Features
General
Enjoy the "Comfort" series by "COOLINE Air Conditioners"
The "Comfort" series of Packaged units (PQ) is another perfect illustration of how "COOLINE Air Conditioners" can simplify the air conditioning business for Clients, Consultants and Contractors. It is a clear statement for all that your life will be more "Comfortable" when you use the (PQ) series.
Some of the Salient Features
Quality/Reliability:
Using proven reliable components, the (PQ) "Comfort" series is designed, assembled and produced to meet the highest quality standards. It will operate to the satisfaction of the End User years after years. That translates into peace of mind and sustained "Comfort".
Simple Selection/Design Integration:
The (PQ) series is conceived to be easily fitted into the system design. Its compact dimensions and optimized air flow performance will provide the designer with an added "Comfort" in the process of selecting and integrating the units in the overall design.
Simple Installation/Maintenance:
Connect the Power cables and the Control wiring (all located in one area), connect ducting using the built-in duct flanges, arrange for proper drainage, reach in for any part/component through wide ample service/access doors...Installation and Maintenance cannot be more
"Comfortable".
Ease of Operation:
Let the digital "Performex-1 TM " controller do all the thinking! Just set the desired temperature level and the "Performex-1
TM
" controller will take care of all the operating functions while monitoring any abnormal signal to prevent/protect the unit and its components from any damage...and ensuring the complete
"Comfort" for the occupants.
And on top of that, the (PQ) "Comfort" series comes with a host of useful features such as the different types of corrosion protection solutions for the coils, Fresh Air Damper and UV Flow
TM
for added
IAQ and "Comfort".
2
CONTENTS
Page
Features ................................................................................................................................................... 2
Model decoding ........................................................................................................................................ 4
Blower drive options ................................................................................................................................. 4
Standard specifications/options/accessories ......................................................................................... 5-7
General data .......................................................................................................................................... 8-9
Selection procedure ............................................................................................................................... 10
Cooling capacities ............................................................................................................................. 11-15
Electrical data .................................................................................................................................... 16-17
Fan performance data ....................................................................................................................... 18-22
Sound level data ................................................................................................................................ 23-28
Pressure drop/blower motor efficiency ................................................................................................... 29
Unit dimensions ................................................................................................................................. 30-32
Controls and sequence of operation .................................................................................................. 33-34
Typical schematic wiring diagram ...................................................................................................... 35-36
CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.
THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
3
MODEL DECODING
MODELS: PQ036 - PQ060 (DIRECT DRIVE MOTOR)
1& 2
BASIC
PQ
COOLINE
PACKAGED
UNIT
3, 4 & 5
NOMINAL
COOLING
CAPACITY
(MBH)
036
048
060
6
ELECTRICAL
SUPPLY
( V-Ph-Hz )
L
: 380/415-3-50
(4 WIRE)
7
BLOWER
MOTOR
Y
:1 HP ODP
(DIRECT DRIVE)
8
DRIVE
OPTIONS
W
: 0.75 HP ODP
(DIRECT DRIVE)
N
: DIRECT
DRIVE
9
HEATER OPTIONS
(kW/STAGE)
10
EVAPORATOR
COIL
11
CONDENSER
COIL
N
: NO HEATER
A
: 5/1
C
: 7.5 /1
D
: 10 /2
*
12
ACCESSORIES
J
:ALUMINUM
FIN
J
:ALUMINUM
FIN
K
: COATED
ALUMINUM FIN
K
: COATED
ALUMINUM FIN
L
:COPPER FIN
L
:COPPER FIN
N
: STANDARD UNIT
NOTE
:
*
– Applicable for PQ060 models only.
MODELS: PQ075 - PQ360 (BELT DRIVEN MOTOR)
1& 2
BASIC
PQ
COOLINE
PACKAGED
UNIT
3, 4 & 5
NOMINAL
COOLING
CAPACITY
(MBH)
075
6
ELECTRICAL
SUPPLY
( V-Ph-Hz )
L
: 380/415-3-50
(4 WIRE)
7
BLOWER
MOTOR
8
DRIVE
OPTIONS
090
100
R
: 1.5 HP ODP
Z
: 2 HP ODP
J
: ALT. I
K
: ALT. II
Z
: 2 HP ODP
E
: 3 HP ODP
120 E
: 3 HP ODP
150
E
: 3 HP ODP
G
: 5 HP ODP
180
210
240
300
360
G
: 5 HP ODP
J
: 7.5 HP ODP
J
: 7.5 HP ODP
J
: 7.5 HP ODP
L
: 10 HP ODP
L
: 10 HP ODP
M
: 15 HP ODP
9
HEATER OPTIONS
(kW/STAGE)
10
EVAPORATOR
COIL
11
CONDENSER
COIL
N
: NO HEATER
C
: 7.5 /1
D
: 10 /2
E
: 12/2
N
: NO HEATER
D
: 10 /2
E
: 12/2
F
: 15 /2
J
L
:ALUMINUM
FIN
:COPPER FIN
J
L
: ALUMINUM
FIN
K
: COATED
ALUMINUM FIN
K
: COATED
ALUMINUM FIN
: COPPER FIN
12
ACCESSORIES
N
: STANDARD UNIT
C
: STD. UNIT WITH
FRESH AIR HOOD &
MANUAL DAMPER
P
: STD. UNIT WITH
PDS
M
:STD. UNIT WITH
PDS, FRESH AIR
HOOD & MANUAL
DAMPER
N
: NO HEATER
E
: 12/2
F
: 15 /2
G
: 20 /2
N
: NO HEATER
F
: 15 /2
G
: 20 /2
H
: 25/2
N
: NO HEATER
G
: 20 /2
H
: 25/2
J
: 30/2
BLOWER DRIVE OPTIONS
MODEL
NUMBER
PQ075
PQ090
PQ100
PQ120
PQ150
PQ180
PQ210
PQ240
PQ300
PQ360
OPTION
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
HP
1.5
2
2
3
2
3
3
3
5
5
7.5
5
7.5
7.5
7.5/10
10
15
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
MOTOR
RPM
PULLEY
PITCH DIA.
(INCH)
2.7 - 3.7
2.7 - 3.7
2.7 - 3.7
3.1 - 4.1
2.7 - 3.7
3.1 - 4.1
3.1 - 4.1
3.1 - 4.1
3.7 - 4.7
4.8 - 6.0
3.7 - 4.7
4.3 - 5.5
3.7 - 4.7
4.3 - 5.5
4.3 - 5.5
4.3 - 5.5
4.3 - 5.5
4.3 - 5.5
4.3 - 5.5
5.5 - 6.9
BLOWER
SPEED RANGE (RPM)
MINIMUM
851
955
851
1096
699
977
737
881
813
941
725
891
766
891
663
843
725
843
692
848
MAXIMUM
1166
1309
1166
1450
958
1292
975
1166
1033
1176
921
1139
974
1139
848
1078
927
1078
886
1064
PULLEY
PITCH DIA.
(INCH)
4.6
4.1
4.6
4.1
5.6
4.6
6.1
5.1
6.6
7.4
7.4
7.0
7.0
7.0
9.4
7.4
8.6
7.4
9.0
9.4
APPROX. SPEED
CHANGE PER
PULLEY TURN
(RPM)
43
53
40
57
53
59
53
59
37
47
33
40
35
41
31
39
34
39
32
36
4
STANDARD SPECIFICATIONS
A. General
Packaged cooling or combination heating and cooling units suitable for mounting on the roof or ground. The packaged unit consists of reciprocating compressors, cooling coil, condenser coil, control wiring and interconnecting piping - all factory assembled and mounted on heavy gauge G-90 galvanized steel sheet press formed base, ready for field connection to utilities and ducts. The packaged unit is of rigid construction with holes provided in the base rails for overhead rigging. The unit is provided with an integral weather resistant control panel.
These units are rated and tested in accordance with ARI standard 210/ ARI 360.
B. Unit Enclosure
Panels are of heavy gauge, G-90 galvanized steel sheet with removable access panels, completely weatherized for outdoor installation and properly reinforced and brazed. Panels and access doors are provided for inspection and access for all internal parts. Enclosures are provided with adequately reinforced points of support for setting the unit. Steel sheet panels are zinc-coated and galvanized by the hot dip process of lock forming quality conforming to ASTM A 653 commercial weight G-90, followed by baked on electrostatic polyester dry powder coat paint, on all external panels.
C. Compressor
Compressors are hermetic reciprocating for PQ036 - PQ060 & PQ090 - PQ100 and hermetic scroll for all other models.
They are provided with all the standard controls and accessories necessary for safe operation. These are equipped with internal motor protector, factory installed crank case heater and rubber vibration isolator for quiet and efficient operation.
D. Air Cooled Condensing Section
1. The air-cooled condensing section is enclosed within the unit housing and consists of condenser coil, fan(s), electric motor(s) and inherently protected compressor(s). Inner grooved copper tubes with wall thickness of 0.0175 inches
(0.445 mm), mechanically bonded to enhanced louvered aluminum fins are standard for all condenser coils. Return bends have 0.022 inch thickness (0.56 mm). As an option, corrugated copper fins or enhanced coated alumi-
num fins may be provided.
Tube support sheets are galvanized steel, formed to provide structural strength.
2. Fans are propeller type, direct driven, upward discharge and provided with fan grille mounted on the casing.
3. Motors are totally enclosed air-over type with class F insulation. Inherent thermal protection is automatic reset type.
E. Evaporator Coil Section
1. All cooling coils are of enhanced louvered fins and inner grooved copper tubes with wall thickness of 0.0175 inches
(0.445mm), mechanically bonded to aluminum fins . Return bend has 0.022 inch thickness (0.56 mm). As option,
enhanced coated aluminum fins or corrugated copper fins may be provided
. Tube support sheets are galvanized steel, formed to provide structural strength.
2. Drain Pan: An insulated drain Pan made of G-90 galvanized steel is provided, for additional corrosion protection, mastic coated lining is provided as the surface.
3. Insulation: Insulation is supplied in adequate density and thickness for all units to prevent condensation from forming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deterioration and erosion from air currents.
F. Evaporator Fan
PQ036 - PQ060:
Evaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/pressure using direct drive motors. These fans are statically / dynamically balanced in the fan housing during final assembly. Fan motors have ball bearings and conform to NEMA MG-1 & MG-2. Motor starters are magnetic contactor, across-the-line type.
PQ075 - PQ360:
Evaporator fan is of centrifugal forward-curved blade design capable of handling total required CFM and static pressure in the low and the medium ranges. Casings are made of galvanized steel. Blower motors are of the open drip proof type (totally enclosed types are optional) and conform to NEMA MG-1 and MG-2. Fan drive is through adjustable pitch pulleys and belt driven. Blower motor is mounted on adjustable base and secured by locking device. Fan wheels shafts and bearing are selected to operate at 25% below first critical speed. Pillow block bearings are selected for at 200,000 hours average life at design operating conditions. Shaft is turned, ground and polished from solid steel. Fans and pulleys are keyed to shaft and designed for continuous operation at maximum motor horse power and fan speed. All rotating components and assemblies are statically and dynamically balanced and every unit is vibration tested before shipment from the factory.
5
G. Performex-1
TM
Controller Electronic Control Board
The COOLINE "Comfort" series Packaged units are provided with technologically advanced new Performex-1
TM Controller
Microprocessor Based Electronic Control Board, incorporating the following benefits and features:
- COMPLETE UNIT CONTROL:
Provides complete unit control for heating and cooling application whether single stage or two stage utilizing the input from sensor that measure temperatures during unit operation.
- COMPRESSOR LOCKOUT:
If any of the unit’s safety controls trip due to abnormal conditions the Electronic Control locks out the compressor, preventing restart, unless attended by qualified service technicians. The unit can be restarted only by reset the thermostat after ensuring safe system conditions.
- LEAD LAG OPERATION:
The unit electronic controls automatically alternate lead and lag the compressors for even operation. Compressor #1 can be set always lead as an option.
- ANTI-RECYCLE TIMER:
For compressor safety in case of accidental manual reset or immediate recycling of thermostat due to load demand. This considerably improves compressor life.
- PUMP DOWN OPTION:
In units equipped with pump down system the time delay creates the required time gap between the solenoid opening and compressor start to equalize the pressure in the system prior to compressor start up.
- AUTO/MANUAL RESET OF THE ALARM SIGNALS.
- FULL CONTROL OF THE INDOOR FAN:
Fan operation can be selected either to run continuously or stage with the compressor/heaters.
H. Electronic Thermostats
General information:
A dedicated electronic thermostat is supplied with the unit controls as standard. This thermostat controls one or two stage heating and cooling applications. The thermostat normally displays room temperature and mode of operation.
The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also allows you to select continuous fan operation, or have the fan on intermittent operation with the equipment. It also displays the status of the unit, thus providing maximum information for the end user. As this is a dedicated thermostat supplied with the unit controller, the said controls can not be connected to any other BMS or DDC controller.
Special controller to be used, if required, for BMS or DDC controller connections.
OPTIONS AND ACCESSORIES
A. Electric Heaters
Electric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equivalent. Electrical characteristics, kW capacities and number of stages are as indicated. Airflow switches, fusible links and overheat limit thermostats are provided to shut-off power in case of airflow failure/overheat. Electric heater kit is installed as an externally mounted kit at the supply opening.
B. UV Flow
TM
Light Emitters:
The damp & dark environment inside the unit could contribute for the growth and development of hazardous bacteria and fungi.
The UV flow
TM
concept uses emitter of Ultra Violet to simulate the effect of healthy sun radiation. This will inhibit the growth of these microorganism reducing in this manner mold related allergies and diseases. Breath safely with UV flow
TM
.
To order UV flow
TM
use the kit number in tables below:
MODEL No. PQ036/048/060
KIT PART No.
700-391-30
PQ075
700-391-23
PQ090
700-391-24
PQ100
700-391-25
PQ120/150 PQ180/210
700-391-26 700-391-27
PQ240/300
700-391-28
PQ360
700-391-31
C. Economizer
This can be provided as an option to be ordered separately if required for horizontal discharge units only. Economizer utilizes cool outside air to satisfy cooling load to minimize energy consumption by maintaining poise between outside air intake and compressor operation when required as per load demand.
The Economizer is operative either by a dry bulb Outdoor Air Thermostat (OAT) or a Solid State Enthalpy Controller (EC) to sense the outdoor air temperature. The unit is equipped with an electronic control board, the PsychroTroll™ with a sensitive feedback system carefully modulating the damper to allow correct percentage of fresh air and return air. The
PsychroTroll™
is designed to match with a separate COOLINE electronic controller & thermostat.
6
STANDARD FEATURES/OPTIONS/ACCESSORIES
DESCRIPTION
Horizontal discharge
Compressor crankcase heaters
Evaporator fan–belt driven
(1)
Evaporator fan motor – ODP type (TEFC type optional)
(2)
Condenser fan – direct drive, propeller type
Condenser fan motor – totally enclosed air-over type
Electric heaters
Filter drier
Filter, synthetic media
Filter, aluminum
Compressor overload protection
Low pressure switch
High pressure switch
Cooling & heating thermostat
Condenser fan guard
Condenser coil guard
Manual outside air damper
(3)
Economizer
Enthalpy sensor
NOTES:
(1) Direct drive motors for PQ036 to PQ060.
(2) TEFC motors are available for PQ075 to PQ360.
(3) Manual outside air damper is available for PQ075 to PQ360.
STANDARD
FEATURES
OPTION
(FACTORY
INSTALLED)
ACCESSORY
(FIELD
INSTALLED)
7
GENERAL DATA
(DIRECT DRIVE MOTOR)
MODEL NUMBER
NOMINAL CAPACITY, TONS (kW)
COMPRESSOR Quantity
Oil (oz)
Refrigerant
CONDENSER FAN
Operating Charge (oz)
Type/Drive
Quantity – Diameter (inch)
Nominal CFM (L/S)
CONDENSER COIL
EVAPORATOR BLOWER
Motor HP – RPM
Type
Tube dia. - Rows - Fins per inch
Total face area, Sq. ft. (Sq. m.)
Type
Size (inch)
Drive type
Nominal CFM (L/S)
EVAPORATOR COIL
LOW PRESSURE
SWITCH
RETURN AIR FILTERS
SHIPPING WEIGHT
Motor HP (Standard)
Type
Tube dia. - Rows - Fins per inch
Total face area, Sq. ft. (Sq. m.)
Open
Close
Quantity
Size (inch)
Kgs.
PQ036 PQ048 PQ060
3 (10.5)
1
40
4 (14)
1
70
R-22
5 (17.6)
1
70
83
1 – 24
3200 (1510)
155
Propeller/Direct
1 – 24
3000 (1415)
208
1 – 24
3000 (1415)
1/3 – 1075 1/3 – 1075 1/3 – 1075
Inner Grooved Tubes and Enhanced Fins
3/8-1-16
10.8 (1)
3/8-2-16
10.8 (1)
Centrifugal
10 x 8
3/8-2-16
10.8 (1)
10 x 8 10 x 8
1200 (566)
0.75
Direct Drive
1600 (755)
0.75
Inner Grooved Tubes and Enhanced Fins
1800 (850)
1
3/8-3-14
4.5 (0.42)
3/8-3-14
5.4 (0.5)
25 ± 5 PSIG
50 ± 5 PSIG
3/8-3-14
5.4 (0.5)
2
16 x 25
197
2
16 x 25
213
2
16 x 25
215
8
GENERAL DATA
MODEL NUMBER PQ075 PQ090 PQ100 PQ120 PQ150 PQ180 PQ210 PQ240 PQ300 PQ360
NOMINAL CAPACITY, TONS (kW)
COMPRESSOR Quantity
Oil (oz)
Refrigerant
Operating Charge (oz)
CONDENSER FAN Type/Drive
Qty. – Diameter (inch)
Nominal CFM (L/S)
6 (21) 7.5 (26.4) 8.5 (30) 10 (35) 12 (42) 15 (53) 17.5 (62) 20 (70.4) 25 (88) 30 (105)
1 2 2 2 2 2 2 2 2 2
60 45 x 2 70 x 2 60 x 2 60 x 2 81 & 110 110 x 2 110 x 2 140 x 2 140 x 2
R-22
178 119 x 2 130 x 2 131 x 2 148 x 2 190 & 201 256 x 2 271 x 2 369 x 2 462 x 2
Propeller/Direct
1 – 26
4800(2265) 5500(2595) 6000 (2830)
2 – 26 2 – 30
11000(5190) 10500(4950)15000(7080) 14300(6750) 14700(6938)
Motor HP – RPM
CONDENSER COIL Type
1/3 – 850
Tube dia. - Rows - Fins per inch 3/8-2-16
Total face area, Sq. ft. (Sq. m.) 14 (1.3) 16 (1.5)
3/4 – 950 1.5 – 950
Inner Grooved Tubes and Enhanced Fins
20 (1.86)
3/8-3-16 3/8-2-14 3/8-3-14 3/8-2-14 3/8-3-14 3/8-3-14
30 (2.78) 38 (3.53) 48 (4)
EVAPORATOR
BLOWER
Type
Size (inch)
Drive type
Nominal CFM (L/S)
12 x 12
Centrifugal
15 x 15
Belt
18 x 18 20 x 18
2400(1135) 3000(1415) 3400(1605) 4000(1890) 4800(2265) 6000(2830) 7000(3300) 7500(3540) 9600(4530) 11250(5309)
LOW PRESSURE
SWITCH
Motor HP - Std. / Alt
Motor Frame (NEMA) Std. / Alt.
1.5/2 2/3 2/3 3 3/5 5/7.5
5/7.5
7.5
7.5/10 10/15
56 / 56 56/184T 184T/213T 213T/215T
215T/254T
Fan RPM range
Factory setting full turns open
Fan pulley pitch dia.
EVAPORATOR COIL Type
Tube dia. - Rows - Fins per inch
850-1310 850-1450 700-1290 735-1165 815-1175 725-1140 765-1140 665-1080 725-1080 692-1064
3
4.6
3
4.6
3
5.6
3
6.1
3
6.6
3
7.4
3
7
Inner Grooved Tubes and Enhanced Fins
3/8-3-14 3/8-2-14
3
9.4
3/8-3-14
3
8.6
3
9
3/8-4-14
Total face area, Sq. ft. (Sq. m.) 6 (0.56) 9 (0.84) 10 (0.93) 11 (1.02) 12.5 (1.16) 19.5 (1.81) 19.5 (1.81) 22 (2.04) 27 (2.5) 27 (2.5)
Open
Close
25 ± 5 PSIG
50 ± 5 PSIG
RETURN AIR
FILTERS
Qty.
Size (inch)
SHIPPING WEIGHT Kgs.
16-1/2 x 18-3/8
337 366
4
441
18 x 24
445 450
6 8
18 x 18 (1)
18 x 24 (3)
24 x 24 (2)
12 x 24 (2)
24 x 24 (6)
800 840 975 1025 1323
9
SELECTION PROCEDURE
1. Determine cooling and heating capacity requirements at design conditions
Data
:
Condenser entering air temperature
Evaporator entering air temperature
Evaporator airflow
Required cooling capacity
Sensible heat capacity
Required heating capacity
External static pressure
Power supply (V-Ph-Hz)
: 95
0
F
: 80
0
F DB / 67
0
F WB
: 7500 CFM
: 235,000 BTUH
: 160,000 BTUH
: 20 kW
: 1.23 INCH WG.
: 380/415-3-50
2. Unit selection based on required cooling capacity
Enter cooling capacity performance data at condenser entering air temp. at 95
0
F and evaporator entering air temp. 80
0
F
DB, 67
0
F WB, 7500 CFM airflow. The PQ240 unit will give 245,800 BTUH cooling capacity (gross) and 179,200 BTUH sensible heat capacity (gross).
3. Electric heater selection
Heating capacity required =20 kW.
Enter electric heating table for PQ240 at 380/415-3-50 power supply.
20 kW heater at 380/415 volts satisfies the required heating.
4. Determine fan speed and power requirements at design conditions
Before entering the fan performance tables, calculate the summation of external static pressure for the required components as follows.
External static pressure
Electric heater
: 1.23 INCH WG.
: 0.17 INCH WG.
1.4 INCH WG.
Enter fan performance table for PQ240 model. For 7500 CFM and external static pressure of 1.4 INCH WG, it require 911 RPM and 4.45 brake horse power (BHP) wherein the standard motor will meet job requirements.
5. Determine input power to motor
Use fan motor efficiency table.
Blower motor watts = BHP x 746 watts = 4.45 x 746 = 4098 watts.
Motor efficiency 0.81
6. Determine net capacities
Above capacities are gross and do not include blower motor heat gain.
Determine net capacities as follows:
Net cooling capacity = Gross cooling capacity – blower motor heat
= 245,800 – (4098 WATTS x 3.413 BTUH/WATTS) = 231,813 BTUH
Net sensible capacity = 179,200 – (4098 WATTS x 3.413 BTUH/WATTS) = 165,213 BTUH
7. Altitude correction factors for cooling capacity
ALTITUDE, FT.
Total capacity
FACTOR
Sensible capacity
2000 4000 6000 8000 10000
0.98
0.93
0.96
0.86
0.93
0.80
0.90
0.75
0.88
0.70
10
COOLING CAPACITIES
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125 kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC
29.66
28.04
3.85
27.30
25.68
4.01
26.08
24.35
4.19
62
33.68
31.69
3.49
31.72
30.75
3.65
1125/0.104
32.53
24.13
4.03
30.04
23.12
4.21
28.68
22.46
4.41
67
36.77
26.21
3.64
34.73
25.57
3.81
35.59
18.74
4.23
32.93
17.79
4.44
31.52
17.22
4.67
72
40.10
20.65
3.79
37.97
20.02
3.99
Model No.: PQ036
EVAPORATOR AIRFLOW, CFM/DR
1225/0.111
EVAPORATOR ENTERING AIR, WBE (
0
F)
30.16
28.51
3.93
27.76
26.11
4.09
26.47
24.73
4.27
62
34.27
33.05
3.58
32.24
31.26
3.73
33.09
25.32
4.11
30.54
24.29
4.30
29.21
23.67
4.50
67
37.39
27.42
3.72
35.32
26.79
3.89
36.22
19.52
4.32
33.53
18.57
4.53
32.10
18.00
4.76
72
40.82
21.44
3.87
38.65
20.83
4.08
30.7
29.0
4.1
28.3
26.6
4.2
26.9
25.2
4.4
62
34.9
33.7
3.7
32.8
31.8
3.8
1350/0.119
33.7
26.8
4.2
31.1
25.7
4.4
29.7
25.1
4.6
67
38.1
28.9
3.8
35.9
28.3
4.0
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
38.94
5.56
37.50
36.75
5.75
35.06
34.35
5.89
62
44.61
40.93
5.32
42.39
39.83
5.36
40.00
1275/0.099
32.40
5.85
41.18
31.43
6.07
38.53
30.38
6.22
67
48.75
34.30
5.55
46.43
33.28
5.62
43.89
25.76
6.15
45.17
24.80
6.39
42.37
23.81
6.58
72
53.20
27.57
5.77
50.78
26.63
5.88
48.09
Model No.: PQ048
EVAPORATOR AIRFLOW, CFM/DR
1450/0.108
EVAPORATOR ENTERING AIR, WBE (
0
F)
40.3
5.7
38.5
37.7
5.9
36.0
35.3
6.0
62
45.9
44.1
5.5
43.6
43.0
5.5
41.1
34.7
6.0
42.4
33.8
6.2
39.7
32.7
6.4
67
50.2
36.7
5.7
47.8
35.7
5.8
45.1
27.3
6.3
46.5
26.3
6.6
43.6
25.3
6.8
72
54.9
29.2
5.9
52.3
28.2
6.0
49.5
41.3
5.9
39.5
38.7
6.1
36.9
36.1
6.2
62
47.1
46.2
5.6
44.7
43.8
5.7
42.1
1650/0.119
37.3
6.2
43.4
36.3
6.4
40.6
35.2
6.6
67
51.6
39.2
5.9
49.1
38.2
5.9
46.4
CONDENSER
ENTERING AIR
TEMP. (
0
F)
1600/0.117
29.6
7.8
53.7
27.2
7.9
50.3
26.1
8.2
72
65.5
31.7
7.0
62.3
30.7
7.4
59.2
Model No.: PQ060
EVAPORATOR AIRFLOW, CFM/DR
1800/0.128
EVAPORATOR ENTERING AIR, WBE (
0
F)
47.9
7.3
45.3
42.4
7.3
42.4
39.7
7.6
62
55.8
50.1
6.7
52.9
48.9
7.0
50.2
39.6
7.6
49.9
36.9
7.7
46.7
35.8
8.0
67
61.3
41.7
6.9
58.1
40.6
7.3
55.3
31.2
8.0
54.9
28.7
8.1
51.4
27.6
8.5
72
67.1
33.2
7.2
63.8
32.2
7.7
60.7
2000/0.139
85
95
105
115
125
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
62
54.6
47.0
6.4
51.7
45.8
6.8
49.1
44.7
7.0
44.3
41.5
7.1
41.5
38.8
7.4
67
59.8
39.4
6.7
56.7
38.3
7.1
54.0
37.2
7.4
48.8
34.6
7.5
45.7
33.5
7.8
62
57.0
53.2
6.8
53.9
51.4
7.2
51.2
48.8
7.4
46.2
43.2
7.5
43.1
40.4
7.8
67
62.5
44.0
7.1
59.2
42.8
7.5
56.3
41.8
7.8
50.9
39.1
7.9
47.6
37.9
8.2
TC – Total Capacity (1000 Btuh) Gross
SC – Sensible Heat Capacity (1000 Btuh) G kW – Total unit power input
DR – Wet Bulb depression ratio
DBE – Dry Bulb Temp. (
0
F) of Air Entering Coil
WBE – Wet Bulb Temp. (
0
F) of Air Entering Coil
DBL – Dry Bulb Temp. ( 0 F) of Air Leaving Coil
WBL – Wet Bulb Temp. (
0
F) of Air Leaving Coil
NOTES:
1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 80 0 F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input at 0.15 ESP for PQ036/PQ048 & 0.2 ESP for PQ060.
32.6
8.2
56.0
30.1
8.3
52.5
29.0
8.7
72
68.5
34.7
7.4
65.1
33.6
7.9
61.9
29.0
6.5
47.7
28.0
6.8
44.7
27.0
7.0
72
56.4
30.8
6.1
53.8
29.8
6.2
50.9
11
37.0
20.5
4.4
34.2
19.5
4.7
32.7
18.9
4.9
72
41.6
22.4
4.0
39.3
21.8
4.2
COOLING CAPACITIES
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125 kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125 kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC
60.35
55.20
8.17
57.29
54.00
8.72
53.98
52.66
9.34
62
67.31
58.40
7.18
64.41
57.18
7.66
70.1
67.1
9.6
66.3
64.6
10.3
62.3
60.8
11.0
62
81.3
73.4
8.6
77.7
71.9
9.1
1900/0.11
66.06
45.94
8.64
62.77
44.76
9.24
59.22
43.51
9.91
67
73.56
49.06
7.57
70.51
47.90
8.08
2400/0.108
77.6
55.8
10.2
73.7
54.5
10.8
69.4
52.9
11.6
67
89.5
61.6
9.0
85.9
60.3
9.5
85.9
44.4
10.7
81.6
43.0
11.5
77.0
41.5
12.4
72
98.6
49.8
9.5
94.9
48.5
10.1
72.31
36.60
9.16
68.71
35.42
9.82
64.86
34.17
10.54
72
80.26
39.55
7.98
77.06
38.45
8.55
Model No.: PQ075
EVAPORATOR AIRFLOW, CFM/DR
2400/0.131
EVAPORATOR ENTERING AIR, WBE (
0
F)
63.06
61.26
8.56
59.82
58.21
9.13
56.37
54.99
9.75
62
70.59
66.54
7.56
67.45
65.28
8.04
69.19
51.89
9.04
65.65
50.68
9.66
61.91
49.43
10.34
67
77.20
55.09
7.96
73.98
53.95
8.48
75.93
40.53
9.60
72.10
39.33
10.28
68.07
38.10
11.03
72
84.41
43.54
8.39
81.00
42.42
8.97
Model No.: PQ090
EVAPORATOR AIRFLOW, CFM/DR
3000/0.128
EVAPORATOR ENTERING AIR, WBE (
0
F)
73.5
71.3
10.1
69.4
67.6
10.8
65.2
63.6
11.5
62
85.2
83.4
9.1
81.6
80.9
9.6
81.6
63.2
10.7
77.3
61.7
11.4
72.8
60.2
12.2
67
94.2
69.2
9.5
90.3
67.8
10.1
90.4
49.2
11.3
85.9
47.9
12.1
81.1
46.4
13.0
72
103.8
54.8
10.0
100.0
53.5
10.6
65.08
63.22
9.02
61.66
60.01
9.60
58.00
56.59
10.23
62
72.91
71.04
8.02
69.63
67.93
8.50
75.9
73.7
10.8
71.7
69.8
11.4
67.5
65.7
12.2
62
88.2
87.3
9.7
84.2
83.5
10.2
2900/0.153
71.54
57.47
9.52
67.76
56.19
10.15
63.87
54.94
10.84
67
79.83
60.67
8.42
76.44
59.51
8.95
3600/0.148
84.4
70.0
11.3
79.9
68.5
12.1
75.2
66.9
12.9
67
97.5
76.2
10.1
93.5
74.7
10.7
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC
80.9
10.6
79.8
78.9
10.9
74.5
73.0
11.2
62
94.8
84.9
9.7
90.0
82.8
10.1
84.9
kW
TC – Total Capacity (1000 Btuh) Gross
SC – Sensible Heat Capacity (1000 Btuh) Gross
2700/0.109
67.5
11.2
87.7
65.4
11.6
81.8
63.2
11.9
67
103.9
71.4
10.2
98.9
69.4
10.7
93.4
kW – Total unit power input
DR – Wet Bulb depression ratio
53.8
11.8
96.3
51.7
12.2
90.0
49.6
12.7
72
113.7
57.6
10.7
108.4
55.7
11.3
102.4
Model No.: PQ100
EVAPORATOR AIRFLOW, CFM/DR
3400/0.13
EVAPORATOR ENTERING AIR, WBE (
0
F)
87.4
11.0
83.6
81.9
11.3
77.9
76.4
11.7
62
99.7
96.7
10.1
94.7
92.8
10.6
89.2
76.3
11.6
92.1
74.2
12.0
85.9
72.0
12.4
67
109.5
80.3
10.6
104.1
78.2
11.1
98.2
59.7
12.2
101.4
57.6
12.7
94.7
55.4
13.2
72
120.0
63.6
11.1
114.3
61.6
11.7
108.0
DBE – Dry Bulb Temp. (
0
F) of Air Entering Coil
WBE – Wet Bulb Temp. (
0
F) of Air Entering Coil
90.3
11.6
86.3
84.6
11.9
80.4
78.8
12.3
62
103.3
101.2
10.7
97.9
95.9
11.1
92.2
4100/0.151
67
113.4
88.4
11.2
107.7
86.3
11.7
101.7
84.5
12.2
95.3
82.3
12.6
88.9
80.1
13.0
72
124.6
68.9
11.7
118.6
66.9
12.3
111.9
64.9
12.8
105.0
62.8
13.4
98.1
60.7
13.8
DBL – Dry Bulb Temp. (
0
F) of Air Leaving Coil
WBL – Wet Bulb Temp. ( 0 F) of Air Leaving Coil
NOTES:
1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 80
0
F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input based on nominal CFM & 0.25 ESP.
78.50
44.08
10.12
74.50
42.86
10.81
70.25
41.60
11.58
72
87.38
47.13
8.88
83.75
45.98
9.48
93.7
53.6
12.0
89.1
52.3
12.8
84.0
50.7
13.7
72
107.7
59.3
10.6
103.7
58.1
11.3
12
COOLING CAPACITIES
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125 kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125 kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC
99.4
94.1
13.0
94.0
91.7
13.6
88.7
88.0
14.2
62
109.7
98.5
11.8
104.9
96.1
12.4
123.0
113.2
16.0
112.9
110.8
17.1
106.1
104.0
18.4
62
132.0
118.3
14.0
125.8
115.7
15.0
3200/0.105
108.9
78.2
13.8
102.9
75.8
14.4
97.1
73.7
15.0
67
120.0
82.5
12.4
114.7
80.2
13.1
3800/0.119
134.8
94.5
16.9
123.7
91.8
18.1
116.5
89.2
19.5
67
144.3
99.3
14.8
137.9
96.9
15.8
Model No.: PQ150
147.6
75.6
17.9
135.6
72.7
19.3
127.6
70.0
20.7
72
157.7
80.0
15.6
150.9
77.7
16.7
119.2
62.0
14.6
112.8
59.8
15.3
106.5
57.7
16.0
72
131.0
66.2
13.1
125.5
64.1
13.9
Model No.: PQ120
EVAPORATOR AIRFLOW, CFM/DR
4000/0.124
EVAPORATOR ENTERING AIR, WBE (
0
F)
103.9
102.8
13.7
98.1
97.2
14.3
92.6
91.8
14.8
62
114.9
111.9
12.4
109.6
108.2
13.1
113.9
88.0
14.4
107.7
85.7
15.1
101.6
83.6
15.7
67
125.9
92.5
13.1
120.2
90.1
13.8
125.0
68.5
15.3
118.3
66.3
16.1
111.6
64.2
16.7
72
137.8
72.8
13.8
131.9
70.7
14.6
EVAPORATOR AIRFLOW, CFM/DR
4800/0.143
EVAPORATOR ENTERING AIR, WBE (
0
F)
128.4
127.6
17.0
117.8
115.4
18.1
110.6
108.4
19.4
62
137.8
134.3
14.9
131.4
128.7
15.9
140.9
106.3
17.9
129.2
103.8
19.2
121.5
101.2
20.6
67
151.1
111.3
15.7
144.2
108.8
16.8
154.6
83.3
19.0
141.7
80.4
20.4
133.5
77.8
21.9
72
165.3
87.8
16.6
158.1
85.5
17.7
107.1
106.0
14.4
101.0
100.0
15.0
95.2
94.4
15.6
62
118.6
117.2
13.2
112.9
111.5
13.8
132.2
131.3
18.2
121.1
118.6
19.3
113.7
111.5
20.6
62
142.0
139.2
16.1
135.2
132.5
17.1
4800/0.143
117.6
97.2
15.2
111.1
94.9
15.9
104.7
92.7
16.5
67
130.1
101.7
13.8
124.2
99.4
14.6
5800/0.167
145.1
117.0
19.1
133.0
114.7
20.4
125.0
112.0
21.8
67
155.9
122.2
16.9
148.6
119.7
18.0
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC
132.5
19.2
138.0
126.6
20.2
129.1
123.1
21.3
62
162.7
142.6
17.4
156.0
138.1
18.4
146.6
kW
TC – Total Capacity (1000 Btuh) Gross
SC – Sensible Heat Capacity (1000 Btuh) Gross
4800/0.177
111.0
20.5
152.3
105.6
21.5
142.8
102.2
22.7
67
179.2
120.6
18.4
171.7
116.3
19.5
161.7
kW – Total unit power input
DR – Wet Bulb depression ratio
89.2
21.7
167.6
84.1
22.8
157.2
80.8
24.1
72
196.6
98.0
19.4
188.7
94.1
20.6
177.9
Model No.: PQ180
EVAPORATOR AIRFLOW, CFM/DR
6000/0.22
EVAPORATOR ENTERING AIR, WBE (
0
F)
148.0
20.6
144.3
139.5
21.6
134.9
130.7
22.6
62
170.5
158.5
18.7
163.1
153.7
19.7
153.5
122.6
21.8
159.5
116.9
22.9
149.3
113.4
24.0
67
187.8
132.5
19.7
180.0
128.1
20.8
169.3
96.9
23.0
175.6
91.6
24.2
164.7
88.3
25.5
72
206.1
105.9
20.7
197.8
101.9
21.9
186.5
DBE – Dry Bulb Temp. (
0
F) of Air Entering Coil
WBE – Wet Bulb Temp. (
0
F) of Air Entering Coil
155.9
22.1
148.7
143.8
23.1
139.0
134.6
24.2
62
176.0
171.8
20.2
168.5
166.9
21.2
158.4
7200/0.264
67
193.8
142.3
21.2
186.0
138.0
22.3
174.8
132.2
23.3
164.5
126.3
24.4
154.2
123.0
25.6
72
213.2
112.5
22.3
204.5
108.3
23.5
192.7
103.3
24.6
181.6
97.9
25.8
170.4
94.6
27.1
DBL – Dry Bulb Temp. (
0
F) of Air Leaving Coil
WBL – Wet Bulb Temp. ( 0 F) of Air Leaving Coil
NOTES:
1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 80
0
F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input based on nominal CFM & 0.35 ESP.
129.3
74.5
16.2
122.3
72.3
16.9
115.2
70.1
17.6
72
142.6
78.8
14.6
136.3
76.6
15.4
159.5
90.3
20.3
146.3
87.5
21.7
137.8
85.0
23.2
72
171.0
95.0
17.8
163.3
92.6
19.0
13
COOLING CAPACITIES
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125 kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125 kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC
169.3
161.9
24.5
157.2
152.6
25.4
146.8
142.7
26.2
62
190.8
171.8
22.7
181.0
167.5
23.6
200.5
184.1
27.2
188.5
179.4
28.7
175.7
174.2
30.2
62
223.5
194.0
24.4
212.0
189.4
25.8
5800/0.117
186.1
134.1
25.9
173.3
128.7
26.9
161.9
124.6
27.7
67
209.5
143.8
23.8
198.9
139.6
24.9
6000/0.095
220.8
154.4
28.6
207.8
149.7
30.3
193.8
144.4
31.9
67
245.3
163.9
25.5
233.1
159.4
27.1
Model No.: PQ240
242.8
124.1
30.2
228.9
119.5
32.0
213.6
114.2
33.9
72
268.7
133.2
26.7
256.0
129.0
28.5
204.8
106.2
27.4
190.8
101.0
28.5
178.5
97.0
29.5
72
229.5
115.3
25.0
218.5
111.4
26.2
Model No.: PQ210
EVAPORATOR AIRFLOW, CFM/DR
7000/0.136
EVAPORATOR ENTERING AIR, WBE (
0
F)
175.4
171.0
26.1
162.9
158.1
27.0
151.9
147.6
27.8
62
198.0
190.9
24.2
187.9
183.9
25.2
193.3
148.4
27.5
180.0
142.9
28.5
168.1
138.8
29.4
67
217.6
158.1
25.4
206.7
153.9
26.5
213.0
115.6
29.0
198.2
110.2
30.2
185.6
106.2
31.2
72
239.0
124.8
26.6
227.2
120.8
27.9
EVAPORATOR AIRFLOW, CFM/DR
7500/0.112
EVAPORATOR ENTERING AIR, WBE (
0
F)
210.8
209.2
28.4
198.0
197.2
29.9
184.3
183.9
31.5
62
235.6
220.5
25.5
223.2
215.8
27.0
232.8
174.1
29.9
218.8
169.3
31.6
203.9
163.9
33.3
67
258.8
183.7
26.7
245.8
179.2
28.3
256.7
137.4
31.6
241.5
132.5
33.5
225.7
127.4
35.5
72
284.5
146.7
28.0
270.9
142.4
29.8
180.1
175.6
27.7
167.2
162.4
28.5
155.8
151.4
29.4
62
203.7
199.3
25.7
192.9
188.8
26.7
218.0
216.4
29.9
204.7
203.8
31.4
190.2
189.7
33.0
62
243.9
241.3
26.9
231.0
229.3
28.4
8200/0.154
198.7
161.6
29.1
184.9
156.0
30.1
172.4
151.6
31.0
67
224.0
171.5
26.9
212.6
167.3
28.0
9000/0.128
241.1
192.2
31.4
226.7
187.5
33.2
211.1
182.1
34.9
67
268.8
202.2
28.1
255.2
197.7
29.8
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC
234.8
32.4
224.8
220.3
34.4
207.8
203.6
36.5
62
267.0
245.6
28.5
254.1
240.3
30.4
240.2
kW
TC – Total Capacity (1000 Btuh) Gross
SC – Sensible Heat Capacity (1000 Btuh) Gross
8000/0.117
195.3
34.1
248.0
188.9
36.4
229.6
182.2
38.7
67
293.4
206.0
29.9
279.9
201.0
32.0
264.6
kW – Total unit power input
DR – Wet Bulb depression ratio
155.4
36.1
273.5
149.1
38.6
253.8
142.6
41.2
72
322.4
166.0
31.4
307.6
160.8
33.6
291.4
Model No.: PQ300
EVAPORATOR AIRFLOW, CFM/DR
9600/0.135
EVAPORATOR ENTERING AIR, WBE (
0
F)
243.5
34.0
232.2
227.5
36.1
214.6
210.3
38.2
62
276.5
271.9
30.1
263.1
257.9
32.0
248.5
214.9
35.8
256.8
208.4
38.1
237.6
201.6
40.5
67
304.7
225.8
31.5
290.1
220.5
33.6
274.3
168.2
37.9
283.9
161.9
40.4
263.2
155.3
43.1
72
334.8
178.7
33.0
319.5
173.7
35.4
302.5
DBE – Dry Bulb Temp. (
0
F) of Air Entering Coil
WBE – Wet Bulb Temp. (
0
F) of Air Entering Coil
249.7
36.0
238.2
233.4
38.1
219.6
215.2
40.2
62
284.0
278.4
32.0
269.9
264.5
33.9
254.8
11200/0.153
67
312.7
243.9
33.4
297.6
238.6
35.5
281.6
233.3
37.8
263.7
226.7
40.1
243.8
219.8
42.5
180.3
39.9
291.6
173.6
42.5
270.3
167.0
45.2
72
344.7
190.8
35.0
328.8
185.6
37.4
311.4
DBL – Dry Bulb Temp. (
0
F) of Air Leaving Coil
WBL – Wet Bulb Temp. ( 0 F) of Air Leaving Coil
NOTES:
1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 80
0
F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input based on nominal CFM & 0.35 ESP.
219.1
124.1
30.7
203.9
118.7
31.9
190.9
114.6
32.9
72
246.4
133.5
28.2
234.0
129.4
29.5
266.5
149.3
33.3
251.0
144.6
35.2
233.9
139.1
37.2
72
296.0
158.9
29.5
281.3
154.3
31.4
14
COOLING CAPACITIES
CONDENSER
ENTERING AIR
TEMP. (
0
F)
85
95
105
115
125
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC kW
TC
SC
62
303.69
276.69
32.15
297.83
271.38
33.79
286.54
257.88
35.59
279.01
248.32
37.31
271.06
241.24
39.75
kW
TC – Total Capacity (1000 Btuh) Gross
SC – Sensible Heat Capacity (1000 Btuh) Gross
9600/0.066
67
330.03
228.32
32.6
323.79
223.56
34.28
311.72
214.33
36.12
303.82
209.22
37.88
295.49
206.39
40.37
kW – Total unit power input
DR – Wet Bulb depression ratio
72
357.93
179.12
33.2
351.72
175.20
34.93
338.90
167.26
36.83
330.62
162.85
38.64
321.52
159.99
41.21
Model No.: PQ360
EVAPORATOR AIRFLOW, CFM/DR
11250/0.078
EVAPORATOR ENTERING AIR, WBE (
0
F)
62
311.27
289.49
33.48
305.39
280.96
35.13
293.63
264.26
36.93
285.78
254.35
38.64
277.94
247.37
41.08
67
338.48
248.05
33.96
332.14
243.17
35.64
319.94
233.69
37.48
311.65
228.27
39.23
302.87
225.31
41.73
72
368.05
192.00
34.65
361.26
187.77
36.39
348.17
179.62
38.29
339.44
174.99
40.11
330.23
172.22
42.68
DBE – Dry Bulb Temp. (
0
F) of Air Entering Coil
WBE – Wet Bulb Temp. (
0
F) of Air Entering Coil
62
315.90
293.79
34.6
309.91
285.12
36.24
297.93
268.14
38.04
290.31
258.37
39.75
281.59
250.62
42.18
12500/0.088
67
344.11
262.89
35.08
337.61
257.83
36.77
325.14
248.00
38.61
316.47
242.26
40.36
307.80
239.51
42.85
72
373.92
201.19
35.85
367.46
197.11
37.59
353.99
188.70
39.5
344.83
183.82
41.31
335.67
181.19
43.9
DBL – Dry Bulb Temp. (
0
F) of Air Leaving Coil
WBL – Wet Bulb Temp. (
0
F) of Air Leaving Coil
NOTES:
1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 80
0
F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].
4. Total unit power input based on nominal CFM & 0.55 ESP.
15
ELECTRICAL DATA
MODELS: PQ036 - PQ060
MODEL
NUMBER
PQ036
PQ048
PQ060
POWER
SUPPLY
(V-Ph-Hz)
VOLTAGE
RANGE
FM COMPRES-
SOR
BLOWER
MOTOR
ELECTRIC
HEATER
MCA MOCP
380/415-3-50
(4 WIRE)
380/415-3-50
(4 WIRE)
380/415-3-50
(4 WIRE)
MIN.
MAX.
FLA RLA LRA HP FLA kW FLA
342
342
342
457
457
457
2.3
2.3
2.3
5.9
10.4
9.6
42
55
65
0.75
0.75
1
5.5
5.5
7.8
–
5
– 15.2
7.6
16.4
7.5
11.4
21.1
10* 15.2
25.9
–
5
– 20.8
7.6
20.8
7.5
11.4
21.1
10* 15.2
25.9
–
5
– 22.1
7.6
22.1
7.5
11.4
24
10* 15.2
28.8
30
30
30
30
20
20
25
30
30
30
30
30
LEGEND:
FLA - Full Load Amps
HP - Horse Power
BM - Blower Motor
LRA - Locked Rotor Amps
RLA - Rated Load Amps
MCA - Minimum Circuit Amps
MOCP - Maximum Over Current Protection
FM - Fan Motor (Condenser)
*
Combination of heater modules
MODELS: PQ075 & PQ090
POWER
SUPPLY
(V-Ph-Hz)
380/415-3-50 (4 WIRE)
MODEL NUMBER
DESCRIPTION
PQ075 PQ090
VOLTAGE
RANGE
Min.
342
FM
(each)
COMPR-
ESSOR
(each)
BM
ELECTRIC
HEATER
MCA MOCP
COMPR-
ESSOR
(each)
Max.
FLA RLA LRA HP FLA Nom. kW FLA
– –
5/6 7.6/9.1
457 2.6
(1.9 FOR
PQ090)
12
21
21/21
30
30/30
101
1.5
(STD)
3.4
7.5/10 11.4/15.2 21/23.3
30/30
10
*
/12
*
15.2/18.2 23.3/27 30/30
15
*
22.8
32.8
35
– – 21.2
30
2
(ALT.)
5/6 7.6/9.1
21.2/21.2
30/30
3.6
7.5/10 11.4/15.2 21.2/23.5
30/30
10
*
/12
*
15.2/18.2 23.5/27.3
30/30
15
*
22.8
33 35
BM
ELECTRIC
HEATER
MCA MOCP
RLA LRA HP FLA Nom. kW FLA
– –
5/6 7.6/9.1
8.2
50
3
(ALT.)
24
24/24
30
30/30
2
(STD)
3.6
7.5/10 11.4/15.2
10
24/24 30/30
*
/12
*
15.2/18.2
24/27.3
30/30
15
*
/20
*
22.8/30.4
33/42.5
35/45
25
*
/30
*
38/45.6
52/61.5
60/70
– – 25.1
30
5/6 7.6/9.1
25.1/25.1
30/30
4.7
7.5/10 11.4/15.2 25.1/25.1
30/30
10
*
/12
*
15.2/18.2 25.1/28.6
30/30
15
*
/20
*
22.8/30.4 34.4/43.9
35/45
25
*
/30
*
38/45.6
53.4/62.9
60/70
MODELS: PQ100 & PQ120
POWER
SUPPLY
(V-Ph-Hz)
380/415-3-50 (4 WIRE)
MODEL NUMBER
DESCRIPTION
PQ100 PQ120
VOLTAGE
RANGE
Min.
342
Max.
FM
(each)
COMPR-
ESSOR
(each)
FLA
457 1.9
BM
ELECTRIC
HEATER
MCA MOCP
COMPR-
ESSOR
(each)
RLA LRA HP FLA Nom. kW FLA
–
5/6
– 28.9
35
7.6/9.1
28.9/28.9
35/35
10.4
55
2
(STD)
3.6
7.5/10 11.4/15.2 28.9/28.9
35/35
10
*
/12
*
15.2/18.2 28.9/28.9
35/35
15
*
/20
*
22.8/30.4
33/42.5
35/45
25
*
/30
*
38/45.6
52/61.5
60/70
– – 30 40
5/6 7.6/9.1
30/30 40/40
3
(ALT.)
4.7
7.5/10 11.4/15.2
10
30/30 40/40
*
/12
*
15.2/18.2
30/30 40/40
15
*
/20
*
22.8/30.4 34.4/43.9
40/45
25
*
/30
*
38/45.6
53.4/62.9
60/70
BM
ELECTRIC
HEATER
MCA MOCP
RLA LRA HP FLA Nom. kW FLA
–
5/6
– 29.1
35
7.6/9.1
29.1/29.1
35/35
10 74
3
(STD)
4.7
7.5/10 11.4/15.2 29.1/29.1
35/35
10
*
/12
*
15.2/18.2 29.1/29.1
35/35
15
*
/20
*
22.8/30.4 34.4/43.9
35/45
25
*
/30
*
38/45.6
53.4/62.9
60/70
– – 33.6
40
5/6 7.6/9.1
33.6/33.6
40/40
5
(ALT.)
9.2
7.5/10 11.4/15.2 33.6/33.6
40/40
10
*
/12
*
15.2/18.2 33.6/34.3
40/40
15
*
/20
*
22.8/30.4
40/49.5
40/50
25
*
/30
*
38/45.6
59/68.5
60/70
16
ELECTRICAL DATA
MODELS: PQ150 & PQ180
POWER
SUPPLY
(V-Ph-Hz)
380/415-3-50 (4 WIRE)
MODEL NUMBER
DESCRIPTION
PQ150 PQ180
VOLTAGE
RANGE
Min.
342
Max.
FM
(each)
COMPR-
ESSOR
(each)
FLA
457 1.9
BM
ELECTRIC
HEATER
MCA MOCP
COMPR-
ESSOR
(each)
RLA LRA HP FLA Nom. kW FLA
–
5/6
– 33.6
45
7.6/9.1
33.6/33.6
45/45
12 101
3
(STD)
4.7
7.5/10 11.4/15.2 33.6/33.6
45/45
10
*
/12
*
15.2/18.2 33.6/33.6
45/45
15
*
/20
*
22.8/30.4 34.4/43.9
45/45
25
*
/30
*
38/45.6
53.4/62.9
60/70
– – 38.1
50
5
(ALT.)
5/6 7.6/9.1
38.1/38.1
50/50
9.2
7.5/10 11.4/15.2 38.1/38.1
50/50
10
*
/12
*
15.2/18.2 38.1/38.1
50/50
15
*
/20
*
22.8/30.4
40/49.5
50/50
25
*
/30
*
38/45.6
59/68.5
60/70
BM
ELECTRIC
HEATER
MCA MOCP
RLA LRA HP FLA Nom. kW FLA
7.5
(ALT.)
– – 51 60
17.3
&
16.4
111
&
95
5
(STD)
9.2
10
*
/12
*
15.2/18.2
51/51 60/60
15
*
/20
*
22.8/30.4
51/51 60/60
25
*
/30
*
38/45.6
59/68.5
60/70
– – 54.8
70
13
10
*
/12
*
15.2/18.2 54.8/54.8
70/70
15
*
/20
*
22.8/30.4 54.8/54.8
70/70
25
*
/30
*
38/45.6
63.8/73.3
70/80
MODELS: PQ210 & PQ240
POWER
SUPPLY
(V-Ph-Hz)
380/415-3-50 (4 WIRE)
MODEL NUMBER
DESCRIPTION
PQ210 PQ240
VOLTAGE
RANGE
Min.
342
FM
(each)
COMPR-
ESSOR
(each)
BM
ELECTRIC
HEATER
MCA
Max.
FLA RLA LRA HP FLA Nom. kW FLA
457 1.9
(2.9 FOR
PQ240)
19.2
125
– – 56.2
70
5
(STD)
9.2
10
*
/12
*
15.2/18.2 56.2/56.2
70/70
15
*
/20
*
22.8/30.4 56.2/56.2
70/70
25
*
/30
*
38/45.6
59/68.5
70/70
7.5
(ALT.)
– – 60 70
13
10
*
/12
*
15.2/18.2
60/60 70/70
15
*
/20
*
22.8/30.4
60/60 70/70
25
*
/30
*
38/45.6
63.8/73.3
70/80
MOCP
COMPR-
ESSOR
(each)
BM
ELECTRIC
HEATER
MCA MOCP
RLA LRA HP FLA Nom. kW
7.5
(STD)
FLA
13
– – 62.9
80
10
*
/12
*
15.2/18.2 62.9/62.9
80/80
15
*
/20
*
22.8/30.4 62.9/62.9
80/80
25
*
/30
*
38/45.6 63.8/73.3
80/80
35
*
/40
*
53.2/60.8 82.8/92.3
90/100
19.6
118
10
(ALT.)
– – 65 80
15.1
10
*
/12
*
15.2/18.2
65/65 80/80
15
*
/20
*
22.8/30.4
65/65 80/80
25
*
/30
*
38/45.6 66.4/75.9
80/80
35
*
/40
*
53.2/60.8 85.4/94.9
90/100
MODEL: PQ300 & PQ360
DESCRIPTION
MODEL NUMBER
PQ300 PQ360
POWER
SUPPLY
(V-Ph-Hz)
380/415-3-50 (4 WIRE)
VOLTAGE
RANGE
Min.
342
Max.
FM
(each)
COMPR-
ESSOR
(each)
FLA
457 2.9
BM
ELECTRIC
HEATER
MCA MOCP
COMPR-
ESSOR
(each)
BM
ELECTRIC
HEATER
MCA MOCP
RLA LRA HP FLA Nom. kW
7.5
(STD)
FLA
13
– – 76.4
100
10
*
/12
*
15.2/18.2 76.4/76.4
100/100
15
*
/20
*
22.8/30.4 76.4/76.4
100/100
25
*
/30
*
38/45.6 76.4/76.4 100/100
35
*
/40
*
53.2/60.8 82.8/92.3 100/100
25.6
167
10
(ALT.)
– – 78.5
100
15.1
10
*
/12
*
15.2/18.2 78.5/78.5
100/100
15
*
/20
*
22.8/30.4 78.5/78.5
100/100
25
*
/30
*
38/45.6 78.5/78.5 100/100
35
*
/40
*
53.2/60.8 85.4/94.9 100/100
RLA LRA HP FLA Nom. kW FLA
27.8
198
10
(STD)
– – 83.5
110
15.1
10
*
/12
*
15.2/18.2 83.5/83.5
110/110
15
*
/20
*
22.8/30.4 83.5/83.5
110/110
25
*
/30
*
38/45.6 83.5/83.5
110/110
35
*
/40
*
53.2/60.8 85.4/94.9
110/110
15
(ALT.)
– – 91 110
22.6
10
*
/12
*
15.2/18.2
91/91 110/110
15
*
/20
*
22.8/30.4
91/91 110/110
25
*
/30
*
38/45.6
91/91 110/110
35
*
/40
*
53.2/60.8 94.8/104.3 110/110
Note:
Please refer to page-16 for legend.
17
FAN PERFORMANCE DATA
(DIRECT DRIVE MOTOR)
BLOWER MOTOR
SPEED
HIGH
MEDIUM
LOW
BLOWER MOTOR
SPEED
HIGH
MEDIUM
LOW
CFM
BHP
CFM
BHP
CFM
BHP
0.1
1380
0.81
1250
0.70
1135
0.63
Model No.: PQ036
EXTERNAL STATIC PRESSURE (inch wg.)
0.2
1320
0.80
1200
0.70
1115
0.62
0.3
1340
0.78
1187
0.69
1092
0.61
0.4
1308
0.77
1177
0.68
1062
0.60
0.5
1275
0.75
1166
0.68
1032
0.58
CFM
BHP
CFM
BHP
CFM
BHP
0.1
1675
1.02
1500
0.84
1300
0.72
0.2
1625
0.96
1400
0.81
1250
0.70
Model No.: PQ048
EXTERNAL STATIC PRESSURE (inch wg.)
0.3
1541
0.94
1363
0.80
1200
0.70
0.4
1509
0.92
1340
0.78
1192
0.69
0.5
1477
0.90
1308
0.77
1187
0.68
0.6
1444
0.88
1275
0.75
1176
0.68
0.7
1410
0.86
1237
0.73
1144
0.67
0.8
1376
0.84
1198
0.71
1111
0.66
0.9
1331
0.81
1173
0.70
1032
0.69
952
0.62
0.59
1.0
1285
0.78
1148
0.6
1237
0.73
1144
0.67
989
0.56
Model No.: PQ060
EXTERNAL STATIC PRESSURE (inch wg.)
BLOWER MOTOR
SPEED
HIGH
CFM
BHP
0.1
2055
1.72
0.2
2000
1.63
0.3
1975
1.58
CFM 1850 1800 1768
MEDIUM
BHP 1.53
1.46
1.43
CFM 1650 1600 1558
LOW
BHP 1.31
1.26
1.24
NOTE:
Values include losses for dry coil, 1" thick filters & unit casing.
0.4
1960
1.54
1756
1.39
1550
1.21
0.5
1950
1.50
1738
1.35
1542
1.19
0.6
1925
1.46
1720
1.30
1534
1.16
0.7
1900
1.43
1701
1.27
1526
1.13
0.8
1870
1.39
1683
1.24
1518
1.11
0.9
1825
1.34
1658
1.20
1494
1.08
1.0
1780
1.28
1633
1.16
1470
1.05
18
FAN PERFORMANCE DATA
Airflow,
CFM (L/S)
1800 (849)
2000 (944)
2200 (1038)
2400 (1133)
2600 (1227)
2800 (1321)
3000 (1416)
0.2
0.4
0.6
Model No.: PQ075
External Static Pressure (inch wg.)
0.8
1.0
1.2
1.4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM
759* 0.43*
0.54*
I
862 0.54
937 0.66
1015 0.78
1088 0.92
1156 1.06
1235 0.98
1270
805*
882 0.65
963 0.78
1039 0.91
1109 1.05
1176 1.19
1242 1.35
1299
845*
861
895
928
962
0.66*
0.79
0.95
1.12
1.31
911
941
971
1001
1044
0.78
0.93
1.09
1.27
1.47
989
1016
1043
1070
1098
0.91
1.06
1.23
1.42
1.63
1062
1080
1111
1135
1161
1.05
1.21
1.38
1.58
1.80
1131
1153
1175
1198
1.19
1.36
1.54
1.75
1196
1216
1237
1258
1.34
1.52
1.71
1.92
1258
1277
1296
1.50
1.68
1.87
1317*
1334*
II
1.6
BHP
1.20
1.51
1.67*
1.85*
Notes:
1. Values include losses for filters, unit casing and wet coils.
2. Standard 1.5 HP motor to be used for the unshaded portion.
3. Alt. 2 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.
*
For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.
Model No.: PQ090
External Static Pressure (inch wg.)
Airflow,
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2400 (1133) 766* 0.65
* 852 0.78
2600 (1227) 815* 0.78*
877
I
0.92
844 0.93
902 1.07
2800 (1321)
3000 (1416)
3200 (1510)
874
904
933
954
0.91
1008 1.05
1079 1.19
1146 1.34
1210 1.50
1271 1.66
1329 1.83
1384 2.00
1.05
1026 1.20
1095 1.35
1161 1.51
1223 1.67
1283 1.83
1340 2.01
1395 2.19
1.09
927 1.24
976 1.22
1046 1.37
1112 1.52
1176 1.69
1237 1.85
1296 2.03
1352 2.21
1406 2.39
998 1.39
1065 1.55
1130 1.72
1192 1.88
1251 2.06
1309 2.24
1364 2.42
1417 2.61
1.27
953 1.43
1021 1.59
1086 1.76
1153 1.93
1209 2.10
1267 2.28
1323 2.47
1377 2.66
1429 2.85
3400 (1605)
3600 (1699)
933
963
1.46
980 1.63
1044 1.80
1107 1.98
1167 2.16
1226 2.34
1282 2.53
1337 2.72
1.68
1007 1.86
1069 2.04
1129 2.22
1187 2.41
1244 2.60
1299 2.79
II
Notes:
1. Values include losses for filters, unit casing and wet coils.
2. Standard 2 HP motor to be used for the unshaded portion.
3. Alt. 3 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.
*
For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.
Model No.: PQ100
External Static Pressure (inch wg.)
Airflow,
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM (L/S)
2700 (1274
2800 (1321)
3400 (1605
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
665* 0.68*
723 0.78
674* 0.74*
725
I
0.82
3000 (1416) 690* 0.78*
737 0.93
3200 (1510) 702* 0.87*
744 1.01
716 0.98
732 1.09
756 1.09
766 1.23
785 0.93
848
788 0.96
849
800 1.08
854
804 1.18
857
815 1.31
864
823 1.40
876
1.07
905 1.24
1.12
906 1.29
1.17
910 1.39
1.23
913 1.49
1.45
919 1.61
1.57
927 1.75
3600 (1699)
961 1.39
1012 1.54
1064 1.73
1114 1.90
1160 2.05
962 1.43
1013 1.59
1065 1.76
1115 1.94
1161 2.11
964 1.54
1015 1.71
1067 1.89
1117 2.11
966 1.65
1017 1.83
1069 2.00
1119 2.23
II
970 1.80
1019 1.96
1071 2.15
974 1.90
1021 2.10
766 1.28
793 1.40
852 1.60
904 1.78
954 1.94
997 2.13
3800 (1793)
4000 (1888)
784 1.42
789 1.48
4100(1935)
820 1.58
829 1.67
870 1.75
918
895 1.83
927
1.93
964 2.13
2.03
972 2.23
Notes:
1. Values include losses for filters, unit casing and wet coils.
2. Standard 2 HP motor to be used for the unshaded portion.
3. Alt. 3 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.
*
For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.
19
FAN PERFORMANCE DATA
Model No.: PQ120
Airflow,
0.2
0.4
3200 (1510) 680* 0.813*
753 1.01
3400 (1605) 697* 0.924*
768
I
1.13
3600 (1699) 716* 1.042*
782 1.26
0.6
External Static Pressure (inch wg.)
0.8
1.0
1.2
1.4
1.87
965 2.02
1029 2.18
1081 2.45
1131 2.72
2.03
970 2.19
1037 2.36
1088 2.63
2.21
985 2.37
1046 2.55
1096 2.83
2.39
995 2.56
1056 2.75
II
1.6
1.8
2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3800 (1793) 733* 1.17*
797 1.39
4000 (1888)
749 1.31
812 1.54
4200 (1982)
767 1.46
827 1.70
822 1.22
886
834 1.35
897
846 1.48
907
859 1.63
918
872 1.78
929
885 1.95
941
1.44
938 1.56
1006 1.69
1061 1.93
1114 2.17
1165 2.41
1.57
946 1.71
1013 1.85
1068 2.09
1120 2.34
1170* 2.60*
1.72
955 1.86
1021 2.01
1074 2.26
1125 2.53
1174* 2.79*
-
-
-
-
4400 (2076)
785 1.62
843 1.87
899 2.12
953
4600 (2170)
802 1.80
820 1.99
4800 (2265)
859 2.05
875 2.24
913 2.31
966
927 2.51
970
2.59
1006 2.77
2.80
Notes:
1. Values include losses for filters, unit casing and wet coils.
2. Standard 3 HP motor to be used.
3. Bordered regions indicate alternative drives I & II.
*
For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.
Model No.: PQ150
External Static Pressure (inch wg.)
Airflow,
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
2.59
1006 2.77
1066 2.96
1113 3.26
1160 3.57
2.80
1018 2.99
1076 3.19
1123 3.49
1168 3.80
3.02
1030 3.21
1087 3.42
1132 3.74 1177* 4.06*
1.8
2.0
CFM (L/S)
4000 (1888)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3800 (1793) 733* 1.17* 797* 1.39*
859 1.63
918
749* 1.31* 812*
I
1.54*
4200 (1982) 767* 1.46*
827 1.70
872 1.78
929
885 1.95
941
1.87
965 2.01
1029 2.18
1081 2.45
1131 2.72
1180* 2.99*
2.03
974 2.19
1037 2.36
1088 2.63
1137 2.91
2.21
985 2.37
1041 2.55
1096 2.83
1145 3.12
2.39
995 2.57
1056 2.75
1105 3.04
1152 3.34
II
-
4400 (2076) 785* 1.62*
843 1.87
4600 (2170) 802* 1.8*
859 2.05
4800 (2265)
5000 (2360)
820 1.99
838 2.18
875
891
2.24
2.45
899 2.12
953
913 2.31
966
927 2.51
981
942 2.73
991
856 2.40
907 2.67
957 2.95
1005 3.25
1042 3.46
1098 3.67
1142 3.99
5200 (2454)
5400 (2548)
5600 (2643)
874 2.62
898 2.86
944 3.12
925 2.90
944 3.15
972
987
3.19
3.45
1019
1032
3.50
3.76
1054
1067
3.71
3.98
1109
1121
3.93
4.21
956 3.41
1002 3.72
1047 4.03
1080 3.26
1133 4.50
1153
1163
4.26
4.54
5800 (2737)
Notes:
1. Values include losses for filters, unit casing and wet coils.
2. Standard 3 HP motor to be used for the unshaded portion.
3. Alt. 5 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.
*
For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.
Model No.: PQ180
External Static Pressure (inch wg.)
Airflow,
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM (L/S)
4800 (2265)
5000 (2360
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
652* 1.47* 711* 1.69*
668* 1.62*
725 1.85
I
728 1.93
763
740 2.10
773
2.18
826 2.25
2.26
844 2.43
880
888
2.53
928 2.57
970
2.62
933 2.77
975
II
2.92
1032 3.22
1075 3.54
3.12
1037 3.43
1077 3.75
5200 (2454) 683* 1.80*
738 2.03
5400 (2548) 699* 1.97*
752 2.21
5600 (2643) 719* 2.16*
766 2.41
5800 (2737)
731 2.36
781 2.61
6000 (2832)
6200 (2926)
6400 (3020)
6600 (3115)
746 2.58
762 2.80
778 3.05
794 3.30
795
809
824
838
2.84
3.07
3.32
3.58
6800 (3209)
7000 (3303)
7200 (3398)
809 3.40
825 3.70
861 4.00
870 3.70
884 4.00
897 4.30
752 2.28
783
764 2.47
807
776 2.67
818
797 2.78
830
811 2.91
854
830 3.15
865
843
857
3.45
3.67
877
887
2.34
853 2.62
896
2.54
858 2.80
2.74
872 3.03
2.96
882 3.26
3.19
893 3.50
3.36
904 3.75
3.65
914 3.85
3.97
927 4.08
904
913
926
939
948
960
968
2.91
3.12
3.13
3.57
3.61
3.86
4.09
4.41
940
948
955
963
972
981
1013
1030
3.11
3.18
3.45
3.66
3.89
4.19
4.46
4.71
981
1008
1017
1024
1031
1039
1047
1056
3.32
3.54
3.77
4.01
4.26
4.53
4.81
5.10
1042
1047
1053
1059
1066
1073
1077
1088
3.64
3.87
4.11
4.35
4.61
4.88
5.16
5.46
1083
1085
1092
1096
1102
1110
1115
1122
3.97
4.20
4.44
4.70
4.96
5.24
5.52
5.83
878 4.00
902 4.30
952 4.60
890 4.30
911 4.60
964 4.90
914 4.60
928
971
990
5.00
5.30
1041
1048
5.30
5.60
1065
1074
5.70
6.00
1098
1102
6.00
6.30
1129
1137
6.40
6.70
4.90
976 5.30
1001 5.60
1060 5.90
1083 6.30
1113 6.70
1145* 7.10*
Notes:
1. Values include losses for filters, unit casing and wet coils.
2. Standard 5 HP motor to be used for the unshaded portion.
3. Alt. 7.5 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.
*
For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.
20
FAN PERFORMANCE DATA
Model No.: PQ210
External Static Pressure (inch wg.)
Airflow,
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5800 (2737) 709* 2.21* 759* 2.46*
I
805 2.93
845
6000 (2832) 725* 2.42*
774 2.68
826 3.00
857
6200 (2926) 741* 2.65*
788 2.90
839 3.35
870
6400 (3020) 757* 2.90*
802 3.17
6600 (3115)
773 3.16
824 3.42
6800 (3209)
808 3.23
846 3.56
7000 (3303)
7200 (3398)
7400 (3492)
7600 (3587)
7800 (3681)
8000 (3775)
8200 (3870)
815
835
855
881
895
903
918
3.56
4.00
4.12
4.40
4.70
5.10
5.45
856 3.95
872
882 4.50
907
912 5.00
927
4.20
4.72
5.40
849
875
892
911
925
938
954
968
988
3.60
3.80
4.40
4.70
5.01
5.25
5.50
882
898
4.11
910
928
935
959
974
987
3.01
892 3.30
3.30
901 3.60
3.60
912 3.90
3.90
925 4.30
4.13
945 4.50
4.45
961 4.80
927
935
946
956
966
977
3.62
973 3.80
1031 4.12
1067 4.46
1103 4.81
3.80
982 4.20
1039 4.60
1074 4.92
1109 5.28
4.20
998 4.50
1047 4.85
1081 5.19
1111 5.55
4.60
1028 4.90
1058 5.20
1088 5.50
1122 5.85
4.80
5.11
1037
1047
5.10
5.41
1064
1074
5.42
5.75
1091
1106
5.78
6.16
1129
1137
4.73
972 5.00
990 5.34
1058 5.69
1082 6.05
1111 6.42
1145* 6.81*
5.00
978 5.35
1015 5.65
1064 5.98
1087 6.30
1120 6.8
1150* 7.23*
5.30
996 5.63
1032 5.93
1079 6.37
1095 6.75
1125 7.12
5.54
5.93
1008
1027
5.90
6.30
5.90
1001 6.25
1054 6.65
1067 7.08
945 5.72
1002 6.32
1016 6.70
1067 7.12
1046
1056
6.30
6.74
1086
1099
6.70
7.11
1099 7.11
II
6.15
6.47
Notes:
1. Values include losses for filters, unit casing and wet coils.
2. Standard 5 HP motor to be used for the unshaded portion.
3. Alt. 7.5 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.
*
For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.
Model No.: PQ240
External Static Pressure (inch wg.)
Airflow,
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6000 (2832) 577* 2.03* 586* 2.13*
689 2.24
741
586* 2.15* 642* 2.25*
695
I
2.36
746
6200 (2926
6400 (3020) 595* 2.27* 649* 2.24*
701 2.50
751
6600 (3115) 605* 2.39* 657* 2.51*
708 2.64
757
6800 (3209) 614* 2.52* 665* 2.64*
715 2.78
763
7000 (3303) 623* 2.66*
673 2.78
7200 (3398) 653* 2.80*
681 2.94
721
728
2.93
3.09
768
774
7400 (3492) 642* 2.95*
689 3.09
7600 (3587) 651* 3.10*
697 3.26
7800 (3681) 660* 3.26*
705 3.43
8000 (3775
670 4.43
714 3.60
735
743
750
757
3.25
3.43
3.60
3.79
780
787
793
800
8200 (3870)
8400 (3964)
8600 (4058)
8800 (4152)
9000 (4247)
679 3.61
689 3.79
698 3.98
707 4.17
716 4.38
707 3.65
730 3.98
739 4.17
747 4.38
756 4.59
764 3.97
806
772 4.17
813
780 4.38
820
787 4.59
826
795 4.81
833
2.36
790 2.68
837
2.49
795 2.83
841
2.63
799 2.98
845
2.78
804 3.13
850
2.93
809 3.29
854
3.09
814 3.46
858
3.25
819 3.63
862
3.43
824 3.81
867
3.61
828 3.97
872
3.79
835 4.18
875
3.98
841 4.38
882
4.17
847 4.59
4.38
853 4.80
4.59
859 5.02
887
892
898
4.81
865 5.24
903
5.04
871 5.48
909
3.02
882 3.12
926
3.17
886 3.28
928
3.33
889 3.44
931
3.49
893 3.61
935
3.66
897 3.79
938
3.83
900 3.97
941
4.01
904 4.15
945
4.20
908 4.35
948
4.39
913 4.55
952
4.59
917 4.75
956
4.79
921 4.97
960
5.01
926 5.18
964
5.23
930 5.41
968
5.45
935 5.64
972
5.68
940 5.88
977
5.93
945 6.13
981
3.48
967
3.64
969
3.81
972
3.99
975
4.17
978
4.36
981
4.55
984
4.75
987
3.84
1006 4.22
4.01
1009 4.39
4.19
1011 4.58
4.38
1014 4.77
4.57
1016 4.97
4.76
1019 5.17
4.96
1022 5.38
5.17
1024 5.59
4.96
990
5.17
994
5.38
1027 5.81
5.60
1030 6.04
5.40
997 5.83
1034 6.28
5.62
1001 6.07
1037 6.52
5.86
1004 6.31
1040 6.77
6.10
1008 6.56
1044 7.02
6.34
1012 6.81
6.60
II
Notes:
1. Values include losses for filters, unit casing and wet coils.
2. Standard 7.5 HP motor to be used for the entire range with either drive I & II.
3. Bordered regions indicate alternative drives I & II.
*
For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.
21
FAN PERFORMANCE DATA
Model No.: PQ300
Airflow,
CFM (L/S)
0.2
0.4
1.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8200 (3870) 679* 3.61* 707* 3.65*
8400 (3964) 689* 3.79*
730 3.98
8600 (4058) 698* 3.98*
739 4.17
8800 (4152) 707* 4.17*
747 4.38
9000 (4247) 716* 4.38*
756 4.59
9200 (4341)
726 4.42
9400 (4436)
9600 (4530)
744 4.84
9800 (4624)
735
754
4.61
5.07
764
773 4.83
781
4.71
5.21
790 5.31
10000 (4719)
763 5.31
10200 (4813)
777 5.57
10400 (4907)
782 5.83
10600 (5002)
792 6.09
10800 (5096)
801 6.37
11000 (5191)
810 6.65
11200 (5286)
820 6.95
799
808
817
825
834
843
852
5.56
5.82
6.09
6.36
6.65
6.94
7.24
764
I
0.6
3.97
External Static Pressure (inch wg.)
8000 (3775 670* 3.43* 714* 3.60*
757 3.79
800
806
772 4.17
813
780 4.38
820
787 4.59
826
795 4.81
833
803 4.92
840
810 5.07
848
818 5.31
855
826
834
5.56
6.22
862
869
842 6.48
874
850 6.76
884
859 7.04
892
867 7.33
900
875 7.63
907
883 7.94
915
0.8
1.0
3.98
841 4.38
882 4.79
4.17
847 4.59
887 5.01
4.38
853 4.80
4.59
859 5.02
892
898
5.23
5.45
4.81
865 5.24
5.04
871 5.48
5.27
875 5.72
5.51
884 5.97
903
909
914
920
5.68
5.93
6.17
6.43
5.76
891 6.22
6.02
897 6.49
6.38
904 6.76
6.66
911 7.04
6.94
918 7.33
7.23
925 7.63
1.2
926 6.69
932 6.97
938 7.25
945 7.53
951 7.83
958 8.13
7.53
932 7.93
7.84
939 8.25
8.15
946 8.57
978 9.10
1.4
921 4.97
960
926 5.18
964
930 5.41
968
935 5.64
972
940 5.88
977
945 6.13
981
950 6.39
986
956 6.65
991
961 6.92
995
967 7.20
1001
7.41
7.70
1029
1034
7.90
8.20
1063
1067
8.41
8.71
972
978
7.49
7.78
1006
1011
7.99
8.29
1039
1044
8.50
8.81
984 8.13
1016 8.60
1049 9.13
990 8.40
1022 8.92
1071
1076
II
9.02
9.33
964 8.45
996 8.72
1028 9.25
971 8.77
1002 9.05
1.8
2.0
5.40
997 5.83
1034 6.28
5.62
1001 6.07
1037 6.52
5.86
1004 6.31
1040 6.77
6.10
1008 6.56
1044 7.02
6.34
1012 6.81
1047 7.28
6.60
1016 7.07
1051 7.55
6.86
1021 7.34
1055 7.83
7.13
1025 7.62
1059 8.12
Notes:
1. Values include losses for filters, unit casing and wet coils.
2. Standard 7.5 HP motor to be used for the unshaded portion.
3. Alt. 10 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.
*
For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.
Model No.: PQ360
External Static Pressure (inch wg.)
Airflow,
CFM (L/S)
0.2
0.4
9600 (4530) 645* 5.40* 675* 5.70*
9800 (4624) 655* 5.60* 685* 5.90*
10000 (4719) 665* 5.80*
695 6.10
10200 (4813) 675* 6.00*
705 6.30
715 6.50
10400 (4907) 685* 6.20*
10600 (5002)
695 6.40
10800 (5096)
705 6.60
725
735
6.70
6.90
11000 (5191)
715 6.80
745 7.10
11200 (5286)
725 7.00
11400 (5380)
735 7.20
11600 (5474)
745 7.40
11800 (5569)
755 7.60
755 7.30
765
775
785
7.50
7.70
7.90
12000 (5663)
765 7.80
12200 (5757)
775 8.00
12400 (5852)
785 8.20
12500 (5899)
795 8.40
795
805
815
825
8.10
8.30
8.50
8.70
0.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
705 6.10
730
715
I
6.30
740
725 6.50
750
735 6.70
760
745 6.90
770
755 7.10
780
765 7.30
790
775 7.50
800
785 7.70
810
795
805
7.90
8.10
820
830
815 8.30
840
825
835
8.50
8.70
850
860
845
855
8.90
870
9.10
880
0.8
1.0
1.2
6.50
760 7.00
790 7.40
6.70
770 7.20
800 7.60
6.90
780 7.40
810 7.80
7.10
790 7.60
820 8.00
7.30
800 7.80
830 8.20
7.50
810 8.00
840 8.40
7.70
820 8.20
7.90
830 8.40
850
860
8.60
8.80
1.4
825 7.90
850
835 8.10
860
845 8.30
870
855 8.50
880
865 8.70
890
875 8.90
900
885 9.10
910
895 9.30
920
1.6
8.40
880
8.60
890
8.80
900
9.00
910
1.8
II
8.80
910
9.00
920
9.20
930
2.0
9.40
9.60
9.80
9.40
940 10.00
9.20
920
9.40
930
9.60
950 10.20
9.80
960 10.40
9.60
940 10.00
970 10.60
9.80
950 10.20
980 10.80
8.10
840 8.60
8.30
850 8.80
8.50
860 9.00
8.70
870 9.20
870
880
890
900
9.00
9.20
9.40
9.60
905
915
925
9.50
9.70
930
940
10.00
10.20
960
970
10.40
990 11.00
10.60 1000 11.20
9.90
950 10.40
980 10.80 1010 11.40
935 10.10
960 10.60
990 11.00 1020 11.60
8.90
880 9.40
9.10
890 9.60
910 9.80
945 10.30
970 10.80 1000 11.20 1030 11.80
920 10.00
955 10.50
980 11.00 1010 11.40 1040 12.00
9.30
900 9.80
930 10.20
965 10.70
990 11.20 1020 11.60 1050 12.20
9.50
910 10.00
940 10.40
975 10.90 1000 11.40 1030 11.80 1060 12.40
Notes:
1. Values include losses for filters, unit casing and wet coils.
2. Standard 10 HP motor to be used for the unshaded portion.
3. Alt. 15 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.
*
For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.
22
SOUND LEVEL DATA
To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP (see step 4 & table below).
2. Read dBA level from respective graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from sound power factor table and add dBA level to each values in the row to obtain
Sound Power Level (dB re 10
-12 watts).
4. Calculate TSP (Total Static Pressure) as follows:
TSP = ISP + ESP
ESP (External Static Pressure) from Job Specification.
ISP (Internal Static Pressure) Calculate from table below.
FACE VELOCITY
(FPM)
INTERNAL STATIC PRESSURE (inch wg.)
200
300
400
450
2 ROW
0.42
0.67
0.88
1.02
3 ROW
0.44
0.73
0.95
1.13
500 1.16
1.29
NOTE:
Pressure drop across filter, coil and casing are included in ISP.
4 ROW
0.47
0.78
1.05
1.23
1.49
23
SOUND LEVEL DATA
MODELS: PQ036 - PQ060
SOUND POWER FACTOR TABLE
VALUES GIVE TO SOUND POWER
Octave Band
Center Frequency – Hz
493-887 RPM
887-1750 RPM
1750-2500 RPM
63
– 7.5
– 8
– 8
125
+ 0.5
+ 0.5
+ 0.5
250
+ 7.5
+ 7
+ 7
500
+ 10.5
+ 7
+ 7
1000
+ 5.5
+ 8
+ 5
2000
+ 2
+ 1.5
+ 4.5
4000
– 1
– 1.5
– 1.5
8000
– 6.5
– 6.5
– 6.5
To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10
-12 watts).
24
SOUND LEVEL DATA
MODELS: PQ075 - PQ090
SOUND POWER FACTOR TABLE
VALUES GIVE TO SOUND POWER
Octave Band
Center Frequency – Hz
251-495 RPM
495-990 RPM
990-1953 RPM
1953-2050 RPM
63
– 6
– 6.5
– 7
– 7
125
+ 2
+ 1.5
+ 1.5
+ 1.5
250
+ 11.5
+ 8
+ 8
+ 8
500
+ 8
+ 10.5
+ 7
+ 7
1000
+ 5.5
+ 5
+ 8
+ 5
2000
+ 2
+ 1.5
+ 1.5
+ 4.5
4000
– 1
– 1.5
– 2
– 2
8000
– 6.5
– 7
– 7.5
– 7.5
To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10
-12 watts).
25
SOUND LEVEL DATA
MODELS: PQ100 - PQ210
Octave Band
Center Frequency – Hz
211-417 RPM
417-835 RPM
835-1647 RPM
63
– 4.5
– 5.5
– 5.5
SOUND POWER FACTOR TABLE
VALUES GIVE TO SOUND POWER
125
+ 3
+ 2.5
+ 2.5
250
+ 12
+ 8.5
+ 8
500
+ 8
+ 10.5
+ 7
1000
+ 5
+ 4.5
+ 7
2000
+ 2
+ 1.5
+ 1
4000
– 1.5
– 2
– 2.5
8000
– 7
– 7.5
– 7.5
To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10
-12 watts).
26
SOUND LEVEL DATA
MODELS: PQ240 - PQ300
Octave Band
Center Frequency – Hz
255-443 RPM
443-887 RPM
887-1750 RPM
63
– 3.5
– 4
– 4
SOUND POWER FACTOR TABLE
VALUES GIVE TO SOUND POWER
125
+ 4
+ 3.5
+ 3.5
250
+ 12.5
+ 9
+ 8.5
500
+ 8
+ 10
+ 7
1000
+ 4.5
+ 4
+ 7
2000
+ 1.5
+ 1
+ 0.5
4000
– 2
– 2.5
– 3
8000
– 7.5
– 8
– 8
To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10
-12 watts).
27
SOUND LEVEL DATA
MODEL: PQ360
Octave Band
Center Frequency – Hz
267-507 RPM
507-1014 RPM
1014-2000 RPM
63
– 3
– 3.5
– 4
SOUND POWER FACTOR TABLE
VALUES GIVE TO SOUND POWER
125
+ 4.5
+ 3.5
+ 3.5
250
+ 12.5
+ 9
+ 8.5
500
+ 7.5
+ 10
+ 7
1000
+ 4.5
+ 4
+ 6.5
2000
+ 1.5
+ 0.5
+ 0.5
4000
– 2
– 2.5
– 3
8000
– 7.5
– 8
– 8
To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite to the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10
-12 watts).
28
STATIC PRESSURE DROP (inch wg.)
MODELS: PQ036 - PQ060
COMPONENT
1 HEATER MODULE
2 HEATER MODULE
900
0.12
0.19
1200
0.12
0.19
1400
0.12
0.19
CFM
1600
0.13
0.20
1800
0.14
0.21
2000
0.15
0.21
MODELS: PQ075 - PQ090
COMPONENT
1 HEATER MODULE
2 HEATER MODULE
CFM
1600 1800 2000 2200 2400 2600 3000 3200 3400 3600 3800
0.11
0.12
0.13
0.13
0.14
0.15
0.16
0.16
0.17
0.18
0.18
0.18
0.19
0.19
0.19
0.20
0.20
0.21
0.21
0.22
0.23
0.23
MODELS: PQ100 - PQ150
COMPONENT
1 HEATER MODULE
2 HEATER MODULE
CFM
2600 2800 3000 3400 3800 4000 4200 4800 5200 5800
0.04
0.06
0.04
0.06
0.05
0.07
0.08
0.10
0.10
0.12
0.11
0.14
0.12
0.15
0.14
0.18
0.16
0.18
0.20 0.22
MODELS: PQ180 - PQ210
COMPONENT
1 HEATER MODULE
2 HEATER MODULE
CFM
4800 5200 5600 6000 6200 6800 7000 7400 7600 7800 8200
0.08
0.08
0.08
0.08
0.08
0.09
0.10
0.10
0.10
0.11
0.11
0.14
0.14
0.14
0.14
0.14
0.16
0.16
0.16
0.16
0.17
0.17
MODELS: PQ240 - PQ360
COMPONENT
1 HEATER MODULE
2 HEATER MODULE
CFM
6000 6600 7200 7800 8400 9000 9600 10200 10800 11400 12000
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.13
0.22
0.14
0.23
0.15
0.24
BLOWER MOTOR EFFICIENCY
MOTOR HP
EFFICIENCY (%)
0.75
0.81
1.0
0.81
1.5
0.80
NOTE:
Convert BHP to watts using following formula
Watts = 746 x BHP
Motor Efficiency
2.0
0.81
3.0
0.81
5.0
0.80
7.5
0.81
10.0
0.80
29
UNIT DIMENSIONS
PQ036 - PQ060
NOTE:
1. All dimensions are in mm (dimensions in brackets are in inches).
30
24
[0.94]
UNIT DIMENSIONS
PQ075 - PQ150
POWER SUPPLY CONN
AIR OUT
CONDENSER COIL
D
B
SIDE VIEW
CONDENSER COIL
COMPRESSOR / CONTROLS
ACCESS PANEL
CONTROL COMPARTMENT
ACCESS PANEL
FOR BLOWER & MOTOR
M
CONDENSATE DRAIN OUTLET
3/4" NPT
AIR IN
(OPTIONAL)
FRESH AIR OPENING/HOOD
AIR IN SUPPLY AIR
TOP VIEW
RETURN AIR
K J H N
L
CONDENSER COIL
P
A
SUPPLY AIR
OPENING
RETURN AIR
OPENING
FRONT VIEW
Ø 12.7 ( 0.5) MOUNTING HOLES
(2 EACH SIDE)
SIDE VIEW
FILTER
ACCESS
PANEL
DRAIN OUTLET
DIMENSIONS
MODEL
A B C D E F G H J K L M N O P
PQ075 - PQ090
2080(81.89) 1162(45.75) 1034(40.71) 1114(43.86) 308(12.15) 550(21.64) 798(31.4) 300(11.81) 251(9.87) 396(15.59) 152(5.98) 175(6.88) 24(0.94) 171(6.73) 1775(69.88)
PQ100 - PQ150
2212(87.1) 1408(55.43) 1085(42.72) 1372(54) 255(10.03) 707(27.84) 790(31.1) 367(14.46) 190(7.48) 476(18.74) 150(5.91) 145(5.71) 48(1.89) 200(7.87) 1907(75.08)
NOTE:
1. All dimensions are in mm (dimensions in brackets are in inches).
31
UNIT DIMENSIONS
PQ180 - PQ360
CONDENSER COIL
A\IR IN
CONTROLS
ACCESS PANEL
ACCESS PANEL
FOR BLOWER & MOTOR
CONTROL COMPARTMENT
S
M
CONDENSATE DRAIN OUTLET
3/4" NPT
POWER INLET
POWER INLET
F
COMPRESSOR
ACCESS PANEL
A\IR IN
CONDENSER COIL
AIR IN SUPPLY AIR
TOP VIEW
RETURN AIR
AIR OUT
K U H N
CONDENSER COIL SUPPLY AIR
OPENING
RETURN AIR OPENING
(OPTIONAL)
FRESH AIR OPENING/HOOD
D
B
SIDE VIEW
G
X
L
A
FRONT VIEW
X G
D
B
16 x 25mm
MOUNTING SLOT (3EACH SIDE)
MOUNTING SLOT (4EACH SIDE-PY/PQ360)
SIDE VIEW
CONTROL BOX
ACCESS PANEL
DRAIN OUTLET
DIMENSIONS
MODEL
A B C D F G H K L N R S M U
PQ180 - PQ210
2794(110) 1778(70) 1266(49.83)1715(67.52) 1737(68.37) 197(7.75) 817(32.17) 720(28.35) 1200(47.25) 83(3.27) 912(35.9) 666(26.22) 194(7.64) 171(6.73)
X
-
PQ240 - PQ300
3048(120) 2196(86.44) 1446(56.94) 2135(84.1) 2152(84.72) 324(12.76) 915(36.02) 740(29.13) 1200(47.25) 84(3.31) 1050(41.34) 666(26.22) 289(11.38) 194(7.64)
PQ360
3683(145) 2184(86) 1446(56.94)2125(83.66) 2184(86) 42(1.65) 938(36.93) 527(20.75) 97(3.83) 1000(39.37) 680(26.77) 254(10)
-
372(14.65) 1125(44.29)
NOTE:
1. All dimensions are in mm (dimensions in brackets are in inches).
32
Performex-1
TM
CONTROLLER: OPERATION & FUNCTIONS
LCD display:
a) Room temperature display b) Mode of operation (Cool/Heat/Auto/Fan system control) c) Set temperature d) Compressor Status - ON/OFF/FAULT e) Error Codes
1. ON/OFF:
Press the ON/OFF button & the unit shall be switched ON. A status Led adjacent to this button shall light up indicating the unit is switched ON. To shut off the unit, press this button again.
2. MODE:
Press the mode button to select the desired mode. On selection the corresponding icon shall be displayed on the LCD display panel.
3. TEMPERATURE RANGE AND SETTING:
The operating temperature range is 16
0
C to 30
0
C (61
0
F to 86
0
F), both inclusive. Press the UP or DN button to select the desired temperature. The temperature setting is effective only for the Cool, Heat and Auto modes.
4. INDOOR (EVAPORATOR) FAN:
There is one indoor fan with single fan speed. When fan speed on LCD panel is
HIGH, indoor fan will always turns on. Indoor fan can be set off, when the compressor is cut off by setting the fan speed to AUTO on the LCD panel by pressing Fan button. By pressing the Fan button again the fan speed can resume to HIGH.
5. COOL MODE:
Whenever the unit is started in cool mode (without Pump Down Solenoid-PDS), the compressors will be turned on one by one depending on the load requirement of the unit.
6. HEAT MODE
(HEATER MODEL): Whenever the unit is started in heat mode, the heaters shall be switched ON one by one to meet the load requirement.
33
7. LEAD/LAG OPERATION:
Whenever a compressor needs to be on, the controller will turn on the compressor with the shorter accumulated run time provided its 3 minutes minimum off time has lapsed. Otherwise the other compressor will on first. Similarly, the compressor with the longer accumulated run time will be the first one to be cut off. This is to load the compressors evenly over long run period. Balance loading is enabled when compressor #1 lead option is disabled.
8. AUTO MODE:
In Auto mode, operating mode will be selected automatically between Heat and Cool mode, depending on the Room Temperature and Set Temperature.
PROTECTION
The following safeties are provided for the system:
1. Compressor high pressure protection (option)
2. Compressor low pressure protection
TYPICAL HIGH AND LOW VOLTAGE FIELD WIRING CONNECTIONS
L1 L2 L3 N
(FOR 380V ONLY)
FUSED DISCONNECT SWITCH
OR CIRCUIT BREAKER
PACKAGE UNIT
CONTROL PANEL
N
G
L1
L2
L3
LEGEND
ECB - ELECTRONIC CONTROL BOARD
HVTB - HIGH VOLTAGE TERMINAL BLOCK
LI - LINE1
L2 - LINE2
L3 - LINE3
N - NEUTRAL TERMINAL BLOCK
G - GROUND
FIELD WIRING
CONTROL WIRES-INTERCONNECTING
( USE 16 TO 22 AWG WIRE)
A B +5V GND
INDOOR THERMOSTAT
34
TYPICAL SCHEMATIC WIRING DIAGRAM
NOTE:
1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
35
TYPICAL SCHEMATIC WIRING DIAGRAM
LEGEND
AR
AFS
ATB
BM
BMC
CC
CCA
CB
AUXILIARY RELAY
AIRFLOW SWITCH
AUXILIARY TERMINAL BLOCK
BLOWER MOTOR
BLOWER MOTOR CONTACTOR
COMPRESSOR CONTACTOR
AUXILIARY CONTACT
CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP COMPRESSOR
ECB
FCS
ELECTRONIC CONTROL BOARD
FAN CYCLING SWITCH
F
FL
FM
FMC
FUSE
FUSE LINK
FAN MOTOR (CONDENSER)
FAN MOTOR CONTACTOR
L3
LPS
LUG
NTB
O/L
OHT
PDS
FR
HC
FAULT RELAY
HEATER CONTACTOR
HPS HIGH PRESSURE SWITCH
HVTB HIGH VOLTAGE TERMINAL BLOCK
HTR
JP
L1
L2
HEATER
JUMPER
LINE 1
LINE 2
LINE 3
LOW PRESSURE SWITCH
LUG GROUND
NEUTRAL TERMINAL BLOCK
OVER LOAD
OVER HEAT THERMOSTAT
PUMP DOWN SOLENOID
SSPS SOLID STATE PROTECTIVE SYSTEM
SD SMOKE DETECTOR
TRANS TRANSFORMER
T'STAT THERMOSTAT
T.O.P.
THERMAL OVERLOAD PROTECTION
UVM
_ _ _
UNDER VOLTAGE MONITOR
FIELD WIRING
+ DISCONNECT TAB - 1/4"
SPLICE-CLOSED END
TERMINAL BLOCK OR TERMINATION POINT
NOTES
1. POWER SUPPLY, 380/415V-3Ph.-50Hz.
2. ANY WIRE REPLACEMENT SHOULD BE OF 90 0 C OR ITS
EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY.
3. IF PDS & HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.
4. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR
MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE
HEATER MUST BE ON FOR 12 HOURS BEFORE OPER-
ATING THE SYSTEM.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE-
SULT IN COMPRESSOR DAMAGE.
5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
TO BE PROVIDED BY CONSUMER WITH RATING AS
RECOMMENDED BY COOLINE.
6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVERLOAD.
7. IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS
SHOWN. PLEASE ALLOW 2-3 MINUTES FOR SSPS SWITCH
TO CLOSE, BEFORE STARTING THE UNIT.
8. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,
TURN OFF POWER FIRST & SET REQUIRED SETTING.
36
PARTS LIST
MODEL NUMBER
COMPRESSOR
CONDENSER FAN MOTOR
BLOWER MOTOR
BLOWER WHEEL
CONDENSER FAN PROPELLER
CONTACTOR COMPRESSOR
CONTACTOR BLOWER MOTOR
CAPACITOR FAN MOTOR
AIR FLOW SWITCH
LOW PRESSURE CONTROL
FAN GRILLE
FILTER DRIER
PQ036L
800-684-08
800-555-26
800-546-94
800-707-34
800-225-02
800-095-01
800-736-27
800-353-15
800-005-02
800-557-00
800-625-46
800-531-08
PQ048L
800-672-52
800-555-26
800-546-94
800-707-34
800-225-02
800-095-01
800-736-27
800-353-15
800-005-02
800-557-00
800-625-46
800-531-08
PQ060L
800-643-01
800-555-26
800-546-95
800-707-34
800-225-02
800-095-01
800-736-27
800-353-15
800-005-02
800-557-00
800-625-46
800-531-08
MODEL NUMBER
COMPRESSOR
CONDENSER FAN MOTOR
BLOWER MOTOR
BLOWER WHEEL
CONDENSER FAN PROPELLER
CONTACTOR COMPRESSOR
CONTACTOR BLOWER MOTOR
CONTACTOR COND. FAN MOTOR
AIRFLOW SWITCH
EXPANSION VALVE
DISTRIBUTOR
PQ075L PQ090L PQ100L PQ120L PQ150L PQ180L PQ210L PQ240L PQ300L PQ360L
800-674-78 800-684-09 800-672-52 800-674-25 800-674-78
800-674-81
800-674-67
800-674-38 800-674-19 800-674-12 800-674-72
800-545-68 800-545-68 800-545-68 800-545-68 800-545-68 800-545-68 800-545-68 800-555-06 800-555-06 800-555-06
800-544-13 800-544-16 800-544-16 800-544-17 800-544-17 800-544-40 800-544-40 800-544-73 800-544-73 800-544-74
800-707-46 800-707-46 800-707-02 800-707-02 800-707-02 800-707-02 800-707-02 800-707-23 800-707-23 800-707-94
800-224-23 800-224-23 800-224-23 800-224-23 800-224-23 800-224-23 800-224-23 800-224-28 800-224-28 800-224-28
800-095-01 800-095-01 800-095-01 800-095-01 800-095-01 800-736-22 800-736-22 800-736-22 800-736-22 800-736-22
800-095-01 800-095-01 800-095-01 800-095-01 800-095-01 800-095-01 800-098-55 800-098-55 800-098-55 800-098-55
N.A.
800-095-01 800-095-01 800-095-01 800-095-01 800-095-01 800-095-01 800-095-01 800-095-01 800-095-01
800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02
800-195-35 800-195-17 800-195-20 800-195-22 800-195-35 800-182-00 800-182-00 800-185-00 800-186-00 800-186-00
800-194-18 800-194-15 800-194-15 800-194-18 800-194-18 800-196-00 800-196-00 800-194-01 800-192-02 800-196-16
LOW PRESSURE CONTROL 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
HIGH PRESSURE CONTROL (OPTION) 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00
FAN GRILLE
FILTER DRIER
800-625-29 800-625-29 800-625-29 800-625-29 800-625-29 800-625-74 800-625-74 800-625-38 800-625-38 800-625-38
800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-05 800-531-05 800-531-05 800-531-05 800-531-01
37
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 Features
- 4 Model decoding
- 4 Blower drive options
- 5 Standard specifications/options/accessories
- 8 General data
- 10 Selection procedure
- 11 Cooling capacities
- 16 Electrical data
- 18 Fan performance data
- 23 Sound level data
- 29 Pressure drop/blower motor efficiency
- 30 Unit dimensions
- 33 Controls and sequence of operation
- 35 Typical schematic wiring diagram