DDC3003 DDC Central Control Unit

DDC3003 DDC Central Control Unit
Technical data sheet 2 . 5 0 - 1 0 . 0 0 3 - 0 1 - e n
Device description
DDC3003 DDC Central Control Unit
DDC3003 DDC Central Control Unit
Basic functions
DDC Central Control Unit for closed- and open-loop
control, optimization, and monitoring functions
·
manual operator control level with push-buttons and
illuminated LCD display
·
direct connection to BMS Central Control Station or
modem connection
·
12 DDC control loops heating / ventilation,
expandable to
21 DDC control loops over DDC software menu fixed
setpoint
·
functional expansion with DDC software menus
·
comprehensive PLC-functions with 499 flags, 99 timers as well as time programs.
·
up to 99 DDC Central Control Units in the bidirectional data exchange (peer-to-peer)
·
permanent system monitoring of the bus communication and all connected DDC components
·
customized plaintexts possible for every parameter
·
error/malfunction message memory, event log with date and time
·
automatic summer / winter time switching
·
interactive dialog in the plaintext for the query and entry of the DDC data, such as current values, setpoints and
times
·
complete operation of the entire DDC System from every connected DDC Central Control Unit (Remote Control)
without additional equipment
·
trend values memory readable via modem
·
DDC Central Control Unit optional with maximum load limit (E-Max-function)
Date 23.05.2001
·
page 1/4
Kieback & Peter
GmbH & Co KG
Tempelhofer Weg 50
D-12347 Berlin
Telefon 030 / 600 95-0
Telefax 030 / 600 95 164
Technical data sheet 2 . 5 0 - 1 0 . 0 0 3 - 0 1 - e n
DDC3003 DDC Central Control Unit
Device description
Technical data
Bus connection
Interfaces
Central Control Unit Bus;
Z-Bus
field bus; F-Bus
Control Cabinet Bus;
SBM-Bus
serial RS232
PCMCIA
operating voltage
Fuses
address switch
Displays
switch / push-button
processor
Memory
operating system
power failure data backup
deg.enclosure protection
ambient temperature
ambient humidity
Enclosure
front panel section
Weight
identification
page 2/4
99 DDC3000 Central Control Units; 1000m,
3000m with drivers; 100kBaud
63 Field Bus Module FBM, Field Bus Reg. FBR;
2000m; 20kBaud, CAN
16 Control Cabinet Bus Module SBM;
200m; 40kBaud, CAN
building management system BMS, modem,
operator display,
printer (optional connection to diagnostic jack)
for memory card; update, data backup / recovery
(behind the front panel)
code key; device diagnosis
diagnostic jack
for DDC Central Control
24V AC ±10%; 50..60Hz; 14VA; 058A
Unit
for Field Bus Module FBM 12V DC +/-20%
mains fuse, T 0.63A
00 .. 99 with 2 turning knobs; Central Control Units address; (behind the front
panel)
4x 20-character illuminated LCD, LED bus, LED Error
30 push-buttons
68302; 32 Bit; 16MHz
1MByte RAM; 2MByte Flash-PROM
PSOS 1.20; programming language C; realtime-capable; multitask-capable:
10 years, battery-buffered clock component
IP40
0..45°C
in operation: 20..80%rF, non-condensing
shut down: 5..90%rF, non-condensing
19" short cassette of plastic, 4-fold cassette
B x H x T ; 202mm x 132mm x 70mm
200.4mm x 112.0mm
0.8kg
CE
Technical data sheet 2 . 5 0 - 1 0 . 0 0 3 - 0 1 - e n
Device description
DDC3003 DDC Central Control Unit
Wiring diagram
FBM..
1..63
20 19 18 17
58
59
60
78 +
79 80
12V DC
0V AC
TX
RX
RS232
P90
F-Bus
Z-Bus
80 79 78
SBM-Bus
DDC3000System
7 6 5
24V AC
24V 50..60Hz
+ -
1
21
12V
17
0
18
+ 19
- 20
38
39
- 40
+
38 39 40
DDC3010
DDC3035
DDC3100
SBM..
1..16
DDC3003
1
Mounting dimensions
3
112,0±0,5
122,5±0,5
189,1±0,5
11,3±0,5
3
Date 23.05.2001
200,4±0,5
page 3/4
Kieback & Peter
GmbH & Co KG
Tempelhofer Weg 50
D-12347 Berlin
Telefon 030 / 600 95-0
Telefax 030 / 600 95 164
Technical data sheet 2 . 5 0 - 1 0 . 0 0 3 - 0 1 - e n
DDC3003 DDC Central Control Unit
page 4/4