Specifier Sheet
Specifier’s guide
4.2 Control panels and repeater panels
FXP5000 series Conventional control panel
“Contemporary
and compact panel
design that provides
a solution to any
conventional system
requirement”
The new FXP5000 series of conventional control panels
is currently available in a 16 zone version. The panel
features an array of user friendly features. The attractive
flush or surface mountable plastic enclosure, with metal
back box, has been designed through intensive voice
of the customer research to provide ample space for
termination of cables.
The FXP50016 comes with a zonal relay card as standard
allowing outputs to be switched on a by zone basis.
Features and benefits
•
•
•
•
•
•
Zonal relay card as standard
One man test facility
Non latching zone feature
Class change input
Fire and fault relays
Discreet enclosure
• Supplied complete with battery for 24 hour standby
Compatible repeater panel
The FXP5000 series includes a repeater panel
(FXP5000RP) which is compatible with the standard
16 zone panel. Specifically designed for ease of
installation, it requires only 2 interconnecting wires
from the main panel, saving material cost and labour
time.
No. of zones
Detectors per zone
No. of alarm circuits
Zonal relay card
FXP50016
16
30
4

EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©February 2015
Specifier’s guide
4.2 Control panels and repeater panels
Technical specification
Code
FXP50016
Description
16 zone control panel
Standards
EN54 Pt2 1998, A1:2006,
EN54 Pt4 1998, A1:2002 + A2:2006
Specification
Number of zones
16
Detectors per zone
30
Number of alarm circuits
4
Alarm circuit load
400mA per circuit, 1.6A total
End of line devices
Detection circuits: EOLM-1
monitoring unit Alarm lines: 6.8KΩ
resistor
Auxiliary fire signal/fault output
1A 24V dc single pole changeover
contacts
Auxiliary dc output
50mA
Repeater port
Yes
Mains input voltage
230V ac -15% +10%
System operating voltage
24V dc
Standby duration
24 hours
Battery (sealed lead acid)
2 x 4Ah
Recharge period
24 hours
Environmental
Operating temperature
-5°C to +40°C
Humidity (non condensing)
0 to 75% RH
Physical
Construction
Polycarbonate housing & metal back
box
Dimensions (H x W x D)
Surface: 276mm x 375mm x 136mm
Cut-out: 232mm x 335mm x 96mm
Weight
6.8kg
Ingress protection
IP30
Cable entry
Top: 12x20mm entries with blanking
plugs
Rear cable entry aperture
Dimensions
W2
D1
D2
H1
H2
W1
Description
16 Zone*
H1 (mm)
W1 (mm)
D1 (mm)
H2 (mm)
W2 (mm)
D2 (mm)
Total height
Total width
Total depth
Back box
height
Back box
width
Back box
depth
276
375
136
232
335
96
*Repeater panel dimensions same as 16 zone control panel
EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©February 2015
Specifier’s guide
4.2 Control panels and repeater panels
System functionality
Detection capacity
1.
Normal and supervisor mode facility. Supervisor mode protected
by 4 digit security code to prevent unauthorised use
1.
Up to 30 detectors per zone. End of line monitoring devices must
be fitted and are supplied as standard.
2.
Supervisor mode provides access to test mode, where a one shot
weekly test facility can be initiated by the user. When in operation,
the user has a period of time in which to put a call point into fire
condition, after which the system automatically resets and returns
to normal mode
2.
Detector circuits are monitored for open circuit, short circuit and
detector removal.
Commissioning walk test feature permits the system to be
easily tested after installation and prior to handover. The panel
automatically resets and returns to normal operation after a
detection device has been tested. Each device can then be tested
in turn via the same procedure
1.
Four separate alarm lines - 400mA maximum load per line.
2.
Alarm lines are monitored for open circuit and short circuit faults.
Supervisor mode also provides facility to disable the following for
maintenance or other purposes:
1.
Repeater matches the style and appearance of the main control
panels
• Each detection zone independently
2.
Facility for signalling to the Repeater panel provided as standard
• The alarm circuits
3.
Repeater requires only a single pair of wires to receive signals
from the main control panel, plus local mains power supply,
reducing the cost of installation
4.
Displays essential information at other key locations in a large
building/site
3.
4.
5.
Non-latching zone facility is available as standard and can be
programmable via Dil switches located on the display board
User interface
1.
Stylish and compact panel with 6 touch button keypad control of
all functions and LED indication
2.
Simple one-shot weekly test with auto-reset facility
3.
Comprehensive power, fire, and fault LED indicators and integral
piezo buzzer for on-board fire or fault indication
4.
Battery high/low voltage alarm facility
5.
Log book storage facility in front panel
Alarm capacity
Repeater panel
• Zone fire or fault conditions
• Zone or alarm lines in test mode
• Zone or alarm lines in disabled mode
• Fault isolations and test mode for control outputs
Interface options
1.
Class change input facility. Terminals provided for switching of
alarm circuits to indicate school/college class change
1
1
2
2
3
EOLM-1
3
2.
2 x1A 24V DC relays for Fire and Fault are available for remote
signalling
3.
Auxiliary 24V DC output power supply provided as standard on all
panels
6K8
Resistor
6K8
Resistor
1
1
2
2
3
EOLM-1
3
Volt free
normally
open
contacts
230VAC
EOLM-1
OUTPUT
EOLM-1
Standard panel connections
L
N
E
Mains
24V 0V
NO C NC NO C NC
External
Fire
Fault
Power Class
Circuit
Circuit
Supply Change
Out
- 1+
E
- 2+
-
+
1
Sounder Circuits
E
-
+
2
E
-
+ E - + E
3
4
Zone Circuits
3 and 4
(4 Zone Version Only)
Zone Circuits
1 and 2
1
1
2
3
2
EOLM-1
3
6K8
Resistor
1
2
Volt free
normally
open
contacts
230VAC
L
N
E
EOLM-1
3
To
Repeater
Panel
EOLM-1
OUTPUT
6K8 Resistors
24V 0V
NO C NC NO C NC
External
Power Class
Fire
Fault
Supply Change
Circuit
Circuit
Out
- 1+
- 2+
- 3+
To EOLM-1
- 4+
- 1+
- 2+
- 3+
- 4+
- 5+
- 6+
- 7+
- 8 + TX+ TX- - 9 + - 10
Zone Circuits
9 to 16
(16 Zone
Panel Only)
Repeater
Mains
1
2
3
Zone Circuits
1 to 8
Sounder Circuits
Catalogue numbers
-
+
-
Description
FRE
-
+
+
Code
Fault
FPE
16 zone control panel
FXP50016
Repeater panel
Fire alarm system log book
FXP5000RP
-
+
-
+
-
+
-
+
AUX 1 AUX 2 AUX 3 AUX 4
-
+
-
+
MFALOG
-
+
-
+
-
+
-
+
-
+
-
+
AUX 1 AUX 2 AUX 3 AUX 4 AUX 5 AUX 6 AUX 7 AUX 8
EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©February 2015