Socomec Diris A40/A41

Socomec Diris A40/A41
DIRIS A40 / A41
Multifunction meters
NEW
 Applications
Ethernet
DIRIS A41
DIRIS A40
diris_744_a_1_cat
DIRIS A40
DIRIS A40
RS485
 Function
The DIRIS A40 and A41 are multifunction
meters which ensure the user has access
to all the measurements required for energy
efficiency projects and monitoring of
electrical distribution.
All this information can be used
and analysed remotely using the
CONTROL VISION software.
 Conformity to standards
• IEC 61557-12
• IEC 62053-22 class 0.5S
• IEC 62053-23 class 2
2
diris_581_e_1_gb_cat
Monitoring and managing
energy for high/low voltage
electrical installations
CONTROL VISION software
Currents
per phase
curve
PLC
Multi measurement
• Current
- instantaneous: I1, I2, I3, In,
Isystem
- average/maximum average:
I1, I2, I3, In
• Voltages & frequency
- instantaneous: U1, U2, U3,
U12, U23, U31, F, Vsystem,
Usystem
- average/maximum average:
U1, U2, U3, U12, U23, U31, F
• Power
- instantaneous: 3P, ΣP, 3Q, ΣQ,
3S, ΣS
- average/maximum average:
ΣP, ΣQ, ΣS
- predictive: (ΣP), (ΣQ), (ΣS)
• Power factor
- instantaneous: 3PF, ΣPF
- average/maximum average:
ΣPF
• Temperatures(1)
- internal
- external via 3 PT100 sensors
Metering
• Active energy:+/- kWh
• Reactive energy:+/- kvarh
• Apparent energy:kVAh
• Hours:
Harmonic analysis
• Harmonic distortion rate
- Currents: thd I1, thd I2, thd I3,
thd In
- Phase-to-neutral voltage: thd
U1, thd U2, thd U3
- Phase to phase voltage: thd
U12, thd U23, thd U31
• Individual up to level 63
- Currents: HI1, HI2, HI3, HIn
- Phase-to-neutral voltage: HU1,
HU2, HU3,
- Phase to phase voltage: HU12,
HU23, HU31
Load curves(1)
• Active and reactive power: ΣP+/-;
ΣQ+/• Voltages & frequency: U1, U2,
U3, U12, U23, U31, F
Events(1)
• Alarms on all electrical values.
Communications(1)
• Analogues 0/4- 20 mA
• Digital RS485 (Jbus/Modbus &
Profibus-DP)
• Ethernet (modbus/TCP or Jbus/
Modbus RTU over TCP and Web
server)
• Ethernet with RS485 gateway
Jbus/Modbus RTU over TCP
Inputs / Outputs(1)
• Pulse metering
• Remote control/command
• Alarm report
• Pulse report
(1) Available as an option
(see the following pages).
General Catalogue 2012-2013 SOCOMEC
appli_384_b
Main
meter panel
PC
Multifunction meters
DIRIS A40 / A41
ÂÂ Front panel
diris_744x_a_1_cat
1. Backlit LCD screen.
2. Pushbutton for currents and setup wiring correction
3. Pushbutton for voltages and frequency.
4. Pushbutton for active, reactive, and apparent power and power factor.
5. Pushbutton for maximum and average current and power values.
6. Pushbutton for harmonics values.
7. Pushbutton for pulse, hours and electrical energy meters.
1
2 3
4
5
6
7
Pulse outputs
diris_445_a_1_cat
ÂÂPlug-in modules
2 configurable pulse outputs (type, weight and run) on ± kWh, ±kvarh and kVAh
diris_447_a_1_cat
JBUS / MODBUS® communication
RS485 link with JBUS / MODBUS® protocol (speed up to 38400 bauds).
PROFIBUS® DP communication
SUB-D9 link with PROFIBUS® DP protocol (speed up to 12 Mbauds).
Ethernet communication
• Ethernet link with MODBUS/TCP or JBUS/MODBUS RTU over TCP
• Embedded Ethernet Webserver software
diris_776_a_1_cat
diris_777_a_1_cat
diris_773_a
diris_775_a_1_cat
DIRIS® A40
Ethernet communication with RS485 JBUS/MODBUS gateway
• Ethernet link with MODBUS/TCP or JBUS/MODBUS RTU over TCP
• Connection of 1 to 247 RS485 JBUS/MODBUS slaves
• Embedded Ethernet Webserver software
DIRIS® A41
diris_448_a_1_cat
Analogue outputs
A maximum of 2 modules may be connected, that is 4 analogue outputs.
2 outputs assignable to:
3I, In, 3V, 3U, F, ±ΣP, ±ΣQ, ΣS, ΣPFL/C, I sys, Vsys, Usys, Ppred, Q pred, Spred,
internal T°C, T°C 1, T°C 2, T°C 3 and to 17 VDC power supply
diris_774_a
diris_449_a_1_cat
2 inputs - 2 outputs
A maximum of 3 modules may be connected, giving 6 inputs.
2 outputs assignable to:
- monitoring: 3I, In, 3V, 3U, F, ±ΣP, ±ΣQ, SS, ΣPFL/C, THD 3I, THD In, THD 3V, THD
3U, Ppred, Qpred, Spred, internal T°C, T°C 1, T°C2, T°C3 and hour meter,
- remote control,
- timed remote control.
diris_682_a_1_cat
Memory
• Storing up to a maximum of 62 days of P+, P-, Q+, Q- with an internal or
external synchronisation signal of 5, 8, 10, 15, 20, 30 and 60 minutes.
• Storing of 10 hour-dated last alarms.
• Storing of the last minimum and maximum instantaneous values for 3U, 3V, 3I, In,
F, ΣP±, ΣQ±, ΣS, THD 3U, THD 3V, THD, 3U, THD, 3V, THD, 3I, THD In.
• Storing of 3U, 3V and F average values based on synchronisation function
(maximum 60 days).
diris_747_a_2_cat
Temperature
SOCOMEC General Catalogue 2012-2013
Temperature indication
• Internal
• External sensor PT 100 (T°C 1)
• External sensor PT 100 (T°C 2)
• External sensor PT 100 (T°C 3)
3
ÂÂDIRIS A40 / A41 - Accessories
Current transformer
IP65 protection
Mounting kit for 144 x 96 mm cut
out plate
diris_718_b_1_cat
trafo_024_a_2_cat
trafo_077_b_2_cat
diris_720_a_2_cat
(see page 334)
ÂÂTerminals
DIRIS A40
diris_569_a_1_x_cat
S1 - S2: current inputs
V1
V2
V3
VN
A U X
S1 S2 S1 S2 S1 S2
I1
I2
AUX: auxiliary power supply Us
V1- V2 - V3 - VN: voltage inputs
I3
DIRIS A40
DIRIS A41
V2
V3
VN
S1 S2 S1 S2 S1 S2 S1 S2
I1
I2
I3
AUX: auxiliary power supply Us
V1- V2 - V3 - VN: voltage inputs
IN
DIRIS A41
0V -
+
1
0n
R = 120
RS485
DIRIS A40 / A41
Pulse output module
1
2
OUT 1
3
Analogue output module
4
diris_573_a_1_x_cat
Communication module
diris_571_a_1_x_cat
A U X
diris_572_a_1_x_cat
diris_570_a_1_x_cat
S1 - S2: current inputs
V1
OUT 2
DIRIS A40 / A41
5
6
7
8
+
- +
0/4-20 mA 0/4-20 mA
OUT 1
OUT 2
DIRIS A40 / A41
1 - 2: pulse output n°1.
3 - 4: pulse output n°2.
5 - 6: analogue output n°1.
7 - 8: analogue output n°2.
2 inputs / 2 outputs module
Memory module
Temperature module
diris_574_b_1_x_cat
OUT 1
A-Cd
OUT 2
A-Cd
1 3 14 15 16
-
+
-
IN 1
+
IN 2
19 20 21 22 23 24 25 26
17 18
+
-
diris_753_a_1_gb_cat
9 10 11 12
diris_683_a_1_x_cat
RS485 link.
R = 120 Ω: internal resistance for the
RS485 link.
IN
synchro
DIRIS A40 / A41
17 - 18: synchronisation input.
9 - 10: relay output n°1.
11 - 12: relay output n°2.
13 - 14: opto input n°1.
15 - 16: opto input n°2.
sensor 2
27 28 29 30
sensor 3
DIRIS A40/A41
Sensor 1
19: Red
20: Red
21: White
22: White
DIRIS A40 / A41
Ethernet Module
sensor 1
Sensor 2
23: Red
24: Red
25: White
26: White
Sensor 3
27: Red
28: Red
29: White
30: White
Ethernet module + RS485 JBUS /
4
10 BASE T
100 BASE T
RJ45
DIRIS A40/A41
diris_751_b_1_gb_cat
diris_752_a_1_x_cat
MODBUS gateway
10 BASE T
100 BASE T
RJ45
0V -
+
RS485 gateway
DIRIS A40/A41
General Catalogue 2012-2013 SOCOMEC
Multifunction meters
DIRIS A40 / A41
ÂÂElectrical characteristics
Current measurement on insulated inputs (TRMS)
Via CT primary
10 000 A
Via CT secondary
1 or 5 A
Measurement range
0 … 11 kA
Input consumption
≤ 0.1 VA
Measurement updating period
1s
Accuracy
0.2 %
Sustained overload
6A
intermittent overload
10 In for 1 s
2 inputs / 2 outputs module: Outputs (alarms / control)
Number of relays
2(1)
Type
250 VAC - 5 A - 1150 VA
2 inputs / 2 outputs module: Phototransistor inputs
Number
2(1)
Power supply
10 … 30 VDC
Minimal signal width
10 ms
Minimum length between 2 impulses
18 ms
Type
phototransistor
Voltage measurements (TRMS)
Direct measurement between phases
Direct measurement between phase and neutral
VT primary
VT secondary
Frequency
Input consumption
Measurement updating period
Accuracy
Sustained overload
50 … 700 VAC
28 … 404 VAC
500 000 VAC
60, 100, 110, 173, 190 VAC
50 / 60 Hz
≤ 0.1 VA
1s
0.2 %
760 VAC
Current-voltage product
Limitation for 1A CT
Limitation for 5A CT
10 000 000
10 000 000
Power measurement
Measurement updating period
Accuracy
1s
0.5 %
Power factor measurement
Measurement updating period
Accuracy
1s
0.5 %
PROFIBUS-DP communication module
Link
SUB-D9
Protocol
PROFIBUS® DP
9.8 kbauds … 12 Mbauds
PROFIBUS® speed
Frequency measurement
Measurement range
Measurement updating period
Accuracy
45 … 65 Hz
1s
0.1 %
Ethernet Communication Module
Connectique
RJ45
Speed
10 base T / 100 base T
Protocol
MODBUS TCP or JBUS/MODBUS RTU over TCP
Energy accuracy
Active (according to IEC 62053-22)
Reactive (according to IEC 62053-23)
class 0.5 S
class 2
Auxiliary power supply
Alternating voltage
AC tolerance
Direct voltage
DC tolerance
Frequency
Consumption
110 … 400 VAC
± 10 %
120 … 350 VDC / 12 … 48 VDC
± 20 % / - 6 … + 20 %
50 / 60 Hz
≤ 10 VA
Module temperature (inputs)
Type
Connection
Dynamic
Accuracy
Maximum length
PT100
2, 3 or 4 wires
- 20°C ... 150°C
+/- 1 digit
300 cm
Operating conditions
Operating temperature
Storage temperature
Relative humidity
- 10 … + 55 °C
- 20 … + 85 °C
95 %
Pulse outputs module
Number of relays
Type
Max. number of operations
2
100 VDC - 0.5 A - 10 VA
≤ 108
Analogue output module
Number of outputs
Type
Scale
Load resistance
Maximum current
2(2)
insulated
0 / 4 … 20 mA
600 Ω
30 mA
JBUS / MODBUS communication module
Link
RS485
Type
2 … 3 half duplex wires
Protocol
JBUS/MODBUS® in RTU mode
®
1400 … 38400 bauds
JBUS/MODBUS speed
(1) Max. 3 modules / Diris.
(2) Max. 2 modules / DIRIS.
ÂÂ Case
92
diris_582_d_1_x_cat
96
DIR
IS
Type
Dimensions W x H x D
Case protection index
Front protection rating
Display type
Terminal blocks type
Voltage and other connection section
Current connection section
Weight
+ 0.8
- 0.0
92
A4
0
60
Panel mounting
96 x 96 x 60 mm
IP30
IP52
LCD
fixed or pull-out
0.2 … 2.5 mm2
0.5 … 6 mm2
400 g
+ 0.8
- 0.0
35
96
SOCOMEC General Catalogue 2012-2013
5
ÂÂDIRIS A40 / A41 - Connections
Recommendation: when disconnecting the DIRIS, the secondaries of each current transformer must be short-circuited. This operation can be carried out automatically by a product in
the SOCOMEC catalogue, PTI: consult us.
In TNC neutral system it is recommanded to use functional earth module.
Low voltage balanced network for DIRIS A40
3/4 wires with 1 CT
Single phase
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
P1
L1
S1
S2
N
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
N
P1
L1
S1
S2
L2
L3
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
P1
L1
S1
S2
L2
1
1
S1 S2 S1 S2 S1 S2
V1 V2 V3 VN
I1
I2
I3
1
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
diris_394_d_1_gb_cat
1
diris_393_d_1_gb_cat
diris_392_d_1_gb_cat
1
Two phase
1
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
Use of 1 CT reduces by 0.5% the accuracy of the
phases, the current of which is worked out by vector
calculation.
Low voltage unbalanced network for DIRIS A40
3/4 wires with 3 CTs
3 wires with 2 CTs
1
1
V1 V2 V3 VN
diris_396_d_1_gb_cat
diris_395_d_1_gb_cat
1
S1 S2 S1 S2 S1 S2
I1
I2
I3
1
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
P1
L1
S1
P1
L2
S1
S2
L3
1
1
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
diris_397_d_1_gb_cat
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
N
P1
L1
S1
S2
L2
P1
L3
S1
S2
1
3 wires with 2 CTs
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
P1
L1
S2
S1
L2
P1
L3
S2
S1
Use of 2 CTs reduces by 0.5% the accuracy of
the phase, whose current is worked out by vector
calculation.
1
1
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
Use of 2 CTs reduces by 0.5% the accuracy of
the phase, whose current is worked out by vector
calculation.
Low voltage unbalanced network for DIRIS A41
4 wires with 4 CTs
1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class
P1
N
P1
S1
L1
S1
S2
L2
P1
L3
S2
S1
diris_575_b_1_gb_cat
1
1
1
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 S1 S2
I1
I2
I3
IN
Additional information
Communication via RS485 link
Voltage transformer for HV networks
AC & DC auxiliary power supply
L1
L2
L3
110 / 400 VAC (IEC)
120 / 350 VDC (IEC)
+
ON
RS485
V1 V2 V3 N
diris_400_g_1_gb_cat
0V -
diris_399_b_1_x_cat
diris_398_c_1_x_cat
LIYCY-CY
A U X
It is recommended that the auxiliary power supply be
protected by the use of 500 mA gG fuses.
6
General Catalogue 2012-2013 SOCOMEC
Multifunction meters
DIRIS A40 / A41
diris_744_a_1_cat
 References
Basic device
Auxiliary power supply Us
110 ... 400 VAC / 120 ... 350 VDC
12 ... 48 VDC
DIRIS A40
Reference
4825 0201
4825 1201
DIRIS A41
with CT on the
neutral
Reference
4825 0202
4825 1202
Reference
4825 0090
4825 0092
4825 0093
4825 0094
4825 0205
4825 0097
4825 0203
4825 0204
4825 0206
4825 0087
Reference
4825 0090
4825 0092
4825 0093
4825 0094
4825 0205
4825 0097
4825 0203
4825 0204
4825 0206
4825 0087
Options
Plug-in modules(1)
Pulse outputs
Sub D9 JBUS/MODBUS® communication
Analogue outputs
2 inputs / 2 outputs
RS485 PROFIBUS®DP communication
Memory
Ethernet communication (embedded Ethernet Webserver software)
Ethernet communication + RS485 gateway JBUS/MODBUS (embedded Ethernet Webserver software)
Temperature inputs
Functional Earth
Accessories
Description of accessories
IP65 protection
Panel mounting kit for a 144 x 96 mm cutout
Fuse combination switches for the protection of voltage inputs (type RM) 3 poles
Fuse combination switches for the protection of the auxiliary supply (type RM) 1 pole + neutral
Fuses type gG 10x38 0.5 A
Current transformers range
To be ordered
in multiples of
1
1
4
6
10
Reference
4825 0089
4825 0088
5601 0018
5601 0017
6012 0000
See page 334
To be ordered
in multiples of
1
1
4
6
10
Reference
4825 0089
4825 0088
5601 0018
5601 0017
6012 0000
See page 334
(1) Ease of integration for additional functions (maximum 4 on A40 and 3 on A41).
Services and Technical assistance
Our expertise extends to a complete offer of
services like commissioning installation audit,
training, maintenance and project engineering.
 Ethernet Webserver
The Webserver is a software, based on
HTML pages, that is embedded in the
optional Ethernet module of the DIRIS.
Access is available using an internet
browser and entering the IP address of
the DIRIS. It enables viewing the main
electrical values, diagnostic analysis,
device monitoring and setting the main
parameters of the DIRIS multifunction
meter.
diris_869_a_1_gb_cat
Panels for viewing all average and instantaneous electrical
values.
Viewing of average and instantaneous energy consumptions.
Device setting
Alarms
diris_868_a_1_gb_cat
Use
Power and Energy
diris_870_a_1_gb_cat
diris_776_a_1_cat
diris_867_a_1_gb_cat
Instantaneous report of measurements
The last 10 alarms are date and time registered. Duration and limit reached
(low limit value / high limit value), as well as the related output alarm number
are also displayed. Data can be extracted in *.csv format.
SOCOMEC General Catalogue 2012-2013
7
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement