Installation Guide PDF
INSTALLATION MANUAL
Gujarat : 1800-2582-583 | Maharashtra : 1800-1024-212
Punjab/Himachal/J & K : 1800-1377-781 | South India: 1800-1200-666 | Rest of India : 1800-1020-666
Dear Customer
Congratulations on being the proud owner of Lloyd Air
Conditioner. Your Air Conditioner comes with Lloyd
Guarantee of Quality.
Lloyd takes great pride in
CONTENTS
Contents
1
Installation sketch
2
Installation instructions
3
Installation of the indoor unit
Securing the mounting plate
Wiring
Installation of the drain hose
Installation of the indoor unit
Pipe connection
Arrangement of the drain hose
Wall sealing and Pipe fastening
3
4
4
5
5
5
5
Installation of the outdoor unit
Wiring
Installation of the drain joint
Joint of the connecting pipe
Air exhausting
Process of flared tube
Adding refrigerant
Operation test
1
6
9
9
9
9
10
10
INSTALLATION SKETCH
Confirm the installation position by the mark of the indoor mounting plate.
or
above
105m
155mm
above 250mm
m
or
or
The connecting pipe can be led
from back, right, underside,
or left-back side.
Above 20mm
left
back
underside left-back
above 500mm
above 500mm
0mm
以0上
vem3
m
1a0b0o
0mm
0m
above 30
v
abo
ve 5
m
m
00m
ve 5
abo
00m
ve 5
e 30
abo
mm
00
ve 5
m
00m
ve 3
0mm
m
Above 500mm
A
B
abo
ve 5
00m
m
OR
Dual Split Model
m
00m
ve 5
abo
m
00m
ve 3
abo
0mm
above 30
TO B INDOOR UNIT
abo
B
A
00m
Dual inverter Model
TO A INDOOR UNIT
above 500mm
abov
UNIT
DOOR
TO B IN
Abo
Single Split Model
Sponge plastic adiabatic
material with the
thickness of 8mm.
B
m
00m
abo
m
0m
e 50
Cover connecting pipe with
adiabatic material.
A
ve 3
m
abo
TO A INDOOR UNIT
While installing the pipeline on the
thin armor plate or on the wall of
metal mesh, you should use the
wooden board to clamp between
the wall and the pipeline, or wrap
up the pipeline with 7-8 layers of
insulating plastic tape.
Attention:
e 30
front
back
right
The allowable length of the connecting
pipe is 10m.
The allowable distance between indoor
unit and outdoor unit is 5m.
abov
Notice: do not raise the
drain hose.
TO A INDOOR UNIT
above
DOOR
TO B IN
abo
ve 5
UNIT
00m
m
2
INSTALLATION INSTRUCTIONS
1 Location of indoor unit
Keep the air inlet and outlet at a far distance from the blockage.
Keep the height distance between the indoor and outdoor unit at most 5m.
Mount on the wall solid enough to bear the weight of the unit and not cause any shake.
Avoid direct sunshine.
A place easy for condensate drain and easy for connecting with the outdoor unit.
Keep a far distance away from the fluorescent lamp, it may influence the operation of remote controller.
Keep at least 1m away from the TV radio and other home appliances.
2 Location of outdoor unit
A place for firm location of the unit, solid enough to bear the weight of the unit and not cause any shake.
Good ventilation, less dust, far from direct rain and sunshine.
A place where the air discharged out of the outdoor unit or the operation noise will not annoy your
neighbours.
No blockage near the outdoor unit.
Avoid places close to inflammable gas leakage.
INSTALLATION OF THE INDOOR UNIT
1 Securing the mounting plate and drill on the wall
Secure the mounting plate
The mounting plate should be attached to the structural part of wall (post etc).
Fasten string at the central hole
fasten string at the central hole
at least 250mm
at least 250mm
at least 250mm
mounting plate
105mm or more
from sidewall
155mm or more
from sidewall
Tapping screw
ST4× 25(5)
NOTICE:
455mm or more
from sidewall
105mm or more
from sidewall
Tapping screw
ST4× 25(5)
plumb
plumb
mounting plate
The holes at solid arrow position must be secured to avoid the shake of mounting plate.
When the expansion bolts are used, two holes ( 11× 20 or 11× 26 ) that the distance
between them is 450mm should be adopted.
Drill on the wall
40mm
fasten string at the central hole
105mm
plumb
NOTICE:
3
45mm
Center of hole(? 65mm)
Confirm the position of holes, and drill holes on the wall.
Center of hole(? 65mm)
fasten string at the central hole
fasten string at the central hole at least 250mm
40mm
at least 180mm
Center of hole(? 65mm)
plumb
120mm
440mm
440mm
at least 80mm
at least 120mm
¦
at least 120mm
230mm
at least 140mm
90mm
plumb
Pipe hole
Center of hole(? 65mm)
¦
90mm
Pipe hole
NOTICE:
The holes at solid arrow position must be secured to avoid the shake of mounting plate.
When the expansion bolts are used, two holes ( 11× 20 or 11× 26 ) that the distance
between them is 450mm should be adopted.
Confirm the position of holes, and drill holes on the wall.
2 Wiring
Open the front grille;
Remove the screw from electrical box cover, pull the
Screw
electrical box cover away from the unit and set aside.
Remove the screw from fastener, pull the fastener
away from the unit and set aside.
Connect the cable.
Indoor unit terminal
Replace the fastener and electrical box cover.
Diagram
Connecting cable
NOTE:
The appliance shall be installed in accordance with national wiring regulations.
The appliance must not be installed in the laundry.
The appliance must be installed 2.5m above the floor.
The appliance must be positioned so that the plug is accessible.
For some models whose cooling capacity are above 4600W (17000BTU/h),
an all-pole disconnection device which has at least 3mm separation distance in
all pole and a residual current device(RCD)with the rating of above 10mA shall
be incorporated in the fixed wiring according to the national rule.
3 Installation of the drain hose
Liquid pipe
NOTE:
The drain hose must be arranged beneath the connecting pipe. Drain hose
The drain hose must not be hunched or twisted.
While wrapping up the drain hose, do not pull it.
The drain hose through the room must be wrapped up by the
thermal insulation materials.
felt
The connecting pipe and the drain hose must be wrapped up by felt
strip. Adiabatic pad should be used at where the pipe contacts
the wall.
gaspipe
Adiabatic
underlay
ROUTE OF PIPE
If pipe comes out of the right side of the indoor unit, cut part
1 of the unit;
If pipe comes out of the lower-right side of the indoor unit, cut
part 2 of the unit;
If pipe comes out of the left side of the indoor unit, cut part 3
of the unit.
1
2
3
4
READJUSTMENT OF DRAIN HOSE
If pipe comes out of the left side of the indoor unit, the drain hose
must be refitted, otherwise water leakage may occur.
Readjustment methods: Interchange the position of drain hose
and drain rubber plug.
Clearance is not allowed after refit, it would lead to water leakage.
Drain rubber
plug
drain hose
4 Installation of the indoor unit
Indoor unit
Let pipe go through the wall hole and attach the indoor
unit to the mounting plate.(Press the rib of indoor unit
inside the hook of the mounting plate.)
the mounting plate
the rib of indoor unit
Bottom
5 Pipe Connection
The number of bent position of the pipe in the indoor unit should not exceed 10.
The number of bent position of the pipe in the indoor unit and the outdoor unit should not exceed 15.
The radius of bent position should be more than 10cm.
Please break the evaporator craft tube with pincers before connecting. After exhausting the inside air,
use the wrench to twist down the nut of connecting tube of the evaporator.(Fig. 1)
Put some seal oil to cover the joint and the flare.
Align the centre of joint in line with that of flare and tighten the nut of connecting pipe with wrench.(Fig. 2)
Attention:
Do not exhaust the inside air just by loosing the nut since there is the air of certain pressure
inside the tube of indoor unit.
Please do not make extra effort for fear of damaging the expansion orifice.
DIAMETER OF PIPE
φ6/φ6.35mm(1/4")
φ9/φ9.52mm(3/8")
φ12/φ12.7mm(1/2")
φ15/φ15.88mm(1/2")
TORQUE(N· m)
12.0---15.0
33.0---36.0
40.0---45.0
73.0---78.0
Evaporator
craft tube
(Fig. 1)
6 Arrangement of the drain hose
(Fig. 2)
To drain the condensate water easily, the drain hose should be declined downwards.
The following 5 arrangement methods are incorrect.
Decline
downward
Decline
downward
Dip hose
into water
Standing water
air
Water
leak
(Fig. 1)
Water
leak
(Fig. 2)
Water
leak
(Fig. 3)
(Fig. 4)
If you find the drain hose not long enough to connect with the indoor
unit, you can extend it with the hoses in the accessory box.
The drain hose through the room must be wrapped up with the special
adiabatic material.
Use putty to seal the wall hole.
Use clamp (pipe fastener) to secure the pipe at specified position.
get rid of unwanted part
clamp
secure the connecting
pipe with clamp
indoor unit
5
(Fig. 5)
Drain hose
Hose(ID 15cm)
PVC hard
7 Wall sealing and Pipe fastening
seal with putty
50mm or less
above floor
screw
INSTALLATION OF THE OUTDOOR UNIT
1 Wiring
Outdoor unit terminal
Connecting
cable
Outdoor unit terminal
Connecting
cable
Outdoor unit terminal
Connecting
cable
OR
Dual Split Model
Single Split Model
Wiring For Above 6000W Model (Above 21000BTU/h Model)
1 Remove the self-tapping screws (2 pcs)
onthe maintenance board and take out the
maintenance board.
The cable wire can be led from the back hole
of the piping hole or ejecting hole.
Please utilize outdoor pipe support when
the cable wire is led from the backside.
Terminal board
Fix the cable wire
with anchor cable
Maintenance
board
Piping cover
2 Loosen the self-tapping screws (2 pcs) on
the fixing clip to loosen the fixing clip.
3 Loosen the fixing screw of the wire terminal
board, pass the power wire and signal wire
through the fixing clip. Then firmly fix the
power wire and signal wire on the terminal
board with the fixing screw. (Earth wire
must be connected firmly.)
Outdoor pipe support
(Outdoor pipe support is not required
when leading the cable wire from other places).
4 Tighten the self-tapping screw on the fixing clip.
5 Install the maintenance board. After the pipes
and cable wire are installed, please seal the
sponge block as per drawing indication.
Maintenance
board
Back wiring
Piping cover
Right wiring
Piping cover Ejecting hole
Sponge
6
Connect diagram
1500 -4600W Model (5000-12000BTU/h Model)
N23 4
2N
N23 4
Indoor unit terminal
Plug housing 1
Indoor unit terminal
Connecting Brown
cable
Blue
Brown
Blue
Yellow/Green
Gray
Brown
Blue
Yellow/Green
Black
Outdoor unit
terminal
N2
N2 3
4 R1R2
Heat pump type
Cool only type
Plug housing 1
Connecting
cable
Brown
Black
Gray
Blue
Brown
Yellow/Green
Blue
Plug housing 2
Outdoor unit terminal
N2 3 4
Heat pump type
OR
5000-5100W Model (17000-18000BTU/h Model)
2N
N23 4
N23 4
Indoor unit terminal
N234
Plug
housing 1
Plug
housing 1
Plug housing 1
Indoor unit terminal
Connecting cable
Connecting cable
Blue
Black
Brown
Blue
Brown
Blue
Yellow/Green
N2
Brown
Blue
Brown
N2 3 4
Yellow/Green
Plug
housing 2
Gray
Yellow/Green
Blue
Brown
Blue
Brown
N2 3 4
N2 3
4 R1R2
Outdoor unit terminal
Outdoor unit terminal
Heat pump type
Cool only type
Brown
Plug
housing 2 Blue
OR Heat pump type
Heat pump type
OR
6000-10000W Model (21000-36000BTU/h Model)
2
L N2 3
L N2
Indoor unit terminal
Indoor unit terminal
L1 L2
L 2
L3N
234
R1 R2
5 6
Blue
Brown
Gray
Yellow/Green
Brown
Blue
Connecting cable
Brown
Black
Gray
Blue
L3 N
Yellow/Green
Blue
Yellow/Green
Connecting cable
Brown
Black
Plug
housing 1
LN2 3 4
Connecting
cable
Brown
Connecting cable
Yellow/Green
Blue
Brown
Blue
Brown
Black
L1 L2
Outdoor unit
Plug
L 2 L3
terminal
housing 2
Outdoor unit terminal
Blue
Brown
Cool only type
OR
Heat pump type
Inverter Type
Dual Split Inverter Type
Indoor unit terminal
Indoor unit A terminal
NL2
Connecting
cable
Blue
Black
Brown
Yellow/Green
Blue
N POWER
L SOURCE
Brown
Dual Split Model
Indoor unit B terminal
2 L N
2 L N
Connecting
cable
Power
source
L N
R1 R2
5 6
Heat pump type
(T3)
Indoor unit A terminal
Connecting
cable
L N 2 Plug housing 2
Outdoor unit terminal
Heat pump type
2 L N
Power
source
Yellow/Green
Brown
234
Indoor unit B terminal
2 L N
Plug housing 1
Gray
N POWER
L SOURCE
Cool only type
(T3)
Heat pump type
Blue
Black
Brown
LN
N
Outdoor unit terminal
7
LN
安装说明
L1 L2
L 2
L N2 3
Plug
housing 1
Indoor unit terminal
Brown
Black
Plug housing 1
LN
L N 2A2B
Blue
Blue Black
Yellow/Green Brown
Heat pump type
Black
Outdoor
unit terminal
L
N 2A2B
Yellow/Green Brown Blue
Outdoor
unit terminal
Black
Cool only and heat pump type
Notice:
If not include the connect diagram you need, please see the wiring diagram.
If you find the color of connecting cable not comply with the top diagram, please take
real objects as major reference. But the terminal of the same sign must be joint with
the connecting cable of the same color.
The plug housing 1 is connected to the matched receptacle housing of the indoor unit.
The plug housing 2 is connected to the matched receptacle housing of the outdoor unit.
If the signal wire has to be bought separately, choose electric wire above 0.75mm.
If not include the connect diagram you need, please see the wiring diagram.
If the interconnection cord for power supply has to be replaced, please see the
following table for reference.
MODEL
2700W(10000BTU/h)
3200W(11000BTU/h) -4000W(15000BTU/h)
4500W(16000BTU/h) -8000W(28000BTU/h)
8500W(29000BTU/h) -9500W(32000BTU/h)
10000W(34000BTU/h) -11000W(38000BTU/h)
SPECS (Interconnection cord)
1.0mm 2
1.5mm 2
2.5mm 2
4.0mm 2
6.0mm 2
WARNING:
Please take the electric circuit diagram attached to the indoor/outdoor units as major
reference while installing.
The power wire and signal wire between the indoor/outdoor units must be connected
one by one as per corresponding number on the wiring terminal board.
The connecting cables must be clipped together.
Special cable must be used to connect indoor unit and outdoor unit. It should be ensured
that the terminals are not influenced by external force. Poor connection may cause fire.
The electric box cover must be mounted and secured in position, otherwise fire or electrical
shock may occur because of dust or moisture.
The temperature of refrigerant circuit will be high, please keep the interconnection cable away
from the connecting tube.
All the models shall be connected with the mains which has system impedance limitations.
While installing the unit, please see the following table for impedance information or consult
with the supply authority.(The following information and specifications are subject to change
without prior notice due to continuing research.)
SERIES
R22
series
R407C
series
R410A
series
MODEL
IMPEDANCE
6800W (24000BTU/h)
5100W (18000BTU/h)
3500W (12000BTU/h)
3200W (11000BTU/h)
2500W (9000BTU/h)
6500W (22000BTU/h)
5100W (18000BTU/h)
3500W (12000BTU/h)
3300W (11500BTU/h)
3200W (11000BTU/h)
2500W (9000BTU/h)
2000W (7000BTU/h)
Dual Split Model(25+25)
≤
≤
≤
≤
≤
≤
0.116Ω
0.160Ω
0.312Ω
0.312Ω
0.467Ω
0.204Ω
≤
≤
≤
≤
≤
≤
≤
0.162Ω
0.148Ω
0.121Ω
0.121Ω
0.323Ω
0.302Ω
0.187Ω
Dual Split Model(25+35)
6800W (24000BTU/h)
5100W (18000BTU/h)
≤ 0.138Ω
≤ 0.124Ω
≤ 0.268Ω
8
2 Installation of the drain joint (only for heat pump type)
Insert the outdoor double-channel drain joint in one of the
bottom holes of the suitable size then connect drain hose
and joint together.
Bottom
3 Joint of the connecting pipe
Double-channel
drain joint
Put some seal oil to cover the joint and the flare.
Drain hose
Align the centre of joint in line with that of flare and tighten the nut of connecting pipe
with wrench. ( Adjust the torque by the same method of connecting pipe for indoor unit.)
4 Air exhausting
Screw down the cap of both gas shut-off valve and
liquid shut-off valve as well as the nut of service port.
Use Allen wrench to turn the valve cork of liquid side
at 90 counter-clockwise, and close it after 10 seconds.
Use soapy water to check the gas leakage especially
at all joint. If there is no gas leakage, please turn the
valve cork of liquid side at 90 counter-clockwise again.
liquid connecting pipe
liquid shut-off valve
allen wrench
gas connecting
pipe
gas shut-off
Press the cork of service port at gas shut-off valve, 10 valve
seconds later, when you see foggy gas discharged, that
means inner air is exhausted out.
valve nuts
service port
service port cap
Use Allen wrench to turn the valve cork of both liquid
shut-off valve and gas shut-off valve counter-clockwise
until they are completely open and then replace the
valve caps and tighten them.
Notice:
Do not vent refrigerant into atmosphere: refrigerant is a fluorinated greenhouse gas, covered by
Kyoto protocol, with a Global Warming Potential (GWP) =1900(R410A)/1600(R407C)/1700(R22).
5 Process of flared tube
Use the pipe cutter to cut off the broken part of flare.
Remove burrs at the cut of the flare.
Insert a nut into the connecting pipe and do flaring
with specified flaring tools, reamers for example.
Outer diameter
φ6/φ6.35mm(1/4")
A(mm)
φ12/φ12.7mm(1/2")
2.0--2.5
3.0--3.5
3.5--4.0
φ15/φ15.88mm(1/2")
4.0--4.5
φ9/φ9.52mm(3/8")
Connecting pipe
90
Burr
D
Oblique
Roughness
Reamer
A
Check the quality of flaring technique.
Connecting pipe
9
Burr
6 Adding refrigerant
If the connecting pipe is longer than 7 metres, add refrigerant as needed. (Cool only type) added
amount A=(Lm-7m) 15g/m ; (Heat pump type)added amount A= (Lm-7m) 50g/m. ( A: amount
of added refrigerant, L: the length of connecting pipe)
The length of connecting pipe (m)
7
8
9
10
(Cool only type)added amount (g)
0
15
30
45
(Heat pump type)added amount (g)
0
50
100
150
Exhaust the air as the above-mentioned method.
Screw the gas shut-off valve to close, connect
charging hose(low pressure) to the service valve
Manifold gauge
Low pressure
valve
Pressure meter
High pressure
valve
and then open gas shut-off valve again.
Connect the refrigerant bottle to the charging hose
and then convert it.
Charging line
Fill in liquid refrigerant as the above table.
Disconnect the manifold gauge after turning off the
Service port
shut-off valve, and then open gas shut-off valve again.
Tighten nuts and caps of each valve.
7 Operation test
Before test operation, wiring safety inspection must be carried out carefully again.
1. Emergency switch operation: Every press of emergency switch, the
air conditioner runs as in the following order:
Cool only type: Cool
Shut off
Heat pump type: Cool
Heat
Shut off
2. Remote controller operation: If the indoor unit sounds like Di, Di when pressing I/O button,
that indicates the air conditioner is under the operation of remote controller. After that, press
every button to test their functions.
3.Check switch operation: Open the front grille and press the check button. Switch on the power
source and then the operation test is activated. If the indicator lamps light up at first and then
go out in succession or the LED window of the indoor unit illuminates at first and then goes out,
the system is under normal operation. If one of the indicator lamps is flashing at all times, or
failure codes are displayed on the LED window of the indoor unit, the system has something
wrong and please check malfunction immediately.