40/40I - Spectrex Inc.

40/40I - Spectrex Inc.
TM
40/40M
40/40I
40/40L-LB
40/40UFL 40/40L4-L4B 40/40U-UB
40/40I
Triple IR (IR3) Flame Detector
40/40R
Superior performance, reliability and immunity to false alarms
FEATURES & BENEFITS
•Multi spectrum design - for long distance detection and high
false alarm immunity
•Sensitivity selection - to ensure no zone crossover detection
•Automatic and Manual Built-In-Test (BIT) - to assure
continued reliable operation
•Heated window - for operation in harsh weather conditions
(snow, ice, condensation)
•Multiple output options for maximum flexibility and
compatibility
- Relays (3) for Alarm, Fault and Auxiliary
- 0-20mA (stepped)
- HART Protocol for maintenance and asset management
- RS-485, Modbus Compatible
•High Reliability - MTBF - minimum 150,000 hours
•Approved to Safety Integrity Level 2 (SIL2 – TUV)
The new 40/40I, a multi spectrum based
on three IR bands (IR3), detects fuel and
gas fires at long distances with the highest
immunity to false alarms. The 40/40I IR3
can detect a 1 ft2 (0.1m2) gasoline pan fire at
215 ft (65m) in less than 5 seconds.
The 40/40I is the most durable and
weather resistant flame detector currently
on the market. Its new features include a
heated window, to eliminate condensation
and icing; HART capabilities for digital
communications; lower power requirements;
and a compact, lighter design.
Due to increased reliability, the 40/40 Series
warranty period has been extended to
5 years and is SIL2 (TUV) approvedto
IEC 61508.
•5-Year Warranty
•User Programmable via HART or RS-485
•Hazardous area zones:
- Zones 1 & 2 with IIC gas group vapors present
- Zones 21 & 22 with IIIC dust type present
•Ex approved to:
- ATEX & IECEx
- FM/FMC/CSA
•3rd party performance tested
- EN54-10 (VdS)
- FM3260
•Marine Approval
- MED ‘Wheelmark’ approval (DNV)
APPLICATIONS
Offshore Oil & Gas installations
Onshore Oil & Gas installations
and pipelines
Chemical plants
Petrochemicals plants
Storage Tank farms
Aircraft hangars
Headquarters: 218 Little Falls Road | Cedar Grove | NJ 07009 | USA
Tel: +1 (973) 239-8398 | +1 (800) 452-2107 (US only) | Fax: +1 (973) 239-7614
Houston: +1 (832) 321-5229 | Europe: +44 (141) 578-0693
E-mail: spectrex@spectrex.net | www.spectrex.net
Power Generation facilities
Pharmaceutical Industry
Printing Industry
Warehouses
Automotive
Explosives & Munitions
Waste Disposal facilities
TM
GENERAL SPECIFICATIONS
Spectral Response
Detection Range
(at highest Sensitivity Setting
for 1ft 2 (0.1m2) pan fire)
Response Time
Adjustable Time Delay
Sensitivity Ranges
Field of View
Built-in-Test (BIT)
Temperature Range
Humidity
Heated Optics
Three IR Bands
Fuel
ft /m
n-Heptane 215/65
Gasoline 215/65
Diesel Fuel 150/45
JP5
150/45
Fuel
ft /m
Kerosene
150/45
Ethanol 95%
135/40
Methanol
115/35
IPA (Isopropyl Alcohol) 135/40
Fuel
Methane*
LPG*
Polypropylene Pellets
Office Paper
ft /m
150/45
150/45
115/35
83 /25
* 30" (0.75m) high, 10" (0.25m) width plume fire
Typically 5 seconds
Up to 30 seconds
4 Sensitive ranges for 1 ft 2 (0.1m2) n-heptane pan fire from 50 ft (15m) to 215 ft (65m)
Horizontal 100º; Vertical 95º
Automatic (and Manual)
Operating: -67ºF to +167ºF
(-55ºC to +75ºC)
Option:
-67ºF to +185ºF (-55ºC to +85ºC)
Storage:
-67ºF to +185ºF (-55ºC to +85ºC)
Up to 95% non-condensing (withstands up to 100% RH for short periods)
To eliminate condensation and icing on the window
ELECTRICAL SPECIFICATIONS
Operating Voltage
Power Consumption
Cable Entries
Wiring
Electrical Input Protection
Electromagnetic Compatibility
Electrical Interface
24 VDC nominal (18-32 VDC)
Standby: Max. 90mA (110mA with heated window)
Alarm:Max. 130mA (160mA with heated window)
2 x 3/4" - 14NPT conduits or 2 x M25 x 1.5 mm ISO
12 - 22AWG (0.3mm2 -2.5mm2)
According to MIL-STD-1275B
EMI/RFI protected to EN61326-3 and EN61000-6-3
The detector includes twelve (12) terminals with five (5) wiring options (factory set)
OUTPUTS
Relays
0-20mA (stepped)
HART Protocol
RS-485
Alarm, Fault and Auxiliary
SPST volt-free contacts rated 2A at 30V DC
Sink (source option) configuration
Fault: 0 +1mA
Warning:
16mA ± 5%
BIT Fault: 2mA ± 10%
Alarm: 20mA ± 5%
Normal: 4mA ± 10%
Resistance Loop: 100-600 Ω
Optional HART communications on the 0-20mA analog current (FSK) - used for maintenance,
configuration changes and asset management, available in mA source output wiring options
RS-485 Modbus compatible communication link that can be used in computer controlled installations
MECHANICAL SPECIFICATIONS
Materials
Enclosure options
Mounting
Dimensions
Weight
Environmental Standards
Water and Dust
- Stainless Steel 316L with electro polish finish
- Heavy duty copper free aluminum (less than 1%), red epoxy enamel finish (not available in FM version)
Stainless Steel 316L with electro polish finish
Detector
4" x 4.6" x 6.18" (101.6 x 117 x 157 mm)
Detector (St.St.)
6.1 lb (2.8 kg)
Tilt mount 2.2 lb (1.0 kg)
Detector, aluminum
2.8 lb (1.3 kg)
Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock, High Temp, Low Temp
IP66 and IP67 per EN60529, NEMA 250 6P
APPROVALS
Hazardous Area
ATEX and IECEx
Ex II 2 G D
Ex d e IIC T5 Gb
Ex d e IIC T4 Gb
Ex tb IIIC T96°C Db
Ex tb IIIC T106°C Db
(-55°C ≤ Ta ≤ +75°C)
(-55°C ≤ Ta ≤ +85°C)
FM/FMC/CSA
Class I Div. 1, Groups B, C & D
Class II/III Div. 1, Groups E, F & G
Performance
EN54-10 (VdS)
FM3260
Reliability
IEC61508 - SIL2 (TUV)
Marine
MED ‘Wheelmark’ approval (DNV)
ACCESSORIES
Flame SimulatorFS-1100 U-Bolt/Pole Mount
789260-2 (2” pole) Mini Laptop Kit777820Weather Cover 777163 (St.St)
Tilt Mount
40/40-001
789260-1 (3” pole) Air Shield
777650 *777263 (Plastic)
Duct Mount777670 USB RS485 Harness Kit794079-5
Cone Viewer
777166
E.O.L Encapsulated Resistor777915-X
*Supplied free of charge with the detector
DS-F-40/40I, June 2015
Specifications subject to change
For more information view manual or website www.spectrex.net