electro-boiler - Electro Industries
ELECTRO-BOILER
Commercial Series
INSTALLATION & OPERATING INSTRUCTIONS
Model EB-C* Series
LOCATE EXACT NUMBER ON NAMEPLATE, LOCATE LINE ITEM ON PAGE 1
APPLICATION:
This Electro-Boiler is factory equipped with WarmFlo smart controller.
WarmFlo automatically regulates outlet water temperature at the temperature
level set on the front panel. This is a dial switch having six positions. Setting of
this dial is dependent upon the model of Electro-Boiler being installed. Two
possible scenarios exist:
 EB-CA-**-** – These models do not utilize an outdoor temperature
sensor. Setting the dial is a fixed value – 90° F – 176°F.
 EB-CO-**-** – These models utilize an outdoor sensor, thus the boiler
output target temperature will shift based on the outdoor temperature.
The values listed on the front decal represent a desired output at 0° F
outside.
Primary application is any hydronic water heating system where reduced flow or
radiation can cause overheat conditions (example, zones). However, if it is a
mixture of large and small zones, the sudden capacity and flow changes may
cause some internal timing/overtemp conditions. With the mixture of zones the
zone controller ZEA-* option is highly recommended (see page 3).
This series is equipped for load management interrupt and can apply to standard
baseboard radiation, dual heat combinations, under floor radiant, wood boiler
supplement, etc.
ACCESSORIES:
Attached BL001 lists various accessory or option items which are not part of
basic Electro-Boiler. Also page 4 has additional information on slab stat. Page 3
gives information on a zone control update which stages elements based upon
zone capacity.
Note: This product meets the requirements of the ASME Boiler and Pressure
Vessel Code.
Drawings:
BX503
BX504
BH505
BH506
Warranty:
XX017 – Single Phase Models
XX024 – 3-Phase Models
06/03/2011
BS505
BS506
BL001
BI507
TABLE OF CONTENTS
Description
Page
Table 1, Specific Model Number, Specific Information
1
Introduction
2
System or Water Flow
3
Multiple Zones & Radiant Temperatures
3
Zone Controller
3
Room Thermostat Placement
4
Multiple Boilers
4
Two-Temperature Operation or Feature
5
Installation Requirements
5
Mechanical Installation
Under-Floor Radiant
7
Dual Heat
8
Electrical Hookup
9
Standby Boiler
10
Remote Display
10
Water Fill Procedure
10
Controller Setup
11
Operational Tips
12
Replacement Parts List
13
Troubleshooting/Repair Helps
13
WarmFlo Operational Information
15
Drawings:
Basic Mechanical and Piping
BX503, BX504
Hookup
BH505, BH506
Internal Wiring Schematic
BS505, BS506
Boiler Accessories
Warranty
06/03/2011
BL001
XX017 – Single Phase Models
XX024 – 3-Phase Models
BI507
Table 1 – Specific Model Number, Specification Information
Stages – kW
Model
EB-C*-18-60
EB-C*-24-60
EB-C*-30-60
EB-C*-36-60
EB-C*-45-60
EB-C*-54-60
EB-C*-18-48
EB-C*-36-48
EB-C*-54-48
EB-C*-27-20
EB-C*-40-20
EB-C*-27-24
EB-C*-40-24
EB-C*-31
EB-C*-36
EB-C*-40
EB-C*-44
Voltage
Rating
600V
3-phase
600V
3-phase
600V
3-phase
600V
3-phase
600V
3-phase
600V
3-phase
480V
3-phase
480V
3-phase
480V
3-phase
208V
3-phase
208V
3-phase
240V
3-phase
240V
3-phase
240V
Single
phase
240V
Single
phase
240V
Single
phase
240V
Single
phase
*A = Staging
06/03/2011
kW
Rating
Disconnect
CB
Source
Terminals
Element
Qty
Btu/h
18
61,500
18
30
3
24
82,000
23
30
30
102,500
29
36
123,000
45
Amps
1
2
3
3
6
6
6
3
6
4
4
8
45
3
6
5
5
35
45
3
6
6
153,500
44
60
3
9
54
184,500
52
70
3
18
61,500
22
30
36
123,000
44
54
184,500
27
Flow Rate
@15° ΔT
Min
Max
GPM GPM
4
4
8
8
4
11
10
10
4
14
6
12
12
4
16
5
10
15
15
4
20
9
6
12
18
18
4
24
3
3
6
6
6
-
4
8
60
3
6
6
6
12
12
4
16
65
80
3
9
6
12
18
18
4
24
92,000
75
100
3
6
4.5
4.5
9
9
4
12
40.5
138,000
113
150
3
9
4.5
9
13.5
13.5
4
18
27
92,000
65
80
3
6
4.5
4.5
9
9
4
12
40.5
138,000
98
125
3
9
4.5
9
13.5
13.5
4
18
31.5
107,500
131
80 + 100
2+2
7
9
9
9
4.5
4
14
36
123,000
150
100 + 100
2+2
8
9
9
9
9
4
16
40
136,500
167
125 + 125
2+2
8
10
10
10
10
4
18
44
150,000
183
125 + 125
2+2
8
11
11
11
11
4
20
O = Staging with Outdoor Reset
1
BI5072
INTRODUCTION
With this WarmFlo configuration, the electric heating elements are automatically controlled to establish a
fixed outlet water temperature. This outlet temperature is sensed by the WarmFlo controller and is
controlled by outside temperature and by setup parameters.
Even though this WarmFlo configured unit adjusts outlet temperature independent of water flow and
prevents high limiting even with marginal water flow, it is still very important that the hydronic system be
correctly designed for the building, the total heat loss requirement, and proper hydronics design and
installation practices. This boiler is the energy source for the water flow and radiation system. If the
water flow and radiation systems are not adequate for the Btuh heat loss of the building, installing the
Electro-Boiler with WarmFlo will not necessarily supply the comfort and heating for the building.
Control and operate as a “cold boiler” concept. Do not, under any circumstances, simply jumper R and W
and allow the temperature sensing controller to operate this Electro-Boiler as a “hot boiler”. Unless there
is at least 4 GPM flow, the staging delays will cause temperature overshoot and could open up the manual
reset limits.
In most dual heat installations this Electro-Boiler is plumbed in series with an existing oil, gas, or wood
boiler. For gas or oil, the Electro-Boiler is generally at the gas/oil outlet; but for wood, the Electro-Boiler
must be on the inlet sides. The standby boiler cannot be operated as “hot boiler”. This will defeat the
Electro-Boiler. Rewire as required using EB-S-SB, standby boiler is turned on from the brown wires.
In the case of existing fossil fuel boiler conversions, it is assumed the expansion tank, valving, air
bleeder, and circulation pump are in place, in good operating condition, and adequate for the overall
system design.
In the case of new installation (floor radiant or baseboard), use standard hydronics water heating practices
for the necessary expansion tank, air bleeder, valving, water pump, etc., sized for the total capacity of the
system. The Electro-Boiler is turned on with an “R and W” closure from the zone system wiring.
The Table 1 model number identification shows the design rating and voltage source required for the
specific model. If you do not use the voltage source required for the specific model, performance derating may need to be taken into consideration. Also damage can result if the specific model is not
serviced with the voltage source shown in Table 1.
This EB-C*-** model series is low pressure (30 psig maximum) hydronic hot water with an operating
range between 90° F and 176° F, supply temperature.
06/03/2011
2
BI5072
APPROVED TUBING/PIPING
When plumbing this boiler and its peripheral parts to the loop system, all plumbing parts and/or tubing
must be sealed to prevent entrance of oxygen.
Use only tubing or polyethylene tubing with oxygen Diffusion Barrier.
SYSTEM OR WATER FLOW
In order to prevent hi-limiting and assure full 20+ years parts life, the piping system/basic
plumbing/circulator pump must be arranged to provide flow greater than minimum GPM shown in Table
1. If zoned system, this applies when the smallest zone is operating.
NOTE: Since this is an automatic temperature sensing system, both sensors (EBCO only) and the
complete control wiring are required before using or turning on this Electro-Boiler.
MULTIPLE ZONES AND RADIANT TEMPERATURES
Same water temperature all zones – in this case the system can be setup as one pump with the water
circulated through the boiler and directly to a manifold containing the various zone valves. Although this
model series has a built-in outlet sensing and controller mechanism for staging the elements, also consider
the next section, Zone Controller. If not using zone controller, the end switches of all of the zone valves
are paralleled and directly control R and W to turn on the boiler.
Various water temperature requirements – if this is the case, a primary loop with mixing valve for the
various zone temperature requirements is necessary. Injection pump techniques can also be used.
However, usually injection pump techniques come with a controller which is designed to protect a gas
boiler from cool water return. This is simply not needed and a duplication with the temp. sensing
controller within this Electro-boiler and the injection pump controller will be of no benefit within the
operating system. The zone valve/zone pump control strategy must be wired to provide the boiler “R and
W” contact closure and the primary pump is connected to the boiler pump contacts. This assures the
primary pump is active and running whenever the boiler is turned on via contact closure on “R and W”.
At least one zone must be open before turning on the primary pump/Electro-Boiler. Do not design a
system where the Electro-Boiler is supposed to operate as a “hot boiler” based upon its outlet sensor
without the primary pump circulating water, minimum 4 GPM is required.
New, improved feature – the EB-ZEA-* or EB-Z2P zone controller priority zone now has the ability to
communicate with this TS Series boiler and it will automatically switch to a low mass high water
temperature (150 or 180) during zone 1, priority switch on, operation. With this feature the TS boiler can
automatically take care of two temperature requirements thus eliminating the need for the technique
described in the paragraph above.
ZONE CONTROLLER
This EB-C series boiler controls the electric elements based upon water
temperature independent of flow; therefore, in theory, a staging zone
controller is not required; however, there are three suggestions or reasons
why a zone controller can simplify the installation and enhance overall
performance.
Zone wiring and troubleshooting convenience – the addition of the zone board allows for easy terminal
block and point to point wiring for each zone thermostat and each zone valve. Also there are LED’s
associated with the thermostat action and the zone valve action. This greatly simplifies wiring and future
troubleshooting with a neat terminal block wiring arrangement and the onboard LED’s.
2. Prevents over control or false staging up and down when the temperature sensors are attempting to
regulate – since Electro Industries’ zone controller also has staging “smarts”, the addition of the zone
controller will provide smoother boiler temperature control. The zone board has a dial switch for each
zone and the installer selects one of four zone capacity sizes. When dialing in the size closest to the zone
3
BI5072
06/03/2011
1.
3.
Btu/h capacity, the zone controller “smarts” only allows the appropriate boiler stage which can handle that
capacity. Also this is additive if more than one zone calls at any one time – order EB-ZEA-1.
Two temperature system with unbalanced zones – if the application includes zone one requiring high
temperature (fin tube, air handler, etc.) and the remaining zones are radiant floor low temperature, this zone
controller (EB-ZEA-1) will automatically raise the output of the high temperature zone. This is a priority
arrangement, zone 1 holds off the other zones while the high temperature output is heating. If at the end of
the high temperature zone there is a call on any of the low temperature zones (up to three plus slave 4),
there will be a pump only function until the outlet temperature drops below the front panel dial setting.
ROOM THERMOSTAT PLACEMENT
Fin tube radiation, fan coil, etc. – heat only wall t-stat, connected to operate zone valves (see previous
section) or for single zone the t-stat is connected directly to Electro-Boiler R and W.
Floor radiant – comfort and proper space heating response is a direct relationship to the thermostat type
and the placement of the thermostat sensing bulb. Typically an under floor heating system can be broken
down into three categories.
A. Energy storage, water tubing is under the concrete or within the
sand base – the controlling thermostat must have a remote bulb, and
this remote bulb must sense the concrete slab temperature (slab stat).
Coordinated with the concrete pour, install a ¾” PVC, minimum bend
radius of 7 inches, and locate at approximately center (vertical) of the
concrete slab. The thermostat sensing bulb can later be pushed down
this PVC conduit. If the slab is already poured without conduit for slab
stat, use electronic remote sensing thermostat such as Electro
Industries’ ES-24-BR. These devices only require a ¼” hole drilled in
the floor at some convenient location (preferably off a center wall, not
within 2 feet of outside wall).
B. Floor covering, medium to high insulation – use slab stat as described in paragraph A above.
C. Quick response, hydronic tubing just under the concrete surface, no flooring material over
the concrete – in this case, heated water can directly radiate into the room, a standard wall mount
room thermostat is adequate. Mount room thermostat on an inside wall similar to most heating
systems.
MULTIPLE BOILERS
This boiler series now includes a method for automatically staging any
number of parallel-plumbed boilers. Order plug-in relay EB-C-STG5.
The thermostat is connected only to the first boiler, when all stages are
on for more than 5 minutes, this new plug-in relay module turns on the
next boiler (R and W), and a second EB-C-STG5 could be used to turn
on the third, etc. (reference BH507).
06/03/2011
4
BI5072
TWO-TEMPERATURE OPERATION OR FEATURE
When using Electro’s zone controller in priority mode, the boiler
system can automatically raise the outlet temperature with zone 1
calling. This is setup for default of 150° or pulling a jumper peg the
high temperature value is 176°. See appropriate zone controller
installation manual for details.
INFORMATION/WATER FLOW CALCULATIONS
Water flow, GPM, can easily be calculated if the temperature rise across
the electric boiler can be measured.
The formula below can only be used when the temperature rise is stable
and the boiler is not hi-limiting. In other words, verify constant current
draw and stable outlet temperatures for at least 15 minutes.
GPM – 1-Phase:
GPM = Volts x Amps x 3.414
500 x Temp. rise
GPM – 3-Phase:
GPM = Volts x Amps x 1.732 x 3.414
500 x Temp. rise
INSTALLATION REQUIREMENTS
1. All installation work must be performed by trained, qualified contractors or technicians. Electro
Industries, Inc., sponsors installation and service schools to assist the installer. Visit our web site at
electromn.com for upcoming service schools.
WARNING
ALL ELECTRICAL WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
AND LOCAL ELECTRIC CODES, ORDINANCES, AND REGULATIONS.
WARNING
OBSERVE ELECTRIC POLARITY AND WIRING COLORS. FAILURE TO OBSERVE COULD
CAUSE ELECTRIC SHOCK AND/OR DAMAGE TO THE EQUIPMENT.
CAUTION
This unit can only be used for its intended design as described in this manual. Any internal
wiring changes, modifications to the circuit board, modifications or bypass of any controls, or
installation practices not according to the details of this manual will void the product warranty,
the CSA/us certification label, and manufacturer product liability. Electro Industries, Inc.,
cannot be held responsible for field modifications, incorrect installations, and conditions which
may bypass or compromise the built-in safety features and controls.
2. This installation manual and Electro-Boiler products relate only to the addition of the Electro-Boiler
to the hydronics system. The owner/ installer assumes all responsibility and/or liability associated
with any needed installation of the gas/oil boiler, pump, plumbing, system design, hydronics systems
or backup gas/oil boiler, etc. Any instructions or comments made within this manual (or factory
phone assistance) relating to the gas/oil furnace are provided as comments of assistance and “helps”
only.
06/03/2011
5
BI5072
CAUTION
Hazards or unsafe practices could result in property damage, product damage, severe personal
injury and/or death.
3. Remember, safety is the installer’s responsibility and the installer must know this product well
enough to instruct the end user on its safe use.
Safety is a matter of common sense - - a matter of thinking before acting. Professional installers have
training and experienced practices for handling electrical, sheet metal, and material handling
processes. Use them.
CLEARANCES
BACK
LEFT
RIGHT
FRONT
TOP
BOTTOM
06/03/2011
MINIMUM CLEARANCE FROM
SUGGESTED MINIMUM
COMBUSTIBLE SURFACES
SERVICE CLEARANCE
0 INCH
0 MM
0 INCH
0 MM
1 INCH
25 MM
16 INCHES
406 MM
1 INCH
25 MM
6 INCHES
152 MM
1 INCH
25 MM
24 INCHES
610 MM
1 INCH
25 MM
24 INCHES
610 MM
REQUIRED CLEARANCE – 16 INCHES/406 MM
6
BI5072
MECHANICAL INSTALLATION – UNDER-FLOOR RADIATION
CAUTION
Electro Industries Inc. requires the use of dielectric isolation between the boiler vessel supply
and return piping when the boiler is plumbed using copper or any other dissimilar metal.
Damage to the vessel caused by galvanic corrosion voids Electro Industries’ warranty.
Reference drawing BX503
1. With the typical radiant floor system, a dual heat backup boiler is uncommon. If a backup boiler is
required, please reference “Mechanical Installation – Dual Heat” section.
2. Unpack the Electro-Boiler, the safety relief and pipe fittings are packed within a small carton. The
safety relief is plumbed to the ¾” pipe as shown on BX503 (or may be part of other components
shown on BX503).
3. The Electro-Boiler must be positioned with the vessel vertical. The water IN/OUT ports must be at
the top. The unit will not function properly with the vessel in a horizontal position.
NOTE: Mount at least 20 inches above the floor to allow element removal and service at the bottom.
4. The plumbing components and plumbing layout shown on drawing BX503 have been very carefully
chosen and should be plumbed as shown. When following this diagram, the water fill procedure
becomes very simple and almost guarantees the removal of all air or prevents air locking problems.
Experienced hydronic heating installers may be able to eliminate some components but the inclusion
of these components guarantees installation and initial operating success.
5. The vessel is factory constructed with an “air trap” chamber at the top of the vessel, connected to the
¾” pipe and arrangement shown on BX503.
6. The key mechanical components required include:
 Expansion Tank – as a closed loop hydronic heating system, a minimal expansion tank is
required. This can be an air diaphragm tank as provided in the plumbing kit or a basic
“empty” tank where air is compressed at the tank top.
 Inlet Temperature Gauge – recommended to observe the operation of the system.
 Air Vent – install with the pressure relief valve as shown on drawing BX503.
 Inline Air separator – this can be installed ahead of the pump with the expansion tank
moved to this point. However, the vessel designed air trap and the piping arrangement
leading to the air bleeder works very well.
 Pressure Safety Valve – this is required and is furnished as a loose component with the
boiler unit itself. Failure to install the provided, 30 PSI, pressure relief valve as shown void
warranty and the product listing. During purging there is a requirement to bleed out the
initial air within this ¾” pipe leg by manually holding open the relief valve. Add the
necessary pipe extension to the relief valve to prevent water damage on this unit or
surrounding area.
 Gate Valve/Drain Valve – these are for servicing and easy fill purposes.
 Circulating Pump – depending upon system lift and system loop resistance, the proper
circulating pump is required to guarantee the minimum GPM flow as specified in Table I,
page 1.
· Comment: Circulator pump can be in the outlet or inlet. Newer, higher quality
pumps seem to work better in the “supply” line.
7. To ensure safe boiler operation adequate system pressure must be maintained. Some expansion tanks
may have an integral regulator and “port” for water source hookup.
8. Depending upon water conditions, determine whether water additives are necessary.
9. Purge and fill water system. Do not allow the electric element to come on until the system is purged
and you have verified proper water circulation. If the pump is needed, jumper the two orange wires
in order to operate the pump directly from its own 120 volt source.
10. Purge each loop individually, one at a time.
11. Check for leaks.
06/03/2011
7
BI5072
MECHANICAL INSTALLATION – DUAL HEAT
CAUTION
Electro Industries Inc. requires the use of dielectric isolation between the boiler vessel supply
and return piping when the boiler is plumbed using copper or any other dissimilar metal.
Damage to the vessel caused by galvanic corrosion voids Electro Industries’ warranty.
Reference drawing BX504
1. Unpack the Electro-Boiler. The safety relief and pipe fittings are packed within a small carton.
2. In most dual heat installations this Electro-Boiler is plumbed in series with an existing oil, gas, or
wood boiler. For gas or oil, the Electro-Boiler is at the gas/oil outlet; but for wood, the Electro-Boiler
must be on the inlet sides. The standby boiler cannot be operated as “hot boiler”. This will defeat the
Electro-Boiler. Rewire using EB-S-SB as required, standby boiler is turned on from the brown wires.
3. Standard hydronic hot water heating practices apply. This procedure assumes adequate piping size to
meet the flow requirements of the specific boiler model, expansion tank, pump, zones, etc. are
properly designed and installed.
4. The Electro-Boiler must be positioned with the vessel vertical. The water IN/OUT ports must be at
the top. The unit will not function properly with the vessel in a horizontal position.
NOTE: Mount at least 20 inches above the floor to allow element removal and service at the bottom.
5. Typically this unit is wall hung next to the existing boiler.
6. Use the ¾” pipe fittings to install the safety relief valve and air vent. Add the necessary piping to the
safety relief valve so that water damages do not occur in the surrounding area.
7. Connect the “hot” water line from the fossil fuel boiler to the Electro-Boiler "inlet". Connect the
Electro-Boiler "outlet" to the main feed line. When facing the Electro-Boiler vessel, the "outlet" is on
the LEFT.
NOTE: Wood applications, plumb so electric feeds the wood boilers.
10. If piping contains any "U" bend, an air vent may be required at the top.
11. When possible, isolating ball valves are recommended for easy servicing.
12. To ensure safe boiler operation and prevent element damage, the system should contain a pressure
regulator and an automatic water fill valve. Expansion tank may have an integral regulator and “port”
for water source hookup.
13. Depending upon water conditions, determine whether water additives are necessary.
14. Purge and fill water system. Do not allow the electric element to come on until the system is purged
and you have verified proper water circulation. If the pump is needed, short out the two orange wires
in order to operate the pump directly from its own 120 volt source.
15. Check for leaks.
06/03/2011
8
BI5072
ELECTRICAL HOOKUP
1. Heating Power Source – using model number on nameplate, locate line item on Table 1, page 1.
This supplies the necessary wiring information. National Electric Code and local codes will
determine the type and size of wire between this unit’s CB disconnect screws and the distribution
panel connection. The “Amps” column represents continuous running current, does not represent the
wiring or disconnect amps.
 Only copper wire is allowed inside Electro Industries’ enclosure.
 The model associated with the design voltage rating has the proper 24-volt transformer. If
installing in any other voltage rating, 24-volt transformer may need to be replaced or resized.
208/480/600 3-phase use drawing BH505.
240 single phase use drawing BH506.
 If single feed to the dual multi-breaker models, single feed bus EM-5716 or EM-5717 may
apply.
2. Grounding – copper conductor is required, size per NEC code relating to the current of each feed.
3. Circulating Pump – the terminal block (orange wires) below the circuit breakers represents a switch
closure (10-amp maximum) to operate an external circulating pump motor. Voltage for the pump
must come from a separate source.
 The pump is controlled as a direct function of the R and W input.
 If this is connected with a standby boiler, generally the assumption is series plumbing with
the single pump. In this case, the R and W function will operate the pump whether in electric
or standby mode.
 If a standby boiler installation has parallel plumbing with two pumps, field wiring and
controls will be necessary to properly operate (and typically check valve isolate) the standby
boiler self-contained pump from the system pump controlled by these two terminal screws.
Note: If using zone pumps, this function and connection is not used.
4. Operating Thermostat – two types can be used. Connection is at the control board bottom.
 Standard Mechanical – connect to “R” and “W”, bottom right. Set thermostat internal heat
anticipator to 0.2.
 Electro-Stat – (ES-24-BR) 3 wire connection required.
 R to R, W to W, C to common
 The Electro-Stat remote sensor can be extended as required. This is a three wire cable,
cut and splice, up to 50 feet. Use only stranded wire, shielded cable is not required.
Comment: If zone valve or zone pumps see appropriate sections.
5. Load Management Interrupt Control – this Electro-Boiler series has been pre-wired and designed
for an external utility load management receiver connection. The control board lower left BLU and
BLU/WHT wires represent the two contact points, extend these wires to the utility load control
device.
As shipped, this unit is only equipped for off-peak = N.C. logic. If reversed logic is required, contact
the factory for modification.
 Optional – if load management is not used, simply keep the two blue wires shorted.
 Optional – if the power company disconnects 240V for load control, please reference BH029
for special wiring requirements.
6. Outdoor Sensor (OT) – only applies with EB-CO Series. If possible shade from direct sun rays.
7. Zone Valves or Zone Pumps – see page 3 for zone controller options.
06/03/2011
9
BI5072
WARNING: The end switches from the zone valves must be an isolated contact with no voltage
present on these wires or screw terminals. This is very important to make sure there isn’t any
interference or feedback between the transformer operating the zone valve system and the transformer
within this Electro-Boiler product. Once this has been determined, all end switches are simply
paralleled with the two wires going to “R” and “W”.
8. If this is a dual heat application with standby boiler, the 2 brown wires from the EB-S-SB connect
to the standby boiler R and W or T and T. These 2 brown wires represent a contact closure to activate
the standby boiler during load control or when the front panel switch is in the “standby” position.
9. Remote Display – an optional remote display (4-wire stat cable) can be added, call factory for
details.
WATER ADDITIVES
1.
Unless the source water is unusually poor and/or rust elements, additives are not required. It is
recommended the water source comes through a water softener or use distilled water.
2.
Impurities within a closed loop hydronics boiler are considerably less damaging than the typical
domestic water heater. In a closed loop electric boiler, the water impurities “boil out” and the
system essentially makes its own pure water. As a closed system, this “pure water” becomes the
operating mode. In the case of domestic water tank, there is always new water entering with new
impurities.
3.
However, if additives are required, use the recommendations and source from your local
professional plumber, specializing in hydronics heating systems.
WATER FILL PROCEDURE
The following procedure applies to non-glycol or antifreeze.
Caution: If the building supply pressure is connected directly to supply water ball valve without
pressure reducing regulator, user needs to make sure the pressure within the boiler loop does not
exceed 30 PSI. Careful control of the supply water ball valve opening can take care of this. Also at
steps 6 and 10, use caution to make sure the building water supply pressure does not “spike” the
system.
1. Connect the temporary water supply source (probably hose connection) to the "water supply
connection" input.
NOTE: If water supply connection is permanent, some local building codes may
require special anti-siphon check valve, RPZ check valve, or equivalent between
the boiler fill regulator and the domestic water source or the city water connection.
2. Connect a drain hose to hose bib, "drain valve".
3. Open "drain valve" and close "inlet gate valve" (between drain valve and boiler inlet).
4. Verify “top gate valve” is open.
5. Do not apply 240 heating power during water fill sequence.
6. Open “water supply valve” and open household water supply source.
7. Allow system to circulate, discharging through drain valve, for at least 15 minutes.
8. Put your ear against the metal pipe and listen for air bubbles. If the water flow is consistent and
quiet, the system is probably purged and water filled.
9. Close the "drain valve". Open the "inlet gate valve".
10. The cold system pressure at the gauge should be approximately 10 to 14 PSI.
11. Close “water supply valve” and disconnect water supply.
06/03/2011
10
BI5072
12. Optional – energize circulating pump during this fill operation. The water pressure from the
household system and as plumbed should typically flow through the circulating pump without the
pump running.
COMMENT: Purge one loop at a time.
CONTROLLER SETUP
Red dial switch, front panel –
EB-CA Series –simply set the “knob” to the desired outlet temperature shown on the front panel
decal.
EB-CO Series – the temperature decal will relate to the OT 0° set point and the “knob” numbers
coincide with the curves below. High and low mass also relate to the ramp-up water temperature
starting point, as shown. Select the high or low mass with the rate of temperature rise based on
outdoor temp (OT). Comment: The WF-ANZ* test set allows field change of the base temperature
start point.
The front panel temperature selection number coincides to the curves below. This temperature value
shown on the front decal is actually the supply water at 0° outside.
Low mass – 120°
High mass – 90°
Circulator pump mode – as factory set, the circulator pump is controlled directly from the “W” input
terminal. In this setup the circulator pump continues during load control interrupt (or optional remote
standby switch). There is a provision within the controller board (inside) to allow the circulator pump to
not operate during load control interrupt.
On the inside control board, just above the two
bottom terminal blocks, is a small pin jumper
arrangement. The black “device” sets up the pump
mode. Just below this pin jumper arrangement are
W and L lettering. When the two pin shorting
device is in the W position, the pump is a direct
function of R to W input. When the two pin jumper
is in the L position, the pump is interrupted during a
load control.
WARNING: This shorting device must be in one of the two positions for the circulator pump to properly
operate.
06/03/2011
11
BI5072
OPERATIONAL TIPS
Monitor Lights, Front Panel
 HI-LIMIT, red – this will only illuminate when the vessel hi-limit opens due to excessive high
water temperature. This hi-limit is self resetting.
 PWR ON, green – basically this is illuminated at all times. It represents 24-volt power source,
good fuse, controller logic is operational, and a good outlet sensor. If the outlet sensor is
inoperative, incorrectly wired, or malfunctioning; this green monitor LED should be in the
blinking or pulsing mode (see page 11).
 EL MODE, amber – when illuminated the system is in the electric mode. If it is not illuminated
the utility load control receiver is in the interrupt or on-peak mode. If there is an optional or
remote standby switch, the status of the standby switch is also monitored by this amber LED.
 HEAT ON, red – indicates a remote switch closure (t-stat or zoning end switch) is closed between
terminals R and W.
Inside Controller Board
 STAGES, red – these four LED’s indicate which electric element stages are on and active.
Manual Reset, Hi-Limit
At the top of the vessel there are surface mount hi-limits preset at 205° F. There is no light indicator
associated with these safety hi-limits. Reset involves locating a small shiny lever or metal tab protruding
on the side of the black safety limit base. This small tab is pressed inward approximately 1/8” to “snap
in” the contacts.
Safety caution – the wires and screws have high voltage potential and can be dangerous. Turn
off circuit breakers before investigating or attempting to reset the 205° F safety limits.
Internal Fuse
The fuse on the controller board protects the transformer secondary, external items connected to “R”, and
the circuit board itself. Replace with 2-amp fast blow, AGC2 or equivalent.
Stat Heat Anticipator - If it is a mechanical stat, verify heat anticipator has been set at Ø.2 (non-zone
system).
System Pressure
The side press/temp. gauge should be at approximately 10 to 16 PSI at room temperature water and
should not rise more than approximately 4 PSI at the operating or hot water temperature. If the pressure
change is more than approximately 4 PSI, the expansion tank is too small or there is a problem with the
expansion tank piping, expansion tank itself.
Cold slab, outdoor reset and temperature sensing prevent full boiler on – by adding a temporary
jumper between the lower W screw terminal and the upper left “E” tab, all temperature sensing functions
are bypassed and the control board will step in all the stages. Caution: This jumper shall not be a
permanent function, jumper needs to be removed after slab is approaching normal temperature.
06/03/2011
12
BI5072
Replacement Parts
WFSB
WFS25F
EB5623CA
EB5623CO
UFUSE0440
5127
5535
5537
5453
5456
EB5520
5541
5542
5543
5527
5528
5126
5661
5662
5663
5658
5659
5660
5657
5653
5643S
5655
5664
5665
EB5508-06
EB5508-04
EB5508-05
EB5520
EB5521
EB5522
EB5524
EB5525
EB5526
Water sensor, 3 ft.
Outdoor sensor (OT)
Controller, ST sensing only
Controller, ST and OT sensing
2-amp fuse, fast blow (AGC2)
Control relay, 1 pole
Safety hi-limit, manual, 205°
First hi-limit, auto-reset, 190°
Relief valve, 30 PSIG
Gauge press/temp.
Electric element, 240, 4.5 kW
Transformer 208/240V primary, 24V, 40VA
Transformer 480V primary, 24V, 50VA
Transformer, 600V primary, 24V, 50VA
Heating relay, 3 pole DP
Heating relay, 1 pole DP
Heating relay, 2 pole DP
30-amp 480V 3 pole circuit breaker
60-amp 480V 3 pole circuit breaker
80-amp 480V 3 pole circuit breaker
100-amp 3 pole circuit breaker
125-amp 3 pole circuit breaker
150-amp 3 pole circuit breaker
80-amp 3 pole circuit breaker
80-amp 2 pole circuit breaker
100-amp 2 pole circuit breaker
50-amp 3 pole 3 phase circuit breaker
70-amp 3 pole 3 phase circuit breaker
45-amp 3 pole 3 phase circuit breaker
Electric element 600, 6 kW
Electric element 600, 4 kW
Electric element 600, 5 kW
Electric element 240, 4.5 kW
Electric element 208, 4.5 kW
Electric element 240, 5.5 kW
Electric element 240, 2.5 kW
Electric element 480, 6 kW
Electric element 240, 5 kW
TROUBLESHOOTING/REPAIR HELPS
1. This WarmFlo controller contains several interference suppression components, but as an electronic
logic product, unpredictable and unusual transients or interference may sometimes cause strange
results. If the WarmFlo controller is “acting strange”, one immediate step would be power down
reset. Simply turn off boiler power or breaker number 1, when the green LED goes out, count to 1Ø,
and re-energize power supply.
2. Inoperative temperature sensor, if the internal program can detect a bad sensor (shorted, open wire,
etc. – not necessarily bad value) the front panel green LED will be pulsing. By checking the pulsing
pattern, the appropriate sensor can be identified.
- OT sensor – 100 ms blink every second
- ST sensor – two, 100 ms blinks every second
- Both bad – ½ second on, ½ second off, alternating
3. The temperature sensor can be further evaluated with diagnostic program from standard PC or Palm
software. This includes the ability to “fool” the sensor or set in an offset for various troubleshooting
purposes. This software disk comes with a special cable needed for PC or Palm hookup.
06/03/2011
13
BI5072
-
ET-SOFT-TS – PC software disk and cable
ET-SOFT-TSP – Palm software disk and cable
4. The terminal blocks for control wire hook-up are designed for a wire insertion and screw clamp
down. If there is no wire connected and the screw is loose, the screw may not necessarily make a
good electrical contact to the inside components. Example - If you are jumpering the thermostat
terminals without thermostat wire connection or if you are attempting to measure voltage on the
screw head, you may get erroneous or unpredictable results if the screw is not tightened down.
5. The outdoor sensor (OT) must be sensing the actual outside temperature for this controller to
correctly operate. Do not simply leave the outdoor sensor “hang in the room” and attempt to run this
system (EB-CO Series boiler only).
6. Temperature sensing bypass – the inside control board, left side, contains a “E” tab which can be
used to directly step in the heating stages and in essence bypass the temperature sensing and control
functions. The “E” tab has the highest priority and overrides all temperature sensor functions. In
other words, when jumpering from W to E all four stages are hard on. Note: Verify pump is
operating prior to using the E terminal. Since activating this E terminal causes full electric element
output, this function should only be used to verify all stages or troubleshoot proper 24Ø current at
each element.
7. Use general heating system logic information and basic understanding of the terminal block wiring
functions measure various voltage points to determine proper operation.
8. Acquiring the PC software or Palm with serial port hookup cable is a positive tool for understanding
and troubleshooting the WarmFlo controller. Either test set device can display all temperatures, real
time evaluation of WarmFlo functions and provide temperature offsets for assimilating winter
conditions.
Sensor Temperature Calibration - Both remote sensors are digital electronic and factory calibrated.
Normally these do not require field calibration or verification. However, if sensor temperature error is
determined, there are two field calibration techniques. Proceed with extreme caution.
1. The outdoor sensor (OT) can be calibrated with ice (32F). This is not a checking temperature
situation. If you proceed with this function, the sensor automatically goes to 32F. Notice a small
push button next to the sensor terminal block, with the sensor at 32F, push and hold for
approximately ten seconds. When the green LED next to the fuse “blinks” at you, release and now
the outdoor sensor is set at 32F.
2. Use PC or Palm software to calibrate sensor. See other paragraphs.
06/03/2011
14
BI5072
OPERATIONAL INFORMATION
In order for the installer to completely understand the WF II functions and operational sequence it is
recommended to thoroughly read and understand the information below. This knowledge can help in
determining settings that can be set according to the end customers needs.
Warning, field reprogramming – within WarmFlo II internal logic and non-volatile memory, it can
detect whether it is operating from one of the above factory pre-programmed chips or if it has been
modified (reprogrammed) with PC software or Handheld. Once the user or field technician has
downloaded (save), from that time forward the WarmFlo II physical control board is no longer governed
by the above table, or the chip code written on the plug-in chip, etc. In other words, power up/power
down, reset, or removing and re-plugging the chip does not affect any altered reprogrammed functions. It
is smart enough to know it is no longer the original chip and that specific physical board, from this time
forward, must be under the control of the PC software/Palm.
Delay, transfer from standby to electric – if the unit was operating in SB for more than 1 minute, the
follow-up transfer back to electric engages a 2-minute delay before any of the electric stages are
activated. The pump will react to the call for heat, but the elements will stay off for 2 minutes in order for
the pump to cool down the standby boiler vessel.
Staging disables at specified outdoor temperatures – the factory setup allows all four stages to come
on at outdoor temperatures below 120° F. Using download reprogramming, an outdoor temperature can
be set for each stage allowing the disable of specific stages above the preset temperature.
06/03/2011
15
BI5072
ELECTRO-BOILER DUAL HEAT PIPING DIAGRAM
TO SYSTEM
FROM SYSTEM
SAFETY
INLET
VALVE
#5453
GATE
1
VALVE
DRAIN VALVE
(THREADED INTO TEE)
IN
OUT
WATER SUPPLY VALVE
AUTO FILL VALVE
EXPANSION
(REGULATOR)
TANK
WATER SUPPLY
CONNECTION
OUT
IN
ELECTROBOILER
NOTES:
1. LOOSE PARTS SHIPPED WITH BASIC
BOILER MODEL.
2. IF WOOD BOILER, REVERSE ORDER
(ELECTRIC FEEDS WOOD).
OIL/GAS BOILER
(WITH PUMP)
2
3. MINIMUM 20" SPACING BETWEEN
FLOOR AND
BOTTOM OF BOILER.
DRAIN
3
ELECTRO INDUSTRIES, INC.
MONTICELLO, MN 55362
BX504
Rev.A 02-14-06
BOILER ACCESSORIES
ZONE CONTROLLER
This will simplify your wiring and make zoning applications much easier. In addition, enhanced communicating
features have the ability to stage the electric boiler based upon the connected zone capacity.
Pumps, Actuators, Valves
Standard Features
EB-ZTA-1 - install within boiler cabinet
EB-ZEA-1 - with enclosure and 40VA transformer
EB-ZEA-2 - add additional 4, enclosure and 40VA
• Utility load control
• Terminal block wiring, visual
wiring layout
• Indicator lights showing zone
operation
Pumps
• 24-volt, 40VA transformer
120/208/240 connection
Zone Valves
EB-Z2P - two pumps with priority and dual temp.
EB-ZTS-1 - install within boiler cabinet, encl. option
EB-ZTS-2 - add additional 4, enclosure and 40VA
• Fuse protection
• Priority option
• Dual temperature operation
• Applies to digital or
standard thermostats
• Dial switch, select each zone
capacity
All Others
EB-ZXA-1 - universal, pumps or valves, non-communicating, for any boiler
EB-ZS-4 - automatic staging system for Brand X boilers or dual EB-R, -L, -E Series
EB-ZC-4 - wiring and convenience interface, isolated boiler end switch
EB-5415A - low cost, 2 or 3 zones, sheds one boiler stage (Mini-Boiler enhancement)
SLAB STAT
Sensing and controlling the system based upon radiant floor surface temperature
or the concrete mass has very positive benefits. Radiant floor air stat in the same
area as a forced air roomstat presents serious control problems. A remote sensing
slab stat for the radiant floor removes this issue.
Remote sensing slab stat is required for storage applications.
ES-24-BR
SWITCHING RELAY - EE-5051
This DPDT 24-volt switching relay provides a convenient
solution to any AC or DC application.
MULTI-BOILER - EB-C-STG5
Electrically connects between 2nd and 3rd, 3rd and 4th, etc.
OTHER OPTIONS
•
•
•
•
Ideal for zone pumps
24V coil
120V, 10A, contact sets
Easy to wire and nicely packaged
SOT-1
5701
5702
EB-S-SB
WF-ANZ*
Switchover to standby, total run time
Single feed bus for 2 CB’s (SQ-D CB)
Single feed bus for 3 CB’s (SQ-D CB)
Dual boiler option for EB-S Series
WarmFlo Analyzer, now applicable to WO and
WA Series
Specifications subject to change without notice, all rights reserved.
TWO SUPPLY WATER TEMPERATURE REQUIREMENT
•
Handled as the priority zone on multi-zone (EB-ZEA-1) or two
pump (EB-Z2P) controllers
•
Priority switch on, zone 1 active - TS boiler automatically changes
to 150° (or selection 176°) supply water setting
•
•
All other zones are held off
With zone 1 satisfied or 60-minute timeout, the boiler automatically
returns to the preset temperature and reacts to the other zones
Low Temp
High Temp
Radiant, slab
Radiant, staple up
Radiant, slab
Baseboard
Radiant, slab
Fan coil
Radiant, slab
Water heater, side arm
Radiant, slab
Hanging unit heater (garage, shop, etc.)
INSTALLATION PLUMBING KITS
These installation kits provide the critical plumbing components needed for easy installation of the Electro-Boiler. In addition to the
items shown in the matrix below, each kit includes all necessary ball valves, drain valve, tees, elbows, nipples, bushings, couplings,
etc. for direct connection to circulator pump and/or manifold.
Electro Industries’ boilers come standard equipped with outlet temperature/pressure gauge, pressure relief safety valve, and when
applicable, the WarmFloTM electronic control sensors. These kits provide the additional components for easy installation:
Model
Application
Return Gauge
EMB-BK
All EMB Series
EMB-PK
All EMB Series
EB-PK-M
EB-MS, -MA, -MO Series
EB-BK-TS
EB-S, -WA, -WO Series
EB-PK-TS
EB-S, -WA, -WO Series
Expansion Tank
Air Vent
2.1 gal. (7.9 L), 40,000 Btu/h
Basic float type
2.1 gal. (7.9 L), 40,000 Btu/h
Enhanced air separator, EAS
4.5 gal. (17 L), 135,000 Btu/h
Enhanced air separator, EAS
4.5 gal. (17 L), 135,000 Btu/h
Basic float type
4.5 gal. (17 L), 135,000 Btu/h
Enhanced air separator, EAS
CIRCULATING PUMPS
5585 - Mini-Boiler &
10 kW TS Series
•
120V, 1/25 HP, maintenance-free wet
rotor circulator
•
Pump curve example - 5 GPM (19 L)
@ 11 ft. of head (32.9 kPa)
07/24/2007
5586 - TS Series, Standard
•
120V, 1/6 HP, maintenance-free oil
lubricated circulator
•
Pump curve example - 10 GPM (37.8 L)
@ 20 ft. of head (50.8 kPa)
5578 - 3/4” Pipe
5582 - 1” Pipe
5579 - 1-1/4” Pipe
•
Two flanges, with isolation valve
BL001
Electro Industries, Inc.
Limited Product Warranty
Effective February 5, 2009
Electro Industries, Inc. warrants to the original owner, at the original installation site, for a period
of two (2) years from date of installation, that the product and product parts manufactured by
Electro Industries are free from manufacturing defects in materials and workmanship, when
used under normal conditions and when such product has not been modified or changed in any
manner after leaving the plant of Electro Industries. If any product or product parts
manufactured by Electro Industries are found to have manufacturing defects in materials or
workmanship, such will be repaired or replaced by Electro Industries. Electro Industries shall
have the opportunity to directly, or through its authorized representative, examine and inspect
the alleged defective product or product parts. Electro Industries may request that the materials
be returned to Electro Industries at the owner’s expense for factory inspection. The
determination as to whether product or product parts shall be repaired, or in the alternative
replaced, shall be made by Electro Industries or its authorized representative. Electro Industries
will cover reasonable labor costs to repair defective product or product parts for ninety (90) days
after installation.
TWENTY YEAR (20) LIMITED WARRANTY ON BOILER ELEMENTS AND VESSELS
Electro Industries, Inc. warrants that the boiler elements and vessels of its products are free
from defects in materials and workmanship through the twentieth year following date of
installation. If any boiler elements or vessels are found to have a manufacturing defect in
materials or workmanship, Electro Industries will replace them.
TWENTY YEAR (20) LIMITED WARRANTY ON SPIN FIN ELEMENTS
Electro Industries, Inc. warrants that the spin fin elements of its products are free from defects in
materials and workmanship through the twentieth year following date of installation. If any spin
fin elements are found to have a manufacturing defect in materials or workmanship, Electro
Industries will replace them.
FIVE YEAR (5) LIMITED WARRANTY ON OPEN WIRE ELEMENTS
Electro Industries, Inc. warrants that the open wire elements of its products are free from
defects in materials and workmanship through the fifth year following date of installation. If any
open wire elements are found to have a manufacturing defect in materials or workmanship,
Electro Industries will replace them.
Page 1 of 2
XX017
THESE WARRANTIES DO NOT COVER:
1. Costs for labor for removal and reinstallation of an alleged defective product or product parts,
transportation to Electro Industries, and any other materials necessary to perform the exchange,
except as stated in this warranty. Replacement material will be invoiced to the distributor in the usual
manner and will be subject to adjustment upon verification of defect.
2. Any product that has been damaged as a result of being improperly serviced or operated, including,
but not limited to, the following: operated with insufficient water or airflow, allowed to freeze,
subjected to flood conditions, subjected to improper voltages or power supplies, operated with airflow
or water conditions and/or fuels or additives which cause unusual deposits or corrosion in or on the
product, chemical or galvanic erosion, improper maintenance or subject to any other abuse or
negligence.
3. Any product that has been damaged as a result of natural disasters, including, but not limited to, the
following: lightning, fire, earthquake, hurricanes, tornadoes or floods.
4. Any product that has been damaged as a result of shipment or handling by the freight carrier. It is the
receiver’s responsibility to claim and process freight damage with the carrier.
5. Any product that has been defaced, abused, or suffered unusual wear and tear as determined by
Electro Industries or its authorized representative.
6. Workmanship of any installer of the product. This warranty does not assume any liability of any
nature for unsatisfactory performance caused by improper installation.
7. Transportation charges for any replacement part or component, service calls, normal maintenance;
replacement of fuses, filters, refrigerant, etc.
CONDITIONS AND LIMITATIONS:
1. If at the time of a request for service the original owner cannot provide an original sales receipt or a
warranty card registration then the warranty period for the product will have deemed to begin thirty
(30) days after the date of manufacture and NOT the date of installation.
2. The product must have been sold and installed by a licensed electrical contractor, a licensed
plumbing contractor, or a licensed heating contractor.
3. The application and installation of the product must be in compliance with Electro Industries’
specifications as stated in the installation and instruction manual, and all state and federal codes and
statutes. If not, the warranty will be null and void.
4. The purchaser shall have maintained the product in accordance with the manual that accompanies
the unit. Annually, a qualified and licensed contractor must inspect the product to assure it is in
proper working condition.
5. All related heating components must be maintained in good operating condition.
6. All lines must be checked to confirm that all condensation drains properly from the unit.
7. Replacement of a product or product part under this limited warranty does not extend the warranty
term or period.
8. Replacement product parts are warranted to be free from defects in material and workmanship for
ninety (90) days from the date of installation. All exclusions, conditions, and limitations expressed in
this warranty apply.
9. Before warranty claims will be honored, Electro Industries shall have the opportunity to directly, or
through its authorized representative, examine and inspect the alleged defective product or product
parts. Remedies under this warranty are limited to repairing or replacing alleged defective product or
product parts. The decision whether to repair or, in the alternative replace, products or product parts
shall be made by Electro Industries or its authorized representative.
THESE WARRANTIES DO NOT EXTEND TO ANYONE EXCEPT THE ORIGINAL PURCHASER AT RETAIL AND ONLY WHEN THE PRODUCT IS IN THE ORIGINAL
INSTALLATION SITE. THE REMEDIES SET FORTH HEREIN ARE EXCLUSIVE.
ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED WITH
RESPECT TO ALL PURCHASERS OR OWNERS. ELECTRO INDUSTRIES, INC. IS NOT BOUND BY PROMISES MADE BY OTHERS BEYOND THE TERMS OF THESE
WARRANTIES. FAILURE TO RETURN THE WARRANTY CARD SHALL HAVE NO EFFECT ON THE DISCLAIMER OF THESE IMPLIED WARRANTIES.
ALL EXPRESS WARRANTIES SHALL BE LIMITED TO THE DURATION OF THIS EXPRESS LIMITED WARRANTIES SET FORTH HEREIN AND EXCLUDE ANY
LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES RESULTING FROM THE BREACH THEREOF. SOME STATES DO NOT ALLOW THE EXCLUSION OR
LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS OR EXCLUSIONS MAY NOT APPLY. PRODUCTS OR PARTS OF
OTHER MANUFACTURERS ATTACHED ARE SPECIFICALLY EXCLUDED FROM THE WARRANTY.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY HAVE OTHER RIGHTS WHICH VARY UNDER THE LAWS OF EACH STATE. IF ANY
PROVISION OF THIS WARRANTY IS PROHIBITED OR INVALID UNDER APPLICABLE STATE LAW, THAT PROVISION SHALL BE INEFFECTIVE TO THE EXTENT OF
THE PROHIBITION OR INVALIDITY WITHOUT INVALIDATING THE REMAINDER OF THE AFFECTED PROVISION OR THE OTHER PROVISIONS OF THIS WARRANTY.
Page 2 of 2
XX017
Electro Industries, Inc.
3-Phase Boiler Limited Product Warranty
Effective September 1, 2008
Electro Industries, Inc. warrants to the original owner, at the original installation site, for
a period of one (1) year from date of installation, that the product and product parts
manufactured by Electro Industries are free from manufacturing defects in materials and
workmanship, when used under normal conditions and when such product has not been
modified or changed in any manner after leaving the plant of Electro Industries. If any
product or product parts manufactured by Electro Industries are found to have
manufacturing defects in materials or workmanship, such will be repaired or replaced by
Electro Industries. Electro Industries, shall have the opportunity to directly, or through
its authorized representative, examine and inspect the alleged defective product or
product parts. Electro Industries may request that the materials be returned to Electro
Industries at owner’s expense for factory inspection. The determination as to whether
product or product parts shall be repaired, or in the alternative, replaced, shall be made
by Electro Industries or its authorized representative.
ONE YEAR (1) LIMITED WARRANTY ON BOILER PARTS
Electro Industries, Inc. warrants that the parts of its 3-Phase Boilers are free from
defects in materials and workmanship through the first year following date of installation.
If any product parts are found to have a manufacturing defect in materials or
workmanship, Electro Industries will repair or replace them at their discretion.
ONE YEAR (1) LIMITED WARRANTY ON BOILER ELEMENTS
Electro Industries, Inc. warrants that the elements of its 3-Phase Boilers are free from
defects in materials and workmanship through the first year following date of installation.
If any elements are found to have a manufacturing defect in materials or workmanship,
Electro Industries will replace them.
FIVE YEAR (5) LIMITED WARRANTY ON BOILER VESSELS
Electro Industries, Inc. warrants that the boiler vessels of its 3-Phase Boilers are free
from defects in materials and workmanship through the fifth year following date of
installation. If any vessels are found to have a manufacturing defect in materials or
workmanship, Electro Industries will repair or replace them at their discretion.
Page 1 of 2
XX024
THESE WARRANTIES DO NOT COVER:
1. Costs for labor for removal and reinstallation of an alleged defective product or product parts,
transportation to Electro Industries, and any other materials necessary to perform the exchange,
except as stated in this warranty. Replacement material will be invoiced to the distributor in the usual
manner and will be subject to adjustment upon verification of defect.
2. Any product that has been damaged as a result of being improperly serviced or operated, including,
but not limited to, the following: operated with insufficient water or air flow; allowed to freeze;
subjected to flood conditions; subjected to improper voltages or power supplies; operated with air flow
or water conditions and/or fuels or additives which cause unusual deposits or corrosion in or on the
product; chemical or galvanic erosion; improper maintenance or subject to any other abuse or
negligence.
3. Any product that has been damaged as a result of natural disasters, including, but not limited to,
lightning, fire, earthquake, hurricanes, tornadoes or floods.
4. Any product that has been damaged as a result of shipment or handling by the freight carrier. It is the
receiver’s responsibility to claim and process freight damage with the carrier.
5. Any product that has been defaced, abused or suffered unusual wear and tear as determined by
Electro Industries or its authorized representative.
6. Workmanship of any installer of the product. This warranty does not assume any liability of any
nature for unsatisfactory performance caused by improper installation.
7. Transportation charges for any replacement part or component, service calls, normal maintenance;
replacement of fuses, filters, refrigerant, etc.
CONDITIONS AND LIMITATIONS:
1. If at the time of a request for service the original owner can not provide an original sales receipt or a
warranty card registration then the warranty period for the product will have deemed to begin thirty
(30) days after the date of manufacture and NOT the date of installation.
2. The product must have been sold and installed by a licensed electrician, plumbing, or heating
contractor.
3. The application and installation of the product must be in compliance with Electro Industries
specifications, as stated in the installation and instruction manual, and all state and federal codes and
statutes. If not, the warranty will be null and void.
4. The purchaser shall have maintained the product in accordance with the manual that accompanies
the unit. Annually, a qualified and licensed contractor must inspect the product to assure it is in
proper working condition.
5. All related heating components must be maintained in good operating condition.
6. All lines must be checked to confirm that all condensation drains properly from the unit.
7. Replacement of a product or product part under this limited warranty does not extend the warranty
term or period.
8. Replacement product parts are warranted to be free from defects in material and workmanship for
ninety (90) days from the date of installation. All exclusions, conditions, and limitations expressed in
this warranty apply.
9. Before warranty claims will be honored, Electro Industries shall have the opportunity to directly, or
through its authorized representative, examine and inspect the alleged defective product or product
parts. Remedies under this warranty are limited to repairing or replacing alleged defective product or
product parts. The decision whether to repair or, in the alternative, replace products or product parts
shall be made by Electro Industries or its authorized representative.
THESE WARRANTIES DO NOT EXTEND TO ANYONE EXCEPT THE ORIGINAL PURCHASER AT RETAIL AND ONLY WHEN THE PRODUCT IS IN THE ORIGINAL
INSTALLATION SITE. THE REMEDIES SET FORTH HEREIN ARE EXCLUSIVE.
ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED WITH
RESPECT TO ALL PURCHASERS OR OWNERS. ELECTRO INDUSTRIES, INC. IS NOT BOUND BY PROMISES MADE BY OTHERS BEYOND THE TERMS OF THESE
WARRANTIES. FAILURE TO RETURN THE WARRANTY CARD SHALL HAVE NO EFFECT ON THE DISCLAIMER OF THESE IMPLIED WARRANTIES.
ALL EXPRESS WARRANTIES SHALL BE LIMITED TO THE DURATION OF THIS EXPRESS LIMITED WARRANTIES SET FORTH HEREIN AND EXCLUDE ANY
LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES RESULTING FROM THE BREACH THEREOF. SOME STATES DO NOT ALLOW THE EXCLUSION OR
LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS OR EXCLUSIONS MAY NOT APPLY. PRODUCTS OR PARTS OF
OTHER MANUFACTURERS ATTACHED ARE SPECIFICALLY EXCLUDED FROM THE WARRANTY.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY HAVE OTHER RIGHTS WHICH VARY UNDER THE LAWS OF EACH STATE. IF ANY
PROVISION OF THIS WARRANTY IS PROHIBITED OR INVALID UNDER APPLICABLE STATE LAW, THAT PROVISION SHALL BE INEFFECTIVE TO THE EXTENT OF
THE PROHIBITION OR INVALIDITY WITHOUT INVALIDATING THE REMAINDER OF THE AFFECTED PROVISION OR THE OTHER PROVISIONS OF THIS WARRANTY.
Page 2 of 2