Various System Trouble Displays

Various System Trouble Displays
Various System Trouble Displays
Alpha Display
Fixed Disp. Meaning
CANCELED ALARM
CA
will appear if an exit or interior zone contained a fault during closing at the time
the Exit Delay ended (e.g., exit door left open), but the system was disarmed during
the Entry Delay time. The alarm sounder and keypad sound continuously, but stop
when the system is disarmed. No message will be transmitted to the central station.
EXIT ALARM
EA
will appear when the Exit Delay ends if an exit or interior zone contained a fault
during closing. The alarm sounder and keypad sound continuously until the system
is disarmed (or timeout occurs). An “Exit Alarm” message is sent to the central
station.
Also results if an alarm from an exit or interior zone occurs within 2 minutes after
the end of an Exit Delay.
CHECK
CHECK
indicates that a problem exists with the displayed zone(s) and requires attention.
Note: The control will sense a high resistance in the loops on hardwired zones 2–8
and display “CHECK” and the affected zone number when the system is in the
disarmed mode. It will not be possible to arm the system as long as this condition
exists (unless this zone is bypassed). If the system is in the armed mode when the
high resistance condition occurs, this display will not appear, but will do so as soon
as the system is disarmed. Check the sensor or loop wiring for the displayed zone.
ALARM 1xx
FAULT 1xx
CHECK 1xx
1xx
1xx
1xx
indicates that communication between control and a zone expander or wireless
receiver is interrupted, where “xx” is the device address. Check the wiring and
DIP switch settings on the units.
If field *199 is set to “1,” all ECP module problems are displayed as “91.”
If there are wireless sensors in the system, the Check condition may also be caused
by some change in the environment that prevents the receiver from receiving
signals from a particular sensor.
91
SYSTEM LO BAT
LO BAT
BAT
BAT
with no zone number indicates that the system's main standby battery is weak.
Busy-Standby
dl
If this remains displayed for more than 1 minute, the system is disabled.
Modem Comm
CC
The system is in communication with the central station for change of function or
status verification.
no display
no display
Power Failure
If there is no keypad display at all and the LEDs are unlit, operating power (AC and
battery) for the system has stopped and the system is inoperative.
If the message “AC LOSS” (Alpha display keypads) or “NO AC” (Fixed-Word display
keypads) is displayed, the keypad is operating on battery power only.
If the battery standby capacity is used up during a prolonged AC power outage, the
control's power will shut down to minimize deep discharge of the battery.
Comm. Failure
Open Circuit
Long Rng Trbl
Bell Failure
RCVR Jam
KEYPAD LOW BAT
Phone Okay
Dialer Off
Test in Progress
Upload Completed
Upload Failed
FC
OC
bF
A communication failure has occurred.
70
Bell supervision failure.
with a zone number and a once-per-minute beeping at the keypad indicates that a
low-battery condition exists in the wireless sensor displayed (zone “00” indicates a
wireless keypad). If the battery is not replaced within 30 days, a “CHECK” display
may occur.
NOTE: Some wireless sensors use a non-replaceable long-life battery which requires
replacement of the entire unit at the end of battery life (e.g., 5802, 5802CP).
The keypad is not receiving signals from the control and sees an open circuit.
Backup LRR communication failure.
90
RF jam detected.
00 BAT
Cd
dO
dd
dC
dF
Wireless keypad low battery
The dialer test has been successful (CID code 601).
The dialer is disabled.
Walk test mode is active(CID code 607).
The upload or download session was completed.
The upload or download session failed before completion.
7URXEOH&RQGLWLRQV
"Check" and
"Battery" Displays
The word CHECK on the keypad's display, accompanied by a
"beeping" at the keypad, indicates a trouble condition in the system.
To silence the beeping for these conditions, press any key.
1. A display of "CHECK" and one or more zone numbers
indicates that a problem exists with the displayed zone(s) and
requires your attention. Determine if the zone(s) displayed are
intact and make them so if they are not. If the problem has been
corrected, the display can be cleared if you enter the OFF
sequence (security code plus OFF key) twice. If the display
persists, CALL FOR SERVICE.
Note: A display of CHECK 70 on Alpha Display keypads
indicates that the wiring connection to the external sounder is
at fault (opened or shorted), and you should CALL FOR
SERVICE. See “BELL FAILURE” on next page. A display of
CHECK 90 indicates that RF interference may be impeding the
operation of wireless sensors* in the system. See “Rcvr Jam”
on next page.
* Not all systems
use wireless
sensors.
2. If there are wireless sensors* in your system, the CHECK
condition may also be caused by some change in the
environment that prevents the wireless receiver from receiving
messages from a particular sensor. CALL FOR SERVICE if this
occurs.
IF YOU CANNOT CORRECT A "CHECK" DISPLAY,
CALL FOR SERVICE.
TYPICAL "CHECK" DISPLAYS
06
AC
CHECK
FIXED-WORD DISPLAY KEYPAD
',)'/
&)(6331;-2(3;
ALPHA DISPLAY KEYPAD
Words or letters in parentheses ( ) are those that are
displayed on Alpha Display keypads.
Other Trouble
Displays
COMM. FAILURE
(or FC)
Indicates that a failure has occurred in
the telephone communication portion of
your system.
CALL FOR SERVICE.
SYSTEM LO BAT
(or BAT with no
zone No.)
Indicates that a low system battery
condition exists. Display is
accompanied by "beeping"* at the
keypad. If this condition persists for
more than one day (with AC present),
CALL FOR SERVICE.
LO BAT
+ zone descriptor
(or BAT with
zone No.)
Indicates that there is a low battery
condition in the wireless transmitter**
number displayed (00 is RF keypad).
Accompanied by a single "beep"* (about
once every 40 seconds) at the keypad.
Either replace the battery yourself, or
CALL FOR SERVICE. If the battery is
not replaced within 30 days, a CHECK
display may occur.
Rcvr Jam
(or CHECK 90)
Wireless part of the system is experiencing
RF interference which may impede
reception from wireless sensors.**
MODEM COMM
(or CC)
Indicates that the control is on-line with
the Central Monitoring Station's remote
computer.
The control will not operate while on-line.
Wait a few minutes — the display should
disappear.
BELL FAILURE
(or CHECK 70)
Indicates that the wiring connection to
the external sounder is at fault (open or
shorted). Accompanied by “beeping” at
the keypad. CALL FOR SERVICE.
* Any “beeping” that
accompanies a trouble
display can be stopped
by depressing any key
on the keypad or by
entering an OFF
sequence (code + OFF)
** Not all systems use
wireless sensors.
Other Trouble
Displays
(Continued)
AC LOSS
(or NO AC)
The system is operating on battery power
only due to an AC power failure.
If only some lights are out on the premises,
check circuit breakers and fuses and
reset or replace as necessary.
If AC power cannot be restored and a
“low system battery” message appears
(see previous page), CALL FOR
SERVICE.
Busy-Standby
(or dI)
If this message remains displayed for more
than 1 minute, system is disabled. CALL
FOR SERVICE.
OPEN CIRCUIT
(or OC)
The keypad is not receiving signals from
the control. CALL FOR SERVICE.
Long Rng Trbl
(or bF)
If part of your system, back-up Long
Range Radio communication has failed.
CALL FOR SERVICE.
TELCO FAULT
(or CHECK 94)
The telephone line has a problem.
CALL FOR SERVICE.
Total Power Failure If there is no keypad display at all, and the READY indicator
is not lit, operating power (from AC and back-up battery) for the
system has stopped and the system is inoperative. CALL FOR
SERVICE.
In The Event Of Telephone Operational Problems
In the event of telephone operational problems, disconnect the control from the phone line by
removing the plug from the phone wall jack. We recommend that your installer demonstrate this
disconnection on installation of the system. Do not attempt to disconnect the phone connection
inside the control. Doing so will result in the loss of your phone lines. If the regular phones work
correctly after the control has been disconnected from the phone wall jack, the control has a
problem and you should immediately call for service. If upon disconnection of the control, there is
still a problem on the phone line, notify the Telephone Company that they have a problem and
request prompt phone repair service. The user may not under any circumstances attempt any
service or repairs to the security system. Repairs must be made only by authorized service (see
the LIMITED WARRANTY statement for information on how to obtain service).
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising