BPC PowerPro HP Layout
PowerPro HP UPS
High Performance advanced power protection
The British Power Conversion Company
PowerPro HP – Professional high performance protection
Designed to give you a UPS with all the flexibility and
adaptability you need. These modern, compact UPS
have the enviable reputation for consistent reliability,
ease of installation and maintenance making it ideal
for sophisticated computer networks, as well as
Telecommunication, Call Centre, Internet, Defence,
Medical and Process Control equipment.
In today’s environment UPS systems must satisfy the
most challenging applications and the versatile
PowerPro HP Range has all the answers with a wide
choice of power ratings and standby autonomies in
compact and stylish cabinets.
PowerPro HP – 100 Series
The HP 100 Series has single phase input and output ratings ranging
from 1kVA to 40kVA. Some models have internal battery options
but for longer runtimes external batteries can be added with
matching battery cabinets. Compact systems incorporating many
intelligent factors to satisfy the most challenging mission critical
applications.
PowerPro HP – 200 Series
The HP 200 series has three phase input and single phase output
ratings ranging from 6kVA to 60kVA. Suitable for enterprise
applications requiring critical protection for server rooms and the
digital network economy.
PowerPro HP – 300 Series
The HP 300 series has a three phase input and output design.
All models can be supplied with matching battery cabinets.
Primarily intended for the information technology market but
capable of providing for the growing demands of data and mobile
switching centres the PowerPro HP has been extended up to
250kVA in single modules.
The UPS that has the ability to grow
with you
All PowerPro HP models have parallelling capability that can give
you absolute flexibility for customer planning of the future power
requirements or greater system security. Power upgrades or N + I
redundant configuration can be achieved up to a total capacity of
1500kVA.
PowerPro HP UPS
High Performance advanced power protection
PowerPro HP uses a new concept known as Adaptive Control
This allows the UPS multi-standard capability to operate as both an on-line double conversion and line interactive UPS.
MANUAL MAINTENANCE BYPASS CB
AUTOMATIC STATIC BYPASS CB
I/P
AC FILTER
MAINS
CB
HARMONIC
REDUCTION
FILTER
RECTIFIER
INVERTER
ISOLATION
TRANSFORMER
AC FILTER
STATIC
SWITCH
LOAD
CB
OPTIONAL
O/P
BATTERY
CB
BATTERY
On-Line mode
RS232
REMOTE
PARALLEL
combines intelligent double conversion technology with an
isolation transformer to provide additional smoothing and
ensures continuity of supply to the load under the
severest conditions imaginable. PowerPro HP utilises an
advanced six pulse rectifier that automatically supplies the
inverter with filtered DC power and simultaneously
recharges the battery following an interruption of the
mains supply.
The latest high frequency IGBT (Insulated Gate Bi-polar
Transistors) inverter technology converts DC power with
high levels of efficiency into the pure sinewave AC power
used to support the load.The highest quality of output
under varying load conditions is assured by sophisticated
microprocessor based control circuits.
CPU
SIGNALLING AND
COMMAND PANEL
Economy mode (factory option)
can be utilised when the mains is relatively stable.The
intelligent microprocessor based control system takes
advantage of the low energy consumption characteristics
offered by its interactive ECONOMY-MODE
configuration. PowerPro HP switches instantaneously to
on-line operation when the mains fluctuates outside preset parameters to provide perfectly stable output and total
protection not only from more subtle problems such as
low frequency electrical noise and frequency instability.
PowerPro HP’s multi-standard capability allows selection of
either On-Line Mode or Economy Mode to be made from
the control panel.
The British Power Conversion Company
PowerPro HP 100 Series
Ranging from 1kVA to 40kVA
– Single Phase Input and Output
An ultra compact range of on-line double conversion High
Performance UPS utilising the very latest innovation in PWM
and IGBT technology producing increased quality of supply
and reliable performance.
PowerPro HP UPS Systems provide complete protection from
all power problems such as mains failure, sags, spikes, surges,
electrical noise, frequency and voltage stabilisation.
This highly integrated and compact range is mounted on
castors for ease of handling.This permits installation in a
restricted space while still allowing access for maintenance
and significantly reducing installation costs. Combined with
innovative design of the transformers and very low noise, high
volume fans has resulted in an extremely quiet range of units
ideally suited for office environments and noise sensitive
environments.
Features:
■ True double conversion technology
■ Galvanic isolation transformer at the inverter stage
■ High reliability with low maintenance
■ Pure sine wave output
■ High efficiency up to 90%
■ Intelligent battery monitoring to maximise service life
■ Automatic static bypass switch providing no-break transfer
■ Capability for parallel redundant operation if required
■ LCD panel providing real time operational status
■ Recorded power history logs
■ RS232 and dry contacts for communication and remote
monitoring
■ Input / output customisation is available
PowerPro HP UPS
High Performance advanced power protection
PowerPro HP 200 Series
Ranging from 6kVA to 60kVA
– Three Phase Input and Single Phase Output
An advanced flexible range of on-line double conversion High
Performance UPS with all the benefits and features of the HP
100 Series.
Designed to supply tightly regulated and controlled sinewave
power irrespective of mains supply and to a variety of critical
loads.This makes the HP 200 Series ideal for protecting all
types of applications ranging from clean environment network
server room systems through to the most rugged industrial
installations.
HP 200 models have three phase rectifiers with “Soft Start”
control incorporating thyristor controlled bridge circuitry to
limit inrush current and prevent overloading marginally rated
mains supplies.These models provide an excellent solution
for higher power, single phase loads and can also reduce the
need for extensive re-cabling during installation.
PowerPro HP UPS are simple and easy to install with all the
input and output terminals conveniently positioned with front
access, ensuring ease of positioning, trouble free installation
and maintenance. Low MTBF (mean time between failure) and
low MTTR (mean time to repair) are both fundamental to the
PowerPro HP design.The inclusion of an integral manual
bypass switch enables maintenance and service to be carried
out without load disruption, resulting in extremely low
maintenance costs.
Simplicity of Operation
PowerPro HP’s advanced microprocessor control system
provides for automatic control with minimum user
intervention. A simple but concise mimic diagram provides
HP100 & HP200 models an immediate indication of the
system status with in depth information available via a robust
membrane Keypad and 2 line liquid crystal display.
The British Power Conversion Company
PowerPro HP 300 Series
– Three Phase Input and Output
A sophisticated and extended range of on-line
double conversion High Performance UPS with
advanced design concepts that have resulted in a
very compact, highly reliable machine with low
energy density and low audible noise figures
providing a cost effective solution for all large
installations.
Powerful Triple Microprocessor
Control and Monitoring Systems
Ensures peace of mind by managing and monitoring all the
critical rectifier, inverter and static switch functions and
collating operating data for archiving and display. During mains
failure it analyses the battery discharge characteristics and
provides accurate information on the remaining runtime.
Rectifier ‘Soft Start’ Control
Incorporates thyristor controlled bridge circuitry to limit
inrush current and prevent overloading marginally rated mains
supplies. Reduced harmonic Rectifier Clean Version options
are available for your installations where lower levels of
reflected harmonic currents or improved Power Factor
Correction are essential.
Intelligent Battery Monitoring to
Maximise Service Life
Genuine advanced battery care is the key to reducing cost of
ownership and maximum service life. PowerPro HP’s ‘Healthy
Battery’ design philosophy provides you with a two stage
charging process and then an Advanced Battery Management
system which can determine the optimum battery float
voltage from intelligent microprocessor control on the basis
of actual operating conditions.
Automatic and Manual Static
Bypass Switch
Allows for instantaneous transfer to mains or reserve supply
if the power demand of the load exceeds the overload level of
the inverter or a short circuit is experienced. A manual bypass
facility is also provided for routine maintenance and battery
replacement.
PowerPro HP UPS
High Performance advanced power protection
Sophisticated Control and
Monitoring Panel
Control and management of the entire system is achieved at
the touch of a button. PowerPro HP Control Logic manages
all the data concerned with running the UPS and provides real
time operational status to the mimic diagram and 2 line liquid
crystal display.Vital operating information is available on
demand via the membrane keypad and in the event of an
alarm condition a description is automatically displayed.
Robust Transistorised Inverter
Utilising the very latest innovation in IGBT technology
PowerPro HP is able to guarantee increased quality of supply
and reliable performance.The high operating frequency of the
inverter has led to a drastic reduction in the PowerPro UPS
size, making is easier to handle and quieter, with a consequent
improvement in energy efficiency and cost savings. All
PowerPro HP UPS systems provide galvanic isolation at the
inverter stage to maximise safety and reliability and ensure
absolute compatibility with any type of load.
High Reliability with Low
Maintenance
Careful attention to assembly detail and technical design
assures great simplicity with a consequent increase in
reliability.With a mean time between failure (MTBF) of
200,000 hours the PowerPro HP is an established market
leader and with easy access to internal system components a
mean time to repair (MTTR) of just 30 minutes can be
achieved.
Ease of installation
Input and output terminals are conveniently positioned so
that all PowerPro HP UPS are simple and easy to install. Cable
entry is via the conveniently situated aperture in the base of
the cabinet with cable retaining brackets.
The British Power Conversion Company
PowerPro HP Range – Optional accessories
BPC UPS in parallel – One step
beyond redundancy
The BPC philosophy is both simple and elegant. UPS outputs
are connected directly to the users distribution system,
eliminating the vulnerable centralised static switch and control
circuits. PowerPro HP can grow with you and give you
complete flexibility whether you are planning to improve
system security or increase your power requirements.
Redundant, symmetric and hot standby modes are all selected
from the LCD control panel.
Rectifier Clean Version’s
Defining new standards in input power factor correction and
reduction of harmonic currents. Both 12 pulse and 18 pulse
clean version rectifiers are available offering improved power
factor correction up to 0.96 and reducing total harmonic
distortion to less then 5%.
Regenerative Load Option
Unique to PowerPro HP UPS this innovative design can cope
with the most arduous types of high power motor loads such
as lifts or high speed machinery that can feedback current
into the UPS under over-run conditions.This current can
seriously interfere with the operation of normal UPS leading
to shutdown or even damage.The PowerPro HP Regenerative
load option safely suppresses this regenerative current and
allows these difficult loads to be supported without problem.
Remote Digital Signalling for the
UPS
All models can be connected to a remote monitoring panel
(RMP) that allows the possibility to monitor different
parameters from the control panel on the UPS. More than
one RMP can be connected together in cascade for
monitoring your UPS system from several different locations
at the same time.
Further UPS System options
These include input and bypass galvanic isolation
transformers, bypass to load configurations, input / output
customisation, frequency converters, additional relay contact
board allows an additional 7 relays to be provided, earth
leakage monitor, RSC 24 model enables the RS232 interface
to be converted into RS485 for connecting RMP to the UPS
over 20 meter distances, customised enclosures with higher IP
protection ratings, etc.
PowerPro HP UPS
High Performance advanced power protection
Matching external battery
cabinets and open racks
For mission critical applications requiring longer runtimes
or higher specification batteries, extra matching battery
cabinets can easily be added.These have been designed
both technically and aesthetically to comprise an integral
part of the UPS, forming a single unit which can be easily
located without the need for special site considerations.
For larger battery systems or specialist battery
installations, lower cost open or cladded racks can also
be provided.
Installation and support
solutions
The BPC Service department deliver and install complete
UPS systems in even the most demanding environments.
Our commitment is to achieve the highest levels of
customer satisfaction by providing real solutions that
work reliably and meet your specific needs.To ensure
optimum customer care and system performance we go
further by offering a total solutions approach from presales advice and planning right through to installation and
commissioning if required.This commitment to customer
care does not stop here, all PowerPro HP products are
backed by a superb after sales service providing
comprehensive technical support and spare parts.
“Virtual Service” five years free
monitoring and health checks
BPC's devotion to excellence is reflected in the enduring
quality of its products and is matched by an equally
lasting commitment to customer care. Virtual Service is
a unique and totally free service from BPC providing an
on demand monitoring service of the PowerPro HP UPS.
All that is required is an internet connection or a suitable
modem/external phone line and BPC's Technical Support
desk can conduct a remote "service visit" to check the
current status of the UPS equipment.
Virtual Service is available to all BPC customers and
includes a "free" automatic three monthly health check.
Customers with HP service plan packages enjoy an
enhanced Virtual Service program with frequent full
status reports on the UPS and continuing examination of
all the current site operating conditions to ensure
complete "peace of mind".
The British Power Conversion Company
PowerPro HP Range –
Network Management and Monitoring Software
T-Mon Server
Supports Windows 95,Windows 98, XP, NT and Windows
2000 plus LINUX.TMON Server connects a computer to the
UPS and collects data which it communicates to the network.
T-Mon SerCon
SerCon program receives the data from TMON Server and
manages the shutdown event on the network clients
computers. In addition to the normal “SerCon” automatic
shutdown program TMON also provides source code so that
a programmer can compile their own requirements.
T-Mon Admin (optional)
TMON Admin is developed to provide UPS
management and monitoring in a WAN system. It
supports TCP/IP and SNMP protocols.
TMON Admin allows you to manage, monitor and
collect all the data logs from hundreds of UPS’s which
are connected to the WAN system.
TMON Admin supports multi SNMP agents such as
Megatec SNMP, NetAgent II and USHA. It is possible
to implant OEM SNMP agents MIB’s as a customer
request.
See TMON UPS Manager data sheet for more
detailed information.
MSSU – Multiple Server Shutdown Units
MSSU 8
MSSU 4
CC06 C ABLE
M2501
M2501
M2501
M2501
M2501
M2501-RUPS C ABLE
M2502-RUPS2 C ABLE
M2501
CC06 CABLE
M2501-RUPS C ABLE
Using either the MSSU 4 (4 servers) or MSSU 8 (8
servers) you can shut down servers through the
same UPS System.You can connect more than one
MSSU in series for shutdown of multiple number of
servers. Additional MSSU can be added.
UPS
1. SERVER
RS 232 + ALARM
DRY CONTACT
SNMP Modules
2. SERVER
8. SERVER
SERVERS
Using the SNMP module your PowerPro HP UPS acts
as a network device, this allows it to monitor more
than one UPS connected to your network through
SNMPVIEW software supplied with the module, or
you can monitor the UPS through an Internet
browser. Also allows the possibility to shutdown the
servers or users with Clientmate software that
communicates with SNMP module.
PowerPro HP
100 Series
Technical data
Series Model
HP102
HP103
HP106
HP107
HP110
HP115
HP120
HP130
HP140
Power (kVA)
2
3
6
7.5
10
15
20
30
40
Power (kW)
1.4
2.1
4.2
5.25
7
10.5
14
21
28
70A
96A
140A
192A
Input
Voltage
230VAC Single Phase
Tolerance
+/-15%
By-pass Voltage
Maximum Current absorbed from mains
230Vac +/-10%
13A
18A
31A
37A
48A
Input frequency
50Hz +/-5%
EMI
EN 50091-2 class A
Output
Wave form
True Sine wave
Nominal Voltage
230Vac
Voltage Stability (Balanced Load)
+/-1%
Voltage Stability (Unbalanced Load)
N/A
Voltage Dynamic Step Load (0 to 100% to 0)
+/-5%
Frequency
50Hz
Line synchronised +/-1%
Free running +/- 0.2%
Frequency Stability
On Line Mode efficiency at full load
>88%
Economy Mode efficiency at full load
>98%
Crest factor
3:1
Over load protection
100% – 125% load for 10min.
125% – 150% load for 1min.
>150% load by-pass
Total Harmonic Distortion (THD)
>3%
Short Circuit Protection
Electronic short circuit protection
Batteries
Type
Sealed Lead Acid Maintenance Free
Number of 12V Blocks
14
14
20
20
20
20
26
26
26
Float charging voltage
189Vdc
189Vdc
270Vdc
270Vdc
270Vdc
270Vdc
351Vdc
351Vdc
351Vdc
End of discharge voltage
140Vdc
140Vdc
200Vdc
200Vdc
200Vdc
200Vdc
260Vdc
260Vdc
260Vdc
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
<45 dbA
<45 dbA
<45 dbA
2.09
3.14
4.18
Equalising Boost Charge voltage
Battery cabinet
Internal
External
Automatic circuit breaker
Battery protection
Battery test
Optional
General
Protection degree
IP21
Colour
RAL 7035 (other colour on request)
Dry contacts plus RS232
Communications
T-Mon standard, SNMP module optional
Software
Temperature range
0°C to 40°C
Altitude
<1000m (above sea level)
Relative humidity (non condensed)
Acoustic noise at 1m distance
Heat dissipation at nominal load (kW)
Dimensions (mm) wxdxh
Weight without batteries (kgs)
90% max
<42 dbA
<42 dbA
<45 dbA
<45 dbA
<45 dbA
<45 dbA
0.23
0.34
0.63
0.78
1.04
1.57
265x560x540
265x560x540
265x740x710
265x740x710
265x740x710
265x740x710
50
55
74
77
91
112
485x675x1145 485x675x1145 485x675x1145
250
300
460
PowerPro HP
PowerPro HP
200 Series
Technical data
300 Series
Technical data
HP206
HP207
HP210
HP215
HP220
HP230
HP240
HP260
HP305
HP310
HP315
HP320
HP330
6
7.5
10
15
20
30
40
60
5
10
15
20
30
4.2
5.25
4.2
5.25
7
10.5
14
28
4
8
12
16
24
3 x 50A
3 x 70A
3 x 100A
3 x 9A
3 x 17A
3 x 24A
3 x 31A
3 x 45A
230/400VAC Three Phase +N
+/-15%
230Vac +/-10%
3 x 12A
3 x 17A
3 x 17A
3 x 25A
3 x 25A
50Hz +/-5%
EN 50091-2 class A
True Sine wave
230Vac
+/-1%
N/A
+/-5%
50Hz
Line synchronised +/-1%
Free running +/- 0.2%
>90%
>98%
3:1
100% – 125% load for 10min.
125% – 150% load for 1min.
>150% load by-pass
>3%
Electronic short circuit protection
Sealed Lead Acid Maintenance Free
20
20
20
26
26
26
26
26
30
30
30
30
30
270V
270V
270V
351Vdc
351Vdc
351Vdc
351Vdc
351Vdc
405Vdc
405Vdc
405Vdc
405Vdc
405Vdc
200V
200V
200V
280Vdc
280Vdc
280Vdc
Internal
260Vdc
260Vdc
365Vdc
260Vdc
365Vdc
External
365Vdc
260Vdc
260Vdc
300Vdc
300Vdc
300Vdc
300Vdc
300Vdc
365Vdc
365Vdc
422Vdc
422Vdc
422Vdc
422Vdc
422Vdc
Internal
External
Automatic circuit breaker
Optional
Automatic every 72 hours
IP21
RAL 7035 (other colour on request)
Dry contacts plus RS232
T-Mon standard, SNMP module optional
0°C to 40°C
<1000m (above sea level)
90% max
<42 dbA
<42 dbA
<55 dbA
<55 dbA
0.62
0.78
1.04
1.57
265x740x710
265x740x710
265x741x710
265x742x710
106
110
160
190
<55 dbA
<55 dbA
<55 dbA
<55 dbA
<56 dbA
<56 dbA
<56 dbA
<56 dbA
<56 dbA
2.09
3.14
4.18
6.3
0.4
0.8
1.18
1.6
1.8
550x855x1360 550x855x1360 550x855x1360 550x855x1360 485x675x1145 485x675x1145 485x675x1145 485x675x1145 485x675x114
277
300
460
540
225
235
250
270
322
Series Model
HP340
HP360
HP380
HP3100
HP3120
HP3150
HP3200
HP3250
40
60
80
100
120
150
200
250
Power (kVA)
32
48
64
80
96
120
160
200
Power (kW)
Input
Voltage
230/400Vac Three Phase, 4 wires, +ground
Tolerance
+/-15%
By-pass Voltage
230/400Vac Three Phase +/-10%
3 x 58A
3 x 85A
3 x 110A
3 x 138A
3 x 165A
3 x 220A
3 x 290A
3 x 365A
Maximum Current absorbed from mains
Input frequency
50Hz +/-5%
EMI
EN 50091-2 class A
Output
Wave form
True Sine wave
230Vac
Nominal Voltage
+/-1%
Voltage Stability (Balanced Load)
Voltage Stability (Unbalanced Load)
N/A
Voltage Dynamic Step Load (0 to 100% to 0)
+/-5%
Frequency
50Hz
Line synchronised +/-1%
Free running +/- 0.2%
Frequency Stability
>90%
On Line Mode efficiency at full load
>98%
Economy Mode efficiency at full load
Crest factor
3:1
100% – 125% load for 10min.
125% – 150% load for 1min.
>150% load by-pass
Over load protection
Total Harmonic Distortion (THD)
>3%
Short Circuit Protection
Electronic short circuit protection
Batteries
Type
Sealed Lead Acid Maintenance Free
30
30
30
30
30
30
30
30
Number of 12V Blocks
405Vdc
405Vdc
405Vdc
405Vdc
405Vdc
405Vdc
405Vdc
405Vdc
Float charging voltage
300Vdc
300Vdc
300Vdc
300Vdc
300Vdc
300Vdc
300Vdc
300Vdc
End of discharge voltage
422Vdc
422Vdc
422Vdc
422Vdc
422Vdc
422Vdc
422Vdc
422Vdc
Equalising Boost Charge voltage
Battery cabinet
External
Battery protection
Automatic circuit breaker
Battery test
Automatic battery test once a week
General
Protection degree
IP21
Colour
RAL 7035 (other colour on request)
Communications
Dry contacts plus RS232
Software
T-Mon standard, SNMP module optional
Temperature range
0°C to 40°C
Altitude
<1000m (above sea level)
Relative humidity (non condensed)
90% max
<56 dbA
2.4
45 570x820x1450
484
<60 dbA
3.6
570x820x1450
562
<60 dbA
<60 dbA
<65 dbA
<65 dbA
<65 dbA
<65 dbA
4.8
6
7.2
9
12
15
710x800x1400 1100x800x1600 1100x800x1600 1100x800x1600 1100x800x1600 1100x800x1600
620
710
810
920
1150
1380
Acoustic noise at 1m distance
Heat dissipation at nominal load (kW)
Dimensions (mm) wxdxh
Weight without batteries (kgs)
BPC has an extensive range of products to meet all your power protection demands
Small Home/Office UPS PowerOffice
Line Interactive UPS PowerPal
PowerStar
PowerPrem
Single Phase Double Conversion UPS PowerGem
PowerGem Plus
PowerOn
PowerPro HP 100 Series
Three Phase Double Conversion UPS PowerPro
PowerPro
PowerPro
PowerPro
RM & RT Series
Plus Transformerless Series
HP 200 Series
HP 300 Series
Emergency Lighting Systems PowerLite EL Series
Industrial Applications PowerPro Frequency Converters
PowerMaster SVR Electronic Stabilisers
PowerMaster AVR Servo Stabilisers
DC Solutions Rectifier and SMPS Modules
Rackmount Cabinets PowerRack 19” Enclosures
Options & Accessories Maintenance Bypass Switches
Battery Cabinets & Enclosures
Remote Alarm Panels
Software & Communication PowerCheck
PowerSmart 210U
RUPS
T-Mon
SafeNet
Batteries PowerStor
PowerStor
PowerStor
PowerStor
PowerStor
PS – Sealed Lead Acid 5 year design life
PSL – Sealed Lead Acid 10 year design life
PSLIFR – (2 Volt blocks) Sealed Lead Acid 15 year design life
Gel and Cyclic options
Nickel Cadmium Vented Cells
Generators Wide range of diesel generators
The British Power Conversion Company
BPC Limited
BPC House
Romsey Industrial Estate
Greatbridge Road
Romsey
Hampshire SO51 0HR
United Kingdom
Tel: +44 (0)1794 521200
Fax: +44 (0)1794 521400
e-mail: sales@bpc-ups.com
www.bpc-ups.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising