The LAARS Gateway RER and Gateway LER. Startup Guide for

The LAARS Gateway RER and Gateway LER. Startup Guide for
LAARS Gateway Startup Guide
The LAARS Gateway Startup Guide
Document 4236B
H2355100A
H2355100A
The LAARS Gateway RER and Gateway LER.
Startup Guide for customer product automation systems
that use the following protocols:
BACnet MSTP, BACnet IP, Modbus TCP,
Metasys N2 by JCI, and LonWorks
to interface with:
LAARS Mascot II, NeoTherm,
NeoTherm LC Boilers and Water Heaters.
H2354400B
APPLICABILITY & EFFECTIVITY
Explains the Gateway RER and LER hardware and how to install it.
The instructions are effective for the above as of September 2012
800.900.9276
Service Advisors)
Advisors)
800.900.9276• •Fax
Fax800.559.1583
800.559.1583 (Customer
(Customer Service, Service
2020
Industrial
603.335.3355(Applications
(ApplicationsEngineering)
Engineering)
IndustrialWay,
Way,Rochester,
Rochester,NH
NH03867
03867•• 603.335.6300
603.335.6300 • Fax 603.335.3355
1869
Sismet
905.238.0100••Fax
Fax905.366.0130
905.366.0130
1869
SismetRoad,
Road,Mississauga,
Mississauga,Ontario,
Ontario,Canada
Canada L4W
L4W 1W8 • 905.238.0100
www.Laars.com
www.Laars.com
Page 2
LAARS Heating Systems
Page 2 of 32
LAARS Gateway Startup Guide
THIS PAGE INTENTIONALLY LEFT BLANK
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
Page 3 of 32
TABLE OF CONTENTS
1
Introduction ................................................................................................................................................... 5
1.1
BTL Mark – BACnet Testing Laboratory .........................................................................................................5
1.2
LonMark Certification ....................................................................................................................................5
2
Bacnet/LonWorks Setup through Protocessor Gateway RER/LER .................................................................. 6
2.1
Installation steps for the customer................................................................................................................6
2.2
Record Identification Data .............................................................................................................................6
2.3
Configure the DIP Switches ...........................................................................................................................6
2.3.1 Setting the Node/ID Device Instance (DIP Switch A0 – A7) for BACnet MS/TP, BACnet/IP, & Metasys N2 ..... 6
2.3.2 Setting the Serial Baud Rate (DIP Switch B0 – B3) for BACnet MS/TP & Metasys N2 ..............................7
2.3.2.1
Baud Rate DIP Switch Selection ......................................................................................................7
2.3.3 Using S0 – S3 bank of DIP Switches to select and load Configuration Files .............................................7
2.3.3.1
S0 – S3 DIP Switch Configuration Settings ......................................................................................7
A.
BACnet MS/TP, BACnet/IP and N2 for the Mascot II, NeoTherm, and NeoTherm LC .......7
B.
LonWorks for the Mascot II, NeoTherm, and NeoTherm LC ...................................................8
3
Interfacing the Gateway to Mascot II, NeoTherm, and NeoTherm LC ............................................................. 9
3.1
Gateway RER and LER showing connection ports .........................................................................................9
3.2
Wiring Connections to Gateway RER and LER .............................................................................................10
3.2.1 Sola wiring to the Gateway using Display..............................................................................................10
3.3
Wiring the Gateway RER to RS-485 BACnet MS/TP or Metasys N2 Field Protocol .....................................11
3.4
Wiring the Gateway LER Field Port to a LonWorks network .......................................................................12
3.5
Power-Up the Gateway RER or LER .............................................................................................................12
3.6
Commissioning the Gateway-LER on a LonWorks network .........................................................................12
4
Connect to Gateway’s Web GUI to Setup ip Address for BACnet/IP and modbus TCP .................................. 13
4.1
Connect the PC to the Gateway via the Ethernet port ................................................................................13
4.2
Use the Gateway Web GUI to Connect to the Gateway ..............................................................................14
4.3
Set IP Address for BACnet/IP or Modbus TCP .............................................................................................14
Appendix A. Troubleshooting Tips if the Unit is Not Working .............................................................................. 16
Appendix A.1. Check Wiring and Settings ................................................................................................................16
Appendix A.2. Take Log With Our FieldServer Utilities............................................................................................16
Appendix A.3. Instructions to upload XIF file from the Gateway LER using RUINET .............................................19
Appendix A.4. LED Diagnostics for Modbus RTU Communications between the Gateway and the LAARS Boilers
.................................................................................................................................................................................20
A.3.1 Gateway RER LEDs .....................................................................................................................................20
A.3.2 Gateway LER Main Board LEDs .................................................................................................................21
Appendix B. Vendor Information ......................................................................................................................... 22
Appendix B.1. Default Modbus COM Settings for Mascot II, NeoTherm, and NeoTherm LC ..................................22
Appendix B.2. Gateway RER: DIP switch settings for Mascot II BACnet MSTP/IP or Mascot II, NeoTherm, and
NeoTherm LC to support 1 through 8 boilers to Modbus TCP ................................................................................22
Appendix B.3. Mascot II, NeoTherm, and NeoTherm LC Modbus RTU Mappings to BACnet MS/TP, BACnet IP,
Metasys, and LonWorks .........................................................................................................................................23
Appendix C. Reference......................................................................................................................................... 25
Appendix C.1. Specifications ....................................................................................................................................25
Appendix C.1.1. Compliance with UL Regulations ............................................................................................25
Appendix C.2. Address DIP Switch Settings .............................................................................................................26
Appendix D. Limited 2 year Warranty .................................................................................................................. 32
LIST OF FIGURES
Figure 1: A0 – A7 DIP Switches ......................................................................................................................................6
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 3
Page 4
LAARS Gateway Startup Guide
LAARS Heating Systems
Page 4 of 32
Figure 2: B0 – B3 DIP Switches ......................................................................................................................................7
Figure 3: S0 – S3 DIP Switches .......................................................................................................................................7
Figure 4: Gateway RER (left) and Gateway LER (right) ..................................................................................................9
Figure 5: Connection from Gateway to RS-485 Field Protocol –BACnet MS/TP or Metasys N2 .................................11
Figure 6: End-of-line termination on from Gateway to RS-485 Field Protocol – BACnet MS/TP or Metasys N2. .......11
Figure 7: Ethernet port location of Gateway ...............................................................................................................13
Figure 8: FST Web GUI screen .....................................................................................................................................14
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
1
Page 5 of 32
INTRODUCTION
The LAARS Gateway is an external, high performance Building Automation multi-protocol gateway that has been
1
preprogrammed for LAARS’ Mascot II, NeoTherm, and NeoTherm LC to support BACnet® MS/TP, BACnet/IP,
2
3
Metasys® N2 by JCI, Modbus TCP, and LonWorks® . Configurations for the various protocols are stored within the
Gateway and are selectable via DIP switches for fast and easy installation. It is not necessary to download any
configuration files to support the required applications.
This document provides the necessary information to facilitate installation of the Gateway.
1.1
BTL Mark – BACnet Testing Laboratory
The BTL Mark on the Gateway RER is a symbol that indicates that a product has
passed a series of rigorous tests conducted by an independent laboratory which
verifies that the product correctly implements the BACnet features claimed in the
listing. The mark is a symbol of a high-quality BACnet product. Go to
http://www.bacnetinternational.net/btl/ for more information about the BACnet
Testing Laboratory.
1.2
LonMark Certification
LonMark International is the recognized authority for certification, education, and
promotion of interoperability standards for the benefit of manufacturers, integrators
and end users. LonMark International has developed extensive product certification
standards and tests to provide the integrator and user with confidence that products
from multiple manufacturers utilizing LonMark devices work together
1
BACnet is a registered trademark of ASHRAE
Metasys is a registered trademark of Johnson Controls Inc.
3
LonMark is a registered trademark of LonMark International
4
LonWorks is a registered trademark of Echelon Corporation
2
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 5
Page 6
LAARS Gateway Startup Guide
2
LAARS Heating Systems
Page 6 of 32
BACNET/LONWORKS SETUP THROUGH PROTOCESSOR GATEWAY RER/LER
2.1
Installation steps for the customer
1.
Record the information about the unit. (See Section 2.2)
2.
Configure each Mascot II, NeoTherm, and NeoTherm LC Modbus node address for each LAARS controller
connected to the Gateway. The first node must start at 1 and go up to 8; if you have a total of 8 LAARS
boilers controls connected to the Gateway. (See Appendix B.1 Note that NeoTherm LC units each have
two controllers.)
3.
Set device addressing: MAC Address and Device Instance/Node-ID for BACnet MS/TP, BACnet/IP, Metasys
N2, and Modbus TCP. (See section 2.3)
4.
Connect the Gateway to the Field protocol port and Honeywell’s Display (RS-485 gateway port) to the
Gateway’s RS-485 interface. (See Section 3)
5.
Power up the Gateway RER and LER.
6.
If the Controls Contractor requires LonWorks Fserver.xif file for the Gateway LER, see Appendix A.3 to
generate the file.
7.
If the Field protocol is BACnet/IP or Modbus TCP, refer to Section 4 to run the Gateway web GUI to
change IP address or the RUINET utility program to change the IP address (Section 4).
2.2
Record Identification Data
Each Gateway has a unique part number located on the underside of the unit. The numbers are as follows:


FieldServer # FPC-N34-103-122-0701 Modbus RTU to BACnet MSTP, BACnet IP, N2, Modbus TCP,
RER, Metasys N2 by JCI.
FieldServer # FPC-N35-103-401-0702 Modbus RTU to LonWorks, LER.
This number should be recorded, as it may be required for technical support.
2.3
Configure the DIP Switches
2.3.1 Setting the Node/ID Device Instance (DIP Switch A0 – A7) for BACnet MS/TP,
BACnet/IP, & Metasys N2

The A Bank DIP switches on the Gateway RER allow users to set the Node-ID/Device Instance on the Field
RS-485.

DIP switches A0 – A7 can also be used to set the MAC Address for BACnet MS/TP and BACnet/IP.
Figure 1: A0 – A7 DIP Switches

Please refer to Appendix C.2 for the full range of addresses to set Node-ID/Device Instance.
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
Page 7 of 32
NOTE: When setting DIP Switches, please ensure that power to the board is OFF.
2.3.2 Setting the Serial Baud Rate (DIP Switch B0 – B3) for BACnet MS/TP & Metasys N2

DIP Switches B0 – B3 can be used to set the serial baud rate to match the baud rate provided by the
Building Management System for BACnet MS/TP.

Metasys N2 is always defaulted to 9600 baud and the B bank is disabled.
B0 B1 B2 B3
Figure 2: B0 – B3 DIP Switches
2.3.2.1
Baud
9600
19200
38400
57600
76800
Baud Rate DIP Switch Selection
B0 B1 B2 B3
On
Off
On
Off
On
On
Off
On
Off
Off
On
Off
Off
On
On
Off
On
On
On
On
2.3.3 Using S0 – S3 bank of DIP Switches to select and load Configuration Files

The S bank of DIP switches, S0 - S3 is used to select and load a configuration file from a group of
pretested/preloaded configuration files which are stored in the Gateway RER (BACnet MS/TP, BACnet/IP
and Metasys N2) and LER (LonWorks).
S0 S1 S2 S3
Figure 3: S0 – S3 DIP Switches
2.3.3.1
S0 – S3 DIP Switch Configuration Settings
H2355100A
S Bank DIP Switches
A.
BACnet MS/TP, BACnet/IP and N2 for the Mascot II, NeoTherm, and NeoTherm LC
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 7
Page 8
LAARS Heating Systems
Page 8 of 32
LAARS Gateway Startup Guide
The Following chart describes S0 – S3 DIP Switch configuration settings for the Mascot II, NeoTherm, and
NeoTherm LC boilers – 1 through 8 units to support BACnet MSTP/IP and Metasys N2 on a Gateway RER. The
Mascot II, NeoTherm, and NeoTherm LC boilers all use the same configuration points list.
Gateway RER
Profile – FPC-N34
BACnet IP/BACnet MSTP Sola 1
BACnet IP/BACnet MSTP Sola 2
BACnet IP/BACnet MSTP Sola 3
BACnet IP/BACnet MSTP Sola 4
BACnet IP/BACnet MSTP Sola 5
BACnet IP/BACnet MSTP Sola 6
BACnet IP/BACnet MSTP Sola 7
BACnet IP/BACnet MSTP Sola 8
Metasys N2 Sola 1
Metasys N2 Sola 2
Metasys N2 Sola 3
Metasys N2 Sola 4
Metasys N2 Sola 5
Metasys N2 Sola 6
Metasys N2 Sola 7
Metasys N2 Sola 8
Gateway S Bank DIP Switches
S0
S1
S2
Off
Off
Off
On
Off
Off
Off
On
Off
On
On
Off
Off
Off
On
On
Off
On
Off
On
On
On
On
On
Off
Off
Off
On
Off
Off
Off
On
Off
On
On
Off
Off
Off
On
On
Off
On
Off
On
On
On
On
On
S3
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
See Appendix B.2 for additional configuration DIP switch settings:

B.
For the Mascot II, NeoTherm, and NeoTherm LC boilers to support Modbus TCP on the Gateway RER
LonWorks for the Mascot II, NeoTherm, and NeoTherm LC
The following chart describes S0 – S3 DIP Switch configuration settings for Mascot II, NeoTherm, and NeoTherm LC
boilers to support LonWorks on a Gateway LER. The Mascot II, NeoTherm, and NeoTherm LC units all use the same
configuration points list.
Gateway LER
Profile - FPC-N35
LonWorks Sola 1
LonWorks Sola 2
LonWorks Sola 3
LonWorks Sola 4
LonWorks Sola 5
LonWorks Sola 6
LonWorks Sola 7
LonWorks Sola 8
Gateway S Bank DIP Switches
S0
S1
S2
Off
Off
Off
On
Off
Off
Off
On
Off
On
On
Off
Off
Off
On
On
Off
On
Off
On
On
On
On
On
S3
Off
Off
Off
Off
Off
Off
Off
Off
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
LAARS Gateway Startup Guide
3
3.1
Page 9 of 32
Page 9 of 32
Page 9
3 INTERFACING THE GATEWAY TO MASCOT II, NEOTHERM, AND NEOTHERM LC BOILERS
INTERFACING THE GATEWAY TO MASCOT II, NEOTHERM, AND NEOTHERM LC BOILERS
3.1 Gateway RER and LER showing connection ports
Gateway RER and LER showing connection ports
RS-485 Port for BACnet
RS-485 Port
for BACnet
MS/TP,
and N2
MS/TP, and N2
LonWorks Port
LonWorks Port
LonWork Service Pin
LonWork Service Pin
H2355100A
H2355100A
10/100
10/100
BaseT for
BaseTIPfor
BACnet
and Modbus TCP
BACnet IP and Modbus TCP
Power +/- and FG 9-30
RS-485 Port for
Power
+/- and FG
9-30
Power
+/and
FG
9-30
VDC
VDC
RS-485 Port for connection
RS-485
Port for to the
connection
Power
+/and
FG
9-30
VDC
VDC
12-24 VAC
12-24 VAC
RS-485 to
Port
connection
thefor
Mascot
II, NT 80 –
connection
toNT
the80 – 850,
Mascot II,
12-24
VAC
12-24
VAC
totothe
II,
NeoTherm,
theMascot
Mascot
II,
NT
80
–
850, and NT 1000 boilers
Mascot
II, NT
801000
– 850,
Mascot
II,NT
NeoTherm,
and
boilers
and
LCboilers
850,NeoTherm
and NT 1000
andNT
NeoTherm
LC
and
1000 boilers
Figure 4: Gateway RER (left) and Gateway LER (right)
Figure 4: Gateway RER (left) and Gateway LER (right)
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
LAARS Heating Systems
Company,
20 Industrial
Way,
Rochester,
NH 03867 USA
Web:
www.laars.com
Toll
Free:
(800) 900-9276
Web: www.laars.com Toll Free: (800) 900-9276
Page 10
LAARS Gateway Startup Guide
3.2
LAARS Heating Systems
Page 10 of 32
Wiring Connections to Gateway RER and LER
Gateway 6 Pin Phoenix connector – Pinouts
3.2.1 Sola wiring to the Gateway using Display



On the System Operator Display, connect terminal Y4 (RS-485+) to Pin 1 - RS 485+ on the Gateway’s 6 pin
Phoenix connector.
Connect terminal Y5 (RS-485) to Pin 2 - RS 485- on the Gateway’s 6 pin on the Gateway’s Phoenix
connector.
Y6 (Ground) does not need to be grounded to the Gateway.
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
3.3
Page 11 of 32
Page 11
Wiring the Gateway RER to RS-485 BACnet MS/TP or Metasys N2 Field Protocol
Connection from Gateway RER to BACnet MS/TP and Metasys N2 networks

The Field Protocol can be connected to the 3-pin connector on Gateway RER as shown:
H2355100A

Figure 5: Connection from Gateway to RS-485 Field Protocol –BACnet MS/TP or Metasys N2

See Section Error! Reference source not found. for information on connecting the Gateway RER to
ACnet/IP of Modbus TCP network.

If the Gateway is the last device on the BACnet MS/TP or Metasys N2 RS-485 trunk, then the End-of-line
termination needs to be enabled. The default is off.
End-of-Line Switch
Figure 6: End-of-line termination on from Gateway to RS-485 Field Protocol – BACnet MS/TP or Metasys N2.
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 12
LAARS Gateway Startup Guide
3.4
Wiring the Gateway LER Field Port to a LonWorks network

3.5
LAARS Heating Systems
Page 12 of 32
Connect the Gateway to the field network with the LonWorks terminal using a twisted pair non-shielded
cable. LonWorks has no polarity.
Power-Up the Gateway RER or LER
Apply power to the device. Ensure that the power supply used complies with the specifications provided in
Appendix C.1. Ensure that the cable is grounded using the “Frame-GND” terminal. The Gateway is factory set for
9-30VDC or 12-24 VAC.
Voltage Pinouts
3.6
Commissioning the Gateway-LER on a LonWorks network
Commissioning may only be performed by the LonWorks administrator.
To commission the Gateway LER LonWorks port, insert a small screwdriver in the commissioning hole on the face
of the LER’s enclosure to access the Service Pin. See the illustration on the Gateway LER as to which way to toggle
the screw driver during commissioning.
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
4
4.1
Page 13 of 32
Page 13
CONNECT TO GATEWAY’S WEB GUI TO SETUP IP ADDRESS FOR BACNET/IP AND
MODBUS TCP

Download the RUINET Utilities from the ProtoCessor web site (under Utilities section – Install.zip)
www.protocessor.com/tech_support/Design_Documents

Run Install.zip and follow the installation instructions

Once installed, the FieldServer Utilities can be located in the Windows Start menu as a desktop icon
Connect the PC to the Gateway via the Ethernet port
Ethernet Port
Figure 7: Ethernet port location of Gateway

Connect a standard CAT5 Ethernet cable (straight through or cross) between the PC and Gateway

The Default IP Address of the Gateway is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and the
Gateway are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network

Go to

Right-click on Local Area Connection > Properties

Highlight

Select: Use the following IP address

Click
>
>
>
twice
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 14
LAARS Gateway Startup Guide
4.2
LAARS Heating Systems
Page 14 of 32
Use the Gateway Web GUI to Connect to the Gateway

Open PC web browser and enter the default IP address of the Gateway 192.168.1.24 to determine if the
Gateway is up and communicating.
Figure 8: FST Web GUI screen
4.3
Set IP Address for BACnet/IP or Modbus TCP

Open a PC web browser, enter the default IP address of the Gateway 192.168.1.24 and connect to the
Gateway.

From the GUI main home page, click on setup and then Network Settings to enter the Edit IP Address
Settings menu.

Modify the IP address (N1 IP address field) of the Gateway Ethernet port.

Type in a new IP address in the format xxx.xxx.xxx.xxx

If necessary, change the Netmask (N1 Netmask field).

Type in a new Subnet Mask

If necessary, change the IP Gateway (Default Gateway field)

Type in a new IP Gateway

Note: If the Gateway is connected to a router, the IP Gateway of the Gateway should be set to the IP
address of the router that it is connected to

Click on Update IP Settings button. This will save IP address and reset the Gateway.

Unplug Ethernet cable from PC and connect it to the network hub or router
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
Page 15 of 32
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 15
Page 16
LAARS Heating Systems
Page 16 of 32
LAARS Gateway Startup Guide
Appendix A. Troubleshooting Tips if the Unit is Not Working
Appendix A.1. Check Wiring and Settings


No COMS on Modbus RTU side. If TX/RX is not flashing rapidly then there is a COM issue on the Modbus
side and you need to check the following things:
o Visual observations of LEDs on Gateway. See Appendix A.3
o Check baud rate, parity, data bits, stop bits
o Check Modbus device address
o Verify wiring
Field COM problems.
o Visual observations of LEDs on Gateway. See Appendix A.3
o Visual dipswitch settings (using correct baud rate and device instance)
o Verify IP address setting
o Verify wiring
If the problem still exists, a log needs to be taken and sent to FieldServer.
Appendix A.2. Take Log With Our FieldServer Utilities

Once the log is complete, email it to support@protocessor.com. The log will allow us to rapidly diagnose
the problem.

Make sure the FieldServer utilities are loaded on the PC.
http://fieldserver.com/techsupport/utility/utility.php
Ethernet Port

Disable any wireless Ethernet adapters on the PC/Laptop

Disable firewall and virus protection software

Connect a standard cat5 Ethernet cable between the PC and

The Default IP Address of the Gateway is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and the
Gateway are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network
For Windows XP:

Go to
>
>
Right-click on Local Area Connection > Properties
Highlight
>
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide

Page 17 of 32
For Windows 7:
Go to
>
>
>
>
Right-click on Local Area Connection > Properties
Highlight
>

For Windows XP and Windows 7, select: Use the following IP address

Click

Double click on the FST Diag Utility.

Step 1: Select an IP Address.

The IP address can be entered manually or selected by clicking on button 1 using the Utility.
twice
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 17
Page 18
LAARS Heating Systems
LAARS Gateway Startup Guide
Page 18 of 32
Type in the Gateway
GatewayIP address
Default IP Address is 192.168.1.24
Press here to retrieve the IP address.
Locate where the log is saved on the PC
Select a log type.
Press the Take Log button.

Step 2: Take a Log

Press the Take Log button. While the Utility runs a few DOS prompts will flash across the monitor. Don't
click or type anything in to these DOS prompts. This step may take a few minutes depending on the
chosen Log Type and computer speed. When the Utility is finished you will be presented with a log of
events that have occurred.

Step 3: Send Log

Click the “Send Log” button located near the bottom of the dialog. The following dialog should appear.

Push the ‘Locate Folder’ button to launch explorer and have it point directly at the correct folder. The file
upload.zip must be sent to support@fieldserver.com.
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide

Step 4: Close the Program

Press the exit button when the log is completed
Page 19 of 32
Page 19
Appendix A.3. Instructions to upload XIF file from the Gateway LER using RUINET

Make sure the utilities are loaded on the PC.
http://fieldserver.com/techsupport/utility/utility.php
Ethernet Port

Disable any wireless Ethernet adapters on the PC/Laptop

Disable firewall and virus protection software

Connect a standard cat5 Ethernet cable between the PC and

The Default IP Address of the Gateway is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and the
Gateway are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network
For Windows XP:

Go to
>
>
Right-click on Local Area Connection > Properties
Highlight

>
For Windows 7:
Go to
>
>
>
>
Right-click on Local Area Connection > Properties
Highlight
>
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 20
LAARS Gateway Startup Guide
LAARS Heating Systems
Page 20 of 32

For Windows XP and Windows 7, select: Use the following IP address

Click

In the main menu of Remote User Interface, type 'u' for upload.

Type 'o' for other.

Type 'r' for remote.

Enter 'fserver.xif' and hit the 'enter' key.

Type 'u' to upload the file

If you are running RUINET through the ruinet.exe, the xif file will be saved in the same directory as the
RUINET executable.

If you are running RUINET through the Remote User Interface icon on the desktop, the xif file will be
saved in: Start -> All Programs -> FieldServer Utilities -> Config File Folder
twice
Appendix A.4. LED Diagnostics for Modbus RTU Communications between the Gateway and the LAARS
Boilers
Please see the diagram below for LED Locations
A.3.1 Gateway RER LEDs
Light
RTC
RUN
ERR
Description
Unused
The RUN LED will start flashing 20 seconds after power up, indicating normal operation.
The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red
light will indicate there is a system error on the Gateway LER. If this occurs, immediately report the
related “system error” shown in the error screen of the RUI interface to FieldServer Technologies for
evaluation.
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
Light
RX
TX
PWR
Page 21 of 32
Page 21
Description
The RX LED will flash when a message is received on the socket port.
The TX LED will flash when a message is sent on the socket port.
This is the power light and should show steady green at all times when the Gateway LER is powered.
A.3.2 Gateway LER Main Board LEDs
Note: The lid on top of the Gateway has to be removed in order to see the LED’s. Pull on the lid while
holding on to the 6 pin Phoenix connector. Please do not hold the wall mount tabs as these are designed to
break off if not required!
RTC
RUN
ERR
RX
TX
.PWR
Light
RTC
RUN
ERR
RX
TX
PWR
Description
Unused
The RUN LED will start flashing 20 seconds after power up, indicating normal operation.
The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red
light will indicate there is a system error on the Gateway LER. If this occurs, immediately report the
related “system error” shown in the error screen of the RUI interface to FieldServer Technologies for
evaluation.
The RX LED will flash when a message is received on the socket port.
The TX LED will flash when a message is sent on the socket port.
This is the power light and should show steady green at all times when the Gateway LER is powered.
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 22
LAARS Heating Systems
LAARS Gateway Startup Guide
Page 22 of 32
Appendix B. Vendor Information
Appendix B.1. Default Modbus COM Settings for Mascot II, NeoTherm, and NeoTherm LC
Serial Port Setting
Mascot II
NeoTherm
NeoTherm LC
Baud Rate
38.4
38.4
38.4
Data Bits
8
8
8
Stop Bits
1
1
1
None
None
None
1 through 8
1 through 8
1 through 8
Parity
Modbus RTU Node_ID: 1 through 8 Boilers
Appendix B.2. Gateway RER: DIP switch settings for Mascot II BACnet MSTP/IP or Mascot II, NeoTherm,
and NeoTherm LC to support 1 through 8 boilers to Modbus TCP
Note: The lid on top of the Gateway has to be removed in order to select the A Bank of DIP switches. Pull on
the lid while holding on to the 6 pin Phoenix connector. Please do not hold the wall mount tabs as these are
designed to break off if not required!

To set select these configurations, open the Gateway and select the A bank of switches (A1 or A2 or A3)
on the small ProtoCessor module that sits on top of the ProtoCarrier (inside the Gateway).
A1, A2, A3 DIP Switches
S Bank DIP Switches
Gateway RER
Profile – FPC-N34
Modbus TCP Sola 1
Modbus TCP Sola 2
Modbus TCP Sola 3
Modbus TCP Sola 4
Modbus TCP Sola 5
Modbus TCP Sola 6
Modbus TCP Sola 7
Modbus TCP Sola 8
Gateway S Bank DIP Switches
S0
S1
S2
S3
Off
Off
Off
Off
On
Off
Off
Off
Off
On
Off
Off
On
On
Off
Off
Off
Off
On
Off
On
Off
On
Off
Off
On
On
Off
On
On
On
Off
ProtoCessor A Bank DIP Switches
A1 A2 A3 A4 A5 A6
On Off Off Off Off Off
On Off Off Off Off Off
On Off Off Off Off Off
On Off Off Off Off Off
On Off Off Off Off Off
On Off Off Off Off Off
On Off Off Off Off Off
On Off Off Off Off Off
A7
Off
Off
Off
Off
Off
Off
Off
Off
A8
Off
Off
Off
Off
Off
Off
Off
Off
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
Page 23
Page 23 of 32
Appendix B.3. Mascot II, NeoTherm and NeoTherm LC Modbus RTU Mappings to BACnet MS/TP,
BACnet IP, Metasys, and LonWorks
Point Name
Demand source
Outlet sensor
Firing rate
Fan speed
Flame signal
Inlet sensor
DHW sensor
S5 sensor
Stack sensor
4 - 20 mA remote ctl
input
Active CH setpoint
Active DHW setpoint
Active LL setpoint
Analog modulation
input
Burner control status
Lockout code
Alarm reason
Hold code
CH status
CH setpoint source
CH heat demand
CH burner demand
CH requested rate
DHW status
DHW Priority Count
BACnet
Object
Id
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
Instnace
1
2
3
4
5
6
7
8
9
Metasys N2
Data Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
Metasys
Point
Address
1
2
3
4
5
6
7
8
9
Lon Name
nvoXDemSrc
nvoXOutletSensor
nvoXFiringRate
nvoXFanSpeed
nvoXFlameSignal
nvoXInletSensor
nvoXDHWSensor
nvoXS5Sensor
nvoXStackSensor
Lon SNVT Type
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
AI
AI
AI
AI
10
11
12
13
AI
AI
AI
AI
10
11
12
13
nvoXRemCtlInput
nvoXAct_CH_SP
nvoXAct_DHW_SP
nvoXAct_LL_SP
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
14
15
16
17
18
19
20
21
22
23
24
25
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
14
15
16
17
18
19
20
21
22
23
24
25
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
DHW heat demand
DHW burner demand
DHW requested rate
DHW pump status
DHW Pump Idle Days
Count
System pump status
System Pump Idle
Days Count
Boiler pump status
Boiler Pump Idle
Days Count
AI
AI
AI
AI
26
27
28
29
AI
AI
AI
AI
26
27
28
29
nvoXAnaModInput
nvoXBrnrCtlStat
nvoXLockoutCode
nvoXAlmReason
nvoXHoldCode
nvoXCH_Status
nvoXCH_SP_Src
nvoXCH_HeatDmnd
nvoXCH_BrnrDmnd
nvoXCH_ReqRate
nvoXDHW_Status
nvoXDHW_PriCnt
nvoXDHW_HeatDmn
d
nvoXDHW_BrnrDmnd
nvoXDHW_ReqRate
nvoXDHW_PmpStat
AI
AI
30
31
AI
AI
30
31
nvoXDHW_PpIdDyCt
nvoXSysPmpStatus
SNVT_count_inc_f
SNVT_count_inc_f
AI
AI
32
33
AI
AI
32
33
nvoXSysPmpIdDyCt
nvoXBlrPmpStatus
SNVT_count_inc_f
SNVT_count_inc_f
AI
34
AI
34
SNVT_count_inc_f
Burner run time
DHW pump cycle
count
System pump cycle
count
Boiler pump cycle
AV
35
AO
35
AV
36
AO
36
AV
AV
37
38
AO
AO
37
38
nvoXBlrPmpIdDyCt
nviX/nvoXBrnrRunTi
me
nviX/nvoXDHWPmpC
ycCnt
nviX/nvoXSysPmpCyc
Cnt
nviX/nvoXBlrPmpCyc
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
LAARS Heating Systems
Page 24
LAARS Gateway Startup Guide
count
Controller Cycle
Count
Controller run time
Lead lag master
status
Lead lag slave status
Lead Lag Master
Setpoint Source
Lead Lag Master
Pump Demand
Outdoor
temperature
CH setpoint
Page 24 of 32
Cnt
AI
AI
39
40
AI
AI
39
40
nvoXCtllerCycCnt
nvoXCtllerRunTim
SNVT_count_inc_f
SNVT_count_inc_f
AI
AI
41
42
AI
AI
41
42
nvoXLdLgMstrStat
nvoXLdLgSlavStat
SNVT_count_inc_f
SNVT_count_inc_f
AI
43
AI
43
nvoXLdLgMstSPSrc
SNVT_count_inc_f
AI
44
AI
44
nvoXLdLgMstPpDmd
SNVT_count_inc_f
AI
AV
45
46
AI
AO
45
46
SNVT_count_inc_f
SNVT_count_inc_f
CH TOD setpoint
AV
47
AO
47
DHW Demand Switch
Outlet high limit
setpoint
Lead Lag setpoint
Leadlag modulation
sensor
Warm weather
shutdown setpoint
Lead Lag active
service
Slave 1 State
Slave 1 firing rate
Slave 2 State
Slave 2 firing rate
Slave 3 State
Slave 3 firing rate
Slave 4 State
Slave 4 firing rate
Slave 5 State
Slave 5 firing rate
Slave 6 State
Slave 6 firing rate
Slave 7 State
Slave 7 firing rate
Slave 8 State
Slave 8 firing rate
Master firing rate
AV
48
AO
48
AV
AV
49
50
AO
AO
49
50
AV
51
AO
51
AV
52
AO
52
nvoXOutdoorTmp
nviX/nvoXCH_SP
nviX/nvoXCH_TOD_S
P
nviX/nvoXDHW_Dmd
Switc
nviX/nvoXOutltHiLim
SP
nviX/nvoXLeadLagSP
nviX/nvoXLdLgModSe
nsr
nviX/nvoXWrmWthrS
htSP
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
nvoXLdLgActSrvc
nvoXSlv1State
nvoXSlv1FirRat
nvoXSlv2State
nvoXSlv2FirRat
nvoXSlv3State
nvoXSlv3FirRat
nvoXSlv4State
nvoXSlv4FirRat
nvoXSlv5State
nvoXSlv5FirRat
nvoXSlv6State
nvoXSlv6FirRat
nvoXSlv7State
nvoXSlv7FirRat
nvoXSlv8State
nvoXSlv8FirRat
nvoXMstrFirRat
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
Page 25 of 32
Appendix C. Reference
Appendix C.1. Specifications
Electrical
Connections
Approvals
Gateway RER
Gateway LER
One 6-pin Phoenix connector, one RS-485 One 6-pin Phoenix connector, one RS-485
+/- ground port, power +/- frame ground +/- ground port, power +/- frame ground
port
port
One 3-pin RS-485 Phoenix connector, one One Ethernet 10/100 BaseT port
RS-485 +/- ground port
One FTT-10 LonWorks port
One Ethernet-10/100 Ethernet port
CE (EN55022;EN55024; EN60950), UL916, FCC Class A Part 15, DNP3 Conformance Tested,
OPC Self-tested for Compliance, RoHS Compliant, CSA 205 Approved
BTL Marked
LonMark Certified
Power
Multi-mode power adapter: 9-30VDC or 12 - 24VAC
Requirements
Physical
11.5 cm L x 8.2 cm W x 4.0 cm H (4.5 x 3.2 x 1.6 in.)
Dimensions
0.2 kg (0.4 lbs)
Weight
Operating
-40°C to 75°C (-40°F to167°F)
Temperature
Surge
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Suppression
5 - 90% RH (non-condensing)
Humidity
(Specifications subject to change without notice)
Appendix C.1.1.
Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating the Gateway.

The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating
temperature range.

The interconnecting power connector and power cable shall:
 Comply with local electrical code
 Be suited to the expected operating temperature range
 Meet the current and voltage rating for the Gateway/Net

Furthermore, the interconnecting power cable shall:
 Be of length not exceeding 3.05m (118.3”)
 Be constructed of materials rated VW-1 or FT-1 or better

If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be
installed in a Restricted Access Area requiring a key or a special tool to gain access.

This device must not be connected to a LAN segment with outdoor wiring.
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 25
LAARS Heating Systems
Page 26
LAARS Gateway Startup Guide
Page 26 of 32
Appendix C.2. Address DIP Switch Settings
A7
A6
A5
A4
A3
A2
A1
A0
Address
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
Page 27
LAARS Gateway Startup Guide
Page 27 of 32
A7
A6
A5
A4
A3
A2
A1
A0
Address
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
LAARS Heating Systems
Page 28
LAARS Gateway Startup Guide
Page 28 of 32
A7
A6
A5
A4
A3
A2
A1
A0
Address
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
Page 29 of 32
A7
A6
A5
A4
A3
A2
A1
A0
Address
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 29
LAARS Heating Systems
Page 30
LAARS Gateway Startup Guide
Page 30 of 32
A7
A6
A5
A4
A3
A2
A1
A0
Address
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
Page 31 of 32
A7
A6
A5
A4
A3
A2
A1
A0
Address
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
Page 31
Page 32 LAARS Gateway Startup Guide
Page 30
of 32
LAARS
Heating
Systems
A7
A6
A5
A4
A3
A2
A1
A0
Address
The LAARS Gateway RER and LER have identical mounting dimensions. The only key
On
Off
On
On
Off
Off
On
Off
178
difference is that the RER can connect to Bacnet, Modbus, and Metasys N2
On
Off
On
On
Off
Off
On
On
179
On
Off
On
On
Off LAARSOn
180
The
Gateway Off
LER has a Off
standard LonWorks
connection.
LAARS
On
Off Gateway
On Startup
On GuideOff
On
Off
On
181
On
Off
On
On
Off
On
On
Off
182
Gateway
RER
Gateway
LER
On
Off
On
On
Off
On
On
On
183
On
Off
On
On
On
Off
Off
Off
184
On
Off
On
On
On
Off
Off
On
185
On
Off
On
On
On
Off
On
Off
186
Top
standard LonWorks
On
Off
On
On
On
Off
On
On
187
On
Off
On
On
On
On
Off
Off
188
On
Off
On
On
On
On
Off
On
189
On
Off
On
On
On
On
On
Off
190
On
Off
On
On
On
On
On
On
191
On
On
Off
Off
Off
Off
Off
Off
192
On
On
Off
Off
Off
Off
Off
On
193
On
On
Off
Off
Off
Off
On
Off
194
On
On
Off
Off
Off
Off
On
On
195
On
On
Off
Off
Off
On
Off
Off
196
LAARSOff
Gateway
On LAARS
On Gateway
Off
Offand Gateway
Off TheOn
On RER and
197 Gateway LER.
The
RER
LER.
On customer
Off
Off
Off
On systems
Off product
198 automation systems
Startup
Guide
for On
customer
StartupOn
Guide for
product
automation
On
On
Off
Off
Off
On
On
On
199
that use the following
protocols:
that
use
the
following
protocols:
On
On
Off
Off
On
Off
Off
Off
200
BACnet
MSTP,
BACnet
IP,
Modbus TCP,
BACnetOffIP, Modbus
TCP,
OnBACnet
OnMSTP,Off
On
Off
Off
On
201
N2Offby JCI,Off
and LonWorks
On Metasys
On
On
OffMetasys
On N2 by
OffJCI, and
202LonWorks
On
On
Off
Off
On
Off
On
On
203
with:
to interface
On
On
Off
Offwith: On
On
Off to interface
Off
204
On
On
Off
On
On LAARS
Off Mascot
On II, NeoTherm,
205
LAARS
Mascot
II,OffNeoTherm,
On
On
Off
Off
On
On
On
Off
206
NeoTherm
LC
Boilers
and
Water Heaters.
NeoTherm
LC
Boilers
and
Water
Heaters.
LAARS Gateway
RER andOnGateway
On
On
Off The Off
On
On
On LER. 207
On
On
Off
On for customer
Off
Off
Off
208
Startup
Guide
productOffautomation
systems
APPLICABILITY
& EFFECTIVITY
On
On APPLICABILITY
Off
Off
Off
Off
On
209
& On
EFFECTIVITY
that use the following protocols:
On
On
Off
On
Off
Off
On
Off
210
BACnet
BACnet
IP,
Modbus
TCP,
theit.
Gateway
RER and
LER hardware and how to install it.
Explains the Gateway RER and LER
hardwareMSTP,
and howExplains
to install
On
On
Off
On
Off
Off
On
On
211
The
instructions
are effective for the above as of September 2012
The instructions are effective for theMetasys
above as of N2
September
2012
by
JCI,
and
LonWorks
On
On
Off
On
Off
On
Off
Off
212
On
On
Off
On
Off
On
Off
On
213
to interface
with:
On
On
Off
On
Off
On
On
Off
214
On
On
Off
On LAARS
Off Mascot
On II, NeoTherm,
On
On
215
On
On
Off
On
On
Off and Water
Off
Off
216
NeoTherm
LC Boilers
Heaters.
Side
Side
Back
On
On
Off
On
On
Off
Off
On
217
On
On
Off
On
On
Off
On
Off
218
APPLICABILITY & EFFECTIVITY
On
On
Off
On
On
Off
On
On
219
Bottom
On
On
Off Explains
Onthe Gateway
On RER andOn
Offand how Off
LER hardware
to install it. 220
On
On
Off The instructions
On
Oneffective for
Onthe aboveOff
On 2012 221
are
as of September
On
On
Off
On
On
On
On
Off
222
H2355100A
H2355100A
H2355100A
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276
The LAARS Gateway LER and RER Startup Guide
LAARS Gateway Startup Guide
Page 33
Page 32 of 32
Appendix D. Limited 2 year Warranty
Gateway Supplier warrants its products to be free from defects in workmanship or material under
normal use and service for two years after date of shipment. Gateway Supplier will repair or replace any
equipment found to be defective during the warranty period. Final determination of the nature and
responsibility for defective or damaged equipment will be made by Gateway Supplier personnel.
All warranties hereunder are contingent upon proper use in the application for which the product was
intended and do not cover products which have been modified or repaired without Gateway Supplier
approval or which have been subjected to accident, improper maintenance, installation or application,
or on which original identification marks have been removed or altered. This Limited Warranty also will
not apply to interconnecting cables or wires, consumables or to any damage resulting from battery
leakage.
In all cases Gateway Supplier responsibility and liability under this warranty shall be limited to the cost
of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item
under this warranty provision and compliance with such instruction shall be a condition of this warranty.
H2354400B
Except for the express warranty stated above, Gateway Supplier disclaims all warranties with regard to
the products sold hereunder including all implied warranties of merchantability and fitness and the
express warranties stated herein are in lieu of all obligations or liabilities on the part of Gateway
Supplier for damages including, but not limited to, consequential damages arising out of/or in
connection with the use or performance of the product.
800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com Printed in U.S.A. © Laars Heating Systems 1208 Document 4236B
LAARS Heating Systems Company, 20 Industrial Way, Rochester, NH 03867 USA
Web: www.laars.com Toll Free: (800) 900-9276