Technical Sheet Uninterruptible Power Supply MASTERYS
File name:
DCB0028-33.doc
Version
23/04/2004
Technical Sheet
Uninterruptible Power Supply
MASTERYS® MC 3/3
R00
Strong Points
-
Applications
VFI-SS-111 (IEC62040-3) On Line double conversion technology
Perfectly stable output voltage and frequency
Parallel configurations of up to 6 MASTERYS MC units ensure
scalability and high reliability.
High input power factor > 0.99
Low current distortion (THDI<3%)
Flexible backup time: different backup capacities available inside
the same cabinet
Advanced graphics display for total system control
RS232/RS485 serial communication interface
Standard LAN (Ethernet) connection and second RS232
2 free slots for ADC relay card and (GSS) generator interface
Backfeed protection
Expert battery system (EBS)
Redundant (separate strings) and “Hot Swappable” batteries
“Always On Mode” function to optimise performance, correcting
harmonics generated by the load
“Energy Saver” function to optimise the performance of redundant
parallel mode
Installable in standard 19” rack cabinets (up to 30kVA)
-
Protection of Mission
Critical IT applications:
Banking EDP centres
IT networks
Hospital institutions
Protection of industrial
applications:
Medium/large enterprises
Industrial transformations
Automatic systems
Protection of public
utility/services applications:
Sorting/distribution centres
Universities
- Railway stations/Airports
MASTERYS is the most effective solution for protecting your loads not only against black outs, but from any other type of electrical noise and
disturbance thanks to the VFI (Voltage and Frequency Independent) on line double conversion technology it uses. This new technology is based
on multiprocessor and IGBT architechture and ensures total reliability in any operating environment and situation.
Description of the UPS system
The MC models offer excellent performance thanks to the IGBT based low distortion rectifier, to the standard LAN connection and to the “Always
On” feature that optimises efficiency keeping the harmonics correction. When necessary or for special protection architectures, up to six units
of the models in the MC range can be connected in parallel. Masterys MC can also manage the generator set thanks to the GSS interface. A new
Expert Battery System optimises battery use and recharging in accordance with the type of battery and environmental conditions rationalising
the use of the accumulators and therefore prolonging the average battery life.
Standard features and benefits
Options
Complete: detailed information and numerous commands thanks to the
advanced mimic panel
Convenient: standard 10Mb Ethernet LAN (RJ45) connection with second
RS232 interface
UPS living: elegant design and ergonomic commands
IT compatible: up to 30kVA installable in standard 19” rack cabinet
(optional kit)
Vertical backup: three UPS cabinet models satisfy a wide range of backup
capacities without additional cabinets.
Easy-to-move: handy wheels simplify inspection and maintenance
operations.
Frequency converter (from 50Hz to 60Hz and vice-versa)
-
Technical Specifications
MASTERYS
MAS-MC 320
20.000/16.000
-
MAS-MC 330
MAS-MC 340
MAS-MC 360
30.000/24.000
40.000/32.000
60.000/48.000
Voltage
400 V ± 15% (up to 35% @ 70% P nominal)
Nominal current
22 A
30 A
44 A
60 A
89 A
Input
Power factor
0.99 (THDi < 3%)
Frequency
50/60 Hz ± 10%
Voltage
400 V ± 1%
Voltage distortion
(1% on linear load) (<6% on distorting load)
Output
Frequency
50/60 Hz ± 2% (up 1% to 8% in operation together with generator)
Overload
125% for 10 minutes 150% for 60 seconds
AC/AC efficiency
Up to 92% (on-line) / 96% (Eco Mode)
By-pass
Automatic
Output nominal voltage ± 15% (up 10% to 20% in operation together with generator)
Battery
Battery backup time*
Up to 11 a 210 min. Up to 10 a 135 min. Up to 10 a 85 min. Up to 10 a 60 min. Up to 12 a 45 min. **
Cabinet
LxDxH (mm)
444x795x800/1400*
444x795x1400
Weight (kg) with batt.
195
245
312
400
170 (UPS only)
Communication
RS232/485 / RS232 / LAN connection
Connectors
Input/output
Terminal block / terminal block
Standards
Safety/EMC
IEC 62040-1-1, IEC60950-1 / (EN) IEC 62040-2 (2° edition), EN 50091-2 class A
Topology
IEC 62040-3 (VFI-SS-111)
Temperature
0 ÷ 40° C (da 15° C a 25° C for improved battery life)
Characteristics
Noise
< 55dB
< 62dB
* backup time at 75% of the maximum loads with cabinet models of different heights (S-M-T-W type)
** External battery cabinet
Socomec Sicon UPS reserves the right to introduce changes referring to new technologies or regulations.
Power (VA/W)
MAS-MC 315
15.000/12.000
-
Advanced Dry Contact (ADC) card, three dry input contacts and
4 dry output contacts (250 V).
Global Supply System (GSS) generator interface, 4 dry input
contacts and 1 dry output contact (60 V)
Net Vision WEB/SNMP manager
Uni Vision pro shutdown software
LCD panel for remote communication
Input/output galvanic isolation transformer
External manual bypass
Rack kit to install BC and MC models up to 30kVA in 19” rack cabinets
Parallel configuration kit
External battery cabinets to extend backup time (W type)
ACS fuction, enables the synchronization with an alternative
power source
MAS-MC 380
80.000/64.000
119 A
Up to 8 a 35 min. **
180 (UPS only)