Below you will find brief information for Heating Cable HWAT L, Heating Cable HWAT M, Heating Cable HWAT R, Heating Cable FS A-2X, Heating Cable FS B-2X, Heating Cable FS C-2X, Heating Cable FS C10-2X, Control Unit HWAT ECO, Control Unit HWAT T55. The HWAT series of heating cables can be used for hot water temperature maintenance, while the FS series is designed for frost protection. The HWAT ECO control unit is designed for easy set-up and operation, providing an efficient way to manage the heating cable’s power output dependent on ambient temperature and moisture. The HWAT T55 thermostat with a line sensor for hot-water branch lines and small hot-water pipe networks provides precise temperature control for your water system. The AT-TS 13 and 14 thermostats are used for frost protection applications and offer reliable temperature control for a variety of applications. The RAYSTAT ECO-10 and CONTROL-10 thermostats are designed for ambient and line temperature control, respectively, providing energy-saving features. With a wide range of heating cables and control units to choose from, Pentair’s Thermal Building Solutions offer a comprehensive range of solutions for winter safety, comfort and performance.
Advertisement
Advertisement
TECHNICAL HANDBOOK
Pentair’S thermal BUilding SolUtionS
KEEp pEOpLE AND INfrAsTruCTurE sAfE frOm HArm, ENHANCE BuILDINg pErfOrmANCE AND BrINg COmfOrT INTO THE HOmE.
THERMAL buiLding SOLuTiOnS WWW.PEnTAiRTHERMAL.COM
buiLding & infRASTRuCTuRE
SOLuTiOnS
We provide quality solutions for winter safety, comfort and performance to building and infrastructure design, construction, operation and maintenance professionals. From pipe freeze protection to maintaining fluid temperatures and melting snow, detecting leaks or heating floors, you can rely on Pentair’s solutions
& services for greater safety, comfort and performance.
THE HEART Of OuR SOLuTiOnS
In 1970, Raychem first developed and launched self-regulating electric heating cables.
The cable delivers the right amount of heat exactly when and where it is needed. As the temperature drops, more heat is produced. Conversely, as the temperature rises, less heat is produced. But there are many more benefits:
• The smart cables can be overlapped without any risk of overheating.
• The heating cables can be cut to length ‘in the field’. This means additional flexibility when plans do not correspond to the ”real life” situation on site.
• The length of pipe corresponds to the length of cable that you need.
A COLd AMbiEnT = HigH POWER OuTPuT
If the temperature in the immediate vicinity of the self-regulating heating cable is cold, the heat output from the heating cable is increased. The polymeric core of the cable contracts, which creates many electrical paths across the integrated carbon particles.
b WARM AMbiEnT = LOW POWER OuTPuT
In response to a warmer environment, the heat output of the self-regulating cable is reduced. The polymeric core of the cable expands, reducing the electrical paths.
C HOT AMbiEnT = ViRTuALLy nO OuTPuT
If the temperature in the environment of the self-regulating heating cable reaches a high temperature, the heat output is minimal. Due to the maximum expansion of the polymeric core of the cable, most of the electrical paths are broken.
A b C
2
THERMAL buiLding SOLuTiOnS
TESTEd And quALifiEd
• Stringent production monitoring
• Approved BS EN 62395
(IEC62395)
• VDE approved
• CE marked
RObuST COnSTRuCTiOn
• Long service life assured through modified polyolefin or fluorpolymer insulation and jacket materials.
LifE TiME
Member of the European
• Intensive tests according to
Mitglied in der European Radiant
Floor Heating Association e.V.
recognized scientific procedures. cables have a service life in excess of 20 years.
Our products satisfy the requirements of the relevant
European Directives.
iT’S nOT OnLy THE CAbLE!
The combination of a self-regulating heating cable and a smart control unit allows for dynamic management of the heating cable’s power output dependent on parameters such as ambient temperature and moisture.
These will help you and your customers to comply with today’s building regulations on energy savings.
A complete Raychem system can result in energy savings of up to 80% !
Our control units
(e.g. HWAT-ECO) are designed for easy set-up and operation. They are easy to access for fast wiring.
Ergonomic buttons, intuitive menu-driven operation and pre-installed programmes allow for quick set-up.
Specific connection systems have been designed and configured to be fully compatible with our heating cables. The RayClic connection system cuts installation time by 80%.
Inserting the stripped cable into the module and a few screws is all it takes.
CuSTOMER SERViCE CEnTRE And TECHniCAL SuPPORT TEAM
Pentair offers a set of tools and services that aim to simplify the professional´s life. Not only do we offer the best quality products, we also support them with unrivalled services.
• Multi-lingual customer service representatives to answer all your questions
• Fast order handling & shipment Europe-wide
• Free documentation service
• “On demand” technical advice
• Free designs and quotations
• Direct support to specifiers and installers
• Training support upon request
• Complete after-sales service
• Also for non-standard applications our team can assist you in finding the right heating solution. Do not hesitate to get in touch with us
Free phone 0800 96 90 13 or Free fax 0800 96 86 24.
RAyCHEM “TRACE-iT”, Add-in SOfTWARE PACKAgE fOR AuTOdESK REViT MEP
• Heat loss calculations for piped services
• Product selection based upon actual systems designed in Revit
• Automatic calculation of BOM including accessories
• Circuit information, power requirements & circuit lengths
• Engineering specification content for installed products
* Complete Trace Heating Revit Schedule direct in the BIM
Trace-it is available, free of charge from Autodesk SEEK.
Technical handbook
3
OVERViEW Of APPLiCATiOnS
3
1
4
5
2
4
4
THERMAL buiLding SOLuTiOnS
CONTENTS
1
Hot water temperature maintenance 6
2
frost protection for pipes 20 frost protection for gutters and downpipes 40
3
4
5
snowmelting of ramps, steps, footpaths and accessways
Electrical underfloor heating
52
55
6
7
multiple application control & monitoring system general installation instructions for self-regulating heat-tracing systems
Technical data – Choice of accessories
62
18
38
64
67
Technical handbook
5
HOT WATER TEMPERATuRE MAINTENANCE
Providing the comfort of instant hot water is the key requirement of any modern hot water system. The Raychem single-pipe system keeps water at the right temperature in a building’s water distribution pipe work. The intelligent system first keeps the investment cost low and then it operates economically and efficiently.
An HygiEniC SySTEM
Less water volume and less heat loss in the pipe work help prevent bacteriological problems.
A fLExibLE And SPACE-SAVing
SySTEM
The space requirement for pipes has been reduced because there are no return pipes. Risers, shafts and openings can be optimised freeing space for other services.
LOW inVESTMEnT COSTS
The heating cable is simply fixed on the supply pipe. There is no need for return pipe work, valves or pumps, nor for complex design and balancing work associated with return systems.
LOWER POWER COnSuMPTiOn
The heat loss in the system is significantly lower as only the heat loss from the feed pipe (and not from the return pipe) is to be compensated for.
There is also no power requirement for circulation pumps.
The single-pipe system can be used with a smaller boiler and as there is no cold return water coming into the boiler, the heat-up of the water is more efficient.
The intelligent HWAT-ECO control unit saves power e.g. it can lower the temperature or switch off during water consumption peaks.
nO MAinTEnAnCE COSTS
The system has no mechanical parts such as a recirculation pump or control valves. There are no parts to wear out.
LOng LifETiME
The selfregulating Raychem heating cable has a lifetime of over 40 years.
1
2
3
4
Gel-filled end seal
(RayClic-E-02)
Heating cable
(HWAT-L, M or R)
4-way connection
(RayClic-X-02)
Power connection
(RayClic-CE-02)
5
4
6
THERMAL buiLding SOLuTiOnS
1
2
3
3
6
7
5
6
7
Sensor HWAT-ECO (incl.)
A three-wire PT-100 temperature sensor (HARD-78) can be installed optionally in an immersion pipe installed on site.
Residual current device (rcd)
(30 mA) Circuit-breaker (C type)
Temperature control unit
(HWAT-ECO)
dESign guidE, COnTROL uniTS And ACCESSORiES
1 HEATing CAbLE SELECTiOn
Optimum water temperature maintenance for single family houses, flats, offices, hotels, hospitals, convalescent homes, sports centres, ...
Heating cable type
Power output
Max. exposure temperature
Outer jacket colour
Control unit: HWAT-ECO
Control unit: HWAT-T55
Control unit: ACS 30
HWAT-L
7W/m at 45°C
65°C yellow
– recommended
–
HWAT-M
9 W/m at 55°C
65°C orange recommended for enhanced energy - efficiency recommended recommended
(project size >1500 m); see page 62
Legionella prevention
HWAT-R
12 W/m at 70°C
80°C red essential mandatory recommended
(project size >1500 m); see page 62
Possibility of thermal legionella prevention up to the draw-off points
2 COMPOSiTiOn Of THE HWAT-L/M/R HEATing CAbLE
1 2 3
4 5
4 inSuLATiOn
THiCKnESSES
6
3 HEATing CAbLE LEngTH
1
Copper conductor (1.2 mm
2
)
2
Self-regulating heating element
3
Modified polyolefin insulation
4
Aluminium foil wrap
5
Protective tinned copper braid
6
Modified polyolefin protective outer jacket.
Technical data: see page 67
The heating cable is installed in a straight line on the pipework
The heating cable can be traced right up to the draw-off points
Total length of pipe to be traced
+ approx. 0.3 m per connection
+ approx. 1.0 m per T-connection
+ approx. 1.2 m per 4-way connection
= required heating cable length
Pipe size (mm)
Insulation thickness (mm)
15
20
22
20
28
25
35
30
Ambient temperature: 18°C
Thermal conductivity λ = 0.035 W/(m.K)
For other thermal conductivity insulation materials, contact your
Pentair representative.
Thermal losses in W/m, pipe 55°C in 18°C ambient temp. insulation dn 15 dn 20 dn 32 dn 40
15 mm
20 mm
30 mm
40 mm
50 mm
60 mm
10
9
7
6
6
5
12
10
8
7
7
6
9
8
8
16
14
11
18
15
12
10
9
8
42
40
54
50
dn 50
12
10
9
21
18
14
Technical handbook
7
Thermal losses in W/m, pipe 55°C in 5°C ambient temp. insulation
15 mm
dn 15
13
dn 20
16
dn 32
21
20 mm
30 mm
40 mm
50 mm
12
10
8
8
13
11
10
9
18
14
12
11
60 mm 7
Calculations with TraceCalc PRO
8 10
• Maintain temperature 55°C
• Building interior
• Safety factor 10%
• Mineral wool, thermal conductivity at 40°C 0.041 W/mk
dn 40 dn 50
24 28
20
16
13
12
11
23
18
15
13
12
5 ELECTRiCAL PROTECTiOn
• The total length of heating cable determines the number and size of the circuit breakers
• Residual current device (rcd) : 30 mA required
• Power cabling for the heating cables according to local regulationsw
• The power connection must be carried out by an approved electrical installer
Circuit-breaker to bSEn 60898 (type C) : the maximum length of the heating circuit is based on a minimum start-up temperature of +12°C, 230 VAC.
10 A
13 A
16 A
20 A
HWAT-L
80 m
110 m
140 m
180 m
HWAT-M
50 m
65 m
80 m
100 m
HWAT-R
50 m
65 m
80 m
100 m
6 CHECKLiST fOR PLAnning THE inSTALLATiOn
The system design should take into account:
• Pipe di am e ter and material
• Insulation type and thickness
• Ambient temperature
• Circuits should divide the plumbing into logical segments
• Don’t exceed the maximum circuit length
• Show connection locations on the drawings
• Locate power connections near the electrical panel
• Locate T-connections in accessible areas
7 TESTing Of THE inSTALLATiOn
See page 64
8 COnTROL PAnELS
SbS-01-HM-ECO-10
Control Panel: Steel plate housing, wall-mounted version, equipped with mains power switch, RCD/CB combination, inlet and outlet terminals. Completely assembled, turnkey condition wired and inspected cable guides in base of housing.
The control panel contains a HWAT-ECO temperature control.
Control panel for heating circuit, basic version.
• PCN: 390056-000
8
THERMAL buiLding SOLuTiOnS
SbS-03-HV-ECO-10
SbS-06-HV-ECO-10
SbS-09-HV-ECO-10
9 COnTROL uniTS
HWAT-ECO
HARd-78
HWAT-T55
10 11 12 13 14 15 16 17 18
HWAT-T55
1 2 3 4 5 6 7 8 9
HWAT-T55-Sensor
Control panel for 2 to 3 heating circuits.
• PCN: 035958-000
Control panel for 4 to 6 heating circuits.
• PCN: 539268-000
Control panel for 7 to 9 heating circuits.
• PCN: 294452-000
Electronic temperature control unit with integrated clock
• Building-specific programme
• Boiler temperature monitoring
• Economy programmes
• Password protection
• Simple user interface
• Compatible with HWAT-L/M/R heating cables
• BMS interface
• Alarm outputs
Technical data: see page 13
PT-100 temperature sensor (HARD-78) for assembly in sensor pipe installed on site.
• Diameter of sensor cable 4 mm
• Diameter of sensor element 6 mm
• Length of sensor element 50 mm
• Sensor length total 3 m
Thermostat with line sensor for hot-water branch lines and small hot-water pipe networks for HWAT-L, M and R
(up to max. 50 m heating cable length)
• Temperature control with line sensor
• DIN-Rail mounted (35 mm)
• Manual ON/OFF
• Digital temperature display
• 3 operation mode –ON/ ECO/ OFF
• 3 pre-set hot water maintain temperatures 55°C, 50°C, 45°C; editable
• Over and lower temperature alarm
• Timer function for energy saving mode/night reduction
• PCN: 294452-000
Technical data: see page 16
Temperature line sensor for HWAT-T55 thermostat for fixing on hot water pipe
• NTC 2K - sensor
• Sensor length: 10 m
• Diameter sensor length: 4 mm
• Diameter sensor probe: 5 mm
• Length sensor probe: 20 mm
• Temperature range: 0°C bis +70°C
• PCN: 1244-015847
Technical data: see page 16
Technical handbook
9
10 ACCESSORiES
RayClic-CE-02
RayClic-T-02
RayClic-PT-02
RayClic-S-02
RayClic-PS-02
RayClic-x-02
10
THERMAL buiLding SOLuTiOnS
Power connection
• With 1.5 m power cable
• End seal and support bracket
• IP 68
• External dimension: L = 240 mm
W = 64 mm
H = 47 mm
T-connection
• Connection for 3 cables
• End seal and support bracket
• IP 68
• External dimension: L = 270 mm
W = 105 mm
H = 42 mm
Power T-connection
• 3 connections with integral 1.5 m power cable
• 3 end seals and 1 support bracket
• IP 68
• External dimension: L = 270 mm
W = 105 mm
H = 42mm
Splice for joining 2 lengths of heating cable
• Connection for 2 cables with 1 support bracket
• IP 68
• External dimension: L = 240 mm
W = 64 mm
H = 47 mm
Powered splice
• Connection for 2 cables with integral 1.5 m power cable
• 2 end seals and 1 support bracket
• IP 68
• External dimension: L = 270 mm
W = 105 mm
H = 42 m
4-way connection
• Connection for 4 cables
• 2 end seals and 1 support bracket
• IP 68
• External dimension: L = 270 mm
W = 105 mm
H = 42 mm
RayClic-E-02
Gel-filled end seal
• For system extensions (to be ordered separately)
• IP 68
KbL-10 gT-66 gS-54
ATE-180
Cable ties
• One pack of 100 required for approx. 30 m of pipework
• Length: 370 mm
• Temperature and UV resistant
Use ATE-180 on plastic pipes
Heat-resistant glass cloth tape
• For steel pipes or for any installation below 4.4°C
• 20 m roll for approx. 20 m of pipework
Use ATE-180 on plastic pipes
Glass cloth tape for attaching heating cable to pipe
• For stainless-steel pipes or for any installation below 4.4°C
• 16 m per roll, 12 mm width
Aluminium adhesive tape
• Heat resistant up to 150°C
• 55 m roll for approx. 50 m of pipework
On plastic pipes: the heating cable must be covered with aluminium adhesive tape along its entire length
iEK-20-M (for HWAT-L, -M) /
Insulation entry kit
iEK-25-04 (for HWAT-R)
• Insertion of heating cable in metal cladding
• Consists of: metal fasteners, metric gland and joint seal
LAb-i-01
ELECTRIC
TRACED
R
Electric traced label
• To be placed at 5 m intervals on insulation surface
Technical handbook
11
11 gEnERAL inSTALLATiOn inSTRuCTiOn
See page 67
Cabinet type unit
Number of heating circuits
Enclosure version
Dimensions Width mm
Height mm
Depth mm
Weight (ready to dispatch) approx.
kg
Connected rating kW
Customer fuse protection max. A
SbS-01-HM-
ECO-10
1
Wall version
380
600
210
21
4,5
1 x 25A
NH-00
SbS-03-HV-
ECO-10
3
Wall version
380
600
210
22
14
3 x 32A
NH-00
Enclosure features
Mains isolator switch, 3-pin, 25 A
Mains isolator switch, 3-pin, 32 A
Mains isolator switch, 3-pin, 63 A
Line protection switch, S 2A
Transformer 230/24 VAC
Combination of RCD / Circuit breaker,
C 20A, 30 mA, 4-pin with auxiliary switch
Power contactor 3 x 35°
Auxiliary contactor
`Operating‘ indicator
`Fault‘ indicator
HWAT-ECO Control
Programmable logic module
* 2-pin unit unit unit unit unit unit unit unit unit unit unit unit
1
1
–
1
1
1
1
1
1
1*
1
1
1
–
1
2
1
1
1
1
1
1
1
1
2
2
2
1
2
1
1
SbS-06-HV-
ECO-10
6
Wall version
600
600
210
32
28
3 x 40A
NH-00
SbS-09-HV-
ECO-10
9
Wall version
600
600
210
33
42
3 x 63A
NH-00
1
1
1
3
2
3
1
1
3
12
THERMAL buiLding SOLuTiOnS
85
HWAT-ECO TEMPERATuRE COnTROL uniT
MOduLE LAyOuT
A B C D E
TECHniCAL dATA
85
165
70
(Dimensions in mm)
A Power supply on (green LED)
b Power to heater on (green LED)
C Legionella prevention (green LED) - heating cable 100% powered -
increased risk of scalding
d Maintain temperature lowered following boiler temperature decrease
(green LED) - boiler temperature is lower than expected.
E Error (red LED)
Change menu selection or position cursor
Escape, backspace or NO
Confirm selection, new value or YES
Product description use
Selectable maintain temperature
Operating voltage
Switching capacity
Internal power consumption
Circuit breaker
Power cable section entry
Auxiliary cable section entry
Weight
Mounting options
Cable glands (entries)
Protection level
Ambient temperature
Housing material
Internal temperature alarm
Master/slave cable
Master/Slave
BMS interface
Alarm relay contacts
Boiler tem per a ture sensor
Power correction factor
Clock back-up time
Clock accuracy
Real time clock
Parameters stored in non-volatile
Approval
EMC
HWAT-ECO
Only for HWAT-L/M/R heating cables
37°C to 65°C in max. 48 timer blocs per day
230 VAC (+10%, –10%), 50 Hz
20 A / AC 230V
2,5 VA
Max. 20 A, C-Characteristic
1.5 - 4 mm
2
for fixed wiring only up to 16 AWG (1.3 mm
2
)
880 g
Wall mount with 2 screws or DIN rail
2 x M20 and 1 x PG13.5 with 3 inputs for external wires of 3-5 mm
IP 54
0°C to 40°C
ABS
85°C
2-wire twisted pair shielded, max.
1.3 mm
2
core and insulation of 500 V
Master is selectable in the unit, up to 8 slaves can be con nect ed
0 - 10 VDC
Max. 24VDC or 24 VAC, 1 A, SPDT voltage free
PTC KTY 81-210 or PT 100 2-wire
60% to 140%
(fine tuning of maintained temperature)
Min. 1 year with lithium battery
CR2025 (3V)
±10 minutes per year
Automatic summer/winter time and leap year correction
All parameters, except date and time memory
VDE according to EN 60730
According to EN 50081-1/2 for emission and EN 50082-1/2 for immunity
Technical handbook
13
Raychem requires the use of a 30 mA residual current device and a C-Characteristic circuit breaker to provide maximum safety and protection from fire.
The unit complies with IEC1000-3-3 (flicker) if installed according to part 3 of VDE 0838. To avoid flicker install the unit in such a way that at the current value of the systems start-up temperature (max. 20 A per heating circuit) the voltage drop does not exceed 1% at the power supply of the lighting apparatus (normally subpanel).
PROgRAMME
The HWAT-ECO has 7 different building specific time/temperature programmes.
These programmes are based on our long experience for optimum comfort and energy saving. For user specific changes in the programming, the Edit timer programme can be used.
Programme name
Programme 0
Programme 1
Programme 2
Programme 3
Programme 4
Programme 5
Programme 6
building type
Constant temperature (±55°C)
Apartment block
Prison / Barracks
Hospital
Hotel
Sports centre / Swimming pool
Office
in addition, user specific programmes can be created
Temperature can be varied in 1/2 h blocks to any desired temperature between:
OFF, economy t°, maintain t° and legionella prevention (100% powered, increased risk of scalding)
14
THERMAL buiLding SOLuTiOnS
WiRing diAgRAM fOR HWAT-L / HWAT-M / HWAT-R
WiTH HWAT-ECO TEMPERATuRE COnTROL uniT
L1
L2
L3
N
*
** cable type RS-485,
2-pole contact ****
***
Optional BMS
+
PE
Alarm
L N
HWAT-ECO
L’ N’
B A
TEMP
PE
BMS
+
L N
HWAT-ECO
B A
TEMP
L’ N’ PE
Alarm
BMS
+
L N
HWAT-ECO
L’ N’
B A
TEMP
PE
Alarm
Self-regulating heating cable
Temperature sensor
Self-regulating heating cable
Self-regulating heating cable
* Two- or four-pole electrical protection by circuit breaker may be needed for local circumstances, standards and regulations
** Depending on the application, one- or three-pole circuit-breakers or contactors may be used
*** Optional: Potential-free circuit-breaker for connection to the BMS
**** The earth wire of shielded RS-485 cable needs to be connected to the
BMS (-) terminal of each HWAT-ECO in the Master / Slave network.
Technical handbook
15
0
A
THERMOSTAT HWAT-T55
TEMPERATuRE COnTROL WiTH (PiPE) LinE SEnSOR fOR HOT WATER bRAnCH LinES
And SMALL HOT WATER PiPE nETWORKS
diSPLAy
1
A LED display (parameter and error indications)
0 Control relay ON
1 Eco-Mode/night reduction activated
2 Programming/confirmation button
3 Reduce value
4 Increase value
4 3 2
TECHniCAL dATA
HOuSing
Abmessungen / Dimensions
30 (1.18)
46 (1.81)
58 (2.28)
HWAT T55 abnehmbar remo
Operating voltage
Power consumption
Control relay (heating)
Connecting terminals
Temperature setting range*
*consider local hygienic standard
Switching hysteresis
Accuracy
Storage temperature
Storage temperature
Programmable parameter settings
3 pre-set temperatures
Timer
Economy-mode/duration
Economy-mode/starting time
Error codes
Hot water-temperature -monitoring
AC 230V, +10%/-10%, 50 Hz
<= 5VA
230 VAC, max 16A
2,5 mm², screwed
40°C - 60°C; factory settings: 55°C
+/–2K
+/- 1,5 K including temperature probe
–20°C bis +55°C
–20°C bis +55°C
55°C ; 50°C, 45°C factory settings; editable
24 hour display, 1 min interval
3-8 hours interval per hour factory settings 6 hours
23:00 factory settings; editable
Sensor
Heating cable
Dimensions
Material
IP rating
Installation
Minimum installations temperature
- Temperature exceeds 66°C
- Temperature is too low (min 5K deviation
from maintain temperature)
- Sensor-short circuit
- Sensor-open loop / Sensor not connected
- Power output relay defective
- Heating cable not connected
51,5 mm x 87, 5mm x 58mm (B/H/T)
Housing ABS
IP 20 ( IP 30 in panel)
DIN 35 mm rail mounted
5°C
TEMPERATuRE SEnSOR
HWAT –T55- Sensor Type
Sensor length
Diameter sensor length
Diameter sensor probe
Length sensor
Temperature range
NTC 2K( 2 wires)
10 m
4 mm
5 mm
20 mm
0°C to +70°C
16
THERMAL buiLding SOLuTiOnS
COnnECTiOn SCHEME fOR THERMOSTAT HWAT-T55
10 11 12 13 14 15 16 17 18
L N
(AC 230V)
10 11
HWAT-T55
1 2 3 4 5 6 7 8 9
17 18
- +
Power supply
PE
1 2
K2
Alarm
K1
Heating cable
4 5 6 7 8 9
L
N
Max
C 16A
30 mA
2A
L
10 11
N (AC 230V)
Power supply K2
Alarm
K1
Heating cable
4 5 6 7 8 9
Thermostat HWAT-T55
Heating cable
Technical handbook
17
HOT WATER TEMPERATuRE MAINTENANCE
12 inSTALLATiOn inSTRuCTiOnS fOR HWAT-L/M/R CAbLES
• The heating cable should be installed in a straight line on the pipework.
• Install on dry surfaces
• Minimum installation temperature: –10°C max. 300 mm
Horizontal pipe
Cut the heating cable at right angles
90
°
Vertical pipe
Smallest bending radius: 10 mm
installation of self-regulating heating cables
• Store in a dry and clean place.
• Temperature range: –40°C to +60°C.
• Protect any cable ends with an end seal.
Avoid:
• sharp edges
• high tractive force
• kinking and crushing
• walking or driving over the cable
• moisture at cable interfaces ca. 45° ca. 45° horizontal pipes Cable tie KBL-10
For plastic pipes use aluminium adhesive tape
ATE-180. Place it over the entire length of the pipe
GT-66 / GS-54 adhesive tape
It is not necessary to spiral the cable around the pipe
Install the heating cables on the outside of the pipe bend
Wall/floor transit
The thickness of thermal insulation must be continuous otherwise compensate by adding heating cable.
18
THERMAL buiLding SOLuTiOnS
ca. 45° ca. 45°
• Run the cable over pipe suspensions
• Do not clamp the cable
Standard installation of PT100 Sensor with in-pipe sensor probe.
MASTER
HWAT
RayClic
PT100 sensor probe installed within the hot water supply pipe work.
≤ 3 m HWAT-L
≤ 3 m
L N
230V
RayClic-T-connection
IEK-20-M / IEK-25-04 for insertion of heating cable in metal cladding
≤ 3 m HWAT-M and HWAT-R
≤ 3 m insulation
> 3m + Rayclic
> 3 m
RayClic
Electric traced label
Technical handbook
19
FROST PROTECTION FOR PIPES
frozen pipes can be a costly problem. When pipes are exposed to sub-zero temperatures they can burst, leading to considerable damage and disruption. The Raychem frost protection system for pipes provides an efficient solution. The self-regulating heating cable, combined with an adequate insulation, prevents water pipes, fire mains, sprinkler systems and fuel oil lines from freezing.
EASy TO inSTALL
The heating cable is simply fixed onto the pipe – under the thermal insulation. Connections are quickly made with the fast RayClic connectors.
duRAbLE And RELiAbLE
The cable’s large copper conductors make it a reliable solution and its specially formulated outer jacket protects it from severe environmental conditions.
LOW POWER COnSuMPTiOn
The smart RAYSTAT -ECO control unit calculates a duty-cycle proportional to the expected minimum temperature.
Where a simple ambient thermostat would energize the heating cable for
100%, the “smart” controller would energize for a fraction of the time, resulting in significant extra savings.
6
4
3
2
5
1
7
8
Optional: SBS-xx-SV control panel contains: RCD (30 mA), Circuit breaker (CB) (C characteristics) space available in switch cabinet for installation of a thermostat.
1
2
3
4
Thermostat with line or ambient temperature sensor
Residual current device (30 mA)
Circuit-breaker (C type)
Junction box
(JB16-02)
T-Connection (RayClic-T-02)
(Not for FS-C-2X / FS-C10-2X)
5
6
7
8
Power connection (RayClic-CE-02)
(Not for FS-C-2X / FS-C10-2X)
Electrical traced label
(LAB-I-01)
Frost protection heating cable
(FS-A-2X, FS-B-2X, FS-C-2X or FS-C10-2X)
End seal (RayClic-E-02)
(Not for FS-C-2X / FS-C10-2X)
20
THERMAL buiLding SOLuTiOnS
dESign guidE, COnTROL uniTS And ACCESSORiES
1 HEATing CAbLE
SELECTiOn
Application frost protection for pipework at max. 65°C operating temperature
FS-A-2X 10 W/m at 5°C
FS-B-2X
FS-C-2X
26 W/m at 5°C
frost protection for pipework at max. 95°C operating temperature and temperature maintenance for metal waste pipes with fatty waste water
31 W/m at 5°C
22 W/m at 40°C
frost Protection for pipework to maximum 90°C operating temperature. for long circuit applications and central heating pipework.
FS-C10-2X 10 W/m at 5°C
TraceCalc.Net Construction is a software tool for product selection based on actual project data. Visit www.pentairthermal.com
2 COMPOSiTiOn Of THE fS-A/b/C/C10-2x HEATing CAbLE
1 2 3
4 5
1
Copper conductor (1.2 mm
2
)
2
Self-regulating heating element
3
Modified polyolefin insulation (FS-C-2X: Fluoropolymer)
4
Protective tinned copper braid
5
Modified polyolefin protective outer jacket.
Note: FS-C10-2X comprises copper conductors (1.4 mm
2
)
3 HEATing CAbLE LEngTH
frost protection down to –20°C.
Pipe diameter insulation
mm 15
thicknesses Inches 1/2”
10 mm fs-a-2X fs-C10-2X
22
3/4”
28
1”
35
5/4”
42
11/2” fs-
B
-2X fs-
B
-2X fs-
B
-2X fs-
B
-2X
54
2”
67
21/2” fs-
B
-2X fs-
B
-2X
76
3”
108
4”
125
5”
150
6”
200
8”
15 mm
20 mm
25 mm
30 mm
40 mm fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-
B
-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-
B
-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fsfs-
B
B
-2X
-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fsfsfs-
B
B
B
-2X
-2X
-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fsfsfsfs-
B
B
B
B
-2X
-2X
-2X
-2X fs-a-2X fs-C10-2X fsfsfsfsfs-
B
B
B
B
B
-2X
-2X
-2X
-2X
-2X fsfsfsfs-
B
B
B
B
-2X
-2X fs-
-2X fs-
-2X fs-
B
B
B
-2X
-2X fs-
-2X fs-
B
B
-2X
-2X
50 mm fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-a-2X fs-C10-2X fs-
a
-2X fs-C10-2X fs-
B
-2X fs-
B
-2X fs-
B
-2X
Frost protection cables FS-A-2X, FS-B-2X and FS-C10-2X are suitable for any pipe material (copper, threaded pipes, stainless steel pipes, plastic pipes and composite metal pipes without restriction).
For plastic pipes, please use aluminium adhesive tape ATE-180. The frost protection cable should be covered along its entire length. Heat insulation l = 0.035 W/(m.K) or better.
important note: frost protection heating cables with fluorpolymer protective jacket must be used for solvent-containing, mixed and/or bitumen-coated heat insulation.
Technical handbook
21
40°C temperature maintenance on pipelines for fatty waste water
Pipe diameter (mm) insulation thicknesses
42
11/2”
54
2”
67
21/2”
30 mm
40 mm fs-C-2X fs-C-2X fs-C-2X fs-C-2X
50 mm
60 mm
76
3”
108
4”
125
5”
150
6”
200
8” fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X fs-C-2X
Min. ambient temperature –10°C. Heat insulation l = 0.035 W/(m.K) or better.
Cable type FS-C-2X should only be used in conjunction with pipework with a minimum continuous temperature resistance of 90°C. A line-sensing control thermostat (type AT-TS-14, RAYSTAT-CONTROL-10 or
RAYSTAT-CONTROL-11-DIN) must be used on plastic pipework
(setting approx. 40°C).
4 CAbLE LEngTH
The heating cable should be installed in a straight line on the pipework.
Cable loops instead of T-connections can be made on short dead legs.
(up to approx. 3 m)
+ approx. 0.3 m per connection
+ approx. 1.0 m per T-connection
+ approx. 1.2 m per 4-way connection
Additional cable required for increased heat sinks at valves from 2” and for uninsulated pipe supports (approx. 1 m)
= required heating cable length
5 ELECTRiCAL PROTECTiOn
• The total length of heating cable determines the number and size of the fuses
• Residual current device (rcd) : 30 mA required, max. 500 m heating cable per rcd
• Installation according to local regulations
• The power connections must be carried out by an approved electrical installer
• use C type circuit-breakers
Max. length of the heating circuit is based on a minimum switch-on temperature of 0°C, 230 VAC.
4 A
6 A
10 A
13 A
16 A
20 A
fS-A-2x
45 m
70 m
110 m
130 m
150 m
–
fS-b-2x
25 m
35 m
65 m
85 m
105 m
–
fS-C-2x
20 m
30 m
55 m
70 m
90 m
–
fS-C10-2x
45 m
70 m
110 m
130 m
150 m
180 m
note: A splice can also be made using an S-06
6 TESTing Of THE inSTALLATiOn
See page 64
7 COnTROL PAnELS
Steel plate housing, wall-mounted version, equipped with mains isolator,
RCD/CB combination(s), power contactor(s), indicators for‚ `Operation and Fault‘, operating mode selector switch, inlet and outlet terminals. Completely assembled, turnkey condition, wired and inspected. wiring schematics in panel housing
An installation slot is provided for a RAYSTAT-CONTROL-11-DIN,
RAYSTAT-CONTROL-10 and/or RAYSTAT-ECO-10 thermostat, each serving
3 heating circuits. Factory fitted. Please contact us for more information.
Technical data: See page 29
22
THERMAL buiLding SOLuTiOnS
SbS-03-SV
SbS-06-SV
SbS-09-SV
SbS-12-SV for sprinkler systems
SbS-02-SnR
SbS-04-SnR
SbS-06-SnR
SbS-08-SnR
SbS-10-SnR
SbS-12-SnR
8 THERMOSTATS
AT-TS-13
AT-TS-14
A T -T
S - 1
3
3 0
0
6 0
C °
9 0
1 2 0
A T -T
S - 1
4
3 0 6 0
0
C °
9 0
1 2 0
Switch cabinet for 1 to 3 heating circuits.
• PCN: 355825-000
Control Panel for 4 to 6 heating circuits.
• PCN: 778308-000
Control Panel for 7 to 9 heating circuits.
• PCN: 767989-000
Control panel for 10 to 12 heating circuits.
• PCN: 1244-000025
Steel plate housing, wall-mounted version, equipped with mains power switch, low-voltage (LV) relay, RCD/CB combination(s), buzzer, power contactor(s), auxiliary contactor(s), operating mode selector switch, Indicators for `Operating and Fault‘, `Mains power‘, inlet and outlet terminals. Completely assembled, wired and inspected. Wiring schematics included in housing 1 temperature controller is installed per heating circuit in the switch cabinet.
Control panel for 2 heating circuits
(Inc. redundant).
Control panel for 4 heating circuits
(Inc. redundant).
Control panel for 6 heating circuits
(Inc. redundant).
Control Panel for 8 heating circuits
(Inc. redundant).
Control panel for 10 heating circuits
(Inc. redundant).
Control panel for 12 heating circuits
(Inc. redundant).
Thermostat
• Adjustable temperature range: –5°C to +15°C
• Line-sensing control thermostat or ambient thermostat
• Max. switching current 16 A, 250 VAC
Technical data: see page 30
Thermostat
• Adjustable temperature range: 0°C to 120°C
• Temperature maintenance on pipelines for fatty waste water
• Line-sensing control thermostat
• Max. switching current 16 A, 250 VAC
Technical data: see page 30
Technical handbook
23
RAySTAT-ECO-10
RAySTAT-COnTROL-10
Ambient temperature thermostat
• Adjustable temperature range: 0°C to 30°C
• Max. switching current 25 A, 250 VAC
• PASC (Proportional Ambient Sensing Control) for energy saving
• Alarm relay: 2 A voltfree with indication of sensor errors, voltage errors and low or high temperature alarm
• Display for visual indication of parameters
Technical data: see page 32
Line-sensing thermostat
• Adjustable temperature range: 0°C to 150°C
• Max. switching current 25 A, 250 VAC
• Alarm relay: 2 A voltfree with indication of sensor errors, voltage errors and low or high temperature alarm
• Display for visual indication of parameters
Technical data: see page 34
RAySTAT-COnTROL-11-din
Line sensing thermostat with digital display for DIN rail mounting applications.
• Set temperature range: 0 - 65°C.
• Digital display of maintain temperature and alarm information.
16A switching.
• Low temperature alarm function
• DIN rail/Panel mountable control.
• Sensor type: PT100.
Technical data: see page 36
Sb-100
Stainless steel support bracket
• Specially constructed to provide heating cable protection between pipe and junction box via a tubular leg.
• For use with AT-TS-13, AT-TS-14, JB16-02 and RAYSTAT-CONTROL-10
Sb-101
Dual-leg support bracket, stainless steel
• Height leg: 160 mm
• For use with AT-TS-13, AT-TS-14, JB16-02 and RAYSTAT-CONTROL-10
24
THERMAL buiLding SOLuTiOnS
Sb-110
Support bracket, stainless steel
• Height leg: 100 mm
• For use with AT-TS-13, AT-TS-14, and JB16-02
Sb-111
Support bracket, stainless steel
• Height leg: 100 mm
• For use with AT-TS-13, AT-TS-14, and JB16-02
9 ACCESSORiES fOR fS-A-2x And fS-b-2x CAbLES
Power connection
Splice
Powered splice
T-connection
Powered T-connection
Four way connection
note: A splice can also be made using an S-06 fS-A-2x / fS-b-2x
RayClic-CE-02
RayClic-S-02
RayClic-PS-02
RayClic-T-02
RayClic-PT-02
RayClic-X-02
RayClic-CE-02
Power connection
• With 1.5 m power cable
• End seal and support bracket
• IP 68
• External dimension: L = 240 mm
W = 64 mm
H = 47 mm
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
RayClic-T-02
T-connection
• Connection for 3 cables
• End seal and support bracket
• IP 68
• External dimension: L = 270 mm
W = 105 mm
H = 42 mm
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
RayClic-PT-02
Power T-connection
• 3 connections with integral 1.5 m power cable
• 3 end seals and 1 support bracket
• IP 68
• External dimension: L = 270 mm
W = 105 mm
H = 42 mm
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
Technical handbook
25
RayClic-S-02
RayClic-PS-02
Splice for joining 2 lengths of heating cable
• Connection for 2 cables with 1 support bracket
• IP 68
• External dimension: L = 240 mm
W = 64 mm
H = 47 mm
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
Powered splice
• Connection for 2 cables with integral 1.5 m power cable
• 2 end seals and 1 support bracket
• IP 68
• External dimension: L = 270 mm
W = 105 mm
H = 42 mm
RayClic-x-02
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
4-way connection
• Connection for 4 cables
• 2 end seals and 1 support bracket
• IP 68
• External dimension: L = 270 mm
W = 105 mm
H = 42 mm
RayClic-E-02
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
Gel-filled end seal
• For system extensions (to be ordered separately)
• IP 68
note: RayClic components are not compatible with fS-C-2x /fS-C10-2x
10 ACCESSORiES fOR fS-C-2x And fS-C10-2x CAbLES
Power connection
Splice
Powered splice
T-connection
Powered T-connection
Four way connection
Jb16-02
1 JB16-02 +
1 JB16-02 +
1 JB16-02
1 JB16-02
1 JB16-02
1 JB16-02 +
+
+
+
for fS-C-2x/fS-
C10-2x
1 CE20-01
2 CE20-01
2 CE20-01
3 CE20-01
3 CE20-01
4 CE20-01
Temperature-resistant junction box
• For FS-C-2X and FS-C10-2X
• For power connection or T-connection
• IP66
• 6 x 4 mm
2
terminals
• 4 Pg 11/16, 4 M20/25 knock-out entries
I P 6 6
6-02
+ JB-SB-08
+ JB-SB-08
+ JB-SB-08
+ JB-SB-08
+ JB-SB-08
+ JB-SB-08
26
THERMAL buiLding SOLuTiOnS
Jb-Sb-08
CE20-01
CCE-04-CT
Single-leg support bracket
• for junction and connection box JB16-02
Connection and end seal kit for FS-C-2X/FS-C10-2X cables
• Heat-shrink technique
• M20 gland
Cold lead connection and end seal kit
• Connection of 3 x 1.5 mm
2
or 3 x 2.5 mm
2
cold lead cable to self-regulating heating cables FS-C -2X and FS-C10-2X.
11 gEnERAL ACCESSORiES
S-06
In-line splice kit
• for FS-A-2X and FS-B-2X
S-19
In-line splice kit
• for FS-C-2X and FS-C10-2X
Technical handbook
27
CCE-03-CR
Cold lead connection and end seal kit
• Connection of 3 x 1.5 mm
2
or 3 x 2.5 mm
2
cold lead cable to self-regulating heating cables FS-A-2X and FS-B-2X
KbL-10 gT-66 gS-54
ATE-180
Cable ties
• One pack of 100 required for approx. 30 m of pipework
• Length: 370 mm
• Temperature and UV resistant
Use ATE-180 on plastic pipes
Heat-resistant glass cloth tape
• For steel pipes or for any installation below 4.4°C
• 20 m roll for approx. 20 m of pipework
Use ATE-180 on plastic pipes
Glass cloth tape for attaching heating cable to pipe
• For stainless-steel pipes or for any installation below 4.4°C
• 16 m per roll, 12 mm width
Aluminium adhesive tape
• Heat resistant
• 55 m roll for approx. 50 m of pipework
On plastic pipes: the heating cable must be covered with aluminium adhesive tape along its entire length
iEK-20-M
LAb-i-01
ELECTRIC
TRACED
R
Insulation entry kit
• Insertion of heating cable in metal cladding
• Consists of: metal fastener, metric gland and joint seal
Electric traced label
• To be placed at 5 m intervals on insulation surface
28
THERMAL buiLding SOLuTiOnS
12 gEnERAL inSTALLATiOn inSTRuCTiOnS
See page 67
13 SPECiAL inSTALLATiOn inSTRuCTiOnS
PLACing Of SEnSOR
Sensor
Junction box
Heating cable
Ambient sensor
Fasten the pipe sensor to the pipework (e.g. alu min i um adhesive tape) unheated premises
Outdoors
Always place the sensor in the coldest part of the installation
Cabinet type
Max. number of heating circuits
Enclosure version
Dimensions Width mm
SbS-03-SV
3
Wall version
SbS-06-SV
6
Wall version
SbS-09-SV
9
Wall version
Height mm
Depth mm
Weight approx.
kg
Connected rating
Customer fuse protection max.
kW
A
380
600
210
20
11
3 x 25A
NH-00
600
600
210
30
22
3 x 32A
NH-00
760
760
210
50
33
3 x 63A
NH-00
Switch cabinet equipment
Mains isolator switch, 3-pin, 25 A
Mains isolator switch, 3-pin, 32 A
Mains isolator switch, 3-pin, 63 A
Mains isolator switch, 3-pin, 100 A
Power isolator, S 2°
Combination of RCD/CB, C 16A,
30 mA, 4-pin, with auxiliary switch
Power contactor, 3 x 35A
Auxiliary contactor
Switch, 3 settings, 1-pin,
‚Manual-0-Automatic‘
Indicator ‚Operating‘ unit unit unit unit unit
unit unit unit
unit
1
1
1
1
1
1
1
2
1
2
1
2
1
3
1
3
1
3 unit 1 2 3
Indicator ‚Fault‘ unit 1 1 1
When using standard control panels for frost protection additional control devices need to be installed.
Factory fitting is possible. Please contact the person responsible at Pentair.
SbS-12-SV
12
Wall version
760
760
210
52
42
3 x 80A
NH-00
4
1
4
1
1
4
4
1
Technical handbook
29
LinE-SEnSing COnTROL And AMbiEnT THERMOSTATS
(AT-TS-13 And AT-TS-14) uniT LAyOuT
A
B
C
A Green LED
b Red LED
C Red LED
Heating cable on
Sensor break
Sensor short-circuit
R
TECHniCAL dATA
122 55
R
HOuSing
TEMPERATuR SEnSing
(HARd-69)
Supply voltage
Power consumption
Approval
Max. switching current
Max. conductor size
Switching differential
Switching accuracy
Switch type
Adjustable temperature range
230 VAC +10% –15% 50/60 Hz
≤ 1.8 VA
CE
16 A, 250 VAC
2.5 mm
2
0.6 to 1 K
AT-TS-13 ±1 K at 5°C (calibration point)
AT-TS-14 ±2 K at 60°C (calibration point)
SPST (normally open)
AT-TS-13 –5°C to +15°C
AT-TS-14 0°C to +120°C
Temperature setting
Exposure temperature
Ingress protection
Entries
Weight (without sensor)
Material
Lid fixing
Mounting inside
–20°C to +50°C
IP65 according to EN 60529
1 x M20 for supply cable (∅ 8-13 mm)
1 x M25 for connection heating cable
(∅ 11–17 mm)
1 x M16 for sensor approx. 440 g
ABS nickel-plated quick release screws
On wall or on support bracket
SB-110/SB-111
Type
Length sensor cable
Diameter sensor cable
Diameter sensor head
PTC KTY 83-110
3 m
5.5 mm
6.5 mm
Max. exposure temperature sensor cable 160°C
The sensor cable may be extended up to 100 m using a cable with a cross-section of 1.5 mm
2
.
The sensor cable should be shielded if it is laid in cable ducts or in the vicinity of high-voltage cables.
30
THERMAL buiLding SOLuTiOnS
WiRing diAgRAM fOR THERMOSTAT
AT-TS-13 OR AT-TS-14
AT-TS-13/14 diRECT
L1
N
A T -T
S - 1
3
3 0
6 0
0
C °
9 0
1 2 0
max.
16A/C
30 mA
*
3
5
1 2
6 8 9 4
Thermostat
AT-TS-13/14 WiTH COnTACTOR
L1
L2
L3
N max.
16A/C
30 mA
Self-regulating heating cable
Temp. Pt 100 sensor
* *
Thermostat
3
5
6
1 2
8 9
4
**
***
Self-regulating heating cable
Temp. Pt 100 sensor
* Two- or four-pole electrical pro-tection by circuit-breaker may be needed
for local circumstances, standards and regulations
** Depending on the application, one- or three-pole circuit-breakers or
contactors may be used
*** Optional: Potential-free circuit-breaker for connection to the BMS
Technical handbook
31
EnERgy SAVing fROST PROTECTiOn COnTROLLER
RAySTAT-ECO-10 diSPLAy
A
TECHniCAL dATA
HOuSing
- 1
- 2
- 3
- 4
TEMPERATuRE SEnSOR
A LED Display (parameter and error indications)
1 Battery activation
2 Parameter menu selection
3 Increase value
4 Decrease value
Operating Voltage
Power Consumption
Main Relay (heating)
Main Terminals
Alarm Relay
Alarm Terminals
Accuracy
Main parameter settings
Energy Saving Algorithm
230 VAC, +10%/–10%, 50/60 Hz
≤ 14 VA
I max
25 A, 250 VAC, SPST
3 x 0.75 mm
2
to 4 mm
2
I max
2 A, 250 VAC, SPDT, voltfree
(3 + ) x 0.75 mm
2
to 2.5 mm
2
±0.5 K at 5°C
Temperature Setpoint
Minimum Expected Ambient
Temperature
Heater Operation if Sensor Error
Voltage Free Operation
Proportional Ambient Sensing Control
(PASC) active below setpoint
0°C to + 30°C (switch off temperature)
–30°C to 0°C
(heating 10 powered)
ON (100%) or OFF
YES or NO
Energy saving with Proportional Ambient Sensing Control (PASC)
Duty cycle (power to heater on) depends on the ambient temperature. For example:
If minimum temperature= –20°C and if maintain temperature (set point)= +5°C
ambient t° % On
–20 100 Min. Ambient
–10
0
60
20
3 0 Set point
Result: At ambient temperature of –10°C, 50% energy is saved
–20 –10 0 3
% ON
100
80
60
40
20
10
0
Ambient temperature
% ON
diagnosed alarms
Sensor Errors
Low Temperature
Sensor short / Sensor open circuit
Min. expected ambient temperature reached
Voltage Errors Low supply voltage / Output voltage / fault
Parameters can be programmed without power supply and parameters are stored in non-volatile memory.
Size
Material
Exposure Temperature Range
Ingress Protection
Entries
Weight
Lid
Mounting
120 mm x 160 mm x 90 mm
Grey polycarbonate
–40°C to +80°C
IP 65
2 x M25, 1 x M20, 1 x M16
Approx. 800 g
Transparent with 4 captive screws
On wall or on support bracket
SB-100/SB-101
Sensor Type
Sensor Head
3-wire Pt100 according to IEC Class B
6 mm
Sensor cable can be extended up to 150 m when a cross-section of 3 x 1.5 mm
2
is used. The sensor cable should be shielded if it is laid in cable ducts or in the vicinity of high-voltage cables.
32
THERMAL buiLding SOLuTiOnS
WiRing diAgRAM fOR RAySTAT-ECO-10 nORMAL OPERATiOn
Heating cable
VOLTAgE fREE OPERATiOn: REMOVE LinKS W1 And W2
Temp. Pt 100 sensor
Temp. Pt 100 sensor
Heating cable
* Electrical protection by circuit breaker may be needed for local circumstances,
standards and regulations.
** Depending on the application, one or three-pole circuit breakers or contactors
may be used.
Technical handbook
33
LinE-SEnSing THERMOSTAT WiTH ALARM RELAy
RAySTAT-COnTROL-10 diSPLAy
A
- 1
- 2
- 3
- 4
A LED Display (parameter and error indications)
1 Battery activation
2 Parameter menu selection
3 Increase value
4 Decrease value
TECHniCAL dATA
HOuSing
TEMPERATuRE SEnSOR
Operating Voltage
Power Consumption
Main Relay (heating)
Main Terminals
Alarm Relay
Alarm Terminals
Accuracy
Ambient temperature
Parameter settings
230 VAC, +10%/–10%, 50/60 Hz
≤ 14 VA
I max
25 A, 250 VAC, SPST
3 x 0.75 mm
2
to 4 mm
2
I max
2 A, 250 VAC, SPDT, voltfree
(3 + ) x 0.75 mm
2
to 2.5 mm
2
±0.5 K at 5°C
–40°C to +40°C
Temperature Setting
Hysteresis
Low Temperature Alarm
0°C to +150°C
1 K to 5 K
–40°C to +148°C
High Temperature Alarm
Heater Operation if Sensor Error
Voltage Free Operation
diagnosed errors
Sensor Errors
Temperature Extremes
+2°C to +150°C or switched OFF
ON or OFF
YES or NO
Sensor short / Sensor open circuit
High temperature / Low temperature
Voltage Errors Low supply voltage / Output fault
Parameters can be programmed without power supply and parameters are stored in non-volatile memory.
Size
Material
Ingress Protection
Entries
Weight
Lid
Mounting
120 mm x 160 mm x 90 mm
Grey polycarbonate
IP 65
2 x M25, 1 x M20, 1 x M16
Approx. 800 g
Transparent with 4 captive screws
On wall or on support bracket
SB-100/SB-101
Sensor Type
Sensor Head
Sensor Cable Length
Cable Exposure Temperature
3-wire Pt100 according to
IEC / Class B
50 mm x ∅ 6 mm
3 m x ∅ 4 mm
–40°C to +150°C
(+215°C, 1000 h max.)
Sensor cable can be extended up to 150 m when a cross-section of 3 x 1.5 mm
2 is used. The sensor cable should be shielded if it is laid in cable ducts or in the vicinity of high-voltage cables.
34
THERMAL buiLding SOLuTiOnS
WiRing diAgRAM fOR RAySTAT-COnTROL-10 nORMAL OPERATiOn
Heating cable
Temp. Pt 100 sensor
VOLTAgE fREE OPERATiOn: REMOVE LinKS W1 And W2
L
N
1
Max.
C 25 A
30 mA
5 L L 8 N N
W1 W2
RAYSTAT-CONTROL-10
R R
A B C
alarm*
2A max.
Heating cable Temp. Pt 100 sensor
* Electrical protection by circuit breaker may be needed for local
circumstances, standards and regulations
** Depending on the application, one or three-pole circuit breakers or
contactors may be used
*** Optional
Technical handbook
35
RAySTAT-COnTROL-11-din LinE-SEnSing
THERMOSTAT fOR RACK MOunTing WiTH ALARM RELAy diSPLAy
1
A
LED display (parameter and error indications)
0 Control relay ON
1 Alarm relay activated
2 Programming button
3 Reduce value
4 Increase value
4 3
TECHniCAL dATA
2
HOuSing
TEMPERATuRE SEnSOR
Operating voltage
Power consumption
Control relay (heating)
Connecting terminals
Alarm relay
Accuracy
Operating temperature
Storage temperature
230 Vac, +10%/–10%, 50/60 Hz
≤5 VA
I max
16 A, AC 250 V, SPST
2.5 mm
2
screwed
I max
8 A, AC 250 V, SPDT, voltage-free
±1 K at 0 to 50°C
–10°C to +55°C
–20°C to +60°C
Programmable parameter settings
Temperature setting
Hysteresis
Low temperature alarm
Heater operation if sensor error
Voltage-free operation
0°C to +63°C
1 K to 5 K
–15°C to 0°C or „Off“ position.
ON or OFF
YES
Factory setting
5°C
1 K
0°C
ON
Diagnosed errors
Sensor error Sensor short-circuit / Sensor open-circuit /
3-wire sensor missing
Temperature error Low temperature
All parameters are stored in a non-volatile memory.
Dimensions
Material
Ingress protection
Mounting
51.5 mm x 87.5 mm x 58 mm (W x H x D)
Housing in ABS
IP 20 (IP 30 installed in switchgear cabinet)
DIN 35 mm rack mounting
Type
Sensor element
Pt 100 (3-wire technology) as per
IEC class B
50 mm x ∅ 6 mm stainless steel sheath
Protection rating
Sensor cable length
Ambient temperature
IP 68
3 m x ∅ 5 mm
–50°C to 105°C
The sensor can be extended with a 3-wire shielded cable with max. 7.5 Ω per wire
(with 3 x 1.5 mm
2
max. 150 m). The shielding should be earthed in the switchgear cabinet.
36
THERMAL buiLding SOLuTiOnS
WiRing diAgRAM fOR RAySTAT-COnTROL-11-din nORMAL OPERATiOn
Max
C 16A
30 mA
3-wire sensor
2A
L N (AC 230V)
10 11 16 17 18
Network mains
K2
Alarm
K1 heating cable
2-wire sensor
16 17 18
4 5 6 7 8 9
RAYSTAT-CONTROL-11-DIN
Heating cable
VOLTAgE-fREE OPERATiOn WiTH POWER COnTACTOR
Max.
C 16A
3-wire sensor
2A
L N (AC 230V)
10 11 16 17 18
Network mains
K2 alarm
K1 heating cable
4 5 6 7 8 9
2-wire sensor
16 17 18
Heating cable
* Regional factors, standards and regulations may require two to four-pole
disconnection by circuit breakers/ground fault circuit interrupters.
** Depending on the application, both single and multipole contactors are
possible.
Technical handbook
37
FROST PROTECTION FOR PIPES
12 inSTALLATiOn inSTRuCTiOnS fOR fS-A/b/C/C10-2x CAbLES
• The heating cable should be installed in a straight line on the pipework.
• Install on dry surfaces
• Minimum installation temperature: –10°C max. 300 mm
Horizontal pipe
Vertical pipe
Cut the heating cable at right angles
90
°
Smallest bending radius: 10 mm ca. 45° ca. 45° horizontal pipes Cable tie KBL-10
For plastic pipes use aluminium adhesive tape
ATE-180. Place it over the entire length of the pipe
GT-66 / GS-54 adhesive tape
It is not necessary to spiral the cable around the pipe
Install the heating cables on the outside of the pipe bend
installation of self-regulating heating cables
• Store in a dry and clean place.
• Temperature range: –40°C to +60°C.
• Protect any cable ends with an end seal.
Avoid:
• sharp edges
• high tractive force
• kinking and crushing
• walking or driving over the cable
• moisture at cable interfaces
38
THERMAL buiLding SOLuTiOnS
ca. 45° ca. 45°
Wall/floor transit
The thickness of thermal insulation must be continuous otherwise compensate by adding heating cable.
• Run the cable over pipe suspensions
• Do not clamp the cable
≤ 3 m
≤ 3 m
> 3m + Rayclic
> 3 m
RayClic
frost protection at valves:
• Valves up to 2” (DN 50) : install the frost protection heating cables in a straight line
• ≥ 2” : lay as shown
• Always insulate valves
RayClic-T-connection
IEK-20-M for insertion of heating cable in metal cladding
Electric traced label
Technical handbook
39
FROST PROTECTION FOR GuTTERS
AND DOWNPIPES
Melting and refreezing of ice can damage roofs and gutters. Heavy icicles may fall and cause injury. Standing water can leak through interior walls onto furnishings.
The Raychem self-regulating snow melting system maintains water flow in gutters and drain pipes and provides a path whereby melting ice and snow can drain safely off the roof, along the gutter and down the drain pipe.
PRACTiCAL TO inSTALL
The self-regulating cable can be closely spaced in gutters without the risk for overheating or burn-outs. There is a cable for each type of roof material.
ECOnOMiCAL TO OPERATE
The self-regulating effect saves energy by automatically increasing its heat output in icy water and decreasing its output in dry air. The smart EMDR-10 control unit only switches the heating cable on when necessary: after the detection of both low temperature and moisture.
4
2
6
1
7
5
3
Optional: SBS-xx.EV-10 control panel
Contains: Residual current device
(RCD 30 mA), Circuit Breaker
(C characteristics) EMDR-10 control unit
do not install RayClic immersed in water. do not bury RayClic in the ground.
8
40
THERMAL buiLding SOLuTiOnS
1
2
3
4
Ambient sensor
EMDR-10 (incl.)
Moisture sensor
EMDR-10 (Incl.)
Heating cable
GM-2X(T)
Fixing bracket
(GM-RAKE)
5
6
7
8
EMDR-10
Control unit
Connection
RayClic CE-02
Residual current device (rcd 30 mA)
Circuit-breaker (C type)
End seal
(RayClic-E-02)
dESign guidE, COnTROL uniTS And ACCESSORiES
1 HEATing CAbLE
SELECTiOn gM-2x, gM-2xT
Self-regulating heating cable for gutters, drain pipes and roof surfaces:
• 36 W/m in iced water and 18 W/m in air at 0°C
2 COMPOSiTiOn Of gM-2x And gM-2xT
1 2 3
4 5
1
Copper conductor (1.2 mm
2
)
2
Self-regulating heating element
3
Insulation made of modified polyolefin
4
Tinned copper braid
5
Protective jacket (uV-resistent) (Modified polyolefin jacket for GM-2X
and fluoropolymer jacket for GM-2XT)
important note: When laying cables on asphalt, bitumen, roofing felt, etc., a cable with a special fluoropolymer jacket (gM-2xT) must be used.
Technical data: see page 67
3 CAbLE LEngTH
• The heating cable should be installed in a straight line in the gutter
• The cable lengths should be adjusted according to the geographical situation and the gutters
• More than one cable should be laid in wide valley, parapet or box gutters
Gutter length
+ drainpipe length
+ 1 m per connection
+ 1 m in the soil (frost line)
= required heating cable length
4 ELECTRiCAL PROTECTiOn
• The length of heating cable determines the number and size of the circuit breakers
• Residual current device (rcd) : 30 mA required, max. 500 m heating cable per rcd
• Installation according to local regulations
• The power connections must be carried out by an approved electrical installer
• Use C type circuit-breakers
Max. length of the heating circuit is based on a minimum switch-on temperature of –10°C, 230 VAC.
gM-2x, gM-2xT
6A
10 A
13 A
16 A
20 A
25 m
40 m
50 m
60 m
80 m
5 TESTing Of THE inSTALLATiOn
See page 64
Technical handbook
41
6 COnTROL uniTS
EMdR-10
R
EMDR-10
PE P
E PE
1
AC 23
IP 20
0V 50
/60Hz
Alarm
: 10(4
)A, AC
)A, A 230V
V
–1
0 1 2
–20 –1
–25
C
5
3
6
4
5
2
–10
–5
5
4 5 6
1
10
0
6
15
7
8
20
T2A
Do not op en while
energized uvrir so nung sion en
8
9
10
11
Smart control unit
• With temperature and moisture sensor
• User-friendly control
• Saves up to 80% energy
• Max. switching capacity 10 A (otherwise switching by contactor)
• Potential free alarm for sensor break age, sensor short and power loss
Technical data: see page 48
HTS-d
3 0 •
2
• 0
• - 1
0
1 0
5
Standard thermostat
• 2 independant switching points
• Max. switching current: 16 A - 250 VAC
• Temperature adjustment range: –20°C to +25°C
• Outdoor installation
• Economical for circuit lengths up to 30 m
Technical data: see page 50
7 ACCESSORiES fOR gM-2x/gM-2xT
RayClic-CE-02
Power connection
• With 1.5 m power cable
• End seal and support bracket
• IP 68
• External dimension: L = 240 mm
W = 64 mm
H = 47 mm
RayClic-T-02
T-connection
• Connection for 3 cables
• 1 end seal and 1 support bracket
• IP 68
• External dimension: L = 270 mm
W = 105 mm
H = 42 mm
42
THERMAL buiLding SOLuTiOnS
RayClic-PT-02
RayClic-PS-02
RayClic-E-02
RayClic-Sb-02 gM-RAKE iceStop-gMK-RC
Power T-connection
• Connection for 3 cables with
integral 1.5 m power cable
• 3 end seals and 1 support bracket
• IP 68
• External dimension: L = 270 mm
W = 105 mm
H = 42mm
Powered splice
• Connection for 2 cables with integral 1.5 m power cable
• 2 end seals and 1 support bracket
• IP 68
• External dimension: L = 270 mm
W = 105 mm
H = 42 m
Gel-filled end seal
• For system extensions (to be ordered separately)
• IP 68
Wall-mounted support bracket
• Fixing bracket/edge protection for drainpipes
• Spacer for use in wide channels or gutters where more than one run of cable is required (a spacer is placed every 100 cm)
• VA steel with UV-resistant cable ties
Roof clip to secure heating cables to roofs and gutters.
Adhesive can be applied on the underside of the roof clip. After curing of the adhesive the heating cable can be clipped between the clamps.
Technical handbook
43
gM-CLiP-S gM-CLiP-L gM-CLiP-M gM-HAngAR
RAyCLiC-Sb-gM-METAL
Clip for quick and reliable fixing of heating cable GM-2X and GM-2XT on wide down pipe funnel.
• Material: Stainless steel EN 1.4310
• Wire: Ø 2,5 mm
• Height: 55 mm
• Gutter type: wide funnel with max.
Frame size of 10 mm
• Box content: 10 Clips/box
• PCN: 1244-013849
• Patent: 001357560-0003
Clip for quick and reliable fixing of heating cable GM-2X and GM-2XT on gutters with L-profile.
• Material: Stainless steel EN 1.4310
• Wire: Ø 2,5 mm
• Height: 150 mm
• Gutter type: gutters with L-Profile
140-150 mm height with max.
15 m frame size
• Box content: 10 Clips/box
• PCN: 1244-013851
• Patent: 001357560-0001
140-150 mm
1.0 meter
Clip for quick and reliable fixing of heating cable GM-2X and GM-2XT on half round gutters .
• Material: Stainless steel EN 1.4310
• Wire: Ø 2,5 mm
• Height: 100 mm
• Gutter type: gutters half-round;
Width: 100-150 mm
Depth: 65-80 mm
height with max. 17 m frame size
• Box content: 10 Clips/box
• PCN: 1244-013850
• Patent: 001357560-0002
100-150 mm
65-80 mm
1.0 meter
Structural support for wide roof inlet funnel for fast and easy installation of the heating cable GM-2X and GM-2XT.
• Material: Edelstahl EN 1.4301
• Wire: Ø 4,0 mm
• Hight: 225 mm
• Gutter type: wide funnel with max.
Frame size of 20 mm
• Suitable for: GM-2X, GM-2XT
• Content box: 5 pcs/box
• PCN: 1244-013852
Bracket for mounting on metal standing seam roofs
• Material: Feuerverzinkter Stahl
• Thickness: 2,0 mm
• Dimension: L 120 x B 130 x H 42 mm
• Gutter type: metal standing seam roofs
• Suitable for: RayClic-CE, -S, -T, -PT,
-PS and –X
• Box content: Unpacked; 1 pcs
• PCN: 1244-013853
44
THERMAL buiLding SOLuTiOnS
gM-SEAL-02
Adhesive for sticking and sealing common construction materials with a base of polyurethane perfectly suitable for metal or plastic gutters, roofing tiles and even asphalt and bitumen surfaces.
• 300 ml pack
CCE-03-CR
(for GM-2X only)
CCE-04-CT
(for GM-2XT only)
Cold lead connection and end seal kit
• Connection of 3 x 1.5 mm
2
or 3 x 2.5 mm
2
cold lead cable to self-regulating heating cable GM-2X
Cold lead connection and end seal kit
• Connection of 3 x 1.5 mm
2
or 3 x 2.5 mm
2
cold lead cable to self-regulating heating cables GM-2XT
8 gEnERAL inSTALLATiOn inSTRuCTiOnS
installation of self-regulating heating cables
•
Store in a dry and clean place.
•
Temperature range: –40°C to
+60°C.
•
Protect any cable ends with an end seal.
Avoid:
• sharp edges
• high tractive force
• kinking and crushing
• walking or driving over the cable
• moisture at cable interfaces
Technical handbook
45
9 COnTROL PAnEL
SbS-03-EV-10
SbS-06-EV-10
SbS-09-EV-10
SbS-12-EV-10
10 COnTROL uniT
EMdR-10
R
EMDR-10
PE P
E PE
1
AC 23
IP 20
0V 50
/60Hz
Alarm
: 10(4
: 2(1)A
)A, AC
, AC 2
30V
–1
0 1 2
–20 –1
–25
C
5
3
4
–10
–5
5
5
2
4 5 6
1
10
0
6
15
7
8
20
T2A
Do not op r Sp ir so
energiz us ten ed sion en
8
9
10
11
Steel plate housing, wall-mounted version, equipped with mains isolator, RCD/CB combination(s), indicators for `Operation and Fault‘, inlet and outlet terminals.
Completely assembled, wired and inspected. Cable guides in base of housing
An EMDR-10 control unit is installed in each switch cabinet.
Technical data: see page 48
Control panel up to 3 heating circuits
• PCN: 295014-000
Control panel up to 6 heating circuits
• PCN: 458484-000
Control panel up to 9 heating circuits
• PCN: 206336-000
Control panel up to 12 heating circuits
• PCN: 282458-000
• With temperature and humidity sensor
• Saves up to 80% energy
• Max. permitted switching current 10 A (otherwise switch via power contactor)
• Alarm relay contact for sensor break, sensor short circuit and power failure.
• PCN: 449554-000
Technical data: see page 48
HTS-d
3 0
2 0 • 1 0
• 0
•
0
2 5 2
0 1 5
1 0
5
Thermostat
• Two independently adjustable switching points
• Max. permitted switching current 16 A - AC 250 V
• Adjustment range –20°C to +25°C
• Assembly in external area
• PCN: C71431-007
Technical data: see page 50
46
THERMAL buiLding SOLuTiOnS
FROST PROTECTION FOR GuTTERS
AND DOWNPIPES
11 SPECiAL inSTALLATiOn inSTRuCTiOnS
box gutter < 200 mm
• One heating cable of GM-2X only
≥
200 mm
≥
200 mm
box gutter > 200 mm
• Multiple heating cables of GM-2X
• 2 pc spacer GM-RAKE per meter of gutter edges: GM-RAKE provides mechanical protection against damages
fastening of the gutter cables
On the roof, eaves bricks, gutter and drainpipe with GM-RAKE edge protection brackets (incl. cable ties).
do not install RayClic immersed in water.
do not bury RayClic in the ground.
in the drainpipe: always install the cable as far as the frost-free area
(approx. 1m deep)
Technical handbook
47
TEMPERATuRE And MOiSTuRE COnTROL uniT EMdR-10
TECHniCAL dATA
90
AC 230V 50/60Hz
IP 20
Relais: 10(4)A, AC 230V
Alarm: 2(1)A, AC 230V
Do not open while energized
Nicht unter Spannung öffnen
Ne pas ouvrir sous tension
R
EMDR-10
–1
0 1
–2
–3
2
C
3
4
5
6
3
4 5
2
1
6
7
8
9
10
–20
–25
TEST
–15
–10
10
20 30 40
50
–5
C
0 60 min T2A IEC127–2/V
PE PE PE 1 2 3 4 5 6 7 8 9 10 11
106
58
53
(Dimensions in mm)
HOuSing
AMbiEnT TEMPERATuRE
SEnSOR (ViA-du-A10)
35 52 40
Supply voltage
Power consumption
Max. switching capacity
Temperature adjustment range
Lower limit temperature
Operating differential
Measuring accuracy
Moisture adjustment range
Post heating time adjustment range
Alarm relay
Moisture sensor (output)
Mounting
Low voltage directive
EMC
Terminals
Protection class
Ambient temperature range
Ingress protection
Housing material
Weight
Sensor type
Ingress protection
Terminals
Sensor cable
Exposure temperature
Mounting
230 VAC, ±10%, 50Hz max. 4 VA
Imax 10(4)A / 230 VAC, SPST, potential 230 VAC
–3°C to +6°C (factory setting +2°C) test, –25°C to –5°C
(factory setting adjustment range –15°C)
±0.5 K
±1.5 K
1 (max. sensibility) to 10 (min. sensibility)
(factory setting 5)
0 to 60 minutes (factory setting 60 minutes)
I max
2(1)A / 230 VAC, SPDT, potential-free
I max
315mA / 230 VAC, with fuse 5 x 20mm
T 315mA according to IEC127-2/V
DIN rail according to DIN EN 50022-35
EN 60730
EN 50081-1 (emission) and EN 50082-1
(immunity)
2.5 mm
2
(stranded conductors),
4 mm
2
(solid conductors)
II (panel mounted)
0°C to +50°C
IP20
Noryl (self-extinguishing according to uL
94 V-0) approx. 350 g
PTC (FL 103)
IP54
2.5 mm
2
2 x 1.5 mm
2
, max. 100 m (not included)
–30°C to +80°C
Wall mounting
PG9 (Dimensions in mm)
MOiSTuRE SEnSOR
(HARd-45)
4 m
650 activ e sensor length
500
Sensor type
Power consumption
Ambient temperature range
Supply voltage
Connection cable
PTC
9 W to 18 W
–30°C to +65°C continuous
230 VAC, ±10%, 50Hz
3 x 1.5 mm
2
, 4 m, the connection cable can be extended to max. 100 m at 3 x 1.5 mm
(Dimensions in mm)
48
THERMAL buiLding SOLuTiOnS
WiRing diAgRAM fOR EMdR-10
EMdR-10 WiTHOuT COnTACTOR
L
N
PE
R
EMDR-10
PE P
E PE
1
AC 23
IP 20
0V 50
/60Hz
–2
–3
0 1 2
–25
2 T
3
C
5
–10
4
6
5
3
2
4 5 6
5
10
–5
5
0
6
15
Relais
: 2(1 )A, AC
230V
C 230
V
8
10
20 min
25
T2A
IE
Ne pas o uvrir nung
öffn sion en
8
9
10
11
30mA
PE PE PE N N N L L LS T1 T2 Alarm
Heating cable
EMdR-10 WiTH COnTACTOR
L1
L2
L3
N
PE
PE PE PE N N N L L LS T1 T2 Alarm
* Two- or four-pole electrical protection by circuit breaker may be needed for local circumstances, standards and regulations
** Depending on the application, one or three-pole circuit breakers or contactors may be used
*** Potential-free alarm contacts for connection to the BMS
Technical handbook
49
THERMOSTAT HTS-d
TECHniCAL dATA
122 mm
110 mm
45 mm
29 mm
Temperature range
Operating voltage
Max. switch current
Max. exposure temperature
Switch temperature difference
Temperature setting
Protective system
–20°C to +25°C
AC 230 V, 50 Hz
16 A / AC 250 V
50°C
1 K - 3 K under the housing cover
IP 65
WiRing diAgRAM fOR HTS-d
HTS-d diRECT
3 0 •
2 0 • 1 0
• 0
•
- 1
0
1 0
5
Self-regulating heating cable
* Two- or four-pole electrical protection by circuit-breaker may be needed for local circumstances, standards and regulations
50
THERMAL buiLding SOLuTiOnS
COnTROL PAnEL
TECHniCAL dATA
Safety system for roof gutters
The standard control panels for 3, 6, 9 or 12 heating circuits comprise a steel plate housing and are completely assembled, in turnkey condition, wired and inspected.
Paintwork
Protection class
Structural paint, RAL 7035, light gray
IP54
Location
Ambient temperatures:
Cable inserts
Interior
+5°C to +35°C
Metal plate in base of housing with metric breakout apertures
Version
Mains power connection acc. to VDE 0660, Part 500 and VBG 4
3-phase to 400V/230V, 50 Hz, with N and PE
Cabinet type
Max. number of heating circuits
Enclosure version
Dimensions Width mm
Height mm
Weight approx.
Connected rating
Depth mm kg kW
A Fuse protection provided max. by customer
Switch cabinet equipment
Mains isolator switch, 3-pin, 32 A unit
Mains isolator switch, 3-pin, 63 A unit
Mains isolator switch, 3-pin, 100 A unit
Power isolator, S 2° unit unit Combination of RCD/CB, C 20A,
30 mA, 4-pin with auxiliary switch
Power contactor, 3 x 35°
Auxiliary contactor
Indicator‘Operating‘ unit unit unit
SbS-03-EV-10 SbS-06-EV-10 SbS-09-EV-10 SbS-12-EV-10
3
Wall version
380
600
6
Wall version
380
600
9
Wall version
600
600
12
Wall version
760
760
210
20
14
3 x 32A
NH-00
210
30
28
3 x 40A
NH-00
210
32
42
3 x 63A
NH-00
210
52
56
3 x 80A
NH-00
1
1
1
1
1
1
1
2
1
2
1
2
1
3
1
3
1
3
4
1
4
1
1
4
Indicator ‘Fault‘
EMDR-10 control unit unit unit
1
1
1
1
1
1
1
1
Technical handbook
51
SNOW MELTING FOR RAMPS, ACCESS WAYS,
AND FOOTPATHS
ice and snow on paths, loading bays, driveways, ramps, stairs and other access ways, can present a major problem causing accidents and delays. Raychem a ground heating solutions prevent snow and ice formation.
APPLiCATiOn in COnCRETE
The Raychem range of products has been specifically designed to meet the requirements of commercial, industrial, and residential applications.
Whether in concrete, sand, or asphalt, a Raychem system exists to provide a fast, reliable, and easy install solution.
Each Raychem heating solution is complete with a Smart control and monitoring unit, providing useful user data and excellent energy efficient performance. The multi-sensor control and monitoring device (VIA-Du-20) is compatible with all ramp snow melting solutions.
2
6
3
4
1
5
7
6
Optional: SBS-xx-VV-20/SBS-xx-CW-40/
SBS-xx-CM-20
Contains: Control panel with RCD (30 mA),
Circuit Breaker (C characteristics), mains contactor VIA-Du 20 control unit
1
2
Ambient temperature sensor*
VIA-Du-A10 (incl.)
Temperature and moisture sensor
VIA-Du-S20
5
6
Control unit
(VIA-Du-20)
Connection and end seal kit
(VIA-CE1)
3
4
Connection and end seal kit
(VIA-CE1)
7
Self-regulating heating cable
(EM2-XR) or constant power heating cable
(EM4-CW)
Connection cable
(VIA-L1)
* Optional, only needed when “local detection” is selected.
RAyCHEM SOLuTiOnS fOR COnCRETE
Product
EM2-XR Reinforced concrete surfaces
Domestic and light commercial ground heating applications.
EM2-CM
Stairs; wheelchair access ramps EM4-CW
description
Self-Regulating heating cable for reinforced concrete ramps
Pre-terminated constant wattage heating mat for ramp, pavement and track heating
400V Pre-terminated constant wattage heating cable solution for larger concrete areas and stairs
52
THERMAL buiLding SOLuTiOnS
APPLiCATiOn in ASPHALT
1
2
3
4
6
5
Optional: SBS-xx-MV-20
Contains: control panel with RCD (30 mA), circuit breaker (C characteristics) Mains contactor for VIA-Du-20 control unit
1
2
3
Ambient temperature sensor*
VIA-Du-A10 (incl.)
Temperature and moisture sensor
VIA-Du-S20
Connection between heater cable and cold lead (Pre-engineered)
4
5
6
Pre-engineered cold lead
Mineral-Insulated heating cable
(EM2-MI)
Control unit
(VIA-Du-20)
* Optional, only needed when “local detection” is selected.
RAyCHEM SOLuTiOnS fOR inSTALLATiOn diRECTLy bELOW HOT-POuREd ASPHALT
Installation in hot asphalt
Product
EM2-MI
description
Mineral insulated, high temperature resistant heating cable for asphalt ramps
For more information on snow melting products, please refer to document CDE-1540.
Technical handbook
53
SySTEM OVERViEW
Product features & Selection guide:
Product features EM2-xR EM2-Mi EM2-CM EM4-CW
Product Description
Features
Voltage Rating
Nominal power output
Maximum circuit length
Maximum exposure temperature
Connections & termination
Cut-to-length system for flexible field termination (using
Raychem heat-shrink components).
Pre-terminated cable lengths (fixed or configured) available.
Contact us.
VIA-Du-20 Compatible control unit
Approvals VDE / CE
Suitable for installation on reinforcement bar
★★★
Highly recommended
Suitable for installation in direct contact with hot poured asphalt
Suitable for embedding in sand sub-level
Cold lead included
Dual Wire / Single
Wire construction
Self-regulating heating cable
Extremely robust self-regulating heating cable for flexible installation under severe site conditions
230 Vac
90 W/m @ 0°C
85 m
100°C
★★
Recommended
Not as standard.
Contact Pentair for information on
Configured EM2-XR heating elements.
Dual
Mineral Insulated constant power heating cable
Pre-terminated heating cable with exceptional resistance to high temperature asphalt surfaces
230 Vac
50 W/m
136 m
250°C
Pre-terminated ramp, walkway, and track heating (Roll-out) mat for fast and simple installation
230 Vac
300 W/m
12.6 m
4 m
2
2
(Mat size =
21 m x 0,60 m)
65°C
400 Vac
25 W/m
250 m
65°C
Factory pre-terminated Factory pre-terminated Factory pre-terminated
VIA-Du-20
VDE / CE
★★
Recommended
★★★
Highly recommended
★★
Recommended
3 m (at each end of heater cable)
Single
Constant power polymeric pre-terminated ramp heating mat system
VIA-Du-20
VDE / CE
★★★
Highly recommended
Dual
Constant power polymeric pre-terminated heating cable system
Pre-terminated constant power heating cable for larger areas
& 400 V power supplies
VIA-Du-20
VDE / CE
★★
Recommended
★★★
Highly recommended
4 m
Dual
54
THERMAL buiLding SOLuTiOnS
ELECTRICAL uNDERFLOOR HEATING
Comfort is everything, especially in the home. With Raychem’s smart electrical underfloor heating, you can offer a beautiful warm floor; hassle free to your customers!
5 gOOd REASOnS TO
CHOOSE RAyCHEM SMART undERfLOOR HEATing
1 Comfortable and safe
2 Hassle free installation and maintenance free
3 Energy-efficient and cost saving
4 Can be installed under all floor coverings
5 Total care warranty
THE RAyCHEM undERfLOOR HEATing RAngE COMPRiSES:
• T2Red: The innovative and unique self- regulating floor heating cable.
• T2Red with T2Reflecta: The energy-saving underfloor heating system.
This system combines the self-regulating heating cable T2Red with T2Reflecta, the grooved, thermally insulated, aluminium-covered plate.
• T2QuickNet: The ultra thin heating mat (two power options available).
• T2Blue: The robust, flexible, pre-terminated (dual wire, and screened) cable system.
• T2Green: the low output heating cable designed specially for very well insulated and near zero energy houses.
• CeraPro: The ultra thin, robust, under tile heating cable solution with
“Tape & Mesh” fixing accessories included.
• “Smart” thermostats which offer zoned, programmable heating control, a requirement of Part L of the building regulations.
• A complete range of installation accessories and components including:
– Floor primers
– Adhesives
– Fixing accessories
Technical handbook
55
SMART SERViCES fOR dESign And SPECifiCATiOn
Pentair offers a comprehensive design and specification service for consultants and architects, free of charge.
using bespoke floor heating design software, we provide:
• Optimised installation plans for the designer and installer in 2 & 3 dimensional views.
• Zone by zone product data including heat output per room and per m
2
in the room.
• Detailed bill of materials, optimised by the software to minimise waste.
With a design proposal complete, we provide specification support to ensure quality procurement.
OnLinE SuPPORT
Design and specification tools are available at:
www.pentairthermal.com
• Product selection guide
• A “We design it for you” e-request service.
LOCAL ExPERT TEAM SuPPORT
The Raychem systems and services are supported by a dedicated specifications team. We can provide sound design advice specific to your project needs.
We are also available to:
• Support consultants and architects at early design/concept stage and
provide floor heating options.
• Visit the project site to survey the requirements and make recommendations for the consultant, client, and contractor.
• Provide contact details of local suppliers and installers of Raychem floor heating systems.
SAfETy And RELiAbiLiTy
12
Total care
warranty
15
Total care
warranty
12 15 20
Total care
warranty
Quality products - installed and checked by a professional electrician - assure home owners the comfort of a warm floor with Total Care. When installing
Raychem floor heating systems, electricians can now offer a 12 Year Total Care
Warranty to their customers.
Total care
warranty
Total care
warranty
product would fail and we cannot repair it, we will not only provide you with a new
20
Total care
warranty
product and pay the costs of installing it. We will also take care that the floor covering is repaired or replaced to the equivalent standard.
* For more information: ask for the Floorheating handbook or go to
www.pentairthermal.com
56
THERMAL buiLding SOLuTiOnS
ELECTRICAL uNDERFLOOR HEATING
T2REd: THE SELf-
REguLATing HEATing
CAbLE
Senses other sources of heat and adjusts its heat output accordingly.
• Makes wet floors dry faster.
• No risk of overheating.
• Can be installed on all sub floors (plastic, concrete, wood, carpets) - in dry or wet areas.
• Can be adapted to all room sizes.
Adhesiv
Tiles
T2Red c
Le abl e e velling c
Wat er barrier
Subfl
Subfl oor oor
Primer e underlay
Laminat
W ood fl e oor e
Wood
Adhesiv oor
Scr eed e e
Expansion
joint
T2Red c abl e
Met
Foil
Insulation
Subfl oor
T2REd WiTH T2REfLECTA:
THE EnERgy-EffiCiEnT
SOLuTiOn
• The T2Reflecta system combines the self-regulating T2Red heating cable with the pre-grooved T2Reflecta; a thermally insulated, aluminium-covered plate.
• Provides extra energy savings of 20% or more
• Can be adapted to all room sizes and be installed on most sub floors.
• First choice for wooden or laminate floors in dry areas.
• Automatically adjusts its heat output dependent on ambient floor temperature. e or w ood
Laminat
Wood fl able oor underlay ect a Plat
T2Red heating c
T2Refl es
Lev elling c ompound
Subfl oor
Expansion
joint
Technical handbook
57
T2quiCKnET: THE idEAL
SOLuTiOn fOR REnOVATiOn
• The thin T2QuickNet mat is the ideal solution for renovation especially for tile floors. The ultra-thin (3 mm) mat is laid directly in the filler.
• It can be installed on all sub floors which are sufficiently insulated and conforming to applicable building regulations.
• T2QuickNet exists in two versions: a very popular 90 W/m
2
version and a
160 W/m
2
version when more output is required.
Topfl oor
Tile adhesiv e
Primer
Expansion joint
T2QuickNet
Subfl oor
T2quiCKnET + iSOLECTA inSuLATiOn bOARd
Ideal for renovation projects:
• Extra insulation layer
• Fast heat up: Reducing heat up time by additional insulation layer underneath of T2QuickNet
• Energy savings up to 65% during heat up and 20% in steady state conditions
Tiles
Tile adhesiv e
Expansion joint
T2QuickNet
Isol ect a 10 mm
Subfl oor
58
THERMAL buiLding SOLuTiOnS
T2bLuE: THE fLExibLE undERfLOOR HEATing
CAbLE
• The flexible underfloor heating cable is suitable for installation directly in a levelling compound, screed, or concrete.
• Heating cable with pre-fabricated power connection cable
• Ideal for complex floor layouts.
• Power output flexibility by varying the distance between heating cables.
• Suitable for laying in milled grooves in the screed/concrete without increasing the total height of the floor structure
Adhesiv e
Expansion joint
Tiles
Wat erpr
Lev
Primer ane (optional) abl e
T2Blue heating c
Subfl oor
Expansion joint
Til es e abl e
Til e adhesiv ompound
Le veling c
T2Blue heating c
Met
Foil
Insulation type
Subfl oor
Technical handbook
59
CERAPRO + iSOLECTA:
THE RObuST, undER TiLE
HEATing CAbLE SOLuTiOn
• The ultra thin, robust heating cable can be installed directly in the tile adhesive without the need for additional screeding over the heater.
• The high grade Fluoropolymer material give high resistance to mechanical damage during installation when compared with market alternatives.
• It can be installed on both wooden and concrete subfloors (maximum installed output of 100 W/m
2
on wooden subfloors.)
• The heater spacing can be adjusted to allow for typical outputs between
100 and 150 W/m
2
.
• The 8 kit sizes are supplied complete with “Tape ‘n’ Mesh” installation products and an easy to use cable spacing guide.
• Isolecta insulation layer
Til e
adhesiv e
Mesh
Doubl e sided t ape
Tiles
Cer aPr
Isol ect abl e
Expansion
joint
Subfl oor
60
THERMAL buiLding SOLuTiOnS
RAYCHEM FLOOR HEATING THERMOSTATS
NRG-DM
3 working modes
• Constant Mode
• Event Mode
• Boost Mode
3 Sets of settings
• Event setting (programming of the weekly schedule)
• user settings (settings that helps users customizing their thermostat)
• Engineer settings (expert settings that help installers fine tune to specific needs)
SOFTWARE IN 11 LANGUAGES
2 SENSORS / 4 SENSING MODES
• Floor sensing
• Room Sensing
• Room sensing with floor limiter
• No sensor mode
GREEN LEAF ELEGANT PROGRAMMABLE THERMOSTAT
ELEGANT LARGE AND CLEAR DISPLAY
EASY NAVIGATION
3 operation modes
• Standard Comfort mode (1 temperature set point- manual on/off).
• Editable program (4 temperature and time periods per day).
• Holiday mode (standby).
CAPACITIVE TOUCH TECHNOLOGY
ONE GREEN LEAF BUTTON DOES IT ALL
NRG-TEMP ROBUST AND EASY TO INSTALL THERMOSTAT
• Backlid LCD display
• Heat-Booster function for fast heat up
• Design for long lasting
• Safety Easy to install
Technical handbook
61
MuLTIPLE APPLICATION CONTROL &
MONITORING SYSTEM
Raychem ACS-30 Multi-circuit, multi-application Control & Monitoring system for commercial heat tracing applications.
RAyCHEM ACS-30
The Raychem ACS-30 system provides electronic control & monitoring for multi-circuit heat tracing applications, including pipe frost protection, surface snow melting, hot water temperature maintenance, gutter & roof de-icing, temperature flow maintenance, and electrical underfloor heating.
The Raychem ACS-30 can control up to 260 heat tracing circuits of any application, from a single user interface, allowing building owners and facilities managers to monitor and manage their building’s heat tracing systems from a single point.
ACS-30 is a modular control & monitoring solution which can be designed to exactly meet the needs of the building. Power and control modules
(PCMs) can be positioned throughout the building in accordance with the building system requirements. Multiple
PCMs can be connected together providing a complete view of the buildings heat tracing systems.
ACS-30-Eu-uiT2
User Interface Terminal (UIT)
PCN: 1244-012864
• Panel mounted touchscreen display
• Control & Monitoring of 260 heating circuits
• 22 cm XGA colour touchscreen display.
• RS485, RS232, or 10/100 Base-T Ethernet communication ports to allow communication with external distributed control systems or building management systems (BMS).
• BACnet, Metasys N2 and LonWorks to Modbus protocol gateways with pre-programmed Modbus registration is also available.
• The ACS-30-EU-UIT2 unit is designed for indoor use in non-hazardous location installations
ACS-30-Eu-PCM2
(Power & Control Module)
6 Version available as standard:
• 5, 10, and 15 circuit control per panel
• 20A or 32A switching capacity per circuit available.
• Power connection, control, and power distribution to the heat tracing circuits.
• Robust enclosure is approved for non-hazardous installation indoor.
• PCM provides connection to the incoming power supply and power distribution
& electrical protection to the heat tracing circuits.
The PCM module also provides:
• Ground fault monitoring
• Line current monitoring
• Alarm capability
• RTD (Resistance Temperature Detector) input capability for each individual heating circuit.
62
THERMAL buiLding SOLuTiOnS
PCn Product name Product description
1244-012868 ACS-30-Eu-PCM2-5-20A Power Control Module for ACS-30
(5 circuit module with 20Amp electrical protection per circuit)
1244-012869 ACS-30-Eu-PCM2-10-20A Power Control Module for ACS-30
(10 circuit module with 20Amp electrical protection per circuit)
1244-012870 ACS-30-Eu-PCM2-15-20A Power Control Module for ACS-30
(15 circuit module with 20Amp electrical protection per circuit)
1244-012871 ACS-30-Eu-PCM2-5-32A Power Control Module for ACS-30
(5 circuit module with 32Amp electrical protection per circuit)
1244-012872 ACS-30-Eu-PCM2-10-32A Power Control Module for ACS-30
(10 circuit module with 32Amp electrical protection per circuit)
1244-012873 ACS-30-Eu-PCM2-15-32A Power Control Module for ACS-30
(15 circuit module with 32Amp electrical protection per circuit)
EAn Code
5414506014341
5414506014358
5414506014365
5414506014372
5414506014389
5414506014396
ACS-30-Eu-MOni-RMM2-E
ACS-30-Eu-EMdR-10-MOd
ACS-30-Eu-ViA-du-20-MOd
Protonode-RER-10K
PCN: 1244-012867
• Collects sensor/temperature inputs for monitoring of the heat tracing.
• 1 RMM provides up to 8 sensor inputs per module with feedback to the ACS-30-Eu-uIT2
• Maximum 16 RMM devices per User interface terminal (UIT).
• Twisted pair RS-485 cable connects up to 16 RMM units providing 128 additional temperature monitoring sensor inputs.
• Remotely located adjacent to the desired measurement locations.
• ACS-30-EU-MONI-RMM2-E module comes pre-installed inside a compact enclosure.
PCN: 1244-012865
• External Sensor device for Gutter snow melting & de-icing applications.
• Provides smart sensor input for roof & gutter de-icing applications.
• Temperature & moisture sensing input for the ACS-30 control system.
• Module can be positioned near to the heated area and is connected to the
PCM module via a 3-wire cable.
• 4 m external temperature and moisture sensor to be positioned at the heated surface. The sensor cold lead cable can be extended to a maximum length of
100 m (using 3 x 1.5 mm2 cable.)
• The output from the ACS-30-EU-EMDR-10 module enables the switching of the heating circuits within the power & control module (PCM).
PCN: 1244-012866
• External Sensor device for ground surface snow melting applications.
• Provides smart sensor input for surface snow melting and de-icing applications.
• The module provides ground temperature and moisture sensing for the
ACS-30 control system.
• Positioned near to the heated area and is connected to the PCM module via a 3-wire cable.
• Provided with a 15 m external ground temperature and moisture sensor to be positioned at the heated surface.
• The output from the ACS-30-EU- VIA-DU-20-MOD enables the switching of the heating circuits within the power & control module (PCM).
PCN: P000001983
The Raychem ProtoNode is an external, high performance multi-protocol gateway for customers needing protocol translation between Building
Management Systems (BMS) using BACnet® or Metasys® N2 and the Raychem ACS-30 or TTSIM controllers.
• The most flexible and versatile multi-protocol device server on the market.
• BACnet International’s BTL Certification makes the ProtoNode-RER the most reliable gateway on the market.
• Multi-client and multi-server support ensures interoperability between any Industrial and or Building Automation protocols.
• Flash upgradable.
Technical handbook
63
GENERAL INSTALLATION INSTRuCTIONS
CHECKLiST fOR PRObLEM-fREE inSTALLATiOn And SAfE OPERATiOn
Typical installation schedule for hot water temperature maintenance
general order of events
• The system is designed and the installation planned
• The pipework is pressure tested or otherwise checked for leaks
• The HWAT-L/M/R cable is tested and then installed on the designated pipes
• The components are installed and each circuit is tested
• The correct thermal insulation is applied, without delay, labelled and the system test repeated
• The supply voltage cables and circuit breakers are installed to each circuit
• The system is commissioned (see “System start-up” below)
Circuit protection, testing and operation for all systems
Circuit protection
• Supply voltage 230 VAC, 50 Hz
• The required protective measures of the relevant regulations must be complied with.
• C type circuit breaker (anti-surge fuse)
• Residual current device (rcd 30 mA) required. Maximum approx. 500 m of self-regulating heating cable can be monitored per rcd
Measurement A
Measurement B
Testing
• Visual inspection for damage and fault-free installation of the accessories
• Proper installation of the system
• Heating cable affixed to all necessary pipes
• No mechanical damage to heating cable (e.g. cuts, cracks, etc.)
• No thermal damage
• Proper connection of all components including power supplies
• Insulation resistance measurement when heating cable is received and before and after installation of the thermal insulation. The test voltage should be
2500 Vdc, but it must not be lower than 500 Vdc. The insulation resistance, irrespective of the cable length, must not be less than 100 Mohms.
If the resistance falls below this value, the source of the fault must be investigated, eliminated, and re-tested.
• Measurement A: Phase and neutral to the braid
• Measurement B: Braid to the pipework
• After switching on, the cable ends must be warm after 5 to 10 minutes
instructions for the placing of the heat insulation
• For problem-free operation of the self-regulating heating cables, the material quality and thickness of the thermal insulation should be in accordance with the design parameters, and this insulation must be installed correctly
• All parts of the pipework, including valves, wall transit points, etc. must be fully insulated
Operation/System start-up
• 1) For small installations, turn on the circuit breakers and preferably leave the system overnight for the water to warm up and stabilise
2) For bigger installations or for a faster start-up, first turn on the main water heater and open the outlet/tap at the end of the pipework run until the water feels warm and then turn on the circuit breakers
If the piping system is closed, such as by pressure-reducing valves or isolation valves, you must provide some method of pressure relief to allow for thermal expansion of the water during heat-up
• Under normal operating conditions, the heating cables are maintenance-free.
Pentair recommend that the insulation resistance should be checked periodically and compared with the original values. If the reading falls below the minimum value (100 Mohms) determine the cause and rectify before re-use
• The specified maximum ambient and operating temperatures should not be exceeded
• In the event of repair to the pipework, the heating cable must be protected against damage. Correct function of the electrical protection system should be maintained. To prevent shock or personal injury, turn off the power at the circuit breaker before testing or working on the heating cable or piping
64
THERMAL buiLding SOLuTiOnS
Standard installation times
• Following the completion of the repair work, the circuit should once again be tested (see above)
• All the important parts of the controls, thermostats, etc. must be checked for correct operation once a year, normally in the autumn
Only for hot water temperature maintenance
Newly installed heating cables have lower power at start-up of the installation.
The nominal power will be reached after approximately 4 weeks of continuous operation
• The maintenance temperature should be 5°C to 10°C below the hot water temperature in the boiler
The actual installation times achieved may deviate according to the conditions on site.
Pipework
Installation of heating cable on pipes including fastening, standard installation:
25 metres/hour
Connection system
(electrical connection)
RayClic-CE-02
RayClic-S-02/RayClic-PS-02
RayClic-T-02/RayClic-PT-02
RayClic-X-02
RayClic-E-02
2 min/pc.
4 min/pc.
6 min/pc.
8 min/pc.
1 min/pc.
Heat-shrink connection system
(electrical connection)
C25-21
E-06
CE20-01
Other
Testing, visual inspection, insulation resistance measurement (2x)
Connecting the heating circuit in the switch box
15 min/pc.
5 min/pc.
20 min/pc.
10 min/heating circuit
10 min/heating circuit
Technical handbook
65
GENERAL INSTALLATION INSTRuCTIONS
Trouble shooting guide
fault
Circuit-breaker trips:
RCD residual current device trips:
Possible causes
Circuit breaker wrong type: e.g. type B instead of C:
Circuit breaker undersized
Circuit too long
Short-circuit/earth fault
Circuit breaker faulty
No end seal
Conductor (or cable) twisted
Measures
Change to C Type
If the power supply cable permits, install a larger circuit breaker
Split the circuit on 2 circuit breakers
Eliminate short-circuit/earth fault
(cable ends should not be twisted)
Replace faulty circuit breaker
Install end seal un-twist and install end seal
More than 500 m of frost protection heating cable installed per rcd
Earth fault at connection or in end seal
Cable damaged
Moisture in the junction box
Install additional rcd residual current device
Rectify earth fault
Repair cable where damaged
Eliminate moisture
Pipeline does not become warm -
Heating cable cold:
Circuit-breaker has tripped
Residual current device has tripped
No mains voltage
Cable or cold lead not connected
Cable not inserted correctly in connection system or end seal
See section circuit breaker
See section residual current device
Switch on
Connect cable or cold lead
Insert cable according to installation instructions (fully insert cable)
Water temperature is not maintained but the cable gives high output:
No insulation Insulation thickness insufficient Insulation according to tables in design guides
Insulation wet
Cold water is running from the boiler
Cold water is pumping through mixer tap into the hot water pipe. Insulation according to tables in design guides.
Dry insulation
Test boiler temperature
Test the mixer tap
Note: Installation and operation information is available from Pentair in document reference: CDE-1547.
66
THERMAL buiLding SOLuTiOnS
TECHNICAL DATA
Choice of accessories
12 W/m at 70°C
9 W/m at 55°C
7 W/m at 45°C
180 m 20 A
90 m 16 A
105 m 16 A
85 m 50 A
80 m 20 A
150 m 16 A min 4,8; max. 6,3
Technical handbook
67
TECHNICAL DATA
dimensions of power cables
Maximum power (Cold Lead) cable lengths based on circuit breaker sizing and cable conductor cross sectional area.
C-type
Circuit breaker
(Ampères)
10
13
16
20
25
32
Cable type
HWAT-L
HWAT-M
HWAT-R
FS-A-2X/FS-C10-2X
FS-B-2X
FS-C-2X
GM-2X/GM-2XT
EM2-XR
EM-MI-PACK-26M
EM-MI-PACK-36M
HWAT-L
HWAT-M
HWAT-R
FS-A-2X/FS-C10-2X
FS-B-2X
FS-C-2X
GM-2X/GM-2XT
EM2-XR
EM-MI-PACK-48M
HWAT-L
HWAT-M
HWAT-R
FS-A-2X/FS-C10-2X
FS-B-2X
FS-C-2X
GM-2X/GM-2XT
EM2-XR
EM-MI-PACK-60M
HWAT-L
HWAT-M
HWAT-R
FS-C10-2X
GM-2X/GM-2XT
EM2-XR
EM-MI-PACK-70M
EM2-XR
EM-MI-PACK-88M
EM2-XR
Max. length of the power cable
Max. Circuit length (m)
3 x 1,5 mm
2
3 x 2,5 mm
2
3 x 4 mm
2
3 x 6 mm
2
3 x 10 mm
2
3 x 16 mm
2
22
48
140
80
80
85
70
50
65
65
130
40
17
26
110
65
55
36
110
80
50
50
35
70
45
100
180
80
88
55
60
28
60
150
105
90
180
100
40 n.p.
70
105
90
30
35
35
120
115
45
120
185
135
50
40
45
45
50 n.p.
n.p.
95 n.p.
n.p.
n.p.
n.p.
n.p.
n.p.
n.p.
n.p.
40
25
30
30
30 n.p.
n.p.
n.p.
65
60
115
175
150
55
60
60
200
190
70
205
310
220
70
85
110
85
70
75
80
155
120
45
35
40
40 n.p.
n.p.
n.p.
50
50
45
65
45
45
90
145
105
95
185
280
245
85
95
95
325
300
115
325
490
355
135
110
115
115
135
180
130
250
65
65
50
195
70
60
50 n.p.
75
80
75
100
70
70
145
230
160
145
280
420
370
485
455
175
125
140
140
490
740
535
205
165
175
175
205
270
195
375
295
110
85
100
100
75
80
65
150
105
110
115
125
115
220
345 n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
490 n.a.
145
165
165
130
130
105 n.a.
n.a.
n.a.
n.a.
n.a.
195
365
570 n.a. = Not applicable n.p. = Not permitted n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
68
THERMAL buiLding SOLuTiOnS
Pentair offers a set of tools and services that aim to simplify the professional´s life. Not only do we offer the best quality products, we also support them with unrivalled services.
An EffiCiEnT CuSTOMER SERViCE CEnTRE:
• Multi-lingual customer service representatives to answer all your questions
• Fast order handling & shipment Europe-wide
• Free documentation service
LARgE TECHniCAL SuPPORT TEAM:
• “On demand” technical advice and product selection
• Design support and cost estimates
• Specification support
• Training support
• Installation, test and commissioning support
• Complete after-sales service
• Online design dESign WizARd TRACECALC nET
• Online technical Support
WWW.PEnTAiRTHERMAL.COM
CALL 0800 96 90 13
FAX 0800 96 86 24
CHARTEREd inSTiTuTE Of buiLding
SERViCES EnginEERS
Pentair is also a proud industry supporter offering approved CPD courses via the Chartered Institute of
Building Services Engineers. Courses include technical and application information for electrical underfloor heating and hot water temperature maintenance systems.
For further information, please consult the CIBSE Course
Directory or contact Pentair.
WWW. PEnTAiRTHERMAL.COM
Our website provides you with all information from product selection to downloadable installation manuals.
Member of the
European Ra di ant Floor
Heat ing Association e.v.
Our products satisfy the
Mitglied in der European Radiant
Floor Heating Association e.V.
Technical handbook
69
70
THERMAL buiLding SOLuTiOnS
Technical handbook
71
WWW.Pentairthermal.Com
United Kingdom
Tel: 0800 969 013
Fax: 0800 968 624 [email protected]
ireland
Tel: 1800 654 241
Fax: 1800 654 240 [email protected]
SoUth eaSt aSia
Tel: +65 67685800
Fax: +65 67322263
aUStralia
Tel: +61 2 97920250
Fax:+61 2 97745931 [email protected]
india - noida
Tel: +91 120 464 9500
Fax: +91 120 464 9548
india - mUmBai
Tel: +91 22 6775 8800/01
Fax: +91 22 2556 1491
Uae
Tel: +971 4 378 1700
Fax: +971 4 378 1777
All Pentair trademarks and logos are owned by Pentair. All other brand or product names are trademarks or registered marks of their respective owners. Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.
Pentair is an equal opportunity employer.
© 1996-2015 Pentair.
THERMAL buiLding SOLuTiOnS
EN-Raychem-TH-CDE0517 Rev12 PCN 1244-001241