TECHNICAL DATA SHEET “INFINITY EVO 3300”

TECHNICAL DATA SHEET “INFINITY EVO 3300”
TECHNICAL DATA SHEET “INFINITY EVO 3300”
30 – 40 kVA
3Ph(In) – 3Ph(Out)
GENERAL INFORMATION
POWER
kVA
UPS Type
Nominal output power (Cosϕ 0.9)
Nominal output power (Cosϕ 1.0)
Efficiency (AC ÷ AC)
(ON LINE - Double Conversion)
kVA
kW
@25% load
@50% load
@75% load
@100% load
Efficiency (AC ÷ AC) (Eco Mode)
%
%
kW
kcal/h
°C
°C
°C
°C
%
m
Heat dissipation at nominal load and voltage
UPS ambient temperature
BATTERY ambient temperature
UPS storage temperature
BATTERY storage temperature
Relative humidity (non condensing)
Altitude
Ventilation
Requested cooling air volume
Audible noise level (according to IEC EN 62040-3)
Standard battery type lead acid
Forced
m3/h
dB
n° cells
Protection degree
Electromagnetic compatibility EMI
Safety
Test and performance
Paint
Accessibility
Installation
Dimensions
Weight
Static load
Input/Output cable connection
Transport
Transport mechanical stress
mm
kg
kg/m2
Design standards
B
Descrizione
Description
General upgrade
40
According to “IEC62040-3”
1% power derating every 100m above 1000m up
to max 2000m
Power derating for altitude > 1000 m
Rev.
30
ON LINE – Double Conversion
30
40
27
36
> 88
> 90
> 91
> 92
> 98
2.34
3.13
2.01
2.69
0 ÷ 40
0 ÷ +25
-10 ÷ +70
-10 ÷ +60
< 95
< 1000 (above sea level)
800
900
< 52 db
2 x 180
2 x 186
IP 20
According to “IEC EN 62040-2” (CE marking)
IEC EN 62040-1
IEC EN 62040-3
RAL 7016
Front and top
10 cm from the wall
W = 450 D = 670 H = 1200
140
464
Bottom front side
By wheels
According to “IEC EN 62040-3”
“IEC EN 62040”
“ISO 9001:2008” - “ISO 14001”
Data
Date
Emesso
Issued
Approvato
Approved
07.02.13
F. Berti
E. Simoni
Lingua
Language
Pagina
Page
E
1
di Pag.
of Pag.
6
Codice / Code
OMD97006
Free contact interface
Serial communication interface
Parallel configuration (optional)
On request
Standard: RS232 - USB
Optional: RS485 (ModBus protocol)
Up to 5+1 (Redundant parallel)
Up to 6 (Power parallel)
BLOCK DIAGRAM
1.
2.
3.
4.
5.
6.
Common input rectifier and bypass
Rectifier and battery charger
External battery
Inverter
Emergency line (optional by-pass with backfeed contactor).
Inverter (SSI) and by-pass (SSB) static switch
OMD97006 REV. B
2
UPS INPUT: RECTIFIER AND BATTERY CHARGER
POWER
kVA
30
Input
Vac
%
Hz
%
Nominal input voltage range
Input frequency range
Input power factor
Input current THD at nominal voltage
and THDV <0,5%
@25% load
@50% load
@75% load
@100% load
DC output voltage accuracy
DC output voltage ripple
Battery recharging characteristic
Maximum recharging current
- at nominal load
Bridge rectifier type
Input protection
Inrush input current
Earth leakage current
Nominal current absorbed from mains
(at nominal load and battery charged)
Maximum current absorbed from mains (at nom.
Load, max. recharging current and nominal. input
voltage)
Settable walk-in
Settable hold-off
%
%
% rms
A
A
mA
40
Three-phase + Neutral
400
-20/+15
50 – 60
±5 / ±10 adjustable
> 0.99
< 14
<7
<5
<4
+/- 1%
1% rms
IU (DIN 41773)
10
8
IGBT PFC
Fuses
< maximum nominal current
< 22
A
43
56
A
54
66
sec
sec
Sectable from 5’’ to 30’’
Sectable from 1’’ to 300’’
BATTERY
POWER
External battery
Standard type
Cells number (settable)
Floating voltage at 25°C (settable)
Minimum battery discharge voltage
Inverter input power (at nominal load)
Inverter input current
(at nominal load and minimum Vdc)
Battery Protection (external to the UPS)
Battery Test
kVA
30
40
Maintenance free
2x180 or 2x186
2x406 or 2x418
Settable
Vdc
Vdc
kW
28.58
38.25
A
40.5
54
Fuses
Included as standard
OMD97006 REV. B
3
UPS OUTPUT: INVERTER
POWER
Inverter Bridge
Nominal output power (Cosϕ 0.9)
Nominal output power (Cosϕ 1.0)
Efficiency (DC ÷ AC)
Output
Nominal output voltage (selectable)
Output voltage stability
- Static (balanced Load)
- Static (unbalanced Load)
- Dynamic (step load 20%÷100%÷20%)
- Output voltage recovery time (after step load)
- IEC EN 62040-3
Output frequency (selectable)
Output frequency stability
- Free running quartz oscillator
- Inverter sync. with mains
- Slew rate
Nominal Output Current (@ 400 Vac output)
- Cosϕ 0.9 (leading and lagging)
- Cosϕ 1 (purely resistive load)
kVA
kVA
kW
%
Vac
30
%
%
%
ms
Hz
±1
±2
±5
< 20
Class 1
50 - 60
Hz
Hz
Hz/s
± 0,001
± 2 (other on request)
±1
A
44
39
A
70
94
Elect. short circuit protection, current limited at
above values.
Automatic stop after 5 seconds
Short circuit characteristic
Selectivity
Output waveform
Output harmonic distortion
- Linear Load
- Non Linear Load
- IEC EN 62040-3
Max crest factor without derating
58
52
125% for 10 min
125%/150% for 30 sec
>150% for 10 sec
Overload capability
Short circuit current
40
Modular IGBT (transformerless)
30
40
27
36
> 95
Three-phase + Neutral
380-400-415
Within ½ cycle (Fuse GL 20% In)
Sinusoidal
%
<1
<5
Fully compliant
3:1
OMD97006 REV. B
4
UPS OUTPUT: BY PASS
Automatic static by-pass
Protection
Bypass
Nominal Voltage (selectable)
Range
Nominal Frequency (selectable)
Range
Transfer mode
Vac
Vac
%
Hz
%
Transfer inverter Æ automatic bypass
Retransfer automatic bypass Æ inverter
Overload Capability
Manual By-Pass
Back feed protection
%
Electronic thyristor switch
Fuses
Three-phase + Neutral
380 – 400 – 415
±10
50-60
±(1÷5) ±10 adjustable
Without break
In case of :
- Short circuit
- Battery end of discharge
- Inverter test
- Inverter not operating
- Automatic
- Block on bypass after 6 transfers within 2
minutes, reset by front panel
150 continuously
1000 for 1 cycle
Standard:
- Electronically controlled
- No break
Optional
OMD97006 REV. B
5
OPTIONS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
BATTERY TEMPERATURE VOLTAGE COMPENSATION
INSULATION TRANSFORMER ON BY-PASS
SEPARETED INPUT KIT
VOLTAGE ADAPTATION AUTO-TRANSFORMERS
BACK FEED PROTECTION
RELAY CARD (Eight signals Alarms/Statuses), Free relay contact
SERIAL INTERFACE RS-485 (MOD-BUS protocol)
SNMP ADAPTER
REMOTE MONITORING PANEL
PARALLEL CARD INTERFACE KIT
EXTERNAL BATTERY CABINET
WALL MOUNTED FUSED SWITCH BOX
SPECIAL PAINT
LOAD-SYNC BUS CARD INTERFACE KIT
DIESEL GENERATOR
EXTERNAL EPO AUXILIARY CONTACT
EXTERNAL MBCB AUXILIARY CONTACT
OTHER SOFTWARE SELECTABLE FEATURES
1.
2.
3.
4.
OFF-LINE
RECTIFIER WALK-IN TIME
RECTIFIER DELAY ON STARTUP (HOLD-OFF TIME)
FREQUENCY CONVERTER MODE
OMD97006 REV. B
6