Regency IP28 Inbuilt Gas Fire Manual

Regency IP28 Inbuilt Gas Fire Manual
 Manual
Owners &
Installation
LISTINGS AND CODE APPROVALS
These gas appliances have been tested in
accordance with AS4553, NZS 5262 and
have been certified by the Australian Gas
Association for installation and operation as
described in these Installation and Operating
Instructions.
Your unit should be serviced annually by
an authorised service person.
IP28 GAS INBUILT
Models:IP28-NG
IP28-PROPANE
IP28-ULPG
PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE
REFERENCE
WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause
injury or property damage. Refer to this
manual. For assistance or additional information consult an authorised installer,
service agency or the gas supplier.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of
this or any other appliance.
Installation and service must be performed
by an authorised installer, service agency or
the gas supplier.
918-938f
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical switch: do not use any
phone in your building.
Immediately call your gas
supplier from a neighbour's
phone. Follow the gas supplier's instructions.
If you cannot reach your
gas supplier, call the fire
department.
04/07/15
REGENCY
GAS INBUILT FIREPLACE
TO THE NEW OWNER
Congratulations! You are the owner of a state-of-the-art Gas Inbuilt Fireplace by FPI. The Regency
Gas Fireplace Series of appliances has been designed to provide you with all the warmth and
charm of a fireplace, at the flick of a switch. The model IP28 of this series has been approved
by Australian Gas Association for both safety and efficiency. As it also bears our own mark, it
promises to provide you with economy, comfort and security for many trouble free years to follow.
Please take a moment now to acquaint yourself with these instructions and the many features of
your Regency Fireplace.
2
Regency IP28 Gas Inbuilt Fireplace
DIMENSIONS
UNIT DIMENSIONS W/ CONTEMPORARY FACEPLATE
14.911
(379mm)
27.298
(694mm)
18.850
(476mm)
23.327
(593mm)
28.180
(716mm)
37.150
(944mm)
MODULAR FACEPLATE AND INFILL PANEL
1-5/8"
(41mm)
38-5/16"
(973mm)
3/8"
(10mm)
25-7/8"
(657mm)
28-5/16"
(719mm)
33-1/2"
(848mm)
Regency IP28 Gas Inbuilt Fireplace
3
DIMENSIONS
UNIT DIMENSIONS W/ SLIM LINE FACEPLATE
16 - 7/8”
(427mm)
27-5/16”
(693mm)
4
18.850
475.8
23-3/8”
(593mm)
28-5/8” (725mm)
40-1/2” (1030mm)
Regency IP28 Gas Inbuilt Fireplace
DIMENSIONS
DIMENSIONS - OPTIONAL MODULAR FIREPLACE SOLUTION
34-7/8”(886mm)
36-15/16”(938mm)
50-3/16” (1275mm)
18-5/16”(465mm)
49”(1245mm)
DIMENSIONS - OPTIONAL WEATHER BOX
775mm
822mm
5°
10
410mm
819mm
Regency IP28 Gas Inbuilt Fireplace
5
TABLE OF CONTENTS
DATA BADGE
Copy of Data Badge ......................................................4
INSTALLATION
Important Message.........................................................8
For Your Safety...............................................................8
Materials Required.........................................................8
Before You Start.............................................................8
Masonary Minimum Fireplace Opening Dimensions......9
Contemporary Fascia.....................................................9
Slim Line Fascia.............................................................9
Combustible Mock fireplace" Minimum Fireplace opening
Dimensions.....................................................................9
Clearances To Combustibles..........................................9
Optional Modular fireplace solution Clearances...........10
Mock Fireplace kit (zero clearance) installation........... 11
Gas Pipe Pressure Testing...........................................12
Exterior Flue Termination Locations.............................13
Venting and termination................................................14
Aeration Settings..........................................................15
Conversion Kit for NG to LPG Model...........................16
Conversion Kit for NG to ULPG Model.........................17
Optional Stainless steel inner panel install...................21
Switch operation...........................................................22
Log set installation........................................................23
Glass Door installation.................................................24
Contemporary faceplate Installation.............................25
Hearth trim Installation.................................................26
Slim line faceplate Installation......................................27
Optional infill panel Installation.....................................28
Modular faceplate Installation.......................................29
Final Check..................................................................30
Wiring...........................................................................30
Standard wiring............................................................30
6
OPERATING INSTRUCTIONS
Operating Instructions .................................................31
Lighting Instructions.....................................................31
Shutdown Instructions..................................................31
First Fire.......................................................................31
Remote Control ...........................................................31
Copy Of Lighting Instruction Plate................................33
Normal Operating Sounds Of ......................................33
Gas Appliances............................................................33
Resetting the unit.........................................................33
MAINTENANCE
Door Glass ..................................................................35
Replacement................................................................35
Glass Gasket................................................................35
Convection Fan replacement.......................................36
Combustion Fan replacement......................................37
Pressure switch replacement.......................................38
Valve assembly replacement........................................39
PARTS LIST
Main Assembly.............................................................41
Contemporary Faceplate Assembly.............................42
Slim line Faceplate Assembly.......................................42
WARRANTY
Warranty.......................................................................43
Regency IP28 Gas Inbuilt Fireplace
SAFETY LABEL
This is a copy of the label that accompanies each Regency IP28 Gas Inbuilt fireplace. We have printed a copy of the contents here for your review.
DATA BADGE NOTE: R
egency units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the
correct one.
(Australia Only)
Regency IP28 Gas Inbuilt Fireplace
7
INSTALLATION
IMPORTANT MESSAGE
BEFORE YOU START
The Regency Gas Inbuilt must be installed in accordance with these instructions. Carefully read all
the instructions in this manual first.
INSTALLATION AND REPAIR SHOULD
BE DONE ONLY BY AN AUTHORISED
PERSON.
Note: Failure to follow these instructions could
cause a malfunction of the heater which
could result in death, serious bodily injury, and/or property damage. Failure to
follow these instructions may also void
your fire insurance and/or warranty.
1) The appliance shall be installed in accordance
with the manufacturer's installation instructions,
local gas fitting regulations, municipal building
codes, water supply regulations, electrical wiring regulations, with AS5601. (AGA gas installation code) NZS 5262(New Zealand). Special
conditions ie. marine environment, should be
avoided.
FOR YOUR SAFETY
2) The appliance should be inspected before
use and at least annually by an authorised
service person. More frequent cleaning may
be required due to excessive lint from carpeting, bedding material, etc. It is imperative that
control compartments, burners and circulating
air passageways of the appliance be kept clean
and free from excessive lint from carpeting.
This appliance requires air for proper combustion.
Always provide adequate combustion and ventilation air. Follow instructions and information in the
current AS5601, NZS 5262 or local codes. Consult
the "authority having jurisdiction" to determine the
need for a permit prior to starting the installation.
3) Always connect this space heater to a approved
flueing and termination provided. Flue to the
outside of the building envelope. Never flue to
another room.
MATERIALS REQUIRED
4) Inspect the flueing system annually for blockage
and any signs of deterioration.
A 240 Volt AC power cord is hooked up to the unit.
Plug 3 wire cord into a suitable receptacle. Do not
cut the ground terminal off under any circumstances.
5) Any safety glass removed for servicing must
be replaced prior to operating the appliance.
When connected with 240 volts, the appliance
must be electrically grounded in accordance with
local codes.
This unit is polarity sensitive and will not
operate if polarity is incorrect.
The power connection must be accessible with
the appliance installed as per AS5601.
8
6) To prevent injury, do not allow anyone who is
unfamiliar with the operation to use the fireplace.
GAS CONNECTION WARNING
Only persons licensed to work with gas piping
may make the necessary gas connections to
this appliance.
Regency IP28 Gas Inbuilt Fireplace
INSTALLATION
MASONARY MINIMUM
FIREPLACE OPENING
DIMENSIONS
(CONTEMPORARY FASCIA)
The minimum fireplace dimensions for the
Regency gas space heater when using the
Contemporary Fascia are shown in the following diagrams:
NOTE: ALLOW FOR SIDE GAS CONNECTION - IF REQUIRED
COMBUSTIBLE
"MOCK FIREPLACE"
MINIMUM FIREPLACE
OPENING DIMENSIONS
The minimum fireplace dimensions for the
Regency gas space heater when installing into
a combustible mock fireplace are shown in the
following diagrams:
(For Contemporary Fascia)
27-1/2” (699mm)
450mm
15-1/8” (384mm)
770mm
CLEARANCES TO
COMBUSTIBLES
Minimum Clearances to Combustibles
From Unit
A
2" / 51mm
B
39-3/8" / 1000mm
C
11" / 279mm
Sides
Ceiling
Mantel
Max. Mantle Depth E
12" / 305mm
(see Dia. 2)
Min. Alcove Width
Max. Alcove Depth
44-7/8" / 1139 mm
36" / 914 mm
F
G
*No hearth required.
27-1/2” (699mm)
702mm
23-1/2” (597mm)
770mm
15-1/8” (384mm)
(SLIM LINE FASCIA)
Mantel Clearances
The minimum fireplace dimensions for the Regency
gas space heater when using the Slim line Fascia
are shown in the following diagrams:
NOTE: ALLOW FOR SIDE GAS CONNECTION
- IF REQUIRED
490mm
(For Slim line Fascia)
20
770mm
27-1/2” (699mm)
18
10
8
6
4
2
0
12
12" Mantel
(305mm)
490mm
17” (432mm)
16
14
10
8
770mm
28-7/8” (735mm)
3-1/2" (89mm)
Mantel
12
6
4
20” (508mm)
11" (279mm)
2
Top
Faceplate
702mm
23-1/2” (597mm)
0
Side View
490mm
17” (432mm)
Regency IP28 Gas Inbuilt Fireplace
9
INSTALLATION
OPTIONAL MODULAR FIREPLACE SOLUTION CLEARANCES
36”
(914mm)
51-7/16” (1305mm)
51-7/16” (1305mm)
39-3/8” (1000mm)
1-7/16”
(37mm)
25-7/8”
(655mm)
20-5/8”
(523mm)
33-7/16” (848mm)
10
Regency IP28 Gas Inbuilt Fireplace
IP28
INSTALLATION
MOCK
MOCK FIREPLACE
FIREPLACE KIT
KIT (ZERO
(ZERO CLEARANCE)
CLEARANCE) INSTALLATION
INSTALLATION
2
Side Brackets
1
Insulation Blanket
770mm
770mm
450mm
Standoffs
490mm
6
Contemporary Fascia
Low Profile Fascia
Zero Clearance Kit
COMBUSTIBLE MOCK FIREPLACE KIT INSTALLATION:
Minimum cavity size for Low profile faceplate:
702mm Height x 770mm Width x 490mm Depth
770mm
770mm
Minimum cavity size for Contemporary faceplate:
702mm Height x 770mm Width x 450mm Depth
10mm
702mm
702mm
VENTING CLEARANCES: 10mm is required all around
venting
490mm
490mm
INSTALLATION OF MOCK FIREPLACE KIT:
1)
Install top two 110 mm stand offs to the top of unit.
Install two 67 mm stand offs to the back of unit - install two 55 mm stand offs to the each side of unit.
2)
Install left and right side nailing flange.
3)
Lay insulation blanket on top of unit so it is flush and tight against backside of faceplate.
4)
Unit is now ready for install into a combustible cavity that has the above mentioned clearances.
Insulation blanket
Top standoffs x 2
Side Nailing Flange x 2
1 on each left & right
Back standoffs x 2
Side standoffs x 2
1 on each side
NOTE: Please adjust nailing flanges in relationship to either Contemporary or Low Profile Faceplate. Faceplate needs to be flush against finished wall.
Regency IP28 Gas Inbuilt Fireplace
918-971
11
1
11/24/10
INSTALLATION
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply
piping system by closing its individual manual shutoff valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 3.45 kPa (14" w.c.).
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note:
To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1) Make sure the valve is in the "OFF" position.
S.I.T. Valve Description
1)
2)
3)
4)
5)
On-Off Solenoid Valve EV1
On-Off Solenoid Valve EV2
Inlet Pressure Test Point
Outlet Pressure Test Point
Connection for Pressure Regulator/
Combustion Chamber Compensation
6) Pressure Regulator for Minimum and
Maximum Outlet Pressure
7) Gas Outlet Pressure Electric Modulator
8) Pilot Outlet
9) Main Gas Outlet
10)Side Outlet
2) Loosen the "IN" (# 3) and/or "OUT" (# 4)
pressure tap(s), turning counterclockwise with
a 1/8" wide flat screwdriver.
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" (8mm) ID hose.
4) Seal and or check the pilot outlet (# 8)
5) The pressure check should be carried out
with the unit burning and the setting should be
within the limits specified on the safety label.
6) When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Screw should be snug, but do not over tighten.
Install to AS5601 (Australia) /
NZS 5262 (New Zealand)
12
Regency IP28 Gas Inbuilt Fireplace
INSTALLATION
EXTERIOR FLUE TERMINATION LOCATIONS
Minimum clearances required for balanced flue terminals or
the flue terminals of outdoor appliances
according to AS5601-2004 (AGA gas installation code) or NZS 5262 (New Zealand)
and local authorities having jurisdiction.
a
b
c
d
e
f
g
h
j
k
Minimum C
learance (mm)
Below eaves, balconies or other projections:
- Appliances up to 50 MJ/h input
300
- Appliances over 50 MJ/h input
500
From the ground or above a balcony
300
From a return wall or external corner
500
From a gas meter (M)
1000
From an electricity meter or fuse box (P)
500
From a drain or soil pipe
150
Horizontal from any building structure (unless appliance is approved
for closer installation) or obstruction facing a terminal
500
From any other flue terminal, cowl or combustion air intake
500
Horizontally from an openable window, door, or non-mechanical air inlet, or
any other opening into a building, with the exception of sub-floor ventilation
(see also Note (I)):
- Appliances up to 150 MJ/h input
500
- Appliances over 150 MJ/h input
1500
Vertically below an openable window, door, or non-mechanical air inlet,
or any other opening into a building, with the exception of sub-floor ventilation
(see also Note (I)): see table below
Clearance 'k' in mm
Space Heaters
Up to 50 MJ/h
All Other Appliances
Up to 50 MJ/h
input
150
Over 50 MJ/h input
Over 150 MJ/h
to 150 MJ/h input
500
1000
input
1500
(I) For mechanical air inlets, including spa blowers, the clearance 'j' and 'k' shall be 1500 mm in all cases.
(II) All distances shall be measured vertically or horizontally along the wall to a point in line with the nearest par to of the terminal.
(III)Prohibited area below electricity meter or fuse box extends to ground level.
(IV)A flue terminal of this type shall not be located under a roofed area unless the roofed area is fully open on at least two sides and a free flow of air at the
appliance is achieved.
Regency IP28 Gas Inbuilt Fireplace
13
INSTALLATION
VENTING AND TERMINATION
This flueing system in combination with the IP28 unit has been tested and listed as a power flue system by the Australian Gas Association.
The termination location must conform to AS5601 as per the diagram in the "Flue Termination Location" section of the manual.
Venting cannot be run vertically.
Venting must have slight downward slope towards terminal.
Masonry and Mock Fireplace Installations:
IP28 must be fitted with the venting and terminal provided.
Ensure cavity is prepared and ready to accept unit and proper measurements are taken to ensure proper vent length and sealing of the terminal and venting.
Preparation of venting for Installation
Maximum and minimum vent lengths:
MAX LENGTH: 605mm
MIN LENGTH: 130mm
NOTE: All vent lengths must have 0.4 degree slope downwards.
24”
605mm
5”
130mm
THIS UNIT MUST ALWAYS
TERMINATE / VENT DIRECTLY TO THE
OUTDOORS.
10mm
CLEARANCES TO COMBUSTIBLES: 10mm is required all around the outer pipe.
1)Install inlet tube to back of unit with screws provided and mark ‘’cut line’’. Remove inlet tube from unit and cut tube to proper length to ensure
sealing at the terminal end.
2)Do the same as above for the outer tube. Secure to unit, ‘’mark cut line’’, remove from unit, and cut tube to proper length to ensure sealing at the
terminal end.
3)Re-install both the inner exhaust tube and outer fresh air tube to the unit.
Be sure not to damage the gasketing. Ensure both the inner and the outer are flush on the ‘’terminal side’’ and measurements are correct.
Once the venting is properly secured to the unit at the correct measurements for the cavity, the unit is now ready for installation.
14
Regency IP28 Gas Inbuilt Fireplace
INSTALLATION
System Data
IP28
Burner Inlet Orifice Sizes:
NG
Propane
Burner #39
#53
Max. Input
NG
28.8 mj
Propane
28.8 mj
ULPG
21 mj
Supply Pressure NG
1.13 kPa
Propane
2.75 kPa
ULPG
2.75 kPa
Manifold Pressure HIGH
NG
0.88 kPa
Propane
2.49 kPa
ULPG
2.49 kPa
ULPG
#55
LOW
0.4kPa
1.6kPa
1.6kPa
Electrical: 240 V. 50Hz.
Circulation: High/LO speed fan,
Log Set: Ceramic fibre, 4 per set.
Aeration Setting
NG
7.94mm open
Propane 15mm open
ULPG 15mm open
AERATION SETTINGS
The burner aeration is factory set but may need adjusting due to either the local gas supply, air supply or altitude. This adjustment is performed by the installer.
(Close the aeration for a more yellow flame, or open it to make the flame bluer). Please adjust and lock into place via screw.
NG:
7.94mm open
LPG
15mm open
ULPG
15mm open
Note: Any damage due to carboning resulting from improperly setting the aeration is NOT covered under warranty.
Regency IP28 Gas Inbuilt Fireplace
15
INSTALLATION
Conversion Kit for NG to LPG Model
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !!
Conversion Kit 456-967 Contains:
Qty. Part #
1 904-345
1 908-528
1 918-272
1 919-107
Description
Burner Orifice #53
Red "LPG" label
Label "Converted to ULPG"
Instruction Sheet
1) Shut off the gas supply and unplug the power
cord.
2)Remove the primary guard and faceplate.
Unplug polarized plug for the switches.
Minimum pressure: Turn unit "ON" to it's
lowest input rating by setting the burner
switch to "LOW". While holding the nut (B)
with a wrench, screw in the screw (C) to
increase the pressure and screw it out to
decrease it. Use a screwdriver 6 x 1 blade.
NOTE: The outlet pressure must be set to
minimum 1.60 kPa.
After carrying out all adjustments, block the
setting screws with paint, taking care not to
obstruct the breather orifice of the pressure.
Put back the modulator plastic cap.
WARNING: To ensure the correct operation of the modulator it is necessary that
the plastic cap (A) is returned to its original
location.
3) Remove the front door.
4) Remove logs.
5) Remove the grate.
6) Remove the burner and adjust the aeration
setting to 15 mm fully open.
7) Remove burner orifice with a 1/2" wrench and
discard. Use a wrench to hold on to the elbow
behind the orifice.
8) Reinstall new burner orifice LPG stamped #53
and tighten.
9) Stick the conversion label "This unit has been
converted to LPG" over top of the serial number
decal.
10)Replace the yellow "NG" label with the red
"LPG" label.
11)Reverse steps 6-2.
12)
Adjusting the Outlet Pressure
All the adjustments must be carried out in the following order:
Remove the modulator plastic cap (A) using
needle nose pliers.
Maximum pressure: Turn unit "ON" to it's
highest input rating by setting the burner switch
to "HIGH" Screw in the nut (B) to increase the
outlet pressure and screw it out to decrease
it. Use a 10 mm wrench.
NOTE: The outlet pressure must be set to
maximum 2.49 kPa.
A
B
C
Figure 1
13)Turn on gas supply and plug in power cord.
14)At the end of all setting and adjustment
operations, check electrical installation and
gas leaks.
15)Check operation of flame control.
16)Check for proper flame appearance and
glow on logs.
Installer Notice:
These instructions must be left
with the appliance.
WARNING:When adjusting maximum pressure do not screw the nut in fully.
If unable to obtain 2.49kPa outlet,
check inlet pressure is adequate.
Damage may occur to the gas valve
if maximum pressure adjustment is
fully screwed in.
16
Regency IP28 Gas Inbuilt Fireplace
IP28
INSTALLATION
Conversion
Kit Kit
for for
NGNG
to ULPG
Model
Conversion
to ULPG
Model
THIS THIS
CONVERSION
MUSTMUST
BE DONE
BY ABY
QUALIFIED
GAS GAS
FITTER
IF INIFDOUBT
DO NOT
DO THIS
CONVERSION
!!
CONVERSION
BE DONE
A QUALIFIED
FITTER
IN DOUBT
DO NOT
DO THIS
CONVERSION
!!
Conversion Kit # 456-967 Contains:
Qty. Part #
1 904-575
1 908-273
1 918-272
1 919-121
1 919-107
Description
Burner Orifice #55
Red "ULPG" label
Label "Converted to ULPG"
ULPG data badge overlay
Instruction Sheet
1) Shut off the gas supply and unplug the power
cord.
Minimum pressure: Turn unit "ON" to it's
lowest input rating by setting the burner
switch to "LOW". While holding the nut (B)
with a wrench, screw in the screw (C) to
increase the pressure and screw it out to
decrease it. Use a screwdriver 6 x 1 blade.
NOTE: The outlet pressure must be set to
minimum 1.60 kPa.
2) Remove the primary guard and faceplate.
Unplug polarized plug for the switches.
After carrying out all adjustments, block the
setting screws with paint, taking care not to
obstruct the breather orifice of the pressure.
3) Remove the front door.
Put back the modulator plastic cap.
4) Remove logs.
WARNING: To ensure the correct operation of the modulator it is necessary that
the plastic cap (A) is returned to its original
location.
5) Remove the grate.
6) Remove the burner and adjust the aeration
setting to 15 mm fully open.
7) Remove burner orifice with a 1/2" wrench and
discard. Use a wrench to hold on to the elbow
behind the orifice.
8) Reinstall new burner orifice ULPG stamped
#55 and tighten.
C
Figure 1
14) At the end of all setting and adjustment
operations, check electrical installation and
gas leaks.
15) Check operation of flame control.
16) Check for proper flame appearance and
glow on logs.
10) Replace the yellow "NG" label with the red
"ULPG" label.
Installer Notice:
These instructions must be left
with the appliance.
12)
B
13) Turn on gas supply and plug in power cord.
9) Stick the conversion label "This unit has been
converted to "ULPG" over top of the serial
number decal.
11) Reverse steps 6-2.
A
Adjusting the Outlet Pressure
All the adjustments must be carried out
in the following order:
Remove the modulator plastic cap (A) using
needle nose pliers.
Maximum pressure: Turn unit "ON" to it's
highest input rating by setting the burner switch
to "HIGH" Screw in the nut (B) to increase the
outlet pressure and screw it out to decrease
it. Use a 10 mm wrench.
NOTE: The outlet pressure must be set to
maximum 2.49 kPa.
WARNING:
When adjusting maximum pressure do not screw the nut in fully.
If unable to obtain 2.49kPa outlet,
check inlet pressure is adequate.
Damage may occur to the gas valve
if maximum pressure adjustment is
fully screwed in.
Regency IP28 Gas Inbuilt Fireplace
919-107
1
17
01/20/12
IP28
INSTALLATION
OPTIONAL MODULAR FIREPLACE SOLUTION INSTALLATION
OPTIONAL MODULAR FIREPLACE SOLUTION INSTALLATION
Follow these instructions to the install the Optional Modular Fireplace Solution
See Installation Manual for overall dimensions and clearances.
Required components
IP28 unit
Modular Fireplace Solution (comes with faceplate
Venting Kit
Before you begin:
Ensure the Modular Fireplace Solution (MFS) is positioned so the gas and electrical connections can enter from the bottom or the back.
1) Follow the installation instructions for the venting and termination as referenced in the installation manual. Please note: WHEN IP 28 IS INSTALLED
WITHIN THE MFS THE UNIT IS RAISED. ENSURE YOUR HOLE TO CENTER IS MARKED AND CUT ACCORDINGLY.
2) Once the hole is prepared to install the venting, place the MFS center of the hole and flush against the wall and position the gas line and electrical
accordingly within the MFS. Secure the MFS to the wall using the screws provided. See screw locations in diagram below.
Note: Front panel shown as transparent to show screw locations.
3) Ensure venting is secured to unit and slide unit carefully into the MFS. NOTE: SLIDE UNIT IN PARTIALLY TO ALLOW ACCESS TO CONNECT
GAS AND ELECTRICAL. Once gas and electrical are connected, slide unit in completely.
18
919-017
1
Regency IP28 Gas Inbuilt Fireplace
05/02/11
IP28
INSTALLATION
4) Secure unit to the MFS using the two securing brackets provided. See Below. Next, secure flue cowl to venting.
Securing brackets
Securing bracket
MFS
Unit
5) Install optional stainless inner panels and remote control if applicable.
See installation manual for detailed instructions. Install decorative log kit as referenced in the installation manual.
6) Install the faceplate as referenced in the installation manual, under slimline faceplate.
7) Ensure the proper gas pressure.
Regency IP28 Gas Inbuilt Fireplace
919-017
19
2
05/02/11
IP28
INSTALLATION
OPTIONAL WEATHER BOX INSTALLATION
OPTIONAL WEATHER BOX INSTALLATION
NOTE: The weather box to be installed ONLY in conjunction with the "Mock Fireplace Kit"
KIT # 456-940 Contains:
456-124
Cover External LH
456-125
Cover External RH
456-128
Cover External Top
456-129
Cover External Bottom
456-130
Cover External Back
440-420F
Plate Gas Line Cover
456-126
Insulation Back
456-127
Insulation Sides
904-643
Screw 10 x 1/2 Hex
1. Attach the side to the back with 4 screws on
each side.
3. Attach the bottom to the sides with 3 screws
on each side.
Ensure return edge is on the inside.
Attach bottom to sides
4. Install back insulation first, when in place,
bend over 4 securing tabs. Install left and right
sides bending over three tabs each side to
secure.
Side panels attached to back
5. Add gas cover plate, if required.
6. With the weather box assembled, secure to
the outside wall with screws.
7. Ensure weather box is sealed against
weather/water ingress etc
8. Before installing unit, ensure flue length, gas
and electrical routing have all been considered.
9. Install unit.
2. Attach the top to the sides with 3 screws on
each side.
Tab
Install insulation - secure by bending
tabs
Attach top to sides
20
919-192
1
Regency IP28 Gas Inbuilt Fireplace
10/09/12
IP28
INSTALLATION
OPTIONAL
STAINLESS
STEEL
INNER
PANEL
INSTALLATION
OPTIONAL
STAINLESS
STEEL
INNER
PANEL
INSTALL
Before you start:
Stainless panels must be inspected for scratches and dimples prior to installation. All claims to be recorded at this time. Claims for
damage after installation will not receive consideration.
To protect the finish during installation and handling - cotton gloves MUST be worn at all times while handling the panels (even
when removing protective coating).
Stainless panels will discolor a little during normal operation. This is normal and should not be considered a defect.
All hand and finger marks MUST be cleaned off with a soft cloth and a stainless steel cleaner. Most stainless steel cleaners leave a
film/residue on the surface of the panels. Use an ammonia based cleaner (ie. glass cleaner) to remove this film before applying heat to
the unit. Failure to do this will result in burn stains on panels which you will be unable to remove. This is not a warranty item.
1) Remove the primary guard and faceplate. Unplug polarized plug
for the switches.. Refer to instructions in this manual.
6) Secure the stainless panel with original bracket and screw - repeat
procedure on the opposite side.
2) Remove glass and glass retainers.
Refer to instructions in this manual for detailed instructions.
7)
Reinstall the logs, glass door, inner door frame with screen
and finally the faceplate. See manual for detailed instructions.
3) Remove all the logs if installed and set aside carefully.
4) Remove the two side brackets and screws (set aside) - then
remove the side panels by tilting the top in and lifting them out.
Final installation of optional stainless panels.
5) Orient the stainless side panels with the angled corner facing the
back of the firebox.
Angled corner
in panel
Regency
IP28 Gas Inbuilt Fireplace
918-957
1
09/16/10
21
INSTALLATION
SWITCH OPERATION
Switch location - Contemporary Faceplate
Switch location - Slim line Faceplate
ON | OFF | REMOTE
HIGH | LOW (FAN)
HIGH | LOW (Mj)
HIGH | LOW (FAN)
ON | OFF | REMOTE
HIGH | LOW (Mj)
Switch operation - Contemporary Faceplate
22
Switch operation - Slim line Faceplate
Regency IP28 Gas Inbuilt Fireplace
IP28
INSTALLATION
LOG SET INSTALLATION
LOG SET INSTALLATION
1)
Install rear log (0113) Ensure proper pin location and positive position
on all logs.
4)
Install top left cross log.
2)
Install left front log (0115).
5)
Place lava rocks on firebox base in front of logs - do not block
porting and spread out evenly.
3)
Install right front log (0115).
6)
Final install.
Regency IP28 Gas Inbuilt Fireplace
918-963
23
1
01/13/11
INSTALLATION
GLASS DOOR INSTALLATION
Before you start: Ensure power is off.
1) Remove the primary guard and faceplate. Unplug polarized plug for the switches.
2) L
oosen 14 screws securing the glass retainers.
Remove as many retainers required to either lift or slide the existing glass out. Ensure glass does not dislodge
3) Carefully remove and replace the glass.
4) With
new glass installed in correct position, reinstall all glass retainers and screws.
Ensure all screws are tightened to create a proper seal. Do not over tighten.
NOTE: Unit will not operate with glass removed
24
Regency IP28 Gas Inbuilt Fireplace
IP28
INSTALLATION
CONTEMPORARY FACEPLATE INSTALLATION
CONTEMPORARY FACEPLATE INSTALLATION
NOTE: If installing the Contemporary Faceplate with the mock fireplace adjust the framing tabs accordingly.
4) Reinstall front frame.
1) Line up faceplate with front of unit.
Install four (4) screws in locations shown below to secure faceplate
5) Final install.
2) Hook up wire harness from faceplate to connection to under unit and
check gas connections.
3) Reinstall bottom louver and install 2 screws in locations shown below.
918-972
Regency IP28 Gas Inbuilt Fireplace
1
11/24/10
25
INSTALLATION
HEARTH TRIM INSTALLATION
1)
L
ine up the hearth trim with the bottom of the fascia until it is flush with
the fascia.
3)
F
rom the backside of the fascia - secure the hearth trim with 3 screws
on each side in locations shown below.
26
Regency IP28 Gas Inbuilt Fireplace
IP28
INSTALLATION
SLIM LINE FACEPLATE INSTALLATION
LOW PROFILE FACEPLATE INSTALLATION
NOTE: If installing the Low Profile Faceplate with the mock fireplace - adjust the framing tabs accordingly
3) Hook up wire harness from faceplate to connection to under unit and
check gas connections.
1) Remove the stabilizer bar by removing 4 screws - install the convention
air duct in the same location using the same 4 screws, see below.
4) Reinstall bottom louver and install 2 screws in locations shown below
5) Reinstall front frame.
2) Install four (4) screws in locations shown below to secure faceplate
6) Final install.
27
Regency IP28 Gas Inbuilt Fireplace
918-973
1
12/16/10
IP28
INSTALLATION
OPTIONAL INFILL PANEL INSTALLATION
OPTIONAL INFILL PANEL INSTALLATION
If required, an optional infill panel is available to cover larger openings.
1. Remove 2 screws on each side of the unit from locatiions shown below.
3. Install 4 support brackets, two on the side, and two on the top of the
unit as shown below.
Top Bracket: Use Front Screw Hole
Side Bracket: Use Back Screw Hole
NOTE: Support brackets are only required for masonary installations.
4. Hook the infill panel onto the brackets installed in Step 2.
2. Install a mounting bracket on each side of the unit, in the same location as where screws removed.
Infill Panel
5. Please see Modular Faceplate instructions to complete installation.
NOTE: Infill panel is required for mock fireplace applications and optional
for masonry applications when installing Modular faceplate.
28
Regency IP28 Gas Inbuilt Fireplace
918-973a
1
05/02/12
IP28
INSTALLATION
MODULAR FACEPLATE INSTALLATION
MODULAR FACEPLATE INSTALLATION
NOTE: If installing the Modular Faceplate with the mock fireplace application - adjust the framing tabs accordingly
3) Hook up wire harness from faceplate to connection to under unit and
check gas connections.
1) Remove the stabilizer bar by removing 4 screws - install the convention
air duct in the same location using the same 4 screws, see below.
4) Reinstall bottom louver and install 2 screws in locations shown below
5) Reinstall front frame.
2) Install four (4) screws in locations shown below to secure faceplate
6) Final install.
Regency IP28 Gas Inbuilt Fireplace
918-973a
29
2
05/02/12
INSTALLATION
FINAL CHECK
Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly. This includes:
1) Clocking the appliance to ensure the correct firing rate (rate noted on label) at 15 minutes.
2) If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15 min. to stabilize.
CAUTION
Any alteration to the product that causes sooting or carboning that results in damage to the exterior facia is not the responsibility of the manufacturer.
WARNING: 240V DISCONNECT POWER TO UNIT PRIOR TO WORKING ON ELECTRICAL COMPONENTS.
WIRING
Caution: Ensure that the wires do not
touch any hot surfaces and are away
from sharp edges.
This unit is polarity sensitive and will
not operate if polarity is incorrect.
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can
cause improper and dangerous operation.
STANDARD WIRING
30
Regency IP28 Gas Inbuilt Fireplace
OPERATING INSTRUCTIONS
INSTALLATION
OPERATING
INSTRUCTIONS
Before operating this appliance, proceed through
the following check list.
1) Read and understand these Instructions before
operating this appliance.
2) Check to see that all wiring is correct and
enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass door is in place. Never
operate the appliance with the door glass
removed.
5) Verify that all flueing and the cap is unobstructed.
6) Verify log placement.
7) The unit should never be turned off and on
again without a minimum of a 2 minute wait.
8) When lighting the appliance, the inside of the
glass may fog up. This will burn off after a few
minutes of operation.
LIGHTING
INSTRUCTIONS
1) Locate the 3 way switch located on the faceplate (refer to switch operation section in this
manual for location).
Manual Operation - Turn 3 way switch to ON
position, after approximately 60 seconds the
spark ignition system will spark for 5 seconds
to light the main burner. If the main burner
fails to light - repeat sequence.
Remote Operation - Turn 3 way switch to the
Remote position, locate Remote - press and
release ON/OFF button once. Wait approximately 60 seconds to light the main burner. If
the main burner fails to light repeat sequence.
FIRST FIRE
The FIRST FIRE in your heater is part of the paint
curing process. To ensure that the paint is properly
cured, it is recommended that you burn your fireplace
for at least four (4) hours the first time you use it
with the fan on.
When first operated, the unit will release an odour
caused by the curing of the paint and the burning
off of any oils remaining from manufacturing. Smoke
detectors in the house may go off at this time. Open
a few windows to ventilate the room for a couple of
hours. The glass may require cleaning.
NOTE:When the glass is cold and the appliance
is lit, it may cause condensation and fog
the glass. This condensation is normal and
will disappear in a few minutes as the glass
heats up.
DO NOT ATTEMPT TO CLEAN THE GLASS
WHILE IT IS STILL HOT!
DO NOT BURN THE APPLIANCE WITHOUT
THE GLASS FRONT IN PLACE.
REMOTE CONTROL
Use the Regency Remote Control Kit approved
for this unit. Use of other systems may void your
warranty.
Note: The remote must be coded into the unit before
it can be operated. See "Remote Control Installation
and Operating Instructions" manual supplied with
the remote control.
The remote control kit comes with a hand held
transmitter and a wall mounting plate.
1) Choose a convenient location, to the left side of
the valve, to mount the hand held transmitter,
protection from extreme heat is very important.
By using the wall mounting plate to house the
transmitter, the remote can also be used as a wall
thermostat.
SHUTDOWN
INSTRUCTIONS
Manual Operation - Turn 3 way switch to OFF
position.
Remote Operation - Press and release ON/
OFF button once or turn 3 way switch from
Remote position to OFF position.
Regency IP28 Gas Inbuilt Fireplace
31
OPERATING INSTRUCTIONS
REMOTE RECEIVER INSTALLATION
Carefully remove blank spades from remote wires in heater.
1) Connect black to black.
2) Connect white to blue.
Remote receiver
Once you connect the black wire, the other 2
wires are identified by the male-female connector.
Place the receiver in the left hand side on the base of the heater.
Ensure the receiver aerial is not touching metal components.
32
Regency IP28 Gas Inbuilt Fireplace
OPERATING INSTRUCTIONS
INSTALLATION
COPY OF LIGHTING INSTRUCTION PLATE
FOR YOUR SAFETY READ BEFORE LIGHTING
This appliance must be installed in accordance
with local codes, if any; if not,
follow the current CAN1-B149/ANSI Z 223.1
(Australia: AS5601-2004, New Zealand: NZS
5261)
WARNING: If you do not follow these
instructions exactly, a fire or explosion
may result causing property damage,
personal injury or loss of life. Improper
installation, adjustment, alteration, service
or maintenance can cause injury or property
damage. Refer to the owner’s information
manual provided with this appliance. For
assistance or additional information consult
a qualified installer, service agency or gas
supplier.
A) BEFORE LIGHTING smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the
floor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electric switch, do not use
any phone in your building
- Immediately call your gas supplier from a
neighbors phone. Follow the gas supplier’s
instructions.
- If you cannot reach your gas supplier, call the fire
department.
B) Do not use this appliance if any part has been under
water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of
the control system and any gas control which has
been under water.
This appliance needs fresh air for safe operation and
must be installed so there are provisions for adequate
combustion and ventilation air.
CAUTION: Hot while in operation. Do not
touch. Severe Burns may result. Due to
high surface temperatures keep children,
clothing and furniture, gasoline and other
liquids having flammable vapors away. Keep
burner and control compartment clean.
See installation and operating instructions
accompanying appliance.
LIGHTING INSTRUCTIONS
STOP! Read the safety information above on this
label.
1)
Ensure the power cord is plugged into the
power outlet and turned on.
2)
Turn 3 way switch to ON position
3)
After approximately 60 seconds the spark
ignition system will spark for 5 seconds to
light the main burner.
4)
If the main burner does not light, repeat step 2
to restart.
1)
Turn 3 way switch to OFF
2)
Turn off all electric power to the unit if service
is to be performed.
TO TURN OFF GAS APPLIANCE
DO NOT REMOVE THIS
INSTRUCTION PLATE
918-958
WARNING:
Colours:
Black on Grey, except for parts in RED
Size: NOTWSPRAY
2.74" x H 12.45" AEROSOLS IN THE VICINITY OF
DO
Sept. 22/10: created draft
THIS APPLIANCE WHILE IN OPERATION.
Oct. 19/10 :revised size
Part #: 918-958
NORMAL OPERATING
SOUNDS OF
GAS APPLIANCES
It is possible that you will hear some sounds
from your gas appliance. This is perfectly normal
due to the fact that there are various gauges
and types of steel used within your appliance.
Listed below are some examples. All are normal
operating sounds and should not be considered
as defects in your appliance.
Fans:
.It is not unusual for the fan to make a "whirring"
sound when ON. This sound will increase or
decrease in volume depending on the speed
setting of your fan speed control.
This appliance is equipped with a combustion
and convection fan. These fans will operate as
soon a the appliance is turned on.
NOTE: T
his appliance will not operate without
the convection fan running at all times.
Burner Tray:
The burner tray is positioned directly under the
burner tube(s) and logs and is made of a different gauge material from the rest of the firebox
and body. Therefore, the varying thicknesses of
steel will expand and contract at slightly different
rates which can cause "ticking" and "cracking"
sounds. You should also be aware that as there
are temperature changes within the unit these
sounds will likely re-occur. Again, this is normal
for steel fireboxes.
Gas Control Valve:
As the gas control valve turns ON and OFF, a
dull clicking sound may be audible, this is normal
operation of a gas regulator or valve.
Unit Body/Firebox:
Different types and thicknesses of steel will
expand and contract at different rates resulting
in some "cracking" and "ticking" sounds will be
heard throughout the cycling process.
RESETTING THE UNIT
If the appliance goes to 'lockout', the system
will have to be reset by unplugging or
pressing switch to OFF position.
*Important: Wait at least 5 min for any
unburned gas to clear before resetting the
appliance.
NOTE: Wait 2 minutes between reset
attempts.
"Appliances incorporating a live fuel effect (designed to operate with blue flames with slight yellow tips) may exhibit slight
carbon deposition."
Regency IP28 Gas Inbuilt Fireplace
33
OPERATING INSTRUCTIONS
All maintenance must be carried out by a licensed qualified service person
IT IS CRITICAL THAT THIS APPLIANCE IS EARTHED AND THAT THE ACTIVE AND NEUTRAL ARE NOT REVERSED
UNIT OPERATION
ACTION REQUIRED
No gas to the burner
The gas valve should open at the same time the ignition commences sparking. If
there is no gas to the burner, turn unit off. Connect manometer to inlet test point
on the gas valve and check static pressure. If O.K. turn unit on and check there is
no significant drop in the pressure. If O.K. connect manometer to outlet test point
of the gas valve, turn unit on and check outlet pressure is present whilst the spark is
being generated.
Unit sparks, main burner ignites after 5 seconds
spark continues even though main flame is present
This can be caused by incorrect polarity.
Check that the wall socket to the appliance has correct polarity. If an extension lead
is fitted check polarity of the lead. Check the polarity of the supply lead to the
appliance. NOTE: The above checks must be carried out by a qualified person
Combustion fan & Convection fan operate but no
ignition after approx 1 minute
ignition module is in lockout. Switch off power to unit for 1 minute to reset module
Then turn on again. Unit should ignite after purge time
NOTE: On initial light up this may occur a number of times until any residual air is
purged from the gas line through the burner system. It is essential the required
waiting time as stated in the manual is observed prior to attempting re ignition
After resetting ignition module, unit still not
operating after 1 minute
Turn burner switch to "ON", fans will operate within 5 secs, listen for audible "click" first from
ignition module, then from pressure switch.
If no "click' heard contact service agent
Confirm spark is produced when heater is turned on
The ignition electrode should spark at the same time the gas control solenoid valve
opens(after approx 1minute purge time). At this point the spark electrode will
activate for up to 5 seconds. A blue spark can be seen when the heater ignition
process starts, Ensure the spark is present between the electrode and burner.
If no spark is produced
Check the combustion fan & pressure switch are operating (there should be an
audible click when the pressure switch makes contact). Providing the spill switch
has continuity the electrode should spark and the gas valve open within 5 seconds
of the completion of the purge cycle.
34
Regency IP28 Gas Inbuilt Fireplace
MAINTENANCE
MAINTENANCE
INSTRUCTIONS
Any maintenance required accessing the glass
door of the unit must be performed by an authorized service person.
1) Always unplug the power cord before cleaning.
For relighting, refer to lighting instructions. Keep
the burner and control compartment clean by
brushing and vacuuming at least once a year.
When cleaning the logs, use a soft clean brush
as the logs are fragile and easily damaged.
2) Clean glass (never when unit is hot), appliance,
louvres, and door with a damp cloth. Never
use an abrasive cleaner. The gold louvres
(and optional gold door) may be scratched if
abrasives are used to clean them.
The heater is finished in a heat resistant paint
and should only be refinished with heat resistant paint (not with wall paint). Regency uses
StoveBright Paint - Metallic Black #6309.
3) Make a periodic check of burner for proper
position and condition. Visually check the
flame of the burner periodically, making sure
the flames are steady; not lifting or floating. If
there is a problem, call an authorized service
person.
4) The appliance and flueing system must be
inspected before use, and at least annually, by
an authorized field service person, to ensure
that the flow of combustion and ventilation air
is not obstructed.
INSTALLATION AND REPAIR SHOULD
BE DONE BY AN AUTHORIZED
SERVICE PERSON. THE APPLIANCE
SHOULD BE INSPECTED BEFORE
USE AND AT LEAST ANNUALLY BY A
PROFESSIONAL SERVICE PERSON.
MORE FREQUENT CLEANING MAY
BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, BEDDING
MATERIAL, ETC. IT IS IMPERATIVETHAT
CONTROL COMPARTMENTS, BURNERS
AND CIRCULATING AIR PASSAGEWAYS
OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE
APPLIANCE SHOULD BE LOCATED
OUT OF TRAFFIC AND AWAY FROM
FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS
APPLIANCE CORRECTLY WILL VOID
YOUR WARRANTY AND MAY CAUSE A
SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE
ALERTED TO THE HAZARDS OF HIGH
SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND
SHOULD STAY AWAY TO AVOID BURNS
OR CLOTHING IGNITION.
Note: Improper positioning of logs may
create carbon build-up and will alter
the unit’s performance which is not
covered under warranty.
DOOR GLASS
REPLACEMENT
Your Regency stove is supplied with high temperature, 5 mm Neoceram ceramic glass that
will withstand the highest heat that your unit will
produce. In the event that you break your glass
by impact, purchase your replacement from an
authorised Regency dealer only, and follow our
step-by-step instructions for replacement.
WARNING: do not operate appliance
with the glass front removed, cracked
or broken. Replacement of the glass
should be done by a licensed or authorised service person.
Flush Glass Replacement
During the annual service call, the burners
should be removed from the burner tray and
cleaned. Replace the embers - do not block
the burner ports.
Slide old glass out of the side frames and replace
with new glass.
5) Keep the area near the appliance clear and
free from combustible materials, gasoline and
other flammable vapours and liquids.
6) Verify proper operation after servicing.
The unit should never be used with broken logs.
Unplug the power cord and allow the unit to cool
before opening door to carefully remove the logs.
If for any reason a log should need replacement,
you must use the proper replacement log. The
position of these logs must be as shown in the
diagram under Log Installation.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE
IN THE SAME AREA AS THE APPLIANCE. TODDLERS, YOUNG CHILDREN
AND OTHERS MAY BE SUSCEPTIBLE
TO ACCIDENTAL CONTACT BURNS. A
PHYSICAL BARRIERS IS RECOMMENDED IF THERE ARE AT RISK INDIVIDUAL
IN THE HOUSE. TO RESTRICT ACCESS
TO A FIREPLACE OR STOVE, INSTALL
AN ADJUSTABLE SAFETY GATE TO
KEEP TODDLERS, YOUNG CHILDREN
AND OTHER AT RISK INDIVIDUALS OUT
OF THE ROOM AND AWAY FROM HOT
SURFACES.
GLASS GASKET
If the glass gasket requires replacement use
glass gasket (Part # 936-233).
CLOTHING OR OTHER FLAMMABLE
MATERIAL SHOULD NOT BE PLACED
ON OR NEAR THE APPLIANCE.
Regency IP28 Gas Inbuilt Fireplace
35
MAINTENANCE
CONVECTION FAN REPLACEMENT
Before you start:
Ensure all power is turned off.
1) Turn the unit off and allow it to cool to room temperature,
8) Reverse steps to reinstall.
NOTE: It is essential that the two washers are re-fitted to the fan mounting
bolts prior to fitting the wing nuts.
2) Unplug or disconnect power source to stove.
3) Open the bottom louvre.
4) Remove 2 wing nuts + washers securing fan - locations shown below.
5) Unclip wires from base of unit and unplug fan.
6) Disconnect polarized plug.
7) Manoeuvre fan from base of unit and replace.
36
Regency IP28 Gas Inbuilt Fireplace
MAINTENANCE
COMBUSTION FAN REPLACEMENT
8) Manoeuvre fan from base of unit and replace.
Before you start:
Ensure all power is turned off.
1) Turn the unit off and allow it to cool to room temperature,
2) Unplug or disconnect power source to stove.
3) Open the bottom louvre.
4) Remove convection fan - see previous page.
5) Remove 4 screws to release fan.
9) Reverse steps to reinstall.
6) Disconnect polarized plug.
7) Disconnect tubing from right side of fan.
Tubing
8) Disconnect ground wire.
Regency IP28 Gas Inbuilt Fireplace
37
PARTS LIST
PRESSURE SWITCH REPLACEMENT
Before you start
Ensure all power is turned off.
1)
Disconnect wire leads and tubing on the switch.
NOTE: It is important to label wires and hose connections to ensure the new switch is hooked up in
the same manner.
2)
Remove the two screws on the mounting bracket.
Remove 2 screws
3) Slide switch out to the left side.
4) Remove switch and replace.
5) Reverse steps to complete installation.
38
Regency IP28 Gas Inbuilt Fireplace
MAINTENANCE
VALVE ASSEMBLY REPLACEMENT
Before you start:
Ensure all power is turned off.
6) Disconnect wires.
1) Turn the unit off and allow it to cool to room temperature,
2) Unplug or disconnect power source to stove.
3) Open the bottom louvre to access valve.
6) Disconnect wire harness plug.
4) Remove screw in location shown below to release valve cover.
7) Remove screw from rectifier,
5) Partially lift out valve cover.
8) Unplug rectifier from valve.
Regency IP28 Gas Inbuilt Fireplace
39
MAINTENANCE
9) Disconnect ground wire from valve.
.
10)Disconnect connection from valve to burner.
11)Disconnect connection from valve to gas outlet.
12)Remove valve and replace.
13)Reverse steps to reinstall.
40
Regency IP28 Gas Inbuilt Fireplace
PARTS LIST
MAIN ASSEMBLY
Part #
1) 911-056/P
2) 911-057/P
Description
Blower 240 Volt Convection
Tube Sensing Combustion Fan IP28
W190615
Thermodisc** 105C
3) 456-968
LPG Conversion Kit**
4) 456-574/P
456-578/P
Valve Assembly NG
Valve Assembly LP
5) 911-064
6) 940-367/P
Valve NG/LP 843 Sigma
Glass Neoceram Flush IP28
7)
Burner Assembly NG C/w Cap IP28
456-091
Baffle Plate IP28
911-040
456-001
Power Cord Assembly 240V IP28
Grate Assembly IP28
456-005 Gasket Combustion Fan IP28
456-004 Gasket Valve Tray IP28
911-047 Silicone Tubing
936-232 Gasket Rope
904-658 Inlet Flex Line Gas SS Steel 24 inch
910-088 Wire ECS Module Spark (Red)
910-089 Wire ECS Module Flame (Red)
911-041 Wire Harness Ignition Module IP28
911-042 Wire Harness Valve Rectifier IP28
911-044 Wire Harness Main Control IP28
911-059 Pressure Switch
911-062 Step Modular Plug Sit
911-063 Ignition Board 45 Sec. Sit
936-232 Door glass gasket (per 305mm)
8)
456-044/F
456-049/F
Description
910-082 Ignition Direct Spark Assy Electronic
Fan Combustion 240 Volt 50hz EU
456-008
456-525
Part #
456-930 Log Set IP28
918-938
Bracket side flange right / IP28
Bracket side flange left / IP28
Manual
*Not available as a replacement part.
** Part not shown.
8
6
Regency IP28 Gas Inbuilt Fireplace
4
7
1
2
41
PARTS LIST
CONTEMPORARY FACEPLATE ASSEMBLY
Part #
14)
Description
456-914 Faceplate & Trim Complete - Regular
*
Faceplate Side Right IP28
*
Faceplate Side Left IP28
*
Faceplate - Top IP28
*
Plate Backing Faceplate IP28
911-043
Wire Harness Control Switch IP28
911-060
Switch Rocker TC201-TB-B On/Off/On
911-061
Switch Rocker TB201-TB-B On/None/On
*Not available as a replacement part.
SLIM LINE FACEPLATE ASSEMBLY
Part #
Description
-
Door Bottom Access Slim F/P IP28
*
Frame Front Slim Faceplate IP28
*
Faceplate Front IP28
911-043
Wire Harness Control Switch IP28
911-060
Switch Rocker TC201-TB-B On/Off/On
911-061
Switch Rocker TB201-TB-B On/None/On
*Not available as a replacement part.
42
Regency IP28 Gas Inbuilt Fireplace
WARRANTY
Regency® Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly
before it leaves our door. Regency® is pleased to extend this limited lifetime warranty to the original purchaser of a Regency® Product. Regency® will repair or replace
goods free of charge in the event of defects arising from faulty materials or workmanship in accordance with the warranty terms in relation to Definitions, Warranty
Conditions and Exclusions stated in this document.
The benefits to the consumer given by this warranty are in addition to all other rights and remedies of the consumer under a law in relation to the goods or services to which the
warranty relates.
Our goods come with the guarantees that cannot be excluded under the Australian Consumer Law. You are entitled to a replacement or refund for a major failure and for compensation
for any other foreseeable loss or damage. You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable quality and the failure does not amount
to a major failure.
The Warranty: Lifetime
Covered under the agreement are the following components: The combustion chamber, heat exchanger, burner tubes/pans, logs, glass crystals, ceramic spa stones, pebbles,
brick panels and gold plating (against defective manufacture only) are covered under the Limited Lifetime Warranty for five (5) years for parts and labour and parts only thereafter.
External casting, surrounds and grills are covered against cracks and warps resulting from manufacturer defects, parts and labour for one (1) year from the date of purchase and
parts only thereafter.
Regency Fireplace Products is not liable for freight or labour on any gas appliance replaced in the field.
Special Finishes - One year on stainless steel panels, nickel overlays, nickel faceplates, brushed nickel and antique copper full screens and doors. You can expect some changes in
color as the product "ages" with constant heating and cooling. FPI warranties the product for any manufacturing defects on the original product. However, the manufacturers warranty
does not cover changing colors and marks, ie. finger prints, etc applied after the purchase of the product. Damage from the use of abrasive cleaners is not covered by warranty.
Electrical components such as fans, switches, ignition modules, wiring, thermodiscs, remote control, thermopiles, thermocouples and gas valves are covered for one year for parts
and labour from the date of purchase.
The warranty on brass parts is for one year, no labour. The brass is not warranted against tarnishing.
Repair/replacement parts purchased by the consumer from Regency® after the original coverage has expired on the unit will carry a 90 day warranty valid with a receipt only. Any
item shown to be defective will be repaired or replaced at our discretion. No labour coverage is included with these parts.
Conditions:
All installations must be performed by a qualified gas fitter and installed according to all applicable local and national codes. Also, all service work must be carried out by a qualified
gas service person provided by the selling dealer. It is the responsibility of the installer to ensure that the appliance is firing as per rating plate. Any part or parts of this unit which in
our judgement show evidence of such defect will be repaired or replaced at Regency®'s option, through an accredited distributor or agent provided that the defective part be returned
to the distributor or agent Transportation Prepaid, if requested. In areas where there is not an approved service agent or the closest approved service agent is situated more than
thirty (30) kilometres from the installation, Regency is not obliged to arrange warranty repairs and travel and/or additional labour charges will apply.
Porcelain/Enamel - Absolute perfection is neither guaranteed nor commercially possible. Any chips must be reported and inspected by an authorised dealer within three days of
installation. Reported damage after this time will be subject to rejection.
It is the general practice of Regency® to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to Regency and
evaluated fro manufacturer defect.
At all time Regency reserves the right to inspect product in the field which is claimed to be defective.
All claims must be submitted to Regency® by authorised selling dealers. It is essential that all submitted claims provide all of the necessary information including customer name,
purchase date, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door or glass gasket or trim. It does not cover installation and operational related problems such as over-firing,
down drafts or spillage caused by environmental conditions, nearby trees, buildings, hilltops, mountains, inadequate flueing or ventilation, excessive offsets, negative air pressures
caused by insufficient make up air, mechanical systems such as furnaces, fans, clothes dryers etc.
Embers, rockwool, gaskets, door handles and paint are not covered under the terms of this warranty policy.
Regency® will not be liable for acts of God, or acts of terrorism, which cause malfunction of the appliance.
Performance problems due to operator error will not be covered by this warranty policy.
The warranty does not extend to any part or parts which show evidence of misuse or abuse, neglect, accident, lack of maintenance, or improper installation.
Products made by other manufacturers and used in conjunction with the operation of this appliance without authorisation from Regency®, may nullify your warranty on this product.
Regency shall in no event be liable for any special, indirect consequential damages of any nature whatsoever which are in excess of the original purchase price of the product. Any
alteration to the unit which causes sooting or carboning that results in damage to the exterior facia is not the responsibility of Regency Fireplace Products.
SUBJECT TO CHANGE.
DISTRIBUTORS:
Western Australia
Eastern Australia
Air Group Australia
Fireplace Products Australia PTY. Ltd.
28-30 Division St.
1-3 Conquest Way
Welshpool, WA 6106
Hallam, VIC 3803
08 9350 2200
03 9799 7277
NOTE: PLEASE RETAIN YOUR INVOICE AS PROOF OF PURCHASE FOR WARRANTY VERIFICATION
INCORRECT INSTALLATION OR GAS PRESSURE SETTINGS ARE NOT COVERED BY WARRANTY
A SERVICE OR CALLOUT FEE WILL BE CHARGED IN THESE CIRCUMSTANCES.
Regency IP28 Gas Inbuilt Fireplace
43
Register your Regency® warranty online
www.regency-fire.com.au
Reasons to register your product online today!
• View and modify a list of all your registered products.
• Request automatic email notification of new product updates.
• Stay informed about the current promotions, events, and special
offers on related products.
• Help assure you get the most out of your warranty.
• Eliminate confusion and frustration if warranty** service is required in
the future.
** Proof of purchase required at time of warranty request.
Installer: Please complete the following information
Dealer Name & Address:_______________________________________________
___________________________________________________________________
Installer:____________________________________________________________
Phone #:____________________________________________________________
Date Installed:_______________________________________________________
Serial No.:___________________________________________________________ © Copyright 2015, FPI Fireplace Products International Ltd. All rights reserved.
Printed in Canada
Was this manual useful for you? yes no
Thank you for your participation!