Powerware 9315 Hot Sync Parallel Redundant (1+1) UPS Module
Powerware 9315 Hot Sync Parallel Redundant (1+1) UPS Module (UPM)
®
®
®
Modbus Profile
164950160 Rev B
Read Input Status
Modbus Function Code 02
Input registers start at 10000.
Register Name
Value
Format
Unit
1 On Battery
0
BOOL
Status
10 On Bypass
0
BOOL
Status
11 System Normal
1
BOOL
Status
16 UPS Off
0
BOOL
Status
112 Rectifier Status
1
BOOL
Status
113 Rectifier Input Status
1
BOOL
Status
114 Bypass Status
0
BOOL
Status
115 Bypass Input Status
1
BOOL
Status
116 Input Circuit Breaker Status (CB1)
1
BOOL
Status
117 Battery Disconnect Status
1
BOOL
Status
118 Inverter Disconnect Status
1
BOOL
Status
119 Inverter Status
1
BOOL
Status
120 UPM Normal
0
BOOL
Status
121 UPM On Battery
0
BOOL
Status
122 UPM Bypass (Off Line)
0
BOOL
Status
123 UPM Notice
0
BOOL
Status
124 UPM Alarm
0
BOOL
Status
125 UPM Standby
0
BOOL
Status
128 MOB Closed
1
BOOL
Status
129 System Redundant
1
BOOL
Status
144 Inverter AC over voltage
0
BOOL
Status
NOTE Registers 1 – 16 are mutually exclusive.
Register Name
2
Value
Format
Unit
145 Inverter AC under voltage
0
BOOL
Status
146 Inverter under or over frequency
0
BOOL
Status
147 Bypass AC over voltage
0
BOOL
Status
148 Bypass AC under voltage
0
BOOL
Status
149 Bypass under or over frequency
0
BOOL
Status
150 Input AC over voltage
0
BOOL
Status
151 Input AC under voltage
0
BOOL
Status
152 Input under or over frequency
0
BOOL
Status
153 Output AC over voltage
0
BOOL
Status
154 Output AC under voltage
0
BOOL
Status
155 Output under or over frequency
0
BOOL
Status
158 Building Alarm 6
0
BOOL
Status
159 Building Alarm 5
0
BOOL
Status
160 Building Alarm 4
0
BOOL
Status
161 Building Alarm 3
0
BOOL
Status
162 Building Alarm 2
0
BOOL
Status
163 Building Alarm 1
0
BOOL
Status
169 Output overload
0
BOOL
Status
172 DC link over voltage
0
BOOL
Status
173 DC link under voltage
0
BOOL
Status
174 Rectifier failed
0
BOOL
Status
176 Battery contactor fail
0
BOOL
Status
177 Bypass breaker fail
0
BOOL
Status
191 Battery current limit
0
BOOL
Status
194 Output current over 100%
0
BOOL
Status
199 Shutdown imminent
0
BOOL
Status
200 Battery low
0
BOOL
Status
212 Battery DC over voltage
0
BOOL
Status
214 Power supply failure
0
BOOL
Status
EATON Powerware® 9315 Hot Sync® Parallel Redundant (1+1) UPS Module (UPM) Modbus® Profile S 164950160 Rev B
Register Name
Value
Format
Unit
217 Reserved
0
BOOL
Status
218 Reserved
0
BOOL
Status
229 Network not responding
0
BOOL
Status
234 Reserved
0
BOOL
Status
241 Emergency shutdown command
0
BOOL
Status
249 Bypass not available
0
BOOL
Status
251 Battery contactor open
0
BOOL
Status
252 Inverter contactor open
0
BOOL
Status
270 Battery totally discharged
0
BOOL
Status
295 Battery not charged
0
BOOL
Status
312 UPS On Battery
0
BOOL
Status
313 UPS On Bypass
0
BOOL
Status
314 Load Dumped (Load Power Off)
0
BOOL
Status
337 Fan Failure
0
BOOL
Status
345 Transformer Over Temperature
0
BOOL
Status
361 Input Breaker Failed
0
BOOL
Status
EATON Powerware® 9315 Hot Sync® Parallel Redundant (1+1) UPS Module (UPM) Modbus® Profile S 164950160 Rev B
3
Read Input Registers
Modbus Function Code 04
Input registers start at 30000.
Register Meter Name
4
Scale
Unit
1 OUTPUT VOLTS AB
/10
Volts
2 OUTPUT VOLTS BC
/10
Volts
3 OUTPUT VOLTS CA
/10
Volts
4 INPUT VOLTS AB
/10
Volts
5 INPUT VOLTS BC
/10
Volts
6 INPUT VOLTS CA
/10
Volts
10 BYPASS VOLTS AB
/10
Volts
11 BYPASS VOLTS BC
/10
Volts
12 BYPASS VOLTS CA
/10
Volts
19 INPUT CURRENT PHASE A
/10
Amps
20 INPUT CURRENT PHASE B
/10
Amps
21 INPUT CURRENT PHASE C
/10
Amps
22 OUTPUT TRUE POWER
/10
kW
23 INPUT TRUE POWER
/10
kW
24 OUTPUT APPARENT POWER
/10
kVA
25 INPUT APPARENT POWER
/10
kVA
26 OUTPUT POWER FACTOR
/100
--
27 INPUT POWER FACTOR
/100
--
28 OUTPUT FREQUENCY
/10
Hz
29 INPUT FREQUENCY
/10
Hz
30 INVERTER FREQUENCY
/10
Hz
31 BYPASS FREQUENCY
/10
Hz
33 BATTERY CURRENT
/10
Amps
34 BATTERY VOLTAGE
/10
Volts
35 % BATTERY LEFT
/10
%
36 BATTERY TIME REMAINING
/10
Minutes
60 INVERTER VOLTS PHASE A
/10
Volts
61 INVERTER VOLTS PHASE B
/10
Volts
62 INVERTER VOLTS PHASE C
/10
Volts
66 LOAD CURRENT PHASE A
/10
Amps
EATON Powerware® 9315 Hot Sync® Parallel Redundant (1+1) UPS Module (UPM) Modbus® Profile S 164950160 Rev B
Register Meter Name
Scale
Unit
67 LOAD CURRENT PHASE B
/10
Amps
68 LOAD CURRENT PHASE C
/10
Amps
69 LOAD CURRENT PHASE A BAR CHART
/10
Amps
70 LOAD CURRENT PHASE B BAR CHART
/10
Amps
71 LOAD CURRENT PHASE C BAR CHART
/10
Amps
72 OUTPUT VA BAR CHART
/10
kVA
79 OUTPUT VOLTS A
/10
Volts
80 OUTPUT VOLTS B
/10
Volts
81 OUTPUT VOLTS C
/10
Volts
Powerware and Powerware Hot Sync are registered trademarks of Eaton Power Quality Corporation.
Modbus is a registered trademark of Modicon.
EATON Powerware® 9315 Hot Sync® Parallel Redundant (1+1) UPS Module (UPM) Modbus® Profile S 164950160 Rev B