PowerSeries – Wireless Zones

PowerSeries – Wireless Zones
PowerSeries – Wireless Zones
Receivers:
PC5132-433, LCD5501Z32-433, RF5501-433
Panels:
PC580 (Power432), PC1555 (Power632)
Overview:
The wireless receiver can be used to enroll up to 32 wireless detection devices. Each wireless
device requires a zone.
Programming wireless zones is an eight-step process:
-
Connect the wireless receiver to the KEYBUS
Programming the zone definitions
Programming the zone attributes
Programming the zone assignments
Programming the Zone Serial Numbers
Disabling the Supervision of Panic Zones
Programming the Wireless Supervisory Window
Performing a Module Placement Test
Program Sections:
Section [001] – [004]
Section [101] – [132]
Section [202] – [205]
Section [804], [01] – [32]
Section [804], [82] – [85]
Section [804], [81]
Section [904], [01] – [32]
Zone Definitions
Zone Attributes
Zone Assignment
Zone Serial Number
Zone Device Supervision
Wireless Supervisory Window
Module Placement Test
Step 1 – Connect the wireless receiver to the KEYBUS
Connect the four KEYBUS terminals of the wireless receiver to the four KEYBUS terminals of the
main control panel.
Note:
If the receiver is not connected to the KEYBUS the wireless data cannot be
programmed.
Step 2 – Program the Zone Definitions
Before wireless zones will operate on the system, they must be defined.
[001]
[002]
[003]
[004]
Zones 1 to 8 Definitions
Zones 9 to 16 Definitions
Zones 17 to 24 Definitions
Zones 25 to 32 Definitions
Note:
Do not define wireless zones as [07], [08] or [09]. If using wireless smoke
detectors, program zone definitions [87] or [88].
Step 3 – Program the Zone Attributes
The panel must be told which zones are wireless. Turn Option [8] ON for all wireless zones in
Sections [101] to [132].
Step 4 – Zone Enable
Before any zone will operate on the system, the zone must be assigned to Partition 1. Make sure
the toggle options corresponding to all zones preset on the system are ON in Sections [202] to
[205].
Section [202] – Partition 1 zones 1 to 8 enable/disable
Section [203] – Partition 1 zones 9 to 16 enable/disable
Section [204] – Partition 1 zones 17 to 24 enable/disable
Section [205] – Partition 1 zones 25 to 32 enable/disable
Step 5 – Enroll Wireless Devices
Enter the ESN number for each wireless detection device in Section [804], subsection [01] to [32].
Note:
HEX digits may be present in the ESN number. Use the following table to program
the HEX digits.
HEX [A]
HEX [B]
HEX [C]
HEX [D]
HEX [E]
HEX [F]
enter [*][1][*]
enter [*][2][*]
enter [*][3][*]
enter [*][4][*]
enter [*][5][*]
enter [*][6][*]
Step 6 – Disabling Supervision of Panic Zones
The wireless Panic Pendent (WLS918-433) does not send a supervisory signal. Supervision
must be disabled for these zones to prevent the panel from generating a zone fault trouble
condition. Turn the corresponding Option OFF in Section [804], subsection [82] to [85] for all
wireless panic pendants zones.
Step 7 – Wireless Supervisory Window
Wireless transmitters check in with the wireless receiver every 64 minutes. The wireless
supervisory window is programmed in 15-minute increments. For example, data [32] = 8 hours,
data [96] = 24 hours. Program the desired supervisory window in Section [804], subsection [81]. If
a signal is not received from the transmitter, a zone fault trouble will be generated.
Note:
The Supervisory Window should not be less than 8 hours.
Step 9 – Perform a Module Placement Test
All wireless transmitters must be tested. To test a wireless transmitter, enter Section [904],
subsection [01] to [32] (the zone to be tested). Activate the device as indicated below:
WLS904-433
WLS906-433
WLS912-433
WLS914-433
WLS918-433
WLS925-433
Create/restore a tamper by removing the back plate then replacing it
Hold a magnet near groove marked on outer rim of bracket
Create/restore tamper by pressing the Tamper Tab for five seconds
Create/restore a tamper by removing the back plate then replacing it
Module Placement Test is not available. Test the unit by activating the Panic
alarm from various points throughout the installation to ensure proper reception
Create/restore an alarm or create/restore a tamper
Wait at least 5 seconds between each test.
The panel will indicate the test result on the keypad:
LED keypads:
ƒ
ƒ
LED 1 indicates GOOD placement
LED 3 indicates BAD placement
LCD Keypads:
ƒ
ƒ
‘Placement is GOOD’ indicates GOOD placement
‘Placement is BAD’ indicates BAD placement
ƒ
ƒ
1 squawk of the siren indicates GOOD placement
3 squawks of the siren indicates BAD placement
Siren:
Note:
The button on the WLS906 smoke detector is a local test only.
Note:
If one transmitter tests BAD, move the transmitter. If several transmitters test BAD,
move the PC5132 receiver.
Technical Tips:
1. When using zone expanders or addressable devices, make sure the wireless detectors
are not assigned a zone already used on a PC5108 or as addressable.
2. The PC5132-433 will generate a Module Tamper if an RF Jam condition is detected. To
disable RF Jam, turn ON option [7] in Section [804], subsection [90].
3. If good placement tests cannot be received from a transmitter, try moving the transmitter.
If there is a problem with multiple detectors, try moving the receiver.
4. If the panel gives a long error tone when a wireless subsection is entered, it indicates the
receiver is not connected to the KEYBUS.
Quick Test:
Violate all wireless detectors and verify all are displayed on the keypad.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising