TCP2U-2500 2500 Watt Front
TCP2U-2500
2500 Watt Front-End Power Supply
TECTROL 2500 WATT 24/48 VOLT 2U FRONT-END POWER SUPPLY
The TCP2U-2500 provides up to 2500 Watts of highly
reliable DC power in a compact 2U module that is designed
to deliver reliable bulk power to distributed power
architecture applications that require high power density.
The TCP2U is available in industry standard 24 and 48 volt
models and can be modified or configured to supply
different power output levels as required.
A compact form factor allows integration of 2 parallel or
redundant TCP2U modules in TECTROL’s TCP2R
configurable 2U Power System (or any standard 84 HP
width 19” 2U rack).
Hot swap capability is implemented through the use of an
industry standard connector that combines both AC power
and DC output connections in a single “blind mate”
configuration.
2
Optional digital interfaces such as I C can be configured on
the TCP2U to meet application-specific needs.
FEATURES
AGENCY COMPLIANCE
• True 2500 Watt output power (no derating)
• UL/cUL Approval
• High line input
• TUV Approval
• Low 2U profile provides high power density
• CE Mark (to the LVD requirements of EN 60950)
• Full hot swap capability
• Harmonic Compliance to EN61000-3-2 (Class A & D
Limits)
• Non-redundant parallel operation or N+1
configuration
• High efficiency
EMISSIONS AND IMMUNITIES
• Single wire active current share
• EN 55022 Class B Emissions
• Integral Isolation (ORing) Diodes
• EN 61000-3-2 Class D Harmonic Compliance
• EN 61000-4 Compliance
• I2C EEPROM Bus Chip option
• Strenuously HALT tested to ensure maximum
reliability and long life
MAX OUTPUT POWER
OUTPUT (Volts)
OUTPUT (Amps)
AC INPUT (Volts)
MODEL NUMBER
2500 W
2500 W
48
24
52
83
175 to 264
175 to 264
TCP2U-2500-48
TCP2U-2500-24
Tectrol Inc.
39 Kodiak Crescent, Toronto, Canada M3J 3E5
Tel: + 1 (416) 630 8108 Fax: + 1 (416) 638 0553
sales@tectrol.com
www.tectrol.com
European Office
Tel: + 44 (208) 399 6824
Fax: + 44 (208) 390 7355
eurosales@tectrol.com
Revision: d04a © Tectrol Inc. 2004
Specifications subject to change
TCP2U-2500
2500 Watt Front-End Power Supply
TECHNICAL SPECIFICATION
INPUT SPECIFICATION
PROTECTION
High Line Input
AC Line Input
175 to 264 Vrms, 50/60 Hz
20.3 Arms max @ 175 VAC input voltage
Overload Protection
< 50 Apk @ 220 VAC, half cycle, cold start
(25 C)
Inception point 125%. Unit protected
against a permanent short circuit (ISC
limited to 110% Imax).
Line Inrush Current
Power Factor
Harmonic Compliance
Over Voltage Protection
60 V max guaranteed shutdown. Reset by
recycling of the incoming AC supply.
Leakage Current
> 0.97 (typically 0.99)
Complies with IEC 1000-4-7 & EN 61000-3-2
Class D Limits
3.0 mArms per module
Voltage Dip/Interruptions
Transients & Surges
Complies with IEC/EN 61000-4-11
Complies with IEC/EN 61000-4-5
Over Temperature Protection Shutdown in the event of operation in
excessive ambient temperature or
blocked/failed airflow (self recovery
following temperature reduction).
Efficiency
> 85% full load, nominal line (including ORing
diodes)
Signals
I/O Signals: AC Fail; DC Good; Over Temp
Module Present; Remote Latch-Off.
LED Indicators
AC Fail; DC Good; OVP Shutdown; Thermal
Shutdown.
OUTPUT SPECIFICATION
MECHANICAL FORMAT
Factory Set Output Voltage 48 + 0.15 V @ 50% FL
Static Voltage Regulation
46.3 to 49.7 (line, load regulation,
temperature)
Input/Output Connector
Mechanical Outline
Positronic PCIH38M400A1 connector; AC
input and DC Output in to a single
connector for true hot swap capability
3.34” (H) x 8.09” (W) x 14.14” (L)
84.84 mm x 205.49 mm x 359.16 mm
Ripple & Noise (PARD)
Output Current
250 mV pp for 48 V; 500 mV pp for 24 V
48 V nom @ 52 A; 24 V nom @ 104 A
Module Power
Current Share
2500 W continuous operation @ 55 C
Single wire active current share
ENVIRONMENTAL
Parallel Operation
Hot Swap Capability
Remote Sense
Compensation
Parallel non-redundant or N+1
Fully hot swappable, blind mate connector
For ORing diodes & connector drop
Temperature Range
Operational: 0 to 55 C, FL no derating
Cooling / Air Flow
Integral high performance fans. Airflow
direction; inlet at fan face; exhaust at
connector face.
Transient Response
5% deviation from nominal set voltage, for
10% - 90% step load change. Recovery to
within 1% within 300 mS.
Tectrol Inc.
39 Kodiak Crescent, Toronto, Canada M3J 3E5
Tel: + 1 (416) 630 8108 Fax: + 1 (416) 638 0553
sales@tectrol.com
www.tectrol.com
European Office
Tel: + 44 (208) 399 6824
Fax: + 44 (208) 390 7355
eurosales@tectrol.com
Revision: d04a © Tectrol Inc. 2004
Specifications subject to change