CF3000 Panel.qxd

CF3000 Panel.qxd
Analogue Fire Panels
CF3000 range
Key Features
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
Description
The CF3000 range of intelligent, analogue
addressable control panels, are the first of a
new generation of fire products, to be launched
by Cooper Fire Systems, setting new standards
for functionality, reliability, end user operation
and system flexibility.
Utilising the most modern electronics and
manufacturing techniques we are able to offer a
technically complex range of facilities and
functions yet retain a simple to install, program
and operate, cost effective system solution.
The enhanced fire panel design allied with the
advanced sensing features of the new 300
series analogue detectors, utilising the
COOPER CLogic system
protocol, work to correctly
identify a fire condition,
speedily, yet disregard
non fire conditions, thus
reducing the incidents of
unwanted alarms.
System flexibility is at the
heart of the CF3000. It
offers a system solution for
all applications, be it a small
single loop system to a
large multi panel network.
The modular, distributed system design of the
CF3000 enables it to be configured to meet the
most demanding system requirements of any
commercial or industrial project.
The CF3000 series panels are available in a
1, 2 or 4 loop configuration which can support
Registered Office:Jephson Court, Tancred Close,
Royal Leamington Spa,Warwickshire. CV31 3RZ
1, 2 & 4 Loop options
Touch sensitive display
Soft addressed
EN54 pt2 and 4 compliant
Up to 200 devices per loop
Networkable up to 63 panels
Robust, reliable system protocol
Flexible cause and effect tables
(Pending)
up to 200 addresses per loop, giving a total of
800 possible detection addresses per 4 loop
panel.
For larger sites the CF3000 can be networked
to extend the system capacity up to 63 panels,
providing a total of 252 detection loops.
The CF3000 series panel is available with a
complete range of intelligent, analogue
addressable fire detection sensors and system
ancillary devices.
With the end user in mind the system user
interface is simplicity itself, with a large
320x240 touch sensitive LCD screen
(120 x 90mm viewable area).
The system controls are
menu driven, guiding the
end user in effectively
operating the control panel,
thus providing a simple yet
intuitive means of system
control.
The CF3000 is designed
with not only the end user in
mind
but
also
the
installation contractor
The modular construction,
integrated power supply and large robust
back box, have been designed to allow for
either surface or semi-flush mounting and give
ample access for cable mounting and
termination, thereby ensuring panel installation
is easily achieved.
Tel: +44(0) 1594 541900
Fax: +44(0) 1594 541910
Email: [email protected]
Web Site: www.cooperfire.co.uk
System Overview
System architecture
The CF3000 has been designed to provide a
feature rich analogue addressable fire
system yet ensure a simple installation
process and provide an intuitive end user,
system control interface.
To this end the system architecture h a s b e e n
d e s i g n e d t o a l l o w maximum flexibility with
a minimum of system hardware and internal
wiring.
The
screen
provides
comprehensive
information as well as a full QWERTY keyboard
enabling not only onsite text entry, should
changes be necessary, but also the ability to
add, remove or change a device without
requiring an engineer to attend site.
The interactive menu driven display
p r e v e n t s non-authorised operation of
the system by the use of user pass codes,
which also allow access to the various system
operation levels.
Basic functions such as mute buzzer, scroll
screen are available access level 1
U s e r f u n c t i o n s such as evacuate, silence
alarms, system reset, disable/enable modes,
view log are a v a i l a b l e a t l e v e l 2 a c c e s s .
System
setup,
reconfiguration
analogue values device test are
protected with a level 3 access code.
Change user/engineering codes are protected
with a level 4 access code.
System setup and reconfiguration f u n c t i o n s
a r e p r o t e c t e d v i a a separate engineering
access code.
To further ease end user operation, panel and
system status information is clearly displayed,
with fire and the various system fault conditions
being highlighted by a comprehensive array of
system status LEDs and 96 zone fire L E D s .
The panel consists of 3 core areas,
1. Integral power supply
2. Loop controller interface
3. Display and system controller
An additional printer controller and printer
assembly are offered as an optional facility.
User interface
Based on the very latest technology, the
CF3000 fire detection system introduces many
innovative ideas. F o r e m o s t o f w h i c h i s t h e
l a r g e interactive, touch sensitive, backlit,
20x90mm viewable area LCD screen, through
which it is possible to access the
comprehensive range of CF3000 functions and
facilities.
The touch sensitive screen automatically
configures itself to the function selected
taking the end user quickly to the required
facility.
F u l l s y s t e m m o n i t o r i n g information is
displayed on the large LCD screen in an easy
to understand format.
The system LCD display panel is fitted with
a smoked polycarbonate, h i n g e d f r o n t
c o v e r p r e v e n t i n g unauthorised access to
the system controls.
Scroll display and mute fault buzzer facilities
are accessed via press buttons mounted in the
cover.
Cooper Fire Systems reserves the right to change product specifications without notice. Although every effort is made to ensure accuracy and avoid errors, we reserve the right to
amend any typographical, photographic, printing or clerical error.
System Overview
Each panel via its microprocessor maintains a
non-volatile 1000-event m e m o r y l o g o f
actions and occurrences on the
system.
The CF3000 can be supplied fitted with a high
speed, low maintenance thermal printer with
simple printer r o l l replacement.
System configuration
The
control
panel
system
architecture has been designed in such a way
that system expansion, within a single panel
solution or as part of a multi-panel network, can
be achieved with the minimum amount of
system downtime.
ƒ
63 Panel network capability
The CF3000 control panel can be
configured for operation as a stand alone
1 loop, 2 loop or 4 loop panel or a s p a r t o f a
6 3 p a n e l integrated network system
solution.
ƒ
Soft addressing
Using intelligent, CLogic system protocol, soft
addressing technology is used to provide a
simple efficient system setup procedure
which a l l e v i a t e s t h e n e e d f o r t i m e
consuming device addressing and p o t e n t i a l
p r o b l e m s d u e t o d u e l addressing.
The system ‘auto learn’ facility once activated,
on initial system start up, will scan the panel
loops and allocate an address number to each
device.
ƒ
200 addresses per loop
CLogic system protocol can support
a m a x i m u m o f 2 0 0 addressable
devices per loop.
ƒ
60 sounders per loop
Up to 60 addressable sounders can be installed
on each loop (low setting).
The sounder tone and volume are programmed
via the main panel.
ƒ
4 conventional alarm lines
To augment the system loop sounder
c a pa b i l i t y, t h e pa n e l h a s 4 c onventional
sounder output lines with a total maximum load
of 1.5A.
Registered Office:Jephson Court, Tancred Close,
Royal Leamington Spa,Warwickshire. CV31 3RZ
ƒ
System interface units
An important feature of the CF3000 is its ability
to interface to external equipment.
It achieves this with a range of innovative
system interfaces, each one designed to
integrate the fire s y s t e m w i t h v a r i o u s
c o n t r o l requirements.
The range includes:3 Channel input/output unit
Zone monitor unit
Mains switching input/output unit
4 output sounder controller
Shop unit monitor
ƒ
Spur isolator facility
Another major feature of the CF3000 is the
ability to ‘spur’ analogue detectors from
the loop. Using a CSI350 - spur isolator unit,
this unit p e r m i ts a z o n e a r e a o f 300 series
analogue detectors to be c o n n e c t e d t o t h e
l o o p a s a s p u r. T h e C S I 3 5 0 h a s an
i n t e g r a l s h o r t c i r c u i t i s o l a t o r ensuring
loop integrity should a short circuit fault occur
between the loop and the first device on the
spur.
ƒ
Loop and network repeaters
The CF3000 system repeater panels are
available in 2 models:
CF3000AR is a fully functional
repeater which is connected to a network
and will display all system wide activity and
provide system control.
CF3000PR can be local panel repeater
c o n n e c t e d v i a a l o o p , acting as a
repeater of its connected panel only, o r a
network
r e p e a t e r,
displaying
all
activity on the system network.
ƒ
Loop mounted beam detection
Cooper Fire Systems are now able to offer a
totally integrated loop mounted reflective beam
unit giving savings on both installation and
equipment costs.
ƒ
Intelligent PA/VA
As part of an overall fire strategy Cooper Fire
Systems are able to offer a comprehensive
range of integrated, intelligent PA/VA systems.
Tel: +44(0) 1594 541900
Fax: +44(0) 1594 541910
Email: [email protected]
Web Site: www.cooperfire.co.uk
System Overview
ƒ
Site Monitor
This is a PC based package that is connected
to the network and provides full system
information,
displaying
FIRE,
FAULT,
PRE-ALARM, etc with panel number, type of
device, zone, analogue value and location text.
All events are logged and can be printed when
required.
It is possible to silence, reset and evacuate any
panel on the network from within this program.
Site
ƒ
and evacuation system.
The networking facility ideally lends itself to
large multi panel, multi building sites where
system flexibility is of prime importance,
allowing system wide fire/fault reporting,
co-ordinated programmed evacuation and
system wide cause and effect operation.
Due to the development of the sophisticated
Cooper system protocol software and the use
of advanced electronics the CF3000 is able to
Graphics Package
This is a PC based package that is connected
to the network and provides full system
information,
displaying
FIRE,
FAULT,
PRE-ALARM, etc with panel number, type of
device, zone, analogue value and location text.
All events are logged and can be printed when
required.
It is possible to silence, reset and evacuate any
panel on the network from within this program.
Site Monitor is password protected for security.
offer the seamless integration of the
Monitor graphics and control package, as
as the various PA/VA packages.
Active repeater panels, system printers
mimic panels can all be interfaced to
CF3000 system via the network.
Site
well
and
the
System programming
It is once the CF3000 system has been
installed that the system programming truly
shows the full versatility of the CF3000 in
achieving a successful project handover.
ƒ
Installation
The generously sized control panel enclosure
allows ease of access to all areas within the
panel and is designed for either surface or a
semi flush installation.
External wiring mounting can be from either the
top or rear of the back box simplifying
installation.
With numerous cable screen earthing points
within the enclosure, loop and alarm line cable
termination is effortlessly achieved.
Networking
The Cooper peer-to-peer network enables up
to 63, stand alone, CF3000 panels to be
integrated into a fully co-ordinated fire detection
Site Installer
Site specific system programming is achieved
using our in-house ‘site installer’, configuration
software. This enables the commissioning
engineer to tailor the system operational profile
to exactly the client’s requirements.
The software is windows based and provides
the interface to configure the system for:
ƒ Site - system configuration
ƒ Site text ƒ Cause and effect configuration
ƒ Relay configuration ƒ Double knock
ƒ Coincidence detection ƒ 3 Stage alarm
ƒ Sounder volume ƒ Sounder tone
ƒ Day / night modeƒ Non latching zones
ƒ Non fire input configuration
ƒ Sounder delays ƒ Call point override
ƒ Input and Output programming
Cooper Fire Systems reserves the right to change product specifications without notice. Although every effort is made to ensure accuracy and avoid errors, we reserve the right to
amend any typographical, photographic, printing or clerical error.
System Architecture
The CF3000 system architecture provides total system flexibility
(Upto 63 panels can be installed on the secure network)
Sensor
Sensor
base sounder
Repeater panel
IP65 Loop
Sounder
Shop monitor
unit
4 way sounder
controller unit
Base sounder
Maximum loop length 2 Km
Callpoint
Shop monitor
unit
Sensor
Analogue detector spur
Spur isolator
Sensor
Up to 200 devices per loop
230V ac
I/O unit
Loop
Sounder
Zone monitor
unit
Sensor
Loop beacon
3 Channel I/O
unit
Fire signal to manned station
Up to 63 panels on network
Registered Office:Jephson Court, Tancred Close,
Royal Leamington Spa,Warwickshire. CV31 3RZ
PA/VA unit
Tel: +44(0) 1594 541900
Fax: +44(0) 1594 541910
Email: [email protected]
Web Site: www.cooperfire.co.uk
Technical Data
Specifications
Type
Configuration
Max. number of loops
Loop capacity
Panel alarm line outputs
Netw ork panel capacity
Standards
Control panel
Integral pow er supply
EMC
Approvals
LPCB
Com patibility
CF3000 Analogue control panel
4
200 addresses
4
63
EN54 pt2
EN54 pt4
CE Marked (EEC89/336)
(Pending)
Series 300 analogue equipment
Pow er
Operating voltage
Batteries
Standby
Mechanical
Back box:
Front door:
Colour
230V ac, 50Hz, +10%, -15%
2x12Vdc, 12Ah SLA
24 hours + 30 mins alarm
*Upgradeable to 72 hours
Mild steel - (pow der coated)
PC/ABS, rating - UL94V0
Silver (pantone - 577c )
Black
Cable entry
Top of back box
Rear of back box
Bottom of back box
Panel mounting
Dim ensions
24 hour standby
72 hour standby
Weight
Including batteries
Including batteries
Excluding batteries
Environm ental
IP rating
Temperature
Humidity
System Printer
Characters per line
Paper type
Order reference
Wiring - loops
Recommended cables
Wiring - netw ork
Recommended cables
35X20mm knockouts
12X20mm knockouts
4x20mm knockouts
Surface or Flush
395mm(H)x495mm(W)x170mm(D)
395mm(H)x495mm(W)x275mm(D)
17Kg - 24 hour standby
29Kg - 72 hour standby
9Kg
IP30 - For indoor applications
-5 to +40 degree C
10% to 90% (non condensing)
40
58x46mm thermal roll
CFS printer roll
Panel system indicators
Display/user controls
System Status LED’s
System
Maximum loop load
Maximum loop load at 1 Km
Maximum loop load at 2Km
Inputs
Class change
Outputs
Alarm lines - panel
maximum load
Alarm output fuses
End of line resistor
Fire routing equipment
Maximum load
Fuse (PTC2)
End of line resistor
Fire protecting equipment
Maximum load
Fuse (PTC2)
End of line resistor
Fault routing equipment
Maximum load
Fuse (PTC2)
End of line resistor
Auxiliary relay
Maximum load
Fuse (PTC4)
**Auxiliary 24V dc supply
Nominal voltage
Fuse (PTC5)
Maximum current
320x240 Touch sensitive,
backlit display (w hite on blue)
Pow er on, Fire, General fault,
System fault, Charger fault,
Sounder fault, General disable,
General test, Delayed output,
FRE, 96 Zone fire LED’s
500 mA
400 mA
300 mA
Operated by volt free contact
1.5A
1.6A - (F1/F2/F3/F4)
6K8
60mA
100mA polysw itch
6K8
60mA
100mA polysw itch
6K8
30mA
100mA polysw itch
6K8
1A @ 24V dc
1.35A polysw itch
24V dc ±10%
100mA polysw itch
30mA
**This output is not used for fire protecting or fire routing
equipment. Pow er taken from this output effects standby duration.
RS485 Port
Maximum cable length
2Km
Min. recommended cable
1mm² (screened)
This is the serial output port for driving the CF3000 repeater panel
and mimic panel. The output is short circuit protected.
RS232 Port
Dracka Firetuf and Firetuf enhanced
Min. recommended cable
Tw isted pair
Dracka Firetuf data cable
This is the serial output port for driving an external modem.
Cooper Fire Systems reserves the right to change product specifications without notice. Although every effort is made to ensure accuracy and avoid errors, we reserve the right to
amend any typographical, photographic, printing or clerical error.
Technical Data
Sensor wiring schematic and dimensions
Panel dimensions
Order codes
CF3000/1/S
CF3000/2/S
CF3000/4/S
CF3000/1/P/S
CF3000/2/P/S
CF3000/4/P/S
1 Loop panel - silver
2 Loop panel - silver
4 Loop panel - silver
1 Loop panel c/w printer - silver
2 Loop panel c/w printer - silver
4 Loop panel c/w printer - silver
Registered Office:Jephson Court, Tancred Close,
Royal Leamington Spa,Warwickshire. CV31 3RZ
CF3000/1/B
CF3000/2/B
CF3000/4/B
CF3000/1/P/B
CF3000/2/P/B
CF3000/4/P/B
1 Loop panel - black
2 Loop panel - black
4 Loop panel - black
1 Loop panel c/w printer - black
2 Loop panel c/w printer - black
4 Loop panel c/w printer - black
Tel: +44(0) 1594 541900
Fax: +44(0) 1594 541910
Email: [email protected]
Web Site: www.cooperfire.co.uk