AnaLASER® II Detector
Effective: August 2002
AnaLASER® II Detector
High Sensitivity Smoke Detector (HSSD®)
89.250
FEATURES
•
Air Sampling Smoke Detector for Early Warning
Applications
• Two Versions Available: “Standard” Detector and
“Ultra” Detector
STANDARD DETECTOR
• Thousands of Times More Sensitive than Conventional Smoke Detectors
• Programmable Sensitivity Range of 0.00075%/
ft. to 0.3%/ft. Obscuration
ULTRA™ DETECTOR
• Recommended for Cleanroom Applications
• Five Times More Sensitive than the Standard
Detector
• Programmable Sensitivity Range of 0.00015%/
ft. to 0.03%/ft. Obscuration
• Laser Particle-Counting Technology
• Uses Particle Size Discrimination—No Filter
Required
• Up to 20,000 Sq. Ft. of Coverage
• Well Suited for High Air-Flow Environments
• Two Programmable Alarm Levels and Two
Programmable Pre-Alarm Levels
• Three Color Status LED
• Optional LCD Display Module
• Configuration and History Data Stored in NonVolatile Memory
• History Buffer Stores Up to 28 Days of Smoke
History
• Advanced Signal Processing Features
• Full Configuration Using LaserNET™ Software
• Modular design for fast and easy servicing
NETWORKING OPTIONS
• Use with Optional Intelligent Interface Module for
Networked Systems of up to 127 Detectors
• Use with Optional AnaLASER® Interface Module
for FenwalNET™ 2000 Addressable Loop Systems
LISTINGS AND APPROVALS
• UL 268 Listed for Open Area Protection and
Special Applications
• UL 268A Listed for Duct Detection
• FM Approved
• ULC Listed for Open Area Protection and Special
Applications
• CSFM Listed 7259-1076:167
• NYC MEA Approved MEA 60-02-E
Figure 1. AnaLASER II Detector with
Optional Display Module
Figure 2. AnaLASER II Detector
DESCRIPTION
The AnaLASER® II High Sensitivity Smoke Detector consists of a laser particle counter detector head, a high-efficiency fan module and a termination board. One AnaLASER
II Detector, when connected to a pipe network designed
using “SNIFF” Version 3 software, provides coverage for
an area up to 20,000 sq. ft.
The AnaLASER II Detector is available in two sensitivity
ranges. The standard AnaLASER II Detector (with a dynamic
sensitivity range of 0.00075% to 0.3%/ft.) is designed for
early warning smoke detection applications such as telecommunications facilities, data processing facilities, museums and warehouses. For cleanroom applications where
the environment must be virtually free of air particulate,
Fenwal developed the Ultra™ AnaLASER II Detector that
is five times more sensitive than a standard high sensitivity
smoke detector. The Ultra AnaLASER II Detector has a
sensitivity range of 0.00015% to 0.03%/ft.
WHY HIGH SENSITIVITY SMOKE
DETECTION?
AIR SAMPLING PIPE NETWORK
The AnaLASER II Detector’s laser particle counter detects
particles of combustion at levels of obscuration as low as
0.00015%/ft. This is sensitive enough to detect invisible
products of combustion such as the outgassing of plasticizers from overheating PVC wire insulation and electrical components, or small changes in the ambient level of obscuration
during the incipient stage of a fire.
When a combustible material reaches it’s ignition temperature, the combustion becomes self-sustaining and is called
a fire. At temperatures much below the ignition temperature, chemical reactions generate airborne particles. This
is typically called the incipient stage of a fire and is followed
by visible smoke, flame and finally an intense heat stage.
Detection during the incipient stage allows time for corrective action, possibly preventing an escalation of the fire condition, and thus minimizing fire damage.
VISIBLE
SMOKE
INCIPIENT STAGE
FLAME
The air sampling pipe network is a system of pipes extended
into the protected area with strategically placed sampling
holes. The UL Listed/FM Approved “SNIFF” Version 3 computer program is used to dynamically balance the pipe network. The “SNIFF” program allows greater flexibility in pipe
configuration and balances the pipe network to insure equal
sensitivity at each sampling hole. Each sample hole may
be considered an equivalent spot-type detector with a maximum coverage of 900 sq. ft. to provide UL Listed Open
Area Protection (see datasheet 89.256).
The AnaLASER II product line offers an array of air sampling network accessories such as a sampling point, capillary tube rolls, sampling point, port and pipe labels.
INTENSE
HEAT
% OBSCURATION
Figure 4. Sampling Point
AMBIENT SMOKE
TIME
Figure 3. AnaLASER II Detects Ambient Smoke in the
Incipient Stage of Fire
PARTICLE SIZE
DISCRIMINATION = NO FILTER!
The AnaLASER II Detector uses a high-efficiency centrifugal fan to draw air continuously from the protected area,
into a piping network and through the detector head, without filtration or flow restriction. As a result, filter maintenance
and loss of sensitivity due to filter clogging is eliminated.
Smoke concentration is determined by counting the number of discrete particles of a specific size in a given time
period. The Detector’s particle size discrimination feature
allows only a specific range of particle sizes (between 0.01
and 10 microns) to be measured and counted as products
of combustion. Anything above or below this range is generally ignored and does not contribute to smoke signal calculations. This discrimination band corresponds to the center
of the range of all particles of combustion. Dust particles,
which are typically larger than 10 microns, are ignored.
Figure 5. Sampling Point with Capillary Tube
FEATURES
DISPLAY OPTIONS:
The AnaLASER II Detector has two display options: a status LED faceplate or a Display Module. The status LED
faceplate is a plastic molded insert with a tri-color LED that
indicates an Alarm, Pre-Alarm or Trouble condition. The
standard configuration of an AnaLASER II Detector has an
installed status LED faceplate. The LED reports the following conditions:
CONTINUOUS GREEN..................
FLASHING GREEN........................
CONTINUOUS YELLOW................
FLASHING RED............................
CONTINUOUS RED.......................
NORMAL
AUTO-SETUP™
TROUBLE/ISOLATED
PRE-ALARM
ALARM
For applications where a user interface at the Detector is
necessary, Fenwal offers an optional Display Module with a
backlit LCD screen. The Display Module allows the user to
browse through more detailed information such as protected
area smoke levels, sampling pipe airflow rate and selected
configuration settings. The optional display module also allows limited detector control functions such as reset, test
and isolate. The Display Module can be integrated into the
AnaLASER II Detector or externally mounted away from the
Detector (see datasheet 89.251).
FIRE ALARM PANEL INTERFACE:
The AnaLASER II Detector was designed with the flexibility
to interface with any fire alarm control panel. There are four
different configurations to choose from depending on the
type of control panel and the number of Detectors in the
system.
The Intelligent Interface Module (IIM) was designed to interface a large AnaLASER II Detector network to a
FenwalNET™ 2000 control panel. The IIM is an easy-toinstall module that plugs into the I/O motherboard assembly inside the FN-2000. Up to 127 AnaLASER II Detectors
can be networked together with an IIM. A computer running
LaserNET™ Version 3 software can communicate with the
IIM, either with a local computer or from a remote computer using a modem. This allows all networked AnaLASER II Detectors to be monitored and configured from a
central location and saves on installation and maintenance
costs (see datasheet 89.253).
For smaller networks connected to a FN-2000 control panel,
the AnaLASER II Detector can be connected to the addressable loop of the FN-2000 using an AnaLASER Interface
Module (AIM). The AIM is a circuit board that plugs into an
AnaLASER II Detector. With an AIM, the AnaLASER II Detector operates as one of up to 255 SmartOne® devices on
the addressable loop (see datasheet 89.252).
The AnaLASER II Detector can also interface to other fire
alarm control panels by using relay contacts inside the Detector. Each AnaLASER II Detector is equipped with six relays (Pre-Alarm 1, Pre-Alarm 2, Alarm 1, Alarm 2, Trouble,
and Isolate) which allows the Detector to directly interface
with the control panel.
Detectors that interface to a fire alarm control panel with
relays can also be networked together with a Stand-Alone
IIM. This allows up to 127 AnaLASER II Detectors to be
monitored and configured from a central location. The StandAlone IIM has the same features as the FN-2000 mounted
IIM except for the FN-2000 interface (see datasheet 89.254).
CONFIGURATION:
The AnaLASER II Detector is configured with LaserNET™
Version 3 software. To configure the Detector, a computer
running LaserNET software is connected via a programming cable to the RS-232 jack located on the side of the
Detector. LaserNET provides the ability to monitor, configure and download history from the Detector. The advanced
signal processing software features of the Detector allow
the response of the detector head to be tailored to the environment it is installed in. This provides the most sensitive
detection with a minimum of unwanted alarms (see
datasheet 89.255).
• Two Pre-Alarm and Two Alarm Levels – Programmable
in increments of 5% of the Detector’s selected output.
Alarm Level 2 and Pre-Alarm Level 2 are optional.
•
•
•
•
Day/Night Alarms – A second set of programmed alarm
levels is available for the night period which allows the
Detector’s response to be more sensitive during the
day.
Alarm Delays – Programmable from 0 to 60 seconds
for each alarm level. The delays can be used to eliminate unwanted alarms caused by transient conditions.
Alarm Latching – An option which allows alarm conditions to remain latched until reset, or to automatically
reset after a programmable delay of 0 to 60 minutes.
Smoke Signal Averaging – An option that averages the
smoke level over a programmable 2, 4, or 8 second
period. This may be used to eliminate spikes in the
smoke level caused by transient smoke.
AUTO-SETUP™ FEATURES:
Automatically sets the AnaLASER II Detector’s optimal
alarm sensitivity threshold at the time of installation. The
Auto-Setup learning time period can be set for fifteen minutes to two weeks.
HISTORY REPORTING FEATURES:
• Smoke Level History – A powerful diagnostic feature of
the Detector. Up to four weeks of date and time stamped
smoke history (40,320 data collection points) may be
stored in the Detector. History sampling rate is programmable from 1 to 60 seconds. Using LaserNET software,
this history can be retrieved and graphically displayed,
printed or stored to disk.
• Event History – Stores up to 128 events such as alarm
or trouble activations, configuration changes or operator actions. Using LaserNET software, this history can
be retrieved and displayed, printed or stored to disk.
This feature aids in the analysis of trouble or alarm incidents.
EASE OF INSTALLATION AND MAINTENANCE:
The AnaLASER II Detector is designed for ease of installation and maintenance. The Detector’s main components
can be serviced without removing the Detector’s enclosure,
conduit, inlet or exhaust pipe. The Detector can be surface-mounted by four #10 mounting holes in the back of
the Detector or by an optional flush mount trim ring.
POWER SUPPLY OPTIONS:
The AnaLASER II Detector has four different power supply
configurations. The Self-Contained Power Supply is designed to provide 24 Vdc power to a Detector from 120 or
240 Vac (see datasheet 89.258). For systems with multiple
AnaLASER II Detectors, a Multi-Zone Power Supply can
provide 24 Vdc power for up to eight Detectors from 120 or
240 Vac. The Multi-Zone Power Supply is also available
with a 48 Vdc to 24 Vdc power converter (see datasheet
89.257).
Detectors can also have 24 Vdc power supplied by the fire
alarm control panel or any listed or approved power supply.
TECHNICAL SPECIFICATIONS
D E S C R IP T ION
Detector Sensi ti vi ty Range
S P E C IF IC AT ION
Standard Detector: 0.00075%/ft. to 0.3%/ft. (0.0025%/m to 1%/m)
Ultra Detector: 0.00015%/ft. to 0.03%/ft. (0.0005%/m to 0.1%/m)
Maxi mum Coverage
20,000 sq. ft. (2000 sq. m)
Input Voltage
24 Vdc nomi nal (18 to 30 Vdc)
Standard Detector: 310mA standby, 342 mA alarm
Input Current
Ultra Detector: 395 mA standby, 427 mA alarm
Operati ng Temperature
Operati ng Humi di ty
Standard Detector: 32º to 120ºF (0º to 49º C)
Ultra Detector: 32º to 100ºF (0º to 38º C)
Standard Detector: 10 to 93% RH non-condensi ng
Ultra Detector: 10 to 70% RH non-condensi ng
Enclosure Rati ng
NEMA-1 (IP-31)
Fi ni sh
Li ght Grey Polycarbonate wi th Pai nted Steel Backbox
Di mensi ons
12.6" W x 8.98" H x 4.25" D (32.0 cm W x 22.8 cm H x 10.8 cm D)
Alarm & Pre-Alarm Relays
Four relays; each has normally open contacts, 2 Amp @ 28 Vdc, resi sti ve
Trouble Relay
Form C, 2 Amp @ 28 Vdc, resi sti ve (energi zed on power-up)
Isolate Relay
Opti onal: Form C, 2 Amp @ 28 Vdc, resi sti ve
Electri cal Connecti ons
18 to 12 AWG (0.75 to 2.5mm 2 ) wi ri ng to removable termi nal blocks
Servi ce Port Connecti on
RS232 communi cati ons wi th modular RJ12 jack. Requi res LaserNET Versi on 3 Software
Network Connecti on
Opti onal: RS485 communi cati ons - 1 pai r i n/1 pai r out, 7 posi ti on address di p swi tch
Remote Di splay Connecti on
Opti onal: 1 pai r RS485 communi cati ons, 1 pai r power
Power Supply Supervi si on Input
Opti onal: Moni tors normally closed contact on power supply
Ai r Inlet Port
3/4" NPT threaded
Exhaust Port
Si de exhaust, opti onal rear exhaust wi th suppli ed adapter, opti onal 1" NPT threaded exhaust pi pe connecti on wi th suppli ed adapter
Standard Detector: 8.0 lb. (3.6 kg)
Wei ght
Ultra Detector: 8.2 lb. (3.7 kg)
ORDERING INFORMATION
4.25 in
108 mm
DIMENSIONS
8.98 in
228 mm
TOP
LEFT
SIDE
RIGHT
SIDE
FRONT
12.6 in
320 mm
BOTTOM
TM
R
Protection Systems
LICO Electronics GmbH, www.mess-regeltechnik.at, office@lico.at
40 MAIN , STRE ASHL ND, MA 0172
TEL: (508) 1-2 AX: F (508) 8 1- 920
.fenwal ir com
C OMP ON E N T
PAR T N U MB E R
AnaLASER II Detector, 0.00075 - 0.3%/ft
(0.0025 - 1%/m)
89-300001-001
AnaLASER II Ultra Detector
0.00015 - 0.03%/ft (0.0005 - 0.1%/m)
89-300002-001
Flush Mount Tri m Ri ng for Detector
89-300005-001
Sampli ng Poi nt Ki t, pkg. of 25: Consi sts of (25)
each: Sampli ng Poi nt, Male 1/2" NPT Capi llary Tube
Adapter, Female 1/2" NPT Capi llary Tube Adapter,
Label for Sample Poi nt
89-300030-001
Capi llary Tube, 3/8" - 250 ft Roll
89-300031-001
Sampli ng Poi nt Label - Roll of 100
89-300032-001
Sampli ng Port Label - Roll of 100
89-300032-002
Sampli ng Pi pe Label - Roll of 100
89-300032-003
AnaLASER II Installati on, Operati on and
Mai ntenance Manual
89.200
This literature is provided for informational purposes only. KIDE-FENWAL,INC.assumes no
responsibility for the product's suitability for a particular application. The product must be
properly applied to work correctly. If you need more information on this product, or if you have
a particular problem or question, contact:
KIDlEep-AFhsoNnLCaW.:,d0(517M82) Te -
89.250
08/02
©2002 Kide-Fenwal, Inc.
PrintedU.SA