DB1000 SERIES DIGITAL INDICATING CONTROLLER

DB1000 SERIES DIGITAL INDICATING CONTROLLER
DB1000 SERIES DIGITAL
INDICATING CONTROLLER
The DB1000 series controllers are 96 × 96mm digital
controllers with the indicating accuracy of ± 0.1%
and the sampling period of 0.1 second.
These controllers have a variety of features including
multi-programming function (8 kinds), universal
inputs scaling function as well as easy-to-read
colored LCD displays and the interactive type
settings with the dot-matrix LCD display.
¢ FEATURES
• Indicating accuracy; ± 0.1%; Sampling period: 0.1 second
The high-performance microprocessor provides the indicating
accuracy of ± 0.1% and the sampling period of 0.1 second.
• Easy simple-mode operation
By separating the parameters at the settings up through switching between
the simple function mode and multi-function mode, the normal running
is simplified.
• 8 kinds of setpoint
By using the front -panel keys, 8 kinds of setpoint being programmed are freely
selectable and independent PID parameters can be set each setting value.
• Universal inputs
Two types of universal inputs, the total of 34 inputs including 28
thermocouple inputs, 5 DC voltage inputs and 1 DC current input, or 12 resistance
thermometer inputs, are prepared.
• Auto-tuning function
The optimum PID parameters can be calculated automatically by the auto tuning function.
• Versatile alarm function
Four alarm points are available on each setpoint. High/low alarm and
deviation/absolute alarm can be set independently on each alarm point.
• Universal power voltage
The controllers are designed for 85 to 264VAC.
• CE-marking (Option)
The models with CE-marking are available as an option.
1
PSE-283
¢ MODEL CODES
DB1 ooooooo
¢ MEASURING RANGE
Input
Input signal
Input range
B
R
1 : Thermocouples, DC voltage/current
2 : Resistance thermometers
S
K
Control mode (Output 1)
1 : On -off pulse type PID
2 : On -off servo type PID (standard)
3 : Current output type PID
E
5 : SSR drive pulse type PID
6 : Voltage Output type PID (option)
8 : On -off servo type PID (Light load)
(option)
0 to 1820°C
0 to 1760°C
0 to 1200°C
0 to 1760°C
-200 to 1 370°C
0 to 600.0 °C
-200.0 to 300.0°C
-270 to 1000°C
32 to 3300°F
32 to 3200°F
32 to 2100°F
32 to 3200°F
-300 to 2450°F
32 to 1100°F
-300 to 550°F
-450 to 1800°F
0 to 700.0°C
-270 to 300°C
32 to 1250°F
450 to 550°F
-270 to 150°C
J
Control mode (Output 2) (optIon)
1 type
1 : On-off pulse type P*1
3 : Current output type P * 2
5 : SSR drive pulse type P * 1
6 : Voltage Output type P *2
M: MOS relay output(Alarm3,4 )* 3
Thermocouple
0 : None
CE-marking
- : None
E : With CE -marking
T
WWRe5-26
450 to 300°F
-200 to 1200°C
-300 to 2100°F
-200.0 to 900. 0°C
-200.0 to 400.0°C
-300 to 1650°F
-300 to 700°F
-100.0 to 200.0°C
-400 to 300°F
-270 to 400°C
-200.0 to 200.0°C
-450 to 700°F
-300 to 300°F
0 to 2320°C
32 to 4200°F
WWRe 0-26
0 to 2320°C
32 to 4200°F
Ni-NiMo
0 to 1310°C
32 to 2350°F
AuFe -Cr
0 to 300.0K
400 to 80°F
32 to 2350°F
Communications interface (option)
N
0 to 1300°C
0 : None
R: RS-232C
PRS-20
0 to 1800°C
32 to 3250°F
A: RS-422A
PR2 0-40
0 to 1880°C
32 to 3400°F
Platinel
-100 to 1390°C
-100 to 2500°F
-100.0 to 600.0°C
400 to 1100°F
U
-200.0 to 400. 0°C
-300 to 750°F
L
-200.0 to 900.0°C
-300 to 1650°F
S : RS-485
.
B: External set value switching input* 4
Transmission signal output (option)
0: None
1: 4 to 2 0mA
DC voltage/ current
Pt 100
2: 0 to 1V
3: 0 to 1 0V
-200.0 to 649. 0°C
,
4: Others
Pt 100
Remote setting for SV (option)
2 type
6: 0 to 1V
7: 0 to 10 V
8: Ot hers
B: External set value switching input* 4
* 1 Applicable when Output 1 is the
current output type PID system or
voltage output type PID system. CE marking is not available.
* 2 Applicable when Output 1 is the on-off
servo type PID system. CE -marking
is not available.
* 3 Applicable except the on-off servo type
PID system (with CE -marking)
* 4 The external set value switching input
can be designated at any place.
2
Resistance Thermometer
B: External set value switching input* 4
0: None
5: 4 to 2 0mA
-10 to 10mV, -20 to 2 0mV, -50 to 5 0mV
-100 to 100 mV, -5 to 5V, -20 to 2 0mA
JPt 100
-300 to 1200°F
-200.0 to 400.0°C
-300 to 700°F
-200.0 to 300. 0°C
-300 to 550°F
-200.0 to 200. 0°C
-300 to 300°F
-100.0 to 100.0°C
-100 to 200°F
-200.0 to 649. 0°C
-300 to 1200°F
-200.0 to 400. 0°C
-300 to 700°F
-200.0 to 300. 0°C
-300 to 550°F
-200.0 to 200. 0°C
-300 to 300°F
-100.0 to 100. 0°C
-100 to 200°F
Pt 50
-200.0 to 649. 0°C
-300 to 1 200°F
Pt-Co
4.0 to 374.0K
450 to 200°F
Upper display Lower display
Display of current set value No.
Setting mode (SET) indicator
• Light in the Setting mode.
(The Setting Mode is entered by
pressing the MODE key.)
Alarm wait (WAIT) indicator
• Light in the Alarm Wait mode.
The Alarm Wait mode is set to inhibit
alann activation until the measured
value (PV) has risen above the higher
alann point or fallen below the lower
alarm point once after running has
started.
Remote setting (REM) indicator
• Lights durrng remote setting
(optional).
Error (ERR) Indicator
• Lights when an error occurs.
Mode key
(1) Press to switch from the running
screen to the setting screen or vice
versa.
(2) Hold down to fast forward setting
items
Select (SEL) key
(1) Press to select the required setting item
(parameter) after the appropriate setting
screen has been selected.
(2) Hold down to fast forward setting items.
Lower cover
• The following are tudden beHind the
lower cover:
— Vertica l angle (V ANGLE)
—
trimmer controlling the viewing
angle of the LCD display.
Fixing screw holding the internal
rack.
Auto/Manual (A/M) key
• Press to switch between
automatic and manual outputs.
Each time this is pressed, the
controller alternates between the
manual and auto modes. Press the
[ENT] key to register the change.
3
Measured value (PV) display
• Displays the current PV obtained
by measurement.
Set value (SV) display
• Displays the current target value
(SV).
Unit indicator
• Displays the selected input unit
(°C, °F, K) or set unit (%, blank).
Alarm indicators (AL1 to 4)
• When an alarm occurs, the
corresponding indicator lights.
Running or setting screen
• During running, the screen shows
the output value and output pattern
(bar graph, On/Off, Open/Closed)
according to the model.
• During constant setting and
function selection, the screen
shows details of parameter setting.
Entry key
• Press to register the parameter
(value of function) in memory.
Up (/\) key
• When setting, press to count up the
selected value by 1. Hold
depressed to count up the value
continuously.
Down (\/) key
• When setting, press to count down
the selected value by 1. Hold
depressed to count down
continuously.
Shill (>) key
• Press to shift to the next digit when
setting a numeric value or to call
up the next function when setting a
funct ion.
• With the running screen, hold
depressed for 2 seconds or more
to increase the resolution of the
PV display by a factor of ten.
(This is done by shifting the
decimal point.)
¢ GENERAL SPECIFICATIONS
Input signals
: Thermocouples: B, R, S, K, E, J,
T, WWRe5-26,
WWRe0-26, Ni -NIMo, AuFe-Cr,
Allowable signal
source resistance
: Thermocouple inputs: Less than 100 Ω
: Voltage inputs: L ess than 300 Ω(± 5V)
Less than 100 Ω ) (mV)
Resistance thermometer inputs:
N. PR5 -20, PR2 0-40, Platinel,
U, L
DC voltages:
Measuring range
± 10mV, ± 20mV, ± 50mV,
± 100mV, ±5V
DC currents:
± 20mA
Resistance thermometers : Pt100, JPt100,
JPt50, Pt-Co
: Refer to the measuring range table.
Type 1: Total of 34; thermocouples × 28,
DC voltages × 5, DC current × 1
Type 2: Total of 12 resistance thermometers;
Pt100 × 5, JPt100 × 5, JPt50 × 1,
PtCo × 1
Measuring accuracy: Larger value of ± 0.1% of input span ± 1 digit or
10µV (With thermocouple inputs, reference junction
temperature compensation accuracy is not included.)
Less than 5Ω (per line)
: Thermocouple and mV inputs:More than 8Ω
Voltage inputs: More than 1MΩ)
Input resistance
Current inputs: 250Ω
Measuring current : 2mA with resistance thermometer inputs
Maximum common : 250VAC
mode voltage
Common mode
: More than 130dB
Rejection ratio
Series mode rejection: More than 50dB
ratio
Insulation resistance : Between measuring terminal and ground
terminal: more than 20MΩ at 500VDC
Between power s upply terminal and ground
terminal: more than 20MΩ at 500VDC
For details, refer to “Detailed Accuracy
Rating Specifications"
Temp. compensation : 0.5°C
accuracy
Sampling period : Approx. 0.1 second
Burn -out
: Higher-limit burnout function provided as
Dielectric strength
standard with thermocouple and mV inputs.
Output in case of burnout:
Optional set value between -5% and 105% of
control output
Operation is case of burnout:
Highe r-limit alarm
Sensor compensation : ± 1000 times the display resolution
Digital filter constant : 0 to 99.9 seconds
Scaling
: DC voltage and DC current inputs. Optional
Displays
Display data
scaling within 4 digits
: Upper: 7 -segment back-lit LCD
Lower: Full dot-matrix (96 × 20 dots)
back-lit LCD
Adjustable angle of viewing (± 20°)
: Upper Display: Simultaneous display of PV
and SV (0 to 3 digits)
Top row
:Measured value (PV), 4 digits
with unit
Bottom row
Others
:Set value(SV), 4 digits with unit
Executing setting number
Indication (1-digit digital
indication)
:Alarm indicators, setting mode
indicator, alarm waiting indicator,
remote setting indicator, error
indicator
Lower Display:
In running mode: Status display (80-dot)
and digital display
(max. 3 digits)
In setting mode: Parameter (value or
function)
Automatic resume : In the setting mode, if no key is pressed for 1
minute or more, the unit automatically returns
to the running mode.
: 85 to 264VAC, 50/60Hz
Power supply
Ambient temperature: -10 to +50°C
Ambient humidity : Less than 90%RH (with no condensation)
Countermeasure
: Parameters held in EEPROM
against power failure
Power consumption
Case
Color
Mounting
Weight
Between measuring terminal and power supply
terminal: more than 20MΩ, at 500VDC
: Between measuring terminal and ground
terminal: 1 minute at 500VAC
Between p ower supply terminal and ground
terminal: 1 minute at 1500VAC
Between measuring terminal and power supply
terminal: 1 minute at 1500VAC
: 100V, max. 15VA, 200V, max. 20VA.
: ABS resin
: Gray
: Flush
: Approx. 750g (1.7 Ibs)
¢ CONTROL SPECIFICATIONS
Control switching : Approx. 0.1 second
period
Control method : Current output type PID
On-off pulse type PID
SSR drive pulse PID
On-off servo type PID
Control set values : 8 (4-digit) values can be set.
Set value change : Setting of slope when the control set point is
Auto tuning
changed.
: 0000 to 9999/minute (0 for step response)
: ± 0.1% of input span
:The relative error between indicated and
actual values: ±1 digit
: Provided as standard. PID constants can also
PlO values
: Can be set independently for each of 8 SVs
Ratio
Control setting
accuracy rating
be set manually.
P: 0 to 999.9% (0 for on/off control)
I: 00,1 to 9999 seconds
D: 0 to 9999 seconds
Anti-reset windup : Setting 1 range
Upper limit +9 9.9 to 0.0%
Lower limit -99.9 to 0.0%
Output limiter
: Independent higher and lower limits can be set.
corresponding to each of 8 SVs, from -5 to
105%
Output change limiter:Independent limits can be set for each of 8 SVs,
from 0.1 to 100%
Output presetting : Output setting in case PV=SV during P operation,
from 0.0 to 100.0%
4
Output deadband
: Can be set during on/off control (with P = 0).
Setting range: 0.1 to 9.9%.
Auto/Manual selection : From Manual to Auto by balanceless bumpless
Control action
Manual output is from 0 to 100%
: Direct/reverse changeable
= Current output type PID system
Output signal: 4 to ,20mA (or 1 to 5mA)
Load resistance: Less than 750Ω (3KΩ) with
1 to 5mA)
= On-off pulse type PID system
Output signal:
On-off pulse conductive signal
Contact capacity:
Resistance load
100VAC less than 2A,
200VAC less than 1A
Inductive load
100VAC less than 1A
200VAC less than 0.5A
On-off pulse period: Variable between
approx.1 to 180 seconds
(in 1-second steps)
= SSR drive pulse PID system
Output signal: On-Off pulse voltage signal
ON: 12VDC% ± 10% (max. 20mA)
OFF: Less than 0.6VDC
On-off pulse period: Variable between
approx. 1 to 180 seconds
(in 1 -second steps)
= On-off servo type PID system
Output signal: On-off servo conductive
signal
Contact capacity: Inductive load 100VAC 1A
200VAC 0.5 A Mm.
20mA Light load: Max.
20mA, Min. 1mA
Feedback resistance: l00Ω to 2KΩ)
¢ ALARM SPECIFICATIONS
Alarm points
Alarm system
Alarm
Alarm
: 4 points for each control set point (SV)
: Higher-limit, lower-limit, deviation and
absolute-value alarms. Independent setting for
each set value.
dead band : 1000 times set resolution
outputs : Transistor open-collector output (max. load 24
VDC, 50mA)*
ALARM 1 and ALARM 2: C terminal used in
common
ALARM 3 and AlARM 4: C terminal used in
common
*MOS relay output available as option
(Note)
The outputs of Alarm 3 and Alarm 4 are not
available on on-off servo type PID system
(with CE -marking)
5
¢ OPTIONAL FUNCTIONS
Option name
Communications
interface
Transmission signal
output
Remote/local switching
Voltage output PID
External set value
switching
Dual output
Lower -limi burnout
MOS relay alarm output
Preset manual*
Relay unit
A/M external switching*
Current output signal 1 to5mA
Abnormal CPU output 100%
4-wire type Pt input
Speed type PID
Screen resume OFF
Square root calculation
Installation above eye level
CE-marking
*
Contents
An RS-232C, RS-422A or RS-485 interface is available
For transmitting set values and measured values to a host computer, or for setting parameters from the computer. It can be
used for zone control.
A signal proportional to the set value, measured value or output value can be output.
Transmitted contents:
1 kin d from set value, measured value and output value is optionally selectable.
Transmission system:
Analog transmission 1 kind from 4 to 20mADC, 0 to 1VDC, and 0 to 10VDC (to be specified)
With scaling function (optionally setting within 4 digits)
Load: Current transmission - Max.400Ω
Voltage transmission - 1mA
Output resolution: 12-bit (0.024%)
Transmission accuracy rating: 0.2% of input span (against indicated value)
Insulation: Isolation between input/output signal and
transmission signal: 500VDC, more than 20 MΩ or 250VAC.
Switching between remote and local operation can be done using an external contact signal. The remote operation mode
allows the control point to be set by an external signal. The ratio and bias of the remote input can also be set and the unit can
also be used as a secondary controller in cascade control.
Remote input: 1 kind from 4 to 20mADC, 0 to 1VDC, and 0 to 10VDC (to be specified) With scaling function (optionally
setting within 4 digits)
Input impedance: 4 to 20mA - 61.9Ω
0 to 1V - approx. 1MΩ
0 to 10V - approx. 100KΩ
Remote input shifting: ± 1000 times the SV set resolution.
Insulation: Isolation between input/output signal and remote input signal
Setting accuracy: ± 0.2% of input span
For use to connect inverters as control equipment
Output signal: 0 to 10VDC
Current capacity: 2mA
The eight internal set values can be selected using external contact signals.
External contact capacity: 12VDC, more than 2mA
By outputting 4 to 20mA for Output 1 and 20 to 4mA for
Dead band: ± 99.9%, of the scale range
Output 2, cooling or heating control is possible.
PID values: Standard on output 1
Output 1
Output 2
P=0 to 9999% (On-off action is done when P=0)
4 to 20mA
20 to 4mA
setting
(Load resistance: 400Ω)
(Load resistance : 400Ω)
Output 1
Output 2
On-off pulse output
On-off pulse output
SSR drive pulse output
SSR drive pulse output
20 to 4mA (Load resistance : 750Ω)
Dead band
In case of burnout, the output is fixed at a set value and a lower-limit alarm is generated.
Control output at burnout: Optional set value between -5 and 105%
Lower-limit alarm output is ON at burnout.
Both AC load and DC load can be used by using solid state MOS relays on AL3 and AL4 in 4 alarm outputs.
Contact capacity: 400VDC, 100mA
264VAC, 50mA
With external make-contact signal, output is fixed at the preset value.
The speed of changing from the auto value to the preset value is limited by the output change limit of this option.
Setting range: Preset value 0 to 100%
Change limit value 0.1 to 100.0%
A unit converting alarm outputs from transistor outputs to relay outputs is available.
Output is maintained at the manual output condition by an external make-contact signal.
The output of a current output type PID controller is 1 to 5mA.
When the CPU is abnormal, the output is set forcibly to 100%.
A resistance thermometer type controller for 4-wire type sensor
A controller modified from position type PID to speed type PID.
The function to automatically resume the running screen from the setting screen can be switched OFF.
The square roots of DC voltage and current inputs are calculated and used for control.
The angle of viewing can be adjusted for optimum viewability.
CE-marking
EN55011 Group 1 Class A
EN50082-2 (Industrial Environment)
EN61010-1 + A2
The indication equivalent to ± 200 µV, the temperature indication equivalent to thermoelectromotive force of ± 200 µV or 5°C
mays vary under the test environment requested by EMC directive.
Max. common mode voltage: 30VAC
In combination with set value switching external input.
6
¢ TERMINAL BOARD DIAGRAM
* : Optional
¢ OPTION TERMINALS
1st OPTION ZONE
2nd OPTION ZONE
3rd OPTION ZONE
+
2nd OUTPUT TERMINAL
-
(COMMUNICATIONS)
RS-232C
(TRANSMISSION>
(R/L)
(2nd outputs type)
(EXTERNAL SET VALUE SWITCHING)
RS-422A RS-485
1st
2nd
3rd
Using zone is decided in the
above order by combination
with other options.
7
* Preset manual or
AIM external
switching terminals.
¢ DETAILED ACCURACY RATING
SPECIFICATIONS
Input
Accuracy
Range
(of Input span)
B
R
S
K
Thermocouple
E
J
T
WWRe 5-26
WWRe 0-26
Ni-NiMo
N
Platinel
U
L
AuFe- Cr
PR5-20
±0.1%±1 digit
However,
• -270 to
-200°C
: ±1.0% ±1digit
• -200 to 0°C
: ±0.15%
±1 digit
< EXTERNAL DIMENSIONS
Exception
0 to 100°C: ±5% ±1 digit
100 to 400°C: ±4% ±1 digit
400 to 800°C : ±0.15% ±1 digit
0 to 200°C: ±0.15% ±1 digit
0 to 200°C: ±0.15% ±1 digit
-270 to -200°C (for measuring range
of -270 to 150°C and -270 to 300°C):
±2% ± 1 digit
0 to 100°C: ±0.3% ±1 digit
• Panel Cut-out Diagram
±0.2% ±1 digit
PR20-40
20 K or under: ±0.5% ±1 digit
20 to 50 K
: ±0.3% ±1 digit
0 to 100°C: ± 4%
100 to 200°C: ±0.5% ±1 digit
0 to 300°C: ±1.5% ±1 digit
300 to 800°C: ±0.8% ±1 digit
DC voltages
Resistance Thermometer
DC currents
±0.1% ±1 digit
Pt100
-100 to 100°C scale: ±0.15% ±1 digit
JPt100
JPt50
±0.1% ±1 digit
-100 to 100°C scale: ±0.15% ±1 digit
Pt-Co
20K or under: ±0.5% ±1 digit
±0.15% 1 digit 20 to 50K: ±0.3% ±1 digit
N: Number of mounted units
Note: 1 digit refers to the set resolution.
UNIT: mm
Specifications subject to change without notice. Original 2000.11
32-8, KUMANO-CHO, ITABASHI-KU, TOKYO 173-8632
PHONE: +81-3-3956-2171
FAX: +81-3-3956-0915
E-mail: [email protected]
Website : http://www.chino.co.jp
8