afp - 2759 - Autronica Fire and Security
CSIRO Verification Services
Highett, Victoria, Australia
+61 (0)3 9252 6000
http://www.activfire.gov.au/
Certificate of Conformity
Certificate num.
afp - 2759
Registration date
9-Mar-2012
Version
Valid until
Number
Issue date
1
9-Mar-2012
Product designation
AutroSafe 4, fire alarm and control system
(Refer to the Schedule/enclosures for further specified details)
Agent/distributor
Kidde Australia
314 Boundary Road, DINGLEY, VIC, AUSTRALIA, 3172
Registrant
Autronica Fire and Security AS
Haakon VII Gt. 4, 7483 Trondheim, NORWAY
Producer
Autronica Fire and Security AS
Haakon VII Gt. 4, 7483 Trondheim, NORWAY
Conformance criteria and evaluation
The AutroSafe 4, fire alarm and control system has been evaluated and verified as
conforming with the relevant requirements of the following criteria.
1. Australian Standard AS 7240.2-2004, 'Fire detection and alarm systems - Control and
indicating equipment (ISO 7240-2:2003, MOD)'.
2. Australian Standard AS 7240.4-2004, 'Fire detection and alarm systems - Power
supply equipment (ISO 7240-4:2003, MOD)'.
3. ActivFire Technical Specification AF-TS002, Version 1.0, 23-Jan-2012, 'Input/Output
modules for control and indicating equipment'.
Limitations/conditions of conformance
Limitations/conditions of conformance, where identified on this certificate, are derived from qualifications
from evaluation(s) for conformity and/or other related technical documentation. All details with respect to
design, assembly and installation instructions and restrictions should be checked against the producer's
current technical manual/data sheets and the requirements of the Authority having Jurisdiction.
Specified limitations/conditions, determined from the evaluation for conformity, include the
following.
i.
Compatibility of this equipment with new or existing actuating devices should be
verified prior to installation.
ii.
The installation of this equipment shall be in areas appropriate to the lower audible
indication level as contemplated in AS 7240.2-2004, clause 13.10.2.
Issued by
Page 1 of 4
31-Dec-2012
This certification is issued within
the scope of CSIRO Verification
Services – Rules governing
ActivFire Scheme and is valid only
for the product(s) as submitted for
evaluation and verification of
conformity, subject to the following
conditions.
• Reference to details, limitations
and requirements, where
documented as a
schedule/enclosure with this
certificate.
• The Registrant is responsible
for their attestation of
conformity and ensuring that
on-going production complies
with the conformance criteria
defined in this certificate.
• This certificate will not be valid
if any changes or modifications
are made to the product which
have not been notified and
validated by CSIRO Verification
Services.
• This certificate is subject to
periodical re-validation upon
verification that all
requirements, as determined
by the conformity assessment
body, continue to be
satisfactorily met by the
Registrant.
• This certificate may only be
reproduced in its published
form, without modification and
inclusive of all
schedules/enclosures.
• Any changes, errors or
omissions, must be submitted
in writing and if necessary or
requested, substantiated with
relevant evidence.
• Any representations, such as
advertising or other marketing
related activities or articles
shall reflect the correct
contents of this certificate and
conform with all relevant trade
practices .and consumer
protection legislation and
regulations.
• Any terms or conditions of use
as applicable to content and
documentation as published or
accessed through web sites
administered by the CSIRO
Verification Services.
David Whittaker
Executive Officer – ActivFire Scheme
© CSIRO Australia, 2012
This certificate remains the property of CSIRO and may be subject to amendment, suspension or withdrawal at any time.
The validity and authenticity of this certificate can be verified by the certification register located at http://www.activfire.gov.au
Schedule to
Certificate of Conformity
Certificate num.
Registration date
afp - 2759
Version
9-Mar-2012
Valid until
Number
Issue date
1
9-Mar-2012
31-Dec-2012
Page 2 of 4
Producer's description
The AutroSafe 4, fire alarm and control system, provides advanced functionality within fire detection for a wide
range of applications.
The system is designed to meet requirements in the high-end segment of the land, maritime and offshore market.
The AutroSafe 4, fire alarm and control system operates on a high-speed and fully redundant Ethernet based
network solution; AutroNet, providing extremely fast data transmission. A maximum of 64 system units (panels,
controllers) can be connected to the AutroNet. A standalone system is also possible, using the Fire Alarm Control
Panel BS-420 (the mandatory panel in any system).
The system has a large capacity, and the fact that all types of loop units can be connected to the same detection
loop gives large flexibility.
Technical specification
The following details are a representative extract of the technical specification for the AutroSafe 4, fire alarm and control system and
may be subject to change. Complete and current details should be determined from the designated producer’s technical manual/data
sheets.
1. Schedule of designated system components
The AutroSafe 4, fire alarm and control system comprises of a number of modules, as detailed below, which mount
into the c.i.e. housing or are field mountable.
System component designation
Conformance
criteria
Component type
Modules included
Fire Alarm Control Panel
BSE-310 – Input Module, monitored
BSB-310 – Output Module, monitored
BSD-310– Loop Driver Module
BSL-310- Communication Module
BSS-310A – Power Supply Module
FL Switch 8TX – 10/100 MBit/s eight Port Ethernet Switch
FL Switch 8TX – 10/100 MBit/s eight Port Ethernet Switch
BSA-400 – Main board
BSR-400 – Front board
AS 7240.2-2004
BC-420
Controller
BSE-320 – Input Module
BSJ-310 – Output Module
BSD-310– Loop Driver Module
BSL-310- Communication Module
BSS-310A – Power Supply Module
BSA-400 – Main board
BSR-400 – Front board
AS 7240.2-2004
Part num.
BN-221/01
Extinguishing Control Unit
BNA-221
AS 7240.2-2004
Part num.
BN-221/02
Monitored Output Unit
BNA-221
AS 7240.2-2004
BP-405
Power Cabinet
BPS-405 – Power Unit
BSF-400 – Main board
MeanWell SC-150-27ME – Power Supply
AS 7240.4-2004
Ident. type
Ident.
BS-420
BS-420G
Product name
(Model)
BS-420G2
BS-420M
Product name
(Model)
Product name
(Model)
Part num.
BN-300
Input Unit
BNB-300
AF-TS002
Part num.
BN-310
Single Relay Output Unit
BNA-320
AF-TS002
2. Specified properties for c.i.e. and p.s.e. modules
BP-405
The Power Cabinet BP-405 provides space for two 12 Vdc / 18 Ah batteries (not included). The maximum power
available is 24 Vdc / 5 A.
Dimensions (mm)
Protection class
Operating Temperature
Current
Input voltage range
Output
Battery size
420 x 346 x 146
IP32
-15 to +70°C
230VAC 1,6A
184 – 264 VAC (47 – 63 Hz )
3.5 A (max load)
5 A (max load without batteries)
7.2 Ah (min)
18 Ah (max)
Schedule to
Certificate of Conformity
Certificate num.
Registration date
afp - 2759
9-Mar-2012
Version
Valid until
Number
Issue date
1
9-Mar-2012
31-Dec-2012
Page 3 of 4
BS-420
BS-420 is a complete fire alarm control panel with full operating capabilities. The panel serves as a operating panel
for one or several operation zones.
All alarm handling and system features can be controlled and monitored from the panel.
The fire alarm control panel is available in three different variants specifically designed for the land market (BS420), maritime market (BS-420M) and petrochemical oil & gas market (BS-420G).
Dimensions (mm)
Protection class
Operating Temperature:
Power supply
350 x 350 x 161
IP32
-15 to 70 °C
Nom. 27.2V DC (18-32V DC)
BC-420
The Controller serves as a connection unit for Loop Driver Modules and I/O modules.
Dimensions (mm)
Protection class
Operating Temperature:
Power supply
350 x 350 x 161
IP32
-15 to 70 °C
Nom. 27.2V DC (18-32V DC)
3. Schedule of optional functions with requirements and alternatives
AS 7240.2 Clause
7.8
7.9
7.10
7.11
7.12
7.13
8
9.3
9.4
9.9
10
10.5
11
12
16.6
16.7
Annex ZA
Annex ZB
Annex ZC
Annex ZD
5.5
9.7
9.8
9.11
Annex ZA
Optional function with requirements
Output to fire alarm devices
Output to fire alarm routing equipment
Output to fire protection equipment
Delays to outputs
Coincidence of protection
Alarm counter
Supervisor condition
Fault signals from points
Total loss of power supply
Output to fault warning routing equipment
Disable condition
Disablement of addressable points
Test condition
Standardized I/O Interface
Impact Test (operational)
Vibration (operational)
Marking requirements
Alarm Acknowledgement Facility
Dry Heat Test
Ancillary Control Function
Battery function check
Impact (operational)
Vibration (operational)
Vibration (endurance)
Marking requirements
Evaluation
Included
Included
*see Note 1
Included
Not evaluated
Not evaluated
Not evaluated
Not evaluated
Included
Not evaluated
Included
Included
Included
Included
Not evaluated
Included
Included
Included
Not evaluated
Included
Not evaluated
Included
Included
Included
Included
Included
Note 1: Output to Fire Protection Equipment may be provided by either BSB-310, BN-221/01 or BN-221/02.
Schedule to
Certificate of Conformity
Certificate num.
Registration date
afp - 2759
9-Mar-2012
Version
Valid until
Number
Issue date
1
9-Mar-2012
31-Dec-2012
Page 4 of 4
4. Schedule of relevant articles
Reference
Ident. type
Report
Number
Report No.
Source
Title
CSIRO, Materials Science
and
Engineering,
Fire
Systems, AU
Conformity Evaluation of the
AutroSafe 4 Fire Detection System
to the requirements of
AS 7240.2 2004 and AS 7240.4 2004
7-Mar-2012
2010-3107
Technical Report – Autronica Fire and Security AS –
Maritime Testing of I/O- and A/V Units
5-May-2010
2009-3710
Rev. 01
Technical Report – Autronica Fire & Security AS –
AutroSafe Release 4 EN 54-2 & EN 54-4 Testing
19-Feb-2010
2009-3691
Rev. 02
Technical Report – Autronica Fire & Security AS –
EMC and Environmental Testing of AutroSafe 4
Components (Maritime Testing)
21-Dec-2009
2009-3664
Rev. 01
Technical Report – Autronica Fire & Security AS –
EMC and Environmental Testing of AutroSafe 4
Components (CE Marking)
11-Dec-2009
2002-3146
Rev. 01
Technical Report – Autronica Fire and Security AS –
Type Test of I/O Units
26-Feb-2002
Ident.
XF2709/R1
Det Norske Veritas, NO
Issue
Report
Number.
XF2709/R2
CSIRO, Materials Science
and
Engineering,
Fire
Systems, AU
Conformity Evaluation of the
AutroSafe BN 300 and BN 310 I/O Modules
to the requirements of ActivFire Technical
Specification AF TS002 Issue 1.0
23-Feb-2012
Report No.
2001-3252
Rev. 01
Det Norske Veritas, NO
Technical Report – Autronica Fire and Security AS –
Type Approval Testing of I/O Units
12-Jul-2001