Getting Started - Siemens Support

Getting Started - Siemens Support
SIEMENS MICROMASTER
MICROMASTER Vector 6SE32
MIDIMASTER Vector 6SE32
Default Parameters:
The MICROMASTER Vector (MMV) and the
MIDIMASTER Vector (MDV) are a range of frequency
inverters for controlling the speed of three phase AC
induction motors.
Step 1
Connecting up the MMV and MDV
230V Single Phase
400V Three Phase
Press this
green button
(RUN button)
to start the
motor.
Forward/
reverse
While the motor is
'STOP'
turning, press this UP
button and watch as
the motor turns faster
and the value in the
display increases. It
will keep increasing
until it reaches 50 Hz
Hz.
Jog
P
This
Thisisisthe
the
'STOP
STOP' button
button.
When the inverter
reaches 50Hz output,
press this DOWN
'DOWN' button
button
and watch the motor
speed and display value
decrease.
At any time, press the 'STOP' button and watch the
motor stop.
Step 3
Delta connection for
230V 3 phase
Star connection for
400V 3 phase
Note: Motors above 11kW are usually configured
400V Delta / 690V Star.
In this case the motor should be connected in Delta.
Caution: Before installing and
putting this equipment into
operation, please read the
Operating Instructions Manual for
Safety Precautions and Warnings
MIDIMASTER Vector (MDV)
The MDV electrical installation section of the
Operator Instructions Manual shows the position of
the terminals used to connect the power and the
motor.
1
2
3
4
5
6
P051 = 1
P052 = 2
P053 = 6
P054 = 6
P055 = 6
P356 = 6
ON right
ON left
Fixed frequency 3
Fixed frequency 2
Fixed frequency 1
Fixed frequency 6
18/19/20 P061 = 6
P062 = 8
21/22
Fault identification
Warning active
5
6
7
8
16
17
Output
Relays
1
2
Changing the speed of the motor
The default output frequency of the drive is 5Hz (see
Hints and Tips to convert this to RPM). This speed will
probably be too low for most applications and a speed
change may be required. The following steps will allow
you to change the preset value of the inverter output to
the required speed.
Getting Started
Digital input Terminal Parameter Default
Fault Codes:
Step / Action
Display
F001
F002
F003
F004
F005
Press the 'P' button to access the parameter settings.
P000
F074
Press the
P005
Other faults, see manual
button 5 times until the display reads P005.
Overvoltage
Overcurrent
Overload
Overheating of motor (PTC)
Inverter overtemperature
(internal PTC)
Motor overtemperature by I²t
calculation
Press the 'P' button to display the current parameter value.
005.0
Press the
button to change the value to 35Hz. (This
number can be any number between 0 and 50Hz - default.)
035.0
Press the 'P' button to store the new value.
P005
For further Technical Support
Information, and to submit your
suggestions for improvements,
see our Web Site:
Press the
P000
http://www.con.siemens.co.uk
button until the display reads P000.
Press the 'P' button to exit the parameterisation procedure.
The display will alternate between the output frequency and
the frequency set point.
000.0
035.0
The required speed has now been stored.
This method is used to access all parameters.
The drive can now be started by pressing the 'RUN'
button. It will ramp up to the frequency held in parameter
P005 and remain there. To stop the drive press the
'STOP' button, the drive will then ramp down to 0Hz
output.
Siemens plc
Automation and Drives
Varey Road
Congleton
Cheshire CW12 1PH
Great Britain
G85139-H1751-U568-D1
May 1999
English
Order Number: 6SE3286-4BA86
Step 4 Controlling the motor speed with
a potentiometer
A potentiometer can be used to control the running
speed of the inverter. This is achieved by varying the
voltage applied to the analogue input. Connect the
potentiometer to the control terminals shown below.
Starting and stopping of the motor may be achieved
by connecting a switch to the digital input terminals
shown.
The following parameter settings are required
P006 Set to 1 to allow analogue input
P007 Set to 0 to enable control via digital input
Hints and Tips
Commissioning MICROMASTER Vector / MIDIMASTER Vector
Display parameters
Basic parameters
Select display
via P001
Ramp-up time
P002 0-650 sec.
Display frequency,
motor current and
motor speed
P001
0 = output frequency
1 = frequency setpoint
2 = motor current
5 = motor speed (RPM)
Ramp-down time
P003 0-650 sec.
Frequency setpoint
P006
0 = digital
1 = analog
2 = fixed frequency
3 = digital setpoint addition
Keypad control
P007
0 = disable 1 = enable
Parameter protection
P009
0 = only P001-P009 can be
altered
2, 3 = all can be altered.
Motor parameters
Frequently used parameters
Nominal rating plate
motor power factor
P080 0.00-1.00
Minimum motor frequency
P012
0-650Hz
Nominal rating plate
frequency for motor
P081 0-650Hz
Maximum motor frequency
P013
0-650Hz
Nominal rating plate
speed for motor
P082 0-9999 RPM
Automatic restart after mains
failure
P015
0 = disable 1 = enable
Nominal rating plate
current for motor
P083 0.1-300.0A
Start on the fly
P016
0 = disable 2 = enable
Nominal rating plate
voltage for motor
P084 0-1000V
Analogue input P023
0 = 0-10V/0-20mA,
1 = 2-10V/4-20mA,
3 = -10V to +10V
Nominal rating plate
power for motor
P085
0-250kW
Fixed frequency operation
P041-044
P046-049
0-650Hz
Motor current limit
P086 0-250%
Input terminal function
P051-055, 356
Automatic calibration
P088
Selection relay output
P061, 062
DC injection braking
P073 0-200%
Telling the drive about your motor
To get the best performance from your drive,
you should enter information from your motor
ratings plate into certain parameters. The
following diagram indicates the location of the
information and the parameters which should
be entered.
P080 P081
Pulse frequency
P076
See Operator Manual
P084
3_ Mot
IEC 56
IM B3
50Hz
230/400
1LA7053-2AA10
Nr. ED510 3053
12 022
IP54
Rot KL 16 I.CI.F
/Y 60 Hz
440V Y
0.34A
0.14kW
Cos 0.81
0.61/ 0.35A
Cos 0.81
0.12kW
2800 /min
VDE 0530
P083 P082
3360 /min
Control mode
P077
See Operator Manual
Continuous Boost
P078 0-250%
S.F. – 1.15
P085
See Operator Manual for other
parameters
The direction of rotation of the motor can be
reversed during commissioning by changing
over two of the output connections on the
inverter, or by pressing the Forward/Reverse
button.
Parameters P000 to P009 can always be
read or set. Access to all other parameters is
controlled by the contents of P009. The
factory default value is '0' which only allows
access to P000 to P009. Changing its value
to ‘3' allows all parameters to be accessed
permanently. See Operator Manual for the
function of other values of P009.
In case there are problems with the
parameter settings and you wish to start
again, change P944 to '1'. This will reset to
the default settings.
The value displayed in P000 is the output
frequency of the inverter, this is the default
setting but it can be changed by altering the
value in P001. For example, changing P001
to a value of '5' will cause the inverter to
display the RPM of the motor in P000. See
the Operator Manual for other settings of
P001.
The default value (0) of parameter P006
ensures that the drive runs at the frequency
set in P005. In order to control the output
frequency by an analogue input signal, the
value of P006 should be set to '1'. For other
methods of control using P006, see the
Operator Manual.
DIP selection switches are used to select a
range of 0-10V or 0-20mA for the
analogue input. See the Operator Manual for
more information.
An F002 fault is often caused by either too
short a ramp time or too much voltage boost.
An increase in the values in P002 will
increase the ramp time. Alternatively lower
the values in P078 and P079 to reduce the
voltage boost. Please note that if P078 falls
below '100' (default value for MMV) then the
motor may under-perform at low frequencies.
An F001 fault is often caused by attempting
to stop the motor too quickly - increasing the
value in P003 (ramp-down time) will reduce
this possibility.
If the display flashes during operation, the
drive is registering a warning. Check P931
for the cause.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising