2100 Series Temperature/Process Controllers

2100 Series Temperature/Process Controllers
2100 Series
Temperature/Process
Controllers
Ideal for
·
·
·
·
·
small ovens
chillers
sterilisers
trace heating
heat sealing
Specifications
Available in compact 1/32 and 1/16 DIN panel sizes, the 2100 series uses
advanced PID algorithms to give stable ‘straight line’ temperature control.
Self tuning is included to optimise the control performance without the
need for specialist knowledge or training.
Dimensions:
A universal input allows selection of nine internally stored
thermocouple types and the Pt100 resistance thermometer. Other input
linearisations may be factory downloaded. Linear inputs can be scaled to
the desired display range.
PID or On/Off
Two outputs are configurable for heating, cooling or alarms.
Operating ambient:
Three internal alarm setpoints are provided, configurable as high, low
or deviation alarms. Alarms can be ‘blocked’ on start-up to prevent
unnecessary operator alerts.
0-55°C, 0-90%RH non-condensing
Heater failure can be detected when the controller is used with a TE10S
Solid State Relay.
Pt100. 4-20mA linear. Custom input
Tactile buttons ensure positive operation.
Output ratings:
Model 2132: 48W x 24H x 103D mm
Model 2116: 48W x 48H x 103D mm
Control modes:
Supply voltages:
85-264Vac, 5.0watts maximum
20-29Vac or dc, 5.0watts maximum
Inputs:
Nine standard thermocouple types.
available
Relay: 2A, 264Vac resistive
The operator interface can be customised to present only those
parameters that an operator needs to see and adjust, while all other
parameters are locked away under password protection.
Logic: 9Vdc, 18mA
Panel sealing:
IP65, plug-in from front panel
Data sheet:
2100 Timer Functionality
Temperature
HA026158
Dwell Time
Setpoint
Ramp
Control
Time
Switch off
Rear terminal connections
Model 2132
Model 2116
External
Relay
Module
1B
1A
Low voltage supply
24
OR
Solid
State
Relay
1A
-
+
V-
V+
L
N
Output 1
(Logic)
1B
20-29Vac/dc
Model 2116
AA
External
Relay
Module
Model 2132
AB
1A
OR
AB
AA
N
1B
L
+
Output 1 1A
(Logic)
1B -
Solid
State
Relay
Line
85-264Vac
Neutral
Output 2
(Relay)
V+
2.49Ω Sensor
inputs
VT/C
Output 2
(Relay)
T/C
24
PT100
mA Input
Neutral Line
85-264Vac
PT100
20-29Vac/dc
24
mA Input
2.49Ω
Sensor inputs
24
Low voltage supply
Ordering codes
Model
Number
Function
Model Number
2132 48x24mm unit
2116 48x48mm unit
Function
CC
NF
TC
TN
PID Controller
On/Off Controller
PID Controller +Timer
On/Off Contr’ + Timer
Supply Voltage
VH 85-264Vac
VL 20-29V dc or ac
Supply
Voltage
Manual
Output 1 (Logic)
XX No function
Logic output
LH Heating
LC Cooling
M1 PDS heater break
detect (note 1)
FH High alarm 1
FL Low alarm 1
DB Dev. band alarm 1
DL Dev. low alarm 1
DH Dev, high alarm 1
NW New alarm
Logic input
AC Alarm ack/reset
KL Keylock
TM Timer Off/On
Output 1
(Logic)
Output 2
(Relay)
Output 2 (Relay)
XX
RH
RC
FH
FL
AL
No function
Heating
Cooling
High alarm 2
Low alarm 2
High alarm 2 & low
alarm 3
DB Dev. band alarm 2
DL Dev. low alarm 2
DH Dev, high alarm 2
NW New alarm
Manual
XXX
ENG
FRA
GER
NED
SPA
SWE
ITA
No manual
English
French
German
Dutch
Spanish
Swedish
Italian
Note 1. PDS heater break detect will
transmit the power demand to a
TE10S Solid State Relay and read
back a heater break alarm.
Note 2. Setpoint min and max : Include the
decimal position required in the
displayed value. Up to one for
temperature inputs, up to two for
process inputs.
Note 3. An external 1% current sense
resistor is supplied as standard. If
greater accuracy is required specify
‘A1’ in the Input Adaptor field.
Sensor
Input
Setpoint
Min
Setpoint
Max
note 2
note 2
Units
Ext. Relay
Module
Sensor Input
Standard Sensor Inputs
J J Thermocouple
K K Thermocouple
T T Thermocouple
L L Thermocouple
N N Thermocouple-Nicrosil/Nisil
R R Thermocouple-Pt/Pt13%Rh
S S Thermocouple-Pt /Pt10%Rh
B B Thermocouple-Pt/Pt30%Rh -6%Rh
P Platinel II Thermocouple
Z RTD/PT100 DIN 43760
Factory Downloaded Input
C C Thermocouple - W5%Re/W26%Re (Hoskins)
D D Thermocouple - W3%Re/W25%Re
E E Thermocouple
1 Ni/Ni18%Mo Thermocouple
2 Pt20%Rh/Pt40%Rh Thermocouple
3 W/W26%Re (Engelhard) Thermocouple
4 W/W26%Re (Hoskins) Thermocouple
5 W5%Re/W26%Re (Engelhard) Thermocouple
6 W5%Re/W26%Re (Bucose) Thermocouple
7 Pt10%Rh/Pt40%Rh Thermocouple
8 Exergen K80 I.R. pyrometer
Process Inputs (Scaled to setpoint min and max)
M -9.99 to +80mV linear
Y 0 to 20mA linear (note 3)
A 4 to 20mA linear (note 3)
V 0 to 10Vdc linear (Input adaptor required)
Input
Adaptor
Setpoint Min
Min
-210
-200
-200
-200
-200
-50
-50
0
0
-200
Min
0
0
-200
0
0
0
0
10
0
200
-45
Min
-1999
-1999
-1999
-1999
Units
Setpoint Max
°C
Max
1200
1372
400
900
1300
1768
1768
1820
1369
850
°C Max
2319
2399
1000
1399
1870
2000
2010
2300
2000
1800
650
°C Max
9999
9999
9999
9999
Example ordering code
2132- CC - VH - ENG - LH - RC - K - 0 - 1000 - C - XX - XX
2132, Controller, 85 to 264Vac, English manual, Logic heating, Relay cooling,
Type K thermocouple, 0 to1000°C, no options
C
F
K
X
Celsius
Fahrenheit
Kelvin
Linear input
Ext. Relay Module
XX Not fitted
R7 Fitted (Operated by
the logic output)
Input Adaptor
XX Not fitted
V1 0-10Vdc
A1 0-20mA or 4-20mA
0.1% current sense
resistor (2.49Ω)
2200e Series
Temperature/Process
Controllers
Ideal for
· extrusion with optimised
fan, or oil cooling
· ovens and furnaces
· cold stores
Specifications
Available in 1/16, 1/8 and 1/4 DIN panel sizes the 2200e series are configurable
for PID, On/off or motorised valve control - satisfying both electrical and gas
heating applications. Self-tuning is included to optimise control performance.
Dimensions:
Modular heating and cooling outputs are provided, as well as a choice of
one or two alarm relay outputs. The 1/8 and 1/4 DIN units have two digital
inputs to select auto/manual transfer, standby mode, second setpoint or alarm
acknowledge. The 1/4 DIN model 2204e has an additional 10 amp high current
output option.
Model 2204e: 96W x 96H x 103D
Digital communications with industry standard protocols including
Modbus® and DeviceNet® are available for easy connection to supervisory
control and data logging systems.
Operating ambient:
Simple heat treatment profiles can be programmed using the internal ramp
generator and dwell timer.
See sensor inputs in the configuration
Abolish ammeters by using Eurotherm’s advanced load current
monitoring facility. Heater current may be displayed and also open or short
circuit faults detected.- See page 3-37 for more information.
Output ratings:
Rear terminal connections
Triac: 1A, 264Vac resistive
Model 2216e
DC or Logic or
or
2A
Logic or
or
L
Line
HB
N
Neutral
1A
DC or Logic or
or
L
HB
N
HE
LB
HF
LC
2A
Output 2
or
2B
3A
Output 3
C
HC O
M
HD M
S
VI
HE
V+
HF
V-
T/C
3B
Output 3
Neutral
Earth
Pt100
The 10A output
for the Model
2404e is wired
to additional
terminals 4A
through to 6D.
3B
3C
Output 4
Relay: 2A, 264Vac resistive
Logic: 18Vdc, 20mA
Dig in 1
Data sheets:
Dig in 2
2216e: HA025546
Common
2208e/2204e: HA025552
AB
AC
3A
coding
Model 2208e, 2204e: IP65
AA
Line
85-264Vac, 10.0watts maximum
Model 2216e: IP65
Output 1
1B
Logic or
HA
Supply voltages:
Inputs:
Earth
LA
Output 2
2B
PID or On/Off or motorised valve
Panel sealing:
HA
C
HC O
M
M
HD
S
Control modes:
DC: Isolated 0-20mA, at 12Vdc
Output 1
1B
Model 2208e: 48W x 96H x 103D
0-55°C, 0-90%RH non-condensing
Model 2208e/2204e
1A
Model 2216e: 48W x 48H x 103D
VI
V+
T/C
V-
Pt100
Ordering codes
Model
Number
Supply
Voltage
Function
Hardware coding
Function
CC PID Control
NF On/off control
VC Motorised Valve
control
AL Alarm unit
Supply Voltage
VH 85-264Vac
Table A: DC retransmission
D6 Fitted unconfigured
First character
V- PV retrans
P- Setpoint retrans
O- Output retrans
Z- Error retrans
Second character
-1 0-20mA
-2 4-20mA
-3 0-5V
-4 1-5V
-5 0-10V
Output 2
Output 3
VH
Model Number
2216e 48x48mm unit
2208e 48x96mm unit
2204e 96x96mm unit
Output 1
Output 4
10 Amp
Output
Omit
for
2216
Omit for
2216 &
2208
Comms
Manual
Output 1
Output 2
Output 3
Output 4
10 Amp Output
XX Not fitted
Relay: 2-pin
R1 Fitted unconfigured
RH Heating output
RU Valve raise output
FH High alarm 1
FL Low alarm 1
DB Dev. band alarm 1
DL Dev. low alarm 1
DH Dev. high alarm 1
Logic
L1 Fitted unconfigured
LH Heating output
M1 PDS Heater break
detect (note 1)
M2 PDS Current
monitoring (note 2)
Triac
T1 Fitted unconfigured
TH Heating output
TU Valve raise output
DC control (Isolated)
D3 Fitted unconfigured
H6 0-20mA heating
H7 4-20mA heating
C6 0-20mA cooling
C7 4-20mA cooling
DC retran. (Isolated)
Select from Table A
XX Not fitted
Relay: 2-pin
R1 Fitted unconfigured
RC Cooling output
RH Heating output
RW Valve lower output
FH High alarm 2
FL Low alarm 2
DB Dev. band alarm 2
DL Dev. low alarm 2
DH Dev. high alarm 2
AL High & low alarms
1&2
Logic output
L1 Fitted unconfigured
LC Cooling output
LH Heating output
Logic input
AM Auto manual select
S2 Setpoint 2 select
AC Alarm ack/reset
EH Integral hold
SB Standby mode
SR PDS Remote SP select
M5 CTX mode 5 current
I/P
Triac
T1 Fitted unconfigured
TC Cooling output
TH Heating output
TW Valve lower output
XX Not fitted
Relay
RF Fitted unconfigured
RH Heating output
RC Cooling output
FH High alarm 3
FL Low alarm 3
DB Dev. band alarm 3
DL Dev. low alarm 3
DH Dev. high alarm 3
AL High & low alarms
3&4
PDS Alarms
LF Heater break detect
HF Current monitoring
heater break
SF Current monitoring
SSR failure
XX Not fitted
Relay
RF Fitted unconfigured
RH Heating output
RC Cooling output
FH High alarm 4
FL Low alarm 4
DB Dev. band alarm 4
DL Dev. low alarm 4
DH Dev. high alarm 4
AL High & low alarms
3&4
PDS Alarms
LF Heater break detect
HF Current monitoring
heater break
SF Current monitoring
SSR failure
XX Not fitted
R5 Fitted unconfigured
RH Heating output
Configuration coding
(optional)
Sensor
input
Sensor Input
Standard Sensor Inputs
J J Thermocouple
K K Thermocouple
T T Thermocouple
L L Thermocouple
N N Thermocouple-Nicrosil/Nisil
R R Thermocouple-Pt/Pt13%Rh
S S Thermocouple-Pt /Pt10%Rh
B B Thermocouple-Pt/Pt30%Rh -6%Rh
P Platinel II Thermocouple
Z RTD/PT100 DIN 43760
Factory Downloaded Input
C C Thermocouple - W5%Re/W26%Re (Hoskins)
D D Thermocouple - W3%Re/W25%Re
E E Thermocouple
1 Ni/Ni18%Mo Thermocouple
2 Pt20%Rh/Pt40%Rh Thermocouple
3 W/W26%Re (Engelhard) Thermocouple
4 W/W26%Re (Hoskins) Thermocouple
5 W5%Re/W26%Re (Engelhard) Thermocouple
6 W5%Re/W26%Re (Bucose) Thermocouple
7 Pt10%Rh/Pt40%Rh Thermocouple
8 Exergen K80 I.R. pyrometer
Process Inputs (Scaled to setpoint min and max)
M -9.99 to 80.00mV linear
Y 0 to 20mA linear (note 4)
A 4 to 20mA linear (note 4)
W 0 to 5Vdc linear
G 1 to 5Vdc linear
V 0 to 10Vdc linear
Setpoint
Min
note 3
Setpoint
Min
Min
-210
-200
-200
-200
-200
-50
-50
0
0
-200
Min
0
0
-250
0
0
0
0
10
0
200
-45
Min
-999
-999
-999
-999
-999
-999
Setpoint
Max
Manual
Display
Units
Setpoint
Max
Max
1200
1372
400
900
1300
1700
1768
1820
1369
850
°C Max
2319
2399
1000
1399
1870
2000
2010
2300
2000
1800
650
°C Max
9999
9999
9999
9999
9999
9999
2XX Not fitted
Modbus protocol
2YM 2-wire RS485
2FM 4-wire RS422
2AMRS232
DeviceNet®
2DN DeviceNet
EI-Bisynch protocol
2YE 2-wire RS485
2FE 4-wire RS422
2AE RS232
PDS input
2RS Setpoint input
XXX
ENG
FRA
GER
NED
SPA
SWE
ITA
note 3
°C
Comms
Digital
Input 1
Digital
Input 2
Omit
for 2216
Omit
for 2216
Display
Units
C
F
K
X
Celsius
Fahrenheit
Kelvin
Linear input
Digital
Input 1 & 2
XX No function
AMManual select
SR PDS Remote
setpoint select
S2 Second setpoint
EH Integral hold
AC Alarm acknowledge
SB Standby mode
M5 CTX mode 5 current
input (input 1 only)
Control
Options
Power
No manual
English
French
German
Dutch
Spanish
Swedish
Italian
Cooling
Options
Control action
XX Reverse acting (std)
DP Direct acting
Power feedback
XX Enabled on logic,
relay & triac heating
outputs
PD Feedback disabled
Cooling options
XX Linear cooling
CF Fan cooling
CW Water cooling
Note 1. PDS heater break detect will transmit
the power demand to a TE10S Solid
State Relay and read back a heater
break alarm.
Note 2. PDS current monitoring will transmit
the power demand signal to a TE10S
Solid State Relay and read back load
current and open and short circuit
alarms.
Note 3. Setpoint limits: Include the decimal
position required in the displayed value.
Up to one for temperature inputs, up to
two for process inputs.
Note 4. An external 1% current sense resistor is
supplied as standard. If greater accuracy
is required, a 0.1% 2.49Ω can be
ordered as part no. SUB2K/249R.1.
2416 Programmable
Temperature/Process
Controllers
Ideal for
· single and multi-zone
ovens and furnaces
· ceramic and brick kilns
· environmental chambers
Specifications
The 2416 is a high stability controller with a wide range of options.
Either PID, On/off or motorised valve control can be configured satisfying both electrical and gas heating applications. Dual PID
settings and advanced tuning algorithms optimise control performance.
Plug-in modules provide outputs for heating, cooling and analogue
retransmission as well as logic telemetry.
Four setpoint programs can be stored with 16 ramp-dwell segments
and three event outputs per program.
High speed digital communications with industry standard protocols
allowing easy connection to supervisory control and data logging
systems.
Abolish ammeters by using Eurotherm’s advanced load current
monitoring facility. Heater current may be displayed and also open or
short circuit faults detected. - See page 1-32 for more information.
Multi-zone programming can be implemented using ‘PDS’ retransmission to deliver a master setpoint to up to three slave controllers with
holdback from any slave if the temperature deviates from the setpoint
by more than a set value.
Dimensions (mm):
48W x 48H x 150D
Control modes:
PID or On/Off or motorised valve
Supply voltages:
85-264Vac, 10watts maximum
20-29Vac or dc, 10watts maximum
Operating ambient:
0-55°C, 0-90%RH non-condensing
Inputs:
See Sensor Inputs in the
Configuration coding
Output ratings:
Relay: 2A, 264Vac resistive
Logic: 18Vdc, 20mA
Triac: 1A, 264Vac resistive
DC: 0-20mA, or 0-10Vdc configurable
Panel sealing:
Programmer Functionality
Temperature
Rear terminal connections
IP65, plug-in from front panel
Model 2416
Data sheet:
HA025564
1A
HA
L
Line
HB
N
Neutral
E
Earth
Module 1
1B
Time
2A
Module 2
Event 1
2B
3A
Event 2
C
HC O
M
HD M
S
VI
HE
V+
HF
V-
Module 3
3B
T/C
+
PV
PT100
Ordering codes
Model
Number
Hardware coding
Function
Supply
Voltage
Module 1
Module 2
Module 3
Comms
Manual
2416
Function
Module 1
Module 2
Module 3
Comms
Standard PID control
CC Controller only
CG 1 x 8 seg Prog
CP 1 x 16 seg Prog
P4 4 x 16 seg Prog
On/Off Control
NF Controller only
NG 1 x 8 seg Prog
NP 1 x 16 seg Prog
N4 4 x 16 seg Prog
Motorised valve control
VC Controller only
VG 1 x 8 seg Prog
VP 1 x 16 seg Prog
V4 4 x 16 seg Prog
XX None
Relay: 2-pin
R2 Fitted unconfigured
RH Heating output
RU Valve raise output
FH High alarm 1
FL Low alarm 1
DB Dev. band alarm 1
DL Dev. low alarm 1
DH Dev. high alarm 1
Logic
L2 Fitted unconfigured
LH Heating output
M1 PDS Heater break
detect (note 1)
M2 PDS Current
monitoring (note 2)
Triac
T2 Fitted unconfigured
TH Heating output
TU Valve raise output
DC control (Non-isol)
D2 Fitted unconfigured
H1 0-20mA PID heating
H2 4-20mA PID heating
H3 0-5V PID heating
H4 1-5V PID heating
H5 0-10V PID heating
XX None
Relay: 2-pin
R2 Fitted unconfigured
RC Cooling output
RW Valve lower output
FH High alarm 2
FL Low alarm 2
DB Dev. band alarm 2
DL Dev. low alarm 2
DH Dev. high alarm 2
PO Program event 1
(not with 8-seg prog)
PE Program END output
Logic
L2 Fitted unconfigured
LC Cooling output
Triac
T2 Fitted unconfigured
TC Cooling output
TW Valve lower output
DC control (Non-isol)
D2 Fitted unconfigured
C1 0-20mA PID cooling
C2 4-20mA PID cooling
C3 0-5V PID cooling
C4 1-5V PID cooling
C5 0-10V PID cooling
XX None
Relay: 2-pin
R2 Fitted unconfigured
FH High alarm 4
FL Low alarm 4
DB Dev. band alarm 4
DL Dev. low alarm 4
DH Dev. high alarm 4
RA Rate of change alarm
PO Program event 2
(not with 8-seg prog.)
PE Program END output
PDS Alarms
LF Heater break detect
HF Current monitoring
heater break
SF Current monitoring
SSR failure
Logic
L2 Fitted unconfigured
Triac
T2 Fitted unconfigured
DC retran (Non-isol)
D2 Fitted unconfigured
First character
V- PV retrans
S- Setpoint retrans
O- Output retrans
Z- Error retrans
Second character
-1 0-20mA
-2 4-20mA
-3 0-5V
-4 1-5V
-5 0-10V
XX None
2 wire, RS485
Y2 Fitted unconfigured
YM Modbus protocol
YE EI-Bisynch protocol
RS232
A2 Fitted unconfigured
AM Modbus protocol
AE EI-Bisynch protocol
4 wire, RS422
F2 Fitted unconfigured
FM Modbus protocol
FE EI-Bisynch protocol
PDS Input
M6 Fitted unconfigured
RS Setpoint input
PDS Output
M7 Fitted unconfigured
PT PV retrans
TS Setpoint retrans
OT Output retrans
Supply Voltage
VH 85-264Vac
VL 20-29Vac/dc
Setpoint
Input
Configuration coding
(optional)
Setpoint
Min
Setpoint
Max
note 3
note 3
Sensor Input
Setpoint
Min
Standard Sensor Inputs
J J Thermocouple
K K Thermocouple
T T Thermocouple
L L Thermocouple
N N Thermocouple-Nicrosil/Nisil
R R Thermocouple-Pt/Pt13%Rh
S S Thermocouple-Pt /Pt10%Rh
B B Thermocouple-Pt/Pt30%Rh -6%Rh
P Platinel II Thermocouple
Z RTD/PT100 DIN 43760
Factory Downloaded Input
C C Thermocouple - W5%Re/W26%Re (Hoskins)
D D Thermocouple - W3%Re/W25%Re
E E Thermocouple
1 Ni/Ni18%Mo Thermocouple
2 Pt20%Rh/Pt40%Rh Thermocouple
3 W/W26%Re (Engelhard) Thermocouple
4 W/W26%Re (Hoskins) Thermocouple
5 W5%Re/W26%Re (Engelhard) Thermocouple
6 W5%Re/W26%Re (Bucose) Thermocouple
7 Pt10%Rh/Pt40%Rh Thermocouple
8 Exergen K80 I.R. pyrometer
Process Inputs (Scaled to setpoint min and max)
F -100 to +100mV linear
Y 0 to 20mA linear (note 4)
A 4 to 20mA linear (note 4)
W 0 to 5Vdc linear
G 1 to 5Vdc linear
V 0 to 10Vdc linear
Min
-210
-200
-200
-200
-250
-50
-50
0
0
-200
Min
0
0
-250
0
0
0
0
10
0
200
-45
Min
-1999
-1999
-1999
-1999
-1999
-1999
Display
Units
Control
Power
Display
Units
Setpoint
Max
°C
Max
1200
1372
400
900
1300
1700
1768
1820
1369
850
°C Max
2319
2399
1000
1399
1870
2000
2010
2300
2000
1800
650
°C Max
9999
9999
9999
9999
9999
9999
C
F
K
X
Celsius
Fahrenheit
Kelvin
Blank
Options
Cooling
Manual
XXX
ENG
FRA
GER
NED
SPA
SWE
ITA
No manual
English
French
German
Dutch
Spanish
Swedish
Italian
Buttons
Note 1. PDS heater break detect will
transmit the power demand
to a TE10S Solid State Relay
and read back a heater
break alarm.
Note 2. PDS current monitoring will
transmit the power demand
signal to a TE10S Solid
State Relay (or PD/CTX) and
read back load current and
open and short circuit alarms.
Note 3. Setpoint limits: Include the
decimal position required in
the displayed value.
Up to one for temperature
inputs, up to two for process
inputs.
Note 4. An external 1% current sense
resistor is supplied as
standard. If greater
accuracy is required, a 0.1%
2.49Ω can be ordered as part
no. SUB2K/249R.1.
Program
Options
Control action
XX Reverse acting (standard)
DP Direct acting
Power feedback
XX Enabled on logic, relay
and triac heating outputs
PD Feedback disabled
Cooling options
XX Linear cooling
CF Fan cooling
CW Water cooling
CL Oil cooling
CO On/Off cooling
Front panel buttons
XX Enabled
MD Auto/manual disabled
MR Auto/man & run/hold
disabled
RD Run/hold disabled
Programmer timing
XX Ramp and dwell in mins
HD Dwell time in hours
HR Ramp rate in units/hour
Example ordering code
2416 - CC - VH - LH - RC - FH - YM - ENG - K - 0 1000 - C - XX - XX - XX - MD - XX
2416, Controller, 85 to 264Vac, Logic heating,
Relay cooling, High alarm relay, RS485, Modbus comms,
English manual, type K thermocouple,
0 to1000°C, Manual button disabled.
2408 and 2404
Temperature/Process
Controllers
Ideal for
· single and multi-zone
ovens, furnaces and kilns
· environmental chambers
· simple ratio & cascade
control
Specifications
Available in 1/8 and 1/4 DIN panel sizes , the 2408 and 2404 are high
stability controllers with an extensive range of options. Either PID, on/off
or motorised valve control can be configured, satisfying both electrical and
gas heating applications. Advanced adaptive tuning algorithms optimise
control performance.
The controllers accept a range of plug-in modules for heating, cooling,
analogue retransmission, second process value input and remote setpoint.
High speed Modbus, PROFIBUS, DeviceNet and ASCII communications
provide easy connection to PLCs, supervisory control and data logging
systems.
20 setpoint programs can be stored with 16 ramp-dwell segments and eight
event outputs.
Abolish ammeters by using Eurotherm’s advanced load current
monitoring facility. Heater current may be displayed and also open or short
circuit faults detected.- See page 3-37 for more information.
Dimensions (mm):
Multi-zone programming can be
implemented using ‘PDS’ retransmission to deliver a master setpoint
to up to three slave controllers with
holdback from any slave if the
temperature deviates from the
setpoint by more than a set value.
Output ratings:
Programmer Functionality
Temperature
Rear terminal connections
Model 2408 and 2404
Event 1
Event 2
HB
1B
4B
3B
6C
3C
JE
6D
3D
JF
JD
Module 3
Common
AA
2
Logic: 18Vdc, 20mA
HA026553
LA
Module 2
6B
Relay: 2A, 264Vac resistive
Data sheet:
LC
JC
Configuration coding
Dig in 2
HF
3A
See Sensor Inputs in the
IP65, plug-in from front panel
2B
6A
Inputs:
Dig in 1
LB
C
O
M
M
S
0-55°C, 0-90%RH non-condensing
Panel sealing:
HE 1
JA
Operating ambient:
Earth
2A
JB
20-29Vac/dc, 15watts maximum
N
5A
2D
85-264Vac, 15watts maximum
DC: 0-20mA or 0-10Vdc configurable
1C
5D
Supply voltages:
Neutral
1D
2C
PID, On/Off or motorised valve
Triac: 1A 264Vac resistive
4C
5C
Control modes:
Line
4D
10A
Output
2404: 96W x 96H x 150D
L
C
HC O
M
M
HD
S
Module1
5B
Time
HA
1A
4A
2408: 48W x 96H x 150D
AB
Alarm
Relay
AC
VI
V+
T/C
V-
PV
Ordering codes
Model
Number
Function
Supply
Voltage
Module 1
Module 2
Alarm
Relay
Module 3
10amp
Output
Hardware coding
Note 1.
Not available with
profibus controllers
Note 2.
PDS heater break detect
will transmit the power
demand to a TE10S
Solid State Relay and read
back a heater break
alarm.
Note 3.
PDS current monitoring
will transmit the power
demand signal to a TE10S
Solid State Relay and read
back load
current and open and
short circuit alarms.
Manual
Function
Module 1
Module 2
Module 3
10amp Output
XX Not fitted
Relay: 2-pin
R2 Fitted unconfigured
RH Heating output
RU Valve raise output
Relay: change over
R4 Fitted unconfigured
YH Heating output
Or alarm 1 from table A
Logic: (Non-isolated)
L2 Fitted unconfigured
LH Heating output
M1 PDS Heater break
detect (note 2)
M2 PDS Current
monitoring (note 3)
Triac
T2 Fitted unconfigured
TH Heating output
TU Valve raise output
DC control (Isolated)
D4 Fitted unconfigured
H6 0-20mA heating
H7 4-20mA heating
H8 0-5V heating
H9 1-5V heating
HZ 0-10V heating
Digital I/O (unconfig’d)
TK Triple contact input
TL Triple logic input
TP Triple logic output
Dual relay
RR Fitted unconfigured
RD Heat + cool
RM VP raise & lower OPs
Dual triac
TT Fitted unconfigured
TD Heat + cool
TM VP raise & lower OPs
Logic+relay
LR Fitted unconfigured
LD Heat + cool
PD Mode 2 + cool
Logic+triac
LT Fitted unconfigured
GD Heat & cool
QD Mode 2 + cool
XX Not fitted
Relay: 2-pin
R2 Fitted unconfigured
RC Cooling output
RW Valve lower output
Relay: change over
R4 Fitted unconfigured
YC Cooling output
PO Program event 1
(not with 8-seg
programmer)
PE Program END output
Or alarm 2 from table A
Dual relay
RR Fitted unconfigured
PP Program events 1 & 2
Logic
L2 Fitted unconfigured
LC Cooling output
Triac
T2 Fitted unconfigured
TC Cooling output
TW Valve lower output
DC control (Isolated)
D4 Fitted unconfigured
C6 0-20mA cooling
C7 4-20mA cooling
C8 0-5V cooling
C9 1-5V cooling
CZ 0-10V cooling
Digital I/O (unconfig’d)
TK Triple contact input
TL Triple logic input
TP Triple logic output
Power supply
MS 24Vdc transmitter
DC retran. (Isolated)
Select from Table B
Potentiometer input
VU Fitted unconfigured
VS Valve position feedback
VR Setpoint input
XX Not fitted
Relay: 2-pin
R2 Fitted unconfigured
Relay: change over
R4 Fitted unconfigured
PO Program event 4
(not with 8-seg
programmer)
PE Program END output
Or alarm 3 from table A
Logic
L2 Fitted unconfigured
Triac
T2 Fitted unconfigured
Dual relay
RR Fitted unconfigured
PP Program event 4 & 5
Digital I/O (unconfig’d)
TK Triple contact input
TL Triple logic input
TP Triple logic output
Power supply
MS 24Vdc transmitter
DC remote input
D5 Fitted unconfigured
W2 4-20mA setpoint
W5 0-10V setpoint
WP Second PV input
DC retran. (Isolated)
Select from Table B
Potentiometer input
VU Fitted unconfigured
VS Valve position feedback
VR Setpoint input
XX Not fitted
R6 Fitted unconfigured
RH Heating
Supply Voltage
VH 85-264Vac
VL 20-29Vac/dc
Note 4.
Setpoint limits: Include the
decimal position required
in the displayed value. Up
to one for temperature
inputs, up to two for
process inputs.
Note 5.
An external 1% current
sense resistor is supplied as
standard. If greater accuracy is required, a 0.1%
2.49Ω can be ordered as
part no.
SUB2K/249R.1.
Table B: DC retransmission
D6 Fitted unconfigured
First character
V- PV retrans
S- Setpoint retrans
O- Output retrans
Z- Error retrans
Second character
-1 0-20mA
-2 4-20mA
-3 0-5V
-4 1-5V
-5 0-10V
Table A: alarm codes
FH High alarm
FL Low alarm
DB Dev. band alarm
DL Dev. low alarm
DH Dev. high alarm
Sensor
Input
Configuration
coding (optional)
Setpoint
Min
Setpoint
Max
note 4
note 4
Display
Units
Digital
Input 1
Display Units
Sensor Input
Setpoint Min/MAX
Refer to 2416 coding
Comms 2
PID control
CC Controller only
CG 1x 8 seg Prog
CP 1x16 seg Prog
P4 4x16 seg Prog
CM 20x16 seg Prog
(note 1)
On/Off Control
NF Controller only
NG 1x8 seg Prog
NP 1x16 seg Prog
N4 4x16 seg Prog
NM 20x16 seg Prog
(note 1)
Motorised valve control
VC Valve positioner
VG 1x8 seg Prog
VP 1x16 seg Prog
V4 4x16 seg Prog
VM 20x16 seg Prog
(note 1)
Model Number
Panel size
2408 48x96mm
2404 96x96mm
Profibus units
2408f 48x96mm
2404f 96x96mm
Comms 1
Omit for
2408
C
F
K
X
Celsius
Fahrenheit
Kelvin
Linear input
Digital
Input 2
Control
Comms 2
Alarm relay
XX Not fitted
Alarm 4 relay
RF Fitted unconfigured
Table A alarm options
plus:
RA Rate of change alarm
PDS Alarms
LF Heater break detect
HF Current monitoring
heater break
SF Current monitoring
SSR failure
PO Program event 7
(not with 8-seg prog)
PE Program END output
Power
Options
Cooling
Digital Input 1 & 2
XX
AM
SR
S2
EH
AC
RP
RN
HO
RE
RH
KL
NT
TN
HB
Disabled
Manual select
Remote SP select
Second setpoint
Integral hold
Alarm acknowledge
SP rate limit enabled
Run program
Hold program
Reset program
Run/hold prog
Keylock
Run/Reset
Reset/Run
Program holdback
P2 Second PID
ST One shot tune
enable
AT Adaptive tune enable
FA Select full access
level
RB Simulates UP button
LB Simulates DOWN
button
SB Simulates SCROLL
button
PB Simulates PAGE
button
B1 Least sig. BCD digit
B2 2nd BCD digit
Comms 1
XX Not fitted
2 wire, RS485
Y2 Fitted unconfigured
YM Modbus protocol
YE EI-Bisynch
protocol (note 1)
RS232
A2 Fitted unconfigured
AM Modbus protocol
AE EI-Bisynch
protocol (note 1)
4 wire RS422
F2 Fitted unconfigured
FM Modbus protocol
FE EI-Bisynch
protocol (note 1)
PDS Output
M7 Fitted unconfigured
PT PV retrans
TS Setpoint retrans
OT Output retrans
Profibus Module
PB High speed RS485
DeviceNet®
DN DeviceNet
XX Not fitted
PDS Input
M6 Fitted unconfigured
RS Setpoint input
PDS Output
M7 Fitted unconfigured
PT PV retrans
TS Setpoint retrans
OT Output retrans
Manual
XXX
ENG
FRA
GER
NED
SPA
SWE
ITA
No manual
English
French
German
Dutch
Spanish
Swedish
Italian
Buttons
Program
Options
B3
B4
B5
B6
SY
SC
SG
PV
AG
M5
3rd BCD digit
4th BCD digit
5th BCD digit
Most significant digit
Standby-all O/Ps OFF
Prog synchronisation
Skip segment
(without changing
SP)
Select PV2
Advance to end of
segment
(& step to target SP)
CTX (mode 5)
Example ordering code
2408 - CC - VH - LH - RC - FL - FH - YM - TS - K - 0 - 1000 - C - AM - S2 - XX - XX - XX - MD - XX
2408, PID Controller, 85 to 264Vac, Logic heating, Relay cooling, Low alarm relay, High alarm relay,
RS485, Modbus comms, PDSIO setpoint retrans, Type K thermocouple, 0 to1000°C, Auto/manual select, 2nd
setpoint select, Manual button disabled.
Control action
XX Reverse acting (standard)
DP Direct acting
Power feedback
XX Enabled on logic,
relay & triac heating
PD Feedback disabled
Cooling options
XX Linear cooling
CF Fan cooling
CW Water cooling
CL Oil cooling
CO On/Off cooling
Front panel buttons
XX Enabled
MD Auto/manual disabled
MR Auto/man & run/hold
disabled
RD Run/hold disabled
Programmer time units
XX Dwell & ramp in mins
HD Dwell time in hours
HR Ramp rate in units/hrs
2604 and 2704
High Performance
Controllers/Programmers
Ideal for
· atmosphere heat
treatment
· reliability test chambers
· composite curing
autoclaves
· vacuum furnaces
· ceramic and brick kilns
· glass furnaces/forehearths
· melt pressure
Specifications
2604 and 2704 are High Stability temperature and process controllers.
The 2604 has a dual 5 digit display and a 2 line LCD panel. The 2704 has a
high visibility graphical user interface, enabling many advanced
features including PV/SP trending. Both units are available in a single,
dual or triple loop format.
A setpoint programming option is available allowing storage of up to 50
programs, each program can profile up to three setpoints.
Using internal Toolkit Blocks, customised user configurations and
special machine controllers can be created.
2604 and 2704 have fixed and modular IO and can use the 2000IO
(see page 1-23) expansion unit to provide further input and output
connections. - See page 3-37 for more information.
Dimensions (mm):
96W x 96H x 150D
Control modes:
3 Control loops
PID, On/off and Motorised Valve,
Cascade, Ratio & Override
Setpoint programmer:
50 Programs, 500 segments
16 Event outputs
Supply voltages:
85-264Vac, 24Vac/dc
Rear terminal connections
Special functions:
Model 2604/2704
Carbon potential, Humidity
Common
Trending (2704), Vacuum (2704)
DC
4A
1A
HA
L
Line
D1
4B
1B
HB
N
Neutral
D2
4C
1C
D3
4D
1D
C
HC O
M
M
HD
S
D4
5A
2A
HE 1
E1
D5
5B
2B
HF
E2
AA
Module1
Module 4
Digital
I/O
Earth
D8
Toolkit blocks:
Maths functions
Logic operations
Digital Input
I/O Expander
or
Digital Input
Timers
Totalisers
Comms:
Module 5
D6
5C
2C
JA
D7
5D
2D
JB
VH
6A
3A
JC
VI
6B
Modbus, Profibus - DP, DeviceNet®
PV
Input
3B
Module 6
JD
Module 3
V+
6C
3C
JE
V-
6D
3D
JF
C
O
M
M
S
2
AB Relay
Data sheet:
AC
BA
BB
BC
Model 2604; HA026669
Analogue
Input ±10V
Model 2704; HA026916
Ordering codes
Controller
Type
Supply
Voltage
Loop/
Programs
Applications
Comms
Manual
Toolkit
Functions
Config.
Tools
I/O slot 1
I/O slot 3
I/O slot 4
I/O slot 5
I/O slot 6
Memory
Module
Comms
Hardware coding
Controller Type
2604 Standard
2604f Profibus
2704 Standard
2704f Profibus
Supply Voltage
VH
VL
85-264Vac
20-29Vac/dc
Loop/Programs
First digit
1-- One loop
2-- Two loops
3-- Three loops
Second digit
-XX No programs
-2- Twenty programs
-5- Fifty programs
Third digit
-XX No programs
--1 1 Profile
--2 2 Profile
--3 3 Profile
I/O slots 1,3,4,5,6
(1)
Applications
XX
ZC
V1
V3
Standard
Zirconia
1 Gauge vacuum
3 Gauge vacuum
XX
R4
R2
RR
T2
TT
D4
D6
PV
TL
TK
TP
MS
VU
G3
G5
AM
DP
LO
None fitted
Change over relay
2 Pin relay
Dual relay
Triac
Dual triac
DC Control
DC retransmission
PV Input (slots 3 &
6 only)
Triple logic input
Triple contact input
Triple logic output
24Vdc transmitter PSU
Potentiometer input
5Vdc transducer PSU
10Vdc transducer PSU
Analogue input module
(not in slot 5)
Dual DC (probe) input(4)
(slots 3 and 6 only)
Isolated single logic OP
Memory Module
Manual
ENG
FRA
GER
ITA
NED
SPA
SWE
XX Not fitted
Comms
First slot (only)
PB Profibus
AE 232 Bisync
YE 2 Wire 485 Bisync
FE 4 Wire 485 Bisync
DN DeviceNet
Both slots
XX None fitted
A2 EIA-232
Y2 2-wire EIA-485
F2 4-wire EIA-485
Config Tools
XX None
IT Standard iTools
English
French
German
Italian
Dutch
Spanish
Swedish
Order separately page 2-7
Toolkit Functions
XX Standard
U1 Toolkit level 1
U2 Toolkit level 2
(2)
(3)
Hardware notes:
1. Basic controller includes 8 digital
registers, 4 timers and 4 totalisers.
2. Toolkit 1 includes 16 analogue, 16 digital,
pattern generator, digital programmer
analogue switch and 4 user values.
3. Toolkit 2 includes Toolkit 1 plus extra
8 analogue, 16 digital and 8 user values.
4. Dual analogue input suitable for Carbon
Probes. (Inputs not isolated from each
other)
Example ordering code
2704 - VH - 323 - XX - RR - PV - D4 - TP - PV - XX - A2 - XX - ENG - U1 - IT
This code describes a 3 loop controller with capability to store 20 three profile programs. Supply voltage is 85-264Vac.
Modular hardware: 2 x PV input, 1 x Dual relay, 1 x DC control, 1 x Triple logic output, EIA-232 Comms.
16 analogue and 16 digital operations, iTools supplied with controller
Loop function
Loop 1
Type
Loop 2
Type
Process inputs
Loop 3
Type
Loop 1
PV
Loop 2
PV
Loop 3
PV
Slot function
Analogue
Input
Slot 1
Slot 3
Slot 4
Slot 5
Slot 6
Configuration
coding (optional)
Loop function
XXXX None
S___ Standard PID
C___ Cascade
R___ Ratio
O___ Override(7)
_PID PID control
_ONF On/Off control
_PIF PID/OnOff control
_VP1 VP without feedback
_VP2 VP with feedback
Process inputs
(Input type)
X
None
J
J Thermocouple
K
K Thermocouple
T
T Thermocouple
L
L Thermocouple
N
N Thermocouple
R
R Thermocouple
S
S Thermocouple
B
B Thermocouple
P
Platinell II
C
C Thermocouple
Z
RTD/Pt100
A
4-20mA linear
Y
0-20mA linear
W
0-5Vdc linear
G
1-5Vdc linear
V
0-10Vdc linear
Custom downloads
Q
Custom curve
D
D thermocouple
E
E thermocouple
1
Ni/Ni18%Mo
2
Pt20%Rh/Pt40%Rh
3
W/W26%Re
(Engelhard)
4
W/W26%Re
(Hoskins)
5
W5%Re/W26%Re
(Engelhard)
6
W5%Re/W26%Re
(Bucose)
7
Pt10%Rh/Pt40%Rh
8
Exergen K80
I.R pyrometer
Analogue input
XXX None
P2- PV Loop 2
P3- PV Loop 3
S1- SP Loop 1
S2- SP Loop 2
S3- SP Loop 3
A1- Aux. PV Loop 1
A2- Aux. PV Loop 2
A3- Aux. PV Loop 3
L1- Ratio Lead PV Loop 1
L2- Ratio Lead PV Loop 2
L3- Ratio Lead PV Loop 3
Input range
Select third digit from
table 1
Table 1
A
4-20mA linear
Y
0-20mA linear
W
0-5Vdc linear
G
1-5Vdc linear
V
0-10Vdc linear
Slot function
XXX Unconfigured
1-- Loop no. 1
2-- Loop no. 2
3-- Loop no. 3
Single relay, triac or
logic
-HX Heat
-CX Cool
Dual relay or triac
-HC PID Heat & Cool
-VH VP Heat
_VC VP Cool
-AA FSH & FSH
-AB FSH & FSL
-AC DH & DL
-AD FSH & DH
-AE FSL & DL
-AF FSL & FSL
-AG FSH & DB
-AH FSL & DB
-AJ DB & DB
HHX Heat output for
loops 1 & 2
P12 Prog events 1 & 2
P34 Prog events 3 & 4
P56 Prog events 5 & 6
P78 Prog events 7 & 8
Triple logic output
-HX CH1 Heat
-CX CH1 Cool
-HC CH 1 Heat, CH2 Cool
HHX Heat output for loops
1&2
HHH Heat output for loops
1, 2 & 3
DC outputs
-H- PID Heat
-C- PID Cool
-TPV retransmission
-S- SP retransmission
For output range select third
digit from table 1
Precision PV input
-PV PV input module
-PA Aux PV input (8)
-PL Ratio lead input
Analogue input
-R- Setpoint
For input range select third
digit from table 1
Aux. & lead PV inputs
-L- Ratio lead input
-B- Aux. PV input
For input range select third
digit from table 1
Potentiometer input
-VF VP heat feedback
-VE Cool feedback
-RS Remote SP
General notes:
1. Loop 1 defaults to main PV input on
microboard. Loop 2 and 3 PV inputs must
be fitted in I/O slots 3 or 6, or be assigned
to the analogue input.
2. Alarm configuration refers to loop alarms.
One selection is allowed per loop.
Additional alarms are available for the
user to configure.
3. Thermocouple and RTD inputs assume
sensor min and max values with no
decimal point.
4. Linear inputs are ranged 0-100%, no
decimal point.
5. Temperature units will be °C, unless
ordered by the USA where °F will be used.
6. Remote setpoints assume min &
max ranges.
7. VP1 or VP2 not available with
Override function.
8. For Cascade and Override inputs
only.
Quick start order code
SVP1 - SPID - SPID - K - Z - A - S1A - 1VH - 2PV - 2HV - 3HC - 3PV
This code configures the hardware specified above:
Loop 1: Valve position control, Type K input, Heat VP output in slot 1, 4-20mA remote setpoint input
Loop 2: PID control, RTD input in slot 3, 0-10Vdc Heat output in slot 4.
Loop 3: PID control, 4-20mA input in slot 6, Logic heat/cool output in slot 5.
2200L Series
PID Temperature Controllers
Ideal for
· plastic extrusion
· ovens
· chillers and cold stores
Specifications
Available in 1/16, 1/8 DIN panel sizes the 2200L temperature controllers
are simple, fixed build versions of the standard 2200e series controllers
offering more cost effective solutions to OEM customers.
Eurotherm’s advanced control techniques give stable ‘straight line’
temperature control. Unique features include: power feedback which
stabilises the controlled temperature against supply voltage changes and
dedicated cooling algorithms which ensure optimum control of fan and
water cooled systems.
Simple operation is achieved using intuitive display formats and tactile
buttons.
Dimensions (mm):
Model 2216L: 48W x 48H x 150D
model 2208L: 48W x 96H x 150D
Supply voltage:
85-264Vac, 10.0watts maximum
Operating ambient:
0-55°C, 0-90%RH non-condensing
Inputs:
As per the ordering code
Output ratings:
Rear terminal connections
Model 2216L
Relay: 2A, 264Vac maximum
Logic: 18Vdc, 20mA
Model 2208L
Panel sealing:
Model 2216L: IP65
1A
Heating
Output
Model 2208L: IP65
L
Line
N
Neutral
or Logic
1B
Data sheet:
HA026153
Earth
LA
Cooling
Output
1A
Heating
Output
or Logic
1B
Alarm
Output
LC
Common
L
Line
AA
N
Neutral
Alarm
AB Output
Earth
AC
2A
Cooling
Output
Standby
or Logic
2B
Setpoint 2
LB
2A
or Logic
2B
VI
VI
3A
V+
Sensor
V+
Input
3B
Sensor
Input
T/C
V-
T/C
Pt100
V-
Pt100
Ordering codes
Model
Number
Control
Supply
Voltage
Heating
Output
Cooling
Output
Alarm
Output
Manual
Sensor
Input
Setpoint
Min
Setpoint
Max
Units
H
Model Number
2216L 1/16 DIN Controller
2208L 1/8 DIN Controller
Supply Voltage
H
85-264Vac
Heating Output
Control
C
N
PID Controller
On/off Controller
X
1
2
Not fitted
Logic
Relay
Cooling Output
X Not fitted
Relay output
A Linear cooling
B Fan cooling
C Water cooling
Logic output
D Linear cooling
E Fan cooling
F Water cooling
Alarm Output
X
1
2
Not fitted
High and low alarms
Deviation band
Manual
X
ENG
FRA
GER
NED
SPA
SWE
ITA
No manual
English
French
German
Dutch
Spanish
Sweden
Italian
Sensor Input
Sensor Inputs
J
J Thermocouple
K K Thermocouple
T T Thermocouple
L L Thermocouple
N N Thermocouple
Z RTD/PT100
Units
C
F
Celsius
Fahrenheit
Setpoint Min
Min
-210
-200
-200
-200
-250
-200
°C
Setpoint Max
Max
1200
1372
400
900
1300
850
Example ordering code
2208 - C - H - 1 - A - 1 - ENG - K - 0 - 1000 - C
2208L, Controller, 85 to 264Vac, Logic heating, Relay linear cooling, High & Low alarm relay, English manual,
Type K thermocouple, 0 to1000°C