 8 PU Not used - set to zero Where : PU = Power up bit W thru W3 = Wire off current loop status for output channels Output Map (Write) - 1794-OE4, -OE4K U 7 U 6 U 5 U 4 U 3 U 2 U 1 U 0 Where :PU = Power up inconfigured S = Sign bit (in 2’s complement) U = Underrange for specified channel Dec. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Oct. 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 Word 0 S Output Data Channel 0 Word 1 S Output Data Channel 1 Word 2 S Output Data Channel 2 Word 3 S Output Data Channel 3 C2 C1 C0 Not used - set to 0 Word 4 Output Map (Write) - 1794-IE8, -IE8K Word 5 Not used - set to 0 Not used - set to 0 C3 Dec. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Oct. 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 Word 6-9 Not used - set to 0 Word 3 C 7 C 6 C 5 C 4 C 3 C 2 C 1 C 0 F 7 F 6 F 5 F 4 F 3 F 2 F 1 F 0 Word 10 S Safe state value for Channel 0 Word 11 S Safe state value for Channel 1 Word 12 S Safe state value for Channel 2 Word 13 S Safe state value for Channel 3 Where : C = Configure select bit F = Full range bit Input Map (Read) - 1794-IE4XOE2 Dec. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Oct. 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 Word 0 S Analog Input Value for Channel 0 Word 1 S Analog Input Value for Channel 1 Word 2 S Analog Input Value for Channel 2 Word 3 S Analog Input Value for Channel 3 Word 4 P U Not used - set to zero W 1 W 0 U 3 U 2 U 1 U 0 Output Map (Write) - 1794-IE4XOE2 15 13 12 11 10 9 8 7 6 5 4 3 2 1 0 15 14 13 12 11 10 7 6 5 4 3 2 1 0 M 1 M 0 F 1 F 0 Oct. 17 16 Word 0 S Analog Output Data - Channel 0 Word 1 S Analog Output Data - Channel 1 Word 2 Not used - set to 0 Word 3 0 Words 4 and 5 Not used - set to 0 0 C 5 C 4 C 3 C 2 Word 6 Safe State Value for Channel 0 Word 7 Safe State Value for Channel 1 C 1 C0 0 0 F5 F4 F3 F 2 M 2 M 1 M 0 F 2 F 1 F 0 Range Selection Bits - 1794-OE4, -OE4K Dec. Bits 0-10V dc/ 0-20mA 4-20mA -10 to +10V dc OFF1 14 M 3 F 3 Where : S = Sign bit (in 2’s complement) M = Multiplex control bit C = Configure select bit F = Full range bit Channel No. Where :PU = Power up inconfigured S = Sign bit (in 2’s complement) W1 and W0 = Diagnostic bits for current output. Wire off current loop status for output channels 0 and 1 U = Underrange for specified channel Dec. 0 In Ch. 0 F0 C0 00 08 In Ch.1 F1 C1 01 09 In Ch. 2 F2 C2 02 10 In Ch. 3 F3 C3 03 11 1 0 1 0 1 0 1 0 0 1 0 1 1 0 0 1 0 1 1 0 0 1 0 1 1 0 0 1 0 1 1 0 Where: C = Configure Select Bit F = Full range 1 When configured to Off, individual output channels will drive 0V/0mA. Specifications Input Specifications Number of Inputs Where : PU = Power up inconfigured FP = Field power off CF = In configuration mode BD = Bad calibration DN = Calibration accepted W1 and W0 = Wire off current loop status for output channels 0 and 1 U = Underrange for specified channel V = Overrange for specified channel P0 and P1 = Outputs holding in response to Q0 and Q1 Range Selection Bits - 1794-IE8, -IE8K and -IE4XOE2 1794-IE8 In Ch. 0 In Ch. 1 In Ch. 2 In Ch. 3 In Ch. 4 In Ch. 5 1794IE4XOE2 In Ch. 0 In Ch.1 In Ch. 2 In Ch. 3 Out Ch. 0 Out Ch. 1 F0 C0 F1 C1 F2 C2 F3 C3 F4 C4 F5 Dec. Bits 00 08 01 09 02 10 03 11 04 12 0-10V dc/ 0-20mA 1 0 1 0 1 0 1 0 1 4-20mA 0 1 0 1 0 1 0 1 -10 to +10V dc 1 1 1 1 1 1 1 1 OFF1 0 0 0 0 0 0 0 0 In Ch. 6 In Ch. 7 C5 F6 C6 F7 C7 05 13 06 14 07 15 0 1 0 1 0 1 0 0 1 0 1 0 1 0 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 Resolution Voltage Current Data Format Conversion Type Conversion Rate Input Current Terminal Input Voltage Terminal Where: C = Configure Select Bit F = Full range 1 When configured to Off, individual input channels will return 0000H; output channels will drive 0V/0mA. Normal Mode Rejection Ratio Voltage Terminal Current Terminal Step Response to 63% Input Impedance Input Resistance Voltage Absolute Accuracy1 Accuracy Drift with Temperature Calibration Required Maximum Overload Indicators Publication 1794-IN100B-EN-P - June 2004 1794-IE8, -IE8K - 8 single-ended, nonisolated 1794-IE4XOE2 - 4 single-ended nonisolated 12 bits unipolar; 11 bits plus sign bipolar 2.56mV/cnt unipolar; 5.13mV/cnt bipolar 5.13μA/cnt left justified, 16 bit 2s complement successive approximation 256μs all channels 4-20mA (user configurable 0-20mA (user configurable +10V (user configurable) 0-10V (user configurable) 3dB @ 17Hz; -20db/decade -10db @ 50Hz;-11.4db @ 60Hz -3dB @ 9Hz; -20db/decade -15.3db @ 50Hz;-16.8db @ 60Hz Voltage Terminal - 9.4ms Current Terminal - 18.2ms Voltage Terminal - 100k ohms Current Terminal - 238 ohms Voltage Terminal - 200k ohms Current Terminal - 238 ohms 0.20% Full Scale @ 25°C Voltage Terminal - 0.00428% Full Scale/°C Current Terminal - 0.00407% Full Scale/°C None required 30V continuous or 32mA continuous, one channel at a time. 1 green power indicator 5 Output Specifications Number of Outputs Resolution Voltage Current Data Format Conversion Type Output Current Terminal Output Voltage Terminal Step Response to 63% Voltage or Current Terminal Current Load on voltage output Absolute Accuracy1 Voltage Terminal Current Terminal Accuracy Drift with Temperature Voltage Terminal Current Terminal Resistive Load on mA Output 1794-OE4, -OE4K - 4 single-ended, nonisolated 1794-IE4XOE2 - 2 single-ended, nonisolated 12 bits plus sign 0.156mV/cnt 0.320μΑ/cnt left justified, 16 bit 2’s complement Pulse width modulation 0mA output until module is configured 4-20mA (user configurable 0-20mA (user configurable 0V output until module is configured +10V (user configurable) 0-10V user configurable) 24ms Surge Transient Immunity Enclosure Type Rating Conductors Wire Size Category2 Certifications (when product is marked)3 3mA maximum 0.133% Full Scale @ 25°C 0.425% Full Scale @ 25°C 0.0045% Full Scale/°C 0.0069% Full Scale/°C 15-750 ohm @ 24V dc 1 2 3 General Specifications for 1794-IE8, -IE8K, -OE4, -OE4K, and -IE4XOE2 Module Location Terminal Base Screw Torque Isolation Voltage External dc Power Supply Voltage Range Supply Current Dimensions (with module installed) Flexbus Current Power Dissipation Thermal Dissipation Keyswitch Position Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Vibration Shock Emissions ESD Immunity Radiated RF Immunity Conducted RF Immunity EFT/B Immunity IEC 61000-4-5: ±2kV line-earth (CM) on shielded ports None (open-style) 22-12AWG (0.34mm2-2.5mm2) stranded copper wire rated at 75°C or higher 3/64 inch (1.2mm) insulation maximum 2 UL UL Listed Industrial Control Equipment UL UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations CULUS UL Listed Industrial Control Equipment, certified for US and Canada (1794-IE8, -OE4) CUL UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for Canada (1794-IE8, -IE8K, -OE4, -OE4K) CSA CSA certified Process Control Equipment CSA CSA certified for Class I, Division 2, Groups A, B, C and D Hazardous locations EEx3 European Union 94/9/EEC ATEX Directive, compliant with: EN 50021; Potentially Explosive Atmospheres, Protection “n” (European Zone 2) CE3 European Union 89/336/EEC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity C-Tick3 - Australian Radiocommunications Act compliant with AS/NZS CISPR 11, Industrial Emissions Includes offset, gain, nonlinearity and repeatability error terms. You use this category information for planning conductor routing as described in Allen-Bradley publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines. For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details. For notification of any additional release notes, refer to www.ab.com/manuals/. Cat. No. 1794-IE8, -IE8K, -IE4XOE2 - 1794-TB2, -TB3, -TB3S, -TB3T, -TB3TS Terminal Base Unit Cat. No. 1794-OE4, -OE4K - 1794-TB2, -TB3, -TB3S, -TB3T, -TB3TS, and -TBN Terminal Base Unit 7 pound-inches (0.8Nm) 9 pound-inches (1.0Nm) for 1794-TBN Tested at 850V dc for 1s between user power to system No isolation between individual channels 24V dc nominal 10.5 to 31.2V dc (includes 5% ac ripple) 1794-IE8, -IB8K - 60mA @ 24V dc; 150mA @ 12V dc 1794-OE4, -OE4K - 70mA @ 24V dc; 150mA @ 12V dc 1794-IE4XOE2 - 70mA @ 24V dc; 150mA @ 12V dc 31.8H x 3.7W x 2.1D inches 45.7H x 94W x 53.3D mm 20mA 1794-IE8, -IB8K - 3.0W maximum @ 31.2V dc 1794-OE4, -OE4K - 4.5W maximum @ 31.2V dc 1794-IE4XOE2 - 4.0W maximum @ 31.2V dc 1794-IE8, -IB8K - Maximum 10.2 BTU/hr @ 31.2V dc 1794-OE4, -OE4K - Maximum 13.6 BTU/hr @ 31.2V dc 1794-IE4XOE2 - Maximum 15.3 BTU/hr @ 31.2V d 1794-IE8, -IB8K - 3 1794-OE4, -OE4K - 4 1794-IE4XOE2 - 5 IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0 to 55°C (32 to 131°F) IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): –40 to 85°C (–40 to 185°F) IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5 to 95% non-condensing IEC60068-2-6 (Test Fc, Operating): 5g @ 10-500Hz IEC60068-2-27 (Test Ea, Unpackaged shock): Operating 30g Non-operating 50g CISPR 11 Group 1, Class A (with appropriate enclosure) EC 61000-4-2: 4kV contact discharges 8kV air discharges IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz IEC 61000-4-6: 10V rms with with 1kHz sine-wave 80%AM from 150kHz to 30MHz IEC 61000-4-4: ±2kV at 5kHz on signal ports Publication 1794-IN100B-EN-P - June 2004 Publication 1794-IN100B-EN-P - June 2004 6 Supersedes Publication 1794-IN100A-EN-P - April 2003 PN 957899-39 Copyright © 2004 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">

Download
Just a friendly reminder. You can view the document right here. But most importantly, our AI has already read it. It can explain complex things in simple terms, answer your questions in any language, and help you quickly navigate even the longest or most compilcated documents.
Advertisement
Key features
- Analog input/output modules
- Hazardous location approval (European Zone 2 and North American)
- Configurable input and output ranges
- 12-bit resolution
- Pulse width modulation (PWM) output
- Flexbus connectivity
- Terminal base compatibility
Frequently asked questions
The modules have an operating temperature range of 0 to 55°C (32 to 131°F) as per IEC 60068-2-1 and IEC 60068-2-2.
Yes, the modules are compatible with Allen-Bradley's Flexbus network. They use a 20mA Flexbus current for communication.
The modules can handle a maximum overload of 30V continuous or 32mA continuous, but only one channel at a time.
The recommended wire size for these modules is 22-12AWG (0.34mm2-2.5mm2) stranded copper wire rated at 75°C or higher with a maximum insulation of 3/64 inch (1.2mm).