Lutron Phase-Adaptive Power Module Power Modules 369356d 1 10.14.16 Phase-Adaptive Power Module Description •Provides capability for a zone on a GRAFIK Eye control unit (or other product) to dim a fully loaded circuit of lighting. •May be used to control incandescent, electronic lowvoltage, magnetic low-voltage, and neon / cold cathode lighting sources, as well as Lutron Tu-Wire fluorescent dimming ballasts. •Automatically selects leading-edge or trailing-edge dimming for low-voltage transformers. •Provides power and dimming for one zone. •Up to 3 power modules may be wired on a single GRAFIK Eye zone. •Models available for 120 V~ control power. •Models available for 120 V~ or 120 - 277 V~ load power. •Not for use with non-dim loads. Works with 120 V~ versions of: •GRAFIK Eye QS control units 1 •GRAFIK Eye 3000 Series control units 2 •LP, LCP, and GP dimming panels 2 •HomeWorks and HomeWorks QS remote power panels** Models and Capacities Model Number PHPM-PA-DV-WH PHPM-PA-120-WH 1 2 Control Power 120 V~ 120 V~ Load Power 120 –277 V~ 120 V~ Capacity 16 A 16 A Set to power module load type Set to incandescent load type ® Job Name: Job Number: S P E C I F I C AT I O N S U B M I T TA L Model Numbers: Page Lutron Phase-Adaptive Power Module Power Modules 369356d 2 10.14.16 Specifications Regulatory Approvals •UL® Listed • CSA certified • NOM certified •Complies with requirements for use in other spaces used for environmental air (plenums) per NEC® 2014 300.22(C)(3) Power •Control voltage: 120 V~ •Load voltage: 1 20 V~ only for PHPM-PA-120-WH 120 –277 V~ for PHPM-PA-DV-WH •Capacity: F ull 16 A 120 V~: 1920 W 120 –277 V~: 1920 – 4432 W •Frequency: 50 / 60 Hz, phase-to-neutral. •Load (output) power: Phase independent of control device / control voltage. Sources / Load Types •Operates these sources with a smooth continuous Square Law dimming curve: – Incandescent (tungsten) – Halogen – Magnetic low-voltage transformer (iron core) – Electronic (solid-state) low-voltage transformer (must be manufacturer approved for reverse-phase control dimming) – Neon / Cold cathode – Lutron Tu-Wire fluorescent dimming ballasts • Incandescent and electronic low-voltage sources may be controlled on the same circuit / control zone. Up to 30% of the unit’s capacity may be used for incandescent lighting. • Incandescent and magnetic low-voltage sources may NOT be controlled on the same circuit / control zone. •PHPM-PA not for use with non-dim loads. Use switching power module (PHPM-SW-DV-WH) for nondim loads. •Minimum load on power module is 10 W. •Output must be directly connected to the load. Load side switching is not recommended. ® Job Name: Job Number: S P E C I F I C AT I O N S U B M I T TA L Model Numbers: Key Design Features •Automatically selects between forward phase / leading edge (e.g., magnetic low-voltage) and reverse phase / trailing edge (e.g., electronic low-voltage) dimming / output based on connected load. •Patented RTISS circuitry compensates in real time for incoming line voltage variations: Compensates for +/-2% change in RMS voltage / cycle and +/-2% Hz change in frequency/second. •Provides air-gap off. •Module protects itself during most temporary overcurrent and over-voltage conditions. •Two LEDs on front of unit provide diagnostic information (visible when faceplate is removed). Terminals •Each terminal accepts up to two 12 AWG (2.5 mm2) wires. Environment •32 °F to 104 °F (0 °C to 40 °C). Relative humidity less than 90% non-condensing. •Indoor use only. •Maximum heat output of module: 135 BTU / hour. Mounting •Surface- or recess-mount. Page Lutron Phase-Adaptive Power Module Power Modules 369356d 3 10.14.16 Dimensions All dimensions shown as: in (mm) 1.2 (30.5) 1.4 (35.5) 5.1 (129.5) 6.3 (160) ® Job Name: Job Number: S P E C I F I C AT I O N S U B M I T TA L Model Numbers: Page Lutron Phase-Adaptive Power Module Power Modules 369356d 4 10.14.16 Mounting •Mount in 2-gang U.S. wallbox 3.5 in (89 mm) deep or 4 in x 4 in (102 mm x 102 mm) junction box 2.1 in (53 mm) deep. •Indoor use only. •This device generates heat; mount only where ambient temperature is 32 °F to 104 °F (0 °C to 40 °C). •Mount with arrows facing up to ensure adequate cooling. Mount to 2-gang U.S. wallbox •Allow 4.5 in (114 mm) above and below unit and between faceplates when mounting several in a vertical layout. •Mount so line (mains) voltage wiring is at least 6 ft (1.8 m) from sound or electronic equipment and wiring. •Mount within 7° of true vertical. Mount to 4 in x 4 in (102 mm x 102 mm), 2.1 in (53 mm) deep U.S. junction box Mount to 4 in x 4 in (102 mm x 102 mm), 2.1 in (53 mm) deep U.S. junction box with barrier (for 277 V~ model if required by local electrical code) Barrier ® Job Name: Job Number: S P E C I F I C AT I O N S U B M I T TA L Model Numbers: Page Lutron Phase-Adaptive Power Module Power Modules 369356d 5 10.14.16 Wiring •Pull 12 AWG (2.5 mm2) copper (Cu) wires [167 °F (75 °C) minimum] for input power and load circuit. •Strip 1/2 in (12 mm) insulation from wires before connecting. •Run separate neutral for load circuit - no common neutrals. •May be used with GFI breaker protected loads. Load circuit wiring (from GFI breaker to power module to load) must be run in its own non-metallic conduit, or nuisance tripping may occur. Maximum 100 ft (30.5 m) between power module and load. •May be used with AFI breaker protected loads. Maximum load on AFI circuit is 1000 W. Exceeding 1000 W may cause nuisance tripping of AFI breaker. Single Power Feed The power module may be on the same circuit as the control unit only if the total load does not exceed the rating of the breaker. GRAFIK Eye QS Circuit breaker 120 V~ 1 2 3 4 5 6 L N L/H N Wire to appropriate zone H/L N Load 120 V~ Zone in Control Neutral DH Legend L /H Line / Hot NNeutral SH Switched Hot DH Dimmed Hot Ground Not Used ® Job Name: Job Number: S P E C I F I C AT I O N S U B M I T TA L Model Numbers: Page Lutron Phase-Adaptive Power Module Power Modules 369356d 6 10.14.16 Wiring (continued) Multiple Power Feeds The load breaker may be on a different phase than the control breaker. GRAFIK Eye QS 1 2 3 4 5 6 L N N 120 V~ L/H Wire to appropriate zone Control breaker Load breaker H/L N L/H N Load wiring 1 Load Zone in Control Neutral DH Legend L / H Line / Hot NNeutral SH Switched Hot DH Dimmed Hot Ground Not Used 1 Load feed: 120 V~ for PHPM-PA-120-WH; 120 – 277 V~ for PHPM-PA-DV-WH ® Job Name: Job Number: S P E C I F I C AT I O N S U B M I T TA L Model Numbers: Page Lutron Phase-Adaptive Power Module Power Modules 369356d 7 10.14.16 Wiring (continued) Multiple Power Modules to a Single GRAFIK Eye Zone Shown with separate feeds for control and loads. All breakers must be turned off prior to installing or servicing the modules. Up to 3 power modules may be wired to a single zone. GRAFIK Eye QS 1 2 3 4 5 6 L N Wire to appropriate zone N L/H 120 V~ Control breaker Load breaker L/H H/L N N Load wiring 1 for Power Module #1 Load Zone in Control Neutral DH Load breaker L/H H/L N N Load wiring 1 for Power Module #2 Load Zone in Control Neutral DH Load breaker H/L N L/H N Load wiring 1 for Power Module #3 1 Load Zone in Control Neutral DH Load feed: 120 V~ for PHPM-PA-120-WH; 120 – 277 V~ for PHPM-PA-DV-WH ® Job Name: Job Number: S P E C I F I C AT I O N S U B M I T TA L Model Numbers: Page Lutron Phase-Adaptive Power Module Power Modules 369356d 8 10.14.16 Wiring (continued) Wiring a Power Module to an LP, LCP, GP, or HomeWorks Panel Up to three 3-wire fluorescent power modules may be wired to an output of a 120 V~ LP or LCP panel. The load type for the output must be set as Eco-10 or Hi-lume fluorescent load type on the panel’s circuit selector (for an LP or GP panel), controller (for an LCP panel), or HomeWorks software (for a HomeWorks panel). Wire to appropriate output Load wiring1 L/H N H/L N Load DH Zone In Control Neutral Dimmed Hot (1) 14 to 10 AWG 2 (2.0 to 4.0 mm ) (1) 14 to 10 AWG (2.0 to 4.0 mm2) Neutral DH DH DH DH H N N N N N Load feed: 120 V~ if used with PHPM-PA-120-WH power module; 120 – 277 V~ if used with PHPM-PA-DV-WH power module 1 )Lutron, Lutron, Eco-10, GRAFIK Eye, Hi-lume, HomeWorks, and Tu-Wire are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts. © 2016 Lutron Electronics Co., Inc. UL and the UL logo are trademarks of UL LLC. ® Job Name: Job Number: 120 V~ Branch Circuit Breakers Neutral Lug Power (Line / Hot) (3) 14 to 2/0 AWG (2.0 to 70 mm2) S P E C I F I C AT I O N S U B M I T TA L Model Numbers: Neutral (1) 14 to 2/0 AWG (2.0 to 70 mm2) Page
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement